Electrical Preventive Maintenance Pays Off! A case study on controlling risks to plant & profits
|
|
|
- Whitney Washington
- 10 years ago
- Views:
Transcription
1 Electrical Preventive Maintenance Pays Off! A case study on controlling risks to plant & profits Joe Gierlach ~ Director, Technical Training and Support TEGG Corporation ~ Pittsburgh, PA ABSTRACT: Electrical power has become the life blood of our everyday needs. In a manufacturing environment where today s lean manufacturing and just in time delivery philosophies are making reliability and plant uptime more critical than ever before, dependable electrical distribution is not an option it is critical to corporate fiscal health. What would be the impact on your company if a major component in your facility s electrical distribution system experienced a catastrophic failure? What would happen to your plant s production line, data center or distribution center? Would the lost opportunity revenue, added to the repair or replacement costs for critical equipment, be more or less than the dollars saved by not having a proactive Electrical Preventive Maintenance (EPM) program in place? What if the cost of damaged customer loyalty and satisfaction are taken into consideration? Let s take a look at a recent real life example where a costly disaster was averted because of an effective EPM program. INTRODUCTION: Global competition has forced production quotas in many companies and industries to increase. At the same time, many of these companies have experienced a reduction in their labor force and maintenance budgets as organizations attempt to improve their bottom lines, increase productivity, improve cash flow, and lower operating costs. Now consider that the typical useful service life of electrical equipment is generally years depending on maintenance and upkeep, and much of our aging infrastructure equipment has been in service for 20 years or more while receiving less than the recommended annual service regimen. Ultimately, companies are finding that catastrophic failure is the unintended consequence of exposing their electrical distribution equipment to extended stresses, more extreme environmental operating conditions, and additional load demands from facility upgrades. Depending on the criticality of the equipment, an arc flash or other destructive electrical failure can literally devastate a planned maintenance budget while the associated downtime and resulting interruptions to processes can affect revenue, profits, and ultimately stock prices in some cases.
2 Production and Reliability Managers face a very real challenge as they try to balance the demands and goals of management, customers, and equipment reliability. Resources such as NFPA 70B can give these managers a clear direction in their effort to enlist the support of others to reduce the risk of catastrophic failures through an EPM program, thereby safeguarding and enhancing profitability. The NFPA (National Fire Protection Association) has developed some of the world s most referenced and respected codes for fire and electrical safety by enlisting a broad consensus of experts. NFPA 70B (4.1) clearly outlines the benefits and details of an effective EPM program stating that dependability can be engineered and built into equipment, but effective maintenance is required to keep it dependable. Experience shows that equipment lasts longer and performs better when covered by an EPM (Electrical Preventative Maintenance) program. The NFPA 70B goes on to state that Infrared inspections of electrical systems are beneficial to reduce the number of costly and catastrophic equipment failures and unscheduled plant shutdowns. The standard recommends that routine infrared inspections of energized electrical systems should be performed annually prior to shutdown. More frequent infrared inspections, for example, quarterly or semiannually, should be performed where warranted by loss experience, installation of new electrical equipment, or changes in environmental, operational, or load conditions. Infrared surveys should be performed during periods of maximum possible loading but not less than 40 percent of rated load of the electrical equipment being inspected. A key to enabling managers to accomplish the goals of NFPA 70B and safeguarding plant assets by reducing or eliminating risks to plant and personnel, is to design an EPM program which is minimally disruptive to operations so that they are also able to meet the demands of increased production and profitability. This is where the expertise of the professionals at TEGG Services pays dividends providing tangible value with services tailored for specific objectives and implemented without interruption to operations. Case Study Feyen Zylstra, LLC, a large electrical contractor located in Grand Rapids, Michigan, secured an Electrical Preventive Maintenance (EPM) program with a new customer located in Middleville, Michigan. The maintenance agreement included a value added product and service that was comprised of the installation of 40 IRISS infrared windows (or IR viewing panes ) on the critical 8.3 KV equipment throughout the facility.
3 Bradford White Corporation, an employeeowned organization, has been manufacturing products ranging from tubs to water heaters since Production runs 24 hours per day, 6 days per week with approximately 1600 employees. Craig Potter, Facility Electrical Engineer, has been with the organization for the past 18 years and in his current position for the past 12 years. There are traditionally two weeks per year (in July and November) that are earmarked for maintenance shutdown in the facility. Reliability and minimal downtime topped the list of the facility s planning priorities. The two scheduled maintenance weeks cause production to cease, which in turn impacts the organization s profitability. With these concerns in mind, Mr. Potter quickly recognized the benefit of protecting the facility s profitability by minimizing the risk of electric failures which could cause unscheduled outages. However, it was also important that any such solutions could not interfere with their production and processes. IRISS VPFR IR Window Figure #1 scheduled maintenance shutdown on July first at Bradford White. A crew of 11 technicians completed the installations and performed cleaning and housekeeping tasks on the high voltage equipment at that time. Feyen Zylstra and TEGG were able to demonstrate to Mr. Potter how an EPM program could be implemented to ensure the health of his power distribution while being totally transparent to his production schedule and processes while eliminating added arc flash risks during surveys. Mr. Potter worked with the maintenance sales professionals at Feyen Zylstra to identify the operation s most critical equipment and processes. The result was a detailed, custom road map to help ensure uptime and profitability by reducing risk to the facility s core processes through the implementation of an EPM. Execution of the service plan started within weeks. The first phase of implementing the program was to install the 40 IRISS VPFR infrared windows (as seen in Figure #1) during the Once this task was completed over the holiday weekend, Feyen Zylstra s certified technicians, Mark DenHartigh and Bruce Boer (Figure #2), began to conduct the energized maintenance services. Mark DenHartigh & Bruce Boer Figure #2
4 DenHartigh has been applying the TEGG Services for Feyen Zylstra since the completion of his initial technical training in Pittsburgh, PA, in July 2005, and Boer completed his initial training in June The technicians received training on TEGGTask maintenance tasking software, ultrasonic testing, TEGG/ASNT Level I infrared certification, power quality, and NFPA 70E electrical safe work practice training. An Anomaly is Discovered: During the second week of the service, the technicians identified a thermal exception on one of the 8.3 KV Cutler Hammer Load Interrupter Switches. These switches are a critical part of the facility s power distribution system, feeding a 2000 KVA transformer which reduces the voltage to 480 volts for distribution to much of the production equipment. Due to the criticality of this switch and the process it is involved with, it was one of the pieces of equipment which had received the installation of an infrared window. Because the IR windows gave the thermographers access to thermographic data of energized components while the panel covers remained closed, the surveys could be performed safely and efficiently without disruption to processes and without the added risk of arc flash associated with openpanel inspections. DenHartigh identified the line side of the B Phase 14.4 KV, 200 amp fuse as the area of interest. At this time (second week of service), the spot temperature of the fuse displayed 64 C (147 F) on the infrared camera. The source of the temperature was oxidized aluminum, and it is important to note that the initial temperature calculation was uncompensated and did not correct for the low Emissivity of the target. Emissivity represents the efficiency at which an object emits infrared radiation; infrared radiation is what an infrared imager or camera detects and uses to calculate temperatures. The less efficiently an object emits radiation, the lower the temperature would appear to the camera (if the object is at a higher temperature than the reflected background radiation). Although an object may be experiencing a significant temperature, the camera s interpretation of the temperature of this low Emissivity target would be dramatically lower since the amount of emitted radiation is significantly less than if the target was made of a higher Emissivity material (ie. a more efficient emitter of infrared radiation). Refer to Stefan Boltzmann law of W = σt 4. The area of concern on the top of the fuse is clearly visible in Figure #3. This image was taken through a VPFR Figure #3
5 infrared window with the camera s parameters properly configured to compensate for the external optics (including Transmissive properties of the window and window temperature). The problem temperature ( Prob on the screen shot) is indicating 64 C (147 F) with the Emissivity set at.96 which is characterized as uncompensated. The anomaly was identified and documented as an area of concern to be monitored for signs of deterioration. The training and certification program, along with the intimate knowledge that electricians possess about the equipment they maintain, is critical to making sound judgment calls on issues such as this. To the untrained eye, the temperature is within acceptable operating parameters. With the TEGG/ASNT Certification program, the execution of this technology is designed to eliminate any uncertainties on such issues. Knowing that this clamp is manufactured with a material that is NOT efficient at emitting radiation (only about a.5 efficiency), the technicians were aware that a camera adjustment was necessary in order to obtain more accurate temperature information. Once this adjustment was made, the 64 C (147 F) temperature was corrected to reflect a more accurate temperature to 107 C (224.6 F), illustrating an error of over 40 C (104 F). These findings prompted the service provider to more closely monitor the fuse clamp; monitoring intervals for this switch were changed to weekly surveys. The technicians continued their service routine over the next ten days at which time TEGG Corporation was scheduled to pay a training and support visit to Bradford White. Upon the arrival of the TEGG Technical Support, DenHartigh advised the instructor of the issue (as he was seeking a second opinion) and asked the instructor to accompany him to view the fuse clamp as part of the agreed upon monitoring cycle. As Figure #4 demonstrates, the result of this survey proved to be far more alarming than the initial survey: The problem temperature had increased to 252 C (486 F) in just ten days since first identified. The new temperature represented an increase over 300%, indicating a significant and accelerated deterioration of the assembly. Figure #4
6 When proper Emissivity was compensated for (Figure #5) the results were more alarming. The extent of the fuse deterioration became crystal clear. The actual temperature was not simply 252 C (486 F); it was in fact almost 508 C (946 F). Also noteworthy is the fact that the angle of view from the IR window did not allow for a direct line to the source of the heat, which was on the top portion. The temperature Figure #5 observed was visible through conduction from the top. To make matters even more pressing, the Plexiglas window above allowed for a visual inspection that revealed the connection was in fact luminescent at this point (as seen in a digital photo in Figure #6). Based on the material and color visible, the actual temperature was calculated at nearly 850 C! This discovery prompted an immediate consultation with the customer. Mr. Potter, the Facility Electrical Engineer at Bradford White, was briefed on the situation, and was quickly escorted to the switch so that he could assess the situation personally. Catastrophic failure was a very real possibility based on the evidence and would have resulted in Figure #6 days of downtime. This was not a prospect that Mr. Potter or Bradford White Corporation welcomed. Mr. Potter immediately met with upper management to advise others of the situation and to begin assembling an action plan. A Lesson Learned: After Mr. Potter reported the serious nature of the overheating fuse clip, Eric Lannes, Vice President of Bradford White, shared a story with him. Mr. Lannes previously worked at a facility in Reno, Nevada; that facility had had a similar incident. A similar type of switch had failed, which resulted in both the switch s and the transformer s destruction. It also resulted in a total of four days of downtime to make the repairs. After sharing this story, Mr. Lannes instructed Mr. Potter to do whatever it takes to get the repairs in place. With that directive, the wheels were set in motion to immediately repair the equipment and restore the facility s major supply of electrical power to premium operating condition.
7 The Solution: TEGG and Feyen Zylstra personnel reviewed three possible courses of action to address this situation at hand: 1. Immediately shut the plant down and inspect and disassemble the fuse assembly to determine which parts would be needed for repair. (This was the least desirable option, as the availability of the necessary parts was not certain at this point and downtime could be significant.) 2. De energize the interrupter switch and configure a by pass of the three, 200 amp fuses, thereby relying on utility protective devices for over current and fault protection. (This also made maintenance and repair impossible until the November shutdown.) 3. Secure a portable generator to supply temporary power to the switchgear lineup which would allow production to continue, minimize the interruption, and afford the opportunity to apply proper and permanent repairs to the switch. 3:45 pm: Mr. Potter elected option number three and issued the authorization to initiate the plan and correct the problem. Phone calls immediately began to companies in the local area that could supply a portable generator and wiring large enough to support the production demand. A 2 MW generator was needed based on the capacity of the facility. Additionally, 18 runs of cable 200 feet long were needed to temporarily run power from the generator to the switchgear lineup. 8:45 pm: The generator and cabling were on site, and with a crew of eight technicians from Feyen Zylstra, the process of stringing the cable runs had begun. 10:30 pm: The cables were in place, and the task of connecting all the cables on both ends was initiated.
8 The technicians feverishly worked to have the generator on line by the 12:00 AM time frame outlined by Mr. Potter to ensure that the midnight shift workers would be able to complete a full production effort. 11:45 pm: With the Equipment in place, the generator technician was instructed to start the unit. 12:15 am: The generator ramped up to speed and stabilized in its operating RPM. The output breaker was then closed, supplying power to the gear lineup. After a phase rotation check of the supply, using the results from a baseline check performed prior to shutdown, the clearance was issued to begin the start up process of the plant production equipment. 1:15am: Full capacity was online and producing. Mr. Potter then breathed a sigh of relief: the switchover was accomplished in 8.5 hours without incident and the immediate electrical needs for production were satisfied. Investigating the extent of damage to the switch and fuse assembly could begin first thing in the morning. Craig Potter, Bradford White Facility Electrical Engineer
9 The Autopsy: It was evident upon inspection that the original suspicions and analysis were on the mark. The results of the extreme temperatures that these components were exposed to are clearly visible. The fuse itself was visually discolored from the heat damage (Figure #7), and the clamp assembly was burnt and gaulded. The plastic tightening knob was melted off its mount (Figure #8) and was found lying on the bottom of the enclosure. All s Well That Ends Well: Within 2.5 days, operations were returning to normal, and there was little evidence that anything at all had taken place. The generator, with several skids and bins of temporary cabling, had been recovered and returned to its staging area. The only thing left to do now was to verify that the repair efforts were successful. Let s compare the before and after images (both compensated for Emissivity). Figure #9 clearly shows the overheating of the fuse clip. A subsequent IR scan (Figure #10) through the newly installed window revealed evenly distributed operating temperatures of approximately 49 C (120 F) on all three fuses representative of what one would expect to view on this type of equipment and load demand conditions in a normal state. Figure #7 Figure #8 Overheated Fuse clip clearly evident Figure #9 After repairs were made the temperatures are moderated Figure #10
10 The Value of EPM: In a subsequent letter from Mr. Potter, he said, I want to recognize the efforts of all of the personnel from Feyen Zylstra. The speed of the response to this critical issue and the professionalism demonstrated by everyone involved has not only been to my delight, but a most impressive exhibition. When the scheduled maintenance took place, the technicians involved with the IR window installation resembled a swarm of bees. I cannot divulge actual costs associated with an outage and loss of production similar to the four day occurrence Eric Lannes was involved with in Reno, but I can say that the business interruption cost to Bradford White would have been extreme if a similar scenario were to have taken place on this issue, likely millions of dollars in lost production revenue. SUMMARY: The decision to include the installation of IRISS infrared windows in conjunction with this maintenance agreement proved to be priceless. Due to the nominal Voltage (8.3KV), access to survey this switch using traditional open panel procedures would not have been possible without disruption to the plant s processes. With the IR windows in place, inspections were performed efficiently and safely under full load (as prescribed by NFPA 70B) without disrupting normal operations and without increasing the level arc flash risk for plant and personnel. Had the windows not been installed, this critical issue would likely have gone undetected until a catastrophic event brought the plant to its knees. The resulting costs to lost production would likely have been in the millions of dollars. Additional costs of lost customer loyalty, hardware replacement costs, and the months of distraction to personnel at all levels of the organization, would have made the actual costs even higher. As your mother probably told you, you never get a second chance to make a first impression. This is especially true in today s competitive business climate where one misstep may lead to consequences that could have a negative impact for years to come. Consequently, it is imperative that our business planning and execution strategies eliminate risk of catastrophic consequences wherever possible. Although the final costs of the events at Bradford White are not disclosed, there is no doubt among management that whatever the final cost, it was a fraction of what it could have been had the issue not been detected and resolved. In short, the proactive approach of Bradford White s management in implementing an EPM program paid dividends. Does preventive maintenance pay? Without a doubt. In fact, the cost associated with taking a proactive posture is not really a cost at all when one considers the alternative costs associated with failing to detect an electrical fault which could result in a catastrophic failure. The real cost
11 comes from inaction and a complacent outlook toward maintenance that sometimes may sound like, I ve been here for 20 years and there has never been a failure in that time. Although this case study revolved around a thermal exception, there are many other considerations in electrical systems that make up a comprehensive and cost effective electrical preventive maintenance program. The value of utilizing trained, licensed, and certified personnel, who are familiar with the equipment construction, manufacturer s maintenance recommendations, and hazards involved with servicing them, cannot be overstated. Items such as safety hazards, national electric code violations, ultrasonic exceptions (highfrequency emissions related to arcing, tracking, corona, and mechanical vibrations), visual inspections, power quality considerations, and of course the science of infrared, are best served by the technicians trained and certified to perform these functions in this application. Perhaps the clock may be ticking and the time running out on the luck your facility has been experiencing. Are you willing to take the chance that luck will remain on your side and that failure will not occur? Or are your organization s pockets deep enough and your customer base strong enough to weather the catastrophe that may be just beyond your sight? Choose wisely and invest in what matters most to you.
OSHA and NFPA 70 Understanding NFPA 70 and its Implications in Electrical Inspections 2010
OSHA and NFPA 70 Understanding NFPA 70 and its Implications in Electrical Inspections 2010 By: Martin Robinson, Level III Thermographer 18-1030-0005 Rev. A The National Fire Protection Association (NFPA)
ACCEPTANCE TESTING, COMMISSIONING & START UP PREDICTIVE & PREVENTATIVE ELECTRICAL TESTING SERVICES ENGINEERING SERVICES
INFRARED INSPECTIONS ACCEPTANCE TESTING, COMMISSIONING & START UP PREDICTIVE & PREVENTATIVE ELECTRICAL TESTING SERVICES ENGINEERING SERVICES 24/7 EMERGENCY SERVICE AND REPAIR DELIVERING A HOST OF TECHNICAL
Enhance Power Equipment Reliability with Predictive Maintenance Technologies
Enhance Power Equipment Reliability with Predictive Maintenance Technologies November 2012/1910DB1208 by S. Frank Waterer, Electrical Engineerinig, Fellow Schneider Electric USA, Inc. Make the most of
NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers
NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers A market position paper from the experts in Business-Critical Continuity TM Executive Summary Electrocutions are the fourth
employed to ensure the continuing reliability of critical systems.
4 Regulations 1989, Regulation 4, places a duty on employers to provide safe systems for their workers: Regulation 4 of the Electricity at Work Regulations 1989 Systems, work activities and protective
Predictive Maintenance in a Mission Critical Environment
March 2009 Predictive Maintenance in a Mission Critical Environment This paper discusses the need to proactively protect mechanical and electrical support systems in data processing centers and data storage
Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches
Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches Downtime Is Not An Option The industrial uninterruptible power supply (UPS) is the foundation of your
WHAT IS INFRARED (IR) THERMOGRAPHY
WHAT IS INFRARED (IR) THERMOGRAPHY IR Thermography is the technique of producing pictures called from the invisible thermal radiation that objects emit. This is a non-contact means of identifying electrical
Applications for Infrared Thermography at Computer Centers
Applications for Infrared Thermography at Computer Centers By Eric Stockton CompuSCANIR, a division of Stockton Infrared Thermographic Services, Inc. 8472 Adams Farm Road Randleman, NC 27317 http://www.compuscanir.com/
Predictive Maintenance
PART ONE of a predictive maintenance series Predictive Maintenance Overview Predictive maintenance programs come in all shapes and sizes, depending on a facility s size, equipment, regulations, and productivity
CONTINGENCY PLANNING FOR DISRUPTED ELECTRIC POWER: The Case for Partnering with a Strong Rental Power Supplier
CONTINGENCY PLANNING FOR DISRUPTED ELECTRIC POWER: The Case for Partnering with a Strong Rental Power Supplier CONTINGENCY PLANNING FOR DISRUPTED ELECTRIC POWER: The Case for Partnering with a Strong Rental
D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.
SECTION 263354 STATIC UPS TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes 1. System start-up services. 2. Battery charging. 3. Load bank testing. 4. Battery load testing. 5.
Lafayette Parish School System Disaster Recovery Services RFP #15 10
Page 1 of 7 Lafayette Parish School System Disaster Recovery Services RFP #15 10 Respondent BELFOR SECTION 2.0 INFORMATION REQUIRED FROM PROPOSERS 2.1 APPROACH TO PROJECT Submitted proposals must detail
Ultrasound Condition Monitoring
Ultrasound Condition Monitoring Whitepaper Alan Bandes UE Systems, Inc. Abstract: Instruments based on airborne/structure borne ultrasound technology offer many opportunities for reducing energy waste
21 st Century Facilities
Electrical Testing 21 st Century Facilities Facility Owners face tough challenges 24 X 7 reliability needed Non linear loads cause harmonics VFD Computers Switching transients disrupt operations Less customer
Electrical Safety Tips. Help us keep you safe
Electrical Safety Tips Help us keep you safe To help you stay safe when using electricity, ActewAGL has compiled these electrical safety tips. For natural gas safety tips please see ActewAGL s natural
Arc Flash Energy Mitigation Techniques
Arc Flash Energy Mitigation Techniques When short circuits occur on an electrical distribution system, an arc flash event usually forms. These arc flash events can cause dangerous and potentially fatal
Use your troubleshooting superpowers for good Application Note
Use your troubleshooting superpowers for good Application Note Unleash your full troubleshooting powers with innovative new tools from Fluke. You ve got skill. You ve got experience. Now you have some
Statement Of Work. Data Center Thermography Assessment. Service. Professional Services. Table of Contents. 1.0 Executive Summary
Statement Of Work Professional Services Data Center Thermography Assessment Data Center Thermography Assessment Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features & Benefits
What Are the Qualifications to Conduct Arc Flash Studies? Where Do You Begin?
What Are the Qualifications to Conduct Arc Flash Studies? Where Do You Begin? Comparing apples-to-apples bids Plant Services Special Report A shock hazard analysis should be included as part of an arc
Roadmap to Compliance with NFPA 70E Arc Flash Requirements
Roadmap to Compliance with NFPA 70E Arc Flash Requirements TAHFM Interlink 2015 March 30, 2015 Antony Parsons, Ph.D., P.E. Schneider Electric Engineering Services 1 2 How do we get to Reliable Power? >
Bypass transfer switch mechanisms
Power topic #6013 Technical information from Cummins Power Generation transfer switch mechanisms > White paper By Gary Olson, Director, Power Systems Development This paper describes the configuration
The Application of Circuit Breakers to Reduce Downtime in Datacentres
The Application of Circuit Breakers to Reduce Downtime in Datacentres Tim Campbell BEng MIET. Marketing Manager, Terasaki Electric (Europe) Ltd. Abstract Circuit breakers fulfil several functions in the
INSPECTION AND TESTING OF EMERGENCY GENERATORS
INSPECTION AND TESTING OF EMERGENCY GENERATORS Certification requirements NFPA 101(00), Sec. 7.9.2.3 requires that emergency generators be installed, tested and maintained in accordance with NFPA 110,
Maximizing Equipment Uptime
Maximizing Equipment Uptime The benefits of maximizing your equipment s uptime are obvious: if your equipment is not running, then it cannot produce; if it is not producing, then your revenue and profits
Understanding Emergency Power Off (EPO)
Understanding Emergency Power Off (EPO) White Paper #22 Executive Summary Emergency Power Off (EPO) is the capability to power down a piece of electronic equipment or an entire installation from a single
Safety During Power Restoration. Steve Thompson Emergency Operations Director Alabama Power Company
Safety During Power Restoration Steve Thompson Emergency Operations Director Alabama Power Company Safety & Training Responsibilities During Major Outages Staging Area Responsibilities Orientations for
Electrical Wiring Methods, Components and Equipment for General Use. Approved for Public Release; Further Dissemination Unlimited
Electrical Wiring Methods, Components and Equipment for General Use Approved for Public Release; Further Dissemination Unlimited At the completion of this unit you shall be able to: 1. Utilize section
IN TOUGH ECONOMIC TIMES: 4 Key Considerations & 7 Creative Solutions for Immediate Savings
REDUCING THE COSTS OF CONTINUOUS OPERATING SCHEDULES IN TOUGH ECONOMIC TIMES: 4 Key Considerations & 7 Creative Solutions for Immediate Savings Bill Davis, Vice President of Operations INTRODUCTION When
shopinkelowna.com/mr--electric---home- Electrician-West-Kelowna/648681.htm
shopinkelowna.com/mr--electric---home- Electrician-West-Kelowna/.htm Website Visibility: by Search Engine % Keyword Rankings: Summary Search engine Keywords Moved Up/Down - - Keyword Rankings Keyword Affordable
Executive Summary. Technical Description
Executive Summary The Cellwatch system is built using modules. The majority of the system is constructed with Data Collection Modules (DCMs). The DCMs are optically linked to Control Units (CUs) that in
Thermal Imaging Scan Reveals the Truth Behind the Wall
Thermal Imaging Scan Reveals the Truth Behind the Wall Peter Hopkins, Certified Thermographer SoCal Infrared (www.socalinfrared.com) ABSTRACT You suspect you have missing insulation in your home. You have
Union County Public Schools. Facilities Department. Electrical. Safe Work Practices
1 Union County Public Schools Facilities Department Electrical Safe Work Practices 2 Purpose In accordance with OSHA Standards 1910.331-335, safety-related work practices shall be used by Union County
Oil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
ELECTRICAL SAFETY RISK ASSESSMENT
ELECTRICAL SAFETY RISK ASSESSMENT The intent of this procedure is to perform a risk assessment, which includes a review of the electrical hazards, the associated foreseeable tasks, and the protective measures
NATIONAL FIRE ALARM AND SIGNALING CODE
GAP.11.1.1.0 A Publication of Global Asset Protection Services LLC NATIONAL FIRE ALARM AND SIGNALING CODE INTRODUCTION National Fire Protection Association (NFPA) documents describe a level of fire protection
C3306 LOCKOUT/TAGOUT FOR AUTHORIZED EMPLOYEES. Leader s Guide. 2005, CLMI Training
C3306 LOCKOUT/TAGOUT FOR AUTHORIZED EMPLOYEES Leader s Guide 2005, CLMI Training LOCKOUT/TAGOUT FOR AUTHORIZED EMPLOYEES This easy-to-use Leader s Guide is provided to assist in conducting a successful
NETWORK SERVICES WITH SOME CREDIT UNIONS PROCESSING 800,000 TRANSACTIONS ANNUALLY AND MOVING OVER 500 MILLION, SYSTEM UPTIME IS CRITICAL.
NETWORK SERVICES WITH SOME CREDIT UNIONS PROCESSING 800,000 TRANSACTIONS ANNUALLY AND MOVING OVER 500 MILLION, SYSTEM UPTIME IS CRITICAL. Your Credit Union information is irreplaceable. Data loss can result
DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS
MIOSHA-STD-1313 (10/15) 6 Pages For further information Ph: 517-284-7740 www.michigan.gov/mioshastandards DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS
SAFE ELECTRICAL WORK PRACTICES & 2015 NFPA 70E
SAFE ELECTRICAL WORK PRACTICES & 2015 NFPA 70E This easy-to-use Leader s Guide is provided to assist in conducting a successful presentation. Featured are: INTRODUCTION: A brief description of the program
INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION
INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION February 2013 NOTE: If conflict exists between St. Thomas Energy s Conditions of Service and this document, the Conditions
October Safety Subject
October Safety Subject Electrical Hazards All electrical equipment should be kept in good repair. Replace defective equipment or have it repaired by a qualified person. Watch for wiring on appliances that
Cyber Security Response to Physical Security Breaches
Cyber Security Response to Physical Security Breaches INTRODUCTION Physical break-ins and other unauthorized entries into critical infrastructure locations, such as electrical power substations, have historically
On-line PD Monitoring Makes Good Business Sense
On-line PD Monitoring Makes Good Business Sense An essential tool for asset managers to ensure reliable operation, improve maintenance efficiency and to extend the life of their electrical assets. Executive
12 Things Facility Managers Need to Know About Critical Power System Installation
12 Things Facility Managers Need to Know About Critical Power System Installation Are you considering managing your next power system installation in-house? As a facilities manager or other facility professional,
City Of Ottawa High Voltage Substation Inspection, Maintenance Rev 00 2015 July 17 and Testing, ROPEC Page 1
2015 July 17 and Testing, ROPEC Page 1 PART 1 GENERAL 1.1. Scope.1 Equipment replacement and testing for a 44 kv 4.16kV/600V substation: a. Replacement of Insulators as indicated on the drawings in Appendix
Addendum #2 Contract UK-11-13
Addendum #2 Contract UK-11-13 Utilities Kingston Purchase and Replacement of Switchgear at Kingston Hydro Substation MS11 March 25, 2011 Delivered to: All RFP recipients Total number of pages: Nine (9)
Thermal Imaging Specialists Consultancy - Camera Sales - Training
Thermal Imaging Specialists Consultancy - Camera Sales - Training A Full Range of Services Thermographic Consultancy Ltd offer a wide range of thermal imaging solutions which include technical support
Backup Fuel Oil System Decommissioning & Restoration Plan
Backup Fuel Oil System Page 1 of 19 Overview of Physical Fuel Oil System and Decommissioning Steps The fuel oil system at Milford Power consists of a number of subsystems. These include the following:
Austin Independent School District Police Department Policy and Procedure Manual
Policy 8.07 Austin Independent School District Police Department Policy and Procedure Manual Life Safety Systems I. POLICY The proper operations of the AISD Life Safety Systems (LSS) are essential for
DATAMENA COLOCATION SERVICE SCHEDULE
DATAMENA COLOCATION SERVICE SCHEDULE This Schedule is applicable to a Service Order for datamena Colocation Service(s) which has been submitted by Customer, and accepted by Supplier, in accordance with
Arc Flash Avoidance and its Application to Overhead Traveling Cranes
Arc Flash Avoidance and its Application to Overhead Traveling Cranes Whitepaper August 2012 Jason Wellnitz, Controls Product Manager Material Handling Numerous technical papers, bulletins, magazine articles
The Prescient Data Center Manager
May/June 2009 The Prescient Data Center Manager www.missioncriticalmagazine.com PRESCIENT The Data Center Manager How to predict standby battery life BY DAVID BROWN Today s modern UPS systems employ cutting
Federal Wage System Job Grading Standards for Electric Power Controlling, 5407. Table of Contents
Federal Wage System Job Grading Standards for Electric Power Controlling, 5407 Table of Contents WORK COVERED... 2 WORK NOT COVERED...2 TITLES... 2 GRADE LEVELS... 2 SPECIAL ADDITIONAL RESPONSIBILITIES...
ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1
KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1 PART 1 - GENERAL 1.01 RELATED DOCUMENTS: SECTION 16050 A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1
DISTRIBUTION OPERATIONS AND MAINTENANCE
EB-00-00 Filed: 00 Aug Page of DISTRIBUTION OPERATIONS AND MAINTENANCE PREVENTIVE MAINTENANCE Preventive Maintenance is intended to maintain or improve customer service reliability, extend equipment life
2. Laptop, Landline, Cell Phone, Modem, Datalogger: How Do You Tell Where the Problem Is?
Silviculture Instrumentation Tech Tips Silviculture and Forest Models Team Pacific Northwest Research Station 3625 93 rd Ave SW Olympia, WA 98512 USA September, 2003 2. Laptop, Landline, Cell Phone, Modem,
FACILITIES MANAGEMENT DEPARTMENT QUICK REFERENCE Guide to Services
FACILITIES MANAGEMENT DEPARTMENT QUICK REFERENCE Guide to Services After-Hours Service Calls Air Conditioning and Heating Bicycle Racks Building Conditions Inspections Contract Construction (handled by
Frequently Asked Questions (Including Definitions)
My Business Income Consultation from Chubb Frequently Asked Questions (Including Definitions) Frequently Asked Questions How To Use The Tool Click on the question that you would like to have answered.
Five Nines and Infrared (IR) Testing at Data Centers
Five Nines and Infrared (IR) Testing at Data Centers By Gregory R. Stockton 99.999% uptime five nines. That is what IT (information technology) customers are looking for. Uptime or availability at data
APPENDIX 7. ICT Disaster Recovery Plan
APPENDIX 7 ICT Disaster Recovery Plan This policy was approved and ratified by the Governing Body of Cox Green School on 20 th October 2015 Signed: Chair of Governors Date: Version Authorisation Approval
Ongoing Help Desk Management Plan
Ongoing Help Desk Management Plan HELP DESK IMPLEMENTATION /MANAGEMENT The Vendor shall provide in its Response to DIR a Help Desk Implementation Plan which shall include, but not be limited to: a. Customer
COMPUTHERM Q7 Programmable, digital room thermostat. Operating Instructions
COMPUTHERM Q7 Programmable, digital room thermostat Operating Instructions GENERAL DESCRIPTION OF THE THERMOSTAT The COMPUTHERM Q7 type switched-mode room thermostat is suitable to regulate the overwhelming
How to Estimate the Cost of a Clean Room and Data Center Equipment Electrical Work. Section 2 Types of Methods of Measurements page 4
How to Estimate the Cost of a Clean Room and Data Center Equipment Electrical Work Table of Contents Section 1 Introduction page 3 Section 2 Types of Methods of Measurements page 4 Section 3 Project Specific
d/b/a ENERGY KEEPERS, Inc. Power Plant Maintenance Engineer Negotiable depending on training, education, and experience
Position: Salary: Location: Employment Status: Supervised By: SXʷNQ EʔELS L SUW EČM / KSUKⱠIⱠMUMAⱠ ʾA K AⱠMUKWAʾITS, Incorporated d/b/a ENERGY KEEPERS, Inc. GENERAL SUMMARY Power Plant Maintenance Engineer
Inspection, Testing and Maintenance
Page 18 ABOUT CODE CORNER CCFS would like to remind you to check with your local Authority Having Jurisdiction (AHJ) for questions and opinions concerning your local Fire and Building Codes. The information
Minor maintenance issues proving difficult to detect for many solar PV system owners
Minor maintenance issues proving difficult to detect for many solar PV system owners Challenges occurring even when system owners have access to their realtime and historical generation data Lack of detection
IMPLEMENTING A RELIABILITY CENTERED MAINTENANCE PROGRAM AT NASA'S KENNEDY SPACE CENTER
IMPLEMENTING A RELIABILITY CENTERED MAINTENANCE PROGRAM AT NASA'S KENNEDY SPACE CENTER Raymond E. Tuttle and Robert R. Pete EG&G Florida BOC-035 Kennedy Space Center FL 32899 (407) 867-5705!qq, Abstract:
Elevator Malfunction Anyone Going Down?
Elevator Malfunction Anyone Going Down? Lessons Learned Volume 04 Issue 41 2004 USW Purpose Elevator Malfunction - Anyone Going Down? To conduct a small group lessons learned activity to share information
Submit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
Putting the Pieces FIRE WATER CONSTRUCTION
Putting the Pieces Back Together FIRE WATER CONSTRUCTION Mooring is a highly responsive full-service, turnkey restoration and construction company. We re a solutions-oriented company that delivers trusted
SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions
SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS POWER DISTRIBUTION RACKS IN A MISSION CRITICAL SYSTEM MODULES IN A MISSION CRITICAL SYSTEM UPS Convertor Main Inverter Load Battery BPC UPS & BATTERY
Common Power Problems & Power Protection Solutions
W H I T E P A P E R Common Power Problems & Power Protection Solutions Executive Summary All systems, from home theaters and office desktops to enterprise IT equipment in data centers, are prone to downtime,
Understanding Alarm Systems
Understanding Alarm Systems A false alarm occurs when an alarm signal designed to elicit an immediate emergency Law Enforcement, Fire, or Medical response is activated, when in fact no emergency exists.
Mobile Data Power Model: MDP-25
Mobile Data Power Model: MDP-25 Topic Section Features... 2 Operational Features Summary... 2 Back-up Battery Power Internal Charger Voltage Spike Protection RF Noise Filtering Warning of Imminent Loss
Root-cause analysis, often called RCA, is a way of thinking about how to
Special Feature by Mark Lautenschlager, P.E. Using Root-Cause Analysis to Find Underlying Causes of Bad Outcomes Root-cause analysis, often called RCA, is a way of thinking about how to fix problems. By
uptimeplus.co.uk predictive maintenance strategy galileo Supported by
uptimeplus.co.uk predictive maintenance strategy galileo Supported by Why galileo? The search for an alternative maintenance methodology is a result of general lack of visibility on asset s reliability,
1. Do you have onsite emergency power generation in any of your facilities? R=992
Load Bank Testing Load Bank Testing Whether required by code or as simply part of good building operations strategy, facility executives whose organizations own emergency generators must test them regularly
MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING
Training Title MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Duration 5 days Training Date MV, HV and EHV Switchgear Testing & Commissioning 5 20 24 Apr $3,750 Dubai, UAE In any of the 5 star
HOUSING QUALITY STANDARDS (HQS)
HOUSING QUALITY STANDARDS (HQS) Series 5 Electrical Safety And INSPECTIONS 5.01 ELS Revised 8-17-06 Electricity is Dangerous All electrical repairs should be made by licensed professionals. Touching any
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according
Mastering Disaster A DATA CENTER CHECKLIST
Mastering Disaster A DATA CENTER CHECKLIST Disaster Doesn t Sleep It s not always a hurricane or a power grid failure that causes businesses to lose their data. More often than not, an isolated event like
ARC FLASH HAZARD OVERVIEW. Presented August 13, 2015 WWOA Lake Michigan District by Mead & Hunt, Inc.
ARC FLASH HAZARD OVERVIEW Presented August 13, 2015 WWOA Lake Michigan District by Mead & Hunt, Inc. ARC FLASH EXPERIENCE Christopher J. DeWaal, MS, MEM, PE, LEED AP, HACCP How did I get involved? A client
Electrical Predictive and Preventative Maintenance
Electrical Predictive and Preventative Maintenance Electrical and mechanical equipment is subject to failure at the worst possible time for no apparent reason. - Mose Ramieh III There are two types
INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS AND EQUIPMENT
CITY OF SPRING LAKE PARK Code Enforcement Department 1301 81 st Avenue NE Spring Lake Park MN 55432 Business Phone 763-784-6491 Fax 763-792-7257 INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS
Arc Flash Hazards. Electrical Hazards. Dan Neeser Field Application Engineer [email protected]. Electrical Hazards 2/18/2015. Shock.
Arc Flash Hazards Dan Neeser Field Application Engineer [email protected] Electrical Hazards Electrical Hazards Shock Arc Flash Arc Blast 2 1 Arcing Fault Basics 35,000 F Radiant Heat & UV Speed of
Facilities Maintenance Standards rev 9-1-2015
Facilities Maintenance Standards rev 9-1-2015 Purpose The purpose of these standards is to outline the minimum requirements for maintaining state owned facilities and infrastructures in a manner that will
Massachusetts FACE Occupational Fatality Report
Massachusetts FACE Occupational Fatality Report Massachusetts Department of Public Health Occupational Health Surveillance Program Fatality Assessment and Control Evaluation Project Apprentice Electrician