Improved Governor Response at the Dinorwig Power Station
|
|
|
- Bernard Malone
- 10 years ago
- Views:
Transcription
1 2013 American Governor Company / First Hydro Company Improved Governor Response at the Dinorwig Power Station Toni Jones, BEng MSc MIET CEng GDF Suez / Mitsui FHC Dinorwig Wales, UK Greg Yohe, EIT CEng American Governor Company Ivyland, Pennsylvania USA Dinorwig Power Station, located in North Wales, UK is one of the largest Pumped Storage facilities in Europe and has the capacity to generate electricity with six (6) 300MW pump generator units. These units make a significant contribution to ensuring the day-to-day stability of the UK, which relies on the Dinorwig Powerhouse to deliver rapid, consistent response. Upgrading the digital governor controls on Unit #1 resulted in reliable, accurate and faster response to a range of frequency excursions. This paper provides an insight to this achievement, which has re-enforced Dinorwig as one of the leading Pumped Storage plants in the World. A. Introduction... 2 B. Why Upgrade The Governor?... 2 C. Specifics of the Dinorwig Governors... 3 D. Solutions to the Issues Facing First Hydro Company... 5 E. Effects and Results of the New Governor Software... 8
2 A. Introduction The First Hydro Company operates a large pumped storage hydroelectric power station located in Dinorwig, North Wales, UK. Six 330MW (300MW declared capacity) pump-turbines operate synchronous generators, that provide power to the UK National Grid. Commissioned in the early 1980s, this power station can generate up to 1320MW of electricity in under 12 seconds while running in condense mode, or 1728MW from standstill in just 90 seconds. Water flows from the upper reservoir downhill through a single tunnel which then splits into six penstocks, and operates at an average head of 557 meters. At full water storage capacity, the plant can generate over 10GWhr of energy. Dinorwig Power Station is one of the fastest responding power plants in the World, and in order to maintain this status, a reliable and accurately responsive Governor is essential. The UK National Grid is an islanded system with and the UK power demand typically varies between 30 to 60 GW at any moment. The UK grid operates at a nominal frequency of 50Hz and is a dynamic system, with the operational range of frequency being between 49.80Hz and 50.20Hz. This in turn requires fast, real-time frequency control and reserve services, which is the primary function of the Dinorwig hydro power plant. The Dinorwig plant is considered a key feature of the UK National Grid and is expected to operate reliably with an extremely high level of availability. B. Why Upgrade The Governor? During the original build of the station, an analogue Governor was installed and commissioned. This was upgraded in the mid-1990s by its natural successor, a PLC based digital solution, specifically designed to control a pumped storage hydroelectric power plant. Over the last 30 years, both of these systems have been reliable and have met the standards required to make Dinorwig unique as the expected primary frequency regulation power plant in the UK. The industrial control systems at Dinorwig have recently been standardised using Rockwell Automation products. Continuous updating of the existing installed systems has resulted in a strong, reliable integrated system at Dinorwig that seamlessly integrates with the SCADA systems. However, the Governor Control System was isolated and vulnerable, facing hardware obsolescence issues, reduced support, and difficult communications with the rest of plant. The programming software was only available on the DOS operating system, and the hardware was on average 16 years old. In addition, the Speed Monitoring system that resided in the same cabinets as the Governor controller was a hardwired analogue/digital relay system that had been in use since the station was originally commissioned in the early 1980 s. This system faced similar obsolescence issues as the Governor. The obvious solution would be to replace the Governor Controller and the Speed Monitoring control system with the Rockwell PLC, since the rest of the unit had already been upgraded with this PLC platform. The main objective was to produce software that was functionally identical to Page 2
3 the original governor. However, with this upgrade, an opportunity to remedy issues in the existing Governor and a potential to make improvements with the new Governor and its related systems presented itself. Following a thorough competitive tendering process, American Governor Company (AGC) was selected to deliver the Governor and Speed Monitoring Control System Upgrade. It must be noted that this upgrade does not include any hydraulic or mechanical aspects of the Governor, just the electronic control system. C. Specifics of the Dinorwig Governors The governor at Dinorwig is a Kvaerner / Boving system (Figure 1) consisting of a Pilot Actuator now driven by the upgraded PLC system, which controls the position of the main distribution valve, via the balancing lever. The distribution valve controls two servomotors in parallel that drive the regulating ring and the Guide Vanes (Wicket Gates). This pilot stage system hydraulically operates at just under 40 Bar. The technical specification for the project was based on providing a new digital governor as good as or better than the existing governor. However, it also presented a number of challenges that many of which were more challenging compared to the usual grid conditions in the US: I. System frequency target is 50.00Hz, and expected frequency excursions are 10X s greater than usual disturbances found on the US grid. II. Time to synchronise and generate power from Standstill to be as good as or better than existing. III. Time to generate power from Spin Generate (Condense mode) to be as good as or better than existing. IV. Option to operate the unit in Power- Control (dead-band mode) or Frequency Control. V. Unit to be capable of meeting UK Grid Code requirements (and therefore contracted positions) with respect to Primary and Secondary Response. This translates to achieving declared power output within a defined time. VI. Respond to Low Frequency events, by achieving maximum power output in 10 seconds. VII. Continuous Frequency Response mode VIII. at various Droop. Use of minimum and maximum Power Output limits Figure 1 Kvarerner/Boving Page 3
4 IX. Dynamic Pumping Control where guide vanes are driven to a set-point determined by System Frequency and Water Column Head. Another considerable challenge at Dinorwig was the limited time to commission the system to have it available for commercial use. Testing control functionality during a commissioning is both time-consuming and high risk. It was widely accepted that a time period would be allocated for on-line commissioning activities, however; the commercial impact of an extended or difficult commissioning period could cost in upwards of tens of thousands of s (pounds), per day. To mitigate the potentially costly commissioning period, a laboratory Simulator and unit Model based on unit site conditions has offered clear advantages. Critical plant operations could be tested offline with no risk to the plant; faults could be detected and remedied at an early stage, and online commissioning time would be significantly reduced. This led to a Governor Model and Simulator being developed by a 3 rd party in Wales, with the intention to pre-commission the Governor Control System before it was installed in the plant. A Plant Model can be presented in many formats. The type best suited to this type of generation scheme is the Hardware-in-the-Loop or HIL Simulator and Model. This type of Model allows for external hardware components to interact with the Model, and to perform their duties and control, as if they were connected to the real plant. This is particularly well-suited to PLC based systems. The function of the hardware-in-the-loop (HIL) Simulator is to act as a substitute for a single Unit of the real Plant and its primary application is to replace the Plant during commissioning of new Governor hardware and software. Ideally, from the point of view of the Governor, the Simulator will appear indistinguishable from the real Plant by: I. Accepting the same control signals from the Governor PLC as the real Plant; II. Sending the same measurement signals to the Governor PLC as the real Plant; III. Communicating the same logic signals to and from the Governor as the real Sequencer; IV. Producing simulated responses which reproduce the steady-state and dynamic characteristics of a single Motor/Generator and turbine in different modes of operation. In order to achieve a true representation of the Dinorwig Plant responses, a number of key characteristics were modelled: I. Simplified unit sequence and controls II. The Guide Vane model III. Hydraulic characteristics including Water Start time, water column oscillations and water hydrostatic pressure. IV. National Grid characteristics including load and stiffness. V. Auxiliary plant such as Auto-synchroniser, VFSE, Blowdown, Dynamic Braking. The resulting Model was implemented on dspace hardware controlled by Matlab/Simulink modelling. A suitable user interface was provided to allow online monitoring, parameter adjustment and test initiation. Further trends and graphs were also made available as well as a feature to export test results into suitable Excel format for further analysis. The Model was compared against true plant responses and it was tuned to provide a typical response under various conditions and power contracts such as high/low water head, Low Frequency on the national grid, spinning reserve, pumping, and run-up to synchronous speed. Page 4
5 Figure 2 HIL HMI user interface. D. Solutions to the Issues Facing First Hydro Company A. The new governor code was specified to be written so as to emulate the existing governor code, with the flexibility to make improvements. Some of the major challenges encountered during the writing of the new governor software were due to the new software having to abide by the following: i). The operational controls of the unit had to be seamless for the operators, whereas the HMI screens had to operate and function exactly like the original governor software. This was a rather difficult procedure due to the fact that improvements to the unit were requested but the operational interfaces could not change. This was a high priority that the HMI screens and control room hardware interfaces remain intact so that the operators did not have to learn a new system. As referenced before, Dinorwig plays a critical role in supporting the UK grid and not having to re-train the operators in learning new screen functionality greatly reduced this potential risk for error. During the commissioning stage of the project, despite several control room distractions such as phones ringing, alarms and requests for permits, etc, the operator continued to operate the new governor and navigate the HMI screens, without delay or difficulty. This was important and proved that the operator was able to take control of the unit in the same manner as before the upgrade. This resulted in the operators gaining trust and familiarity with the new system from the outset. ii). It was desirable not to have a separate Governor PLC, but to make it a subroutine of the existing main unit control PLC i.e. the Governor PLC rack was simply remote I/O to the main Sequence PLC. Why is this unusual? Typically, due to the stringent requirements demanded by the governor, the core governor PLC code (unless dictated by the project requirements, minor Page 5
6 auxiliary equipment may also be coded within it) is usually done by a standalone PLC processor, with its own direct, hard-wired I/O signals that may or may not be interfaced with another PLC that controls most if not all of the units auxiliary equipment. If the governor is to perform its duty of controlling the unit in response to grid disturbances, then the speed of the PLC processor and accuracy of the speed sensing systems must have deterministic scan times and fast I/O update rates in order to abide by speed regulations set forth by the industry. To verify and prove that the new governor PLC code would not be hampered by integrating it into the existing code (which controlled all of the units auxiliary s and sequencing); extensive tests were performed to prove that the system architecture was robust and that the governor s performance was time stamped as if the governor code was operating in a standalone PLC. The system architecture was developed using the Allen-Bradley Contrologix PLC platform. The governor I/O was mounted in a remote rack that communicated over an Allen-Bradley ControlNet communications backbone that offered consistent and deterministic update rates of 5ms for the entire governor I/O. The remote governor I/O chassis consisted of critical hard wired signals like Generator speed, Grid or Bus speed, Unit Megawatts, Generator Current, actual Guide Vane position and the Guide Vane commanded position just to name a few. Not only was care taken to make sure that the I/O was updated appropriately, but that the core governor program was tasked at specific intervals as to not to debilitate its performance. iii). With specific requirements demanded of the Dinorwig power station, these unique system functions needed to be integrated into American Governor s core standard governor software. Droop: Typically droop is set at 5% in the United States; however, at Dinorwig there is a mandatory requirement of 4% droop (with an optional droop setting below this) based on system frequency of 50Hz. This is predominantly due to greater frequency excursions in the UK than in the US. It is not uncommon that the frequency range fluctuates from 50.2 Hz to 48.8 Hz in the course of hours. The UK is basically an Islanded grid, which is why the Dinorwig Pump Storage Plant is so very critical to the stability of the UK grid. Part Load Response (PLR): This is a mode in which the unit is set to respond to frequency at an optional droop setting producing a greater range of output. If the unit is set in PLR mode, the governor will respond to the grid frequencies normally, but if the grid frequency falls outside of operational limits the unit will achieve maximum Megawatt rating in less than 10 seconds. With this rapid loading of a unit, the frequency quickly stabilizes and or recovers within a short period of time. The demands of the Dinorwig plant are critical and this is why the modeling tests were important to perform. Manual Mode: If a fault in the system were to occur, the unit will be placed in Manual mode in which the guide vanes will be directly controlled by open/close direct-acting hydraulic solenoid valves that are energized by the operator through an open/close selector switch located at the main room control panel. The governor PLC is no longer in control of the guide vanes at this point. Once in Manual mode the governor will follow the guide vane position and once the fault is cleared the unit can be placed back in auto Page 6
7 control and the governor will perform a bumpless transfer from the current manual guide vane position into an equivalent MW setpoint with droop. B. After the software was developed, testing was implemented by using the FHC unit modeling software. This sophisticated software models the complete water-hydraulics, mechanical and electrical characteristics of a unit. A functional description was written by American Governor to First Hydro Company, in essence to prove that the concepts of how the Dinorwig Power plant operates with its unique functionalities were fully understood. With the approval of the functional description, project detail engineering was started. Many drawings were modified to show the demolition of the existing governor equipment and the installation of the new equipment. At the same time, the governor PLC programming was started. After completion of the preliminary governor software, extensive testing was performed. This was probably the most critical path to prove the governor software functionality and robustness. The modeling software in conjunction with the PLC hardware was utilized to test the governor software in which many tests were performed. Thanks to ever evolving technology, the interfacing between the United States and Wales was completed remotely via a secure VPN connection. This allowed American Governor to connect to the test governor PLC and run simulated events with the modeling software. This greatly reduced the costs of travel and engineering time. With the five hour time difference, First Hydro would run simulated tests, evaluate the tests and then forward the results to American Governor before they arrived for work. Any changes that were required were completed over the VPN network. After two weeks of remote testing support, the final factory acceptance test was conducted at the Dinorwig power plant with an American Governor field engineer on site. The 124 page final acceptance test was completed with results documented and signed. The testing incorporated the following functionalities with each test performed (when applicable) at a simulated range of High, Medium and Low Net Head levels: I. Human Machine Interface Testing (HMI) II. Normal Starts / Stops III. PID tuning IV. Pump Starts / Stops V. Spin Gen Mode (Spinning Reserve or Condensing mode) VI. Spin Pump Mode VII. Black Start VIII. Part Load Reserve Mode (PLR) IX. Megawatt Control with frequency control X. Droop testing in Megawatt control XI. Megawatt setpoint changes to verify the advanced feed-forward logic XII. Load Rejections XIII. Generator Current Limiting Logic XIV. Governor Alarms, Trips and Faults XV. Manual Mode XVI. Speed Monitoring Logic XVII. Extensive National Grid Tests. Page 7
8 These tests carried out with the new American Governor / Rockwell Governor on the Model proved to be invaluable. A two week testing program with well over 200 start-ups, pumping runs, frequency response, droop tests, fault/negative tests and many more operations pre-tested resulted in a system that was pre-commissioned and ready to be installed and deployed at the actual Dinorwig plant. E. Effects and Results of the New Governor Software Preliminary software testing was completed using the FHC modeling to prove that the new software abided by the stringent National Grid requirements. Improvements were made in the software to further increase the functionality and response of the governor. For example: a Megawatt feed-forward routine was developed to very accurately achieve the desired Megawatt setpoint with little or no overshoot or undershoot while in the Power Control Mode. Power Control Mode is a mode in which the governor regulates Generator Megawatts based on a Megawatt Setpoint while still drooping according to grid frequency deviations. Along with the updated governor PLC, new and less complicated speed sensing was incorporated. An existing compound voltage and current transformer configuration was originally utilized to sense the generator and bus voltage along with the current of the generator. This configuration was very complicated due to the wiring between the transformers. With the upgrade, all of the interconnecting wiring of the existing circuit was removed and replaced by separating each circuit individually and re-wiring them to new VT sensing modules supplied by American Governor. In addition, the generator VT and CT signals were wired to a new power transducer. This simplified the speed sensing circuit, plus with the direct VT sensing, standard PLC cards could be utilized without compromising the sensitivity and accuracy of the speed signals. Upgrading the speed sensing also eliminated the existing speed monitoring system. This had been a very complicated wiring design, which utilized 3 separate proximity probes that provided pulses by sensing a toothed disk. That speed monitoring system had been used to sense the speed of the generator and energize outputs at pre-programmed speed setpoints (speed switches). All of the relays and control boards of the existing speed monitoring system were replaced; by utilizing the same American Governor Speed sensing modules and adding a PLC output and input card we were able to recreate the speed monitoring system with less hardware, wiring and software. The proximity probes were re-used but were now directly wired into a new PLC input card. A. Effects of Megawatt Feedforward With the improved Megawatt feed-forward PLC code, overshoot and undershoot upon any MW setpoint change was greatly reduced. The phenomenon that occurs from the transients of the water column with rapid movement of the guide vanes can cause a governor to overreact. In the new governor, the advanced algorithm prevents the governor from reacting to these transients, which results in little or no megawatt swings around the new setpoint. As depicted below in Figure 3 of an actual plant data trend, the setpoint was changed from 150 megawatts to 300 megawatts. The guide vanes are ramped at a constant rate until 300 Page 8
9 megawatts was achieved. Notice in the graph that the megawatts reached this new setpoint and the governor maintained the 300 megawatt generator load without any oscillations brought on by the change in the head level and the water-hydraulic transients associated with the physical movement of the guide vanes. In this example the Net Head started out at meters. After the new Megawatt setpoint was achieved, the Net Head descended to meters before recovering to near its original value. With the fast movement of the guide vanes, the head level varied by meters or 36 feet of head and the megawatt feedback signal had a lag of approximately 1.1 seconds associated with it. The guide vanes were still in control via the PID, but the guide vanes were not overcompensating for the extreme head deviation or the lag in the megawatt signal. Especially in the case of rapid movements of the guide vanes, a typical governor will try to compensate for these deviations while in the Megawatt control mode, which causes oscillations in the guide vanes. The 150MW increase in load took approximately 12 seconds with amazing stability and predictability. Effects of Improved Frequency Response At the start of the actual trend data below, the left side, the start time is 09:55 AM: I. Units 2, 3, and 5 are shutdown and Unit 4 is in Spin Generate (Condense mode). II. Unit 1 and 6 are in Frequency control mode, with minimum Power Output set to 150MW, Setpoint Power at 150MW, Droop at 1% and maximum Power Setpoint at 320MW. III. Unit 1 has the new Governor Control System, all other units are on the original Governor. IV. As the frequency varies from the start of the chart to B, Units 1 and 6 respond to Frequency, and the difference in response between Unit 1 and 6 can be clearly seen at A and F, where the Unit is responding quicker and accurately to frequency variations. V. At B, the System Frequency drops below 49.80Hz, and Units 1 and 6 react without causing significant disturbance to the grid (i.e. oscillations in power). Key: Figure 3 White = Net Head Green = Actual Guide Vane Position Purple = MW Setpoint Yellow = Actual MW Page 9
10 VI. VII. VIII. At C, both units 1 and 6 have achieved response correctly, and deliberately overshoot the target, but where unit 6 remains at a level above the setpoint, unit 1 recovers to 320MW in under 30 seconds. Then a minute later unit 4 is set to 300MW and the hydraulic disturbance can be observed on units 1 and 6, and the recovery is good without any further grid disturbance. As units 1 and 6 are brought back to lower loads, frequency control is resumed, with little undershoot from Unit 1. Notice that in Section D, Unit 1 recovers to the setpoint of 150 MW s. In section E, Unit 6 goes to 150 MW s but bounces up to approximately 160 MW s and then recovers to 150 MW s in over 2 minutes. C Key: Figure 4 Unit 1 Unit 4 Unit 6 System Frequency D F A E B Figure 4 clearly demonstrates that the new governor is fully capable of responding to the stringent requirements of the National Grid. While maintaining the functionality of the original governor, the new governor has improved the response in frequency control, plus greatly reduced the over/undershooting of the targeted power setpoints without causing stability issues or excessive disturbance to the transmission system. In Conclusion With the successful upgrade of Unit 1 Governor at the Dinorwig plant, First Hydro Company, along with American Governor Company, will in full faith move forward to integrate the new governor system on the remaining five units. The continuation of these governor upgrades will re-enforce Dinorwig Power Stations position as one of the most innovative and fastest responding Pumped Storage hydro power stations in the World. Page 10
Alain Nifenecker - General Electric Manager Controls Engineering
GE Energy Benefits of Integrating a Single Plant-Wide Control System Into a Standard Plant Design Philosophy Authors: Luis Cerrada Duque - Empresarios Agrupados Director of I&C Department Charles Weidner
Emulated Digital Control System Validation in Nuclear Power Plant Training Simulators
Digital Control System Validation in Nuclear Power Training s Gregory W. Silvaggio Westinghouse Electric Company LLC [email protected] Keywords: Validation, nuclear, digital control systems Abstract
TURBOtech srl. SED-635 Digital Excitation System. Industrial Electronics Sector FEATURES
SED-635 Digital Excitation System SED-635 is a complete excitation system capable of adapting to control synchronous generators of any size. The integration of the TOUCH SCREEN operator interface and a
Introduction. Chapter 1. 1.1 The Motivation
Chapter 1 Introduction 1.1 The Motivation Hydroelectric power plants, like real systems, have nonlinear behaviour. In order to design turbine controllers, it was normal practice in the past, when computer
Basics electronic speed Governor
Basics electronic speed Governor 1 MAN B&W Diesel Aktiengesellschaft, Augsburg Why do we need Governors? Power sources must be controlled to be converted to useful work. Uncontrolled prime movers, not
ABB PSPS Erich Steinmann; Generator control-2013
ABB PSPS Erich Steinmann; Generator control-2013 GENERATOR CONTROL THE MODULAR SOLUTION FOR GENERATORS To make sure that power is efficiently converted into electric energy, it is necessary to supervise
SCADA. The Heart of an Energy Management System. Presented by: Doug Van Slyke SCADA Specialist
SCADA The Heart of an Energy Management System Presented by: Doug Van Slyke SCADA Specialist What is SCADA/EMS? SCADA: Supervisory Control and Data Acquisition Retrieves data and alarms from remote sites
General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System
General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System Direction Planification des actifs et expertise de transport February 2011 TABLE OF CONTENTS 1. CONDUCTING
CHAPTER 1 INTRODUCTION
CHAPTER 1 INTRODUCTION Power systems form the largest man made complex system. It basically consists of generating sources, transmission network and distribution centers. Secure and economic operation
Paralleling Switchgear
Paralleling Switchgear By Maurice D Mello, P.Eng. Systems Engineer, GE Consumer & Industrial, Canada What is Paralleling? Paralleling is the operation in which multiple power sources, usually two or more
Kevin Kochirka, ABB Turbine Automation, June 29, 2016. Flexible turbine control retrofits Webinar
Kevin Kochirka, ABB Turbine Automation, June 29, 2016 Flexible turbine control retrofits Webinar Welcome Speaker introduction Kevin Kochirka Sr. Applications Engineer with ABB Inc. [email protected]
Safety Requirements Specification Guideline
Safety Requirements Specification Comments on this report are gratefully received by Johan Hedberg at SP Swedish National Testing and Research Institute mailto:[email protected] -1- Summary Safety Requirement
FULL ELECTRICAL LNG PLANTS: HIGHEST AVAILABILITY AND ENERGY EFFICIENCY THROUGH OVERALL SYSTEM DESIGN
FULL ELECTRICAL LN PLANTS: HIHEST AVAILABILITY AND ENERY EFFICIENCY THROUH OVERALL SYSTEM DESIN Dr. Edwin Lerch Siemens A Infrastructure and Cities Sector, IC S SE PTI, ermany Phone: 49-9131-7-34052 Fax:
Monitoring & Control of Small-scale Renewable Energy Sources
Small Scale Renewable Energy Sources and Energy Saving: 6-17 th July 2009 Monitoring & Control of Small-scale Renewable Energy Sources Dr G A Taylor Brunel Institute of Power Systems Brunel University,
1115 4G SERIES GOVERNOR. 4-20 ma ANALOGUE DIGITAL SPEED SETTING
1115 4G SERIES GOVERNOR with 4-20 ma ANALOGUE & DIGITAL SPEED SETTING PO Box 28, 9300AA Roden, The Netherlands Tel: +31 505019888 Fax: +31 505013618 E-mail: [email protected] 1115 4G
Wide Area Monitoring Current Continental Europe TSOs Applications Overview
Wide Area Monitoring Current Continental Europe TSOs Applications Overview Version 5 System Protection & Dynamics Working Group 20th September 2015 1. Content 1. Content... 2 2. Introduction... 3 3. Main
ADVANCED CONTROL TECHNIQUE OF CENTRIFUGAL COMPRESSOR FOR COMPLEX GAS COMPRESSION PROCESSES
ADVANCED CONTROL TECHNIQUE OF CENTRIFUGAL COMPRESSOR FOR COMPLEX GAS COMPRESSION PROCESSES by Kazuhiro Takeda Research Manager, Research and Development Center and Kengo Hirano Instrument and Control Engineer,
Turbine Controls Update
Turbine Controls Update David Cicconi, Business Development Manager Emerson Process Management Power & Water Solutions Define Project Scope and Objectives Address obsolescence Best solution for new operational
The Business case for monitoring points... PCM architecture...
The Business case for monitoring points... Points Condition Monitoring (PCM) measures key parameters related to the performance of switch machines and turnouts in real time at every movement. Intelligent
Operational Overview and Controls Guide
DOCUMENT: ECSEQ2-1 EFFECTIVE: 02/14/07 SUPERSEDES: 02/26/03 Operational Overview and Controls Guide Standard Two or Three Pump Type VFD Booster Controls 6700 Best Friend Road. Norcross, GA 30071. (770)
DDX 7000 & 8003. Digital Partial Discharge Detectors FEATURES APPLICATIONS
DDX 7000 & 8003 Digital Partial Discharge Detectors The HAEFELY HIPOTRONICS DDX Digital Partial Discharge Detector offers the high accuracy and flexibility of digital technology, plus the real-time display
PMCS. Integrated Energy Management Solution. Unlock the Full Potential of Power Networks Through Integration. Complete Solution. Informed Decisions
PMCS Integrated Energy Management Solution Unlock the Full Potential of Power Networks Through Integration Power Management Control System (PMCS) is a highly customizable, fully integrated end-to-end Energy
SPPA-D3000 Plant Monitor Technical Description
SPPA-D3000 Plant Monitor Technical Description Model-based monitoring and early fault detection for components and processes May 2008 Answers for energy. 1 Siemens AG 2008. All Rights Reserved Contents
AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL
ATS-220 AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL For Use in 208 to 240 Volts Single and 3 Phase ATS Systems With 110Volt AC or DC Control Motors and selenoids 4501 NW 27 ave Miami FL 33142
water is cooled in a secondary cooling control tasks: use of seawater. Treatment of the seawater formation of algal vegetation.
for the start-up and shut-down procedures in the case of longer standstills. The diesel exhaust is fed into two turbochargers. A portion of the exhaust gases can be utilized in a waste-heat boiler producing
Testing Intelligent Device Communications in a Distributed System
Testing Intelligent Device Communications in a Distributed System David Goughnour (Triangle MicroWorks), Joe Stevens (Triangle MicroWorks) [email protected] United States Smart Grid systems
Context: significant penetration of DG = increased risks for system security
Distributed Generation: towards an effective contribution to power system security IEEE Tampa GM 2007: Panel on Impact of Dispersed Generation on Power System structure & security Bruno Meyer Outline Context:
2011, The McGraw-Hill Companies, Inc. Chapter 5
Chapter 5 5.1 Processor Memory Organization The memory structure for a PLC processor consists of several areas, some of these having specific roles. With rack-based memory structures addresses are derived
GE Intelligent Platforms. PACSystems High Availability Solutions
GE Intelligent Platforms PACSystems Solutions Minimizing the high cost of downtime To keep your essential systems running, PACSystems ensures continuous, efficient operations with superior performance
Federal Wage System Job Grading Standards for Electric Power Controlling, 5407. Table of Contents
Federal Wage System Job Grading Standards for Electric Power Controlling, 5407 Table of Contents WORK COVERED... 2 WORK NOT COVERED...2 TITLES... 2 GRADE LEVELS... 2 SPECIAL ADDITIONAL RESPONSIBILITIES...
Technical Information POWER PLANT CONTROLLER
Technical Information POWER PLANT CONTROLLER Content The Power Plant Controller offers intelligent and flexible solutions for the control of all PV power plants in the megawatt range. It is suitable for
SECTION 13XXX CONTROL DESCRIPTION (DICP Models 02-412NC, 412, 622, 826, 1030)
PART 1 - GENERAL SECTION 13XXX CONTROL DESCRIPTION (DICP Models 02-412NC, 412, 622, 826, 1030) 1.01 SUMMARY This section describes the operation and control of a drip irrigation system. The major components
Controller Automation, Model II+
Controller Automation Page 2 of 2 Automation with the RADAK II+ power controller II+ I/O Points: Inputs 5 Programmable Digital inputs 2 Dedicated digital inputs (Channel select and External SCR control
Remote I/O Network Determinism
Remote I/O Network Determinism September 2011 by David Doggett & Manuel J. Palomino Make the most of your energy Summary Executive Summary... p 3 Introduction... p 4 Network Determinism vs Overall Performance...
How can I manage all automation software tasks in one engineering environment?
How can I manage all automation software tasks in one engineering environment? With Totally Integrated Automation Portal: One integrated engineering framework for all your automation tasks. Answers for
MTS Power Products MIAMI FL 33142 ATS-22AG. Automatic Transfer Switch And Control PLC Operator s Manual
MTS Power Products MIAMI FL 33142 ATS-22AG Automatic Transfer Switch And Control PLC Operator s Manual Dedicated Single Phase Transfer Switch With Touch Screen Controls Normal Power Connections Emergency
FAST METHODS FOR SLOW LOOPS: TUNE YOUR TEMPERATURE CONTROLS IN 15 MINUTES
FAST METHODS FOR SLOW LOOPS: TUNE YOUR TEMPERATURE CONTROLS IN 15 MINUTES Michel Ruel P.E. President, TOP Control Inc 4734 Sonseeahray Drive 49, Bel-Air St, #103 Hubertus, WI 53033 Levis Qc G6W 6K9 USA
D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.
SECTION 263354 STATIC UPS TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes 1. System start-up services. 2. Battery charging. 3. Load bank testing. 4. Battery load testing. 5.
Procidia Control Solutions Dedicated Backup in a Single Variable Control Loop
APPLICATION DATA AD353-109 Rev 3 April 2012 Procidia Control Solutions Dedicated Backup in a Single Variable Control Loop In critical control applications, a dedicated backup controller can provide increased
Chapter 5. System security and ancillary services
Chapter 5. System security and ancillary services 1 Introduction Markets for electrical energy can function only if they are supported by the infrastructure of a power system. System should continue to
ARCHITECTURE OF INDUSTRIAL AUTOMATION SYSTEMS
ARCHITECTURE OF INDUSTRIAL AUTOMATION SYSTEMS Abdu Idris Omer Taleb M.M., PhD Majmaah University, Kingdom of Saudia Arabia Abstract This article is aimed to name the levels of industrial automation, describes
ABB North America. Substation Automation Systems Innovative solutions for reliable and optimized power delivery
ABB North America Substation Automation Systems Innovative solutions for reliable and optimized power delivery Substation Automation Systems Advanced substation automation, protection and control solutions
GPD 506/P5 Start-up Procedure and Checklist
GPD 506/P5 Start-up Procedure and Checklist Preparation for GPD506/P5 Drive Start-Up...2 HVAC Start-Up Procedure for GPD 506/P5 WITH Bypass Option:...4 HVAC Start-Up Procedure for GPD 506/P5 WITHOUT Bypass
Software INTERACT. MachineLogic. The Shortest Distance Between Man and Machine
Software INTERACT MachineLogic The Shortest Distance Between Man and Machine Fully IntegrateYour HMI and PC-Based Control With MachineShop Project Management MachineShop s Project Management is a simple,
PROGRAMMABLE LOGIC CONTROL
PROGRAMMABLE LOGIC CONTROL James Vernon: control systems principles.co.uk ABSTRACT: This is one of a series of white papers on systems modelling, analysis and control, prepared by Control Systems Principles.co.uk
PowerPC Microprocessor Clock Modes
nc. Freescale Semiconductor AN1269 (Freescale Order Number) 1/96 Application Note PowerPC Microprocessor Clock Modes The PowerPC microprocessors offer customers numerous clocking options. An internal phase-lock
HYDRO-ELECTRIC POWER PLANTS
HYDRO-ELECTRIC POWER PLANTS SOLINA MYCZKOWCE ROŻNÓW Supervisory and control systems for Hydro-Electric Power Plants R E L I A B L E S O L U T I O N S O F A U T O M A T I O N S Y S T E M S Doc. No. ENPN007
NEW GENERATION PROGRAMMABLE AUTOMATION CONTROLLER
NEW GENERATION PROGRAMMABLE AUTOMATION CONTROLLER NEW GENERATION PROGRAMMABLE AUTOMATION CONTROLLER Understanding what a PAC is starts from the understanding of PLC. A PLC is a Programmable Logic while
Operational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives
DOCUMENT: ECSEQ6-0 EFFECTIVE: 09/23/10 SUPERSEDES: Operational Overview and Controls Guide Two or Three Pump IronHeart Lite with Variable Frequency Drives 6700 Best Friend Road. Norcross, GA 30071. (770)
15 Organisation/ICT/02/01/15 Back- up
15 Organisation/ICT/02/01/15 Back- up 15.1 Description Backup is a copy of a program or file that is stored separately from the original. These duplicated copies of data on different storage media or additional
Programming Logic controllers
Programming Logic controllers Programmable Logic Controller (PLC) is a microprocessor based system that uses programmable memory to store instructions and implement functions such as logic, sequencing,
Computer Controlled Generating Stations Control and Regulation Simulator, with SCADA SCE
Technical Teaching Equipment Computer Controlled Generating Stations Control and Regulation Simulator, with SCADA SCE EDIBON SCADA System Teaching Technique used 4 5 2 Data Acquisition Board Cables and
DeviceNet Communication Manual
DeviceNet Communication Manual Soft-Starter Series: SSW-07/SSW-08 Language: English Document: 10000046963 / 00 03/2008 Summary ABOUT THIS MANUAL... 5 ABBREVIATIONS AND DEFINITIONS... 5 NUMERICAL REPRESENTATION...
Case Study - University at Buffalo State University of New York. Lower Energy Usage Costs with Real Time Monitoring, Campus-wide
Case Study - University at Buffalo State University of New York Lower Energy Usage Costs with Real Time Monitoring, Campus-wide Reduce Energy Consumption through Awareness of Energy Use Analyze Power Quality
Series Six Plus Programmable Controller
Series Six Plus Programmable Controller Gl?K-0147B June 1989 Central Processor Unit 8-Slot Rack 1l-Slot Rack General Description The Central Processor Unit (CPU) for the Series Six Plus Programmable Logic
..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...
..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark... TIME MARK CORPORATION 11440 EAST PINE STREET TULSA, OK 74116 USA tel 918 438-1220 fax 918 437-7584 www.time-mark.com
Combined Cycle Control Overview
Combined Cycle Control Overview Introduction The Combined Cycle (CC) solution provides for the control and monitoring of a typical CC power plant in a cost effective, preengineered package. Basic Architecture
ATTACHMENT G. Network Operating Agreement
ATTACHMENT G Network Operating Agreement 1. PURPOSE OF NETWORK OPERATING AGREEMENT The purpose of this Agreement is to identify contractual requirements related to Network Integration Transmission Service
Agile Project Execution
ebook Agile Project Execution The future of Industrial Process Automation projects v1.4 EMK(VDS)-TR-EB-01 APEX ebook Table of Contents Intro Agile Project Execution Page 2. Chapter 1 Conventional Project
INTRODUCTION TO SYNCHRONIZING AUTOMATIC SYNCHRONIZING CONSIDERATIONS AND APPLICATIONS
INTRODUCTION TO SYNCHRONIZING AUTOMATIC SYNCHRONIZING CONSIDERATIONS AND APPLICATIONS INTRODUCTION It is the intention of this presentation to provide an explanation of the automatic synchronizing process,
Critical-Power Automatic Transfer Systems Design and Application
Critical-Power Automatic Transfer Systems Design and Application Bill Brown, P.E., Jay Guditis, Square D Critical Power Competency Center 1. INTRODUCTION An important requirement of mission-critical electric
IPB-IB ELECTRIC ACTUATORS FOR INDUSTRIAL PROCESS CONTROL INDUSTRIAL STEAM BOILERS. BECK VIDEO Scan w/ Smartphone
IPB-IB R ELECTRIC ACTUATORS FOR INDUSTRIAL PROCESS CONTROL INDUSTRIAL STEAM BOILERS BECK VIDEO Scan w/ Smartphone 1 Increasing Business Pressures Necessitate Boiler Control Improvements Today s industrial
Application Note AN-SERV-006
THIS INFORMATION PROVIDED BY AUTOMATIONDIRECT.COM TECHNICAL SUPPORT IS SUPPLIED "AS IS", WITHOUT ANY GUARANTEE OF ANY KIND. These documents are provided by our technical support department to assist others.
NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL
NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL CONTENTS GENERAL INFORMATION...3 INSTALLATION...3 FIELD WIRING...4 PROGRAMMING...4 Circuit Monitor Options...5 Power Frequency...5 Alarm Silence
Real Time Test Bed Development for Power System Operation, Control and Cyber Security
1 Real Time Test Bed Development for Power System Operation, Control and Cyber Security Ram Mohan Reddi, Student Member, IEEE, and Anurag K Srivastava, Senior Member, IEEE Abstract--With ongoing smart
Ultrasound Condition Monitoring
Ultrasound Condition Monitoring Whitepaper Alan Bandes UE Systems, Inc. Abstract: Instruments based on airborne/structure borne ultrasound technology offer many opportunities for reducing energy waste
Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies
Soonwook Hong, Ph. D. Michael Zuercher Martinson Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies 1. Introduction PV inverters use semiconductor devices to transform the
PLCs and SCADA Systems
Hands-On Programmable Logic Controllers and Supervisory Control / Data Acquisition Course Description This extensive course covers the essentials of SCADA and PLC systems, which are often used in close
System Protection Schemes in Eastern Denmark
System Protection Schemes in Eastern Denmark Joana Rasmussen COWI A/S, Energy Department System Protection Schemes in Eastern Denmark 1.Advanced system protection schemes are investigated and perspectives
Isolated-Parallel UPS Configuration
Isolated-Parallel UPS Configuration 1 Inhalt 1 Introduction... 4 2 IP systems configuration... 6 3 Projects... 17 4 Conclusions... 17 2 Abstract The isolated-parallel UPS configuration has become well
Gas Genset Controls. Genset Control Panel (GCP2) with PCS (PowerCommand Supervisor) Features. Description
Gas Genset Controls Genset Control Panel (GCP2) with PCS (PowerCommand Supervisor) Description The Cummins Power Genset Control Panel (GCP2) is an integrated monitoring and control system for the Cummins
PSS E. High-Performance Transmission Planning Application for the Power Industry. Answers for energy.
PSS E High-Performance Transmission Planning Application for the Power Industry Answers for energy. PSS E architecture power flow, short circuit and dynamic simulation Siemens Power Technologies International
ORC TURBOGENERATOR TYPE CHP - Organic Rankine Cycle Turbogenerator fed by thermal oil, for the combined production of electric energy and heat -
Doc. : 08C00031_e Date : 10.02.2009 Page : 1 / 9 ORC TURBOGENERATOR TYPE CHP - Organic Rankine Cycle Turbogenerator fed by thermal oil, for the combined production of electric - (Preliminary) Doc. : 08C00031_e
Control of Boiler Operation using PLC SCADA
Control of Boiler Operation using PLC SCADA K. Gowri Shankar Abstract This paper outlines the various stages of operation involved in the conversion of a manually operated boiler towards a fully automated
Bioreactor Process Plant Powered by NI LabVIEW and NI CompactRIO
Bioreactor Process Plant Powered by NI LabVIEW and NI CompactRIO Segment: Industry Country: Singapore Author(s): Sanka Hettiarachchi, Providev Kevin Kho, Technologies Unlimited Products: NI crio-9075 (Integrated
Short Form Catalogue. Alarm Systems. Reliable Supervision and Control
Short Form Catalogue Alarm Systems Reliable Supervision and Control Alarm Monitors and Indicators The SELCO product range includes a number of alarm monitors and indicator panels for use in numerous applications.
SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks
SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks Introduction SCADA (Supervisory Controlled and Data Acquisition) controlled multi-step metalenclosed automatic capacitor
Gsm Based Controlled Switching Circuit Between Supply Mains and Captive Power Plant
International Journal of Computational Engineering Research Vol, 03 Issue, 4 Gsm Based Controlled Switching Circuit Between Supply Mains and Captive Power Plant 1, Mr.S.Vimalraj, 2, Gausalya.R.B, 3, Samyuktha.V,
Echtzeittesten mit MathWorks leicht gemacht Simulink Real-Time Tobias Kuschmider Applikationsingenieur
Echtzeittesten mit MathWorks leicht gemacht Simulink Real-Time Tobias Kuschmider Applikationsingenieur 2015 The MathWorks, Inc. 1 Model-Based Design Continuous Verification and Validation Requirements
Evolution of Control for the Smart Transmission Grid
Evolution of Control for the Smart Transmission Grid Anjan Bose Washington State University Pullman, WA SCE Smart Grid Research Symposium California Institute Of Technology October, 2011 The Past (before
Nuclear Power Plant Electrical Power Supply System Requirements
1 Nuclear Power Plant Electrical Power Supply System Requirements Željko Jurković, Krško NPP, [email protected] Abstract Various regulations and standards require from electrical power system of the
26 3213.13 Diesel Engine Driven Generators Page 1 of 6
Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at
Bosch Packaging Academy Essential Training
Essential Training Operating Fundamentals Work safely during operation Understand the basic functions of the equipment Get familiar with the operating elements Be able to operate the equipment Get familiar
www.klmtechgroup.com TABLE OF CONTENT
Page : 1 of 13 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia TABLE OF CONTENT SCOPE 2 REFERENCES
Substation Automation Systems. We are exceptional grid stability PSGuard Wide Area Monitoring System
Substation Automation Systems We are exceptional grid stability PSGuard Wide Area Monitoring System We are exceptional grid stability PSGuard Wide Area Monitoring System 2 We are exceptional grid stability
A Proposed Integration of Hierarchical Mobile IP based Networks in SCADA Systems
, pp. 49-56 http://dx.doi.org/10.14257/ijsh.2013.7.5.05 A Proposed Integration of Hierarchical Mobile IP based Networks in SCADA Systems Minkyu Choi 1 and Ronnie D. Caytiles 2 1 Security Engineering Research
GENe Software Suite. GENe-at-a-glance. GE Energy Digital Energy
GE Energy Digital Energy GENe Software Suite Today s utilities have complex requirements that need sophisticated solutions. GE Energy s GENe provides these solutions. Using the latest advances in technology,
FlexPak 3000 Digital DC Drive Software Reference Manual Version 4.3
FlexPak 3000 Digital DC Drive Software Reference Manual Version 4.3 Instruction Manual D2-3405-2 The information in this manual is subject to change without notice. Throughout this manual, the following
The South African Grid Code
The South African Grid Code The Scheduling and Dispatch Rules Draft Revision 7.15T Comments to this document can be forwarded to: Attention: Mr. Nhlanhla Lucky Ngidi National Energy Regulator of South
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fi re pumps
L5354 ControlNet Communications Interface
L5354 ControlNet Communications Interface Technical Manual HA470733 Issue 2 Copyright SSD Drives Inc 2005 All rights strictly reserved. No part of this document may be stored in a retrieval system, or
Computer Network. Interconnected collection of autonomous computers that are able to exchange information
Introduction Computer Network. Interconnected collection of autonomous computers that are able to exchange information No master/slave relationship between the computers in the network Data Communications.
TwinCAT NC Configuration
TwinCAT NC Configuration NC Tasks The NC-System (Numeric Control) has 2 tasks 1 is the SVB task and the SAF task. The SVB task is the setpoint generator and generates the velocity and position control
Distribution Operations with High-penetration of Beyond the Meter Intermittent Renewables. Bob Yinger Southern California Edison April 15, 2014
1 Distribution Operations with High-penetration of Beyond the Meter Intermittent Renewables Bob Yinger Southern California Edison April 15, 2014 Southern California Edison SCE provides power to: Nearly
Technical Training Module ( 30 Days)
Annexure - I Technical Training Module ( 30 Days) Section 1 : Programmable Logic Controller (PLC) 1. Introduction to Programmable Logic Controller - A Brief History, Need and advantages of PLC, PLC configuration,
IEC 61850: Communication Networks and Systems in Substations
IEC 61850: Communication Networks and Systems in Substations Sistemi e strumenti per l'automazione, A. Flammini, AA2011-2012 Background I: Power Grid Sistemi e strumenti per l'automazione A. Flammini,
Pow-R-Con Multi Function Control
37264 Pow-R-Con Multi Function Control Product Specification Product Specification 37264 Product Information DYNA Power Controls Pow-R-Con TM GENERAL The Barber-Colman Pow-R-Con TM represents an integrated