Rack-mount Power Distribution Units and UL
|
|
|
- Dennis Anderson
- 10 years ago
- Views:
Transcription
1 Rack-mount Power Distribution Units and UL Overview The intent of this document is to define UL , provide an overview of this standard as it applies to rackmount power distribution units (PDUs). In addition the document will discuss the impact of products that may or may not comply with this standard as they relate to end-user implementation. Introduction As data centers become more complex and as more companies invest millions of dollars into data center integrity and safety, the need for equipment that has been tested to applicable standards is widely recognized. These standards ensure uptime, network and human safety. Standards such as UL are beginning to make an impact on design and implementation of IT equipment in the data center, yet products are still widely available that have not been redesigned to be compliant with this standard or have not been tested to this standard. What is UL ? UL Information Technology Equipment - Safety - Part 1. This standard is applicable to mains-powered or battery-powered information technology equipment, including electrical business equipment and associated equipment. [ UL is a relatively new Underwriters Laboratory (UL) standard that applies to Information Technology Equipment installed and implemented in the data center. Rackmount powerstrips, analogous to some as power distribution units (PDUs), fall into this category of equipment as defined by UL. Potentially the most impacting piece of the standard, as it applies to PDUs in relation to data center safety, is the branch circuit protection. Branch circuit protection requires that all outlets and receptacles be protected by an Overcurrent Protection Device such as a circuit breaker or fuse rated at or set at no more than the rating of the outlet or receptacle. This allows for compliance with the National Electric Code and engenders one of the main characteristic of differentiation
2 between PDUs that comply with the standard vs. PDUs that may only be UL Recognized, comply with legacy standards or may have no UL Certification. Why is UL important when implementing PDUs in data centers? It is important to note that non-ul certified PDUs, and PDUs that do not comply with applicable standards, may work for specific applications and within certain environments. However, it is equally important to understand that if approved branch circuit protection is not used within the data center environment, the following may happen: Claims Payment: Fire or damage created or contributed by a rackmount PDU that is not certified by an applicable agency in compliance with its intended use may be denied or reduced by the provider issuing property and/or casualty insurance Local Code Violations: Building inspectors who seek to enforce compliance of NEC codes and local or state civil codes may find PDUs that have not been designed to UL standards in violation of branch circuit protection safety requirements. Insurance Risks: An organization that installs, sells, manufactures or distributes PDUs that do not meet UL s requirements for branch circuit protection and/or have not sought the appropriate listing to verify compliance may increase limitations of liability, may face reductions of coverage, may incur higher premiums or may face losing general liability insurance, altogether. The Technicalities of UL All products, utilized for Information Technology Equipment, submitted for UL certification, must meet the standards of UL PDUs fall into this classification PDUs certified to the standard & the National Electric Code (NEC) must have branch circuit protection for the receptacles The standard requires that all outlets and receptacles be protected by an Overcurrent Protection Device such as a circuit breaker of fuse rated at or set at no more than the rating of the outlet or receptacle The standard does not allow for the use of supplementary Overcurrent Protection Device for the
3 branch circuit. Supplementary Overcurrent Protection Device is defined as any device not integrated into the PDU or upstream of the PDU, between the primary distribution panel and the PDU, that is intended to provide some type of overcurrent protection to multiple branch circuits. The Overcurrent Protection Device such as a fuse or circuit breaker must be compliant with the NEC, ANSI/NFPA 70 For PDUs with multiple branch circuits, an overload protection device such as an approved fuse or circuit breaker must reside inside the PDU for each branch circuit. 30-amp PDUs must have a UL 489 breaker or a UL #248 fuse complying with JDDZ categorization. This coupled with the need for individual branch circuit protection intrinsically adds more component cost to the PDU itself. Why are many rack and enclosure manufacturers demanding that their ODM/OEM suppliers of PDUs now be compliant with UL 60950? In order to provide insight prior to developing an answer to this question, one must first understand the difference between UL recognized and UL Listed. UL recognized is a component to be used in the construction of another product. A UL Listed product is complete in its entirety and can be used by the purchaser. An example of this may be the purchaser of an Uninterruptible Power Supply (UPS) who examines the UPS and finds a UL Listing Mark on the product indicating the product meets the standards outlined in UL 1778, Uninterruptible Power Systems (UPS). [ The same customer may purchase another brand of UPS and after careful evaluation notice the unit does not have a UL Listing mark, however, recognizes the fan inside the unit and digital display have the UL Recognized Component marks. The purchaser decides to contact the manufacturer to inquire about the safety of the product and the manufacturer claims that the product was built with UL Recognized components, therefore must meet the requirements to be UL Listed. But this is not necessarily the case, because the UL Recognized component means the component alone meets the requirement for a specific, limited use.
4 This concept has impacted many data center enclosure manufacturers who have obtained and/or are seeking UL certification for their newest products. In the ultra-competitive data center enclosure industry, many manufacturers are starting to differentiate by offering value-added services such as installing PDUs into the cabinet prior to shipping, which benefits the customer by decreasing the mean time of installation. Thus, if installed in the unit prior to shipping, the PDU becomes part of the UL enclosure system,. Herein lies the crux of the issue: Does the enclosure now have to remove its UL Listed label if the PDU, that has been installed prior to shipment, is not UL Listed? Arno Zandbergen, Product Manager for Great Lakes Case and Cabinet believes so: We have spent considerable time and effort pursing and obtaining the most applicable data center safety standard for our enclosures, UL We have discussed this with our UL liaisons and have been advised that installing PDUs without the associated UL listing would require the removal of the UL Listing sticker from the enclosure prior to shipment. Not only does UL offer improvements in branch circuit protection that directly affects safety, we believe our customers should be afforded the ability to know that the enclosure has obtained this standard by viewing the UL Listing mark. We believe in providing the added value of installed PDUs and it would not make sense for us to offer anything other than a PDU that has obtained this listing. Therefore, we now require and have obtained this certification for our entire PDU offering. This demand by these enclosure producers may not only be based solely on the attraction to the extra branch circuit protection afforded by the standard, but may also be because the producers are desirous to be in complete compliance with UL and its guidelines at all times, regardless of local interpretation. Why aren t many manufacturers offering power strips or PDUs with the UL certification? Cost Redesign costs may include new UL fees, potential case redesign, more costly component costs associated with branch circuit protection requirements and the need to utilize UL 489 breakers are potentially viewed as decreasing product margins. Market Awareness/Complexity- Many companies find it difficult to navigate through the maze of design and safety standards, therefore applicable certifications may not be pursued, may not be understood and may not be required.
5 Timing Many products may currently be undergoing development and testing to the standard, however, may not be available for shipment to customers
6 Summary and Availability The market is still flooded with PDUs that are UL Recognized Components and may only be compliant with UL 1363 or may have no certification at all. Based upon safety requirements for branch circuit protection and potential avoidance of liability, it may be prudent that UL PDUs be required. Para Systems, Inc. manufacturer of a variety of power technology products, offers a full line of vertical, horizontal, amp-metered and non-amp-metered PDUs in various amperages that are UL listed and provide the industry-leading cost to features ratio.
Server Technology, Inc.
Server Technology, Inc. Branch Circuit Protection: Power Distribution for IT Equipment in the Data Center Server Technology, Inc. 1040 Sandhill Drive Reno, NV 89521 +1 (775) 284-2000 www.servertech.com
Data Center Power Overload Protection: Circuit breakers and branch circuit protection for data centers
Data Center Power Overload Protection: Circuit breakers and branch circuit protection for data centers 2009, Raritan Inc. Introduction Over the past few years, average power consumption per server has
Server Technology Inc.
Server Technology Inc. Alternating Phase Power Distribution at the Data Center Rack PDU White Paper STI-100-012 2013-April-18 By Steve Hammond, Product Manager, Server Technology Headquarters Server Technology,
Alternating Phase Power Distribution at the Data Center Rack PDU
Alternating Phase Power Distribution at the Data Center Rack PDU White Paper STI-100-012 November 2013 - Updated August 2014 By Steve Hammond, Product Manager, Server Technology Marc Cram, Director of
The U.S. Department of Labor projects that electrician careers will grow to 698,200 by 2022.
The U.S. Department of Labor projects that electrician careers will grow to 698,200 by 2022. Train now for affordable Electrician careers and get wired for success. Residential Electrician Diploma Program
Center for Clinical Standards and Quality /Survey & Certification Group. Categorical Waiver for Power Strips Use in Patient Care Areas
DEPARTMENT OF HEALTH & HUMAN SERVICES Centers for Medicare & Medicaid Services 7500 Security Boulevard, Mail Stop C2-21-16 Baltimore, Maryland 21244-1850 Center for Clinical Standards and Quality /Survey
Power Distribution Considerations for Data Center Racks
Power Distribution Considerations for Data Center Racks Power Distribution Considerations for Data Center Racks Table of Contents 3 Overview 4 At what voltage do you run all the IT equipment? 4 What electrical
Distributing Power to Blade Servers
Distributing Power to Blade Servers Ten steps to selecting the optimal power distribution design With the growth in blade servers with dual or triple power supplies, a single rack of equipment can easily
Lightning Protection Services Prevent loss from lightning damage with UL s Inspection Certificate
Lightning Protection Services Prevent loss from lightning damage with UL s Inspection Certificate Your first strike against lightning damage. Increase safety, minimize risk, protect from liability. Having
Mission Critical Data Center Systems
Mission Critical Systems Mission Critical/ Electrical Distribution Systems Data center electrical distribution designs are rapidly evolving, driven by needs such as increasing power densities, energy efficiency,
Power Distribution Systems for the Dell PowerEdge M1000e Modular Server Enclosure - Selection and Installation
One Dell Way Round Rock, Texas 78682 www.dell.com Dell Enterprise White Paper Power Distribution Systems for the Dell PowerEdge M1000e Modular Server Enclosure - Selection and Installation January, 2008
Short-circuit current rating (SCCR) of. industrial control panels. NEC Article 409 and UL 508A
Short-circuit current rating (SCCR) of industrial control panels NEC Article 409 and UL 508A Short-circuit current rating (SCCR) of industrial control panels 1 Introduction 2 Overview of NEC Article 409
Proper Application of 415V Systems in North American Data Centers. A White Paper from the Experts in Business-Critical Continuity
Proper Application of 415V Systems in North American Data Centers A White Paper from the Experts in Business-Critical Continuity Introduction Increasing pressure to reduce operating expenses and be more
Key Considerations for Selecting Server Cabinets for Seismic Areas
Key Considerations for Selecting Server Cabinets for Seismic Areas Protect Up to 1500 of Critical Network Equipment without Sacrificing Flexibility Planning a data center in a seismically active area requires
ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:
ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS: Chapter 12 of the Burlington Code of ordinances allows owner occupants of single family homes to do their own wiring if they choose. If you choose to
ZONIT POWER DISTRIBUTION SYSTEM ORDER CATALOG
ZONIT POWER DISTRIBUTION SYSTEM ORDER CATALOG Introduction The Zonit Data Center Power Distribution System (zpds ) offers an ultrareliable, turnkey power distribution system for modern high-availability
Fire Life Safety ORC Review Guidelines for PPD Experimental Installations
Fire Life Safety ORC Review Guidelines for PPD Experimental Installations Fire Protection Review for the Fixed Target ES&H Review Committee September 2010 By James Priest PhD DRAFT Overview: When reviewing
8146/5 Series Breaker Panelboards
8146/5 Series Breaker Panelboards DISTRIBUTION BREAKER PANELBOARDS FOR HAZARDOUS & CORROSIVE ENVIRONMENTS Breaker Panels Features: Wide variety of Flameproof branch circuit breakers for Zone 1 & Division
SOUTH CAROLINA. Standard for Interconnecting Small Generation 100 kw or Less with Electric Power Systems (EPS) (Interconnection Standard)
SOUTH CAROLINA Standard for Interconnecting Small Generation 100 kw or Less with Electric Power Systems (EPS) (Interconnection Standard) 1. Overview: This Standard contains the requirements, in addition
Power to the adaptable data center
Business Unit Manager, Data Center Solutions, Eaton s electrical group IT managers have more options than ever to tailor the power infrastructure to their unique data center and business requirements.
Spec Sheet. Cisco R42610 Rack CISCO SYSTEMS PUBLICATION HISTORY 170 WEST TASMAN DR. SAN JOSE, CA, 95134 REV A.6 DECEMBER 9, 2014 WWW.CISCO.
Spec Sheet CISCO SYSTEMS PUBLICATION HISTORY 170 WEST TASMAN DR. SAN JOSE, CA, 95134 REV A.6 DECEMBER 9, 2014 WWW.CISCO.COM Overview................................................ 3 Rack Certifications
ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1
KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1 PART 1 - GENERAL 1.01 RELATED DOCUMENTS: SECTION 16050 A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1
The Anatomy of a. High-Availability Rack. November 2009. Online Tech, Inc. 220 E. Huron Ann Arbor, MI 48104 (734) 213-2020. www.onlinetech.
Online Technologies Corporation September 2008 If you have questions, please contact: The Anatomy of a Onl (734) 213-2020 phone High-Availability Rack November 2009 Online Tech, Inc. 220 E. Huron Ann Arbor,
Circuit Breakers in Data Centers: The Hidden Danger
Circuit Breakers in Data Centers: The Hidden Danger How to efficiently protect critical IT equipment by choosing the most reliable overcurrent protection device for your Rack Power Distribution Unit. By
Efficiency and Other Benefits of 208 Volt Over 120 Volt Input for IT Equipment
Efficiency and Other Benefits of 208 Volt Over 120 Volt Input for IT Equipment By Neil Rasmussen White Paper #27 Revision 2 Executive Summary Decisions made regarding the distribution of 208V or 120V power
42U/45U 28" Wide Rack Installation & Service Guide
42U/45U 28" Wide Rack Installation & Service Guide 96-00171-005 Rev B Important Information Information in this document is subject to change without notice and does not represent a commitment on the part
Types of Electrical Meters in Data Centers
Types of Electrical Meters in Data Centers White Paper 172 Revision 1 by David Kidd and Wendy Torell > Executive summary There are several different types of meters that can be designed into a data center,
DVI DA2 and DVI DA 4 User Guide
DVI DA2 and DVI DA 4 User Guide This guide describes the installation and operation of the Extron DVI DA2 and DVI DA4 Distribution Amplifiers. Unless stated otherwise, distribution amplifier or the unit
UL guidelines, chapter 6.2 / 6.3 Motor Branch Circuits acc. to UL
UL guidelines, chapter 6.2 / 6.3 Motor Branch Circuits acc. to UL Definition of Terms / Explanations Overview of Basic Devices Construction Types acc. to UL 508 Self-Protected Combination Motor Controller
High-Efficiency AC Power Distribution for Data Centers
High-Efficiency AC Power Distribution for Data Centers White Paper 128 Revision 2 by Neil Rasmussen > Executive summary The use of 240 volt power distribution for data centers saves floor space, simplifies
NEC Class 2 Power Circuits and Power Supplies
NEC Class 2 Power Circuits and Power Supplies Abstract: The NEC (National Electrical Code) is a North American standard, which can be regarded as a law in most of the North American states. Among others,
Electrical Plan Design
CHAPTER 1 Electrical Plan Design Chapter Outline Chapter Outline Introduction The Design Process Understanding the Project Scope Defining Parts of the Electrical Plan Determining Applicable Standards Creating
Intelligent power measurement in data centres
Intelligent power measurement in data centres Table of contents 1. About Schleifenbauer 02 2. Why measure power? 03 3. Portfolio of products 04 4. Customer-oriented, durable quality products 07 5. The
Rack Power Distribution. Worldwide
Rack Distribution Worldwide Introduction APC TM by Schneider Electric TM offers a wide array of standardized Rack Distribution Units (PDUs) designed to increase manageability and efficiency in your data
PrinciplesofAccounting II Lesson #5
PrinciplesofAccounting II Lesson #5 Financial Statement Analysis By Laurie L. Swanson Click the button below to navigate to the next slide. Financial Statement Analysis The process of analyzing businesses
Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services
Circuit Breakers and Switchgear Thomas Greer Director of Engineering TLG Services Presentation Outline Switchgear Definition Overcurrent Protection Devices Circuit Breaker Trip Curves and Coordination
Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint
Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint Energy usage in the data center Electricity Transformer/ UPS Air 10% Movement 12% Cooling 25% Lighting, etc. 3% IT Equipment
LT Charging Cart for Laptops
Built with Anthro-DNA LT Charging Cart for Laptops Owners Manual This unit has been tested to Underwriters Laboratories U.S. and Canadian (Bi-National) Standard for Safety of Informational Technology Equipment,
101 BASICS SERIES LEARNING MODULE 3: FUNDAMENTALS OF ELECTRICAL DISTRIBUTION. Cutler-Hammer
101 BASICS SERIES LEARNING MODULE 3: FUNDAMENTALS OF ELECTRICAL DISTRIBUTION Cutler-Hammer WELCOME Welcome to Module 3, Fundamentals of Electrical Distribution. If you have successfully completed Module
Introduction to TAA Compliance for Government IT Suppliers, Distributors, Resellers and Contractors
W H I T E P A P E R Introduction to TAA Compliance for Government IT Suppliers, Distributors, Resellers and Contractors Executive Summary If you supply products for GSA Schedules and other government contracts,
RISK MODIFICATION PLANS
Amended Regulation 5-1-11 RISK MODIFICATION PLANS Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section 7 Section 8 Authority Basis and Purpose Rules Enforcement Severability Dissemination
Application Briefs: Remote Office Environment
Overview Remote offices are a definite sign of growth, but it can constitute an immense challenge from an IT infrastructure standpoint. Remote offices may include a wide variety of wiring closets and small
1. Introduction... 2 2. Availability & types of colocation... 2
Service Description Service Description COLOCATION SERVICES 1. Introduction... 2 2. Availability & types of colocation... 2 2.1 Signature Colocation... 2 2.2 Sterling Colocation... 3 2.3 Network Colocation...
Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers
9229 Waterford Centre Dr. Bldg C, Suite 110 Austin, Tx 78758 Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers Current Version: 13 AC Modules are a new product
How To Manage A Power Station
CARESERV TECHNOLOGIES, LLC SERVICE AGREEMENT COLOCATION SERVICES SCHEDULE Version 2014.1 (01.01.2014) This Schedule, together with any Order referencing this Schedule or pursuant to which the services
Engineering Series Ratings: Is It Practical?
Engineering Series Ratings: Is It Practical? By the National Electrical Manufacturers Association The 2005 National Electrical Code (NEC) introduces a change regarding series ratings for circuit breakers
Simplified Guide To Understanding Short-Circuit Current Rating FIND IT, FIX IT, FORGET IT
Simplified Guide To Understanding Short-Circuit Current Rating FIND IT, FIX IT, FORGET IT Are You Ready For The New SCCR Marking Requirements? What Is A Short-Circuit Current Rating (SCCR)? SCCRs on components
How To Power A Bladecenter H Servers
Solutions Guide for IBM Data Center Architecture: IBM BladeCenter H Servers In today s high-demand enterprise environment, organizations need a reliable infrastructure to run compute-intensive applications
Project Name: Nortrax Section 26 41 00 Project No: 13-013 SURGE PROTECTION DEVICES Page 1
Page 1 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Divisions 1 Specification sections apply to
LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification
08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and
Measuring Power in your Data Center
RESEARCH UNDERWRITER WHITE PAPER LEAN, CLEAN & GREEN Raritan Measuring Power in your Data Center Herman Chan, Director, Power Solutions Business Unit, and Greg More, Senior Product Marketing Manager There
Qualitative Analysis of Power Distribution Configurations for Data Centers
Qualitative Analysis of Power Distribution Configurations for Data Centers White Paper #4 2007 The Green Grid. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted,
Power Management Strategies for High-Density IT Facilities and Systems. A White Paper from the Experts in Business-Critical Continuity TM
Power Management Strategies for High-Density IT Facilities and Systems A White Paper from the Experts in Business-Critical Continuity TM Executive Summary Increases in data center density and diversity
Data center solutions Medium & large enterprise, multi-tenant and hyperscale. Energize your data center, maximize the value of your investment
Data center solutions Medium & large enterprise, multi-tenant and hyperscale Energize your data center, maximize the value of your investment We serve the needs of data centers of all sizes, around the
Optimizing Power Distribution for High-Density Computing
Optimizing Power Distribution for High-Density Computing Choosing the right power distribution units for today and preparing for the future By Michael Camesano Product Manager Eaton Corporation Executive
Data Centre Infrastructure Assessment
Data Centre Infrastructure Assessment Prepared for: ACME INC SAMPLE REPORT Attention: Mr DC Manager This report represents a generic sample data centre audit for a generic customer by Focus Group Technologies.
Dominion PX. General Questions. What is Dominion PX (PX)?
Dominion PX Question General Questions What is Dominion PX (PX)? Is Raritan new to the rack power distribution unit market? Can the PX be used as a stand-alone device? Does PX work with Raritan s CommandCenter
The Problem with UL Approval of Rigid Flex Circuits
A Printed Circuits, Inc. White Paper 1200 West 96 th Street Minneapolis, Minnesota 55431 952.888.7900 PrintedCircuits.com The Problem with UL Approval of Rigid Flex Circuits By Bob Burns, National Sales
QuickSpecs. HP 480/277 Volt Solutions. Overview
Overview As the quest for efficiency continues it becomes apparent that what worked in the past needs improvement. More and more data center managers are looking at alternate power plans to distribute
Electrical Contractors. and the. New Jersey. Rehabilitation Code
Electrical Contractors and the New Jersey Rehabilitation Code Alan Chech Electrical Seminars 609-890-7072 www.alanchech.com Information is based on the presently adopted electrical subcode NEC 2005. Current
DCF Optimized Rack System Selection Guide
DCF Optimized Rack System Selection Guide DCF Optimized Rack System: Optimized Design, Optimized Delivery, Optimized Value A Rack System Designed to Meet The Challenges Your Data Center Faces Today Your
APC Step-Down Transformer. User s Manual
APC Step-Down Transformer Models: AP9621, SURT005, SURT006, SUTF3, SYTF2, SYTF2J, SYTF3 and SYTF3J User s Manual English 990-7820D, July 2003 TABLE OF CONTENTS APC Contact Numbers and Support Visit the
SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A
SURGE PROTECTIVE DEVICES (SPDs) INTEGRATED UNITS LOW VOLTAGE AC SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS PART 1 GENERAL 01 02 03 SCOPE The Contractor shall furnish and install the Surge Protective
Rack Power Distribution
The Rack PDU Selector is located at: www.apc.com/tools/selector/pdu Test drive a metered or switched Rack Power Distribution Rack PDU at testdrive.apc.com 132 Fairgrounds Road West Kingston, RI 02892 Phone:
Increasing Data Center Efficiency by Using Improved High Density Power Distribution
Increasing Data Center Efficiency by Using Improved High Density Power Distribution By Neil Rasmussen White Paper #128 Executive Summary A new approach to power distribution for high density server installations
EX PARTE EMERGENCY ORDER TO CEASE AND DESIST THE UNAUTHORIZED AND UNLAWFUL TRANSACTION OF THE BUSINESS OF TITLE INSURANCE IN THE STATE OF COLORADO
BEFORE THE DIVISION OF INSURANCE STATE OF COLORADO Case File No. 144415 Order No. O-05-020 EX PARTE EMERGENCY ORDER TO CEASE AND DESIST THE UNAUTHORIZED AND UNLAWFUL TRANSACTION OF THE BUSINESS OF TITLE
Solar Home System Kit Quality Standards
Solar Home System Kit Quality Standards Version 1 December 2015 Lighting Global has expanded the quality assurance framework to cover solar home system kits. This document describes the Quality Standards
City of San Diego Residential Photovoltaic Systems Inspection Guidelines
City of San Diego Residential Photovoltaic Systems Inspection Guidelines The purpose of inspections by DSD staff is to ensure compliance with the California Electrical Code (CEC), other applicable codes
Fire Alarm System Monitoring - CAN/ULC-S561-03
Fire Alarm System Monitoring - CAN/ULC-S561-03 Brian McBain ULC Regulatory Services May 4, 2011 Copyright 1995-2007 Underwriters' Laboratories of Canada. All rights reserved. No portion of this material
Emerson Network Power Rack PDU Solutions Rack Power Distribution For Critical IT Equipment. AC Power For Business-Critical Continuity
Emerson Network Power Rack PDU Solutions Rack Power Distribution For Critical IT Equipment AC Power For Business-Critical Continuity Enhanced Performance And Management Of Dynamic IT Spaces IT space is
misconceptions about arc-flash hazard assessments
misconceptions about arc-flash hazard assessments There are some common misconceptions about Arc-Flash Hazard Assessments which reduce the effectiveness of the Assessments and can increase electrical hazards.
Essential NCPI Management Requirements for Next Generation Data Centers
Essential NCPI Requirements for Next Generation Data Centers By Ted Ives White Paper #14 1 Executive Summary The management of physical infrastructure in data centers can no longer be considered independently
Busting the UL 300 Money Myth
WHITE PAPER Busting the UL 300 Money Myth Four Reasons You Can t Wait to Upgrade to a UL 300 Fire Suppression System One Stanton Street / Marinette, WI 54143-2542, USA / +1-715-735-7411 / www.ansul.com
DATAMENA COLOCATION SERVICE SCHEDULE
DATAMENA COLOCATION SERVICE SCHEDULE This Schedule is applicable to a Service Order for datamena Colocation Service(s) which has been submitted by Customer, and accepted by Supplier, in accordance with
Data Centers and Mission Critical Facilities Operations Procedures
Planning & Facilities Data Centers and Mission Critical Facilities Operations Procedures Attachment A (Referenced in UW Information Technology Data Centers and Mission Critical Facilities Operations Policy)
Power Commander Power Distribution Units from Wiremold/Legrand offer
Power Commander Power Distribution Units Rack Power Distribution Solutions for IT/Network Environments Power Commander Power Distribution Units from Wiremold/Legrand offer comprehensive power distribution
IR WINDOW CERTIFICATION GUIDEBOOK. Copyright CorDEX Instruments Ltd. www.irwindows.com training@cord ex.com. ID 4016 Rev A
IR WINDOW CERTIFICATION GUIDEBOOK Copyright CorDEX Instruments Ltd. www.irwindows.com training@cord ex.com ID 4016 Rev A Content 1. General... Page 3 2. Introduction... Page 4 3. UL Underwriters Laboratories...
Installation. Basic Rack Power Distribution Unit for Blade Servers
Installation Basic Rack Power Distribution Unit for Blade Servers Contents Preliminary Information...................1 Features............................. 1 Receiving inspection................... 1
Utility Distribution Systems
Utility Distribution Systems 6/2012 A0011037 1 WARRANTY This equipment is warranted to be free from defects in materials and workmanship, under normal use and service, for a period of 12 months from date
Learning Module 13: Panelboards and Switchboards. 101 Basic Series
Learning Module 13: Panelboards and Switchboards 101 Basic Series What You Will Learn We ll step through each of these topics in detail: Introduction 4 Definitions 4 Similarities Between Panelboards and
Cabinets 101: Configuring A Network Or Server Cabinet
Cabinets 101: Configuring A Network Or Server Cabinet North, South and Central America White Paper May 2012 www.commscope.com Contents Background Information 3 What is a network or server cabinet? 3 What
HP UPS R1500 Generation 3
HP UPS R1500 Generation 3 Installation Instructions Part Number 650952-001 NOTE: The rating label on the device provides the class (A or B) of the equipment. Class B devices have a Federal Communications
Increase the efficiency of power distribution in your high-density data center
Increase the efficiency of power distribution in your high-density data center Abstract As power density in modern data centers increases, more focus has been placed on improving efficiency in the power
Database Design for Electrical Panels
Christian Brothers University 650 East Parkway South Memphis, TN 38104-5581 Database Design for Electrical Panels By Shalini Gupta, Monte DePouw John Ventura MEMPHIS AREA ENGINEERING AND SCIENCES CONFERENCE
Emerson Network Power Rack PDU Systems
AC Power For Business-Critical Continuity Emerson Network Power Rack PDU Systems Product Selection Guide - North American Models TABLE OF CONTENTS 1.0 EMERSON NETWORK POWER RACK PDU SYSTEMS..............................1
Low Voltage Fuses For Motor Protection
Code Requirements The NEC or CEC requires that motor branch circuits be protected against overloads and short circuits. Overload protection may be provided by fuses, overload relays or motor thermal protectors.
KSR-SK-DB In-Line Splice Kit KSR Snow Melting Cable INSTALLATION PROCEDURES
KSR-SK-DB In-Line Splice Kit KSR Snow Melting Cable INSTALLATION PROCEDURES KSR-SK-DB The following installation procedures are suggested guidelines for the installation of in-line cable splices. They
Ceiling Mount Air Handler Manual
www.surna.com 303.993.5271 Ceiling Mount Air Handler Manual Models: CMAH12, CMAH18, CMAH24, CMAH30, CMAH36, CMAH48, CMAH60 Revised: September 2014 Table of Contents Warranty Information 4 Limited Warranty
LEHI CITY POWER NET METERING STANDARDS For Customer-Owned Electric Generating Systems
LEHI CITY POWER NET METERING STANDARDS For Customer-Owned Electric Generating Systems A. General This Net Metering Standard for Customer-Owned Grid Connected Electric Generating Systems sets forth the