Calculation of Underground Cable Ampacity
|
|
|
- Gabriel Jones
- 9 years ago
- Views:
Transcription
1 Calculation of Underground Cable Ampity Francisco de León CYME International T&D 485 Roberval, Suite 04 St. Bruno, Quebec, Canada, J3V 3P8 Tel. (450) Abstrt This paper introduces the heat transfer mechanisms in underground cable installations and analyzes the available solution methods of the diffusion equation. The heat sources and thermal resistances of the different layers of a cable installation are described. The basic concepts behind the Neher-McGrath method (IEEE) are discussed, along with its differences with the IEC standards for underground cable installations. The available commercial computer programs, designed to perform ampity calculations are listed along with a description of the modeling capabilities of CYME's CYMCAP. Index Terms Ampity. Underground Cables. Neher-McGrath. IEC Standards. CYMCAP. Cables. A I. INTRODUCTION TO CABLE AMPACITY MPACITY is a term given by Del Mar in 95 to the current-carrying capity of a cable. Ampity in an underground cable system is determined by the capity of the installation to extrt heat from the cable and dissipate it in the surrounding soil and atmosphere. The maximum operating temperature of a cable is a function of the damage that the insulation can suffer as a consequence of high operating temperatures. The insulation withstands different temperatures as function of the duration of the current circulating in the conductors. There are three standardized ampity ratings: steady state, transient (or emergency) and short-circuit. Only steady state ampity ratings are discussed in this paper. Ampity calculation techniques are as old as the cables themselves. Anders has summarized the history of ampity calculations in his 997 book []. There are analytical and numerical approhes to calculate cable ampity. The two major international standard associations, the IEEE and the IEC, have adopted the analytical methods as the basis for their standards [], [3-9]. The numerical approhes are mainly based on finite differences or finite elements techniques. The finite elements technique is better suited for cable ampity because of the round geometry of cables. This paper focuses on the analytical techniques for the computation of cable ampity in steady-state through the use of assumptions that simplify the problem. For transient (or emergency) calculations the reader is referred to [], [8], [9], [] and [3]. Calculation of short-circuit ratings is described in [4] for both adiabatic and non-adiabatic conditions. II. AN OVERVIEW OF HEAT FLOW There are three physical mechanisms for heat transfer: Conduction Convection Radiation Fourier Law describes the heat transferred by conduction. In very simple terms, the heat flux is proportional to the ratio of temperature over spe. In an underground cable installation heat conduction occurs everywhere except in the air spe in the conduit. Convection of heat occurs in moving fluids (air, water, etc.) and obeys Newton's Law. The flow of heat is proportional to the temperature difference. In an underground cable installation convection takes ple in the air spe inside the ducts and at the surfe of the earth. The Stefan-Boltzmann Law describes the radiation of heat phenomenon as being proportional to the difference the temperatures at the power of four (t 4 f t 4 0 ). In underground cables radiation of heat occurs from the cable(s) to the ducts. Figure show a typical temperature distribution for a duct bank installation using an engineered bkfill on top of the duct bank. From the figure one can appreciate the diffusion of heat that occurs in underground cable systems. Diffusion is a process by which heat is transferred for one region to another in a slow, spe-limited fashion described by decaying exponentials. Therefore, there is a prtical distance, away from the heat source, beyond which the heating effects are not felt. Figure. Typical temperature distribution of an underground cable installation CYME International T&D, 005
2 III. HEAT SOURCES IN CABLE SYSTEMS The heat sources in cable installations can be divided into two generic groups: heat generated in conductors and heat generated in insulators. Figure shows a complex cable construction, for illustration purposes, containing many of the possible layers in a cable. The losses in the metallic (conductors) elements are by far the most significant losses in a cable and they are caused by: (a) Joule losses due to impressed currents, circulating currents or induced (eddy current) losses; (b) Hysteresis losses in conductors that are also magnetic. The following metallic components of a cable system will produce heat: Core conductors Sheaths Concentric neutrals Armors Skid wires Pipes/ducts The losses in those components are functions of the frequency (f.) and the temperature (t) of operation and proportional to the square of the current (I). Customarily, the dependency with temperature and frequency is included in an equivalent resistance to express Joule law as: W = R Insulating materials also produce heat. The heat produced in the insulating layers is only important under certain high voltage conditions. The following components could be considered: Main insulation Shields Screens Jkets Beddings/servings The loss relationship is given by: W d = Gd V = ( f, t) I ω CV where C is the capitance, V is the voltage applied and δ is the loss angle. Figure. Illustration of a complex cable construction tan( δ ) () () IV. HEAT FLOW IN UNDERGROUND CABLE INSTALLATIONS In an underground cable system the main heat transfer mechanism is by conduction. With the exception of the air inside the conduits in duct banks or buried ducts installations all the heat is transferred by conduction. Since the longitudinal dimension of a cable is always much larger than the depth of the installation, the problem becomes a two-dimensional heat conduction problem. In Cartesian coordinates one must solve the diffusion equation given by []: t( x, y, t) t x y t t x y t W = c x x + (,, ) y y + (,, ) ρ ρ t where: ρ = Thermal conductivity of the material c = Volumetric thermal capity of the material W = Rate of energy (heat) generated Equation (3) cannot be solved in closed form for the complicated geometry of an underground cable arrangement (see Figure ). Additionally, numerical solutions could not be obtained in the pre-computer era (before 950's). However, cables are being installed since the 890's. Furthermore, since numerical solutions, considering all particularities of the installation, require of the solution of a large number of linear (or nonlinear) equations only with the powerful computers available nowadays, it is becoming prtical to get numerical solutions for cable rating purposes. In view of the complications of the ampity problem, engineers found prtical solutions by combining analytical solutions to simplified geometries with heuristic results. In particular the use of thermal-electrical analogies with empirical work has been very popular with cable engineers. To that effect, the paper published by Neher and McGrath in 957 [0] is remarkable; they summarized the knowledge on the ampity calculation field to that date, and today (005), the Neher-McGrath method is still being used and it is the base for the IEEE and the IEC standards. V. THE NEHER-MCGRATH METHOD The technique known as the Neher-McGrath method for ampity calculations is based on a thermal-electrical analogy method due to Pashkis and Baker (94) []. The basic idea is to subdivide the study area in layers. Then one substitutes the heat sources by current sources, the thermal resistances by electrical resistances and the thermal capitances by electrical capitances. Figure 3 shows the correspondence between the cable installation components and the electric circuit elements for steady state ampity calculations. Note that the capitances play no part in steady state ratings. To find the ampity we first note that the potential of every node in the circuit is analog to the temperature of the regions between the layers. Thus, the potential difference between the terminals of the circuits and the innermost current source represents the temperature rise of the core of the cable with respect to the ambient temperature. Therefore the temperature (3) CYME International T&D, 005
3 3 of the cable's core is the ambient temperature plus t; see Figure 4. T 4 T 3 T T t ambient t exterior W a W s ½W d ½W d Figure 3. Thermal-electrical equivalent Figure 4. Electrical equivalent From Figure 4 we can compute t as follows: t = W W T W c t conductor ( W + W + W ) T + ( W + W + W + W )( T T ) c + d + c d s c d s a 3 + To derive an expression from where the ampity can be computed directly, the heat sources (electrical losses) W 's are expressed as proportion of the conductor losses (W c ). The conductor losses are computed using the resistance and the current. Thus, by substituting the following expressions: s λ Wc Wa = in (4) and re-arranging we have: W = λ Wc W = c R I I = t Wd ( T + T + T3 + T4 ) R T + R ( + λ + λ )( T + T ) t T T T 3 T 4 W c ½W d ½W d W s W a From expression (6) one can compute the ampity of a cable. Of paramount importance for cable rating is the curate calculation of the thermal resistances T, the loss ftors λ and the resistance R of the core of the cable. The loss ftors λ take into count eddy losses induced and circulating currents, while R considers the temperature dependency of the resistances. Calculation of Thermal Resistances In the Neher-McGrath method, the thermal resistances are either computed from basic principles or from heuristics. One can appreciate, from Figure 3, that some of the internal layers of a cable can be considered as tubular geometries. The following expression is used for the computation of the thermal resistance of tubular geometries: 3 4 t 0 4 (4) (5) (6) l ρ r T = ρ = ln (7) A π r Equation (7) is applicable for most internal to the cable layers (T, T, T 3 ). For complicated geometries and for the layers external to the cable, such as three-core cables, duct banks, etc., heuristics are used. For uniformity with (7) the following expression has been proposed: ρ T = G (8) π G is called the geometrical ftor because it is a function of the shape and dimensions of the particular geometry under analysis. There are a number heuristics used in the calculation of thermal resistances. For example, there are expressions for: equally or unequally loaded cables, for touching or not touching cables, for flat or triangular formations, trefoils, bkfills, duct banks, etc. There are too many possibilities to be considered in this paper, the interested reader can find all the details in list references of this paper. Numerical methods (finite elements) have been used to determine extensions to the geometrical ftors when heuristics do not exist. The external to the cable thermal resistivity is commonly computed assuming that the surfe of the earth in the neighborhood of the cable installation is an isothermal. Kennelly made this assumption in 893 and it is still being used. This assumption allows for the application of the image method to compute the external to the cable thermal resistance (T 4 ). The following expression results from the image method: L T = ρ 4 ln (9) π D e The thermal resistance of the layers external to the cable (T 4 ) must also include the duct when present, and the air inside. The duct itself is of tubular geometry and it very easy to model, however, the treatment of the air inside of a duct is a complex matter. The heat transfer is dominated by convection and radiation and not by conduction. There exist simple formulas, which have been obtained experimentally and that work fine for the conditions tested. Loss Ftors (λ) Loss ftors in equation (5) relate to the losses that metallic layers (sheaths, armors, etc.) produce in proportion to the losses of the cable core. These losses include circulating currents and induced currents (eddy currents). The geometrical arrangements are diverse and some are quite complicated. The bonding used for sheaths (or concentric neutrals) plays a very important role in the current intensity that circulates in them. Thus the losses are very much dependent on the bonding type and the geometrical arrangement of the cables (flat or triangular formation). The possibilities are too many to be discussed in this paper; the interested reader can see all the details in references [], [3] and [4]. Currently, even finite elements ampity programs use analytical expressions to compute the losses produced in every layer of the cable installation. CYME International T&D, 005
4 4 AC Resistance The operating resistance of a cable is a function of the temperature and the frequency. The temperature variation is described by: R( t) = R0[ + α ( t t0)] (0) where: R 0 = Resistance at a base temperature (t 0 = 0 C) α = Coefficient of variation with temperature Although there exists an analytical expression, using Bessel functions, for the modeling of eddy current effects in cables, for low frequencies (50 and 60 Hz), there are very simple and curate formulas adequate for ampity calculations. The eddy current effects are included by two ftors. One considers the skin effect (y s ) and the other, the proximity effect (y p ). The mathematical expression to count for these losses is: R ( f ) = RDC( + ys + y p) () Combining (0) and () we have: R t, f ) = R [ + α ( t t )]( + y + y ) () ( 0 0 s p The values for y s and y p are computed from simplified analytical expressions particular to eh cable core construction (solid, stranded, segmented, etc.). VI. IEC VERSUS NEHER-MCGRATH A detailed description of the difference between the two methods can be found in Appendix F of []. For steady state ampity simulations the two approhes are virtually the same. The greatest difference is that the IEC equations use the metric system while Neher-McGrath use the imperial system. Thus equations look very different, but the two methods are equivalent. In the Neher-McGrath method, there are explicit equations for the transient rating, while in the IEC, detailed methodologies are given. In general, IEC methods are more up to date and consider more cases than the Neher-McGrath method. Following is a description of the most important modeling differences: Eddy Losses In the Neher-McGrath approh only the eddy losses for triangular configurations are computed. IEC includes flat formations as well. In the IEC standards the magnetic armors are considered, while they are not in the Neher-McGrath method. Thermal Resistances IEC gives expressions for geometric ftors of threecore, oil-filled, belted, etc., cables. IEC considers more insulation materials than Neher- McGrath. IEC makes a distinction between trefoil and flat configurations (touching and not touching) for T 4. IEC considers in detail unequally loaded cables. Soil dry-out is considered in IEC. VII. COMMERCIAL AMPACITY PROGRAMS The first and most advanced commercial program for cable ampity calculations is CYMCAP. Its development started in the 980's jointly by Ontario Hydro (Hydro One), McMaster University and CYME International, under the auspices of the Canadian Electricity Association (CEATI). CYMCAP is based on the IEC Standards and features a very friendly GUI (Graphical User Interfe). Over 00 companies in close to 50 countries use CYMCAP. This program can compute steady state ampities and transient ampities. CYMCAP features a duct bank optimizer and the possibility to handle several duct banks with different thermal resistivities in the same installation. USAmp is next in the development ladder. It is based on the Neher-McGrath method for steady state ampity calculations. It supports transients based on the CIGRE report [3]. It has a GUI, but data is entered and displayed mostly in tabular form. USAmp has been used to obtain the IEEE Standard tables published in []. ETAP is another tabular program based on the Neher- McGrath method. It does not support transient ampity calculations. There are other smaller programs such as: PCORP, Underground Cable Ampity Calculator, etc. with rudimentary GUI's and calculation engines. Some are royalty free, with no documentation or technical support. VIII. CYMCAP CYMCAP is a dedicated computer program for performing ampity and temperature rise calculations for power cable installations. A description of its main features is given below. Analytical Capabilities Iterative techniques based on the IEC Standards. A detailed graphical representation of virtually any type of power cable. This fility can be used to modify existing cables and enrich the program s cable library with new ones, including single-core, three-core, belted, pipe-type, submarine, sheathed, and armored cables. Different cable installation conditions such as directly buried, thermal bkfill, underground ducts, duct banks and multiple soil layers with different thermal resistivity. Cables in pipes with the pipe directly buried or in a thermal bkfill. Independent libraries and databases for cables, ductbanks, load curves, heat sources and installations. Simulation of cables on riser poles, groups of cables in air, moisture migration, nearby heat sources and heat sinks, etc. Different cable types within one installation. Non-isothermal earth surfe modeling. Cyclic loading patterns as per IEC Multiple cables per phase with proper modeling of the sheath mutual inductances, which greatly CYME International T&D, 005
5 5 influence circulating current losses, and thus derating. All bonding arrangements for flat and triangular formations are supported with explicit modeling of minor section lengths, unequal cable sping, etc. Figure 5 presents a typical graphical display screen of a duct bank installation containing trefoil arrangements, threecore cables and single-phase circuits. Also, any of its cables can be displayed and edited simultaneously. temperature as a function of time simultaneously with the load curve, the installation arrangement and the cables used. Duct Bank Optimizer The Duct Bank Optimizer is an add-on module to CYMCAP that allows the user to determine the optimal plement of several circuits within a duct bank. More specifically, the module can recommend the various circuit dispositions within the duct bank in order that: The duct bank overall ampity, i.e. the sum of the ampities for all circuits, is maximized. The duct bank overall ampity, i.e. the sum of the ampities for all circuits, is minimized. The ampity of any given circuit is maximized. The ampity of any given circuit is minimized. OPT 0,000 + Combinations Figure 5. Typical CYMCAP Screen Transient Analysis The program supports transient thermal analyses including the following: Ampity given time and temperature. Temperature analysis given time and ampity. Time to reh a given temperature, given the ampity Ampity and temperature analysis as a function of time. User-defined load profiles per circuit. Multiple cables per installation. Circuits can be loaded simultaneously or one at a time. Figure 6. Typical transient simulation report Figure 6 shows a graphical display of the results of a transient simulation. In CYMCAP one can display the 50 A 590 A Figure 7. Results of a duct bank optimization simulation Figure 7 presents a 3 by 4 duct bank with three trefoils and one three-phase circuit (one phase per conduit). There are over 0,000 possible combinations. However, CYMCAP has an elaborated mathematical algorithm that prevents the repetitive calculation of equivalent cases, therefore the solution is obtained very efficiently. The left hand side condition in Figure 7 shows the cables pled automatically. On the right-hand side one can see the optimal cable location that maximizes ampity. Multiple Duct Banks The Multiple Duct Banks module (MDB) is the extension to CYMCAP designed to determine the steady state ampity of cables installed in several neighboring duct banks and/or bkfills with different thermal resistivity. The module presents a unique solution combining standard and nonstandard calculation methods. The module computes the values of T 4 (the external to the cable thermal resistance) using finite elements and then the ampity (or operating temperature) of the cable system is obtained using the IEC standardized solution method. The following capabilities can be highlighted: Modeling up to eleven rectangular areas with different thermal resistivity. Modeling up to three duct banks in a single installation. Modeling one heat source or sink in the installation. Computation of the steady state ampity or temperature. CYME International T&D, 005
6 6 Figure 8 exemplifies two of the many possibilities that the MDB (Multiple Duck Bank) modeling filities of CYMCAP can handle. Figure 8. Illustration of the MDB module of CYMCAP Validation CYMCAP has been validated against field tests. In Figure 9 a comparison between time simulations and field tests is presented. One can appreciate that the simulated and measured results match with reasonable cury. X. REFERENCES [] George J. Anders, "Rating of Electric Power Cables: Ampity Computations for Transmission, Distribution, and Industrial Applications, IEEE Press / McGraw Hill, 997. [] IEEE Standard Power Cable Ampity Tables, IEEE Std [3] Electric Cables Calculation of the current rating Part : Current rating equations (00% load ftor) and calculation of losses Section : General. IEC Standard 87-- (994-). [4] Electric Cables Calculation of the current rating Part : Current rating equations (00% load ftor) and calculation of losses Section : Sheath eddy current loss ftors for two circuits in flat formation. IEC Standard 87-- (993-). [5] Electric Cables Calculation of the current rating Part : Thermal resistance Section : Calculation of the thermal resistance. IEC Standard 87-- (994-). [6] Electric Cables Calculation of the current rating Part : Thermal resistance Section A: A method for calculating reduction ftors for groups of cables in free air, protected from solar radiation. IEC Standard 87-- (995-05). [7] Electric Cables Calculation of the current rating Part 3: Sections on operating conditions Section : Reference operating conditions and selection of cable type. IEC Standard (995-07). [8] Calculation of the cyclic and emergency current rating of cables Part : Cyclic rating ftor for cables up to and including 8/30 (36) kv. IEC Publication 853- (985). [9] Calculation of the cyclic and emergency current rating of cables Part : Cyclic rating of cables greater than 8/30 (36) kv and emergency ratings for cables of all voltages. IEC Publication 853- (989-07). [0] J.H. Neher and M.H. McGrath, The Calculation of the Temperature Rise and Load Capability of Cable Systems, AIEE Transtions Part III - Power Apparatus and Systems, Vol. 76, October 957, pp [] V. Pashkis and H. Baker, "A method for determining the steady-state heat transfer by means of an electrical analogy", ASME Transtions, Vol. 04, pp. 05-0, 94. [] J.H. Neher, The Transient Temperature Rise of Buried Cable Systems, IEEE Transtions on Power Apparatus and Systems, Vol. PAS-83, February 964, pp See also the Discussion by McGrath. [3] CIGRE, "Current Ratings of Cables for Cycling and Emergency Loads. Part. Cyclic Rating (load ftor less than 00%) and Response to a Step Function", Electra No. 4, pp [4] Calculation of Thermally Permissible Short-Circuit Currents, Taking into Account Non-Adiabatic Heating Effects, IEC Standard 949, 988. XI. BIOGRAPHY Figure 9. CYMCAP simulations versus field tests CYME offers the very best customer support with the commitment of answering support questions within 4 hours. Additionally, CYME holds a one-day CYMCAP seminar during its yearly User's Group in Montreal. IX. SUMMARY An introduction to the heat transfer mechanisms in underground cable installations was given. An analysis of the possible solution methods of the diffusion equations was presented. A description of the heat sources and thermal resistances of the different layers of a cable installation has been offered. The basic concepts behind the Neher-McGrath method were discussed together with the differences between the IEEE (Neher-McGrath method) and the IEC standards for underground cable installations. A description of the modeling capabilities CYMCAP, CYME's cable ampity program, was presented. Francisco de León was born in Mexico City in 959. He received the B.Sc. and the M.Sc. (summa cum laude) degrees in Electrical Engineering from the National Polytechnic Institute (Mexico), in 983 and 986 respectively, and obtained his Ph.D. degree from the University of Toronto, Canada, in 99. He has held several ademic positions in Mexico and has worked for the Canadian electric industry. Currently working with CYME International T&D in St. Bruno (Quebec, Canada), he develops professional grade software for power and distribution systems and is the leading technical support of CYMCAP, CYME's cable ampity program. He has published over a dozen papers in refereed journals (IEEE/IEE), which have been cited over 00 times in journals listed in the Science Citation Index. Francisco is a Senior Member of the IEEE. CYME International T&D, 005
Direction of current flow through conductor. Fig. 1 Magnetic field generated by current flow
ingle Conductor Cable Copper heathed Cable heath Currents ingle conductor cables present certain application considerations that do not arise in multiconductor cable installations. These considerations
Current Ratings. TABLE BEC 107. (Continued) Current ratings for 6350/11000 volts grade PILC/SWA/PVC cable to BS6480/69
Ratings TBLE BEC 107. (Continued) ratings for 60/11000 volts grade PILC/SW/PVC cable to BS64/69 CBLES LID IN IR: The ratings given in the foregoing tables are based on an ambient of C. It is recommended
Offshore Wind Farm Export Cable Current Rating Optimisation
Offshore Wind Farm Export Cable Current Rating Optimisation James Pilgrim 1, Simon Catmull 2, Richard Chippendale 1, Richard Tyreman 3 and Paul Lewin 1 1. Tony Davies High Voltage Laboratory, Southampton
4 IX D N E P P A Installation methods Current-carrying capacity and voltage drop for cables Reference method IET Wiring Matters
8 Appendix 4 of BS 7671 by Mark Coles Appendix 4, Current-carrying capacity and voltage drop for cables and flexible cords, has seen significant changes with the publishing of BS 7671:2008. This article
Effects of the circulating sheath currents in the magnetic field generated by an underground power line
Effects of the circulating sheath currents in the magnetic field generated by an underground power line J.R. Riba Ruiz 1, X. Alabern Morera 2 1 Department d'enginyeria Elèctrica, UPC EUETII-"L'Escola d'adoberia"
FEASIBILITY OF ELECTRICAL SEPARATION OF PROXIMATE GROUNDING SYSTEMS AS A FUNCTION OF SOIL STRUCTURE
FEASIBILITY OF ELECTRICAL SEPARATION OF PROXIMATE GROUNDING SYSTEMS AS A FUNCTION OF SOIL STRUCTURE Sharon Tee and Farid P. Dawalibi Safe Engineering Services & technologies ltd. 1544 Viel, Montreal, Quebec,
EARTHING SYSTEM CALCULATION
BAZIAN STEAL FACTORY S/S 132/11kV, 1x30/40MVA EARTHING SYSTEM CALCULATION Kurdistan Region Sulaimani May 2011 Bazian Steal Factory S/S 132/11kV, 1x30/40 MVA Contents: 1. Introduction... 3 2. List of references
Motor-CAD Software for Thermal Analysis of Electrical Motors - Links to Electromagnetic and Drive Simulation Models
Motor-CAD Software for Thermal Analysis of Electrical Motors - Links to Electromagnetic and Drive Simulation Models Dave Staton, Douglas Hawkins and Mircea Popescu Motor Design Ltd., Ellesmere, Shropshire,
6 ELECTRICAL PARAMETERS
6 ELECTRICAL PARAMETERS For power, low voltage and medium voltage cables, cross section nominal areas are calculated in taking into account several parameters as: permissible current carrying capacities
Cable Size Selection for Energy Efficiency
Cable Size Selection for Energy Efficiency Introduction The traditional method for determining the appropriate cable size for a particular installation involves the selection of the smallest size conductor
Modeling of Transmission Lines
Modeling of Transmission Lines Electric Power Transmission The electric energy produced at generating stations is transported over high-voltage transmission lines to utilization points. The trend toward
SLOT FRINGING EFFECT ON THE MAGNETIC CHARACTERISTICS OF ELECTRICAL MACHINES
Journal of ELECTRICAL ENGINEERING, VOL. 60, NO. 1, 2009, 18 23 SLOT FRINGING EFFECT ON THE MAGNETIC CHARACTERISTICS OF ELECTRICAL MACHINES Mohammad B. B. Sharifian Mohammad R. Feyzi Meysam Farrokhifar
HARMONIC distortion in low voltage electrical installations. Cable Heating Effects due to Harmonic Distortion in Electrical Installations
Cable Heating Effects due to Harmonic Distortion in Electrical Installations Kevin O Connell, Martin Barrett, Jonathan Blackledge and Anthony Sung Abstract The increasing use of non-linear loads in electrical
Effects of Cell Phone Radiation on the Head. BEE 4530 Computer-Aided Engineering: Applications to Biomedical Processes
Effects of Cell Phone Radiation on the Head BEE 4530 Computer-Aided Engineering: Applications to Biomedical Processes Group 3 Angela Cai Youjin Cho Mytien Nguyen Praveen Polamraju Table of Contents I.
The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies
The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies DATE: November 17, 1999 REVISION: AUTHOR: John Merrell Introduction In some short circuit studies, the X/R ratio is ignored when comparing
M. GELDON Brugg Kabel CZ. Ing. D. RÚŽEK PREdistribuce. Switzerland Czech Rep. Czech Rep. Czech Rep., Switzerland Germany
21, rue d Artois, F-75008 PARIS Paper number CIGRE 2012 http : //www.cigre.org 6 characters (to be provided later) Correlation between calculated transmission capacity and actual one D. WALD* Eifelkabel
High Voltage Systems. Today. The history of cables
High Voltage Cables High Voltage Systems Today Prysmian Cables and Systems B.V. is part of the Prysmian Group, a leading player in the industry of high-technology cables and systems for energy and telecommunications,
Session 14 Cable Support Systems
Session 14 Cable Support Systems Cable Support Systems in the IEC World A new IEC Standard, IEC61537 2001 has been developed If full details of the cabling layout are available then the likely cable load
Current and Temperature Ratings
Document 361-1 Current and Temperature Ratings Introduction This application note describes: How to interpret Coilcraft inductor current and temperature ratings Our current ratings measurement method and
MV CABLE TYPE C 33-226
MV CABLE TYPE C 33-226 Standards : CENELEC HD 620 C 33-226 Rated voltage Rated voltage : 12/20 (24) kv Design 1 Stranded aluminium, class 2 conductor 2 Extruded conducting screen on conductor 3 XLPE insulation
Effect of design parameters on temperature rise of windings of dry type electrical transformer
Effect of design parameters on temperature rise of windings of dry type electrical transformer Vikas Kumar a, *, T. Vijay Kumar b, K.B. Dora c a Centre for Development of Advanced Computing, Pune University
CONFLEX ELECTRIC CABLE
CONFLEX ELECTRIC CABLE CONFLEX - 0.6/1kV Flexible VSD/EMC Cables Applications WW VSD/EMC cables are manufactured for use where electrical interference distorts signal transmission in electric motors. Standard
ENERGY. TECWATER S1BN8-F 0,6/1 kv. Cable for Water Application
ENERGY TECWATER S1BN8-F 0,6/1 kv Cable for Water Application Technical Data Electrical parameters Thermal parameters Trademark Type designation Specification Approval Application Rated voltage Maximum
Coupling Effect in Substation Ground Measurements
SERBIAN JOURNAL OF ELECTRICAL ENGINEERING Vol. 9, No. 3, October 2012, 315-324 UDK: 621.316.13.011.2 DOI: 10.2298/SJEE1203315F Coupling Effect in Substation Ground Measurements Alex Farber 1, Boris Katz
MEDIUM VOLTAGE CABLES Up to and including 36 KV
MEDIUM VOLTAGE CABLES Up to and including 6 KV NOTICE As this catalogue is not intendedto cover all of LIBAN CABLES SAL possibilities in special cables manufacturing, the hereafter listing of the types
COMPUTATION OF THREE-DIMENSIONAL ELECTRIC FIELD PROBLEMS BY A BOUNDARY INTEGRAL METHOD AND ITS APPLICATION TO INSULATION DESIGN
PERIODICA POLYTECHNICA SER. EL. ENG. VOL. 38, NO. ~, PP. 381-393 (199~) COMPUTATION OF THREE-DIMENSIONAL ELECTRIC FIELD PROBLEMS BY A BOUNDARY INTEGRAL METHOD AND ITS APPLICATION TO INSULATION DESIGN H.
Ampacity simulation of a high voltage cable to connecting off shore wind farms
Ampacity simulation of a high voltage cable to connecting off shore wind farms Eva Pelster 1, Dr. David Wenger 1 1 Wenger Engineering GmbH, Einsteinstr. 55, 89077 Ulm, [email protected] Abstract:
SES Training & Certification Programs Welcome to the SES Grounding, EMI and Lightning Academy
SES Training & Certification Programs Welcome to the SES Grounding, EMI and Lightning Academy A Center of Excellence, Where Experts are Created and Certified 1 SES: Training You and Your Staff to Carry
GroundRod AC Substation Earthing Tutorial
1 GroundRod AC Substation Earthing Tutorial 1. Functions of an earthing system The two primary functions of a safe earthing system are: To ensure that a person who is in the vicinity of earthed facilities
Underground Cable Temperature Monitoring in the Real World
Underground Cable Temperature Monitoring in the Real World Executive Summary Background Brain Storming Possible Causes to Duct Bank Over Heating Mitigating Duct Bank Overheating DTS Installation for Duct
Substation Grounding Study Specification
Substation Grounding Study Specification Introduction A grounding study is required for name of station, a / / kv substation located in name of location and connected to the following circuits: number
Frequency-dependent underground cable model for electromagnetic transient simulation
Frequency-dependent underground cable model for electromagnetic transient simulation Vasco José Realista Medeiros Soeiro Abstract A computation method for transients in a three-phase underground power-transmission
Selecting IHLP Composite Inductors for Non-Isolated Converters Utilizing Vishay s Application Sheet
VISHAY DALE www.vishay.com Magnetics Selecting IHLP Composite Inductors for Non-Isolated Converters INTRODUCTION This application note will provide information to assist in the specification of IHLP composite
Integration of a fin experiment into the undergraduate heat transfer laboratory
Integration of a fin experiment into the undergraduate heat transfer laboratory H. I. Abu-Mulaweh Mechanical Engineering Department, Purdue University at Fort Wayne, Fort Wayne, IN 46805, USA E-mail: [email protected]
Power over Ethernet Requirements and Limitations due to the Cabling System
Power over Ethernet Requirements and Limitations due to the Cabling System Power over Ethernet - Code Requirements and Approvals - the meaning of Cable Rating in NEC and UL 444/CSA 22.2 No. 214 (and any
HIGH VOLTAGE XLPE CABLE SYSTEMS. Technical User Guide
HIGH VOLTAGE XLPE CABLE SYSTEMS Technical User Guide Content 1. General information on High Voltage XLPE Cable Systems 1.1. Introduction 1.2. Cable selection process 1.3. Service life 3 3 3 4 2. Cable
Heat Transfer Prof. Dr. Aloke Kumar Ghosal Department of Chemical Engineering Indian Institute of Technology, Guwahati
Heat Transfer Prof. Dr. Aloke Kumar Ghosal Department of Chemical Engineering Indian Institute of Technology, Guwahati Module No. # 02 One Dimensional Steady State Heat Transfer Lecture No. # 05 Extended
Gulf Cable & Electrical Ind. Co.
CONTENTS INTRODUCTION PRODUCT RANGE I PRODUCT DATA TABLES XLPE INSULATED 600/1000V CABLES Two Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC 1 Three Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC 2 Four Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC
AS COMPETITION PAPER 2007 SOLUTIONS
AS COMPETITION PAPER 2007 Total Mark/50 SOLUTIONS Section A: Multiple Choice 1. C 2. D 3. B 4. B 5. B 6. A 7. A 8. C 1 Section B: Written Answer Question 9. A mass M is attached to the end of a horizontal
Calculation of Temperature in a Large Turbine Generator with Multilayer Roebel Transposition Coils
Calculation of Temperature in a Large Turbine Generator with Multilayer Roebel Transposition Coils Kenichi Hattori *, Kazuhiko Takahashi, Kazumasa Ide, Keiji Kobashi, Hiroshi Okabe, and Takashi Watanabe
Module 1 : Conduction. Lecture 5 : 1D conduction example problems. 2D conduction
Module 1 : Conduction Lecture 5 : 1D conduction example problems. 2D conduction Objectives In this class: An example of optimization for insulation thickness is solved. The 1D conduction is considered
General Calculations. Excerpt from PRYSMIAN S WIRE AND CABLE ENGINEERING GUIDE
Excerpt from PRYMIAN WIRE AND CABLE ENGINEERING GUIDE Page 1 of 0 Voltage Rating The selection of the cable insulation level to be used in a particular installation shall be made on the basis of the applicable
POWER AND VOLTAGE RATING
POWER AND VOLTAGE RATING SCOPE: The purpose of this document is to take the confusion out of power and voltage ratings in specifications and in product information publications. This will be accomplished
Two-Dimensional Conduction: Shape Factors and Dimensionless Conduction Heat Rates
Two-Dimensional Conduction: Shape Factors and Dimensionless Conduction Heat Rates Chapter 4 Sections 4.1 and 4.3 make use of commercial FEA program to look at this. D Conduction- General Considerations
Estimating Line-Flow Limits
Estimating Line-Flow Limits University of Wisconsin-Madison May 1, 2013 Specifying reasonable line-flow limits requires two quantities: the surge impedance loading for the line and an estimate of the line
AS COMPETITION PAPER 2008
AS COMPETITION PAPER 28 Name School Town & County Total Mark/5 Time Allowed: One hour Attempt as many questions as you can. Write your answers on this question paper. Marks allocated for each question
Network Standard Advice No. 1420C 9/6/2011
Network Standard Advice No. 1420C 9/6/2011 TO: Customers, Service Providers and Ausgrid Staff. Advisory Note on Changes to the Use of 11kV Cable Types. Introduction This Network Standard Advice (NSA) provides
NUMERICAL SIMULATION OF BIOHEAT TRANSFER PROCESS IN THE HUMAN EYE USING FINITE ELEMENT METHOD
Scientific Research of the Institute of Mathematics and Computer Science NUMERICAL SIMULATION OF BIOHEAT TRANSFER PROCESS IN THE HUMAN EYE USING FINITE ELEMENT METHOD Marek Paruch Department for Strength
Eðlisfræði 2, vor 2007
[ Assignment View ] [ Print ] Eðlisfræði 2, vor 2007 30. Inductance Assignment is due at 2:00am on Wednesday, March 14, 2007 Credit for problems submitted late will decrease to 0% after the deadline has
Conductor Sizing and the National Electrical Code
Conductor Sizing and the National Electrical Code The National Electrical Code requirements for conductor sizing and overcurrent protection have always been confusing and complex. Factors that must be
Comparison of Power Título Transmission Line Models with Finite Elements
CEPEL Comparison of Power Título Transmission do trabalho Line Models with Finite Elements Carlos K. C. Arruda, Anny A. Silveira, Fernando C. Dart Autor/apresentador Área Departamento de Linhas e Estações
Heat Transfer and Energy
What is Heat? Heat Transfer and Energy Heat is Energy in Transit. Recall the First law from Thermodynamics. U = Q - W What did we mean by all the terms? What is U? What is Q? What is W? What is Heat Transfer?
Chapter 15: Transformer design
Chapter 15 Transformer Design Some more advanced design issues, not considered in previous chapter: : n Inclusion of core loss + + Selection of operating flux i 1 density to optimize total loss v 1 v Multiple
Cables, Cable Laying & Accessories Manual
Distribution Business Cables, Cable Laying & Accessories Manual Database ref: File Ref: Title Page & Revision Log For Cables & Access v4 - Nov 2003.doc Manual Name: Cables & Accessories Manual Version
Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
Effect of Aspect Ratio on Laminar Natural Convection in Partially Heated Enclosure
Universal Journal of Mechanical Engineering (1): 8-33, 014 DOI: 10.13189/ujme.014.00104 http://www.hrpub.org Effect of Aspect Ratio on Laminar Natural Convection in Partially Heated Enclosure Alireza Falahat
Edmund Li. Where is defined as the mutual inductance between and and has the SI units of Henries (H).
INDUCTANCE MUTUAL INDUCTANCE If we consider two neighbouring closed loops and with bounding surfaces respectively then a current through will create a magnetic field which will link with as the flux passes
Resistor Theory and Technology
Resistor Theory and Technology Felix Zandman Chairman, Scientific Director, and CEO, Vishay Intertechnology, Inc. Paul-Rene Simon Consultant Joseph Szwarc Chief Engineer, Vishay Israel Ltd SciTECH PUBLISHING;
Heat Transfer Prof. Dr. Ale Kumar Ghosal Department of Chemical Engineering Indian Institute of Technology, Guwahati
Heat Transfer Prof. Dr. Ale Kumar Ghosal Department of Chemical Engineering Indian Institute of Technology, Guwahati Module No. # 04 Convective Heat Transfer Lecture No. # 03 Heat Transfer Correlation
WHITEPAPER CABLE CONDUCTOR SIZING
WHITEPAPER CABLE CONDUCTOR SIZING FOR MINIMUM LIFE CYCLE COST Bruno De Wachter, Walter Hulshorst, Rodolfo di Stefano July 2011 ECI Available from www.leonardo-energy.org/node/156451 Document Issue Control
Using NTC Temperature Sensors Integrated into Power Modules
Using NTC Temperature Sensors Integrated into Power Modules Pierre-Laurent Doumergue R&D Engineer Advanced Power Technology Europe Chemin de Magret 33700 Mérignac, France Introduction Most APTE (Advanced
CABLE MONITORING SOLUTION
POWER CABLE MONITORING SOLUTION Kuljit Singh BSc Honours MIEE(IET,UK) Dan Watley Ph. D, B.A MEng (UK), MIEEE, UK 8-9 November 2011 PREDICT WITH CERTAINTY Definition DTS: Distributed Temperature Sensor
DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION
ÿþ üûúùø öõöôùóùõò CT Dimensioning DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION Application note GER3973 1 CT Dimensioning ÿþ üûúùø öõöôùóùõò GER-3973 Application note ÿþ üûúùø öõöôùóùõò
Survey of Harmonics Measurements in Electrical Distribution Systems
Survey of Harmonics Measurements in Electrical Distribution Systems Leon M. Tolbert, Member, IEEE Oak Ridge National Laboratory* P.O. Box 28, Bldg Oak Ridge, TN 3783-6334 Alexandria, VA 2235-3862 Phone:
Electrical Design Training Class Ampacity WSDOT Winter 2008 BZA
Electrical Design Training Class Ampacity WSDOT Winter 2008 BZA presented by: Keith Calais 1 What is it? Ampacity is the current, in Amperes, that a conductor can carry continuously under the conditions
Dynamic Process Modeling. Process Dynamics and Control
Dynamic Process Modeling Process Dynamics and Control 1 Description of process dynamics Classes of models What do we need for control? Modeling for control Mechanical Systems Modeling Electrical circuits
Objectives. Capacitors 262 CHAPTER 5 ENERGY
Objectives Describe a capacitor. Explain how a capacitor stores energy. Define capacitance. Calculate the electrical energy stored in a capacitor. Describe an inductor. Explain how an inductor stores energy.
THE PATHWAY TO POWER HIGH-VOLTAGE CABLES
THE PATHWAY TO POWER HIGH-VOLTAGE CABLES TABLE OF CONTENTS HIGH-VOLTAGE CABLES 3 Advantages of XLPE-insulated cable systems 3 PROPOSAL 4 Cable systems 4 Providing System Solutions 4 Continuous temperature
Adaptation of General Purpose CFD Code for Fusion MHD Applications*
Adaptation of General Purpose CFD Code for Fusion MHD Applications* Andrei Khodak Princeton Plasma Physics Laboratory P.O. Box 451 Princeton, NJ, 08540 USA [email protected] Abstract Analysis of many fusion
Radial Distribution Test Feeders
Radial Distribution Test Feeders Distribution System Analysis Subcommittee Report Abstract: Many computer programs are available for the analysis of radial distribution feeders. In 1992 a paper was published
Steady Heat Conduction
Steady Heat Conduction In thermodynamics, we considered the amount of heat transfer as a system undergoes a process from one equilibrium state to another. hermodynamics gives no indication of how long
EDS 02-0027 11KV TRIPLEX CABLE
THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE Document Number: EDS 02-0027 ENGINEERING DESIGN STANDARD EDS 02-0027 11KV TRIPLEX CABLE Network(s): EPN, LPN, SPN Summary:
Numerical Simulation of Temperature and Stress Fields in the Rock Heating Experiment
Numerical Simulation of Temperature and Stress Fields in the Rock Heating Experiment Author P. Rálek 1*, M. Hokr 1 1 Technical University of Liberec, Liberec, Czech Republic *Corresponding author: [email protected]
Numerical Model for the Study of the Velocity Dependence Of the Ionisation Growth in Gas Discharge Plasma
Journal of Basrah Researches ((Sciences)) Volume 37.Number 5.A ((2011)) Available online at: www.basra-science -journal.org ISSN 1817 2695 Numerical Model for the Study of the Velocity Dependence Of the
Iron Powder Cores for Switchmode Power Supply Inductors. by: Jim Cox
HOME APPLICATION NOTES Iron Powder Cores for Switchmode Power Supply Inductors by: Jim Cox Purpose: The purpose of this application note is to cover the properties of iron powder as a magnetic core material
Optimization of electronic devices placement on printed circuit board
Optimization of electronic devices placement on printed circuit board Abstract by M. Felczak, T.Wajman and B. Więcek Technical University of Łódź, Wólczańska 211/215, 90-924 Łódź, Poland Power densities
Lecture 3 Fluid Dynamics and Balance Equa6ons for Reac6ng Flows
Lecture 3 Fluid Dynamics and Balance Equa6ons for Reac6ng Flows 3.- 1 Basics: equations of continuum mechanics - balance equations for mass and momentum - balance equations for the energy and the chemical
Power Electronics. Prof. K. Gopakumar. Centre for Electronics Design and Technology. Indian Institute of Science, Bangalore.
Power Electronics Prof. K. Gopakumar Centre for Electronics Design and Technology Indian Institute of Science, Bangalore Lecture - 1 Electric Drive Today, we will start with the topic on industrial drive
Development of Specialized Modelling Tools for Crystal Growth Processes
International Scientific Colloquium Modelling for Material Processing Riga, June 8-9, 2006 Development of Specialized Modelling Tools for Crystal Growth Processes A. Rudevics, A. Muiznieks, B. Nacke, V.
Power Dissipation Considerations in High Precision Vishay Sfernice Thin Film Chips Resistors and Arrays (P, PRA etc.) (High Temperature Applications)
VISHAY SFERNICE Resistive Products Application Note ABSTRACT On our thin film chips resistors and arrays the main path for the heat, more than 90 %, is conduction through the body of the component, the
TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS. What Is Tan δ, Or Tan Delta?
TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS What Is Tan δ, Or Tan Delta? Tan Delta, also called Loss Angle or Dissipation Factor testing, is a diagnostic method of testing
However, industrial applications may utilize a relay, which short-circuits the ICL path after the inrush sequence.
Application note for Inrush Current Limiters (ICL) Turning on electrical devices generally cause high inrush currents which can damage electronic components and cause interruption of the line voltage if
CHAPTER 2 EXAMPLES AND TABLES
CHAPTER 2 EXAMPLES AND TABLES COMMENTARY AT 210.20(A) EXCEPTION An overcurrent device that supplies continuous and noncontinuous loads must have a rating that is not less than the sum of 100 percent of
Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.
By Darrell G. Broussard, P.E. Introduction: As engineers, we are aware that electrical power systems have grown. How much have they grown? When was the last time you specified a 2400-volt system, a 4160-volt
WEEKLY SCHEDULE. GROUPS (mark X) SPECIAL ROOM FOR SESSION (Computer class room, audio-visual class room)
SESSION WEEK COURSE: THERMAL ENGINEERING DEGREE: Aerospace Engineering YEAR: 2nd TERM: 2nd The course has 29 sessions distributed in 14 weeks. The laboratory sessions are included in these sessions. The
XLPE Land Cable Systems User s Guide. Rev 5
XLPE Land Cable Systems User s Guide Rev 5 CONTENT XLPE Land Cable Systems Introduction... 3 Design, installation and testing... 4 XLPE cables... 4 Cable accessories... 4 Installation of XLPE cable systems...
INVESTIGATION OF ELECTRIC FIELD INTENSITY AND DEGREE OF UNIFORMITY BETWEEN ELECTRODES UNDER HIGH VOLTAGE BY CHARGE SIMULATIO METHOD
INVESTIGATION OF ELECTRIC FIELD INTENSITY AND DEGREE OF UNIFORMITY BETWEEN ELECTRODES UNDER HIGH VOLTAGE BY CHARGE SIMULATIO METHOD Md. Ahsan Habib, Muhammad Abdul Goffar Khan, Md. Khaled Hossain, Shafaet
Laminar Flow and Heat Transfer of Herschel-Bulkley Fluids in a Rectangular Duct; Finite-Element Analysis
Tamkang Journal of Science and Engineering, Vol. 12, No. 1, pp. 99 107 (2009) 99 Laminar Flow and Heat Transfer of Herschel-Bulkley Fluids in a Rectangular Duct; Finite-Element Analysis M. E. Sayed-Ahmed
EVALUATION OF ON-SITE DIELECTRIC RESPONSE METHODS FOR NON- DESTRUCTIVE TESTING OF WATER TREED MV XLPE CABLES
EVALUATION OF ON-SITE DIELECTRIC RESPONSE METHODS FOR NON- DESTRUCTIVE TESTING OF WATER TREED MV XLPE CABLES Sverre Hvidsten*, Peter Werelius**, Jørgen Christensen*** * SINTEF Energy Research (SEfAS),
Estimation results on the location error when using cable locator
Estimation results on the location error when using cable locator HITOSHI KIJIMA TOMOHIKO HATTORI Tokaigakuin University 5-68 Naka Kirino Kagamigahara, Gifu 504-8511 JAPAN [email protected], [email protected]
Voltage Loss Formula s
www.litz-wire.com HM Wire International Inc. Phone: 330-244-8501 Fax: 330-244-8561 Voltage Loss Formula s www.hmwire.com Voltage loss in a wire is synonymous to pressure loss in a pipe. Electric current
State, trends and evolutions of HV/EHV power cables systems and contributions of SC B1 to their ongoing progress
0611-048-Mep229 12/12/06 6:44 Page 22 State, trends and evolutions of HV/EHV power cables systems and contributions of SC B1 to their ongoing progress Reinhard SCHROTH, Chairman of SC B1 2002-2006 High
Grounding Demystified
Grounding Demystified 3-1 Importance Of Grounding Techniques 45 40 35 30 25 20 15 10 5 0 Grounding 42% Case 22% Cable 18% Percent Used Filter 12% PCB 6% Grounding 42% Case Shield 22% Cable Shielding 18%
Carbon Cable. Sergio Rubio Carles Paul Albert Monte
Carbon Cable Sergio Rubio Carles Paul Albert Monte Carbon, Copper and Manganine PhYsical PropERTieS CARBON PROPERTIES Carbon physical Properties Temperature Coefficient α -0,0005 ºC-1 Density D 2260 kg/m3
An equivalent circuit of a loop antenna.
3.2.1. Circuit Modeling: Loop Impedance A loop antenna can be represented by a lumped circuit when its dimension is small with respect to a wavelength. In this representation, the circuit parameters (generally
Fault location on power cables. Fault location on power cables
Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 01. Introduction Fault location on communication and power cables
Glencoe. correlated to SOUTH CAROLINA MATH CURRICULUM STANDARDS GRADE 6 3-3, 5-8 8-4, 8-7 1-6, 4-9
Glencoe correlated to SOUTH CAROLINA MATH CURRICULUM STANDARDS GRADE 6 STANDARDS 6-8 Number and Operations (NO) Standard I. Understand numbers, ways of representing numbers, relationships among numbers,
HOW ACCURATE ARE THOSE THERMOCOUPLES?
HOW ACCURATE ARE THOSE THERMOCOUPLES? Deggary N. Priest Priest & Associates Consulting, LLC INTRODUCTION Inevitably, during any QC Audit of the Laboratory s calibration procedures, the question of thermocouple
THERMAL DESIGN AND TEST REQUIREMENTS FOR OUTSIDE PLANT CABLE TELECOMMUNICATIONS EQUIPMENT Al Marshall, P.E. Philips Broadband Networks
THERMAL DESIGN AND TEST REQUIREMENTS FOR OUTSIDE PLANT CABLE TELECOMMUNICATIONS EQUIPMENT Al Marshall, P.E. Philips Broadband Networks Abstract Shrinking thermal margins, driven by sophisticated but thermally
TWO-DIMENSIONAL FINITE ELEMENT ANALYSIS OF FORCED CONVECTION FLOW AND HEAT TRANSFER IN A LAMINAR CHANNEL FLOW
TWO-DIMENSIONAL FINITE ELEMENT ANALYSIS OF FORCED CONVECTION FLOW AND HEAT TRANSFER IN A LAMINAR CHANNEL FLOW Rajesh Khatri 1, 1 M.Tech Scholar, Department of Mechanical Engineering, S.A.T.I., vidisha