Installation, Operation and Maintenance Instructions Viper -S Solid Dielectric Reclosers Three Phase, Vacuum Recloser.

Size: px
Start display at page:

Download "Installation, Operation and Maintenance Instructions Viper -S Solid Dielectric Reclosers Three Phase, Vacuum Recloser."

Transcription

1 Installation, Operation and Maintenance Instructions Viper -S Solid Dielectric Reclosers Three Phase, Vacuum Recloser GWI Rev. 6 May, 2008 Supersedes Rev. 5 dated October,2005 Table of Contents Section Page 1. Introduction 2 2. Safety Information & Practices 4 3. Recloser Description 6 4. Installation 7 5. Operation Maintenance Testing Troubleshooting Ratings Attachments 38 This information is transmitted by G&W Electric Co. and accepted by you subject to the following understanding and agreement: By accepting these instructions and any included drawings you agree that all rights to the drawing and information contained herein, as well as the proprietary and novel features of the subject matter, are reserved by G&W Electric Co. and that devices embodying such features or information derived from these disclosures will not be manufactured by you or disclosed to others without the expressed written consent of G&W Electric Co. These drawings and information contained herein are and remain the property of G&W Electric Co. and are not to be copied, reproduced or disclosed to others without the expressed written consent of G&W Electric Co. Page 1 G&W ELECTRIC CO G&W Electric Co. PRINTED IN U.S.A.

2 SECTION 1 INTRODUCTION 1.1 General This document is intended to provide the user with necessary information to properly receive, inspect, test, install and maintain G&W Viper-S solid dielectric reclosers. If after reviewing the information contained herein, you should have any questions, please contact your G&W representative or call our customer service number. Read these Instructions Keep these Instructions Read and understand the contents of this document and follow all locally approved procedures and safety practices before installing, operating or maintaining this equipment. Be sure to read and understand the Safety Information in Section 2. This document is a permanent part of your G&W recloser. Keep it in a safe location where it can be readily available and referred to as necessary. How to Contact G&W By Phone: By Fax: Mail: Internet: , Monday through Friday, 8:00 AM to 5:00 PM Central Time webmail@gwelec.com 3500 W. 127 th Street, Blue Island, Illinois 60406, USA To find your local G&W Representative visit our Web site: Qualified Persons WARNING The equipment covered by this document is intended to be installed, operated and maintained by qualified persons who are trained in the installation, operation and maintenance of electric power distribution equipment along with the associated hazards. A qualified person has been trained and is competent: To de-energize, clear and tag circuits and equipment in accordance with established safety procedures To distinguish between live parts from non-live parts of the equipment In the proper use of insulated tools, wears protective equipment such as rubber gloves, hard hat, safety glasses, flash-clothes, etc. in accordance with established safety practices and is trained in the care of such equipment Is certified in rendering first aid, especially in the technique of removing a person in contact with a live circuit and in applying cardiopulmonary respiration. These instructions are intended only for qualified persons and are not intended as a substitute for adequate training and experience in safety procedures for this type of equipment. 1.3 Shipment Inspection Each recloser is completely assembled, tested, and inspected at the factory. It is in good condition when accepted by the carrier for shipment. Examine the crated equipment carefully for any damage that may have occurred in transit. If damage is found, a claim must be filed at once with the transportation company. Uncrate and remove packing as soon as possible after receiving the equipment. Examine the equipment carefully for any hidden damage that may have occurred in transit and was previously undetected. If damage is found, a claim should be filed at once with the transportation company. Page 2 GWI Rev. 6

3 Batteries in recloser control(s) are shipped with the positive lead disconnected. If required for inspection, the batteries may be reconnected to the control. It is possible that the batteries may discharge during shipment and/or storage and may need to be recharged prior to having the capacity to operate the control and/or the recloser. 1.4 Storage Reclosers that will not be installed immediately should be suitably stored in a clean, dry location. Make certain reclosers are protected from potential damage. If the batteries in the control are connected during receiving inspection, they should be disconnected by removing the positive lead from the battery pack until such time as the recloser is installed. 1.5 Standards G&W Viper-S reclosers are designed and tested in accordance with the following standards: ANSI/IEEE C ANSI/IEEE C ANSI C IEC ANSI ANSI C62.41 Page 3 GWI Rev. 6

4 SECTION 2. SAFETY INFORMATION AND PRECAUTIONS 2.1 Safety Alert Messages The following is important safety information. For safe installation and operation, be sure to read and understand all danger, warning and caution information. The various types of safety alert messages are described below: DANGER DANGER - Indicates an imminently hazardous situation which if not avoided, will result in death or serious injury. WARNING WARNING - Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. CAUTION CAUTION - Indicates a potentially hazardous situation which if not avoided, may result in minor or moderate injury. May also be used to alert against unsafe practices. 2.2 Following Safety Instructions Carefully read all safety messages in this manual and on your equipment. Keep safety signs in good condition. Replace missing or damaged safety signs. Keep your equipment in proper working condition. Unauthorized modifications to the equipment may impair the function and/or safety and effect equipment life. If you do not understand any part of these safety instructions and need assistance, contact your G&W representative or G&W customer service. 2.3 Replacement Instruction and Labels Replacement instructions and safety labels are available from G&W. To obtain them, please contact Customer Service. 2.4 X- Radiation Limits G&W Viper reclosers are designed and tested in accordance with applicable sections of ANSI/IEEE C and C , which include the following information. Reference the above standards for more detailed information. The known United States manufacturers of vacuum interrupters initiated a test program during July of 1968 (as a Task Force of the NEMA Switchgear Section) to determine the present levels of X-radiation, if any, being emitted from high-voltage power vacuum interrupters, and to suggest permissible levels of radiation from such interrupters on the basis of their recognized application. Each manufacturer conducted a series of tests on new vacuum interrupters taken from stock and recorded the X- Page 4 GWI Rev. 6

5 radiation levels, if any, under the following conditions: 1. Dielectric withstand test voltage applied to new interrupters 2. Fault current interruption (where applicable) 3. Load current interruption 4. Dielectric withstand test voltages after fault current interruption 5. Dielectric withstand test voltages after load current interruption As a result of evaluating the results of the aforementioned tests, the manufacturers concluded that neither the general public nor users will be subjected to harmful X-radiation due to normal application and operation of 15.5kV rated vacuum interrupter devices when applied within their assigned ratings and when the voltage applied across the open contacts of the interrupters is 15.5kV or less. The manufacturers also concluded that at the permissible user dielectric withstand test voltage of 37.5kV radiation levels are negligible for vacuum interrupters rated 15.5kV. Normal electrical safety precautions will require the user to be at a safe distance from the interrupters which will provide sufficient protection. Precautions: If distances normally required for electrical safety are maintained, the exposure to test personnel will generally not exceed established dose limits. It is nevertheless recommended that adequate precautions such as shielding or distance be used to protect test personnel against possible higher X-radiation occurrences due, for example, to incorrect contact spacing or to the application of voltages in excess of those specified in column of Table 1. Table 1 Test Voltage and X-Radiation Limits at One-Meter Distance (Note 1) Maximum X-Radiation Averaged Over an Area Not Greater than 100 cm 2 (mr/h) Rated Max Voltage (kv RMS) (note 2) (Col 1) Low-Frequency Insulation Level Withstand Test (kv RMS) (Col 2) At Rated Max Voltage (Col 3) At Low Frequency Insulation Withstand Test Voltage (Col 4) (Note 3) Notes: (1) Table 1 will be expanded as additional ratings become available (2) This rating is the maximum line-to-line system voltage on which the vacuum interrupter is normally applied, whether the interrupter is rated on a single-phase or on a three-phase basis, using one interrupter per pole. (3) See Appendix A of ANSI C for derivation of this value. Page 5 GWI Rev. 6

6 SECTION 3 RECLOSER DESCRIPTION 3.1 General These instructions provide installation, operating and maintenance instructions for the G&W solid dielectric, threephase, microprocessor-controlled Viper-S recloser. 3.2 Read This Manual First Read and understand the contents of this manual and follow all locally approved procedures and safety practices before installing or operating this equipment. The Viper-S recloser designed for use with various Schweitzer Engineering Laboratories controls including the SEL-351R Recloser Control, SEL-651R Recloser Control, and SEL- 351S Feed Management Control. Refer to the separate operating and maintenance instructions provided with the control. 3.3 Additional Information These instructions cannot cover all details or variations in the equipment, procedures, or processes described nor provide directions for meeting every possible contingency during installation, operation, or maintenance. For additional information, contact your G&W representative. 3.4 Description of Operation G&W s Viper-S recloser is a three-phase, microprocessor-controlled, vacuum recloser. The recloser can be operated and interrogated through a SCADA system for fault detection and recloser isolation. The recloser is suitable for operation through a temperature range of -40ºC to +65ºC (-40ºF to +150ºF). Figure 1. Viper-S recloser with horizontal pole mount bracket shown. Page 6 GWI Rev. 6

7 SECTION 4 INSTALLATION WARNING This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply can result in death, severe personal injury and equipment damage. WARNING Hazardous voltage. Always use a hook stick when working with this equipment. Failure to do so can result in contact with high voltage, which will cause severe injury or death. When installing the recloser, refer to the applicable recloser mounting instructions. 4.1 Check the data plate ratings. Make sure the ratings and settings on the recloser data plate are correct for the planned installation. 4.2 Perform high-potential withstand tests. Prior to installing the Viper recloser, perform high-potential withstand tests. Refer to Section 7.2 for high-potential withstand test procedures. 4.3 Install the recloser. WARNING Do not lift or handle recloser by the bushings. Doing so may result in damage to the recloser and possible injury or death to personnel Lifting recloser Follow all approved safety practices when lifting the equipment. Viper-S reclosers have four lifting eyes located on the tank (Figure 2). All lifting eyes must be used when lifting. There are also two holes in the top of the bracket if needed. Lift the unit smoothly and do not allow the unit to shift. Use proper equipment to obtain a vertical lift without damaging the unit. See recloser customer drawing for approximate weight and lifting provision details. Viper-S reclosers are shipped palletized (bolted on to a pallet). When moving with a forklift truck, the recloser must remain bolted to the pallet to avoid damage. When ready to mount to the pole, make certain to unbolt the recloser and bracket assembly from the pallet. G&W mounting brackets should always be used Mounting to pole The horizontal pole mount bracket is supplied with two mounting holes (Figure 2). Measure the distance between the holes and drill the pole to the desired position. Position one ½ bolt with flat washer through the top hole and secure with a flat washer, lock washer and nut on the back of the pole such that the front bolt head extends from the pole approximately 3-4 inches. Slowly lift the bracket and recloser assembly and position the top slotted mounting hole of the bracket over the front bolt and washer installed in the pole. Slowly lower the unit such that the top bolt seats itself through the slot on the bracket. Do not remove lifting equipment until the unit is completely secured to the pole. Tighten the top bolt and hardware. Insert the bottom bolt with the same hardware as the top through the bottom hole of the bracket and secure to the pole. Take care when removing the lifting equipment as to not damage the recloser. Page 7 GWI Rev. 6

8 Figure 2. Lifting provision locations and horizontal mounting bracket hole dimensions. Check that the recloser, in its installed position, is secured and that mountings are adequate to support the weight of the recloser. WARNING Hazardous voltage. Always use a hook stick when operating this equipment. Failure to do so can result in contact with high voltage, which will cause severe injury or death. CAUTION Bushings may have sharp edges. Wear protective gloves when handling the unit. Failure to do so can result in personal injury. Page 8 GWI Rev. 6

9 4.4 Ground the recloser. Make the ground connection to the ground connector. Ground bosses are located on the recloser mechanism enclosure. See customer drawing for boss location(s). See Figure 3 for the required grounding procedures for the Viper recloser. To ensure a good ground connection, the top surface of each boss must be sanded to expose bare metal before making a ground connection. The recloser tank and control must be attached at a common grounding point located at the base of the pole or substation rack. 4.5 Install the control. Refer to the control installation manual and install the control. Make sure the control cable is connected between the control and the recloser, the control is properly programmed for the planned installation, and the control is grounded. Page 9 GWI Rev. 6

10 Figure 3: Recommended grounding method for Viper-S reclosers. Page 10 GWI Rev. 6

11 CAUTION Follow all locally approved safety practices when lifting and mounting the equipment. Use the lifting lugs provided. Lift the unit smoothly and do not allow the unit to shift. Improper lifting can result in equipment damage. 4.6 Make high-voltage line connections (Figure 4). Note: Six single phase and one three phase disconnect bypass switches are not required, but are highly recommended as they facilitate switching and isolation. Each cable must be properly terminated. Bushings are not intended to provide strain relief. Figure 4. Connection diagram shows complete surge protection and illustrates bypass and disconnect switches. WARNING Do not terminate the overhead conductor directly to the bushing without the use of a separate strain relief device. Failure to use a strain relief may result in damage to the recloser Connect high voltage lines to recloser bushing terminals Provide surge arrester protection. Surge arrester protection should be provided on both sides of the recloser. Refer to Figure 5 for terminal identification of the Viper-S solid dielectric reclosers. Page 11 GWI Rev. 6

12 4.7 Operation Check & Installation Testing Figure 5. Terminal identification of Viper-S reclosers. High potential testing on reclosers may be conducted. Refer to Section 7, Testing. Each unit has been fully tested at the factory in accordance with the appropriate standards. It is highly recommended that a high-voltage test be conducted prior to the final connection of the unit to the electrical system. Tests should be conducted across each recloser in the open position and between each phase and ground (earth) with the recloser in the closed position. Each recloser termination must be properly terminated prior to high-voltage testing. See Section 7 for testing levels. Page 12 GWI Rev. 6

13 SECTION 5 OPERATION 5.1 General Reclosers are assigned ratings by the manufacturer and have been designed and tested using levels established by ANSI and/or IEC standards. Design and production tests are conducted to demonstrate that the equipment will perform within the ratings on the nameplate and customer drawing. See Section 9 for ratings and customer drawing in Section 10. Reclosers are designed to be operated only by Qualified Persons. See Section 1 for qualifications. WARNING Equipment in service will perform to established ratings only if properly installed, operated and maintained. Power reclosers are characterized by high voltage and high continuous and short circuit currents. It should be installed, operated and maintained by Qualified Personnel. Failure to follow instructions or install operate or maintain the equipment may result in failure of the equipment and serious injury or death. For further information on operation and maintenance of equipment see ANSI C2 standards. Reclosers have been designed and evaluated using the levels established by applicable sections of ANSI and IEC Standards, which assure the expected life of the recloser with minimal maintenance. See Section 6 for maintenance recommendations. WARNING Do not attempt to close into fault in excess of the recloser ratings or to interrupt currents in excess of interrupting ratings. Either may result in damage to the recloser and possible injury or death. WARNING This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply can result in death, severe personal injury and equipment damage. WARNING Hazardous Voltage. Do not rely on the position indication indicator or the manual open handle. They do not insure that the line has been de-energized. Always establish a visible disconnect. Failure to follow proper safety precautions can result in contact with high voltage and serious injury or death. Page 13 GWI Rev. 6

14 5.2 Electrical Operation The Viper-S recloser utilizes an interface circuit located in the mechanism enclosure. The electronic interface circuit controls the opening and closing signals to the magnetic actuator. See Figure 7 for connection and wiring diagrams. IMPORTANT: If the yellow manual OPEN handle remains in the down position, the recloser cannot be closed 5.3 AC Interface Referencing Figure 6, select the appropriate option and connect the AC power. Option 1: Recloser powered through control. Option 2: Recloser powered direct from potential transformer. Figure 6. Viper-S recloser configuration with AC interface options. Page 14 GWI Rev. 6

15 Figure 7. Connection diagram for Viper recloser with AC interface. Page 15 GWI Rev. 6

16 5.4 OPEN/CLOSE Contact Position Indicator WARNING Hazardous Voltage. Do not rely on the position indication indicator or the manual open handle. They do not insure that the line has been de-energized. Always establish a visible disconnect. Failure to follow proper safety precautions can result in contact with high voltage and serious injury or death. The OPEN/CLOSE contact position indicator consists of a red CLOSED and a green OPEN indicator located on the bottom of the mechanism housing (see Figure 8). 5.5 Hook stick Operation (Manual Open, Electrical Close) The recloser may be opened manually by using a hook stick to pull down the manual OPEN handle located on the front of the recloser (see Figure 8) approximately 45 below horizontal. This will require a typically pulling force of 50 pounds. The recloser microprocessor control is deactivated until the yellow manual handle is returned to the UP position. To close the recloser, first push the yellow manual open handle up to the horizontal position. Then close the recloser using the microprocessor control. Page 16 GWI Rev. 6

17 Figure 8. Viper-S recloser components. Operating handle shown in lockout position. Page 17 GWI Rev. 6

18 5.6 Dead-line Operation and Remote Status Option (if included) AC and DC Interface. Available only with SEL 351R. This optional feature requires the addition of a 6-pin cable and permits the following capabilities: 1) Dead line operation: The DC/DC converter that is housed within the Viper-S mechanism housing is connected to the 24VDC batteries via one of the 351R output ports. In order for the dead line operation feature to operate properly, the following setting has been programmed by G&W into the SEL 351R: The designated output port is programmed at the factory to turn ON when AC is lost and to turn OFF when the AC is present. The default factory program line is: OUT107 = DISCHG *!DISTST Any output port of the 351R controller can be assigned for use with the dead line operation feature. In order to designate a different output port for use with this feature, the conductor on the terminal block of the 351R must be moved from Output 107 to the desired output location. In order to reassign the output within the 351R, the following programming line should be used: OUTXXX = DISCHG *!DISTST (where XXX refers to the output destination. i.e., 107). If new settings are uploaded to the control after leaving the factory, the program line above must be reentered manually. For devices shipped prior to the effective date of these instructions, the factory assigned output port used may vary, or in some cases, no output port was used. For these devices, the output port may be reassigned by the user by following the above steps. 2) AC/DC Power Supply Status: Monitors the status of the output of the interrupter power supply and randomly displays it s status at the control. Reference Figure 10 for remote monitoring connection location. Option 1: Recloser powered through control. Option 2: Recloser powered direct from potential transformer. Figure 9. Viper-S recloser configuration with AC/DC interface options. Page 18 GWI Rev. 6

19 Figure 10. Connection diagram for Viper-S recloser with dead-line operation Page 19 GWI Rev. 6

20 5.7 Voltage Sensing Bushings (if included) Available only with SEL 651R This optional feature requires a SEL 651R Recloser control and a 19 pin connector. The Viper-S can be equipped with internal voltage screens for voltage sensing. The voltage sensors provide voltage measurement to the SEL 651R control. Each Viper-S and 651R control is pretested and calibrated at the factory prior to shipment. Three ratio correction factors are determined, as a result of the calibration, and programmed into the control. Refer to the 651R Operations Manual for Ratio Correction setting information. Ratio Correction Factor values for each recloser are printed on two labels and supplied with the recloser and control. One label is located on the inside of the SEL 651R enclosure front door while the other can be found on the inside surface of the lid of the Viper-S mechanism enclosure. Option 1: Recloser powered through control. Option 2: Recloser powered direct from potential transformer. Figure 11: Viper recloser configuration with AC/DC interface options. Page 20 GWI Rev. 6

21 Figure 12: Connection diagram for Viper-S recloser with Voltage Sensing Bushings Page 21 GWI Rev. 6

22 5.8 The DC Power Option requires the utilization of DC power systems VDC The following are the required specifications when utilizing 48V DC Power Systems Operation Voltage range of DC/DC converter is 36VDC 76VDC. There is no voltage transient protection in front of the DC/DC converter. CAUTION Battery voltage exceeding 200VDC can damage the DC/DC converter. This can damage the switch and/or leave it inoperative. Make certain 68VDC battery voltage does not exceed 180VDC. Capacitor charging time after opening operation is approximately 200ms. First reclose interval should be greater than 300ms. Capacitor charging time after closing operation is approximately 450ms. The second, third and fourth reclose intervals should be greater than 650ms The following are the required specifications when utilizing 125V DC Power Systems Operation Voltage range of DC/DC converter is 100VDC 200VDC. There is no voltage transient protection in front of the DC/DC converter. CAUTION CAUTION Battery voltage exceeding 200VDC can damage the DC/DC converter. This can damage the switch and/or leave it inoperative. Make certain battery voltage does not exceed 180VDC. Capacitor charging time after opening operation is approximately 200ms. First reclose interval should be greater than 300ms. Capacitor charging time after closing operation is approximately 450ms. The second, third and fourth reclose intervals should be greater than 650ms. Page 22 GWI Rev. 6

23 5.8.3 DC Power Interface Reference Figure 13 for typical DC power, Control Cable and AC (for Heaters) cable connections. Reference Figure 14a for typical interface connections with AC heater. Reference Figure 14b for typical interface connections with DC heater. 2 Pin AC Heater Connection 14 pin Control Cable Connection DC Power Connection 48 VDC or 125 VDC Figure 13. Viper-S recloser configurations with DC interface option. CAUTION CAUTION Incorrect polarity can damage the DC/DC converter. This can damage the switch and/or leave it inoperative. Make certain to make connections to the proper polarity DC Power Requirements DC power supply with AC heater: Figure 14a 500 Watts Peak: One second 50 Watts Nominal DC power supply with DC heater: Figure 14b 600 Watts Peak: One second 100 Watts Nominal Page 23 GWI Rev. 6

24 Figure 14a. Connection diagram for DC Viper with AC heater Page 24 GWI Rev. 6

25 Figure 14b. Connection diagram for DC Viper with DC heater Page 25 GWI Rev. 6

26 5.9 Changing the Current Transformer Ratio without Voltage Screen 1) Disconnect AC power cable from the interrupter. 2) Remove the bottom of the interrupter mechanism enclosure. 3) Locate the light green CT connection/protection board (Figure 15a). The board is approximately 6 x 8. The board is labeled CONTROL and has two columns of three, three position female connectors. One column will be labeled 1000 and the other ) To change the CT ratio, simply move, one at a time, the three male connectors from the 1000 column to the adjacent female connection point in the 500 column or vice versa (Figure 15b). Be certain the connections are landed properly when moving. NOTE: The control will be required to be re-programmed to recognize the new CT ratio. 5) Replace the bottom panel of the mechanism enclosure. 6) Reconnect AC power cable to the interrupter. 7) Re-program the control to recognize the new CT ratio. Figure 15a: CT board location. CT Board Figure 15b: Changing CT connections. Page 26 GWI Rev. 6

27 5.10. Changing Current Transformer ratio With Voltage Screen Technology (if applicable) 1) De-energize the recloser 2) Open the Interrupters using the yellow manual lockout handle. 3) Remove the bottom of the interrupter mechanism enclosure. 4) Locate the three small plastic jumpers in the upper left hand corner of the Junction Board (Figure 16). 5) To change the CT ratio, simply move, one at a time, the small black jumper from the 1000 position to the adjacent 500 position (Figure 16). Be certain the jumpers are landed properly when moving. NOTE: The control will be required to be re-programmed to recognize the new CT ratio (refer to SEL-651R manual). 6) Replace the bottom panel of the mechanism enclosure. 7) Reconnect AC power cable to the interrupter. 8) Reconnect the control cable to the control. 9) Push all three yellow manual lockout handles up, then push the Close button(s) in the control. Jumper location Figure 16 CT jumpers setting for 1000:1 and 500:1 CT ratio CT jumper 1000:1 500:1 500:1 1000:1 500:1 1000: Current Polarity for the CT within the Viper Page 27 GWI Rev. 6

28 Figure 17. Current Polarity from the Viper-S Recloser Primary to SEL 351R and 651R Recloser Controls Current Inputs Page 28 GWI Rev. 6

29 SECTION 6 MAINTENANCE 6.1 General The following information is for reference as a general guideline when operating or performing maintenance of Viper-S reclosers. It is difficult to anticipate all possible situations that may occur. Any questions on how to handle a specific situation should be forwarded to the local G&W representative. State and local regulations should always be considered. The G&W Viper-S recloser has been designed with a minimum mechanical life of 10,000 operations. The Viper-S recloser requires routine inspection to check for physical damage and to verify proper operation. No internal maintenance of the mechanism housing is required. However, if the recloser must be opened, personnel should be instructed to take certain precautions. During any internal maintenance, the recloser must be de-energized. WARNING Failure to place the yellow Manual Open handle in the lower position will allow the recloser to be operated either automatically, manually by use of the microprocessor control, or remotely (if so equipped). Contact with the magnetic actuator and/or linkage during operation may cause personal injury. The cover is held in place with 10, 1/4"-20 hex head bolts. The cover weighs approximately 16 lbs (7.3 kg). Take care when removing the cover. Keep the gasket surfaces clean and protect the gasket from damage. G&W recommends that the customer take advantage of SEL vacuum bottle contact wear monitoring. Please contact G&W with the Viper-S serial number to obtain data point specific to your vacuum bottle that can be used to program your SEL relay for predictive maintenance and end of life determination of your recloser. Occasional visual inspection of the recloser is recommended and if possible, should be performed periodically. Because these reclosers are applied under widely varying operating and climatic conditions, service intervals are best determined by the user based on actual operating experience. WARNING Outside Recloser Mechanism Enclosure - The mechanism may appear to have hot spots when scanned with thermal imaging devices due to internal resistance heater. This is normal. Locations of these heated areas are noted in Figure 18 as Resistance Heater and Heater. Inside Recloser Mechanism Enclosure - Make certain to avoid contact with other components inside the mechanism housing. Reference Figure 18. Specifically, do not touch the following: - The resistance heater may be hot. Contact with the heater may cause burns or personal injury. - The capacitors may maintain a voltage charge up to 55VDC for an extended period of time i.e. several days. Contact with the capacitor leads may cause a shock, misoperation or damage to the equipment. - The magnet actuator and linkage contain moving parts. Contact with moving parts if accidentally operated may cause personal injury. - Circuit boards. Contact with the control or protective circuitry may cause a static discharge and possible damage to the equipment. Page 29 GWI Rev. 6

30 Prior to returning the Manual Open handle to the UP position, secure the bottom mechanism cover and gasket with the bolts and nuts and tighten. When replacing the cover, cross-torque the bolts to 79 in-lbs. To close the recloser, first push the yellow Manual Open handle UP to the horizontal position. Then close the recloser using the microprocessor control. Figure 18: Bottom view of inside mechanism enclosure 6.2 Finish of Recloser The recloser paint finish is comprised of a two-part epoxy, gray coating (Munsell No. 5BG7/0.4). Clean using soap and water. Touch up paint is available from the factory. 6.3 Repair and Spare Parts Items such as operating handles, bushings, gaskets, UV guards, etc. are available from the factory if required. To inquire about spare or repair parts, contact G&W Representative or customer service with the recloser serial number. 6.4 Returning Equipment to Service Make sure that the line grounding means are removed Make certain recloser is in the open position. 6.5 Recloser Control The only maintainable components in the control are the batteries. Maximum life of the batteries will be achieved if the control is powered continuously allowing the batteries to maintain a full state of charge. Leaving the batteries in a discharged state for extended periods of time will substantially shorten expected battery life. Maximum battery life expectancy is five years. Batteries should be replaced with units having the same amp-hour rating as the original units. Used batteries must be disposed of properly in accordance with applicable environmental regulations. This recloser is used with Schweitzer Engineering Laboratories microprocessor-based recloser controls. Refer to the separate control operation manual. Page 30 GWI Rev. 6

31 SECTION 7 TESTING 7.1 Operations Testing After reclosers are completely installed in accordance with local practices, high voltage testing may be performed before the recloser is energized. Insure the test equipment is used in accordance with the manufacturer's instructions. DANGER Do not exceed the Maximum Dielectric Test Levels as shown in Section Exceeding the test levels can cause flash over. This can lead to a fault in the recloser or test equipment and cause serious personal injury or death. WARNING Follow these precautions when performing electrical tests: 1. Completely de-energize the recloser and disconnect it from all power sources. 2. Terminate all bushings with an insulated cap or other suitable cable termination capable of withstanding the test voltage. Failure to observe these precautions can result in flash over, injury and equipment damage. WARNING The DC withstand capability of reclosers may be reduced due to damage, electrical or mechanical wear. The DC test voltage must not exceed the withstand limits of the recloser. Application of DC voltages greater than the withstand capability of the recloser can result in flash over, injury and equipment damage. WARNING When it is necessary to test the cables connected to an energized recloser, proper insulation between the power-frequency source and the DC test equipment must be maintained. Follow the recommendations of the manufacturer of the test or fault location equipment. WARNING Hazardous Voltage. Do not rely on the position indication indicator or the manual open handle. They do not insure that the line has been de-energized. Always establish a visible disconnect. Failure to follow proper safety precautions can result in contact with high voltage and serious injury or death Check the data plate ratings. Make sure the ratings and settings on the recloser data plate (see Figure 8) are correct for the planned testing Test electrical open and close operation. Close and open the recloser contacts using the microprocessor control. Confirm that the contacts have closed and opened by: Page 31 GWI Rev. 6

32 The OPEN/CLOSE contact position indicator, or By continuity check between the recloser terminals, Test manual open. Pull the yellow manual open handle (see Figure 8) down to open the recloser contacts. Confirm that the contacts have opened by: The OPEN/CLOSE contact position indicator, or By continuity check between the recloser terminals, To close the recloser contacts: First, push the yellow manual open handle up Close the recloser using the microprocessor based control. 7.2 High Potential Withstand Testing WARNING Hazardous Voltage. Do not rely on the position indication indicator or the manual open handle. They do not insure that the line has been de-energized. Always establish a visible disconnect. Failure to follow proper safety precautions can result in contact with high voltage and serious injury or death. Use the following procedures to perform high potential withstand tests at 75% of the rated low-frequency withstand voltage for 60 seconds. See Table 3 for rated voltages and Figure 17 for test connection diagrams. Page 32 GWI Rev. 6

33 Figure 19. Connection diagrams for high potential withstand testing Test 1 (Figure 19) Close the recloser contacts Ground the recloser Connect terminals C2, B2 and A2 (see Figure 5) together Apply proper test voltage (see Table 3) to terminals C2, B2 and A The recloser should withstand the test voltage for 60 seconds. Page 33 GWI Rev. 6

34 7.2.2 Test 2 (Figure 19) Close the recloser contacts Ground the recloser Ground Phase A (terminal C2) and Phase C (terminal A2) Apply proper test voltage to Phase B (terminal B2) The recloser should withstand the test voltage for 60 seconds Test 3 (Figure 19) Open the recloser contacts Ground the recloser Connect and ground terminals C1, B1 and A1 (see Figure 5) Connect terminals C2, B2 and A Apply proper test voltage to terminals C2, B2 and A The recloser should withstand the test voltage for 60 seconds Reverse the connections, ground terminals C2, B2 and A Apply test voltage to terminals C1, B1 and A1 for 60 seconds The recloser should withstand the test voltage for 60 seconds. 7.3 Withstand Test Results The high potential withstand tests provide information on the dielectric condition of the recloser and the vacuum integrity of the interrupters. If the recloser passes the closed-contacts tests (Tests 1 and 2), but fails the open-contacts test (Test 3), the cause is likely to be in the interrupter assembly. Retest each phase individually to determine the failed phase or phases. If the recloser does not pass Tests 1, 2, or 3, contact your G&W Electric Co. representative. Page 34 GWI Rev. 6

35 Table 3. Viper-S Recloser Withstand Test Voltage - Ratings Information Recloser Rating 50 Hz 60 Hz Impulse (BIL) Withstand Rated Voltage Power Frequency 12kV 15.5kV 110kV 50kV 24kV 27kV 125kV 60kV 36kV 38kV 150kV 70kV 7.4 Factory Production Tests The following tests are performed at the factory as part of the routing production of the recloser: Circuit Resistance High Voltage Withstand Operating Assurance Tests Page 35 GWI Rev. 6

36 SECTION 8 TROUBLESHOOTING 8.1 If the Viper recloser does not perform as described in the OPERATION section of this manual, the following information may assist in troubleshooting Unit Will Not Close Make sure the yellow manual open handle is completely up Check all cables for proper connection Verify that the control has power Upon loss of ac power, check battery level Check ac power supply (potential transformer) Unit Will Not Open Electrically Check all cables for proper connection Verify that the control has power For a detail trouble shooting guide please contact G&W representative at Viper-S Recloser: Explanation of Operation and Troubleshooting Guide. Page 36 GWI Rev. 6

37 SECTION 9 RATINGS AND SPECIFICATIONS 9.1 Check Recloser Ratings Prior To Installation The recloser must be applied within its specified ratings. Check data plate ratings and compare with the system characteristics at the point of application, prior to installation. Tables 4, 5, 6, and 7 list the ratings and specifications for the Viper-S recloser. Table 4. Voltage Ratings (kv) Description 15 kv 27 kv 38 kv Maximum Voltage 15.5 kv 27 kv 38 kv Rated Basic Impulse Voltage 110 kv 125 kv 150 kv Radio Noise Limit (microvolts) 9.4 kv kv 23 kv Power Frequency Withstand (Dry) 50 kv 60 kv 70 kv Power Frequency Withstand (Wet) 45 kv 50 kv 60 kv Table 5. Current Ratings (Amperes) Description 15 kv 27 kv 38 kv Rated Continuous Current 800 A 800 A 800 A Rated 8-hour Overload Current 960 A 960 A 960 A Short Circuit Current, Symmetrical 12.5 ka 12.5 ka 12.5 ka Making Current, Asymmetrical Peak 32 ka 32 ka 32 ka Making Current, Asymmetrical RMS 20 ka 20 ka 20 ka Table 6. Mechanical Ratings Description 15 kv 27 kv 38 kv Mechanical Operations: Close/Open (minimum) 10,000 10,000 10,000 Table 7. Duty Cycle Percentage of Interrupting Rating Number of Unit Operations Minimum Circuit X/R Value Total 116 Table 8. Resistance Description 15 kv 27 kv 38 kv Busing to bushing resistance mohm max mohm max mohm max. Page 37 GWI Rev. 6

38 SECTION 10 ATTACHMENTS 10.1 Customer Drawing(s) 10.2 Supplemental Instructions Recloser Control Page 38 GWI Rev. 6

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 READ CAREFULLY These instructions are intended to cover good practices in

More information

Instructions For SF 6 Refill Kit

Instructions For SF 6 Refill Kit S&C Vista Underground Distribution Switchgear UnderCover, Vault-Mounted, and Pad-Mounted Styles Instructions For SF 6 Refill Kit TABLE OF CONTENTS Section Page Section Page INTRODUCTION..................................

More information

PART 1 - INTRODUCTION...

PART 1 - INTRODUCTION... Table of Contents PART 1 - INTRODUCTION... 3 1.1 General... 3 1.2 Sensor Features... 3 1.3 Sensor Specifications (CDE-45P)... 4 Figure 1-1 CDE-45P Sensor Dimensions (standard, convertible style)... 4 PART

More information

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Submit shop drawings for equipment provided under this section Shop drawings shall indicate: Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,

More information

Model 1756 Test Lead Kit

Model 1756 Test Lead Kit Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-888-KEITHLEY http://www.keithley.com Model 1756 Test Lead Kit Gerneral Purpose Test Lead Information Description These test leads allow you

More information

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information

OEM Manual MODEL 2350 ELECTRONIC DUAL CYLINDER SCALE

OEM Manual MODEL 2350 ELECTRONIC DUAL CYLINDER SCALE OEM Manual MODEL 2350 ELECTRONIC DUAL CYLINDER SCALE Scaletron Industries, Ltd. Bedminster Industrial Park 53 Apple Tree Lane P.O. Box 365 Plumsteadville, PA 18949 USA Toll Free: 1-800-257-5911 (USA &

More information

OPERATOR S MANUAL 18 VOLT, 1 HOUR CHARGER

OPERATOR S MANUAL 18 VOLT, 1 HOUR CHARGER OPERATOR S MANUAL 18 VOLT, 1 HOUR CHARGER P110 Your battery charger has been engineered and manufactured to Ryobi s high standard for dependability, ease of operation, and operator safety. When properly

More information

OPERATING INSTRUCTIONS

OPERATING INSTRUCTIONS PIPELINE INSPECTION COMPANY LTD. OPERATING INSTRUCTIONS Wet Sponge Holiday Detectors 670,673, and MSRB Wet Sponge Holiday Detectors Portable and In-Plant Detectors Table of Contents General Information.......................3

More information

OPL BASIC. Dosing System for Professional Laundry machines. Contents

OPL BASIC. Dosing System for Professional Laundry machines. Contents OPL BASIC Dosing System for Professional Laundry machines Contents 1 Getting Started. Page 2 2 Installation. Page 4 3 Set Up & Operation. Page 8 4 Maintenance & Accessories. Page 10 5 Troubleshooting Page

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS LIGHTING CONTROL PANELS 4 AND 8 RELAYS INSTALLATION INSTRUCTIONS INSTALLATION OVERVIEW The installation instructions contained in this document are provided as a guide for proper and reliable installation.

More information

Installer s Guide WARNING: 18-GJ11D1-2. Ultraviolet (UV-C) Lamp Kit for 2-5 Ton Air Handlers HAZARDOUS VOLTAGE - DISCONNECT POWER BEFORE SERVICING

Installer s Guide WARNING: 18-GJ11D1-2. Ultraviolet (UV-C) Lamp Kit for 2-5 Ton Air Handlers HAZARDOUS VOLTAGE - DISCONNECT POWER BEFORE SERVICING Installer s Guide 18-GJ11D1-2 : Models: BAYUVCLK001-40 Watt, 2 Lamp NOTE: A BAYCC24VK01 can be installed for Series 8 Air Handlers to extend the life of the lamp. This accessory kit will disable the lamp

More information

HP UPS R1500 Generation 3

HP UPS R1500 Generation 3 HP UPS R1500 Generation 3 Installation Instructions Part Number 650952-001 NOTE: The rating label on the device provides the class (A or B) of the equipment. Class B devices have a Federal Communications

More information

Mobile Data Power Model: MDP-25

Mobile Data Power Model: MDP-25 Mobile Data Power Model: MDP-25 Topic Section Features... 2 Operational Features Summary... 2 Back-up Battery Power Internal Charger Voltage Spike Protection RF Noise Filtering Warning of Imminent Loss

More information

Lightning Arresters P30027 18 KVA P30038 10 KVA. Description & Installation

Lightning Arresters P30027 18 KVA P30038 10 KVA. Description & Installation Lightning Arresters P30027 18 KVA P30038 10 KVA Description & Installation Printed in USA 09/11 TO330 Rev. B Table of Contents Page 1.0 SCOPE 2 2.0 PRODUCT OVERVIEW 2 2.1 Intended Uses 2 2.2 Lightning

More information

MCR1900 Media Converter 19-Slot Chassis

MCR1900 Media Converter 19-Slot Chassis MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the

More information

Manual Ranging MultiMeter

Manual Ranging MultiMeter Owner s Manual Manual Ranging MultiMeter Model 82345 CAUTION: Read, understand and follow Safety Rules and Operating Instructions in this manual before using this product.! Safety! Operation! Maintenance!

More information

Manual for Fire Suppression & Methane Detection System

Manual for Fire Suppression & Methane Detection System Manual for Fire Suppression & Methane Detection System Fogmaker North America Post address: 150 Gordon Dr Exton, PA 19341 Delivery address: 150 Gordon Dr Exton, PA 19341 Tel: 610-265-3610 Fax: 610-265-8327

More information

ATS Overhead Table Shelf System INSTRUCTION MANUAL

ATS Overhead Table Shelf System INSTRUCTION MANUAL ATS Overhead Table Shelf System INSTRUCTION MANUAL ATS Overhead Table Shelf System Instruction Manual Warranty Newport Corporation warrants this product to be free of defects in material and workmanship

More information

Step 1. Item 6. Item 1

Step 1. Item 6. Item 1 Voltage Regulators QD3/T350 Motor Replacement Kit Kit Number 57A63675100B Service Information S225-50-35 Contents General..................................... 1 Parts Supplied...............................

More information

Installation. Smart-UPS VT MGE Galaxy 3500. Maintenance Bypass Panel. 10-40 kva 400 V

Installation. Smart-UPS VT MGE Galaxy 3500. Maintenance Bypass Panel. 10-40 kva 400 V Installation Smart-UPS VT MGE Galaxy 3500 Maintenance Bypass Panel 10-40 kva 400 V Contents Safety.................................................. 1 Save these instructions...................................

More information

PowerFlex 700S and 700H Frame 12 DC Bus Connector Kit

PowerFlex 700S and 700H Frame 12 DC Bus Connector Kit PowerFlex 700S and 700H Frame 12 DC Bus Connector Kit Installation Instructions This document provides instructions for the installation of a DC bus connector kit for PowerFlex 700S and 700H frame 12 drives

More information

HP ProLiant DL380 G6 Carrier-Grade Server Read Before Install

HP ProLiant DL380 G6 Carrier-Grade Server Read Before Install HP ProLiant DL380 G6 Carrier-Grade Server Read Before Install Carrier-Grade Instructions HP Part Number: AM275-9001A Published: July 2012 Edition: 3 Copyright 2009, 2012 Hewlett-Packard Development Company,

More information

StorTrends 3400 Hardware Guide for Onsite Support

StorTrends 3400 Hardware Guide for Onsite Support StorTrends 3400 Hardware Guide for Onsite Support MAN-3400-SS 11/21/2012 Copyright 1985-2012 American Megatrends, Inc. All rights reserved. American Megatrends, Inc. 5555 Oakbrook Parkway, Building 200

More information

Replacement of 600-Ampere Bushing and 200-Ampere Bushing-Well Adapters

Replacement of 600-Ampere Bushing and 200-Ampere Bushing-Well Adapters S&C Vista SD Underground Distribution Switchgear Pad-Mounted and Vault-Mounted Style Outdoor Distribution (17.5 kv and 29 kv) With Visi-Gap Load Interrupter Switches and Visi-Gap Fault Inetrrupters Replacement

More information

Model 201 Wiegand Touchpad Reader Installation Guide

Model 201 Wiegand Touchpad Reader Installation Guide Model 201 Wiegand Touchpad Reader Installation Guide P/N 460353001C 15AUG11 2011 UTC Fire & Security. All rights reserved. This document may not be copied in whole or in part or otherwise reproduced without

More information

How To Use A Power Supply Unit (Upu)

How To Use A Power Supply Unit (Upu) BRAVER UPS (Uninterruptible Power System) User s Manual Safety CAUTION! This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user replaceable parts.

More information

Arc Flash Avoidance and its Application to Overhead Traveling Cranes

Arc Flash Avoidance and its Application to Overhead Traveling Cranes Arc Flash Avoidance and its Application to Overhead Traveling Cranes Whitepaper August 2012 Jason Wellnitz, Controls Product Manager Material Handling Numerous technical papers, bulletins, magazine articles

More information

Uninterruptible Power Supply. 500 kva - 750 kva

Uninterruptible Power Supply. 500 kva - 750 kva 9 315 Uninterruptible Power Supply 500 kva - 750 kva T1 and T3 Installation Addendum 164201244-001 Rev. A ------------------------------------------------------------------------ ------------------------------------------------------------------------

More information

AutoRanging Digital MultiMeter

AutoRanging Digital MultiMeter Owner's Manual AutoRanging Digital MultiMeter Model No. 82139 CAUTION: Read, understand and follow Safety Rules and Operating Instructions in this manual before using this product. Safety Operation Maintenance

More information

=============================== WARNING

=============================== WARNING =============================== WARNING EXPLANATION OF GRAPHICAL SYMBOLS This symbol is intended to alert the user to the presence of unprotected dangerous voltage" within the product's enclosure that

More information

WE-350 Series ¼ Turn Electric Actuator

WE-350 Series ¼ Turn Electric Actuator WE-350 Series ¼ Turn Electric Actuator Operation and Installation Manual Pg 1 (Rev. 020113) Table of Contents 1.0 General 1.1 Pre-Installation Inspection 1.2 Storage 1.3 Features & General Information

More information

RAY-MAX Integrated Solar Power Strip

RAY-MAX Integrated Solar Power Strip RAY-MAX Integrated Solar Power Strip 600008, 600009, 600010, 600208, 600209, 600210 Owner s Manual NEXTRONEX, INC. Revision Date: 10/27/14 Contents 1. Safety Instructions... 3 2. General Equipment Warnings...

More information

MS4000/MS4000U Mini-Siren

MS4000/MS4000U Mini-Siren MAN MS4000 INSTALL REV: 1/26/01 255331B INSTALLATION AND OPERATING INSTRUCTIONS MS4000/MS4000U Mini-Siren i Section Title Page I General Description...... 1 II Specifications... 2 III Safety Message To

More information

Co-location Interconnect Power Panel (CIPP) Installation Guide

Co-location Interconnect Power Panel (CIPP) Installation Guide Co-location Interconnect Power Panel (CIPP) Installation Guide Document INS-97xxxxxxx This guide covers the following part numbers- Trimm 97xxxxxxx Series Table of Contents Section 1 - General Information...

More information

DE1600 DSA E-Series iscsi Disk Arrays. Installation Manual

DE1600 DSA E-Series iscsi Disk Arrays. Installation Manual DE1600 DSA E-Series iscsi Disk Arrays en Installation Manual DE1600 DSA E-Series iscsi Disk Arrays Table of Contents en 3 Table of Contents 1 Safety Precautions 4 1.1 Warning Notices 4 1.2 Caution Notices

More information

SDX Submersible Depth Transmitter User Manual

SDX Submersible Depth Transmitter User Manual SDX Submersible Depth Transmitter User Manual January 2011 USER INFORMATION Stevens makes no warranty as to the information furnished in these instructions and the reader assumes all risk in the use thereof.

More information

Express5800/120Ed. Rack Mount Kit Installation Procedures PN: 455-01607-001

Express5800/120Ed. Rack Mount Kit Installation Procedures PN: 455-01607-001 Express5800/120Ed Rack Mount Kit Installation Procedures PN: 455-01607-001 Proprietary Notice and Liability Disclaimer The information disclosed in this document, including all designs and related materials,

More information

UV100A Ultraviolet Air Treatment System

UV100A Ultraviolet Air Treatment System UV100A Ultraviolet Air Treatment System INSTALLATION INSTRUCTIONS APPLICATION When installed in forced air heating and cooling systems, the UV100A Ultraviolet Air Treatment System kills airborne microorganism

More information

Installation Instructions for Alarm Module Kit A043F059

Installation Instructions for Alarm Module Kit A043F059 Instruction Sheet 07-2013 Installation Instructions for Alarm Module Kit A043F059 1 Introduction The information contained within is based on information available at the time of going to print. In line

More information

Operating Manual. Los Angeles Abrasion Machine HM-70A & HM-70AF

Operating Manual. Los Angeles Abrasion Machine HM-70A & HM-70AF Operating Manual Los Angeles Abrasion Machine HM-70A & HM-70AF Rev: 07/19/2012 PHONE: 800-444-1508 P.O. Box 200, Lewis Center, Ohio 43035-0200 FAX: 800-255-5314 740-548-7298 E-mail: customerservice@gilsonco.com

More information

TraceTek TTDM Series Leak Detection and Location Modules Replacement Parts Installation Instructions

TraceTek TTDM Series Leak Detection and Location Modules Replacement Parts Installation Instructions TraceTek TTDM Series Leak Detection and Location Modules Replacement Parts Installation Instructions TRACETEK TraceTek TTDM Replacement Parts General Information These instructions detail the steps to

More information

OASIS-PLUS 120V READ ALL INSTRUCTIONS BEFORE OPERATING READ ALL INSTRUCTIONS BEFORE OPERATING OZONE IS A POWERFUL OXIDIZER AND MUST BE USED WITH CARE

OASIS-PLUS 120V READ ALL INSTRUCTIONS BEFORE OPERATING READ ALL INSTRUCTIONS BEFORE OPERATING OZONE IS A POWERFUL OXIDIZER AND MUST BE USED WITH CARE OASIS-PLUS 120V INFORMATION & OPERATING INSTRUCTIONS READ ALL INSTRUCTIONS BEFORE OPERATING READ ALL INSTRUCTIONS BEFORE OPERATING OZONE IS A POWERFUL OXIDIZER AND MUST BE USED WITH CARE 56041852 WARNING:

More information

OVR Three-Phase Recloser and PCD Control Style Guide 1VAL264001-SG October 13, 2009 Revision F

OVR Three-Phase Recloser and PCD Control Style Guide 1VAL264001-SG October 13, 2009 Revision F OVR Three-Phase Recloser and PCD Control Style Guide 1VAL264001-SG October 13, 2009 Revision F The OVR three-phase recloser style guide aids in the proper selection of your OVR three-phase style number.

More information

Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide

Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide Instruction Bulletin EAV85226 08/2014 Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide Retain for future use. Product Description Kit Contents The Wiser Panel Meter is for use in energy management

More information

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Optional Standby Power Generator Systems A. Furnish and install automatic transfer switches

More information

GreenWay Solar LED Path and Trail Lighting System. Installation and Owner s Manual

GreenWay Solar LED Path and Trail Lighting System. Installation and Owner s Manual GreenWay Solar LED Path and Trail Lighting System Installation and Owner s Manual Important Notes and Warnings This installation and instruction manual provides installation, operation, and maintenance

More information

Instruction Bulletin. MCS025 Sync-Check Module Installation Sheet

Instruction Bulletin. MCS025 Sync-Check Module Installation Sheet Instruction Bulletin 63230-216-244B1 LaVergne, TN, USA MCS025 Sync-Check Module Installation Sheet Retain for future use. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Only qualified electrical

More information

AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle

AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle Scope This specification stipulates the minimum requirements for mechanically linked three-phase electronic sectionalizers, for use on outdoor medium voltage overhead lines of 15, 27, and 38 kv. Electronic

More information

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description Samba OPLC SM35-J-R20 Installation Guide The Unitronics SM35-J-R20 offers the following onboard I/Os: 12 Digital Inputs, configurable via wiring to include: 1 HSC/Shaft-encoder Input, 2 Analog inputs (only

More information

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms ABB innovations for changing demands ABB (www.abb.com) is a leader in power and automation technologies that enables utility

More information

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Course No: E02-010 Credit: 2 PDH Boris Shvartsberg, Ph.D., P.E., P.M.P. Continuing Education

More information

Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers

Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers Specification Guide for RVAC Direct Replacement AC Medium Voltage Circuit Breakers Table of Contents 1.0 General Work Scope...3 2.0 Standards...3 3.0 Supplier Qualifications...4 4.0 Circuit Breaker Element

More information

LIEBERT VNSA Installation Sheet

LIEBERT VNSA Installation Sheet LIEBERT VNSA Installation Sheet Description The Liebert vnsa network switch is designed for connecting multiple Ethernet-ready devices and comes in various models. The unit may have: A Liebert icom display

More information

HM-W536 Install Guide

HM-W536 Install Guide HM-W536 Install Guide 9/13/2013 IMPORTANT SAFETY INSTRUCTIONS Warning - When using electrical devices, basic safety precautions should be followed to reduce the risk of fire, electrical shock or injury.

More information

Owner s Manual. For Automatic Transfer Switch. 100-200 Amp, Service Entrance/Non-Service Entrance

Owner s Manual. For Automatic Transfer Switch. 100-200 Amp, Service Entrance/Non-Service Entrance Owner s Manual For Automatic Transfer Switch 100-200 Amp, Service Entrance/Non-Service Entrance Model Numbers RTST100A3 RTSP100A3 RTST150A3 RTST200A3 RTSP200A3 MODEL NUMBER: SERIAL NUMBER: DATE PURCHASED:

More information

Single Phase Soft Starter

Single Phase Soft Starter Single Phase Soft Starter Installation & Operating Manual 6/02 Table of Contents Section 1 General Information................................................... 1 1 General Description................................................

More information

Applied Electronics. Commercial Dimming System UPDATE NOTICE

Applied Electronics. Commercial Dimming System UPDATE NOTICE REV. A Applied Electronics Commercial Dimming System UPDATE NOTICE This notice is to inform the end user of an additional feature added to this DP12/2400 dimming unit. This unit has been outfitted with

More information

Ceiling Fan Installation Instructions

Ceiling Fan Installation Instructions Ceiling Fan Installation Instructions 1525..series OWNER S MANUAL READ AND SAVE THESE INSTRUCTIONS Total fan wieght with light kit 1-1525-CUL-English INSTALLATION CH-545 Safety Tips WARNING: TO REDUCE

More information

SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL

SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated

More information

Oil and Coolant Circulating Heating System. Model - OCSM

Oil and Coolant Circulating Heating System. Model - OCSM Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine

More information

ST Series POWER SUPPLIES USER INSTRUCTIONS

ST Series POWER SUPPLIES USER INSTRUCTIONS Introduction These instructions detail the installation and operation requirements for the ST20 & ST35 power supplies. These have been designed for operation in RV s providing a DC power system, with optional

More information

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132

More information

MODEL 2202IQ (1991-MSRP $549.00)

MODEL 2202IQ (1991-MSRP $549.00) F O R T H E L O V E O F M U S I C F O R T H E L O V E O F M U S I C MODEL 2202IQ (1991-MSRP $549.00) OWNER'S MANUAL AND INSTALLATION GUIDE INTRODUCTION Congratulations on your decision to purchase a LINEAR

More information

INSTALLATION AND OPERATING INSTRUCTIONS For Model GL1 Gate Locks

INSTALLATION AND OPERATING INSTRUCTIONS For Model GL1 Gate Locks Securitron Magnalock Corp. www.securitron.com ASSA ABLOY, the global leader Tel 800.624.5625 techsupport@securitron.com in door opening solutions INSTALLATION AND OPERATING INSTRUCTIONS For Model GL1 Gate

More information

12-Volt 10-Amp Regulated Power Supply

12-Volt 10-Amp Regulated Power Supply 22-506.fm Page 1 Friday, August 6, 1999 12:55 PM Cat. No. 22-506 OWNER S MANUAL Please read before using this equipment. 12-Volt 10-Amp Regulated Power Supply 22-506.fm Page 2 Friday, August 6, 1999 12:55

More information

ISL-540 TBTS SERIES D EMERGENCY LIGHTING EQUIPMENT

ISL-540 TBTS SERIES D EMERGENCY LIGHTING EQUIPMENT P.O. BOX 11846 TUCSON, AZ 85734 (520) 294-3292 FAX (520) 741-2837 www.iotaengineering.com INSTRUCTION MANUAL IMPORTANT SAFEGUARDS When using electrical equipment, basic safety precautions should always

More information

User s Manual AURORA 1.2K/2.2K

User s Manual AURORA 1.2K/2.2K User s Manual AURORA 1.2K/2.2K Uninterruptible Power System Safety CAUTION This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user serviceable

More information

2. Remove rear cover of head lamp if bulbs are covered/sealed within the housings, and remove halogen bulb carefully.

2. Remove rear cover of head lamp if bulbs are covered/sealed within the housings, and remove halogen bulb carefully. These instructions are designed to address most general installation procedures across vehicles and should not be considered vehicle make, model or year specific. Please contact the vendor directly for

More information

MIC-WKT and MIC-WKT-IR

MIC-WKT and MIC-WKT-IR MIC-WKT and MIC-WKT-IR Installation Manual Bosch Security Systems EN Installation and Operation Manual MIC-WKTI and MIC-WKT-IR Installation Manual EN 2 MIC-WKT and MIC-WKT-IR Washer Pump Drive Card Kits

More information

Modular I/O System Analog and Digital Interface Modules

Modular I/O System Analog and Digital Interface Modules OPERATING INSTRUCTIONS Modular I/O System Analog and Digital Interface Modules Installation Operation Maintenance Document Information Document ID Title: Operating Instructions Modular I/O System Part

More information

Universal Vehicle Power Supply 9007AX01. Installation Instructions

Universal Vehicle Power Supply 9007AX01. Installation Instructions Universal Vehicle Power Supply 9007AX01 Installation Instructions Disclaimer Honeywell International Inc. ( HII ) reserves the right to make changes in specifications and other information contained in

More information

TSn SERIES Surge Protective Device

TSn SERIES Surge Protective Device Page: 1 of 8 TSn SERIES Surge Protective Installation & Operation Manual 3621 Saunders Avenue www.systems.us Ph 804.355.1100 Richmond, VA 23227 4354 Sales@Systems.us Fax 804.355.8900 Page: 2 of 8 Quick

More information

ADM1TE 5/30A DIN rail single phase two wire energy meter

ADM1TE 5/30A DIN rail single phase two wire energy meter ADMTE 5/30A DIN rail single phase two wire energy meter. Safety instruction.2 Foreword.3 Performance criteria.4 Specifications.5 Basic errors.6 Description.7 Dimensions.8 Installation.9 Operating.0 Troubleshooting.

More information

INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930

INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930 INSTALLATION GUIDE Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930 Card Reader and Controller Model 3.5 with KIM Swipe Reader Table of Contents 1. Features..................................

More information

WARNING: FAILURE TO FOLLOW THESE RULES MAY RESULT IN SERIOUS PERSONAL INJURY CAUTION: INSTALLATION LOCATION:

WARNING: FAILURE TO FOLLOW THESE RULES MAY RESULT IN SERIOUS PERSONAL INJURY CAUTION: INSTALLATION LOCATION: Revision Level: 01 Revision Date: 07/07/2011 Please read all instructions carefully to help ensure a correct and SAFE installation of your Second Wind Ultraviolet Germicidal Air Purifier. Failure to do

More information

Owner's/Installation Manual

Owner's/Installation Manual Owner's/Installation Manual Power Management Module (PMM) and Starter Kit NOTE: The starter kit must be purchased and installed prior to individual PMM usage. Model Numbers: 00686-0 PMM 00699-0 PMM WITH

More information

LESTRONIC DV AUTOMATIC 12 OR 24 VOLT DUAL OUTPUT DUAL MODE BATTERY CHARGER MODEL 16350 TYPE 12/24EL40-10ET

LESTRONIC DV AUTOMATIC 12 OR 24 VOLT DUAL OUTPUT DUAL MODE BATTERY CHARGER MODEL 16350 TYPE 12/24EL40-10ET LESTRONIC DV AUTOMATIC 12 OR 2 VOLT DUAL OUTPUT DUAL MODE BATTERY CHARGER MODEL 16350 TYPE 12/2EL0-10ET PLEASE SAVE THESE IMPORTANT SAFETY AND OPERATING INSTRUCTIONS For correct operation of the equipment,

More information

LED Security Spotlight User Manual

LED Security Spotlight User Manual MOT ION-TR ACKING LED Security Spotlight User Manual www.jascoproducts.com 1-800-654-8483 2 TABLE OF CONTENTS Parts List 3 Questions? Missing Parts? 4 Installation (Wall mount) 6-9 Installation (Eave mount)

More information

* DISCLAIMER: Contents. How to Use This Guide: COMMERCIAL INSTALL GUIDE 2

* DISCLAIMER: Contents. How to Use This Guide: COMMERCIAL INSTALL GUIDE 2 COMMERCIAL INSTALL GUIDE 2 Contents How to Use This Guide: The first section of this guide is designed to assist you with the installation of your DECK Monitoring hardware. The revenue grade meter and

More information

Table of Contents WARNING SYMBOLS AND DEFINITIONS

Table of Contents WARNING SYMBOLS AND DEFINITIONS Table of Contents SAFETY INSTALLATION OPERATION MAINTENANCE Safety... 2 Specifications... 4 Installation... 5 Operation... 8 WARNING SYMBOLS AND DEFINITIONS Maintenance... 9 Parts List and Assembly Diagram...

More information

SureSite Magnetic Liquid Level Indicator

SureSite Magnetic Liquid Level Indicator SureSite Magnetic Liquid Level Indicator Instruction Bulletin No. 177664-1 (Rev. E) Section 1: Weldments Thank you for purchasing the GEMS SureSite Magnetic Level Indicator. Please read this document prior

More information

DRM75A 230V 20/100A DIN rail single phase two wire energy meter

DRM75A 230V 20/100A DIN rail single phase two wire energy meter DRM75A 230V 20/100A DIN rail single phase two wire energy meter 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Description 1.7 Dimensions 1.8 Installation

More information

-1- SPECIFICATIONS 002085 CONE SETTER PLATFORM ATTACHMENT INDEX

-1- SPECIFICATIONS 002085 CONE SETTER PLATFORM ATTACHMENT INDEX -1-002085 CONE SETTER PLATFORM ATTACHMENT INDEX I. GENERAL EQUIPMENT : A. Intent Statement B. Cone Setter Platform II. III. 1. Understructure Frame 2. Mounting Components 3. Paint 4. Basket 5. Labels 6.

More information

REDI-LINE ELECTRIC GENERATORS USER'S GUIDE. Rugged, Reliable, DC to AC Power Conversion

REDI-LINE ELECTRIC GENERATORS USER'S GUIDE. Rugged, Reliable, DC to AC Power Conversion REDI-LINE ELECTRIC GENERATORS USER'S GUIDE Rugged, Reliable, DC to AC Power Conversion REDI-LINE ELECTRIC GENERATOR MODEL INPUT ACTUAL OUTPUT ACTUAL OUTPUT WATTS SERIAL NO. PACIFIC SCIENTIFIC MOTOR PRODUCTS

More information

Inductive Sensors Single or Dual Loop Detectors Type LD with teach-in

Inductive Sensors Single or Dual Loop Detectors Type LD with teach-in Inductive Sensors Single or Dual Loop Detectors Type LD with teach-in Single or Dual loop detector Automatically adjustment of detection level Manual sensitivity for compensations of variations Easy installation

More information

Lighting Controls ! WARNING RISK OF ELECTRIC SHOCK. Installation Instructions DESCRIPTION

Lighting Controls ! WARNING RISK OF ELECTRIC SHOCK. Installation Instructions DESCRIPTION GE Lighting Installation Instructions Lighting Controls Centralized Lighting Control Panel Interior Catalog Number CLCINTxx DESCRIPTION The Centralized Lighting Control System is a small network of relay

More information

Float and Thermostatic Traps Series H, C and X

Float and Thermostatic Traps Series H, C and X Hoffman Specialty Installation & Maintenance Instructions HS-(E) and Thermostatic Traps Series H, C and X Series C & NPT Series C NPT Series X NPT Series C NPT Series H Ratings Maximum Max. Operating NPT

More information

CITY OF LOS ANGELES CALIFORNIA

CITY OF LOS ANGELES CALIFORNIA BOARD OF BUILDING AND SAFETY COMMISSIONERS VAN AMBATIELOS PRESIDENT E. FELICIA BRANNON VICE-PRESIDENT JOSELYN GEAGA-ROSENTHAL GEORGE HOVAGUIMIAN JAVIER NUNEZ CITY OF LOS ANGELES CALIFORNIA ERIC GARCETTI

More information

PT-6000 Power Tower INSTALLATION MANUAL SPECIFICATIONS

PT-6000 Power Tower INSTALLATION MANUAL SPECIFICATIONS PT-6000 Power Tower INSTALLATION MANUAL 10.5 9.75 12 22.75 10.75 MAXIMUM SOIL HEIGHT: DO NOT ALLOW FILL TO EXCEED THIS LEVEL! 11.5 4 4 13 Optional PT-BASE for new installations or when previous 2000/6000

More information

LS1024B / LS2024B/ LS3024B. Solar Charge Controller USER MANUAL

LS1024B / LS2024B/ LS3024B. Solar Charge Controller USER MANUAL EPSOLAR LS1024B / LS2024B/ LS3024B Solar Charge Controller USER MANUAL Thank you very much for selecting our product! This manual offers important information and suggestions with respect to installation,

More information

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification 08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and

More information

5800 Temperature Sensor Cable Assembly

5800 Temperature Sensor Cable Assembly 5800 Temperature Sensor Cable Assembly Removal and Replacement Instruction Sheet #60-4702-070 Revision D, January 14, 2013 Overview The 5800 has two refrigeration temperature sensors, one attached to the

More information

Instruction Manual. 2in1 LAN Tester & Multimeter. Model: LA-1011

Instruction Manual. 2in1 LAN Tester & Multimeter. Model: LA-1011 Instruction Manual 2in1 LAN Tester & Multimeter Model: LA-1011 1 Contents Introduction... Features... Safety Precautions.. Meter Description... Electrical Specification... Operation.. AutoRanging Multimeter.

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to

More information

Installation and safety instructions for AC/DC built-in devices

Installation and safety instructions for AC/DC built-in devices The device type and date of manufacture (week/year) can be found on the device rating plate. In the event of any queries about the device, please quote all the details given on the rating plate. For further

More information

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A AUTOMATIC TRANSFER SWITCH Changeover Type from 250A to 2500A Table of Contents Preamble 1.1 Theoretical base 1.2 Selection the size of automatic transfer switch 1.3 Automatic transfer switch components

More information

Union County Public Schools. Facilities Department. Electrical. Safe Work Practices

Union County Public Schools. Facilities Department. Electrical. Safe Work Practices 1 Union County Public Schools Facilities Department Electrical Safe Work Practices 2 Purpose In accordance with OSHA Standards 1910.331-335, safety-related work practices shall be used by Union County

More information

SERVICE MANUAL RESIDENTIAL ELECTRIC AND LIGHT DUTY COMMERCIAL ELECTRIC WATER HEATERS. Troubleshooting Guide and Instructions for Service

SERVICE MANUAL RESIDENTIAL ELECTRIC AND LIGHT DUTY COMMERCIAL ELECTRIC WATER HEATERS. Troubleshooting Guide and Instructions for Service RESIDENTIAL ELECTRIC AND LIGHT DUTY COMMERCIAL ELECTRIC WATER HEATERS SERVICE MANUAL Troubleshooting Guide and Instructions for Service (To be performed ONLY by qualified service providers) Models Covered

More information