Fire Alarm System Submissions
|
|
- Henry Shaw
- 8 years ago
- Views:
Transcription
1 Gypsum Fire Protection District Fire Alarm System Submissions As of July 1 st, 2007 all Fire Alarm Submissions will be required to be signed by a NICET Level 3 or higher. Fire Alarm System Submissions for permit will fall under one of two categories: new installations or remodels. New installations or remodels of significant impact will require a full Submission for review. Remodels of limited scope, remodels of relatively minor impact and tenant finishes may be submitted in the form of a Scope of Work application. If you are unsure about your project, you may call us to discuss the project. The following documents are to be included in the Submission with the exception of the permit fee schedule: 1)Application Form 2)No Work Without Permit Form To ensure your Submission is complete and can be processed in the shortest time possible, please review the following fire alarm checklist. All Submissions must be delivered to Justin Kirkland at the Gypsum Fire Protection District offices located at 511 Second Street, Gypsum, CO Submissions may also be mailed to PO Box 243, Gypsum, CO We will not accept incomplete Submissions. All incomplete Submissions will be returned without review. Submissions which have been reviewed, rejected and returned to the contractor will be subject to a re-submission fee. Please Note: No work of any kind on any project will be allowed until the Gypsum Fire Protection District has issued a permit for the project. Any work done without a permit will be subjected to fines of four times the permit fee plus the actual permit and review fees. Gypsum Fire Protection District Fire Prevention will make every effort to review, comment, and issue approval on complete Submissions within 10 working days. More complex or special use projects may require a longer review process. Please plan your project accordingly. Reviews beyond a normal scope will be forwarded to our Fire Protection Engineer for review at a set hourly rate. You will be advised of this and invoiced for charges including shipping. Any such charges must be paid in full prior to any rough or final fire alarm inspections. If you require a rush review the Submission will be forwarded to our Fire Protection Engineer. You will be invoiced at the hourly review rate for rush review, and any other charges including shipping. Any such charges must be paid in full prior to any field inspections
2 Fire Alarm Plan Submission Check List Several forms require an original signature. All Submissions must be presented with original ink signatures. Faxes, s, or copies without original ink signatures will be returned. Illegible materials will result in the return of the Submission for correction. If you are submitting under a Scope of Work permit, you must provide those materials with an asterisk (*). o *A completed permit form. All requested information must be provided. o *A copy of the building permit. o *A copy of the No Work to be Done form. o *A copy of your local business license, if applicable. o *A check or money order for the correct fee. o *Complete battery calculations or a statement of impact of the project on existing systems. o *Voltage drop calculations or a statement of impact on existing systems. o *A complete set of manufacturer s cut sheets for all devices used. A statement of compatibility may be required if using devices manufactured by several companies. All model types must be indicated on the cut sheets. o *Identification on the plans (or Scope of Work letter) of the engineer of record and the system designer (including the level of training if applicable). o *For Scope of Work projects: a complete and detailed outline of the work to be done, including anticipated relocation of devices, deletion or addition of devices (including number of devices) must be submitted. The letter must include information on the impact of system changes on existing battery or other back-up power supplies. Device compatibility must be documented. o At least one copy of the reflected ceiling plan. o At least one copy of scale interior elevations. Be sure all ceiling heights are called out. o At least one site plan. o At least three (3) complete sets of plans in ¼ inch scale. o Electronic copy of plans submitted via PDF for archiving. o At least three (3) complete sets of manufacturer s cut sheets for ALL devices used. A statement of compatibility may be required if using devices manufactured by several companies. All model types must be indicated on the cut sheets. o Measured or estimated ambient sound levels used for design. o Once a Submission has been received, reviewed, and a permit issued, the permit holder may call for rough inspections as necessary for the project
3 Fire Alarm Rough Inspection Any work done on a fire alarm project must be inspected. Usually these inspections will fall under one of two categories: fire alarm rough (construction) and fire alarm final acceptance. These inspections must be conducted regardless if the project is a newconstruction fire alarm system or a minor remodel. Any questions regarding scheduling or conducting inspections should be directed to either Justin Kirkland or Wade Droegemeier. Requests for fire alarm rough inspections must be placed at least twenty-four (24) hours in advance. An approved set of plans and cut sheets MUST be available during the inspection. Should the job be a Scope of Work, an approved copy of the letter and appropriate cut sheets must be available. On all jobs, a copy of the signed permit must be present at ALL times. A representative of the fire alarm permit holder s company, familiar with the job must be on-site and available to walk with the inspector. All necessary tools, personnel and equipment shall be present and available. Prior to calling for a Fire Alarm Rough Inspection, ensure that the following issues have been addressed: All device locations are laid out per plans and NFPA 72, and all device boxes have been installed. The correct size and type of fire alarm wire must be installed and visible for inspection. All work has been done in accordance with the NFPA 70 (the NEC) and in a workman-like manner. Please note: Smoke detectors or heat detectors are not to be installed during construction. Any minor changes from approved plans are documented on a field copy (red lines) for review. Any major changes must have been submitted and approved prior to inspections. Any work that has been inspected and changed must have been submitted for review and re-inspection. All inspections are based on the call-in information. Should an installation be denied, a re-inspect time will be rescheduled for a later time
4 Fire Alarm Final Acceptance Inspections A representative of the fire alarm permit holder s company, familiar with the job must be on-site and available to walk with the inspector. All necessary tools, personnel and equipment shall be present and available. Prior to final acceptance, all devices must have been checked and tested according to the manufacturer s instructions the permit holder will have conducted a 100% pre-test of the system, and has programmed the system per Gypsum Fire Protection District and the sequence of operations requirements. A memo stating the system has been 100% pre tested must be available at the time of the inspection. Calls for final inspections must be made at least twenty-four (24) hours in advance. An approved set of plans and cut sheets MUST be available during the inspection. All asbuilts or red-lines must be available for the inspection. Should the job be a Scope of Work, an approved copy of the letter and appropriate cut sheets must be available. On all jobs, a copy of the signed permit must be present at ALL times. Final acceptance testing is conducted concurrently with other life safety systems if present. It is the permit holder s responsibility to coordinate with other trades as necessary for final inspections. The construction site must be substantially clean and free of debris, minimal construction activity is present, and arrangements have been made to protect devices after the test have been made if necessary. There shall be no smoke detectors installed prior to final cleaning of the project. All detectors installed prior to final cleaning must be removed, cleaned and calibrated in accordance with manufacturer s instructions. Documentation of such must be submitted. All phone lines or other approved communications equipment must be installed and a copy of a monitoring contract must be made available for review. The call list has been submitted to the monitoring company and all signal types have been tested and verified prior to the acceptance test. The Fire Department Dispatch Center must be listed as first notified for water flow and alarm signals. The alarm sequence of operations must be verified as correct by the permit holder. A Knox Box has been installed in an approved location and all necessary keys are on-site and have been physically tested. Any required paperwork issues have been resolved. The permit holder has completed and signed all required completion paperwork. For new systems and major remodels, an NFPA form of Completion is required. For Scope of Work projects, a signed, company letterhead stating that the work is complete and in accordance with that called out in the permit and has been done to code. Electronic copy of As Builts submitted in PDF format for Fire Dept archiving
5 Fire Alarm Systems Annual Test and Inspection Requirements Fire Alarm Systems must be maintained and tested regularly. A quality maintenance program will increase the likelihood that the system will operate as it is designed in the event of a fire. The Gypsum Fire Protection District requires fire alarm systems to undergo an annual test and inspection in accordance with NFPA 72. Upon completion of the inspection process and all repairs, the appropriate documentation must be completed and copies forwarded to the property owner, property management, and the Gypsum Fire Protection District Fire Prevention. Should discrepancies or conditions be found that prevent the system from operating as designed, repairs must be scheduled and completed in a timely manner. Major repairs or situations that require that the system be taken out of service for any reason must be reported to the Fire Marshal for review and approval prior to conducting the work. All Annual Tests and Inspections must be recorded and submitted to the Fire District on the most current National Fire Protection Agency Inspection and Testing (NFPA) form. Other forms will not be accepted. If such forms are submitted they will be returned and the property in question will be recorded as not in compliance with code until such time the proper documentation is submitted
Gypsum Fire Protection District. Fire Sprinkler System Submissions
Gypsum Fire Protection District Fire Sprinkler System Submissions Fire Sprinkler System Submissions for permit will fall under one of two categories: new installations or remodels. New installations or
More informationRancho Cucamonga Fire Protection District Prevention Bureau Standard
Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Revised: January 2014 INTENT The intent
More informationFire Alarm Systems Permit Packet. City of Greer Fire Department
Fire Alarm Systems Permit Packet City of Greer Fire Department Updated July 2004 If you have any questions or comments regarding the information contained within; or of you need assistance interpreting
More informationHow To Install A Carbon Monoxide Detector
NASSAU COUNTY FIRE COMMISSION OFFICE OF THE FIRE MARSHAL Nassau County Public Safety Center 1194 Prospect Avenue Westbury, New York 11590 (516) 573-9900 / nassaucountyny.gov Chief Fire Marshal Scott D.
More informationBold items are particular to the City of Euless
EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 2/12 Fire Chief Wes Rhodes Fire Marshal Paul Smith EFD-FMO 3-2 2009 International Fire & Building Code as Amended NFPA Standards Adopted
More informationFIRE ALARM APPLICATION
FIRE ALARM APPLICATION ENUMCLAW FIRE DEPARTMENT 1330 Wells St, Enumclaw, WA 98022 Phone: 360-825-5544 Fax: 360-825-9442 COMMUNITY DEVELOPMENT, BUILDING DEPARTMENT 1309 Myrtle Ave Enumclaw WA 98022 Phone:
More informationHow To Get A Fire Alarm Permit In Vail
Fire and Emergency Services 2399 N. Frontage Road W. Vail, Colorado 81657 Tel: 970-479-2252 www.vailgov.com Fire Marshal FIRE ALARM PERMIT Commercial and Residential Fire Alarm shop drawings are required
More informationFire Alarm Submittal Requirements and Acceptance Testing
Lubbock Fire Marshal s Office 1601 Mac Davis Lane Lubbock, Texas 79401 806-775-2646 Fax 806-775-3508 fireprevention@mylubbock.us Fire Alarm Submittal Requirements and Acceptance Testing To all Registered
More informationCommercial Fire Alarm Standards July 1, 2010 Edition Page 1 of 14
City of Mercer Island Development Services Group Fire Code Review and Inspection 9611 SE 36 th Street Mercer Island, WA 98040-3732 PHONE (206) 275-7605 FAX (206) 275-7726 www.mercergov.org Commercial Fire
More informationFIRE ALARM SYSTEM PLAN SUBMITTAL CHECKLIST
FIRE ALARM SYSTEM PLAN SUBMITTAL CHECKLIST All fire alarm system plan submittals must include this Fire Alarm System Plan Submittal Checklist. PLAN APPROVAL - No work shall be performed until plans are
More informationFire Alarm Systems Certification
Fire Alarm Systems Certification The skills and knowledge listed under each task are suggestive of those involved in that task, but are not intended to constitute an exhaustive listing. 2.1 Submittal Preparation
More informationEXHIBIT A SCOPE OF WORK
EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,
More informationBELMONT FIRE DEPARTMENT FIRE ALARM SYSTEM REQUIREMENTS BFD-OFM-10-011
Fire Alarm System plan(s) MUST be reviewed and approved by the Belmont Fire Department prior to the start of construction. The design and any changes must be fully compliant with NFPA 1, NFPA 101, NFPA
More informationCity of Temple Burglar Alarm Permit Process Information Sheet
City of Temple Burglar Alarm Permit Process Information Sheet Initial Permit FREE Renewal Permit Fee $ 10.00 -EVERY TWO YEARS Make checks / money orders payable to: The City of Temple, FARP Mail to: Temple
More informationCity of Columbus Department of Building and Zoning Services
City of Columbus Department of Building and Zoning Services Introduction This manual is designed to provide you, the contractor, owner or design professional with a step-by-step guide to our process, beginning
More informationFire Alarm System Plans Submittal Guidelines For New and Existing Systems
Fire Alarm System Plans Submittal Guidelines For New and Existing Systems SCOPE The Temecula Fire Prevention Bureau (TFPB) has established the following requirements for the submittal of all fire alarms,
More informationFIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011
Office of the Fire Marshal 1.0 PERMITS FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011 1.1 To acquire an installation
More informationInvitation to Bid FIRE ALARM & DETECTION SYSTEM
Invitation to Bid FIRE ALARM & DETECTION SYSTEM Responses to an Invitation to Bid will be received by the Purchasing Supervisor, Sumner County Board of Education, 1500 Airport Road, Gallatin, TN 37066
More informationCITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS
CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS PROPERTY ADDRESS (BRT Address Required) TESTING CONTRACTOR (Name and Address) License No. ANNUAL
More informationSTATEMENT OF WORK FOR FIRE ALARM SYSTEM TESTING & MAINTENANCE. Project No. SAQMMA-07-C0060 ***OUAGA, BURKINA FASO***
STATEMENT OF WORK FOR FIRE ALARM SYSTEM TESTING & MAINTENANCE Project No. SAQMMA-07-C0060 ***OUAGA, BURKINA FASO*** CONTENTS: 1.0 Introduction 2.0 Objectives 3.0 General Requirements 4.0 Specific Requirements
More informationOriginal Document 10/16/07 Revised 01/30/09 2 nd Revision 01-23-12 3 rd Revision- 12/18/14
North Collier Fire Control & Rescue District Greater Naples Fire Rescue District Immokalee Fire Control & Rescue District 2800 North Horseshoe Drive Naples, Florida 34104 SYSTEM REHABILITATION PLAN CHECKLIST
More informationHERNANDO COUNTY FIRE ALARM GUIDELINES
HERNANDO COUNTY FIRE ALARM GUIDELINES To be used for all commercial building fire alarm system plan review. The procedures set forth in this document are the minimum requirements necessary to ensure a
More information1.0 General. Inspection, Testing, and Maintenance 1 of 8
1.0 General 1.1 Scope This specifications covers the minimum requirements for the inspection, testing, and maintenance of the existing Notifier fire alarm systems at Bergen Community College (BCC) campus
More informationTAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems
More informationDanville, IN Code of Ordinances CHAPTER 90: ALARM SYSTEMS, SMOKE DETECTORS AND THE LIKE. Alarm Systems. Smoke Detectors. Key and Data Storage Boxes
Danville, IN Code of Ordinances CHAPTER 90: ALARM SYSTEMS, SMOKE DETECTORS AND THE LIKE Section Alarm Systems 90.01 Purpose 90.02 Definitions 90.03 Exemptions 90.04 Registration 90.05 Violations; fines
More informationGeneral Fire Code Requirements Within Commercial Tenant Spaces
FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding
More informationMOVE-IN/MOVE-OUT PROCEDURES
MOVE-IN/MOVE-OUT PROCEDURES PRIOR TO YOUR MOVE - SCHEDULING TO ENSURE PROPER SCHEDULING AND AVAILABILITY OF THE MOVE-IN/MOVE-OUT ELEVATOR DESIGNATED FOR YOUR MOVE, EACH OWNER MUST SCHEDULE THEIR MOVE AT
More informationSUBCHAPTER F. SMOKE ALARMS AND FIRE EXTINGUISHERS
SUBCHAPTER F. SMOKE ALARMS AND FIRE EXTINGUISHERS Sec. 92.251. DEFINITIONS. In this subchapter: (1) "Bedroom" means a room designed with the intent that it be used for sleeping purposes. (2) "Dwelling
More informationOBOA 2009 Huntsville, ON Overview of ULC Standards Affecting Building Occupancy Alan Cavers Area Manager Fire & Security Systems Group
OBOA 2009 Huntsville, ON Overview of ULC Standards Affecting Building Occupancy Alan Cavers Area Manager Fire & Security Systems Group Course Title: Rev Date Agenda Introduction to Underwriters Laboratories
More informationBUILDING MOVE PROCESS INSIDE CITY LIMITS
To move a building from outside or within the City to a site within City limits, the following STEPS must be taken before the move can take place: 1. A written request to relocate a dwelling must be provided
More informationThe Mission Critical Fire Protection Experts
The Mission Critical Fire Protection Experts Protection Systems Protection Systems HFC-227ea / FM200 / FE-227 FE-25 / ECARO-25 Novec 1230 Inergen / Argonite Halon Drop-in Systems High and Low Pressure
More informationFIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION
PERMITS AND INSPECTIONS FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION 911 Assigned PROJECT LOCATION Subdivision: Lot: Blk: Sec: PROJECT New Construction Addition/Remodel Demolition Other: Number
More informationCLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services
CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 105.8a-6.1 TITLE: FIRE ALARM SYSTEM REQUIREMENTS SCOPE: This guideline
More informationUnderstanding Fire Alarm Requirements & Inspections. Presented By Bill Conroy Technical Sales For Briscoe Protective Systems Inc
Understanding Fire Alarm Requirements & Inspections Presented By Bill Conroy Technical Sales For Briscoe Protective Systems Inc Introduction Fire Alarm Requirements are structured through a system of codes.
More informationGOLDEN FIRE DEPARTMENT FIRE & LIFE SAFETY DIVISION
GOLDEN FIRE DEPARTMENT FIRE & LIFE SAFETY DIVISION 911 10 TH Street Golden, Colorado 80401 303-384-8094 Contractor s Permit & Inspection Guide *Note: this is not an all inclusive list of requirements;
More informationFIRE ALARM AND DETECTION SYSTEMS SECTION 16721
PART 1 - GENERAL 1.01 WORK INCLUDED FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 A. Provide a complete fully addressable, power limited, fire detection and evacuation system. The system shall be connected
More informationAMERICAN SOCIETY OF CERTIFIED ENGINEERING TECHNICIANS
GREEN TAG/RED TAG AMERICAN SOCIETY OF CERTIFIED ENGINEERING TECHNICIANS ORLANDO CHAPTER ORLANDO, FL February 7, 2013 2012 FLORIDA STATUTES 633.082 Inspection of fire control systems, fire hydrants, and
More informationDELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION
Phone System Owner Phone System Engineered by: of Record Drawings: of System Manuals: of Test Reports: System Installer 1. GENERAL INFORMATION Phone Delaware License No: Certificate Holder No. System Supplier
More informationSARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS
SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS I. APPLICATION AND DEFINITIONS 1.01 Authorization for Standards 1.02 Application of Standards 1.03 Definitions
More informationFire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines
Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines Red Oak Fire Rescue Office of the Fire Marshal 547 N. Methodist Red Oak, TX 75154 Phone: 469-218-7713 Fax: 468-218-7719
More informationCOMMISSIONING OF FIRE ALARM SYSTEMS
COMMISSIONING OF FIRE ALARM SYSTEMS OWNER FURNISHED The owner directly contracts an independent third party commissioning agent for this project. This Commissioning Plan has been included for reference
More informationBlack River-Matheson Fire Department
Black River-Matheson Fire Department New Smoke Alarm Legislation Under The Ontario Fire Code Effective March 1, 2006 Every home in Ontario must have a working smoke alarm on every storey and outside all
More informationLOUISVILLE FIRE PROTECTION DISTRICT 895 West Via Appia, Louisville, Colorado 80027 303-666-8809
LOUISVILLE FIRE PROTECTION DISTRICT 895 West Via Appia, Louisville, Colorado 80027 303-666-8809 Contractor s Checklist and Installation Guide TABLE OF CONTENTS Fire Protection Narrative........... 3 Fire
More informationElectrical Contractor Registration
Electrical Contractor Registration To register as an electrical contractor, please complete the following: PRINT OR TYPE INFORMATION REQUESTED. FORM MUST BE COMPLETE AND LEGIBLE TO BE PROCESSED) State
More informationUniversity Design Standard. Fire Alarm Systems
University Design Standard Fire Alarm Systems 1.0 Overview This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit
More informationSECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM
SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION INTELLIGENT REPORTING FIRE DETECTION SYSTEM PART 1 GENERAL 1.1 DESCRIPTION A. This specification includes the furnishing,
More informationMichael Catalano 24 Nassau Avenue, Islip NY 11751 Phone (631) 224-5477 Chief Fire Marshal fireprevention@islipny.gov Fax (631) 224-5458
OFFICE OF THE FIRE MARSHAL BUREAU OF FIRE PREVENTION Michael Catalano, Phone Chief Fire Marshal fireprevention@islipny.gov Fax To whom it may concern: Enclosed please find the NFPA 72 forms needed for
More informationORDINANCE REGARDING ALARMS IN THE TOWN OF PLAINVILLE
ORDINANCE REGARDING ALARMS IN THE TOWN OF PLAINVILLE SECTION I. PURPOSE AND INTENT. The purpose of this ordinance is to encourage Alarm Users and Alarm Businesses to maintain the operational reliability
More informationSolar Panel Installations
Solar Panel Installations Page 1 of 6 SINGLE-FAMILY RESIDENTIAL CHECKLIST City of Hayward Development Services Department Revised: 7-09-15 PERMIT REQUIREMENTS Permits are required for all solar panel installations.
More information2014 Limited Plan Submittal Checklist
City of Aurora Public Works Department WET AND DRY CHEMICAL HOOD SUPPRESSION SYSTEM 2014 Limited Plan Submittal Checklist Building Division 15151 E. Alameda Parkway, Ste 2400 Aurora, CO 80012 303-739-7420
More informationModule 4, Lesson 12 Fire Alarm Systems
Student Manual Module 4, Lesson 12 Fire Alarm Systems Performance Objectives At the conclusion of this lesson, you will be able to: Identify the components and functions of a fire alarm system and determine
More informationREQUEST FOR PROPOSAL FOR: Fire and Security Alarm Service and Monitoring
MCC13-04 REQUEST FOR PROPOSAL FOR: Fire and Security Alarm Service and Monitoring Manchester Community College PURPOSE: The purpose of this REQUEST FOR PROPOSAL is to establish a contract for Manchester
More informationTelluride Fire Protection District Fire Alarm Systems Policy Version 03/2007
Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007 FIRE ALARM SYSTEMS POLICY TELLURIDE FIRE PROTECTION DISTRICT TABLE OF CONTENTS FIRE ALARM PROTECTION POLICY PLAN REVIEW SUBMITTAL
More informationSMOKE ALARM MAINTENANCE PROGRAM
SMOKE ALARM MAINTENANCE PROGRAM The intent of this program is for owners who normally do not get in to their rental units on an annual basis to make sure the smoke alarms are properly maintained. By having
More informationCity of St. Charles Basement Finish or Remodel
City of St. Charles Basement Finish or Remodel Building & Code Enforcement Division 2 East Main Street St. Charles IL 60174 630.377.4406 (Office) 630.443.4638 (Fax) http://www.stcharlesil.gov Please direct
More informationSmoke Detector/Carbon Monoxide Detector Inspections
MIDDLESEX COUNTY FIRE MARSHAL 1001 Fire Academy Drive Sayreville, NJ 08872 732-316-7171 (office) 732-316-7638 (fax) To: All Real Estate Agencies/Home Owners Subject: Smoke Detector/Carbon Monoxide Detector
More informationSam Docknevich, PSP, Security Service Portfolio Manager. Are You Prepared? The impending impact of Code on Servicing Security Systems
Sam Docknevich, PSP, Security Service Portfolio Manager Are You Prepared? The impending impact of Code on Servicing Security Systems usa.siemens.com/infrastructure-cities Share current and upcoming standards
More informationProgram No. 1.6.1. Section Heading
ENVIRONMENTAL HEALTH AND SAFETY EHS PROGRAM MANUAL Program Title 1.0 INTRODUCTION The New York City Fire Department (FDNY) is responsible for approving and/or inspecting fire alarm systems, buildings,
More informationNATIONAL INSTITUTE FOR CERTIFICATION IN ENGINEERING TECHNOLOGIES. Level III Content Outline
Fire Alarm Systems Level III Content Outline The skills and knowledge listed under each task are suggestive of those involved in that task, but are not intended to constitute an exhaustive listing. 3.1
More informationSMOKE ALARM MAINTENANCE PROGRAM
SMOKE ALARM MAINTENANCE PROGRAM The intent of this program is for owners who normally do not access their rental units on an annual basis to ensure the maintenance of the smoke alarms. The goal is twofold:
More informationNC State University Design and Construction Guidelines Division 26 Fire Alarm Systems
NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems 1.0 Purpose A. The following guideline provides the minimum standards and requirements for fire alarm systems. 2.0
More informationBUILDING PERMIT RESIDENTIAL BASEMENT FINISH
BUILDING PERMIT RESIDENTIAL BASEMENT FINISH DOCUMENTS YOU WILL NEED 1. Building Permit Residential Basement Finish Package 2. Contractors copy of state and business license ADDITIONAL FORMS YOU MAY NEED
More informationCSC-DIVISION 1-MASTER SECTIONS Description
CSC-DIVISION 1-MASTER SECTIONS Description 01 11 00 Summary of Work by Consultant 01 12 00 Multiple Contract Summary by Consultant 01 14 00 Work Restrictions see below 01 21 00 Allowances by Consultant
More informationFIRE ALARM SYSTEMS INFORMATION PACKET
FIRE ALARM SYSTEMS INFORMATION PACKET Exeter Township Fire Department Office of the Fire Official 2010 1 TABLE OF CONTENTS PURPOSE, SCOPE, DEFINITIONS...3 GUIDELINES...3 I. INTRODUCTION...3 A. APPLICABLE
More informationHow To Get A Job Done
CUMBERLAND COUNTY COMMUNITY DEVELOPMENT (CCCD) HOUSING REHABILITATION PROGRAM PO DRAWER 1829 707 EXECUTIVE PLACE FAYETTEVILLE, NC 28302-1829 CONTRACTOR QUALIFICATIONS: REHABILITATION CONTRACTOR'S HANDBOOK
More informationSITE PLAN APPROVAL PROCESS INTRODUCTION
SITE PLAN APPROVAL PROCESS INTRODUCTION File Manager System for Site Plan Approval Process Site Plan Control in the City of London The City of London utilizes site plan control to ensure high quality site
More informationH.V.A.C. Design Plumbing Design
H.V.A.C. Design H.V.A.C. Design Mira Costa College Arts Complex CP Upgrade 1. PART 1 GENERAL 1.1. DESCRIPTION SECTION 23 09 00 HVAC INSTRUMENTATION AND CONTROL 2. PART 2 - PRODUCTS 2.1. Materials
More informationC. Conform to requirements of Americans with Disabilities Act (ADA).
SECTION 28 31 00 - FIRE ALARM AND DETECTION SYSTEMS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire alarm and detection systems 1.2 REFERENCES A. NFPA 70 - National Electrical Code B. NFPA 72 - National
More informationBUILDING PERMIT APPLICATION APPLICABLE TO CITY LIMITS AND ETJ CHAPTER 18, General
BUILDING PERMIT APPLICATION APPLICABLE TO CITY LIMITS AND ETJ CHAPTER 18, General Property Address: Property Owner: Lot: Block: Subdivision: Lot Size: Scope of Work: Note: Please attach copies of all general
More informationAmendments to the 2012 INTERNATIONAL FIRE CODE
Amendments to the 2012 INTERNATIONAL FIRE CODE 2012 Edition, International Fire Code. Section 101.1 Amend to read as follows. 101.1 Title. These regulations shall be known as the Fire Code of the City
More informationMONTGOMERY COUNTY ALARMS RULES GOVERNING ALARMS RESPONDED TO BY LAW ENFORCEMENT SECTION 1. PURPOSE SECTION 2. DEFINITIONS
MONTGOMERY COUNTY ALARMS RULES GOVERNING ALARMS RESPONDED TO BY LAW ENFORCEMENT These rules and procedures are adopted pursuant to Chapter 233 of the Texas Local Government Code. A copy of these rules
More informationInstructions for Obtaining a Certificate of Smoke Detector, Carbon Monoxide Alarm, and Kitchen Fire Extinguisher Compliance
Princeton Department of Emergency & Safety Services Instructions for Obtaining a Certificate of, Carbon Monoxide Alarm, and Kitchen Fire Extinguisher Compliance 1. Obtain an application Download from /forms
More informationPRIVATE ALARM CONTRACTOR LICENSURE EXAMINATION INFORMATION
PRIVATE ALARM CONTRACTOR LICENSURE EXAMINATION INFORMATION The following information should help you prepare for the Private Alarm Contractor licensure examination. Part I contains general information
More informationMERCER ISLAND FIRE DEPARTMENT FIRE COMMERCIAL SPRINKLER STANDARDS
MERCER ISLAND FIRE DEPARTMENT FIRE COMMERCIAL SPRINKLER STANDARDS COMMERCIAL FIRE SPRINKLER SYSTEMS Page 1-5 SCOPE: Fire sprinkler systems in the City of Mercer Island shall meet the criteria as set forth
More informationdpd Seattle Permits Tip www.seattle.gov/dpd Small Business: Getting Your Use and Building Permit from DPD RESEARCH RESOURCES
dpd Department of Planning and Development Tip 102 Seattle Permits part of a multi-departmental City of Seattle series on getting a permit Small Business: Getting Your Use and Building Permit from DPD
More informationFVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY
FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fire-alarm control unit. 2. Addressable interface
More informationAustin Independent School District Police Department Policy and Procedure Manual
Policy 8.07 Austin Independent School District Police Department Policy and Procedure Manual Life Safety Systems I. POLICY The proper operations of the AISD Life Safety Systems (LSS) are essential for
More informationSPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT
SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT The purpose of these specifications is to insure that there are minimum
More informationPLAN REVIEW GUIDE FOR FIRE ALARM
PLAN REVIEW GUIDE FOR FIRE ALARM PROJECT NAME: PERMIT # PROJECT ADDRESS: CONTACT PERSON: PHONE Fire alarm system installation information shall be provided on the appropriate architectural and electrical
More information527 CMR: BOARD OF FIRE PREVENTION REGULATIONS
527 CMR 24.00: FIRE WARNING SYSTEMS INSTALLED IN BUILDINGS WITHIN THE COMMONWEALTH OF MASSACHUSETTS Section 24.01: Purpose 24.02: Scope 24.03: Definitions 24.04: Approval of Design 24.05: Power Supply
More informationARTICLE III. FIRE ALARMS. Sec. 6-56. Purpose. Sec. 6-57. Definitions.
ARTICLE III. FIRE ALARMS Sec. 6-56. Purpose. It is the intent of this article to reduce the number of false alarms occurring within the city and the resultant waste of fire department resources. Through
More informationJULY 2013 UCB STANDARDS 16720-1
SECTION 16720 FIRE ALARM AND DETECTION SYSTEMS PART 1 GENERAL 1.01 Reference A. Related Sections 1. Section 15300 Fire Protection 2. Section 15950 Controls 3. Division 16 Electrical 4. Division 14 - Conveying
More informationSCHOOL FIRE AND LIFE SAFETY INSPECTION CHECKLIST
SCHOOL FIRE AND LIFE SAFETY INSPECTION CHECKLIST School Name: School Address: Town: Phone: Inspected By (Please Print): Inspection Organization Name: Inspector Phone: Date of Inspection: Building Name:
More informationFIRE ALARM /FIRE PROTECTION OUTAGE/IMPAIRMENT RESPONSE GUIDELINE
Page 1 of 10 FIRE ALARM /FIRE PROTECTION OUTAGE/IMPAIRMENT RESPONSE GUIDELINE SYSTEM TESTING 1. Testing of the Fire Alarm and Fire Protection Systems 1.1. The Building Engineer, Electrician, Plumber (or
More informationThe Pennsylvania State University ------------- Physical Security Office. Intrusion Alarm. Performance Specification
The Pennsylvania State University ------------- Physical Security Office Intrusion Alarm Performance Specification By PHYSICAL SECURITY OFFICE Group (Access Controls & Electronic Security Programs) and
More informationFIRE ALARM SYSTEM RECORD OF COMPLETION
FUNDAMENTALS OF FIRE ALARM SYSTEMS 72 33 FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. PROTECTED PROPERTY
More informationResidential Plan Routing Information
Residential Plan Routing Information BUILDING INSPECTIONS 800 4th AVENUE EAST WEST FARGO, ND 58078 PHONE: 701-433-5480 The building Inspection s Department receives and issues all applications for building
More informationSample Company SECTION 019113 GENERAL COMMISSIONING REQUIREMENTS PART 1 GENERAL 1.1 SUMMARY AND CONTRACT RESPONSIBILITIES
SECTION 019113 GENERAL COMMISSIONING REQUIREMENTS PART 1 GENERAL 1.1 SUMMARY AND CONTRACT RESPONSIBILITIES A. The Owner will contract separately and directly for the majority of the commissioning work
More informationCONTRACT MONITORING SERVICES NEW DEALER INFORMATION AND PROCEDURES
2178 Washington Blvd Ogden, UT 84401 5911 Orchard St West Tacoma, WA 98467 CONTRACT MONITORING SERVICES NEW DEALER INFORMATION AND PROCEDURES Company Dealer # Assigned Address City State Zip Mailing Address
More informationFIRE ALARM SYSTEM RECORD OF COMPLETION
FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. Protected Property Information Name of property: Description
More informationPARK COUNTY BUILDING PERMIT GUIDE PO Box 517 Fairplay, CO 80440 719-836-4255 Fax: 719-836-4268 Inspections: 719-836-4257 www.parkco.
PARK COUNTY BUILDING PERMIT GUIDE PO Box 517 Fairplay, CO 80440 719-836-4255 Fax: 719-836-4268 Inspections: 719-836-4257 www.parkco.us Welcome to the Park County Building Department. The following information
More informationBuilding Permits Permit Counter
Building Permits Permit Counter APPLICATION CHECKLIST SUBMITTAL REQUIREMENTS: 1. Completed signed and notarized Development Services Department Permit Application, submit to Permit Counter. 2. Copy of
More informationBusiness Checklist for Severe Weather
Business Checklist for Severe Weather When faced with a hurricane watch or warning, flood warning or other impending potential natural disaster, refer to this checklist for guidelines on how to prepare
More informationSECTION 16853 ZONED (DC LOOP) FIREALARM SYSTEM
SECTION 16853 ZONED (DC LOOP) FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1
More informationALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.252 WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600
OSHA REGULATION: 9 CFR 90.5 WELDING, CUTTING, AND BRAZING ( HOT WORK ) A. POLICY. This procedure follows requirements set forth in 9 CFR 90.5.. This policy applies to all Hot Work operations being done
More informationELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1
KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1 PART 1 - GENERAL 1.01 RELATED DOCUMENTS: SECTION 16050 A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1
More information946 CMR: MASSACHUSETTS DEVELOPMENT FINANCE AGENCY 946 CMR 7.00: DEVENS REGIONAL ENTERPRISE ZONE FIRE AND POLICE RULES
946 CMR 7.00: DEVENS REGIONAL ENTERPRISE ZONE FIRE AND POLICE RULES Section 7.01: Scope and Purpose 7.02: Definitions - Fire and Police Alarms 7.03: Duties of Fire Chief 7.04: Smoke Detectors in Certain
More informationCHAPTER 277 CERTIFICATION OF ALARM SYSTEM CONTRACTORS AND INSTALLERS. 661 277.1(100C) Establishment of program. There is established within the fire
Adopt the following new chapter: CHAPTER 277 CERTIFICATION OF ALARM SYSTEM CONTRACTORS AND INSTALLERS 661 277.1(100C) Establishment of program. There is established within the fire marshal division an
More informationNUNAVUT HOUSING CORPORATION. Home Repair Program (HRP)
NUNAVUT HOUSING CORPORATION Home Repair (HRP) October 2014 Home Renovation (HRP) Date October 201 TABLE OF CONTENTS OBJECTIVE... 1 SUMMARY... 1 ENABLING LEGISLATION... 1 ELIGIBLE CLIENTS... 1 PRIORITY
More information