1 BEST2 Strategic Issues in Building Design Session WB1 Thermographic Assessment Specification Requirements for Commissioning and Building Condition Applications Antonio Colantonio 1 and Michel Theauvette 2 ABSTRACT The National Master Specification Secretariat (NMS) Directorate, through consultations with the building industry and departmental experts in Public Works and Government Services Canada (PWGSC) has developed four sections for commonly implemented infrared thermographic services associated with building construction and maintenance. These include inspection services for building envelopes, roofs, mechanical equipment, and electrical systems. The NMS is the generic specification format used extensively in the Canadian construction industry for the preparation of specifications used in bid documents for new and retrofitted commercial building projects. It uses the same format as the comparable specification systems found in the USA. This paper introduces the thermographic assessment sections and discusses the relevant information in each section that is pertinent to each type of inspection service. These sections have been developed to include all aspects of such services and are all encompassing in their scope. Users of the NMS generic format are free to use and modify any part of these sections that are relevant to their building project. Building owners and property managers can also employ the specification format to call up services for building condition studies. Although the NMS sections have been developed for use in commercial buildings, the residential construction industry can modify any section for their use. This paper will discuss these differences and provide suggestions for the development of such a residential specification format. 1.0 INTRODUCTION Although a few standards and guidelines have been developed for the used of infrared thermography in specific building applications over the last 30 years, there has not been any concerted effort by specification writers to standardize call up for services in the building industry. The NMS Secretariat within the Canadian federal government s department of PWGSC felt that there was sufficient information within the industry to produce generic specifications for the request for services of contractors who use infrared thermographic equipment for building inspections and assessments. 1
2 2.0 THE NATIONAL MASTER SPECIFICATION (NMS) For well over 30 years, the Canadian National Master Construction Specification (known as the NMS) has been leading the way in providing the Architectural, Engineering, Contracting and Facility Management (AECFM) community with the largest bilingual generic master construction specification available commercially in North America. Since the 1970 s, the NMS has spearheaded many Federal Government s initiatives, which resulted in many improvements to the construction industry in Canada; building accessibility, sustainable development in construction practices, LEED requirements, performance specifications for design-build type contracts, and building communications and security. The latest innovation for specification writers and practitioners of building sciences is a tool for Specifying Infrared Thermographic Services for Large Buildings. The NMS is a comprehensive library of construction specification sections used by government and private industry. Specification writers and other construction specialists use it as a tool to produce clear, complete and accurate specifications for inclusion into construction project manuals. As a guide specification and as a delete master, the NMS is designed to produce construction contract documents that are easy for contractors to understand and reduce the risk of misunderstandings and litigation. All Canadian Government retrofit and new construction are mandated by Departmental Policy 039 The Use of the NMS, in using the latest version as the basis for developing the Project Manual, or more specifically the project construction specifications. The Department of National Defense (DND) uses the NMS for all of its construction work including military quarters, even though the document is intended for commercial applications. The NMS is used throughout Canada by non-federal government organizations, architectural and engineering offices either directly or as a tool for updating their office master specification system. 3.0 NMS FORMAT STRUCTURE The style, language and format of the NMS follows the recommendations of the Construction Specifications Canada (CSC), Manual of Practice, published in In the United States of America, the counterpart of CSC is the Construction Specifications Institute (CSI). CSC and CSI have jointly produced a master list of numbers and titles for the construction industry in North America called MasterFormat 2004 (MF04). The structure of the NMS, follows the standards filing and retrieval scheme allowing specification sections to be classified by work results and construction practices. The Groups, Subgroups and Divisions are in accordance with this classification system and use the MF04 as a basis for its Section Numbers and Titles. The NMS follows the recommendations of CSC/CSI s PageFormat and recently update (2008), Section Format documents to further ensure consistency in the way types of information, names of articles and paragraphs and the layout of content of individual sections appear. 4.0 OTHER MASTER SPECIFICATION SYSTEMS IN THE USA 2
3 The two most well known master specification systems in the USA are: MASTERSPEC, published by Architectural Computer Services Inc., (ARCOM) exclusively for the American Institute of Architects (AIA). SPECLINK, published by Building Systems Design Inc., (BSD). Both these systems currently do not offer sections on thermographic assessment of building systems. 5.0 WHY GENERIC SPEC S FOR THERMOGRAPHIC ASSESSMENTS Over the past decade there has been resurgence in the use of infrared thermographic equipment for assessments of building systems performances. The 1990 s saw the development of truly portable equipment aimed at electrical and mechanical systems assessments. These types of assessment applications have become well established throughout North America and Europe. The refinement of equipment for these market sectors has resulted in more low cost, portable, user-friendly imagers and radiometers into the hands of more people who may or may not be suitably trained in the operation of the equipment. In addition, these users may not have the suitable disciplinary or professional expertise to render accurate analysis and provide clients with adequate assessments. The time was right to develop a series of sections within the NMS to deal with the complexities and variables being introduced to the market place by equipment manufacturers and the needs of the building industry. With the establishment of methodologies for relevant building condition assessment and commissioning procedures, it was important to define not only what type of equipment was suitable for each application, but more importantly what the qualification requirements should be for equipment operators and report authors. This type of information within tender documents allows for more equitable bids for consultant services and creates a better understanding of expectations between clients and bidders. 6.0 INFRARED EQUIPMENT USED IN BUILDING ASSESSMENTS Current imaging and radiometric infrared systems can be broken down into various generic types based on the following general criteria: Detector Image Size: (Focal Plane Arrays (FPA) row/columns of: 80 x 60, 100 x 100, 160 x 120, 320 x 240, or 640 x 480 pixels) Wave Length: Short Waveband (1.5 3 µ); Mid Waveband (2 6 µ); or Long Waveband (7 14 microns) Detector Type: Thermal (Microbolometers, Ferroelectric), Photon (InSb, PtSi, QWIP) The level of complexity increases exponentially once you factor in all the hardware and software considerations that need to be determined for these types of imaging and measurement systems. Table #1 lists the technical specs along with optional features offered for present day infrared equipment. Over the past few years, commercial infrared thermographic equipment manufacturers have introduced a wide range of low cost imagers and radiometers with varying specifications for a wide range of applications. These new systems (generally with 20,000 detectors or less) primarily target the predictive maintenance fields of electrical and mechanical systems inspections along with conventional roofing 3
4 assembly inspections. Confusion within the market place arose when operators with these types of equipment branched out into other large building inspection services without regard for the necessary technical requirements of equipment used in exterior inspection work to obtain credible spot size resolution for fault detection. TECHNICAL SPECIFICATIONS Detector Array Size and Type Lens Field of View and Interchangeability Spatial Resolution (IFOV expressed in milliradians) Measurement Resolution (Distance to Measurement Spot Ratio) Detectable Temperature Range Calibration range (may be different from Temperature Range) Radiometrics (Accuracy and repeatability) Operating Temperature Range Thermal Sensitivity (NETD) OPTIONAL FEATURES Weight, size, ergonomics Batteries Display; LCD, Viewfinder, both Visual Imaging and Fusion capabilities Video, flash capture Supplemental lenses Text and Voice Annotation Manual vs motorized focus Laser Pointer Digital camera for visual photos Image Storage Capacity and Media Onboard Software Features Image Analysis and Reporting Software Table #1: Technical specifications versus optional features for infrared equipment. 14 Given the broad range of infrared thermographic equipment on the market today, the intent of inspection and assessment specifications is to ensure that suitable equipment is used in each type of applications so as to meet current standards and guidelines. Where current standards are not presently defined, suitable procedures are specified related to specific equipment and their use in achieving acceptable thermal and spatial resolution for fault detection for assessment purposes. With the current resurgence of the building inspection market, it is important that specifications deal with the technical requirements of the equipment, the thermographer, and the professional requirements of the person analyzing the thermal imagery and providing recommendations to clients. In the building industry, there is a clear delineation between the roles and responsibilities of trades people, technicians, and professionals from each discipline. Different groups in the residential and commercial building sectors meet these responsibilities. In most cases, warrantee and liability issues dictate who assumes jurisdiction. The specific sections dealing with thermographic assessments within the NMS identify the varying requirements for equipment, equipment operators and report authors providing analysis and recommendations for actions and retrofit options. These requirements differ within each section since disciplinary expertise required comes from different professional and technical personnel. The NMS is specifically targeted to commercial building projects where professional jurisdiction is exercised according to building ordinances. For the most part NMS specifications are not used in low-rise residential project but are applicable in the high-rise sector where generally professional jurisdiction is required by law. 7.0 BUILDING SYSTEMS THAT UTILIZE THERMOGRAPHIC ASSESSMENT PROCEDURES Different applications of infrared technology were examined. It was determined that there was sufficient 4
5 diversity within four distinct building systems that each required their own section dealing with thermographic assessment services. The NMS developed four separate sections on thermographic assessments for a) Electrical systems, b) Mechanical equipment, c) Roofing and d) Building Envelopes. The electrical and mechanical systems sections are relatively straightforward and cover all components of these systems that could be inspected using infrared thermographic equipment. Both methodologies incorporate quantitative methodologies for fault detection. Adequate standards exist that outline fault severity assessments that allow operators and report writers to develop accurate predictive assessment reports for systems inspected multiple times over multiple years. The roofing section focuses on inspection of low-sloped roof assemblies with water permeable insulation. The section on building envelopes is the most complex section since it deals with applications related to detection of defective insulation, air leakage, voids and moisture on surfaces and interstitial spaces within the building envelope. In cases where specific standards and guidelines are available, they are referenced in these sections to define inspection methodologies. Where standard procedures have not yet been developed, (as in the case of moisture detection by means of phase change), procedures were required to be spelled out within the appropriate section. The roofing and building enclosure sections deal with qualitative methodologies and the complexity of their sections stem from the fact that there is generally more than one acceptable methodology to obtain the same diagnostic information. 8.0 NMS CONTENT STRUCTURE When calling up requests for services for infrared thermographic assessments, it is important to specify the following items for each type of inspection: Reference the appropriate standards having relevance to the work to be performed Definition of the most relevant terms found in the request for services State the submittals being requested; include relevant information to be included in the report along with appendices and additional back up documentation. Reference qualifications required by equipment operators, analyzers and report authors. Itemize the scheduling requirements. Itemize specifications for equipment required to carry out work. State requirements for examinations of relevant bid and as built documents. List required items to be carried out in preparation of field inspections. List general field inspection requirements. List specific inspection requirements for each type of infrared thermography inspection methodology being requested. List data and information to be recorded as part of the inspection services. List re-inspection requirements if remediation work is carried out. State cleaning requirements and job site status after inspection services. Since the technical requirements for the four basic types of infrared thermographic assessment within buildings vary significantly, each should be specified separately. The qualifications of personnel required for residential inspections will vary from those required for large building inspections. The qualifications of technical and professional personnel for each of the applications for large buildings are unique and need to be spelled out. Equally important are the technical specifications of the equipment used in each type of assessment and the limitations of each type of equipment used in a specific inspection procedure. Each section of the four 5
6 sections dealing with thermographic assessments has unique requirements that do not necessarily relate to the other sections. 9.0 STANDARDS GOVERNING THERMOGRAPHY ASSESSMENTS In Canada, standards for infrared thermography are developed through the Canadian General Standards Board (CGSB) and Non Destructive Testing Board (NDT). In the United States, these standards are developed through the American Society for Testing and Materials (ASTM) and American Society for Nondestructive Testing (ASNT). These organizations joined with the American National Standards Institute (ANSI) to become a part of a national body coordinating standards development. ANSI has become an umbrella standards organization coordinating the development of worldwide standards. The International Standards Organization (ISO) is another standards organization developing worldwide standards. Both ANSI and ISO work independent of each other but much of their work overlaps in many fields. Canada and the USA provide representatives to many of the standards being produced by both organizations. In Europe, thermographic standards are developed through the ISO. ISO standards are used to develop national standards in European countries. All these organizations operate as truly voluntary consensus groups. Standards from each organization are written by groups of end users representing customers, service providers and general interest groups. The NMS references over 400 consensus standards throughout the 750 individual specification sections, and include predominantly: the American Society for Testing and Materials International (ASTM), the Canadian Standards Association (CSA International), the Canadian General Standards Board (CGSB) and Underwriters Laboratories of Canada (ULC). Of concern to this paper, are the four types of ASTM standards: Test Methods, Specifications, Practices and Guides. Test Methods: a definitive procedure to produce a specific result with a specified precision. (i.e. ANSI/ASTM E1213 Standard Test Method for minimum resolvable temperature difference for thermal imagers) Specifications: are explicit sets of requirements to be satisfied by materials, products, systems or services. (i.e. ANSI/ASTM CP-189 ASNT Standard for Qualification and Certification of Nondestructive Testing Personnel) Practices: are a definitive set of instructions for performing specific operations that do not produce a definitive test result (i.e. ANSI/AST C1153 Standard Practice for location of wet insulation in roofing systems using infrared imaging) Guides: are tutorials indicating how something is to be done and provides recommended but nonmandatory guidelines on things to be considered. (i.e. E1934 Standard Guide for examining electrical and mechanical equipment using infrared thermography) The purpose of these documents is to establish a set of uniform expectations between people who want the work done and those doing the work. For this reason, they are the cornerstones of information used by all sections of the NMS. ASNT is also under the ANSI umbrella. Its function is to promote standards for personnel qualifications and certification in nondestructive testing technologies. It publishes the authoritative standards for personnel training and qualifications in nondestructive testing. These include SNT-TC-1A and CP-189. ASNT-CP-198 is an ANSI/ASTM specification. To conform to this standard, a person must comply with all of the requirements within CP-189 plus any additional specific requirements requested by the user. 6
7 ASNT-SNT-TC-1A is an ANSI/ASTM guide. It is similar to a specification in content but intended to be modified by users to meet their needs. The actual requirement to be compliant with SNT-TC-1A is to have a written practice, keep records in accordance with your written practice and do what you say you will do. Standards provide a basis for common understanding among people. They are completely voluntary to users unless they are legislated into law. One such recognized standard in some states and provinces in North America is the National Electric Code (NEC) administered by the National Fire Protection Association (NFPA). Another such standard is NFPA 70E, Standard for Electrical Safety in the Workplace. This standard is legislated by the federal government and adopted into law in the Code of Federal Regulations (CFR). The NMS, in its quest to produce a set of uniform expectations between people who want the work done and those doing the work, utilizes the guidelines and standards developed by ASNT to specify the qualifications of personnel providing services DIFFERENCES BETWEEN RESIDENTIAL & COMMERCIAL APPLICATIONS There are clear differences in the requirements for equipment specifications, equipment operator knowledge and qualifications and report author disciplinary knowledge and qualifications for low-rise residential applications compared to large commercial buildings and high-rise residential. Although the NMS primary market is the commercial building sector, understanding these differences allows the NMS format to also be modified for use in the low-rise residential sector. On the equipment side, the primary difference is the shorter distances to target surfaces for all applications (electrical, mechanical and building envelope) for residential inspections. This allows for use of smaller focal plane array (FPA) thermographic equipment. Interior inspections are the norm in low rise residential since most relevant information can easily be obtained from these procedures. Low temperature operating specifications for equipment used inside are less stringent than equipment required for use outdoors during cold winter months. Equipment used for commercial building applications require larger FPA equipment and telephoto lenses to deal with greater distances to target surfaces. Greater variability in job site conditions for electrical and mechanical systems may require the use of wide-angle lenses as well as mandatory personal protective clothing due to greater system loads and increased risk for arc flash fires. Design of equipment for use with protective clothing and gloves set them apart from residential inspections that do not necessarily require such protective clothing. Exterior inspections are the norm for large building envelope studies and low operating temperatures are a primary requirement for cold weather testing. Equipment manufacturers today make equipment that is dedicated to specific applications and it is imperative that specifications define appropriate requirements for equipment used for each type of application for either low-rise small buildings versus large or high-rise commercial buildings. The level of professional or disciplinary knowledge required to assess infrared thermographic inspections of low rise residential and high-rise commercial buildings are significantly different and specifications need to address these issues. Many complex building enclosure inspection procedures are not defined by present standards and guidelines. Thus more qualified professionals are required to develop inspection and assessment procedures for these types of building than residential buildings where current guidelines define well prescriptive methodologies for generic assembly details. Current standards exist for both residential and commercial electrical, mechanical systems but disciplinary expertise may differ between 7
8 these types of projects. Report authors should ensure that they have the necessary professional expertise to determine system load, suitable equipment performance and assess fault detection THERMOGRAPHIC ASSESSMENTS: ELECTRICAL SYSTEMS Section of the NMS deals with all the items listed above in the NMS content structure. Appropriate references are provided along with standard definitions. All submittals by the contractor are listed along with quality assurance and qualifications requirements of operators, reporters and report authors. It is important to note that Level II certification is proposed as a minimum requirement for both equipment operators and report authors when dealing with large building electrical system assessments. For low-rise residential electrical equipment assessments, Level I certification is acceptable. Equipment requirements are listed not only for infrared thermographic equipment but also for all other related equipment needed to carry out assessments. This section does not limit the use of low-resolution radiometers in assessments but does place maximum distance restrictions for specific types of infrared equipment based on spot size resolution and measurement resolution of critical components. These limitations are listed in the thermographic inspection procedures since they are not spelled out definitively in referenced guidelines and standards. Interior inspections are suitable with 3 mrad IFOV radiometers while exterior inspections are limited to 1.5 mrad IFOV radiometers. 3 mrad IFOV equipment need to limit distance to target surfaces to 2 m, while 1.5 mrad IFOV equipment is limited to 4 m distance to target surfaces. Distances greater than these to target surfaces require the use of telephoto lenses to ensure accurate temperature measurements. Appropriate inspection and re-inspections procedures are defined along with a list of recorded data necessary for inclusion in the deliverables as indicated in the submittal section THERMOGRAPHIC ASSESSMENTS: MECHANICAL SYSTEMS Section of the NMS deals with all the items listed above in NMS content structure. For the most part, the technical details for qualifications of equipment operators and report authors and specifications for infrared and other related equipment are almost identical to those found in section , electrical equipment. It is important to note that Level II certification is proposed as a minimum requirement for both equipment operators and report authors when dealing with large building mechanical system assessments. For low-rise residential mechanical equipment assessments, Level I certification is acceptable. This section does not limit the use of low-resolution radiometers in assessments but does place maximum distance restrictions for specific types of infrared equipment based on spot size resolution and measurement resolution of critical components. These limitations are listed in the thermographic inspection procedures since they are not spelled out definitively in referenced guidelines and standards. Interior inspections are suitable with 3 mrad IFOV radiometers while exterior inspections are limited to 1.5 mrad IFOV radiometers. 3 mrad IFOV equipment need to limit distance to target surfaces to 2 m, while 1.5 mrad IFOV equipment is limited to 4 m distance to target surfaces. Distances greater than these to target surfaces require the use of telephoto lenses to ensure accurate temperature measurements. Sections and both stress temperature measurement procedures as the primary means of 8
9 fault detection and assessment of severity. Spot size resolution is critical to temperature measurement and assessment of fault severity THERMOGRAPHIC ASSESSMENTS: ROOFING Section deals with all the items listed above in NMS content structure. The significant difference between the electrical and mechanical equipment sections and this one is that this section is focused on qualitative fault detection only. Since the methodologies primarily employed to detect moisture in roof insulation are transient heat flow procedures, absolute temperature measurement is not relevant. As such spatial resolution of equipment is the key equipment specification requirement. Most roof inspections are carried out from the exterior. As such, 3 mrad IFOV imagers are suitable for roof inspections where maximum distance to target surface is limited to 10 m. These are appropriate distances for walk on roof inspections. Where inspections are carried out from other rooftops or by aerial means (fixed wing airplanes or helicopters) telephoto lenses or imagers with greater spatial resolution are required to maintain acceptable levels of spatial resolution for pattern recognition of detailed faults. (Images courtesy of Paul Frisk, FLIR Systems Canada) Figure 1; Moisture within insulation under one ply sheet membrane roof assembly as seen from exterior Figure 2; Moisture within insulation as seen from interior of building. It is important to note that Level I certification is proposed as a minimum requirement for equipment operators and level II certification along with expert knowledge of roofing assemblies is required for report authors when dealing with large building low sloped roof assessments. There is little requirement for lowsloped roof inspection services in low rise residential and therefore is not addressed in the specifications THERMOGRAPHIC ASSESSMENTS: BUILDING ENVELOPES Section is by far the most complex of all the sections dealing with thermographic assessments of building systems. Even though the procedures are primarily qualitative (due to the transient heat flow characteristics of envelope assessments), there are still some procedures that can be carried out in which steady state conditions apply and quantification of data is necessary for determination of fault severity. 9
10 Imagers with 3-mrad IFOV spatial resolution are acceptable for work on interiors provided that they are operated within 5 m of their target surfaces. Imagers with greater spatial resolution are required for exterior inspections where distances to target objects increase to more than 50 m and larger FPA s or telephoto lenses are needed to ensure acceptable levels of spatial resolution of potential faults. Another important issue that is specific to building envelope inspections relates to the need for greater thermal resolution requirements for detection of certain faults related to imbedded moisture and convective heat flow within assemblies. Imagers are required to have a minimum of.1 o C and preferred.05 o C thermal resolution specification for all types of spatial resolution imagers used in both interior and exterior inspections. This section deals with a number of related but different assessment procedures that relationally belong together. These include inspections procedures for determination of insulation defects, thermal bridges, detection of surface and interstitial moisture, detection of air leakage and convection heat loss, and voids in composite and homogeneous materials. Methodologies for assessment of each fault type is very specific and minimum environmental conditions are specified as means of providing guidance to service providers where gaps in present day standards and guidelines exist. Courtesy Stockton Infrared Figure #3 (Interior, night time) Figure #4 (Interior, day time) Concrete Filled Cells in Block Walls Appear Cooler in the Night Time and Warmer in the Day Time The complex nature of the inspection methodologies along with the variety of building enclosure assemblies required to inspect create absolute need for Level II certification for both equipment operators as well as report authors. In addition expert professional knowledge of building science is required for analysis of enclosure problems in large buildings. Expert building science knowledge related to residential construction is required for low rise residential and therefore Level I certification is acceptable for both equipment operators as well as report authors providing they have expert building knowledge to draw on FUTURE APPLICATIONS: THERMAL COMFORT, MATERIALS, STRUCTURAL, PEST ASSESSMENTS The present NMS sections dealing with thermographic assessments represent the current state of the art related to known standards and guidelines. There are other building applications that infrared thermography is being used in that could be developed into separate sections within the NMS. These include but are not limited to detailed detection of; interstitial trapped moisture within various materials found in walls, floors, ceilings of buildings, thermal comfort problems within perimeter zones of buildings, 10
11 material deterioration (organic and inorganic composite assemblies), structural defects (voids in concrete), biological infestations and voids in structural organic members, etc. As equipment evolves, newer data collection, storage and display methodologies will result as a consequence of consumer requests and market forces. These will result in the upgrade of existing standards and guidelines and the development of new ones. As these occur, the NMS will be constantly upgraded to include the latest version of applicable reference material AMENDMENT FOR RESIDENTIAL CONSTRUCTION The use of the NMS sections for application in the low-rise residential market place to request the services of home building inspectors can be accommodated but it will be dictated by the requirements of owner, lending institutions and the cost of the service that the market will bear. Although the technical requirements for equipment and qualification requirements for operators may not be as demanding as commercial buildings, there is nevertheless a need within the industry to ensure that the expectations of services by both the client and the service provider are similar. To this end, the NMS can certainly address the potential problems that could arise in such a fractured home inspection market. The applications and equipment considerations can be summarized in the following table: Small Building Detection Measurement Field of View Thermal Sensitivity Operator Knowledge * Author Knowledge * Electrical < 3mrad >100:1 >20 degrees 30C L I L I Mechanical <3mrad >100:1 >20 degrees 30C L I L I Interior <3mrad >100:1 >20 degrees 30C L I L I Exterior <3mrad n/a >20 degrees 0C L I L I Large Building Electrical <3mrad (Outdoors<1mrad) >100:1 Outdoors 300:1 >60 degrees if through IR window Mechanical <3mrad >100:1 >45 degrees on large equipment 30C L I L II 30C L I L II Interior <3 mrad >100:1 >20 degrees 30C L II L II Exterior <0.5mrad n/a >45 degrees preferred 0C L II L II <10 degrees to meet IFOV Low slope <3mrad n/a >20 degrees 30C L I L II roof *Certification level follows ASNT Guidelines Table #2: Summary of spatial resolution, measurement resolution, field of view, thermal sensitivity, operator and report author requirements for building types and system/applications assessments
12 17.0 SUMMARY There are similarities in the inspection procedures and requirements to carry out interior electrical and mechanical system inspections for both low-rise residential and large buildings but the level of complexity with large building components and the potential for exterior inspections necessitates the use of cameras with high spatial resolution and wide field of view when distances to target surfaces become greater than 5 m. In addition these complexities require the expertise of a professional high voltage electrician or engineer to determine fault severity. Residential systems are straightforward enough that trained home building inspectors could determine fault severity with lower cost/lower resolution equipment. Low-sloped roofing inspections for low-rise residential and large building are similar enough that a trained roofer or home inspector can carry out the inspection and provide appropriate reporting and documentation of faults. Low cost imagers are acceptable for this application provided that roofs are not inspected from distance greater than 10 m. In these cases, higher resolution (e.g.: 320 x 240 FPA s or greater) may be required to provide detailed information. The major difference in infrared thermographic inspections procedures, analysis and reporting come into play when looking at building envelopes of low-rise residential and large buildings. Residential inspections, carried out from the interior, can be carried out during daytime. Large building thermographic inspections are carried out from the exterior since interior enclosure surfaces are obscured from view due to suspended ceilings and perimeter heating systems. These inspections can only be carried out at night for non-transient heat flow methodologies and at daybreak or sunset for transient heat flow methodologies. The variety of assembly types and configurations and levels of professional liability involved in the inspection of assemblies found in large building and the types of remediation recommendations require the services of professional architects or building science engineers. In most cases, architectural and structural technologists will not have the required liability insurance to carry out such work. Their level of liability may be acceptable for low-rise residential building inspections but liability insurers for large building projects will most certainly discount these people from the process. In addition to these professional limitations, the use of low cost, low resolution imagers (e.g. 160 x 120 FPA s or less) are limited for large building inspections due to their spatial resolution at distance greater than 10 m. Buildings up to 4 stories in height are best inspected with high resolution (e.g.: 320 x 240 FPA s or greater) radiometers while taller buildings may require additional telephoto lenses to achieve suitable spatial resolution to detect fine detailed thermal signatures. These detailed inspection procedures also require that thermal patterns from one section of the elevation be related to others and thus composite mosaics are beneficial in large building inspections. Similar specifications can be used for the low-rise residential market but much of the demand for quality control of services will be overkill for that market sector due to current market service rates. Creating a level playing field for infrared thermographic service providers for large building inspections requires that specific standards be identified for types of equipment suitable for inspection activities, qualifications of service providers, type of information to be provided by the inspection report and the procedures required to obtain suitable results. They will go a long way to creating a level playing field in the industry to ensure that proper services are provided for all projects. 12
13 18.0 REFERENCES 1. ASNT SNT-TC-1A- [(2001)], Recommended Practice for Training and Certification Non-Destructive Testing 2. NECA 90-[2004], Recommended Practice for Commissioning Building Electrical Systems 3. ASTM C1155- [95 (2001)], Standard Practice for Determining Thermal Resistance of Building Envelope Components from the In-Situ Data 4. ASTM C1060- [90 (2003)], Standard Practice for Thermographic Inspection of Insulation Installations in Envelope Cavities of Frame Buildings 5. ASTM E 1186 [03], Standard Practice for Air Leakage Site Detection in Building Envelopes and Air Barrier Systems 6. ASTM E , Standard Practice for Determining Air Leakage Rate By Fan Pressurization 7. CAN/CGSB 149-GP-2MP- [February 1986], Manual for Thermographic Analysis of Building Enclosures 8. CAN/CGSB [M86], Determination of the Airtightness of Building Envelopes by the Fan Depressurization Method 9. CAN/CGSB [96 (Amd-99)], Determination of the Overall Envelope Airtightness of Buildings by the Fan Pressurization Method using the Building's Air Handling Systems 10. ASTM C1153- [97 (2003) e1], Standard Practice for Location of Wet Insulation in Roofing Systems Using Infrared Imaging 11. NFPA 70B [2006], Recommended Practice for Electrical Equipment Maintenance 12. NETA Maintenance Testing Specifications- [2005], Section 9.0 Thermographic Survey 13. NFPA 70E [2004], Standard for Electrical Safety in the Workplace 14. McIntosh, G., Colantonio, A. Large Building Thermography, Short Course Notes, Thermal Solutions, Sarasota, Colantonio, A., McIntosh, G. The Difference Between Large Buildings and Residential Infrared Thermographic Inspections Is Like Day and Night, Thermal Solutions 2007, Sarasota, Clausing, T., Standards in Infrared Thermography and Thermal Analysis, Thermal Solutions 2007, Sarasota, ACKNOWLEDGEMENTS The authors wish to thank Public Works and Government Services Canada and the National Master Specification Secretariat for funding this work. We wish to thank the many people within the public and private sectors for working on the initial drafts, reviewing and providing considerable insight and direction into the final products for publication for the industry. Special thanks go out to Keith Robinson, (Cohos Evamy, Integrate Design) for the initial drafts and Greg McIntosh (Snell Infrared Canada) for his insight and considerable contributions to this work. 13
Mario D. Gonçalves, Patenaude-Trempe 1 Pierre Gendron, Patenaude-Trempe 2 Tony Colantonio, PWGSC 3. Abstract
Commissioning of Exterior Building Envelopes of Large Buildings for Air Leakage and Resultant Moisture Accumulation using Infrared Thermography and Other Diagnostic Tools Mario D. Gonçalves, Patenaude-Trempe
Evaluating the Field Performance of Windows and Curtain Walls of Large Buildings
Best2 Airtightness of Buildings Session WB6-2 Evaluating the Field Performance of Windows and Curtain Walls of Large Buildings Mario D. Gonçalves, Patenaude-Trempe and Robert Jutras, Air-Ins Introduction
Comparison of Thermal Imaging Systems Used in Thermography as a Non Destructive Testing Method for Composite Parts
ECNDT 26 - Tu.4.6.4 Comparison of Thermal Imaging Systems Used in Thermography as a Non Destructive Testing Method for Composite Parts Nathalie GERLACH, Haute Ecole Rennequin Sualem, Liège, Belgium Abstract:
Infrared Cameras Can Aid Building Inspectors in Detecting Roof Leaks, Water Damage, Mold and Other Moisture Related Problems
Infrared Cameras Can Aid Building Inspectors in Detecting Roof Leaks, Water Damage, Mold and Other Moisture Related Problems Infrared imaging is rapidly becoming the norm for building inspections. With
Nondestructive Evaluation of. Outback Steakhouse/Bertucci s Building at. 2207 Forest Drive, Annapolis, MD. Provided by: HurleyIR
Nondestructive Evaluation of Outback Steakhouse/Bertucci s Building at 2207 Forest Drive, Annapolis, MD Provided by: HurleyIR On Monday, June 2, 2014, HurleyIR provided a nondestructive evaluation for
Nondestructive Evaluation of USCG. 2401 Hawkins Pt. Road Curtis Bay, MD 21226. Provided by: HurleyIR
Nondestructive Evaluation of USCG 2401 Hawkins Pt. Road Curtis Bay, MD 21226 Provided by: HurleyIR On Tuesday May 20 th 2014, HurleyIR provided a nondestructive evaluation for Ruff Roofers of the USCG
BLUESTAR INFRARED. Description: Thermal Properties Comparison. Project Location: Client: 759 South Federal Hwy 225 Bayshore Drive 800-216-1820
BLUESTAR INFRARED We Bring Bad Things to Light SERVING ALL OF FLORIDA Infrared Inspection Services 24 Hour Emergency Service I n f r a r e d I n s p e c t i o n R e p o r t 772-215-8794 Description: Thermal
Expert Level Thermal Imaging Cameras
Expert Level Thermal Imaging Cameras Features & Specifications Powerful Infrared Image Integrated Digital Camera Real-Time Recording Ergonomic Viewfinder + LCD Display Accurate Measurement & Analysis Tools
Preventing Ice Dams on Roofs
Preventing Ice Dams on Roofs Facility Manager November/December 2005 When a roof leaks, facility managers inevitably receive complaints from building occupants. If it is winter, ice dams are often the
WHAT IS INFRARED (IR) THERMOGRAPHY
WHAT IS INFRARED (IR) THERMOGRAPHY IR Thermography is the technique of producing pictures called from the invisible thermal radiation that objects emit. This is a non-contact means of identifying electrical
research highlight Water Penetration Resistance of Windows - Study of Codes, Standards,Testing, and Certification
research highlight November 2003 Technical Series 03-125 Water Penetration Resistance of Windows - Study of Codes, Standards,Testing, and Certification introduction Over the past decade, there has been
Infrared Moisture Detection
What it can do for you... what it can t and why 1. Infrared camera basics 2. Examples Lew Harriman MoistureDM.com 3. Summary - The 4 most important facts about infrared moisture detection 1 of 19 Infrared
Infrared Thermography and Water Damage Assessment
Infrared Thermography and Water Damage Assessment Noah Ceteras / Scott Wood Four Star Cleaning and Restoration / Building Science Institute ABSTRACT Thermal imaging devices have many uses across a wide
Aerial Infrared Roof Moisture Surveys
Aerial Infrared Roof Moisture Surveys INTRODUCTION IR P/PM (infrared predictive/preventive maintenance) is not limited to annual infrared surveys of electrical switchgear. For instance, infrared thermography
FLIR i-series Point-and-Shoot Thermal Imaging Cameras
FLIR i-series Point-and-Shoot Thermal Imaging Cameras Missing insulation and water damage. Hot electrical component. Hot pipe and water leak in wall. Compact and Rugged Groundbreaking Affordability Easy
BECx& Building Airtightness. Presented by: Eric Amhaus Principal
BECx& Building Airtightness Presented by: Eric Amhaus Principal The Building Enclosure 2007 study: out of 17,000 construction defect claims, 69% result of moisture related defects in building enclosure
Maintenance Matters. Window and Door Replacement
Number 13 Maintenance Matters building maintenance bulletin Window and Door Replacement As part of the ongoing maintenance of your home or multi-unit residential building, windows and doors will eventually
Standard Practice for Quality Control Systems for Nondestructive Testing Agencies 1
Designation: E 1212 99 AMERICAN SOCIETY FOR TESTING AND MATERIALS 100 Barr Harbor Dr., West Conshohocken, PA 19428 Reprinted from the Annual Book of ASTM Standards. Copyright ASTM Standard Practice for
Response, Reliability and Results in the delivery of leak detection services
Response, Reliability and Results in the delivery of leak detection services Response, Reliability and Results Polygon is a global provider of property damage restoration, property performance services
Schematic Design: Quality Management Phase Checklist Project Phase Checklist Series
Best Practices : Project Phase Series Contributed by Micheal J. Lough, AIA, Principal, Integral Consulting The AIA collects and disseminates Best Practices as a service to AIA members without endorsement
Solar Panel Installations
Solar Panel Installations Page 1 of 6 SINGLE-FAMILY RESIDENTIAL CHECKLIST City of Hayward Development Services Department Revised: 7-09-15 PERMIT REQUIREMENTS Permits are required for all solar panel installations.
THE VALUES OF ROOF CONSULTING SERVICES. About RCI
THE VALUES OF ROOF CONSULTING SERVICES About RCI RCI, Inc is an international non-profit association of professional consultants, architects and engineers who specialize in roofing, waterproofing and building
Sam Docknevich, PSP, Security Service Portfolio Manager. Are You Prepared? The impending impact of Code on Servicing Security Systems
Sam Docknevich, PSP, Security Service Portfolio Manager Are You Prepared? The impending impact of Code on Servicing Security Systems usa.siemens.com/infrastructure-cities Share current and upcoming standards
Non Invasive Roof Leak Detection Using Infrared Thermography
Non Invasive Roof Leak Detection Using Infrared Thermography Scott Wood Four Star Cleaning and Restoration, Inc. ABSTRACT Residential roofs without attics are typically inspected for leaks by installing
INFRARED DIAGNOSTIC REPORT ABLE INSPECTION COMPANY Post Office Box 820129 Houston, Texas 77282 (713) 465-0000
www.ableinfrared.co www.flirthermography.com INFRARED DIAGNOSTIC REPORT ABLE INSPECTION COMPANY Post Office Box 820129 Houston, Texas 77282 (713) 465-0000 CLIENT: PROPERTY SURVEYED: EMAIL: DATE: In accordance
2014 British Columbia Building Code Changes
District of Houston 250-845-2238 2014 British Columbia Building Code Changes A District of Houston interpretation of the 2014 Building Code Changes for 9.36 & 9.32 The following changes reflect the most
FIELD TESTING SERVICES
FIELD TESTING SERVICES Chris Leach Director of Testing Baton Rouge, Louisiana Destin, Florida Scott Leach David Nichols Field Testing Representative Field Testing Representative 17485 Opportunity Avenue
Design Development Quality Management Phase Checklist Project Phase Checklist Series
Best Practices Design Checklist Project Phase Checklist Series Contributed by Micheal J. Lough, AIA, Principal, Integral Consulting The AIA collects and disseminates Best Practices as a service to AIA
Inspecting to a higher standard.
Inspecting to a higher standard. Rob Hopkin Silver Spring, MD 20902 Monday, June 2, 2014 ProTec Inspection Services Inc. 19736 Selby Ave Poolesville, MD 20837 301-972-8531 www.protec-inspections.com [email protected]
Building Diagnostic Tests as Assessment Tools 診 斷 樓 宇 狀 況 的 測 試 : 樓 宇 檢 驗 的 評 估 工 具
Building Diagnostic Tests as Assessment Tools 診 斷 樓 宇 狀 況 的 測 試 : 樓 宇 檢 驗 的 評 估 工 具 presented by Ir Samson K.Y. WONG Senior Accreditation Officer, Hong Kong Accreditation Service, Innovation and Technology
2013 BUILDING ENERGY EFFICIENCY STANDARDS
2013 BUILDING ENERGY EFFICIENCY STANDARDS Title 24, Part 6, and Associated Administrative Regulations in Part 1 CALIFORNIA ENERGY COMMISSION Edmund G. Brown Jr., Governor MAY 2012 CEC 400 2012 004 CMF
Before You Start an Energy Efficiency Retrofit The Building Envelope
ABOUT YOUR HOUSE Before You Start an Energy Efficiency Retrofit The Building Envelope The building envelope is the outer layer of the building that separates the indoor living space from the outdoor environment,
CONDENSATION IN REFRIDGERATED BUILDINGS
CONDENSATION IN REFRIDGERATED BUILDINGS By: Steve Salisbury Nov. 10, 2010 (revised Nov. 14, 2013) Introduction The following discussion reviews the basic causes of condensation in refrigerated buildings
Exterior Elevated Elements Inspection Guidelines
Exterior Elevated Elements Inspection Guidelines Planning and Development 1. Guideline Purpose These guidelines are intended to assist practicing professionals in complying with Berkeley Municipal Code
GENERAL AND SPECIFIC OBJECTIVES
GENERAL AND SPECIFIC OBJECTIVES 2015 LICENSING AUTHORITIES WHICH RECOGNIZE THE EXAC ARE: Alberta Association of Architects [ AAA ] Architectural Institute of British Columbia [ AIBC ] Architect s Association
Infrared Thermometer Calibration A Complete Guide
Infrared Thermometer Calibration A Complete Guide Application note With proper setup and planning, infrared calibrations can be accurate. The steps outlined below should be followed to perform accurate
Low-slope reroofing guidelines
Low-slope reroofing guidelines by Thomas Bollnow and Joan P. Crowe, AIA The NRCA Roofing and Waterproofing Manual, Fifth Edition, contains reroofing guidelines for steep- and low-slope roofing. The August
The Building Group First Tuesdays First Saint Paul s Lutheran Church 1301 North LaSalle Street, Chicago, Illinois
Wiss, Janney, Elstner Associates, Inc. 10 South LaSalle Street, Suite 2600 Chicago, Illinois 60603 312.372.0555 tel 312.372.0873 fax www.wje.com The Building Group First Tuesdays October 2, 2012 Jason
Effects of Solar Photovoltaic Panels on Roof Heat Transfer
Effects of Solar Photovoltaic Panels on Roof Heat Transfer A. Dominguez, J. Kleissl, & M. Samady, Univ of California, San Diego J. C. Luvall, NASA, Marshall Space Flight Center Building Heating, Ventilation
Safety, Health and Accessibility Design Guidelines For Architects, Engineers and Design Firms
Safety, Health and Accessibility Design Guidelines For Architects, Engineers and Design Firms U.S. Department of the Interior Bureau of Indian Affairs Division of Safety and Risk Management Introduction
Technical Data. FLIR T620 25 (incl. Wi-Fi)
Technical Data FLIR T620 25 (incl. WiFi) Part number: 559010102 Copyright 2012, FLIR Systems, Inc. All rights reserved worldwide. Names and marks appearing herein are either registered trademarks or trademarks
Thermal Imaging for Home Inspectors
Thermal Imaging for Home Inspectors Structural member placement The gabled end of a cathedral ceiling. Note the studs and the ceiling joists with blocking. What is that glow in the upper right hand corner?
Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association
Air-Conditioning, Heating, and Refrigeration Institute Sheet Metal and Air-Conditioning Contractors National Association GUIDELINE B-1997 ACKNOWLEDGEMENT These guidelines for Roof Mounted Outdoor Air-
Technical Data FLIR E40bx (incl. Wi-Fi)
Technical Data FLIR E40bx (incl. Wi-Fi) Part number: 64501-0501 Copyright 2013, FLIR Systems, Inc. All rights reserved worldwide. Names and marks appearing herein are either registered trademarks or trademarks
ROOFS, SNOW AND ICE DAMS
ROOFS, SNOW AND ICE DAMS The Problem Ice dams are a common roof performance problem in cold climate buildings. Simply put, they are ridges of ice and icicles caused by melt water from further up the roof
Automated Infrared Thermography Complete Solutions from a Single Source
Automated Infrared Thermography Complete Solutions from a Single Source Temperature monitoring of processes Automatic surveying of thermal marks Early fire detection and site security Just ask the specialists...
Exhibit C: Scope of Work and Schedule of Deliverables
Exhibit C: Scope of Work and Schedule of Deliverables Project Scope of Work Phases: A City Hall Envelope Renovations B City Hall Skylight Replacement C City Hall Chiller Replacement D City Hall Annex Plaza
Building Energy Codes 101 October 23, 2013. Matthew Giudice Building Policy Associate Midwest Energy Efficiency Alliance
Building Energy Codes 101 October 23, 2013 Matthew Giudice Building Policy Associate Midwest Energy Efficiency Alliance OVERVIEW 1. Introduction 2. Energy Code Development 3. Adoption Process 4. Elements
PIMA Technical Bulletin #115. The High R Roof: Guidelines for Energy-Efficient Roofing and Re-Roofing. What is a High R Roof?
PIMA Technical Bulletin #115 The High R Roof: Guidelines for Energy-Efficient Roofing and Re-Roofing About Polysio Insulation Polyiso is a rigid foam insulation used in over 70% of commercial roof construction,
Water Damage & Repair
Water Damage & Repair Chinatown Preservation Talks 2015 James Engler, P.A Glenn Mason, AIA Mason Architects Program Outline Terminology & Waterproofing Basics Discussion of why this is important Below
2012 Ontario Building Code Changes Affecting Fire Alarm Systems
2012 Ontario Building Code Changes Affecting Fire Alarm Systems CFAA Annual Technical Seminar May 31, 2013 Ken Baird VP Systems www.lrifire.com LRI 2010 Developments in Life Safety Introduction Code Development
Civil Engineering and Architecture (CEA) Detailed Outline
Civil Engineering and Architecture (CEA) Detailed Outline Unit 1: Overview of Civil Engineering and Architecture (23 days) Lesson 1.1: History of Civil Engineering and Architecture 1. Many features of
FACILITY FIRE-SUPPRESSION WATER-SERVICE PIPING 21 11 00
211100_flexheadin_01_MS_0409 5/22/09 PTC 56 Lowland Street Holliston, MA 01746 Phone: (800) 829-6975 Phone: (508) 893-9596 Fax: (508) 893-6020 E-mail: [email protected] www.flexhead.com This MANU-SPEC
Understanding Evaporation:
Feature n n n Understanding Evaporation: Why Don t Leaks Always Appear on my Thermal Images? By Terry Carson, B.Sc., MBA, B.S.S.O., R.H.I., C. Tech. Infrared thermal imagers are often touted as an easy
Home Energy Evaluation Report for Fritz Kreiss and Catherine McQueen
Home Energy Evaluation Report for Fritz Kreiss and Catherine McQueen May 2008 Wisconsin Area PO BOX 115 Lake Geneva, WI 53147 CELL (414) 550-4765 Home Performance with ENERGY STAR Evaluation Report Customer
Stop guessing - Start seeing
Stop guessing - Start seeing Infrared technology for building applications A complete camera range for all users and budgets Thermal Insulation Maintaining acceptable temperatures in buildings (by heating
OFFICE OF PERSONNEL MANAGEMENT ATLANTA OVERSIGHT DIVISION ATLANTA, GEORGIA
OFFICE OF PERSONNEL MANAGEMENT ATLANTA OVERSIGHT DIVISION ATLANTA, GEORGIA CLASSIFICATION APPEAL DECISION Under section 5112(b) of title 5, United States Code Appellant: [the appellant] Position: Engineering
UPDATE October 8, 2012 Chicago Roofing Contractors Association CHICAGOLAND S ROOFING, INSULATION, AIR-BARRIER REQUIREMENTS
UPDATE October 8, 2012 Chicago Roofing Contractors Association CHICAGOLAND S ROOFING, INSULATION, AIR-BARRIER REQUIREMENTS Executive Summary: There is a proposal at the Joint Committee on Administrative
Application for Approved (Overseas/Local) Third Party Inspection Agency for Lifting Equipment
Occupational Safety and Health Division 18 Havelock Road #03-02 Singapore 059764 Tel: 64385122 www.mom.gov.sg [email protected] Application for Approved (Overseas/Local) Third Party Inspection Agency
COMMON FOR ARCHITECTS AND ENGINEERS Excerpts from HB 2284, 82 nd R
Legislation passed by the 82 nd legislature has modified the Texas Engineering Practice Act and the Texas Architect Practice Act. In order to give the public a clearer understanding of these changes, the
SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM
SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION INTELLIGENT REPORTING FIRE DETECTION SYSTEM PART 1 GENERAL 1.1 DESCRIPTION A. This specification includes the furnishing,
Assessing Curtain Walls
Assessing Curtain Walls Considerations and Best Practices Paul E Beers GCI Consultants, LLC [email protected] What is a Curtain Wall System? A curtain wall system is an outer covering of a building
Architectural Testing
FIELD AND MOCK-UP TESTING SERVICES 130 Derry Court York, PA 17406-8405 phone: 717-764-7700 fax: 717-764-4129 www.archtest.com Mock-up Test Methods (Laboratory Mock-up or Field Mock-up): ASTM E 283, Standard
Thermal Imaging Scan Reveals the Truth Behind the Wall
Thermal Imaging Scan Reveals the Truth Behind the Wall Peter Hopkins, Certified Thermographer SoCal Infrared (www.socalinfrared.com) ABSTRACT You suspect you have missing insulation in your home. You have
COMMERCIAL BUILDING APPLICATIONS
EXPANDED POLYSTYRENE FOR COMMERCIAL BUILDING APPLICATIONS www.falconfoam.com Commercial Building Ap Expanded Polystyrene Insulation Falcon Foam leads the commercial building industry with products that
Request for Qualifications 2015-162
Kitsap County Human Services Department Request for Qualifications 2015-162 Architectural and Project Management Services - Kitsap County Work Release Facility Remodel Response Deadline: November 17, 2015
Article. Protecting the Building Envelope from Water Damage. MemBrain Smart Vapor Retarder & Air Barrier Film
Article Protecting the Building Envelope from Water Damage Vapor Retarders Play a Crucial Role in Moisture Management Whether we like it or not, moisture in the form of water vapor diffusion and humid
Fire Alarm Systems Certification
Fire Alarm Systems Certification The skills and knowledge listed under each task are suggestive of those involved in that task, but are not intended to constitute an exhaustive listing. 2.1 Submittal Preparation
Underwriters Laboratories Testing Information
Underwriters Laboratories Testing Information R-8078 Underwriters Laboratories Inc. R-13173 Classified Spray Fiber Surface burning characteristics applied to inorganic reinforced cement board with a maximum
ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1
KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1 PART 1 - GENERAL 1.01 RELATED DOCUMENTS: SECTION 16050 A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1
Quality Assurance and Diagnostic Water Leakage Field Check of Installed Storefronts, Curtain Walls and Sloped Glazing Systems
Method of Test Committee Approval Product Group Approval Approved via 5/21/15 MOT CC Out for Ballot (#805-15) PUBLICATION NO. AAMA 501.2-XX DRAFT #2 DATED 5/21/15 Quality Assurance and Diagnostic Water
Code Requirements for Existing Buildings
Code Requirements for Existing Buildings Kevin S. Hastings, P.E., LEED AP R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617) 523-8227 www.rwsullivan.com R.W. Sullivan Engineering (RWS)
PENNSYLVANIA HOUSING FINANCE AGENCY (2015 UNDERWRITING APPLICATION) Tab 34 Physical/Capital Needs Assessment & Energy Audit
Tab 34 Physical/Capital Needs Assessment & Energy Audit All Preservation developments must submit both of the following: A. Physical/Capital Needs Assessment A Physical/Capital Needs Assessment must be
BEST 2 WB 3 4 SIX WAYS FOR CONDENSATION IN BUILDINGS. Wagdy Anis, FAIA, LEED ap*
BEST 2 WB 3 4 SIX WAYS FOR CONDENSATION IN BUILDINGS Wagdy Anis, FAIA, LEED ap* Abstract: Six of the ways condensation can occur on cold surfaces in buildings are discussed here. They are: 1. Air Leakage,
Bureau Veritas Contact Information
Bureau Veritas Contact Information Permit Submittal The permit documents and fees will be submitted to the city. Submittal documents should be complete to expedite plan review and permit issuance. Please
Response, Reliability and Results. for Managed Property
Response, Reliability and Results for Managed Property Contents Response, Reliability and Results 1 Profit from your property 2 Property Performance Services 3 Energy assessments - beyond compliance 4
Certification: Building Plans Examiner. Exam ID: B3
Certification: Building Plans Examiner Exam ID: B3 Scope: A Building Plans Examiner will be responsible for reviewing submitted plans to determine if they meet the requirements of the various Building
Indiana Boiler and Pressure Vessel Safety Section Frequently Asked Questions
Indiana Boiler and Pressure Vessel Safety Section Frequently Asked Questions What are the licensing requirements for boiler operators? Answer: Indiana statute (IC 22-15-6) and administrative rules (680
Section 1. The title of Section 101-07 of Subchapter A of Chapter 100 of Title 1 of the Rules of the City of New York is amended to read as follows:
Section 1. The title of Section 101-07 of Subchapter A of Chapter 100 of Title 1 of the Rules of the City of New York is amended to read as follows: 101-07 [Inspections and] [a] Approved [a] Agencies.
Roof Insulation Building. Energy. Environment friendly e-library
Roof Insulation Building Codes & Energy Efficiency Environment friendly e-library Building Code Driver Buildings consumer almost 50% of all energy. Experts believe that a 30% increase in building efficiency
STATEMENT OF WORK (SOW) On-Call Certified Welding Inspections and Nondestructive Testing
1.0 INTRODUCTION Colorado Springs Utilities (UTILITIES) is seeking qualified firms to provide verification welding inspection services, nondestructive testing services, and technical reporting to Colorado
Canadian Regulatory Compliance for Stationary Battery Systems North American Update
Canadian Regulatory Compliance for Stationary Battery Systems North American Update ComplianceKnowledgeCenter.com What is Compliance? In general: compliance means conforming to a rule, such as: a specification,
FIRESTOPPING & SMOKE SEALS
SPECIFICATION SECTION 07 84 00 FIRESTOPPING & SMOKE SEALS 1 GENERAL 1.1 SECTION INCLUDES 1.1.1 Comply with Division 1, General Requirements and Documents referred to therein. 1.1.2 It is the intent of
TIMBER PEST INSPECTION AGREEMENT
TIMBER PEST INSPECTION AGREEMENT PROPERTY TO INSPECT: CLIENT NAME: AGREEMENT NUMBER: Inspection and Report: The inspection will be as outlined in Australian Standard AS4349.3-2010 Inspection of Buildings
State of Connecticut Department of Public Health RADON PROGRAM
State of Connecticut Department of Public Health RADON PROGRAM Scope The Connecticut Department of Public Health (DPH) Radon Program is providing this information for contractors who decide to build radon
Residential Duct Systems for New and Retrofit Homes
Residential Duct Systems for New and Retrofit Homes Why it is important to properly design and install high quality, efficient ducted air systems? The efficiency of air distribution systems has been found
A Guide to Renovation and Repair Contract Warranties
A Guide to Renovation and Repair Contract Warranties By Gerald A. Dalrymple, PE A fter being retained to review the merits of several major disputes involving the scope of warranties in renovation and
Innovative capture and modeling of existing building conditions using 3D laser scanning. Entry B Submission
Innovative capture and modeling of existing building conditions using 3D laser scanning Entry B Submission Executive Summary As a large owner organization, understanding and developing new technologies
Continuous Insulation Using Polyiso Wall Sheathing
PIMA Technical Bulletin #403 Continuous Insulation Using Polyiso Wall Sheathing What it is, what it does, and why you need it About Polyiso Insulation Polyiso is a rigid foam insulation used in over 70%
Chapter Seven RESNET Standards
Chapter Seven RESNET Standards 700 RESNET NATIONAL STANDARD FOR HOME ENERGY AUDITS 701 GENERAL PROVISIONS 701.1 Purpose The provisions of this Standard are intended to define a framework for a home energy
Know the Code: Using Spray Foam Insulation In Attics and Crawl Spaces
center for the polyurethanes industry October 2009 Know the Code: Using Spray Foam Insulation In Attics and Crawl Spaces One of the largest growing uses of spray polyurethane foam (SPF) insulation is in