Design Validation and Improvement Study of HVAC Plumbing Line Assembly under Random Loading Condition
|
|
|
- Oliver Jefferson
- 9 years ago
- Views:
Transcription
1 Design Validation and Improvement Study of HVAC Plumbing Line Assembly under Random Loading Condition Rakesh Jakhwal Senior Engineer Chrysler Group LLC RMZ Millenia II, Perungudi Chennai , India Yogesh Kumar Senior Engineer Chrysler Group LLC RMZ Millenia II, Perungudi Chennai , India Muthukumar Arunachalam Manager Chrysler Group LLC RMZ Millenia II, Perungudi Chennai , India Abstract Automotive OEMs are currently addressing faster product development cycle needs with increasingly robust and efficient virtual validation processes facilitated by improved CAE tools and techniques. This includes developing reliable virtual methods for complex problems. The objective of this paper is to present a validation process for HVAC Plumbing line Assembly under random vibration loading condition for a specific test setup. The process is validated by correlating virtual prediction of potential problems locations on the plumbing line to the corresponding observations in physical test. The method is then used to develop design modifications in the virtual models to address and mitigate the problem which is then verified in the physical re-test. The virtual methodology has been currently developed on HyperWorks platform (version 11.0). Introduction: The purpose of the HVAC plumbing assembly is to provide a reliable leak-free and efficient method of transferring refrigerant and oil between air conditioning components at high and low temperatures and pressures. HVAC Plumbing shall be routed and supported in a manner which ensures functionality during life cycle of the product. HVAC Plumbing must be routed so as to either be sufficiently constrained or have sufficient clearance with surrounding components to prevent harmful contact. Suction Line-Tube that convey refrigerant gas or vapor from evaporator outlet to the suction inlet compressor. Discharge Line Tube that convey the compressed refrigerant vapor from compressor to the condenser inlet. Liquid Line Tube used to convey liquid refrigerant from the condenser outlet to the refrigerant control device of evaporator. 1
2 Figure 1: Plumbing line routing sketch diagram An automobile traveling down a rough road is subjected to random excitation. The Random vibration test verifies the components capability to meet applicable functional/performance requirement during or after exposure to the service life random vibration environments. Real world vibrations are usually of the random type. Figure 2: (a) sine wave (b) Random profile (c) PSD curve The difference between sine vibration and random vibration is that for random vibration, at any point in time, any frequency can be happening that will excite, or resonate, multiple bodies at once. What this means is although one member of the system may have a low frequency, and another high, they can both be resonating at the same instant in a random vibration environment. The sine environment will run the input curve over the frequency band from 20 to 2000 hertz that can be experienced in the vehicle and only one member will resonate at a time, assuming of course two members do not share a natural frequency. Most of the time a sine scan is run to determine the resonances of the vehicle. A 1G input over the entire frequency band is used, and is not meant to induce fatigue damage. This data is used to validate the FEA before certification or qualification testing occurs. 2
3 Sigma (σ) & Sigma Clipping: Figure 3: sigma clipping Sigma is the standard deviation of a statistical PDF. A Gaussian PDF distribution is assumed for random vibration which takes the shape of a bell shaped curve. Since the amplitude or intensity of the random vibration will change over time, the time spent at different amplitude excursions is measured using a PDF. Figure 3 shows a Gaussian PDF. The vertical axis would be 1/G, the horizontal axis would be sigma and µ is the mean which is equal to zero for a shaker control. For a Gaussian distribution, 68.2% of the peak G excursions occur between ± 1 sigma, 95.4% between ± 2 sigma, 99.7% between ± 3 sigma. Process Methodology: Figure 4: HVAC Plumbing line Validation Process 3
4 Physical Test Setup: Test set up placed in a group of 4-6 samples to be tested in tri - axial shaker table with bolted with the location as per vehicle condition. Generic random vibration profile as per standard provided to run specific hours for each individual axis. Figure 5: Controlled input PSD profiles for shaker table Performance Criteria: Vibration testing shall be performed with plumbing line assembly installed in bench test condition. The acceptance criteria are: - No issues, Leak Test prior to the vibration test for each axis for specifichrs. cycle run. - No issues s (cracks, deformation, etc.) of add-on components such as brackets, clips, isolators, transducer, service valves, etc., following evaluation, Florescent Liquid Penetrate Inspection. CAE process and correlation: Meshing -AC plumbing line FE modeling is done as per standard guidelines. Boundary Condition -Plumbing Line is constrained as per Physical Test shown above. Analysis -Modal analysis is performed to check the natural frequency of the plumbing line assembly, followed by random vibration analysis using vehicle road profile. Problem could be predicted when the 3 sigma stress is higher than the material yield stress. Example of which is shown below. Figure 6: CAE Model Set Up 4
5 Results & Discussions: Two- Piece bracket design Baseline Physical Test Problem observed beforespecific hours in first axis at marked location Virtual Test Maximum 3-sigma RMS stress isobserved more than material yieldstress at marked location Figure 7: Physical and CAE results for baseline bracket CAE simulation correlates well with the Test. 3-sigma RMS stress are higher than the Yield stress of the bracket. Design Iterations were carried out to avoid problems with material and gauge change. Design Modification Baseline - 2 pieces Bracket material aluminum. Proposed - single piece Bracket Material aluminum with bead. Figure 8: Bracket design modification 5
6 CAE proposed- single piece bracket design with bead Physical Test No issue observed tillspecific hours in the test. Virtual Test Maximum 3-sigma RMS stress isobserved less than material yieldstress. Figure 9: CAE and Physical Test Results for Modified Bracket Benefits Summary: The random vibration analysis tool reduces the product development phase as virtual tools consumes less time. It helps to evaluate the performance of a design before cutting tools or physically building prototypes. The cost of the design verification in the different stages eliminates by reducing number of physical test or sample size. Challenges: The major challenge with random vibration analysis to solving time and file size is more. Nonlinearity affect need to take care for this type of analysis. Extra care need to be carried for averaging and filtering the data from road profiles to make PSD curve. Future Plans: Current CAE validation using random vibration analysis can be extended to fatigue life prediction which would yield the information of number of cycles. Conclusions: It is necessary to take structural loads due to sine and random environment to define the frequency domain and reach a conclusion. Even though there have been many advances in CAE, and it is widely used in the engineering field, physical testing is still used as a final confirmation for subsystems due to the fact that CAE cannot predict all variables in complex assemblies. 6
7 ACKNOWLEDGEMENTS We would like to thank the Chrysler Management for their continuous support in accomplishing this task and also like to thanks to design and testing team for continuous support to execute the process. REFERENCES [1] Francis J. Andrews: Random Vibration An Overview [2] Tom Irvine : Power Spectral Density units:[g^2/hz] Revision A [3] Tom Irvine: An Introduction to Random Vibration Revision B [4] OptiStruct reference guide [5] NWM Bishop: Vibration Fatigue Analysis In Finite Element Environment,
Similar benefits are also derived through modal testing of other space structures.
PAGE 1 OF 5 PREFERRED RELIABILITY PRACTICES MODAL TESTING: MEASURING DYNAMIC STRUCTURAL CHARACTERISTICS Practice: Modal testing is a structural testing practice that provides low levels of mechanical excitation
Methods to predict fatigue in CubeSat structures and mechanisms
Methods to predict fatigue in CubeSat structures and mechanisms By Walter Holemans (PSC), Floyd Azure (PSC) and Ryan Hevner (PSC) Page 1 Outline Problem Statement What is fatigue? Cyclic loading and strength
Modal Analysis of Structures Loaded With Fluid Using Virtual Fluid Mass Method
Modal Analysis of Structures Loaded With Fluid Using Virtual Fluid Mass Method S.Arun Kumar Manager Ashok Leyland Limited Chennai-600103 India [email protected] S.Sivasankaran Sr.Manager Ashok
RANDOM VIBRATION AN OVERVIEW by Barry Controls, Hopkinton, MA
RANDOM VIBRATION AN OVERVIEW by Barry Controls, Hopkinton, MA ABSTRACT Random vibration is becoming increasingly recognized as the most realistic method of simulating the dynamic environment of military
The Application of Process Automation and Optimisation in the Rapid Development of New Passenger Vehicles at SAIC Motor
The Application of Process Automation and Optimisation in the Rapid Development of New Passenger Vehicles at SAIC Motor Dave Husson Vehicle CAE Manager, SAIC Motor UK Technical Centre Lowhill Lane, Longbridge,
Rock Bolt Condition Monitoring Using Ultrasonic Guided Waves
Rock Bolt Condition Monitoring Using Ultrasonic Guided Waves Bennie Buys Department of Mechanical and Aeronautical Engineering University of Pretoria Introduction Rock Bolts and their associated problems
Testing Capabilities. Worldwide Designers & Manufacturers of Air Moving Equipment
Testing Capabilities Twin Twin City City Fan Fan Companies, Companies, Ltd. Ltd. Worldwide Designers & Manufacturers of Air Moving Equipment TestingCapabilities Twin City Fan Companies, Ltd. In today s
Automobile Air Conditioning Primer
Automobile Air Conditioning Primer An air conditioner is basically a refrigerator without the insulated box. It uses the evaporation of a refrigerant, like Freon, to provide cooling. The mechanics of the
Finite Element Analysis for Acoustic Behavior of a Refrigeration Compressor
Finite Element Analysis for Acoustic Behavior of a Refrigeration Compressor Swapan Kumar Nandi Tata Consultancy Services GEDC, 185 LR, Chennai 600086, India Abstract When structures in contact with a fluid
Comparison of the Response of a Simple Structure to Single Axis and Multiple Axis Random Vibration Inputs
Comparison of the Response of a Simple Structure to Single Axis and Multiple Axis Random Vibration Inputs Dan Gregory Sandia National Laboratories Albuquerque NM 87185 (505) 844-9743 Fernando Bitsie Sandia
Elements Elements describe the essential outcomes. 1. Prepare to diagnose and repair air conditioning and HVAC system
AURETU004 Application Competency Field Unit Sector Elements Elements describe the essential outcomes. 1. Prepare to diagnose and repair air conditioning and HVAC system 2. Diagnose air conditioning and
Herschel PACS Test Procedure STM PACS-KT-PR-011 Issue: 1 Revision: -
CASE GmbH Westendstrasse 125 80339 München Herschel PACS Test Procedure STM 1 Revision: - i Document Approval Sheet Title: Herschel PACS Subtitle: Test Procedure STM Doc. No: 1 Revision: - Prepared:......
Topology Optimization of Engine Mount Brackets Dr. Dirk Sprengel Ford Werke GmbH
Topology Optimization of Engine Mount Brackets Dr. Dirk Sprengel Ford Werke GmbH Dr. D. Sprengel 6/2007 Topology Optimization of EMS Bracket 1 ( 21 ) EMS Bracket Funktion EMS: Engine Mount System Link
HVAC-02, Air Conditioning Troubleshooting and Repair
HVAC-02, Air Conditioning Troubleshooting and Introduction Since I'm constantly receiving questions on 944 air conditioning systems, I figured it's time to come up with come helpful troubleshooting tips.
Numerical Analysis of Independent Wire Strand Core (IWSC) Wire Rope
Numerical Analysis of Independent Wire Strand Core (IWSC) Wire Rope Rakesh Sidharthan 1 Gnanavel B K 2 Assistant professor Mechanical, Department Professor, Mechanical Department, Gojan engineering college,
Flushing and Cleaning the A/C System
Flushing and Cleaning the A/C System Once an AC system has been contaminated or has suffered a failure, the most important part of the AC service to restore the cooling performance to the system = FLUSHING
Elements Elements describe the essential outcomes.
Application Competency Field Unit Sector Elements Elements describe the essential outcomes. This unit describes the performance outcomes required to service air conditioning systems, including heating,
THE COMPOSITE DISC - A NEW JOINT FOR HIGH POWER DRIVESHAFTS
THE COMPOSITE DISC - A NEW JOINT FOR HIGH POWER DRIVESHAFTS Dr Andrew Pollard Principal Engineer GKN Technology UK INTRODUCTION There is a wide choice of flexible couplings for power transmission applications,
Cylinder Head Gasket Contact Pressure Simulation for a Hermetic Compressor
Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2006 Cylinder Head Gasket Contact Pressure Simulation for a Hermetic Compressor Pavan P.
Elements Elements describe the essential outcomes. 1. Prepare to dismantle air conditioning compressor
Application Competency Field Unit Sector Elements Elements describe the essential outcomes. 1. Prepare to dismantle air conditioning compressor 2. Dismantle and evaluate compressor and This unit describes
GMC 2013: Piping Misalignment and Vibration Related Fatigue Failures
GMC 2013: Piping Misalignment and Vibration Related Fatigue Failures www.betamachinery.com Authors/Presenters: Gary Maxwell, General Manager, BETA Machinery Analysis Brian Howes, Chief Engineer, BETA Machinery
Air Conditioning 101. STN Presentation AC101
Air Conditioning 101 What is Refrigeration? Refrigeration is Cooling by the Removal of Heat Heat is Measured In BTU s A BTU is a British Thermal Unit It is the Amount of Heat to Raise One Pound of Water,
Overview. also give you an idea of ANSYS capabilities. In this chapter, we will define Finite Element Analysis and. Topics covered: B.
2. FEA and ANSYS FEA and ANSYS Overview In this chapter, we will define Finite Element Analysis and also give you an idea of ANSYS capabilities. Topics covered: A. What is FEA? B. About ANSYS FEA and ANSYS
DESIGN OF AIR CONDITIONING SYSTEM IN AUTOMOBILE
DESIGN OF AIR CONDITIONING SYSTEM IN AUTOMOBILE Md Shahid Imam, Dr.M.Shameer Basha, Dr.Md.Azizuddin, Dr. K.Vijaya Kumar Reddy 4 M.Tech HVAC II Yr, Royal Institute of Technology & Science Chevella R.R Dist
Managing The Integrity Threat Of Subsea Pipework Fatigue Failure. John Hill Senior Consultant Xodus Group
Managing The Integrity Threat Of Subsea Pipework Fatigue Failure John Hill Senior Consultant Xodus Group Contents > Vibration-induced fatigue as an integrity issue subsea > Fatigue assessment of subsea
Time Domain and Frequency Domain Techniques For Multi Shaker Time Waveform Replication
Time Domain and Frequency Domain Techniques For Multi Shaker Time Waveform Replication Thomas Reilly Data Physics Corporation 1741 Technology Drive, Suite 260 San Jose, CA 95110 (408) 216-8440 This paper
Systematic Optimisation of Gearboxes for Hybrid and Electric Vehicles in Terms of Efficiency, NVH and Durability
Systematic Optimisation of Gearboxes for Hybrid and Electric Vehicles in Terms of Efficiency, NVH and Durability Dr. Artur Grunwald GKN Driveline 1 Content of presentation Scope and introduction Gearbox
Chapter 3.5: Fans and Blowers
Part I: Objective type questions and answers Chapter 3.5: Fans and Blowers 1. The parameter used by ASME to define fans, blowers and compressors is a) Fan ration b) Specific ratio c) Blade ratio d) Twist
Elements Elements describe the essential outcomes.
AURETU005 Application Competency Field Unit Sector Elements Elements describe the essential outcomes. Retrofit and modify air conditioning and HVAC systems This unit describes the performance outcomes
01-3 6820-11 6820-11 AIR CONDITIONER GENERAL 1. SPECIFICATIONS AIR CONDITIONER REXTON 2010.01
682011 013 GENERAL 1. SPECIFICATIONS 682011 014 682011 2. REPAIR INSTRUCTIONS 1) Precautions for Working with R134a R12 refrigerant and R134a refrigerant are not compatible. These refrigerants must never
Troubleshooting HVAC/R systems using refrigerant superheat and subcooling
Troubleshooting HVAC/R systems using refrigerant superheat and subcooling Application Note Troubleshooting and servicing refrigeration and air conditioning systems can be a challenging process for both
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
Shock and Vibration Testing
Shock and Vibration Testing Agenda Shock Testing Comparison and Selection of Methods Comparison of Specs Rationale for Selection of Testing Vibration Testing Comparison and Selection of Methods Comparison
The Piping System Model a New Life Cycle Document. Elements of the Piping System Model
Piping System Model as a Life Cycle Document White Paper Introduction When designing piping systems, a variety of documents are created providing the details necessary to design, purchase, build, and test
A Comparison of Analytical and Finite Element Solutions for Laminar Flow Conditions Near Gaussian Constrictions
A Comparison of Analytical and Finite Element Solutions for Laminar Flow Conditions Near Gaussian Constrictions by Laura Noelle Race An Engineering Project Submitted to the Graduate Faculty of Rensselaer
Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications
Simulation Analysis Optimisation. Computer Aided Engineering
Simulation Analysis Optimisation Computer Aided Engineering Computer Aided Engineering Simulation Analysis Optimisation Simulation Analysis Optimisation Increasing demands on new products in terms of functionality,
ASE 7 - Heating, Ventilation, and Air Conditioning. Module 8 Diagnosis, Testing & Repair
ASE 7 - Heating, Ventilation, and Air Conditioning Module 8 Acknowledgements General Motors, the IAGMASEP Association Board of Directors, and Raytheon Professional Services, GM's training partner for GM's
Chapter 2 P-H Diagram Refrigeration Cycle Analysis & Refrigerant Flow Diagram
Chapter 2 P-H Diagram Refrigeration Cycle Analysis & Refrigerant Flow Diagram Copy Right By: Thomas T.S. Wan 温 到 祥 著 Sept. 3, 2008 All rights reserved Industrial refrigeration system design starts from
ON-VEHICLE INSPECTION
Sight Glass I11244 ONVEHICLE INSPECTION 1. INSPECT REFRIGERANT VOLUME Observe the sight glass on the liquid tube. AC3 AC22F05 Test conditions: Running engine at 1,500 rpm Blower speed control switch: HI
INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES. Interpretations of the FTP
INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES Interpretations of the FTP CONTENTS FTP1 Adhesives used in A or B class divisions (FTP Code 3.1, Res A.754 para. 3.2.3) June 2000 FTP2 Pipe and duct
POLICY BULLETIN Tecumseh Compressor Company Compressor Group
to Bulk Milk Coolers and Other System Page 1 of 5 Overall reliability can be enhanced if there exists a complete understanding of the features, system design, installation requirements, processing, charging
OUTPUT-ONLY MODAL ANALYSIS FOR A 50 YEARS OLD CONCRETE BRIDGE
OUTPUT-ONLY MODAL ANALYSIS FOR A 50 YEARS OLD CONCRETE BRIDGE Tiago Albino a, Cláudio José Martins a, Tiago A. Soares b, and Alberto Ortigão b a Federal Centre for Technological Education of Minas Gerais,
UN Manual of Tests and Criteria, Sub-section 38.3, Amendments to the 5 th edition, effective 2014 January 1 st
1 UN Manual of Tests and Criteria, Sub-section 38.3, Amendments to the 5 th edition, effective 2014 January 1 st 38.3 Lithium metal and lithium ion batteries 38.3.1 Purpose This section presents the procedures
ELECTRON SPIN RESONANCE Last Revised: July 2007
QUESTION TO BE INVESTIGATED ELECTRON SPIN RESONANCE Last Revised: July 2007 How can we measure the Landé g factor for the free electron in DPPH as predicted by quantum mechanics? INTRODUCTION Electron
2004 Standard For Performance Rating Of Positive Displacement Refrigerant Compressors And Compressor Units
2004 Standard For Performance Rating Of Positive Displacement Refrigerant Compressors And Compressor Units ANSI/AHRI Standard 540 (formerly ARI Standard 540) IMPORTANT SAFETY RECOMMENDATIONS ARI does not
Unit 3: States of Matter Practice Exam
Page 1 Unit 3: States of Matter Practice Exam Multiple Choice. Identify the choice that best completes the statement or answers the question. 1. Two gases with unequal masses are injected into opposite
specializing in AIR CONDITIONING, PARTS AND SYSTEMS for your classic vehicle PERFECT FIT IN-DASH HEAT/ COOL/ DEFROST 1967-72 CHEVROLET PICKUP
specializing in AIR CONDITIONING, PARTS AND SYSTEMS for your classic vehicle PERFECT FIT IN-DASH HEAT/ COOL/ DEFROST 1967-72 CHEVROLET PICKUP CONTROL & OPERATING INSTRUCTIONS The controls on your new Perfect
Engineering Recommendation on: Accumulators Revised 6-17-99 Issued January 10, 1979 Page 1 of 7
Issued January 10, 1979 Page 1 of 7 Accumulators have long been recognized by the industry as an effective means of maintaining good system balance by storing excess refrigerant as the condenser or evaporator
Development of High Stability Supports for NSLS-II RF BPMS
BNL-82316-2009-CP Development of High Stability Supports for NSLS-II RF BPMS B. Kosciuk, R. Alforque, B. Bacha, P. Cameron, F. Lincoln, V. Ravindranath, I. Pinayev, S. Sharma, O. Singh Brookhaven National
DfRSoft 2-Day Course Shock & Vibration: Test, Design, and Design Assurance
DfRSoft 2-Day Course Shock & Vibration: Test, Design, and Design Assurance Understanding of vibration and shock stresses is important for the design of reliable products for diverse applications, ranging
TECHNICAL BULLETIN SEPTEMBER 2015 COLD, HARD FACTS ON A/C REPAIR
TECHNICAL BULLETIN SEPTEMBER 2015 This article was written by Tim Sramcik, contributing editor of Auto Body Repair Network Magazine (ABRN). It was published in the April 2015 edition. COLD, HARD FACTS
The elements used in commercial codes can be classified in two basic categories:
CHAPTER 3 Truss Element 3.1 Introduction The single most important concept in understanding FEA, is the basic understanding of various finite elements that we employ in an analysis. Elements are used for
Fatigue Analysis of an Inline Skate Axel
FATIGUE ANALYSIS OF AN INLINE SKATE AXEL 57 Fatigue Analysis of an Inline Skate Axel Authors: Faculty Sponsor: Department: Garrett Hansen, Mike Woizeschke Dr. Shanzhong (Shawn) Duan Mechanical Engineering
PUMPED Nd:YAG LASER. Last Revision: August 21, 2007
PUMPED Nd:YAG LASER Last Revision: August 21, 2007 QUESTION TO BE INVESTIGATED: How can an efficient atomic transition laser be constructed and characterized? INTRODUCTION: This lab exercise will allow
MAXIMUM HEAT LOAD TEMPERATURE TESTING ( Differential Temperature Testing )
MAXIMUM HEAT LOAD TEMPERATURE TESTING ( Differential Temperature Testing ) The Concept Maximum Heat Load Temperature Testing is a powerful air-conditioning diagnostic and evaluation technique. It is also
Application Engineering
Application Engineering February 2012 Digital Capacity Control for Copeland Scroll Refrigeration Compressors INDEX Page 1. Introduction... 1 2. Theory of Operation... 1 3. Nomenclature... 1 4. Digital
Open Cycle Refrigeration System
Chapter 9 Open Cycle Refrigeration System Copy Right By: Thomas T.S. Wan 温 到 祥 著 Sept. 3, 2008 All rights reserved An open cycle refrigeration system is that the system is without a traditional evaporator.
Low GWP Replacements for R404A in Commercial Refrigeration Applications
Low GWP Replacements for R404A in Commercial Refrigeration Applications Samuel YANA MOTTA, Mark SPATZ Honeywell International, 20 Peabody Street, Buffalo, NY 14210, [email protected] Abstract
Fluid structure interaction of a vibrating circular plate in a bounded fluid volume: simulation and experiment
Fluid Structure Interaction VI 3 Fluid structure interaction of a vibrating circular plate in a bounded fluid volume: simulation and experiment J. Hengstler & J. Dual Department of Mechanical and Process
ALLDATA Online - 2006 Dodge Truck RAM 2500 Truck 2WD L6-5.9L DSL Turbo VI... Service and Repair
Page 1 of 15 Home Account Contact ALLDATA Log Out Help PAUL REDEHOFT Select Vehicle New TSBs Technician's Reference Component Search: OK 2006 Dodge Truck RAM 2500 Truck 2WD L6-5.9L DSL Turbo VIN C Conversion
export compressor instability detection using system 1* and proficy** smartsignal software
BP MAGNUS PLATFORM export compressor instability detection using system 1* and proficy** smartsignal software part 1 58 ORBIT Vol.32 No.3 Jul.2012 THIS CASE STUDY DESCRIBES AN EXAMPLE OF A GAS COMPRESSOR
1.3 Turbochargers are categorised in three groups depending on served power by cylinder groups with:
(Feb 2015) Turbochargers 1. Scope 1.1 These requirements are applicable for s with regard to design approval, type testing and certification and their matching on engines. Turbochargers are to be type
Centrifugal Water Chillers. Scott Meyerkord
Centrifugal Water Chillers Scott Meyerkord Trane Account Manager Chilled Water System absorption centrifugal helical-rotary Centrifugal Water Chillers Centrifugal Water Chillers Components components of
The Calculation of G rms
The Calculation of G rms QualMark Corp. Neill Doertenbach The metric of G rms is typically used to specify and compare the energy in repetitive shock vibration systems. However, the method of arriving
AN EXPLANATION OF JOINT DIAGRAMS
AN EXPLANATION OF JOINT DIAGRAMS When bolted joints are subjected to external tensile loads, what forces and elastic deformation really exist? The majority of engineers in both the fastener manufacturing
Refrigeration Basics 101. By: Eric Nelson
Refrigeration Basics 101 By: Eric Nelson Basics Refrigeration is the removal of heat from a material or space, so that it s temperature is lower than that of it s surroundings. When refrigerant absorbs
Vibration and Shock tests on a typical Current Transformer Set
Vibration and Shock tests on a typical Current Transformer Set FR409P11 Mastering Electricity www.eleq.com Nationaal Lucht- en Ruimtevaartlaboratorium National Aerospace Laboratory NLR NLR-CR-2009-412
Safakcan Tuncdemir 1, William M. Bradley *2. 1. Introduction
Modeling and Experimental Verification of the Power Transfer and Thermal Characteristics of Piezoelectric Transformers Subjected to Combined Mechanical and Electrical Loading Safakcan Tuncdemir 1, William
Ultrasound Condition Monitoring
Ultrasound Condition Monitoring Whitepaper Alan Bandes UE Systems, Inc. Abstract: Instruments based on airborne/structure borne ultrasound technology offer many opportunities for reducing energy waste
Investigation of Stress Intensity Factor of Axial Compressor Blade of Helicopter
Investigation of Stress Intensity Factor of Axial Compressor Blade of Helicopter Neelesh V K Mr. Manjunath M V Mr. Devaraj Dept. of Mechanical Engineering Asst prof, Dept. of Mechanical Engineering Asst
Subminiature Load Cell Model 8417
w Technical Product Information Subminiature Load Cell 1. Introduction... 2 2. Preparing for use... 2 2.1 Unpacking... 2 2.2 Using the instrument for the first time... 2 2.3 Grounding and potential connection...
Heat Recovery In Retail Refrigeration
This article was published in ASHRAE Journal, February 2010. Copyright 2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not
Simulation in design of high performance machine tools
P. Wagner, Gebr. HELLER Maschinenfabrik GmbH 1. Introduktion Machine tools have been constructed and used for industrial applications for more than 100 years. Today, almost 100 large-sized companies and
Contents and Nomenclature
DX Coils Contents and Nomenclature Nomenclature... 1 Evaporator Coil Types EN... 2 EF... 2 ER... 2 EJ... 3 EK... 3 Evaporator Construction Connections... 4 Tubing... 4 Headers... 5 Tube Supports... 5 Coil
Pressure sensors for automotive HVAC systems
Pressure sensors for automotive HVAC systems Tom Kwa, PhD CTO DunAn Sensing LLC Automotive Sensor and Electronics Expo 20-21 May 2015 Detroit, Michigan 1 Outline The need for automotive A/C and the need
COURSE OUTLINE. Course Title Automotive Air Conditioning. Co- or Pre-requisite AUT 110, AUT 111
COURSE OUTLINE Course Number AUT 212 Course Title Automotive Air Conditioning Credits 3 Hours: lecture/lab/other 2 2 Co- or Pre-requisite AUT 110, AUT 111 Implementation Summer 2015 Catalog description
AE21-1319 R6 December 2013. Digital Capacity Control for Copeland Scroll Refrigeration Compressors AE21-1319 R6
AE21-1319 R6 December 2013 Digital Capacity Control for Copeland Scroll Refrigeration Compressors TABLE OF CONTENTS Section Page Section Page Safety Safety Instructions...2 Safety Icon Explanation...2
How Ground/Water Source Heat Pumps Work
How Ground/Water Source s Work Steve Kavanaugh, Professor Emeritus of Mechanical Engineering, University of Alabama Ground Source s (a.k.a. Geothermal s) are becoming more common as the costs of energy
SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS
SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating
Subject: 2005 Air Conditioning Service Guidelines
Date: June 27, 2005 Bulletin Number: 05D-J-114 To: DDG Headquarters and Branches and Jobbers Category: Service From: Steve Sigg, Product Service and Training Line(s): 10 and 15 Subject: 2005 Air Conditioning
TRANSPORT OF DANGEROUS GOODS
Recommendations on the TRANSPORT OF DANGEROUS GOODS Manual of Tests and Criteria Fifth revised edition Amendment 1 UNITED NATIONS SECTION 38 38.3 Amend to read as follows: "38.3 Lithium metal and lithium
Precision Miniature Load Cell. Models 8431, 8432 with Overload Protection
w Technical Product Information Precision Miniature Load Cell with Overload Protection 1. Introduction The load cells in the model 8431 and 8432 series are primarily designed for the measurement of force
Engineering & Testing Services. Hydraulic Fitting Design and Hydro-Mechanical Testing
Engineering & Testing Services Hydraulic Fitting Design and Hydro-Mechanical Testing Aerofit, Inc. APT Laboratory 1425 South Acacia Avenue Fullerton, CA 92831 Main: 714-521-5060 Fax: 714-535-9862 Our Company
APPLICATION OF TOPOLOGY, SIZING AND SHAPE OPTIMIZATION METHODS TO OPTIMAL DESIGN OF AIRCRAFT COMPONENTS
APPLICATION OF TOPOLOGY, SIZING AND SHAPE OPTIMIZATION METHODS TO OPTIMAL DESIGN OF AIRCRAFT COMPONENTS Lars Krog, Alastair Tucker and Gerrit Rollema Airbus UK Ltd Advanced Numerical Simulations Department
INSTALL INSTRUCTIONS KK-C-HVAC-1 HVAC UNIT 2003-2014 CHEVROLET/GMC VANS FOR
INSTALL INSTRUCTIONS KK-C-HVAC-1 HVAC UNIT 2003-2014 CHEVROLET/GMC VANS FOR (For NEW 2007 ALL WHITE KWIK-KITS ONLY) Warning do not attempt to install A/C units unless you are experienced with servicing
AABC Specifications for Testing and Balancing HVAC Systems
AABC Specifications for Testing and Balancing HVAC Systems The Associated Air Balance Council (AABC) Total System Balancing Specifications for HVAC Testing, Balancing and Performance Verification TOTAL
D Youville College July 31, 2008 New Academic Building Cannon Design Project No. 002935.00
SECTION 22 6119 - COMPRESSED-AIR EQUIPMENT FOR LABORATORY AND HEALTHCARE PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged, oilless scroll air compressors. 1.2 DEFINITIONS A. Actual Air: Air
Skills Canada National Competition Instructions and Competition Details 38 Refrigeration and Air Conditioning / Post - Secondary May 27-30, 2015 -
Skills Canada National Competition Instructions and Competition Details / Post - Secondary May 27-30, 2015 - Saskatoon 1. Test Project Details This project is designed to test the range of skills used
JEDEC STANDARD. Vibration, Variable Frequency. JESD22-B103B (Revision of JESD22-B103-A) JEDEC SOLID STATE TECHNOLOGY ASSOCIATION
JEDEC STANDARD Vibration, Variable Frequency JESD22-B103B (Revision of JESD22-B103-A) JUNE 2002, Reaffirmed: June 2006 JEDEC SOLID STATE TECHNOLOGY ASSOCIATION NOTICE JEDEC standards and publications contain
Heating and Air Conditioning
Heating and Air Conditioning S Y L L A B U S Your Course Learning Plan UAWLETC EK 4-13-06 A. General Course Information Course description: The Heating and Air Conditioning students of UAW-LETC will successfully
Application Note Noise Frequently Asked Questions
: What is? is a random signal inherent in all physical components. It directly limits the detection and processing of all information. The common form of noise is white Gaussian due to the many random
Any Service Technician Can Fix It A Good Service Technician Can Figure Out What s Wrong With It.
I Dave s Statement If the thermostat calls for cooling, and the furnace fan is running properly, and the coil airflow is adequate, and the condenser fan is running properly, and the condenser airflow is
Fatigue Life Estimates Using Goodman Diagrams
Fatigue Life Estimates Using Goodman Diagrams by Robert Stone The purpose of this paper is to review the proper methods by which spring manufacturers should estimate the fatigue life of a helical compression
ASE 133 AUTO HVAC SYSTEMS
ASE 133 AUTO HVAC SYSTEMS PRESENTED AND APPROVED: DECEMBER 7, 2012 EFFECTIVE: FALL 2013-14 Prefix & Number ASE 133 Course : Auto HVAC Systems Purpose of this submission: New Change/Updated Retire If this
Test Code: 8297 / Version 1
Blueprint HVAC Maintenance Technology PA Test Code: 8297 / Version 1 Copyright 2014. All Rights Reserved. General Assessment Information HVAC Maintenance Technology PA Blueprint Contents General Assessment