A FEASIBILITY STUDY OF A MULTI-SOURCE HYBRID DISTRICT GEOTHERMAL HEAT PUMP SYSTEM
|
|
|
- Shannon Alban Manning
- 10 years ago
- Views:
Transcription
1 A FEASIBILITY STUDY OF A MULTI-SOURCE HYBRID DISTRICT GEOTHERMAL HEAT PUMP SYSTEM Andrew Chiasson, Geo-Heat Center, Klamath Falls, OR INTRODUCTION Accurate calculation of transient subsurface heat transfer is critically important in sizing ground heat exchangers (GHX) in geothermal heat pump (GHP) systems. The size of the GHX is a complicated function of a number of design variables that include the thermal properties of the subsurface, and the dynamics of short- and long-term building heating and cooling loads. So-called hybrid GHPs have received considerable attention in recent years (eg., Hackel, 2008) because they have been show to significantly improve the economics and energy use of GHP systems. Hybrid GHP systems couple a supplemental heat extraction or rejection subsystem to a conventional GHP system to handle some portion of the building or the ground loads, and as such, permit the use of a smaller, lower-cost GHX. Hybrid GHPs are especially effective in applications that have large peak loads and/or have highly imbalanced loads over the year (i.e. heavily heating or heavily cooling-dominated buildings). Hybrid GHP systems are more complex in their design than conventional GHP systems due to the transient nature of the supplemental component. Further, recent research on hybrid GHPs identifies more than one method to design a hybrid GHP. For example, Chiasson and Yavuzturk (2009a, 2009b) describe a method for designing hybrid GHP systems based on annual ground load balancing. Xu (2007) and Hackel et al. (2009) describe hybrid GHP system design based on lowest life-cycle cost, while Kavanaugh (1998) describes a method based on designing the GHX for the nondominant load, and the hybrid component for the balance of the load. Cullin and Spitler (2010) describe yet another method based on minimizing first cost of the system, while designing the GHX to supply both the minimum and maximum design entering heat pump fluid temperature over the life-cycle of the system. Recent research on hybrid GHP systems highlights the complexity of their design. Published research mainly deals with single building applications with one hybrid component. Much less research, if any, has dealt with hybrid GHP Figure 1. Concept schematic of a multi-source hybrid GHP system. GHC BULLETIN, MAY
2 systems with more than one hybrid component in a district application. The objective of this article, therefore, is to describe a system simulation approach to examine the feasibility of a multi-source hybrid GHP system for an actual proposed district heating application in a cold climate, where conventional GHP systems were deemed to be infeasible and impractical. THE MULTI-SOURCE HYBRID CONCEPT Here, the term multi-source hybrid is used to describe a hybrid GHP system with multiple heat sources. The concept is shown schematically in Figure 1 for a cold climate with very little to no cooling load. The basic design concept shown in Figure 1 takes advantage of a modular plug-and-play structure such that heat sources or sinks can be added as practical. The concept is centered around a common low-temperature supply pipeline that serves to distribute energy in the form of an aqueous antifreeze solution to the sources and sinks. A lowtemperature distribution loop was conceived in this design so that lower-grade heat sources could be rejected to the loop. A lower temperature fluid distribution loop typically requires larger diameter pipe relative to that used in a hightemperature loop, but the added advantage of larger pipe diameter means more fluid volume in the loop and correspondingly more thermal mass (or thermal inertia) of fluid in the pipe, which helps to damp large fluid temperature excursions during peak load times. Amplification of the lowtemperature source loop to useful temperatures for space heating is accomplished with water-to-air or water-to-water heat pumps distributed throughout the district in the buildings they serve. The minimum heat pump supply temperature of 0 C was chosen because of the low ground temperatures in cold climates. An integral component of the district energy system is the ground heat exchanger (GHX), which could consist of one central array or multiple de-centralized arrays. The GHX acts to provide a baseload heat source for heat pumps, supplemented by a peaking boiler during extreme cold periods. In addition, the GHX acts as a short-term and longterm (i.e., seasonal) storage medium for various waste and other available heat sources, which help to improve the GHX thermal performance during times when heat is needed. The waste and other heat sources considered in this study were limited to solar energy and heat recovered from sanitary sewers. As noted in Figure 1, general options exist for other heat sources and sinks, which could conceivably include heat rejection from refrigeration systems (i.e., ice rinks) or any other source deemed practical. This box could also represent another modular GHX as the district system expands and/or additional GHX s are incorporated at de-centralized locations. Each of the individual components of the district GHP systems are described in further detail below. THE GROUND HEAT EXCHANGER (GHX) Two types of loads are important in sizing a GHX to meet intended loads: (i) the peak hour load and (ii) the annual load. Sizing a GHX therefore differs from sizing conventional heating and cooling equipment (i.e., boilers and chillers) because the earth does not respond instantaneously to heat rejected to and extracted from it; long-term temperature changes take place in the underground GHX storage volume if annual loads are not balanced (i.e., the same amount of energy added approximately equals the amount taken out). When annual loads are not balanced, the GHX must be increased in size to accommodate long-term underground temperature changes over years and decades. Annual loads are sometimes naturally balanced by a distinct heating and cooling season, but this is not the case in a sub-arctic environment, and the size of the GHX to meet all of the intended loads is excessive and unnecessary, which led to this concept of a hybrid system. Supplemental systems are used to offset peak loads and annual loads on the ground. The GHX design consists of a closed network of vertical boreholes drilled to approximately 100 m deep. Each borehole would be completed with a HDPE plastic u-tube heat exchanger grouted in place with standard bentonitebased grout. The heat transfer fluid consists of an aqueous solution of 20% propylene glycol. GEOTHERMAL HEAT PUMPS The district energy concept presented here involves heat pumps distributed throughout the district, located in the buildings they serve. GHPs would simply replace conventional furnaces or boilers in buildings, and would be installed during construction of each individual building. Individual heat pumps would be sized to meet the intended loads of the building; the hybrid components are only designed to assist the GHX in providing source energy to the heat pumps. Therefore, no supplemental heating is necessary within individual buildings, and emergency back-up heating in buildings would be up to the preference of the individual building owner. The concept of providing low-temperature source water to customer buildings allows for customer flexibility to choose their preferred type of heating system, either ducted forced air or radiant floor heating. PEAKING BOILER For consistent delivery temperature of source fluid from which thermal energy can be extracted by heat pumps, a peaking boiler is added to the district system concept. A peaking boiler system serves to offset peak loads on the ground, thus reducing unnecessary GHX size and cost. The optimum size of the boiler depends on the economic tradeoff between the avoided GHX cost and the annual operating cost of the boiler. The fuel source for the boiler could be natural gas, biomass, heating oil, or combined fuel. The design concept involves only operating the boiler during times when the fluid temperature exiting the GHX falls below 0 C, which will occur during peak heating load hours. The boiler will therefore contribute very little to 10 GHC BULLETIN, MAY 2011
3 operational costs. The boiler operates on a temperature control, set to maintain a minimum supply temperature of 0 C to the district loop. An additional benefit of a peaking boiler system is that it could be used as a backup in the event of sewage heat recovery interruption (sewer heat exchanger maintenance) or GHX maintenance. SOLAR THERMAL RECHARGE AND SEWER HEAT RECOVERY The role of solar thermal and sewer heat recovery is to offset annually imbalanced loads on the ground by recharging the GHX with thermal energy. Balancing ground loads allows for further reductions in the GHX size and cost. As with a peaking system, the optimum size of the solar collector array and sewer heat recovery system depends on the economic trade-off between the avoided GHX cost and the capital and operating cost of the load balancing systems. As shown in the district schematic concept (Figure 1), solar energy would be the first energy source added to the district loop, mainly because the most strategic location for solar collector location is on customer roof tops. Solar energy would therefore be added to the district loop immediately downstream of the heat pumps. This would be accomplished with existing off-the-shelf, flat-plate solar technology. Solar collectors are typically operated using a differential set point control, meaning that the collector must be warmer than the district loop by a set amount (typically at least 5 C) for useful heat transfer to occur. Thus, useful heat can be collected beginning at low solar collector temperatures (i.e., less than 5 C). Similar to the solar recharging concept, sewer heat would be added to the loop at a strategic location as the fluid returns to the GHX. This allows heat to be collected at any time during year and stored underground in the GHX to improve its thermal performance. Useful heat could only be transferred to the district loop when the wastewater temperature exceeds the district loop temperature METHOD OF FEASIBILITY ANALYSIS Heating Load The hybrid district GHP system described here is intended to serve approximately 124,000 m2 of mixed residential and commercial floor space in a new subdivision in Whitehorse, Yukon, Canada. Weather conditions at the subject site are sub-arctic, with a heating design temperature of -37oF, and 12,447 of-day (6,915 C-day) heating degree days. The underground earth temperature is approximately 3 C (37.4oF). The peak heating load is estimated at 5,840 kw (19.9 million Btu/hr), and the annual heating energy load is estimated at 9.4 MWh. Parametric Analysis with Optimization. Parametric analysis with optimization, in general, refers to a systematic investigation aimed at finding the maximum or minimum value of a particular parameter of interest. Here, GHC BULLETIN, MAY 2011 the optimization procedure seeks the minimum life-cycle cost of the hybrid GHP district energy system. An optimization analysis is needed in hybrid GHP system design because a multitude of combinations of hybrid component sizes is possible (i.e., combinations of GHX size, number of solar collectors, sewer heat recovery, and peaking boiler size). There is a trade-off in cost savings in reducing the size of a GHX in favor of adding initial and operating cost of a hybrid component. Therefore, the objective of the optimization analysis presented here is to find workable combinations of hybrid GHP system components (i.e., the GHX, solar collectors, sewer heat recovery, and peaking boiler) that result in minimum life-cycle cost. It is emphasized that the goal of this optimization analysis is not to find the precise combination of hybrid system component sizes, but to provide a first approximation of whether feasible combinations exist. Precise sizing of hybrid components is an analysis left for later stages of the design process. The methodology in conducting the optimization analysis involved examining numerous combinations of hybrid system component sizes. The thermal performance of 25 hybrid GHP cases with various combinations of GHX size, number of solar collectors, and peaking boiler fraction were simulated with and without sewer heat recovery. Therefore, a total number of 50 combinations were examined. Hybrid GHP energy simulations were conducted using TRNSYS (SEL, 2000), which is a state-of-the-art transient energy simulation software tool. Computer models were configured similar to the concept diagram shown in Figure 1. Once constructed, the use of TRNSYS computer models allowed examination of several what-if alternatives. The GHX configuration and thermal properties were modeled as described above. Glazed flat plate solar thermal collectors were modeled with properties similar to those described by Numerical Logics (2008). Solar collector glycol-based loops were separated from the main district loop with isolation heat exchangers. The peaking boiler was controlled to maintain a minimum fluid supply temperature to building heat pumps of 0 C. The sewer heat recovery heat exchanger was modeled with a heat exchanger effectiveness of 0.80, controlled to shut off when the wastewater temperature dropped to 2 C. Energy simulations were conducted for fifty years. LIFE-CYCLE ECONOMIC ANALYSIS Fifty-year life-cycle cost analyses were conducted for each parametric case using the energy simulation results, along with capital cost and other economic data. The rate-of-return (ROR) method was used as the economic indicator to evaluate options. The ROR represents the true interest yield provided by the project equity over its life before income tax. It is calculated using the pre-tax yearly cash flows and the project life. It is also referred to as the internal rate of return (IRR). It is calculated by finding the discount rate that causes the net present value of the equity to be equal to zero. Therefore, it is not necessary to establish the discount rate of an organization to use this indicator, as it is for use of the net 11
4 present value method. The ROR obtained is specific to the project and applies to all investors in the project. Capital costs assumptions in the economic analysis are as follows: GHX costs are estimated at $100/m, based on professional judgement, discussions with installers, and lack of local contractors, Solar collector costs are based on a correlating equation from Hackel (2008), where solar collector array cost = $5096(0.135N ), where N is the number of glazed flat plate collectors, Peaking boiler costs are based on a correlating equation from Hackel (2008), where boiler cost = $3825( f f ) for f<=31.2 or boiler bost = $3825(0.118f ) for f>31.3, where f = ratio of boiler size to a nominal reference 122 MBH boiler, Distribution piping system = $600/m. This estimated cost include piping material, installation, pumping system, and customer connections expressed per meter of street length. Street lengths are multiplied by 10% to account for branch lines to customer buildings. Piping costs are for preinsulated HDPE pipe per vendor quote. The total distribution system cost is estimated from NRCan (2008), at a proportion of 45% for pipe material, 45% for installation and connections, and 10% for the pumping system, Mechanical building cost = $1,600/m2, Sewer heat recovery cost = $0.78 million, Engineering and design fees = 10% of capital cost, Arctic cost multiplier = 1.3, Contingency = 30%, and Grants and incentives: none. Annual operating and maintenance costs assumptions in the economic analysis are as follows: Maintenance costs on the distribution system are estimated at 1% of capital cost, Table 1. Additional Assumptions in Economic Analysis. District system administrative, management, and billing costs are estimated at $1/ m2of floor space, Boiler system maintenance costs are based on a correlating equation from Hackel (2008), where boiler maintenance cost = $759( f f ) for f<=11, or boiler maintenance cost $759(0.0196f ) for f>11, where f = ratio of boiler size to a nominal reference 122 MBH boiler, and Sewer heat recovery system maintenance costs are estimated at $1,000. Additional assumptions in the economic analysis are shown in Table 1. DISCUSSION OF RESULTS One challenge in the examination of feasibility of a multisource hybrid GHP system is visualizing the numerous options. Here, the most economically favorable general combination of hybrid component sizes was found graphically by constructing optimization plots. The plots display the 50-yr rate of return as a function of GHX size, number of solar collectors, and annual energy fraction contributed by a peaking system (Figure 2). Optimization plots were constructed for cases with sewer heat recovery and for cases without sewer heat recovery. Prior to discussion of the results, some explanation is necessary for interpretation of the plots. Contour lines represent the number of 100-m deep GHX boreholes required to provide all thermal source energy to the district heat pumps with assistance from various numbers of solar collectors (shown on the bottom or x-axis) and annual fractions of energy from a peaking boiler system (shown on the left axis or y-axis). Therefore, the lower left-hand corner of each plot represents the case of a GHX providing energy to heat pumps with no solar or boiler hybrid assistance. The annual fraction of energy provided by a boiler system on the left or y-axis is expressed relative to the total annual building heating load. Therefore, the maximum amount of annual Boiler life expectancy 25 yrs. Estimate. With proper maintenance. Sewer HX life expectancy 15 yrs. Per manufacturer. Fossil fuel combustion efficiency 80% For peaking boiler and fuel oil furnace base case. Fuel oil rates (residential) $1/L Based on Yukon Energy price tracking. Fuel oil rates (commercial) $0.8/L Based on Yukon Energy price tracking. Blended electricity rate $0.13/kWh Based on current Yukon Electric schedule. Commercial Electric Demand Charge $7.3/kW Based on current Yukon Electric schedule. Annual inflation rate 2% Typical assumption. Annual fuel oil inflation rate 4% Conservative. Actual inflation rate ~ 7%. Annual electricity inflation rate 2% Conservative. Actual inflation rate over last 10 years is close to 0%. District system income is presumed to be based on energy sales to building owners (customers). The energy charge to customers is based on cost savings of operating geothermal heat pumps over the conventional choice of fuel oil. 12 GHC BULLETIN, MAY 2011
5 energy a boiler could supply, even with no GHX, is less than 100% due to heat pump thermodynamic principles. The source-side energy of a heat pump in heating mode is less than the load side energy by a factor equal to (COP-1)/COP. Finally, the colored areas of the plots represent the ROR of the particular combination of hybrid components. A ROR color legend is shown to the right of the optimization plot. A non-hybrid GHX (i.e., one with no assistance from hybrid components) sized to provide all of the thermal energy to heat pumps in the district buildings with no sewer heat recovery (i.e., the lower left-hand corner of Figure 2) would require approximately 6, m deep boreholes and occupy a footprint area of about 65 ha, exceeding the land area available for potential drilling. The capital cost of a non-hybrid district GHP system is approximately $80 million with a 50-year ROR of about 1.2%. With the inclusion of sewer heat recovery as the only hybrid component, the GHX size reduces to approximately 5, m deep boreholes, occupying a footprint area of about 56 ha. The reduction in the GHX size is due to extraction and underground storage of thermal energy from wastewater. The savings in GHX cost, with the addition of sewer heat recovery infrastructure, results in a lower overall capital cost of $71 million and a higher 50-year ROR of about 1.6%, relative to a non-hybrid district GHP system. The optimization analysis reveals that the capital cost and ROR can be significantly improved with the integration of a solar collector array and peaking boiler system. The levelling off of the borehole curves beyond about 3,000 to 5,000 solar collectors means that there is diminishing benefit for the added cost of solar collectors exceeding this amount. The near optimum ROR with no sewer heat recovery is about 7.2% with a reduced GHX of m deep boreholes, 3,000 solar thermal collectors, and a peaking boiler system that supplies only 9% of the annual heating load. The reduced GHX size would occupy a footprint area of about 2.5 ha. The capital cost of this case is about $15.2 million. The near optimum ROR with sewer heat recovery is about 6.7% with a reduced GHX of m deep boreholes, 3,000 solar thermal collectors, and a peaking boiler system that supplies only 1% of the annual heating load. The reduced GHX size would occupy a footprint area of about 5 ha. The capital cost of this case is about $18.8 million. This feasibility study has used a number of cost assumptions, typical at an early concept stage of a project, and a sensitivity analysis gives some insight into the effect of major cost items on the computed ROR. A sensitivity analysis is a standard method to vary input parameters to a computation individually and in a systematic way, to see the relative effect on the output (in this case ROR%). A sensitivity Figure 2. Optimization plot showing investment rate of return for number of GHX boreholes as a function of number of solar collectors, and average annual fraction of energy provided by a peaking boiler system. GHC BULLETIN, MAY
6 analysis was conducted on the input parameters in order to quantify uncertainty in the cost estimates. Cost items of the hybrid GHP district system were varied from -50% to +50% of the assumptions used to calculate the ROR. The cost items varied included: annual fuel oil escalation rate, electricity escalation rate, GHX cost, solar thermal collector array cost, piping/distribution network cost, boiler costs, and sewer heat recovery system cost. The results of the sensitivity analysis are shown in Figure 3. Rate of Return 10.0% 9.0% 8.0% 7.0% 6.0% 5.0% 4.0% 3.0% Scenario 3(a) Sensitivity of Major Cost Items on ROR Analysis 50% 40% 30% 20% 10% 0% 10% 20% 30% 40% 50% Fuel Oil Escalation Rate Ground Heat Exchanger Solar Collectors Relative Change in Cost Item Electricity Escalation Rate Piping/Distribution System Boiler Figure 3. Sensitivity of major cost items on 50-year rate of return. A review of Figure 3 reveals that the most sensitive cost item on the 50-year ROR of the hybrid GHP district system is the annual fuel oil escalation rate. The fuel oil price was used to project energy revenues from the district system, and deviation from this assumption affects the ROR. If the annual fuel oil escalation rate were to increase by 50% (i.e., closer to what it actually has been over the past 10 years), the ROR increases to 9 to 10%. On the other hand, if the annual fuel oil escalation were to decrease by 50%, the ROR would decrease to 3 to 4%. Sensitivity of the ROR is next most sensitive to the cost of the piping/distribution system. A 50% decrease in the piping/ distribution system cost increases the ROR to 8 to 9%. A 50% increase in the piping/distribution system cost decreases the ROR to 5.7 to 6%. The ROR is not significantly sensitive to the GHX cost, solar collector array cost, or the annual electricity escalation rate. A ±50% change in these cost items changes the ROR by less than 0.7%. The ROR is relatively insensitive to boiler costs and sewer heat recovery system cost CONCLUSIONS This paper has presented a method of analyzing the practicality and feasibility of a multi-source hybrid geothermal heat pump system in a sub-arctic climate. This work has had two main outcomes: (i) without a system simulation approach, feasible design of a multi-source hybrid GHP system is extremely difficult to complete due to numerous transient design variables, and (ii) in an impractical situation for a conventional GHP system, practical and feasible designs can be found for multi-source hybrid GHP systems, where the GHX is used as a thermal storage medium. REFERENCES Chiasson, A.D., and Yavuzturk, C., 2009a, A design tool for hybrid geothermal heat pump systems in heating-dominated buildings, ASHRAE Transactions 115(2): Chiasson, A.D., and Yavuzturk, C., 2009b, A design tool for hybrid geothermal heat pump systems in cooling-dominated buildings, ASHRAE Transactions 115(2): Cullin, J and Spitler, J.D., 2010, Comparison of Simulation-based Design Procedures for Hybrid Ground Source Heat Pump Systems, Proceedings of the 8th International Conference on System Simulation in Buildings Liege, Belgium. Hackel, S, 2008, Development of Design Guidelines for Hybrid Ground-Coupled Heat Pump Systems. ASHRAE Technical Research Project 1384, American Society of Heating, Refrigerating, and Air Conditioning Engineers (ASHRAE), Atlanta, GA. Hackel, S., Nellis, G. and Klein, S., 2009, Optimization of cooling-dominated hybrid ground-coupled heat pump systems, ASHRAE Transactions 115(1): Kavanaugh, S.P., 1998, A design method for hybrid groundsource heat pumps, ASHRAE Transactions 104(2): 691:698. Numerical Logics, Inc., 2008, Solar Domestic Hot Water System Sizing for Whitehorse, YT and Dawson, YT, Waterloo, ON. SEL, 2000, TRNSYS, A Transient Systems Simulation Program, Version 15. Solar Engineering Laboratory (SEL), University of Wisconsin-Madison, Madison, Wisconsin, USA. Xu, X. 2007, Simulation and optimal control of hybrid ground source heat pump systems, Ph.D. Thesis, Oklahoma State University, Stillwater, Oklahoma. 14 GHC BULLETIN, MAY 2011
Optimization of a Hybrid Ground Source Heat Pump using the Response Surface Method
Optimization of a Hybrid Ground Source Heat Pump using the Response Surface Method Honghee Park 1, Wonuk Kim 1, Joo Seoung Lee 1 and Yongchan Kim 2* 1 Graduate School of Division of Mechanical Engineering,
Development of Design Guidelines for Hybrid Ground-Coupled Heat Pump Systems
Development of Design Guidelines for Hybrid Ground-Coupled Heat Pump Systems ASHRAE TRP-1384 Scott P. Hackel Under the supervision of Professors Greg Nellis and Sanford Klein and the University of Wisconsin
Geothermal Heat Pumps in Agricultural Applications
Geothermal Heat Pumps in Agricultural Applications Oregon Geothermal Working Group Meeting May 17, 2006 Alternative Farming Center, Johnson County, Tennessee Andrew Chiasson Geo-Heat Center Oregon Institute
Closed-Loop Ground-Coupled Heat Pump Systems
The following article was published in ASHRAE Journal, September 2006. Copyright 2006 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes
OPTIMIZATION OF HYBRID GEOTHERMAL HEAT PUMP SYSTEMS
1 OPTIMIZATION OF HYBRID GEOTHERMAL HEAT PUMP SYSTEMS Scott Hackel, Graduate Research Assistant; Gregory Nellis, Professor; Sanford Klein, Professor; all from the University of Wisconsin Solar Energy Lab,
FINAL REPORT LIFE-CYCLE COST STUDY OF A GEOTHERMAL HEAT PUMP SYSTEM BIA OFFICE BLDG., WINNEBAGO, NE
FINAL REPORT LIFE-CYCLE COST STUDY OF A GEOTHERMAL HEAT PUMP SYSTEM BIA OFFICE BLDG., WINNEBAGO, NE February 2006 FINAL REPORT LIFE-CYCLE COST STUDY OF A GEOTHERMAL HEAT PUMP SYSTEM BIA OFFICE BLDG., WINNEBAGO,
Geothermal Heat Pump Systems: From Basics to Hybrids
Geothermal Heat Pump Systems: From Basics to Hybrids January 17, 2013 Scott Hackel Energy Center of Wisconsin www.ecw.org/hybrid Today s discussion The basics of geothermal The hybrid approach, our recent
GEOTHERMAL HEAT PUMPS - TRENDS AND COMPARISONS - John W. Lund Geo-Heat Center
GEOTHERMAL HEAT PUMPS - TRENDS AND COMPARISONS - John W. Lund Geo-Heat Center Heat pumps are used where geothermal water or ground temperatures are only slightly above normal, generally 50 to 90 o F. Conventional
Basic Design Considerations for Geothermal Heat Pump Systems
Basic Design Considerations for Geothermal Heat Pump Systems 2005 Tri-Service Infrastructure Systems Conference and Exhibition Gary Phetteplace US Army Engineer Research and Development Center Cold Regions
Ground Source Heat Pumps The Fundamentals. Southington, Connecticut 860 628 4622 John F. Sima III P.E.
Ground Source Heat Pumps The Fundamentals Southington, Connecticut 860 628 4622 John F. Sima III P.E. Winter/Spring 2010 Ground Source Heat Pumps The Fundamentals TOPICS: Heat Pump Terminology Basic Physics
Drake Landing Solar Community
www.dlsc.ca Innovation. Drake Landing Solar Community The Drake Landing Solar Community (DLSC) is a master-planned neighbourhood of 52 homes in the Town of Okotoks, Alberta, Canada that has successfully
Field test of a novel combined solar thermal and heat pump system with an ice store
Field test of a novel combined solar thermal and system with an ice store Anja Loose Institute for Thermodynamics and Thermal Engineering (ITW), Research and Testing Centre for Thermal Solar Systems (TZS),
How Ground/Water Source Heat Pumps Work
How Ground/Water Source s Work Steve Kavanaugh, Professor Emeritus of Mechanical Engineering, University of Alabama Ground Source s (a.k.a. Geothermal s) are becoming more common as the costs of energy
Thermal Coupling Of Cooling and Heating Systems
This article was published in ASHRAE Journal, February 2011. Copyright 2011 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not
HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY
HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY Benson Kwong, CVS, PE, CEM, LEED AP, CCE envergie consulting, LLC Biography Benson Kwong is an independent consultant providing
GEOTHERMAL POWER GENERATION A PRIMER ON LOW-TEMPERATURE, SMALL-SCALE APPLICATIONS
GEOTHERMAL POWER GENERATION A PRIMER ON LOW-TEMPERATURE, SMALL-SCALE APPLICATIONS by Kevin Rafferty Geo-Heat Center January 2000 REALITY CHECK Owners of low-temperature geothermal resources are often interested
ALONE. small scale solar cooling device Project No TREN FP7EN 218952. Project No TREN/FP7EN/218952 ALONE. small scale solar cooling device
Project No TREN/FP7EN/218952 ALONE small scale solar cooling device Collaborative Project Small or Medium-scale Focused Research Project DELIVERABLE D5.2 Start date of the project: October 2008, Duration:
Hybrid geothermal systems: less is more
Hybrid geothermal systems: less is more Lessons learned, impacts and tools IGSHPA Conference 2014 Scott Hackel Energy Center of Wisconsin www.ecw.org/hybrid Today s discussion The basics of the hybrid
GEOTHERMAL HEATING AND COOLING INTRODUCTION
GEOTHERMAL HEATING AND COOLING INTRODUCTION Geothermal Heating and Cooling Systems provide space conditioning -- heating, cooling, and humidity control. They may also provide water heating -- either to
Federation of European Heating, Ventilation and Air-conditioning Associations
Federation of European Heating, Ventilation and Air-conditioning Associations Address: Rue Washington 40 1050 Brussels Belgium www.rehva.eu [email protected] Tel: +32 2 514 11 71 Fax: +32 2 512 90 62 REHVA
Hybrid Ground-Source Heat Pump Installations:
PREPARED BY Energy Center of Wisconsin with the assistance of The University of Wisconsin Solar Energy Laboratory Hybrid Ground-Source Heat Pump Installations: Experiences, Improvements and Tools June
Renewable Heat Pumps. A guide for the technically minded
Renewable Heat Pumps A guide for the technically minded How do heat pumps work? A heat pump is an environmental energy technology that extracts heat from low temperature sources (air, water, ground), upgrades
Executive summary. - It has a favorable geographical location with significant direct solar irradiation.
Executive summary Introduction The use of solar concentrated energy in thermal applications has very little presence in Spain. In particular, the integration of solar thermal systems in district heating
THERMAL ANALYSIS OF A DATA CENTRE COOLING SYSTEM UNDER FAULT CONDITIONS
Eleventh International IBPSA Conference Glasgow, Scotland July 27-30, 2009 THERMAL ANALYSIS OF A DATA CENTRE COOLING SYSTEM UNDER FAULT CONDITIONS Michaël Kummert 1, William Dempster 1, and Ken McLean
A NEW CONCEPT OF A HYBRID STORAGE SYSTEM FOR SEASONAL THERMAL ENERGY STORAGE IN SOLAR DISTRICT HEATING
A NEW CONCEPT OF A HYBRID STORAGE SYSTEM FOR SEASONAL THERMAL ENERGY STORAGE IN SOLAR DISTRICT HEATING M. Reuß*, J.P. Mueller*, B. Roehle**, M. Weckler**, W. Schoelkopf** * Institut of Agric. Engineering,
Heating & Cooling Efficiency
Heating & Cooling Efficiency Advantages of Geothermal HVAC Efficiency Keith Swilley Gulf Power Company Why Gulf Power Promotes Energy Efficiency? Customer Satisfaction Education Help Customers Make Smart
A heat pump system with a latent heat storage utilizing seawater installed in an aquarium
Energy and Buildings xxx (2005) xxx xxx www.elsevier.com/locate/enbuild A heat pump system with a latent heat storage utilizing seawater installed in an aquarium Satoru Okamoto * Department of Mathematics
Energy Analysis and Comparison of Advanced Vapour Compression Heat Pump Arrangements
Energy Analysis and Comparison of Advanced Vapour Compression Heat Pump Arrangements Stuart Self 1, Marc Rosen 1, and Bale Reddy 1 1 University of Ontario Institute of Technology, Oshawa, Ontario Abstract
How a Ground Source Heat Pump Works for a School or College
How a Ground Source Heat Pump Works for a School or College Vertical System Image courtesy of Climate Master 1 Geothermal avoids the need for outdoor equipment..reducing vandalism and liability Image courtesy
Geothermal Heat Pump Systems
Geothermal Heat Pump Systems GeoExchange Technology Curtis J. Klaassen, P.E. Iowa Energy Center Energy Resource Station Geothermal Heat Pump Technology Introduction What is Geothermal Energy? Geothermal
Natural geothermal energy.
ROTEX ground source heat pump Natural geothermal energy. ROTEX HPU ground the ground source heat pump that heats with free geothermal energy. Compact, environmentally responsible and uniquely efficient.
Designing coaxial ground heat exchangers with a thermally enhanced outer pipe
Raymond et al. Geothermal Energy (2015) 3:7 DOI 10.1186/s40517-015-0027-3 RESEARCH ARTICLE Open Access Designing coaxial ground heat exchangers with a thermally enhanced outer pipe Jasmin Raymond 1*, Serge
Effects of Ultra-High Turndown in Hydronic Boilers By Sean Lobdell and Brian Huibregtse January 2014
Effects of Ultra-High Turndown in Hydronic Boilers By Sean Lobdell and Brian Huibregtse January 2014 Today, hydronic boilers are producing greater efficiencies than previously thought possible, all due
The ASHRAE HQ Building Can the energy efficiency of the different mechanical systems really be compared? RESIDENTIAL LIGHT COMMERCIAL COMMERCIAL
The ASHRAE HQ Building Can the energy efficiency of the different mechanical systems really be compared? RESIDENTIAL LIGHT COMMERCIAL COMMERCIAL Technical Article April 2013 The ASHRAE HQ Building Can
Geothermal: The Clean Energy Secret May 7, 2008
Geothermal: The Clean Energy Secret May 7, 2008 Published by Dr. Patrick Moore in conjunction with the New York Affordable Reliable Electricity Alliance (New York AREA) Geothermal: The Clean Energy Secret
Geothermal Heat Pumps: A Pathway to Zero Net Energy (ZNE) for Schools, Homes and Businesses
Lisa Meline, P.E. Meline Engineering Corp. [email protected] Office: 916.366.3458 Geothermal Heat Pumps: A Pathway to Zero Net Energy (ZNE) for Schools, Homes and Businesses Session C: Institutional Applications
MECHANICAL PROJECT PROPOSAL
PSUAE MECHANICAL PROJECT PROPOSAL REDESIGN PROJECT Nicholas B Scheib 2010 M e c h a n i c a l O p t i o n - IP Table of Contents Executive Summary... 2 Project Summary... 3 Existing Mechanical System Summary...
THE EUROPEAN GREEN BUILDING PROGRAMME. Technical Module on Combined Heat and Power
THE EUROPEAN GREEN BUILDING PROGRAMME Technical Module on Combined Heat and Power Contents Foreword...1 1. Introduction...2 2. Inventory of the CHP system...3 3. Assessment of technical energy saving measures...5
ENERGY PILE AND HEAT PUMP MODELING IN WHOLE BUILDING SIMULATION MODEL
ENERGY PILE AND HEAT PUMP MODELING IN WHOLE BUILDING SIMULATION MODEL Jevgeni Fadejev, Jarek Kurnitski Faculty of Civil Engineering, Tallinn University of Technology, Tallinn, Estonia [email protected];
Solar Aquaponics Designing a 100% Solar Aquaponics Greenhouse
Solar Aquaponics Designing a 100% Solar Aquaponics Greenhouse Dan Chiras, Ph.D. Director, The Evergreen Institute Gerald, MO 63037 www.evergreeninstitute.org Topics Creating a 100% solar operation Efficiency
Case Study. Southwestern Manitoba town simplifies ice-making while reducing costs. Miami, Manitoba Hockey Arena and Community Hall
Case Study Earth Energy Systems Volume 1, Issue 4 April 2000 Southwestern Manitoba town simplifies ice-making while reducing costs Miami, Manitoba Hockey Arena and Community Hall Phased approach spreads
SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP
research journal 2013 / VOL 05.01 www.perkinswill.com SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP ARCHITECTURE AND ENGINEERING OF SUSTAINABLE BUILDINGS Current Trends in Low-Energy HVAC Design
Solar Thermal TECHNOLOGY. Eric Buchanan Renewable Energy Scientist West Central Research and Outreach Center Wcroc.cfans.umn.edu
Solar Thermal TECHNOLOGY Eric Buchanan Renewable Energy Scientist West Central Research and Outreach Center Wcroc.cfans.umn.edu Solar Energy History Solar Thermal 700 BC Chinese use burning mirrors 1760
Design of a Heat Pump Assisted Solar Thermal System
Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2014 Design of a Heat Pump Assisted Solar Thermal System Kyle G. Krockenberger Purdue
The efficient heat pump
The efficient heat pump KCP&L has worked hard to build one of the best reliability records in the industry and we want to help you make the most of the energy we provide. That s why we offer information
How To Use A Water Source Heat Pump
Geothermal Energy Using Water-Source Heat Pumps By VIRSTAR Corporation Geothermal Expertise Since 1978 All information contained herein is the exclusive property of VIRSTAR Corporation, all rights reserved.
Sustainable water heating solutions through solar systems
VIESMANN Sustainable water heating solutions through solar systems Murat Aydemir Managing Director Viessmann Middle East FZE Viessmann is a Registered Provider with The American Institute of Architects
Three-years operation experience of a ground source heat pump system in Northern Greece
Energy and Buildings 39 (2007) 328 334 www.elsevier.com/locate/enbuild Three-years operation experience of a ground source heat pump system in Northern Greece A. Michopoulos, D. Bozis, P. Kikidis, K. Papakostas,
Solar Cooling with Concentrators
2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions (2010, vol 116,part 2). For personal use only. Additional reproduction,
LG Electronics AE Company, Commercial Air Conditioning
www.lgeaircon.com New concept Ecofriendly Highefficiency Heating solution Total heating & Hot water Solution for MULTI V LG Electronics AE Company, Commercial Air Conditioning 2 Yeouidodong, Yeongdeungpogu,
AE-1483 Ground-source Heat Pumps. Carl Pedersen Energy Educator
AE-1483 Ground-source Heat Pumps Carl Pedersen Energy Educator A heat pump can be an efficient alternative to a standard home heating system. Moreover, during the cooling season, its function can be reversed,
Our Deep Geothermal Energy Potential: A Case Study in Saskatchewan with Application Throughout the Western Canadian Sedimentary Basin
Our Deep Geothermal Energy Potential: A Case Study in Saskatchewan with Application Throughout the Western Canadian Sedimentary Basin Introduction Deep geothermal energy relates to the heat-energy stored
Analysis of data centre cooling energy efficiency
Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe
Commercial Earth Energy Systems:
Commercial Earth Energy Systems: A buyer s Guide Natural Resources Canada Ressources naturelles Canada Commercial Earth Energy Systems Buyer s Guide B Preface This publication is distributed for informational
Small-Scale Solar Heating and Cooling Systems
Contact Austria: AEE INTEC (www.aee-intec.at) France: Tecsol (www.tecsol.fr) Germany: Fraunhofer ISE (www.ise.fraunhofer.de) Greece: CRES (www.cres.gr) Italy: EURAC (www.eurac.edu) University of Bergamo
Summary technical description of the SUNSTORE 4 plant in Marstal
Summary technical description of the SUNSTORE 4 plant in Marstal The purpose of the SUNSTORE concept implemented in Marstal is to show that district heating can be produced with 100 % RES of which solar
Energy Audits. Good energy management begins with an energy audit
Energy Audits Good energy management begins with an energy audit Effective management of energy-consuming systems can lead to significant cost and energy savings as well as increased comfort, lower maintenance
EVALUATION OF GEOTHERMAL ENERGY AS HEAT SOURCE OF DISTRICT HEATING SYSTEMS IN TIANJIN, CHINA
EVALUATION OF GEOTHERMAL ENERGY AS HEAT SOURCE OF DISTRICT HEATING SYSTEMS IN TIANJIN, CHINA Jingyu Zhang, Xiaoti Jiang, Jun Zhou, and Jiangxiong Song Tianjin University, North China Municipal Engineering
SAN DIEGO COMMUNITY COLLEGE DISTRICT CITY COLLEGE ASSOCIATE DEGREE COURSE OUTLINE
AIRE 160 CIC Approval: 12/11/2008 BOT APPROVAL: 01/22/2009 STATE APPROVAL: EFFECTIVE TERM: SECTION I SAN DIEGO COMMUNITY COLLEGE DISTRICT CITY COLLEGE ASSOCIATE DEGREE COURSE OUTLINE SUBJECT AREA AND COURSE
SDH ONLINE-CALCULATOR
CALCULATION PROGRAM FOR THE COST-BENEFIT ANALYSIS OF SOLAR DISTRICT HEATING SYSTEMS WWW.SDH-ONLINE.SOLITES.DE Dipl.-Ing. Thomas Schmidt and Dipl.-Ing. Laure Deschaintre Solites Steinbeis Research Institute
Vicot Solar Air Conditioning. V i c o t A i r C o n d i t i o n i n g C o., l t d Tel: 86-531-8235 5576 Fax: 86-531-82357911 Http://www.vicot.com.
Vicot Solar Air Conditioning V i c o t A i r C o n d i t i o n i n g C o., l t d Tel: 86-531-8235 5576 Fax: 86-531-82357911 Http://www.vicot.com.cn Cooling, heating, and domestic hot water. Return on investment
Gas Absorption Heat Pumps. Future proofing your heating and hot water
Gas Absorption Heat Pumps Future proofing your heating and hot water Gas Absorption Heat Pumps 1 Contents Gas Absorption Heat Pumps (GAHPs) The heating solution What is a Gas Absorption Heat Pump? How
Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics
Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics A Presentation of Work in Progress 4 October 2006 in the Intelligent
GEOTHERMAL HEATING APPLICATIONS FOR RESIDENTIAL HOMES
GEOTHERMAL HEATING APPLICATIONS FOR RESIDENTIAL HOMES GAGNON HEATING & AIR CONDITIONING RT. 302, P.O. BOX 814 BRIDGTON, ME 04009 207-647-8782 mainegeothermal.com GOODWIN WELL & WATER, INC. 2282 AUBURN
SENSITIVITY OF CONCENTRATING SOLAR POWER TROUGH PERFORMANCE, COST, AND FINANCING WITH THE SOLAR ADVISOR MODEL
Abstract SENSITIVITY OF CONCENTRATING SOLAR POWER TROUGH PERFORMANCE, COST, AND FINANCING WITH THE SOLAR ADVISOR MODEL Nate Blair *, Mark Mehos, Craig Christensen Senior Energy Analyst, CSP Program Manager,
A NEW DESICCANT EVAPORATIVE COOLING CYCLE FOR SOLAR AIR CONDITIONING AND HOT WATER HEATING
A NEW DESICCANT EVAPORATIVE COOLING CYCLE FOR SOLAR AIR CONDITIONING AND HOT WATER HEATING John Archibald American Solar Roofing Company 8703 Chippendale Court Annandale, Va. 22003 e-mail: [email protected]
Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment
Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment The heating, ventilation and cooling loads of typical commercial office space can range
Best Practice Guide. Heat Pump Technologies
Best Practice Guide Heat Pump Technologies Objectives of this Guide: Whether installing a heat pump in a new or existing dwelling, the initial capital investment will generally be greater than for a conventional
Nordic Heat Pump Product Guide
Nordic Heat Pump Product Guide About Maritime Geothermal Maritime Geothermal is a privately owned, Canadian based manufacturer of geothermal heat pumps. We began manufacturing the Nordic line of heat pumps
Sustainable Schools 2009. Renewable Energy Technologies. Andrew Lyle RD Energy Solutions
Sustainable Schools 2009 Renewable Energy Technologies Andrew Lyle RD Energy Solutions RD Energy Solutions Energy efficiency and renewable energy consultancy Project management of installations Maintenance
New technical solutions for energy efficient buildings
- New technical solutions for energy efficient buildings State of the Art Report New technologies for heat pumps Authors: Heimo Staller, Angelika Tisch, IFZ Oct. 2010 Background Heat pumps are machines
OPTIMIZING CONDENSER WATER FLOW RATES. W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa
OPTIMIZING CONDENSER WATER FLOW RATES W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa T.A. Brown, P.E. Thermal Energy Corporation Houston, Texas ABSTRACT Most chillers are designed for a
Commissioning - Construction Documents (Page 1 of 6)
Commissioning - Construction Documents (Page 1 of 6) A. General Information Climate Zone: Building Type: Conditioned Area (sf): Reviewer's Name: Reviewer's Agency: Note: Design Review for each system/subsystem
HVAC Applications for PE Pipe
463 Introduction The performance and use characteristics of polyethylene pipe make it an ideal choice for use in certain HVAC Heating, Ventilation, and Air Conditioning applications. Typically, HVAC is
Fiscal Year 2011 Resource Plan
Salt River Project Fiscal Year 2011 Resource Plan Page 1 Last summer SRP hosted three resource planning workshops for a diverse group of stakeholders and customers to explain the planning process, discuss
6 18 A steam power plant receives heat from a furnace at a rate of 280 GJ/h. Heat losses to the surrounding air from the steam as it passes through
Thermo 1 (MEP 261) Thermodynamics An Engineering Approach Yunus A. Cengel & Michael A. Boles 7 th Edition, McGraw-Hill Companies, ISBN-978-0-07-352932-5, 2008 Sheet 6:Chapter 6 6 17 A 600-MW steam power
Abstract. emails: [email protected], [email protected], phone: 860-429-6508, fax: 860-429-4456
SOLAR THERMAL POWER PLANT WITH THERMAL STORAGE Ronald C. Derby, President Samuel P. Lazzara, Chief Technical Officer Cenicom Solar Energy LLC * Abstract TM employs 88 parabolic mirrors (concentrating dishes)
Building Energy Systems. - HVAC: Heating, Distribution -
* Some of the images used in these slides are taken from the internet for instructional purposes only Building Energy Systems - HVAC: Heating, Distribution - Bryan Eisenhower Associate Director Center
Indiana Energy and Cost Savings
BUILDING TECHNOLOGIES PROGRAM Indiana Energy and Cost Savings for New Single and Multifamily Homes: 2012 IECC as Compared to the 2009 IECC 1 2012 IECC AS COMPARED TO THE 2009 IECC Indiana Energy and Cost
2009 Seattle Energy Code Impacts: See below for a recap of Changes in Envelope performance from 2006 to 2009
2009 Seattle Energy Code Impacts: Building Envelope Impacts: Below is a Summary of Changes that impact building envelope construction planned for 624 Yale. There are several modifications are required
Optimization of Water - Cooled Chiller Cooling Tower Combinations
Optimization of Water - Cooled Chiller Cooling Tower Combinations by: James W. Furlong & Frank T. Morrison Baltimore Aircoil Company The warm water leaving the chilled water coils is pumped to the evaporator
Serenbe Green Geothermal Solutions with Bosch Thermotechnology
Serenbe Green Geothermal Solutions with Bosch Thermotechnology Geothermal Heating and Cooling boschheatingandcooling.com C1 Residential Geothermal Heat Pumps The Bosch Complete Solution The Serenbe Community,
Introduction to Project Finance Analytic Methods
Introduction to Project Finance Analytic Methods Renewable Energy and Project Development and Financing for California Tribes Sacramento, CA Jack Whittier, McNeil Technologies January 2008 Why? Use a model
Heating and cooling with wastewater
WASTE WATER Solutions Heating and cooling with wastewater Recovery of thermal energy from municipal and industrial wastewater Uc Ud Ub Ua a sewer b wastewater shaft with HUBER screen and delivery pump
Codes and High Performance Hot Water Systems. Gary Klein Affiliated International Management, LLC 916 549 7080 gary@aim4sustainability.
Codes and High Performance Hot Water Systems Gary Klein Affiliated International Management, LLC 916 549 7080 [email protected] Annual Energy Use for Heating Water Natural Gas Gallons Per Day
Hybrid heating and cooling system optimisation with TRNSYS
Hybrid heating and cooling system optimisation with TRNSYS Submitted in partial fulfilment with the requirements of the degree MSc in Energy Systems and the Environment DEPARTMENT OF MECHANICAL ENGINEERING
