DESIGN OF CLOSED-LOOP GEOTHERMAL HEAT EXCHANGERS IN THE U.S.
|
|
|
- Bruno Newman
- 9 years ago
- Views:
Transcription
1 Chapter 2.4 DESIGN OF CLOSED-LOOP GEOTHERMAL HEAT EXCHANGERS IN THE U.S. Edited by John W. Lund Geo-Heat Center INTRODUCTION and some western European countries. The size of individual units, however, range from Geothermal heat pumps (aka groundsource 5.5 kw (Poland and Sweden) for residential heat pumps) (GHP or GSHP) are use to large units over 150 kw (Germany used in two basic modes: ground coupled and the United States) for commercial and (vertical or horizontal) closed loop, or institutional installations (Sanner, 2001). groundwater types open loop (Figure 1 In the United States, most units are sized and 2). The installation and use of geothermal for the peak cooling load and are oversized heat pumps worldwide have had a for heating (except in the northern states) large increase over the past ten years at and, thus, are estimated to average only almost 10% annually. Most of this growth 1,000 full-load heating hours per year (capacity has occurred in the United States and factor of 0.11). In Europe most units Europe, though interest is developing in are sized for the heating load and are often other countries such as Japan and Turkey designed to provide just the base load with (see Geo-Heat Center Quarterly Bulletin, peaking by fossil fuel. As a result, these Vol. 22, No. 1, March, 2001). At the beginning units may operate from 2,000 to 6,000 full- of 2000 the worldwide installed load hours per year (capacity factor of 0.23 capacity in 27 countries was 6,875 MWt and to 0.68). An average value for European the annual energy use was 23,287 TJ/yr countries is approximately 2,200 full-load (Lund, 2001a). The actual number of installed hours per year (Rybach and Sanner, 1999; units is around 500,000, but the data Sanner 2001). are incomplete. The equivalent number of In the United States, geothermal heat 12 kw units installed is slightly over pump installations have steadily increased 570,000. The 12 kw (3.4 tons) equivalent is over the past 10 years with an annual growth used as typical of homes in the United States rate of about 12%, mostly in the mid- 1
2 International Course on GEOTHERMAL HEAT PUMPS western and eastern states from North Dakota to Florida. Today there are an estimated 500,000 units (12 kw equivalent) installed with 50,000 installed annually. Of these 46% are vertical closed loop, 38% horizontal closed loop and 15% open loop systems (Lund, 2001). Projections for the future are that the growth rate will increase about 12% annually, so that by 2010 an estimated 140,000 new units would be installed in that year, thus, adding almost one million units for a total of about 1.5 million units. Over 600 schools have installled these units for heating and cooling, especially in Texas. Using a Coefficient of Performance (COP) of 4.0 and 1,000 full-load hours per year in the heating mode, the 500,000 equivalent units remove approximately 16,200 TJ/yr from the ground. The cooling mode energy is not considered geothermal, since this rejects heat to the ground; however, the cooling mode does replace other forms of energy and is, thus considered in fossil fuel and greenhouse gases emission savings. It should be noted at this point, that in the United States, heat pumps are rated on tonnage (i.e., one ton of cooling power produced by a ton of ice) is equivalent to 12,000 Btu/hr or 3.52 kw. vertical horizontal Figure 1. Ground-coupled (closed-loop) types. direct two well pond Figure 2. Groundwater (open-loop) types. Recent converts to this form of energy sa-vings is U. S. President George W. Bush, who recently installed a 49 kw closed loop geothermal heat pump on his Texas ranch. A general introduction to geothermal heat pumps can be found in Lund (2001b). 2
3 BACKGROUND: CLOSED LOOP SYSTEMS The following presentation is a summary of material (with the appropriate unit conversions) presented in Ground-Source Heat Pumps -- Design of Geothermal Systems for Commercial and Institutional Buildings by Stephen P. Kavanaugh and Kevin Rafferty, and published by the American Society of Heating, Refrigeration and Air-Conditioning Engineers, Inc., (ASHRAE) Atlanta, GA (1997), and in Earth-Source Heat Exchanger for Heat Pumps by Harry J. Braud, James Oliver and Henry Klimkowski, and published in the Geo- Heat Center Quarterly Bulletin, Vol. 11, No. 1, Summer, As stated in Chapter 3 of Kavanaugh and Rafferty (1997) on Fundamentals of Vertical Ground Heat Exchanger Design : The design of vertical ground heat exchangers is complicated by the variety of geological formations and properties that affect thermal performance. Proper identification of materials, moisture content, and water movement is an involved process and cannot be economically justified for every project. Therefore, the necessary information for complex analysis is usually unavailable. A more prudent design approach is to apply empirical data to a simple solution of heated (or cooled) pipes place in the ground. The thermal properties can be estimated by using values for soils in a particular group and moisture content that is characteristic of local conditions. This method has proved successful for residential and light commercial systems... Some permanent change in the local ground temperature may be expected for systems with large annual differences between the amount of heat extracted (heating mode) and the amount rejected (cooling mode). This problem is compounded in commercial systems where earth heat exchangers are more likely to be installed in close proximity because the available ground area is more limited. Two schools of thought are that the maximum and minimum ground temperatures may take several years to occur depending on the amount of heat extracted or rejected to the ground (Claesson and Eskilson, 1987). This is especially true for multiple boreholes close to each other, as the worst case condition may occur several years after installation. Thus, in this case, the design should consider the long term performance. On the other hand, Kavanaugh (1984) suggests that detailed simulations for a great many years is unnecessary. He feels that an estimate of the annual net amount is sufficient for accurate determination of performance as variations in heat transfer are damped by the large thermal mass of the ground surrounding the coil. RULES OF THUMB Rules of thumb that is often used for the initial planning and cost estimate in the U.S. (Kavanaugh and Gilbreath, 1995; Rafferty, 2001) to 200 feet/ton (13 to 17 m/kw) for vertical loops 2. Approximately 30% to 50% longer for horizontal loops under the same conditions. 3. US$ 750/ton ($213/kW) for horizontal ground loop installation. 4. US$1,050/ton ($300/kW) for vertical ground loop installation. 5. US$8,200/ton ($2,330/kW) total installed cost for horizontal system (loop, heat pump, ductwork, etc.) 6. US$9,000/ton ($2,560/kW) total installed cost for vertical system (loop, heat pump, ductwork, etc.) 7. Typical U.S. residence of 2,000-2,400 ft 2 (186 to 223 m 2 ) requires 3 to 4 tons (10.6 to 11.4 kw) of heating supply, depending on climate. It should be noted at this point, that design of horizontal loops, buried in trenches 4 to 6 feet (1.2 to 1.8 m) deep, are heavily influence by solar radiation and the number of loops in each 3
4 International Course on GEOTHERMAL HEAT PUMPS trench. Since the solar radiation is difficult to quantify, no design methods are available for horizontal loops. THE SIMPLIFIED METHOD Ingersoll et al. (1954) uses a simple steadystate heat transfer equation to solve for the shorter term variation: where, q = L (t g - t w ) / R [1] q = rate of heat transfer for the heat exchanger length (Btu/hr or W), L = length of heat exchanger (bore length) (ft or m), t g = temperature of the ground ( o F or o C), t w = average temperature of the fluid in the pipes ( o F or o C), and R = thermal resistance of the ground (h. ft.o F/Btu or m.o C/W) This equation can be rewritten as (Braud, et al., 1988): q = L (U. T) [2] where, U = the conductance rate for heat transfer from the circulating fluid To the earth (Btu/h. ft.o F or W/m.o C), and T = (T 2 - T 1 )/2 - T o, the difference in the average fluid temperature in the pipes ((T 2 - T 1 )/2)), and the earth temperature (T o ). THE LONG METHOD Kavanaugh and Rafferty ( chapters 3 and 4) describe a more precise method of calculating coil length which transforms the steadystate equation to give the variable heat rate of a ground heat exchanger by using a series of constant heat rate pulses. The thermal resistance of the ground per unit length is calculated as a function of time, which corresponds to the time for a particular heat pulse. A term is also included to account for the thermal resistance of the pipe wall and interfaces between the pipe and fluid and the pipe and the ground. The equations for cooling bore length (L c ) and heating bore length (L h ) are as follows: Where, 4 For cooling: L c = q a R ga + (q lc W c )(R b + PLF m R gm + R gd F sc )/(t g - (t wi + t wo )/2 - t p ) [3] For heating L h = q a R ga + (q lh W h )(R b + PLF m R gm + R gd F sc )/(t g - (t wi + t wo )/2 - t p )[4] F sc = short-circuit heat loss factor PLF m = part-load factor during design month q a = net annual average heat transfer to the ground (Btu/h) q lc = building design cooling block load (Btu/h) q lh = building design heating block load (Btu/h) R ga = effective thermal resistance of the ground, annual pulse (h. ft.o F/Btu) R gd = effective thermal resistance of the ground, daily pulse (h. ft.o F/Btu) R gm = effective thermal resistance of the ground, monthly pulse (h. ft.o F/Btu) R b = thermal resistance of the bore (h. ft.o F/Btu) t g = undisturbed ground temperature ( o F) t p = temperature penalty for interference of adjacent bores ( o F) t wi = liquid temperature at heat pump inlet ( o F) t wo = liquid temperature of heat pump outlet ( o F) W c = power input at design cooling load (W) W h = power input at design heating load (W)
5 Note: heat transfer rates, building loads, and In many cases, especially in commercial and temperature penalties are positive for heating institutional buildings, the cooling load is larger and negative for cooling. resulting in a longer length (L c ) of pipe for According to Kavanaugh and Rafferty cooling. If this length is use, then excess heat (1997) the above equations [3, 4] consider three will be available during the heating season. An different pulses of heat to account for (1) alterative, is to design for the shorter heating long-term heat imbalances (q a ), (2) average bore length (L h ) and then use a cooling tower to monthly heat rates during the design month, and compensate for the additional cooling load as (3) the maximum heat rates for a short-term described in Rafferty (1995) and discussed later period during the design day - which could be as in this paper. short as one hour, but a four-hour block is Again, according to Kavanaugh and Rafferty recommended. (1997), equations [3, 4] can be simplified as The required bore length is the larger of the follows: two determined by the above equations [3, 4]. L c = q a R ga + (C fc. q lc )(R b + PLF m R gm + R gd F sc )/(t g - (t wi + t wo )/2 - t p ) [5] L h = q a R ga + (C fh. q lh )(R b + PLF m R gm + R gd F sc )/(t g - (t wi + t wo )/2 - t p ) [6] The correction factors, C fc and C fh, account for the amount of heat rejected or absorbed by the heat pumps, which is dependent on the respective EER and COP of the units. Equations [5, 6] require the average EER and COP of all the units in a particular building. In addition, the average annual heat rate to the ground (q a ) can be found by using the annual equivalent full-load cooling and heating hours. q a = (C fc. q lc. EFL hours c + C fh. q lh. EFL hours h )/8760 hours [7] The heat pumps correction factors used in equations [5, 6 and 7] are given in Table 1 (Kavanaugh and Rafferty, 1997). Table 1. Heat Pumps Correction Factors. Note: The heating performance, COP (coefficient of performance) is the heating affect produced by the unit (Btu/h or W) divided by the energy equivalent of the electrical input (Btu/h or W) resulting in a dimensionless numbers (the same in the U.S. and in Europe). However, the Cooling EER C fc Heating COP C fh 11 (3.22) (3.81) (4.40) (4.98) cooling performance, EER (energy efficiency ratio) is different between the U.S. and Europe. In the U.S. it is defined by the cooling affect produced by the unit (Btu/h) divided by the electrical input (W) resulting in units of Btu/watt. h as shown in Table 1. European units would 5
6 International Course on GEOTHERMAL HEAT PUMPS be W/W and is dimensionless - multiple the EER number in Table 1 by (shown in parentheses). All heat pumps are rated by the Air Conditioning and Refrigerant Institute (ARI) and are published every six months in the Directory of Certified Applied Air Conditioning Products for Geothermal Heat Pumps. Closed loop systems were rated under ARI 330 and open loops under ARI 325. As of January 2000 these ratings are combined under ISO rating system. EXAMPLE PROPERTIES Tables with examples of various properties associated with closed-loop systems are presented in Kavanaugh and Rafferty (1997). Abridged samples of these tables are reproduced below: 5 in. bore (127 mm) 0.75 in. U-tube (19 mm) 0.14 (NR) (NR) (NR) in. U-tube (25 mm) 0.11 (NR) (NR) (NR) in. U-tube (32 mm) (NR) Table 2. Thermal Resistances (R b ) for Polyethylene U-Tubes* [Pipe (bore) thermal resistance: h. ft.o F/Btu (m.o C/W)] U-tube Dia. Type For water 20% Prop. 20% Prop. 20% Prop. Flows above Glycol flow Glycol Flow Glycol Flow 2.0 gpm 3.0 gpm 5.0 gpm 10.0 gpm (0.13 L/s) (0.19 L/s) (0.32 L/s) (0.63 L/s) 0.75 in. (19 mm) Sch (0.058) 0.14 (0.081) NR NR 1.0 in. (25 mm) Sch ( (0.087) 0.11(0.064) NR 1.24 in. (32 mm) Sch (0.052) 0.15 (0.087) 0.12 (0.069) 0.09 (0.052) Based on using borehole cuttings for backfilling around U-tube. Use Table 3 corrections for other conditions NR = Not Recommended Table 3. Thermal Resistance Adjustments for Other Borehole Backfills or Grouts. (Add values to base resistance in Table 2). Natural Soil Cond. 0.9 Btu/h. ft.o F 1.3 Btu/h. ft.o F 1.7 Btu/h. ft.o F (1.56 W/m.o C) (2.25 W/m.o C) (2.94 W/m.o C) Backfill or Grout 0.5 Btu/ 2.0 Btu/ 0.5 Btu/ 1.0 Btu/ 2.0 Btu/ 0.5 Btu/ 1.0Btu/ Conductivity h. ft.o F* h. ft.o F h. ft.o F h. ft.o F h. ft.o F h. ft.o F h. ft.o F 4 in. bore (102 mm) 0.75 in. U-tube (19 mm) 0.11 (NR) (NR) (NR) in. U-tube (25 mm) (NR) 0.04
7 NR = Not Recommended - For low thermal conductivity grouts, use small bore diameter. Air Gaps add 0.2 to 0.4 h. ft.o F/Btu to bore resistance (0.12 to 0.23 m.o C/W). * to convert to W/m.o C - multiply Btu/h. ft.o F x Note: some adjustments are negative, which indicates a thermal enhancement and a lower net thermal resistance compared to natural backfills. Table 4. Thermal Conductivity of Sand and Clay Soils in Btu/h. ft.o F (W/m.o C). Soil Type Dry Density 5% moisture 10% moisture 15% moisture 20% moisture Coarse* 100 lb/ft % sand 1.60 g/cm lb/ft g/cm Fine grained 100 lb/ft % clay 1.60 g/cm * Coarse grained = to 5 mm; fine grained = <0.075 mm diameter particles. Table 5. Thermal Properties of Rocks at 77 0 F (25 o C) Rock Type Thermal Conductivity* Density Btu/h. ft.o F (W/m.o C) lb/ft 3 (g/cm 3 ) Granite (25% quartz) ( ) 165 (2.64) Andesite ( ) 160 (2.56) Basalt ( ) 180 (2.88) Limestone ( ) ( ) Sandstone ( ) ( ) Wet Shale (no quartz) ( ) ( ) Dry Shale (no quartz) ( ) ( ) Gneiss ( ) ( ) Schist ( ) ( ) * this represents the mid-range for samples of rock Table 6. Thermal Conductivities of Typical Grouts and Backfills. Btu/h. ft.o F (W/m.o C) Grouts without additives 20% bentonite 0.42 (0.73) Cement mortar ( ) Concrete (150 lbs/ft g/cm 3 ) 0.80 (1.38) 7
8 International Course on GEOTHERMAL HEAT PUMPS Thermally enchanced grouts 20% bentonite - 40% quartzite 0.85 (1.47) 30% bentonite - 30% iron ore 0.45 (0.78) 60% quartzite - flowable fill 1.07 (1.85) (Cement + fly ash + sand) Table 7. Approximate Liquid Temperature Change Through GCHP Units. System Flow Temperature Rise Temperature Drop gpm/ton in Cooling - o F ( o C) In Heating - o F ( o C) (L/s/kW) 3.0 (0.054) 10 (5.6) 6 (3.3) 2.5 (0.045) 13 (7.2) 7-8 ( ) 2.0 (0.036) 15 (8.3) 9 (5.0) The details of how to determined the vertical bore hole lengths for heating and cooling using the above tables and the more detailed formulas ( The Long Way ) can be found in Chapters 3 and 4 of Kavanaugh and Rafferty (1997). Since this computational method is very time consuming, and it is difficult to evaluate the impact of design alternatives as calculations must be repeated - a computer program currently available on the market is then discussed. COMPUTER PROGRAM A computer program is available from Stephen Kavanaugh, Energy Information Services, PO Box , Tuscaloosa, AL ( [email protected]) - called Geothermal Heat Pump Design Software for Commercial Buildings GchpCalc. The developer states: 8 GchpCalc is a program for sizing commercial ground coupled heat pump (GCHP) systems. This program integrates concepts familiar to HVAC engineers with information necessary to design ground heat exchangers. The program user begins by entering the results of a cooling load and heat loss calculation. After a heat pump model line is selected (data from 12 manufacturers has been preloaded), the designer specifies desired water flows, temperatures, and vertical ground coil arrangement. Ground properties are entered with help from information tables. Data is entered in easy to use screens, which can be easily modified. Output appears in four formats. The program selects the heat pump model for each zone and specifies the required coil length. Hybrid GHP systems can also be designed. A variety of system performance data are listed. These include maximum block loads, required water flow rates, peak demands and average heat pump and system efficiencies. The program allows the user to easily change any input and quickly determine resulting effects on ground coil size and system performance.
9 The Geothermal Heat Pump Design Software for Commercial Version 3.1 features: * Easy Hybrid System Design * Hybrid Cooler Sized to Meet Peak Demand or Balance Annual Ground Heat * Rejection Load * Automatic or Manual Cooler Fan Motor Sizing * New and Updated Heat Pump Manufacturer List * Automatic Calculation of * Bore Resistance (no more tables) * Automatic Pump Size Selection * Expanded Tables of Rock and Soil Thermal Properties * New Table of Grout and Backfill Thermal Properties * Expanded and Simplified Zone Load Handling Capabilities An evaluation copy of the computer program can be obtained for a 10-day period by ac-cessing it on the Internet at: A number of other computer design systems are available in the United States, including the International Ground Source Heat Pump Association (GLHEPRO and CLGS); RIGHT- LOOP by Wright Associ-ates, Lexington, MA; ECA by Elite Software Inc., Bryan, TX; WFEA by WaterFurnace Int l., Inc., Fort Wayne, IN, GL-Source by Kansas Electric Utility, Topeka, KS; and GEOCALC by HVACR Programs, Ferris State Univ., Big Rapids, MI (Sanner, et al, 1999). Heat Pump Circulating Pump Closed Cirucit Cooling Tower Vertical Bore Ground Loops Figure 3. Hybrid ground-coupled heat pump system. 9
10 International Course on GEOTHERMAL HEAT PUMPS HYBRID SYSTEM Due to the high cost associated with installing a ground loop to meet the peak cooling load in commercial buildings, a hybrid system using a cooling tower should be considered (Figure 3). The use of the cooling tower allows the designer to size the ground loop for the heating load and use it in combination with the tower to meet the peak cooling load. The tower preserves some of the energy efficiency of the system, but reduces the capital cost associated with the ground loop installation (Raffety, 1995). Generally, the hybrid system is attractive in situations where ground loop costs per ton (kw) are high, and where the heating loop length requirement is low relative to the cooling loop length requirement. According to Rafferty (1995), the most favorable conditions for a hybrid system is where the loop length ratios (heating/ cooling) are in the range of 0.3 to 0.4. The conclusions are based on 60 o F (16 o C) soil, ground coupled line cost of $5.00/ft ($16.40/m) and 200 ft/ton (17 m/kw). ECONOMICS h 1. Installed cost - ground loop Ground coupled - horizontal: Ground coupled - slinky Ground coupled - vertical Ground water - 3 ton (10.5 kw) GROUT FOR GROUND-COUPLED SYSTEMS Recent work by Brookhaven national laboratory (Allan, 1998) studied the thermal conductivity of various cement-sand grouts used in GCHP. The research investigated the suitability of this material for grouting vertical boreholes. The role of mix variables such as water/cement ratio, sand/cement ratio and super-plasticizers dosage were measured. The work summarized the thermal conductivity, permeability and bond strength results for selected grout mixes. Addition of sand and use of super-plasticizers to reduce water/cement ratio improved grout performance compared with net cements. The conclusion were: Super-plasticized cement-silica sand grounts have thermal conductivities in the range of to Btu/h. ft.o F (2.161 to W/m.o C) for sand/cement ratios by mass of 2. To 2.5. Cement-sand grouts have significantly higher thermal conductivity than neat cement or bentonite grouts and retain conductive properties under drying conditions. Bond strength and interfacial impermeability are improved by addition of sand and control of water/cement ratio. Field trials were also undertaken. According to Kavanaugh and Gilbreath (1995), and Rafferty (2001), residential geothermal heat pump systems would have the following costs. $ 741/ton ($210/kW) $ 904/ton ($258/kW) $1,028/ton ($292/kW) $ 675/ton ($192/kW) 2. Cost of water-to-air heat pump units Ground coupled - horizontal $8,136 Ground coupled - slinky $8, tons (8.8 kw) $2, tons (10.6 kw) $2, tons (14.1 kw) $3, Total installed cost - 3 ton (10.6 kw) system - includes ground loop, unit, ductwork, etc.
11 Ground coupled - vertical $8,997 Ground water $6,873 Air-source heat pump $4,430 Gas with air conditioning $4, Estimation of payback Assuming a typical residence in the U.S. using 40,000 Btu/ft 2 / yr (126 kwh/m 2 / yr) for heating and at 2,000 ft 2 (186 m 2 ) and with natural gas at $9.13/million Btu ($0.0312/ kwh) - the annual heating cost would be: $730. The difference in cost between a vertical ground coupled system and the gas system is $4,666. Assuming that the electricity input into the heat pump (COP = 4.0) is 25% of the energy output (5,860 kwh/yr), the simple pay back of the geothermal system for heating would be 14.5 years. Using an electric furnace (assuming cost is the same as the gas furnace) and with electricity at $0.07/kWh - the annual cost would be $1,640. The simple payback for heating would then be 3.8 years. These numbers are for the state of Oregon, and will be higher for other parts of the U.S (the payback period would be less). If cooling is also considered (at 40,000 Btu/ft 2 /yr kwh/m 2 /yr and EER = 13.6/4.0) then the payback period compared to natural gas would be 7.3 years, and compared to electricity would be 1.9 years. EXAMPLE CALCULATIONS (SHORT METHOD) Given the following data: A sample calculation is provided by Braud et al. (1988) using the short method with formula [2]. Table 8. Earth Heat Exchange Rate with Steel Casing and SCH 40 PVC Inner Pipe. Percent run time U (W/ o C/m) Earth Resistance R s ( O C. m/w) Table 9. Heat Exchanger Parameters for PVC Casing and Inner Pipe. Percent run time U (W/ o C/m) PVC Pipe Resistance R p ( O C. m/w) Table 10. Conductance to Earth with Polyethylene U-Bend Heat Exchanger. Percent run time U (W/ o C/m) The problem is to determine the vertical heat exchanger length for the following conditions: * Heat pump with cooling capacity of 7032 W at 35 o C * Earth temperature, T = 21 o C * Heat pump duty cycle is estimated at 50% run time during warmest summer days * Manufacturer specifications: high 11
12 International Course on GEOTHERMAL HEAT PUMPS temperature limit of 35 o C entering water * Heat pump discharge water will be 5.6 o C warmer than entry * Total heat rejection of the heat pump = 9493 W * In the heating mode the heat pump has a heat absorption value of 7325 W at 7.2 o C * Discharge water will be 3.23 o C cooler than entry * Low temperature limit for entering water is 7.2 o C Design with PVC pipe, concentric pipe configuration. 1. Cooling mode: Find the design water-to-earth temperature difference, T. T = [(35 + ( ))/2] -21 = 16.8 o C From Table 9, read the effective conductance rate for PVC pipe casing with 50% du- Solve for L in equation [2]. ty cycle, U = 4.85 W/ o C/m. L = 9483 W/(4.85 W/ o C/m x 16.8 o C) = 117 m 2. Heating mode: Find design water-to-earth temperature difference, _T. T = (( ) + 7.2)/2 = 15.6 o C Assume that the heat pump will run 12 h in 24 h in coldest weather. The 50% duty cycle value for U then applies. U = 4.85 W/ o C/m. Solve for L in equation [2]. L = 7325 W/(4.85 W/ o C/m x 15.6 o C) = 97 m As this example shows, the heat exchanger length needed is the larger value of 117 m of CONCLUSIONS. There are several methods available for designing geothermal heat pump groundcoupled heat exchanger used in the vertical configuration. Calculation can be done by a simplified ( short method ) equation that will give approximate results, but not take bore hole (loop of PVC heat exchange pipe) for the heat pump in the cooling mode. into consideration the long term of affects of removing and/or rejecting heat to the ground. A more involved ( long way ) method takes these long term effects and the effects of adjacent heat exchangers into consideration. Computer programs are available to look at various alternatives using the more involved calculation procedure. REFERENCES Allan, M., Cementitious Grouts for Geothermal Heat Pump Systems, Transactions, Vol. 22, Geothermal Resources Council, Davis, CA, pp American Refrigeration Institute, Directory of Certified Applied Air Conditioning Products, ARI, Arlington, VA. 12 Braud, H. J., Oliver, J., and H. Klimkowski, Earth-Source Heat Exchanger for Heat Pumps, Geo-Heat Center Quarterly Bulletin, Vol. 11, No. 1, (Summer), pp Claesson, J. And P. Eskilson, Thermal Analysis of Heat Extraction Bore Holes, Lund Institute of
13 Technology, Sweden. Ingersoll, L. R., O. J. Zobel, and A. C. Ingersoll (1954). Heat Conduction, Engineering and Geological Applications, 2 nd edition, McGraw-Hill, NY. Kavanaugh, S. P., Simulation and Experimental Verification of Vertical Ground-Coupled Heat Pump Systems, Ph.D. dissertation, Oklahoma State University, Stillwater, OK. Kavanaugh, S. K., and C. Gilbreath, Cost Containment of Ground Source Heat Pumps, Tennessee Valley Authority, Chattanooga, TN (December), 121 p. Kavanaugh, S. P. And K. Rafferty, Ground-Source Heat Pumps, ASHRAE, Atlanta, Georgia, 167 p. Lund, J. W., 2001a. Geothermal Heat Pumps - An Overview, Geo-Heat Center Quarterly Bulletin, Vol. 22, No. 1, (March), pp Lund, J. W., 2001b. Ground-Source (Geothermal) Heat Pumps, Text Book, European Summer School on Geothermal Energy Applications, University of Oradea, Romania, pp Rafferty, K., A Capital Cost Comparison of Commercial Ground-Source Heat Pumps Systems, Geo-Heat Center Quarterly Bulletin, Vol. 16, No. 2 (February), Geo- Heat Center, Klamath Falls, OR, pp Rafferty, K., An Information Survival Kit for the Prospective Geothermal Heat Pump Owner, Geo-Heat Center, Klamath Falls, OR, 23 p. Rybach, L., and B. Sanner, Ground- Source Heat Pump Systems - the European Experience, Proceedings of the International Summer School - Oregon 1999, Geo- Heat Center, Klamath Falls, OR, pp Sanner, B., Shallow Geothermal Energy, Proceedings of the European Summer School on Geothermal Energy Applications, University of Oradea, Romania, pp Sanner B., Phetteplace, G., and G. Hellström, Introduction to Computer Models for Geothermal Heat Pumps, Proceedings of the International Summer School - Oregon 1999, Geo-Heat Center, Klamath Falls, OR, pp
GSHP Design Recommendations- Residential & Light Commercial
GSHP Design Recommendations- Residential & Light Commercial These residential closed- loop ground source heat pump (a.k.a geothermal or groundcoupled heat pumps) design guidelines were developed in conjunction
GEOTHERMAL HEAT PUMPS - TRENDS AND COMPARISONS - John W. Lund Geo-Heat Center
GEOTHERMAL HEAT PUMPS - TRENDS AND COMPARISONS - John W. Lund Geo-Heat Center Heat pumps are used where geothermal water or ground temperatures are only slightly above normal, generally 50 to 90 o F. Conventional
Closed-Loop Ground-Coupled Heat Pump Systems
The following article was published in ASHRAE Journal, September 2006. Copyright 2006 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes
Basic Design Considerations for Geothermal Heat Pump Systems
Basic Design Considerations for Geothermal Heat Pump Systems 2005 Tri-Service Infrastructure Systems Conference and Exhibition Gary Phetteplace US Army Engineer Research and Development Center Cold Regions
Application Guide AG 31-008. Geothermal Heat Pump. Design Manual. 2002 McQuay International
Application Guide AG 31-008 Geothermal Heat Pump Design Manual 2002 McQuay International Table of Contents Introduction...3 Why are Geothermal Heat Pumps So Effective?...3 Other Benefits...5 Loop Design
How Ground/Water Source Heat Pumps Work
How Ground/Water Source s Work Steve Kavanaugh, Professor Emeritus of Mechanical Engineering, University of Alabama Ground Source s (a.k.a. Geothermal s) are becoming more common as the costs of energy
Geothermal Heat Pumps in Agricultural Applications
Geothermal Heat Pumps in Agricultural Applications Oregon Geothermal Working Group Meeting May 17, 2006 Alternative Farming Center, Johnson County, Tennessee Andrew Chiasson Geo-Heat Center Oregon Institute
GROUND-SOURCE (GEOTHERMAL) HEAT PUMPS
GROUND-SOURCE (GEOTHERMAL) HEAT PUMPS by John W. LUND 1. INTRODUCTION When a geothermal resource temperature falls below the 40-50 C range, it is frequently impractical to use the fluid directly for most
Heating & Cooling Efficiency
Heating & Cooling Efficiency Advantages of Geothermal HVAC Efficiency Keith Swilley Gulf Power Company Why Gulf Power Promotes Energy Efficiency? Customer Satisfaction Education Help Customers Make Smart
Ground Source Heat Pumps The Fundamentals. Southington, Connecticut 860 628 4622 John F. Sima III P.E.
Ground Source Heat Pumps The Fundamentals Southington, Connecticut 860 628 4622 John F. Sima III P.E. Winter/Spring 2010 Ground Source Heat Pumps The Fundamentals TOPICS: Heat Pump Terminology Basic Physics
GEOTHERMAL HEATING AND COOLING INTRODUCTION
GEOTHERMAL HEATING AND COOLING INTRODUCTION Geothermal Heating and Cooling Systems provide space conditioning -- heating, cooling, and humidity control. They may also provide water heating -- either to
Geothermal Heat Pump Systems
Geothermal Heat Pump Systems GeoExchange Technology Curtis J. Klaassen, P.E. Iowa Energy Center Energy Resource Station Geothermal Heat Pump Technology Introduction What is Geothermal Energy? Geothermal
WaterFurnace Explains GEOTHERMAL HEATING & COOLING
WaterFurnace Explains GEOTHERMAL HEATING & COOLING GEOTHERMAL HEATING AND COOLING AN INTRODUCTION WaterFurnace geothermal heating and cooling systems use the clean, renewable energy in your back yard to
AE-1483 Ground-source Heat Pumps. Carl Pedersen Energy Educator
AE-1483 Ground-source Heat Pumps Carl Pedersen Energy Educator A heat pump can be an efficient alternative to a standard home heating system. Moreover, during the cooling season, its function can be reversed,
How a Ground Source Heat Pump Works for a School or College
How a Ground Source Heat Pump Works for a School or College Vertical System Image courtesy of Climate Master 1 Geothermal avoids the need for outdoor equipment..reducing vandalism and liability Image courtesy
Rating Water-Source Heat Pumps Using ARI Standard 320 and ISO Standard 13256-1
Rating Water-Source Heat Pumps Using ARI Standard 320 and ISO Standard 13256-1 W. Vance Payne and Piotr A. Domanski National Institute of Standards and Technology Building and Fire Research Laboratory
Development of Design Guidelines for Hybrid Ground-Coupled Heat Pump Systems
Development of Design Guidelines for Hybrid Ground-Coupled Heat Pump Systems ASHRAE TRP-1384 Scott P. Hackel Under the supervision of Professors Greg Nellis and Sanford Klein and the University of Wisconsin
Zhao et al. 2.2 Experimental Results in Winter Season The analysis given below was based on the data collected from Nov. 2003 to Mar. 15, 2004.
Proceedings World Geothermal Congress 2005 Antalya, Turkey, 24-29 April 2005 A Case Study of Ground Source Heat Pump System in China Jun Zhao, Chuanshan Dai, Xinguo Li, Qiang Zhu and Lixin Li College of
HVAC Efficiency Definitions
HVAC Efficiency Definitions Term page EER - 2 SEER - 3 COP - 4 HSPF - 5 IPLV - 6 John Mix May 2006 Carrier Corporation 1 Energy Efficiency Ratio (EER) The energy efficiency ratio is used to evaluate the
Renewable Heat Pumps. A guide for the technically minded
Renewable Heat Pumps A guide for the technically minded How do heat pumps work? A heat pump is an environmental energy technology that extracts heat from low temperature sources (air, water, ground), upgrades
The ASHRAE HQ Building Can the energy efficiency of the different mechanical systems really be compared? RESIDENTIAL LIGHT COMMERCIAL COMMERCIAL
The ASHRAE HQ Building Can the energy efficiency of the different mechanical systems really be compared? RESIDENTIAL LIGHT COMMERCIAL COMMERCIAL Technical Article April 2013 The ASHRAE HQ Building Can
HOME HEATING USING GEOTHERMAL ENERGY. An introduction to using ground sourced central heating in New Zealand
HOME HEATING USING GEOTHERMAL ENERGY An introduction to using ground sourced central heating in New Zealand Introduction The purpose of this guide is to give the end user the basic information required
OPTIMIZATION OF HYBRID GEOTHERMAL HEAT PUMP SYSTEMS
1 OPTIMIZATION OF HYBRID GEOTHERMAL HEAT PUMP SYSTEMS Scott Hackel, Graduate Research Assistant; Gregory Nellis, Professor; Sanford Klein, Professor; all from the University of Wisconsin Solar Energy Lab,
GEOTHERMAL POWER GENERATION A PRIMER ON LOW-TEMPERATURE, SMALL-SCALE APPLICATIONS
GEOTHERMAL POWER GENERATION A PRIMER ON LOW-TEMPERATURE, SMALL-SCALE APPLICATIONS by Kevin Rafferty Geo-Heat Center January 2000 REALITY CHECK Owners of low-temperature geothermal resources are often interested
Evaporative Cooling System for Aquacultural Production 1
Fact Sheet EES-100 March 1993 Evaporative Cooling System for Aquacultural Production 1 C. D. Baird, R. A. Bucklin, C. A. Watson and F. A. Chapman 2 INTRODUCTION Florida aquaculture sales totaled $54 million
FINAL REPORT LIFE-CYCLE COST STUDY OF A GEOTHERMAL HEAT PUMP SYSTEM BIA OFFICE BLDG., WINNEBAGO, NE
FINAL REPORT LIFE-CYCLE COST STUDY OF A GEOTHERMAL HEAT PUMP SYSTEM BIA OFFICE BLDG., WINNEBAGO, NE February 2006 FINAL REPORT LIFE-CYCLE COST STUDY OF A GEOTHERMAL HEAT PUMP SYSTEM BIA OFFICE BLDG., WINNEBAGO,
How To Use A Water Source Heat Pump
Geothermal Energy Using Water-Source Heat Pumps By VIRSTAR Corporation Geothermal Expertise Since 1978 All information contained herein is the exclusive property of VIRSTAR Corporation, all rights reserved.
A FEASIBILITY STUDY OF A MULTI-SOURCE HYBRID DISTRICT GEOTHERMAL HEAT PUMP SYSTEM
A FEASIBILITY STUDY OF A MULTI-SOURCE HYBRID DISTRICT GEOTHERMAL HEAT PUMP SYSTEM Andrew Chiasson, Geo-Heat Center, Klamath Falls, OR INTRODUCTION Accurate calculation of transient subsurface heat transfer
Designing coaxial ground heat exchangers with a thermally enhanced outer pipe
Raymond et al. Geothermal Energy (2015) 3:7 DOI 10.1186/s40517-015-0027-3 RESEARCH ARTICLE Open Access Designing coaxial ground heat exchangers with a thermally enhanced outer pipe Jasmin Raymond 1*, Serge
Three-years operation experience of a ground source heat pump system in Northern Greece
Energy and Buildings 39 (2007) 328 334 www.elsevier.com/locate/enbuild Three-years operation experience of a ground source heat pump system in Northern Greece A. Michopoulos, D. Bozis, P. Kikidis, K. Papakostas,
Creating Efficient HVAC Systems
Creating Efficient HVAC Systems Heating and Cooling Fundamentals for Commercial Buildings Heating, ventilating, and air conditioning (HVAC) systems account for nearly half of the energy used in a typical
Earth-Coupled Air Conditioning Unit Design Analysis. Abstract
Earth-Coupled Air Conditioning Unit Design Analysis Jassmine Duron, Manuel Monroy, M. A. Rafe Biswas Mechanical Engineering Department The University of Texas at Tyler [email protected], [email protected],
The efficient heat pump
The efficient heat pump KCP&L has worked hard to build one of the best reliability records in the industry and we want to help you make the most of the energy we provide. That s why we offer information
HVAC Applications for PE Pipe
463 Introduction The performance and use characteristics of polyethylene pipe make it an ideal choice for use in certain HVAC Heating, Ventilation, and Air Conditioning applications. Typically, HVAC is
ADVANTAGES OF USING THE HYBRID GEOTHERMAL OPTION
ADVANTAGES OF USING THE HYBRID GEOTHERMAL OPTION J. B. Singh, PE* Gustav Foster, Jr. PE** *J and P Engineers, P.A. 14 Kory Drive Kendall Park, NJ 08824 USA phone: 732-940-7994 fax: 732-940-5528 **Conectiv
Glossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
Optimization of Water - Cooled Chiller Cooling Tower Combinations
Optimization of Water - Cooled Chiller Cooling Tower Combinations by: James W. Furlong & Frank T. Morrison Baltimore Aircoil Company The warm water leaving the chilled water coils is pumped to the evaporator
Solar Thermal TECHNOLOGY. Eric Buchanan Renewable Energy Scientist West Central Research and Outreach Center Wcroc.cfans.umn.edu
Solar Thermal TECHNOLOGY Eric Buchanan Renewable Energy Scientist West Central Research and Outreach Center Wcroc.cfans.umn.edu Solar Energy History Solar Thermal 700 BC Chinese use burning mirrors 1760
Understanding Heating Seasonal Performance Factors for Heat Pumps
Understanding Heating Seasonal Performance Factors for Heat Pumps Paul W. Francisco, University of Illinois, Building Research Council Larry Palmiter and David Baylon, Ecotope, Inc. ABSTRACT The heating
Commercial Earth Energy Systems:
Commercial Earth Energy Systems: A buyer s Guide Natural Resources Canada Ressources naturelles Canada Commercial Earth Energy Systems Buyer s Guide B Preface This publication is distributed for informational
Energy Analysis and Comparison of Advanced Vapour Compression Heat Pump Arrangements
Energy Analysis and Comparison of Advanced Vapour Compression Heat Pump Arrangements Stuart Self 1, Marc Rosen 1, and Bale Reddy 1 1 University of Ontario Institute of Technology, Oshawa, Ontario Abstract
Energy Efficiency Technologies Air Source Heat Pump vs. Ground Source Heat Pump
Vol. 2, No. 2 Journal of Sustainable Development Energy Efficiency Technologies Air Source Heat Pump vs. Ground Source Heat Pump Ruqun Wu OEP Faculty of Land and Environment, The University of Melbourne
Ground-Source Variable Refrigerant Flow Heat Pumps:
Energy Efficiency Factsheet: Ground-Source Variable Refrigerant Flow Heat Pumps Page 1 Ground-Source Variable Refrigerant Flow Heat Pumps: A Solution for Affordable Housing, Assisted Living, Hotels and
Heat transfer analysis of boreholes in vertical ground heat exchangers
International Journal of Heat and Mass Transfer 46 (2003) 4467 4481 www.elsevier.com/locate/ijhmt Heat transfer analysis of boreholes in vertical ground heat exchangers Heyi Zeng, Nairen Diao, Zhaohong
Determination of Thermal Conductivity of Coarse and Fine Sand Soils
Proceedings World Geothermal Congress Bali, Indonesia, - April Determination of Thermal Conductivity of Coarse and Fine Sand Soils Indra Noer Hamdhan 1 and Barry G. Clarke 2 1 Bandung National of Institute
Design and Implementation of Geothermal Systems for Heating and Air Conditioning
, 23-25 October, 2013, San Francisco, USA Design and Implementation of Geothermal Systems for Heating and Air Conditioning M. Fathizadeh, Daniel Seim Abstract--Geothermal is the Earth s thermal energy.
Contents. 1 Introduction systems and applications 3 1.1 Types of system 3 1.2 Applications 4 1.3 Potential benefits 4. 2 General design 6
Contents 1 Introduction systems and applications 3 1.1 Types of system 3 1.2 Applications 4 1.3 Potential benefits 4 2 General design 6 3 Ground heat exchanger 7 3.1 Types of ground heat exchanger 7 3.2
Chapter 3.4: HVAC & Refrigeration System
Chapter 3.4: HVAC & Refrigeration System Part I: Objective type questions and answers 1. One ton of refrigeration (TR) is equal to. a) Kcal/h b) 3.51 kw c) 120oo BTU/h d) all 2. The driving force for refrigeration
Design of a Heat Pump Assisted Solar Thermal System
Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2014 Design of a Heat Pump Assisted Solar Thermal System Kyle G. Krockenberger Purdue
Geothermal Energy. How it Works
Geothermal Energy The Ocean Pines Association Board of Directors asked the OPA Environment and Natural Assets Advisory Committee (ENAAC) to provide information about how geothermal energy could be useful
Calculating System Flow Requirements
Calculating System Flow Requirements To select a pump, we need to know the flow rate (the amount of fluid to be pumped) and the system resistance or head. In the U.S., flow rates are given in gallons per
J O U R N A L. Energy Performance for. Proper Specification of Air Terminal Units Future Climate Impacts on Building Design
Copyright 24, American Society of Heating, Refrigerating & Air-Conditioning Engineers, Inc., 79 Tullie Circle NE, Atlanta, GA. 3329. Reprinted by permission from the September 24 Issue of ASHRAE Journal
Geothermal Heat Pumps: A Pathway to Zero Net Energy (ZNE) for Schools, Homes and Businesses
Lisa Meline, P.E. Meline Engineering Corp. [email protected] Office: 916.366.3458 Geothermal Heat Pumps: A Pathway to Zero Net Energy (ZNE) for Schools, Homes and Businesses Session C: Institutional Applications
Ground Source Heat Pumps versus High Efficiency Natural Gas Furnaces in Alberta
Ground Source Heat Pumps versus High Efficiency Natural Gas Furnaces in Alberta Jerry Shaw Ph D, P Ag February 2, 2003 Ground Source Heat Pumps (GSHPs) have been used for heating and cooling buildings
Optimization of a Hybrid Ground Source Heat Pump using the Response Surface Method
Optimization of a Hybrid Ground Source Heat Pump using the Response Surface Method Honghee Park 1, Wonuk Kim 1, Joo Seoung Lee 1 and Yongchan Kim 2* 1 Graduate School of Division of Mechanical Engineering,
GEOTHERMAL HEATING APPLICATIONS FOR RESIDENTIAL HOMES
GEOTHERMAL HEATING APPLICATIONS FOR RESIDENTIAL HOMES GAGNON HEATING & AIR CONDITIONING RT. 302, P.O. BOX 814 BRIDGTON, ME 04009 207-647-8782 mainegeothermal.com GOODWIN WELL & WATER, INC. 2282 AUBURN
GROUND SOURCE HEAT PUMPS. An Overview
GROUND SOURCE HEAT PUMPS An Overview PRESENTERS: CHAD MARTIN, PE, / EASTERN REGIONAL MANAGER / GEOTHERMAL RESOURCE TECHNOLOGIES CHRIS EDMONDSON / CEO / JAMES M. PLEASANTS COMPANY ADAM SPACH, PE, LEED AP
Exploitation Tests of Borehole Heat Exchangers in the Laboratory of Renewable Energy Sources in Miekinia Poland
Proceedings World Geothermal Congress 2015 Melbourne, Australia, 19-25 April 2015 Exploitation Tests of Borehole Heat Exchangers in the Laboratory of Renewable Energy Sources in Miekinia Poland Jaroslaw
Residential Ground-Source Heat Pumps: In-Field System Performance and Energy Modeling
GRC Transactions, Vol. 34, 2010 Residential Ground-Source Heat Pumps: In-Field System Performance and Energy Modeling Srikanth Puttagunta, Robb A. Aldrich, Douglas Owens, and Pallavi Mantha Steven Winter
Geothermal Heat Pump Systems: From Basics to Hybrids
Geothermal Heat Pump Systems: From Basics to Hybrids January 17, 2013 Scott Hackel Energy Center of Wisconsin www.ecw.org/hybrid Today s discussion The basics of geothermal The hybrid approach, our recent
District Cooling Plant : Refrigeration Plant Simulation
1 District Cooling Plant : Refrigeration Plant Simulation Dr. Chirdpun Vitooraporn Department of Mechanical Engineering Chulalongkorn University Phayathai Rd., Patumwan, Bangkok, 13. THAILAND E-mail: [email protected]
A Feasibility of Geothermal Cooling in Middle East
A Feasibility of Geothermal Cooling in Middle East ASAD SALEM & HAFIZ ELSIR MIRGHANI HASHIM Department of Mechanical Engineering Rochester Institute of Technology Rochester Institute of Technology, Dubai
Federation of European Heating, Ventilation and Air-conditioning Associations
Federation of European Heating, Ventilation and Air-conditioning Associations Address: Rue Washington 40 1050 Brussels Belgium www.rehva.eu [email protected] Tel: +32 2 514 11 71 Fax: +32 2 512 90 62 REHVA
GEOTHERMAL HEAT PUMP SYSTEMS ARE RED HOT BUT ARE THEY REALLY GREEN?
GEOTHERMAL HEAT PUMP SYSTEMS ARE RED HOT BUT ARE THEY REALLY GREEN? Richard C. Niess 1 Gilbert & Associates / Apogee Interactive, Inc., Gloucester Point, Virginia 23062 Phone & Fax (804) 642 0400 ABSTRACT
RESEARCH HIGHLIGHT. Performance Assessment of a Cold-Climate Air Source Heat Pump
RESEARCH HIGHLIGHT December 2014 Technical Series 14-102 Performance Assessment of a Cold-Climate Air Source Heat Pump INTRODUCTION Most Canadians are familiar with air source heat pump technology in the
Heating, Ventilation & Air Conditioning Equipment
FinAnswer Express Wyoming Incentive Catalog Effective as of October 1, 2011 Heating, Ventilation & Air Conditioning Equipment Rocky Mountain Power provides incentives for many types of energy efficient
Heat pumps: better by nature
Heat pumps: better by nature For office buildings, hospitals, swimming pools, Heat, more than 80% of our energy consumption The burning of fossil fuels to meet our energy demand is resulting in the emission
Yijun Gao, Wei Wu, Zongwei Han, Xianting Li *
Study on the performance of air conditioning system combining heat pipe and vapor compression based on ground source energy-bus for commercial buildings in north China Yijun Gao, Wei Wu, Zongwei Han, Xianting
ENERGY PILE AND HEAT PUMP MODELING IN WHOLE BUILDING SIMULATION MODEL
ENERGY PILE AND HEAT PUMP MODELING IN WHOLE BUILDING SIMULATION MODEL Jevgeni Fadejev, Jarek Kurnitski Faculty of Civil Engineering, Tallinn University of Technology, Tallinn, Estonia [email protected];
Design Considerations for Underfloor Heating Systems. What is Frost Heave Protection?
Design Considerations for Underfloor Heating Systems Daniel Dettmers Industrial Refrigeration Consortium University of Wisconsin-Madison What is Frost Heave Protection? As soil drops below freezing, moisture
ENERGY BALANCE OF LOW ENERGY HOUSE WITH GHPS IN HOKKAIDO
ENERGY BALANCE OF LOW ENERGY HOUSE WITH GHPS IN HOKKAIDO Yasuhiro Hamada, Kiyoshi Ochifuji, Makoto Nakamura and Katsunori Nagano Division of Urban and Environmental Engineering Graduate School of Engineering,
9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS
9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS 9.1 Introduction Air conditioning and refrigeration consume significant amount of energy in buildings and in process industries. The energy consumed in
Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance
Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory
Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory Title: Comparison of energy efficiency between variable refrigerant flow systems and ground source heat pump systems Author:
AHRI Standard 325 (Formerly ARI Standard 325) 1998 Standard for Ground Water-Source Heat Pumps
AHRI Standard 325 (Formerly ARI Standard 325) 1998 Standard for Ground Water-Source Heat Pumps IMPORTANT SAFETY RECOMMENDATIONS It is strongly recommended that the product be designed, constructed, assembled
How a Ground Source Heat Pump Works for Commercial Buildings
How a Ground Source Heat Pump Works for Commercial Buildings 1 Geothermal avoids the need for outdoor equipment..reducing vandalism and liability Image courtesy of Climate Master 2 Why geothermal heat
HVACPowDen.xls An Easy-to-Use Tool for Recognizing Energy Efficient Buildings and HVAC Systems
HVACPowDen.xls An Easy-to-Use Tool for Recognizing Energy Efficient Buildings and HVAC Systems Fundamental Principles of Environmentally Responsible, Energy Efficient Buildings 1. Energy efficiency is
HVAC Basic Science - System Capacity
HVAC Basic Science - System Capacity Btu/hour, btu/h, b/h, btuh. btu?? 1 MBH = 1000 btu/hour 1 KBH = 1000 btu/hour 1 ton of cooling= 12,000 btu/hour 1 watt = 3.414 btu/hour 1 kilowatt = 1000 watts = 3,414
6 18 A steam power plant receives heat from a furnace at a rate of 280 GJ/h. Heat losses to the surrounding air from the steam as it passes through
Thermo 1 (MEP 261) Thermodynamics An Engineering Approach Yunus A. Cengel & Michael A. Boles 7 th Edition, McGraw-Hill Companies, ISBN-978-0-07-352932-5, 2008 Sheet 6:Chapter 6 6 17 A 600-MW steam power
GEOTHERMAL (GROUND-SOURCE) HEAT PUMPS A WORLD OVERVIEW
GEOTHERMAL (GROUND-SOURCE) HEAT PUMPS A WORLD OVERVIEW J. Lund 1, B. Sanner 2, L. Rybach 3, R. Curtis 4, G. Hellström 5 1 Geo-Heat Center, Oregon Institute of Technology, Klamath Falls, Oregon, USA 2 Institute
A heat pump system with a latent heat storage utilizing seawater installed in an aquarium
Energy and Buildings xxx (2005) xxx xxx www.elsevier.com/locate/enbuild A heat pump system with a latent heat storage utilizing seawater installed in an aquarium Satoru Okamoto * Department of Mathematics
Hybrid (Dual Fuel) - Gas Heat and Air Source Heat Pump
s.doty 10-2014 White Paper #30 Hybrid (Dual Fuel) - Gas Heat and Air Source Heat Pump System Switches Fuels Automatically for Economy. What is an Air-Source Heat Pump? A heat pump is a modified air conditioning
Impacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions
Impacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions M. Liu, Y. Zhu, D. E. Claridge Energy Systems Laboratory Texas A&M University Ed. White Energy Management Operation
Thermal Coupling Of Cooling and Heating Systems
This article was published in ASHRAE Journal, February 2011. Copyright 2011 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not