1 BCFC Part 4 Flammable and Combustible Liquids Application: BCFC Part 4 Part 4 provides for the storage, handling, use and processing of flammable liquids and combustible liquids in buildings,, structures and open areas. Bob Furlong BCFC Part 4 Part 4 DOES NOT apply to: transportation of flammable liquids or combustible liquids appliances and their ancillary equipment within the scope of CAN/CSA-B139, Installation Code for Oil-Burning Equipment the storage of flammable liquids or combustible liquids on farms for individual farm use and on isolated construction projects, or the storage of aerosol products covered under Subsection Flammable & Combustible Liquids BCFC focuses on Flash Point (FP) and Boiling Point (BP) to establish a Class Rating. Different classes of flammable and combustible liquids pose different hazards and therefore have different rules. Classifying Flammable Liquids Flammable liquid classes: Classifying Combustible Liquids Combustible Liquid Classes Class IA F.P. below 22.8 C (73 F), boiling point below 37.8 C (100 F) Class IB F.P. below 22.8 C (73 F), boiling point at or above 37.8 C (100 F) Class IC F.P.. at or above 22.8 C (73 F), and below 37.8 C (100 F), Class II F.P. at or above 37.8 C (100 F) but below 60 C (140 F.) Class IIIA F.P. at or above 60 C (140 F) but below 93.3 C (200 F.) Class IIIB F.P. at or above 93.3 C (200 F.). 1

2 Boiling Point Temperature at which the saturated vapour pressure of a liquid is equal to atmospheric pressure Flammable and Combustible Liquids Combustible liquid classes: Class II Flash Point _> 37.8øC and below 60øC Class IIIA Flash Point => 60øC and below 93.3øC Flashpoint and Boiling Point Refer to: Manufacturer's Material Safety Data Sheets (MSDS) Flashpoint and Boiling Point Manufacturer's Material Safety Data Sheets (MSDS) Exercise F F LIQUID F.P. B.P. Class Diesel Fuel # Gasoline Motor Oil 450 >500 Isoamyl Acetate Ethyl Ether Formalin Mixture 98% Motor Oil and 2% Gasoline Use the FP (Flash Point) and the BP (Boiling Point) to determine the Class using the Flammable CombustibleLiquid Chart. Exercise F F LIQUID F.P. B.P. Class Diesel Fuel # Class II Gasoline Class IB Motor Oil 450 >500 Class IIIB Isoamyl Acetate Class IC Ethyl Ether Class IA Formalin Class II Mixture 98% Motor Oil and 2% Gasoline Class IB Use the FP (Flash Point) and the BP (Boiling Point) to determine the Class using the Flammable CombustibleLiquid Chart. Flammable and Combustible Liquids Flammable and Combustible Liquids Heated Liquid? When a liquid having a flash point at or above 37.8 C is being processed, stored, handled or used at a temperature at or above its flash point, it shall be treated as a Class I liquid. Used Lubricating Oil? Classify as a Class IIIA liquid. EXCEPT - When Class I or II liquids are added to the used oils classify: through tests (BCFC ) or as a Class IC liquid if Class I liquids are added, or as a Class II liquid if only Class II liquids are added. 2

3 Flammable Liquids Mixtures containing component/s with a flash point of 100 F or higher which make up 99% or more of the total volume of the mixture, are not considered flammable. Fire Tetrahedron Fuel Heat Source Oxygen Combustible Flammable Liquid Increases Surface Temperature Production of Ignitable Vapours Therefore, mixtures containing more than 1% of a liquid with a flash point below 100 F are considered flammable. Sustained Combustion Suitable Chemical Reaction Flame Established Flammable Limits Lower explosive limit (LEL) minimum concentration of vapour or gas in air below which propagation of flame does not occur on contact with a source of ignition. Upper Explosive Limit (UEL) maximum proportion of vapour in air above which propagation of flame does not occur. LEL or UEL are usually expressed in terms of percentage by volume of vapour in air. Fire Protection and Prevention Considerations BASICS Management of: Ignition sources Flammable vapours Spills or leaks Ground vegetation and accumulations of combustible materials not essential to operations. Contaminated rags and similar materials 15 Fire Protection and Prevention Considerations Flammable and Combustible Liquids BASIC Access for fire fighting Management of Hot Works Fire Safety and Emergency Plan Electrical Installations Electrical equipment in a location where flammable liquids or combustible liquids are present shall conform to the British Columbia Safety Standards Act and pursuant regulations 3

4 Electrical - Classes Canadian Electrical Code (C.E.C.), Part I, Section 18 - Hazardous Locations, identifies three classes of hazardous locations: Class I - Gas and Vapour Environments Explosion Proof Electrical Divisions or Zones Division - pre-1998 C.E.C. Zone C.E.C. Class II - Dust Environments Class III - Fibers and Flyings Environments Done to here Go back to flash point Hazardous atmosphere is expected to be present during normal operations on a continuous, intermittent or periodic basis Div 1 Flammable atmosphere highly likely to Done to here Go back be to present flash point - may be present for long periods or even continuously Zone 0 Zone 1 Flammable atmosphere possible but unlikely to be present for long periods Div 2 Volatile flammable liquids or gases are handled, processed or used but in which they would normally be confined within closed containers or closed systems from which they can escape only in the event of an accidental rupture or breakdown of the containers or systems. Zone 2 Flammable atmosphere unlikely to be present except for short periods of time - typically as a result of a process fault condition. Electrical Division Vs. Zone Terminology Electrical - Group Gas Groups specific members! 4

5 Comparisons Static Electric Charge Bonding & Grounding Screw clamp Solvent Drum Terminal lug Wire ground connector Flexible wire bonding Spring clamp Safety can Ground conductor Ground Evaluate Steps to Protect Evaluate Liquid in use (i.e. flammable or combustible) Quantity limits suitable for occupancy Method/location of storage Separation needs Storage, processing or dispensing? Sources of ignition Ventilation (natural or mechanical) Spill or leak management Protection (none, sprinkler or other) Fire Safety Planning & supervisory staff training Flammable Liquids Steps to Protect Liquid Classification Class IA Class IB Class IC Flash Point <73 F and Boiling Point <100 F. Flash Point <73 F and Boiling Point 100 F. Flash Point 73 F and <100 F. 5

6 Protection Steps to Protect Other Items for Flammable Liquid Areas Floor / Wall Openings / Penetrations Fire s Fire Dampers Fire Stopping Materials. Protection Steps to Protect Other Items for Flammable Liquid Areas Explosion Venting NFPA 30 requires for storage of Class IA liquids. Generally required if dispensing liquids with flash point <100 F. Protection Steps to Protect Other Items for Flammable Liquid Areas Bonding and Grounding Generally only needed if dispensing liquids. Container Type Containers Flammable Liquids Combustible Liquids Class IA Class IB Class IC Class II Class III Glass or approved plastic 1 pt. 1 qt. 1 gal. 1 gal. 1 gal. Metal (other than DOT drums) 1 gal. 5 gal. 5 gal. 5 gal. 5 gal. Safety cans 2 gal. 5 gal. 5 gal. 5 gal. 5 gal. Metal drums (DOT specifications) 60 gal. 60 gal. 60 gal. 60 gal. 60 gal. Approved portable tanks 660 gal. 660 gal. 660 gal. 660 gal. 660 gal. Note: Container exemptions: (a) Medicines, beverages, foodstuffs, cosmetics, andother commonconsumer items, when packaged according to commonlyaccepted practices, shall be exempt fromthe requirements of. Container and Portable Tank Storage Storage cabinets Cabinets shall be labeled in conspicuous lettering, "Flammable Keep Fire Away" Must be fire resistant Contain no more than 60 gallons of Class I or Class II nor contain no more than 120 gallons of Class III liquids Specific requirements for metal and wood Container and Portable Tank Storage Inside storage rooms Shall be constructed to meet the required fire-resistive resistive rating for their use If used for Class I liquids, electrical wiring and equipment in inside storage rooms shall be approved for Class I, Division 2 Hazardous Locations Provided with either a gravity or a mechanical exhaust ventilation system 6

7 Container and Portable Tank Storage In inside storage rooms Maintain one clear aisle at least 3 feet wide Containers over 30 gallons capacity shall not be stacked one upon the other Dispensing shall be by approved pump or self-closing faucet only Storage shall comply with Table H-13 Fire Protection (1) Provided Storage Inside Rooms Fire Resistance Maximum Size Total Allowable Quantities gals./sq. ft/floor area Yes 2 hours 500 Sq. Ft. 10 No 2 hours 500 Sq. Ft. 4* Yes 1 hour 150 Sq. Ft. 5* No 1 hour 150 Sq. Ft. 2 Footnote( 1) Fire protection system shall be sprinkler, water spray, carbon dioxide, or other acceptable suppression system. Container and Portable Tank Storage Office occupancies Storage prohibited except if required for maintenance, operation of building and operation of equipment Shall be kept in closed metal containers stored in a storage cabinet or in safety cans or in an inside storage room Incidental Use Incidental storage or use of flammable and combustible liquids Quantity located outside of an inside storage room or storage cabinet: 25 gallons of Class IA liquids 120 gallons of Class IB, IC, II, or III liquids 660 gallons of Class IB, IC, II, or III liquids Kept in covered containers when not in use Fire Extinguishers Portable fire extinguishment and control equipment shall be provided to meet the special hazards of operation and storage. ITM. Plants Class I liquids shall not be dispensed into containers unless the nozzle and container are electrically interconnected (grounding). Spills shall be cleaned up promptly. 7

8 Summarizing Storage Requirements Consider the following: Occupancy Class of liquids that will be present Engineering specifications such as fire wall size, fire suppression systems, tank design, etc. Maximum volume restrictions Codes and Local Bylaws Marking and labeling requirements Summarizing Storage Requirements The flash point determines if a substance falls within the scope of the standard. The flash point and boiling point together, determine how substances are stored: Container capacity and spacing Maximum amount per location The. help you determine storage limits, venting capacities, allowable sizes of containers and more... Assembly & Residential When a single class of liquid is stored, the total quantity shall not exceed: Assembly & Residential When a two or more classes of liquid are stored in the building, the total quantity shall not exceed: Assembly/Residential Class I Class II Class III Quantity (max) 30 liter 150 liter 600 liter qi + qii + qiiia < qi qii qiii = actual qty. of Class I = actual qty. of Class II = actual qty. of Class III Assembly & Residential Example calculation: Qty of Class I = 15 liters Qty of Class II = 60 liters Qty of Class III = 100 liters qi + qii + qiiia < qi qii qiii = actual qty. of Class I = actual qty. of Class II = actual qty. of Class III Storage Facilities Incidental use BCFC Subsection Cabinets BCFC Subsection , Rooms BCFC Subsection , or Storage areas BCFC Article

9 Storage Areas Storage areas BCFC Article * Where a building or part of building is designed for the storage of flammable liquids or combustible liquids, there is no limit on the total quantity of storage per fire compartment provided the building or part of building is separated from adjacent buildings or parts of buildings by a)a firewall having a fire-resistance rating of at least 4 h, or b)spatial separation in conformance with the British Columbia Building Code. When a two or more classes of liquid are stored in the building, the total quantity shall not exceed: Storage Cabinets BCFC The maximum quantity of flammable liquids and combustible liquids stored in a cabinet shall be 500 L, of which not more than 250 L shall be Class I liquids. Storage Cabinets BCFC Storage Cabinets The total quantity of flammable liquids and combustible liquids stored in cabinets in a single fire compartment shall not exceed the quantity permitted for 3 cabinets. Except, the fire compartment qty can be exceeded if: the total quantity stored in a group of cabinets is not more than the quantity permitted for 3 cabinets, and the distance between groups of cabinets is not less than 30 m. 9

10 Incidental use Incidental use BCFC Subsection Applies to industrial occupancies where the use, storage and handling of flammable liquids or combustible liquids is secondary to the principal activity Incidental use Quantity permitted to be located outside of storage rooms or storage cabinets in any one fire compartment of a building, shall not be more than: 600 L of flammable liquids and combustible liquids in closed containers, of which not more than 100 L shall be Class IA liquids, and L of Class IB, IC, II and IIIA liquids in storage tanks or portable tanks Where required for normal plant activity, quantities are permitted to exceed the above, but shall not be greater than the supply for one day of normal operation. Incidental use Handling: Areas in which flammable liquids or combustible liquids are transferred from one container or storage tank to another, or where they are used in such a way as to release potentially explosive concentrations of flammable vapours, shall be separated from possible sources of ignition by a spatial separation of not less than 6 m, or by a fire separation. Incidental use General Storage: When a single class of liquid is stored, the total quantity in a single fire compartment shall be not more than: a)2 500 L of Class IB and IC liquids, b)5 000 L of Class II liquids, or c) L of Class IIIA liquids. Incidental use General Storage: When 2 or more classes of liquid are stored in the same fire compartment, the total quantity permitted for each class of liquid shall be: Incidental use General Storage: When 2 or more classes of liquid are stored in the same individual storage area, the maximum quantity permitted in the individual storage area shall be that permitted for the liquid with the lowest limit of: a)2 500 L of Class IB and IC liquids, b)5 000 L of Class II liquids, or c) L of Class IIIA liquids 10

11 Plunger Safety Can Dispensing Safety Can NO! Used Rag Waste Cans Waste cans for the disposal of oily rags should be of metal Storage Room Kept closed Not ignite from outside sources Oxygen is limited Not allow a sustained fire if ignition occurs. The maximum quantities and densities of flammable liquids and combustible liquids are permitted to be doubled provided the storage room is protected by an automatic fire suppression system Storage Room The maximum quantities of Class I liquids in an unprotected storage room with a fire separation having a fire-resistance rating of not less than 2 h shall: not exceed those specified for unprotected storage, and comply with limits for multiple flash points. Storage Rooms BCFC Storage rooms referred to in Article shall be liquid-tight where the walls join the floor 11

12 Storage Rooms BCFC The contents of flammable liquid and combustible liquid storage rooms referred to in Article shall be arranged to provide aisle widths of not less than 1 m. Storage Rooms BCFC Dispensing of flammable liquids or combustible liquids from containers having a capacity of more than 30 L shall be by pumps or through selfclosing valves, designed in conformance with good engineering practice. (See A (1) in Appendix A Storage Rooms BCFC Where Class IA or IB liquids are dispensed within a storage room, the room shall be designed to prevent critical structural and mechanical damage from an internal explosion in conformance with good engineering practice such as that described in NFPA 68, Venting of Deflagrations. (See A (1)(d) in Appendix A.) Storage Rooms BCFC Ventilation Rooms or Enclosed Spaces 1) Where flammable liquids and combustible liquids are processed, handled, stored, dispensed or used within rooms or enclosed spaces, ventilation shall conform to the applicable requirements of this Part and the British Columbia Building Code. (See Appendix A.) Storage Rooms BCFC Ventilation Except as permitted in Sentence (2), a room or enclosed space referred to in Article shall be provided with one of the following ventilation systems: a)continuous mechanical ventilation where Class I liquids are processed, dispensed or used in a manner that releases flammable vapours into the room or enclosed space, b)either natural or continuous mechanical ventilation where i)class I liquids are stored, processed, Control of Static charge 12

13 transfer Drainage System Curb to contain credible spill. Sill and containment of possible spill Spill Control Plan view No Smoking Control ignition Sources Spill Control Drainage System: Terminates in area which does not impose fire hazard or risk Directs spill away from buildings, means of egress, fire dept. access routes,valves controlling flow of flammable liquids or fire fighting water supplies. 13

14 Ventilation of vapours heavier than air At least 1 air inlet at a point near a wall, and no higher than 300 mm from the floor Keep inlet/exhaust openings free of obstructions 12 inches 300 mm max from floor At least 1 air outlet located near the opposite wall no higher than 300 mm from the floor Plan view Ventilation vapours lighter than air At least 1 air inlet at a point near a wall, and no lower than 300 mm from the ceiling 12 inches 300 mm max from ceiling Keep inlet/exhaust openings free of obstructions At least 1 air outlet located near the opposite wall no lower than 300 mm from the ceiling Plan view Ventilation vapours heavier AND lighter than air Where dispensing of flammable liquids 12 inches 300 mm max from floor AND ceiling Duct systems: not to be used for ANY other ventilation or exhaust system. Sander 14

15 Exhaust air is not to discharge TOWARDS any unprotected opening within 7.0 meters of the discharge point roof Not less than 3 m to any building opening roof When average air velocity in the room exceeds 0.5 m/second, make-up air is required. Ventilation: 18 cubic meters/hour/square meter area (1 CFM per FT 2 ) but not less than 250 cubic meters/hour (150 CFM) Make-up air: for natural ventilation system, take air from point outside Make-up air taken from a point remote from exhaust discharge roof roof Make-up air: for mechanical ventilation system, taking air from within building thru a DAMPER opening Interlocks: where continuous ventilation is installed to maintain 25% LEL, the ventilation shall be interlocked to shut-down activity creating flammable vapours when ventilation is not active, AND sound an audible alarm in an attended area. Make-up air taken from a point remote from exhaust discharge Penetration of wall assembly Heater Lighting Light switch conduit Sill Conduit seal/plug Light switch Plan view 15

16 16

Notes. Material 1. Appropriate Flammable Liquids

Notes. Material 1. Appropriate Flammable Liquids 29 CFR 1910.106 Flammable Materials Flammable Liquids Preparation 1. Read Applicable Background information and related Company Policy Chapter. 2. Make Copies of this Lesson Plan for Personnel 3. Make

More information

Sample Written Program. For. Flammable Liquids

Sample Written Program. For. Flammable Liquids Sample Written Program For Flammable Liquids 1 Flammable Liquids. (YOUR COMPANY NAME) Purpose Proper Storage and use of flammable liquids can significantly reduce the possibility of accidental fires and

More information

FLAMMABLE AND COMBUSTIBLE LIQUIDS. n OSHA Changes

FLAMMABLE AND COMBUSTIBLE LIQUIDS. n OSHA Changes FLAMMABLE AND COMBUSTIBLE LIQUIDS OSHA Changes Introduction This module covers the two primary hazards associated with flammable and combustible liquids: explosion and fire. In order to prevent these hazards,

More information

Flammable and Combustible Liquids. Slide 1 (of 23)

Flammable and Combustible Liquids. Slide 1 (of 23) Flammable and Combustible Liquids Slide 1 (of 23) Introduction The two primary hazards associated with flammable and combustible liquids are explosion and fire Safe handling and storage of flammable liquids

More information

ADMINISTRATIVE SERVICES MANUAL

ADMINISTRATIVE SERVICES MANUAL Purpose Responsibilities Proper Storage and use of flammable liquids can significantly reduce the possibility of accidental fires and injuries. To minimize risk to life and properly, the requirements of

More information

HealthandSafetyOntario.ca. Introduction. Storage Containers. Storing Flammable Liquids

HealthandSafetyOntario.ca. Introduction. Storage Containers. Storing Flammable Liquids Flammable Liquids Storage Introduction This guideline is designed to help you store flammable liquids safely. It is based on the requirements of the Ontario Fire Code, Part 4, and of the Regulations for

More information

OSHA Office of Training and Education 1

OSHA Office of Training and Education 1 Flammable and Combustible Liquids OSHA Office of Training and Education 1 Introduction The two primary hazards associated with flammable and combustible liquids are explosion and fire Safe handling and

More information

Flammable Liquids Storage

Flammable Liquids Storage A Health and Safety Guideline for Your Workplace Flammable Liquids Storage Introduction This guideline is designed to help you store flammable liquids safely. It is based on the requirements of the Ontario

More information

Flammable Liquids 29 CFR 1910.106

Flammable Liquids 29 CFR 1910.106 Flammable Liquids 29 CFR 1910.106 OSHA s Directorate of Training and Education These materials were developed by OSHA s Directorate of Training and Education and are intended to assist employers, workers,

More information

Flammable Liquids Storage

Flammable Liquids Storage A Health and Safety Guideline for Your Workplace Flammable Liquids Storage Introduction This guideline is designed to help you store flammable liquids safely. It is based on the requirements of the Ontario

More information

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable

More information

Queen's University Environmental Health and Safety

Queen's University Environmental Health and Safety April, 2009 1 SOP-Chem-08 1.0 Introduction This document is intended as a guide to the Queen s University requirements for handling and storing flammable and combustible material in non-laboratories areas.

More information

TYPICAL FIRE SAFETY INSPECTION VIOLATIONS

TYPICAL FIRE SAFETY INSPECTION VIOLATIONS TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to

More information

FLAMMABLE AND COMBUSTIBLE LIQUIDS

FLAMMABLE AND COMBUSTIBLE LIQUIDS FLAMMABLE AND COMBUSTIBLE LIQUIDS These guidelines provide requirements for all University faculty, staff, and students using, handling, or storing flammable and combustible liquids. These requirements

More information

BP WIND ENERGY POLICIES AND PROCEDURES

BP WIND ENERGY POLICIES AND PROCEDURES BP WIND ENERGY POLICIES AND PROCEDURES Document Control Details 1.0 Purpose/Scope 1.1 This procedure provides the minimum requirements to be followed for the storage of flammable or combustible materials

More information

STORAGE AND HANDLING OF FLAMMABLE AND COMBUSTIBLE LIQUIDS

STORAGE AND HANDLING OF FLAMMABLE AND COMBUSTIBLE LIQUIDS Page 1 of 10 STORAGE AND HANDLING OF These guidelines provide requirements for all University faculty, staff, and students using, handling, or storing flammable and combustible liquids. These requirements

More information

Static Electricity. A Health and Safety Guideline for Your Workplace. What Are Some Sources of Static Electricity? What is Static Electricity?

Static Electricity. A Health and Safety Guideline for Your Workplace. What Are Some Sources of Static Electricity? What is Static Electricity? A Health and Safety Guideline for Your Workplace What is static electricity? What causes it? How is it hazardous? And, most importantly, how can it be controlled? All of these questions will be answered

More information

Model Safety Program

Model Safety Program Model Safety Program DATE: SUBJECT: Flammable and Combustible Liquids Safety Program REGULATORY STATUTE: OSHA 29 CFR 1910.106 OVERALL RESPONSIBILITY: The (YOUR COMPANY) Safety Officer is. He/she is solely

More information

Section III Hazardous Materials Management

Section III Hazardous Materials Management Section III Hazardous Materials Management This section of the Everyday Hazmat User s Training Guide covers various types of hazardous materials commonly found in the USDA Forest Service. Federal regulations

More information

General Fire Code Requirements Within Commercial Tenant Spaces

General Fire Code Requirements Within Commercial Tenant Spaces FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding

More information

Presented by: Rich Perry Marsh Risk Consulting

Presented by: Rich Perry Marsh Risk Consulting Flammable and Combustible Liquids Presented by: Rich Perry Marsh Risk Consulting What s the Big Deal? Flammable and combustible liquids are easily ignited Ignite with explosive force Burn readily and give

More information

Static Spark Ignites Flammable Liquid during Portable Tank Filling Operation

Static Spark Ignites Flammable Liquid during Portable Tank Filling Operation Static Spark Ignites Flammable Liquid during Portable Tank Filling Operation No. 2008-02-I-IA (September 2008) Key Lessons for Safe Handling and Storage of Flammables Ensure that equipment, such as fill

More information

Ethanol Vehicle and Infrastructure Codes and Standards Citations

Ethanol Vehicle and Infrastructure Codes and Standards Citations Ethanol Vehicle and Infrastructure Codes and Standards Citations This document lists codes and standards typically used for U.S. ethanol vehicle and infrastructure projects. To determine which codes and

More information

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS 527 CMR 14.00: FLAMMABLE AND COMBUSTIBLE LIQUIDS, FLAMMABLE SOLIDS OR FLAMMABLE GASES

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS 527 CMR 14.00: FLAMMABLE AND COMBUSTIBLE LIQUIDS, FLAMMABLE SOLIDS OR FLAMMABLE GASES 527 CMR 14.00: FLAMMABLE AND COMBUSTIBLE LIQUIDS, FLAMMABLE SOLIDS OR FLAMMABLE GASES Section 14.01: Scope 14.02: Definitions 14.03: Storage 14.04: Handling of Flammable Fluids 14.05: Handling of Flammable

More information

MOTOR FUEL DISPENSING SAFETY

MOTOR FUEL DISPENSING SAFETY STRATEGIC OUTCOMES PRACTICE TECHNICAL ADVISORY BULLETIN January 2010 MOTOR FUEL DISPENSING SAFETY Fire! Not an alarm anyone wants to hear, especially not when the fire is burning at a major fuel source.

More information

FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS. 1. All Floors (inspect from top floor to basement): Yes No

FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS. 1. All Floors (inspect from top floor to basement): Yes No General Inspection FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS 1. All Floors (inspect from top floor to basement): Yes are fire exits and directional signs properly illuminated? is the emergency

More information

Requirements for Hydrogen Storage and Use

Requirements for Hydrogen Storage and Use Requirements for Hydrogen Storage and Use I. INTRODUCTION Fire and Life-Safety Group (FLS) The following is a summary of the fire and building code requirements for the storage and use of hydrogen. These

More information

In accordance with NFPA 30, these containers are not to store Class I flammable liquids.

In accordance with NFPA 30, these containers are not to store Class I flammable liquids. In accordance with NFPA 30, these containers are not to store Class I flammable liquids. Zurich recommends storing these containers in dedicated liquid storage rooms, detached buildings, or in listed dispensing

More information

OREGON FIRE CODE Interpretations and Technical Advisories

OREGON FIRE CODE Interpretations and Technical Advisories OREGON FIRE CODE Interpretations and Technical Advisories A collaborative service by local and state fire professionals, along with our stakeholders and customers, to provide consistent and concise application

More information

FLAMMABLE LIQUIDS COMPLIANCE NOTE

FLAMMABLE LIQUIDS COMPLIANCE NOTE Issued by: Heather Rice Page: 1 of 7 COMPLIANCE NOTE INTRODUCTION This document provides additional guidance to support the Arrangement on Flammable Liquids (Ref No. CYC/HS/A27) CONTENTS Section Topic

More information

Spray Booth Guideline

Spray Booth Guideline Department of Development Service 135 North D Street, Perris CA. 92570 Phone: (951) 443-1029 Fax: (951) 943-3293 PURPOSE The intent of this guideline is to provide the information necessary to ensure that

More information

FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS

FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS The attached self-inspection form is intended for staff use at regular, frequent intervals. It should not take the place of two other vital measures

More information

STORE HAZARDOUS SUBSTANCES SAFELY. incompatibles gas cylinders

STORE HAZARDOUS SUBSTANCES SAFELY. incompatibles gas cylinders STORE HAZARDOUS SUBSTANCES SAFELY Suitable containers incompatibles gas cylinders Oxy-Acetylene welding flammable substances 35 36 STORE HAZARDOUS SUBSTANCES SAFELY STORE HAZARDOUS SUBSTANCES SAFELY Storing

More information

Flammable Storage in a Biotech Facility

Flammable Storage in a Biotech Facility Deputy Chief Gerard Mahoney; Chairman 100 Smith Place Cambridge, MA, 02138 (617) 349-4944 Fax: (617) 349-4905 Mailing Address: 491 Broadway Cambridge, MA 02138 Flammable Storage - Intro Date: 12/09/2009

More information

Waste Oil Collection / Storage

Waste Oil Collection / Storage ENVIRONMENTAL & REGULATORY SERVICES Storage Tank Regulation Section P. O. Box 7837 Madison, Wisconsin 53707-7837 TDD #: (608) 264-8777 http://www.commerce.state.wi.us http://www.wisconsin.gov Jim Doyle,

More information

GUIDELINE FOR SAFETY IN THE HANDLING OF FLAMMABLE LIQUIDS

GUIDELINE FOR SAFETY IN THE HANDLING OF FLAMMABLE LIQUIDS GUIDELINE FOR SAFETY IN THE HANDLING OF FLAMMABLE LIQUIDS September 2007 Replaces the July 2004 edition 1. Purpose Purpose of present Guideline is to specify conditions for the safe handling of flammable

More information

Wilkins Safety Group

Wilkins Safety Group H & S Guidance - Flammable Liquids See also: other pages INTRODUCTION Flammable liquids are liquids with a flashpoint of 55ºC or below and hence includes all liquids that are classified as flammable, highly

More information

Civil Engineering Sector Labour-Management Health and Safety Committee

Civil Engineering Sector Labour-Management Health and Safety Committee PROCEDURE FOR THE STORAGE AND HANDLING OF FUEL ON CONSTRUCTION SITES Civil Engineering Sector Labour-Management Health and Safety Committee July 2008 PROCEDURE FOR THE STORAGE AND HANDLING OF FUEL ON CONSTRUCTION

More information

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011 FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or comments regarding the

More information

Practical Guidelines for Electrical Area Classification in Combustion Turbine-Generator Power Plants

Practical Guidelines for Electrical Area Classification in Combustion Turbine-Generator Power Plants Practical Guidelines for Electrical Area Classification in Combustion Turbine-Generator Power Plants Ram K. Saini, P.E. Principal Engineer, Chuck Emma, P.E. Principal Engineer, Burns and Roe Enterprises,

More information

Site and Storage Conditions for Class 3.1 Flammable Liquids

Site and Storage Conditions for Class 3.1 Flammable Liquids Site and Storage Conditions for Class 3.1 Flammable Liquids Introduction Contents Introduction... 1 SITE AND STORAGE CONDITIONS...2 Part 1 General Flammability Conditions...2 Part 2 Conditions Relating

More information

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression

More information

CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES

CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES Review the following information pertaining to Construction Fire Safety Planning: B.C. Building Code Sections 8.1 up to and including Subsection 8.2.3 B.C.

More information

Mechanical Systems Competency 1.20

Mechanical Systems Competency 1.20 Competency 1.20 Mechanical systems personnel shall demonstrate a working level knowledge of the safety and health fundamentals of mechanical systems and/or components. 1. Supporting Knowledge and Skills

More information

February 2014 Alberta Fire Code 4.2.6.3. Page 1 of 5. Fire Safety and Hand Hygiene in Healthcare Facilities

February 2014 Alberta Fire Code 4.2.6.3. Page 1 of 5. Fire Safety and Hand Hygiene in Healthcare Facilities FIRE CODE VARIANCE February 2014 Alberta Fire Code 4.2.6.3. Page 1 of 5 ISSUE: Fire Safety and Hand Hygiene in Healthcare Facilities This Variance covers alcohol based hand hygiene products used in healthcare

More information

Dennis Fire Department Fire Prevention Mark Dellner Fire Chief

Dennis Fire Department Fire Prevention Mark Dellner Fire Chief Dennis Fire Department Fire Prevention Mark Dellner Fire Chief FIRE SAFETY INSPECTION GUIDELINES FOR COMMERCIAL PROPERTIES (MA Fire Prevention Regulations 527 CMR, MGL Chapter 148) FIRE PREVENTION CHECKLIST-

More information

Fire Prevention Plan for Commons 1655 Musketeer Drive

Fire Prevention Plan for Commons 1655 Musketeer Drive Commons for Commons 1655 Musketeer Drive Xavier University November 7, 2006 Ken Grossman Page 1 10/29/2013 Table of Contents Introduction... 3 Responsibilities... 3 Major Workplace Fire Hazards... 3 Methods

More information

SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT

SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT INTRODUCTION No matter how reliable fire protection equipment may seem, periodic maintenance is needed to ensure proper operation. Fire protection

More information

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011, Updated March 2012 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or

More information

HOT WORK PERMIT PROCEDURES

HOT WORK PERMIT PROCEDURES COLUMBIA UNIVERSITY ENVIRONMENTAL HEALTH & SAFETY HOT WORK PERMIT PROCEDURES COLUMBIA UNIVERSITY MEDICAL CENTER February 2010 1 TABLE OF CONTENTS A. PURPOSE 3 B. SCOPE 3 C. POLICIES AND PROCEDURES 3-4

More information

Standard Operating Procedure: Flammable Liquids

Standard Operating Procedure: Flammable Liquids Standard Operating Procedure: Flammable Liquids Standard operating procedures (SOP) are intended to provide you with general guidance on how to safely work with a specific class of chemical or hazard.

More information

FLAMMABLE AND COMBUSTIBLE LIQUIDS

FLAMMABLE AND COMBUSTIBLE LIQUIDS GAP.8.1.0 A Publication of Global Asset Protection Services LLC FLAMMABLE AND COMBUSTIBLE LIQUIDS INTRODUCTION National Fire Protection Association (NFPA) documents describe a level of fire protection

More information

JOINT CBA AND SIA GUIDANCE FOR THE STORAGE OF FLAMMABLE LIQUIDS IN SEALED PACKAGES IN SPECIFIED EXTERNAL STORAGE AREAS

JOINT CBA AND SIA GUIDANCE FOR THE STORAGE OF FLAMMABLE LIQUIDS IN SEALED PACKAGES IN SPECIFIED EXTERNAL STORAGE AREAS JOINT CBA AND SIA GUIDANCE FOR THE STORAGE OF FLAMMABLE LIQUIDS IN SEALED PACKAGES IN SPECIFIED EXTERNAL STORAGE AREAS 1 JOINT CBA AND SIA GUIDANCE FOR THE STORAGE OF FLAMMABLE LIQUIDS IN SEALED PACKAGES

More information

Containment Requirements

Containment Requirements Introduction: Building and fire codes are developed by associations for adoption by federal, state and local authorities having jurisdiction. The local municipalities often make amendments or changes to

More information

Code Compliance Guideline: Swimming Pool Chemicals

Code Compliance Guideline: Swimming Pool Chemicals A publication of Fairfax County, Virginia CODE COMPLIANCE GUIDELINE SWIMMING POOL CHEMICALS AND FIRE SAFETY REQUIREMENTS RELATED TO POOL OPERATIONS This publication outlines the Fire Prevention Code requirements

More information

CHAPTER 10 BOILERS, WATER HEATERS AND PRESSURE VESSELS

CHAPTER 10 BOILERS, WATER HEATERS AND PRESSURE VESSELS CHAPTER 10 BOILERS, WATER HEATERS AND PRESSURE VESSELS SECTION 1001 GENERAL 1001.1 Scope. This chapter shall govern the installation, alteration and repair of boilers, water heaters and pressure vessels.

More information

ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.252 WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600

ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.252 WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600 OSHA REGULATION: 9 CFR 90.5 WELDING, CUTTING, AND BRAZING ( HOT WORK ) A. POLICY. This procedure follows requirements set forth in 9 CFR 90.5.. This policy applies to all Hot Work operations being done

More information

FDNY C14 Certificate of Fitness Quiz

FDNY C14 Certificate of Fitness Quiz FDNY C14 Certificate of Fitness Quiz Name: Date: 1. Who issues a New York City laboratory permit? a) Department of Environmental Protection (DEP) b) Department of Environmental Conservation (DEC) c) Occupational

More information

Dip Tanks. RS 1030 (9/13) 2013 Nationwide Mutual Insurance Company Page 1 of 9 All Rights Reserved

Dip Tanks. RS 1030 (9/13) 2013 Nationwide Mutual Insurance Company Page 1 of 9 All Rights Reserved This Data Sheet discusses the fire and explosion hazards associated with dip tanks as well as several fire prevention tactics. EPA information is included as an added benefit only. The information from

More information

Building Code Clarifications - 7. Fire Resistance

Building Code Clarifications - 7. Fire Resistance Building Code Clarifications - 7. Fire Resistance 7.1 (15-12-030) Use of combustibles in Type III construction roof assemblies Code Section (15-12-030) Use of Combustibles was revised on May 17, 2000,

More information

A Code Review for Emergency Generators and Indoor Use of Portable Generators

A Code Review for Emergency Generators and Indoor Use of Portable Generators A Code Review for Emergency Generators and Indoor Use of Portable Generators By: the Fire and Life-Safety Group (FLS) Fire Code requires that emergency generators be stationary generators. Therefore, a

More information

Technical Requirements for Aboveground Storage Tanks (ASTs) Storing Class IIIB Liquids (other than used oil)

Technical Requirements for Aboveground Storage Tanks (ASTs) Storing Class IIIB Liquids (other than used oil) Technical Requirements for Aboveground Storage Tanks (ASTs) Storing Class IIIB Liquids (other than used oil) References: Comm 10 2009 EDITION / NFPA 30 2008 EDITION ITEM DESCRIPTION Comm 10 / NFPA General

More information

HOT WORK PERMIT PROGRAM TRAINING. John Braun

HOT WORK PERMIT PROGRAM TRAINING. John Braun HOT WORK PERMIT PROGRAM TRAINING John Braun 1.0 INTRODUCTION 1.2 Purpose The Hot Work Permit Program has been developed for University employees that work on or around hot work activities. This program

More information

EXPLOSIVE ATMOSPHERES - CLASSIFICATION OF HAZARDOUS AREAS (ZONING) AND SELECTION OF EQUIPMENT

EXPLOSIVE ATMOSPHERES - CLASSIFICATION OF HAZARDOUS AREAS (ZONING) AND SELECTION OF EQUIPMENT EXPLOSIVE ATMOSPHERES - CLASSIFICATION OF HAZARDOUS AREAS (ZONING) AND SELECTION OF EQUIPMENT OVERVIEW ASSESSING THE RISK RELATIONSHIP BETWEEN FIRES AND EXPLOSIONS CLASSIFYING HAZARDOUS AREAS INTO ZONES

More information

Overview of Hotel Fire Safety Requirements

Overview of Hotel Fire Safety Requirements Overview of Hotel Fire Safety Requirements in the Fire Code Susan Clarke, P.Eng. Office of the Fire Marshal - January 10, 2012 1 Agenda Regulation History - Hotels Fire Code Overview (Parts 1 to 8) Defined

More information

9/15/2011. Presented by: Jason Reason, CIH, CSP, CHMM Senior Industrial Hygienist Indiana Occupational Safety and Health Administration

9/15/2011. Presented by: Jason Reason, CIH, CSP, CHMM Senior Industrial Hygienist Indiana Occupational Safety and Health Administration OSHA Combustible Dust Inspections Presented by: Jason Reason, CIH, CSP, CHMM Senior Industrial Hygienist Indiana Occupational Safety and Health Administration Overview Background Information OSHA Combustible

More information

Safe Operating Procedure

Safe Operating Procedure Safe Operating Procedure HAZARDS OF FLAMMABLE GASES, LIQUIDS & AEROSOLS & RISK MINIMIZATION (For assistance, please contact EHS at (402) 472-4925, or visit our web site at http://ehs.unl.edu/) (1/13) Background

More information

The following definitions apply with regard to requirements specified in this document:

The following definitions apply with regard to requirements specified in this document: GUIDELINES FOR INSTALLATION OF TEMPORARY AND PERMANENT ABOVEGROUND DIESEL FUEL TANKS FOR EMERGENCY AND STANDBY POWER SYSTEMS LOCATED OUTSIDE OF BUILDINGS For Use by Unidocs Member Agencies or where approved

More information

Fire Alarm System Standpipes Sprinkler Systems Fire Drills Commercial Cooking Hood and more

Fire Alarm System Standpipes Sprinkler Systems Fire Drills Commercial Cooking Hood and more FIRE PROTECTION SYSTEMS Fire protection systems, measures and equipment are all related to the safety of the occupants and the protection of the property. As part of a building design and its intended

More information

Flammable and Combustible Storage Checklist

Flammable and Combustible Storage Checklist Flammable and Combustible Storage Checklist Occupational Safety and Health Bureau Montana Department of Labor and Industry Prepared for Montana Employers by the Occupational Safety & Health Bureau Department

More information

Medicine Hat Fire Department. Special Event Requirements. medicinehat.ca/fire. August 2012

Medicine Hat Fire Department. Special Event Requirements. medicinehat.ca/fire. August 2012 Medicine Hat Fire Department Special Event Requirements August 202 medicinehat.ca/fire The following is a standard guide for event organizers to ensure occupant safety and compliance with the Alberta Fire

More information

The following definitions apply with regard to requirements specified in this document:

The following definitions apply with regard to requirements specified in this document: GUIDELINES FOR INSTALLATION OF TEMPORARY AND PERMANENT ABOVEGROUND DIESEL FUEL TANKS FOR EMERGENCY AND STANDBY POWER SYSTEMS LOCATED OUTSIDE OF BUILDINGS For Use by Unidocs Member Agencies or where approved

More information

Standard Operating Procedure

Standard Operating Procedure Standard Operating Procedure FLAMMABLE LIQUIDS This standard operating procedure (SOP) is intended to provide general guidance on how to safely work with flammable liquids. This SOP is generic in nature

More information

FUELING AND FUEL STORAGE

FUELING AND FUEL STORAGE FUELING AND FUEL STORAGE BENCHMARK Implement spill prevention measures whenever fuel is handled or stored. Report, minimize, contain and clean up spills that do occur. FUELING BMPS Spills of diesel, oil,

More information

Name Of Occupancy Date. Yes No Describe

Name Of Occupancy Date. Yes No Describe FIRE PREVENTION INSPECTION CHECKLIST For Class A Occupancy (For Assembly Buildings, Bars, Restaurants, Gyms, Churches, Arenas, Theatres or wherever people gather) Name Of Occupancy Date Physical Address

More information

THE FACTORIES A D OTHER PLACES OF WORK ACT (Cap 514)

THE FACTORIES A D OTHER PLACES OF WORK ACT (Cap 514) THE FACTORIES A D OTHER PLACES OF WORK ACT (Cap 514) I EXERCISE of the powers conferred by section 41 2(k) of the Factories and other places of Work Act, the Minister for Labour and Human Resource Development

More information

FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST

FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST Date of Inspection: Conducted by: Location: Reviewed by: Date of Review: Comments or additional corrective action taken as a result

More information

Installation Instructions for Alarm Module Kit A043F059

Installation Instructions for Alarm Module Kit A043F059 Instruction Sheet 07-2013 Installation Instructions for Alarm Module Kit A043F059 1 Introduction The information contained within is based on information available at the time of going to print. In line

More information

Standards for Material Handling, Storage, and Disposal

Standards for Material Handling, Storage, and Disposal Section 11 Standards for Material Handling, Storage, and Disposal This section sets forth the requirements for handling, storage, and disposal of material. It specifically addresses the requirements for

More information

presents Cooking With Fire Fixed Fire Suppression & Exhaust Systems for Cooking Environments Monday, 17 June, 13

presents Cooking With Fire Fixed Fire Suppression & Exhaust Systems for Cooking Environments Monday, 17 June, 13 presents Cooking With Fire Fixed Fire Suppression & Exhaust Systems for Cooking Environments Who is the AFSA? Safe and Secure Alberta Fire Safety Association Fire industry members working together to improve

More information

Vehicle Maintenance Facilities Requirements for CNG and LNG Vehicles

Vehicle Maintenance Facilities Requirements for CNG and LNG Vehicles Vehicle Maintenance Facilities Requirements for CNG and LNG Vehicles Presented by: Leo Thomason Executive Director Natural Gas Vehicle Institute (NGVi) at NFPA Conference and Expo, June 11, 2014 Leo Thomason

More information

Outline. Background. NFPA 820 Applicability to Wastewater Treatment Facilities. Hazardous Area Classifications. Treatment Plant Area Classifications

Outline. Background. NFPA 820 Applicability to Wastewater Treatment Facilities. Hazardous Area Classifications. Treatment Plant Area Classifications Outline Background NFPA 820 Applicability to Wastewater Treatment Facilities Hazardous Area Classifications Treatment Plant Area Classifications Locations of Concern Background NFPA 820 Standard for fire

More information

We hope these Frequently Asked Questions will be of use both to municipal officials and fire inspectors.

We hope these Frequently Asked Questions will be of use both to municipal officials and fire inspectors. September 14, 2012 Dear AMM Member: Please see the attached Fire Code Frequently Asked Questions. This document was compiled by the Office of the Fire Commissioner at the AMM s request to help clarify

More information

Automatic fire-extinguishing systems for commercial cooking

Automatic fire-extinguishing systems for commercial cooking Automatic fire-extinguishing systems for commercial cooking Leading Items First Ignited in Eating and Drinking Establishment Structure Fires, 2000-2004 Annual Averages Cooking materials, incl. food and

More information

Combustible Dust Ensuring Safety and Compliance. Brian Edwards, PE Conversion Technology Inc. ENVIRONMENTAL & SAFETY CONSULTING ENGINEERS

Combustible Dust Ensuring Safety and Compliance. Brian Edwards, PE Conversion Technology Inc. ENVIRONMENTAL & SAFETY CONSULTING ENGINEERS Combustible Dust Ensuring Safety and Compliance Prepared for: REGION IV VPPPA Presented by: Brian Edwards, PE Conversion Technology Inc. ENVIRONMENTAL & SAFETY CONSULTING ENGINEERS 1 Scope of Discussion

More information

Material Safety Data Sheet

Material Safety Data Sheet Date of Issue: 26/5/2009 MSDS No.: Q54-1300B Material Safety Data Sheet 1. PRODUCT AND COMPANY IDENTIFICATION Product Name : Daily Maintenance Kit(Wipe Cleaning) Product Code : IP6-108 -Application model

More information

FIRE PREVENTION PLAN

FIRE PREVENTION PLAN FIRE PREVENTION PLAN 1 FIRE PREVENTION PLAN OSHA s Fire Prevention Plan regulation, found at 29 CFR 1910.38(b) and 29 CFR 1926.24, requires Northern Clearing, Inc. to have a written fire prevention plan

More information

GUIDANCE FOR DEVELOPMENT OF SPILL AND SLUG PREVENTION CONTROL PLANS AND FACILITIES FOR THE CITY OF ATTLEBORO SEWER USERS

GUIDANCE FOR DEVELOPMENT OF SPILL AND SLUG PREVENTION CONTROL PLANS AND FACILITIES FOR THE CITY OF ATTLEBORO SEWER USERS Company Name: Address: The City of Attleboro s Rules and Regulations for the use of Wastewater Facilities require each user to provide protection from accidental discharge of prohibited materials and substances

More information

FIRE SAFETY ONLINE TRAINING

FIRE SAFETY ONLINE TRAINING INTRODUCTION This Fire Safety Training module is designed to teach you preventive measures that will eliminate or minimize causes of fire or fire hazards in the workplace, and to teach you proper emergency

More information

PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS

PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS January 1997 PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS 1.0 PERMIT 1.1 After receipt of a Building Permit from the City of San Jose Building Department, submit

More information

Warehouse Checklist. Warehouse Construction

Warehouse Checklist. Warehouse Construction PAGE 1 Warehouse Checklist Recent NFPA statistics estimate that in 1998 approximately 36,000 fires occurred in structures used for storage, accounting for $687mm of damage (over 10% of total fire damage

More information

Winnipeg Fire Department Fire Prevention Branch

Winnipeg Fire Department Fire Prevention Branch Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of

More information

TCC Fire Regulations Exhibits & Displays in Public Buildings

TCC Fire Regulations Exhibits & Displays in Public Buildings TCC Fire Regulations Exhibits & Displays in Public Buildings TCC Fire Regulations The purpose of these requirements is to maintain an acceptable level of fire safety within The Toronto Congress Centre

More information

Electrical Classification

Electrical Classification Electrical Classification Using NFPA 70 and NFPA 499 to Classify Hazardous Locations Electrical classifications are established in accordance with the National Electrical Code, NFPA 70, also referred to

More information

An inventory of hazardous materials used in your workplace will prove useful.

An inventory of hazardous materials used in your workplace will prove useful. Introduction Fire Protection is an organized approach designed to prevent fires. In the event of a fire, a fire protection program will help prevent or minimize personal injuries, losses, and harm to the

More information

PROCEDURES PREVENTION OF ACCIDENTAL IGNITION

PROCEDURES PREVENTION OF ACCIDENTAL IGNITION Page No: 1 of 7 6.0 PURPOSE (192.751) All possible precautions shall be exercised to prevent the accidental escape and ignition of gas. Whenever possible, potential sources of ignition should be eliminated

More information

ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS

ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS In this document are the fire safety equipment maintenance requirements that are found in Division B of the Alberta Fire Code (AFC 2006) for

More information

Fire Prevention Plan for Flynn Hall 1648 Musketeer Drive

Fire Prevention Plan for Flynn Hall 1648 Musketeer Drive Audit and Risk Management and Xavier Police Fire Prevention Plan for Flynn Hall 1648 Musketeer Drive Xavier University October 12, 2006 Ken Grossman Page 1 10/29/2013 Table of Contents Fire Prevention

More information

A. Fire Protection Plan. B. Access and Parking

A. Fire Protection Plan. B. Access and Parking Standards for Construction Site Fire Safety For Use by Unidocs Member Agencies or where approved by your Local Jurisdiction Authority Cited: California Fire Code (CFC) These standards are intended to prescribe

More information

c. As mandated by law, facilities must obtain and maintain valid zoning permits as well as permits for intended use.

c. As mandated by law, facilities must obtain and maintain valid zoning permits as well as permits for intended use. Walmart Standards for Suppliers Section 7. Health and Safety 7. Health and Safety Suppliers must provide workers with a safe and healthy work environment. Suppliers must take proactive measures to prevent

More information