(BIM) Guidelines version 1.6
|
|
|
- Ashley Gray
- 9 years ago
- Views:
Transcription
1 Table of Contents University of Southern California Building Information Modeling (BIM) Guidelines Building Information Modeling (BIM) Guidelines version 1.6 For Design Bid Build Contracts USC Capital Construction Development and Facilities Management Services 1 Introduction STATEMENT OF PURPOSE BUILDING INFORMATION MODEL KEY INGREDIENTS FOR SUCCESS 5 2 USC Responsibilities 6 3 Deliverables BIM EXECUTION PLAN MODEL AND DATA DELIVERY 7 4 DESIGN TEAM BIM Process and Modeling Requirements BIM AUTHORING SOFTWARE GEO REFERENCED MODEL PROJECT COLLABORATION SERVER DESIGN BIM FACILITATOR MODEL QUALITY AND LEVEL OF DETAIL: ARCHITECTURAL AND MEPF AUDIO VISUAL AND OTHER SPECIALTY DESIGN DISCIPLINES 9 FINAL DRAFT_ April 18, 2012
2 Table of Contents 1 Introduction STATEMENT OF PURPOSE BUILDING INFORMATION MODEL KEY INGREDIENTS FOR SUCCESS 5 2 USC Responsibilities 6 3 Deliverables BIM EXECUTION PLAN MODEL AND DATA DELIVERY 7 4 Design Team: BIM Process and Modeling Requirements BIM AUTHORING SOFTWARE GEO REFERENCED MODEL PROJECT COLLABORATION SERVER DESIGN BIM FACILITATOR MODEL QUALITY AND LEVEL OF DETAIL: ARCHITECTURAL AND MEPF AUDIO VISUAL AND OTHER SPECIALTY DESIGN DISCIPLINES COBie 10 5 MEPF Specifications SHARED PARAMETERS WORKSETS ISOLATABLE SYSTEMS AND ZONES BUILDING LINE 11 6 Design Phases DELIVERABLE SCHEDULE AND MILESTONES SCHEMATIC DESIGN PHASE General Model Content 13 a. Civil Surface and Utilities 13 b. Architectural & MEP Level of Detail Program and Space Validation COBie Design Data Initial Collision Report and Constructability DESIGN DEVELOPMENT PHASE General Model Content Level of Detail 15 2 Version 1.6_April 18, 2012
3 6.3.4 COBie Design Data Collision Detection and Constructability CONSTRUCTION DOCUMENTS PHASE General Model Content Level of Detail Program and Space Validation Other Analysis and Checking Tools COBie Design Data Collision Detection and Constructability BIDDING PHASE Archiving of Design BIMs Bid Deliverable BIM Execution Plan Co-location Design Model Updates Model Mash Ups 18 7 Construction Team: BIM Process and Modeling Requirements BIM EXECUTION PLAN FEEDBACK AND REVISIONS CONSTRUCTION BIM FACILITATOR COBie DATA EXTRACTING INFORMATION FROM THE DESIGN MODEL CONSTRUCTION MODEL UPDATES TRADE COORDINATION Kick off Meeting Suggested Coordination Process Installation Requirements for 3D Models, Formats and Model Structure 20 APPENDIX A: MODEL ELEMENTS AND LEVEL OF DETAIL FOR MODELS 24 DESIGN DEVELOPMENT AND CONSTRUCTION DOCUMENTS 24 CONSTRUCTION COORDINATION 24 APPENDIX B: BIM DATA ACQUISITION GUIDELINES FOR FACILITIES MANAGEMENT 30 APPENDIX C: NOMENCLATURE 34 APPENDIX D: INSTALLATION CHANGE LOG 38 3 Version 1.6_April 18, 2012
4 APPENDIX E: REVIT MODEL REQUIREMENTS 39 APPENDIX F: COLLISION DETECTION 40 APPENDIX G: USC FMS OUTLINE SCHEDULE DATA SPECIFICATIONS 41 APPENDIX H: ECODOMUS 51 APPENDIX I: BIM EXECUTION PLAN TEMPLATE 54 GLOSSARY 64 REFERENCES/ACKNOWLEDGEMENTS 66 4 Version 1.6_April 18, 2012
5 1. Introduction This document defines the Design and Construction scope of work and deliverables for using Building Information Modeling (BIM) on new USC construction projects, major renovations and other projects as required by USC, based on a Design Bid Build form of Contract. 1.1 STATEMENT OF PURPOSE If used effectively, BIM provides opportunities to vastly improve upon traditional methods of design and construction coordination thereby reducing the potential for costly change orders, providing multiple opportunities for Owner review and participation by means of 3D visualization of the project and specialty spaces, and reducing design and construction schedules. In addition, BIM creates opportunities for reusing data for multiple purposes, including the operation and maintenance of USC s facilities. To achieve these ends, the BIM must be structured to achieve the required purposes. This document describes USC s requirements for the production and use of Building Information Models (BIM) in the design, construction and maintenance of its facilities. 1.2 BUILDING INFORMATION MODEL Building Information Model (BIM) is a parametric, computable representation of the project design developed by the Designer and their consultants, the Contractor, and their subcontractors, including construction details developed by the Contractor and its respective consultants and subcontractors that are integrated into the model. As used in this BIM Specification, references to Building Information Model, BIM, or the Model, include the primary design model or models and all linked, related, affiliated or subsidiary models developed for design, analysis, estimating, detailing, fabrication, construction, operation or maintenance of the project, or any portion or element of the project, whether the model is prepared by the Designers, the Contractor or prepared by the Contractor s subcontractors or consultants. 1.3 KEY INGREDIENTS FOR SUCCESS There are several factors that will affect the successful outcome of a BIM based project: a. Establishing a collaborative environment and a collaborative use of the BIMs during the design and construction process where the Designers, Contractor, subcontractors and Owner work together with a proactive approach to issue resolution. Under the most collaborative of environments, the number of RFI s generated can be significantly reduced as the team resolves many issues in face to face or webbased meetings. b. Leveraging the BIMs to the fullest extent possible to shorten the construction schedule and reduce construction costs. This would include reviewing the BIMs with users and Facilities Management Services (FMS) personnel to ensure that all key personnel understand what the final product will look like and that accesses and clearances meet their expectations. The fewer surprises, the less likely there will be change orders down the line. c. Ensuring that the I in BIM is fully represented in the data provided by the Building Information Models and that the data delivered is COBie compliant. 5 Version 1.6_April 18, 2012
6 2. USC Responsibilities Throughout the processes defined below, various USC departments will be reviewing the BIMs and verifying that the model content is accurate and up to date. These departments and their involvement as it pertains to the BIMs are as follows: USC CAPITAL CONSTRUCTION AND DEVELOPMENT USC REAL ESTATE AND ASSET MANAGEMENT USC FACILITIES MANAGEMENT SERVICES (FMS): Defines the FM model and data requirements (Appendix A and B). Reviews access and clearances to mechanical equipment and object naming conventions. In conjunction with the BIM Manager and/or BIM Facilitator, verifies that the systems and zones are defined appropriately. THIRD PARTY COMMISSIONING AGENT: To be identified in the bid documents. USC CAPITAL CONSTRUCTION PROJECT MANAGER: Coordinates BIM reviews with various departments. Inserts initial project information in BIM Execution Plan. Insures that the BIM Project Execution Plan is adhered to for the duration of the project. Facilitates access to e Builder, USC s PMIS and project collaboration server. USC INFORMATION TECHNOLOGY SERVICES: Defines IT data and model requirements. USER GROUPS: Review of BIM for layout, access, etc. USC BIM CONSULTANT/FACILITATOR Provides model mash ups for all MEPF trades in Navisworks (see illustration on page 20). The mash ups are overlays of the final as constructed fabrication models (provided by the subcontractors) with the 100% CD MEPF design models. This provides the Designers with a visual comparison of the two model types design vs. fabrication to assist them in making any required adjustments to their design model to match the as constructed condition. In conjunction with USC FMS, will validate design models and subcontractor submittals for COBie compliance periodically and provide feedback for corrections. 6 Version 1.6_April 18, 2012
7 3. Deliverables 3.1 BIM EXECUTION PLAN As part of their respective proposals/bid submittals, the Architect and the General Contractor must submit a BIM Execution Plan (BEP) describing processes and procedures in place within their organizations used to coordinate and deliver the BIM s and associated data according to the guidelines contained herein. See Appendix H for the BIM Execution Plan template to be used. USC will evaluate the BEP s and provide feedback to the successful bidder at the time of contract award, after which the Contractor will have 2 weeks to make changes to the BEP and resubmit. 3.2 MODEL AND DATA DELIVERY The final delivery of the BIM and associated data to USC will be in the form of: a. Fully coordinated architectural, structural, civil and MEP 3D models in Revit at 100% CD by the Design Team. b. All equipment schedules must be generated from the parameters embedded in the Revit model objects. c. As constructed native format MEPF and structural models provided by the General Contractor. d. Complete as constructed Revit models provided by the Designers conforming to USC FMS requirements as detailed in Appendix B.* e. The following COBie 2.4 standard worksheets*, submitted by the General Contractor, with particular emphasis on the MEPF systems, shall be provided (at minimum) to meet the long term Facilities Management Goals: Contact (all fields) Facility (all fields) Floor (all fields) Space (all fields) Zone (all fields) Type (all fields) Component (all fields) System (all fields) Spare (all fields) Resource (all fields) Job (all fields) Document for those documents that are assignable to an associated BIM element or system (all fields, installed equipment documentation, Approval By= Contractor Certified, Stage= As Built ) All documents will be placed in the assigned location on e Builder. Attribute (all fields, manufacturer provided attributes, Category= As Built ) *The COBie spreadsheet and information on how to use COBie may be found at Additional resources can be found in the sub folder named BIM Guidelines Reference Docs in the General Documentation folder in e Builder. e Builder is USC s Project Management Information System. Access to e Builder will be granted through USC s Project Manager. f. A narrative describing the software used to create the BIMs including the software publisher, software name and version number. 7 Version 1.6_April 18, 2012
8 8 Version 1.6_April 18, 2012
9 4. Design Team: BIM Process and Modeling Requirements 4.1 BIM AUTHORING SOFTWARE The Architects and MEPF Designers must model their systems in Revit. The Civil Engineer and the Structural Engineer may opt to use alternative software such as Civil 3D and Tekla. The version number of any software to be used including collaboration software (e.g. Revit, Tekla, Navisworks, etc.) must be announced at the start of the project and must be maintained throughout project close out unless the team as a whole agrees to upgrade to a newer version. 4.2 GEO REFERENCED MODEL The Architects will set the spatial coordinates at the beginning of the project. The coordinates will be accurately geo referenced to a permanent campus monument. This will be coordinated between the Civil Engineer, the Architects and USC. It is the Architects responsibility to verify the accuracy of the coordinates and to provide a grid intersection at 0,0 for all other team members. 4.3 PROJECT COLLABORATION SERVER The Design and Construction team is required to use USC s PMIS server, e Builder for all project related documentation, including all BIMs. Each project contains a BIM folder (see illustration below). The BIM folder is strictly dedicated to 3D coordination models and files (such as REvit, Naviworks NWD s, NWC s, DWGs, etc.). Access to e Builder will be provided by USC. Models will be accessible to all parties in both their native formats and in dwg and/or NWD/NWC/IFC formats (as requested). They will be posted to e Builder on a regular basis as they get updated and/or modified. XXX Building Partial sample project page in e Builder 4.4 DESIGN BIM FACILITATOR The Design Consultant must have a dedicated full time BIM Facilitator/BIM Engineer. Facilitator responsibilities include: Design BIM a. Ensuring that all members of their Design Team are delivering and updating the BIM s according to schedule. 9 Version 1.6_April 18, 2012
10 b. Ensuring that the BIM s get uploaded to the common server on time and in the correct file format(s). c. Ensuring that the submitted BIM s comply with all of the requirements as defined in this document including COBie data requirements. d. Assembling the submitted BIM s into a single consolidated BIM in Navisworks and reviewing the consolidated BIM for coordination and constructability issues. e. Providing design coordination and constructability feedback. f. Facilitating design coordination meetings and e mailing webcast invitations to the meetings at least 1 day prior to meeting.* g. Having a solid working knowledge of Navisworks, Revit, and any other software tools to be used for BIM and model checking. h. Ensuring that BIM s are used appropriately to test design requirements/ criteria. i. Serves as POC for all internal and external BIM s with USC and the General Contractor. j. Ensuring that the model is geospatially located. (see item #6.) k. Ensuring that the common reference point is distributed and used by ALL team members. l. Having a pro active approach to problem solving and ensuring that everyone has what they need when they need it. *Equipment and webcasting software used for the coordination meetings should be checked at least 15 minutes prior to the meeting. 4.5 MODEL QUALITY AND LEVEL OF DETAIL: ARCHITECTURAL AND MEPF a. The Designers will set up the required parameters and fields in Revit to meet the FMS requirements. b. The Architects and MEPF Designers will review the Revit warnings periodically throughout the entire design process and correct any significant modeling issues. See Appendix E for a list of Revit model requirements and Revit warnings to correct. c. All interior walls must be modeled to their correct heights and the corresponding Revit families must represent the entire wall assemble accurately. d. Acoustic tile and hard lid ceilings may be represented as a plane with a thickness representing the total construction thickness. 4.6 AUDIO VISUAL AND OTHER SPECIALTY DESIGN DISCIPLINES The AV system and any other specialty disciplines will be provided in a separate Revit file. All of the same rules apply as for the main design disciplines. 4.7 COBie a. The Design Team shall submit the design data to USC as a COBie compliant Excel file. The COBiecompliant file should be in the current version at the time of the submission (version 2.4 is the current version as of January 2011). EcoDomus may be used to automate the extraction of the COBie data from the Revit models. See APPENDIX H for a description of the verification process using EcoDomus. b. USC, in conjunction with the BIM Consultant, will check the quality of the data against the requirements provided by the Owner and detailed herein. If the requirements are not met, the Design Team shall resubmit the data within two weeks after USC provides a report of inaccurate or missing data. If the second submission does not satisfy USC s requirements the Design Team shall resubmit the data within one week after USC provides a report on found errors. c. The COBie Excel file should contain the fields ExtSystem, ExtObject, ExtIdentifier properly populated for all provided elements in order to establish a relationship between the authoring BIM/CAD or project management software and corresponding elements in the COBie file. 10 Version 1.6_April 18, 2012
11 5. MEPF Specifications 5.1 SHARED PARAMETERS The Designers must submit their Revit templates and shared parameters files with USC FMS for review and approval. See Appendix B: MASTER ATTRIBUTES (page 28) for required parameter fields for ALL MEPF system families. 5.2 NOMENCLATURE Naming conventions for equipment types should be succinct, useful and descriptive. The names provided should allow for easy identification and be easily understood in order to facilitate the operation, repair and maintenance of USC equipment. Appendix C provides nomenclature guidance. 5.3 WORKSETS The MEPF Designers will create separate worksets in Revit for each MEPF trade and corresponding 3D views for each trade. The 3D views will be stored in a separate folder in the project browser designated: 3D for COORDINATION. It is the responsibility of the Designers BIM Facilitator to ensure the correct and necessary visibility of the items in the designated views. At a minimum, the following 3D MEPF views should be created without overlap of associated data: a. Plumbing b. HVAC Wet (i.e. HHW, CHW) c. HVAC Dry (i.e Ducts) d. Mechanical Equipment e. Electrical Power f. Lights (with light source disabled in the light families)* g. Fire Sprinkler h. Methane (if applicable) *The purpose for disabling the revit family light sources is to remove the glow that appears in Navisworks as an object. Spherical glow when exporting lights to Navisworks from Revit if light source is not disabled. This interferes with clash detection and obstructs views of other elements. 5.4 ISOLATABLE SYSTEMS AND ZONES MEPF systems must be defined within Revit such that each system can be isolated and viewed separately. AREAS The Architectural model must contain areas, such as occupancy or departmental, as required by the program design. ZONES The Mechanical model must contain MEPF zones, such as air circulation zones or others as required by the program. 11 Version 1.6_April 18, 2012
12 5.5 BUILDING LINE The Design Team will create a building line in CAD (approx. 5 from building) up to which all underground utilities should be extended. The defined building line is not arbitrary. The civil utilities will be taken precisely up to that line where they will meet the corresponding building utilities. There should be no overlapping of utilities around the defined building line. 6. Design Phases 6.1 DELIVERABLE SCHEDULE AND MILESTONES (to be completed by the end of each phase) Milestone Contract Award Deliverable Final BIM Execution Plan Schematic Design Phase Architectural Model Civil Model COBie Design Data Contact Facility Floor Space Zone Design Development Architectural Model Civil Model MEPF Model or Models Structural Model COBie Design Data Contact Facility Floor Space Type Component Construction Documents Architectural Model Civil Model MEPF Model or Models Structural Model COBie Design Data Contact Facility Floor Space Zone Type 12 Version 1.6_April 18, 2012
13 Milestone Deliverable Component System Document Attribute 6.2 SCHEMATIC DESIGN PHASE GENERAL The Design Team may use any method to begin the design process but shall be using a BIM authored model(s) by completion of this phase. All information needed to describe the schematic design shall be included in and derived from these models. Deliverables are required as stated in the Deliverable and Milestones schedule MODEL CONTENT a. Civil Surface and Utilities Detailed requirements of what is to be included in surveying deliverables is managed by USC staff in consultation with the Design Team on a project by project basis. Surveys shall be provided in electronic format and minimally include 3D topographic information including paving and retaining walls and all civil utilities. See item #6 on Geo referencing requirements. The Civil Engineer will provide Control Points to be used by the Design Team as a reference for developing the project gridlines and location. The Design Team shall model all existing conditions as needed and the level of information to be included will be determined based upon project needs. The BIM Execution Plan should define the agreed upon scope of the modeling effort. b. Architectural The model geometry shall include: a. The building footprint definition and all exterior walls. b. All interior wall definitions with all rooms modeled individually. c. All fenestration. d. All doors. e. All overhangs, sun shades and roof monitors. f. All floors, with a separate floor finish model element per room LEVEL OF DETAIL (LOD) All elements shall be modeled to AIA standard LOD 100 by the appropriate design disciplines. Clearances and access zones should be modeled on separate layers, one layer per system. LOD 100 Model Content Requirements: Overall building massing indicative of area, height, volume, location and orientation PROGRAM AND SPACE VALIDATION The Design Team shall use the BIM Authoring software or other analysis tools to compare and validate the stated program requirements with the actual design solution. The following shall be developed automatically from the Building Information Model: a. Assignable Areas and Non assignable Areas measured to inside face of wall objects and designated boundaries of areas. b. Gross Area measured to the outside face of wall objects. 13 Version 1.6_April 18, 2012
14 6.2.5 COBie DESIGN DATA The Design Team shall submit the design data to USC in spread sheet format in compliance with the most current version of COBie**. This data set shall include those COBie designer worksheets related to the architectural program. The following COBie Design worksheets shall be provided in the Schematic Design Set: Contact (all fields) Facility Facility(ies) referenced in the file (all fields) Floor Description of vertical levels (all fields) Space Spaces referenced in the project (all fields) Zone (all fields) **Alternatively, EcoDomus software can be used to automate the extraction of the data from the BIM. At later design and construction phases EcoDomus can also be used to link related documents to the BIM objects, for field data entry, and for data quality control. EcoDomus Revit plug in 3D Interface in EcoDomus with all integrated data INITIAL COLLISION REPORT AND CONSTRUCTABILITY The Design Team BIM Facilitator is to assemble all of the models into a single consolidated model and may use automated collision detection software for this phase of the work in addition to performing a visual walk through of the model from various perspectives and cross sections to detect any constructability issues that would not necessarily be detected automatically. If practical, review the consolidated model and corresponding clashes on a floor by floor basis. All disciplines should be clashed against one another and all clearances and access zones should be verified either by clash detection or visual inspection to be clear of any unacceptable obstructions. The intention is to have as error and collision free a model as possible at each submission phase. See Appendix F for suggested methodology for tracking collision and design issues. 6.3 DESIGN DEVELOPMENT PHASE GENERAL The Design Team shall continue developing their BIMs. Parametric links shall be maintained within the models to enable automatic generation of all plans, sections, elevations, custom details and schedules as well as 3D views. Deliverables are required as stated in the Deliverable and Milestones schedule (see item 6.1) MODEL CONTENT See Appendix A for the list of minimum required model elements. 14 Version 1.6_April 18, 2012
15 6.3.3 LEVEL OF DETAIL (LOD) All elements shall be modeled to AIA standard minimum LOD 200 by the appropriate design disciplines. Clearances and access zones should be modeled on separate layers, one layer per system. LOD 200 Model Content Requirements: Model Elements are modeled as generalized systems or assemblies with approximate quantities, size, shape, location and orientation COBie DESIGN DATA The Design Team shall submit the design data in conformance with the most current version of COBie. This data set shall include those COBie designer worksheets related to the architectural program. The Designer shall specifically identify spatial and systems zoning to reflect the space circulation zones and building service zones that are reflected in the design drawings and specifications. The following COBie Design worksheets shall be provided in the Schematic Design Set: Contact (all fields) Facility (all fields) Floor (all fields) Space (all fields) Zone (all fields) Type (Name, CreatedBy, CreatedOn, Category, Description, AssetType, ExtSystem, ExtObject, ExtIdentifier) Component (Name, CreatedBy, CreatedOn, TypeName, Space, Description, ExtSystem, ExtObject, ExtIdentifier) System (all fields) COLLISION DETECTION AND CONSTRUCTABILITY Repeat process described in Appendix F. 6.4 CONSTRUCTION DOCUMENTS PHASE GENERAL The Design Team shall continue development of the models created in the Design Development Phase. Parametric links shall be maintained within the models to enable automatic generation of all plans, sections, elevations, custom details and schedules as well as 3D views. Deliverables are required as stated in the Deliverable and Milestones schedule, item #6.1. See Appendix A for the list of minimum required model elements MODEL CONTENT Refinement of the model content defined in the design development phase. Whatever content was not known at that time should be accurately represented in this phase LEVEL OF DETAIL (LOD) All elements shall be modeled to AIA standard minimum LOD 300 by the appropriate design disciplines. Clearances and access zones should be modeled on separate layers, one layer per system. LOD 300 Model Content Requirements: Model elements are modeled as specific assemblies accurate in terms of quantity, size, shape, location and orientation. 15 Version 1.6_April 18, 2012
16 6.4.4 PROGRAM AND SPACE VALIDATION The Design Team shall use the methodology described in item to reconfirm the program OTHER ANALYSIS AND CHECKING TOOLS The Design Team shall analyze the design using software that interacts with the model in order to refine load calculations, daylighting, natural ventilation, acoustics, code issues and design issues in addition to reviewing and correcting any relevant issues arising out of the Revit warnings in both Revit Architecture and Revit MEP COBie DESIGN DATA The Design Team shall re submit the design data that was developed in the Design Development phase but further refined at this phase, to USC in conformance with the most current version of COBie. Contact (all fields) Facility (all fields) Floor (all fields) Space (all fields) Zone (all fields) Type (Name, Created By, Created On, Category, Description, Asset Type, Ext System, ExtObject, ExtIdentifier) Component (Name, Space, Typename, CreatedBy, CreatedOn, Category, Description, ExtSystem, ExtObject, ExtIdentifier) System (all fields) Document (all fields, submittals and similar documents, ApprovalBy = Information Only, Stage = Requirement )* Attribute (all fields, design intent attributes, Category = Requirement ) *For all required closeout documents, go to: COLLISION DETECTION AND CONSTRUCTABILITY a. The Design Team must provide a clash free design model employing the methodology described in item b. If there are any outstanding unresolved issues, The Design Team must submit a list of these with an explanation of why they could not be resolved. 6.5 BIDDING PHASE ARCHIVING OF DESIGN BIMS At the completion of Construction Documents, the 100% CD design BIMs will be archived in e Builder and designated As Designed BID DELIVERABLE The 100% CD BIMs and associated documentation will be made available to prospective General Contractor s and their subcontractors for bidding purposes. The Design Team BIM Facilitator will provide the General Contractor with access to the BIM files. It will be the responsibility of the General Contractor to distribute models as they deem necessary to bidding subcontractors. It should be noted however, that access to the BIMs is provided for reference, clarification and design intent only and if used for estimating or any other purpose, is done so at the sole risk of the General Contractor and its subcontractors. 16 Version 1.6_April 18, 2012
17 6.5.3 BIM EXECUTION PLAN The General Contractor shall submit a BIM Execution Plan describing processes and procedures in place within their organization to coordinate and deliver the BIM s and associated data according to the guidelines contained herein. See Appendix I for the BEP template to be used CO LOCATION While co location of the design and construction teams during construction is desirable and highly encouraged, USC recognizes that there are often space limitations which preclude this type of interactive engagement. It is imperative, however that all project team members remain pro actively engaged and responsive for the duration of the construction phase. Collaboration procedures shall be detailed in the BIM Execution Plan (Appendix H) DESIGN MODEL UPDATES a. The Design Team will continue to develop and update the design models throughout the entire construction process. For any design changes that have a direct and immediate effect on construction coordination, the Design Team must update and re upload their design models to the project BIM folder in e Builder within 3 work days if there is an ASI, MSI, SSI or any other question that is answered by the Design Team that requires a design change or a change order that affects coordination or that is driven by coordination (such as ceiling elevation changes or a change in the size of a shaft opening). b. The MEP Engineers will not be uploading changes to the MEPF models but will be updating their MEPF design models immediately following the subcontractor sign off of a given floor on a floor by floor basis. Model mash ups (see item below) can be used as a check to ensure that the design model mimics the fabrication models. c. All stakeholders can subscribe to automatic notification when new models are uploaded to e Builder. Select the folder in your project to which you wish to subscribe (i.e. BIM) and click on subscribe in the menu bar. e Builder folder subscription d. The Architects will publish a monthly bulletin summarizing all questions, resolutions and model changes/updates, and all decisions for design or for value engineering that have been made and will post the bulletins to the server as a non editable file along with the updated models. All of the above described bulletin items shall be recorded in the model with labeled bubbles around the affected area with reference to the bulletin item number. e. The Structural Designer will be updating the design model in parallel with the steel fabricator. In some cases, the Designer s structural model may be the only model used throughout. 17 Version 1.6_April 18, 2012
18 6.5.6 MODEL MASH UPS USC will provide model mash ups for all MEPF trades in Navisworks. The mash ups are overlays of the final as constructed fabrication models with the most up to date MEPF design models. This provides the Designers with a visual comparison of the two model types design vs. fabrication to assist them in making any required adjustments to their design model to match the as constructed condition. Model mash ups will be created as each floor s coordination is complete and is signed off by all of the trade subcontractors. Sample mash up of ductwork. Green duct must be adjusted to match as built blue duct. 7. Construction Team: BIM Process and Modeling Requirements 7.1 BIM EXECUTION PLAN FEEDBACK AND REVISIONS USC will provide a marked up version of the General Contractor s BIM Execution plan with any comments or exceptions upon award of the contract. The General Contractor is required to make the appropriate revisions and re submit for final approval one week after receipt of the marked up plan. 7.2 CONSTRUCTION BIM FACILITATOR The General Contractor must have a dedicated full time BIM Facilitator/BIM Engineer on staff with proven at least 3 years of MEPF coordination experience and whose responsibilities include, but are not limited to: a. Ensuring that all of the subcontractors are updating the BIMs according to schedule. b. Ensuring that the BIM s get uploaded to the common server on time and in the correct file format(s). c. Ensuring that the submitted BIMs comply with all of the requirements as defined in this document including COBie data requirements. d. Assembling the submitted BIMs into a single consolidated BIM in Navisworks and reviewing the consolidated BIM for coordination and constructability issues. e. Providing construction coordination and constructability feedback. f. Facilitating construction coordination meetings. g. Having a solid working knowledge of Navisworks, Revit and any other software tools to be used for BIM and model checking. h. Serving as the POC for all internal and external BIM s with USC and the Designers. i. Having pro active approach to problem solving and ensuring that everyone has what they need when they need it.* j. Creating a 3D Grid. 18 Version 1.6_April 18, 2012
19 *This often entails constant reminders to responsible parties (including USC) to make timely decisions or provide information expediently. 7.3 COBie CONSTRUCTION DATA At the appropriate time, determined by the USC Project Manager, the General Contractor will be provided with an EcoDomus license and access to the EcoDomus project site which will contain partially populated COBie data derived from the design models. See Appendix H. The General Contractor will be responsible for updating and adding additional data in EcoDomus as the data becomes available from the subcontractors, including: Contact (all fields) Facility (all fields) Floor (all fields) Space (all fields) Zone (all fields) Type (all fields) Component (all fields) System (all fields) Spare (all fields) Resource (all fields) Job (all fields) Document (all fields, installed equipment documentation, ApprovalBy = Owner Approval, Stage = As Built ) Attribute (all fields, manufacturer provided attributes, Category = As Built ) The Quality of the COBie data will be checked against the requirements provided by the Owner and detailed herein. If the requirements are not met, the General Contractor shall resubmit the data within two weeks after USC provides a report of inaccurate or missing data. If the second submission does not satisfy USC s requirements, the General Contractor shall resubmit the data within one week after USC provides a report on found errors. EcoDomus can be used for COBie compliance checking and data input. EcoDomus will be used by USC for linking all of the associated data in the 3D models to USC s Facility Management and Maintenance systems and it is essential that the required fields and filenaming conventions be followed accurately. The COBie compliant data will be verified and feedback provided by USC in conjunction with USC s BIM Consultant at a minimum at the following construction stages: 75% Substantial Completion Commissioning Complete Project Close Out 7.4 EXTRACTING INFORMATION FROM THE DESIGN MODEL The General Contractor can extract any required 2D background, such as floor plans or reflected ceiling plans from the most current Revit files. It is the General Contractor s responsibility to export the individual trades and systems from Revit in an appropriate file format (.dwg OR.nwc, for example) for the corresponding subcontractors if necessary. 7.5 CONSTRUCTION MODEL UPDATES All subcontractors shall update their models regularly during construction to reflect the accurate as constructed/as installed condition. This shall not be left until the end of the project. The General Contractor s BIM Facilitator will be responsible for ensuring that this process is in place and for verifying compliance. Where installation differs from the coordinated model, a log of adjusted installations will be 19 Version 1.6_April 18, 2012
20 kept detailing what the change was, the reason for the change and confirming that the 3D model has been updated accordingly. See Appendix D for sample log. 7.6 TRADE COORDINATION Kick off Meeting All members of the design and construction team are required to attend the initial BIM kick off meeting in person at a designated USC location. There must be at least one representative from each trade. The General Contractor will provide the details of the meeting date, time and place Suggested Coordination Process The process outlined below describes requirements and provides some guidance for a suggested coordination process. The General Contractor s BIM Execution Plan will confirm the actual intended procedures to be implemented. A BIM folder has been created in e Builder (see illustration on p. 9) for uploading the 3D models produced by the Designers and subcontractors. These models will be accessible to authorized team members for individual coordination purposes on a trade by trade basis. The General Contractor s BIM Facilitator shall be responsible for integrating all of the 3D models into a single consolidated Navisworks NWF and NWD per floor, running clash detection and creating viewpoints of identified issues. The MEPF detailers are required to submit models that are clash free from any structural components that are included in the structural model provided, to the best of their ability. One integrated BIM per floor or zone shall be published in a Navisworks NWD file format and shall include numbered and labeled view sets of clashes and/or other design/constructability issues that the General Contractor uncovers during this process. The individual team members will be responsible for reviewing the saved views one by one prior to the next coordination meeting. To this end, all team members must have at their disposal one copy of Navisworks Manage. Each party can be notified automatically when any file is uploaded if he/she so chooses. For all e mail communications on this project, preface the subject line with the acronym for this project: PROJECTNAMEACRONYM. The General Contractor shall create a 3D grid for incorporation into the Navisworks file. A minimum of one copy of the 3D grid should be placed at each floor level and should be named according to the level that it is placed, e.g. 3D grid_l01. This will provide the viewer with a quick point of reference when navigating through the model. All 3D detailers and associated foremen shall be required to attend regularly scheduled interactive coordination sessions facilitated by the General Contractor s BIM Facilitator. Designers should be available upon request and should expect to attend a number of these sessions as well. During these sessions the coordination team shall review the consolidated model and the saved viewpoints on a floor by floor basis and find solutions to identified issues. Attendance via webcast is an option. The BIM Facilitator shall include in the BIM Execution Plan a description of the methodology to be used for tracking and ensuring the timely resolution of clashes and/or constructability issues. A Clash matrix must be provided by the General Contractor s BIM Facilitator with numbered viewpoints and with a description of the trades that are affected, matching the viewpoint numbers and labels in the associated Navisworks file. This matrix can be used by all parties to identify the agreed upon party(ies) responsible for resolving the clashes and to add personal notes. ALL matrix issues should be resolved by the designated trades responsible at least 24 hrs prior to the following coordination meeting. 20 Version 1.6_April 18, 2012
21 The General Contractor must provide a BIM coordination room in a mutually agreed upon location for regularly scheduled 3D coordination meetings. The BIM Room must be equipped with the following minimum equipment and software specifications: 64 bit operating system on a desktop or laptop Navisworks Manage Document viewing software Projection system that allows for dual display The General Contractor must be vigilant about engaging the design team on a regular basis to review, assess and provide feedback on any design related issues AS THEY ARISE. Shear wall and slab penetration location information must be provided to the Structural Engineer as soon as a set location for said penetrations has been determined as a result of the 3D coordination effort. Initial locations of suggested penetrations can be provided by means of 3D viewpoints saved as jpegs, with dimensional information and grid references (if one or more of the 3D grid intersections can be seen in the view, that is sufficient) and/or in the form of 2D elevations with dimensions and grid references Installation a. Field installation will use some form of optical survey or GPS instruments for hanger inserts at a minimum and for any other installation where practicable. b. It is the General Contractor s responsibility to ensure that all field personnel involved in the installation of MEPF at any level have at least minimal familiarity with the BIM models and understand by visual means what the repercussions are for changing the location of an installed item. c. The General Contractor must have at least one dedicated workstation in the field (or within easy access) with the most current Navisworks files and documentation loaded (updated daily) for the duration of the construction process. This workstation shall be accessible by all field personnel. The Navisworks files shall have saved viewpoints for specific areas based on the planned and scheduled subdivision of work areas Requirements for 3D models, Formats and Model Structures a. FILE FORMAT: All files should be exported to 3D DWG or Navisworks NWC or NWD format. Revit has a Navisworks plug in for direct export to NWC. In addition, IFC files may be required and all subcontractors are required to have the capability of saving BIMs in the most current version of IFC. b. 3D SOLIDS: All objects must be modeled as 3D solids, not wire frame or lines. c. MODEL STRUCTURE: Models should be created on a floor by floor basis from top of slab to top of slab. If this is impractical for certain trades, alternate solutions can be discussed. d. LEVEL OF DETAIL (LOD): The models should contain the same level of detail as required for fabrication and installation. See Appendix A for required LOD. e. LIGHT SOURCES TURNED OFF: Prior to exporting lights to Navisworks, make sure that the lights source is turned off in all of the light families. Otherwise the light source appears as a spherical object in Navisworks which is difficult to isolate globally. f. LOCAL COORDINATES: When exporting Revit files to Navisworks, use local coordinates. g. CLEARANCES AND ACCESS: All clearances and access to equipment, valves, etc. required by code or requested by USC for the purposes of operations and maintenance must be 21 Version 1.6_April 18, 2012
22 modeled in 3D and kept in a separate layer and labeled correspondingly. These should be reviewed by the USC maintenance staff at approximately 80% coordination completion of each floor to verify the adequacy and practicality of the assigned space reservations and signed off at 95% to 100% coordination of each floor. This process shall be coordinated by USC s Project Manager. h. TRADE COLORS: Each trade shall be identifiable by a single color within Navisworks with the exception of architectural and structural elements as follows: HVAC Pipe: Lime Green Lights: Yellow Fire Sprinklers: Red Ceilings: Orange Steel: Maroon Methane: Forest Green Electrical: Cyan HVAC Duct: Blue Plumbing: Magenta Framing: Purple Concrete: Grey There is no need for individual trades to change their working color schemes; these will be altered when imported into Navisworks by the BIM Facilitator. i. COMMON REFERENCE POINT: Once established, every trade must use the same agreed upon reference point or global coordinate system. The 2D reference grid, located accordingly, shall be provided by the Architects. j. CLEAN MODELS NO X REFS: The 3D DWG and /or Navisworks models submitted should contain only relevant 3D data and no extraneous 2D data, nor should it contain any x referenced files. k. FILE NAMING: A file naming schema shall be provided by USC and this must be adhered to for all BIM uploads to the server. See BIM Execution Plan template, Appendix H. l. SOFTWARE: The General Contractor must list the BIM software and versions they and their subcontractors will be using for this project. EXCEPTIONS: List any exceptions to this document or alternate processes/methodologies that you would like to suggest subject to approval by USC and prior to submitting your BIM Execution Plan. 22 Version 1.6_April 18, 2012
23 APPENDIX A: MODEL ELEMENTS AND LEVEL OF DETAIL FOR MODELS DESIGN DEVELOPMENT AND CONSTRUCTION DOCUMENTS 1. Architectural Model the architectural elements to a level that defines the design intent and accurately represents the design solution. The detail and responsibility to fulfill these modeling requirements should be addressed fully within the BIM Execution Plan. Architectural Site Plan (also see Civil Engineering section below). Paving, grades, sidewalks, curbs, gutters, site amenities and other elements typically included on enlarged scale site drawings in vicinity of building. Existing conditions to the extent required. New interior and exterior walls to their correct and accurate height including but not limited to: Doors, windows, openings All finishes need to be included within the wall type regardless of the thickness of the finish Interior and exterior soffits, overhangs, sun control elements Parapets, screening elements Architectural precast Floor, ceiling and roof systems including but not limited to: Appropriate structural items listed below if not provided by the Structural Engineer and integrated into the architectural model for coordination and document generation. Insulation, ceiling systems, and floor are to be included. Roof, floor and ceiling slopes, if needed, shall be modeled. Soffits, openings, and accessories shall also be modeled. Elevators, stairs, ramps including railing systems. Casework, shelving, and other interior architectural elements. Furnishings, fixtures, and equipment if not provided by others and integrated into the architectural model for coordination and document generation. Furniture (Fixed and Loose). Furniture Systems. Specialty equipment (food service, medical, etc.). Model mechanical, electrical and plumbing items that require architectural space (toilets/sinks/etc), require color/finish selection (louvers, diffusers, etc.) or affect 3D visualization (lighting fixtures) unless provided by Engineers. Clearance zones for access, door swings, service space requirements, gauge reading, and other operational clearance must be modeled as part of all equipment and checked for conflicts with other elements. These clearance zones should be modeled as translucent solids on a separate layer. 2. Structural Model the following structural elements. The detail and responsibility to fulfill these modeling requirements should be addressed fully within the BIM Execution Plan. Foundations such as: Spread Foundations Caisson Foundations Pile Foundations Mat Foundations Load bearing Wall Foundations Framing such as: Steel Columns (with correct shape and size) Steel Floor C Joists Open Web Joists Joist Girders Steel Beams (with correct shape and size) Precast Concrete Elements (Hollow Core Plank may be modeled as a slab unless coordination with mechanical systems needs to occur because the hollow core is being used for those systems). 23 Version 1.6_April 18, 2012
24 Cast In Place Concrete Elements Floors, including overall extents and openings Overall thickness of wood floor systems Wood Posts/Columns All other Joists Wood Trusses Solid Wood or Laminated Beams Fireproofing, if required alternatively use a 2 clearance for clash detection Wall Types including openings: Load Bearing Walls for calculations only (Masonry, Concrete, Cold Formed Steel, and Wood) Model overall thickness of Cold Formed Steel and Wood Stud walls (individual members may be modeled at the Design Team s option) Structural Foundation Walls including brick ledges These items may be modeled at the Design Team s option: Steel reinforcing in concrete Embeds in concrete Miscellaneous Steel Angles for openings, deck bearing, etc. Channels for mechanical units needed for coordination reviews between structural and mechanical Lintels (unless considered a major member) Metal decks 3. HVAC Systems Model the following HVAC elements at a minimum. The detail and responsibility to fulfill these modeling requirements should be addressed fully within the BIM Execution Plan. Equipment Fans, VAV s, compressors, chillers, cooling towers, air handlers etc. Distribution Supply, return, exhaust, relief and outside air ductwork modeled to outside face dimension or duct insulation (whichever is greater). Duct Joints Diffusers, grilles, louvers, hoods, radiant panels, perimeter units, wall units. Pipes sized at and over 3/4 diameter, include any insulation in model unless otherwise noted by the BIM Execution Plan. Clearance zones for access, door swings, service space requirements, gauge reading, and other operational clearance must be modeled as part of the HVAC equipment and checked for conflicts with other elements. These clearance zones should be modeled as invisible solids within the object. 4. Electrical systems Model the following electrical elements at a minimum. The detail and responsibility to fulfill these modeling requirements should be addressed fully within the BIM Execution Plan. Data, Power and Telecommunications Interior and exterior transformers, emergency generators, and other equipment. Main and distribution panels and switchgear including access clearances. Main IDF s Outlets, switches, junction boxes. Lighting Permanently mounted lighting fixtures (moveable, plug in fixtures need not be modeled as part of the electrical package unless needed for plug load calculations or for estimating purposes within a loose furnishings package. Should be discussed and agreed upon within the BIM Execution Plan). Lighting Controls Switches Junction Boxes Fire Alarm and Security Systems Input devices Notification devices 24 Version 1.6_April 18, 2012
25 Associated equipment and access clearances Permanently mounted fixtures Electrical Power Off Buttons (EPOs) 5. Plumbing and Fire Protection Model the following plumbing and fire protection elements at a minimum. The detail and responsibility to fulfill these modeling requirements should be addressed fully within the BIM Execution Plan. Waste and Vent Piping sized at and over 3/4 diameter, includes any insulation in the model unless otherwise noted by the BIM Execution Plan. Roof and floor drains, leaders, sumps, grease interceptors, tanks, water treatments and other major items. Supply Piping sized at and over 3/4 diameter, includes any insulation in the model unless otherwise noted by the BIM Execution Plan. Domestic Booster Pumps. Fixtures: sinks, toilet fixtures, water tanks, floor sinks Fire protection Sprinkler lines at and over 3/4 diameter. Sprinkler heads, Fire Protection Pumps. Stand pipes, wall hydrants, fire department connections, risers, including valve clearances. Clearance zones for access, service space requirements, gauge reading, valve clearances and other operational clearance must be modeled as part of the plumbing and fire protections system and checked for conflicts with other elements. These clearance zones should be modeled as invisible solids within the object. 6. Specialty Equipment Suppliers should be requested to provide equipment models to an appropriate level of detail. If the latter are not obtainable, model the following specialty consultant elements to the correct size and in the correct location. Some of these items might occur in the above mentioned disciplines and should be discussed within the BIM Execution Plan. Equipment provided or specified by said consultant. Rough in connection points for power, data, communications, water service and waste, gas, steam, or other needed utilities. Extent of specialty consultant modeling shall be coordinated with the Design Team and described in the BIM Execution Plan. Clearance zones for access, doors swings, service space requirements, controls, gauge reading, and other operational clearance must be modeled as part of the equipment and checked for conflicts with other elements. 7. Civil Engineering Model the following civil engineering elements at a minimum: Topography 3D terrain of all site work as designed, including retaining walls. This model should include the site and surrounding areas that contribute to the site s drainage system or otherwise impact on the site. In most cases this shall require that adjacent roadways be modeled. Landscaping elements: planting areas, such as raised planting beds and berms, parking islands, pools/ponds/other water features, terraces and other items not included elsewhere in the model. Stormwater management structures pump stations, fueling systems, manholes and other major items that impact on the overall project understanding or which may become project design constraints. All items must be geo referenced such that all elements can be viewed as an overlay in the building information model. CONSTRUCTION COORDINATION 25 Version 1.6_April 18, 2012
26 General Concepts Installation of all utilities, regardless of size or diameter, shall be modeled. Layers shall be labeled as per the architectural drawings to identify the utilities. Model Clearance Requirements Model should include code and maintenance items, such as valve handle swings and pull chain drops. Constructability clearances for a specific utility line or equipment shall be modeled in 3D and contained on one dedicated layer. Insulation should be included on all piping, plumbing and ductwork where required. Pre Fabrication Any pre fabricated item shall be included in the model to ensure proper space and connections. All modeled objects must be custom/specific objects from the manufacturer Generic model pieces should not be used for the signed off coordination models. MEPF systems should contain a minimum amount of associated data for ease of identification: hot water, cold water, waste, supply, return, overall duct and pipe sizes, elevation, etc. The models shall include, but are not limited to: 1. Architectural Model Wall thickness and height Required for routing main utilities, locating VAV boxes, identifying priority wall framing, wall penetrations, fire stopping. Hard ceilings and soffits Required for identifying HVAC diffuser locations, electrical fixture locations, and routing of utilities with openings for diffusers and lights. Exteriors walls / storefront Required for identifying the location of rain water leaders. Shafts, wall chases Required for identifying the correct locations of plumbing vents, and HVAC shafts. Architectural features requiring utilities Required for utility routing. Architectural features in mechanical spaces Required for utility routing. 2. Structural Model Beams and columns Braces and gusset plates Supplemental steel Miscellaneous supports for equipment, toilet partitions, etc. External wall framing connections 3. Drywall/Framing Model Studs, bottom and top track Kickers or other drywall supports Roof framing 4. Concrete Model Footings and foundations Area of influence zones under foundations Slabs and slab depressions 5. Mechanical Model Medium pressure duct Required for coordination and routing of other trades as well as pre fabrication. Low pressure duct Required for coordination and routing of other trades as well as pre fabrication. Shaft locations Required for coordination and routing of other trades and for locating smoke dampers, etc. Flanges VAV boxes Required for pre fabrication purposes, coordination with HVAC heating hot water piping, tagged with correct Equipment ID. Fire smoke dampers Required in coordination, tagged with correct Equipment ID. Flex ducts Required for showing how low pressure ducts connect to the diffusers. Diffuser locations and sizes Required for coordination of finish utilities with the other fixtures in a room (like electrical fixtures, etc.). All duct and pipe insulation Should be included where required so that the maximum sizes are represented in the model. Required for coordination. 26 Version 1.6_April 18, 2012
27 Hangers and seismic bracing Required for coordination and routing of other trades and for inserting the deck correctly before installation begins. HVAC piping to VAV boxes Main lines are required for coordinating with other trades; also required if they will be pre fabricated; connections to VAV boxes can be left for field routing. HVAC piping to Equipment Main lines are required for coordinating with other trades; also required if they will be pre fabricated; final connections to equipment need to be coordinated on model as well. Underground utilities Required for underground MEP / FP coordination. Mechanical room All equipment Required for coordinating with other trades, tagged with correct Equipment ID. 6. Electrical Model Branch and feeder conduits Required for coordination with other trades and for pre fabrication. Conduits 3/4 and greater need to be modeled. Flex and MC not required. All underground conduits Required for underground MEP / FP coordination. Junction boxes Required for coordination with other trades. Lighting fixtures Required for coordination with other trades and finish utilities like ceiling grid, sprinkler heads, HVAC diffusers and specialty lighting. Tag with Circuit number. All lighting supports for special lighting Required for routing and coordination of other trades. Cable trays and other supports Required for coordination with other trades. Hangers and seismic bracing Required for coordination with other trades and for inserting the deck. Equipment Panels Required for coordinating with wall framing to determine backing, etc. Tag with Panel number. Electrical rooms Required for coordination with wall framing and other trades. Bundles of cable or wiring Useful for coordination and pre fabrication. Outlets and switch locations in rooms Useful for pre fabrication and coordination. Tag with Circuit number. Electrical power off buttons All equipment Required for coordinating with other trades. 7. Plumbing Model Plumbing fixtures Required for coordination with other MEP trades. Graded cast iron pipe lines Required for coordination with other trades and pre fabrication. Underground storm and sewer pipes Required for underground utilities coordination and for prefabrication. Waste and vent lines Required for coordination with other trades and with architectural walls, shafts and for pre fabrication. Cold and hot water piping Required for coordination with other trades and for pre fabrication. Identify valves and tag with appropriate valve number. Hangers and seismic bracing details Required for coordination with other trades and for inserting before installation. Specialty piping Required for coordination with other trades and for pre fabrication. All equipment Required for coordination. Methane 8. Sprinkler Model Sprinkler mains and branches Required for coordination with other trades and for pre fabrication. Sprinkler head drops Required for coordination with finish utilities like electrical lighting, diffusers, etc. Sprinkler pipes Required if hard pipe is used, useful if the newer type of flex pipe is used. Hangers and seismic bracing Required for coordination with other trades and for inserting the deck correctly before installation begins. Underground utilities Required for underground MEP / FP coordination. All equipment Required for coordination. 9. Process Piping Model Process piping All piping, valves, actuators, and fittings required for coordination with other trades. Hangers and seismic bracing Required for coordination and routing of other trades and for inserting the deck correctly before installation begins. Process equipment A model of each piece of equipment must be provided by the equipment manufacturer for coordination with other trades. 27 Version 1.6_April 18, 2012
28 10. Controls Model Conduit and tubing All Instrument Air, power and control wiring conduit, conduit and distribution boxes serving control tubing are required for coordinating with other trades. Equipment panels Required with associated conduit and gutters in the model for space coordination with other trades as well as determining backing. Raceways Required for coordination with other trades. 11. Requested by USC Information Technology Services: a. Underground OSP System a) Conduits size b) Conduits number c) Conduit locations d) Trench line location e) Conduit depths and details f) MH locations g) MH size h) MH details/cable layout splice locations I) Copper cable type, size j) Copper cable ID # k) Copper cable splice cases l) Fiber cables type, size m) Fibers ID # n) Fiber splice cases b. Building Inside Cable Supports Infrastructures a) OSP conduits entering MDF room. b) Riser system from main telecom room to other telecom rooms. Amount, size and route. c) MDF room size location and layouts. d) Other Telecom room size and layout. e) Conduits, sleeves, stub up conduits, boxes, cable trays and their location and sizes. f) Telecom Jack locations, wall mounted floor mounted. g) Telecom outlets types, quad, duplex, single, rack mount patch panels. h) Wi Fi location and cable. I) Telecom room s power outlet locations. j) Telecom room ground Bus Bar. k) Telecom room AC location and size. l) All associated supports (wire and/or rods). m) Distributed Antenna System (DAS). n) Cable or satellite TV. o) Security cameras. p) Building or site emergency phones. q) Area of refuge phone requirement. 28 Version 1.6_April 18, 2012
29 APPENDIX B: BIM DATA ACQUISITION GUIDELINE FOR FACILITIES MANAGEMENT SERVICES The information below is meant to provide guidance on the following: Capturing of attribute data related to equipment / building system(s), that which USC Facilities Management Services deems of importance to on going operations. Minimum modeling requirements / standards in the development of models (BIM) for a new building construction project. Anticipated deliverables (from the design and construction teams), as associated with their respective modeling efforts. Goals and broad deliverables associated with the transfer of project information in a COBie compliant fashion. Recommended workflows anticipated to aid in the delivery on all of the above mentioned items, and that which may be considered in a subsequent project BIM Implementation Plan. For context USC has identified the following goals and practical benefits for leveraging BIM within Facilities Management Services. FM Enterprise Information System Data Population. Timely and accurate management of project turn over/documentation. Management and updating of evolving building space. MASTER ATTRIBUTES Within the BIM authoring application, the following (type or instance) parameter fields shall be populated, either centrally in the model or applied to individual MEP+F system families. The fields that are to be populated with USC designated information may be left empty if that information is not yet available. NOTE: The field names must appear EXACTLY as shown. Use the Shared Parameter TXT file below: 29 Version 1.6_April 18, 2012
30 USC MASTER ATTRIBUTES Obtained from USC REVIT PARAMETER NAME Description USC Site Code USC Building Number USC Floor Number USC Equipment Number USC EMSID Number Name OmniClass Number OmniClass Title USC Site Code Designation USC Building Designation USC Floor Designation USC Equipment Number Unique Id assigned to selected pieces of USC equipment for Energy Management purposes USC Room Number designation USC Room Name designation Corresponding OmniClass XX XX XX XX XX number Corresponding OmniClass description to the OmniClass number Uniformat Number Master Format Number Type Name Type Description Corresponding product s UniFormat number Corresponding products s Master Format number According to USC Nomenclature Guideline According to USC Nomenclature Guideline USC NOMENCLATURE Instance Name Instance Description According to USC Nomenclature Guideline According to USC Nomenclature Guideline ASSET MANAGEMENT ATTRIBUTES Specification and performance type data, typically found in an equipment schedule, shall be captured within the design models. Provisions for these parameter fields, for doing so shall be maintained when developing families. See attached exhibit entitled USC FMS MEP Outline Schedule Data Specifications.pdf, (organized by Master Format 2004 Specification Format) for required equipment specific MEP+F type parameters. These fields are to be established as at the start of modeling, and subsequently updated through the progression of design and construction. 30 Version 1.6_April 18, 2012
31 These exhibits are the beginning of what will be an evolving list, and shall be expanded once it is determined that additional types of equipment (not covered) are to be specified and installed in subsequent phases of construction. SPACE MANAGEMENT OBJECTIVES For the purpose of allowing Facilities Management Services to carry out downstream space management related functions, at minimum the following objects shall be modeled (and not massed) so to be able to enclose an area and represent all rooms. The intent is to solicit such information as (1) square footage, (2) heights, and (3) volumes. COBie 1. Walls 2. Floors 3. Roofs 4. Windows 5. Doors 6. Ceilings 7. Shafts (stairs, elevators, etc) Information Tiers For the purpose of categorizing data that would eventually be delivered in a COBie compliant format, the following tiers have been established. 1. Tier #1: Master Attributes + Asset Management Attributes It is anticipated that these will be found and maintained (throughout the project) within the design models. 2. Tier #2: Balance of information required of COBie It is anticipated that these shall be found and maintained (throughout the project) within the agreed upon depository of COBie worksheets. 3. Tier #3: Project close out documents It is anticipated that these shall be found and maintained (throughout the project) within the agreed upon depository of COBie worksheets. 31 Version 1.6_April 18, 2012
32 COBie standard worksheets The following COBie standard worksheets shall be provided (at minimum) to meet the long term Facilities Management goals. The standard fields within these respective sheets shall be consistent with the current COBie 2 standards. a. Design models: 1. Contact 2. Facility 3. Floor 4. Space should be classified using OmniClass and Net Area is provided (Gross Area is generated by Revit). 5. Zones should have categories assigned. 6. Types should have Name, Category (OmniClass), Description, AssetType. 7. Components should have Name, Description, Type and Space. 8. Systems should have Name, Category (OmniClass), Components. 9. Document 10. Attribute (see Tier#1 for minimum requirements) b. Construction models 1. Type information updated by providing manufacturer, model number, warranty information (parts and labor and duration), replacement cost. 2. Component information updated by providing serial number, installation date, warranty start date, tag number and/or barcode. Installation date for major equipment will be the finish date of the scheduled activity. 3. Spare parts provided for types. 4. Attributes provided for types and components. c. Commissioning Models 1. Attributes corrected based on real measurements. 2. Documents linked to COBie worksheet. COBie update schedule It is anticipated that the master COBie compliant worksheet is updated to reflect the available information at the following stages in a project. 100% Design Documents (validation of Tier#1 fields provided) Issuance of For Construction 75% Substantial Completion Commissioning Complete Project Close Out 32 Version 1.6_April 18, 2012
33 APPENDIX C: NOMENCLATURE (updated 2/18/2012) Families, Types, Instances (Components), Systems and Zones Naming Requirements INDUSTRY CODES USC requires the use of the latest version* of OmniClass as the coding standard. * (for latest version) OmniClass Table 23 Products are used to digitally code and classify Equipment Type & Components. For example, is the digital code for equipment axial flow compressors. OmniClass Table 21 Elements are used to digitally code and classify Equipment Systems and Zones. For example, is the digital code for equipment system named Domestic Water Distribution. EQUIPMENT FAMILY, TYPE AND INSTANCES (COMPONENTS) NOMENCLATURE Naming conventions for equipment types should be succinct, useful and descriptive. The names provided should allow for easy identification and be easily understood in order to facilitate the operation, repair and maintenance of USC equipment. USC uses a combination of Industry Standard nomenclature OmniClass Table 23 Products, the U.S. National CAD Standards (NCS) 3.1 Module 5 : Terms and Abbreviations and an Equipment Operation Description to name equipment types and instances as illustrated below. Please follow this guide accordingly: FAMILY NAME Industry Standard OmniClass Table 23 Products exact wording of equipment description TYPE NAME U.S. National CAD Standards (NCS) 3.1 Module 5 : Terms and Abbreviations + Equipment Operation Description Description denoting size / type as easily identified & understood INSTANCE NAME U.S. National CAD Standards (NCS) 3.1 Module 5 : Terms and Abbreviations + ID Unique to that Component as identified in the equipment schedule For example: Variable Air Volume (VAV) Box with ID D01, the Type and Instance Names: FAMILY NAME Variable Air Volume Terminal Units Variable Air Volume Terminal Units TYPE NAME VAV + Box Reheat 6 Inches VAV Box Reheat 6 Inches INSTANCE NAME VAV + D01 VAV D01 33 Version 1.6_April 18, 2012
34 TYPE DESCRIPTION U.S. National CAD Standards (NCS) 3.1 Module 5 : Terms and Abbreviations + Equipment Operation Description Extended description denoting manufacturer /type/size as easily identified & understood INSTANCE DESCRIPTION U.S. National CAD Standards (NCS) 3.1 Module 5 : Terms and Abbreviations + Detailed Equipment Operation Description Extended Description denoting type/size/id/location unique to that instance For example: Variable Air Volume (VAV) Boxes the Type and Instance Descriptions: TYPE DESCRIPTION VAV + with Reheat Price SDV 6 Inches VAV with Reheat Price SDV 6 Inches INSTANCE DESCRIPTION VAV + with Reheat 6 Inches + D01 with VAV Reheat 6 Inches D01 HELP FILES Execution of Equipment Family, Type and Instances (Components) Nomenclature Details on how to populate the nomenclature in Autodesk Revit describing the parameters to use, where to place them, and relevant examples, can be found in the documents entitled "USC Nomenclature & Systems.ppt" and "USC Revit Parameters List.xls" which are located in the subfolder named BIM Guidelines Reference Docs in the Project Documentation folder in e Builder. An Autodesk Revit shared parameters file is also available in e Builder to populate Autodesk Revit files with the USC required parameters and/or with the creation of Revit families. 34 Version 1.6_April 18, 2012
35 SYSTEMS NOMENCLATURE USC uses a combination of the Industry Standard nomenclature OmniClass Table 21 Elements, the U.S. National CAD Standards (NCS) 3.1 Module 5: Terms and Abbreviations and an Equipment Operation Description to name systems as illustrated below. Please follow this guide accordingly. Execution of Systems and Zones Nomenclature Further illustration and relevant examples of USC conforming systems and zones nomenclature can be found in the documents entitled "USC Nomenclature & Systems.ppt" which are located in the sub folder named BIM Guidelines Reference Docs in the Project Documentation folder in e Builder. Industry Standard + Discipline OmniClass Table 21 Elements exact wording of element description U.S. National CAD Standards (NCS) 3.1 Module 5 : Terms and Abbreviations + Equipment Operation Description Description denoting size / type as easily identified SYSTEM NAME For example: Supply Air System for Air Handling Unit (AHU) D 1 = Mechanical Supply Air AHU D Supply Air + Discipline "Mechanical" Mechanical Supply Air AHU + Description "D1" AHU D1 SYSTEM NAME Mechanical Supply Air AHU D1 For systems that are not directly connected to a piece of equipment, follow the convention below: Industry Standard OmniClass Table 21 Elements exact wording of element description + Discipline National CAD Standard + Equipment Operation Description for equipment associated with the duct if applicable + Floor + USC official Room Number and Room Name SYSTEM NAME 35 Version 1.6_April 18, 2012
36 For example: Ductless return air system consisting of pieces of ductwork and a return air grille, "RG 1"= Mechanical Return Air RG 1 2 nd Floor 214A Office Return Air + Discipline "Mechanical" Mechanical Return Air RG 1 + 2nd Floor 214A Office SYSTEM NAME Mechanical Return Air RG 1 2nd Floor 214A Office ZONES NOMENCLATURE In order to identify zones USC uses a combination of the U.S. National CAD Standards (NCS) 3.1 Module 5 : Terms and Abbreviations, an Equipment Operation Description and USC official Room Numbers to name zones as illustrated below. Please follow this guide accordingly: U.S. National CAD Standards (NCS) 3.1 Module 5 : Terms and Abbreviations + Equipment Operation Description Description denoting size / type as easily identified USC official Room Name and Numbers for rooms contained in that Zone ZONE NAME For example: The HVAC Zone associated with VAV Box D01 serving Offices 100,101,102= VAV D01 Offices 100,101,102 VAV + equipment number from schedule (i.e. D01) VAV D01 Office 100, 101, 102 ZONE NAME VAV D01 Offices 100,101,102 SPACES Spaces should be named according the official USC room numbers as provided by Space Management. 36 Version 1.6_April 18, 2012
37 APPENDIX D: Installation Change Log Where installation differs from the coordinated model, a log of adjusted installations will be kept detailing what the change was, the reason for the change and confirming that the 3D model has been updated accordingly. The following template can be used for this purpose. ITEM DESCRIPTION OF CHANGE REASON FOR CHANGE DATE OF MODEL UPDATE CHANGED BY: 37 Version 1.6_April 18, 2012
38 APPENDIX E: Revit Model Requirements and Warnings The following represents the Revit model requirements and Revit warnings to correct. Overlapping of design elements (especially walls and room boundaries). All floors are subdivided by room. Space enclosures. All spaces must be bounded by walls and floors. Every space has a name and a room number, including all shafts and stairs. There is only one space instance per space, no duplicates. Resolve all orphans (resulting from using copy/paste. All walls are connected to the top of slab at bottom and bottom of slab at top (if full height). All mechanical spaces are defined floor to floor, unless there is a plenum. Plenums are defined as a separate space. All mechanical systems are defined (every element belongs to a system). This can be verified using the Revit MEP system browser. Sidewall diffusers are placed in defined spaces and attached to corresponding walls. Ensure that the Revit MEP file is linked to the Revit architectural file.(this can be checked by using the Revit System Browser and verifying that the space name and space number columns are populated). Ensuring that all system components within a workset belong to that workset. Ensuring that all mechanical zones are defined. Ensuring that there are no unassigned components (View/User Interface/System Browser). Mapping MEP space names to architectural room names. 38 Version 1.6_April 18, 2012
39 APPENDIX F: Collision Detection and Design Review The best methodology for tracking collision issues is to save named viewpoints for each clash in a dated folder. Sharing this collision checked file with other Design Team members allows individuals to review issues that pertain to them in a systematic way. This should be done by the BIM Facilitator using an iterative process: Clash detection* MEPF against structure MEPF against MEPF MEPF against FFE FFE against structure Visual inspection Cross sectioning through building Viewing ceilings from below for MEPF penetrations MEPF anomalies with architecture Architectural and structural misalignment Ceilings elevations relative to fenestration Etc. Save viewpoints (in a folder for that date) Review issues with the Design Team Each discipline resolves issues pertaining to their discipline Re clash Move resolved issue viewpoints to a Resolved folder Create new viewpoints for new issues in a dated folder Review previous unresolved issues and new issues Resolve issues Re clash *This is best done in the collision detection software such as Navisworks, not in Revit. 39 Version 1.6_April 18, 2012
40 APPENDIX G: USC FMS Outline Schedule Data Specification Section Schedules for Plumbing Piping and Pumps (SUMP / SEWAGE EJECTOR) PUMP SCHEDULE Tag Manufacturer Model Number Location Service Fluid Type / Configuration Basin Size Inlet Size Discharge Size Design Flow Rate (GPM) Total Design Head RPM Minimum Efficiency (%) Impeller Size (as applicable) Motor Data o Break Horse Power o Horse Power o Rotations Per Minute o Voltage o Phase o Hertz Operation Weight Master Format Reference Number Uni Format Reference Number USC Equipment Reference Number Section Schedules for Plumbing Equipment HOT WATER GENERATOR SCHEDULE Tag Service Manufacturer Model Number Location Type Storage Capacity (Gallons) Recovery Capacity ΔT) Outlet Water Supply Temperature Outlet Water Supply Flow Recovery Capacity ΔT) Operating Weight Master Format Reference Number Uni Format Reference Number USC Equipment Reference Number 40 Version 1.6_April 18, 2012
41 Section Schedules for Plumbing Fixtures FIXTURE SCHEDULE Tag Fixture Type Water Demand Fixture Unit o Cold Water o Hot Water Waste Demand Fixture Unit Branch Pipe Connections o Waste o Trap o Vent o Cold o Hot Master Format Reference Number Uni Format Reference Number USC Equipment Reference Number Section Schedules for HVAC Piping and Pumps PUMP SCHEDULE Tag Manufacturer Model Number Location Service Fluid Type / Configuration Inlet Size Discharge Size Design Flow Rate Total Design Head RPM Minimum Efficiency (%) Impeller Size (as applicable) Motor Data o Break Horse Power o Horse Power o Rotations Per Minute (RPM) o Voltage o Phase o Hertz Operation Weight Master Format Reference Number Uni Format Reference Number USC Equipment Reference Number 41 Version 1.6_April 18, 2012
42 Section Schedules for HVAC Air Distribution FAN SCHEDULE Tag Manufacturer Model Number Location Area Served Service Type Configuration CFM External Static Pressure Total Static Pressure Wheel Diameter (Inches) Rotations Per Minute Motor Data o Break Horse Power o Horse Power o Rotations Per Minute o Voltage o Phase o Hertz Operating Weight (Lbs) Master Format Reference Number Uni Format Reference Number USC Equipment Reference Number AIR TERMINAL UNIT (Constant / Variable) Tag Manufacturer Model Number Area Served Central System Serving Inlet Size (Inches) CFM o Maximum o Minimum (as applicable) Other (as applicable) Maximum Pressure Drop Re heat Coil (See requirements listed elsewhere in specification section) Branch Pipe Size Operating Weight Discharge NC Radiated NC RE HEAT COIL SCHEDULE Tag Manufacturer Model Number (as applicable) Location Area Served Coil Area (Sq. Ft) CFM 42 Version 1.6_April 18, 2012
43 Total Capacity (MBH) Minimum Rows Deep Coil Construction Material Fins Per Inch (as applicable) Fin Construction Material Air Conditions o Entering Dry Bulb Temp. o Leaving Dry Bulb Temp. GPM Water Conditions o Entering Dry Bulb Temp. o Leaving Dry Bulb Temp. o Maximum Pressure Loss Air Side o Water Side DIFFUSER / REGISTER SCHEDULE Tag Manufacturer Model Number Material Finish Type Mounting Nominal Dimensions (in. X in.) Inlet / Neck Dimensions (in. X in.) Maximum Static Pressure Throw Pattern Maximum Design Air Flow Minimum Design Air Flow Maximum Design Air Flow Minimum Design Air Flow Noise Max Air Flow Border Type Master Format Reference Number Uni Format Reference Number USC Equipment Reference Number SOUND ATTENUATOR SCHEDULE Tag Manufacturer Model Number Location Dimensions o Width o Height o Length CFM Maximum Pressure Drop Minimum Dynamic Insertion Loss (In Db) FPM o 63 Hz o 125 Hz o 250 Hz o 500 Hz o 1 Khz o 2 Khz 43 Version 1.6_April 18, 2012
44 o 4 Khz o 8 Khz Self Noise Power Level (In Db) Fpm Face Velocity o 63 Hz o 125 Hz o 250 Hz o 500 Hz o 1 Khz o 2 Khz o 4 Khz o 8 Khz Master Format Reference Number Uni Format Reference Number USC Equipment Reference Number Section Schedules for Central HVAC Equipment AIR HANDLING UNIT Tag Manufacturer Model Number Location Area Served Supply & Return Fan(s) o CFM o External Static Pressure (Inches WC) o Total Static Pressure (Inches WC) o Rotations Per Minute (RPM) o Motor Data Break Horse Power Horse Power Rotations Per Minute Voltage Phase Hertz o Wheel Diameter (Inches) Cooling / Heating Coil o Maximum Face Velocity (FPM) o Coil Area (Sq. Ft) o CFM o Total Capacity (MBH) o Sensible Capacity (MBH) as applicable o Minimum Rows Deep o Coil Construction Material o Fins Per Inch o Fin Construction Material o Entering Air Conditions Dry Bulb Temp. Wet Bulb Temp. o Leaving Air Conditions Dry Bulb Temp. Wet Bulb Temp. o GPM o Water Conditions Entering Temp. Leaving Temp. Maximum Pressure Loss (Psi / FT) 44 Version 1.6_April 18, 2012
45 Air Side Water Side Filters o Quantity o Size o Type o Minimum Effective (%) o Minimum MERV Operational Weight (Lb) Minimum Outside Weight (Lb) Master Format Uni Format USC Equipment Number Section Schedules for Decentralized HVAC Equipment COMPUTER ROOM AIR CONDITIONING UNITS Tag Manufacturer Model Number Location Area Served Supply Fan o CFM o External Static Pressure o Total Static Pressure o Rotations Per Minute o Motor Data Break Horse Power Horse Power Rotations Per Minute Voltage Phase Hertz Cooling Coil o Maximum Face Velocity (FPM) o Coil Area (Sq. Ft) o Total Capacity (MBH) o Sensible Capacity (MBH) o Entering Air Conditions Dry Bulb Temp. ( F) Wet Bulb Temp. ( F) o Leaving Air Conditions Dry Bulb Temp ( F) Wet Bulb Temp ( F) o Flow Rate (GPM) o Water Temperature Entering Conditions ( F) Leaving Conditions ( F) o Max. Pressure Loss / Drop (Psi / Ft.) Filters o Quantity o Size o Type o Minimum Efficiency % Minimum MERV Humidifier 45 Version 1.6_April 18, 2012
46 o Manufacturer (if different from unit manufacturer) o Model Number o Type o Capacity Unit Electrical Data o FLA o MCA o MOCP o Volts o Phase o Hertz Operating Weight Master Format Number Reference Number Uni Format Reference Number USC Equipment Reference Number FAN COIL UNITS Tag Manufacturer Model Number Location Area Served Supply Fan o CFM o External Static Pressure o Total Static Pressure o Rotations Per Minute o Motor Data Break Horse Power Horse Power Rotations Per Minute Voltage Phase Hertz Cooling / Heating Coil o Maximum Face Velocity (FPM) o Coil Area (Sq. Ft) o Total Capacity (MBH) o Sensible Capacity (MBH) o Minimum Rows Deep o Coil Construction Material o Fins Per Inch o Fin Construction Material o Entering Air Conditions Dry Bulb Temperature ( F) Wet Bulb Temperature ( F) o Leaving Air Conditions Dry Bulb Temperature ( F) Wet Bulb Temperature ( F) o Flow Rate (GPM) o Water Temperature Entering Condition ( F) Leaving Conditions ( F) o Max. Pressure Loss / Drop (Psi / Ft.) Air Side Water Side Filters o Quantity 46 Version 1.6_April 18, 2012
47 o Size o Type o Minimum Efficiency (%) o Minimum MERV Unit Electrical Data o FLA o MCA o MOCP o Volts o Phase o Hertz Operating Weight Minimum Outside Air (CFM) Master Format Reference Number Uni Format Reference Number USC Equipment Reference Number RADIANT PANEL SCHEDULE Tag Manufacturer Model Number (as applicable) Area Served Total Panel Area (Sq.Ft.) Total Panel Area (Sq.Ft.) Heating Only Total Panel Area (Sq.Ft.) Cooling Only Radiant System Pump Number Flow Rate (GPM) o Heating o Cooling Room Operating Conditions o Space Temperature Set Point Heating ( F) Cooling ( F) o Supply Air Temperature Set Point Heating ( F) Cooling ( F) Cooling o Specified Panel Capacity (Btu/H / Sq.Ft) o Total Capacity (Btu/H) o Minimum Surface Temperature ( F) o Radiant Supply Temperature ( F) o Radiant Return Temperature ( F) Heating o Specified Panel Capacity (Btu/H / Sq.Ft) o Total Capacity (Btu/H) o Minimum Surface Temperature ( F) o Radiant Supply Temperature ( F) o Radiant Return Temperature ( F) Operating Weight Master Format Reference Number Uni Format Reference Number USC Equipment Reference Number RADIANT FLOOR SCHEDULE Tag 47 Version 1.6_April 18, 2012
48 Manufacturer Model Number Location Fluid Radiant System Pump Number Flow Rate (GPM) Radiant Panel Area (Sq.Ft) Surface Resistance Loop o Total Tube Length (Ft) o Maximum Loop Length (Ft) o Maximum Pressure Drop o Tube Type o Tube Outside Diameter (Inches) o Tube Spacing (Inches) Cooling o Specified Space Capacity (Btu/H / Sq.Ft) o Short Wave Capacity (Btu/H / Sq.Ft) o Total Capacity (Btu/H) o Minimum Surface Temp. ( F) o Radiant Supply Temp. ( F) o Radiant Return Temp. ( F) Heating o Specified Space Capacity (Btu/H / Sq.Ft) o Short Wave Capacity (Btu/H / Sq.Ft) o Total Capacity (Btu/H) o Minimum Surface Temp. ( F) o Radiant Supply Temp. ( F) o Radiant Return Temp. ( F) Maximum Flow Rate (GPM) o Heating o Cooling Master Format Reference Number Uni Format Reference Number USC Equipment Reference Number Section Schedules for Low Voltage Electrical Distribution ELECTRICAL PANEL SCHEDULE Panel Name Panel Location Fed From Voltage Phase Wire Main Circuit Breaker o Yes o No o Main Circuit Breaker Size (If Yes Above) Bus Size Type of Mounting o Surface o Flush Isolated Ground Bus o Yes o No 48 Version 1.6_April 18, 2012
49 Shunt Trip o Yes o No Neutral Size o 100% o 200% Feed Through o Yes o No Master Format Reference Number Uni Format Reference Number USC Equipment Reference Number Section Schedules for Lighting LIGHTING FIXTURE SCHEDULE Type Description Fixture Manufacturer Fixture Catalogue / Model Number Finish Mounting Lamp o Type o Manufacturer o Catalogue / Model Number o Quantity o Input Wattage Voltage Master Format Reference Number Uni Format Reference Number USC Equipment Reference Number (as applicable) 49 Version 1.6_April 18, 2012
50 APPENDIX H: ECODOMUS The following describes the process used for implementing EcoDomus on USC projects. 1. Configure COBie QC template USC will set up the Data Acquisition Template in EcoDomus PM, to provide a baseline that all COBie2 requirements can be measured against in the automated QC process. OmniClass based rules are set for the attributes, naming conventions, and documentation, allowing for easy integration of the data with other data sets with the same classification system. COBie Quality Control Template in Ecodomus with all requested COBie data. 2. Populate Project Equipment Database The construction team will populate extended properties and documentation provided in shop drawings and equipment schedules for the installed equipment in EcoDomus PM. This equipment data will be attached by batch to the relevant objects in the uploaded BIM. Data Entry Template in EcoDomus 50 Version 1.6_April 18, 2012
51 BIMGUIDELINES 3. LoadGeometryValidatedBIMintoEcoDomusPM OncethegeometryoftheBIMhasbeenverifiedtoaccuratelyreflecttheas builtconditions,uscwillloadthebim intoecodomususingtherevitecodomusplug in.thisprocessincludessynchingwithrevitintheecodomuspm desktop,andthenadatapushtotheecodomuspmwebapplication. GeometryValidatedModel EcoDomus Revitplug in 3DInterfaceinEcoDomus withallintegrateddata 4. PerformCOBieQualityControl TheProjectEquipmentDatabasewillbeattachedtothemodelinEcoDomusinanautomatedprocesstoensure efficienciesofthebimdatapopulation.oncethedataisattachedtotheassociatedobjectsinthemodel,itwillbe validatedviaaqualitycontrolprocesstoensurecompliancewithcobieanddatarequirements. MissingAttributesreport(COBiedatacheck) 51 Version1.6_April18,2012
52 Any missing information generated in the report will be checked in the field using mobile devices, and against corresponding shop drawings and schedules provided by the project team. Data will then be added in the corresponding object field in EcoDomus web or client application. Enter field data directly against 3D object or in associated web form 5. Populate Complete Data Set to Revit Augmented BIM The accumulated, verified data can be pushed back into the geometrically verified Revit model using the EcoDomus Revit plug in. 52 Version 1.6_April 18, 2012
53 APPENDIX I BUILDING INFORMATION MODELING (BIM) EXECUTION PLAN VS 1.0 FOR [PROJECT TITLE] DEVELOPED BY [AUTHOR COMPANY] 53 Version 1.6_April 18, 2012
54 TABLE OF CONTENTS SECTION A:... BIM PROJECT EXECUTION PLAN OVERVIEW SECTION B:... PROJECT INFORMATION SECTION C:... KEY PROJECT CONTACTS SECTION D:... BIM PROCESSES AND COLLABORATION PROCEDURES SECTION E:... BIM AND FACILITY DATA REQUIREMENTS SECTION F:... BIM AND DATA QUALITY CONTROL SECTION G:... MODEL STRUCTURE SECTION H:... PROJECT DELIVERABLES SECTION I:... ATTACHMENTS 54 Version 1.6_April 18, 2012
55 SECTION A: BIM PROJECT EXECUTION PLAN OVERVIEW This BIM Project Execution Plan defines uses for BIM on the project (e.g. design authoring, cost estimating, and design coordination), along with a detailed design of the process for executing BIM throughout the project lifecycle. [INSERT ADDITIONAL INFORMATION HERE IF APPLICABLE. FOR EXAMPLE: BIM MISSION STATEMENT This is the location to provide additional BIM overview information. Additional detailed information can be included as an attachment to this document. 55 Version 1.6_April 18, 2012
56 SECTION B: PROJECT INFORMATION This section defines basic project reference information and determined project milestones. 1. PROJECT OWNER: 2. PROJECT NAME: 3. PROJECT LOCATION AND ADDRESS: 4. CONTRACT TYPE / DELIVERY METHOD: 5. BRIEF PROJECT DESCRIPTION: [NUMBER OF FACILITIES, GENERAL SIZE, ETC] 6. ADDITIONAL PROJECT INFORMATION: [UNIQUE BIM PROJECT CHARACTERISTICS AND REQUIREMENTS] 7. PROJECT NUMBERS: PROJECT INFORMATION USC CONTRACT NUMBER: USC PROJECT NUMBER: USC SITE CODE: USC BUILDING NUMBER: NUMBER 8. PROJECT SCHEDULE / PHASES / MILESTONES: Include BIM milestones, pre design activities, major design reviews, stakeholder reviews, and any other major events which occur during the project lifecycle. PROJECT PHASE/MILESTONE ESTIMATED START DATE ESTIMATED COMPLETION DATE PROJECT STAKEHOLDERS INVOLVED SCHEMATIC DESIGN 50% CONSTRUCTION DOCUMENTS FACILITIES MANAGEMENT SERVICES REVIEW 100% CONSTRUCTION DOCUMENTS 56 Version 1.6_April 18, 2012
57 SECTION C: KEY PROJECT CONTACTS List each of the lead BIM contacts for each organization on the project. Additional contacts can be included later in the document. USC s e-builder Project Management Information System (PMIS) will be used for the storage and access of all contract documents including BIMs. Permissions will be set up by USC. Please indicate whether the project contacts listed below will require access to e-builder. ORGANIZATION CONTACT NAME ROLE E BUILDER ACCESS REQUIRED Y/N LOCATION E MAIL PHONE 57 Version 1.6_April 18, 2012
58 SECTION D: BIM PROCESSES AND COLLABORATION PROCEDURES 1. Collaboration Strategies and BIM Processes Describe the collaboration strategies and detailed processes used for developing, coordinating and leveraging the BIMs for the following purposes (as applicable). List the project team participants required for each: a. Existing conditions determining control points, how the data is collected (laser scanning, or other) b. Design reviews c. Design coordination d. Design assist (GMAX contracts only) e. Energy analysis f. Construction coordination g. Design model updates during construction h. Engagement of USC departments i. Record modeling j. Estimating k. Other (describe) 2. Model Delivery Schedule, Application and File Exchange Type Document the information exchanges and file transfers that will occur on the project. DISCIPLINE ARCHITECTURE ARCHITECTURE BIM USE ONE TIME or FREQUENCY DUE DATE or START DATE MODEL FILE MODEL SOFTWARE NATIVE FILE TYPE DESIGN AUTHORING WEEKLY 20 ARCH Revit.RVT 3D COORDINATION WEEKLY COORD Navisworks.NWD.NWF STRUCTURE WEEKLY [DATE] STRUCT DESIGN APP.XYZ MECHANICAL WEEKLY [DATE] MECH DESIGN APP.XYZ ETC VERSION FILE EXCHANGE TYPE.RVT.DWG.NWC.NWD.XYZ.ABC.XYZ.ABC 3. Interactive Workspace and Communication Technology The project team should consider the physical environment it will need throughout the lifecycle of the project to accommodate the necessary collaboration, communication and reviews that will improve the BIM Plan decision making process. Describe how the project team will be located. Consider questions like will the team be collocated? If so, where is the location and what will be in that space? Will there be a BIM Trailer? If yes, where will it be located and what will be in the space such as computers, projectors, tables, table configurations. If not co located, what communication technology (Webex, Gotomeeting, etc.) will be implemented? The project. 58 Version 1.6_April 18, 2012
59 SECTION E: BIM AND FACILITY DATA REQUIREMENTS Describe the methodologies to be used to fulfill the USC FMS data requirements as described in the body of this document. 59 Version 1.6_April 18, 2012
60 SECTION F: BIM AND DATA QUALITY CONTROL Describe the strategy to control the quality of the model and the checks to be performed to assure quality. CHECKS DEFINITION RESPONSIBLE PARTY VISUAL CHECK INTERFERENCE CHECK Ensure there are no unintended model components and the design intent has been followed. Detect problems in the model where two building components are clashing including soft and hard. SOFTWARE FREQUENCY STANDARDS CHECK MODEL INTEGRITY CHECKS Ensure that the BIM standards have been followed (filenaming, discipline colors,etc..) Describe the QC validation process used to ensure that the Project Facility Data set has no undefined, incorrectly defined, incorrectly named or duplicated elements and the reporting process on noncompliant elements and corrective action plans. REVIT WARNINGS CHECKS Etc. 60 Version 1.6_April 18, 2012
61 SECTION G: MODEL STRUCTURE 1. FILE NAMING STRUCTURE: FILE NAMES FOR MODELS SHOULD BE FORMATTED AS: BUILDING ACRONYM _CONSTRUCTION (CON) OR DESIGN PHASE_LEVEL_DISCIPLINE _ ORGANIZATION _DATE (YEAR MONTH DAY) XYZ_50%CD*_ARCH_ LXX_ZXY_???????? ARCHITECTURAL MODEL CIVIL MODEL MECHANICAL (HVAC) MODEL* MECHANICAL (PIPE) MODEL* PLUMBING MODEL* FIRE SPRINKLER* ELECTRICAL MODEL* STRUCTURAL MODEL (STEEL)* STRUCTURAL MODEL (CONCRETE)* STRUCTURAL MODEL (REBAR) COORDINATION MODEL XYZ_50%CD _CIV_ LXX_ZXY_???????? XYZ_50%CD _HVAC_ LXX_ZXY_???????? XYZ_50%CD _MECH_ LXX_ZXY_???????? XYZ_50%CD _PLBG_ LXX_ZXY_???????? XYZ_50%CD _FIRE_ LXX_ZXY_???????? XYZ_50%CD _ELEC_ LXX_ZXY_???????? XYZ_50%CD _STEEL_ LXX_ZXY_???????? XYZ_50%CD _CONC_ LXX_ZXY_???????? XYZ_50%CD _REBAR_ LXX_ZXY_???????? XYZ_50%CD _COORD _ LXX_ZXY_???????? *50%CD could be 100%CD or DD or SD, for example. *CON during construction For example: ANN_CON_HVAC_ L01_GFC_ MODEL STRUCTURE: Describe and diagram how the model is separated, e.g., by building, by floor, by zone, by area, and/or by discipline. 3. MEASUREMENT AND COORDINATE SYSTEMS: Describe the measurement system (Imperial or Metric) and coordinate system (geo referenced) used. 4. MODEL ACCURACY AND TOLERANCES: PHASE DISCIPLINE TOLERANCE DESIGN DOCUMENTS ARCH ACCURATE TO +/ [ # ] OF ACTUAL SIZE AND LOCATION SHOP DRAWINGS MECH CONTRACTOR ACCURATE TO +/ [ # ] OF ACTUAL SIZE AND LOCATION 61 Version 1.6_April 18, 2012
62 SECTION H: PROJECT DELIVERABLES BIM SUBMITTAL ITEM STAGE Design Development APPROXIMATE DUE DATE FORMAT NOTES In this section, list the BIM deliverables Construction for the project and the format in which the information will be delivered. Documents Construction Record Model Close out (.xyz) See Record Model Information Exchange to ensure that the proper information is contained in this model 62 Version 1.6_April 18, 2012
63 SECTION I: ATTACHMENTS List the supporting attachments that are supplementary to this BIM Execution Plan. 63 Version 1.6_April 18, 2012
64 GLOSSARY COBie: (Construction Operations Building Information Exchange) COBie is an information exchange specification for the life cycle capture and delivery of information needed by facility managers. COBie can be viewed in design, construction, and maintenance software as well as in simple spreadsheets. BIM Execution Plan: The BEP defines the uses for BIM on a project along with a detailed process for executing BIM. Geo referencing: A system that links information to a position on the earth s surface. That is, establishing its location in terms of map projections or coordinate systems. e Builder: USC s Project Management Information System. The repository for all USC construction project information. NWF: Navisworks file where only a list with pointers to the files currently loaded is saved, along with the scene's environment, the current view, clash results, if available, and favorite viewpoints (including redlines and comments). To open an NWF file, a Navisworks product is required, such as Review, Simulate, or Manage (not Freedom), as well as access to the original CAD files. NWD: The published version of a Navisworks file with all loaded models and viewpoints saved to a single (NWD) file. This file type can be opened with any of the Navisworks products including Navisworks Freedom (the free viewer). NWC: When you open a CAD file in Navisworks, by default, a corresponding cache file (NWC) is created, which contains all of the conversion details required by Navisworks. To open an NWC file, a Navisworks product is required, such as Review, Simulate, or Manage (not Freedom). Certain Applications, like Revit, will export the corresponding model to an NWC file. IFC: The Industry Foundations Classes is an open, neutral and standardied specification for Building Information Models. DWG: DWG ("drawing") is a binary file format used for storing two and three dimensional design data and metadata. It is the native format for several CAD packages. In addition, DWG is supported nonnatively [2] by many other CAD applications. Shared parameters: Shared parameters are parameters that you can add to families or projects and then share with other families and projects. They give you the ability to add specific data that is not already predefined in the family file or the project template. Co Location: The assembling of the entire BIM design and construction team in a single location to enable instant and direct communication and coordination. Co Location of all team members provides the environment and opportunity to build trust among teammates, while efficiently designing the 64 Version 1.6_April 18, 2012
65 project. Project issues are transparent and solutions evolve in real time because everyone is working in the same physical space. Model Mash up: The process of overlaying as built fabrication BIMs with as designed BIMs in order to compare differences in order to adjust the design BIMs to as built conditions. Omniclass: The OmniClass Construction Classification System (known as OmniClass or OCCS) is a classification system for the construction industry. It incorporates other extant systems currently in use as the basis of many of its Tables MasterFormat for work results and UniFormat for elements. UniFormat: UniFormat, a publication of CSI and CSC, is a method of arranging construction information based on functional elements, or parts of a facility characterized by their functions, without regard to the materials and methods used to accomplish them. These elements are often referred to as systems or assemblies. MasterFormat: MasterFormat, a publication of CSI and CSC, is a master list of numbers and titles classified by work results. It is primarily used to organize project manuals and detailed cost information, and to relate drawing notations to specifications. Consolidated model: An assembled model containing all of the project models in one file. 65 Version 1.6_April 18, 2012
66 REFERENCES Indiana University BIM Guidelines Construction Specifications Institute (CSI). (2011). OmniClass Table 21 Elements. The Secretariat for the OCCS Development Committee. Alexandria, Virginia: Construction Specifications Institute (CSI). Construction Specifications Institute (CSI). (2010). OmniClass Table 23 Products. Construction Specifications Institute (CSI). Alexandria, Virginia: The Secretariat for the OCCS Development Committee. Copyright 2006 the Secretariat for the OCCS Development Committee. All Rights Reserved. General Services Administration (GSA) National Equipment Standard Team (NEST). (2011). GSA National Equipment Standard. Office of Design and Construcion Public Buildings Services, The National 3D 4D BIM Program. Washington, DC: General Services Administration. Copyright 2006 the Secretariat for the OCCS Development Committee. All Rights Reserved. National Institute of Building Sciences. ( ). U.S. National CAD Standard Version 3.1 CD ROM Module 05: Terms and Abbreviations. Washington, DC: National Institute of Building Sciences. The Computer Integrated Construction Research Program. PennState Department of Architecture and Engineering The National BIM Standards US ACKNOWLEDGEMENTS View By View wishes to acknowledge the following people who have been active participants and contributors to the development and review of these guidelines: Tom Leary USC Vice President, Capital Construction and Facilities Management Jose Delgado USC Facilities Management CAD Manager Victor Aspurez Assistant Director, USC FMS Engineering Services John Muse Associate Director, USC FMS Management Information Systems Jay Simons USC Office of the University Architect Igor Starkov President, EcoDomus, Inc. View By View, Inc. 66 Version 1.6_April 18, 2012
2012 BIM Guidelines and Standards (Rev. 00) University at Albany
A. Building Information Modeling (BIM) Guidelines: The Office of AECM will require the submission of BIM modeling files as part of an electronic file submission to the AECM project manager as requested
BIM. Guidelines & Standards for Architects, Engineers, and Contractors. Initiated: Sept. 10th, 2009. Revised: July 1st, 2015
BIM Guidelines & Standards for Architects, Engineers, and Contractors Initiated: Sept. 10th, 2009 Revised: July 1st, 2015 Acknowledgements Indiana University is indebted to those many organizations that
Olilo's AEC Design Services. SrinSoft Inc, Partners of
Olilo's AEC Design Services SrinSoft Inc, Partners of Olilo provides design services that include design and analysis, cost estimation, 3D modeling, 2D drafting, conversion from 2D to 2D, quantity take-off,
All substantial design decisions and budget confirmation shall be resolved for the College to approve the Design Development Submittal.
2.02 DESIGN DEVELOPMENT PHASE GENERAL The Architect shall prepare the Design Development Documents from the approved Schematic Design. The Design Development Documents shall consist of drawings and other
Design Development Quality Management Phase Checklist Project Phase Checklist Series
Best Practices Design Checklist Project Phase Checklist Series Contributed by Micheal J. Lough, AIA, Principal, Integral Consulting The AIA collects and disseminates Best Practices as a service to AIA
Facilities Management
Facilities Management June 29, 2015 THIS PAGE INTENTIONALLY LEFT BLANK University of South Florida BIM Guidelines and Standards Page 2 of 32 BIM Guidelines and Standards Table of Contents SECTION 1: BIM
Facility Summary. Facility Condition Summary. Seattle School District David T. Denny International Infrastructure. Facility Components
Infrastructure Facility Condition Summary Weighted Avg Condition Score Facility Components Systems Surveyor/ Date Done Comments G Sitework.9 Site Improvements Parking Pedestrian Paving Site Development
Autodesk Revit LEARNING PATH BUILDING DESIGN SUITE
Autodesk Revit LEARNING PATH FUNDAMENTALS Duration: 3 days Cost: R5 500 (excl VAT) Revit MEP Duration: 3 days Cost: R5 500 (excl VAT) Revit Structure Duration: 3 days Cost: R5 500 (excl VAT) REVIT ADVANCED
BIM: FOR PROJECT MANAGERS. 2011 CSI Southwest Region Conference Program 1B 8:45am 11:00am
BIM: FOR PROJECT MANAGERS ANA BAKER BRANDON GARRETT 2011 CSI Southwest Region Conference Program 1B 8:45am 11:00am 1 2 3 4 BIM Overview BIM Level of Development Evolution of the Drawing Process BIM Workflow
CITY COLLEGE OF SAN FRANCISCO (CCSF) Building Information Modeling (BIM) Standards for Design-Bid Build Projects. CCSFBIMS Version 1.
CITY COLLEGE OF SAN FRANCISCO (CCSF) Building Information Modeling (BIM) Standards for Design-Bid Build Projects CCSFBIMS Version 1.0 Prepared by: CCSF Facilities Planning & Construction (FPC) Department
Construction Technologies Career Field Pathways and Course Structure
Courses in Structural Systems (DD) Construction Technologies Career Field Pathways and Course Structure PATHWAY COURSES SUBJECT CODE Construction Technology-Core and Sustainable Construction 1 178000 Carpentry
SECTION 3: ANNEX J UNC CHARLOTTE ILM IMPLEMENTATION PLAN (New Section)
University of North Carolina at Charlotte Design and Construction Manual Section 3, Annex J UNC Charlotte ILM Implementation Plan SECTION 3: ANNEX J UNC CHARLOTTE ILM IMPLEMENTATION PLAN (New Section)
Schematic Design: Quality Management Phase Checklist Project Phase Checklist Series
Best Practices : Project Phase Series Contributed by Micheal J. Lough, AIA, Principal, Integral Consulting The AIA collects and disseminates Best Practices as a service to AIA members without endorsement
ST. MONICA FOOD PANTRY HOUSTON, TEXAS
PROJECT MANUAL FOR ST. MONICA FOOD PANTRY HOUSTON, TEXAS OWNER: ST. MONICA CATHOLIC CHURCH 8421 W. MONTGOMERY ROAD HOUSTON, TEXAS 77088 ARCHITECT: C SIX ARCHITECTURE, LLC 4606 F.M. 1960 WEST, STE 400 HOUSTON,
ATTACHMENT A STRUCTURAL INTERIOR DESIGN (SID) REQUIREMENTS
ATTACHMENT A STRUCTURAL INTERIOR DESIGN (SID) REQUIREMENTS 1.0 GENERAL INFORMATION Structural Interior Design includes all building related elements and components generally part of the building itself,
LACCD Building Information Modeling Standards For Design-Bid Build Projects
LACCD Building Information Modeling Standards For Design-Bid Build Projects (LACCD BIMS) Interim Version 2.0 Prepared by: September 9, 2009 TABLE OF CONTENTS 1. INTRODUCTION 1 1.1. Overview 1.2. Main Objectives
School Building Authority of West Virginia BUILDING INFORMATION MODELING (BIM) EXECUTION PLAN SBA FORM 191
School Building Authority of West Virginia BUILDING INFORMATION MODELING (BIM) EXECUTION PLAN SBA FORM 191 Section 1: General 1.0 Alignment with Organizational Vision In the space provided below, read
PROJECT REQUIREMENT, PR 20 VIRTUAL DESIGN & CONSTRUCTION (VDC), BUILDING INFORMATION MODEL (BIM)
PROJECT REQUIREMENT, PR 20 VIRTUAL DESIGN & CONSTRUCTION (VDC), BUILDING INFORMATION MODEL (BIM) A. GENERAL: 1. Summary: Design/Builder will employ VDC and BIM tools to facilitate the construction, coordination,
CPIx on Line. Post Contract-Award Building Information Modelling (BIM) Execution Plan (BEP) Supporting the HMG Construction Strategy.
CPIx on Line Post Contract-Award Building Information Modelling (BIM) Execution Plan (BEP) Project Name: Project Address: Project Number: Date: Document No: Date: March 2013 Revision: R1 Status: Published
ESSENTIAL CURRICULUM ARCHITECTURAL DESIGN ACADEMY
ESSENTIAL CURRICULUM ARCHITECTURAL DESIGN ACADEMY HOWARD COUNTY MARYLAND ARCHITECTURAL DESIGN ACADEMY Architectural Design 1 Introduction / Overview of Course This course will introduce the basic principles
CAD Standards Guideline For Facility Documentation and Construction Projects
CAD Standards Guideline For Facility Documentation and Construction Projects Implemented March 2010 Page 1 of 9 Table of Contents A. Software B. CAD Methods 1. Layer Standards 2. Font 3. Lineweights 4.
Exhibit C: Scope of Work and Schedule of Deliverables
Exhibit C: Scope of Work and Schedule of Deliverables Project Scope of Work Phases: A City Hall Envelope Renovations B City Hall Skylight Replacement C City Hall Chiller Replacement D City Hall Annex Plaza
BUILDING SAFETY UNIT
POLICY Page 1 of 5 SUBMITTAL REQUIREMENTS FOR ONE AND TWO FAMILY DWELLINGS, ADDITIONS AND RENOVATIONS All submittals shall be site specific and designed to the provisions of the 2012 International Residential
BIM GUIDE. Developed for
BIM GUIDE Developed for BIM GUIDE Protocols and Project Execution Plan 1 Table of Contents.. Objective... P. 4.. Roles & Responsibilities... P. 5.. Contract Strategies... P. 8.. Level of Development...
Sample Drawing Package for One and Two Family Dwelling Applications
Sample Drawing Package for One and Two Family Dwelling Applications For a full list of submission requirements, refer to the relevant checklist for your application found on our website: http://vancouver.ca/home-property-development/application-forms-and-checklists.aspx
CAD Standards Guideline For Facility Documentation and Construction Projects
CAD Standards Guideline For Facility Documentation and Construction Projects Page 1 of 12 Table of Contents A. Software B. CAD Methods 1. Layer Standards 2. Font 3. Lineweights 4. External References 5.
1 TABLE OF CONTENTS. 1. BIM Execution Plan. BIM Execution Plan- UF Minor Projects Template UF-000 2 of 20 pages. 1.1. Processes...
1 TABLE OF CONTENTS 1. BIM Execution Plan 1.1. Processes... 3 1.2. Addendum to UF Contracts... 4 1.3. Methodology... 4 1.4. Project Overview / General Information... 4 1.5. Project Collaboration Team...
DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS
DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS NOTICE TO BIDDERS BID FORM INSTRUCTIONS TO BIDDERS CONTRACTOR S BID FOR PUBLIC WORK - FORM 96 MINORITY AND WOMEN S BUSINESS ENTERPRISE PARTICIPATION
COMMERCIAL PLAN SUBMISSION FOR NEW CONSTRUCTION AND/OR RENOVATIONS
COMMERCIAL PLAN SUBMISSION FOR NEW CONSTRUCTION AND/OR RENOVATIONS Permit applicants shall submit three (3) COMPLETE SETS of plans and specifications with each application for a permit. Plans and specifications
Sub-Bid Contractor Update Statement. Tab A - Invitation for Bids. Tab B - Instructions to Bidders
INTRODUCTORY INFORMATION TABLE OF CONTENTS 00 0101 PROJECT TITLE PAGE PROCUREMENT REQUIREMENTS (PROJECT MANUAL) Tab A - Invitation for Bids Tab B - Instructions to Bidders Tab C Bid Form for General Bids
SECTION 00 0110 TABLE OF CONTENTS. H. 00 2115.01 - Proposed Material, Product or Equipment Substitution Request
SECTION 00 0110 PROCUREMENT AND CONTRACTING REQUIREMENTS 1.1 DIVISION 00 -- PROCUREMENT AND CONTRACTING REQUIREMENTS A. 00 0101 - Project Title Page B. 00 0105 - Certifications Page C. 00 0110 - Table
Execution Plan Template Design Modeling
Execution Plan Template Design Modeling NEW CONSTRUCTION By signature below, this Execution Plan is herewith adopted and incorporated into the Agreement, dated, for Professional Design Services between
City of Treasure Island FEMA Cost Breakdown Worksheet For Substantial Improvement / Damage
City of Treasure Island FEMA Cost Breakdown Worksheet For Substantial Improvement / Damage Property Address: Company Name: Contractor Name: Contractor Address: City: State: Zip: License Number: Phone Number
NEW YORK CITY DEPARTMENT OF DESIGN + CONSTRUCTION
NEW YORK CITY DEPARTMENT OF DESIGN + CONSTRUCTION July 2012 BIM Guidelines Michael R. Bloomberg, Mayor David J. Burney, FAIA, Commissioner David Resnick, AIA, Deputy Commissioner TABLE OF Contents Message
State of Connecticut Department of Public Health RADON PROGRAM
State of Connecticut Department of Public Health RADON PROGRAM Scope The Connecticut Department of Public Health (DPH) Radon Program is providing this information for contractors who decide to build radon
OPTIONAL IMAGE OR RENDERING OF BUILDING OR SITE
OPTIONAL IMAGE OR RENDERING OF BUILDING OR SITE MIT BIM Execution Plan v3.2 2 MIT Project Name MIT Project Number DEVELOPED IN COLLABORATION WITH Construction Company Architect AND Engineer MIT BIM Execution
DRAFT BUILDING INFORMATION MODELING SCOPE OF SERVICES AND REQUIREMENTS FOR ARCHITECTS AND ENGINEERS
DRAFT BUILDING INFORMATION MODELING SCOPE OF SERVICES AND REQUIREMENTS FOR ARCHITECTS AND ENGINEERS Table of Contents 1 Introduction...3 1.1. Statement of Purpose...3 1.2. BIM Competence and Responsibilities...3
Effective Collaboration using Revit Structure and AutoCAD MEP
REVIT STRUCTURE Effective Collaboration using Revit Structure and AutoCAD MEP This white paper explains how structural engineers using Revit Structure software and mechanical/electrical/plumbing (MEP)
ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1
KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1 PART 1 - GENERAL 1.01 RELATED DOCUMENTS: SECTION 16050 A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1
BIM and Digital Fabrication
REVIT BUILDING INFORMATION MODELING BIM and Digital Fabrication This whitepaper examines how structural building information models are being used for the digital fabrication of structural steel and the
2301.1 Scope: Communications and Electronic Systems addressed in this section include:
Chapter 23 COMMUNICATIONS / ELECTRONIC SYSTEMS SECTION 2301 - GENERAL 2301.1 Scope: Communications and Electronic Systems addressed in this section include: 1. Fire Alarm System 2. Telecommunication and
What s New in Autodesk Revit 2014
Building Design Suite 2014 What s New in Revit 2014 * Revit 2014 software is only available as part of the Building Design Suite 2014 Premium and Ultimate Editions. New & Enhanced Features Platform & For
Quality Control and Quality Assurance Guide
Quality Control and Quality Assurance Guide Bridge Division, Design Section October 2013 Table of Contents Chapter 1 About this Guide... 3 Chapter 2 Goals and Objectives... 5 Chapter 3 Participants...
city of edmonds development information
#B17 city of edmonds development information Commercial Kitchen Hood & Hood Fire Suppression System Permit Submittal Requirements PERMIT REQUIRED: CODES: FEES: A Commercial Kitchen Hood Mechanical Permit
EXHIBIT "A" RESPONSIBILITIES AND SERVICES OF ARCHITECT TABLE OF CONTENTS
EXHIBIT "A" RESPONSIBILITIES AND SERVICES OF ARCHITECT TABLE OF CONTENTS A. SCOPE OF PROJECT... 1 B. BASIC SERVICES... 1 C. PRE-DESIGN AND START-UP SERVICES... 4 D. SCHEMATIC DESIGN PHASE... 7 E. DESIGN
Certified Instructors & Curriculum
Our Promise. TPM is dedicated to provide the most extensive and high-quality training programs to help you maximize your investment. Although the investment in time and money may seem substantial, it will
Building Information Modelling (BIM); How it Improves Building Performance. R.P. Kumanayake Lecturer, Department of Civil Engineering
Building Information Modelling (BIM); How it Improves Building Performance R.P. Kumanayake Lecturer, Department of Civil Engineering R.M.P.S. Bandara Lecturer, Department of Mechanical Engineering Faculty
17,280 square feet Overview:
CENTRAL OFFICE Located at 167 Boston Post Road, East Lyme, Connecticut, the Central Office was built in 1916 as the original Flanders Elementary School and remains connected to the current school. The
T170 Interior Design Technology MTCU Code 61833 Program Learning Outcomes
T170 Interior Design Technology MTCU Code 61833 Program Learning Outcomes Synopsis of the Vocational Learning Outcomes The graduate has reliably demonstrated the ability to 1. analyze a client's needs
TABLE OF CONTENTS. INTRODUCTION... 5 Advance Concrete... 5 Where to find information?... 6 INSTALLATION... 7 STARTING ADVANCE CONCRETE...
Starting Guide TABLE OF CONTENTS INTRODUCTION... 5 Advance Concrete... 5 Where to find information?... 6 INSTALLATION... 7 STARTING ADVANCE CONCRETE... 7 ADVANCE CONCRETE USER INTERFACE... 7 Other important
Sample Company SECTION 019113 GENERAL COMMISSIONING REQUIREMENTS PART 1 GENERAL 1.1 SUMMARY AND CONTRACT RESPONSIBILITIES
SECTION 019113 GENERAL COMMISSIONING REQUIREMENTS PART 1 GENERAL 1.1 SUMMARY AND CONTRACT RESPONSIBILITIES A. The Owner will contract separately and directly for the majority of the commissioning work
TABLE OF CONTENTS 1 2 APPENDIX A. MPA BIM USES EXISTING CONDITIONS MODELING DESIGN AND BUILDING SYSTEM AUTHORING ANALYSIS AND REPORTING
APPEN DIX A // MPA BIM GU ID ELINE S 1 EXISTING CONDITIONS MODELING 1.1 BIM Project Site Modeling Also Infrastructure Modeling 1.2 Surrounding Site Modeling 1.3 Existing Conditions Laser Scanning 1.4 Existing
Professional CAD System
Professional CAD System > ARCHITECTS site plans > BUILDERS > RESIDENTIAL DESIGNERS floor plans elevations 3D models details sigma design BuildersCAD Complete System Only $ 995 Professional CAD System High
Revit MEP. Autodesk Navisworks
What is BIM? Autodesk BIM is an intelligent model-based process that helps owners and service providers achieve business results by enabling more accurate, accessible, and actionable insight throughout
BIM UNDERSTANDING THE PROCESS The State of the Art Tool in Design and Construction SPONSORED BY SAME, DC POST IN ASSOCIATION WITH ACEC M/W
BIM UNDERSTANDING THE PROCESS The State of the Art Tool in Design and Construction SPONSORED BY SAME, DC POST IN ASSOCIATION WITH ACEC M/W Insanity: doing the same thing over and over again and expecting
Exterior Elevated Elements Inspection Guidelines
Exterior Elevated Elements Inspection Guidelines Planning and Development 1. Guideline Purpose These guidelines are intended to assist practicing professionals in complying with Berkeley Municipal Code
Certification: Building Plans Examiner. Exam ID: B3
Certification: Building Plans Examiner Exam ID: B3 Scope: A Building Plans Examiner will be responsible for reviewing submitted plans to determine if they meet the requirements of the various Building
MTA UNIVERSAL STATION PEDESTRIAN BRIDGE Los Angeles, CA. Project Manual and Specification 100% PE SUBMITTAL TABLE OF CONTENTS
Los Angeles, CA Project Manual and Specification DIVISION 1 GENERAL CONDITIONS 01 01 10 STATEMENT OF WORK 01 11 00 SUMMARY OF THE WORK 01 14 05 METRO (OWNER) - DIRECTED STOPPAGES 01 20 00 PRICE AND PAYMENT
Building Code Clarifications - 7. Fire Resistance
Building Code Clarifications - 7. Fire Resistance 7.1 (15-12-030) Use of combustibles in Type III construction roof assemblies Code Section (15-12-030) Use of Combustibles was revised on May 17, 2000,
Effective Collaboration
AUTODESK BUILDING SOLUTIONS Effective Collaboration Exporting Revit Architecture Models as ACIS Solids for Use in AutoCAD MEP The intent of this paper is to explain a process by which architects using
SAMPLE SCHEDULE OF VALUES APPLICATION & CERTIFICATE FOR PAYMENT
SAMPLE SCHEDULE OF S 1.00 General Conditions 1.01 Project Management 1.02 General Superintendent 1.03 Superintendents 1.04 Safety Engineer 1.05 Scheduling 1.06 Field Engineering 1.07 Bonds 1.08 Trailer
SECTION 23 05 12 GENERAL PROVISIONS FOR HVAC WORK
SECTION 23 05 12 GENERAL PROVISIONS FOR HVAC WORK 1 GENERAL 1.1 GENERAL REQUIREMENTS A. This Section is coordinated with and complementary to the General Conditions and Supplementary General Conditions
Element Z General Design Requirements Owner Standards and other Requirements
Element Z General Design Furniture and Accessories PART 1 - REQUIREMENTS FOR WORKING WITH MD ANDERSON PLANNER DESIGNER 1.01 OVERVIEW A. The MD Anderson Planner/Designer shall participate in the space,
D Sample Notices to Property Owners, Sample Affidavits, and Other Material
D Sample Notices to Property Owners, Sample Affidavits, and Other Material These samples are offered to illustrate specific points in the Desk Reference. States and communities should examine them carefully
BUILDING INFORMATION MODELING SCOPE OF SERVICES AND REQUIREMENTS FOR CONSTRUCTION CONTRACTOR IN A DESIGN- BID-BUILD PROCESS
BUILDING INFORMATION MODELING SCOPE OF SERVICES AND REQUIREMENTS FOR CONSTRUCTION CONTRACTOR IN A DESIGN- BID-BUILD PROCESS Final Version March 16, 2011 TABLE OF CONTENTS Page Contents 1. Introduction...
EAST LYME HIGH SCHOOL
Overview: 1971 N 1966 GYM 1966 CLASSROOM WING 1966 AUD. 1971 GYM 1998 1998 POOL EAST LYME HIGH SCHOOL Original 1966 Building: The original East Lyme High School was constructed in 1966 and was composed
Saint Cloud Business Center
Saint Cloud Business Center 14 7th Avenue North Saint Cloud, MN 56303 For Sale Located on 7th Avenue in the heart of downtown across from the Court House Square. A large professional reception area with
When is a Permit Required? What Types of Permits are Required? The most common types of projects that require permits are:
When is a Permit Required? The most common types of projects that require permits are: -New Houses or buildings -Room Additions or Expansions -Structural repairs, remodeling and alterations -Accessory
OPEN ITEMS LIST - CONSTRUCTION Project Name: East Central Middle School - Jackson County CLA#: 11003
OPEN ITEMS LIST - CONSTRUCTION Project Name: East Central Middle School - Jackson County CLA#: 11003 No. Discipline Sent to Name Item Date Noted Date Resolved How item was resolved Electrical Contractor
How to Estimate the Cost of Interior Building Finishes from Schematic Drawings. CPE Candidate No. 0714108. December 2014
How to Estimate the Cost of Interior Building Finishes from Schematic Drawings CPE Candidate No. 0714108 December 2014 1 How to Estimate the Cost of Interior Building Finishes from Schematic Drawings Table
REVEWED BY: Ross Rogien B.O/P.R. ADDITIONAL REVIEW(S) REQ.-FIRE DEPT Y/N
PLAN REVIEW FOR: PROJECT NAME: OWNER: ARCH/DESIGNER: ADDRESS: Ph/Fx: Plans Dated: E-mail: Sealed By: Estimated Project Cost - $ REVEWED BY: Ross Rogien B.O/P.R. ADDITIONAL REVIEW(S) REQ.-FIRE DEPT Y/N
Slavic Village Building Condition Review
Slavic Village Building Condition Review Slavic Village Development May 8, 2015 Page 1 EXECUTIVE SUMMARY City Architecture was commissioned by Slavic Village Development to review five existing facilities
3Dcities INDIA. www.3dcindia.com. Architecture and Engineering Outsourcing Company since 1999
3Dcities INDIA Architecture and Engineering Outsourcing Company since 1999 www.3dcindia.com We are an India based organisation provides a range of products and services linked to our core discipline of
#506 New Multi-Family Buildings & Additions Plan Intake Submittal Checklist
#506 New Multi-Family Buildings & Additions Plan Intake Submittal Checklist Case #: Date: Project Name: Site Address: Application Submittal Building permit applications and plans can be submitted to the
BIM and Lean Construction Can BIM remove waste from construction processes?
Tekla European BIM Forum 2014 BIM and Lean Construction Can BIM remove waste from construction processes? Assoc. Professor Rafael Sacks What is Lean Construction? Waste in construction? Lean and BIM Synergies
BIM Extension into Later Stages of Project Life Cycle
BIM Extension into Later Stages of Project Life Cycle Pavan Meadati, Ph.D. Southern Polytechnic State University Marietta, Georgia This paper discusses the process for extending the implementation of the
Requirements for Building Application Submission
THE DEVELOPMENT CONTROL AND PLANNING BOARD P O Box 597 Phone: 869 465-2277 Bladen Commercial Development Fax: 869 465-5842 Basseterre, St. Kitts Email: [email protected] To: Architects, Designers
Gramercy Place Condo Association, Inc.
Gramercy Place Condo Association, Inc. UNIT MODIFICATION REQUEST Date of Application: Name of Owner (s): Telephone: (Home) (Cell) E-Mail: Anticipated start date: Anticipated ending date: Permission is
STATE OF MINNESOTA. BIM GUIDELINE State of Minnesota s Facilities Administration Data Capture Plan
STATE OF MINNESOTA BIM GUIDELINE State of Minnesota s Facilities Administration Data Capture Plan January 2014 TABLE OF CONTENTS GENERAL INFORMATION BUILDING INFORMATION MODELING (BIM)... 1 PURPOSE OF
WESTERN MICHIGAN UNIVERSITY
WESTERN MICHIGAN UNIVERSITY Facilities Management Department DeVon Miller Building Commissioning Administrator 1 INTRODUCTION DeVon C. Miller, CPMP, LEED AP Building Commissioning Administrator Engineering
RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS
RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS The following guidelines are intended to assist with the permit acquisition process with regard to Plumbing Alterations. Not all information, or additional
Using the Autodesk Revit GSA Spatial Template
Autodesk Revit Template for the U.S. General Services Administration Using the Autodesk Revit GSA Spatial Template This document helps you to get started in using the GSA Spatial Template Revit file in
CITY OF BERKELEY BUILDING PERMIT DETAILED CHECKLIST
CITY OF BERKELEY DETAILED CHECKLIST This checklist will assist you in preparing plans for submittal with a building permit application. Alterations, additions and remodeling projects may not require all
WHITE PAPERS. Food Processing Plant Design
WHITE PAPERS Food Processing Plant Design Preface The design of your food processing plant can be a lengthy and tedious process, but is where the most critical decisions will be made. Your architects and
necessary for years of satisfactory service. SmartBlock insulating form concrete walls share the
Chapter 7 PLUMBING AND ELECTRICAL 7.1 Introduction to Plumbing and Electrical Consideration of support services such as plumbing and electrical systems from the preliminary schematics phase through final
Civil Engineering and Architecture (CEA) Detailed Outline
Civil Engineering and Architecture (CEA) Detailed Outline Unit 1: Overview of Civil Engineering and Architecture (23 days) Lesson 1.1: History of Civil Engineering and Architecture 1. Many features of
NECESSITY OF SCHOOL CONSTRUCTION STAGE III DESIGN REVIEWS
NECESSITY OF SCHOOL CONSTRUCTION STAGE III DESIGN REVIEWS Rhode Island Department of Education School Building Authority 255 Westminster Street, Providence, RI 02909 Telephone (401)222-4600 Website: www.ride.ri.gov
Excerpts from the Canadian National Building Code (NBC)
Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more
How To Design A Bim Project
BIM Virtual Construction & Integrated Project Delivery Randy LaNear BIM Manager Barnhart - Heery Synonyms & Related Terms Integrated Practice Integrated Project Delivery Virtual Building (Environment)
PDmB, Inc. Definitions
Page 1 of 11 Definitions S Satisfactory Meets industry standards for proper material and installation NP Not Present Condition or item was not present at time of inspection NI Not Inspected Condition or
Coordinating and Sharing Information with Revit Architecture and Revit Structure Best Practices!
Revit Architecture and Revit Structure Best Practices! Erleen Hatfield Thornton-Tomasetti Uk Jung SE304-1 This class identifies best practices using Revit Architecture and Revit Structure for sharing and
Inspecting to a higher standard.
Inspecting to a higher standard. Rob Hopkin Silver Spring, MD 20902 Monday, June 2, 2014 ProTec Inspection Services Inc. 19736 Selby Ave Poolesville, MD 20837 301-972-8531 www.protec-inspections.com [email protected]
Bureau Veritas Contact Information
Bureau Veritas Contact Information Permit Submittal The permit documents and fees will be submitted to the city. Submittal documents should be complete to expedite plan review and permit issuance. Please
2.4 Hardcopy submittals shall be provided at adequate size so that all notes are readable.
DESIGN EQUIEMENTS POJECT DELIVEABLES CHECKLISTS GENEAL INFOMATION 1.1 The following is a checklist to be used as a guide for the required deliverables for the Schematic Design phase. 1.2 Schematic Design
A WORKFLOW ANALYSIS FOR BIM SOFTWARE: ARCHITECTURAL AND MECHANICAL ENGINEERING DEPARTMENT OF ARUP TURKEY
ISTANBUL TECHNICAL UNIVERSITY FACULTY OF ARCHITECTURE DEPARTMENT OF DESIGN COMPUTING BIM 2037 / BUILDING INFORMATION MODELS INSTRUCTOR: Salih OFLUOĞLU A WORKFLOW ANALYSIS FOR BIM SOFTWARE: ARCHITECTURAL
Occupancy: Assembly (A-3) and Business -Includes offices, seminar rooms, classrooms, and café facility. Duke University Medical School
Introduction Background The Duke School of Nursing building offers a new three-story state of the art facility that has helped strengthen the quality and integrity of the School of Nursing at Duke. The
SECTION 11 78 13 MORTUARY REFRIGERATORS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in