Effective Use of Two Stage Alarms & Voice Communication Systems
|
|
|
- Vivien Hines
- 9 years ago
- Views:
Transcription
1 Effective Use of Two Stage Alarms & Voice Communication Systems Approving These in Fire Safety Plans Sean Tracey, P.Eng., MIFireE Canadian Regional Director NFPA
2 Outline of the Presentation Background Overview of Fire Alarm Provisions Code provisions for voice systems Advantages Hurdles Fire Safety Plan Considerations Resources
3 Background Why begin to look at this? National Capital Region issues The selection and effective use of alarm and comms systems has an impact on fire ground operations
4 World Trade Center Disaster September 11 th, 2001 NFPA only Standards Developer on initial BPAT Recommended changes from NIST studies being forwarded through TCs NFPA forms High Rise Advisory Council
5 Chicago Fire October 17 th, 2003 Around 5 pm Storage closet on the 12 th floor 6 fatalities Major recommendations regarding sprinklering, employee training, and fire department operations
6 Fire Alarm Systems Purpose of a fire alarm system Notify occupants of a fire Signal indicating an emergency Occupants to start required evacuation On activating give sufficient time for evacuation.
7 Code Requirements Note: NFPA has different terminology including general evacuation alarm, private mode and pre-signal mode
8 Fire Alarm Systems One Stage vs. Two Stage Single stage: upon the operation of any manual station, waterflow detecting device, or fire detector, cause an alarm signal to sound on all audible signal devices in the system
9 Two stage: Fire Alarm Systems One Stage vs. Two Stage a) alert signal upon the operation of any manual station, waterflow detecting device, or fire detector, b) Automatic alarm if not acknowledged within 5 min of its initiation, and c) have manual stations, that causes an alarm signal to sound Allows supervisory staff to investigate as well can allow for zoning
10 Types of Fire Alarm Systems A single-stage system in a Group F, Division 1 occupancy, A 2-stage system in a Group B occupancy, A single- or 2-stage system in a Group B, Division 3 occupancy where the building is 3 storeys or less, and A single- or 2-stage system in all other cases. Technically you can have a single stage fire alarm system in a high-rise office tower or hotel. Should this impact the design of means of egress and fire safety plans?
11 Fire Alarm Systems One Stage vs. Two Stage Two-stage alarm systems are normally used if programmed evacuation is required or if a general alarm would cause undue distress to the occupants, for example in health care facilities. Reduces the potential for false alarms In high buildings this can facilitate the staged evacuation and thus reduce the impact of the evacuation on the means of egress
12 Voice Communications Systems NBC High Buildings A voice communication system conforming to Article shall be provided in a building if a) the floor of the top storey is more than 36 m above grade, or b) a floor area or part of a floor area located above the third storey is designed or intended for use as a Group B, Division 2 or 3 occupancy.
13 Voice Communications Systems NBC also requires those with more than 1000 occupants and having a two stage alarm system to have voice communication systems to facilitate in the evacuation and messaging to the occupants. To operate the alarm system the facility is required to establish a control facility [ ]
14 Comms Centre Requirements a) a two-way means of communication with the central alarm and control facility and to the mechanical control centre from each floor area, and b) intelligible loudspeakers operated from the central alarm and control facility
15 The Problem Code may require a two stage alarm system but the NFC does not mandate that this be used This can result in inconsistent application within a jurisdiction impacts operations! The best solution is to have consistent requirements when approving fire safety plans
16 Supervisory Staff and Voice Comms Elements in the FSP The training of supervisory staff in the use of the voice communication system, The the action to be taken by supervisory staff in initiating any fire emergency systems until the fire department arrives, Instructions to the supervisory staff and fire department for the operation of the systems referred to in Clause (c), and
17 Problem with Supervisory Staff Training, and Availability The problem is that supervisory staff may not be adequately trained on how to use the system and may not be confident in its use. Property Owners let these go to alarm Impacts the credibility of the alarm system What happens when supervisory staff are not available or after hours? System goes to alarm
18 Fire Safety Messaging by Supervisory Staff Intelligible pre-recorded, synthesized, or live messages shall be designed so that the alarm signal in shall be designed so that the alarm signal in a 2-stage fire alarm system can be selectively transmitted to any zone or zones while maintaining an alert signal or selectively transmitting voice instructions to any other zone or zones in the building
19 Human Behaviour During Fire Confidence in Emergency Procedures - clear concise messaging by supervisory staff ensures that the building occupants have confidence in the overall alarm system Voice Communications are proven reinforcing queues* -- reduces alarm recognition time
20 Evacuating People with Disabilities Fire Safety Plan should identify if this is an issue and the procedures to follow Are there adequate features to allow defence in areas of refuge?
21 Types of Evacuations Total Total staged Partial Relocation Horizontal Vertical
22 Total Evacuation ALARM Single stage evacuation of a building
23 Staged Evacuation ALARM Found with 2 stage alarms alarm sent to the fire floor and remaining floors in alert notification.
24 Horizontal Relocation
25 Relocation ALARM Relocation Area Two stage alarm - notification of fire floor remainder of building in alert stage.
26 USFA Special Report Operational Considerations for Highrise Firefighting, April 1996, In some cases, occupants may be safest if they remain in place or evacuate to a floor beneath the fire floor instead of exiting the building. Firefighters should determine as quickly as possible in a fire incident whether a full, partial, or no evacuation is necessary, and communicate their evacuation plan to occupants by using a public address system or other means. Experience shows that occupants will need guidance with evacuation. Waiting until the incident to determine the evacuation plan is too late. Needs to be part of the pre-incident plan and therefore Fire Safety Plan.
27 Which Type of Evacuation? Occupancy type Risks present Occupant issues Determined in the FSP for the facility by the property owner but this selection impacts FD Ops. Building size (both height and footprint) Building layout presence of zones Building construction Protective features & alarm systems
28 Means of Egress Capacity & Occupancy Load Module 3-28 Module 3-28
29 An example of queuing. Photo taken by John Labrioladuring WTC evacuations.
30 An example of cross flow. Photo taken by John Labrioladuring WTC evacuations.
31 FD Operations Impact on operations Cross flow Can t commence stairwell attack Staging of apparatus Fire service is expected to take over voice comms on arrival SOPs needed when two stage alarm systems are present with voice comms
32 FD Operations No consistent standards or procedures adopted for this Need procedures on how they will direct occupants to evacuate. Has a direct impact on FD considerations Pre-Incident plans reflect what expectations are of building owners SOPs needed to clarify this so building owners will understand their responsibilities
33 Advantages of Effective Alarm System to Tenants/Occupants Greater confidence in systems Potential for injury is reduced Lessens the impact of false alarms on Lessens the impact of false alarms on workplace productivity
34 Advantages of an Effective Alarm System to Fire Services Proven better managed evacuations More effective fire ground operations Reduces the potential for cross flow Quicker setup in stairwell Smoother transition to take over of facility communications
35 Advantages of an Effective Alarm System to Property Owner Enhanced trust in reliability of voice systems Less lost time due to false alarms Lessens potential liability for injuries during false alarm evacuations Disadvantage need a greater emphasis on supervisory staff training on use of the system and messaging (technically required by the code)
36 Fire Safety Plans Opportunity to effect change must be approved by the local AHJ Consider an SOP for when two stage alarms with voice comms are present They must use the voice system Training & exercises for Supervisory Staff Examples of community fire safety plan templates can be downloaded on the web
37 Additional Requirements for FSP/Supervisory Staff Training Outline expectations for maintenance and testing of the system Clearly identify expectations of employees during alert and alarm stages and evacuation type required FD should consider a standardized FSP for all fire safety plans with 2 stage alarms and voice systems Example provided with the presentation
38 Additional Requirements for FSP/Supervisory Staff Training Have a working knowledge of the building fire and life safety systems. Ensure the building fire and life safety systems are in operating condition. Arrange for a substitute in their absence. Daily, monthly and yearly checks of voice and alarm systems as required by the Fire Code
39 Additional Requirements for FSP/Supervisory Staff Training Consider having standardized messaging or scripts for staff to follow Should have staff training using realistic scenarios to walk through the scripts
40 Resources NFPA Guide to Introduction to Employee Fire and Life Safety 2001 USFA Special Report: Operational Considerations for Highrise Firefighting - USFA-TR-082/April 1996
41 10 of the 29 scholarships to attend went to Canadians Including 4 from BC Continue to work to improve fire safety messaging EMAC Approved Messages - as a downloadable resource Fire Prevention Week Theme 2012 Fire Prevention Week - Have 2 Ways Out
42 PTSC-Online NFPA became a gold level sponsor in 2011 Dedicated NFPA section on the site Use for policy development and sharing materials Presentation and an opportunity to participate in a discussion forum available at:
43 Conclusion The effective use of voice comms with 2 stage alarm systems have been proven to enhance confidence in the alarm system Fire department operations are directly impacted by facilities use of these systems Standardize practice that uses the benefits of these systems and effective staff trainig benefits all
44 CONTACTING US Canadian Regional Manager: (bilingual service) Sean A. Tracey (613) (W) (613) (F) Web sites: Presentation and an opportunity to participate in a discussion forum available at:
45
46
47
48
49
CBD-233. Fire Alarm and Detection Systems
Page 1 of 5 CBD-233. Fire Alarm and Detection Systems Originally published August 1984. R.H.L. McEwen Fire alarm systems are normally required by building codes. In the case of new buildings, this is usually
CITY OF HOUSTON HIGH-RISE OFFICE BUILDING FIRE SAFETY PLAN
CITY OF HOUSTON HIGH-RISE OFFICE BUILDING FIRE SAFETY PLAN DATE PROPERTY MANAGER ADDRESS Houston, TX _(Zip Code)_ PHONE NUMBER LIFE SAFETY IS THE GOAL OF THIS PLAN. ALL DUTIES CALLED FOR HEREIN SHOULD
Life Safety Code Enabling References
SUPPLEMENT 4 Life Safety Code Enabling References Editor s Note: Supplement 4 provides users of NFPA 72, National Fire Alarm and Signaling Code, with a summary of requirements from NFPA 101, Life Safety
General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission
General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission Local Fire Alarm 064. FIRE ALARM SYSTEMS 01. Scope 02. Definitions 03.
SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES (Adopted by the State of Oregon)
SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES (Adopted by the State of Oregon) SECTION SR101 GENERAL SR101.1 General. Group SR occupancies shall comply with the provisions of this appendix
North York General Hospital Policy Manual
Page 1 of 6 POLICY STATEMENT North York General Hospital staff is responsible to follow the guidelines outlined in this document in the event of a fire to minimize injury and/or damage. DEFINITIONS Code
FIRE PREVENTION & INVESTIGATION DIVISION 125 Idylwyld Drive South Saskatoon, SK S7M 1L4 Phone: (306) 975-2578 Fax: (306) 975-2589.
FIRE PREVENTION & INVESTIGATION DIVISION 125 Idylwyld Drive South Saskatoon, SK S7M 1L4 Phone: (306) 975-2578 Fax: (306) 975-2589 Bulletin 16-12 Fire Drills This guideline was developed to assist persons
(Sample) Building Emergency Plan
(Sample) Building Emergency Plan for XXXXXX 2815 Commons Way Cincinnati, OH 45221 August 2016 University of Cincinnati Department of Public Safety Department a 2 Table of Contents A. Introduction B. Components
Module 4, Lesson 12 Fire Alarm Systems
Student Manual Module 4, Lesson 12 Fire Alarm Systems Performance Objectives At the conclusion of this lesson, you will be able to: Identify the components and functions of a fire alarm system and determine
CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002
CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002 Three new chapters were added. What was chapter 1 in 1999 was reorganized into chapters 1 (Fundamentals), 2 (Referenced Publications), and 3 (Definitions).
Rancho Cucamonga Fire Protection District Prevention Bureau Standard
Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Revised: January 2014 INTENT The intent
2007 ICC FINAL ACTION AGENDA
907.2.1.1 System initiation in Group A occupancies with an occupant load of 1,000 or more. Activation of the fire alarm in Group A occupancies with an occupant load of 1,000 or more shall initiate a signal
2012 Ontario Building Code Changes Affecting Fire Alarm Systems
2012 Ontario Building Code Changes Affecting Fire Alarm Systems CFAA Annual Technical Seminar May 31, 2013 Ken Baird VP Systems www.lrifire.com LRI 2010 Developments in Life Safety Introduction Code Development
NY Fire Safety Institute
NY Fire Safety Institute Presents the FDNY Coordinator of Fire Safety and Alarm Systems Homeless Shelters (Premise Related) Certificate of Fitness F-80 Definitions and Terminology Established 1995 Preparing
NFPA 72. Exception No. 1: Where ambient conditions prohibit installation of automatic smoke detection, automatic heat detection shall be permitted.
NFPA 72 3.3.7.2 3.3.7.2 False Alarm. Activation or reporting of an alarm for which no such alarm condition, fire or emergency actually exists. Additionally, False Alarm is the willful and knowing initiating
Hotel Fire Safety for staff
Teaching Guide Hotel Fire Safety for staff Seattle Fire Department Fire Prevention Division Hotel Fire Safety Instructor Outline Introduction Goals: To ensure that hotel employees are knowledgeable in
Fire Safety Director On Site Examination for Hotels and Office Buildings F-58 Study Guide
Fire Safety Director On Site Examination for Hotels and Office Buildings F-58 Study Guide It is recommended that this guide be kept at all times at the Fire Command Center. This publication is provided
Bold items are particular to the City of Euless
EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 2/12 Fire Chief Wes Rhodes Fire Marshal Paul Smith EFD-FMO 3-2 2009 International Fire & Building Code as Amended NFPA Standards Adopted
Fire Response Plan - Code Red
Fire Response Plan - Code Red SUMMARY & PURPOSE The purpose of the Fire Response Plan Code Red is to provide guidelines for hospital personnel to follow during a Code Red. As more fully described below,
c. As mandated by law, facilities must obtain and maintain valid zoning permits as well as permits for intended use.
Walmart Standards for Suppliers Section 7. Health and Safety 7. Health and Safety Suppliers must provide workers with a safe and healthy work environment. Suppliers must take proactive measures to prevent
Fire Alarm System Monitoring - CAN/ULC-S561-03
Fire Alarm System Monitoring - CAN/ULC-S561-03 Brian McBain ULC Regulatory Services May 4, 2011 Copyright 1995-2007 Underwriters' Laboratories of Canada. All rights reserved. No portion of this material
MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY
MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY State Fire Marshal Division 444 Cedar Street, Suite 145, St. Paul, Minnesota 55101-5145 Phone: 651/201-7200 FAX: 651/215-0525 TTY: 651/282/6555 Internet: http://www.fire.state.mn.us
A. OCCUPANT FIRE PROCEDURES... 3 B. THE TENANT FIRE SAFETY TEAM... 6 C. SENIOR FIRE WARDEN... 7 D. DEPUTY FIRE WARDEN... 8
Brookfield Place BROOKFIELD PLACE Page 2 of 12 OCTOBER 2006 TABLE OF CONTENTS A. OCCUPANT FIRE PROCEDURES... 3 B. THE TENANT FIRE SAFETY TEAM... 6 C. SENIOR FIRE WARDEN... 7 D. DEPUTY FIRE WARDEN... 8
IR F-1 EMERGENCY VOICE/ALARM COMMUNICATION SYSTEMS
IR F-1 Disciplines: Fire/Life Safety History: Revised 10-01-15 Issued 06-23-15 PURPOSE: This Interpretation of Regulations (IR) is being issued by the Division of the State Architect (DSA) to clarify when
Fire Alarm Systems Requirements by Occupancy Type
WALT WHITE Fire Chief 5770 Freeport Blvd., Suite 200 Sacramento, CA 95822-3516 Ph: (916) 808-1300 Fax: (916) 808-1629 www.sacfire.org Fire Alarm Systems Requirements by Occupancy Type 2013 California Building
Emergency Voice Communication in High-Rise Buildings. Presented by: Michael J. Klemenz, PE, SFPE
Emergency Voice Communication in High-Rise Buildings Presented by: Michael J. Klemenz, PE, SFPE Society of Fire Protection Engineers (SFPE) Established in 1950 and incorporated as an independent organization
An inventory of hazardous materials used in your workplace will prove useful.
Introduction Fire Protection is an organized approach designed to prevent fires. In the event of a fire, a fire protection program will help prevent or minimize personal injuries, losses, and harm to the
City of Bettendorf Fire Alarm System Requirements
City of Bettendorf Fire Alarm System Requirements Section 907 of the 2009 Edition of the International Fire Code (IFC) and Section 10-7-3 of the Municipal Code provide fire alarm requirements. IFC Section
The Mission Critical Fire Protection Experts
The Mission Critical Fire Protection Experts Protection Systems Protection Systems HFC-227ea / FM200 / FE-227 FE-25 / ECARO-25 Novec 1230 Inergen / Argonite Halon Drop-in Systems High and Low Pressure
COMMONWEALTH OF MASSACHUSETTS STATE BUILDING CODE 780 CMR, 6 th Edition FIRE PROTECTION SYSTEMS CHAPTER 9
COMMONWEALTH OF MASSACHUSETTS STATE BUILDING CODE 780 CMR, 6 th Edition FIRE PROTECTION SYSTEMS CHAPTER 9 GUIDELINES FOR THE PREPARATION OF FIRE PROTECTION SYSTEM NARRATIVE REPORTS 780 CMR 903.1.1 State
CHAPTER 8. Village of Caledonia Alarm Systems Ordinance (2013-11 07/01/13)
CHAPTER 8 Village of Caledonia Alarm Systems Ordinance (2013-11 07/01/13) Section Title Number 5-8-1 Title 5-8-2 Declaration of Purpose 5-8-3 Definitions 5-8-4 Administrative Rules 5-8-5 Supervised Fire
CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES
CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES Review the following information pertaining to Construction Fire Safety Planning: B.C. Building Code Sections 8.1 up to and including Subsection 8.2.3 B.C.
CTBUH Technical Paper
CTBUH Technical Paper http://technicalpapers.ctbuh.org Subject: Paper Title: Building Case Study, Fire and Safety Burj Dubai: Life Safety and Crisis Response Planning Enhancements Author(s): Evenson, J.1
Rhode Island State Fire Marshal Fire Protection Systems Narrative Reports. What is a Narrative Report?
RHODE ISLAND DIVISION OF STATE FIRE MARSHAL 1951 Smith Street, North Providence, RI 02911 Telephone: (401) 383-7717 Fax: (401) 383-8879 John E. Chartier, EFO, CFI State Fire Marshal Rhode Island State
CFAA NCR CHAPTER ANNUAL SENINAR. Commonly Overlooked Fire Alarm Requirements
CFAA NCR CHAPTER ANNUAL SENINAR Commonly Overlooked Fire Alarm Requirements Introduction of Who I Am And My Experience (aka: only legitimate chance to catch a quick nap) Definitions ( if you nap during
Agenda. Agenda (continued) Fundamentals of Fire Alarm Systems
Fundamentals of Fire Alarm Systems Sponsored by UL SFPE Austin/San Antonio Chapter San Marcos, Texas 7 January 2015 Agenda Introduction and Administration Historical Context of Today s NFPA 72 Fire Alarm
Module 5. Fire and Emergency Alarm System Part I- Basics
Module 5 Fire and Emergency Alarm System Part I- Basics 1 This module will describe: 1. Components and the arrangements of components in fire and emergency alarm systems. 2. How these systems work. 3.
OFM-TG-01-2004. Office of the Fire Marshal F M FIRE DRILLS GUIDELINE
O FIRE DRILLS F M October 2004 GUIDELINE TABLE OF CONTENTS SECTION PAGE Abstract... 3 1.0 INTRODUCTION... 4 2.0 DEFINITIONS... 4 3.0 LEGAL OBLIGATIONS... 5 4.0 FIRE DRILL OBJECTIVES... 5 5.0 FIRE DRILL
Mobile Fire Rescue Department Bureau of Fire Prevention
222 Mobile Fire Rescue Department Bureau of Fire Prevention Samuel L. Jones Mayor Stephen A. Dean Fire Chief February 2011 2009 International Fire Code Fire Alarm and Detection Systems 907.1 General. This
FIRE SPRINKLER SYSTEM SUPERVISORY SERVICE User s Guide (DamarNet RAR Service)
FIRE SPRINKLER SYSTEM SUPERVISORY SERVICE User s Guide (DamarNet RAR Service) The information provided in this user guide pertains to fire suppression sprinkler system monitoring service provided over
CAN/ULC S1001-11 Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning
CAN/ULC S1001-11 Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning Presentation To: Canadian Fire Alarm Association (CFAA) Alberta Technical Seminar
Rapid Intervention Team (RIT)
(RIT) This section identifies the appropriate AHJ Occupational Health and Safety Regulation that pertains to RIT. It further defines the various levels of RIT, procedures for deployment and suggested equipment
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems
FIRE ALARM SYSTEM RECORD OF COMPLETION
FUNDAMENTALS OF FIRE ALARM SYSTEMS 72 33 FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. PROTECTED PROPERTY
FIRE-FIGHTING DESIGN BRIEF REPORT
P a g e 1 SECTION 04 (Doc.No.A/DBR 001) FIRE-FIGHTING DESIGN BRIEF REPORT P a g e 2 1.0 SCOPE 2.0 STANDARDS AND CODES 3.0 TYPES OF SYSTEM PROPOSED 4.0 FIRE HYDRANT SYSTEM 5.0 AUTOMATIC SPRINKLER SYSTEM
FIRE ALARM SYSTEM RECORD OF COMPLETION
FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. Protected Property Information Name of property: Description
FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL
FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:
Understanding the Life Safety Code
Loss Control Department Technical Information Paper Series Understanding the Life Safety Code Copyright 1997 The Hartford Loss Control Department TIPS Series S 681.131 Printed in U.S.A. This document is
Fire Alarm Log Book. Any activity regarding this system must be documented in writing.
CASTLE ROCK FIRE AND RESCUE DEPARTMENT 300 Perry Street Castle Rock, Colo. 80104 303-660-1066 Do not remove from the premises: Fire Alarm Log Book Any activity regarding this system must be documented
HERNANDO COUNTY FIRE ALARM GUIDELINES
HERNANDO COUNTY FIRE ALARM GUIDELINES To be used for all commercial building fire alarm system plan review. The procedures set forth in this document are the minimum requirements necessary to ensure a
FIRE CODE INTERPRETATION
FIRE CODE INTERPRETATION March 2008 ISSUE: Existing Fire Alarm Systems FCI-08-06 Page 1 of 9 The purpose of this bulletin is to identify conditions where a building fire alarm system may be subject to
A study of the nature of fire risks in tall buildings
A study of the nature of fire risks in tall buildings David Charters and Carl Sherwood BRE Global 12 th March 2013 Part of the BRE Trust Overview 1. Introduction 2. Challenges of tall buildings 3. Analysis
TOWN OF WAYLAND POSITION DESCRIPTION
TOWN OF WAYLAND POSITION DESCRIPTION Title: Department: Appointing Authority: Affiliation: Assistant Fire Chief Fire Fire Chief Non-Union Grade: N-9 Personnel Board Approved: 02/29/16 Summary of Duties
Low Frequency Notification Appliances
A P P L I C A T I O N S G U I D E Low Frequency Notification Appliances APPLICATIONS GUIDE: LOW FREQUENCY NOTIFICATION APPLIANCES Low Frequency Notification Appliances Contents Introduction...3 Waking
FIRE ALARM PLAN REVIEW. Office of the State Fire Marshal Massachusetts Department of Fire Services December 2009
FIRE ALARM PLAN REVIEW Office of the State Fire Marshal Massachusetts December 2009 SURPRISE QUIZ 1. A fire alarm system is required to be installed by the MSBC, what edition of NFPA 72 do you use? 2.
Strategies for Ensuring Appropriate Occupant Response to Fire Alarm Signals
Construction Technology Update No. 43 Strategies for Ensuring Appropriate Occupant Response to Fire Alarm Signals By Guylène Proulx This Update presents strategies designed to ensure that building occupants
FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION
FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. It shall be permitted to modify this
Understanding Fire Alarm Requirements & Inspections. Presented By Bill Conroy Technical Sales For Briscoe Protective Systems Inc
Understanding Fire Alarm Requirements & Inspections Presented By Bill Conroy Technical Sales For Briscoe Protective Systems Inc Introduction Fire Alarm Requirements are structured through a system of codes.
2.4 Protected Elevators For Egress And Access During Fires In Tall Buildings
2.4 Protected Elevators For Egress And Access During Fires In Tall Buildings Richard W. Bukowski, P.E., FSFPE NIST Building and Fire Research Laboratory The events of September 11, 2001 have generated
Overview of Hotel Fire Safety Requirements
Overview of Hotel Fire Safety Requirements in the Fire Code Susan Clarke, P.Eng. Office of the Fire Marshal - January 10, 2012 1 Agenda Regulation History - Hotels Fire Code Overview (Parts 1 to 8) Defined
Workplace Fire Safety
Teaching Guide Workplace Fire Safety for staff Seattle Fire Department Fire Prevention Division Workplace Fire Safety Instructor Outline Introduction Goals: To ensure that employees are knowledgeable in
Fire Watch. Fire safety systems may not be deactivated in whole or in part for any reason other than for repairs or hot work.
Emergency Guideline GU.FAC.039 For Team Leaders, Caretakers, Trades, and Project Supervisors Approved by FS Leadership Team, August 28, 2013 Fire Watch A Fire Watch is a temporary surveillance system for
Educational. Educational-Existing 1/28/2014. OCCUPANT LOADS [no change] Application. Application
February 2014 Code Requirements and Inspections in Educational Occupancies Presented By: Barry W. Rickert Douglas M. Schanne Fire Marshal Training Program Supervisor Office of Education & Data Management
FACILITY FIRE DRILL SOP TABLE OF CONTENTS
FACILITY FIRE DRILL SOP TABLE OF CONTENTS SECTION PAGE 1. Introduction...2 2. Definitions...3 3. Fire Drill Objectives...3 4. Fire Drill Frequencies...3 5. Fire Incidents and Accidental Alarms...3 6. Drill
EMERGENCY ACTION AND FIRE PREVENTION PLAN
Sample Written Safety Program For EMERGENCY ACTION AND FIRE PREVENTION PLAN Page 1 EMERGENCY ACTION AND FIRE PREVENTION PLAN (YOUR COMPANY NAME) EMPLOYEE EMERGENCY AND FIRE PREVENTION PLANS Emergencies
ONYX EXITPOINT TM THE SOUND OF SAFETY
ONYX EXITPOINT TM THE SOUND OF SAFETY In an emergency evacuation, people often rely on their senses - especially eyesight - and memory. But in a crisis, confusion can set in. Smoke, dust, debris or visual
Fire Alarm Trainee Log Book
Fire Alarm Trainee Log Book this page is intentionally left blank canadian fire alarm association l association canadienne d alarme incendie PREFACE This training record document was developed by the Canadian
Fire Alarm System Plans Review Checklist Property location Date of Review
Fire Alarm System Plans Review Checklist Property location Date of Review 1. Is application completed in entirety? 2. Are the plans review fee submitted with the application? 3. Does floor plan include
TITLE 9-1 BURGLAR AND HOLDUP ALARM USERS REGISTRATION; FALSE ALARM
CHAPTER 1 BURGLAR AND HOLDUP ALARM USERS REGISTRATION; FALSE ALARMS SECTION: 9-1-1: Purpose 9-1-2: Definitions 9-1-3: Automatic Dialing Service; lnterconnection to Primary Trunklines 9-1-4: Testing Equipment
PARTICIPATION HOUSE 9 BUTTERNUT LANE, MARKHAM
PARTICIPATION HOUSE 9 BUTTERNUT LANE, MARKHAM B 3 CASE STUDY RANDAL BROWN & ASSOCIATES ENGINEERING LTD. CONSULTING ENGINEERS LIFE SAFETY & FIRE PROTECTION 105 6 LANSING SQUARE TORONTO, ONTARIO PARTICIPATION
UL s Alarm Certification Programs
s Alarm Certification Programs Providing confidence that systems comply with nationally recognized codes and standards by Tom Presnak Underwriters Laboratories offers several types of alarm system certification
CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services
CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 105.8a-6.1 TITLE: FIRE ALARM SYSTEM REQUIREMENTS SCOPE: This guideline
OBOA 2009 Huntsville, ON Overview of ULC Standards Affecting Building Occupancy Alan Cavers Area Manager Fire & Security Systems Group
OBOA 2009 Huntsville, ON Overview of ULC Standards Affecting Building Occupancy Alan Cavers Area Manager Fire & Security Systems Group Course Title: Rev Date Agenda Introduction to Underwriters Laboratories
How To Evacuate The University Of California Building
University of California Washington Center Emergency Evacuation Plan UC Washington Center 1608 Rhode Island Ave., NW Washington, DC 20036 Revised February 16, 2012 I. Purpose of the Plan II. Building Description
Fire Alarm system Installation Guide
Fire Alarm system Installation Guide Fire Alarm System Categories Systems designed for Protection of Property only, fall into two classifications P1 or P2. but a manual system is also needed, then this
Guidelines to Developing Emergency Action Plans for All-Hazard Emergencies in High-Rise Office Buildings
Guidelines to Developing Emergency Action Plans for All-Hazard Emergencies in High-Rise Office Buildings (Photo courtesy of Gary718/Dreamstime.com) Copyright 2013 National Fire Protection Association January
FIRE AND LIFE SAFETY TRAINING
FIRE AND LIFE SAFETY TRAINING 1 Objectives General Information Emergency Evacuation Plans / Regulatory Requirements Notification Systems Emergency Exits and Fire Doors Electrical Safety Fire Prevention
What Should I Expect From My Alarm Monitoring Station?
What Should I Expect From My Alarm Monitoring Station? When the alarm goes off... What actions will the operators take? When will they dispatch the authorities? What actions do I need to take? Monitoring
EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM
EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29CFR1910.36-29CFR1910.38-29CFR1910.157-29CFR1910.165 NFPA-10 BASIS: The OSHA Emergency Action Planning and the
DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION
Phone System Owner Phone System Engineered by: of Record Drawings: of System Manuals: of Test Reports: System Installer 1. GENERAL INFORMATION Phone Delaware License No: Certificate Holder No. System Supplier
FIRE SAFETY MANUAL. Table of contents can be found on the left side of this document.
FIRE SAFETY MANUAL Table of contents can be found on the left side of this document. 1. INTRODUCTION The University of Regina strives to preserve life and property by recognizing that a prompt, efficient
Important Ontario Fire Code Information for Building Owners in the City of Windsor
Important Ontario Fire Code Information for Building Owners in the City of Windsor This information is intended to be used a reference only. For a complete listing consult the Ontario Fire Code or contact
FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011
Office of the Fire Marshal 1.0 PERMITS FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011 1.1 To acquire an installation
FIRE ALARM SYSTEM PLAN SUBMITTAL CHECKLIST
FIRE ALARM SYSTEM PLAN SUBMITTAL CHECKLIST All fire alarm system plan submittals must include this Fire Alarm System Plan Submittal Checklist. PLAN APPROVAL - No work shall be performed until plans are
SECTION 16721 FIRE ALARM AND DETECTION SYSTEM
1. GENERAL 1.1. Related Documents: 1.2. Scope: 1.1.1. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements apply to the work specified in this
INSTRUCT-O-GRAM FIRE ALARM SYSTEMS THE HANDS-ON TRAINING GUIDE FOR THE FIRE INSTRUCTOR PERFORMANCE OBJECTIVES TASK
INSTRUCT-O-GRAM THE HANDS-ON TRAINING GUIDE FOR THE FIRE INSTRUCTOR VOLUME XIV, ISSUE 2 FIRE ALARM SYSTEMS FEBRUARY 1993 FIRE ALARM SYSTEMS ^ TASK To review public fire alarm boxes, their resetting and/or
FIRE RATED WIRING. What the FT4! Paul Latreille, C.E.T. Ottawa Branch Manager
FIRE RATED WIRING What the FT4! Paul Latreille, C.E.T. Ottawa Branch Manager INTRODUCTION OBC requirements for emergency power OBC requirements for emergency power for fire alarm systems and other building
Building Codes Update: The 2009 International Fire Code and the Apartment Industry
! Building Codes Update: The 2009 International Fire Code and the Apartment Industry Apartment operators and developers should be aware of organizational changes in the 2009 edition of the International