A Paradigm Shift in Data Center Sustainability Going Beyond Aisle Containment and Economization

Size: px
Start display at page:

Download "A Paradigm Shift in Data Center Sustainability Going Beyond Aisle Containment and Economization"

Transcription

1 A Paradigm Shift in Data Center Sustainability Going Beyond Aisle Containment and Economization A CONTENTS Introduction... 1 Introduction to Oil Submersion Cooling... 2 The CarnotJet System... 3 Conclusion... 6 References... 7 INTRODUCTION A Paradigm Shift in Data Center Sustainability Green Revolution Cooling (512) info@grcooling.com 1

2 water requirements for the data centers as well. This paper will look center operators reduce their energy and water consumption, cost effectively. Introduction to Oil Submersion Cooling Oil submersion cooling, as the name suggests is where entire servers are submerged in a mineral oil based dielectric coolant. The coolant that is a good conductor of heat but not electricity, making it ideal for the cooling of IT equipment. Such methods of cooling have been used for nearly a century in electrical transformers and industrial capacitors. Similar applications of fluid submersion cooling in the world of HPC date back to as early as the 1980s 1. But concerns regarding the cost, safety, and environmental impact of the coolants used led to limited adoption. ElectroSafe on the other hand is a non-toxic, eco-friendly, dielectric mineral oil blend. The oils used to make ElectroSafe have a history of being used in not just computing and electric power applications but in medical and domestic applications as well. The high performance, low cost oil is readily available and is rated as substance by the National Fire Prevention Association (NFPA), meaning that it poses no risk to human health, does not ignite readily, and can be treated with any fire suppression substance, including water 2. A Paradigm Shift in Data Center Sustainability Green Revolution Cooling (512) info@grcooling.com 2

3 The CarnotJet System Green Revolution Cooling has brought to the data center market an industrial scale oil submersion cooling solution that works with servers from any manufacturer. The technology consists of four major components; the tank with a horizontal rack (42U), the pump module including the heat exchanger and strainer, the control system, and a cooling tower* to extract heat from the system. The tub of circulating dielectric liquid. The liquid captures heat produced by IT equipment and sends it to a heat exchanger. The open system tanks support servers manufactured by Dell, HP, Supermicro, IBM, Intel, SGI, Quanta, and more. Energy Savings = Lower Carbon and Water Footprint The CarnotJet system yields a mechanical PUE of as reported by Intel after a year of testing 3. This extremely efficient cooling is enabled by the use of the ElectroSafe coolant that has superior heat conductivity and 1,200 times the heat capacity of air. The superior heat conductivity means that ElectroSafe is much more efficient in both extracting heat from the equipment and subsequently expelling it out of the data hall. For example, 1 Furthermore, the CarnotJet system allows reduction in the power consumed by servers as well. This server power reduction is driven by the removal of server fans, and through superior thermal management allowing servers to run cooler. This improvement in energy efficiency directly translates into lower carbon foot print and reduction in the water required for cooling the data center. *The system can also be used with a dry cooler or other low water consumption alternatives A Paradigm Shift in Data Center Sustainability Green Revolution Cooling (512) info@grcooling.com 3

4 Emissions Reduction On average, one kilowatt-hour of electricity purchased in the United States generates about 1 pound of carbon dioxide 4. Comparing the carbon footprint of an extremely efficient traditional data center (avg. PUE = 1.21), and a CarnotJet enabled data center (avg. PUE = 1.09) of similar computing capacity reveals an annual Carbon emissions reduction of over 10,000 metric tons per annum, a 21% improvement over what is considered an extremely efficient facility. CUE or Carbon Usage Effectiveness is a metric defined by Green Grid 5. CUE is defined as follows: CUE = Total CO 2 Emissions caused by the total Data Center Energy IT Equipment Energy A Paradigm Shift in Data Center Sustainability Green Revolution Cooling (512) info@grcooling.com 4

5 The reduction in power directly relates to lower Scope-2 and Scope-1 (from diesel generators) emissions on the CDP (Carbon Disclosure Project), helping organizations achieve better scores on the CDP and reach their carbon reduction goals. Further, the improved energy efficiency and the resulting decrease in carbon emissions, can give organizations access to energy efficiency grants and programs offered by local utilities, or state and federal governments. PG&E recently published a test report regarding the energy savings with the use of the CarnotJet system and its inclusion in their energy efficiency programs 6. Water Savings designs that stop using water. Apart from the indirect water savings related with the generation of electricity, the CarnotJet system also helps directly reduce the water use and requirements at the data center. The CarnotJet system enables the use of a hybrid cooling tower or an adiabatic dry cooler, both of which only require additional water the same example as above, in a data center supporting 24,000 servers the CarnotJet system helps save close to 300 million Liters or 90% reduction in water consumption. A Paradigm Shift in Data Center Sustainability Green Revolution Cooling (512) info@grcooling.com 5

6 * 7 **US average of L/kWh WUE or Water Usage Effectiveness is a metric defined by the Green Grid 8. WUE is defined as follows: WUE SOURCE = Annual Energy Source Water Usage + Annual Site Water Usage IT Equipment Energy Conclusion Data center energy and water efficiency has improved drastically over the past few years. However, there is still a lot of scope for in data center efficiency, and that too cost-effectively. To learn more about how GRC can help you cut Carbon emissions, and water consumption while lowering build, and operating costs mail us at info@grcooling.com. A Paradigm Shift in Data Center Sustainability Green Revolution Cooling (512) info@grcooling.com 6

7 References Pfanner, E. (2014). Liquid-Cooled Supercomputers, to Trim the Power Bill. International New York Times. [online] Available at: [Accessed 11 Jul. 2014]. ElectroSafe Dielectric liquid coolant. (n.d.). 1st ed. [ebook] Available at: [Accessed 11 Jul. 2014]. Miller, R. (2012). Intel Embraces Submerging Servers in Oil Data Center Knowledge. [online] Data Center Knowledge. Available at: eral-oil-cooling/ [Accessed 11 Jul. 2014]. Stewartmarion.com, (2014). BlueSkyModel.org carbon dioxide created by one kilowatt-hour. [online] Available at: [Accessed 27 Aug. 2014]. The Green Grid, (2010). Carbon Usage Effectiveness (CUE): A Green Grid Data Center Sustainability Metric. Available at: ectiveness%20white%20paper_v3.pdf?lang=en [Accessed 27 Aug. 2014]. Pacific Gas and Electric Company, (2014). Submersion Cooling Evaluation. Company. 7. Miller, R. (2012). Data Center Water Use Moves to the Forefront Data Center Knowledge. [online] Data Center Knowledge. Available at -use-moves-to-center-stage/ [Accessed 27 Aug. 2014]. 8. The Green Grid, (2011). Water Usage Effectiveness (WUETM): A Green Grid Data Center Sustainability Metric. Available at: [Accessed 27 Aug. 2014]. Written by: Edited by: Graphics & Arrangement: Dhruv Varma Christiaan Best Matthew Solomon A Paradigm Shift in Data Center Sustainability Green Revolution Cooling (512) info@grcooling.com 7

Oil Submersion Cooling for Todayʼs Data Centers. An analysis of the technology and its business implications

Oil Submersion Cooling for Todayʼs Data Centers. An analysis of the technology and its business implications Oil Submersion Cooling for Todayʼs Data Centers An analysis of the technology and its business implications Contents Introduction... 2 Data Center Cooling Technologies... 2 Oil Submersion Cooling... 2

More information

Heat Recovery from Data Centres Conference Designing Energy Efficient Data Centres

Heat Recovery from Data Centres Conference Designing Energy Efficient Data Centres What factors determine the energy efficiency of a data centre? Where is the energy used? Local Climate Data Hall Temperatures Chiller / DX Energy Condenser / Dry Cooler / Cooling Tower Energy Pump Energy

More information

Submersion Cooling Evaluation

Submersion Cooling Evaluation Submersion Cooling Evaluation ET Project Number: Project Manager: Jeff Beresini Pacific Gas and Electric Company Prepared By: Luke Werner, P.E. Energy Resources Integration (ERI) 251 Donahue St. Sausalito,

More information

DATA CENTRE DESIGN AND

DATA CENTRE DESIGN AND SPUSC 2008 SOUTH PACIFIC USER SERVICES CONFERENCE DATA CENTRE DESIGN AND ENERGY INITIATIVES Presented by Jarrad Clift Electrical Engineer Greenstar Accredited Presentation Content Data Centres General

More information

Excool Indirect Adiabatic and Evaporative Data Centre Cooling. World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling

Excool Indirect Adiabatic and Evaporative Data Centre Cooling. World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling Excool Indirect Adiabatic and Evaporative Data Centre Cooling World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling Indirect Adiabatic and Evaporative Data Centre Cooling Solutions by

More information

HPC TCO: Cooling and Computer Room Efficiency

HPC TCO: Cooling and Computer Room Efficiency HPC TCO: Cooling and Computer Room Efficiency 1 Route Plan Motivation (Why do we care?) HPC Building Blocks: Compuer Hardware (What s inside my dataroom? What needs to be cooled?) HPC Building Blocks:

More information

Optimizing the Efficiency of the NCAR-Wyoming Supercomputing Center Facility. Ademola Olarinde Mentor: Aaron Andersen

Optimizing the Efficiency of the NCAR-Wyoming Supercomputing Center Facility. Ademola Olarinde Mentor: Aaron Andersen Optimizing the Efficiency of the NCAR-Wyoming Supercomputing Center Facility Ademola Olarinde Mentor: Aaron Andersen August 2, 2013 1 Education: Mechanical Engineering Grad Student Texas A&M University

More information

The New Data Center Cooling Paradigm The Tiered Approach

The New Data Center Cooling Paradigm The Tiered Approach Product Footprint - Heat Density Trends The New Data Center Cooling Paradigm The Tiered Approach Lennart Ståhl Amdahl, Cisco, Compaq, Cray, Dell, EMC, HP, IBM, Intel, Lucent, Motorola, Nokia, Nortel, Sun,

More information

Typical Air Cooled Data Centre Compared to Iceotope s Liquid Cooled Solution

Typical Air Cooled Data Centre Compared to Iceotope s Liquid Cooled Solution Typical Air Cooled Data Centre Compared to Iceotope s Liquid Cooled Solution White Paper July 2013 Yong Quiang Chi University of Leeds Contents Background of the Work... 3 The Design of the Iceotope Liquid

More information

Table of Contents. 2 Why IT Organizations Everywhere Need to go Green. 3 Greening the Data Center

Table of Contents. 2 Why IT Organizations Everywhere Need to go Green. 3 Greening the Data Center WHITE PAPER: Energy Efficiency Go Green: Energy Efficiency for the IT Organization Table of Contents 2 Why IT Organizations Everywhere Need to go Green 3 Greening the Data Center 5 Savvis Commitment to

More information

Green Computing: Datacentres

Green Computing: Datacentres Green Computing: Datacentres Simin Nadjm-Tehrani Department of Computer and Information Science (IDA) Linköping University Sweden Many thanks to Jordi Cucurull For earlier versions of this course material

More information

DataCenter 2020: first results for energy-optimization at existing data centers

DataCenter 2020: first results for energy-optimization at existing data centers DataCenter : first results for energy-optimization at existing data centers July Powered by WHITE PAPER: DataCenter DataCenter : first results for energy-optimization at existing data centers Introduction

More information

Green Computing: Datacentres

Green Computing: Datacentres Green Computing: Datacentres Simin Nadjm-Tehrani Department of Computer and Information Science (IDA) Linköping University Sweden Many thanks to Jordi Cucurull For earlier versions of this course material

More information

U.S. Department of Energy, National Renewable Energy Laboratory, IT Sustainability Case Study

U.S. Department of Energy, National Renewable Energy Laboratory, IT Sustainability Case Study SUMMARY The U.S. Department of Energy s (DOE) National Renewable Energy Laboratory (NREL) designed the Research Support Facility (RSF) to demonstrate that a large office building could lead the way in

More information

TSUBAME-KFC : a Modern Liquid Submersion Cooling Prototype Towards Exascale

TSUBAME-KFC : a Modern Liquid Submersion Cooling Prototype Towards Exascale TSUBAME-KFC : a Modern Liquid Submersion Cooling Prototype Towards Exascale Toshio Endo,Akira Nukada, Satoshi Matsuoka GSIC, Tokyo Institute of Technology ( 東 京 工 業 大 学 ) Performance/Watt is the Issue

More information

Direct Fresh Air Free Cooling of Data Centres

Direct Fresh Air Free Cooling of Data Centres White Paper Introduction There have been many different cooling systems deployed in Data Centres in the past to maintain an acceptable environment for the equipment and for Data Centre operatives. The

More information

Managing Data Centre Heat Issues

Managing Data Centre Heat Issues Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design

More information

Bytes and BTUs: Holistic Approaches to Data Center Energy Efficiency. Steve Hammond NREL

Bytes and BTUs: Holistic Approaches to Data Center Energy Efficiency. Steve Hammond NREL Bytes and BTUs: Holistic Approaches to Data Center Energy Efficiency NREL 1 National Renewable Energy Laboratory Presentation Road Map A Holistic Approach to Efficiency: Power, Packaging, Cooling, Integration

More information

Capgemini UK Infrastructure Outsourcing

Capgemini UK Infrastructure Outsourcing Together. Free your energies Capgemini UK Infrastructure Outsourcing Project Arthur Improved Data Centre Efficiency Paul Feeney Capgemini Tony Mills Spie Matthew Hall Project Arthur The Toltec data centre,

More information

Guideline for Water and Energy Considerations During Federal Data Center Consolidations

Guideline for Water and Energy Considerations During Federal Data Center Consolidations Guideline for Water and Energy Considerations During Federal Data Center Consolidations Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory

More information

1. Data Centre Environment Why focus on Data Centres? Hitachi Eco-Friendly Data Centre Solutions

1. Data Centre Environment Why focus on Data Centres? Hitachi Eco-Friendly Data Centre Solutions Hitachi Eco-Friendly Data Centre Solutions Why are efficient data centres a necessity and how can they be delivered 24 th September 2009 1 1. Data Centre Environment Why focus on Data Centres? Why are

More information

IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT

IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT DATA CENTER RESOURCES WHITE PAPER IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT BY: STEVE HAMBRUCH EXECUTIVE SUMMARY Data centers have experienced explosive growth in the last decade.

More information

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES

More information

Data Center Lifecycle and Energy Efficiency

Data Center Lifecycle and Energy Efficiency Data Center Lifecycle and Energy Efficiency Lifecycle infrastructure management, power management, thermal management, and simulation solutions enable data center modernization. White Paper October 2014

More information

Data Center Equipment Power Trends

Data Center Equipment Power Trends Green field data center design 11 Jan 2010 by Shlomo Novotny Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. explores water cooling for maximum efficiency - Part 1 Overview Data

More information

I-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 4, Lancaster University, 2 nd July 2014

I-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 4, Lancaster University, 2 nd July 2014 I-STUTE Project - WP2.3 Data Centre Cooling Project Review Meeting 4, Lancaster University, 2 nd July 2014 Background Data centres estimated to use 2-3% of total electricity consumption in the UK and generate

More information

ICT and the Green Data Centre

ICT and the Green Data Centre ICT and the Green Data Centre Scott McConnell Sales Manager c/o Tanya Duncan MD Interxion Ireland Green Data Centres Our Responsibility Data centre greenhouse gas emissions are projected to quadruple by

More information

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com

More information

Understanding Power Usage Effectiveness (PUE) & Data Center Infrastructure Management (DCIM)

Understanding Power Usage Effectiveness (PUE) & Data Center Infrastructure Management (DCIM) Understanding Power Usage Effectiveness (PUE) & Data Center Infrastructure Management (DCIM) Salim Janbeh Physical Infrastructure Consultant uae-sj@panduit.com PANDUIT You Can t Manage What You Don t Measure:

More information

How a Ground Source Heat Pump Works for a School or College

How a Ground Source Heat Pump Works for a School or College How a Ground Source Heat Pump Works for a School or College Vertical System Image courtesy of Climate Master 1 Geothermal avoids the need for outdoor equipment..reducing vandalism and liability Image courtesy

More information

DATA CENTERS BEST IN CLASS

DATA CENTERS BEST IN CLASS Data Energy Audit Chameleon Data Center DATA CENTERS BEST IN CLASS... By Wouter Kok, MSc, Strategic Advisor Global Data Center Practice Deerns leads the way in making data centers greener, by reducing

More information

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory

More information

GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY. Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp.

GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY. Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. Overview Data centers are an ever growing part of our economy.

More information

Data Center Facility Basics

Data Center Facility Basics Data Center Facility Basics Ofer Lior, Spring 2015 Challenges in Modern Data Centers Management, Spring 2015 1 Information provided in these slides is for educational purposes only Challenges in Modern

More information

Trends in Data Center Design ASHRAE Leads the Way to Large Energy Savings

Trends in Data Center Design ASHRAE Leads the Way to Large Energy Savings Trends in Data Center Design ASHRAE Leads the Way to Large Energy Savings ASHRAE Conference, Denver Otto Van Geet, PE June 24, 2014 NREL/PR-6A40-58902 NREL is a national laboratory of the U.S. Department

More information

Global Green Data Center Best Practices In Action

Global Green Data Center Best Practices In Action Global Green Data Center Best Practices In Action DOUG WASHBURN VICE PRESIDENT & RESEARCH DIRECTOR September 25, 2013 Four questions I will answer 1 Why is green important to your business? 2 Why is green

More information

CarbonDecisions. The green data centre. Why becoming a green data centre makes good business sense

CarbonDecisions. The green data centre. Why becoming a green data centre makes good business sense CarbonDecisions The green data centre Why becoming a green data centre makes good business sense Contents What is a green data centre? Why being a green data centre makes good business sense 5 steps to

More information

Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015

Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015 Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015 Presentation Outline Mechanical Overview Chillers and Pumps Pipework and Ancillaries In Row Cooling Units

More information

Three Steps To Perfectly Green

Three Steps To Perfectly Green R E S E A R C H U N D E R W R I T E R W H I T E P A P E R LEAN, CLEAN & GREEN Deerns Consulting Engineers Three Steps To Perfectly Green By Wouter M. Kok, Manager, Cleanroom, Laboratory, and Data Center

More information

University of Melbourne Symposium on ICT Sustainability Dan Pointon 25 November 2008

University of Melbourne Symposium on ICT Sustainability Dan Pointon 25 November 2008 University of Melbourne Symposium on ICT Sustainability Dan Pointon 25 November 2008 Contents Welcome and Introduction Chapter 1: Data centre energy recap Chapter 2: Co-generation Chapter 3: CTC case study

More information

Guide to Minimizing Compressor-based Cooling in Data Centers

Guide to Minimizing Compressor-based Cooling in Data Centers Guide to Minimizing Compressor-based Cooling in Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By: Lawrence Berkeley National Laboratory Author: William Tschudi

More information

IT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS

IT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS IT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS SUMMARY As computer manufacturers pack more and more processing power into smaller packages, the challenge of data center

More information

Technical Systems. Helen Bedford

Technical Systems. Helen Bedford Technical Systems in Data Centres Helen Bedford Technical Systems in Data Centres Overview Cooling IT and Peripheral Equipment Security: Access and Control Building Management System (BMS) Data Centre

More information

Protecting Our Information, Protecting Our Resources

Protecting Our Information, Protecting Our Resources Solutions For Business-Critical Continuity Protecting Our Information, Protecting Our Resources Energy Efficient Power And Cooling For IT And Telecommunications Network Infrastructures The Challenge You

More information

Gas Absorption Heat Pumps. Future proofing your heating and hot water

Gas Absorption Heat Pumps. Future proofing your heating and hot water Gas Absorption Heat Pumps Future proofing your heating and hot water Gas Absorption Heat Pumps 1 Contents Gas Absorption Heat Pumps (GAHPs) The heating solution What is a Gas Absorption Heat Pump? How

More information

Opportunities for Combined Heating and Cooling Using Data Centres

Opportunities for Combined Heating and Cooling Using Data Centres Opportunities for Combined Heating and Cooling Using Data Centres Gareth Davies School of the Built Environment and Architecture, London South Bank University 103 Borough Road, London SE1 0AA Email: daviesg@lsbu.ac.uk

More information

Initial Steps in Capacity Management for the Green Datacenter

Initial Steps in Capacity Management for the Green Datacenter Initial Steps in Capacity Management for the Green Datacenter Stephen Marksamer, Aetna Inc. James Castronovo, Inventa Technologies Table of Contents Introduction... 3 Who Are the Stewards of Green?...

More information

Questions to be responded to by the firm submitting the application. Why do you think this project should receive an award? How does it demonstrate:

Questions to be responded to by the firm submitting the application. Why do you think this project should receive an award? How does it demonstrate: Questions to be responded to by the firm submitting the application Why do you think this project should receive an award? How does it demonstrate: innovation, quality, and professional excellence transparency

More information

Enterprise Data Centre

Enterprise Data Centre Members Meeting The Challenges and Changes for the Data Centre Manager 1 Continuity Forum Members Meeting May 2009 Introduction Increase awareness of IT energy usage Understand processes and practices

More information

Product description NCC Data Center

Product description NCC Data Center Product description NCC Data Center Concept General As one of the largest actors in the Nordic construction industry, NCC Construction plays a leading role in shaping the future of our society. After building

More information

imagine SOLAR AIR CONDITIONING MADE EASY

imagine SOLAR AIR CONDITIONING MADE EASY imagine SOLAR AIR CONDITIONING MADE EASY WHY SOLAR COOLING? Imagine...being able to fit a solar air conditioning system to your building that would result in dramatic reductions in electricity consumption

More information

Rittal White Paper 507: Understanding Data Center Cooling Energy Usage & Reduction Methods By: Daniel Kennedy

Rittal White Paper 507: Understanding Data Center Cooling Energy Usage & Reduction Methods By: Daniel Kennedy Rittal White Paper 507: Understanding Data Center Cooling Energy Usage & Reduction Methods By: Daniel Kennedy Executive Summary Data center energy usage has risen dramatically over the past decade and

More information

Sanjeev Gupta Product Manager Site and Facilities Services

Sanjeev Gupta Product Manager Site and Facilities Services IBM Global Technology Services IBM Project Big Green Delivering Client Value Sanjeev Gupta Product Manager Site and Facilities Services Data centers are at a tipping point and energy use and cost is the

More information

CIBSE ASHRAE Group. Data Centre Energy Efficiency: Who, What, Why, When, Where & How

CIBSE ASHRAE Group. Data Centre Energy Efficiency: Who, What, Why, When, Where & How CIBSE ASHRAE Group Data Centre Energy Efficiency: Who, What, Why, When, Where & How Presenters Don Beaty PE, FASHRAE Founder, President & Managing Director DLB Associates Consulting Engineers Paul Finch

More information

DC Pro Assessment Tools. November 14, 2010

DC Pro Assessment Tools. November 14, 2010 DC Pro Assessment Tools November 14, 2010 William Tschudi, PE Lawrence Berkeley National Laboratory WFTschudi@lbl.gov 510-495-2417 1 Slide 1 Assessment tools LBNL is developing tools to assist in performing

More information

CENIC 2009 Conference

CENIC 2009 Conference Green Datacenter Initiatives at UCSD CENIC 2009 Conference Dallas Thornton SDSC Division Director, Cyberinfrastructure Services dallas@sdsc.edu Campus Quick Facts With a daily population of over 45,000,

More information

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program

More information

Assessment to support the planning of sustainable data centers with high availability

Assessment to support the planning of sustainable data centers with high availability Assessment to support the planning of sustainable data centers with high availability Gustavo Rau de Almeida Callou grac@cin.ufpe.br Supervisor: Prof. Paulo Romero Martins Maciel prmm@cin.ufpe.br Introduction

More information

BC43: Virtualization and the Green Factor. Ed Harnish

BC43: Virtualization and the Green Factor. Ed Harnish BC43: Virtualization and the Green Factor Ed Harnish Agenda The Need for a Green Datacenter Using Greener Technologies Reducing Server Footprints Moving to new Processor Architectures The Benefits of Virtualization

More information

Green Fleet Action Plan 2011-2014

Green Fleet Action Plan 2011-2014 Green Fleet Action Plan 2011-2014 2013 Year-end Update Department of Finance and Management Division of Fleet Management 1 City of Columbus Green Fleet Action Plan 2011-2014 2013 Year-end Update Mayor

More information

Energy Efficiency and Availability Management in Consolidated Data Centers

Energy Efficiency and Availability Management in Consolidated Data Centers Energy Efficiency and Availability Management in Consolidated Data Centers Abstract The Federal Data Center Consolidation Initiative (FDCCI) was driven by the recognition that growth in the number of Federal

More information

Datacenter Efficiency

Datacenter Efficiency EXECUTIVE STRATEGY BRIEF Operating highly-efficient datacenters is imperative as more consumers and companies move to a cloud computing environment. With high energy costs and pressure to reduce carbon

More information

Solve your IT energy crisis WITH An energy SMArT SoluTIon FroM Dell

Solve your IT energy crisis WITH An energy SMArT SoluTIon FroM Dell Solve your IT energy crisis WITH AN ENERGY SMART SOLUTION FROM DELL overcome DATA center energy challenges IT managers share a common and pressing problem: how to reduce energy consumption and cost without

More information

Green ICT: Consistent Actions to Reduce Energy Consumption

Green ICT: Consistent Actions to Reduce Energy Consumption / Martin Chaloupek Vienna, 2010 02 22 Green ICT: Consistent Actions to Reduce Energy Consumption Input to Conference Energy Efficiency Chances of Green ICT and Electronics Vienna, 2010 03 05 20010 IBM

More information

WHITE PAPER. How To Build A Real Green Data Centre. Contents. Part 1: Drivers for Data Centre energy efficiency. February 2008

WHITE PAPER. How To Build A Real Green Data Centre. Contents. Part 1: Drivers for Data Centre energy efficiency. February 2008 NORMAN DISNEY & YOUNG LEVEL 1 60 MILLER STREET NORTH SYDNEY AUSTRALIA 2060+61 2 9928 6800 +61 2 9955 6900 URL www.ndy.comndy MANAGEMENT PTY LIMITED TRADING AS NORMAN DISNEY & YOUNG ABN 29 003 234 571 `

More information

Recommendations for Measuring and Reporting Overall Data Center Efficiency

Recommendations for Measuring and Reporting Overall Data Center Efficiency Recommendations for Measuring and Reporting Overall Data Center Efficiency Version 2 Measuring PUE for Data Centers 17 May 2011 Table of Contents 1 Introduction... 1 1.1 Purpose Recommendations for Measuring

More information

Overview of Green Energy Strategies and Techniques for Modern Data Centers

Overview of Green Energy Strategies and Techniques for Modern Data Centers Overview of Green Energy Strategies and Techniques for Modern Data Centers Introduction Data centers ensure the operation of critical business IT equipment including servers, networking and storage devices.

More information

SEMINAR 23: Data Center and IT Equipment Liquid Cooling: Performance Capabilities, Implementation and Emerging Technologies

SEMINAR 23: Data Center and IT Equipment Liquid Cooling: Performance Capabilities, Implementation and Emerging Technologies Michael K Pa+erson, PhD, PE, DCEP Intel Corpora7on michael.k.pa+erson@intel.com SEMINAR 23: Data Center and IT Equipment Liquid Cooling: Performance Capabilities, Implementation and Emerging Technologies

More information

State of the Art Energy Efficient Data Centre Air Conditioning

State of the Art Energy Efficient Data Centre Air Conditioning - White Paper - State of the Art Energy Efficient Data Centre Air Conditioning - Dynamic Free Cooling - Release 2, April 2008 Contents ABSTRACT... 3 1. WHY DO I NEED AN ENERGY EFFICIENT COOLING SYSTEM...

More information

Rainwater Harvesting

Rainwater Harvesting Rainwater Harvesting With climate change now a reality rather than a speculated possibility, the demand on water resources has gone up, whilst the amount of water available for supply has gone down. Forth

More information

University of St Andrews. Energy Efficient Data Centre Cooling

University of St Andrews. Energy Efficient Data Centre Cooling Energy Efficient Data Centre Cooling St. Andrews and Elsewhere Richard Lumb Consultant Engineer Future-Tech Energy Efficient Data Centre Cooling There is no one single best cooling solution for all Data

More information

Carbon Footprint of CMC Hospital for 2013

Carbon Footprint of CMC Hospital for 2013 Carbon Footprint of CMC Hospital for 2013 Carbon footprint of CMC Hospital campus was estimated for the year 2011 and 2012 and the total CO2e emission was estimated at 15271.74 CO2e tons and 15456.61 CO2e

More information

Driving the Green Data Center Strategy in Established Environments

Driving the Green Data Center Strategy in Established Environments Driving the Green Data Center Strategy in Established Environments November 2008 Agenda Green IT defined Arrow Green Initiatives Data Center Other Initiatives Green Challenges Green IT Optimal use of information

More information

Data center lifecycle and energy efficiency

Data center lifecycle and energy efficiency Data center lifecycle and energy efficiency White Paper Lifecycle management, thermal management, and simulation solutions enable data center energy modernization Introduction Data centers are coming under

More information

Rules of Thumb Energy Efficiency in Buildings

Rules of Thumb Energy Efficiency in Buildings Energy Efficiency in Buildings Energy Savings Cost Savings Increased Productivity Economic Development Other Standard lighting retrofits: $0.90-$1.20 per square foot. High-efficiency packaged and split

More information

Drives and motors. A guide to using variable-speed drives and motors in data centres

Drives and motors. A guide to using variable-speed drives and motors in data centres Drives motors A guide to using variable-speed drives motors in data centres The power behind the data Private public businesses, from banks to supermarkets, to telecommunications companies internet providers

More information

Data Centre Outsourcing a Buyer s Guide

Data Centre Outsourcing a Buyer s Guide Data Centre Outsourcing a Buyer s Guide The inside guide to deciding whether to outsource your data centre facility and operations and how to select an appropriate partner. This Guide will help you Determine

More information

ENERGY PRODUCING SYSTEMS

ENERGY PRODUCING SYSTEMS ENERGY PRODUCING SYSTEMS SOLAR POWER INTRODUCTION Energy from the sun falls on our planet on a daily basis. The warmth of the sun creates conditions on earth conducive to life. The weather patterns that

More information

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power and cooling savings through the use of Intel

More information

The Efficient Data Center

The Efficient Data Center WHITE PAPER Data Center Efficiency and Optimization Data Center Management The Efficient Data Center Using data center instrumentation and server refresh to optimize compute performance in constrained

More information

An addendum for France & the UK to Cloud Computing the IT Solution for the 21 st Century

An addendum for France & the UK to Cloud Computing the IT Solution for the 21 st Century Carbon Disclosure Project Study 2011 An addendum for France & the UK to Cloud Computing the IT Solution for the 21 st Century Study produced for Carbon Disclosure Project by: 1 Introduction This report

More information

BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0

BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0 BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0 To achieve GREEN MARK Award Pre-requisite Requirement All relevant pre-requisite requirements for the specific Green Mark Rating are to be complied

More information

The Policy and Status of Global Green Data Center Certifications

The Policy and Status of Global Green Data Center Certifications The Policy and Status of Global Green Data Center Certifications International Green Datacenter Symposium 2013 Ed Ansett i 3 Solutions Group Current Energy Efficiencies 10.00% 20.00% 70.00% Servers Storage

More information

Data Center Industry Leaders Reach Agreement on Guiding Principles for Energy Efficiency Metrics

Data Center Industry Leaders Reach Agreement on Guiding Principles for Energy Efficiency Metrics On January 13, 2010, 7x24 Exchange Chairman Robert Cassiliano and Vice President David Schirmacher met in Washington, DC with representatives from the EPA, the DOE and 7 leading industry organizations

More information

CITY OF MINNEAPOLIS GREEN FLEET POLICY

CITY OF MINNEAPOLIS GREEN FLEET POLICY CITY OF MINNEAPOLIS GREEN FLEET POLICY TABLE OF CONTENTS I. Introduction Purpose & Objectives Oversight: The Green Fleet Team II. Establishing a Baseline for Inventory III. Implementation Strategies Optimize

More information

Data Centre Cooling Technologies. Jon Pettitt, EMEA DataCenter Business Development Manager

Data Centre Cooling Technologies. Jon Pettitt, EMEA DataCenter Business Development Manager Data Centre Cooling Technologies 1 Jon Pettitt, EMEA DataCenter Business Development Manager Munters Group Key facts 3.000 Employees 30 Countries Turnover of 470 M HQ in Sweden Global DC Support 25+ Data

More information

HP Data Center Efficiency For The Next Generation. Pete Deacon Canadian Portfolio Manager Power and Cooling Services

HP Data Center Efficiency For The Next Generation. Pete Deacon Canadian Portfolio Manager Power and Cooling Services HP Data Center Efficiency For The Next Generation Pete Deacon Canadian Portfolio Manager Power and Cooling Services The HP difference Industry-wide expertise, global reach HP operations span more than

More information

Interested in conducting your own webinar? Email webinars@bnpmedia.com

Interested in conducting your own webinar? Email webinars@bnpmedia.com Interested in conducting your own webinar? Email webinars@bnpmedia.com Improving Efficiencies by Integrating Data Center Systems August 30 th, 2012 Audio Abstract Presenter Info Slides Handouts Group Chat

More information

11 Top Tips for Energy-Efficient Data Center Design and Operation

11 Top Tips for Energy-Efficient Data Center Design and Operation 11 Top Tips for Energy-Efficient Data Center Design and Operation A High-Level How To Guide M e c h a n i c a l a n a l y s i s W h i t e P a p e r w w w. m e n t o r. c o m When is Data Center Thermal

More information

European Code of Conduct for Data Centre. Presentation of the Awards 2013

European Code of Conduct for Data Centre. Presentation of the Awards 2013 European Code of Conduct for Data Centre Presentation of the Awards 2013 Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 The Code of Conduct for Data Centre Results Started

More information

Energy Benchmarking Report for Lafayette Elementary School Bound Brook, NJ

Energy Benchmarking Report for Lafayette Elementary School Bound Brook, NJ Energy Benchmarking Report for Lafayette Elementary School Bound Brook, NJ (for the period: March 2007 through February 2009) Prepared by: Background & Findings The New Jersey Clean Energy Program (NJCEP)

More information

Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre

Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre S. Luong 1*, K. Liu 2, James Robey 3 1 Technologies for Sustainable Built Environments, University of Reading,

More information

MEGWARE HPC Cluster am LRZ eine mehr als 12-jährige Zusammenarbeit. Prof. Dieter Kranzlmüller (LRZ)

MEGWARE HPC Cluster am LRZ eine mehr als 12-jährige Zusammenarbeit. Prof. Dieter Kranzlmüller (LRZ) MEGWARE HPC Cluster am LRZ eine mehr als 12-jährige Zusammenarbeit Prof. Dieter Kranzlmüller (LRZ) LRZ HPC-Systems at the End of the UNIX-Era (Years 2000-2002) German national supercomputer Hitachi SR800

More information

Green Evaluation Metrics and Software Tool for Data Center

Green Evaluation Metrics and Software Tool for Data Center Green Evaluation Metrics and Software Tool for Data Center Wong Hui Shin Faculty of Computing and Informatics, Multimedia University, Cyberjaya, Selangor, Malaysia. hswong@mmu.edu.my Saravanan Muthaiyah

More information

Control of Computer Room Air Handlers Using Wireless Sensors. Energy Efficient Data Center Demonstration Project

Control of Computer Room Air Handlers Using Wireless Sensors. Energy Efficient Data Center Demonstration Project Control of Computer Room Air Handlers Using Wireless Sensors Energy Efficient Data Center Demonstration Project About the Energy Efficient Data Center Demonstration Project The project s goal is to identify

More information

Recommendations for Measuring and Reporting Overall Data Center Efficiency

Recommendations for Measuring and Reporting Overall Data Center Efficiency Recommendations for Measuring and Reporting Overall Data Center Efficiency Version 1 Measuring PUE at Dedicated Data Centers 15 July 2010 Table of Contents 1 Introduction... 1 1.1 Purpose Recommendations

More information

Addressing the Energy Challenge in Singapore s Data Centres

Addressing the Energy Challenge in Singapore s Data Centres Addressing the Energy Challenge in Singapore s Data Centres Gain Singapore Green Data Centre Certifications and reduce energy costs by up to 30% with Schneider Electric s proven data centre lifecycle approach

More information

City of Columbus Green Fleet Action Plan

City of Columbus Green Fleet Action Plan City of Columbus Green Fleet Action Plan 2011-2014 Department of Finance and Management Division of Fleet Management 1 City of Columbus Green Fleet Action Plan 2011-2014 Mayor Michael B. Coleman Section

More information

Making Existing Server Rooms More Efficient Steve Bowes-Phipps, Data Centre Manager University of Hertfordshire. http://rare-idc.herts.ac.

Making Existing Server Rooms More Efficient Steve Bowes-Phipps, Data Centre Manager University of Hertfordshire. http://rare-idc.herts.ac. Making Existing Server Rooms More Efficient Steve Bowes-Phipps, Data Centre Manager University of Hertfordshire http://rare-idc.herts.ac.uk Making Existing Server Rooms More Efficient Reduction and Re-use

More information

Data Center & IT Infrastructure Optimization. Trends & Best Practices. Mickey Iqbal - IBM Distinguished Engineer. IBM Global Technology Services

Data Center & IT Infrastructure Optimization. Trends & Best Practices. Mickey Iqbal - IBM Distinguished Engineer. IBM Global Technology Services Data Center & IT Infrastructure Optimization Trends & Best Practices Mickey Iqbal - IBM Distinguished Engineer IBM Global Technology Services IT Organizations are Challenged by a Set of Operational Issues

More information