New energy evaluating methodology of Air conditioner and Heat pump
|
|
|
- Ralf Goodman
- 10 years ago
- Views:
Transcription
1 New energy evaluating methodology of Air conditioner and Heat pump The 3 rd Conference Research and Development of Heat Pump and Thermal Storage Technologies in Industrial and Residential Sectors 8 October 2013 Jun Choi Korea Testing Laboratory 1
2 Global Market Global market : 61.5B$(2008) 170B$ (2012) Major Market : US, Japan, Europe, China CAGR : more than 14% Ductless(67%)>Chille r(ahu included, 19%)>Unitary(14%) China(20%)>NA(19 %)>Europe(16%)>J apan(14%) World market : 170 B$ in
3 High Efficiency What is high efficiency? Cooling EER = Cooling Capacity / Effective Power Input Large is Efficient Heating COP = Heating Capacity / Effective Power Input Large is Efficient Averaged COP = (EER + COP)/2 Japan But, COP and EER at one point is not real usage Part load efficiency is necessary SEER (CSPF and HSPF) is using in some countries, but complicated New high efficiency products are adopted with inverter-driven compressor and 2 or 3 combined compressors 3
4 Improved Technology Trend 70 s 80~90 s 2000 s 2007 s Fixed Speed Compressor Variable capacity with Bypass compressor AC Inverter Compressor DC Inverter Compressor 4
5 High Efficiency Air conditioners Korean Market a new model adopted with a new technology, two stage or variable capacity models in order to meet a new high EELSP in a market even a high price High Efficiency AC Models,Split type, 4.0 kw RCC < 10.0 kw High Efficiency AC Models,Split type, 10.0 kw RCC < 17.5 kw Models Models Split type, 4.0 kw RCC < 10.0 kw Two stages or variable capacity Split type, 10.0 kw RCC < 17.5 kw Two stages or variable capacity Split type, 4.0 kw RCC < 10.0 kw Fixed capacity Split type, 10.0 kw RCC < 17.5 kw Fixed capacity 5
6 Power consumption rate of stocked AC in fiscal year has reduced 23.6% from 2001 to Power consumption rate of stocked air conditioners in fiscal year "n" 23.6% 3.00 MWh Year 6
7 Energy efficiency for Part loads SEER (Seasonal Energy Efficiency Ratio) Annual energy use for the appliances or system, unitary AC Variable-speed, two-speed systems SEER was developed by NIST, US (Parken et al 1977; Kelly & Parken 1978; Parken et al 1985) Based on a bin analysis that calculated the cooling load, capacity and efficiency over a range of ambient temperature CSPF (Cooling Seasonal Performance Factor) & HSPF (Heating Seasonal Performance Factor) US, Japan, Korea IPLV (Integrated part load value) For Chiller developed in 1986, US IPLV (Integrated part load value) 7
8 ISO TC86 SC6 WG1 Japan proposed APF(Annual Performance factor) NWIP in 2006, and it was accepted in 2007 ISO TC86 SC6 WG1 is running to develop a new test method for AC/HP ISO Air-cooled air conditioners and air-to-air heat pumps -Testing and calculating methods for seasonal performance factors Part1 : Cooling seasonal performance factor Part2 : Heating seasonal performance factor Part3 : Annual performance factor Convenor is Mr. Bernard Hugh from England Japan, USA, Korea, France, and Spain are participated Currently FDIS ballot stage, ISO FDIS Not available on water source Air-to-Water, Water-to-Air, Water-to-Water, Water-to Brine etc 8
9 Types fixed capacity unit equipment which does not have possibility to change its capacity. This definition applies to each cooling and heating operation individually. two (2)-stage capacity unit equipment where the capacity is varied by no more than two steps. This definition applies to each cooling and heating operation individually. multi-stage capacity unit equipment where the capacity is varied by 3 or 4 steps. This definition applies to each cooling and heating operation individually variable capacity unit equipment where the capacity is varied by 5 or more steps to represent continuously variable capacity. This definition applies to each cooling and heating operation individually. 9
10 Cooling mode 10
11 11
12 TCSPF(Total cooling seasonal performance factor) 12
13 Heating mode 13
14 14
15 THSPF(Total heating seasonal performance factor) 15
16 APF(Annual Performance Factor) 16
17 Europe Standard - EN EN Air conditioners, liquid chilling packages and heat pumps, with electrically compressors, for space heating and cooling Testing and rating at part load conditions and calculation of seasonal performance. Published March Will be the harmonized standard for the European Directive on seasonal efficiency of air conditioners (revision summer 2013). Developed using the data of a preliminary study of the European Commission, determining average climates in Europe and representative types of buildings and internal loads schedules. Bin method (number of hours at a given outdoor temperature) Includes the electrical input when the unit is not cooling nor heating. Testing methods for the cooling and heating capacities: EN
18 3) Testing procedures and calculations reference design conditions for cooling (Tdesignc) temperature conditions at 35 C dry bulb (24 C wet bulb) outdoor tem perature and 27 C dry bulb (19 C wet bulb) indoor temperature reference design conditions for heating (Tdesignh) temperature conditions for average, colder and warmer climates Tdesign "average" T design "colder" T design "warmer" temperature conditions at -10 o C dry bulb outdoor temperature and 20 o C dry bulb indoor temperature temperature conditions at -22 C dry bulb outdoor temperature and 20 C dry bulb indoor temperature temperature conditions at +2 C dry bulb outdoor temperature and 20 C dry bulb indoor temperature 18
19 3) Testing procedures and calculations bivalent temperature (Tbivalent) lowest outdoor temperature point at which the heat pump is de clared to have a capacity able to meet 100% of the heating de mand - for the average heating season, the bivalent temperature is +2 CDB or lower - for the colder heating season, the bivalent temperature is -7 CDB or lower - for the warmer heating season, the bivalent temperature is +7 CDB or lower operation limit temperature (TOL) lowest outdoor temperature at which the heat pump can still de liver heating capacity, as declared by the manufacturer Important: both temperatures are declared by the manufacturer. 19
20 3) Testing procedures and calculations The cooling demand Pc(Tj) can be determin ed by multiplying the full load value (Pdesig nc) with the part load ratio % for each corre sponding bin. This part load ratio % is calc ulated as follows: Cooling mode: Part load ratio % = (Tj-16) / (35-16) SEER Part load ratio (%) on n j1 Outdoor air dry bulb temperature ( C) n j1 hj Pc(Tj) hj Pc(Tj) EER(Tj) Indoor air dry bulb (wet bulb) temperatures ( C) A 100% 35 27(19) B 74% 30 27(19) C 47% 25 27(19) D 21% 20 27(19) The EER values at each bin are determined via interpolation of the EER values at part lo ad conditions A,B,C,D as mentioned in the t ables of Clause 4 of this standard. For part load conditions above part loa d condition A, the same EER values as for condition A are used. For part load conditions below part loa d condition D, the same EER values as for condition D are used. Tj = the bin temperature; j = the bin number; n = the amount of bins; Pc(Tj) = the cooling demand of the building for the corresponding temperature Tj; hj = the number of bin hours occurring at the corresponding temperature Tj; EER(Tj) = the EER values of the unit for the corresponding temperature Tj. 20
21 3) Testing procedures and calculations for fixed capacity units For each part load conditions B,C,D the EER is calculated as follows: Pc EER C, D EER DC (1 Cd (1 )) B, DC EER DC = the EER corresponding to the declared capacity (DC) of the unit at the same temperature conditions as for part load conditions B,C,D. Cd = the degradation coefficient Pc = cooling demand of the building in conditions B, C, D; DC= declared capacity of the unit at the same temperature conditions as for part load conditions B,C,D. If the degradation coefficient Cd is not measured, a default value of 0.25 shall be used. for variable capacity units For each part load conditions B,C,D the EER has to be measured and during the test the part load capacity shall be within ± 10% of the target load. If not possible, the measu rement is done at the closest steps and the EER is calculated in a linear way from the two results. If there is no step giving a load lower than the target, then Cd is used. 21
22 3) Testing procedures and calculations Building load Cooling capacity Cooling capacity of the air conditioner (FIXED CAPACITY) Values of EER to be claimed Pdesign (Declared) Outdoor temperature Tdesign 39 22
23 3) Testing procedures and calculations Building load Cooling capacity Cooling capacity of the air conditioner (VARIABLE CAPACITY) Values of EER to be claimed Pdesign (Declared) Minimum frequency Outdoor temperature Tdesign 39 23
24 3) Testing procedures and calculations Reference SEER SEER QCE SEER on H TO P TO H SB Q CE P SB H CK P CK H OFF P OFF HTO, HSB, HCK, HOFF = the number of hours the unit is considered to work in respectively thermostat off m ode, standby mode, crankcase heater mode and off mode; PTO, PSB, PCK, POFF = the electricity consumption during respectively thermostat off mode, standby mode, crankcase heater mode and off mode, expressed in kw. With Q ce P designc H ce (Hce = 350 hours) 24
25 3) Testing procedures and calculations Heating mode (Average climate): Part load ratio (%) Outdoor air dry bulb (wet bulb) temperatures ( C) Indoor air dry bulb temperature ( C) A 88% -7(-8) 20 B 54% 2(1) 20 C 35% 7(6) 20 D 15% 12(11) 20 E TOL 20 F Tbivalent 20 TOL: Temperature operation limit (lower temperature) Tbivalent: Lower temperature the heat pump can satisfy the heating load Outdoor wet bulb temperature at TOL and Tbivalent: not required below -7ºC 25
26 SCOP on n n j1 hj Ph(Tj) Ph(Tj) - elbu(tj) hj COP (Tj) elbu(tj) SCOP j1 PL j1 Tj = the bin temperature; j = the bin number; n = the amount of bins; Ph(Tj) = the heating demand of the building for the corresponding temperature Tj; hj = the number of bin hours occurring at the corresponding temperature Tj; COP PL (Tj) = the COP values of the unit for the corresponding temperature Tj. Elbu(Tj) = the required capacity of an electric backup heater for the corresponding temperature Tj,, expressed in kw n j1 net n hj (Ph(Tj) - elbu(tj)) Ph(Tj) - elbu(tj) hj COPPL (Tj) The heating demand Ph(Tj) can be determined by multiplying the full load value (Pdesignh) wi th the part load ratio % for each corresponding bin. This part load ratio % is calculated as follo ws : For the average climate : Part load ratio % = (Tj-16) / (-10-16) % For the warmer climate : Part load ratio % = (Tj-16) / (+2-16) % For the colder climate : Part load ratio % = (Tj-16) / (-22-16) % 26
27 3) Testing procedures and calculations Building load Average heating season Building load Heating capacity Pdesign (Declared) Heating capacity of the heat pump (FIXED CAPACITY) TOL Tdesign Tbivalent (Declared) 2 7 Values of COP to be claimed Heating needs covered by the heat pump Heating needs covered by an electrical heater COP = Outdoor temperature 27
28 3) Testing procedures and calculations Building load Average heating season Building load Heating capacity Pdesign (Declared) Heating capacity of the heat pump (VARIABLE CAPACITY) Minimum frequency TOL Tdesign Tbivalent (Declared) Outdoor temperature 28
29 hours (h) 3) Testing procedures and calculations Warm Average cold Outdoor temperature (ºC) 29
30 Standards in KOREA KS C is available for SEER (CSPF & HSPF) Annex 5 provides the guidelines to define CSPF & HSPF Originally it come from ARI, and ASHRAE (US) standards, and developed in 1992 Compromised with ISO It was effective for Energy Efficiency Label and Standard Three types Fixed Speed Compressor Multi-speed & 2-Compressor Variable speed compressor 30
31 Revision KS provides information to calculate SEER Two stage capacity units and variable capacity units should be adopted with CSPF method But, KS is a little bit different with proposed ISO method Temperature bin Temperature conditions, and etc.. KS is being considered to revise with ISO 31
32 Energy Efficiency Level for heatpump in KOREA Effective from Jan : Single heat Pump R = Cooling EER(CEER) + Heating EER(HEER) 2 Non-ducted and ducted unitary (Including window type) R Level 3.20 R R < R < R < R < Split type, RCC < 4kW R Level 4.00 R R < R < R < R < Asia-Pacific Economic Cooperation 32
33 Split type, 4kW RCC < 10kW Split type, 10kW RCC < 23.0kW R Level 3.80 R R < R < R < R < R Level 3.20 R R < R < R < R <
34 Conclusion Promote higher energy efficiency product Need a actual usage under a range of climates, and more realistically and accurately assessing the performance of variable-speed drive compressor systems under conditions of actual use. (e.g. a range of part load conditions) Aligning to ISO 5151 (ISO and ISO FDIS as applicable) would appear to be a feasible option Some member countries already introduced New products were introduced ; Heat Pump water heater 34
WORKING DOCUMENT ON. Possible requirements for air heating products, cooling products and high temperature process chillers TRANSITIONAL METHODS
WORKING DOCUMENT ON Possible requirements for air heating products, cooling products and high temperature process chillers TRANSITIONAL METHODS WORKING DOCUMENT in the framework of the implementation of
1116, Suenaga, Takatsu-ku, Kawasaki 213-8502, Japan http://www.fujitsu-general.com/
1116, Suenaga, Takatsu-ku, Kawasaki 213-8502, Japan http://www.fujitsu-general.com/ ISO 9001 ISO 14001 Certified number : 01 100 89394 Certified number : 01 104 9245101 Fujitsu General (Thailand) Co.,
REFRIGERATOR AND AIR-CONDITIONER TESTING IN THE REPUBLIC OF KOREA
REFRIGERATOR AND AIR-CONDITIONER TESTING IN THE REPUBLIC OF KOREA Junyoung Choi Korea Testing Laboratory, Republic of Korea ENERGY LABELING PROGRAM Korea has a limited natural resources, This, together
The new Ecodesign regulation for heaters: what does it mean for heat pumps?
The new Ecodesign regulation for heaters: what does it mean for heat pumps? Michel Roffe-Vidal AIRWELL citat: there are persistent sales of lowefficiency heaters, because end-user base their purchase decision
Heating, Ventilation & Air Conditioning Equipment
FinAnswer Express Utah Incentive Catalog Effective as of May 19, 2012 Heating, Ventilation & Air Conditioning Equipment Rocky Mountain Power provides incentives for many types of energy-efficient technologies.
HVAC Efficiency Definitions
HVAC Efficiency Definitions Term page EER - 2 SEER - 3 COP - 4 HSPF - 5 IPLV - 6 John Mix May 2006 Carrier Corporation 1 Energy Efficiency Ratio (EER) The energy efficiency ratio is used to evaluate the
Energy efficient room air conditioners best available technology (BAT)
Energy efficient room air conditioners best available technology (BAT) Anette Michel, Eric Bush, Jürg Nipkow, Conrad U. Brunner, Hu Bo Topten International Services Abstract More than 5 million room air
Heating, Ventilation & Air Conditioning Equipment
FinAnswer Express Wyoming Incentive Catalog Effective as of October 1, 2011 Heating, Ventilation & Air Conditioning Equipment Rocky Mountain Power provides incentives for many types of energy efficient
Understanding Heating Seasonal Performance Factors for Heat Pumps
Understanding Heating Seasonal Performance Factors for Heat Pumps Paul W. Francisco, University of Illinois, Building Research Council Larry Palmiter and David Baylon, Ecotope, Inc. ABSTRACT The heating
OM-1-2015 Published December 2014. OPERATIONAL MANUAL for the CERTIFICATION of AIR CONDITIONERS
OM-1-2015 OPERATIONAL MANUAL for the CERTIFICATION of AIR CONDITIONERS OM-1-2015 To supersede OM-1-2014 (Dec. 2013) Editing (date): Arnaud LACOURT 23 July 2014 Checking (date): Jean FOURCROY 13 November
COOLING BENCHMARKING STUDY REPORT
COOLING BENCHMARKING STUDY REPORT BY Econoler, Navigant, CEIS and ACEEE June 2011 in Partnership with The Collaborative Labeling and Appliance Standards Program (CLASP) ACKNOWLEDGEMENT The project team
SASO 2663 :2014 ENERGY LABELLING AND MINIMUM ENERGY PERFORMANCE REQUIREMENTS FOR AIR-CONDITIONERS
SASO 2663 :2014 (SASO 2663/2012 including the modifications approved in Saudi Council Board No../2014) ENERGY LABELLING AND MINIMUM ENERGY PERFORMANCE REQUIREMENTS FOR AIR-CONDITIONERS ENERGY LABELLING
Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance
ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE
ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce
Appendix C. Minimum Equipment Efficiency Standards
Appendix C Minimum Equipment Efficiency Standards Appendix C: Minimum Equipment Efficiency Standards This Appendix is an overview of building and equipment standards in the State of California that have
Air-Conditioning Buying Guide
Air-Conditioning Buying Guide Buying a new air-conditioning system is a big decision. This Air-Conditioning Buying Guide can help you make the right choice, save energy and money. Shop with confidence
QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM
QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM TOGETHERWESAVE.COM IS IT TIME TO REPLACE YOUR HVAC SYSTEM? If your heating and cooling system is 15 to 20 years old and is experiencing problems,
Poor Performing AC? High Electric Bills? High Humidity?
Poor Performing AC? High Electric Bills? High Humidity? If you answered yes to any or all of these questions, it may be time to consider a new Air Conditioning system. Read on for useful information when
How To Design A Building In New Delhi
ENERGY EFFICIENT HVAC DESIGN FOR COMPOSITE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce energy consumption
Achieving ENERGY EFFICIENCY with Standard Air-Conditioning Units. Mike West, PhD, PE Advantek Consulting, Inc
Achieving ENERGY EFFICIENCY with Standard Air-Conditioning Units Mike West, PhD, PE Advantek Consulting, Inc Standard Air Conditioning Unit Packaged Unit Split System DX (not chilled water) Air-cooled
Hybrid (Dual Fuel) - Gas Heat and Air Source Heat Pump
s.doty 10-2014 White Paper #30 Hybrid (Dual Fuel) - Gas Heat and Air Source Heat Pump System Switches Fuels Automatically for Economy. What is an Air-Source Heat Pump? A heat pump is a modified air conditioning
Creating Efficient HVAC Systems
Creating Efficient HVAC Systems Heating and Cooling Fundamentals for Commercial Buildings Heating, ventilating, and air conditioning (HVAC) systems account for nearly half of the energy used in a typical
ENERGY STAR Program Requirements for Residential Air Source Heat Pump (ASHPs) and Central Air Conditioner Equipment. Partner Commitments.
ENERGY STAR Program Requirements for Residential Air Source Heat Pump (ASHPs) and Central Air Conditioner Equipment Partner Commitments Commitment The following are the terms of the ENERGY STAR Partnership
forair optimal air environments ResidentialPresentation
forair optimal air environments ResidentialPresentation Quick Fact Countless neighborhood residents never recognize their home air conditioning system works roughly 3,000+ hours each year. In order to
Rating Water-Source Heat Pumps Using ARI Standard 320 and ISO Standard 13256-1
Rating Water-Source Heat Pumps Using ARI Standard 320 and ISO Standard 13256-1 W. Vance Payne and Piotr A. Domanski National Institute of Standards and Technology Building and Fire Research Laboratory
How to choose a heat pump and use it wisely
How to choose a heat pump and use it wisely Contents How does a heat pump work? 2 Insulating your home 3 Heat loss in the home Not all heat pumps are created equal 4 Choosing a heat pump 4 Choosing by
Massachusetts COOL SMART. RESIDENTIAL CENTRAL AC/DUCTED AIR SOURCE HEAT PUMP Rebate Application
Massachusetts COOL SMART 2015 RESIDENTIAL CENTRAL AC/DUCTED AIR SOURCE HEAT PUMP Rebate Application COOL SMART CENTRAL AC/HP PROGRAM COOL SMART is a residential central air conditioning rebate program
Air Conditioner Cooling Capacity Test AS/NZS 3823.1.1:1998
ABC FOUR CORNERS Air Conditioner Cooling Capacity Test AS/NZS 3823.1.1:1998 Reverse Cycle, High Wall Mounted, Non-Ducted, Single Phase, Single Split System Air Conditioner OPTICAL ACC-25V2 Report No. 30W-07-0038-TRP-221466-0
Development and testing of a multi-type air conditioner without using AC inverters
Energy Conversion and Management 46 (2005) 373 383 www.elsevier.com/locate/enconman Development and testing of a multi-type air conditioner without using AC inverters Shih-Cheng Hu *, Rong-Hwa Yang Department
HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation. Richard Lord Carrier Fellow
HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation Richard Lord Carrier Fellow HVAC Industry Challenges and Issues Ozone Deletion Global Warming
DECISION TIME? A REPAIR OR REPLACEMENT GUIDE FOR HVAC EQUIPMENT REPAIR OR REPLACEMENT GUIDE
DECISION TIME? A REPAIR OR REPLACEMENT GUIDE FOR HVAC EQUIPMENT REPAIR OR REPLACEMENT GUIDE REPAIR vs. REPLACE CURRENT SYSTEM Brand Name Age of Unit Warranty Coverage Efficiency Rating Refrigerant Type
Economic Evaluation of Residential Air Conditioner Designs for Hot and Dry Climates
Economic Evaluation of Residential Air Conditioner Designs for Hot and Dry Climates Arthur Rosenfeld, California Energy Commission Gregory Rosenquist, Lawrence Berkeley National Laboratory C. Keith Rice,
Energy Efficiency Testing for HVAC/R Helping you comply with energy efficiency regulatory programs
HVAC/R EQUIPMENT Energy Efficiency Testing for HVAC/R Helping you comply with energy efficiency regulatory programs As global demand for energy consumption continues to increase, the race to build more
RosevilleProject. LoE _ 2 Glass Products. You can reduce your cooling energy usage by 25% or more. Here is the proof.
RosevilleProject Glass Products You can reduce your cooling energy usage by 25% or more. Here is the proof. Hot-Button Issues Residents of California, Arizona, and Nevada don t need a weather forecast
DECISION TIME? A REPAIR OR REPLACEMENT GUIDE FOR HVAC EQUIPMENT
DECISION TIME? A REPAIR OR REPLACEMENT GUIDE FOR HVAC EQUIPMENT CURRENT SYSTEM Brand Name Age of Unit Warranty Coverage Efficiency Rating Refrigerant Type Type of Thermostat Estimated Life Expectancy Estimated
A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures
R2-1 A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures W. Vance Payne and Piotr A. Domanski National Institute of Standards and Technology Building Environment
Glossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system.
ROOFTOP - HEAT PUMP UNIT Technical data Applies to Model YNRA R410A This document applies when installing into an air handler or as part of an air handling system. CONTENTS 1. General description... 2
Cooling kw 5.2 6.0 7.1 Heating kw 5.65 6.35 7.75
Specifications COOLING ONLY / HEAT PUMP 005 006 007 Capacity (Eurovent) Cooling kw 5.2 6.0 7.1 Heating kw 5.65 6.35 7.75 Nominal input (Eurovent) Cooling kw 1.89 2.35 2.95 Heating kw 1.97 2.24 2.83 EER
New Deluxe Wall Mounted Heat Pump Series EXTERIOS
New Deluxe Wall Mounted Heat Pump Series EXTERIOS May 2013 New Deluxe Wall Mounted Heat Pump Series Panasonic Adding New Air Conditioner Lineup Setting Another Mile Stone in the US Ductless Split History
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program
Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling
Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com
Schedule 3(A) Room Air Conditioners
Schedule 3(A) Room Air Conditioners Revision : 1 Date : 21/08/15 1. Scope 1.1 This Standard specifies the energy labeling requirements for single-phase split air conditioners of the vapour compression
HIGH-EFFICIENCY DUCTLESS INDOOR COMFORT
UP TO 15 SEER Performance MINI-SPLIT SYSTEM UNITS AIR CONDITIONING AND HEAT PUMPS COMPLETE ROOM COMFORT WITH EASY-TO-USE REMOTE CONTROL HIGH-EFFICIENCY DUCTLESS INDOOR COMFORT The Goodman brand offers
GEOTHERMAL HEAT PUMP SYSTEMS ARE RED HOT BUT ARE THEY REALLY GREEN?
GEOTHERMAL HEAT PUMP SYSTEMS ARE RED HOT BUT ARE THEY REALLY GREEN? Richard C. Niess 1 Gilbert & Associates / Apogee Interactive, Inc., Gloucester Point, Virginia 23062 Phone & Fax (804) 642 0400 ABSTRACT
HVAC Systems: Overview
HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct
Research on annual energy consumption of packaged air-conditioning units
Research on annual energy consumption of packaged air-conditioning units Graduate School of Frontier Sciences The University of Tokyo Eiji Hihara, Jianfeng Wang June 4, 2004 in Yokohama, Japan. Research
Study on Performance Evaluation of a Split Air Conditioning System Under the Actual Conditions
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 Study on Performance Evaluation of a Split Air Conditioning System Under
Ground-Source Variable Refrigerant Flow Heat Pumps:
Energy Efficiency Factsheet: Ground-Source Variable Refrigerant Flow Heat Pumps Page 1 Ground-Source Variable Refrigerant Flow Heat Pumps: A Solution for Affordable Housing, Assisted Living, Hotels and
3/29/2012 INTRODUCTION HVAC BASICS
INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O HVAC systems or Heating, Ventilating and Air-Conditioning systems control the environment for people and equipment in our facilities.
The Development of a Frost-Less Heat Pump
The Development of a Frost-Less Heat Pump V. C. Mei, R. E. Domitrovic, and F. C. Chen, Oak Ridge National Laboratory J. K. Kilpatrick, Tennessee Valley Authority ABSTRACT There are two major concerns associated
Development of Air-to-Water Heat Pump for Home Air conditioning/hot Water Supply Combination System with Chilled/Hot Water in European Markets
2 Development of Air-to-Water Heat Pump for Home Air conditioning/hot Water Supply Combination System with Chilled/Hot Water in European Markets - Extending Use of New Heat Pump System in Cold Regions
Commercial Gas Heat Pump - VRF
SANYO GHP Introduction Commercial Gas Heat Pump - VRF 01.12.2011 Agenda 1. SANYO GHP History 2. SANYO GHP Range 3. GHP Market Position 4. 2-WAY 5. GHP Power 6. 3-WAY 7. EER/COP 8. Water Heat Exchanger
Lower Energy Costs with Rooftop Air-Conditioning Package Units
Lower Energy Costs with Rooftop Air-Conditioning Package Units Sponsored by Mike West, PhD, PE Advantek Consulting, Inc Package Unit Efficiency Factors Sensible and latent performance ratings Unit efficiency
RESEARCH HIGHLIGHT. Performance Assessment of a Cold-Climate Air Source Heat Pump
RESEARCH HIGHLIGHT December 2014 Technical Series 14-102 Performance Assessment of a Cold-Climate Air Source Heat Pump INTRODUCTION Most Canadians are familiar with air source heat pump technology in the
Emerging End Use Technologies
Emerging End Use Technologies August 11, 2013 Ron Domitrovic Program Manager, Energy Efficiency EPRI s Role Collaboratively Move Technologies to the Commercialization Stage Basic Research and Development
SOLAR COOLING WITH ICE STORAGE
SOLAR COOLING WITH ICE STORAGE Beth Magerman Patrick Phelan Arizona State University 95 N. College Ave Tempe, Arizona, 8581 [email protected] [email protected] ABSTRACT An investigation is undertaken of a
BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0
BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0 To achieve GREEN MARK Award Pre-requisite Requirement All relevant pre-requisite requirements for the specific Green Mark Rating are to be complied
Air Conditioners Technical Data
Air Conditioners Technical Data O u t d o o r U n i t E E D E N 2-0 0 RX-JV Outdoor Unit RX-JV TABLE OF CONTENTS RX-JV Features............................................................. 2 2 Specifications.......................................................
Opportunities for Success and CO 2 Savings from Appliance Energy Efficiency Harmonisation:
Opportunities for Success and CO 2 Savings from Appliance Energy Efficiency Harmonisation: Part 2: An Assessment of Test Procedures and Efficiency Metrics PUBLISHED MARCH 2011 By Paul Waide, Navigant Consulting
Introduction To VRF: System Overview, Applications, & Savings Opportunities
Introduction To VRF: System Overview, Applications, & Savings Opportunities System Overview What is VRF? Zoning System Two-Pipe / Three Pipe System Packaged DDC Control Operates as a Heat Pump Simultaneous
Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions
Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the
KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO. SAUDI STANDARD DRAFT No. 3457/2005
KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO SAUDI STANDARD DRAFT No. 3457/2005 NON-DUCTED AIR CONDITIONERS AND HEAT PUMPS TESTING AND RATING PERFORMANCE This standard is developed
Greenhouse and Energy Minimum Standards (Air Conditioners and Heat Pumps) Determination 2012 1
Greenhouse and Energy Minimum Standards (Air Conditioners and Heat 1 Greenhouse and Energy Minimum Standards Act 2012 I, MARK DREYFUS, Parliamentary Secretary for Climate Change and Energy Efficiency,
CHILLER PLANT CONTROL MULTIPLE CHILLER CONTROLS
CHILLER PLANT CONTROL MULTIPLE CHILLER CONTROLS By: Michael J. Bitondo, Mark J. Tozzi Carrier Corporation Syracuse, New York August 1999 INTRODUCTION In December of 1998, the American Refrigeration Institute
Energy Efficiency. Energy Efficient Home Cooling:
Energy Efficiency Energy Efficient Home Cooling: Choosing an air conditioning system is an important decision. A poor choice may be costly to purchase and operate and yet fail to provide the desired cooling
Standards & Labeling System for Air-conditioning Equipment in US, Europe and Japan
Standards & Labeling System for Air-conditioning Equipment in US, Europe and Japan The Japan Refrigeration and Air Conditioning Industry Association (JRAIA) Tetsuro Kishimoto, President Sugawara Sakuo,
Evaporative Cooling for Residential and Light-Commercial
EMERGING TECHNOLOGIES This article was published in ASHRAE Journal, October 2011. Copyright 2011 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org.
Hitachi Air Conditioning. Engineered for tomorrow. Room Air Conditioning GENERAL CATALOGUE
Hitachi Air Conditioning Engineered for tomorrow. Room Air Conditioning GENERAL CATALOGUE Contents Page 04 Product Range 08-09 RAC Summit Wall Mounted 10 RAC Shirokuma Wall mounted 11 RAC S Series - Wall
Commercial Energy Efficiency Program. Save money, reduce energy use and earn incentives. Save money, reduce energy use and qualify for incentives
Save money, reduce energy use and earn incentives by improving the energy efficiency of your business. Georgia Power s Commercial Energy Efficiency Program makes incorporating energy-efficient improvements
Laboratory Test Report for Fujitsu 12RLS and Mitsubishi FE12NA Mini-Split Heat Pumps
Laboratory Test Report for Fujitsu 12RLS and Mitsubishi FE12NA Mini-Split Heat Pumps Jon Winkler, Ph.D. September 2011 NOTICE This report was prepared as an account of work sponsored by an agency of the
The efficient heat pump
The efficient heat pump KCP&L has worked hard to build one of the best reliability records in the industry and we want to help you make the most of the energy we provide. That s why we offer information
9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS
9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS 9.1 Introduction Air conditioning and refrigeration consume significant amount of energy in buildings and in process industries. The energy consumed in
Todd M. Rossi, Ph.D. President
Residential Air Conditioning Fault Detection and Diagnostics (FDD) and Protocols to Support Efficient Operation DOE - Building America Program Residential Buildings Integration Meeting - July 20-22, 2010
The ASHRAE HQ Building Can the energy efficiency of the different mechanical systems really be compared? RESIDENTIAL LIGHT COMMERCIAL COMMERCIAL
The ASHRAE HQ Building Can the energy efficiency of the different mechanical systems really be compared? RESIDENTIAL LIGHT COMMERCIAL COMMERCIAL Technical Article April 2013 The ASHRAE HQ Building Can
Daikin Altherma. hybrid heat pump. The natural combination
Daikin Altherma hybrid heat pump The natural combination Why choose Daikin? As an industry leader, Daikin combines broad experience, technical innovation and responsive customer service to help you meet
FTQ. Daikin Inverter Ducted Heat Pump
FTQ Daikin Inverter Ducted Heat Pump A TRADITIONAL CENTRAL AIR SYSTEM MADE BETTER WITH DAIKIN CONSTANT COMFORT INVERTER TECHNOLOGY. The Daikin Inverter Ducted Heat Pump line is a cost effective alternative
Eurovent Certification
Eurovent Certification Performance Testing and Certification Dedicated Outdoor Air Systems AHU s & Cooling Towers REHVA Seminar ACREX 7 th March 2013 Ian Butler ECC Audit Manager & Key Speaker 2/30 First
Analysis of data centre cooling energy efficiency
Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe
Process and Impact Evaluation of Roseville Electric s Residential New Construction, HVAC Retrofit and Commercial Custom Rebate Programs: FY2007/08
Process and Impact Evaluation of Roseville Electric s Residential New Construction, HVAC Retrofit and Commercial Custom Rebate Programs: FY2007/08 Submitted to: Roseville Electric February 27, 2009 Final
Regency TAFE, SA. An evaluation of the effects of PermaFrost treatment on a Fujitsu Heat Pump. July 2008. Prepared by
Regency TAFE, SA An evaluation of the effects of PermaFrost treatment on a Fujitsu Heat Pump July 2008 Prepared by Andrew Pang Andrew Pang & Associates Pty Ltd Phone: 0438 188 180 Facsimile: 9331 0898
Measurement And Application of Performance Characteristics Of A Free Piston Stirling Cooler
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 00 Measurement And Application of Performance Characteristics Of A Free Piston
J O U R N A L. Energy Performance for. Proper Specification of Air Terminal Units Future Climate Impacts on Building Design
Copyright 24, American Society of Heating, Refrigerating & Air-Conditioning Engineers, Inc., 79 Tullie Circle NE, Atlanta, GA. 3329. Reprinted by permission from the September 24 Issue of ASHRAE Journal
Elements of Energy Efficiency in Data Centre Cooling Architecture
Elements of Energy Efficiency in Data Centre Cooling Architecture Energy Efficient Data Center Cooling 1 STULZ Group of Companies Turnover 2006 Plastics Technology 400 Mio A/C Technology 200 Mio Total
Understanding Compressor Modulation in Air Conditioning Applications. The key to addressing capacity and energy efficiency needs.
Understanding Compressor Modulation in Air Conditioning Applications The key to addressing capacity and energy efficiency needs. Table of Contents Chapter 1 Compressor Modulation Overview Purpose of ebook
ZUBA-CENTRALTM. Heating & Cooling. Evolved. HEATING AND AIR CONDITIONING FOR WHOLE-HOME, YEAR-ROUND COMFORT
ZUBA-CENTRALTM Heating & Cooling. Evolved. HEATING AND AIR CONDITIONING FOR WHOLE-HOME, YEAR-ROUND COMFORT Energy-efficient. Easy to install. Extremely quiet. Zuba-Central is simply the new and better
1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53%
1 1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53% 2. How much money do commercial facilities spend per square foot on energy costs
Final Report by Air Conditioner Evaluation Standard Subcommittee, Energy Efficiency Standards Subcommittee of the Advisory Committee for Natural
Final Report by Air Conditioner Evaluation Standard Subcommittee, Energy Efficiency Standards Subcommittee of the Advisory Committee for Natural Resources and Energy Regarding air conditioners, the target
Evolution Extreme Heat Pump
Prior to Your Purchase Bryant has a history of doing whatever it takes to deliver trusted quality, comfort and value to millions of homeowners nationwide. The Evolution Extreme heat pump offers an exceptionally
Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER
Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER SUMMARY A proper balance of temperature and humidity control is essential for efficient data center operation, and integral
Vitocaldens 222-F Compact Gas-Hybrid appliance
Vitocaldens 222-F Compact Gas-Hybrid appliance Heating systems Industrial systems Refrigeration systems 2/3 Vitocaldens 222-F: The future-proof energy-source mix in one appliance Choosing Vitocaldens