Medium Voltage Instrument Transformers
|
|
|
- Logan Ross
- 9 years ago
- Views:
Transcription
1 Medium Voltage Instrument Transformers Standard Transformers
2 RITZ Instrument Transformers GmbH Core competency Under the trading name RITZ Instrument Transformers GmbH RITZ has been pooling its activities to gather new strengths since The tradition and knowledge of the parent company RITZ Messwandler Hamburg and the subsidiary RITZ Messwandler Dresden (TuR) has been united with the companies Wandler- und Transformatoren-Werk Wirges (WTW) and Messwandlerbau Bamberg (MWB) under this name. This merger unites a total of more than two hundred years of knowhow in instrument transformers production. In addition, RITZ has decided to concentrate on the core business of medium voltage and low voltage transformers in which the high voltage division is sold. The resources gained through this shall now be applied for additional innovations and quality standards in the medium and low voltage products. RITZ is therefore securing its position on the global market. The overseas corporations of RITZ Instrument Transformers GmbH in Austria (Marchtrenk), Hungary (Kecskemét), China (Shanghai) and USA (Hartwell) strengthen the company s position on the international market. 2
3 Contents Introduction Medium Voltage Instrument Current and Voltage Transformers 1.1 General Design Current Transformer Choice limitations of the Rated Burden Definitions Metering Current Transformer Protective Current Transformer Reconnection of Current Transformer Over Current Range Service and Grounding Capacitive Divider Voltage Transformer V-Connection of Two Double Pole Insulated Voltage Transformer General Design Definitions Service and Grounding Ferroresonances Service Conditions Altitude Test Voltages and Insulation Levels for Instrument Transformers Insulation Class 14s 1.8 Partial Discharge Test Standards Products Product Selection List Current Transformer Indoor up to 72,5 kv Support Type Current Transformer Indoor Block-Type (narrow type) ASS 12 17, , Support Type Current Transformer Indoor Block-Type GSW 12/ Support Type Current Transformer Indoor Block-Type ASN 12 17, Current Transformer Indoor GI 52 72, High Current Transformer Indoor GSSO 12 17, Bushing Current Transformer with Fixed Bars Indoor GDS 12 17, Current Transformer Outdoor up to 72,5 kv Support Type Current Transformer Outdoor Compact GIFK 12 17, Support Type Current Transformer Outdoor Standard GIFS 12 17, Current Transformer Outdoor Head Type GIF 10 17, , Voltage Transformer Single Pole up to 72,5 kv Indoor Voltage Transformer Indoor VES 12 17, Voltage Transformer Indoor GSE 12/ Voltage Transformer Indoor VEN 12 17, ,5 29 Outdoor Voltage Transformer Outdoor VEF 12 17, Voltage Transformer Outdoor Head Type VEF 52 VEF 72, Voltage Transformer Double Pole up to 36 kv Indoor Voltage Transformer Indoor VZS 12 17, Voltage Transformer Indoor GSZ 12/ Voltage Transformer Indoor VZN 12 17, Outdoor Voltage Transformer Outdoor VZF 12 17, Low Voltage Instrument Transformers 36 Cast Resin Insulated Bus Bar Systems up to 72,5 kv, 6500 A 37 Cast Resin Insulated Power Transformers up to 40,5 kv, 25 MVA 38 Electronic Instrument Transformers & Sensors Customised Cast Resin Parts 39 Medium Voltage Instrument Transformers 3
4 1.0. Medium Voltage Current and Voltage Transformers 1.1 General Instrument transformers are transformers, which convert high currents or voltages into measurable and standardized currents or voltages, which are proportional and in-phase to the primary signal. They are intended to supply electrical measuring instruments, meters, relays or other electrical devices. CT according to DIN-Design PT according to DIN-Design Current Transformer A current transformer is designed to convert the primary rated current which flows through the primary winding. The secondary winding must generally be short circuited at any time, otherwise dangerous high voltages can occur at the secondary terminals. The secondary connected devices are connected in series. Current Transformers can be equipped with one or more independent magnetic cores with equal or different characteristics for measuring, metering and/or protective purposes. Voltage Transformer Voltage transformers have only one iron core with attached secondary winding (s). If an open delta circuit (da-dn) is necessary, an additional winding can be provided for single pole insulated transformers. It is extremely dangerous to short circuit a voltage t ransformer. For single pole insulated transformers the end of the primary winding is grounded as N inside of the secondary terminal box, and must not be removed during operation. 4
5 1.2 Design Instrument transformers can be differentiated into different designs through their specification and application. The following basic designs exit: Supporting types according to DIN (only for indoor use) or designed according to customer requirement for indoor and outdoor application Bushing types for indoor and outdoor application Voltage transformers, single or double pole insulated, for indoor and outdoor application. Support type current transformers for indoor applicationss Single pole voltage transformer for indoor applications High current bushing type current transformer Outdoor voltage transformer with characteristic shields to extend the creepage distance Medium Voltage Instrument Transformers 5
6 1.3 Current Transformer Rating Plate Primary Conductor (W1) Cast Resin Current transformers are transformers which convert high currents into measurable and standardized currents proportional and in-phase to the primary signal. A current transformer can be equipped with one or more independent ferromagnetic cores made of silicon or nickel iron steel. Terminal Box sealable Earthing Terminal The secondary winding (W2) is symmetrically wound around the iron core. This causes a very intensive magnetic coupling of the primary to the secondary winding. The number of turns of the secondary winding depends on the ratio between the primary and the secondary rated current. The iron core(s) and the secondary winding must be grounded. Depending on the primary rated current and the short time current (Ith), the primary winding (W1) consists of one solid winding (primary conductor) or a number of turns. The primary winding is designed for the full rated current and has the same potential as the busbar. The highest system voltage (phase to phase voltage) has to be considered for the design of the transformer with respect to its insulation between the primary and the secondary winding. The windings W1 and W2 as well as the iron core(s), together with the secondary winding(s) are completely resin-embedded and casted in a single production step by using a pressure gelation casting process. Cable Bushing Secondary Terminals Core 1 Core 2 (W2) (W2) General design sample of a current transformer The resin body is mounted on a metal plate. The secondary terminals are embedded in the resin body and protected by a plastic box. The cover of the box is removable and can be sealed. Each secondary terminal can be separately grounded inside the secondary terminal box. The grounding screw is connected to the bottom plate. The terminal box is equipped with two or three removable cable plugs, which makes wiring easy. The ends of the primary winding are provided with flat t erminals ( P1/P2 ), made of copper or brass alloy, and l ocated at the top of the resin body. Bottom Plate A M8 grounding screw is available on the bottom plate for grounding the current transformer. Grounding can take place directly on the frame of the switchgear or on a separate grounding bar. 6
7 1.3.1 Choice Limitations of the Rated Burden Especially for small rated primary currents, and high rated short time thermal currents (Ith), the rated burden of a current transformer is limited due to the maximum permissible kaw-value (ampere turns). In this case, information should be requested from the manufacturer. If the rated burden of a current transformer is calculated according to the formula Rated Continuous Thermal Current This is the value of the current which can be permitted to flow continuously through the primary winding while the secondary winding is connected to the rated burden, without the rise in temperature exceeding the values specified. It is common practice that the rated continuous thermal current is equal to the rated current but a higher current can also be defined. P N = (AW) 2. Q Fe. K l Fe [VA] Rated Short Time Thermal Current The r.m.s value of the primary current is the value which a transformer will withstand for one or three seconds without suffering harmful effects, should the secondary wiring be short circuited. AW Q Fe K l Fe primary ampere turns iron cross section (mm2) constant ferromagnetic circuit (cm) it becomes evident that, if the ampere turns (AW) can be doubled, a burden which is four times higher can be achieved. Physically speaking, however, this is not always feasible, because the ampere turns are limited by the rated dynamic current (Idyn). The reason for this is the force of the magnetic field intensity which, in case of a short circuit, attempts to mutually balance the individual primary windings. Furthermore, the maximum rated burden depends on the size of the resin body Definitions Rated Dynamic Current The peak value of the primary current is the value which a transformer will withstand, without being damaged electrically or mechanically by the resulting electromagnetic forces, should the secondary winding be short circuited Burden Burden is the impedance of the secondary circuit and power factor in ohms. The burden is usually expressed as the apparent power in volt amperes (VA) at a specified power factor and at the rated secondary current Rated Burden The value of the burden is based on the accuracy requirements of this specification Rated Primary and Secondary Current The value of the primary and secondary current indicates the performance rating of the transformer. A common practice is to use a secondary rated current of 1 or 5 A. The primary rated current depends on the network and is defined by the end user. Economically speaking, a secondary rated current of 1A should be chosen in order to keep the rated burden low, especially for long wiring distances. P N = I² R+P B Medium Voltage Instrument Transformers 7
8 Error Limits The composite error for metering cores has to be higher than 10% to protect the connected metering devices in case of over currents. In the opposite the composite error for protection cores at the rated accuracy limit of the primary current should be smaller or equal 5% (5P) or 10% (10P) to secure a proper tripping of the connected protection devices Instrument Security Factor In the event of a system fault when a current is flowing through the primary winding of a current transformer, the apparatus is offered the highest level of protection by the transformer when the security factor value (FS) of the rated instrument is small Metering Current Transformer This is a current transformer intended to supply indication instruments, integrating meters and similar apparatus Accuracy Class This is the limit of the permissible percentage of current error at the rated current. In general, the limits of current error are calculated for a range between 1% up to 120% of rated current. Permissible limits for current error (F i ) and phase displacement (δ i ) according to IEC Accuracy Class ± percentage of current error at percentage of rated current ± phase displacement in minutes at percentage of rated current Measuring Current Transformers 0,1-0,4 0,2 0,1 0, ,2S 0,75 0,35 0,2 0,2 0, ,2-0,75 0,35 0,2 0, ,5S 1,5 0,75 0,5 0,5 0, ,5-1,5 0,75 0,5 0, ,0 1,5 1,0 1, Protective Current Transformers 5P P Instrument Transformer Error Limits for Accuracy Class 0.1 Instrument Transformer Error Limits for Accuracy Class 0.2s; 0.2 Rated Current I N [%] Rated Current I N [% Instrument Transformer Error Limits for Accuracy Class 0.5s; 0.5 Instrument Transformer Error Limits for Accuracy Class 1 Error F [%] Error F [%] Error F [%] Error F [%] Rated Current I N [%] Rated Current I N [%] 8
9 1.3.4 Protective Current Transformer A current transformer intended to supply protective relays. Protective current transformers are marked with the letter P Special Request On request current transformers can be designed for higher extended current ratings than the standard value of 120%. Additional typical values are for example 150% and 200%. This means that accuracy is guaranteed at 150% or 200% of the rated primary current Reconnection of Current Transformer In case of changeable ratios, for example extension of nominal rated current, it is possible to design the transformer with primary reconnection or secondary tapping Primary Reconnection The primary reconnection can only be used for primary currents up to 2 x 600A and for current transformers which have a primary winding consisting of several primary turns. The ratio of the reconnection is always 1:2. P1 C1 C2 P Secondary Tapping For secondary tapping the secondary winding is wound on the iron core in two or more separate sections. The ends of these are connected to the secondary terminals. Changeover will be performed at the secondary side. In the case that the primary rated current should be changed to the lower current, the accuracy class between 0.2 and 3 will decrease at approximately the square value of the reduction in primary current. The ratings of the protective cores of class 5P or 10P decrease almost proportionally to the reduction of the primary current. The values of the rated short time thermal current, as well as the dynamic current, remains the same at all ratios. P1 S1 S3 high rated current Circuit Diagram Secondary Tapping S1 S2 S3 P2 S1 S2 low rated current Over Current Range In the event of a system fault, the secondary rated current increases in proportion to the primary rated current up to the limit of the primary current. The error limits will only be observed of the secondary burden is equal to the rated burden. If the burden is different to the rated burden, the instrument security factor will be changed. 1S1 1S2 C1 C2 low rated current P1/C1 P2/C2 high rated current Circuit Diagram Primary Reconnection For primary reconnection, the primary winding consists of two winding sections (P1-C2 & C1-P2) which can either be connected in series or parallel. The changeover will be done at the primary side by using joint bars. In case of primary reconnection the rated burden, the accuracy, and the instrument security factor remains unchanged. IS/ISN 10 5 Protection core 5P10 Fg > 10 % Fg < 5 % Measurement core Cl. 1Fs IP/IPN Medium Voltage Instrument Transformers 9
10 1.3.7 Service and Grounding The secondary winding must generally be connected to a burden or be short circuited at all times; otherwise dangerous high voltages can occur in the secondary terminals. One end of the secondary winding as well as all other metal parts of the transformer must be grounded. All supporting type current transformers can be equipped with a capacitive divider. The capacitive divider is embedded in the resin body. The capacity C 2W is connected to the terminal CK inside of the secondary terminal box. A surge arrester is connected between the terminals CK and earth and is intended to limit the output voltage. Secondary terminal with grounding screw of a current transformer type ASS Capacitive Divider With reference to the guidelines of the modern switch gear it is required, and it is common practice with respect to safe handling of the switch gear, that the doors and all coverings can only be opened after the panel is de-energized. This will be achieved by using a voltage indicator which is mounted in the front door of the panel. The voltage indicator consists of a capacitive divider splitting the voltage U between phase and ground into two voltages, namely U1 and U2. An indicating device, which is connected between the terminal CK inside of the secondary terminal box and earth. Circuit diagram capacitive divider C 2A voltage indicator C 1 upper capacity C 2W lower capacity C 2L lead capacity Ck terminal L high voltage U line to ground voltage U 1 partial voltage at C 1 U 2 partial voltage at C 2 (C 2W + C 2L + C 2A ) V surge arrester Indication range: Smaller than 0,1 x U N no indication Equal or greater than 0,4 x U N safe indication 10
11 1.4 Voltage Transformer Voltage transformers are transformers which convert high voltages into measurable and standardized voltages proportional and in-phase to the primary signal. Voltage transformers have only one magnetic iron core with attached secondary winding (s). Voltage transformers can be provided either as single pole or double pole insulated designs. An additional winding can be provided for single pole insulated transformers (da-dn) if necessary for an open delta circuit V-Connection of Two Double Pole Insulated Voltage Transformers When using two double pole insulated transformers connected in V-connection, it must be strictly observed that the secondary winding(s) of only one of the two transformers is grounded. This is in order to avoid a short circuit between these two transformers. A N a n da dn Schematic single pole insulated voltage transformer with an open delta winding A a B b Schematic V-connection General Design Voltage transformers have only one magnetic iron core. For single pole insulated voltage transformers the secondary winding(s) are attached directly to the grounded iron core. In single pole insulated transformers the secondary winding(s) are directly attached to the grounded iron core. In double pole insulated voltage transformers the insulation between primary and secondary winding(s) has to be designed for one half of the phase to ground voltage. The secondary windings are designed to withstand a test voltage of 3 kv against each other. Schematic double pole insulated voltage transformer It is extremely dangerous to short circuit a voltage transformer. The end of the primary winding in single pole insulated t ransformers is grounded as N inside of the secondary terminal box, and must not be removed during operation. General design sample of a single pole voltage transformer Medium Voltage Instrument Transformers 11
12 The high voltage winding as well as the secondary winding(s) are completely embedded in resin and casted in a single production step by using a pressure gelation casting process. The resin body is mounted on a metal plate. The secondary terminals are embedded in the resin body and protected by a plastic box. The cover of the box is removable and can be sealed. Each secondary terminal can be separately grounded inside the secondary terminal box. The grounding screw is connected to the bottom plate. The terminal box is equipped with two or three removable cable plugs, which makes wiring easier Rated Transformation Ratio The ratio of the rated primary voltage to the rated secondary voltage Limits of Voltage Error and Phase Displacement The voltage error (Fu) and phase displacement (δu) at the rated frequency shall not exceed the values given in the f ollowing table at any voltage between 80% and 120% of rated voltage, and with burdens between 25% and 100% of the rated burden and a power factor of 0.8. The end(s) of the primary winding are provided with inserts (M10) made of copper or brass alloy, and located at the top of the resin body. A M8 grounding screw is available on the bottom plate for grounding the voltage transformer. Grounding can take place directly on the frame of the switchgear or on a separate grounding bar Definitions Highest Voltage for Equipment The highest r.m.s. phase to phase voltage for which a transformer is designed with respect to its insulation Rated Primary and Secondary Voltage The value of the primary and secondary voltage, which appears in the designation of the transformer, and on which its performance is based. The values are indicated in the transformer rating plate. accuracy class ± voltage error (%) ± phase displacement (minutes) 0,2 0,2 10 0,5 0, Rated Output The value of the apparent power (in VA at a specified power factor), which the transformer is intended to supply to the secondary circuit at the rated secondary voltage, and with rated burden connected to it Rated Burden The apparent resistance of the connected burden including the wiring on which the accuracy requirements are based Thermal Limiting Output The value of the apparent power with reference to the rated voltage, which can be taken from a secondary winding at the applied rated primary voltage, without exceeding the limitations of the rise in temperature. 12
13 Rated Thermal Limiting Output of the Residual Voltage Winding The thermal limiting output of the residual winding shall be specified in volt ampere (VA) in relation to the secondary voltage with the unit power factor. The preferred values are given in the IEC-Standard. Since the residual windings are connected in an open delta circuit, these windings are only loaded under fault conditions. Therefore, a maximum duration of 8 hours for example, can be chosen Rated Voltage Factor The rated voltage factor is determined by the maximum operating voltage depending on the system grounding conditions. In single pole insulated transformers, it is common practice to use a rated voltage factor of 1,9 x the rated voltage for a load duration of 8 hours. The rated factor is defined as 1,2. UN for all other types Reconnection of Voltage Transformer Due to dielectric reasons the reconnection of a voltage transformer is only possible by secondary tapping. A a1 a2 The ends of the winding are connected to the secondary terminals. Changeover will be performed at the secondary side. In the case that the primary rated voltage is to be changed to the lower voltage, the accuracy class remains unchanged. The rated burden decreases at approximately the square value of the reduction in the primary voltage Service and Grounding Contrary to current transformers, voltage transformers must never be short circuited to the secondary side. The N t erminal is grounded to the bottom plate in the secondary terminal box and may never be removed when in service. Each secondary terminal can be grounded inside the secondary terminal box. N n Secondary part with earthing terminal of the voltage transformer types VES/VEN Ferroresonances In electrical installations ferroresonances can occur if the following criteria are present: Use of single pole insulated voltage transformer The network is ungrounded (insulated neutral starpoint) Voltage surges caused by prior switching operations In such a case an oscillating circuit between the earth capacity (C e ) and the transformer inductance (L w ) will occur, which will lead to a very intensive voltage increase and subsequently, saturation of the iron core of the transformer. Overheating of the iron core as well as the materials used inside the primary winding is the consequence. The high temperature leads to the destruction of the resin matrix. Flashover of the high voltage to the grounded iron core and the secondary winding will occur. The resulting pressure increase inside the resin body leads to bursting of the resin body. To avoid such damage the transformers can be equipped with a residual winding connected in an open delta circuit and equipped with a dumping device (resistor, reactor or a combination of the two). The design of this device depends on the thermal limiting output of the residual winding. da dn da RD dn da dn Attention: To avoid a secondary short circuit it must be strictly observed that the open delta circuit is only grounded once. Medium Voltage Instrument Transformers 13
14 1.5 Service Conditions All current and voltage transformers are designed in accordance with the conditions described in the international standards. Formula The transformers are classified in two categories as given in the following table. Transformers for indoor applications Lowest temperature - 5 C Highest temperature + 40 C Relative humidity/24 hours 95% Relative humidity/months 90% Transformers for outdoor applications Lowest temperature -25/-40 C Highest temperature + 40 C Relative humidity 100% Altitude For an installation at an altitude higher than 1000 meters the arcing distance under the standardized reference atmospheric conditions shall be determined by multiplying the withstand voltages required at the service location by a factor K a in accordance with the following table. Correction factor 1,6 1,5 1,4 1,3 1,2 1, Altitude correction factor Altitude at side U BIL under atmospheric reference U k BIL under service location K a altitude correction factor according to the above graph Example: For a BIL of 75 kv (1,2/50 µs) at 2500 meters above sea level a corrected value of 90 kv must be chosen. (75 kv 1,2 = 90 kv) 1.6 Test Voltages and Insulation Levels for Instrument Transformers In order to guarantee safe operation of an instrument transformer throughout its designed lifetime, the following test must be carried out during type tests and routine tests. Rated lightning impulse withstand voltage test (type test) Power frequency withstand voltage test on primary and secondary windings (routine test) Partial discharge test (routine test) Determination of errors (routine test) Highest voltage for equipment [kv] 1.7 Insulation Class Power frequency voltage [kv] Lightning impulse voltage [kv] 7, , Most of the instrument transformers are designed for the insulation class E as described in the IEC-standard, whereby the absolute maximum temperature is 115 C. The maximum temperature increase must not exceed 75 K at an ambient temperature of 40 C. 14
15 1.8 Partial Discharge Test In spite of a safety view of the dielectric of an instrument transformer, a partial discharge test has to be carried out. Such a test is required for all transformers with a rated voltage higher than 3.6 kv. The max. permissible levels are listed in the following table. Instrument Transformer Type Test Voltage 1 Minute Partial Discharge Level (pc) Current Transformer 1,2. U m 50 Single Pole Voltage Transformer 1,2. U m / 3 20 Double Pole Voltage Transformer 1,2. U m Standards Current and voltage transformers are generally designed in accordance with the following standards: IEC current transformers IEC inductive voltage transformers ANSI/IEEE-standard All other relevant worldwide standards Handling after Receipt: All transformers are suitably packed for transportation. The packaging should be inspected immediately upon receipt for any damages caused in during transportation. Should any external damage(s) be found or any signs of improper handling are present, please notify Ritz Instrument Transformers GmbH immediately. Safety Advice Hazardous voltage occurs in this electrical equipment during operation. Violation of the service instructions can result in property damage, severe personal injury or even death. Only qualified personnel should work on or around this equipment, and only after becoming thoroughly familiar with warnings, safety notices, and maintenance procedures. The successful and safe operation of this equipment depends on proper handling, installation, operation, and maintenance. Medium Voltage Instrument Transformers 15
16 2.0 Products Design U m (kv) Type Page Current Transformer for Indoor Applications Support Type Current Transformer Indoor Block Type Narrow Type DIN 42600, Part 8, available as Size 1, 2, 3 Support Type Current Transformer Indoor Block Type Small Type DIN 42600, Part 4 Support Type Current Transformer Indoor Block Type Large Type DIN 42600, Part 5 Current Transformer Indoor Head Type 12 17, ,5 ASS 12 17, ,5 3,6 7,2 12 GSW 12/ , ASN 12 17, ,5 GI 52 72, High Current Transformer Indoor 12 17,5 24 GSSO 12 17, Bushing Type Current Transformer Indoor 12 17, GDS 12 17, Current Transformer for Outdoor Applications Support Type Current Transformer Outdoor Compact Type 12 17, GIFK 12 17, Support Type Current Transformer Outdoor Standard Type 12 17, GIFS 12 17, Head Type Outdoor GOST certificate available 10 17, ,5 GIF 10 17, ,
17 Voltage Transformer Single Pole Indoor Indoor Single Pole Narrow Type DIN 42600, Part 9 Design U m (kv) Type Page 12 17,5 24 VES 12 17, Indoor Single Pole Small Type DIN 42600, Part 7 3,6 7,2 12 GSE 12/0 28 Outdoor Indoor Single Pole Large Type DIN 42600, Part 3 VEN 52 and 72,5 not according DIN Outdoor Single Pole GOST Certificate available 12 17, VEN 12 17, ,5 VEN 52 72, , VEF 12 17, Outdoor Single Pole Head Type 52 72,5 VEF 52 72,5 31 Voltage Transformer Double Pole Indoor Indoor Double Pole Narrow Type DIN 42600, Part ,5 24 VZS 12 17, Indoo Double Pole Small Type DIN 42600, Part 7 3,6 7,2 12 GSZ 12/0 33 Indoor Double Pole Large Type DIN 42600, Part , VZN 12 17, Outdoor Outdoor Double Pole GOST Certificate available 12 17, VZF 12 17, Medium Voltage Instrument Transformers 17
18 ASS 2.1 Current Transformer Indoor up to 72,5 kv Support Type Current Transformer Indoor Block Type ASS 12 17, ,5 TYPE ASS Dimensions mm ASS 12 ASS 17,5 ASS 24 ASS 36 ASS 40,5 A B a b d H TYPE ASS ASS 12 ASS 17,5 ASS 24 ASS 36 ASS 40,5 U m kv 12 17, ,5 Test voltages kv Rated Primary Current I PN A up to 2500 up to 2500 up to 2500 up to 2500 up to 2500 Rated Secondary Current I SN A Rated Short Time Thermal Current I th up to 1000 x I PN max. 100 ka Rated Peak Current I dyn 2,5 x I th Core(s), Number of Cores Must be determined on the basis of the requirements accuracy class, over-current value, burden Frequency Hz Weight kg Subject to Technical Changes 18
19 GSW 12/ Support Type Current Transformer Indoor Block Type GSW 12/0 3,6 7,2 12 TYPE GSW 12/0 Dimensions mm Size DIN A B a b H H L I I I DIN - Bottom plate TYPE GSW 12/0 Size DIN U m kv Test voltages kv Rated Primary Current I PN A 5 up to up to up to up to 800 Rated Secondary Current I SN A Rated Short Time Thermal Current I th up to 600 x I PN max. 60 ka Rated Peak Current I dyn 2,5 x I th Core(s), Number of Cores Must be determined on the basis of the requirements accuracy class, over-current value, burden. Frequency Hz Weight kg Subject to Technical Changes Medium Voltage Instrument Transformers 19
20 ASN Support Type Current Transformer Indoor Block Type ASN 12 17, TYPE ASN Dimensions mm ASN 12 ASN 17,5 ASN 24 ASN 36 A B a b d H TYPE ASN ASN 12 ASN 17,5 ASN 24 ASN 36 U m kv 12 17, Test voltages kv Rated Primary Current I PN A up to 1500 up to 1500 up to 1500 up to 1500 Rated Secondary Current I SN A Rated Secondary Current I th up to 1000 x IPN max. 100 ka Rated Peak Current I dyn 2,5 x Ith Core(s), Number of Cores Must be determined on the basis of the requirements accuracy class, over-current value, burden Frequency Hz Weight kg Subject to Technical Changes 20
21 GI Current Transformer Indoor Head Type GI 52 72,5 TYPE GI Dimensions mm GI 52 GI 72,5 A B a b C H H H3 557,5 745 GI 52 GI 52 GI 52 GI 52 up to 600 A 600 A A A A 2000 A 3000 A L 1322 d GI 72,5 GI 72,5 GI 72,5 up to 1250 A 2000 A A L d TYPE GI GI 52 GI 72,5 U m kv 52 72,5 Test voltages kv Rated Primary Current I PN A up to 3000 Rated Secondary Current I SN A 1 5 Rated Short Time Thermal Current I th bis 1000 x IPN max. 100 ka Rated Peak Current I dyn 2,5 x Ith Core(s), Number of Cores Must be determined on the basis of the requirements accuracy class, over-current value, burden Frequency Hz Weight kg Subject to Technical Changes Medium Voltage Instrument Transformers 21
22 GSSO High Current Transformer Indoor GSSO 12 17,5 24 TYPE GSSO Dimensions mm Size A B a b l l l l Design d TYPE GSSO Size U m kv Test voltages kv Rated Primary Current I PN A 100 up to 4000 Rated Secondary Current I SN A Rated Short Time Thermal Current I th up to 1000 x I PN max. 200 ka Rated Peak Current I dyn 2,5 x I th Core(s), Number of Cores Must be determined on the basis of the requirements accuracy class, over-current value, burden Frequency Hz Weight kg Subject to Technical Changes 22
23 GDS Bushing Type Current Transformer Indoor GDS 12 17, TYPE GDS Dimensions mm GDS 12 GDS 24 GDS 36 Size a d1 180 d A e A A A e A A Weigh [kg] TYPE GDS GDS 12 GDS 17,5 GDS 24 GDS 36 U m kv 12 17, Test voltage kv Rated Primary Current I PN A 150 A up to 2500 A on request 3000 A Rated Secondary Current I SN A Rated Short Time Thermal Current I th up to 1000 x IPN max. 100 ka Rated Peak Current I dyn 2,5 x Ith Core(s), Number of Cores Must be determined on the basis of the requirements accuracy class, over-current value, burden Frequency Hz Subject to Technical Changes Medium Voltage Instrument Transformers 23
24 GIFK 2.2 Current Transformer Outdoor up to 72,5 kv Support Type Current Transformer Outdoor Compact Type GIFK 12 17, TYPE GIFK Dimensions mm GIFK 12 17,5 24 GIFK 36 A B a b C H TYPE GIFK GIFK 12 GIFK 17,5 GIFK 24 GIFK 36 U m kv 12 17, Test voltages kv Rated Primary Current I PN A up to 1250 Rated Secondary Current I SN A Rated Short Time Thermal Current I th up to 1000 x IPN max. 63 ka Rated peak Current I dyn 2,5 x Ith, max. 100 ka Core(s), Number of Cores Must be determined on the basis of the requirements accuracy class, over-current value, burden Frequency Hz Creepage Distance mm Weight kg Subject to Technical Changes 24
25 GIFS Support Type Current Transformer Outdoor Standard Type GIFS 12 17, TYPE GIFS Dimensions mm GIFS 12 17,5 24 GIFS 36 A B a b C H TYPE GIFS GIFS 12 GIFS 17,5 GIFS 24 GIFS 36 U m kv 12 17, Test voltages kv Rated Primary Current I PN A up to 1250 Rated Secondary Current I SN A Rated Short Time Thermal Current I th up to 1000 x I PN max. 63 ka Rated peak Current I dyn 2,5 x Ith, max. 100 ka Core(s), Number of Cores Must be determined on the basis of the requirements accuracy class, over-current value, burden Frequency Hz Creepage Distance mm Weight kg Subject to Technical Changes Medium Voltage Instrument Transformers 25
26 GIF Current Transformer Outdoor Head Type GIF 10 17, ,5 TYPE GIF Dimensions mm GIF 10 17,5 GIF 20 GIF 30 GIF 36 GIF 52 GIF 72,5 A B a b C H H ¹ H , up to 600 A L 600 A up to 1250 A A up to 2000 A A up to 3000 A ¹ Without primary reconnection TYPE GIF GIF 10 GIF 17,5 GIF 20 GIF 30 GIF 36 GIF 52 GIF 72,5 U m kv 12 17, ,5 Test voltages kv ² Rated Primary Current I PN A up to 3000 Rated Secondary Current I SN A Rated Short Time Thermal Current I th up to 1000 x I PN max. 63 ka Rated Peak Current I dyn 2,5 x I th, max. 100 ka Core(s), Number of Cores Must be determined on the basis of the requirements accuracy class, over-current value, burden Frequency Hz Creepage Distance mm Weight kg ² Increased BIL possible 70/200 Subject to Technical Changes 26
27 2.3 Voltage Transformer Single Pole up to 72,5kV VES Voltage Transformer Indoor VES 12 17,5 24 TYPE VES Dimensions mm VES 12 VES 17,5 VES 24 A B a b H TYPE VES VES 12 VES 17,5 VES 24 U m kv 12 17,5 24 Test voltages kv Rated Primary Current I PN V 10000/ / 3 Rated Secondary Voltage U SN Rated Secondary Voltage for the Earthing Corens Rated Output in Accuracy Class (IEC) V V 13800/ / 3 100/ 3 110/ 3 100/3 110/ / / 3 0,2 VA ,5 VA ,0 VA Thermal Limit Current A Thermal Limit Current at A ,9 x U n / 8h Frequency Hz Weight kg Subject to Technical Changes Medium Voltage Instrument Transformers 27
28 GSE Voltage Transformer Indoor GSE 12/0 3,6 7,2 12 DIN - Bottom plate TYPE GSE Dimensions mm GSE 12/0 GSE 12/0 DIN A B a b H l l l l TYPE GSE GSE 12 0 U m kv 2 Test voltages kv Rated Primary Voltage U PN V 3000/ / / / 3 Rated Secondary V Voltage U SN 100/ 3 110/ 3 Rated Secondary Voltage V for the Earthing Core (en) 100/3 110/3 Rated Output in Accuracy Class (IEC) 0,2 VA 30 0,5 VA 90 1,0 VA 180 Thermal Limit Current A 7 Thermal Limit Current at A 6 1,9 x U n / 8h Frequency Hz Weight kg 18 Subject to Technical Changes 28
29 VEN Voltage Transformer Indoor VEN 12 17, ,5 TYPE VEN Dimensions mm VEN 12 VEN 17,5 VEN 24 VEN 36 VEN 52 VEN 72,5 A B a b H VEN up to 36 kv VEN up to 72,5 kv TYPE VEN VEN 12 VEN 17,5 VEN 24 VEN 36 VEN 52 VEN 72,5 U m kv 12 17, ,5 Test voltages kv Rated Primary Voltage UPN V 10000/ / 3 Rated Secondary V Voltage U SN 13800/ / / / / / 3 100/ 3 110/ / / / / 3 Rated Secondary Voltage for the Earthing Core(en) V 100/3 110/3 Rated Output in Accuracy Class (IEC) 0,2 VA ,5 VA ,0 VA Thermal Limit Current A Thermal Limit Current at 1,9 x U n / 8h A Frequency Hz Weight kg , Subject to Technical Changes Medium Voltage Instrument Transformers 29
30 VEF Voltage Transformer Outdoor VEF 12 17, TYPE VEF Abmessungen mm VEF 12 VEF 17,5 VEF 24 VEF 36 A B a b H TYPE VEF VEF 12 VEF 17,5 VEF 24 VEF 36 U m kv 12 17, Test voltages kv Rated Primary Voltage U PN 10000/ / / / 3 V 11000/ / / / 3 Rated Secondary Voltage U SN V 100/ 3 110/ 3 Rated Secondary Voltage for the Earthing Core (en) V 100/3 110/3 Rated Output in Accuracy Class (IEC) Thermal Limit Current 0,2 VA ,5 VA ,0 VA A Thermal Limit Current at 1,9 x U n / 8h A Frequency Hz Creepage Distance mm Weight kg 33,5 35,5 35,5 51 Subject to Technical Changes 30
31 VEF Voltage Transformer Outdoor Head Type VEF 52 72,5 TYPE VEF Dimensions mm VEF 52 VEF 72,5 A B a b D H TYPE VEF VEF 52 VEF 72,5 U m kv 52 72,5 Test voltages kv Rated Primary Voltage U PN 45000/ / 3 V 50000/ / 3 Rated Secondary Voltage U SN V 100/ 3 110/ 3 Rated Secondary Voltage for the Earthing Core (en) V 100/3 110/3 Rated Output in Accuracy Class (IEC) Thermal Limit Current 0,2 VA ,5 VA ,0 VA A Thermal Limit Curre nt at 1,9 x U n / 8h A 9 9 Frequency Hz Creepage Distance mm Weight kg Subject to Technical Changes Medium Voltage Instrument Transformers 31
32 VZS 2.4 Voltage Transformer Double Pole up to 36 kv Voltage Transformer Indoor VZS 12 17,5 24 TYPE VZS Dimensions mm VZS 12 VZS 17,5 VZS 24 A B a b C d H TYPE VZS VZS 12 VZS 17,5 VZS 24 U m kv 12 17,5 24 Test voltages kv Rated Primary Voltage U PN V Rated Secondary Voltage U SN V Rated Secondary 0,2 VA Voltage Class (IEC) 0,5 VA ,0 VA Thermal Limit Current A Frequency Hz Weight kg Subject to Technical Changes 32
33 GSZ Voltage Transformer Indoor GSZ 12/0 3,6 7,2 12 DIN - Bottom plate TYPE GSZ Dimensions mm GSZ 12/0 GSZ 12/0 DIN A B a b C H l l l l TYPE GSZ GSZ 12 U m kv 12 Test voltages kv Rated Primary Voltage U PN V Rated Secondary Voltage U SN V Rated Secondary Class (IEC) 0,2 VA 10 0,5 VA 45 1,0 VA 150 Thermal Limit Current A 4 Frequency Hz Weight kg 18 Subject to Technical Changes Medium Voltage Instrument Transformers 33
34 VZN Voltage Transformer Indoor VZN 12 17, TYPE VZN Dimensions mm VZN 12 VZN 17,5 VZN 24 VZN 36 A B a b d H TYPE VZN VZN 12 VZN 17,5 VZN 24 VZN 36 U m kv 12 17, Test voltages kv Rated Primary Voltage U PN V Rated Secondary Voltage U SN V Rated Secondary Voltage Class (IEC) 0,2 VA ,5 VA ,0 VA Thermal Limit Current A Frequency Hz Weight kg ,5 70 Subject to Technical Changes 34
35 VZF Voltage Transformer Outdoor VZF 12 17, TYPE VZF Dimensions mm VZF 12 VZF 17,5 VZF 24 VZF 36 A B a b C H TYPE VZF VZF 12 VZF 17,5 VZF 24 VZF 36 U m kv 12 17, Test voltages kv Rated Primary Voltage U PN V Rated Secondary Voltage U SN V Rated Output in Accuracy Class (IEC) Thermal Limit Current 0,2 VA ,5 VA ,0 VA A Frequency Hz Creepage Distance mm Weight kg Subject to Technical Changes Medium Voltage Instrument Transformers 35
36 RITZ Product Overview Low Volta ge In stru m ent Trans for mers Low-Voltage Instrument Transformers up to 1.2 kv c.t.s for measuring and protection purposes Wound primary c.t. Auxiliary c.t. Summation c.t. Window type c.t. C.t.s for switch fuses Tube type c.t. Multi-range c.t. Split-core c.t. Window type c.t.s for high currents Split core types for earth fault protection 36
37 RITZ Product Overview Cast Resin Bus Bar Systems up to 72,5 kv & 6500 A The Alternative to Parallel-Connected Cables The RITZ Solid Insulated Bus Bar System especially offers for transmission of higher currents and/or limited space requirements a cost-effective and safe alternative to parallel-connected cable systems, metal-enclosed bus bar or bus duct systems. RITZ Service Minimized project engineering for YOU as customer due to complete engineering service for bus bar routing including fixation system as 3D CAD model. Providing complete Installation documentation Supervisor support on request available Installation team on request available Bus Bar Design Principle 1. Conductor 2. Epoxy-impregnated paper wrapping 3. Earth layer 4. Capacitive grading 5. End ring Metal ring System Specific Benefits Compact design Reduced requirements for the installation space Small bending radii 3-dimensional geometric shape is possible Natural cooling due to effectual conductor design High opererational reliability due to factory routine test of each bus bar No maintenance A Safety Benefits Touch Safe Fully insulated and capacitive graded system High thermal and dynamic short circuit current withstand capabilities Excluded phase to phase short-circuits No toxic fumes in case of fire - self extinguishing High operating reliability due to routine tests for each bus bar element Section A-B Bus Bar Fixing Plastic fixing clamps 2. Aluminium 3. Aluminium fixing angles 3 Installation Easy installation due to standardized installation and fixing parts Medium Voltage Instrument Transformers 37
38 RITZ Product Overview Cast Resin Insulated Power Transformers up to 40,5 kv Cast Resin Power Transformers 50 kva up to 25 MVA RITZ produces transformers in Glass Fibre reinforced Vacuum Technology (GVT) for ratings up to 25 MVA and for a maximum system voltage of 40,5 kv voltage class Applications Power Distribution Traction Power Systems Rectifier Drives (Streetcar, Tram, Metro, Railway) Oil Platforms / Vessels Generator Excitation Injection Systems Transmitter Systems Grounding Systems Laboratory Systems Customer oriented package solutions Transformer Installation Disposal of existing oil and PCB transformers Start-up Glass Fibre reinforced Vacuum Technology (GVT) is used for High Voltage coils and optionally for Low Voltage coils in order to guarantee the highest possible quality and reliability to avoid cracks or voids during manufacturing and service. Characteristics mpulse voltage proof Partial discharge free Short circuit proof Highest mechanical strength Cooling channels in HV&LV coils Pre-galvanised steel frame RITZ transformers are designed according to the required international specifications like DIN/VDE or IEC. Further more they fulfil all climatic, environmental and fire protection requirements: Enviromental class E2 Climate class C2 Fire protection class F1 Basic impulse level List 2 The requirements of the environmental protection is taken Glass Fibre reinforced Vacuum Technology (GVT) is used for into account for design of the RITZ cast resin transformers. Special Transformers Injection transformers for ripple control applications Reactors for ripple control applications High current transformers Earthing transformers Medium frequency transformers Filter and blocking reactors Smoothing and interphase reactors 38
39 RITZ Product Overview Electronic Instrument Transformers and Sensor Voltage-Sensoric Current-Sensoric Voltage up to 90 kv Current up to A Accuracy of 0,2 % Accuracy of 0,01 % Frequen y from a to 10kHz Frequency from a to 10kHz Applications Power Engineering Grid Analyse Protection Technology Electrochemistry Switchgear Systems Automobile Industry Environment Engineering Research Rail Transportation Power Supply Block-Type Multi Sensor The sensor provides signals for current and voltage measurement as well as voltage reference for electronic protection relays. Current measurement Using a Rogowski coil Voltage measurement Using an ohmic voltage divider Voltage reference Using a coupling electrode Cast Resin Parts We develop and formulate casting resin molding materials for electrical applications in the low and medium voltage range and for electronics, We sketch and produce casting resin-isolated devices and shaped parts for application in electrical energy engineering for example special bushings. fuse housings etc. Medium Voltage Instrument Transformers 39
40 Sales HAMBURG Instrument Transformers GmbH Wandsbeker Zollstraße Hamburg GERMANY Tel Fax Medium Voltage Fax Low Voltage WIRGES Instrument Transformers GmbH Siemensstraße Wirges GERMANY Tel Fax Low Voltage Instrument Transformers Medium Voltage Instrument Transformers Cast Resin Insulated Bus Bar Systems Cast Resin Power Transformers Electronic Insrtument Transformers and Sensor Customised Cast Resin Parts DRESDEN Instrument Transformers GmbH Bergener Ring Ottendorf-Okrilla GERMANY Tel Fax KIRCHAICH Instrument Transformers GmbH Mühlberg Oberaurach-Kirchaich GERMANY Tel Fax MARCHTRENK Instrument Transformers GmbH Linzer Straße Marchtrenk AUSTRIA Tel Fax KECSKEMÉT Instrument Transformers Kft. Technik-Park Heliport 6000 Kecskemét-Kadafalva HUNGARY Tel Fax SHANGHAI Instrument Transformers Shanghai Co. Ltd. 99 Huajia Road, Building 1-3, Huabin Industrial Park Songjiang Industrial Zone Shanghai, P.R. China Tel Fax HARTWELL Instrument Transformers Inc. 25 Hamburg Avenue Lavonia, GA USA Tel Fax [email protected] Rev_ JSW
Metal Clad Indoor Instrument Transformer for Plug-In Systems
Metal Clad Indoor Instrument Transformer for Plug-In Systems RITZ Instrument Transformers GmbH Core competency Under the trading name RITZ Instrument Transformers GmbH RITZ has been pooling its activities
Medium-voltage transformers
Medium-voltage transformers We make energy measurable and take care of your future www.mbs-ag.com Page 2 E-Mail: [email protected] Web: www.mbs-ag.com Contents Current transformers Technical characteristics
Digital Energy ITI. Instrument Transformer Basic Technical Information and Application
g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER
Enhanced Quality with a Touch of Style
Rudolf Current Transformer Enhanced Quality with a Touch of Style Current Transformer Enhanced Quality with a Touch of Style New Products Rudolf launched our new encapsulated current transformer. Portraying
KOLMA and IHDA Indoor type Cable Current Transformers Catalogue ABB Power Distribution ABB Transmit 1 KKOLMA 1 GB
KOLMA and IHDA Indoor type Cable Current Transformers Catalogue ABB Power Distribution ABB Transmit 1 KKOLMA 1 GB KOLMA and IHDA Indoor Type Cable Current Transformers Index Description... 3 Technical
Instrument Transformers Application Guide
Instrument Transformers Application Guide Edited by ABB AB High Voltage Products Department: Marketing & Sales Text: Knut Sjövall, ABB Layout, 3D and images: Mats Findell, ABB SE-771 80 LUDVIKA, Sweden
LOW-VOLTAGE CURRENT TRANSFORMERS
LOWVOLTAGE CURRENT TRANSFORMERS 5 A Power network meters ND0 and ND type. N4Z and N5Z Tel: (+48 68) 45 75 39; 45 75 305; 45 75 3; 45 75 368; email: [email protected] ul. Słubicka 657 Zielona Góra CONTENTS
Vario-Series Accessories
Accessories and spare parts for GMW analogue panel meters and controllers Current Transformers pages 2-9 Shunt Resistors 10-11 Voltage Dividers 12 Power supply for indicator/controllers 13 Blanking Plates
Current transformers (CT) & Shunts
Current transformers (CT) & Shunts Genreal overview LV CURRENT TRANSFORMERS Product selection guide Standard industrial transformers?????? TCR - TCRO range NEW 9 9 9 Current summation JVM 0 9 TCR usbar
NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements
NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems Safe energy distribution that meets the highest industrial requirements NATUS switchgear systems your advantages minimal use of insulant
Pressure monitoring equipment for oil-sf 6. bushings, type GOEK
Pressure monitoring equipment for oil-sf 6 bushings, type GOEK Installation and maintenance guide 5693 827-6 en, Rev. 3, 2002-01-30 This document must not be copied without our written permission, and
Medium voltage product. Instrument transformers for indoor applications Product overview
Medium voltage product Instrument transformers for indoor applications Product overview 02 Contents Introduction Current transformers Supporting type 6 TPU, TPE 7 KOFA, IHBF 10 Dummy Bus type 8 KOKS 12,
Transformer Bushings for GIS
Transformer Bushings for GIS Oil to SF6 Connections GARIP RTKG 725-55 kv SQS certified ISO 91 / ISO 141 Bushings RIP - Technology for SF6 / Oil - Bushings In modern metal enclosed switchgear SF6 -gas is
Presentation of the France Transfo factories
Presentation of the France Transfo factories France Transfo's internationally recognised and highly esteemed expertise is today exported to more than 80 countries throughout the world. Over the past 15
Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
MiCAFIL. 1 RIP Technology. Bushings. Z. Zic 09/2003
MiCAFIL 1 RIP Technology Z. Zic 09/2003 )XQFWLRQRI+LJK9ROWDJH%XVKLQJ Uncontrolled (natural) electrical field Capacity-controlled electrical field %XVKLQJV0DLQ,QVXODWLRQ6\VWHPV 7\SH 0DLQ,QVXODWLRQ +RXVLQJFRYHU
3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance
SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132
T 3000. Substation Maintenance and Commissioning Test Equipment
T 3000 Substation Maintenance and Commissioning Test Equipment Multi function system for testing substation equipment such as: current, voltage and power transformers, all type of protection relays, energy
UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution
UniGear ZS1 Medium voltage, arc proof, air insulated switchgear for primary distribution UniGear ZS1: an innovative solution for all installation requirements ABB UniGear is medium voltage metal-clad,
PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES
PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES BUSHING WITH PLUG CONNECTION WITH OUTER CONE PPS CHARACTERISTICS The PPS bushing can be used as a fixed section for the entry of medium
Tape Wound, Split Core and Ebony Current Transformers
Tape Wound, Split Core and Ebony Current Transformers Current Transformers Contents Page Tape Wound Measuring and Protection Current Transformers 2 6 Split Core Current Transformers 7 9 3-in-1 Current
High-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv
High-Voltage Compact Switchgear AP1 DTC for 1 kv and kv Answers for energy. The AP1 DTC Complying with our Customers demands Experience you can rely on - at anytime, anywhere Decades of experience in high-voltage
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to
2. INDUCTIVE VOLTAGE TRANSFORMERS Oil-paper insulation Gas insulation
2. INDUCTIVE VOLTAGE TRANSFORMERS Oil-paper insulation Gas insulation 123 kv Inductive Fingrid (Finland). 18 Instrument transformers igh voltage INTRODUCTION Inductive voltage transformers are designed
Earth Fault Detection Basics in Theory
Earth Fault Detection Basics in Theory Author: Dipl.-Ing. Ingo Kühnen Woodward Power Solutions Krefelder Weg 47 47906 Kempen, Germany Kempen, 16.04.2010 Earth_Fault_Detection_20100416.doc page 1 1. Star
R.C.C.B. s two-pole LEXIC
87045 LIMOGES Cedex Telephone : (+33) 05 55 06 87 87 Fax : (+ 33) 05 55 06 88 88 R.C.C.B. s two-pole LEXIC 089 06/09/10/11/12/15/16/17/18/ 27/28/29/30/35, CONTENTS PAGES 1. Electrical and mechanical characteristics...
Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.
By Darrell G. Broussard, P.E. Introduction: As engineers, we are aware that electrical power systems have grown. How much have they grown? When was the last time you specified a 2400-volt system, a 4160-volt
Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description
Type: EASY719 DC RC Article.: 274119 Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC Description 12 digital inputs (4 inputs available as analog inputs) 6 relay outputs LCD display
MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4
CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,
METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast.
METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV tgood.com Energy. Fast. TGOOD produces over 5000 switchgear units annually for projects around the globe PRODUCT OVERVIEW Integral substation component
ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU
ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU George CURCANU, Constantin ILINCA, Ilie SBORA ICMET Craiova, Romania, Calea Bucuresti 144, phone:
Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy
Our brand A strong brand for strong products: The ENERGOLINE brand represents our product portfolio of INDUSTRIAL SWITCHGEAR SYSTEMS. Our products are characterized by a high degree of safety, flexibility
MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS
MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS Meher Capacitors offers reliable and innovative products and solutions in the fields of Reactive Power Compensation, Power Quality and Energy
Current transformer selection guide
The selection of a current transformer is a simple task. There are four phases in the selection procedure. Current transformer selection guide KEEP IN MIND efine customer requirements based on the primary
Power transformers. Special transformers Railway
Power transformers Special transformers Railway A leader in railway systems Our compact and low-weight transformers fully comply with the customer s specifications. The products are developed together
Unified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
SECTION 16461 DRY-TYPE TRANSFORMERS
SECTION 16461 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Furnishing and installation of and testing of cast resin dry type MV/LV distribution transformer in accordance with specifications and drawings. Any
LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS
Specification for LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS CEYLON ELECTRICITY BOARD SRI LANKA Specification for LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS CEB Standard 027: 1998 CEYLON
Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components
Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Course No: E02-010 Credit: 2 PDH Boris Shvartsberg, Ph.D., P.E., P.M.P. Continuing Education
Capacitor Voltage Transformer. Answers for energy.
Capacitor Voltage Transformer Answers for energy. Capacitor Voltage Transformer Siemens Capacitor Voltage Transformers are based on technology from Trench, a recognized world leader in the design and manufacture
keep your measure under control
INSTRUMENTACIÓN INDUSTRIAL ZURC, S.A. keep your measure under control CURRENT For measuring instruments. Mounted in selfexinguishing, plastic, strengthened cases. Isolation voltage V Made as per UNEEN
1ZSC000563-AAC en, Rev. 7. Resin impregnated paper bushing, oil to air, type GSB Technical guide
1ZSC000563-AAC en, Rev. 7 Resin impregnated paper bushing, oil to air, type GSB Technical guide Original instruction The information provided in this document is intended to be general and does not cover
ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.
1SR 430 824 F9300 Features Monitoring of three-phase mains for phase sequence and failure Powered by the measuring circuit 2 c/o (SPDT) contacts 1 LED for status indication Approvals R: yellow LED - relay
Using Current Transformers with the 78M661x
A Maxim Integrated Products Brand Using Current Transformers with the 78M661x APPLICATION NOTE AN_661x_021 April 2010 Introduction This application note describes using current transformers (CT) with the
TYPE TEST CERTIFICATE OF SHORT-CIRCUIT PERFORMANCE. A three-phase outdoor oil-immersed distribution transformer
168-08 TYPE TEST CERTIFICATE OF SHORT-CIRCUIT PERFORMANCE APPARATUS A three-phase outdoor oil-immersed distribution transformer DESIGNATION 1000 kva SERIAL No. 1-08-112-01-0001 Rated power Rated voltage
Measurement and Instrumentation
POWER QUALITY ENERGY PERFORMANCE Measurement and Instrumentation Transformers and shunts Transformers Overview of ranges Selection guide Info & advice Standard industrial transformers TCR TCRO ranges Adaptable
CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.
425 CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE General purpose single phase thyristors and solid state relays Product data abc 425 EUROCUBE A complete range of low cost solid state relays and
The Intelligent AX1 Switchgear for Medium Voltage
The Intelligent AX1 Switchgear for Medium Voltage Leif Lundin, Manager of Research and Development, Division Medium Voltage and Compact Substations, ABB Distribution, Sweden Abstract The newly launched
DS 600. A contact free flux gate based current measurement sensor 600A rms
DS 600 A contact free flux gate based current measurement sensor 600A rms DS 600 is member of the small housing sensor family. The family includes a 200A and a 600A version. 600A rms - 900A peak Maximum
Tape Wound, Split Core and Ebony Current Transformers
Tape Wound, Split Core and Ebony Current Transformers Table of contents Tape Wound Measuring and Protection Current Transformers 2 MR Series Measuring Range 3 PR Series Protection Range 4 Class PX Current
Lightning Arresters P30027 18 KVA P30038 10 KVA. Description & Installation
Lightning Arresters P30027 18 KVA P30038 10 KVA Description & Installation Printed in USA 09/11 TO330 Rev. B Table of Contents Page 1.0 SCOPE 2 2.0 PRODUCT OVERVIEW 2 2.1 Intended Uses 2 2.2 Lightning
3) What is the difference between "Insulating", "Isolating", and "Shielded Winding" transformers?
Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 1) What is a transformer and how does it work? A transformer
Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.
Power Voltage Transformers for Air Insulated Substations THE PROVEN POWER. Introduction Trench Power Voltage Transformers (Power VTs) combine the attributes of an inductive voltage transformer with the
2013 RESIBLOC transformers Product presentation. ABB Group October 2, 2013 Slide 1
2013 RESIBLOC transformers Product presentation October 2, 2013 Slide 1 Dry-type transformers For customers with high requirements Does your transformer application requires one of the following characteristic?
High-Voltage Circuit-Breakers 3AP1/2 72.5 kv up to 550 kv. Power Transmission and Distribution
High-Voltage Circuit-Breakers AP/ 7.5 kv up to 550 kv Power Transmission and Distribution The AP/ High-Voltage Circuit-Breakers Now Applicable for 550 kv Decades of our experience in high-voltage switching
SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL
SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated
5SV Residual Current Protective Devices
s Siemens AG 2013 SENTRON 5SV Residual Current Protective Devices New portfolio for reliable personnel, material and fire protection Safe protection against residual currents Residual current protective
REVIEWED BY CAPITAL PROJECTS MANAGER (DAN REDDY) GENERAL MANAGER EQUIPMENT ENGINEERING & ASSET MANAGEMENT (HAMILTON NXUMALO)
SA Port Operations DOCUMENT TYPE: REFERENCE EEAM-Q-014 (ORIGINAL SPECIFICATION HE8.2.3 Ver5) REVISION 0 SPECIFICATION TITLE: SPECIFICATION FOR ELECTRICAL MOTORS AND GENERATORS PAGE 0 of 07 COMPILED BY
DRM75A 230V 20/100A DIN rail single phase two wire energy meter
DRM75A 230V 20/100A DIN rail single phase two wire energy meter 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Description 1.7 Dimensions 1.8 Installation
Guidance for upgrading to GB4943.1-2011 (IEC 60950-1: 2005, MOD)
Guidance for upgrading to GB4943.1-2011 (IEC 60950-1: 2005, MOD) Note: This guidance document is a translation of official Chinese document which is issued by CQC (China Quality Certification Center) on
Cable Solutions for Servo and Variable Frequency Drives (VFD)
Cable Solutions for Servo and Variable Frequency Drives (VFD) Electric drive systems with continuous torque and speed control are widespread today. They allow an optimal adjustment of the drive with respect
EARTHING SYSTEM CALCULATION
BAZIAN STEAL FACTORY S/S 132/11kV, 1x30/40MVA EARTHING SYSTEM CALCULATION Kurdistan Region Sulaimani May 2011 Bazian Steal Factory S/S 132/11kV, 1x30/40 MVA Contents: 1. Introduction... 3 2. List of references
Current Transformers
Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 Current Transformers Current transformers (CT's) provide
WINDING RESISTANCE TESTING
WINDING RESISTANCE TESTING WINDING RESISTANCE TEST SET, MODEL WRT-100 ADWEL INTERNATIONAL LTD. 60 Ironside Crescent, Unit 9 Scarborough, Ontario, Canada M1X 1G4 Telephone: (416) 321-1988 Fax: (416) 321-1991
Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1
Power Supply Unit, Primary Switched, Narrow Design MINI POWER provides: Extra narrow design with widths of 22.5 mm, 45 mm, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a wide-range input
Primary and Secondary Electrical Distribution Systems
Primary and Secondary Electrical Distribution Systems Critical Facilities Round Table 12th Quarterly Membership Meeting June 2, 2006 David D. Roybal. P.E. Eaton Electrical Cutler-Hammer Products Utility
HEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR
HEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR 2 MB 103 TRANSFORMER TEMPERATURE CONTROL UNIT WITH CONTROL SIGNAL Recent approval of new
RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC
Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage
Secondary Unit Substations
14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically
SPECIFICATIONS FOR 220KV CAPACITOR VOLTAGE TRANSFORMER. The equipment is required for 220KV system. The system data is given as under:
REQUIREMENT : The equipment offered shall be highly reliable suitable to operate satisfactorily in hot humid and polluted climate. The equipments offered shall work satisfactorily within temperature range
Voltage Regulator SPAU 341 C. Product Guide
Issued: July 1998 Status: Updated Version: D/25.04.2006 Data subject to change without notice Features Comprehensive voltage regulation for power transformers with on-load tapchangers in distribution substations
MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation
MTE SERIES RLW World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930 2009 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RLW reactors are components designed to improve the reliability
Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms
Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms ABB innovations for changing demands ABB (www.abb.com) is a leader in power and automation technologies that enables utility
KAM 25-32 A Lighting Busbar System KAP 40-63 A Plug-in Busbar Distribution System
2-32 A Lighting Busbar System 4-63 A Plug-in Busbar Distribution System / E-LINE KX Compact Busbar Distribution System 63...63 A E-LINE KB Compact Busbar Distribution System 8...63 A E-LINE KO Plug-in
Safety technique. Emergency stop module BO 5988 safemaster
Safety technique Emergency stop module BO 5988 safemaster 0221562 Function diagram Pushbutton on Mains or emergencystop () K1 According to EC Directive for machines 98/37/EG According to IEC/E 60204-1
Thermistor motor protection
Thermistor motor protection CM-E Range Thermistor motor protection Thermistor motor protection relays Benefits and advantages Selection table Operating principle and fields of application for thermistor
HERZ-Thermal Actuators
HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01
INTERNATIONAL POWER DISTRIBUTION CONGRESS CIDEL ARGENTINA 2002
INTERNATIONAL POWER DISTRIBUTION CONGRESS CIDEL ARGENTINA 2002 NEW GAS INSULATED SWITCHGEAR (GIS) FOR ALL MEDIUM VOLTAGE APPLICATIONS H. Fink, ABB Calor Emag Mittelspannungs GmbH; M. Hyrenbach, ABB Calor
Submit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c 91052 Erlangen Germany. www.siemens.
Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c 91052 Erlangen Germany www.siemens.com/energy For questions on power transmission and distribution, please contact
CURRENT TRANSFORMER MODEL 546 UL1015 #16 AWG LEAD WIRE, STANDARD LENGTH IS 24" 1 X
CURRENT TRANSFORMER MODEL 546 1.10" I.D. PAGE No 1-38 REV 15DEC00 TERMINAL OPTION LEAD WIRE OPTION 1.10 0 1.20 2.55 3.00 3.47 0.18 x 0.31 SLOT ( 2 PLACES) 8-32 BRASS STUD (2 PLACES) UL1015 #16 AWG LEAD
TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY
TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY 2 TRACTION NETWORK MONITORING AND PROTECTION SYSTEM Traction network monitoring and protection system,
Electronic overload relay EF19 and EF45
Data sheet Electronic overload relay EF19 and EF45 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays. Motor
ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories
2CDC 251 014 F0t09 Features Monitoring of three-phase mains for grid feeding Type-tested in accordance with DIN V VDE V 0126-1-1: February 2006 Neutral conductor connection configurable Can also be used
Three-phase monitoring relay CM-PFE
Data sheet Three-phase monitoring relay CM-PFE The CM-PFE is a three-phase monitoring relay that monitors the phase parameter phase sequence and phase failure in three-phase mains. 2CDC 251 005 S0012 Characteristics
ABB Drives. User s Manual. Pulse Encoder Interface Module RTAC-01
ABB Drives User s Manual Pulse Encoder Interface Module RTAC-0 Pulse Encoder Interface Module RTAC-0 User s Manual 3AFE 64486853 REV A EN EFFECTIVE:.5.00 00 ABB Oy. All Rights Reserved. Safety instructions
For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.
Current Transducer HO-P series I PN = 6, 10, 25 A Ref: HO 6-P, HO 10-P, HO 25-P For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary
Power Plant Electrical Distribution Systems
PDH Course E184 Power Plant Electrical Distribution Systems Gary W Castleberry, PE 2008 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com
Current and voltage measuring relays
Current and voltage measuring relays RXIK 1, RXEEB 1 and Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice RXIK 1 RXEEB 1 (SE980082) (SE980081) (SE970869) Features Application
Fault location on power cables. Fault location on power cables
Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 01. Introduction Fault location on communication and power cables
SF 6 Gas Insulated Switchgear Type SDF for 170 kv
Three Phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDF for 170 kv 06B1-E-0001 With Trustworthy Technology, Structure Fuji Electric as a manufacturer of comprehensive substation equipment
ADM1TE 5/30A DIN rail single phase two wire energy meter
ADMTE 5/30A DIN rail single phase two wire energy meter. Safety instruction.2 Foreword.3 Performance criteria.4 Specifications.5 Basic errors.6 Description.7 Dimensions.8 Installation.9 Operating.0 Troubleshooting.
Table of Contents. TransformerIQ FAQs 1
[12/12] FAQs Table of Contents FAQ 1. What size transformer will TransformerIQ monitor?... 2 FAQ 2. Are there different TransformerIQ versions?... 2 FAQ 3. How are the units powered?... 2 FAQ 4. What is
EMOSAFE EN-100. Network Isolators for PCB assembly 1 GENERAL DESCRIPTION. Product Data Sheet ENGLISH
ENGLISH EMOSAFE EN-100 Product Data Sheet Network Isolators for PCB assembly November 2013 1 GENERAL DESCRIPTION The EMOSAFE EN-100 Network Isolator interrupts all galvanically conducting connections (conductors
Digital inductive conductivity transmitter
Digital inductive conductivity transmitter Optimal solution for conductivity measurements in difficult fluids (polluted, dirty,...) PEEK/PPA version for CIP applications Large range of process connections
Floodlight Range Installation Guide
SPARTAN Floodlight Range Installation Guide CML13ATEX3007 IEC Ex CML14.0001 This installation guide provides instructions for installing the Infra-Red and White-Light SPARTAN SPX series of explosion protected
Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous
Safety relay for monitoring E-STOP pushbuttons. Approvals Unit features Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous Safe separation of
Arc Terminator Active Arc-Resistant Switchgear
Arc Terminator Active Arc-Resistant Switchgear Increasing safety and productivity by extinguishing internal arcing faults within the switchgear. The Square D Arc Terminator from Schneider Electric offers
The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies
The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies DATE: November 17, 1999 REVISION: AUTHOR: John Merrell Introduction In some short circuit studies, the X/R ratio is ignored when comparing
CURRENT TRANSFORMERS INSTALLATION GUIDE
CURRENT TRANSFORMERS INSTALLATION GUIDE Information contained within this document is subject to change without notice and does not represent a commitment on the part of PRI Ltd or its agents. E&OE. Copyright