Construction Engineering. Research Laboratory. Membrane and Flashing Condition Indexes for Modified Bitumen Roofs ERDC/CERL TR-10-5
|
|
|
- Polly Foster
- 10 years ago
- Views:
Transcription
1 ERDC/CERL TR-10-5 Membrane and Flashing Condition Indexes for Modified Bitumen Roofs Inspection and Distress Manual David M. Bailey March 2010 Construction Engineering Research Laboratory Approved for public release; distribution is unlimited.
2
3 ERDC/CERL TR-10-5 March 2010 Membrane and Flashing Condition Indexes for Modified Bitumen Roofs Inspection and Distress Manual David M. Bailey Construction Engineering Research Laboratory U.S. Army Engineer Research and Development Center 2902 Newmark Drive Champaign, IL Final report Approved for public release; distribution is unlimited. Prepared for Under The Assistant Chief of Staff for Installation Management (ACSIM) Arlington, VA Reimbursable Customer Order MIPR8H0DFG7068, Implementation Guidance to Installations for Sustainment Management Systems Compliance
4 ERDC/CERL TR-10-5 ii Abstract: The U.S. Army is currently responsible for maintaining millions of square feet of modified bitumen roofing on its facilities. Modified bitumen roofing systems share a number of characteristics with other common systems, but they also employ certain unique materials and therefore have their own specialized distress and degradation mechanisms. Dedicated inspection guidance and condition index calculation methods are required to quantify the condition of an installation s modified bitumen roofing assets in order to make the best use of Army maintenance and repair resources. This document was developed to provide roof inspectors with a standard reference for performing inspections, and calculating a flashing condition index (FCI) and membrane condition index (MCI) for use in facility maintenance management activities. It represents a new implementation of the widely used ROOFER Sustainment Management System for roofing asset management. DISCLAIMER: The contents of this report are not to be used for advertising, publication, or promotional purposes. Citation of trade names does not constitute an official endorsement or approval of the use of such commercial products. All product names and trademarks cited are the property of their respective owners. The findings of this report are not to be construed as an official Department of the Army position unless so designated by other authorized documents. DESTROY THIS REPORT WHEN NO LONGER NEEDED. DO NOT RETURN IT TO THE ORIGINATOR.
5 ERDC/CERL TR-10-5 iii Table of Contents List of Figures and Tables...v Preface...vi Unit Conversion Factors...vii 1 Introduction... 1 Background... 1 Objective... 1 Approach... 2 How to use this manual... 2 Mode of technology transfer Procedures for Roof Inspection and Calculation of Indexes... 4 Introduction... 4 Roof sections... 4 Roof plans... 5 Inspection procedure... 7 Survey team... 7 Supplies... 7 Survey preparation... 8 Distress survey... 8 Inspection guidelines...10 Base flashing...10 Metal cap flashing...10 Embedded edge metal...10 Flashed penetrations...11 Interior drains and roof-level scuppers...11 Membrane...11 General...11 FCI and MCI calculations...12 Determine deduct values...12 Determine corrected deduct values...15 Compute FCI and MCI...15 RCI calculation Flashing Distresses...18 Base Flashing (BF)...18 Metal Cap Flashing (MC)...23 Embedded Edge Metal (EM) Flashed Penetrations (FP) Pitch Pans (PP)...34 Interior Drains and Roof-Level Scuppers (DR)... 37
6 ERDC/CERL TR-10-5 iv 4 Membrane Distresses...40 Blisters (BL)...40 Ridges (RG)...43 Splits (SP)...46 Holes (HL)...48 Defective Seams (DS)...50 Surface Deterioration (SR)...53 Slippage (SL)...57 Patching (PA)...59 Debris and Vegetation (DV)...61 Improper Equipment Supports (EQ)...63 Ponding (PD)...65 Appendix A: Deduct Value Curves...68 Appendix B: Inspection and Rating Forms...79 Report Documentation Page
7 ERDC/CERL TR-10-5 v List of Figures and Tables Figures Figure 1. Roof inspection worksheet with roof section plan... 6 Figure 2. Legend to be used on roof section plans... 7 Figure 3. Example of completed roof inspection worksheet... 9 Figure 4. Example of completed roof section rating form Figure 5. Steps for determining condition indexes and ratings Figure 6. Flashing and membrane condition indexes (FCI and MCI) and ratings Tables Table 1. Determination of corrected flashing deduct value using data from Figure Table 2. Determination of corrected membrane deduct value using data from Figure
8 ERDC/CERL TR-10-5 vi Preface This study was conducted for U.S. Army Assistant Chief of Staff for Installation Management (ACSIM), under Reimbursable Customer Order MIPR8H0DFG7068, Implementation Guidance to Installations for Sustainment Management Systems Compliance, dated 30 June The technical monitor was Phil Columbus, Assistant Chief of Staff for Installation Management, Facilities Policy Directorate (DAIM-ODF). The work was performed by the Materials and Structures Branch (CF-M) of the Facilities Division (CF), U.S. Army Engineer Research and Development Center Construction Engineering Research Laboratory (ERDC- CERL). At the time of publication, Vicki L. Van Blaricum was Chief, CEERD-CF-M; L. Michael Golish was Chief, CEERD-CF; and Martin J. Savoie was the Technical Director for Installations. The Deputy Director of ERDC-CERL was Dr. Kirankumar Topudurti, and the Director was Dr. Ilker Adiguzel. Many of the procedures, figures, and methods presented in this manual were previously developed in ROOFER implementations for bituminous built-up roofs, single-ply roofs, and asphalt shingle steep roofs. This inspection and distress manual incorporates applicable technology from established ROOFER implementations as well as adaptations and new methodologies specifically for modified bitumen roofing systems. The following individuals are acknowledged for their technical review and comment on draft versions of this manual: William Andy Anderson, Architect, Engineering Services, Department of Public Works, Fort Riley, KS Dane Bradford, President, Bradford Roof Management, Inc., Billings MT Tim Benzie, INSPEC, Minneapolis, MN. COL Gary E. Johnston was the Commander and Executive Director of ERDC, and Dr. James R. Houston was the Director.
9 ERDC/CERL TR-10-5 vii Unit Conversion Factors Multiply By To Obtain feet meters inches meters mils millimeters square feet square meters
10 ERDC/CERL TR Introduction Background Objective In order to help effectively track the condition and maintenance requirements of the most widely used roofing systems installed on facilities managed by the U.S. military services, the U.S. Army Engineer Research and Development Center Construction Engineering Research Laboratory (ERDC-CERL) and other agencies developed a Sustainment Management System * called ROOFER. Previous implementations of ROOFER have been developed for bituminous built-up roofs (Bailey et al. 1989; Bailey, Brotherson, and Tobiasson 1989), single ply roofs (Bailey et al. 1993), and asphalt shingle steep roofs (Bailey 1999). The U.S. Army is currently responsible for maintaining millions of square feet of modified bitumen roofing on its facilities. Modified bitumen roofing systems share a number of characteristics with other common systems, but they also employ certain unique materials and therefore have their own specialized distress and degradation mechanisms. Dedicated inspection guidance and condition index calculation methods are required to quantify the condition of an installation s modified bitumen roofing assets in order to make the best use of Army maintenance and repair resources. This document was developed to provide roof inspectors with a standard reference for performing inspections, and calculating a flashing condition index (FCI) and membrane condition index (MCI) for use in facility maintenance management activities. The objective of this work was to develop ROOFER inspection procedures specifically for modified bitumen roofing systems based on visual inspection of the flashing and membrane components. * Sustainment Management Systems were originally referred to as Engineered Management Systems, or EMS.
11 ERDC/CERL TR Approach The concepts and theory behind the ROOFER condition indexing methodology, and the process used to develop and field-validate the distress definitions and deduct value curves, were documented in Shahin, Bailey, and Brotherson (1987a). The procedures for determining membrane and flashing condition indexes for built-up and single-ply roofs (Shahin, Bailey, and Brotherson 1987b; Bailey et al. 1993) provide a basis for the current work. An initial inspection and distress manual for modified bitumen roofing systems was developed by identifying similar applicable distresses from the established built-up and single-ply procedures, then making necessary modifications to more accurately assess modified bitumen roof condition. The modified bitumen procedures were finalized through iterations of field testing and revision to refine the distress definitions. How to use this manual Chapter 2 describes inspection and condition evaluation procedures for modified bitumen roofs using the established ROOFER methodology. Descriptions and illustrations of distresses for flashings and the membrane are presented in Chapters 3 and 4, respectively. Those chapters provide detail about the distresses, severity levels, defect definitions, measurement criteria, and photographs of applicable defects. Inspectors should study this manual and carry a copy for reference during inspections. Results of the roof inspections are to be used in conjunction with the calculation procedures described in Chapter 2 to determine the FCI and MCI and the corresponding condition ratings. The computed indexes are also used to determine a roof condition index (RCI) that provides an overall measure of the roof condition. For reference, Appendix A contains the deduct value curves for every modified bitumen roof system component and distress. Appendix B includes a blank specimen of both the ROOFER roof inspection worksheet and the roof section rating form, which may be photocopied for use by inspectors. Mode of technology transfer Information about the ROOFER SMS, computer software, support, training, and implementation costs are available at the U.S. Army Engineer Research and Development Center online fact sheet navigation page:
12 ERDC/CERL TR Inquiries about ROOFER may be directed to Chief, Materials and Structures Branch (CEERD-CF-M), U.S. Army Engineer Research and Development Center Construction Engineering Research Laboratory (ERDC- CERL), P.O. Box 9005, Champaign, IL ,
13 ERDC/CERL TR Procedures for Roof Inspection and Calculation of Indexes Introduction Determining the condition indexes for modified bitumen roofing requires measurement of all current roof flashing and membrane distresses. A thorough roof inspection must be made to determine the types, severity, specific defects, and amounts (density) of each distress present. This inspection must be carefully organized and planned in order to provide the necessary information for determining the flashing and membrane conditions. For the purposes of this document, a modified bitumen roofing system is defined as a membrane system that can be used for low-slope roof applications. The membrane consists of at least two plies comprising a base layer and a surface layer. One or both layers consist of a rolled sheet material having a bitumen and polymer blend that provides waterproofing. The polymer modifiers, which can be elastomeric or thermoplastic, provide enhanced mechanical and physical properties. The surface layer will typically be a factory-applied mineral surface, a smooth surface with an added coating, a metal foil surface, or a layer of aggregate embedded in bitumen. This chapter presents the procedures for visually inspecting bituminous modified bitumen roofs and computing the flashing and membrane condition indexes. Roof sections Dividing a building s roof into sections and rating each separately provides a more accurate indication of maintenance and repair requirements because (1) a roof section that is in poor condition does not detract from the condition index of a good roof section on the same building and (2) a condition index indicating that replacement of the section is necessary does mean that the entire roof needs to be replaced. The division of a roof into sections, therefore, helps to avoid unnecessary asset management costs by excluding intact portions of the roof that require no repair and focusing on sections that have advanced degradation or may fail soon.
14 ERDC/CERL TR Roof plans A roof section is generally delineated by at least one of the following boundaries or distinctions: expansion joints or area dividers different roof elevations areas of major repair or replacement areas that were built at different times areas having different roof systems, different amounts of rooftop traffic, rooftop equipment, or radically different occupancies below the roof areas having particularly sensitive occupancies below, such as computer centers, operating rooms or command centers Some judgment is necessary in cases where the roof is segmented into very small areas or if there are no identifiable delineations on large roofs. Small sections may be combined where practical. However, areas with clearly different characteristics, such as different roofing systems, supporting structural systems, or environments below the roof structure (e.g., canopies, freezers, unheated warehouses) should be treated as individual sections. Large areas without delineations can be divided into sections with areas of 25,000 to 40,000 sq ft. Each roof section should have a roof plan drawn to a scale (approximately 1 in. = 30 ft) that fits on the roof inspection worksheet (Figure 1). The plan should show all physical roof features, including perimeter conditions (roof edge, expansion joint, penthouse, etc.), rooftop equipment, projections through the roof, roof drains, walkways, sign supports, piping, etc. Standard symbols, such as those shown in Figure 2, should be used to identify these items whenever possible.
15 ERDC/CERL TR Figure 1. Roof inspection worksheet showing roof section plan.
16 ERDC/CERL TR Inspection procedure Survey team Figure 2. Legend showing standard symbols to be used on roof section plans. The roof inspection should be performed by a team of at least two people: an inspector and a recorder. The inspector surveys the roof, identifying distresses and determining severity levels, specific defects, and quantities. The recorder fills in the information on the roof inspection worksheet and assists in measuring distress quantities when required. The recorder must also serve as the safety observer for the team. Supplies The following supplies are required for performing the inspection: this inspection and distress manual pencil and clipboard roof inspection worksheets small 3 in. pointing trowel (to scrape granules, dirt, and debris) can of spray paint lumber crayon
17 ERDC/CERL TR stiff bristle whisk broom pocket knife 12 ft and 100 ft measuring tapes large plastic bag (to collect rooftop debris) satchel (for carrying tools and materials). Survey preparation Before beginning the inspection, the roof section plan should be developed (or verified, if a plan already exists). Check plan dimensions against actual field dimensions. Locate all penetrations, projections, rooftop equipment, and perimeter conditions on the plan. Measure and record dimensions on the roof plan. Measure and record the total length of perimeter flashing, which is the flashing at the perimeter of the roof section (i.e., roof edge, expansion joint, area divider, parapet wall, etc.) in the appropriate space on the heading of the roof inspection worksheet. Also determine and record on the worksheet the length of curb flashing around rooftop penetrations (i.e., equipment curbs). These flashing quantities are important because they are used to determine the relative amounts of flashing defects as compared with the total amount of flashing component that exists on the roof section. Distress survey Perform the distress survey using the following sequence: 1. Inspect the perimeter flashing. Establish a starting point at one corner of the roof section. Walk the entire perimeter, examining the base flashing, embedded edge metal flashing, and metal cap flashing. 2. Identify all distresses and specific defects according to the distress manual. Mark each medium- and high-severity distress with spray paint or a lumber crayon. Enter each identified distress by type, severity level, specific defect (specific defects are listed numerically for each distress [see Chapters 3 and 4]), and quantity on the Roof Inspection Worksheet. Note the location of each distress on the roof plan using an identification number, as shown in Figure 3. Determine the distress quantities using the measurement criteria provided for the particular distress. 3. After inspecting the perimeter, work across the roof area inspecting all other flashings: curbed penetrations, flashed penetrations, pitch pans, drains, etc. Record the data on the Roof Inspection Worksheet.
18 ERDC/CERL TR Figure 3. Example of completed roof inspection worksheet.
19 ERDC/CERL TR Inspect the roof membrane. Establish a starting point at one corner of the roof section. Survey that section by inspecting strips ft wide, proceeding back and forth until the entire membrane has been inspected. Record the data. 5. Complete the Remarks section on the back of the roof inspection worksheet. Note: It is imperative to use the distress definitions listed in this manual (Chapters 3 and 4) when performing roof inspections. If these definitions are not followed, accurate indexes cannot be developed. Use a second roof inspection worksheet if the first one becomes filled. Inspection guidelines The guidelines below should be followed when performing the visual inspection and distress survey. Base flashing Measure the height of top termination of base flashing above the roof surface. To establish the height, run fingers up behind the counterflashing. If the base flashing height cannot be determined, assume it is adequate. Metal cap flashing Check for looseness of metal cap flashing by attempting to lift it by hand at several locations. Embedded edge metal Check that the embedded edge metal flashing is secure by attempting to lift the outside edge. For roof surfaces where defects above the joints in the underlying course of edge metal are not readily apparent (i.e., embedded aggregate surfacing), use the following sampling technique. Determine the total number of joints by dividing the total length of embedded edge metal flashing by the stock length of the edge metal sections (typically 10 ft). Inspect every fourth joint for splits in the stripping plies, removing any loose granules, gravel or dirt from the joint using the small whisk broom and pointing trowel. Determine the number of inspected joints that are high severity (i.e., have splits in the stripping plies) and multiply by 4 to get the total number of high-severity joints (one joint equals 1 ft). All other joints are considered medium-severity. Multiply the number of inspected joints
20 ERDC/CERL TR not counted as high-severity by 4 to obtain the total number of mediumseverity joints. Flashed penetrations Check the height of the flashing sleeve above the roof surface. Use a whisk broom and trowel to examine stripping plies. Interior drains and roof-level scuppers Check all drains and scuppers and remove debris whenever possible. When inspecting drains, make sure the clamping ring is tight. Stripping plies around scuppers should be inspected for holes at corners. Membrane Membrane inspection requires surveying the entire roof area. However, when large areas of a particular distress and severity level are present, the representative sampling technique can be used. Select a portion of the roof (approximately 1,000 sq ft) that appears to be typical of the entire roof area. Measure the quantity of distress in the sample area and, by extrapolation, calculate the quantity for the entire roof area. An area that differs greatly from the majority of the roof should be surveyed separately. General The following is a list of general guidelines for the roof inspection: Be careful not to damage the roof. Do not step on blisters, kick base flashing, or step on edge flashing. Note existing problems that are not included in the lists of flashing and membrane distresses in the "remarks" section on the back of the worksheet. Walk the building perimeter at ground level and look for water stains, efflorescence, missing mortar, spalled brick, and gutter and drainage problems. Walk the interior of the building and examine the ceiling below the roof deck for water marks. Note rusting or other signs of water penetration or leaks in the "remarks" section on the back of the worksheet. If there is snow or a large area of ponding on the roof, postpone the inspection until the roof is clear. Wherever possible, use a measuring tape to determine roofing distress quantities. Estimating is acceptable when necessary, but the rating ac-
21 ERDC/CERL TR curacy will be only as good as the estimating accuracy. Pacing to find lengths, or some other quantifying estimating method, is preferable to an eyeball estimate. If more than one severity level of a distress exists in a localized area, assign the highest severity level to the entire area. FCI and MCI calculations The FCI and MCI of a roof section are determined from the information recorded on the roof inspection worksheet. The condition indexes can be calculated by entering the distress information into the ROOFER software program. The indexes can also be determined manually using the roof section rating form (Figure 4) with the following procedure. A blank copy of the form is provided in Appendix B. With the initial step being the visual inspection, the other steps for manual determination are described below and illustrated in Figure 5. Determine deduct values Use information from the roof inspection worksheet to complete the heading section of the roof section rating form. Transfer the quantities for each combination of distress type and severity level to the roof section rating form, as illustrated in Figure 4. Flashing distresses are tabulated on the left side of the page and membrane distresses on the right. Total the quantities for each severity of each distress, calculate each density using the distress-specific equations given in Chapters 3 and 4, and determine deduct values (DV) using the distress-specific deduct value curves in Appendix A.
22 ERDC/CERL TR Figure 4. Example of completed roof section rating form.
23 ERDC/CERL TR Step 1. Inspect roof. Determine distress types, severity levels and defects. Determine quantities and calculate densities. Step 2. Determine deduct values. CORRECTED DEDUCT VALUES Corrected Deduct Values for Flashing. q=1 q=2 q=4 q=6 q=> SUM OF DEDUCT VALUES q = number of deducts greater than 1 point. Step 3. Compute corrected deduct value. Step 4. Compute cond. index Figure 5. Steps for determining condition indexes and ratings.
24 ERDC/CERL TR Determine corrected deduct values Tabulate flashing deduct values in descending order using the data obtained from the roof section rating form. Table 1 illustrates how the flashing component deduct value would be determined manually using the example data shown in Figure 4. Calculate the sum of the flashing deduct values ( DV) and the sum of the number of distresses with deduct values greater than 1 (DV <1 = q), then use those two values and the component-specific deduct graph in Appendix A to determine corrected deduct values (CDV) for the flashing distresses. Select the maximum value of CDV, as shown in bold in Table 1. In this case the Max. CDV flashing is 24. Table 1. Determination of corrected flashing deduct value using data from Figure 5. DV DV q CDV flashing Use the same process in conjunction with the distress-specific graph in Appendix A to determine the maximum corrected deduct value for the membrane. In this case, using the example data from Figure 4, the Max. CDV membrane is 16 (shown in bold type in Table 2). Table 2. Determination of corrected membrane deduct value using data from Figure 5. DV DV q CDV membrane Compute FCI and MCI Calculate flashing and membrane condition indexes using the following equations:
25 ERDC/CERL TR FCI = Max. CDV flashing MCI = Max. CDV membrane Determine the corresponding descriptive condition ratings from Figure 6 for both indexes. For these data, FCI = 76 and MCI = 84, meaning that both the flashings and membrane are rated very good. RCI calculation Figure 6. Flashing and membrane condition indexes (FCI and MCI) and ratings. Each individual index (FCI, MCI) reflects the component s ability to provide its intended service and indicates repair/replacement needs. As is typical with other low-slope membrane roofing systems, modified bitumen roofs normally will have one or more layers of insulation board placed between the membrane and roof deck. For those roofs having underlying insulation, these two condition indexes are combined with an insulation condition index (ICI). The ICI is determined us-
26 ERDC/CERL TR ing roof moisture survey techniques and gravimetric analyses of core cuts extracted from areas of wet insulation. Since the components must interact to function as a roof system, they are dependent on each other. The indexes, in total, provide an assessment of the condition of the roof section. By combining these indexes, a roof condition index (RCI) can be calculated. This single index is useful for evaluating the overall condition of a roof section and for comparing conditions between roof sections. The RCI allows the user to rank individual roof sections in accordance with their ability to perform. For insulated roofing systems, the following equation is used to determine the RCI: RCI = (0.7 x lowest condition index) + (0.15 x sum of the remaining condition indexes). For non-insulated roofs, which will not have an ICI, use the following equation. RCI = (0.7 x lowest condition index) + (0.3 x remaining condition index) The above equations gives the greatest weight to the component with the lowest condition index and then modifies it by adding value from the remaining index(es). The following example illustrates how this relationship works for the inspection results presented here and assuming that the ICI has been determined to be 100: Example: FCI = 76; MCI = 84; ICI = 100 RCI = (0.7 x 76) + (0.15 x 184) = 81
27 ERDC/CERL TR Flashing Distresses Base Flashing (BF) Description: Base flashing is one or more plies of material that extend from the roof surface up onto a vertical or inclined surface providing a watertight termination of the membrane. The base flashing surface ply may be mineral surfaced, smooth coated, uncoated, or metal foil surfaced. Base flashing details. Distress severity levels: Low: Any of the following defects: 1. Loss of granules or coating or delamination of foil surfacing and poor appearance (including patching) but no visible deterioration of base flashing. 2. Top of base flashing is less than 6 in. above the roof surface. 3. Flashing has permanent repairs. Medium: Any of the following defects: 1. Slippage, wrinkling, blistering, or pulling of base flashing material. 2. Loss of granules or coating or delamination of foil surfacing and some visible deterioration of base flashing; but no holes, splits, or tears. 3. Grease, solvent, or oil drippings on the base flashing but no visible deterioration of base flashing.
28 ERDC/CERL TR Flashing has temporary repairs. High: Any of the following defects: 1. Holes, splits, or tears in flashing caused by deterioration or physical damage. 2. Exposed gaps at the top of the base flashing which are not covered by counterflashing or open side laps in the flashing which allow water to channel behind them. 3. Grease, solvent, or oil drippings on the base flashing with deterioration through the base flashing. 4. No base flashing exists. Measurement: Measure lineal feet of base flashing having the above defects. Holes, open side laps, and seams count as 1 ft each. If an area of the base flashing is at medium severity and holes are closer than 6 in., count that entire length of distressed base flashing as high severity. Density: A Problem Density = 100 B A = length of base flashing defects (ft) B = total length of flashed perimeter of roof section being rated (including flashings for penthouses, courtyards, and curbed projections) Note: The problem density is calculated for each existing severity level. Causes: Flashing splits or tears can result from mechanical damage, material shrinkage, unattached membrane pulling the flashing, or differential movement between the wall and the deck. Delamination and sliding result from weak or no attachment between the flashing plies or between the flashing and the substrate. This can result from any of the following conditions: o When first installed, the flashing plies were not firmly pressed into the bitumen to form a solid, continuous laminate. o No primer was used on the wall.
29 ERDC/CERL TR o The wrong flashing adhesive was used to attach the flashing plies to the wall. o The flashing adhesive was improper, incompatible, incorrectly applied or of poor quality. o The hot-mopped bitumen was allowed to cool before the flashing plies were applied. o Fasteners were improper type or too few to hold flashing to substrate. o Inadequate heat-applied to back of torched materials. o Loss of surfacing on mineral surfaced materials can result from ambient temperatures being too high.
30 ERDC/CERL TR Reference photographs BF-L-2: Top of base flashing is less than 6 in. above the roof surface. BF-L-3: Flashing has permanent repairs. BF-M-1: Slippage, wrinkling, blistering, or pulling of base flashing material. BF-M-4: Flashing has temporary repairs. BF-H-1: Holes, splits, or tears in flashing caused by deterioration or physical damage. BF-H-2: Exposed gaps at the top of the base flashing that are not covered by counterflashing or open side laps in the flashing.
31 ERDC/CERL TR BF-H-4: No base flashing is present.
32 ERDC/CERL TR Metal Cap Flashing (MC) Description: Metal cap flashing includes counterflashing and any sheet metal coping cap which serves as part of the counterflashing or the cover over a detail such as a roof area divider, equipment curb, raised roof edge, or an expansion joint (including the rubber bellows of an expansion joint). Metal cap flashing details.
33 ERDC/CERL TR Counterflashing is the material, usually sheet metal, which protects the top termination of base flashing and sheds water away from it. Counterflashing should be free to expand and contract. Distress severity levels: Low: Any of the following defects: 1. Loss of paint or protective coating or start of metal corrosion. 2. Metal coping cap is deformed and allows water to pond on the top. 3. Counterflashing is deformed but still performing its function. 4. Counterflashing has been sealed to the base flashing. Medium: Any of the following defects: 1. Corrosion holes have occurred through the metal on a vertical surface. 2. Metal coping cap has loose fasteners, failure of soldered or sealed joints, open joints, or loss of attachment. 3. Sealant at reglet or top of counterflashing is missing or no longer functioning, allowing water to channel behind counterflashing. 4. Counterflashing is loose at the top, allowing water to channel behind it. 5. Counterflashing does not extend over top of base flashing. High: Any of the following defects: 1. Metal coping cap or counterflashing is missing or displaced from its original position. 2. Corrosion holes have occurred through the metal on a horizontal surface or rubber bellows of an expansion joint cover. 3. Metal coping cap has missing joint covers where joint covers were originally installed. Measurement: Measure lineal feet of metal cap flashing having the above defects. Individual defects (i.e., joints, holes) count as one foot minimum. Density: A Problem Density = 100 B A = length of metal cap flashing defects (ft)
34 ERDC/CERL TR B = total length of flashed perimeter of roof section being rated (including flashings for penthouses, courtyards, and curbed projections) Note: The problem density is calculated for each existing severity level.
35 ERDC/CERL TR Reference photographs MC-L-2: Metal coping cap is deformed and allows water to pond on the top. MC-M-2: Metal coping cap has loose fasteners, failure of soldered or sealed joints, open joints, or loss of attachment. MC-M-3: Sealant at reglet or top of counterflashing is missing or no longer functioning, allowing water to channel behind. MC-H-1 : Metal coping cap or counterflashing is missing or displaced from its original position. MC-H-2: Corrosion holes penetrating metal on horizontal surface or rubber bellows of an expansion joint cover. MC-H-3: Metal coping cap has missing joint covers where joint covers were originally installed.
36 ERDC/CERL TR Embedded Edge Metal (EM) Description: Formed strip of metal at the roof edge which continues down the vertical part of the wall to form a fascia or drip. The roof flange of the metal flashing may be covered by the surfacing ply or separate stripping plies. This flashing provides a finished termination for the roofing membrane. A formed vertical projection (gravel stop) may be incorporated to prevent loose aggregate from rolling or washing off the roof. Exterior and interior gutters, which are embedded into the membrane, are considered as embedded edge metal. (An interior gutter is a built-in trough of metal or other material which collects water from the roof and carries it to a downspout.) Embedded edge metal details. Note: A raised roof edge which is not stripped in, is rated as metal cap flashing and not as embedded edge metal.
37 ERDC/CERL TR Distress severity levels: Low: 1. The entire length of embedded edge metal flashings is rated low severity as a minimum due to the maintenance problems associated with it. Medium: Any of the following defects: 1. The joints in embedded edge metal flashings are rated medium severity as a minimum due to the maintenance problems associated with them. 2. Loss of granules or coating or delamination of foil surfacing and some deterioration of surfacing plies; but no holes, splits, or tears. 3. Nails attaching the metal to the nailer are backing out or are exposed. 4. Corrosion of the metal. 5. Loose or lifted metal flange without deterioration of the surfacing plies. 6. The entire length of interior gutter is rated medium severity as a minimum due to the maintenance problems and high potential for leak damage associated with its presence. High: Any of the following defects: 1. Surfacing plies are loose or missing, leaving metal flange exposed. 2. Splits in the surfacing plies above the metal joints. 3. Holes, splits, or tears in surfacing plies caused by deterioration or physical damage. 4. Holes have occurred through the metal. 5. Loose or lifted metal flange with deterioration of the surfacing plies. 6. Holes or joint movement are present in the interior gutter. Measurement: Measure lineal feet of embedded edge metal flashing having the above defects. Each split above a joint is counted as one foot. As a method of sampling the joints, determine the total number of joints by dividing the total length of embedded edge metal flashing by the length of edge metal sections (normally 10 ft). Every fourth joint should be inspected for splits in the surfacing plies. Count the number of inspected joints that are high severity and multiply by 4 to determine the total lineal feet of high-severity joints. All other joints are rated medium severity. Multiply the number of inspected joints not rated high severity by 4 to determine the total lineal feet of medium-severity joints.
38 ERDC/CERL TR Density: A Problem Density = 100 B A = length of embedded edge metal flashing defects (ft) B = total length of flashed perimeter of roof section being rated (including flashings for penthouses, courtyards and curbed projections) Note: The problem density is calculated for each existing severity level. Causes: Splits in the surfacing plies and loose surfacing plies are caused by: o Insufficient or improper nailing of the metal flange allowing it to move. o Insufficient or no priming of the metal flange (top and bottom) before installation. This prevents bonding of the bitumen to the metal. o The widely different expansion coefficients of the metal and bituminous components. o Inadequate adhesive or inadequate heat for the application of torch applied materials. Exposed metal flanges can result from surfacing ply deterioration or the flange may never have been stripped-in. Loose or lifted metal edge is caused by insufficient fastening, rotting, or lack of a wood perimeter nailer.
39 ERDC/CERL TR Reference photographs EM-L-1: The entire length of embedded edge metal flashings is rated low severity at minimum due to the maintenance problems. EM-M-3: Nails attaching the metal to the nailer are backing out or exposed. EM-M-6: Entire length of interior gutter is rated medium severity at minimum due to the maintenance problems. EM-H-1: Surfacing plies are missing or loose. EM-H-2: Splits in the surfacing plies above the metal joints.
40 ERDC/CERL TR Flashed Penetrations (FP) Description: Open pipes, plumbing vent stacks, flues, ducts, continuous pipes, guy wires, drain sumps, and other penetrations through the roof membrane (excluding pitch pans but including metal curbing for hatches and ventilators), where the flange is stripped into the membrane. Flashed penetration details. Distress severity levels: Low: Any of the following defects: 1. Flashing sleeve is deformed. 2. Opening in the penetration or flashing is less than 6 in. above the roof surface. 3. Loss of granules or coating or delamination of foil surfacing and poor appearance (including patching) but no visible deterioration of stripping ply. Medium: Any of the following defects: 1. Loss of granules or coating or delamination of foil surfacing and some deterioration of stripping ply; but no holes, splits, or tears. 2. Top of flashing sleeve is not sealed or has not been rolled down into an existing plumbing vent stack. 3. The sleeve or umbrella is open or no umbrella is present (where required). 4. Metal is corroded.
41 ERDC/CERL TR High: Any of the following defects: 1. Flashing sleeve or metal curb has been installed with no stripping plies. 2. Flashing sleeve or metal curb is cracked, broken, or corroded through. 3. No flashing sleeve is present. 4. Penetration is not sealed at the membrane level. 5. Holes, splits, or tears in stripping ply caused by deterioration or physical damage. Measurement: Count each distressed flashed penetration as one linear ft at the highest severity level which exists. For metal curbs and ducts with greater than 1 ft of perimeter, count the actual length (in feet) of distressed perimeter. Density: A Problem Density = 100 B A = lineal feet of distressed flashed penetrations B = total length of flashed perimeter of roof section being rated (including flashings for penthouses, courtyards and curbed projections) Note: The problem density is calculated for each existing severity level.
42 ERDC/CERL TR Reference photographs FP-L-1: Flashing sleeve is deformed. FP-L-2: Opening in the penetration or flashing is less than 6 in. above the roof surface. FP-M-2: Top of flashing sleeve is not sealed or has not been rolled down into an existing plumbing vent stack. FP-M-3: The sleeve or umbrella is open or no umbrella is present (where required). FP-H-1: Flashing sleeve or metal curb has been installed with no stripping plies. FP-H-3: No flashing sleeve is present.
43 ERDC/CERL TR Pitch Pans (PP) Description: A pitch pan is a flanged metal sleeve placed around a roofpenetrating element and filled with a sealer. Distress severity levels: Low: Pitch pan details. 1. Pitch pans are rated low severity as a minimum due to the maintenance problems associated with them. Medium: 1. Loss of granules or coating or delamination of foil surfacing and some deterioration of the stripping ply; but no holes, splits, or tears. High: Any of the following defects: 1. Metal corrosion. 2. Sealing material is below metal rim. 3. Holes, splits, or tears in stripping ply caused by deterioration or physical damage. 4. Sealing material has cracked or separated from pan or penetration. Measurement: Each distressed pitch pan should be counted once at the highest severity level that exists.
44 ERDC/CERL TR Density: A Problem Density = 100 B A = number of distressed pitch pans B = total length of flashed perimeter of roof section being rated (including flashings for penthouses, courtyards, and curbed projections) Note: The problem density is calculated for each existing severity level.
45 ERDC/CERL TR Reference photographs PP-L-1: Pitch pans are rated low severity as a minimum due to the maintenance problems associated with them. PP-H-2: Sealing material does not fill pitch pan to top of metal rim. PP-H-4 : Sealing material has cracked or separated from pan or penetration.
46 ERDC/CERL TR Interior Drains and Roof-Level Scuppers (DR) Description: A drain is a penetration at the roof membrane which allows water to flow from the roof surface into a piped drainage system. The drain fixture at the roof has a flange and/or clamping arrangement to which the roofing membrane is attached. The lead flashing may be covered by the surfacing ply or separate stripping plies. A roof-level scupper is a channel through a parapet or raised roof edge which is designed for peripheral drainage of the roof. Details for interior drain (left) and roof-level scupper (right). Note: Stripping plies around scuppers should be carefully inspected for holes at corners. Distress severity levels: Low: Either of the following defects: 1. Bitumen has flowed into the drain leader but the drain is not clogged. 2. Loss of granules or coating or delamination of foil surfacing and poor appearance (including patching) but no visible deterioration of surfacing/stripping ply. Medium: Any of the following defects: 1. Loss of granules or coating or delamination of foil surfacing and some deterioration of surfacing/stripping ply; but no holes, splits, or tears. 2. Strainer is broken or missing.
47 ERDC/CERL TR Scupper shows loss of paint or protective coating or start of metal corrosion. 4. Field seam exists under clamping ring. High: Any of the following defects: 1. Holes, splits, or tears in stripping ply caused by deterioration or physical damage. 2. Clamping ring is loose or missing from drain body or bolts are missing. 3. Drain is clogged. 4. Scupper metal is broken or holes have occurred through the metal. Measurement: Each distressed drain and scupper should be counted once at the highest severity level which exists. Density: A Problem Density = 100 B A = number of distressed interior drains and roof-level scuppers B = total length of flashed perimeter of roof section being rated (including flashings for penthouses, courtyards and curbed projections) Note: The problem density is calculated for each existing severity level.
48 ERDC/CERL TR Reference photographs DR-L-1: Bitumen has flowed into the drain leader but the drain is not clogged. (Strainer was removed for photograph.) DR-M-1: Loss of granules or coating or delamination of foil surfacing and some deterioration of surfacing/stripping ply. DR-M-4: Field seam exists under clamping ring. DR-H-1: Holes, splits, or tears in stripping ply caused by deterioration or physical damage. DR-H-3: Drain is clogged.
49 ERDC/CERL TR Membrane Distresses Blisters (BL) Description: Blisters are round or elongated raised areas of the membrane which are filled with air. Note: Blisters and ridges are difficult to differentiate at the low and medium severity levels. The rating error will be insignificant because of the similarity in the deduct curves. At high severity, however, it is important to distinguish between the two distresses due to their different leak potentials. Blister severity levels: Low: 1. The raised areas are noticeable by vision or feel. The surfacing is still in place and there is no membrane deterioration. Medium: Either of the following defects: 1. The raised areas have a loss of surfacing (on mineral-surfaced membrane) and some deterioration of the membrane; but no holes, splits or tears. 2. Blister is beneath a seam, which has exposed unsurfaced membrane along the seam. High: Either of the following defects: 1. The blisters are broken; there are holes, splits or tears. 2. Blister is beneath a seam, that has separated the surfacing plies at the lap and seam is open through its entire depth allowing water to penetrate.
50 ERDC/CERL TR Measurement: Measure the length and width of the blister in lineal feet and calculate the area (length times width). If the distance between individual blisters is less than 5 ft, measure the entire affected area in sq ft. When large quantities of this problem are present (especially on large roofs), the representative sampling technique can be used. Density: A Problem Density = 100 B A = total area of membrane blisters (sq ft) B = total area of roof section being rated (sq ft) Note: The problem density is calculated for each existing severity level. Causes: Blisters are caused by voids or lack of attachment within the membrane. Moisture and gasses within the void greatly increases the potential for growth.
51 ERDC/CERL TR Blister photographs BL-L-1: The raised areas are noticeable by vision or touch. The surfacing is still in place and there is no membrane deterioration. BL-L-1: The raised areas are noticeable by vision or feel. The surfacing is still in place and there is no membrane deterioration. BL-M-2: Blister is beneath a seam, which has exposed unsurfaced membrane along the seam. BL-H-1: The blisters are broken; there are holes, splits or tears. BL-H-1: The blisters are broken; there are holes, splits or tears.
52 ERDC/CERL TR Ridges (RG) Description: Ridges are long, narrow (usually less than 3 in. wide), raised portions of the roof membrane. Their maximum height is about 2 in. Usually ridges occur directly above the insulation board joints and run perpendicular or parallel to the felts. They typically include all the plies and therefore are generally stiffer than blisters. Note: Blisters and ridges are difficult to differentiate at the low and medium severity. The rating error will be insignificant because of the similarity in the deduct curves. However at the high severity, it is important to distinguish between the two distresses due to their different leak potentials. Distress severity levels: Low: 1. The ridges are noticeable but the surfacing is still in place and there is no membrane deterioration. Medium: Either of the following defects: 1. The ridges are raised and clearly visible. The raised areas have loss of granules or coating or delamination of foil surfacing and some deterioration; but no holes, splits, or tears. 2. The ridge runs across seams, which have exposed unsurfaced membrane along the seams but do not allow water to penetrate through. High: Either of the following defects: 1. Open breaks have developed in the ridge. 2. The ridge runs across seams, which have separated surfacing plies and the seams are open through their entire depth. Measurement: Measure lineal feet of ridges running in all directions. Density: A Problem Density = 100 B
53 ERDC/CERL TR A = total length of membrane ridges (ft) B = total area of roof section being rated (sq ft) Note: The problem density is calculated for each existing severity level. Causes: Ridging can be the result of internally generated moisture vapor collecting at insulation joints and affecting the membrane or of movement of the substrate.
54 ERDC/CERL TR Ridge photographs RG-L-1: The ridges are noticeable but the surfacing is still in place and there is no membrane deterioration.
55 ERDC/CERL TR Splits (SP) Description: Splits are tears that extend through the top surface ply. They vary in length from a few feet to the length of the roof, and in width from a hairline crack to more than an inch. Splits generally occur directly above the joints between the long sides of insulation boards and run in the direction the felts were installed. Distress severity levels: High: 1. An unrepaired split or a repaired split which has started to re-open. Measurement: Measure lineal feet of split. Density: A Problem Density = 100 B Causes: A = total length of membrane splits (ft) B = total area of roof section being rated (sq ft) There is little or no attachment between any of the following: membrane, insulation, vapor retarder (if any), and deck. Differential movement at deck joints. Structural movement within the roof system. Stress concentration due to shrinkage cracking of a poured deck. The membrane is too weak.
56 ERDC/CERL TR Reference photograph SP-H-1: An unrepaired split or a repaired split which has started to reopen.
57 ERDC/CERL TR Holes (HL) Description: A membrane hole is any visible opening that penetrates through the top surfacing ply. Holes can be of various sizes and shapes, and can be located anywhere on the roof surface. Distress severity levels: High: 1. All holes are considered high severity due to their high leak potential. Measurement: Count the total number of holes in the membrane. If the distance between two holes is less than 1 ft, count them as one hole. Density: A Problem Density = 100 B A = number of membrane holes B = total area of roof section being rated (sq ft)
58 ERDC/CERL TR Hole photographs HL-H-1: All holes are considered high severity due to their high leak potential. HL-H-1: All holes are considered high severity due to their high leak potential.
59 ERDC/CERL TR Defective Seams (DS) Description: Defective seams include incomplete, damaged, or weak seams that join two adjacent surfacing plies. Distress severity levels: Low: Either of the following defects: 1. Seam is open less than ½ inch. 2. Fishmouths, wrinkling, blistering or ridging at seam that is watertight. Medium: Any of the following defects: 1. Seam is open ½ inch or more, but does not allow water to penetrate the membrane. 2. Pinch wrinkle at seam. 3. Lap seam has exposed unsurfaced membrane (selvage edge) but does not allow water to penetrate the membrane. High: Either of the following defects: 1. Seam is open through its entire depth, allowing water to penetrate. 2. Fishmouths, wrinkling, blistering or ridging at the seams that allow water to penetrate. Measurement: Measure lineal feet of defective seams. Density: A Problem Density = 100 B A = total length of defective seams (ft) B = total area of roof section being rated (sq ft) Note: The problem density is calculated for each existing severity level.
60 ERDC/CERL TR Causes: Seams improperly made. Seams damaged in use. Misalignment of surface plies during application.
61 ERDC/CERL TR Defective seam photographs DS-L-1: Seam is open less than ½ inch. DS-L-1: Seam is open less than ½ inch. DS-M-1: Seam is open ½ inch or more, but does not allow water to penetrate the membrane. DS-H-1: Seam is open through its entire depth, allowing water to penetrate. DS-H-2: Fishmouths, wrinkling, blistering or ridging at the seams that allow water to penetrate.
62 ERDC/CERL TR Surface Deterioration (SR) Description: A modified bitumen membrane will generally have one of the following types of surfacing: mineral surface-cap, smooth liquid applied, metal foil or aggregate or may be unsurfaced. Note: Walkways are treated as part of the membrane surfacing. Distress severity levels: Low: Any of the following defects: 1. On aggregate surfacing, the aggregate is not embedded or is poorly embedded but the underlying ply remains covered with aggregate. 2. On smooth liquid applied surfacing, there is loss of coating but no visible deterioration of surfacing ply. 3. On smooth liquid applied surfacing, there is evidence of crazing of top surface with hairline cracks (alligatoring). 4. On mineral surfaced capsheet surfacing, there is loss of granules and poor appearance but no visible deterioration of surfacing ply. 5. On metal foil surfacing, there is delamination of foil surfacing and poor appearance but no visible deterioration of surfacing ply. 6. Walkway shows loss of surfacing, loss of adhesion, cracks, blistering or cracked coating. Medium: Any of the following defects: 1. On aggregate surfacing, the aggregate is displaced and the top coat of bitumen is exposed. 2. On mineral surfaced capsheet surfacing, there is loss of granules, exposing the surfacing ply. 3. On smooth liquid applied surfacing, there is a loss of surface coating and reinforcement is exposed. 4. On smooth liquid applied surfacing, alligator cracks extend down through the coating to the surfacing ply. 5. On metal foil surfacing, the foil is torn, peeled or missing; exposing the underlying bitumen. 6. On unsurfaced membranes, there is alligatoring or loss of material exposing the reinforcement, but no deterioration of the membrane.
63 ERDC/CERL TR High: Any of the following defects: 1. On aggregate surfaced roofs, the aggregate cover has been displaced and the underlying surfacing ply is deteriorated. 2. On mineral surfaced-cap sheet roofs, there is loss of granules, exposing the modified bitumen and membrane is deteriorated. 3. On smooth liquid applied surfacing, there is loss of surfacing, modified bitumen is exposed and membrane is deteriorated. 4. On smooth liquid applied surfacing, alligator cracks extend down to the reinforcement and the membrane is deteriorated. 5. On metal foil surfacing, the foil is torn, peeled or missing; exposing the reinforcement and the membrane is deteriorated. 6. Shrinking of the walkway has torn the membrane below it. Measurement: Measure square feet of each affected area and rate at highest severity level which exists. When large quantities of this problem are present (especially on large roofs), the representative sampling technique can be used. Density: A Problem Density = 100 B Causes: A = total area of surface deterioration (sq ft) B = total area of roof section being rated (sq ft) Note: The problem density is calculated for each existing severity level. Poor granule embedment in bitumen during manufacturing. Wind erosion such as occurs at roof corners and water erosion such as occurs when downspouts empty directly onto the membrane. Alligatoring results from over-application of bitumen or aging bitumen, combined with weathering and temperature cycling. The bitumen
64 ERDC/CERL TR gradually loses the ability to flow back together and alligatoring is enhanced. For metal foil surfacing, excessive heat applied to back of sheet during application. Inadequate top pour coat during aggregate application. Use of bitumen on a slope that is greater than proper for that bitumen. The bitumen and gravel run off, leaving the underlying ply exposed. This can affect localized areas or the entire roof. Inadequate embedment of aggregate during application.
65 ERDC/CERL TR Surface deterioration photographs SR-L-2: On smooth liquid applied surfacing, there is loss of coating but no visible deterioration of surfacing ply. SR-L-3: On smooth liquid applied surfacing, there is evidence of crazing of top surface with hairline cracks (alligatoring). SR-M-2: On mineral surfaced capsheet surfacing, there is loss of granules, exposing the surfacing ply. SR-M-2: On mineral surfaced capsheet surfacing, there is loss of granules, exposing the surfacing ply. SR-M-4: On smooth liquid-applied surfacing, alligator cracks extend down through coating to the surfacing ply.
66 ERDC/CERL TR Slippage (SL) Description: Slippage is a downslope lateral movement of membrane plies. Slippage usually occurs on roofs with slopes greater than 1/4 in./ft. Distress severity levels: Low: 1. Less than 2 in. of slippage has occurred, evidenced by the presence of narrow bare strips perpendicular to the slope. High: 1. More than 2 in. of slippage has occurred or the exposed bitumen has shown deterioration. There may be evidence of humping and wrinkling. Measurement: Measure square feet of affected roof area. The affected area extends from the high point on the slope where bare felts are noticeable, down to the low point of the slope or the area where humping and wrinkling are noticeable. Density: A Problem Density = 100 B Causes: A = total affected area of roof (sq ft) B = total area of roof section being rated (sq ft) Note: The problem density is calculated for each existing severity level. Inadequate fastening of membrane plies for the amount of roof slope present. Use of improper bitumen. Thickness of bitumen interply moppings is too great, reducing horizontal shear resistance between plies.
67 ERDC/CERL TR Slippage photographs SL-H-1: More than 2 in. of slippage has occurred or the exposed bitumen has shown deterioration. There may be evidence of humping and wrinkling. SL-H-1: More than 2 in. of slippage has occurred or the exposed bitumen has shown deterioration. There may be evidence of humping and wrinkling.
68 ERDC/CERL TR Patching (PA) Description: A localized repair of the membrane done with cold-applied adhesive with fabric or felt embedded in it, with hot bitumen and felts, or modified bitumen materials. It should be obvious that the work is not part of the original roof construction. Distress severity levels: Low: 1. All patches are rated low severity as a minimum. Medium: 1. The materials and workmanship of the patch are not equal to or better than the existing membrane. High: 1. Ruptures or other membrane distresses of at least medium severity are present within the patched area (count as patching distress only). Measurement: Measure square feet of each patch having the above defects. When large quantities of this problem are present (especially on large roofs), the representative sampling technique can be used. Density: A Problem Density = 100 B A = total area of patching (sq ft) B = total area of roof section being rated (sq ft) Note: The problem density is calculated for each existing severity level.
69 ERDC/CERL TR Patching photographs PA-M-1: The materials and workmanship of the patch are not equal to or better than the existing membrane. PA-M-1: The materials and workmanship of the patch are not equal to or better than the existing membrane. PA-H-1: Ruptures or other membrane distresses of at least medium severity are present within the patched area.
70 ERDC/CERL TR Debris and Vegetation (DV) Description: Foreign objects on the roof which could damage or puncture the membrane. The growth of vegetation on the roof. Accumulation of grease, solvent, or oil drippings on the roof. Distress severity levels: Medium: Any of the following defects: 1. The collection of foreign objects which are not removed from the roof during the inspection. 2. Grease, solvent, or oil drippings on the roof that show no degradation of the roof membrane. 3. Evidence of vegetation, but not penetrating the membrane. High: Either of the following defects: 1. Grease, solvent, or oil drippings on the roof that is causing degradation to the roofing system. 2. Vegetation roots that have penetrated the membrane. Measurement: Measure square feet of affected area. Each isolated case of debris and vegetation of less than 1 sq ft in area should be counted as 1 sq ft. Density: A Problem Density = 100 B A = total area of debris and vegetation (sq ft) B = total area of roof section being rated (sq ft) Note: The problem density is calculated for each existing severity level.
71 ERDC/CERL TR Debris and vegetation photographs DV-M-1: The collection of foreign objects which are not removed from the roof during the inspection. DV-M-2: Grease, solvent, or oil drippings on the roof which show no degradation of the roof membrane.
72 ERDC/CERL TR Improper Equipment Supports (EQ) Description: Pipe, conduit, and mechanical equipment supports (wood sleepers, channels, etc.) which are placed directly on the roof surface with no protective pad or placed at insufficient height to allow for maintaining the membrane below the equipment. Repairing this distress may require replacing the surrounding insulation and membrane. Note: Terminations for guy wires are to be rated as flashed penetrations. Distress severity levels: Low: 1. All improper equipment supports are rated low severity as a minimum due to the maintenance problems associated with them. Medium: Either of the following defects: 1. Movement of the support has caused displacement of the roof surfacing but has not damaged the membrane. 2. The equipment is bolted through the membrane but the bolts appear to be sealed. High: Either of the following defects: 1. The support has caused damage to the roof membrane. 2. The equipment is bolted through the membrane and the bolts appear not to be sealed. Measurement: Measure square feet of each improper equipment support. The minimum dimension for length and width of a support shall be 1 ft. Density: A Problem Density = 100 B A = total area of improper equipment supports (sq ft) B = total area of roof section being rated (sq ft) Note: The problem density is calculated for each existing severity level
73 ERDC/CERL TR Improper equipment support photographs EQ-L-1: All improper equipment supports are rated low severity as a minimum due to the maintenance problems. EQ-L-1: All improper equipment supports are rated low severity as a minimum due to the maintenance problems. EQ-M-2: The equipment is bolted through the membrane but the bolts appear to be sealed. EQ-H-2: The equipment is bolted through the membrane and the bolts appear not to be sealed.
74 ERDC/CERL TR Ponding (PD) Description: Standing water is present or there is evidence of ponding by the presence of staining. Water that remains for more than 48 hours after rainfall is considered ponded water. Distress severity levels: Low: 1. Ponding is rated low severity due to the maintenance problems associated with correcting it. Measurement: Measure square feet of affected area. Density: A Problem Density = 100 B A = total area of ponding (sq ft) B = total area of roof section being rated (sq ft) Causes: Improper design of roof drainage system. Irregularities of membrane surface. Clogged roof drains and scuppers or obstructions.
75 ERDC/CERL TR Ponding PD-L-1: Ponding is rated low severity due to the maintenance problems associated with it. PD-L-1: Ponding is rated low severity due to the maintenance problems associated with it.
76 ERDC/CERL TR References Bailey, D.M., ROOFER: Steep Roofing Inventory Procedures and Inspection and Distress Manual for Asphalt Shingle Roofs, CERL Technical Report 99/100/ADA (U.S. Army Construction Engineering Research Laboratory [CERL], December 1999). Bailey, D.M., D.E. Brotherson, W. Tobiasson, S. Foltz and A. Knehans, ROOFER: Membrane and Flashing Condition Indexes for Single-Ply Membrane Roofs - Inspection and Distress Manual, CERL Technical Report FM-93/11/ADA (CERL, April 1993). Bailey, D.M., D. Brotherson, W. Tobiasson, and A. Knehans, ROOFER: An Engineered Management System (EMS) For Bituminous Built-Up Roofs, CERL Technical Report M-90/04/-ADA (CERL, December 1989). Bailey, D.M., B. Young, S. Hansen, and J. Elston, Micro ROOFER User's Guide, CERL ADP Report M-90/12 (CERL, April 1990). Shahin, M.Y., D. Bailey, and D. Brotherson, Membrane and Flashing Condition Indexes for Built-Up Roofs Volume I: Development of the Procedure, Technical Report M-87/13/ADA (CERL, September 1987a). Shahin, M.Y., D. Bailey, and D. Brotherson, Membrane and Flashing Condition Indexes for Built-Up Roofs Volume II: Inspection and Distress Manual, Technical Report M-87/13/ADA (CERL, September 1987b).
77 ERDC/CERL TR Appendix A: Deduct Value Curves
78 ERDC/CERL TR
79 ERDC/CERL TR
80 ERDC/CERL TR
81 ERDC/CERL TR
82 ERDC/CERL TR
83 ERDC/CERL TR
84 ERDC/CERL TR
85 ERDC/CERL TR
86 ERDC/CERL TR
87 ERDC/CERL TR
88 ERDC/CERL TR Appendix B: Inspection and Rating Forms On the following pages are a roof inspection worksheet (front and back) and a roof section rating form that may be photocopied for use.
89 ERDC/CERL TR
90 ERDC/CERL TR
91 ERDC/CERL TR
92 REPORT DOCUMENTATION PAGE Form Approved OMB No Public reporting burden for this collection of information is estimated to average 1 hour per response, including the time for reviewing instructions, searching existing data sources, gathering and maintaining the data needed, and completing and reviewing this collection of information. Send comments regarding this burden estimate or any other aspect of this collection of information, including suggestions for reducing this burden to Department of Defense, Washington Headquarters Services, Directorate for Information Operations and Reports ( ), 1215 Jefferson Davis Highway, Suite 1204, Arlington, VA Respondents should be aware that notwithstanding any other provision of law, no person shall be subject to any penalty for failing to comply with a collection of information if it does not display a currently valid OMB control number. PLEASE DO NOT RETURN YOUR FORM TO THE ABOVE ADDRESS. 1. REPORT DATE (DD-MM-YYYY) 3. DATES COVERED (From - To) 2. REPORT TYPE Final March TITLE AND SUBTITLE Membrane and Flashing Condition Indexes for Modified Bitumen Roofs: Inspection and Distress Manual 5a. CONTRACT NUMBER 5b. GRANT NUMBER 5c. PROGRAM ELEMENT NUMBER 6. AUTHOR(S) David M. Bailey 7. PERFORMING ORGANIZATION NAME(S) AND ADDRESS(ES) U.S. Army Engineer Research and Development Center Construction Engineering Research Laboratory P.O. Box 9005 Champaign, IL d. PROJECT NUMBER 5e. TASK NUMBER MIPR8H0DFG7068 5f. WORK UNIT NUMBER 8. PERFORMING ORGANIZATION REPORT NUMBER ERDC/CERL TR SPONSORING / MONITORING AGENCY NAME(S) AND ADDRESS(ES) Office of the Assistant Chief of Staff for Installation Management Facilities Branch (DAIM-ODF) 2511 Jefferson Davis Highway Arlington, VA SPONSOR/MONITOR S ACRONYM(S) ACSIM 11. SPONSOR/MONITOR S REPORT NUMBER(S) 12. DISTRIBUTION / AVAILABILITY STATEMENT Approved for public release; distribution is unlimited. 13. SUPPLEMENTARY NOTES 14. ABSTRACT The U.S. Army is currently responsible for maintaining hundreds of millions of square feet of modified bitumen roofing on its facilities. Modified bitumen roofing systems share a number of characteristics with other common systems, but they also employ certain unique materials and therefore have their own specialized distress and degradation mechanisms. Dedicated inspection guidance and condition index calculation methods are required to quantify the condition of an installation s modified bitumen roofing assets in order to make the best use of Army maintenance and repair resources. This document was developed to provide roof inspectors with a standard reference for performing inspections, and calculating a flashing condition index (FCI) and membrane condition index (MCI) for use in facility maintenance management activities. It represents a new implementation of the widely used ROOFER Sustainment Management System for roofing asset maintenance management. 15. SUBJECT TERMS ROOFER, roofing inspection, engineered management systems, sustainment management systems, modified bitumen roofs, asset management 16. SECURITY CLASSIFICATION OF: 17. LIMITATION OF ABSTRACT a. REPORT Unclassified b. ABSTRACT Unclassified c. THIS PAGE Unclassified 18. NUMBER OF PAGES 90 19a. NAME OF RESPONSIBLE PERSON 19b. TELEPHONE NUMBER (include area code) Standard Form 298 (Rev. 8-98) Prescribed by ANSI Std
Commercial Roof Inspection Form
Inspection Date: Inspector: Building Information Building ID: No.: Used For: Year Roof Applied: Building Description: Permanent Temporary Building Type: Retail Industrial Residential Building Name: Building
Maintenance & Inspection Guide
ADDRESSING THE NEEDS OF OUR CUSTOMERS AND THE ENVIRONMENT ONE high Performance roofing SOLUTION AT A TIME. Maintenance & Inspection Guide TABLE OF CONTENTS Topic: Page: I. Introduction 1 II. Maintenance
Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association
Air-Conditioning, Heating, and Refrigeration Institute Sheet Metal and Air-Conditioning Contractors National Association GUIDELINE B-1997 ACKNOWLEDGEMENT These guidelines for Roof Mounted Outdoor Air-
ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS
ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS 1. 2. 3. 3.0 Scope 1.1 This application standard shall be used where the authority having jurisdiction has adopted its use, and
NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS
NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS The (NRDCA) has prepared this document to provide customers and installers information that the industry
!!! !!!! !!! !!! !!! !!! !!!!!!!!! Table of Contents! Section 1: Most Common Types of Flat Roofing! Section 2: Better Understand Your Flat Roof!
Table of Contents Section 1: Most Common Types of Flat Roofing Section 2: Better Understand Your Flat Roof Section 3: Flat Roofing Cost in 2015: Four Factors that Dictate Section 4: Planning A Flat Roofing
CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles
CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503 Re-Roofing: Asphalt Shingles This is a summary of the standard requirements based on the
TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09
TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09 PMT GUIDE # 10 Book of Order Section G-10.0102o: "The session is responsible for the mission and government of the particular church. It
TARRANT COUNTY DETAIL STANDARDS
TARRANT COUNTY DETAIL STANDARDS 1. Standard Coping 2. Coping at End Wall 3. Standard Sheet Metal Engagement Details 4. Gravel Guard 5. Gravel Guard Wall Termination 6. Gravel Guard, Gutter, and Downspout
SELF-INSPECTION CHECKLIST Maintain Your Roof and Identify Potential Issues With Bloom s Comprehensive Self-Inspection Guide
SELF-INSPECTION CHECKLIST Maintain Your Roof and Identify Potential Issues With Bloom s Comprehensive Self-Inspection Guide Inspection Questions? Call Bloom At 800-483-9932 www.bloomroofing.com DISCLAIMER
ROOF INSPECTION & MAINTENANCE
Physical Plant Administration Facilities Maintenance Department ROOF INSPECTION & MAINTENANCE All roofs require periodic inspection and maintenance in order to perform as designed and to provide a long
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings
Final inspections are completed by site visit only. Access to fenced yards shall be planned.
ROOFING RESIDENTIAL BUILDING INSPECTIONS DEPARTMENT www.ci.blaine.mn.us This handout is intended only as a guide and is based in part on the 2015 Minnesota State Building Code, Blaine City ordinances,
Commercial Roof Management
Disclaimer: This material is designed and intended for general informational purposes only, and is not intended, nor shall it be construed or relied upon, as specific legal advice. Roof damage is a leading
Roof Inspection. Summary Report
www.real-estate-inspections.com Roof Inspection Summary Report Subject Property Prepared for: File Number: Client in Detroit 05-15-RF-004 Inspector: Craig Milliken, PE # 32779 CPM Real Estate Inspections,
SINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION
SINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION As of October 1, 2007, this mitigation form must be submitted as part of the roofing permit application package. Secondary water barrier (if applicable)
MODULAR EPDM ROOFING SYSTEMS
MODULAR EPDM ROOFING SYSTEMS INSPECTION, REPAIR & MAINTENANCE HANDBOOK Now that you ve selected one of the best roofing systems available today, please take the time to read through this handbook carefully
WATERPROOFING FOR CONCRETE STRUCTURES
MANUAL OF CONTRACT DOCUMENTS FOR ROAD WORKS VOLUME 1 SPECIFICATION FOR ROAD WORKS SERIES 2000 WATERPROOFING FOR CONCRETE STRUCTURES Contents Clause Title Page 2001 General 2 2002 Protection of Bridge Deck
Warranty Information TABLE OF CONTENTS PROCEDURES FOR WARRANTY 2
Warranty Information TABLE OF CONTENTS PROCEDURES FOR WARRANTY 2 PROTECTING YOUR DURO-LAST ROOFING 3 Safety Measures 3 Inspection 3 Maintenance Program 4 Sealants 4 Drainage 4 Parapets Walls 4 Building
THERMOTEK MODIFIED BITUMEN TORCH MEMBRANE OVER
THERMOTEK MODIFIED BITUMEN TORCH MEMBRANE OVER DESCRIPTION TORCH OVER (15,17,19 YR) TH/BS-TH/CS 2 1 0 No 0. SUBSTRATE 1. THERMOTEK USA 2.0 FV TORCH SMOOTH 2. THERMOTEK USA PRO FP TORCH GRANULE COMPONENTS
Inspecting to a higher standard.
Inspecting to a higher standard. Rob Hopkin Silver Spring, MD 20902 Monday, June 2, 2014 ProTec Inspection Services Inc. 19736 Selby Ave Poolesville, MD 20837 301-972-8531 www.protec-inspections.com [email protected]
CHAPTER 6 ASPHALT ROLL ROOFING
CHAPTER 6 ASPHALT ROLL ROOFING Section I. DESCRIPTION AND GENERAL DISCUSSION 6.1.1 General 6.1.3 Mineral-Surfaced Asphalt roll roofing is roofing in sheet form Mineral-surfaced roll roofing is composed
WESTERN COOL ROOF SYSTEMS Sustainable - Energy Efficient FLUID APPLIED REINFORCED ROOF SYSTEM
WESTERN COOL ROOF SYSTEMS Sustainable - Energy Efficient FLUID APPLIED REINFORCED ROOF SYSTEM SPECIFICATION NO. SMAA-2P-8xE UPGRADE SMOOTH SURFACE / CAP SHEET / SINGLE PLY 2 PLY POLYESTER REINFORCED ACRYLIC
UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Architectural. Roofing. Basis of Design
Basis of Design This section applies to roofing membranes, flashing and accessories. Design Criteria Adhere to the standards and details of the latest editions of the National Contractors Association (NRCA)
STANDARD PROCEDURES FOR INSTALLATION OF METAL ROOF SYSTEMS
ROOFING APPLICATION STANDARD (RAS) No. 133 STANDARD PROCEDURES FOR INSTALLATION OF METAL ROOF SYSTEMS 1. Scope 1.1 This application standard has been developed to provide consistent information for the
WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12
WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12 87 88 GOOD INDUSTRY PRACTICES 12 WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12.1 BACKGROUND Most roofs in Singapore are constructed using reinforced
Durapax Coal Tar BUR Application Guide
400 Old Reading Pike, Suite 304 Pottstown, PA 19464 Tel: 610-579-9075 Fax: 610-323-0115 www.durapax.com Durapax Coal Tar BUR Application Guide DESIGN CONSIDERATIONS The proper specifications of any roof
STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES
ROOFING APPLICATION STANDARD (RAS) No. 117 STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES Scope 1.1.
CHAPTER VII. TITLE: STANDARDS FOR NEW ROOFING July 2015 CONSTRUCTION, RE-ROOFING CONSTRUCTION AND ROOFING SYSTEM GUARANTEE REQUIREMENTS
TITLE: STANDARDS FOR NEW ROOFING CONSTRUCTION, RE-ROOFING CONSTRUCTION AND ROOFING SYSTEM GUARANTEE REQUIREMENTS Responsible Organization: Office of Facilities Planning Instructions: This Manual supersedes
THERMOTEK SELF ADHESIVE MEMBRANE +G2 OVER WOOD SYSTEM DESCRIPTION SELF ADHESIVE OVER WOOD (8YR) BS-SA/CS
THERMOTEK SELF ADHESIVE MEMBRANE +G OVER DESCRIPTION SELF ADHESIVE OVER (8YR) BS-SA/CS 1 0 No 0. SUBSTRATE 1. BASE SHEET G FIBER GLASS BASE. THERMOTEK SELF ADHESIVE 3.0 FP GRANULE COMPONENTS AND WEIGHTS
FLAT ROOF REPAIR CUT COST WITHOUT CUTTING CORNERS
FLAT ROOF REPAIR CUT COST WITHOUT CUTTING CORNERS Table of Contents Chapter 1: FLAT ROOF REPAIR - CUT COST WITHOUT CUTTING CORNERS Chapter 2: PVC RECOVER SYSTEM HOW IT WORKS Chapter 3: 8 STRATEGIES TO
APPLICATION INFORMATION FOR RESIDENTIAL ROOFING AND RESIDENTIAL ROOFING PACKET
Environmental Protection and Growth Management Department PERMITTING, LICENSING AND CONSUMER PROTECTION DIVISION 1 N. University Drive, Box #302 Plantation, Florida 33324 954-765-4400 www.broward.org/permittingandlicensing
CHAPTER 7: Building Systems ROOFING SYSTEMS
ROOFING SYSTEMS Purpose Examples 1. Shingle roof system 2. Metal roof with blanket insulation 3. Metal roof with rigid insulation 4. Built-up asphalt roof system 5. Single-ply roof system 6. Modified Bitumen
Chapter 9: INSTALLING ROOFING
9.1 LEAK BARRIER (ICE AND WATER SHIELD) 9.2 SHINGLE UNDERLAYMENT 9.3 INSTALLING GUTTER APRON AND GABLE D-EDGE 9.4 INSTALLING SHINGLES 9.5 RIDGE VENT AND CAP Tools needed by each volunteer: Hammer (16 oz.
Smooth cap sheet - 0-10 SQ $ 139.00. Smooth cap sheet - 11-50 SQ $ 63.00. Smooth cap sheet - 51-100 SQ $ 36.00 Smooth cap sheet - 101-200 SQ $ 36.
Demolition/Removal of Work 4-ply built up roofing to the insulation (smooth cap sheet) Smooth cap sheet - 0-10 SQ $ 63.00 Smooth cap sheet - 11-50 SQ $ 63.00 Smooth cap sheet - 51-100 SQ $ 35.00 Smooth
NEOGARD. Preventive Maintenance Manual
NEOGARD Preventive Maintenance Manual Fluid-Applied Roof Coating Systems December 2014 Notes NEOGARD luid-applied roof coating systems are designed to be long lasting, monolithic membranes which provide
The existing roof angle change terminations and flashings when sound and intact can be reused.
January 2, 2015 Summary Specification Re-Skinning an Existing Roof Maintenance and Repair Warranty Upgrade for Up to 30 Years Re-Skinning Over an Existing Roof with a New C-EPDM Membrane Using The Existing
Quality You Can Trust Since 1886... From North America s Largest Roofing Manufacturer
Quality You Can Trust Since 1886... From North America s Largest Roofing Manufacturer Leak Buster Repair & Maintenance Products Quality You Can Trust Since 1886...From North America s Largest Roofing Manufacturer
Your guide to home maintenance. Flat Roofs
Your guide to home maintenance Flat Roofs Your guide to home maintenance is a series of information leaflets that gives you all the information you need to keep your home in tiptop condition. Flat Roofs
Waterproofing Problems: A Simple Explanation, A Simple Solution
Waterproofing Problems: A Simple Explanation, A Simple Solution The purpose of this paper is to point out the underlying causes of waterproofing problems and simple means of preventing them. Such problems
THERMOTEK MODIFIED BITUMEN TORCH MEMBRANE OVER POLYSOCYANURATE SYSTEM DESCRIPTION TORCH SYSTEM OVER POLYISO (15,17,19 YR) TH/BS-TH/CS
OPTIONAL TITLE 24 CRITICAL POINTS POLYISO THERMOTEK MODIFIED BITUMEN TORCH MEMBRANE OVER POLYSOCYANURATE DESCRIPTION TORCH OVER POLYISO (5,7,9 YR) TH/BS-TH/CS 2 No 0. SUBSTRATE. THERMOTEK USA PRO 2.0 FV
BITUMINOUS ROOF COATINGS, CEMENTS, PRIMERS AND ADHESIVES
BITUMINOUS ROOF COATINGS, CEMENTS, PRIMERS AND ADHESIVES ABOUT POLYGLASS U.S.A., INC. MODIFIED CEMENTS & ADHESIVES MASTICS ALUMINUM COATINGS EMULSIONS & PRIMERS PROTECTIVE COATINGS Polyglass manufactures
SWEPCO HEAVY DUTY POLYMASTER ROOF SYSTEM 201
31 SC: 33 SWEPCO POLYMASTER ROOF SYSTEM 201 APPLICATION SPECIFICATIONS IMPORTANT -- These application specifications are provided for the use of all persons who are to apply SWEPCO Products. Please read
EPDM System Repair and Cleaning
EPDM single-ply roof systems have represented a third of the volume of the low-sloped commercial market for close to twenty years. The majority of these roofs were installed to receive the manufacturer
Low-slope reroofing guidelines
Low-slope reroofing guidelines by Thomas Bollnow and Joan P. Crowe, AIA The NRCA Roofing and Waterproofing Manual, Fifth Edition, contains reroofing guidelines for steep- and low-slope roofing. The August
Crescent Valley High School Roof Investigation
Crescent Valley High School Roof Investigation Project: Corvallis School District Crescent Valley High School Roof Date: July 26, 2011 Report By: Rowell Brokaw Architects: Mark Young, AIA, Chris Andrejko
BITUMEN-POLYMER WATERPROOFING MEMBRANE, MADE FROM SELECT APP AND DISTILLED BITUMEN, REINFORCED WITH SPUNBOND POLYESTER FABRIC.
93-106 Revised March 2007 BITUMEN-POLYMER WATERPROOFING MEMBRANE, MADE FROM SELECT APP AND DISTILLED BITUMEN, REINFORCED WITH SPUNBOND POLYESTER FABRIC. BITEC APM-4.5T is a torch applied, mineral surfaced,
Roof Inspection. Summary Report
Phone: (561) 866 9956 www.real-estate-inspections.com Roof Inspection Summary Report Subject Property File Number: 05-15-RF-002 Inspector: Craig Milliken, PE CPM Real Estate Inspections, Inc. Date of Inspection:
Roof Repair Project Report. Fairbank Complex 40 Fairbank Road Sudbury, Massachusetts. February 14, 2014. RBA Project No. 2014007.00.
Report Fairbank Complex 40 Fairbank Road RBA Project No. 2014007.00 Prepared by: 33 Center Street, 2 nd Floor Burlington, MA Tel: 781-273-1537 Fax: 781-273-1695 TABLE OF CONTENTS Roof Repair Project Report...
NEW ELECTRICAL SUBSTATION Building 300 SECTION 07 53 23 ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK
ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK PART 1 GENERAL 1.1 REFERENCES The publications listed below form a part of this specification to the extent referenced. The publications are referred to within
Residential Roofing Guide
Residential Roofing Guide TABLE OF CONTENTS Building Detail and Accessories...... 1 Panel Introduction and Handling...... 2 Cutting and Trimming.... 3 Roof Preparation..... 3 Roof Slope..... 3 Re-roofing...
Although we do a fair amount of residential roofing, my family s breadand-butter. Installing a. Sealants aren t universal
Installing a Low-Slope Exposed EPDM for roof transition Exposed EPDM for resistance to ice damming Sidewall flashing Done with care, a flat roof can provide 0 years or more of leak-free service Gravel
SEAMS SEAMING USING SEAM TAPE
SEAMING USING SEAM TAPE SEAMS The membrane should be positioned so that the width of the seam is 3. Remove excess chalk from a chalk line by snapping the line into the air and then chalk a line one-quarter
Asphalt Shingle Application Requirements
Alberta Allied Roofing Association Asphalt Shingle Application Requirements Section 1 Roof Decks 1.1 General Asphalt Shingles are not permitted to be installed directly over rigid insulation. When Asphalt
Roofing Repairs 07511-1
SECTION 07511 ROOF AND FLASHING RESTORATION WITH TITLE 24 / COOL ROOF SURFACING PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the contract, including General and Supplementary
How to repair your existing low slope flat roof.
How to repair your existing low slope flat roof. Recycled Rubber Roofing is not a "Roof Coating." It is a liquid emulsion used as the underlayment of a new or retrofit, built-up roofing system. One of
Sheet A-1 KEY SHEET A-1. Football Roof Plan SHEET A-2 SHEET A-3 SHEET A-4. LaCross Roof Plan. Soccor 2 Roof Plan 88' 45' 87' 46' 45' 45' 10' 3' 25'
Sheet A-1 SHEET A-1 Football Roof Plan 5 LaCross Roof Plan 5 88' 87' SHEET A- 1 DRIP EDGE WITH STANDING SEAM PANEL 2 RAKEWALL SHEET A- RIDGE HIP HEAD WALL 11700 Pierson Rd. Wellington, FL. 1 Soccor 2 Roof
BUILT-UP ROOF COATING SMOOTH and GRANULE SURFACE SPECIFICATION
07560 BUR BUILT-UP ROOF COATING SMOOTH and GRANULE SURFACE SPECIFICATION PART 1: GENERAL 1.01 SCOPE: To extend the useful service life of the aged or new asphalt built-up roof system and to reduce cooling
Rooftop Matters. 2 0 1 2 Benchmark Report. Executive Summary
The 2012 Benchmark Report is our initial survey covering results from roof inspections and service calls over a six-month period. Our intention is to update these results annually in order to provide meaningful
ITEM 599.06060008 THERMOPLASTIC MEMBRANE ROOFING
DESCRIPTION Construct adhered membrane roofing system, roof insulation, and vapor retarder in accordance with these specifications. MATERIALS: General: Provide installed roofing membrane and base flashings
METAL ROOF RESTORATION SAMPLE DESIGN GUIDELINES
METAL ROOF RESTORATION SAMPLE DESIGN GUIDELINES REFLECTICLEAN ACRYLIC/URETHANE Elastomeric Roofing Systems, Inc 6900 Bleck Dr. Rockford, MN 55373 800.403.7747 -or- 763.565.6900 fax: 763.565.6901 email:
StuccoSpec Moisture Testing Inspection
e-mail - [email protected] StuccoSpec Moisture Testing Inspection Property Located At: 265 Elm Street, Anywhere, USA 01/27/02 Ordered by: Mr. & Mrs. John Doe #2 Song Sparrow Place, The Woodlands, T 77381281-364-0012
Preventing Ice Dams on Roofs
Preventing Ice Dams on Roofs Facility Manager November/December 2005 When a roof leaks, facility managers inevitably receive complaints from building occupants. If it is winter, ice dams are often the
Waterproofing System for Wastewater Tanks in Petrochemical Industries and Refineries
Waterproofing System for Wastewater Tanks in Petrochemical Industries and Refineries Introduction Wastewater of petrochemical industries and refineries contains high amounts of emulsified aliphatic or
Reroof or Restore? The right decision can save weeks of time and thousands of dollars
APOC A DIVISION OF GARDNER - GIBSON 5903 Paramount Boulevard Long Beach, California 90805 Telephone (800) 562-5669 Fax (562) 423-9597 www.apoc.com THE FOLLOWING TECHNICAL ARTICLE WAS PUBLISHED IN A MAJOR
September 3, 2009. Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901
September 3, 2009 Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901 RE: Ketchikan Gateway Borough Gateway Recreation Center Roof Observations and Intrusive Inspections
Read and understand all installation instructions and precautions before installing. GENERAL APPLICATION INSTRUCTIONS
AC TOPSEAL SELF-ADHERED, GRANULAR SURFACED, SINGLE PLY, LOW SLOPE ROLLED ROOFING 3 X 33.3 = 100 SQ. FT. 10 YEAR MATERIAL LIMITED WARRANTY For Use on Porches / Sheds / Utility Buildings / Accessory Buildings
BLACK JACK ALL WEATHER ROOF COATING
PAGE: 1 of 6 PRINT DATE: 16/09/2004 BLACK JACK ALL WEATHER ROOF COATING DESCRIPTION BLACK JACK ALL WEATHER ROOF COATING is a solvent based, full bodied black brushable compound with added fibres for reinforcement.
ROOF INSPECTION REPORT
ROOF INSPECTION REPORT Date: October 9, 2012 Requesting Firm: FIRST CHOICE INSPECTIONS Santiago Salazar Address: 447 Chilberg Court, San Jose, CA 95133 Phone #: 408-771-7563 Roof Inspected At: 1465 Gerlach
CertainTeed. Self-Adhering Roof Systems for Low Slope Residential Roofs
CertainTeed Self-Adhering Roof Systems for Low Slope Residential Roofs Goes down fast. Stays on strong. Flintlastic SA performs in all the right ways. What s more important to you? Speed of installation,
Shingle Roofing: What s below the surface is important
What s below the surface is important The roof is leaking, the shingles look old, and the downspouts are dripping. It must be time to replace the roof or is it? Shingle roofs may seem simple, but a roof
bout your HOUSE before you start Repairing And Replacing Materials Exterior Walls
A bout your HOUSE before you start Repairing And Replacing Materials Exterior Walls CE 28 h Exterior finish materials are expected to protect the house from the elements while providing an attractive appearance.
Water Damage & Repair
Water Damage & Repair Chinatown Preservation Talks 2015 James Engler, P.A Glenn Mason, AIA Mason Architects Program Outline Terminology & Waterproofing Basics Discussion of why this is important Below
1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system.
SECTION 075416 - PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system. 1.2 PERFORMANCE REQUIREMENTS A. Solar Reflectance
SECTION 07 61 13 STANDING SEAM METAL ROOFING
SECTION 07 61 13 STANDING SEAM METAL ROOFING PART 1 GENERAL 1.01 SCOPE OF WORK A. The Work shall include all labor, materials, equipment and supervision required to complete the work of the above referenced
Roof. Walking on roofs
Roof The roof cannot be adequately evaluated during dry weather, especially during a hot, dry summer. Consequently, roof problems might not be detected at the time of the inspection and might not be able
A. This Section includes rubberized asphalt sheet membrane waterproofing systems.
SECTION 07110 SHEET MEMBRANE WATERPROOFING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
Building Owners Guide to a Duro-Last System!
Building Owners Guide to a Duro-Last System Table of Contents Section 1: Introduction to Duro-Last Roofing Systems Section 2: Benefits of a Duro-Last Roofing System Section 3: Comparing a Duro-Last Roof
3 Installation. 9 Roof Edges... p. 3. 19 10 Wall Terminations... p. 3. 20 11 Membrane Repair... p. 3. 21 12 Miscellaneous... p. 3. 22. 3.
3 Installation The information provided within this chapter may assist the contractor to install the Firestone UltraPly TPO Systems in accordance with Firestone s requirements. It may also help him and
Vision Home Inspection
Vision Home Inspection 324 Rams Run Shepherdsville KY 40165-7877 Inspector: James McFadden Property Inspection Report Client(s): Property address: Inspection date: View report summary This report is the
T R A N S F E R A B L E F U L LY
HSTOPS A WALL OF WATER 22 FT. HIG! F U L LY T R A N S F E R A B L E RESISTS10 PSI ! 1 F U L LY T R A N S F E R A B L E HSTOPS A WALL OF WATER 22 FT. HIG RESISTS10 PSI Guaranteed To Stop Water Even Under
We urge you to read and follow the attached installation instructions. Failure to do so may void the warranty of this garden window unit.
Important Information for New Construction Installations Attention Installer! We urge you to read and follow the attached installation instructions. Failure to do so may void the warranty of this garden
Modified Bitumen Roofing Membranes
SPECIFICATIONS The Dibiten Specifications Manual has been prepared to serve as a guide for architects, specifiers, roofing contractors and others involved in the roof system selection and application process.
Foundation Experts, LLC Specializes in Foundation Repair and Waterproofing
1 Most basements show some signs of leaking and cracking. Through the years, problems with water, poor soils, grading, drainage and possible settling affect the integrity of a basement. Being able to recognize
Total Home Inspection Checklist
Total Home Inspection Checklist Use a checklist like this to make sure that you are looking at all parts of the house. Check off those items that are in good condition and make notes about those that are
EAST LYME HIGH SCHOOL
Overview: 1971 N 1966 GYM 1966 CLASSROOM WING 1966 AUD. 1971 GYM 1998 1998 POOL EAST LYME HIGH SCHOOL Original 1966 Building: The original East Lyme High School was constructed in 1966 and was composed
THIRD PARTY INSPECTION GUIDELINES FOR OWNERS AND GENERAL CONTRACTORS/CONSTRUCTION MANAGERS DS150
THIRD PARTY INSPECTION GUIDELINES FOR OWNERS AND GENERAL CONTRACTORS/CONSTRUCTION MANAGERS DS150 SECTION ONE A. Objective The objective of this guide is to provide Owners and General Contractors/Construction
Distributed by: BEST MATERIALS LLC, Phoenix AZ Ph: 800-474-7570, 602-272-8128 Fx: 602-272-8014 www.bestmaterials.com Email: Sales@BestMaterials.
FULLY-ADHERED ROOFING SYSTEM INSTALLATION INSTRUCTIONS Distributed by: BEST MATERIALS LLC, Phoenix AZ Ph: 800-474-7570, 602-272-8128 Fx: 602-272-8014 www.bestmaterials.com Email: [email protected]
FIRESTONE BUILT-UP ROOFING SYSTEMS APPLICATION GUIDE 3/14/2011
FIRESTONE BUILT-UP ROOFING SYSTEMS APPLICATION GUIDE TABLE OF CONTENTS 2.01.1 GENERAL......2 2.02.1 JOB SITE CONSIDERATIONS (CAUTION AND WARNINGS)...2 2.03.1 ROOF SUBSTRATE PREPARATION...2 2.04.1 WOOD
Please read the entire document before purchasing and installing any of these products
Please read the entire document before purchasing and installing any of these products USA SBS UNDERLAYMENT ROOFING UNDERLAYMENT SBS Mineral Surfaced MINERAL SURFACE CAP SHEET Ice and Water Protection
Basement & Foundation Damage
Basement & Foundation Damage Please note-this presentation is only intended to be used as a basic educational tool and is by no means all encompassing. Each property should be treated on a case by case
HEB 38 BLANCO AND WEST AVENUE FLUID APPLIED EPDM RUBBER ROOF RECOVERY SYSTEM APPLICATION
HEB 38 BLANCO AND WEST AVENUE FLUID APPLIED EPDM RUBBER ROOF RECOVERY SYSTEM APPLICATION David Marut TEST CASE REPORT July 1, 2014 Case Study Pro Guard EPDM Super Coat Liquid Rubber Membrane Roof System