RS 485 Repeater SIMATIC. RS 485 Repeater. Preface 1. Introduction. Description 3. Installation 4. Connecting. Technical data 6.
|
|
|
- Marcus Walker
- 9 years ago
- Views:
Transcription
1 Preface 1 Introduction 2 SIMATIC Manual Description 3 Installation 4 Connecting 5 Technical data 6 Dimension drawings 7 02/2011 A5E
2 Legal information Legal information Warning notice system This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger. DANGER indicates that death or severe personal injury will result if proper precautions are not taken. WARNING indicates that death or severe personal injury may result if proper precautions are not taken. CAUTION with a safety alert symbol, indicates that minor personal injury can result if proper precautions are not taken. CAUTION without a safety alert symbol, indicates that property damage can result if proper precautions are not taken. NOTICE indicates that an unintended result or situation can occur if the corresponding information is not taken into account. If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage. Qualified Personnel The product/system described in this documentation may be operated only by personnel qualified for the specific task in accordance with the relevant documentation for the specific task, in particular its warning notices and safety instructions. Qualified personnel are those who, based on their training and experience, are capable of identifying risks and avoiding potential hazards when working with these products/systems. Proper use of Siemens products Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems. The permissible ambient conditions must be adhered to. The information in the relevant documentation must be observed. Trademarks All names identified by are registered trademarks of the Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner. Disclaimer of Liability We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions. Siemens AG Industry Sector Postfach NÜRNBERG GERMANY A5E P 03/2011 Copyright Siemens AG Technical data subject to change
3 Table of contents 1 Preface Introduction Description Area of application and properties Design of the RS 485 repeater Installation Installing and uninstalling the RS 485 repeater Connecting in ungrounded and grounded operation Connecting the power supply Connecting the bus cable Configuration options with the RS 485 repeater Technical data General technical data Standards and approvals Electromagnetic Compatibility Shipping and storage conditions for modules and backup batteries Mechanical and ambient climatic conditions for S7-300 operation Specification of dielectric tests, protection class, degree of protection, and rated voltage of S Technical data the Dimension drawings Dimension drawings...39 Glossary Index Manual, 02/2011, A5E
4 Table of contents 4 Manual, 02/2011, A5E
5 Preface 1 Introduction This manual describes the RS 485 repeater. It supports you during the configuration, installation and commissioning. It is intended for people who work in the following areas: the configuring, commissioning and servicing of automation systems. Basic knowledge required This manual presumes general knowledge in the field of automation engineering. Range of validity of this manual The manual is valid for the RS 485 repeater with the order number 6ES7972-0AA02-0XA0. Additional support If you have any questions relating to the products described in this product information and do not find the answers in this document, please contact your local Siemens representative on the Internet ( A guide to the technical documentation provided for the various SIMATIC products and systems is available on the Internet ( The online catalog and ordering systems are available on the Internet ( Technical Support You can contact Technical Support for all Industry Automation products by means of the Internet Web form for the Support Request on the Internet ( Additional information about Siemens Technical Support is available on the Internet ( Manual, 02/2011, A5E
6 Preface Service & Support on the Internet In addition to our documentation, we offer a comprehensive knowledge base. On the Internet ( There you will find: Our Newsletter, which constantly provides you with the latest information about your products. The right documentation for you using our Service & Support search engine. The bulletin board, a worldwide knowledge exchange for users and experts. Your local contact for Automation & Drives in our contact database. Information about on-site services, repairs, spare parts, and lots more. 6 Manual, 02/2011, A5E
7 Introduction 2 This chapter This chapter describes the RS 485 repeater in detail. This includes: Description of the RS 485 repeater The maximum cable lengths between two RS 485 repeaters The functions of the various operating elements and terminals Mounting and removing information about grounded and nongrounded operation Connecting the power supply and bus line Technical specifications and the block diagram Dimension drawings Diagnostic Repeater Compared to the RS 485 repeater, the Diagnostic Repeater has new characteristics: Diagnostic function and modeling as the DP slave. For additional information, refer to the Diagnostic Repeater for PROFIBUS DP manual on the Internet ( Manual, 02/2011, A5E
8 Introduction 8 Manual, 02/2011, A5E
9 Description Area of application and properties Order number 6ES7972-0AA02-0XA0 What is the RS 485 repeater? The RS 485 repeater amplifies data signals (amplitude, edge slope and signal width) on bus lines and couples segments. Application of the The RS 485 repeater connects two PROFIBUS or MPI segments using RS 485 technology with maximum 32 nodes. It enables transfer rates from 9.6 kbps to 12 Mbps. You need an RS 485 repeater if: More than 32 nodes (maximum 127, including repeaters) are connected to the bus Segments are operated ungrounded on the bus (electrical isolation of segments) The maximum cable length of a bus segment is exceeded (see the table below) Help is required during the commissioning Switch for disconnecting segments Display of bus activity Disconnecting a bus segment in the case of incorrectly inserted terminating resistors The signals are to be regenerated in amplitude and time Table 3-1 Maximum cable length of a bus segment Transmission rate Max. cable length of a bus segment (in m) 9.6 to kbps kbps Mbps to 12 Mbps 100 Manual, 02/2011, A5E
10 Description 3.1 Area of application and properties Rules If you set up a PROFIBUS network with RS 485 repeaters: The number of RS 485 repeaters in series must be configured in STEP 7. Up to nine RS 485 repeaters may be connected in series. The maximum cable length between two nodes with RS 485 repeater may not exceed the values listed in the table below. Table 3-2 Maximum cable length between two RS 485 repeaters Transmission rate Maximum cable length between 2 nodes (in m) with RS 485 repeater 9.6 to kbps kbps Mbps to 12 Mbps Manual, 02/2011, A5E
11 Description 3.2 Design of the RS 485 repeater 3.2 Design of the RS 485 repeater The following table shows the design and functions of the RS 485 repeater. Table 3-3 Design and functions of the RS 485 repeater Design of the repeater no. Function 1 Connection for the RS 485 repeater power supply (pin "M5.2" is the ground reference, if you want to measure the voltage difference s between terminals "A2" and "B2"). 2 Shield clamp for the strain relief and grounding of the bus cable of bus segments 1 or 2 3 Terminals for the bus cable of bus segment 1 4 Switches for terminating resistance for bus segment 1 5 LED for bus segment 1 6 OFF switch (= isolate bus segments from each other, for example, for commissioning) 7 LED for bus segment 2 8 Switches for terminating resistance for bus segment 2 9 LED 24 V supply voltage 10 Terminals for the bus cable of bus segment 2 11 Slide for mounting and removing the RS 485 repeater on the standard mounting rail 12 Interface for PG/OP on bus segment 1 Note Terminal M 5.2 of the power supply serves as ground reference for signal measurements in the event of a fault and should not be wired. Manual, 02/2011, A5E
12 Description 3.2 Design of the RS 485 repeater 12 Manual, 02/2011, A5E
13 Installation Installing and uninstalling the RS 485 repeater Overview You can install the RS 485 repeater as follows: On an S7-300 mounting rail On a standard mounting rail (order number 6ES5710-8MA..) Installation on an S7-300 mounting rail To install the RS 485 repeater on an S7-300 mounting rail, the catch on the rear of the RS 485 repeater must first be removed (see the following figure): 1. Insert a screwdriver below the tongue of the catch (1) and 2. Push the screwdriver towards the rear of the module (2). Hold the screwdriver in this position! Result: The catch of the RS 485 repeater is released. 3. Using your free hand lift the catch up as far as it will go and then remove the catch (3). Result: The catch is removed from the RS 485 repeater. 4. Fit the RS 485 repeater into the S7300 mounting rail (4). Manual, 02/2011, A5E
14 Installation 4.1 Installing and uninstalling the RS 485 repeater 5. Push it towards the back as far as it will go (5). 6. Tighten the securing screw with a torque of 80 to 110 Ncm (6). Rear: Front: to 110 Ncm Figure 4-1 Installing the RS 485 repeater on an S7-300 mounting rail Removing the repeater from an S7-300 mounting rail To remove the RS 485 repeater from the S7-300 mounting rail: 1. Loosen the fixing screw of the RS 485 repeater (1) and 2. Pull the RS 485 repeater up and out (2). 1 2 Figure 4-2 Removing the RS 485 repeater from the S7-300 mounting rail 14 Manual, 02/2011, A5E
15 Installation 4.1 Installing and uninstalling the RS 485 repeater Installation on a standard mounting rail To be able to install the repeater on a standard mounting rail, the catch must be present on the rear of the RS 485 repeater: 1. Fit the RS 485 repeater into the standard mounting rail from above and 2. Push it towards the back until the catch locks it in place. Removal from the standard mounting rail To remove the RS 485 repeater from the standard mounting rail: 1. Press down the catch on the bottom of the RS 485 repeater using a screwdriver and 2. Pull the RS 485 repeater upwards and out to remove it from the standard mounting rail. Manual, 02/2011, A5E
16 Installation 4.1 Installing and uninstalling the RS 485 repeater 16 Manual, 02/2011, A5E
17 Connecting in ungrounded and grounded operation Grounded or ungrounded The RS 485 repeater is Grounded, if all other nodes on the bus segment are also operated on ground potential Ungrounded, if all other nodes in the bus segment are operated on ungrounded potential Note Bus segment 1 is referenced to ground if you connect a PG to the PG/OP socket of the RS 485 repeater. The bus segment is grounded because the MPI in the PG is grounded, and the PG/OP socket of the RS 485 repeater is connected internally with bus segment 1. Grounded operation of the For grounded operation of the RS 485 repeater, you must bridge terminals "M" and "PE" on the top of the RS 485 repeater. Ungrounded operation of the RS 485 repeater For ungrounded operation of the RS 485 repeater, do not interconnect "M" and "PE" on the top of the RS 485 repeater. In addition, the supply voltage to the RS 485 repeater must be ungrounded. Manual, 02/2011, A5E
18 Connecting 5.1 in ungrounded and grounded operation Wiring diagram In a repeater configuration with ungrounded reference potential (ungrounded operation), any interference currents and static charges are discharged to the protective conductor by means of an RC network integrated in the repeater (refer to the figure below). s 1 Ground busbar 18 Manual, 02/2011, A5E
19 Connecting 5.1 in ungrounded and grounded operation Electrical isolation between bus segments Bus segments 1 and 2 are electrically isolated. The PG/OP interface is connected internally to the port for bus segment 1. The figure below shows the front panel of the RS 485 repeater. s 1 PG/OP interface 2 Terminals for bus segment 1 3 Terminals for bus segment 2 4 Electrical isolation Manual, 02/2011, A5E
20 Connecting 5.2 Connecting the power supply Amplification of bus signals The amplification of the bus signals takes place between the port for bus segment 1 or the PG/OP interface and the port for bus segment Connecting the power supply Cable type To connect the 24 V DC power supply, use flexible cables with a cross section of 0.25 mm 2 to 2.5 mm 2 (AWG 26 to 14). Connecting the power supply To connect the power supply of the RS-485 repeater: Strip the insulation from the cable for the 24 V DC power supply. Connect the cable to terminals "L+", "M" and "PE". 20 Manual, 02/2011, A5E
21 Connecting 5.3 Connecting the bus cable 5.3 Connecting the bus cable Connecting the PROFIBUS cable Connect the PROFIBUS cable to the RS 485 repeater, as follows: 1. Cut the PROFIBUS cable to the required length. 2. Strip the PROFIBUS cable as shown in the figure. The braid shield must be folded back on to the cable. Only then can the shield clamp serve as strain relief and as the shield contact. Figure 5-1 Stripping length for connecting to the RS 485 repeater 1. Connect the PROFIBUS cable to the RS 485 repeater: Connect the same wires (green/red for the PROFIBUS cable) to the same terminal A or B (in other words, always connect terminal A with a green wire and terminal B with a red wire or vice versa). 2. Tighten the shield clamps so that the shield makes good contact with the clamp. You can also find the stripping length printed on the RS 485 repeater: SIMATIC NET PROFIBUS cables You can find an overview of the PROFIBUS cables and their mechanical and electrical properties in the PROFIBUS system manual on the Internet ( Manual, 02/2011, A5E
22 Connecting 5.4 Configuration options with the RS 485 repeater 5.4 Configuration options with the RS 485 repeater Overview The following section explains the configurations in which you can use the RS 485 repeater: Bus segment 1 and bus segment 2 terminated on the RS 485 repeater. Bus segment 1 terminated on the RS 485 repeater and bus segment 2 looped through on the RS 485 repeater. Bus segment 1 and bus segment 2 looped through on the RS 485 repeater. Terminating resistor on/off the following figure shows the setting for the terminating resistor: Terminating resistor activated on Terminating resistor NOT activated on Figure 5-2 Setting of the terminating resistor Bus segments 1 and 2 terminated The following figure shows how to connect the RS 485 repeater to the ends between two bus segments: Bus segment 1 Bus segment 1 Terminating resistor Bus segment 1 enabling R Bus segment 2 Terminating resistor Bus segment 2 enabling Bus segment 2 Figure 5-3 Connecting two bus segments to the RS 485 repeater 22 Manual, 02/2011, A5E
23 Connecting 5.4 Configuration options with the RS 485 repeater Bus segment 1 terminated, bus segment 2 looped through The following figures show how to couple two bus segments using an RS 485 repeater. One bus segment is looped through. Bus segment 1 Bus segment 1 Terminating resistor Bus segment 1 enabling R Bus segment 2 Bus segment 2 Terminating resistor Bus segment 2 Do not enable! Figure 5-4 Connecting two bus segments to the RS 485 repeater Manual, 02/2011, A5E
24 Connecting 5.4 Configuration options with the RS 485 repeater Bus segments 1 and 2 looped through The following figures show how to couple two bus segments using an RS 485 repeater. Each bus cable is looped through on the RS 485 repeater. Bus segment 1 Bus segment 1 Bus segment 2 R Terminating resistor Bus segment 1 Do not enable! Terminating resistor Bus segment 2 Do not enable! Bus segment 2 Figure 5-5 Connecting two bus segments to the RS 485 repeater Note When you turn off the power supply of a complete bus segment, the terminating resistors of the connected nodes are also without power supply. This can lead to disruptions or undefined signal states in this bus segment that are not recognized by the RS 485 repeater and can then lead to problems in the other bus segment. Whenever possible, we recommend the following procedure: Alternative 1: Disconnect the two bus segments before turning off the power supply using switch 6 (refer to chapter Design of the ) on the repeater (set to "OFF"). Alternative 2: Connect the RS 485 repeater to the power supply of the bus segment to be turned off so that the repeater is also turned off. In this case, make sure that the RS 485 repeater is not at the end of the previous bus segment, since the RS 485 repeater then acts as the terminator which has no effect if there is no power supply. If this solution is required, use a PROFIBUS terminator with a permanent power supply downstream from the RS 485 repeater. Alternative 3: If you want the RS 485 repeater to retain its power supply, use PROFIBUS terminators to terminate the bus segment you want to turn off since these also require a permanent power supply. You require 1 terminator if the bus segment to be turned off ends at the RS 485 repeater, otherwise you require 2 terminators. See also Design of the RS 485 repeater (Page 11) 24 Manual, 02/2011, A5E
25 Technical data General technical data Standards and approvals Introduction Contents of general technical data: The standards and test values that the S7-300 automation system and its associated components comply with and satisfy. The test criteria that were used for the test. Note Information on the nameplate You will find the current markings and approvals on the type plate of the respective components. Safety guidelines WARNING Personal injury and damage to property may occur. In potentially explosive environments, there is a risk of injury or damage if you disconnect any connectors while the S7-300 is in operation. Always isolate the S7-300 operated in such areas before you disconnect and connectors. WARNING Explosion hazard Components may no longer qualify for Class I, Div. 2 if they are replaced. WARNING This S7-300 modules are only suitable for use in Class I, Div. 2, Group A, B, C, D, or in non-hazardous areas. Manual, 02/2011, A5E
26 Technical data 6.1 General technical data Test symbols and their significance The test symbols and their meaning are described in the following section. CE Label The S7-300 automation system satisfies the requirements and protection goals of the following EC directives, and conforms with the harmonized European standards (EN) for programmable logic controllers announced in the Official Journals of the European Community: 2006/95/EC "Electrical Equipment Designed for Use within Certain Voltage Limits" (Low- Voltage Directive) 2004/108/EC "Electromagnetic Compatibility" (EMC Directive) 94/9/EC "Equipment and protective systems intended for use in potentially explosive atmospheres" (Explosion Protection Directive) The EC declaration of conformity is held on file available to competent authorities at: Siemens AG Automation & Drives Group Industry Sector I IA AS R&D DH A P.O. Box Amberg, Germany You can also download this under the keyword "Declaration of conformity" on the Internet. UL certification Underwriters Laboratories Inc. complying with UL 508 (Industrial Control Equipment) CSA approval Canadian Standards Association to C22.2 No. 142 (Process Control Equipment) or 26 Manual, 02/2011, A5E
27 Technical data 6.1 General technical data culus approval Underwriters Laboratories Inc. complying with UL 508 (Industrial Control Equipment) CSA C22.2 No. 142 (Process Control Equipment) or culus HAZ. LOC. - approval Underwriters Laboratories Inc., complying with UL 508 (Industrial Control Equipment) UL 1604 (Hazardous Location) CSA C22.2 No. 142 (Process Control Equipment) CSA C22.2 No. 213 (Hazardous Location) APPROVED for use in Class I, Division 2, Group A, B, C, D Tx; Class I, Zone 2, Group IIC Tx FM approval Factory Mutual Research (FM) in accordance with Approval Standard Class Number 3611, 3600, 3810 APPROVED for use in Class I, Division 2, Group A, B, C, D Tx; Class I, Zone 2, Group IIC Tx Manual, 02/2011, A5E
28 Technical data 6.1 General technical data ATEX approval In accordance with EN (Electrical Apparatus for Potentially Explosive Atmospheres; Type of Protection "n") and EN (Electrical apparatus for potentially explosive gas atmospheres - Part 0: General Requirements) Marking for Australia and New Zealand The S7-300 automation system satisfies requirements of standards to AS/NZS CISPR 16. IEC The S7-300 automation system satisfies requirements and criteria to IEC (Programmable Controllers, Part 2: Equipment requirements and tests). Marine approval Classification societies: ABS (American Bureau of Shipping) BV (Bureau Veritas) DNV (Det Norske Veritas) GL (Germanischer Lloyd) LRS (Lloyds Register of Shipping) Class NK (Nippon Kaiji Kyokai) Use in industrial environments SIMATIC products are designed for industrial applications. Table 6-1 Field of application Use in industrial environments Noise emission requirements Noise immunity requirements Industry EN : 2007 EN : Manual, 02/2011, A5E
29 Technical data 6.1 General technical data Use in residential areas Note The S7-300 is designed for use in industrial areas; using it in residential areas could disturb radio and TV reception. To operate an S7-300 in a residential area, it's RF emission must comply with Limit Value Class B to EN Suitable measures for achieving the required Class B radio interference level include, for example: S7-300 installation in grounded switch cabinets / cubicles Use of noise filters in the supply lines Manual, 02/2011, A5E
30 Technical data 6.1 General technical data Electromagnetic Compatibility Definition Electromagnetic compatibility (EMC) is the ability of an electrical installation to function satisfactorily in its electromagnetic environment without interfering with that environment. The S7-300 modules also satisfy requirements of EMC legislation for the European domestic market. Compliance of the S7-300 system with specifications and directives on electric design is prerequisite. Pulseshaped disturbance The table below shows the EMC compatibility of S7 modules in areas subject to pulseshaped disturbance. Pulse-shaped disturbance Test voltage corresponds with degree of severity Electrostatic discharge according to IEC Air discharge: ± 8 kv Contact discharge ± 4 kv Burst pulses (high-speed 2 kv (power supply lines) transient disturbance) 2 kv (signal lines > 3 m) to IEC kv (signal lines < 3 m) High-energy single pulse (surge) to IEC External protective circuit required (refer to operating instructions SIMATIC S7-300, CPU 31xC and CPU 31x: Installing ( in Chapter "Lightning and overvoltage protection") asymmetric coupling 2 kv (power supply lines) DC with protective elements 2 kv (signal/ data line only > 3 m), with protective elements as required symmetric coupling 1 kv (power supply lines) DC with protective elements 1 kv (signal/ data line only > 3 m), with protective elements as required Additional measures When connecting an S7-300 system to the public network, always ensure compliance with Limit Value Class B to EN Manual, 02/2011, A5E
31 Technical data 6.1 General technical data Sinusoidal disturbance The table below shows the EMC compatibility of S7-300 modules in areas subject to sinusoidal disturbance. HF radiation HF radiation according to IEC Electromagnetic HF field, amplitude-modulated 80 MHz to 1,000 MHz; 1.4 GHz to 2 GHz 2.0 GHz to 2.7 GHz 10 V/m 1 V/m 80% AM (1 khz) Corresponds with degree of severity 3, 2, 1 HF coupling HF coupling according to IEC MHz to 80 MHz 10 Vrms unmodulated 80% AM (1 khz) 150 Ω source impedance Corresponds with degree of severity 3 Emission of radio interference Electromagnetic interference according to EN 55016: Limit Value Class A (measured at a distance of 10 m). Frequency Noise emission 30 MHz to 230 MHz < 40 db (µv/m)q 230 MHz to 1000 MHz < 47 db (µv/m)q Noise emission via AC mains to EN 55016: Limit value class A, Group 1. Frequency From 0.15 to 0.5 MHz Noise emission < 79 db (µv/m)q < 66 db (µv/m)m 0.5 MHz to 5 MHz < 73 db (µv/m)q < 60 db (µv/m)m 5 MHz to 30 MHz < 73 db (µv/m)q < 60 db (µv/m)m Manual, 02/2011, A5E
32 Technical data 6.1 General technical data Shipping and storage conditions for modules and backup batteries Introduction The shipping and storage conditions of S7-300 modules surpass requirements to IEC The data below apply to modules shipped or put on shelf in their original packing. The modules are compliant with climatic conditions to IEC , Class 3K7 (storage), and with IEC , Class 2K4 (shipping.) Mechanical conditions are compliant with IEC , Class 2M2. Shipping and storage conditions for modules Type of condition Permissible range Free fall (in shipping package) 1 m Temperature - 40 C to + 70 C Barometric pressure 1080 hpa to 660 hpa (corresponds with an altitude of m to 3500 m) Relative humidity 10% to 95%, no condensation Sinusoidal oscillation to IEC Shock to IEC Hz to 9 Hz: 3.5 mm 9 Hz to 150 Hz: 9.8 m/s m/s 2, 6 ms, 1000 shocks Shipment of backup batteries Backup batteries should always be shipped in their original package. Note the regulations governing the transport of hazardous goods. The backup battery has a lithium content of approx g. Storing backup batteries Always store backup batteries in a cool and dry place. The batteries have a maximum shelf life of 5 years. WARNING Improper handling of backup batteries can result in injury and damage to property. Improperly handled backup batteries may explode or cause severe burns. Observe the following rules when handling the backup batteries of your S7-300 automation system: Never charge the batteries Never heat the batteries Never throw the batteries in an open fire Never damage the batteries mechanically (drill, squeeze, etc.) 32 Manual, 02/2011, A5E
33 Technical data 6.1 General technical data Mechanical and ambient climatic conditions for S7-300 operation Operating conditions S7-300 systems are designed for stationary use in weather-proof locations. The operating conditions surpass requirements to DIN IEC Class 3M3 (mechanical requirements) Class 3K3 (climatic requirements) Use with additional measures The S7-300 may not be used under the conditions outlined below without taking additional measures: at locations with a high degree of ionizing radiation in aggressive environments caused, for example, by the development of dust corrosive vapors or gases strong electric or magnetic fields in installations requiring special monitoring, for example elevators electrical plants in potentially hazardous areas An additional measure could be an installation of the S7-300 in a cabinet or housing. Mechanical environmental conditions The table below shows the mechanical environmental conditions in the form of sinusoidal oscillations. Frequency band Continuous Infrequently 10 Hz f 58 Hz mm amplitude 0.75 mm amplitude 58 Hz f 150 Hz 0.5 g constant acceleration 1 g constant acceleration Reducing vibrations If your S7-300 modules are exposed to severe shock or vibration, take appropriate measures to reduce acceleration or the amplitude. We recommend the installation of the S7-300 on damping materials (for example, rubberbonded-to-metal mounting.) Manual, 02/2011, A5E
34 Technical data 6.1 General technical data Test of mechanical environmental conditions The table below provides important information with respect to the type and scope of the test of ambient mechanical conditions. Condition tested Test Standard Comment Vibration Shock Vibration test to IEC (sinusoidal) Shock, tested to IEC Type of oscillation: Frequency sweeps with a rate of change of 1 octave/minute. 5 Hz f 9 Hz, constant amplitude 3.5 mm 9 Hz f 150Hz, constant acceleration 1 g Duration of oscillation: 10 frequency sweeps per axis at each of three vertically aligned axes Type of shock: half-sine Severity of shock: 15 g peak value, 11 ms duration Direction of shock: 3 shocks in each direction (+/-) at each of three vertically aligned axes Climatic environmental conditions The S7-300 may be operated on following environmental conditions: Environmental conditions Permitted range Comments Temperature: - horizontal mounting position: vertical mounting position: 0 C to 60 C 0 C to 40 C Relative humidity 10 % to 95 % No condensation, corresponds to relative humidity (RH) Class 2 to IEC 61131, Part 2 Barometric pressure 1080 hpa to 795 hpa Corresponds with an altitude of m to 2000 m Concentration of pollutants SO2: < 0.5 ppm; RH < 60 %, no condensation H2S: < 0.1 ppm; RH < 60 %, no condensation Test: 10 ppm; 4 days Test: 1 ppm; 4 days ISA-S71.04 severity level G1; G2; G3-34 Manual, 02/2011, A5E
35 Technical data 6.1 General technical data Specification of dielectric tests, protection class, degree of protection, and rated voltage of S7-300 Test voltage Proof of dielectric strength must be provided in the type test at a test voltage to IEC : Circuits with rated voltage Ve to other circuits or ground. Test voltage < 50 V 500 VDC < 150 V 2500 VDC < 250 V 4000 VDC Protection class Protection class I to IEC 60536, i.e., a protective conductor must be connected to the mounting rail! Protection against the ingress of foreign matter and water Degree of protection IP 20 according to IEC 60529, i.e., protection against contact with standard probes. No protection against the ingress of water. Manual, 02/2011, A5E
36 Technical data 6.2 Technical data the 6.2 Technical data the Technical data the Technical data Power supply Rated voltage 24 VDC Ripple (static limit) 20.4 VDC to 28.8 VDC Current consumption at rated voltage without load on PG/OP socket Max. 100 ma Load on PG/OP socket (5 V/90 ma) Max. 130 ma Load on PG/OP socket (24 V/100 ma) Max. 200 ma Electrical isolation Redundancy mode Supports isochronous mode yes, 500 VAC Transmission rate (automatically detected by the repeater) 9.6 kbps, 19.2 kbps, kbps, kbps, kbps, 500 kbps, 1.5 Mbps, 3 Mbps, 6 Mbps, 12 Mbps Throughput times Transmission rate: 12 Mbps Transmission rate: 6 Mbps Transmission rate: 3 Mbps Transmission rate: 1.5 Mbps Transmission rate: <1.5 Mbps 3.0 TBIT+80 ns 2.4 TBIT+80 ns 2.2 TBIT+80 ns 2.1 TBIT+80 ns 0.5 TBIT+80 ns Jitter 1T = 1/48 MHz = ns Operating temperature 0 C to 60 C Storage temperature 40 C to 70 C Relative humidity (operation) 95% at 25 C Degree of protection IP 20 Connection system Bus cables 2 terminal blocks no Yes Power supply Terminal block Connection of fiber-optic conductors yes, via repeater adapters Dimensions W x H x D (mm) 45 x 128 x 67 Weight (includes packaging) 350 g 36 Manual, 02/2011, A5E
37 Technical data 6.2 Technical data the Pin assignment of the sub-d connector (PG/OP socket) View Pin no. Signal name Designation M24V Ground 24 V 3 RxD/TxD-P Data line B 4 RTS Request To Send 5 M5V2 Data reference potential (from station) 6 P5V2 Supply plus (from station) 7 P24V 24 V 8 RxD/TxD-N Data line A Block diagram of the Bus segments 1 and 2 are electrically isolated. Bus segment 2 and the PG/OP socket are electrically isolated. Signals are amplified between bus segments 1 and 2 between PG/OP socket and bus segment Bus segment 1 2 Bus segment 2 3 PG/OP socket 4 PG/OP socket Manual, 02/2011, A5E
38 Technical data 6.2 Technical data the 38 Manual, 02/2011, A5E
39 Dimension drawings Dimension drawings on standard mounting rail The figure below shows the dimensional drawing of the RS 485 repeater mounted on the standard mounting rail. Figure 7-1 RS 485 repeater on standard mounting rail Manual, 02/2011, A5E
40 Dimension drawings 7.1 Dimension drawings RS 485 repeater on mounting rail The figure below shows the dimensional drawing of the RS 485 repeater on an S7-300 mounting rail. Figure 7-2 RS 485 repeater on standard rail 40 Manual, 02/2011, A5E
41 Glossary Active RS 485 terminator Separate -> terminating resistor in segments at transmission rates of 9.6 kbps to 12 Mbps. The power supply is separate from the bus nodes. Bus Data transfer bus to which all nodes are connected. It has two defined ends. In the case of PROFIBUS, the bus is a twisted-pair cable or optical fiber cable. Bus connector Physical connection between the node and bus cable. Bus segment -> Segment The bus line between two terminating resistors forms a bus segment. A bus segment may contain up to 32 bus nodes. Segments can be coupled, for example via RS 485 repeater or diagnostic repeater. Bus segment -> Segment The bus line between two terminating resistors forms a bus segment. A bus segment may contain up to 32 bus nodes. Segments can be coupled, for example via RS 485 repeater or diagnostic repeater. Bus system All nodes physically connected to a bus cable form a bus system. Configuring Configuring means entering a PROFIBUS configuration with all the specific parameters using, for example, STEP 7 or COM PROFIBUS. Manual, 02/2011, A5E
42 Glossary DP master In the DP system, the DP master conducts the communication with the DP slaves according to a defined algorithm. To do this, the DP master uses the functions for communication with the DP slaves which are defined by PROFIBUS DP. DP slave The DP slave can be addressed by DP masters. The DP slave provides specified functions (I/O data, diagnostics etc.) to the DP masters. Master A master station that is in possession of the token can send data to other nodes and request data from these (= active node.) Master-slave process Bus access method where only one node is master, and all other nodes are slaves. Nodes Device whose data can be sent and/or received via the bus, for example a DP master or a DP slave. This device requires a unique PROFIBUS address for this. PROFIBUS PROcess FIeld BUS, bit-serial fieldbus system standardized in IEC as "Type 3". The standard specifies functional, electrical and mechanical properties. PROFIBUS is a bus system that connects PROFIBUS compatible automation systems and field devices on a cell and field level. PROFIBUS exists with the DP protocol (= Distributed Peripheral I/Os), FMS protocol (= Fieldbus Message Specification) or PA protocol (= Process Automation). PROFIBUS address To identify it uniquely, every bus node must be assigned a PROFIBUS address. PCs/PGs are assigned PROFIBUS address "0". DP master and slaves use a PROFIBUS address between 1 and 125. PROFIBUS DP PROFIBUS bus system with the DP protocol. DP stands for the German equivalent of distributed I/O. The main task of PROFIBUSDP is the fast, cyclic data exchange between the central DP master and the peripheral devices. 42 Manual, 02/2011, A5E
43 Glossary Reference potential Reference potential for the evaluation / measuring of the voltages of participating circuits. RS 485 Asynchronous data transmission technology for PROFIBUS DP to ANSI TIA/EIA-RS485-A. RS 485 repeater Device for amplifying bus signals and for linking segments over long distances. Slave A slave may only exchange data with a master when requested to do so. Slaves include, for example, all DP slaves such as ET 200S, ET 200X, ET 200M etc. Standard mounting rail Metal rail standardized in compliance with EN The standard mounting rail is used for the snap-on installation of network components such as OLMs, repeaters etc. Terminator -> terminating resistor in segments at transmission rates of 9.6 kbps to 12 Mbps; the power supply is separate from the bus nodes. Transmission rate -> Transmission speed Transmission speed The transmission speed specifies the number of bits transmitted per second. On PROFIBUS, transmission speeds of 9.6 kbps to 12 Mbps are possible. Manual, 02/2011, A5E
44 Glossary 44 Manual, 02/2011, A5E
45 Index A Approval, 25 CSA, 26 FM, 27 Marine, 28 UL, 26 Use in industrial environments, 28 Use in residential areas, 29 C Configuration, 22 Connecting Bus cable, 21 Supply voltage, 20 Connecting the bus cable, 21 CSA approval, 26 D Degree of protection IP 20, 35 Dimension drawings, 39 disturbance variables, 30 E Electrical isolation, 19 EMV (Electromagnetic compatibility), 30 disturbance variables, 30 Environmental conditions Climatic, 34 Mechanical, 33 Operating condition, 33 F FM approval, 27 G grounded operation, 17 I IEC 61131, 28 Insulation test, 35 Internet, Service & Support, 6 M Marine approval, 28 Mounting Mounting rail for S7-300, 13 Standard mounting rail, 15 O Order number 6ES7972-0AA01-0XA0, 9 P Protection class, 35 R Repeater, 7, 7 Design, 11 Dimensional drawing, 39 Electrical isolation, 19 grounded operation, 17 Installation rules, 10 Pin assignment, 37 Properties, 9 Schematic circuit diagram, 37 Technical data, 36 ungrounded operation, 17 S Service & Support, 6 Shipping conditions, 32 Standards, 25 Storage conditions, 32 Supply voltage, 20 Manual, 02/2011, A5E
46 Index T Technical data, 36 EMV (Electromagnetic compatibility), 30 Shipping and storage conditions, 32 Standards and approvals, 25 Technical Support, 5 Terminating resistor, 22 Test voltage, 35 U UL certification, 26 ungrounded operation, Manual, 02/2011, A5E
SIMATIC NET Industrial Ethernet switches MM900 media modules for SCALANCE XR-500M
SIMATIC NET Industrial Ethernet switches MM900 media modules for SCALANCE XR-500M Compact Operating Instructions Legal information Qualified Personnel The product/system described in this documentation
SIMATIC. S7-300 and M7-300 Programmable Controllers Module Specifications. Preface, Contents. General Technical Specifications. Power Supply Modules
SIMATIC S7-300 and M7-300 Programmable Controllers Module Specifications Reference manual This manual is part of the following documentation packages with order nos: S7 300 Programmable Controller: 6ES7
Redundancy Module QUINT-DIODE/40
Redundancy Module QUT DIODE provides: 00% decoupling of power supplies connected in parallel Can be installed in potentially explosive areas Load currents up to 60 A supported Easy assembly by snapping
Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1
Power Supply Unit, Primary Switched, Narrow Design MINI POWER provides: Extra narrow design with widths of 22.5 mm, 45 mm, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a wide-range input
SIMATIC. PC Adapter USB. Preface, Contents Properties of the PC Adapter USB 1. Package Components
s SIMATIC Manual Preface, Contents Properties of the 1 Package Components 2 Requirements for Operation 3 Hardware Design of the 4 Working with the 5 on the MPI/DP Network 6 Firmware Update 7 Error Diagnostics
CPU 317-2 PN/DP: Configuring an ET. 200S as PROFINET IO device SIMATIC. PROFINET CPU 317-2 PN/DP: Configuring an ET 200S as PROFINET IO device
CPU 317-2 PN/DP: Configuring an ET 200S as PROFINET IO device SIMATIC PROFINET CPU 317-2 PN/DP: Configuring an ET 200S as PROFINET IO device Introduction 1 Preparation 2 Learning units 3 Further Information
MCR-VDC-UI-B-DC. Voltage Transducer for DC Voltages. INTERFACE Data Sheet 100260_en_01. 1 Description
Voltage Transducer for DC Voltages TERFACE Data Sheet 000_en_0 PHOENIX CONTACT - /00 Description The MCR voltage transducer measures DC voltages in several signal ranges from 0... ±0 V DC to 0... ±0 V
SIMATIC. ET 200S distributed I/O Digital electronic module 8DO DC24V/0.5 A (6ES7132-4BF00-0AA0) Preface. Properties 1. Diagnostics 2.
SIMATIC ET 200S distributed I/O SIMATIC Preface Properties 1 Diagnostics 2 ET 200S distributed I/O Digital electronic module 8DO DC24V/0.5 A (6ES7132-4BF00-0AA0) Manual 04/2007 A5E01077385-01 Safety Guidelines
R4D0-FB-IA* FieldBarrier. Features. Assembly. Function. Connection IN + - S OUT ... ... Spur 2. Spur 1. Zone 1. Zone 0
FieldBarrier Features Assembly 8... 12 outputs Ex ia IIC, FISCO and Entity Advanced fault isolation and diagnostics at the spur FieldBarrier in Zone 1/Div. 2 Instruments in Zone 0...1/Div. 1 For FOUNDATION
CompactLogix Power Supplies Specifications
Technical Data CompactLogix Power Supplies Specifications 1768 CompactLogix Power Supplies Catalog Numbers 1768-PA3, 1768-PB3 1769 Compact I/O Power Supplies Catalog Numbers 1769-PA2, 1769-PB2, 1769-PA4,
SIMATIC. ET 200S distributed I/O Digital electronic module 8DI DC24V (6ES7131-4BF00-0AA0) Preface. Properties 1. Diagnostics 2.
SIMATIC ET 200S distributed I/O SIMATIC Preface Properties 1 Diagnostics 2 ET 200S distributed I/O Digital electronic module 8DI DC24V (6ES7131-4BF00-0AA0) Manual 04/2007 A5E01077339-01 Safety Guidelines
SIMATIC. ET 200S distributed I/O 2AO I ST analog electronic module (6ES7135-4GB01-0AB0) Preface. Properties 1. Parameters 2.
SIMATIC ET 200S distributed I/O SIMATIC ET 200S distributed I/O 2AO I ST analog electronic module (6ES7135-4GB01-0AB0) Manual Preface Properties 1 Parameters 2 Diagnostics 3 Analog value representation
STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: 2868567. DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase
Extract from the online catalog STEP-PS/1AC/12DC/1.5 Order No.: 2868567 DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase Commercial data EAN 4046356292924 Pack 1 pcs. Customs tariff
Waveguide Access Point WGA631. Product Guide
Waveguide Access Point Product Guide Waveguide Access Point Contents 1. Description............................ 3 2. Application............................ 3 3. Technical data... 4 4. Physical interfaces......................
TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC - 0.5 A - M8 connector
Product datasheet Characteristics TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC - 0.5 A - M8 connector Main Range of product Product or component type Range compatibility Enclosure material Bus
LOGO!Power. Power supply. LOGO!Power. Overview. Description, device design, dimension drawing. Mounting/Disassembly 2
Overview Description, device design, dimension drawing 1 Power supply Operating Instructions Mounting/Disassembly 2 Mounting position, installation clearances 3 Installation 4 Applications 5 Technical
Digital input modules
8 172 TX-I/O Digital input modules TXM1.8D TXM1.16D Two fully compatible versions: TXM1.8D: 8 inputs, each with a three-color LED (green, yellow or red) TXM1.16D: As TXM1.8X, but 16 inputs, each with a
Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description
Type: EASY719 DC RC Article.: 274119 Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC Description 12 digital inputs (4 inputs available as analog inputs) 6 relay outputs LCD display
MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)
MILLENIUM Table of contents 1. INTRODUCTION 1 2. HARDWARE DESCRIPTION 2 3. INSTALLATION 5 4. CONNECTION 6 5. USER SAFETY AND PROTECTION OF EQUIPMENT 8 1. Introduction The MILLENIUM series has been designed
Chrome DIN Rail Power Supply 24V 30W 1 Phase (Class II & NEC Class 2) / DRC-24V30W1AZ
Highlights & Features Protection Class II, Double Isolation (No Earth connection is required) Universal AC input voltage without power de-rating Efficiency > 87.0% @ 115Vac & 230Vac NEC Class 2 / Limited
SIMATIC. PC Adapter USB. Preface, Contents Properties of the. PC Adapter USB. Package Components 2
s SIMATIC Manual Preface, Contents Properties of the 1 Package Components 2 Requirements for Operation 3 Hardware Design of the 4 Working with the 5 on the MPI/DP Network 6 Firmware Update 7 Error Diagnostics
Analog signal converters CC-E I/I Current / current isolators
ata sheet Analog signal converters CC-E I/I Current / current isolators The CC-E I/I is an isolator for the electrical isolation of current signals without auxiliary supply. It allows the isolation between
SIMATIC S7-300. Getting Started for First Time Users. Order No.: 6ZB5310-0NC02-0BA0 04/2007 A5E01094750-01
SIMATIC S7-300 Getting Started for First Time Users Order No.: 6ZB5310-0NC02-0BA0 04/2007 A5E01094750-01 Safety Guidelines This manual contains notices you have to observe in order to ensure your personal
CliQ DIN Rail Power Supply 24V 120W 1 Phase / DRP024V120W1AA
Highlights & Features Reliable design, with expected life of 10 years Compact, rugged design for ease of handling and installation Multiple connections to terminals allowed Designed for Class I Div. 2
Modular I/O System Analog and Digital Interface Modules
OPERATING INSTRUCTIONS Modular I/O System Analog and Digital Interface Modules Installation Operation Maintenance Document Information Document ID Title: Operating Instructions Modular I/O System Part
Chrome DIN Rail Power Supply 24V 91.2W 1 Phase (Class II & NEC Class 2) / DRC-24V100W1AZ
Highlights & Features Protection Class II, Double Isolation (No Earth connection is required) Universal AC input voltage without power de-rating Efficiency > 87.0% @ 115Vac, > 89.0% @ 230Vac NEC Class
Power Supply, Primary Switch Mode, Narrow Design MINI-PS-100-240AC/24DC/2
Power Supply, Primary Switch Mode, Narrow Design -PS-100-240AC/24/2 POWER provides: Extra narrow widths of 22.5 and 45 mm (0.886 and 1.772 in.) Global use due to a wide range input A high level of operational
Chrome DIN Rail Power Supply 12V 54W 1 Phase (Class II & NEC Class 2) / DRC-12V60W1AG
Highlights & Features Protection Class II, Double Isolation (No Earth connection is required) Universal AC input voltage and full power up to 55 C Power will not de-rate for the entire input voltage range
Documentation for. KL2602 and KL2622. Two-channel Relay Output Terminals for 230 V AC / 30 V DC. Version: 1.4 Date: 2013-03-20
Documentation for KL2602 and KL2622 Two-channel Relay Output Terminals for 230 V AC / 30 V DC Version: 1.4 Date: 2013-03-20 Table of contents Table of contents 1 Foreword 1 1.1 Notes on the documentation
Telephone- and leased line modem for industrial applications TD-36
Telephone- and leased line modem for industrial applications TD-36 Modem for industrial PSTN- and leased line applications The TD-36 is an analogue V.34 PSTN modem as well as an industrial 2-wire leased
Square D Clipsal DIN-Rail Four-Channel Auxiliary Input Unit
Square D Clipsal DIN-Rail Four-Channel Auxiliary Input Unit SLCLE5504AUX for Use with Wired C-Bus Networks Instruction Bulletin Retain for future use. Square D Clipsal DIN-Rail Four-Channel Auxiliary Input
1788 Linking Device Specifications
Technical Data 1788 Linking Device Specifications Catalog Numbers 1788-EN2DNROM, 1788-EN2DNR, 1788-EN2FFR, 1788-EN2PAR, 1788-CN2DN, 1788-CN2FFR, 1788-CN2PAR, 1788-FBJB4R, 1788-FBJB6 Topic Page 1788-EN2DNR
Power Supply, Primary Switch Mode, Narrow Design MINI-PS-100-240AC/2x15DC/1
Power Supply, Primary Switch Mode, Narrow Design -PS-100-240AC/2x15DC/1 POWER provides: Extra narrow widths of 22.5 and 45 mm (0.886 and 1.772 in.) Global use due to a wide range input A high level of
MCR1900 Media Converter 19-Slot Chassis
MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the
Power Supplies 3. SDN-P DIN Rail Series
SDN-P DIN Rail Series The SDN DIN Rail power supplies provide industry leading performance. Sag Immunity, transient suppression and noise tolerant, the SDN series ensures compatibility in demanding applications.
UniStream CPU-for-Panel
UniStream CPU-for-Panel Installation Guide USC-P-B10 Unitronics UniStream platform comprises control devices that provide robust, flexible solutions for industrial automation. This guide provides basic
Rack mounted telephone- and leased line modem for industrial applications
Rack mounted telephone- and leased line modem for industrial applications TR-6 Rack modem for industrial PSTNand /-wire leased line applications The TR-6 is an analogue V. 9 -rack PSTN modem as well as
LOGO!Power. Power supply. LOGO!Power. Overview. Safety instructions. Description, device design, dimension drawing. Mounting/disassembly
Overview Safety instructions 1 Power supply Operating Instructions Description, device design, dimension drawing 2 Mounting/disassembly 3 Mounting position, mounting clearances 4 Installation 5 Technical
Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information.
Product and Applications Description The power supply units N 125/x2 can supply DC 24 V power from an additional pair of terminals (yellowwhite). This DC 24 V output voltage can be used to power e.g. an
MINI MCR-SL-R-UI(-SP)
Resistance/potiposition transducer INTERFACE Data Sheet 0807_en_05 Description PHOENIX CONTACT - 0/008 Features The slim MINI MCR-SL-R-UI... potiposition transducer has a width of only 6. mm and converts
USB-to-Data Highway Plus Cable
Installation Instructions USB-to-Data Highway Plus Cable Catalog Number 1784-U2DHP Topic Page Important User Information 2 Environment and Enclosure 3 Install the Cable 5 Configure the DH+ Node Address
TX OPEN RS232/485 module
s 8 185 8185P01 TX-I/O ; DESIGO OPEN TX OPEN RS/485 module for integrating third-party systems and devices to DESIGO (V4 or higher) TXI1.OPEN Platform to integrate third-party systems and devices to the
1756 ControlLogix Chassis Specifications
Technical Data 1756 ControlLogix Chassis Specifications Catalog Numbers 1756-A4/B, 1756-A4K/B, 1756-A4/C, 1756-A4K/C, 1756-A7/B, 1756-A7K/B, 1756-A7/C, 1756-A7K/C, 1756-A10/B, 1756-A10K/B, 1756-A10/C,
Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
SIMATIC. ET 200S distributed I/O 2AI U ST analog electronic module (6ES7134-4FB01-0AB0) Preface. Properties 1. Parameters 2.
SIMATIC ET 200S distributed I/O SIMATIC ET 200S distributed I/O 2AI U ST analog electronic module (6ES7134-4FB01-0AB0) Manual Preface Properties 1 Parameters 2 Diagnostics 3 Analog value representation
HMIGTO4310 advanced touchscreen panel 640 x 480 pixels VGA- 7.5" - TFT - 96 MB
Product datasheet Characteristics HMIGTO4310 advanced touchscreen panel 640 x 480 pixels VGA- 7.5" - TFT - 96 MB Main Range of product Product or component type Display colour Display size Supply Magelis
S-series SQ Controller
DeltaV Distributed Control System Product Data Sheet December 2015 S-series SQ Controller Scalable controllers Quick assembly Easy-to-use Field proven architecture Designed for Electonic Marshalling Advanced
RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC
Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage
DVPPF02-H2. PROFIBUS DP Slave Communication Module Application Manual
DVPPF02-H2 PROFIBUS DP Slave Communication Module Application Manual Warning Please read this instruction carefully before use and follow this instruction to operate the device in order to prevent damages
Programmable set for Ethernet Modbus/TCP in IP67 TI-BL67-PG-EN-2
Type code Ident no. 1545065 Number of channels 2 Dimensions (W x L x H) 108 x 145 x 77.5 mm CoDeSys-programmable acc. to IEC 61131-3 Cable max. 50 m between interface and read/write head 10/100 Mbps Male
PCS0100en 02.2008. Persy Control Services B.V. Netherlands
P-Bus Gateway PBGW2.128 Universal gateway between the P-bus protocol and open standard protocols. The variety of available electrical interfaces on the gateway offers a wide range of possibilities for
Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs
E031026 000823 Process modules Digital input PMI for inputs for 120 V AC inputs PMI Input E4, E5, GND L- PMI 120 V AC Input E4, E5, Common C E6, E7, GND L- E6, E7, Common C LEDs for the inputs operation
AXIS T81B22 DC 30W Midspan
INSTALLATION GUIDE AXIS T81B22 DC 30W Midspan ENGLISH About this Document This document includes instructions for installing AXIS T81B22 on your network. Previous experience of networking will be beneficial
Adjustment functions for both span and shift have been incorporated
SENSORS FOR SERIES LED Type Wafer Alignment Sensor FX-0-F FT-F9 FD-F7 EX-F70/F60 M SH-7 FD-L4 M-DW The use of a safe LED light beam now allows for high precision detection with a resolution of 0!m (.8
Voltage Regulator SPAU 341 C. Product Guide
Issued: July 1998 Status: Updated Version: D/25.04.2006 Data subject to change without notice Features Comprehensive voltage regulation for power transformers with on-load tapchangers in distribution substations
NI 9423. NI C Series Overview DATASHEET. 8-Channel Sinking Digital Input Module
DATASHEET NI 9423 8-Channel Sinking Digital Input Module 8-channel, 100 µs digital input 24 V logic, sinking digital input Compatible with NI CompactDAQ counters 250 Vrms, CAT II isolation 10-position
TECHNICAL DATASHEET #TD1404AX PWM CONTROLLED SOLENOID DRIVER
TECHNICAL DATASHEET #TD1404AX PWM CONTROLLED SOLENOID DRIVER (PWM Input, 1.2A or 2A Output, Metal Box or PCB) PCB Board - P/N: PWMC-PCB-2A, PWMC-PCB-1.2A Packaged Driver (metal box with 1.5 m (5 ft.) cable)
Drayton Digistat +2RF/+3RF
/+3RF Programmable Room Thermostat Wireless Model: RF700/22090 Model: RF701/22092 Power Supply: Battery - Thermostat Mains - Digistat SCR Invensys Controls Europe Customer Service Tel: 0845 130 5522 Customer
ConneXium Ethernet Switches TCSESU0 F N0 Quick Reference Guide
31007950 7/2009 ConneXium Ethernet Switches TCSESU0 F N0 Quick Reference Guide 7/2009 31007950.02 www.schneider-electric.com NOTICE Read these instructions carefully, and look at the equipment to become
Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact
Data sheet Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact The CT-AHD.12 is an electronic time relay with OFF-delay. It is from the CT-D range. With their MDRC profile and a width of only
SIMATIC NET. CP 243-2 AS-Interface Master B C. Preface Contents. Technical Description and Installation Instructions Interface to the User Program
Preface Contents SIMATIC NET CP 243-2 AS-Interface Master Manual Technical Description and Installation Instructions Interface to the User Program 2 in the S7-200 CPU Access to the Data of the AS-i Slaves
Plug-in relays Mini ISO relays
Powertrain Systems Chassis Systems Safety Security Body Driver Information Convenience Description Features Limiting continuous current 70 A Dimensional characteristics and the functional allocation of
PSI-REP-PROFIBUS/12MB
Repeater for PROFIBUS Systems up to 12 Mbps INTERFACE Data Sheet 102986_02_en PHOENIX CONTACT - 03/2007 1 Description The PSI-REP-PROFIBUS/12MB DIN rail-mountable modular PROFIBUS repeater is designed
PD30ETB20xxIS. Photoelectrics, Background Suppression reflective with IR light. Main features. Description
Photoelectrics, Background Suppression reflective with IR light Main features Description The PD30ET... stainless steel sensors are built with high-quality materials and designed for harsh environments.
33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application
33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application Features Compliant with the IEEE802.3at Standard -40 to +60 C Temperature Range Diagnostic LEDs Full Protection
5SV Residual Current Protective Devices
s Siemens AG 2013 SENTRON 5SV Residual Current Protective Devices New portfolio for reliable personnel, material and fire protection Safe protection against residual currents Residual current protective
Power Supply Guide Version 1.0 for D-Show
Power Supply Guide Version 1.0 for D-Show Digidesign 2001 Junipero Serra Boulevard Daly City, CA 94014-3886 USA tel: 650 731 6300 fax: 650 731 6399 Technical Support (USA) tel: 650 731 6100 fax: 650 731
Foxboro Evo Process Automation System
Foxboro Evo Process Automation System Product Specifications PSS 31H-2Z32 FBM232 Field Device System Integrator Module, 10/100 Mbps Ethernet, Single The FBM232 Field Device System Integrator (FDSI) module
NX safety stand-alone
NX-S@ NX safety stand-alone stand-alone into machine automation Expandable safety system up to 32 safety connections or 63 standard connections controller flexible system lets your freely mix safety I/O
CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.
425 CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE General purpose single phase thyristors and solid state relays Product data abc 425 EUROCUBE A complete range of low cost solid state relays and
Cable Solutions for Servo and Variable Frequency Drives (VFD)
Cable Solutions for Servo and Variable Frequency Drives (VFD) Electric drive systems with continuous torque and speed control are widespread today. They allow an optimal adjustment of the drive with respect
Product and functional description
Product and functional description The KNX / DALI gateway N 141/02 is a 4 MU wide, DINrail mounted KNX device with one DALI interface to which up to 64 DALI actuators (e.g. DALI ballasts) can be connected
Safety technique. Emergency stop module BO 5988 safemaster
Safety technique Emergency stop module BO 5988 safemaster 0221562 Function diagram Pushbutton on Mains or emergencystop () K1 According to EC Directive for machines 98/37/EG According to IEC/E 60204-1
Molded Case Circuit Breaker Specifications Bulletin Number 140U-D
Technical Data Molded Case Circuit Breaker Specifications Bulletin Number 140U-D Topic Page Product Line Overview 2 Specifications 3 Trip Curves 4 Approximate Dimensions 6 Additional Resources These documents
FIBER OPTIC APPLICATION IN A PROFIBUS NETWORK
FIBER OPTIC APPLICATION IN A PROFIBUS NETWORK Field busses are industrial control systems using Programmable Logic lers (PLC) to control and manage field devices found in industrial environments. The communication
RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER
Application : The RISH CON - Hz transducer is used for frequency measurement. The output signal is proportional to measured frequency and is either load independent DC Current or load independent DC Voltage.
RM4TG20 three-phase network control relay RM4-T - range 200..500 V
Characteristics three-phase network control relay RM4-T - range 200..500 V Complementary [Us] rated supply voltage Output contacts Setting accuracy of time delay Delay at power up Measuring cycle Marking
Three-phase monitoring relay CM-PFE
Data sheet Three-phase monitoring relay CM-PFE The CM-PFE is a three-phase monitoring relay that monitors the phase parameter phase sequence and phase failure in three-phase mains. 2CDC 251 005 S0012 Characteristics
S-series Mass Connection Solutions
DeltaV Distributed Control System Product Data Sheet March 2015 S-series Mass Connection Solutions Fast, easy and error-free cabinet wiring Modular design, improves reliability Lowers overall termination
Validity 1. Improvements in STEP 7 2. Improvements in WinCC 3 SIMATIC. Readme. Programming and Operating Manual
Validity 1 Improvements in STEP 7 2 SIMATIC Improvements in WinCC 3 Readme Programming and Operating Manual 07/2013 Legal information Warning notice system This manual contains notices you have to observe
Perle Protocol Transparent Media Converter Modules
Perle Protocol Transparent Media Converter Modules Installation Guide C-4GPT-DSFP CM-4GPT-DSFP Part# 5500335-10 Overview This document contains instructions necessary for the installation and operation
Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages
Data sheet Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages The CM-ESS.2 is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of
STRATO LED Drivers 70W, Single output
Features STRATO switch mode driver technology is designed to generate one constant current output from a wide range AC input. The size and performance of these products make them the ideal choice for LED
EMOSAFE EN-100. Network Isolators for PCB assembly 1 GENERAL DESCRIPTION. Product Data Sheet ENGLISH
ENGLISH EMOSAFE EN-100 Product Data Sheet Network Isolators for PCB assembly November 2013 1 GENERAL DESCRIPTION The EMOSAFE EN-100 Network Isolator interrupts all galvanically conducting connections (conductors
Mounting instructions. Junction box VKK2R-8 DIGITAL. A1145-1.0 en
Mounting instructions Junction box VKK2R-8 DIGITAL VKK2R-8 DIGITAL 3 Contents Page Safety instructions... 4 1 Introduction and appropriate use... 7 2 Mechanical construction... 8 2.1 Mounting... 9 3 Electrical
DLP-PU/E Instruction Manual
Instruction Manual BEFORE USING THE POWER SUPPLY UNIT Pay attention to all warnings and cautions before using the unit. Incorrect usage could lead to an electrical shock, damage to the unit or a fire hazard.
MICROSENS. Central 48 V DC Power Supplies for PoE-Components. Description. Features
Central 48 V DC Power Supplies for PoE-Components MICROSENS Description Active network equipment which is supporting the Power-over-Ethernet functions, typically requires a powerful 48 V DC power supply.
Energy Management Energy Meter Type EM23 DIN
Energy Management Energy Meter Type EM23 DIN Class 1 (kwh) according to EN62053-21 Class B (kwh) according to EN50470-3 Class 2 (kvarh) according to EN62053-23 Accuracy ±0.5 RDG (current/voltage) Energy
FLUORESCENT UV- RING LIGHT OPERATING INSTRUCTION
FLUORESCENT UV- RING LIGHT OPERATING INSTRUCTION Caution! UV-radiation of this device is in the range of UV-A (320-400 nm). Direct exposure to eyes shall therefore be avoided. UV protection glasses shall
ST Series POWER SUPPLIES USER INSTRUCTIONS
Introduction These instructions detail the installation and operation requirements for the ST20 & ST35 power supplies. These have been designed for operation in RV s providing a DC power system, with optional
Magnetic field sensor for pneumatic cylinders BIM-INT-Y1X-H1141
ATEX category II 1 G, Ex zone 0 ATEX category II 1 D, Ex zone 20 SIL2 as per IEC 61508 Rectangular, height 6mm Plastic, PA12 Magnetic-inductive sensor DC 2-wire, nom. 8.2 VDC Output acc. to DIN EN 60947-5-6
CliQ DIN Rail Power Supply 24V 120W 1 Phase / DRP024V120W1AA
Highlights & Features Universal AC input voltage Power will not de-rate for the entire input voltage range Power Boost of 150% for 3 seconds Full corrosion resistant aluminium chassis SEMI F47 certified
Universal Serial Bus (USB) to DH-485 Interface Converter
Installation Instructions Universal Serial Bus (USB) to DH-485 Interface Converter Catalog Number 1747-UIC Contents Overview..................................................3 Computer and Operating System
ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories
2CDC 251 014 F0t09 Features Monitoring of three-phase mains for grid feeding Type-tested in accordance with DIN V VDE V 0126-1-1: February 2006 Neutral conductor connection configurable Can also be used
Inductive sensor NI10-M18-Y1X-H1141
ATEX category II 1 G, Ex zone 0 ATEX category II 1 D, Ex zone 20 SIL2 as per IEC 61508 Threaded barrel, M18 x 1 Chrome-plated brass DC 2-wire, nom. 8.2 VDC Output acc. to DIN EN 60947-5-6 (NA- MUR) M12
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical Relays
LAB 1 TECHNICAL DOC 3 IN ONE LAB DEVICE. Velleman Legen Heirweg 33 9890 Gavere Belgium
LAB 1 TECHNICAL DOC 3 IN ONE LAB DEVICE Velleman Legen Heirweg 33 9890 Gavere Belgium SPECIFICATIONS DIGITAL MULTIMETER 3 1/2 backlit LCD Automatic polarity indication DC voltage 200mV to 600V in 5 steps
Electronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet
Characteristics Single-function OFF-delay timer for DC contactors, without auxiliary voltage Width.5 mm CDC 5 6 F3 Approvals A culus E CCC CT-VBS a Circuit diagram b Marker label Marks a CE b C-Tick Order
PHOENIX CONTACT - 2012-12-14. Features
Electronic monitoring relay for phase sequence, phase failure, and asymmetry monitoring Data sheet 101748_en_03 1 Description PHOEIX COTACT - 2012-12-14 Features Increasingly higher demands are being placed
PCAN-B10011S Bus Converter High-speed CAN to Truck Trailer CAN. User Manual. Document version 2.1.0 (2013-11-15)
PCAN-B10011S Bus Converter High-speed CAN to Truck Trailer CAN User Manual Document version 2.1.0 (2013-11-15) Products taken into account Product Name Model Part number PCAN-B10011S IPEH-002041 CANopen
