TABLE OF CONTENTS MAINTENANCE & TROUBLESHOOTING
|
|
|
- Susan George
- 9 years ago
- Views:
Transcription
1 SUNLINE 2000 GAS / ELECTRIC SINGLE PACKAGE AIR CONDITIONERS INSTALLATION INSTRUCTION Supersedes: N6Y (1298) N6Y (500) MODELS D2CG180 & 240 (STY. B) ( EER) /230/460 VOLT ONLY 208/230/575 VOLT ONLY SAFETY CONSIDERATIONS Due to system pressure, moving parts and electrical components, installation and servicing of air conditioning equipment can be hazardous. Only qualified, trained, service personnel should install, repair, maintain or service this equipment. Observe all precautions in the literature, on labels and tags accompanying the equipment whenever working on air conditioning equipment. Be sure to follow all other safety precautions that apply. Wear safety glasses and work gloves, and follow all safety codes. Use a quenching cloth and have a fire extinguisher available for all brazing operations. GENERAL YORK Model DCG units are single package gas-fired central heating furnaces with cooling unit designed for outdoor installation on a rooftop or a slab. The units are completely assembled on rigid, permanently attached base rails. All piping, refrigerant charge, and electrical wiring is factory installed and tested. The units require electric power, gas connection, duct connections, installation of combustion air inlet hood, flue gas outlet hoods and fixed outdoor air intake damper (units without economizer or motorized damper option only) at the point of installation. FOR YOUR SAFETY If you smell gas: 1. Open windows. 2. Don t touch electrical switches; do not use any phones in the area of the gas leak. 3. Extinguish any open flame. 4. Immediately call your gas supplier from another location. Follow your gas supplier s instructions. 5. If you cannot reach your gas supplier, call the fire department. FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. The gas-fired heaters have aluminized-steel tubular heat exchangers and spark ignition with proven pilot. INSPECTION As soon as a unit is received, it should be inspected for possible damage during transit. If damage is evident, the extent of the damage should be noted on the carrier s freight bill. A separate request for inspection by the carrier s agent should be made in writing. Refer to Form NM for additional information. REFERENCE Additional information on the design, installation, operation and service of this equipment is available in the following reference forms: Barometric Relief Damper Accessory N6.1V - Propane Conversion Accessory (USA) N6.2V - High Altitude Accessory (Nat. Gas) N6.3V - High Altitude Accessory (Propane) N13Y - Coil Guard Installation Renewal Parts: Refer to the Renewal Parts Manual for complete listing of replacement parts on this equipment. All forms referenced in this instruction may be ordered from: Standard Register 2101 West Tecumeseh Road Norman, Oklahoma Toll Free Fax: (877) Toll Free Phone: (877) APPROVALS Design certified by ETL & CGA as follows: 1. For use as a forced air furnace with cooling unit. 2. For outdoor installation only. 3. For installation on combustible material. 4. For use with natural gas or propane gas. CAUTION THIS PRODUCT MUST BE INSTALLED IN STRICT COMPLIANCE WITH THE ENCLOSED INSTALLATION INSTRUCTIONS AND ANY APPLICABLE LOCAL, STATE, AND NATIONAL CODES INCLUDING, BUT NOT LIMITED TO, BUILDING, ELECTRICAL, AND MECHANICAL CODES. WARNING INCORRECT INSTALLATION MAY CREATE A CONDITION WHERE THE OPERATION OF THE PRODUCT COULD CAUSE PERSONAL INJURY OR PROPERTY DAMAGE Installer should pay particular attention to the words: NOTE, CAUTION and WARNING. Notes are intended to clarify or make the installation easier. Cautions are given to prevent equipment damage. Warnings are given to alert installer that personal injury and/or equipment damage may result if installation procedure is not handled properly.
2 General... 1 Inspection... 1 Reference... 1 Approvals... 1 Nomenclature... 2 INSTALLATION Limitations... 3 Location... 3 Rigging and Handling... 3 Clearances... 3 Ductwork... 3 Fixed Outdoor Air Intake Damper... 4 Condensate Drain... 4 Compressors... 4 Filters... 4 Service Access... 4 Thermostat... 5 Power and Control Wiring... 5 Combustion Discharge... 5 Gas Piping... 5 Gas Connection... 6 L.P. Units, Tanks and Piping... 6 Vent and Combustion Air Hoods... 6 Optional Economizer/Mot. Damper Rain Hood... 7 Optional Power Exhaust Rain Hood... 9 OPERATION Cooling System Preliminary Operation Cooling Cooling Sequence of Operation Safety Controls (Cooling) Heating System Safety Controls (Heating) Heat Anticipator Setpoints Pre-Start Check List START-UP Operating Instructions Post-Start Check List Manifold Gas Pressure Adjustment Pilot Checkout Burner Instructions Burner Air Shutter Adjustment Checking Supply Air CFM Adjustment of Temperature Rise Checking Gas Input Secure Owner s Approval TABLE OF CONTENTS MAINTENANCE & TROUBLESHOOTING Normal Maintenance Cleaning Flue Passages and Heating Elements Troubleshooting Replacement Parts TABLES No. Description Page 1 Unit Application Data Control Wire Sizes Gas Heat Application Data Pipe Sizing Physical Data Electrical Data Four And Six Point Loads Supply Air Blower Perf. 15 Ton Supply Air Blower Perf. 20 Ton Static Resistances Power Exhaust Performance Blower Motor and Drive Data Limit Control Setting Gas Rate - Cubic Feet Per Hour FIGURES No. Description Page 1 Typical Rigging Center of Gravity Fixed Outdoor Air Damper Assembly Recommended Drain Piping Typical Field Wiring External Supply Connection Bottom Supply Connection Vent and Combustion Air Hoods Adjusting Enthalpy Setpoint Dimensions and Clearances Four and Six Point Loads Gas Valve Piping Gas Valve and Controls Typical Gas Valve Proper Flame Adjustment Typical Flame Appearance Belt Adjustment Pressure Drop versus Supply Air CFM Typical Flue Baffle Installation PRODUCT NOMENCLATURE D 2 C G N E C PRODUCT CATEGORY D = Single Package Air Conditioner (Air Cooled) PRODUCT GENERATION 2 = 2nd Generation PRODUCT IDENTIFIER NOMINAL HEATING OUTPUT CAPACITY FACTORY INSTALLED OPTION CODE EC = Sing. Input Economizer DK = Diff. Input Economizer FD = Sing. Input Economizer w/power Exhaust CF = Diff. Input Economizer w/power Exhaust BG = Motor Outdoor Air Damper CG = Gas/Electric NOMINAL COOLING CAPACITY 180 = 15 Tons 240 = 20 Tons FACTORY INSTALLED HEAT N = Natural Gas GAS 240 = 240 MBH 320 = 320 MBH VOLTAGE CODE 25 = 208/ = = Unitary Products Group
3 LIMITATIONS These units must be installed in accordance with the following national and local safety codes: In U.S.A.: 1. National Electrical Code ANSI/NFPA No National Fuel Gas Code Z Gas-Fired Central Furnace Standard ANSI Z21.47a. 4. Local gas utility requirements. In Canada: 1. Current Canadian Electrical Code C Current Gas Installation Codes CAN/CGA-B149.1 and.2 3. Local plumbing and waste water codes. 4. Other applicable local codes. Refer to the Unit Application Data table and to the Gas Heat Application Data table. After installation, the unit must be adjusted to obtain a temperature rise within the range specified on the unit rating plate. If components are to be added to a unit to meet local codes, they are to be installed at the dealer s and/or the customer s expense. Size of unit for proposed installation should be based on heat loss/heat gain calculation made according to the methods of the Air Conditioning Contractors of America (ACCA). This furnace is not to be used for temporary heating of buildings or structures under construction. TABLE 1 - UNIT APPLICATION DATA Model Size 15 TON 20 TON 208/ / 253 Voltage Variation, Min. / Max / / 630 Supply Air CFM, Min. / Max / / 9400 Wet Bulb Temperature ( F) of Air on 57 / 72 Evaporator Coil, Min. / Max. Dry Bulb Temperature ( F) of Air on Condenser Coil, Min / 120 / Max. 1Utilization range A in accordance with ARI Standard A low ambient accessory is available for operation down to 0 F. LOCATION Use the following guidelines to select a suitable location for these units. 1. Unit is designed for outdoor installation only. 2. Condenser coils must have an unlimited supply of air. Where a choice of location is possible, position the unit on either north or east side of building. WARNING:Excessive exposure of this furnace to contaminated combustion air may result in equipment damage or personal injury. Typical contaminates include: permanent wave solutions, chlorinated waxes and cleaners, chlorine based swimming pool chemicals, water softening chemicals, carbon tetrachloride, Halogen type refrigerants, cleaning solvents (e.g. perchloroethylene), printing inks, paint removers, varnishes, hydrochloric acid, cements and glues, antistatic fabric softeners for clothes dryers, masonry acid washing materials. 3. For ground level installation, use a level concrete slab with a minimum thickness of 4 inches. The length and width should be at least 6 inches greater than the unit base rails. Do not tie slab to the building foundation. 4. Roof structures must be able to support the weight of the unit and its options and/or accessories. Unit must be INSTALLATION installed on a solid level roof curb or appropriate angle iron frame. CAUTION: If a unit is to be installed on a roof curb or special frame other than a YORK roof curb, gasketing must be applied to all surfaces that come in contact with the unit underside. 5. Maintain level tolerance to 1/2 inch maximum across the entire length or width of the unit. RIGGING AND HANDLING Exercise care when moving the unit. Do not remove any packaging until the unit is near the place of installation. Rig the unit by attaching chain or cable slings to the round lifting holes provided in the base rails. Spreaders, whose length exceeds the largest dimension across the unit, MUST be used across the top of the unit. Refer to the figure below. FIG. 1 - TYPICAL RIGGING N6Y CAUTION: Before lifitng a unit, make sure that all panels are in place and that its weight is distrbuted equally on all cables so it will lift evenly. Units may also be moved or lifted with a forklift, from the front or rear only, providing that an accessory skid is used. LENGTH OF FORKS MUST BE A MINIMUM OF 90". CAUTION: An adhesive backed label is provided over the outside of the combustion air inlet opening to prevent moisture from entering the unit which could cause damage to electrical components. Allow this closure label to remain in place until the combustion air hood is to be installed (refer to Vent and Combustion Hood Figure). Refer to the Physical DataTable for unit weights and to the figure below for approximate center of gravity. FIG. 2 - CENTER OF GRAVITY CLEARANCES All units require certain clearances for proper operation and service. Installer must make provisions for adequate combustion and ventilation air in accordance with Section 5.3, Air for Combustion and Ventilation of the National Fuel Gas Code, ANSI Z223.1 (in U.S.A.) or Sections 7.2, 7.3 or 7.4 of Gas Installation Codes CAN/CGA-B149.1 and.2 (in Canada) and/or applicable provisions of the local building codes. Refer to Dimensions and Clearances Figure for the clearances required for combustible construction, servicing, and proper unit operation. WARNING: Do not permit overhanging structures or shrubs to obstruct outdoor air discharge outlet, combustion air inlet or vent outlets. Unitary Products Group 3
4 DUCTWORK Ductwork should be designed and sized according to the methods in Manual Q of the Air Conditioning Contractors of America (ACCA). A closed return duct system shall be used. This shall not preclude use of economizers or outdoor fresh air intake. The supply and return air duct connections at the unit should be made with flexible joints to minimize noise. The supply and return air duct systems should be designed for the CFM and static requirements of the job. They should NOT be sized to match the dimensions of the duct connections on the unit. CAUTION: When fastening ductwork to side duct flanges on unit, insert screws through duct flanges only. DO NOT insert screws through casing. Outdoor ductwork must be insulated and waterproofed. Refer to Dimensions and Clearances Figure for information concerning side and bottom supply and return air duct openings. It is recommended that, in Canada, the outlet duct be provided with a removable access panel. It is recommended that this opening be accessible when the unit is installed in service, and of a size such that smoke or reflected light may be observed inside the casing to indicate the presence of leaks in the heat exchanger. The cover should be attached in a manner adequate to prevent leakage. FIXED OUTDOOR AIR INTAKE DAMPER FIG. 3 - FIXED OUTDOOR AIR DAMPER from the one-inch NPT female connection on the unit to an open drain. An alternate drain connection (one-inch NPT female coupling) is provided inboard on the same centerline as the exterior location. NOTE: The condensate drain operates in a negative pressure in the cabinet. The condensate drain line MUST be trapped to provide proper drainage. See figure below. This damper is shipped inside the return air compartment. It is completely assembled and ready for installation. A damper baffle inside of the hood is adjustable to provide variable amounts of outdoor air intake on units that are not provided with an economizer or a motorized damper option. Refer to the Fixed Outdoor Damper figure. Gasketing and mounting screws are provided in a parts bag attached to the hood assembly. Apply gasketing to the three flange surfaces on the hood prior to installing the hood. Extend gasketing 1/4 inch beyond the top and bottom of the two side flanges to insure adequate sealing. Adjusting the damper to the desired air flow may be done before mounting the hood into position or (after installation) by removing the front hood panel or the screen on the bottom of the hood. Damper baffle in position 1 will allow approximately 10% recirculated air flow, position 2 approximately 15% and, to allow approximately 25%, remove the damper baffle. On units with bottom return air applications, install the damper assembly over the opening in the side return air access panel. Remove and discard the opening cover and the covering over the hood mounting holes (used for shipping) before installing. Secure with the screws provided. On units with side return air applications, install the damper assembly on the return air ductwork as close to the unit as possible. Cut an opening 16 inches high by 18 inches wide in the ductwork to accommodate the damper. Using the holes in the hood flanges as a template, drill 9/64 inch dia. (#26 drill) holes into the ductwork and secure with the screws provided. CAUTION: If outdoor air intake will not be required on units with bottom return air applications, the damper assembly should still be mounted on the side return air access panel, per the instructions above, to insure moisture is not drawn into the unit during operation. The covering over the mounting holes only need be removed. Do not remove the opening cover. CONDENSATE DRAIN Plumbing must conform to local codes. Use a sealing compound on male pipe threads. Install a condensate drain line FIG. 4 - RECOMMENDED DRAIN PIPING COMPRESSORS Units are shipped with compressor mountings factory-adjusted and ready for operation. CAUTION: Do Not loosen compressor mounting bolts. FILTERS Two-inch filters are supplied with each unit. Filters must always be installed ahead of the evaporator coil and must be kept clean or replaced with same size and type. Dirty filters will reduce the capacity of the unit and will result in frosted coils or safety shutdown. Minimum filter area and required sizes are shown in Physical Data Table. SERVICE ACCESS Access to all serviceable components is provided by the following removable panels: Compressor compartment Gas Heat compartment (Two panels) Side Supply & Return Air compartments (Two panels) Blower compartment (Three panels) Main control box Filter compartment Outdoor Air compartment (Two panels) Refer to the Dimensions and Clearances Figure for location of these access panels. CAUTION: Make sure that all screws and panel latches are replaced and properly positioned on the unit to maintain an air-tight seal. 4 Unitary Products Group
5 N6Y FIG. 5 - TYPICAL FIELD WIRING THERMOSTAT The room thermostat should be located on an inside wall approximately 56 inches above the floor where it will not be subject to drafts, sun exposure or heat from electrical fixtures or appliances. Follow manufacturer s instructions enclosed with thermostat for general installation procedure. Seven color coded insulated wires (#18 AWG) should be used to connect thermostat to unit. POWER AND CONTROL WIRING Field wiring to the unit must conform to provisions of the National Electrical Code, ANSI / NFPA No. 70 (in U.S.A.), current Canadian Electrical Code C22.1 (in Canada) and/or local ordinances. The unit must be electrically grounded in accordance with NEC and CEC (as specified above) and/or local codes. Voltage tolerances which must be maintained at the compressor terminals during starting and running conditions are indicated on the unit Rating Plate and the Unit Application Data table. The internal wiring harness furnished with this unit is an integral part of a ETL and CGA design certified unit. Field alteration to comply with electrical codes should not be required. A fused disconnect switch should be field provided for the unit. The switch must be separate from all other circuits. Wire entry at knockout openings require conduit fittings to comply with NEC (in U.S.A.), CEC (in Canada) and/or local codes. Refer to the Dimensions and Clearnaces Figure for installation location. If any of the wire supplied with the unit must be replaced, replacement wire must be of the type shown on the wiring diagram and the same minimum gauge as the replaced wire. Electrical line must be sized properly to carry the load. Use copperconductors only. Each unit must be wired with a separate branch circuit fed directly from the meter panel and properly fused. CAUTION: When connecting electrical power and control wiring to the unit, waterproof type connectors MUST BE USED so that water or moisture cannot be drawn into the unit during normal operation. The above waterproofing conditions will also apply when installing a field-supplied disconnect switch. Refer to the Typical Field Wiring figure and to the appropriate unit wiring diagram for control circuit and power wiring information. TABLE 2 - CONTROL WIRE SIZES Wire Size 1 AWG. Gauge Maximum Wire Length 2 Feet Notes: 1. Solid, Class II copper wire 2. Based on a voltage drop of 1.2 volts per wire. 3. Total wire length is from unit to room thermostat, and back to unit Unitary Products Group 5
6 TABLE 3 - GAS HEAT APPLICATION DATA Input Capacity (Mbh) 0 To 2,000 Feet Above Sea Level 2,000 To 4,500 Feet Above Sea Level 1 Output Capacity (Mbh) 0 To 2,000 Feet Above Sea Level 2,000 To 4,500 Feet Above Sea Level 1 Available on Models Gas Rate 2 (Ft. 3 /Hr.) Temp. Rise F At Full Input 3 Max. Min. Max. Min. Max. Max. Min. Max & 20 Ton & 20 Ton NOTE: Heaters are shipped available for natural gas, but can be converted to L.P. / Propane with Kit Model No. 1NP MBH rating should be reduced at the rate of 4 percent for each 1,000 feet above 4,500 feet. 2 Based on maximum input and 1075 Btu/Ft 3. 3 The air flow must be adjusted to obtain a temperature rise within the range shown. COMBUSTION DISCHARGE The products of combustion are discharged horizontally through two screened (hooded) openings on the upper gas heat access panel. GAS PIPING Proper sizing of gas piping depends on the cubic feet per hour of gas flow required, specific gravity of the gas and the length of run. National Fuel Gas Code Z223.1 (in U.S.A.) or the current Gas Installation Codes CAN/CGA-B149.1 and.2 (in Canada) should be followed in all cases unless superseded by local codes or gas utility requirements. Refer to the Pipe Sizing table. The heating value of the gas may differ with locality. The value should be checked with the local gas utility. NOTE: There may be a local gas utility requirement specifying a minimum diameter for gas piping. All units require a one-inch pipe connection at the entrance fitting. TABLE 4 - PIPE SIZING Length in Feet Nominal Iron Pipe Size 1 in. 1-1/4 in , Maximum capacity of pipe in cubic feet of gas per hour. (Based upon a pressure drop of 0.3 inch water column and 0.6 specific gravity gas). lie below the bottom gas manifold to avoid interference with the burner assembly. Two grommets are shipped in the blower compartment (in parts bag taped to the blower housing) of every unit with gas heat and should be used in the knockouts when the gas piping penetrates the front of the unit. After the gas supply piping has been installed, the bottom opening in the unit should be sealed to prevent water from leaking into the building. Gas piping recommendations: 1. A drip leg and a ground joint union must be installed in the gas piping. 2. When required by local codes, a manual shut-off valve may have to be installed outside of the unit. 3. Use wrought iron or steel pipe for all gas lines. Pipe compound should be applied sparingly to male threads only. WARNING: Natural gas may contain some propane. Propane, being an excellent solvent, will quickly dissolve white lead or most standard commercial compounds. Therefore, a special pipe compound must be applied when wrought iron or steel pipe is used. Shellac base compounds such as Gaskolac or Stalastic, and compounds such as Rectorseal #5, Cyde s or John Crane may be used. 4. All piping should be cleaned of dirt and scale by hammering on the outside of the pipe and blowing out the loose dirt and scale. Before initial start-up, be sure that all of the gas lines external to the unit have been purged of air. 5. The gas supply should be a separate line and installed in accordance with all safety codes as prescribed under Limitations. After the gas connections have been completed, open the main shut-off valve admitting normal gas pressure to the mains. Check all joints for leaks with soap solution or other material suitable for the purpose. NEVER USE A FLAME. 6. The furnace and its individual manual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.48kPa). The furnace must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.48kPa). 7. A 1/8 inch NPT plugged tapping, accessible for test gage connection, must be installed immediately upstream of the gas supply connection to the furnace. FIG. 6 - EXTERNAL SUPPLY CONNECTION EXTERNAL SHUT-OFF GAS CONNECTION The gas supply line can be routed through the knockouts located on the front of the unit or through the opening provided in the unit s base. Refer to the Dimensions and Clearances figure to locate these access openings. Typical supply piping arrangements are shown in the figures on this page. All shaded items are field-supplied. If gas supply line is routed through the unit s base ensure that the burner assembly can be removed for maintenance without disturbing the supply line. The supply piping and fittings must FIG. 7 - BOTTOM SUPPLY CONNECTION EXTERNAL SHUT-OFF L.P. UNITS, TANKS AND PIPING All gas heat units are shipped from the factory equipped for natural gas use only. The unit may be converted in the field for use with L.P./propane gas with accessory kit model number 1NP Unitary Products Group
7 VENT AND COMBUSTION AIR HOODS N6Y VENT AIR OUTLET HOODS COMBUSTION AIR INTAKE HOOD SLOTTED OPENINGS IN ACCESS PANEL GAS HEAT ACCESS PANELS Two vent hoods and a combustion air hood (with screens) are shipped attached to the blower housing in the blower compartment. These hoods must be installed to assure proper unit function. All hoods must be fastened to the outside of the gas heat access panel with the screws provided in the bag also attached to the blower housing. The screen for the combustion air intake hood is secured to the inside of the access panel opening with four fasteners and the screws used for mounting the hood to the panel. The top flange of this hood slips in under the top of the access panel opening when installing. Refer to Vent and Combustion Air Hood figure. Each vent hood is installed by inserting the top flange of the hood into the slotted opening in the access panel and securing in place. OPTIONAL ECONOMIZER/MOTORIZED DAMPER RAIN HOOD The instruction for the optional economizer/motorized damper rain hood can be found in form Use these instructions when field assembling an economizer rain hood onto a unit. The outdoor and return air dampers, the damper actuator, the damper linkage, the outdoor and return air divider baffles, and all the control sensors are factory mounted as part of the Factory installed economizer option. ENTHALPY SET POINT ADJUSTMENT FIG. 8 - VENT AND COMBUSTION AIR HOODS All L.P./propane gas equipment must conform to the safety standards of the National Fire Protection Association. For satisfactory operation, L.P./propane gas pressure must be 8.8 inch W.C at the unit under full load. Maintaining proper gas pressure depends on three main factors: 1. The vaporization rate which depends on (a) the temperature of the liquid and (b) the wetted surface area of the container or containers. 2. The proper pressure regulation. (Two-stage regulation is recommended from the standpoint of both cost and efficiency.) 3. The pressure drop in the lines between regulators and between the second stage regulator and the appliance. Pipe size required will depend on the length of the pipe run and the total load of all appliances. Complete information regarding tank sizing for vaporization, recommended regulator settings, and pipe sizing is available from most regulator manufacturers and L.P./propane gas suppliers. L.P./propane gas is an excellent solvent and special pipe compound must be used when assembling piping for this gas as it will quickly dissolve white lead or most standard commercial compounds. Shellac base compounds such as Rectorseal #5 are satisfactory for this type of gas. Check all connections for leaks when piping is completed, using a soap solution. NEVER USE A FLAME. Remove the economizer access panel from the unit to check the following adjustments. Loosen but do not remove the two panel latches. CAUTION: Extreme care must be exercised in turning both the setpoint and minimum position adjusting screws to prevent twisting them off. 6. The enthalpy set point may now be set by selecting the desired setpoint shown in the Adjsuting Enthalpy Setpoint figure. Adjust as follows: For a single enthalpy operation, carefully turn the set point adjusting screw to the A, B, C or D setting corresponding to the lettered curve. For a dual enthalpy operation, carefully turn the set point adjusting screw fully clockwise past the D setting. 7. To check that the damper blades move smoothly without binding, carefully turn the minimum position adjusting screw fully clockwise and then energize and de-energize terminals R to G. With terminals R to G energized, turn the minimum position screw counterclockwise until the desired minimum position has been attained. 8. Replace the economizer access panel. Reposition the two latches horizontally and retighten the screws. POWER EXHAUST/BAROMETRIC RELIEF DAMPER AND RAIN HOOD OPTION The instructions for the power exhaust/barometric relief damper and rain hood can be found in form The exhaust fan, all supporting brackets, angles, and the wiring are factory installed as part of the power exhaust option. All of the components, including the dampers, hardware, and mounting instructions are shipped in a single package external from the unit. The hood must be field assembled and installed. Power exhaust is not available as a field installed option. Unitary Products Group 7
8 FIG. 9 - ENTHALPY SETPOINT ADJUSTMENT 8 Unitary Products Group
9 TABLE 5 - PHYSICAL DATA EVAPORATOR BLOWER EVAPORATOR COIL CONDENSER FAN (Two Per Unit) CONDENSER COIL COMPRESSOR (Qty. Per Unit) AIR FILTERS CHARGE *This compressor will be energized first. MODELS UNIT SIZE 15 TON 20 TON CENTRIFUGAL BLOWER (Dia. x Wd. in.) 15 x x 15 FAN MOTOR HP ROWS DEEP 3 3 FINS PER INCH FACE AREA (Sq. Ft.) PROPELLER DIA. (in.) (Each) FAN MOTOR HP (Each) 1 1 NOM. CFM TOTAL (Each) ROWS DEEP 2 2 FINS PER INCH FACE AREA (Sq. Ft.) TON TANDEM 1* 2 5-TON HERMETIC 1 - QUANTITY PER UNIT (16" X 20" X 2") - 4 QUANTITY PER UNIT (16" X 25" X 2") - 4 QUANTITY PER UNIT (18" X 24" X 2") 5 - TOTAL FACE AREA (sq. ft.) REFRIGERANT 22 SYSTEM NO. 1 17/8 18/0 (lbs./oz.) SYSTEM NO. 2 8/8 18/0 OPERATING WEIGHTS (LBS.) 15 TON 20 TON Basic Unit 240 Mbh Mbh Economizer 160 Options Economizer with Power Exhaust 245 Motorized Damper 150 Roof Curb Accessories Barometric Damper Wood Skid Unitary Products Group 9
10 TABLE 6 - ELECTRICAL DATA MODEL DCG180 DCG240 POWER SUPPLY COMPRESSORS #1 #2 RLA LRA RLA LRA COND. FAN MOTORS (#1 & #2) HP FLA EACH EACH SUPPLY AIR BLOWER MOTOR HP FLA MINIMUM CIRCUIT AMPACITY (AMPS) MAXIMUM TIME DELAY FUSE SIZE (AMPS) 208/ / / / / / / / VOLTAGE POWER SUPPLY MIN. MAX. VOLTAGE LIMITATIONS** 208/ **Utilization Range A in accordance with ARI Standard Unitary Products Group
11 * 9-4 ) * ) * ) ) ) K N EE= HO. 1 -, ,, ) ,, ) : -, 7 6, ) - ) 1 4 ), : 0 ) ) 1 0, 5 5 A A J = E ; ) A A J = E : ) + 1 / 7 ) 4, RETURN AIR SUPPLY AIR, /. HF HA I I K HA, H F 4 A E C / ) ) 6 ) * ) ) D M I A F = H = J A O J EK, I JH = J A * J J, K? J F A E C I 2/ ) M5 A5H7 2 2 ; / = I 2 EF E C + A? J-E 6 4 ;? = JE I! " & 6 - " $ # &. H? K H > K J K EJ I H A B A H J J D A? K H > D = C A H ' E A I E I B J D A? K H > B H J D A F H F A H I E A B J D A I K F F O HA JK H= EH@ K? J? A? JE I & & '! " " & # & # 6 # # & 6 * / ; ) / ; CONDENSER AIR OUTDOOR AIR (Economizer) 8-6 ) 1 4 +, , 5 # + * % & ) # " # 6 0,! $ " 6 All dimensions are in inches. They are subject to change without notice. Certified di- $! & '! " ' + # % & mensions will be provided upon request. ) / ) ; / ; " $ # & ; * : ) ! # * / UTILITIES ENTRY DATA * ; ; ), OPENING ) / 5 " # 6 5 A A J A HOLE SIZE USED FOR! # " ) 1 4!! " (DIA.)!! ; 1-1/8" KO Control Front ) 1 4 A 3/4" NPS (Fem.) Wiring Bottom B 3-5/8" KO Power Front 3" NPS (Fem.) Wiring Bottom C 2-3/8" KO Gas Piping (Front) D 1-11/16" Hole Gas Piping (Bottom)* *Opening in the bottom of the unit can be located by the slice in the insulation. DUCT COVERS - Units are shipped with the bottom duct openings covered. An accessory flange kit is available for connecting side ducts. For bottom duct applications: 1. Remove the side panels from the supply and return air compartments to gain access to the bottom supply and return air duct covers. 2. Remove and discard the bottom duct covers. (Duct openings are closed with sheet metal covers except when the unit includes a power exhaust option. The covering consists of a heavy black paper composition.) 3. Replace the side supply and return air compartment panels. For side duct applications; 1. Replace the side panels on the supply and return air compartments with the accessory flange kit panels. 2. Connect ductwork to the duct flanges on the rear of the unit. / ) 7 / ) "! & # ) ) , ; ) 14 ) ) 1 4 ) ; ) 1 4 & # & # & ) 1 4 %! " 7 6, 4 ) 1 4 & # & # 6 I! ' # & 6 I - 8 ) 2 4 ) " 7 6, 4 ) ) ) ) - +,, 4 ) DETAIL X (ACCESSORY SIDE SUPPLY AND RETURN AIR OPENINGS) FIG DIMENSIONS & CLEARANCES - 15 & 20 TON , ) ; : 0 ) 7 5 6, ) ) ) 1 0, 4 ) 1 0, 4 A J K ) H EH + F = H J A J K H ) EH + F = - H + J A J , - ), 2-4 ), : 0 ) ) 1 0, 5, /. HF HA I I K H F H A E C ) ! $ $ $. 1 : -, 7 6, ) ) 0-,? = J 4 A JK H) EH + F = H J A J 4 - ) , - 6 ) 1 ; ) 1 0, 5 CLEARANCES! " " #! $ " $ & Front 36" Back 24" (Less Economizer) 49" (With Economizer) Left Side (Filter Access) 24" (Less Economizer) 36" 3 (With Economizer) Right Side (Cond. Coil) 36" Below Unit 1 20" 72" With 36" Maximum Above Unit 2 Horizontal Overhang (For Condenser Air Discharge Outlet) +, ) 6 -, 4 ) 1 K I J > A J H = F F 1Units (applicable in U.S.A. only) may be installed on combustible floors made from wood or class A, B or C roof covering material. 2 Units must be installed oudoors. Overhanging structures or shrubs should not obstruct condenser air discharge outlet. 3 If economizer is factory installed, the assembled hood kit must be removed prior to final installation. This hood is 54" long. NOTE: A one-inch clearance must be provided between any combustible material and the supply air ductwork for a distance of 3 feet from the unit. The products of combustion must not be allowed to accumulate within a confined space and recirculate. Locate unit so that the vent air outlet hoods are at least: Three (3) feet above any forced air inlet located within 10 horizontal feet (excluding those integral to the unit). Four (4) feet below, 4 horizontal feet from, or 1 foot above any door or gravity air inlet into the building. Four (4) feet from electric meters, gas meters, regulators and relief equip- Unitary Products Group 11 '
12 4 POINT LOADS FIG FOUR AND SIX POINT LOADS 6 POINT LOADS TABLE 7 - FOUR AND SIX POINT LOADS UNIT 4 - POINT LOADS (LBS) TOTAL A B C D NOTE: These weights are with economizer, and the largest blower motor available. UNIT 6 - POINT LOADS (LBS) TOTAL A B C D E F NOTE: These weights are with economizer and the largest blower motor available. CENTER OF GRAVITY 12 Unitary Products Group
13 TABLE 8 - SUPPLY AIR BLOWER PERFORMANCE (15 TON) N6Y DCG180 - BOTTOM DUCT CONNECTIONS BLOWER SPEED, (RPM) MOTOR PULLEY (TURNS OPEN)* CFM ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW 208 VOLT AND STANDARD DRIVE ** VOLT AND HIGH SPEED DRIVE ACCESSORY /460 VOLT AND STANDARD DRIVE ** /460 VOLT AND HIGH SPEED DRIVE ACCESSORY NOTES: 1. Blower performance includes a gas-fired heat exchanger, fixed outdoor air, two-inch T/A filters and a dry evaporator coil. 2. Refer to the additional Static Resistances table. ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower. * Do NOT close the pulley below 1 turn open. ** Factory setting. Unitary Products Group 13
14 TABLE 9 - SUPPLY AIR BLOWER PERFORMANCE (20 TON) DCG240 - BOTTOM DUCT CONNECTIONS BLOWER SPEED, (RPM) MOTOR PULLEY (TURNS OPEN)* CFM ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW 208 VOLT AND STANDARD DRIVE ** VOLT AND HIGH SPEED DRIVE ACCESSORY /460 VOLT AND STANDARD DRIVE ** /460 VOLT AND HIGH SPEED DRIVE ACCESSORY NOTES: 1. Blower performance includes a gas-fired heat exchanger, fixed outdoor air, two-inch T/A filters and a dry evaporator coil. 2. Refer to the additional Static Resistances table. ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower. * Do NOT close the pulley below 1 turn open. ** Factory setting. 14 Unitary Products Group
15 TABLE 10 - STATIC RESISTANCES* EXTERNAL STATIC PRESSURE DROP RESISTANCE, IWG DESCRIPTION CFM 15 TON 20 TON WET COIL ECONOMIZER OPTION HORIZONTAL DUCT CONNECTIONS *Deduct these resistance values from the available unit ESP values listed in the respective blower performance table except for Horizontal Duct Connections (Shaded ). Add these values due to less airflow resistance. TABLE 11 - POWER EXHAUST PERFORMANCE MOTOR SPEED STATIC RESISTANCE OF RETURN DUCTWORK, IWG CFM KW CFM KW CFM KW CFM KW CFM KW HIGH* MEDIUM LOW *Factory Setting Power Exhaust motor is a 3/4 HP, PSC type with sleeve bearings, a 48 frame and inherent protection. TABLE 12 - BLOWER MOTOR AND DRIVE DATA MOTOR 1 BELT ADJUSTABLE MOTOR PULLEY FIXED BLOWER PULLEY BLOWER (NOTCHED) MODEL DRIVE RANGE SIZE (RPM) HP FRAME EFF. OUTSIDE PITCH OUTSIDE PITCH PITCH DESIG- BORE DESIG- BORE DESIG- DIA. DIA. DIA. DIA. LENGTH QTY. (%) NATION (IN.) NATION (IN.) NATION (IN.) (IN.) (IN.) (IN.) (IN.) Standard 850/1065 BK BX TON High 5 184T 83 1VP /8 Speed 965/1190 BK BX Access Standard 870/1025 BK /16 BX TON High T 89 1VP /8 Speed 950/1120 BK /16 BX Access 1All motors have a nominal speed of 1800 RPM, a 1.15 service factor and a solid base. They can operate to the limit of their service factor because they are located in the moving air, upstream of any heating device. 2 Do NOT close this pulley below 1 turn open. Unitary Products Group 15
16 OPERATION COOLING SYSTEM The cooling section is a complete factory package utilizing an air-cooled condenser. The system is factory-charged with Refrigerant-22. The compressors are hermetically sealed, internally sprung and base mounted with rubber insulated hold-down bolts. Compressors have inherent (internal protection. If there is an abnormal temperature rise in compressor, the protector will open to shut down the compressor. PRELIMINARY OPERATION COOLING After installation has been completed, energize the crankcase heaters for at lest four hours before operation the unit. After the initial installation, the compressors should be given three false starts (energized just long enough to make a few revolutions with 5-7 minutes delay between each start, before being put into full time service. COOLING SEQUENCE OF OPERATION NO OUTDOOR AIR OPTIONS - When the room thermostat calls for first-stage cooling, the low voltage control circuit from R to G and Y1" is completed to energize compressor #1, condenser fan motor #1, condenser fan motor #2 (if the ambient temperature is above 60 F), and the supply air blower motor (if the fan switch on the room thermostat is set in the AUTO" position). When the thermostat calls for second-stage cooling, the low voltage control circuit from R to Y2" is completed to energize compressor #2. After the thermostat is satisfied and opens, all components will stop simultaneously. The blower motor will continue to operate if the fan switch on the room thermostat is set in the ON position. ECONOMIZER WITH SINGLE ENTHALPY SENSOR - When the room thermostat calls for first-stage cooling, the low voltage control circuit from R to G and Y1" is completed. The R" to G circuit energizes the blower motor (if the fan switch on the room thermostat is set in the AUTO position) and drives the economizer dampers from fully closed to their minimum position. If the enthalpy of the outdoor air is below the setpoint of the enthalpy controller (previously determined), Y1" energizes the economizer. The dampers will modulate to maintain a constant supply air temperature as monitored by the discharge air sensor. If the outdoor air enthalpy is above the setpoint, Y1" energizes compressor #1, condenser fan motor #1, and condenser fan motor #2 (if the ambient temperature is above 60 F). When the thermostat calls for second-stage cooling, the low voltage control circuit from R to Y2" is completed. If the enthalpy of the outdoor air is below the setpoint of the enthalpy controller (i.e. first stage has energized the economizer), Y2" will energize compressor #1. If the outdoor air is above the setpoint, Y2" will energize compressor #2. After the thermostat is satisfied and opens, all components will stop simultaneously. The blower motor will continue to operate if the fan switch on the room thermostat is set in the ON position. ECONOMIZER WITH DUAL ENTHALPY SENSORS - The operation with the dual enthalpy sensors is identical to the single sensor except that a second enthalpy sensor is mounted in the return air. This return air sensor allows the economizer to choose between outdoor air and return air, whichever has the lowest enthalpy value, to provide maximum operating efficiency. ECONOMIZER (SINGLE OR DUAL) WITH POWER EXHAUST - This system operates as specified above with one addition. The power exhaust motor is energized whenever the economizer is chosen by the enthalpy sensor for first stage cooling, Y1". As always, the R" to G connection provides minimum position but does not provide power exhaust operation. MOTORIZED OUTDOOR AIR DAMPERS - This system operation is the same as the units with no outdoor air options with one exception. When the R to G circuit is complete, the motorized damper drives open to a position set by the thumbwheel on the damper motor. When the R to G circuit is opened, the damper spring returns fully closed. CONTINUOUS BLOWER - Continuous blower operation is possible by closing the R to G circuit on the thermostat. SAFETY CONTROLS Each refrigerant system is equipped with the following safety controls: 1. A Suction Line Freezestat to protect against low evaporator temperatures due to a low air flow or a low return air temperature. (Opens at 26 F +5 F and resets at 38 F + 5 F.) 2. A High Pressure Cutout Switch to protect against excessive discharge pressures due to a blocked condenser coil or a condenser motor failure. (Opens at 380 psig + 10 and resets at 300 psig + 10.) 3. A Low Pressure Switch to protect against loss of refrigerant charge. (Opens at 7 psiog + 3 and resets at 22 psig + 5.) If either one of the above safety controls opens, that individual refrigerant system will be locked out. The other refrigerant system will continue in operation unless it too is effected by the same fault. The lock out of either system can be reset by opening the 24V circuit either at the room thermostat or at the unit disconnect. HEATING SYSTEM The following sequence describes the operation of the gas heat section. CONTINUOUS BLOWER With the room thermostat switch set to ON, the supply air blower will operate continuously. The normally closed contact K5-1" provides 24 volt power to the 3M contactor. The 3M-1, 2 & 3" power contacts close and the blower motor operates. INTERMITTENT BLOWER With the room thermostat system switch set to the AUTO or HEAT position and the fan switch set to AUTO, the supply air blower will operate after the room thermostat calls for heat and the time delay relay closes. The TH1" closes, the heat relay RW1" is energized. The RW1-1 power contact closes energizing the line voltage draft motor. The RW1-2" contact is also closed. As the speed of the draft motor reaches approximately 2500 RPM, the centrifugal switch contact located on the end of the draft motor shaft closes to power the first stage ignition module IC1. Ignition module IC1" will immediately start the first stage ignitor sparking and will open the redundant valve located inside the first stage main gas valve GV1 to allow a flow of gas to only the first stage carryover tube. Only after the pilot flame has been ignited and the presence of pilot flame detected at the IC1 by a signal sent back through the flame sensor is sparking terminated and the first stage main gas valve opened. Gas flows into each of the main burners and is ignited from the carryover tube flame. If IC1 fails to detect a pilot flame, it will continue to try for a maximum of 85 seconds to ignite the pilot tube. If the pilot flame is not detected, then IC1" will lock out first stage furnace 16 Unitary Products Group
17 operation until 24V power is removed from the module either at the unit or by resetting the room thermostat. At the same time power was supplied to the RW1, a parallel circuit activates ETD which closes the ETD contact after approximately 35 seconds and energizes K5" which closes K5-2" and starts the blower by energizing 3M. When TH2" closes, heat relay RW2" is energized. The RW2-1" contact is closed energizing the second stage ignition module IC2". IC2" will immediately start the second stage ignitor sparking and will open the redundant valve located inside the second stage main gas valve GV2" to allow a flow of gas to the second stage carryover tube. Only after the pilot flame has been ignited and the presence of pilot flame detected at IC2" by a signal sent back through the flame sensor is sparking terminated and the main gas valve opened. Gas flows into each of the second stage main burners and is ignited from the carryover tube flame. If IC2" fails to detect a pilot flame, it will continue to try for a maximum of 85 seconds to ignite the pilot tube. If the pilot flame is not detected, then IC2" will lock out first stage furnace operation until 24V power is removed from the module either at the unit or by resetting the room thermostat. Note that the second stage furnace can operate even if first stage has locked out N6Y 4. Flame Sensor Rod / 100% Ignition Control Lock-Out. The flame rods and controls are located per Proper Flame Adjustment figure. If an ignition control fails to detect a signal from the flame sensor indicating the pilot flame is properly ignited, then the main gas valve will not open. It will continue to try and ignite the pilot for a maximum of 85 seconds, then if the pilot flame is not detected, the ignition control will lock out furnace operation until 24V power is removed from the module either at the unit or by resetting the room thermostat. 5. Rollout Switch. This switch is located above the main burners in the control compartment which in the event of a sustained main burner rollout shuts off and locks out both ignition controls closing both gas valves. The ignition controls lock out furnace operation until 24V power is removed from the controls either at the unit or by resetting the room thermostat. Note the auto reset rollout switch must reset before allowing furnace operation. 6. Auxiliary limit switch (AUX) - This control is located inside the heat exchanger compartment and is set to open at TABLE 13 - LIMIT CONTROL SETTING Units Capacity, MBH Limit Control (Tons) Input Output Opens, F 15 & & REDUNDANT VALVE MAIN VALVE 1 / GAS MAIN GAS VALVE TO PILOT BURNER FIG GAS VALVE PIPING When the heating cycle is complete, TH2" opens de-energizing the RW2" then TH1" opens de-energizing RW1" and ETD, thus closing all gas valves. The blower motor will continue to run (approximately 45 seconds after the furnace is shut down) until ETD opens, de-energizing the K5" relay and 3M" contactor. SAFETY CONTROLS TO MAIN BURNER The control circuit includes the following safety controls: 1. Limit Control (LS). This control is located inside the heat exchanger compartment and is set to open at the temperature indicated in the Limit Control Setting Table. It resets automatically. The limit switch operates when a high temperature condition, caused by inadequate supply air flow occurs, thus shutting down the ignition control and closing the main gas valves and energizing the blower. 2. Centrifugal Switch (CS). If the draft motor should fail, the centrifugal switch attached to the shaft of the motor prevents the ignition controls and gas valves from being energized. 3. Redundant Gas Valve. There are two separate gas valves in the furnace. Each valve contains a main and a redundant valve. The redundant valves are located upstream of the main gas valves. Should either or both of the main gas valves fail in the open position the redundant valves serve as back-ups and shuts off the flow of gas. 1/ F. It is a manual reset switch. If AUX trips, then the primary limit has not functioned correctly. Replace the primary limit. HEAT ANTICIPATOR SETPOINTS It is important that the anticipator setpoint be correct. Too high of a setting will result in longer heat cycles and a greater temperature swing in the conditioned space. Reducing the value below the correct setpoint will give shorter ON cycles and may result in the lowering of the temperture within the conditioned space. Gas Valve / 8 / ) 5 8 ) 8-1 / Honeywell VR8440 White-Rodgers 36C / 8 / ) 5 8 ) 8-1 / * ) FIG 13-GAS VALVE AND CONTROLS Anticipator Setpoint 1st Stage 2nd Stage 0.30 amp 0.11 amp Unitary Products Group 17
18 PRE-START CHECK LIST Complete the following checks before starting the unit. START-UP inches, nor the operating pressure drop below 5.0" for natural gas units. If gas pressure is outside these limits, contact the local gas utility for corrective action. 1. Check the type of gas being supplied. Be sure that it is the same as listed on the unit nameplate. 2. Make sure that the vent and combustion air hoods have been properly installed. OPERATING INSTRUCTIONS CAUTION: This furnace is equipped with an intermittent pilot and automatic re-ignition system. DO NOT attempt to manually light the pilot. TO LIGHT PILOT AND MAIN BURNERS: 1. Turn off electric power to unit. 2. Turn room thermostat to lowest setting. 3. Turn gas valve knob to on position. 4. Turn on electric power to unit. 5. Set room thermostat to desired temperature. (If thermostat set temperature is above room temperature, pilot burner ignition will occur and, after an interval to prove pilot flame, main burners will ignite). TO SHUT DOWN: MANIFOLD GAS PRESSURE ADJUSTMENT Small adjustments to the high-fire gas flow may be made by turning the pressure regulator adjusting screw on the automatic gas valve. Adjust as follows: 1. Remove the cap on the regulator. It s located next to the push-on electrical terminals. 2. To decrease the gas pressure, turn the adjusting screw counterclockwise. 3. To increase the gas pressure, turn the adjusting screw clockwise. NOTE: The correct manifold pressure for these furnaces is 3.65 IWG ±0.3. * ) * ; * 4 ) ) * 7 * 1. Turn off electric power to unit. 2. Depress knob of gas valve while turning to off position. POST-START CHECK LIST (GAS) After the entire control circuit has been energized and the heating section is operating, make the following checks: 1. Check for gas leaks in the unit piping as well as the supply piping. 2. Check for correct manifold gas pressures. See Checking Gas Input. 3. Check the supply gas pressure. It must be within the limits shown on rating nameplate. Supply pressure should be checked with all gas appliances in the building at full fire. At no time should the stand by gas line pressure exceed 13 ON-OFF CONTROL HIGH FIRE ADJ. (UNDER SCREW) PILOT ADJ. (UNDER SCREW) FIG TYPICAL GAS VALVE PILOT CHECKOUT The pilot flame should envelope the end of the flame sensor. To adjust pilot flame, (1) remove pilot adjustment cover screw, (2) increase or decrease the clearance for air to the desired level, (3) be sure to replace cover screw after adjustment to prevent possible gas leakage. Put the system into operation and observe through complete cycle to be sure all controls function properly. BURNER INSTRUCTIONS & / ) 2 * ) 4 4 ; * - ),. ) * 7 * + ) 4 4 ; * - FIG PROPER FLAME ADJUSTMENT To check or change burners, pilot or orifices, CLOSE MAIN MANUAL SHUT-OFF VALVE AND SHUT OFF ALL ELECTRIC POWER TO THE UNIT. 1. Remove the screws holding either end of the manifold to the burner supports. 2. Open the union fitting in the gas supply line just upstream of the unit gas valve and downstream from the main manual shut-off valve. 18 Unitary Products Group
19 3. Remove the gas piping closure panel. 4. Disconnect wiring to the gas valves and spark ignitors. Remove the manifold-burner gas valve assembly by lifting up and pulling back N6Y static pressures. Use Model 1LD0416 for 15 ton units and Model 1LD0417 for 20 ton units. Refer to the Blower Motor and Drive Data Table. Note the following: 1. The supply air CFM must be within the limitations shown in the Applications Data Table. 2. Pulleys can be adjusted in half turn increments. 3. The tension on the belt should be adjusted as shown in the Belt Adjustment figure. FIG TYPICAL FLAME APPEARANCE Burners are now accessible for service. Reverse the above procedure to replace the assemblies. Make sure that burners are level and seat at the rear of the heat exchanger. BURNER AIR SHUTTER ADJUSTMENT Adjust burner shutters so no yellow flame is observed in the heat exchanger tubes. CHECKING SUPPLY AIR CFM The RPM of the supply air blower will depend on the required CFM, the unit accessories or options and the static resistances of both the supply and the return air duct systems. With this information, the RPM for the supply air blower and the motor pulley adjustment (turns open) can be determined from the Blower Performance Data Tables. Start the supply air blower motor. Adjust the resistances in both the supply and the return air duct systems to balance the air distribution throughout the conditioned space. The job specifications may require that this balancing be done by someone other than the equipment installer. To check the supply air CFM after the initial balancing has been completed: 1. Remove the two 5/16 inch dot plugs from the blower motor and the filter access panels shown in the Dimensions and Clearances figure. 2. Insert at least 8 inches of 1/4 inch tubing into each of these holes for sufficient penetration into the air flow on both sides of the indoor coil. NOTE: The tubes must be inserted and held in a position perpendicular to the air flow so that velocity pressure will not affect the static pressure readings. 3. Using an inclined manometer, determine the pressure drop across a dry evaporator coil. Since the moisture on an evaporator coil may vary greatly, measuring the pressure drop across a wet coil under field conditions would be High speed drive accessories (containing a smaller blower pulley and a shorter belt) are available for applications requiring the supply air blower to produce higher CFM s and/or higher FIG.17 - BELT ADJUSTMENT FIG PRESSURE DROP ACROSS A DRY INDOOR COIL VS SUPPLY AIR CFM Unitary Products Group 19
20 inaccurate. To assure a dry coil, the compressors should be deactivated while the test is being run. 4. Knowing the pressure drop across a dry coil, the actual CFM through the unit and clean 2 inch filters, can be determined from the curve in Pressure Drop vs. Supply Air CFM figure. WARNING: Failure to properly adjust the total system air quantity can result in extensive blower damage. After readings have been obtained, remove the tubes and reinstall the two 5/16 inch dot plugs that were removed in Step 1. NOTE: DE-ENERGIZE THE COMPRESSORS BEFORE TAKING ANY TEST MEASUREMENTS TO ASSURE A DRY INDOOR COIL. ADJUSTMENT OF TEMPERATURE RISE The temperature rise (or temperature difference between the return air and the heated air from the furnace) must lie within the range shown on the ETL rating plate and the data in the Gas Heat Application Table. After the temperature rise has been determined, the cfm can be calculated as follows: After about 20 minutes of operation, determine the furnace temperature rise. Take readings of both the return air and the heated air in the ducts (about six feet from the furnace) where they will not be affected by radiant heat. Increase the blower cfm to decrease the temperature rise; decrease the blower cfm to increase the rise. Refer to the Blower Motor and Drive Data Table. BELT DRIVE BLOWER Btuh Input x 0.8 CFM = 1.08 x o F Temp. Rise All units have belt drive single-speed blower motors. The variable pitch pulley on the blower motor can be adjusted to obtain the desired supply air CFM. 1. Turn off all other gas appliances connected to the gas meter. 2. With the furnace turned on, measure the time needed for one revolution of the hand on the smallest dial on the meter. A typical gas meter usually has a 1/2 or a 1 cubic foot test dial. 3. Using the number of seconds for each revolution and the size of the test dial increment, find the cubic feet of gas consumed per hour from the Gas Rate - Cubic Feet Per Hour Table. If the actual input is not within 5% of the furnace rating (with allowance being made for the permissible range of the regulator setting), replace the orifice spuds with spuds of the proper size. NOTE To find the Btu input, multiply the number of cubic feet of gas consumed per hour by the Btu content of the gas in TABLE 14 - GAS RATE - CUBIC FEET PER HOUR Seconds for One Rev Size of Test Dial 1/2 cu. ft. 1 cu. ft Example: By actual measurement, it takes 13 seconds for the hand on the 1-cubic foot dial to make a revolution with just a 300,000 Btuh furnace running. Read across to the column in the table above, headed 1 Cubic Foot, where you will see that 278 cubic feet of gas per hour are consumed by the furnace at that rate. Multiply 278 x 1050 (the Btu rating of the gas obtained from the local gas company). The result is 292,425 Btuh, which is close to the 300,000 Btuh rating of the furnace. CHECKING GAS INPUT NATURAL GAS SECURE OWNER S APPROVAL: When the system is functioning properly, secure the owner s approval. Show him the location of all disconnect switches and the thermostat. Teach him how to start and stop the unit and how to adjust temperature settings within the limitations of the system. 20 Unitary Products Group
21 your particular locality (contact your gas company for this information - it varies widely from city to city.) NORMAL MAINTENANCE CAUTION: Prior to any of the following maintenance procedures, shut off all electric power to the unit to prevent personal injury. Periodic maintenance normally consists of changing or cleaning filters and (under some conditions) cleaning the main burners. FILTERS - Inspect once a month. Replace disposable or clean permanent type as necessary. DO NOT replace permanent type with disposable. The dimensional size of the replacement filter must be the same as the replaced filter. MOTORS Outdoor fan motors are permanently lubricated and require no maintenance. Ventor motor is factory lubricated for an estimated 10 year life. Indoor Blower Motor and Drive - The indoor blower motor features ball bearings that do not require periodic lubrication. Periodic lubrication of the motor and bearings can extend the life of components but is optional. CAUTION: Damage can occur if the bearings are overlubricated. Use grease sparingly. WARNING: Perform all maintenance operations on the blower motor with electric power disconnected from the unit. Do not attempt to lubricate bearings with the unit in operation. On an annual basis, check the motor for accumulations of dust, etc. that may block the cooling slots in the motor shell. Check for loose, damaged or misaligned drive components. Check that all mounting bolts are tight. Replace defective parts as required. If desired, every three years remove both pipe plugs at each end shell and clean out any hardened grease or foreign matter. Replace one plug on each end with a clean grease fitting. Using a low pressure grease gun, pump grease (Chevron SRI-2 or equivalent) into the bearing cavity until new grease shows at the open port. Do not over lubricate. Run the motor for ten minutes until excess grease is purged from the cavity. Replace the plugs. On 20 ton only, units are supplied with blower shaft bearings that do not require maintenance but may be relubricated if desired. Every three years, using a low pressure grease gun, pump grease into the bearing grease fitting until grease just begins to show at the seals. Do not over lubricate. Use any lithium base grease recommended for ball bearing service. OUTDOOR COIL - Dirt should not be allowed to accumulate on the outdoor coil surface or other parts in the air circuit. Cleaning should be as often as necessary to keep coil clean. Use a brush, vacuum cleaner attachment, or other suitable means. If water is used to clean coil, be sure electric power to the unit is shut off prior to cleaning. NOTE: Exercise care when cleaning the coil so that the coil fins are not damaged. Do not permit the hot condenser air discharge to be obstructed by overhanging structures of shrubs. MAINTENANCE explained under BURNER AIR SHUTTER ADJUSTMENT. If it is not possible to adjust for the proper flame, the burners may need cleaning. TO CLEAN BURNERS - Remove them from the furnace as explained in Burner Instructions. Clean burners with hot water applied along top of the burner. COMBUSTION AIR DISCHARGE - Visually inspect discharge outlet periodically to make sure that the buildup of soot and dirt is not excessive. If necessary, clean to maintain adequate combustion air discharge. CLEANING FLUE PASSAGES AND HEATING ELEMENTS N6Y With proper combustion adjustment the heating element of a gas fired furnace will seldom need cleaning. If the element should become sooted, it can be cleaned as follows: 1. Remove the burner assembly as outlined in BURNER INSTRUCTIONS. 2. Remove the roof over the gas heat section. 3. At the top plate from the top draft blower housing and the top draft blower wheel. 4. Remove the screws holding the top of the flue collector box. Carefully remove the top of the flue collector box without ripping the adjacent insulation. Then remove the center divider plate separating the upper and lower flue boxes. 5. On the inside of the flue collector box, remove the flue baffles from the tube interiors. Note the last bend of the baffle fits tightly against the tube forcing the end of the baffle to lock into the tube collar. This collar is formed when the tube is expanded into the end sheet. To remove, move the end of the baffle toward the center of the tube releasing the end of the baffle from the tube collar, then pull straight out of the tube. Refer to Typical Flue Baffle figure. 6. Using a wire brush on a flexible wand, brush out the inside of each heat exchanger from the burner inlet and flue outlet ends. 7. Brush out the inside of the flue collector box and the flue baffles. 8. Run the wire brush down the vent hoods from the flue collector end. 9. If soot build-up is particularly bad, remove the vent motor and clean the wheel and housings. Run the wire brush down the flue extentions at the outlet of the vent housings. 10. After brushing is complete, blow all brushed areas with air or nitrogen. Vacuum as needed. 11. Replace parts in the order they were removed in Steps 1 thru When replacing the center and top of the flue collector box, be careful not to tear the adjoining insulation. BURNER & PILOT - Periodically (at least annually at the beginning of each heating season) make a visual check of the pilot and main burner flame. If necessary, adjust main burner primary air shutters to give a distinct, sharp blue flame as FIG TYPICAL FLUE BAFFLE INSTALLATION Unitary Products Group 21
22 TROUBLESHOOTING 13. Ensure that all seams on the vent side of the combustion system are air tight. Apply a high temperature (+500 F) sealing compound where needed. WARNING: Troubleshooting of components necessarily requires opening the electrical control box with the power connected to the unit. Use extreme care when working with live circuits! Check the unit nameplate for the correct line voltage and set the volt meter to the correct range before making any connections with line terminals. WARNING: Prior to any of the following maintenance procedures, shut off all electric power to the unit to prevent personal injury. CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing. NOTE To find the Btu input, multiply the number of cubic feet of gas consumed per hour by the Btu content of the gas in your particular locality (contact your gas company for this information - it varies widely from city to city.) 1. The indoor blower motor is a non-inherently protected three-phase motor. Protection is provided by an overload relay for overcurrent and fuses for short circuit. If the motor fails to run, check the line voltage circuit and control voltage circuit per the following procedure: a. If the Indoor Blower Motor does not operate, check visually that contactor M3 is pulled in. If so, check for line voltage between all three phases at the line terminals of the Blower Overload Relay (BOR). If line voltage is found, check the leads to the blower motor for open circuit. If line voltage is found at the motor leads (inside the conduit box on the motor shell), disconnect the motor and check for open windings per the motor wiring diagram. If open windings are found, replace the motor. If line voltage is not found at the BOR, trace the leads back to the field supply terminal block, checking for an open circuit or blown fuses. b. If the contactor M3 is not pulled in, check for control voltage (24V) at the M3 coil. If voltage is found, replace the contactor. If control voltage is not found at M3, check for voltage across terminals 95 & 96 of the BOR. If voltage exists, the BOR is open on overload. The BOR should be set to the auto reset position. The BOR must cool down in order to reset. If the BOR will not reset, replace the BOR. If the BOR resets and M3 pulls in, but the indoor blower motor will still not run, refer to para. (a) for troubleshooting the line voltage supply circuit. If control voltage is not found at the BOR, trace the circuit back to the relay board and thermostat per the unit wiring diagram. Replace any defective components. 2. Draft motor operates and furnace lights but supply air blower does not start after a short time delay with room thermostat fan switch set to AUTO. a. Set fan switch to ON. If blower motor runs, go to Step f. If it does not, check to see if line voltage is being supplied to the contacts of the contactor (M3), and if the contactor is pulled in. Check for loose wiring. b. If contactor (M3) is pulled in, proceed with the troubleshooting steps indicated in Step 1 above. c. If (M3) is pulled in and the blower motor still does not run, replace the blower motor. d. If (M3) is not pulled in, check for 24 volts at the (M3) coil. If 24 volts is present, replace the (M3) contactor. e. If 24 volts is not present at the (M3) coil, check for loose 24 volt wiring back to the relay board. Check control wiring to the room thermostat. If all is fine, replace the relay board. f. If the blower motor runs with the fan switch in the ON position but does not run soon after the furnace has ignited with the fan switch in the AUTO position, check for loose 24 volt wiring between the relay board in the main control box, the Mate-N-Lok connector in the partition between the evaporator and gas heat sections and the time delay relay (ETD). g. If all control wiring is fine, check for 24 volts at the relay board. If 24 volts is present, replace the relay board. If 24 volts is not present, replace the (ETD) relay. NOTE: The furnace may shut itself down on a high temperature condition during the procedure, but this will not effect the test if it is done within 5 minutes of furnace shut-down. 3. The supply air blower operates but the draft motor does not when the room thermostat is set to call for heat and the fan switch in the ON position. a. The draft motor has inherent protection. If the motor shell is hot to the touch, wait for the internal overload to reset. b. If the motor shell is cold with the room thermostat calling for heat, check for line voltage at the motor s Mate-N- Lok connector attached to the evaporator partition. If line voltage is present, replace the draft motor. c. If line voltage is not present, check for line voltage at the heat relay (RW1) contacts in the main control box and check to see if the (RW1) is pulled in. d. If the (RW1) relay is pulled in, check for a loose line voltage connection. e. If the (RW1) relay is not pulled in, check for 24 volts at the (RW1) coil. If 24 volts is present, replace the (RW1) relay. If 24 volts is not present, check for a loose 24 volt connection back to the relay board and check the connections from the room thermostat to the relay board. If all connections are correct, replace the relay board. 4. The draft motor runs but the furnace does not light and the sparker does not spark. a. The ignition control (IC1, IC2) may be locked out due to either a flame roll out or 100% shut off. These safety features are described above. If lock-out has occurred, 24V must be removed from the ignition controls. This is done at the unit or by resetting the room thermostat. After resetting 24V, check for proper furnace operation. Cont d. 22 Unitary Products Group
23 If lock-out continues to occur, locate the source of the problem and correct. b. Check all 24 volt connections from the relay board to and in the gas heat section. Check low voltage connections to the (ETD) located in the control box. c. If the furnace is hot, it may be out on an over-temperature condition, wait for limit reset. d. If the furnace is cold, check for 24 volts at wire 241 attached to the electrical time delay (ETD) located in the main control box. If 24 volts is not found, replace the ETD. TROUBLESHOOTING - Cont d N6Y d. If 24 volts is present, remove the pilot burner and remove the pilot orifice from the pilot burner. The orifice is removed in the direction opposite the flow of gas. Inspect the orifice for obstruction. If it is clear, replace the main gas valve. 6. The sparker sparks at the pilot burner but the pilot does not ignite and a gas odor is detected at the draft motor outlet. a. Adjust the pilot adjust screw on the gas valve as described in PILOT CHECKOUT. b. Check the supply pressure as described in POST START CHECK LIST. Make adjustments as necessary. e. 24 volts is found at wire 241, remove the wires attached to the (TDR) and with a VOM, check for continuity across contacts 1 and 2. If none is found, the (TDR) is open and must be replaced. If there is continuity, re-attach the wires.with the draft motor running, check for 24 volts at terminal 4 of (RW1-2) and (RW2-1). If 24 volts is not present, the centrifugal switch (CS) has not closed or has gone bad. Check the line voltage to the unit - if it is correct, replace the draft motor. If line voltage is low, call the power company. f. Check for 24V at terminal 2 of (RW1-2 and RW2-1). If 24V is not present, check for 24V at (RW1 and RW2) relay coils. If these relays are pulled in, then check for a loose connection at terminal 2 and terminal 4 of each relay. If no problem is found, then replace (RW1 and/or RW2) as required. g. If 24 volts is present at the ignitor controls, check all control wiring at the ignitor controls and the high tension wire to the ignitors. Check that the ground wires from the ignitor controls, the gas valves and pilot burners are all intact and making good electrical connection. Check to make sure that the ceramic insulator on the pilot ignitors or sensors is not broken or cracked, if all are intact, replace the ignition control IC1 or IC2. 5. The draft motor runs and the sparker sparks at the pilot burner but the pilot does not ignite and a gas odor is not detected at the draft motor outlet. a. Check to make sure gas is being supplied to the unit. Make sure that the gas pressure to the unit is within the proper limits as described in the POST START CHECK LIST and that the pilot adjust screw is allowing some flow of gas as described in PILOT CHECKOUT. b. Check all wiring between the ignitor control and the gas valve. Check to make sure the ground connections are intact. c. If the wiring is intact, check for 24 volts across terminals PV and COMMON on the ignitor control. If 24 volts is not present, replace the ignitor control. c. Check the pilot orifice for obstruction as described in para. 5d. Clean as needed but the problem should not be the gas valve. 7. The pilot burner ignites but the sparker continues to spark and the main burners do not ignite. a. Make the same checks and adjustment as described in para. 6. b. Make sure that the pilot burner is not bent or damaged. c. Make sure that the ground connections at the pilot burner, gas valve and ignitor control are intact. Check the high tension wire for good electrical connection. If all are intact, replace the ignitor module. 8. The pilot burner lights and the spark stops but the main burners do not light. a. Check electrical connections between the ignitor control and the gas valve. If intact, check for 24 volts across terminals MV and COMMON terminals. If no voltage detected, replace ignitor control. If voltage is present, replace gas valve. 9. Furnace lights with roll-out or one burner has delayed ignition. a. Make sure that the pilot burner is aligned properly with the carryover as described in PILOT CHECKOUT. b. Make sure that the carryovers on adjoining burners are screwed fast and are level with respect to one another. 10. Main burners light but exhibit erratic flame characteristics. a. Adjust air shutters as described in BURNER AIR SHUTTER ADJUSTMENT. b. Check the main burner orifices for obstruction and alignment. Removal procedure is described in BURNER INSTRUCTIONS. Clean or replace burner orifices and burners as needed. Unitary Products Group 23
24 COMPRESSOR SECTION Hermetic compressor Compressor mounting MOTOR SECTION Blower motor Fan motor Ventor motor ELECTRICAL SECTION Ignition control Relay board Contactor Circuit breaker Temperature controls Capacitors Relays Transformers Connectors REPLACEMENT PARTS GAS HEAT SECTION Heat exchanger Gas valve Pilot Flame sensor Spark ignitor Gas manifold Gas burner AIR MOVING SECTION Blower wheel Blower wheel housing REFRIGERANT SECTION Evaporator coil Evaporator coil header Expansion valve assembly Condenser coil Condenser coil header FABRICATED PARTS SECTION Panels Posts Covers Drain pans Base rails Air hoods MISCELLANEOUS SECTION Air inlet hood screen Fan guard Air filters TO OBTAIN PARTS INFORMATION: Replacement parts and information from OUR current parts list for this unit are available to your servicing contractor through our local distributor. The name and address of our nearest distributor may be obtained by consulting the Yellow Pages of a local telephone directory. IMPORTANT: In order to supply the correct part or information from the parts list, our distributor will need to be provided with the complete model number listed on the rating plate located on your unit. See page 2 for Product Nomenclature. WARNING: IMPROPER INSTALLATION, ADJUSTMENT, SERVICE OR MAINTENANCE CAN CAUSE INJURY OR PROPERTY DAMAGE. CONSULT A QUALIFIED INSTALLER, SERVICE AGENCY OR YOUR LOCAL GAS SUPPLIER FOR INFORMATION OR ASSISTANCE. Unitary Products Group 5005 York Drive, Norman, Oklahoma Subject to change without notice. Printed in U.S.A Copyright by York International Corporation All Rights Reserved. Supersedes: N6Y (1298) Code: SBY N6Y(500)
MAINTENANCE & TROUBLESHOOTING INSTALLATION TABLES FIGURES OPERATION START-UP
SUNLINE 2000 GAS / ELECTRIC SINGLE PACKAGE AIR CONDITIONERS INSTALLATION INSTRUCTION Supersedes: 530.18N10Y (693) 530.18N10Y (995) MODELS D3CG090, 102, 120 (STYLE B) & D4CG150 (STYLE A) (8.59.0 EER) 03513092
USER S, MAINTENANCE and SERVICE INFORMATION MANUAL
CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY....................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS........................... 2 INTERMITTENT IGNITION DEVICE...........
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
Your safety and the safety of others are very important.
NATURAL GAS TO PROPANE CONVERSION KIT 090 INSTALLATION INSTRUCTIONS FOR ALTITUDES 0 -,00 FT. ONLY PROPANE CONVERSION KIT SAFETY... INSTALLATION REQUIREMENTS... Tools and Parts... LP Gas Requirements...
Commercial Gas Furnace Upflow
Commercial Gas Furnace Upflow Model G24-200 80% A.F.U.E. 200,000 Btuh Input Heating Cap. 7.5 or 10 Tons Nominal Add-On Cooling GUK FEATURES Certified by A.G.A./C.G.A. Laboratories. Heavy gauge painted
36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve
Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. DESCRIPTION
G26 Corp. 9721-L11 Revised 07-2001 LENNOXOEMPARTS.COM. Service Literature G26 SERIES UNITS
Service Literature G26 SERIES UNITS G26 series units are high-efficiency upflow gas furnaces manufactured with DuralokPlust aluminized steel clamshell-type heat exchangers. G26 units are available in heating
SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS
SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating
M7RL Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. High Efficiency / Direct Vent Condensing Downflow Gas Furnace
TECHNICAL SPECIFICATIONS M7RL Series High Efficiency / Direct Vent Condensing Downflow Gas Furnace Induced Draft - 9%+ AFUE Input 4,000 thru 7,000 Btuh The high efficiency downflow gas furnace is especially
SWIMMING POOL HEAT PUMP
SWIMMING POOL HEAT PUMP Installation & User Manual Model HP40B HP50B HP65B Hayward Pool Products Canada, Inc. T: 1-888-238-7665 www.haywardpool.ca CONTENT I. Application 4 II. Features 4 III. Technical
Cooling Capacity CFM range @.5 in. w.c. (125 Pa)
N8MXL Product Specifications 80% ECM Single Stage Heating Furnace EASIER TO SELL 80% AFUE Flame roll out sensors standard Category I venting Blocked vent switch 24 VAC humidifier terminal Electronic air
INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST
INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST MODEL CHCRV-5 For Use with Bard CH Series 3, 4 & 5 Ton 2-Stage Wall Mount Heat Pumps AND W38H, W43H, W49H and W61H Single Stage Wall Mount
Installation Instructions
05,06 Single Package, Displacement Ventilation or Single Zone Variable Airflow Rooftop Units Electric Cooling with PURONr (R---410A) Refrigerant and COMFORTLinkt Controls Installation Instructions IMPORTANT:
48/50EJ,EK,EW,EY038, 044, 048 SINGLE-PACKAGE COOLING UNITS VARIABLE VOLUME CONSTANT VOLUME FACTORY-INSTALLED OPTIONAL HEAT
48/50E-4SB 48/50EJ,EK,EW,EY038, 044, 048 SINGLE-PACKAGE COOLING UNITS VARIABLE VOLUME CONSTANT VOLUME FACTORY-INSTALLED OPTIONAL HEAT GAS HEAT ELECTRIC HEAT PERFORMANCE DATA CERTIFIED DIMENSION PRINT CERTIFIED
TECHNICAL GUIDE 95.5% SINGLE STAGE GAS-FIRED RESIDENTIAL MULTI-POSITION GAS FURNACES MODELS: TG9S DESCRIPTION FEATURES
TECHNICAL GUIDE 95.5% SINGLE STAGE GAS-FIRED RESIDENTIAL MULTI-POSITION GAS FURNACES MODELS: TG9S NATURAL GAS 40-130 MBH INPUT Due to continuous product improvement, specifications are subject to change
Cooktop Low-Profile Ventilation Hoods
INSTALLATION GUIDE Cooktop Low-Profile Ventilation Hoods Contents Wolf Cooktop Low-Profile Ventilation Hoods........ 3 Cooktop Low-Profile Hood Specifications.......... 4 Cooktop Low-Profile Hood Installation............
THC 85 INDUSTRIAL / COMMERCIAL SPACE HEATER
THC 85 INDUSTRIAL / COMMERCIAL SPACE HEATER Certified to / Certifié à CGA 2.14 M2000 Conforms to / Conforme à ANSI std Z83.7 2000 Suitable for indoor or outdoor installation / Unvented / Unattended Type
Gas Unit Heaters Duct Furnaces Horizontal - 60 HZ Form No. LF24-100-400 (10/2011) LF24 Standard
LF Standard Features Horizontal unit heaters are compact in design and easy to install. Steady State Efficiencies of up to 80.%. Ideal for economical commercial heating systems. Shipped completely assembled
DC REFRIGERATORS 12/24 VOLTS INSTALLATION AND OWNER S MANUAL
DC REFRIGERATORS 12/24 VOLTS INSTALLATION AND OWNER S MANUAL Service Information If service or parts are required, contact the nearest Norcold Service Center. To find an authorized Norcold Service Center
SECTION 15732 AIR CONDITIONING UNIT
SECTION 15732 AIR CONDITIONING UNIT PART 1 GENERAL 1.01 SUMMARY A. Section includes: 1. Packaged, split system air conditioning unit No. 1. 1.02 REFERENCES A. Air-Conditioning, Heating, and Refrigeration
Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS
Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS Ducted System RECORD THIS UNIT INFORMATION FOR FUTURE REFERENCE: Model Number: Serial Number: Date Purchased: This manual must be read and
SL280UHV SERIES GAS FURNACE WARNING
2010 Lennox Industries Inc. Dallas, Texas, USA 506677 01 11/2010 Supersedes 506409 01 SL280UHV SERIES GAS FURNACE Litho U.S.A. FIRE OR EXPLOSION HAZARD. Failure to follow safety warnings exactly could
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety
Cooling Capacity CFM range @.5 in. w.c. (125 Pa)
96% AFUE, Single Stage, ECM Gas Furnace EASIER TO SELL 96% AFUE, all models all positions Xtra SEER ECM blower motor Supports two stage cooling units Dehumidification feature in cooling California NOx
Cooling Capacity CFM range @.5 in. w.c. (125 Pa)
96% AFUE, Two Stage ECM Gas Furnace EASIER TO SELL 96% AFUE, all models, all positions Two stage heating operation Xtra SEER ECM blower motor Supports two stage cooling units Dehumidification feature in
GCS16 GCS20 WARNING CAUTION
Service Literature Corp. 0110 L6 Revised 12 2004 GCS16/GCS20 SERIES UNITS GCS16 GCS20 2 to 5 Ton GCS16/20 series units in the 2 to 5 ton (7.0 to 17.0 kw) cooling size are packaged combination gas heat
G670 Intermittent Pilot Ignition Controls
Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin Issue Date 0300 Intermittent Pilot Ignition Controls Figure 1: Intermittent Pilot Ignition Control
Packaged Terminal Air Conditioner Wall Sleeve Installation
Installation & Maintenance Data IM 1196 Group: PTAC Part Number: 910141799 Date: October 2013 Packaged Terminal Air Conditioner Installation x 42" PGAN with Top-Mounted Hydronic Heat Note: Installation
Installation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008
Installation Manual Rental Services Air Handling Units July 2008 CHS-SVN01A-EN Copyright 2008 Trane All rights reserved This document and the information in it are the property of Trane and may not be
Owner Retain this manual in a safe place to provide your serviceman information if it becomes necessary.
INSTALLATION, OPERATING AND SERVICE MANUAL FOR EASY RADIANT WORKS HEATWAVE MODEL GH-25-40 GAS FIRED, VENTED INFRARED TUBE HEATER FOR RESIDENTIAL & COMMERCIAL / INDUSTRIAL APPLICATIONS. For Your Safety
CROWN BOILER COMPANY BWF SERIES BOILER CATEGORY I VENT KIT INSTALLATION AND OPERATING INSTRUCTIONS
CROWN BOILER COMPANY BWF SERIES BOILER CATEGORY I VENT KIT INSTALLATION AND OPERATING INSTRUCTIONS WARNING Improper installation, adjustment, alteration, service, or maintenance of this product can cause
ASX7-4-IOM-7 J30-08579
INSTALLATION INSTRUCTIONS 4" COMBUSTION AIR INLET KIT TUBULAR GAS FIRED DIRECT SPARK PROPELLER UNIT HEATERS UNIT CONVERSION & CATEGORY III VENTING FOR SEPARATED COMBUSTION For 30,000 to 75,000 BTU/HR SUPPLEMENT
Applies to: Models F, B, FE, and BE FOR YOUR SAFETY
Form CP-F/B-GC (Version A.2) Obsoletes Form CP-F/B-GC (Version A) Gas Conversion Kits and Instructions Applies to: Models F, B, FE, and BE Model B Model F All gas conversion must be done by a qualified
SECTION 23 81 43 HEAT PUMPS
SECTION 23 81 43 HEAT PUMPS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop heat pumps. 1.2 REFERENCES A. American Society of Heating, Refrigerating and Air-Conditioning Engineers:
Operator: Save these instructions for future use!
WHITE-RODGERS 36C01 Combination Gas Valves (24 Volt and 120 Volt Models) INSTALLATI INSTRUCTIS FAILURE TO READ AND FOLLOW ALL INSTRUCTIS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CTROL COULD CAUSE
Tankless Water Heater
Tankless Water Heater USER S INFORMATION MANUAL Models WGRTNG199 / WGRTLP199 WGRTCNG199 / WGRTCLP199 NOTICE: Westinghouse reserves the right to make product changes or updates without notice and will not
Installation Instructions
CNPVU CNRVU Uncased Coils Upflow - Downflow Heating - Cooling Installation Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS...
Air Conditioner 457915 B57915 459516 B59516 540315 540316 640312 640315
RECORD THIS INFORMATION FOR FUTURE REFERENCE: Number Serial Number ADB Number ADB Serial Number Date Purchased USA SERVICE OFFICE Dometic Corporation 2320 Industrial Parkway Elkhart, IN 46516 CANADA Dometic
BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION
Air Conditioning Central Heating & Cooling BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION INSTALLATION AND SERVICE MANUAL 2 PROJECT: ADDRESS: MODEL: SERIAL NUMBER: INSTALLER: ADDRESS: PHONE NUMBER: INSTALLATION
Evaluate, Clean, and Tune Guidance
Evaluate, Clean, and Tune Guidance The Evaluate, Clean and Tune (ECT) process serves three essential purposes in the Weatherization Assistance Program (WAP). The first is to evaluate the existing system
BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS
BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS PLEASE READ COMPLETE INSTRUCTIONS BEFORE YOU BEGIN LEAVE INSTALLATION INSTRUCTIONS AND USER'S GUIDE WITH OWNER ALL ELECTRIC WIRING AND PLUMBING MUST BE DONE
Your safety and the safety of others are very important.
NATURAL GAS TO PROPANE CONVERSION KIT ALPKT7- INSTALLATION INSTRUCTIONS PROPANE CONVERSION KIT SAFETY... INSTALLATION REQUIREMENTS... Tools and Parts... LP Gas Requirements... INSTALLATION INSTRUCTIONS...
MAC-120HE-01 Air-Cooled Chiller
MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01
LPM-06 CONVERSION KIT
LPM-06 CONVERSION KIT TWO-STAGE FURNACE NATURAL GAS TO L.P. GAS CONVERSION Goodman Manufacturing Company, L.P. 2009-2011 5151 San Felipe, Suite 500, Houston, TX 77056 www.goodmanmfg.com -or- www.amana-hac.com
F9MXE. Product Specifications
96% AFUE, Single Stage, ECM Gas Furnace EASIER TO SELL 96% AFUE, all models all positions Select models earn the ENERGY STAR (See below, indicated with check mark.) Xtra SEER ECM blower motor Supports
INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX
Fan Coil Replacement Coil Kit EBX & EBXX These instructions must be read and understood completely before attempting installation. These instructions covers the installation of replacement coil kit into
http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html
http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html TECHNICAL SERVICE DEPARTMENT Effective October 2007, we transitioned to the White Rodgers (Intelli-Vent TM )Thermostat Control for
2010 Residential Water Heater Replacement Check List
2010 Residential Water Heater Replacement Check List The intent of this check list is to provide installers a general reference for the enforcement of code requirements in the Greater San Diego Area. This
Chromalox. Installation, Operation. Portable Industrial Unit Blower Air Heater Type DRA RENEWAL PARTS IDENTIFICATION
Chromalox Installation, Operation RENEWAL PARTS IDENTIFICATION Portable Industrial Unit Blower Air Type DRA and DIVISION SALES REFERENCE DATE SECTION (Supersedes P-) PF-) NOVEMBER, 00 DRA PF- -0-00 Specifications
NAVIEN AMERICA INC. 17855 FITCH AVENUE
Navien America Inc. Specification Details for the Navien models: CC-240 CC-240A For Potable Water Heating and Space Heating NAVIEN AMERICA INC. 17855 FITCH AVENUE IRVINE, CALIFORNIA, USA 92614 Toll Free:
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled
Air Conditioning Sign-Off Sheet
Air Conditioning Sign-Off Sheet Printed Technician Name Address Social Security Number Telephone Number City State Zip Code Install Or Verify The Accuracy Of An Air Conditioner s Installation The candidate
Replacement parts. WM97+ gas-fired water boiler Boiler Manual. OBTAIN PARTS ONLY THROUGH WEIL-McLAIN THE BOILER CONTAINS CERAMIC FIBER MATERIALS
Replacement parts DO NOT SERVICE THE BOILER WITHOUT A WM97+ MAINTENANCE KIT AVAILABLE Failure to adhere to these guidelines can result in severe personal injury, death or substantial property damage. The
Installation Instructions
H5HK Series Installation Instructions 3 Phase Electric Heater Kits 7.5 and 0 TON Package A/C Systems Description Installation of 08/40V and 480V H5HK 3 Phase Heater Kits in 7.5 and 0 TON Packaged Air Conditioners.
TECHNICAL MANUAL GDS8 & GHS8
TECHNICAL MANUAL AL GDS8 & GHS8 33-3/8" 80% Gas Furnace Units Refer to Service Manual RS6610004 for installation, operation, and troubleshooting information. All safety information must be followed as
XV80 UPFLOW/HORIZONTAL 2-STAGE, VARIABLE SPEED GAS-FIRED FURNACE
UPF/HORIZONTAL 2-, VARIABLE SPEED GAS-FIRED FURNACE XV80 MODELS TUD2B060A9V3VB, TUD2B080A9V3VB TUD2C080A9V4VB, TUD2C080B9V4VB TUD2B00A9V3VB, TUD2C00A9V5VB TUD2C00B9V5VB, TUD2DA9V5VB TUD2DB9V5VB, TUD2DA9V5VB
INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS
INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS MODEL: WA121 Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead, just as planned. Manual : 2100-234 E Supersedes: 2100-234
UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual
UHIR Series Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater Owner s Manual This manual covers installation, maintenance and repair parts. Read carefully before attempting to
E2 Series Electric Furnaces
E2 Series Electric Furnaces Service Manual Table of Contents Electrical Requirements... 10 Codes, Specifications Requirements... 10 Connection Supply Service Wires... 10 Furnace Sequence of Operation...
G9MXE. Product Specifications
Up to 96% AFUE, Single Stage, ECM Gas Furnace EASIER TO SELL Up to 96% AFUE, all models all positions California NOx approved Select models earn the ENERGY STAR (See below, indicated with check mark.)
INSTRUCTIONS FOR HOW TO PROPERLY SELECT A FAN OR BLOWER
INSTRUCTIONS FOR HOW TO PROPERLY SELECT A FAN OR BLOWER The instructions that follow are to assist you in completing the information required when making a fan or blower selection. If you need additional
Arapahoe County Residential Water Heater Installation and Inspection Guide
Arapahoe County Residential Water Heater Installation and Inspection Guide The attached handout is designed to be a general permit submittal and inspection guide covering most installation instances, however
WON0502-B INSTALLATION INSTRUCTIONS FOR ELECTRIC FURNACES. Bulletin 30-34 / March 2013
Bulletin 30-34 / March 2013 INSTALLATION INSTRUCTIONS FOR ELECTRIC FURNACES General The information on the following pages is to provide the installer the necessary information to properly install the
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Plan Review 2009 International Fire Code and NFPA 20 Date of Review / / BLD201 - Project Address: Project Name: Contractor s Business
INSTALLATION AND OPERATIONS GUIDE FOR GRAND CANYON GAS LOG SYSTEMS
INSTALLATION AND OPERATIONS GUIDE FOR GRAND CANYON GAS LOG SYSTEMS Installation and service must be provided by a qualified installer, service agency or gas supplier Grand Canyon Gas Logs, logs are made
Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association
Air-Conditioning, Heating, and Refrigeration Institute Sheet Metal and Air-Conditioning Contractors National Association GUIDELINE B-1997 ACKNOWLEDGEMENT These guidelines for Roof Mounted Outdoor Air-
Acumen Enterprises, Inc.
Hourly rates Discount w/o Rebate Electrician $78.00 10% $70.20 $70.73 HVAC Technician $78.00 10% $70.20 $70.73 Insulator $42.00 10% $37.80 $38.08 Sheet Metal Worker $74.00 10% $66.60 $67.10 Plumber/Pipefitter
Propane Conversion Kit PROPANE CONVERSION KIT INSTALLATION MANUAL
Propane Conversion Kit Supersedes: 145.25-IOM2 (708) Form 145.25-IOM2 (908) PROPANE CONVERSION KIT INSTALLATION MANUAL "LPKIT " - PROPANE CONVERSION KIT Kits are available for field conversion from natural
WMSLW / WMBLWH Series Hydronic Upflow/Horizontal Left or Right, Heating and Cooling Air Handler
WMSLW / WMBLWH Series Hydronic Upflow/Horizontal Left or Right, Heating and Cooling Air Handler Installation Operation Maintenance The WMSLW/WMBLW series is designed for installation in a closet, utility
NFPA31FuelOilPiping 1 Revised 3-1-11
NFPA 31 Fuel Oil Piping, Installation and Testing Chapter 8 Fuel Piping Systems and Components 8.1 Scope. This chapter shall apply to piping systems and their components used to transfer fuel oil from
Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal
Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable
CARING FOR YOUR WATER HEATER
http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html Water Heater Inspections CARING FOR YOUR WATER HEATER Venting System (Direct Vent Only) The venting system should be inspected
CEILING CASSETTE FAN COIL UNIT
CEILING CASSETTE FAN COIL UNIT Operation and Installation Manual MHCFC4W-04, 08, 12, 16 Four way ceiling cassette fan coil unit Please read this manual before using the fan coil unit. Installation and
Portable Air Conditioner
Portable Air Conditioner Owner's Manual Model:3 in 1 12,000 Btu/h Series 3 Please read this owner s manual carefully before operation and retain it for future reference. CONTENTS 1. SUMMARY...1 2. PORTABLE
SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT)
SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT) MAINTENANCE TYPE: STATUTORY 1.0 SCOPE OF SERVICES The Contractor shall provide maintenance Services for
Electrical Connection. Provide Proper Electrical Supply. Electrical Requirements. Connecting using the supplied cord and plug
Electrical Connection When installed the range must be electrically grounded in accordance with local codes or; in the absence of local codes with the National Electrical Code ANSI/NFPA 70, latest edition.
GCS16-024-030-036-048-060
Packaged Unit & Gas Heat 2-5 Ton Capacity 50,000-120,000 Btuh Input Heating Capacity GCS16-024-030-036-048-060 FEATURES Designed for outdoor rooftop or ground level installations Down-flow or horizontal
Float and Thermostatic Traps Series H, C and X
Hoffman Specialty Installation & Maintenance Instructions HS-(E) and Thermostatic Traps Series H, C and X Series C & NPT Series C NPT Series X NPT Series C NPT Series H Ratings Maximum Max. Operating NPT
Installer s Guide 18-AH39D1-13
18-AH39D1-13 Cased Aluminum "Convertible" Coils 4TXCA018BC3HC** 4TXCA024BC3HC** 4TXCB025BC3HC** 4TXCB026BC3HC** 4TXCB031BC3HC** 4TXCB032BC3HC** ALL phases of this installation must comply with NATIONAL,
ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013
ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 READ CAREFULLY These instructions are intended to cover good practices in
Fire Pump Plan Review March 2010
Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:
Installation Instructions for Alarm Module Kit A043F059
Instruction Sheet 07-2013 Installation Instructions for Alarm Module Kit A043F059 1 Introduction The information contained within is based on information available at the time of going to print. In line
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
Recirculating Roof Fans Models ESRMD, ESRMDF and ERD
Recirculating Roof Fans Models ESRMD, ESRMDF and ERD Four-Way Fan Exhaust Supply Mix Recirculate BUILDING VALUE IN AIR. October 2005 Recirculating Roof Fans Exhaust/Supply/Recirculation/Mix Model ESRMD
ARMSTRONG AIR HEAT PUMPS www.armstrongair.com
INDEX ELECTRIC FURNACE MODULAR AIR SYSTEM EFC/EFV... 5-10 electric Heat Kits... 5-11 evaporator coils EC1P / EM1P UPFLOW / COUNTERFLOW APPLICATIONS and upflow / horizontal applications (CASED)... 5-6 5-7
INSTALLATION INSTRUCTIONS
2008 Lennox Industries Inc. Dallas, Texas, USA WARNING Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and
PRE-ASSEMBLED INSTALLATION INSTRUCTIONS FOR PACB SERIES COAL FIRED OVENS
PRE-ASSEMBLED INSTALLATION INSTRUCTIONS FOR PACB SERIES COAL FIRED OVENS OVENS MANUFACTURED BY: EARTHSTONE OVENS-6717 SAN FERNANDO RD GLENDALE CA 91201 TELEPHONE: 800-840-4915 818-553-1134 FAX: 818-553-1133
REFRIGERATED TYPE COMPRESSED AIR DRYERS INSTRUCTION MANUAL. For Sales & Service please contact:
7610.478.16 8/99 INSTRUCTION MANUAL Models 8005, 8010, 8015 For Sales & Service please contact: CENTRAIR Air Systems & Supplies Phone: 705-722-5747 Fax: 705-722-5458 Email: [email protected] Website: www.centrair.ca
THE WALL-MOUNT ONE TON AIR CONDITIONER GREEN REFRIGERANT R-410A. 10,800 Btuh 9.00 EER Right Side Control Panel. Engineered Features
THE WALL-MOUNT ONE TON AIR CONDITIONER W2A,800 Btuh 9.00 EER Right Side Control Panel 60Hz GREEN REFRIGERANT R-A The Bard Wall-Mount One Ton Air Conditioner is a self contained energy efficient heating
ECOCIAT. Domestic hot water heat recovery unit
Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY
PACKAGE COOLING, PACKAGE HEAT PUMP & PACKAGE GAS UNITS
PACKAGE COOLING, PACKAGE HEAT PUMP & PACKAGE GAS UNITS SERVICE INSTRUCTIONS AMANA REFRIGERATION, INC., AMANA, IOWA 52204 MANUFACTURING NUMBERS COVERED IN THIS MANUAL SEE MODEL AND MANUFACTURING NUMBERS
543-0032-00, 943-0032-00. User s Manual
543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and
LAKE COUNTY ANIMAL SERVICES EXPANSION SECTION 15459
SECTION 15459 PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification sections, apply to work
Installation Instructions
VentilAire IV Whole-House Fresh Air Supply System Installation Instructions 914228 Flat Roof Kit 914229 Sloped Roof Kit 5" x 11' Class I Insulated Flexible Duct Plastic Clamps (2) Metal Clamps (2) Ceiling
Not required for most applications Not required for most applications High pressure (12-803 provided) High pressure (12-803 provided)
ELECTRIC FUEL PUMPS P/N 12-801-1, 712-801-1, 12-802-1, 712-802-1, 12-815-1, & 712-815-1 FUEL PRESSURE REGULATORS P/N 12-803, 12-501, 12-804, 12-500, & 15812NOS Installation Instructions THESE INSTRUCTIONS
WALL MOUNTED PACKAGED AIR CONDITIONER INSTALLATION INSTRUCTIONS. Models: WA182, WA242. Bard Manufacturing Company, Inc.
INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGED AIR CONDITIONER Models: WA82, WA242 Bard Manufacturing Company, Inc. Bryan, Ohio 43506 Since 94...Moving ahead just as planned Manual No.: 200-369E Supersedes:
All work shall comply with applicable codes and ordinances. Work shall comply with the BOCA National Plumbing Code, latest edition.
DIVISION 15 MECHANICAL SECTION 15100 - PLUMBING PART 1 - GENERAL SCOPE Plumbing work includes all domestic water, gas, and sanitary sewer systems as shown on plans. Also all fixtures and equipment which
SECTION 11 78 13 MORTUARY REFRIGERATORS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in
PROAIR Water-Cooled Air Conditioner. CR43WC Model INSTRUCTION MANUAL. Rev. E 2013 Pentair Technical Products P/N 10-1008-167
PROAIR Water-Cooled Air Conditioner CR43WC Model INSTRUCTION MANUAL Rev. E 2013 Pentair Technical Products P/N 10-1008-167 87976466 TABLE OF CONTENTS HANDLING & TESTING THE AIR CONDITIONER...3 INSTALLATION
AIR HANDLERS AIR HANDLERS AIR HANDLERS. RHLA- High Efficiency. featuring R-22 Refrigerant. RHLL- High Efficiency
FORM NO. H11-52 REV. 3 Supersedes Form H11-52 Rev. 2 AIR HANDLERS AIR HANDLERS RHLA- Efficiency featuring R-22 Refrigerant RHLL- Efficiency featuring Earth-Friendly R-10A Refrigerant earth friendly refrigerant