Industrial Ventilation Design Guidebook Chapter 10 LOCAL VENTILATION
|
|
|
- Peter Craig
- 9 years ago
- Views:
Transcription
1 Industrial Ventilation Design Guidebook Chapter 10 LOCAL VENTILATION LARS OLANDER, LORRAINE CONROY, ILPO KULMALA, RICHARD P. GARRISON, MICHAEL ELLENBECKER, BERNHARD BIEGERT, BERNARD FLETCHER, HOWARD D. GOODFELLOW, GUNNAR ROSÉN, BENGT LJUNGQVIST, BERIT REINMÜLLER, ANTONIO DUMAS, MICHAEL ROBINSON, DEREK B. INGHAM, ALBRECHT LOMMEL, KATSUHIKO TSUJI, IRMA WELLING, XIANYUN WEN
2 LOCAL VENTILATION Short definition: Local Ventilation systems are used to transport contaminants or heat from the occupancy zone.
3 LOCAL VENTILATION Long definition: Local Ventilation uses an air flow rate that is as low as possible, but sufficient to minimise the amount of airborne contaminants entering a specified volume or passing specified point(s). These are usually intended to be at the breathing zone of occupants. This minimisation of air flow can be achieved either by capturing (or containing) the airborne contaminant into an exhaust hood before it enters the workspace, by blowing noncontaminated air from a supply inlet through the volume to prevent the contaminant from entering the workspace, or a combination of those.
4 Local Ventilation Modes Fixed. No changes to the system, except perhaps opening and closing of lids and doors, are possible. One example is the laboratory fume hood. Flexible. The suction opening or supply device is placed inside a limited area or volume. The exhaust (or supply) opening and duct (or tube) is connected to the fan by moveable elbows or flexible tubes. One example is a wall mounted hood for welding exhaust. Mobile. The exhaust (supply) opening may be placed almost anywhere inside a workroom. The whole system (exhaust/supply opening, duct, fan) is on wheels or a portable frame. Or a separate exhaust part (opening and short tube) is connected to a central duct system at many places. One example is a welding exhaust (with filter) on a small carriage and another is a centralized exhaust system for connection to car exhaust pipes. It also includes portable systems.
5
6 Description of each Local Ventilation system General comments Principle, including sketches and/or figures Applicability of contaminant sources Different forms and boundaries to other types Relative location of supply and exhaust openings and source(s) Location of worker and tools relative to exhaust and source(s) Disturbances Specific problems Changing flow rates Design equations and/or parameters Evaluation procedures
7 Velocity distributions outside round (top left), round with flange (top right), and square (bottom) exhaust opening.
8
9 The air shower principle creates a zone of clean air around the worker and pushes away the contaminant plume from the breathing zone.
10 Examples of principal arrangements of open unidirectional airflow benches.
11 A push-pull system is a combination of an exhaust and an inlet system.
12 A schematic representation of the Aaberg principle in a combined exhaust-supply system.
13 D.Gubler: REEXS Reinforced Exhaust System, Optimization of operating and design parameters. ETS Switzerland, 2002.
14 Principe for auxiliary air supply to a laboratory fume hood.
15 The Class III Biological Safety Cabinet is a combined exhaust-supply system. A: Glove ports with O-ring for attaching arm-length gloves to cabinet. B: Sash. C: Exhaust HEPA filter. D: Supply HEPA filter. E: Double-ended autoclave or pass-through box. Note: Connection of the exhaust to building exhaust system is required.
16 Different configurations of supply air inlets and exhaust air outlets in an abrasive blasting room. A1: Supply in ceiling and exhaust through floor. A2: Supply in ceiling and exhaust along floor sides. A3: Supply in one end of ceiling and exhaust through one opposite wall. A4: Supply in one end of ceiling and exhaust in corners of opposite wall. B1: Supply in one wall and exhaust through opposite wall. B2: Supply in one wall and exhaust in corners of opposite wall. B3: Supply in corners of one wall and exhaust through opposite wall. B4: Supply in corners of one wall and exhaust in corners of opposite wall. C1 and C2: Not recommended (INRS, 1994).
17
18 EVALUATION OF LOCAL VENTILATION SYSTEMS The evaluation methods could be direct, e.g., measuring a containment index, or indirect, e.g., measuring pressure loss or velocity distribution.
19 Indirect methods are used to determine regulatory compliance. For example, specified minimum and maximum face velocities for laboratory fume hoods and static pressure (negative) inside enclosed hoods. Monitoring instruments can be connected to alarms. Capture efficiency is the fraction of generated contaminant that is directly captured by the hood. This means measuring concentration of process-generated contaminant or a tracer material. Using contaminant requires instruments suited to each specific contaminant and its conditions. It is easier to use a tracer. Simple evaluations by checking the air flow rates into the opening, presuming that many parameters have not changed since the detailed evaluation was done. Static pressure loss for a hood can be used to monitor the flow rate into the hood. If the flow rate and the pressure loss were measured at the same time as the efficiency, the pressure loss can be used for monitoring hood performance. Another simple way is to use smoke to visualize the air streamlines. It is sometimes possible to see how far an exhaust reaches by observing smoke movement.
20 Hood types Exterior hoods Basic openings, Rim exhausts, LVHV, Receptor hoods, Special: Fit to machines Enclosures Booths, Laboratory fume hoods, Safety cabinets, Glove boxes, Storage cabinets, Built-in processes Evaluation procedures Capture efficiency, Capture velocity Containment indices such as: Protection factor and similar. Leakage factor and similar. Pressure difference. Opening velocity.
21 Thank you! Lars Olander Professor Building Services Engineering Royal Institute of Technology (KTH) SE Stockholm SWEDEN
Fume Hood Questions and Answers
Fume Hood Questions and Answers 1. When should I use a fume hood? Use a chemical fume hood anytime your work involves: Chemicals with a National Fire Protection Association (NFPA) Health rating of 3 or
Principles of Ventilation. Patrick N. Breysse, PhD, CIH Peter S.J. Lees, PhD, CIH Johns Hopkins University
This work is licensed under a Creative Commons Attribution-NonCommercial-ShareAlike License. Your use of this material constitutes acceptance of that license and the conditions of use of materials on this
Procedures for the Effective Use of Biological Safety Cabinets
Procedures for the Effective Use of Biological Safety Cabinets APPROVAL DATE BY BIOHAZARDS SUBCOMMITTEE: August 10, 2012 SUPERSEDES: March 1, 2012 This corporate guideline/procedure is intended as a minimum
Chemical Fume Hoods. Environmental Health and Safety 974-5084
Chemical Fume Hoods Environmental Health and Safety 974-5084 Regulatory References Prudent Practices in the Laboratory 2011 (National Research Council of The National Academies): Laboratory chemical hoods
Effectiveness of Engineering controls (LEVs)
Carlos Fito López Responsable A.T. Seguridad & Coordinador de Proyectos de Nanoseguridad [email protected] Sevilla 3 de Diciembre de 2014 Jornada de Nanotecnología y prevención de riesgos Nuevos desarrollos
Risk Assessment: Biosafety Cabinet
Risk Assessment: Biosafety Cabinet Biosafety cabinets (BSCs) serve as primary containment devices for operations involving potential splashes, spills or aerosolization of hazardous biological materials.
Asbestos in the Workplace: A Guide to Removal of Friable Asbestos Containing Material
Asbestos in the Workplace: A Guide to Removal of Friable Asbestos Containing Material Revised November 21, 2013 Application Code of Practice Where asbestos is present or believed to be present in a workplace
CHAPTER 4 VENTILATION
CHAPTER 4 VENTILATION SECTION 401 GENERAL 401.1 Scope. This chapter, in conjunction with the building code, shall govern the ventilation of spaces within a building intended to be occupied. Mechanical
SECTION 15950 - TESTING, ADJUSTING, AND BALANCING
SECTION 15950 - TESTING, ADJUSTING, AND BALANCING PART 1 - GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
Fume Extraction: Guide to Safely Managing Solder Fumes in the Workplace
Fume Extraction: Guide to Safely Managing Solder Fumes in the Workplace Our thanks to OK International for allowing us to reprint the following. Why do we need fume extraction? Today s Electronics workplace
PI s Name Date Bldg./Rm# CDC Biosafety Level 3 (BSL-3)
PI s Name Date Bldg./Rm# CDC Biosafety Level 3 (BSL-3) Yes No 1. Is access to the laboratory limited or restricted at the discretion of the laboratory director when experiments are in progress? Yes No
Components HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis
Components HVAC General System Selection Life Cycle Cost Analysis Outdoor Air Design Values Indoor Air Design Values Outdoor Air Ventilation Welding Ventilation Temperature Control Systems Ductwork HVAC
OSHA and Welding Exhaust
OSHA and Welding Exhaust The following has been taken directly from OSHA s General Industry Standards and Interpretations, Part 1910, Subpart Q Welding, Cutting, and Brazing. We have omitted irrelevant
Controlling health risks from rosin (colophony)-based solder flux fume
Controlling health risks from rosin (colophony)-based solder flux fume Introduction This leaflet gives guidance on how to protect your employees from the risk of ill health caused by rosin (colophony)-based
Visualisation and control of solder fume exposure
Health and Safety Executive Visualisation and control of solder fume exposure A quantitative assessment of LEV effectiveness Prepared by the Health and Safety Laboratory for the Health and Safety Executive
SPECIAL APPLICATIONS
Page 1 SPECIAL APPLICATIONS The protection of microelectronics clean rooms using aspirating smoke detection systems requires special consideration. The physical configuration of the room(s) and the direction
Class II Type B2 Laminar Flow Biological Safety Cabinets at Ordering Criteria for the National Institutes of Health
Background Class II Type B2 Laminar Flow Biological Safety Cabinets at Ordering Criteria for the National Institutes of Health This document provides guidelines for the design and installation of Class
Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,
4658.4500 PLUMBING SYSTEMS; NEW CONSTRUCTION. Subpart 1. Installation. All plumbing systems must be installed and tested according to this chapter and chapter 4715, the Minnesota Plumbing Code. Subp. 2.
INSTRUCTIONS FOR HOW TO PROPERLY SELECT A FAN OR BLOWER
INSTRUCTIONS FOR HOW TO PROPERLY SELECT A FAN OR BLOWER The instructions that follow are to assist you in completing the information required when making a fan or blower selection. If you need additional
Essam E. Khalil [email protected]
AIR-CONDITIONING SYSTEMS DEVELOPMENTS IN HOSPITALS: COMFORT, AIR QUALITY, AND ENERGY UTILIZATION Essam E. Khalil [email protected] PROFESSOR OF MECHANICAL ENGINEERING, CAIRO UNIVERSITY, EGYPT Abstract
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
SAM HOUSTON STATE UNIVERSITY
PART 1: GENERAL 1.01 General Requirements A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the
Australian/New Zealand Standard
Australian/New Zealand Standard The use of ventilation and air conditioning in buildings - Part 1: Fire and smoke control in buildings UPDATED AS/NZS 1668.1:2015 What is the scope of this Standard? The
Spray Booth Guideline
Department of Development Service 135 North D Street, Perris CA. 92570 Phone: (951) 443-1029 Fax: (951) 943-3293 PURPOSE The intent of this guideline is to provide the information necessary to ensure that
Cleanroom Solutions Ltd T: 01273 760 060 F: 01273 760 061 E: [email protected] W: www.cleanroom-solutions.co.uk
Cleanroom Solutions Ltd T: 01273 760 060 F: 01273 760 061 E: [email protected] W: Introduction Cleanroom Solutions Ltd has a wealth of experience together with a solid track record in the
National System of Garage Ventilation s Engineering Guide
National System of Garage Ventilation s Engineering Guide In designing a fume removal system, it is extremely important to determine the following: 1. Type of apparatus to be exhausted (i.e. gasoline,
Displacement ventilation
General The displacement ventilation principle is the oldest form of ventilation and can be achieved without the use of fans. Air movement occurs by means of the density differences between supply air
Design Information. Designing Your Dust Collection System. Typical dust or fume collection system
Design Information Designing Your Dust Collection System There are five simple steps to designing an effective and efficient dust collection system. 1. Draw a floor plan of your shop Important Terms to
GenStore Archive Cabinet
GenStore Archive Cabinet Setup and Maintenance Manual Version A April 2014 Two GenStore Archives shown mounted on optional table stand. 2 Contents Getting Started... 4 Using this Manual...4 Safety Precautions...4
Fan Performance By: Mark Stevens AMCA International Deputy Executive Director Technical Affairs
Fan Performance By: Mark Stevens AMCA International Deputy Executive Director Technical Affairs Fan Performance (Paper I.D. 021) Mark Stevens Air Movement and Control Association International Abstract
Chapter 12 Industrial Ventilation
Chapter 1 Industrial Ventilation Introduction Industrial Ventilation is an important method for reducing employee exposures to airborne contaminants. Ventilation is used to reduce or remove contaminates
BIOLOGICAL SAFETY CABINET PROGRAM
BIOLOGICAL SAFETY CABINET PROGRAM TABLE OF CONTENTS: 1. INTRODUCTION 2. PURPOSE AND SCOPE 3. SELECTION AND INSTALLATION 4. USE OF BIOLOGICAL SAFETY CABINETS 5. CERTIFICATION OF BIOLOGICAL SAFETY CABINETS
Element D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
A SELF-EVALUATION CHECKLIST of BEST PRACTICES for AUTO REFINISH SHOPS and SCHOOLS
A of BEST PRACTICES for AUTO REFINISH SHOPS and SCHOOLS www.epa.gov/dfe/pubs/projects/auto/ WHAT IS THE DESIGN FOR THE ENVIRONMENT (DFE) AUTO REFINISH PROJECT? The DfE Program has been working with the
How to Measure HVAC System Airflow
How to Measure HVAC System Airflow About National Comfort Institute National Comfort Institute is an international training Since our and beginning development in 1994 company we have trained with and
Data Bulletin. Mounting Variable Frequency Drives in Electrical Enclosures Thermal Concerns OVERVIEW WHY VARIABLE FREQUENCY DRIVES THERMAL MANAGEMENT?
Data Bulletin April 2001 Raleigh, NC, USA Mounting Variable Frequency Drives in Electrical Enclosures Thermal Concerns OVERVIEW Variable frequency drives are available from manufacturers as enclosed engineered
Fan Applications & System Guide
Fan Applications & System Guide Airflow for general ventilation can be calculated by; Area Method Air Change Method Occupancy Method Ventilation Calculation Methods Area Method Derives the ventilation
Mechanical and Natural Ventilation
BBSE3006: Air Conditioning and Refrigeration II http://www.hku.hk/bse/bbse3006/ Mechanical and Natural Ventilation Dr. Sam C. M. Hui Department of Mechanical Engineering The University of Hong Kong E-mail:
Today, healthcare facilities must be prepared to face
Alternate Methods for USING GERMICIDAL UV-C Disinfection Lamps TO SUPPLEMENT HEPA Filtration By Dave Shagott Today, healthcare facilities must be prepared to face potential large-scale threats from chemical,
Spetec. Laminar Flow Box. Portable Clean Room Technology
Spetec Laminar Flow Box Portable Clean Room Technology 1 Fundamentals Portable Clean Room Technology Laminar Flow The basis for the development of the clean room technology was first established in the
CETA Application Guide for the Exhaust System Requirements of Class II, Type B Biosafety Cabinets CAG-007-2010 March 24, 2010
CETA Application Guide for the Exhaust System Requirements of Class II, Type B Biosafety Cabinets CAG-007-2010 March 24, 2010 1. Background Class II Type B Biosafety Cabinets (BSCs) are unique laboratory
Winnipeg Fire Department Fire Prevention Branch
Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of
Development of Ventilation Strategy in Diesel Engine Power Plant by Using CFD Modelling
Development of Ventilation Strategy in Diesel Engine Power Plant by Using CFD Modelling Panu Mustakallio and Risto Kosonen Halton Oy, Haltonintie 1-3, 47400 Kausala, Finland E-mail: [email protected]
VAV Laboratory Room Airflow The Lowdown on Turndown
Technology Report March, 2003 VAV Laboratory The Lowdown on Turndown Turndown comparison of these two turndown ratios. Note the small actual airflow difference between them. control ranges are normally
Exhaust Calculation Booklet
Exhaust Calculation Booklet American Dryer Corporation 88 Currant Road Fall River MA 02720-4781 Telephone: (508) 678-9000 / Fax: (508) 678-9447 e-mail: [email protected] ADC Part No. 450450 Exhaust
ASTACEA4 Inspect complex/central air conditioning systems
Overview This Unit covers the competences required to inspect complex/central air conditioning systems as defined by the CIBSE TM 44 Figure 1.1: Summary of system types and their component parts. The air
SENTRY AIR SYSTEMS, INC. PHARMACEUTICAL COMPOUNDING CONTAINMENT SYSTEMS SIMPLE SOLUTIONS FOR CLEANER AIR. www.sentryair.com 1.800.799.
SENTRY AIR SYSTEMS, INC. PHARMACEUTICAL COMPOUNDING CONTAINMENT SYSTEMS SIMPLE SOLUTIONS FOR CLEANER AIR 1.800.799.4609 www.sentryair.com Pharmaceutical Compounding Safety Solutions Sentry Air Systems
city of edmonds development information
#B17 city of edmonds development information Commercial Kitchen Hood & Hood Fire Suppression System Permit Submittal Requirements PERMIT REQUIRED: CODES: FEES: A Commercial Kitchen Hood Mechanical Permit
Biosafety Level 2 (BSL-2) Safety Guidelines
BLS-4 Biosafety Level 2 (BSL-2) Safety Guidelines BSL-3 BSL-2 BSL-1 BSL-2 builds upon BSL-1. If you work in a lab that is designated a BSL-2, the microbes used pose moderate hazards to laboratory staff
Guide to in situ leak testing of HEPA filter configurations that cannot be conventionally scan tested
DOP Solutions Technical Document: Guide to in situ leak testing of HEPA filter configurations that cannot be conventionally scan tested Issue 1: Prepared by Neil Stephenson and Tim Triggs and edited by
Geismar Site Reviewed: 07/05/16 Effective: 07/05/16 Supersedes: 08/04/14 Preparer: Owner: Approver: S/IH Team Leader S/IH Team Leader Manager LA Hub
BASF Corporation Title: LOCAL EXHAUST VENTILATION Individual Unit Function: Industrial Hygiene Procedure No.: IH-3 Page: 1 of 12 Geismar Site Reviewed: 07/05/16 Effective: 07/05/16 Supersedes: 08/04/14
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB
Lead Exposure Management Plan
Lead Exposure Management Plan 1.0. Policy CSUF has developed the Lead Exposure Management Plan to reduce occupational and environmental exposure to lead, a potent neurotoxin and carcinogen that causes
VENTILATION CHAPTER 4
CHAPTER 4 VENTILATION SECTION MC 401 GENERAL 401.1 Scope. This chapter shall govern the ventilation of spaces within a building intended to be occupied. This chapter does not govern the requirements for
SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION
SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION The purpose of this guide specification is to assist the specifier in correctly specifying Mechanical System Testing
CONTROL METHODS. There are five ways to control the release of asbestos fibers:
Control Methods CONTROL METHODS When asbestos containing materials are found in a building, the owner must decide which method or methods will be used to deal with the asbestos. The decision will be based
UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS
UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS: Carefully read these instructions before installing your new air-conditioner. AUSTRALIAN AUTOMOTIVE AIR AL00500054E 1 Table
WIBObarrier OCS - Open Containment Systems WIBObarrier CCS - Closed Containment Systems
WIBOjekt and WIBObarrier Air Curtain Systems. The perfect protection for person, product and environment. Filling Weighing Sampling Research Safe handling with high potent products / API WIBObarrier OCS
Stainless Steel Worksurface 3 Feet Hood A10-WS-PR3 A10-WS-SR3 4 Feet Hood A10-WS-PR4 A10-WS-SR4 6 Feet Hood A10-WS-PR6 A10-WS-SR6.
Product Sampler #1 Laminar Flow Hoods / Laminar Flow Cabinets: 1- Benchtop Vertical Laminar Flow Hoods- Air Recirculation Available s: Clean Bench Class 100 Bench-top Vertical Laminar Flow Hoods with Air-recirculation
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to
Fläkt Woods Building Future
Energy, Expertise and Environment with Fläkt Woods Fläkt Woods Building Future Saving energy in building ventilation You must save 20% on energy before 2020. Following the Kyoto protocol the European Union
International Standard ISO 14644
International Standard ISO 14644 Cleanrooms and associated controlled environments Praphon Angtrakool Food and Drug Administration 1 International Standard : ISO 14644 ISO 14644 consists of the following
Basic Selection & Proper Application of Overhead Air Distribution Devices
Basic Selection & Proper Application of Overhead Air Distribution Devices GRD Selection & Application Terms Selection Throw Sound Installation Variations affect Performance Inlet Effects Basics Return
Planning Information. Passenger and Freight Elevators.
A company of ThyssenKrupp Elevator Thyssen Aufzüge tk This planning information will give you an overview of the most important planning criteria of passenger and freight elevators. However you should
product application guide
Understanding Fan System Effects Fan Application FA/101-99 product application guide A technical bulletin for engineers, contractors and students in the air movement and control industry. The air moving
Both health-care facility classification and area classification, as per CSA, determine the design requirements.
HEATING, VENTILATION AND AIR-CONDITIONING SYSTEM (HVAC) Class 1 Facility: General Anesthesia Heating, ventilation and air-conditioning system standards are a primary infection prevention and control strategy
HEPA-filtered Negative Air Machines and their Role in Creating Airborne Infection Isolation Rooms with the ECU AnteRoom. Frequently Asked Questions
HEPA-filtered Negative Air Machines and their Role in Creating Airborne Infection Isolation Rooms with the ECU AnteRoom Frequently Asked Questions What is a negative air machine and why do I need one?
KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS
St. Louis County Department of Public Works Division of Code Enforcement KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS This guideline is intended to provide the homeowner/contractor with the
Using Portable Spot Air Conditioners in Industrial Applications
Using Portable Spot Air Conditioners in Industrial Applications Cooling People, Processes and Equipment In today s highly competitive manufacturing sector, companies are constantly looking for new ways
Cooking at the Speed of light!
Cooking at the Infrared Cooking & Colouring Infrabaker is a modular infrared continuous cooking system developed by Infrabaker International. The machine is designed to cook and/or put colour on a wide
SPACE TYPE: LABORATORY (WET) FOR CHEMISTRY AND BIOLOGY
SPACE TYPE: LABORATORY (WET) FOR CHEMISTRY AND BIOLOGY Construction Criteria The unit costs for (Wet) space types are based on the construction quality and design features in the following table. This
Ventilation Solutions Radon Mitigation
Ventilation Solutions Radon Mitigation 2 Radon Mitigation Radon is a health hazard with a simple solution Radon is everywhere! You can t see radon and you can t smell it or taste it, but it may be a problem
Specification of Requirements for Ventilated Cage Rack System
Specification of Requirements for Ventilated Cage Rack System 1.0 General 1.1 This specification comprises minimum requirements for purchase and installation of ten (10) each Ventilated Cage Racks with
How to Estimate the Cost of a. Laboratory Renovation. Candidate Number: 0714144
How to Estimate the Cost of a Laboratory Renovation Candidate Number: 0714144 December 15, 2014 1 Table of Contents Cover Page Page 1 Table of Contents Page 2 Introduction Page 3 Types & Methods of Measurements
ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS
ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS In this document are the fire safety equipment maintenance requirements that are found in Division B of the Alberta Fire Code (AFC 2006) for
Laboratory Safety and Environmental Health Assessment Program
Laboratory Safety and Environmental Health Assessment Program Principal Investigators and Faculty are vital to the success of safety and environmental compliance programs in Colorado School of Mines research
Questions & Answers (Q & A) Regarding Asbestos Treatment with the Fire Suppression and Renovation Project
Questions & Answers (Q & A) Regarding Asbestos Treatment with the Fire Suppression and Renovation Project The Watergate Community is currently in the process with the fire suppression and interior renovations
HVAC Code Requirements
one and two family dwellings? Answer: SECTION 2001: GENERAL 2001.1 Air supply. Fuel-burning equipment shall be provided with a supply of air for fuel combustion, draft hood dilution and ventilation of
Mechanical Heating Ventilation and Air Conditioning Ductwork and Duct Accessories
Basis of Design This section applies to the design and installation of ductwork, air terminal boxes, air outlets and inlets, volume dampers, pressure relief dampers, smoke/fire dampers, and smoke/fire
Air Conditioning. The opportunity for energy efficiency. Low cost actions to reduce energy usage now
Fact Sheet #6 Air Conditioning In this fact sheet you will discover: The opportunity for energy efficiency How air conditioning works Low cost actions to reduce energy usage now Investments to reduce costs
Both health-care facility classification and area classification, as per CSA, determine the design requirements.
HEATING, VENTILATION AND AIR-CONDITIONING SYSTEM (HVAC) Class 3 Facility: Local Anesthesia Heating, ventilation and air-conditioning system standards are a primary infection prevention and control strategy
Bring the fresh in. Dedicated Outside Air Systems
Bring the fresh in. Dedicated Outside Air Systems The inside story on outside air. On average, we breathe in 3,400 gallons of air each day. Ambient indoor air pollution is a major problem, affecting health
Laboratory Design & Construction Guidelines
Laboratory Design & Construction Guidelines Department of Environmental Health & Safety EHS-M-35 Page 1 Issue Date: 03/01/10 General Health and Safety The USC Environmental Health and Safety Department
Procedure for testing the integrity of the Festo and Numatics valve stacks:
Procedure for testing the integrity of the Festo and Numatics valve stacks: 1. Disconnect the Injection Cylinder Clevis from the Injection Lever; let the Injection Cylinder lean back clear of the Injection
R432. Health, Health Systems Improvement, Licensing. R432-5. Nursing Facility Construction. R432-5-1. Legal Authority. R432-5-2. Purpose.
R432. Health, Health Systems Improvement, Licensing. R432-5. Nursing Facility Construction. R432-5-1. Legal Authority. This rule is promulgated pursuant to Title 26, Chapter 21. R432-5-2. Purpose. The
Laminar Flow Cabinets and Workstations
VERTICAL AND HORIZONTAL HEPA FILTERED SYSTEMS FOR PROCESS OR OPERATOR PROTECTION Laminar Flow Cabinets and Workstations For procedures requiring protection from particulate contamination and for aseptic
Electrical. This section applies to the design and installation of building power distribution systems.
Basis of Design This section applies to the design and installation of building power distribution systems. Design Criteria This section contains the architectural, structural and mechanical provisions
HVAC Systems in Schools & Commercial Buildings and Radon
HVAC Systems in Schools & Commercial Buildings and Radon References US EPA Radon Prevention in the Design and Construction of Schools and Other Large Buildings http://www.epa.gov/ordntrnt/ord/nrmrl/pubs/1993/air/
LEAD COMPLIANCE PLAN University of California Santa Cruz
University of California Santa Cruz Lead Safety Programs, July 2009 I. PURPOSE LEAD COMPLIANCE PLAN University of California Santa Cruz The purpose of this program is to establish specific policy concerning
How To Test A Fume Cupboard
Jürgen Liebsch WALDNER Labor EN 14175 Requirements for Fume Cupboards DIN 12924 EN 14175 The contents of the DIN 12924 part 1 standard is divided into 5 parts in the EN 14175 standard: 14175-1 Terms and
Single Family Residential Basement Finish
How to Use This Guide Building Guide Pottawattamie County Planning & Development Department Building & Safety Division Single Family Residential Basement Finish Provide two (2) sets of plans and complete
Using Carbon Dioxide as a Tracer Gas to Measure Air Change Rate in a Single Zone
Using Carbon Dioxide as a Tracer Gas to Measure Air Change Rate in a Single Zone C. Simmons, F. Boelter, G. Crawford, Boelter & Yates, Inc., Park Ridge, IL Presented by: Catherine E. Simmons, CIH Situation
Range Equipment HVAC Design & Supply Modular Ranges
Range Equipment HVAC Design & Supply Modular Ranges SRI Shooting Range Industries LLC, SRI is a premier design and manufacturing company of quality and innovative live fire Modular Containerized Small
2014 British Columbia Building Code Changes
District of Houston 250-845-2238 2014 British Columbia Building Code Changes A District of Houston interpretation of the 2014 Building Code Changes for 9.36 & 9.32 The following changes reflect the most
Environmental Monitoring
Chapter 10 Environmental Monitoring By the end of this chapter, you will be able to: l List the types of environmental testing l Name three types of checks that are carried out to ensure the isolator is
HVAC Characteristics. Test Space HVAC Characteristics
HVAC Characteristics Information on the characteristics of the heating, ventilation, and air conditioning (HVAC) system(s) in the entire BASE building including types of ventilation, equipment configurations,
DRY CLEANING PLANTS REQUIREMENTS FOR INSTALLATION AND OPERATION
DEPARTMENT OF TRADE MERCHANT SHIPPING NOTICE NO.M.847 DRY CLEANING PLANTS REQUIREMENTS FOR INSTALLATION AND OPERATION Notice to Shipowners, Masters, Shipbuilders and Repairers 1. It has come to the notice
REQUIREMENT 5. Light Switches, Electrical Outlets, Thermostats, and Other Environmental Controls in Accessible Locations
Chapter Five: REQUIREMENT 5 Light Switches, Electrical Outlets, Thermostats, and Other Environmental Controls in Accessible Locations 5...covered multifamily dwellings with a building entrance on an accessible
How To Control A Medical Device With A Pc System
Clean room monitoring and disinfection FMS 5.0, the Leading Facility Monitoring Software TSI FMS system is an advanced, reliable, and user-friendly monitoring software suite that features a truly open
Acoustical Design Guidelines for HVAC Systems in Schools
Acoustical Design Guidelines for HVAC Systems in Schools Seminar 9, ASHRAE Summer Meeting Albuquerque, New Mexico Sponsor: TC 2.6 Sound and Vibration Robert M. Lilkendey Associate Principal Consultant