Water Penetration Test Report
|
|
|
- Cornelius Jacobs
- 10 years ago
- Views:
Transcription
1 Water Penetration Test Report Report No. 30B TRP Vipac Engineers & Scientists Ltd Melbourne VIC 25 th March 2011
2 Report No. 30B TRP Water Penetration Test Report Page 2 of 20 DOCUMENT CONTROL REPORT NO: 30B TRP Water Penetration Test Report LIBRARY CODE: PREPARED FOR: PREPARED BY: Vipac Engineers & Scientists Ltd 67 Henderson Road Private Bag 16 Clayton Port Melbourne VIC 3207 VIC AUSTRALIA Contact: David Dent [email protected] Phone: Phone: Fax : Fax : AUTHOR: REVIEWED BY: REVISION HISTORY: Gokul Krishnan Rajamani Date: Project Engineer Dr. Seifu Bekele Date: Principal Wind Consultant Revision No. Date Issued Reason/Comments DISTRIBUTION: 17 th March th March 2011 Initial Draft Issue Final Issue Copy No. Location 1 Project 2 Uncontrolled Copy Client (PDF Format) KEYWORDS:, Water Penetration Test NOTE: This is a controlled document within the document control system. SUPERSEDED and returned to the Vipac QA Representative. If revised, it must be marked
3 Report No. 30B TRP Water Penetration Test Report Page 3 of 20 TABLE OF CONTENTS 1. INTRODUCTION TEST DETAILS TEST REFERENCE & APPLICATION STD TEST SAMPLE SAMPLE DESCRIPTION TEST RIG INSTRUMENTATION ORDERS OF ACCURACY TEST CONDITIONS & PROCEDURE TEST RESULTS PRELOAD WATER PENETRATION TEST BY STATIC PRESSURE WATER PENETRATION TEST BY CYCLIC PRESSURE CONCLUSION...12 APPENDIX A - TEST PHOTOS...13 APPENDIX B CERTIFICATE OF IDENTIFICATION...14
4 Report No. 30B TRP Water Penetration Test Report Page 4 of INTRODUCTION Document Type: - Company: - Water Penetration Test Report TEST DETAILS Date: 2 nd March 2011 Time: Venue: 2pm 3pm Test Rig, located at 279 Normanby Road, Port Melbourne. Test Personnel: Vipac Engineers & Scientists Ltd Mr Gokul Krishnan Rajamani Dr. Zhuyun Xu 2. TEST REFERENCE & APPLICATION STD. AS/NZS 4284: Australian/New Zealand Standard -Testing of Building Facades 3. TEST SAMPLE 3.1. SAMPLE DESCRIPTION manufactured and installed the sample wall cladding system on the test rig at Vipac Laboratories in Melbourne. Nuclad polystyrene panels are made up of (M) Grade expanded polystyrene (EPS) in sheet form oven cured for a minimum of 3 days. The boards are render coated using approved Poly render system and prepared for final coat and decorative effects. Nuclad panels come in sizes of 2500mm x 1200mm and 5000mm x 1200mm in nominal standard thicknesses of 50, 75mm and 100mm. The test sample was 2400mm wide (two panels joined), 2500mm high and 75mm thick, constructed over a timber frame with operable window approximately oriented near the mid-span of the panel (window glazing not considered to be a part of the current tests) as shown in Figures 1 and 2.
5 Report No. 30B TRP Water Penetration Test Report Page 5 of 20 Figure 1. Test Sample Outer Side (i.e. side subjected to test) Figure 2. Test Sample Inner Side (i.e. observation side)
6 Report No. 30B TRP Water Penetration Test Report Page 6 of TEST RIG The test rig was constructed to accommodate the façade sample (see Figure 3). The water spray assembly, which includes an inlet manifold/ header, spray pipes and spray nozzles were assembled so that each spray nozzles delivers/ sprays water at 0.05 L/ m 2 s. Figure 3. Façade Test Rig Figure 4. Spray Nozzle
7 Report No. 30B TRP Water Penetration Test Report Page 7 of INSTRUMENTATION Instrument Make & Model Calibration Serial No. Flow Meter Endress Hauser Promag 50 Swiss Calibration September Manometer TSE GTS August ORDERS OF ACCURACY Table 1. List of Instruments Air pressure Range 0-300Pa 1% or 2 Pa Range Pa 1% or 10 Pa Airflow rate 4% Water flow rate 8%
8 Report No. 30B TRP Water Penetration Test Report Page 8 of TEST CONDITIONS & PROCEDURE No. Test Method Requirement 1 Preliminary Loading Subject sample to a static pressure of 50% of the positive and negative design loads. This is a settling/take up period for the system. 2 Water Penetration test by static pressure 3 Water Penetration test by cyclic pressure AS 4284:2008 Table 2. Test Conditions and Procedure Apply water spray of 0.05 L/m 2.s at 0 Pa for 5 minutes. 300 Pa for 15 minutes. Observe sample with no spray at 0Pa for 5 minutes. Apply water spray of 0.05 L/m 2.s at 0 Pa for 5 minutes Pa (3-5s cycle) for 5 minutes. Water spray at 0 Pa for 2 minutes Pa (3-5s cycle) for 5 minutes. Water spray at 0 Pa for 2 minutes Pa (3-5s cycle) for 5 minutes. No water spray at 0Pa for 5 minutes. The sample as constructed formed one of the faces of the sealed test rig. During each test the pressure differential was achieved across the sample by partially evacuating and pressurising the chamber using a fan (this was also partly achieved by adjusting the damper arrangement located at the outlet). Static Water Pressurisation Test Water was applied continuously and completely over the exterior face of the test sample at a rate not less that 0.05 L/m 2.s (water spray rate was monitored using a flow meter at the inlet as shown in Figure 5). At the start of the test the water spray operation was carried out at 0Pa pressure difference for duration of 5 minutes. This was followed by a further 15 minutes at the test pressure of 300Pa. Observations were made on the inner side of the panel during water spray operation and for 5 minutes after the water spray had stopped with 0Pa pressure difference. Cyclic Water Pressurisation Test The cyclic water penetration tests were performed upon completion of the static water pressurisation tests. Water was applied continuously and completely over the exterior face of the test sample at a rate not less that 0.05 L/m 2.s (water spray rate was monitored using a flow meter at the inlet as shown in Figure 5), while a cyclic positive
9 Report No. 30B TRP Water Penetration Test Report Page 9 of 20 air pressure was applied (see table 4) for duration of not less than 5 minutes/ stage. The applied positive pressure was varied between specific limits with a cycle time of 3 5s. The air pressure differential was reduced to zero for 2 minutes between consecutive steps with water sprays still in operation. The internal surface of the façade sample was observed during the water spray operation and for 5 minutes after the water spray had stopped with 0Pa pressure difference. Figure 5. Flow Meter connected at water inlet
10 Report No. 30B TRP Water Penetration Test Report Page 10 of TEST RESULTS The following are the results of the performance testing PRELOAD The sample was subjected to a preload of 50% of positive and negative design loads. This is a settling/take up period for the system WATER PENETRATION TEST BY STATIC PRESSURE Test Date: 2 nd March 2011 Water Rate: 0.05 L/ m 2.s Test Chamber Pressure: 300Pa Positive Static Pressure Criteria: Water penetration is considered to occur when: - Water appears on the interior side of the plane of the innermost face of the test sample, is visible to building occupants and would stain or damage any part of the completed building or furnishings. Overflow, percolation or leakage of water from sill tracks is also not acceptable. Water penetration is not considered to occur when: - Water is contained within the curtain wall without ill effect and drains to the exterior. Water from condensation occurring during testing is not considered as a leakage. Results: Test Static Duration Observation Remarks Stage Pressure (Pa) (min) No Leakage Pass 2 300Pa 15 No Leakage Pass No Leakage Pass Observations: Table 3. Test Results Water Penetration by Static Pressures At 0Pa pressure difference with water sprays still operating, no leakage was detected on the inner side of the test sample. When the sample was subjected to a static load of 300Pa for duration of 15 minutes (test pressure for static loading condition), no leakage was observed between the façade panel and the sub-frame.
11 Report No. 30B TRP Water Penetration Test Report Page 11 of 20 At 0Pa pressure difference with water sprays turned OFF, no leakage was detected on the inner side of the test sample. Note: Water leakage occurred within the window to window housing NOT window housing to Nutex panel interface, therefore leakage not considered to constitute a failure. Please see images from Appendix A for leakage from window sub-frames WATER PENETRATION TEST BY CYCLIC PRESSURE Test Date: 2 nd March 2011 Water Rate: 0.05 L/ m 2.s Test Chamber Pressure: Pa Cyclic Pressure Steps Criteria: Water penetration is considered to occur when: - Water appears on the interior side of the plane of the innermost face of the test sample, is visible to building occupants and would stain or damage any part of the completed building or furnishings. Overflow, percolation or leakage of water from sill tracks is also not acceptable Water penetration is not considered to occur when Water is contained within the curtain wall without ill effect and drains to the exterior. Water from condensation occurring during testing is not considered as a leakage. Results: Test Stage Cyclic Pressure (Pa) Duration (min) Observation Remarks Minimum Maximum No Leakage Pass No Leakage Pass No Leakage Pass Observations Table 4. Test Results Water Penetration by Cyclic Pressures At 0Pa pressure difference with water sprays still operating, no leakage was detected on the inner side of the test sample. When the sample was subjected to cyclic loads in three stages between 150 and 600Pa (test pressure for cyclic loading), no leakage was observed in the inner face of the test sample. At 0Pa pressure difference with water sprays turned OFF, no leakage was detected on the inner side of the test sample.
12 Report No. 30B TRP Water Penetration Test Report Page 12 of 20 Note: Water leakage occurred within the window to window housing NOT window housing to Nutex panel interface, therefore leakage not considered to constitute a failure. Please see images from Appendix A for leakage from window sub-frames. 6. CONCLUSION The sample wall cladding erected by when subjected to the following tests, satisfied the performance criteria for water penetration and meets P of the BCA according to test standard AS/NZS 4284:2008. The results are as follows. No. Test Requirement Observation Result 1 Water Penetration test by static pressure Apply water spray of 0.05 L/m 2.s at 0 Pa for 5 minutes. 300 Pa for 15 minutes. Observe sample with no spray at 0Pa for 5 minutes. The cladding was not observed to cause any leakage. Pass 2 Water Penetration test by cyclic pressure Apply water spray of 0.05 L/m 2.s at 0 Pa for 5 minutes Pa (3-5s cycle) for 5 minutes (Stage 1). Water spray at 0 Pa for 2 minutes Pa (3-5s cycle) for 5 minutes (Stage2). Water spray at 0 Pa for 2 minutes Pa (3-5s cycle) for 5 minutes (Stage 3). No water spray at 0Pa for 5 minutes. Table 5. Summary of Test Results The cladding was not observed to cause any leakage. Pass Water leakage occurred within the window to window housing NOT window housing to Nutex panel interface, therefore leakage not considered to constitute a failure.
13 APPENDIX A - TEST PHOTOS Leakage observed near the window sub-frame Water leakage occurred only within the window-to-window housing and NOT window housing to panel interface, therefore leakage not considered to constitute a failure and the test was considered a PASS.
14 APPENDIX B CERTIFICATE OF IDENTIFICATION Date: 11 th March 2011 TO WHOM IT MAY CONCERN This is to certify that the façade test sample (75mm Nuclad EIFS) is a true representation of the façade to be erected on the building and it incorporates identical materials and construction methods. Details of the façade tested are described in the attached drawings. The fastener details are as follows, mm fastener offset from the stud edge mm centres fastener to fastener on both stud and noggins. 3. All of the above frame and fastening positions are applicable only to panels for construction in non-cyclonic regions as specified in AS/NZS standard. Please do not hesitate to contact me if you have any further queries in this regard. Yours Sincerely Pty Ltd
15 A. Installation and Fixing Detail I N S T A L L A T I O N Weather Wrap recommends use of NUCLAD Breathable Weather Wrap. Note: Under no circumstances should standard non-breathable paper be used behind NUCLAD panels. polystyrene Layout NUCLAD panels may be laid either vertically or horizontally according to the best fit for the 2500mm x 1200mm sheet - horizontal, staggered joint layout is always the preferred option. If the wall height is less than or equal to 2500mm, then practicality may dictate that the NUCLAD panel be laid vertically - but horizontal layout is the preferred option. If the wall height is greater than 2500mm, then the panels should always be laid horizontally, in a brickwork pattern, with each 1200mm vertical joint staggered up through the height of the wall. A horizontal layout is the preferred option. Minimum length of a trimmed NUCLAD panel should be restricted to 450mm or one stud spacing. Supporting Framework Edges of the NUCLAD panels require support on studs, noggings or other intermediate blocking. NUCLAD panels may be cantilevered or projected beyond supports by the same distance as a given panel s thickness. Fixed-back blocking techniques are mandatory. Full-stud width (min 90mm) support is required. Back blocking timber must be MGP 10 or greater. Merchant grade is not permitted. Adhesive fixed back blocking is not permitted. Supports/blocking are required to all edges around openings. Double studs will generally be required for vertical, full-height butt joints, or where a control joint is to be located. Cutting Masonry Blade: A diamond-tipped masonry blade is the most accurate, time-efficient and clean way to cut/trim panels (see MSDS), particularly when cutting 45º angles for external corners. Hand saw NUCLAD panels should be accurately cut to size to produce close butt joints between panels. Health & Safety Use of personal protective equipment (face masks and safety goggles) is recommended. The fine dust created by mechanical cutting is hazardous, and protection is recommended, including face masks and safety goggles. Mechanical cutting should be performed in well-ventilated spaces. Power tools should be fitted with effective dust-extraction systems. Refer to NUCLAD Material Safety Data Sheet (MSDS).
16 Fixing To Framing Centres: On a stud spacing of either 450mm or 600mm, fixings are to be at a maximum 280mm centres vertically to all perimeter and intermediate supports. Average 12 fixings per m2. Fixings: Fixing screws and washers should be the type and suitability as set out in this guide. Appearance: When fastened correctly, the screw head and washer should be slightly countersunk in a concave recess on the outer surface of the panel, and located so as to not crush the edge of the panel. The washer should always retain its circular shape i.e. if the washer begins to flare, it has been screwed too far towards the frame. Fixing To Masonry/Concrete Contact NUCLAD technical support for details. Sealing Joints Prior to closing up of all joints between panels (and between panels and other building elements), a 15mm (40mm removed from nozzles provided) bead of liquid construction urethane or a flexible urethane foam is required to the centre of meeting surfaces. This forms a mechanical seal for weatherproofing, and converts the many individual panels into a single skin. Liquid foam or flexible urethane sealant is therefore required to: All butt joints All external corners and butt jointed internal corners All vertical returns on all roof fastenings to maintain a weather seal with the panel. Sealing Openings Prior to the application of the panel all openings must be flashed from the reveal to the frame. This is now a Building Code requirement. recommends and supplies adhesive aluminum flashing tape for just this purpose - suitable for both aluminum and timber windows. This proven method reduces the risk of water penetration. In turn the panels are then to be sealed with Urethane (liquid, not foam) at the rear to the flashing tape to form a gasket around the opening. Note: Polystyrene panels should not be sealed to window/door reveals at this point. Sealants should never be rendered over, as render systems, with limited movement capabilities, will restrict a sealant's ability to move according to manufacturer s specification. Sealants for openings should be applied after the render system has been applied never before! Sealing Other Penetrations (including wiring, plumbing, joists, ducting) Where possible all penetrations through the NUCLAD system should be treated as per window detail, incorporating flashing tape and liquid urethane sealant. This is of high importance for floor and pergola joist penetrations, electrical meter boxes, ducting and the like. It is then recommended that a 10mm minimum clearance gap be left between the NUCLAD panel and the penetration and caulked using either NUCLAD approved liquid urethane sealant or flexible expanding foam urethane sealant prior to render application. Smaller penetrations such as plumbing or electrical conduit should have a 10mm minimum clearance gap between the NUCLAD panel and the pipe and caulked using either NUCLAD approved liquid urethane sealant or flexible expanding foam urethane sealant prior to render application.
17 Note: Extra fibre mesh tape is recommended around the penetration for added reinforcing during the render process. recommends the use of sealants on all openings after the rendering process has been completed. Please note that render systems are not sealants i.e. an opening cannot be sealed by the application of an Poly render system. Control Joints Control and expansion joints will be determined by the building structure and substrate. It is recommended that control joints be installed on walls over 20 metres long or over 6 metres high. The low co-efficient of linear thermal expansion of NUCLAD panels allows for large areas of panels without control joints. Where control joints are part of the building construction, the joint is to be expressed in the NUCLAD panels as an open joint, free of the construction urethane, and finished as for all other open edges (including external corners applied to each edge). Panel to panel control joints should be located on double studs, which are then to be sealed with flashing tape, which is then sealed to the rear of each panel with the use of polyurethane sealant. All control joints should feature either Ableflex (or similar) or backer rod as the primary sealer, which should set back in the control joint a minimum of 8mm where it must be sealed by others after the render process has been completed. Corners, Edges, Openings & Returns All panels to external corners must be butt joined so that the maximum area of the facing is retained. Mitred joints are not required on internal angle corners, as the joint will occur in the apex of the corner. Liquid or foam urethane sealant is required in this butt joint. To form a total weatherproof face, all joints and abutments require sealing with the liquid or foam urethane sealant. NUCLAD s Alloy External Corners should be applied to all of the following areas: 1. All external corners 2. All openings 3. All exposed bottom edges of panel These trims are to be in long lengths and set accurately to be plumb, level and straight. Flashing & Waterproofing The NUCLAD panel has a sealed face and there is no drained cavity. All door frames, window frames and other items set into the wall must include integral drainage provisions. Drained sub-sills are an alternative. All exposed edges to parapets and similar locations must be fitted with a folded metal capping, preferably zincalume or Colorbond. Junctions with lower roofs, balconies, terraces and decks must be fitted with folded metal under flashing, preferably zincalume to metal roofs, lead to tiled roofs and stainless steel to terraces. The bottom edge of the NUCLAD panel can be undercut at 45º, to produce a close, straight joint. An air gap to a minimum of 15mm is required between the finished bottom edge and the finished surface of a terrace or balcony.
18 A minimum air gap of 15mm is recommended between the finished bottom edge of the panels and the roof flashing. At ground level all exposed raw edges and exposed rear areas of panels up to the bottom plate or last fix point must be sealed with a suitable Poly tanking formula (see NUCLAD for product details) or fitted with a UPVC starter channel to suit the panel thickness. Panels should not be set less than 150mm from open ground and not less than 100mm above concrete pavers. Any exposed plinth is to be finished separately to the NUCLAD panel. Curved Walls NUCLAD panels can be installed to curved shapes of a single radius. Tight curves can be achieved by utilising 50mm panel, fixed to maximum 300 centered stud frame. Contact the manufacturer for details. Finishing When all NUCLAD panels have been installed (complete with sealants and edge trims) a 5mm minimum thickness of an approved Poly render system is required. The reinforcing mesh over the sheet joints is incorporated in the first skim coat. The approved Poly render is applied using conventional techniques. No primer is required to the NUCLAD surface. The render also flush finishes all mechanical fixings. Traditional sand/cement renders are not suitable for application to NUCLAD panels. When the skim coats are dry, the selected approved finishing coat can be applied. This coat can be smooth or textured, and coloured as preferred. A minimum acceptable result can be achieved by the following sequence: 1. 3mm skim coat (including Reinforcing Mesh Jointing Tape) 2. 2mm skim coat mm top coat and/or paint finish Storage, Handling, Protection NUCLAD panels delivered to site should be stored flat and evenly supported. They should be covered or otherwise protected from damage or soiling. When stored outside, the uppermost panel in each stack must be turned polystyrene side up. If panel stacks are to be covered, a material/canvas cover should be utilized. Under no circumstances should a black plastic cover be used. During installation, the NUCLAD panels should be handled with care to prevent edge damage or fracture. Particular care is required during windy conditions, as unsecured panels can be severely damaged. Continuous exposure may result in deterioration and minor fretting of exposed edges of EPS. This is to be removed prior to proceeding with finishing or sealing. As with all sheet materials, protection from impact damage is required. The application of the approved Poly render may follow the installation of internal services, fittings and linings when the risk of damage is minimised. Timely application of the render will complete the installation and protect the panels from damage.
19 Repair Panels that are fractured or severely damaged (before or after fixing) should be rejected or cut down to size for use. Minor penetrations, edge fractures or crushed areas may be site-patched with the reinforcing mesh and an approved Poly patching render. Waste Management Being lightweight, the EPS material is readily dispersed by the wind. To prevent a nuisance, all off-cuts and residue from cutting should be stored in tied plastic bags for removal to a place of legal disposal. Attention to detail and in particular to spacing of supports will contribute to a reduction in the amount of waste and off-cut materials.
20 B. Fastener Location Drawing 450 C. Stud Construction Drawing
Sun Windows General Information Sun New Construction Window Installation Instructions
Sun Windows General Information Section 1 G F H H H A. Apply Weather Resistive Barrier B. Apply Sill Flashing Tape C. Place Waterproof Sill Shims D. Caulk Back of Nail Fin Sides & Top, Set Window, Fasten
7. Installation. installation 7.1.1. CAST-IN WINDOW SYSTEM 7.1. INSTALLATION OF WINDOW MAIN FRAME
7. Installation Window involves the fixing of window frame at an earlier construction stage and subsequent of the window sashes. This is a highly workmanship dependent process. Only trained and approved
The WANZ Guide to Window Installation
The WANZ Guide to Window Installation as described in E2/AS1 Amendment 5 Ver. 1.1 Page 2 of 74 Contents Overview Page 5 Objective Page 5 Scope Page 5 Opening Preparation Page 7 Step P1 Preliminary Check
Linea Weatherboard DIRECT FIX CONCRETE SLAB AND SOFFIT FIGURE 1
Top plate Stud Soffit lining 45mm min nog Fix scotia bead Building underlay/james Hardie rigid air barrier Soffit Detail Building underlay/james Hardie rigid air barrier Bottom plate 25mm wide cant strip.
INSTALLATION OF A BAY WINDOW
INSTALLATION OF A BAY WINDOW Installation of a Bay Window These instructions relate to the replacement of an existing bay window or replacement of a straight window with a new bay window, in an opening
NRG 75 CRF NRG GREENBOARD WALL SYSTEM
NRG GREENBOARD WALL SYSTEM NRG Energy Efficient Building Systems is pleased to announce a revolution in lightweight cladding systems. NRG Building Systems is the first and only company to achieve CodeMark
INSTALLATION INSTRUCTIONS for Vinyl Windows with Integral Nailing Fin (JII001)
Thank you for selecting JELD-WEN products. Attached are JELD-WEN s recommended installation instructions for Vinyl windows with an integral nailing fin. While the use of these installation instructions
The WANZ Guide to Window Installation
The WANZ Guide to Window Installation as described in E2/AS1 Amendment 5 2 of 60 Contents Overview 5 Objective 5 Scope 5 Opening Preparation 7 Step P1 Preliminary Check 8 Step P2 Cut the Underlay 9 Step
Superform Products Ltd.
TYPICAL CORNER REINFORCING NOTE : SEE ENGINEERED REBAR SCHEDULES SUPPLIED BY THE MANUFACTURER STEEL REINFORCEMENT WALL CORNER 90 Copyright 2012 Sept. 2012 5.1.1 Rebar Spacing 6" 12" Max. Load LB./FT. 2000
Installation Window Building In Details
Installation Window Building In Details INSTALLATION Photo courtesy of Rowe Aluminium DATE: NOVEMBER 2009 REPLACES: AUGUST 2003 INSTALLATION Installation Replaces: Scale: NOT TO SCALE Vantage snap-on couplers
Window Installation Instructions
Caution The correct installation methods of windows in full frame or insert applications is critical towards achieving the tested performance of the window and longterm enjoyment and energy savings for
Storage Store the siding in a dry and ventilated area. Do not place it directly on the ground. Always cover the siding after a day s work.
Installation Guide Before you begin, take the time to read this entire guide to clearly understand the requirements and steps to follow for proper installation. Warning Do not install defective material.
!!!!!! !!! Decra Plus DPSW010 DPSTW011 DPSW012 DPSW013 DPSW014 DPSW015 DPSW016 DPSW020 DPSW021 DPSW024 DPSW030 DPSW031 DPSW035 DPSW030 DPSW031 DPSW035
Decra Plus Drawing no DPSW010 DPSTW011 DPSW012 DPSW013 DPSW014 DPSW015 Description Shown In Decra Brochure Most Commonly Used Detail t~êã=oççñ=b~îéë=aéí~áä=b~îéë=lîéêü~åö=táíü=fåëìä~íéç=c~ëåá~=~åç=pçññáí
WINDOW INSTALLATION GUIDE FOR NEW CONSTRUCTION - WOOD FRAMING
WINDOW INSTALLATION GUIDE FOR NEW CONSTRUCTION - WOOD FRAMING IMPORTANT NOTICES AND INFORMATION Read these instructions in their entirety prior to installing windows. Any local building code requirements
How To Repair A Boat Landing Deck With A Boat Bed
RESIDENTIAL INSULATED SHEATHING INSTALLATION GUIDE Residential Insulated Sheathing Installation Guide ROXUL COMFORTBOARD IS Table of Contents Slab-on-grade-to Above Grade Wall...1 Foundation Wall at Footing
EXTERNAL WATERPROOFING MEMBRANES BEST PRACTICE GUIDELINES
Building and Construction Industry A joint industry initiative produced by BSA Supershow logo.indd 1 30/01/2008 9:43:29 AM EXTERNAL WATERPROOFING MEMBRANES BEST PRACTICE GUIDELINES FAILING WATERPROOFING
Quality Assurance and Diagnostic Water Leakage Field Check of Installed Storefronts, Curtain Walls and Sloped Glazing Systems
Method of Test Committee Approval Product Group Approval Approved via 5/21/15 MOT CC Out for Ballot (#805-15) PUBLICATION NO. AAMA 501.2-XX DRAFT #2 DATED 5/21/15 Quality Assurance and Diagnostic Water
The better way to build TM. Installation Manual. FOUNDATION SIPs & FROST WALLS SIPs
The better way to build TM Installation Manual FOUNDATION SIPs & FROST WALLS SIPs February 2016 PWF FOUNDATION & FROST WALL SIPs Installation Manual Table of Contents Topics General Requirements...................................
Installation Details. D1 General D2 Walls D3 Ceilings D4 Reference. D Installation Details
D Installation Details D1 General D2 Walls D3 Ceilings D4 Reference D Installation Details D Contents D1 General Installation and Fastening Sequence for Steel Studs D1.1 Fastener Selection D1.3 D2 Walls
Clad Direct Glaze Window Installation Instructions
Clad Direct Glaze Window Installation Instructions Sill flashing and sealing: 2. An overview of the proper flashing sequence is shown in figure 1. Please read entire installation instructions carefully
WATER LEAKAGE IN GLAZED CURTAIN WALL SYSTEMS:
WATER LEAKAGE IN GLAZED CURTAIN WALL SYSTEMS: BY WILLIAM D. SMITH Figure 1 Four Corporate Center, Franklin, TN. Architect: Little & Associates,Charlotte, NC. Gen. Contractor: Ray Bell Const. Co., Nashville,
Residential Inspection Guidelines
Residential Inspection Guidelines 201 Pre-Pour Foundation Dimensions Building Location Certificate - if required in the building consent Construction and Advice Notes Check the building dimensions against
THIRD PARTY INSPECTION GUIDELINES FOR OWNERS AND GENERAL CONTRACTORS/CONSTRUCTION MANAGERS DS150
THIRD PARTY INSPECTION GUIDELINES FOR OWNERS AND GENERAL CONTRACTORS/CONSTRUCTION MANAGERS DS150 SECTION ONE A. Objective The objective of this guide is to provide Owners and General Contractors/Construction
SECTION 07 61 13 STANDING SEAM METAL ROOFING
SECTION 07 61 13 STANDING SEAM METAL ROOFING PART 1 GENERAL 1.01 SCOPE OF WORK A. The Work shall include all labor, materials, equipment and supervision required to complete the work of the above referenced
Tundra Series Windows January 2016
Tundra Series Windows January 2016 New Construction Installation Instructions Nail Fin, J-Fin and Brickmold Aplications product. ATTENTION! Read and understand all installation instructions before installing
Melbourne balcony Assessments
Balcony Assessment Melbourne balcony Assessments Address: SAMPLE Date: Assessor: Luke O Neill Registered Builder DBL-C 31305 Assessment Guidelines This is an assessment of balcony and elements as presented
CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011
CERTIFICATE NAME OF PRODUCT No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011 H-CONTROL REFLEX+ reflective insulating vapour control layer for roof and wall applications MANUFACTURER ACTIS
Barewood Octagon and Elongated Windows Installation Instructions
Step-by-step instructions to a beautiful window. Measuring and Installation of your new window from Century Specialty Windows couldn't be easier with our step-by-step instructions. Quality, function and
Finegan Inspection Services, Inc.
Finegan Inspection Services, Inc. Report Prepared For: Phone 513-683-0733 Fa 513-697-0163 Owners Property Address City, State, ZIP Phone FAX Owners Realtor Realty Company Phone FAX OWNER INFORMATION PROPERTY
PART 1 GENERAL 1.1 SECTION INCLUDES
J-1 Section 09110 Long Form Specification INTERIOR METAL STUD FRAMING This section includes lightweight, usually 0.036 inch (0.9 mm) thick or lighter, non-axial load bearing metal stud framing including
The better way to build TM. Installation Manual. EXTERIOR WALL SIPs
The better way to build TM Installation Manual EXTERIOR WALL SIPs July 2015 EXTERIOR WALL SIPs Installation Manual Table of Contents Topics General Requirements................................... 3 Materials..............................................
Excerpts from the Canadian National Building Code (NBC)
Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more
SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS. System 402 Flush-Glazed Screw Spline Storefront
PART 1 GENERAL 1.01 Work Included SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS System 402 Flush-Glazed Screw Spline Storefront A. Furnish and install aluminum architectural storefront system
MOCK-UP TEST REPORT. Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up
MOCK-UP TEST REPORT Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up Report No: 85616.01-120-32 Test Completion Date: 01/15/09 Report Date: 02/11/09 Record Retention End Date: 01/15/13
March 14, 2007. Installation of Bay, Bow and Garden Windows
March 14, 2007 Re: Installation of Bay, Bow and Garden Windows Attached are the Atrium Companies, Inc recommendation for the installation of bay, bow and garden windows. These instructions were developed
Replacement Window Installation Guide Non-Impact & Impact Resistant Windows without Nailing Fin
Replacement Window Installation Guide Non-Impact & Impact Resistant Windows without Nailing Fin americancraftsmanwindows.com Project Requirements: Failure to follow these instructions may void product
We urge you to read and follow the attached installation instructions. Failure to do so may void the warranty of this garden window unit.
Important Information for New Construction Installations Attention Installer! We urge you to read and follow the attached installation instructions. Failure to do so may void the warranty of this garden
TEST REPORT. Report No.: A9814.01 109 44. Rendered to: BAMCO INC. Middlesex, New Jersey. PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept
Architectural Testing TEST REPORT Report No.: A9814.01 109 44 Rendered to: BAMCO INC. Middlesex, New Jersey PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept AAMA 508 07, Voluntary Test Method
PANELIZED HOME INSTALLATION GUIDELINE
PANELIZED HOME INSTALLATION GUIDELINE A typical home package will be constructed of Snap-N-Lock Insulated Panels clad with steel skins. 4" panels will be used for the walls, and 6" panels for the roof.
SOUND INSULATION FOR EXTERIOR WALLS AND FACADE SYSTEMS
NOISE TECHNICAL FACT SHEET FACT SHEET 5 SOUND INSULATION FOR EXTERIOR WALLS AND FACADE SYSTEMS The sound insulation of exterior walls and roof-ceiling systems refers to their ability to reduce external
GUIDELINE SPECIFICATIONS
GUIDELINE SPECIFICATIONS GORDON SOFFIT-SHIELD - An Exterior Metal Soffit System DIVISION 05 5800 or DIVISION 07 7700 Note To Specifier: SOFFIT-SHIELD should be installed by tradesmen that are experienced
We urge you to read and follow the attached installation instructions. Failure to do so may void the warranty of this garden window unit.
Important Information for New Construction Installations Attention Installer! We urge you to read and follow the attached installation instructions. Failure to do so may void the warranty of this garden
Fig. 2 WALL-TO-WALL PANEL CONNECTIONS CORNER WALL CONNECTION
SIPS SCREWS WITH MINIMUM 1" PENETRATION IN WOOD MEMBER IN SIP WALL PANEL CONNECTED TO @ 24" O.C. MAXIMUM OUTSIDE SKIN EACH SIDE OF FRAMING TYP. AS RECOMMENDED BY FOAM CORE AS EACH SIDE OF FRAMING TYP.
Leaky Homes Financial Assistance Package (FAP) Repair plan example
LEAKY HOMES FINANCIAL ASSISTANCE PACKAGE FACT SHEET Repair Plan Example - June 2014 Page 1 Leaky Homes Financial Assistance Package (FAP) Repair plan example Introduction This repair plan example is intended
EASY$ TIP SHEETS. Energy Advice Saving Yukoners Money
EASY$ TIP SHEETS Energy Advice Saving Yukoners Money Quick Links How to check for leaks Draftproofing products Sealants Draft proofing your home Draftproofing can be a cost-effective measure you take to
Issue of the Guidelines on Prevention of Water Seepage in New Buildings
graphic: Buildings Department Your REF 來 函 檔 號 :. OUR REF 本 處 檔 號 :.BD GR/1-55/173 FAX 圖 文 傳 真 :..28400451 TEL 電 話 :..2626 1717 www.info.gov.hk/bd To : All Authorized Persons 7 March 2005 Registered Structural
Schluter -KERDI-BOARD Substrate, building panel, bonded waterproofing
Schluter -KERDI-BOARD Substrate, building panel, bonded waterproofing Schluter -KERDI-BOARD The universal substrate for tiles Flat. Level. Plumb. Square. No matter the quality, cost, or extravagance of
2.18 INTERIOR & EXTERIOR FINISHES 2.18.1 VAPOR & AIR BARRIERS
2.18 INTERIOR & EXTERIOR FINISHES 2.18.1 VAPOR & AIR BARRIERS The LOGIX wall assembly has no need for an additional vapor barrier, the solid concrete core covered with the low permeance EPS (Type II) foam
Inspecting to a higher standard.
Inspecting to a higher standard. Rob Hopkin Silver Spring, MD 20902 Monday, June 2, 2014 ProTec Inspection Services Inc. 19736 Selby Ave Poolesville, MD 20837 301-972-8531 www.protec-inspections.com [email protected]
Knauf Aquapanel Interior. Tile Backing. Cement board for wet areas. Will not deteriorate in water. Easy to score and snap
Tile Backing Will not deteriorate in water Easy to score and snap Resistant to mould and mildew Knauf Aquapanel Interior Cement board for wet areas Knauf Aquapanel Interior Cement Board Drywall for Wet
The compliance of a roof to part of a new house at 28D Rata Street, Oxford, Waimakariri
Determination 2009/103 The compliance of a roof to part of a new house at 28D Rata Street, Oxford, Waimakariri 1. The matters to be determined 1.1 This is a determination under Part 3 Subpart 1 of the
AAMA 2400-10. Standard Practice for Installation of Windows with a Mounting Flange in Open Stud Frame Construction for Low Wind/Water Exposure
A M E R I C A N A R C H I T E C T U R A L AAMA 2400-10 Standard Practice for Installation of Windows with a Mounting Flange in Open Stud Frame Construction for Low Wind/Water Exposure M A N U F A C T U
Introduction...COMB-2 Design Considerations and Examples...COMB-3
SECTION DIRECTORY General Information Introduction...COMB-2 Design Considerations and Examples...COMB-3 Combination Assembly Recommendations and Limitations Composite Configurations...COMB-4 Typical Sealant
INSTALLATION INSPECTION GUIDE FOR 3RD PARTY INSPECTORS FOR PAREX USA EXTERIOR INSULATION AND FINISH SYSTEMS
INSTALLATION INSPECTION GUIDE FOR 3RD PARTY INSPECTORS FOR PAREX USA EXTERIOR INSULATION AND FINISH SYSTEMS Introduction This inspection guide is organized to follow the EIF System's Installation Guide.
STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM
Chapter 9 STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM 9.1 BACKGROUND Steel is widely used in the construction of multi-storey buildings. However, steel construction is seldom used and is traditionally
Schlüter -KERDI-BOARD Substrate, structural panel, bonded waterproofing
Substrate, structural panel, bonded waterproofing The universal substrate for tiles Perfect covering No matter whether you work with mosaics or large format tiles, an absolutely level substrate with straight
Installation Instructions Double-Hung, Single-Hung, Casement, Awning, Sliding, Picture & Shapes Non-Impact & Impact Resistant Nailing Fin Windows
Installation Instructions Double-Hung, Single-Hung, Casement, Awning, Sliding, Picture & Shapes Non-Impact & Impact Resistant Nailing Fin Windows americancraftsmanwindows.com Project Requirements: Read
Energy Company Obligation (ECO): Technical Monitoring Questions
Energy Company Obligation (ECO) Technical Monitoring Questions v1 30/05/2013 Energy Company Obligation (ECO): Technical Monitoring Questions Under ECO suppliers are required to instruct suitably qualified
NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS
NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS The (NRDCA) has prepared this document to provide customers and installers information that the industry
EAST LYME HIGH SCHOOL
Overview: 1971 N 1966 GYM 1966 CLASSROOM WING 1966 AUD. 1971 GYM 1998 1998 POOL EAST LYME HIGH SCHOOL Original 1966 Building: The original East Lyme High School was constructed in 1966 and was composed
GYPSUM AREA SEPARATION FIREWALLS GA-620-2011
GYPSUM AREA SEPARATION FIREWALLS GA-620-2011 GA-620-2011 Copyright 2011 Gypsum Association All rights reserved. Printed in U.S.A. Characteristics, properties, or performance of materials or systems herein
How To Test For An Architectural Test
Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Rendered to: CORAL ARCHITECTURAL PRODUCTS SERIES/MODEL: PW 256 with Door Openings PRODUCT TYPE: Aluminum Impact Resistant Curtain Wall System
Comment Form on Proposed Gut Rehabilitation Alternatives
Comment Form on Gut Rehabilitation Alternatives Name: Organization: Email: Instructions Submission: Please submit this form to [email protected] by October 10 th, 2012 with the subject line
Manual lifting and handling
Manual lifting and handling When installing British Gypsum products and systems care should be taken to ensure that appropriate methods of handling and lifting are adopted. The following guidance details
Tested to BS 6375: Part 1: 1989 and achieved a weathertightness classification of 2000 Pa (Special)
THE B6 GLAZING SYSTEM GLAZING SYSTEMS FOR SEPTEMBER 2013 THE B6 HEEL BEAD SEAL SECURITY GLAZING SYSTEM Page 1 DESCRIPTION The B6 Heel Bead Seal Security Glazing System is suitable for installing all types
Installing Window and Door Mouldings
Installing Window and Door Mouldings About Window and Door Mouldings The trim around windows and doors greatly influences the look and style of your interior. They also bridge the gaps and cover spaces
GENERAL RUBBER LINING PRINCIPLES
GENERAL RUBBER LINING PRINCIPLES I. METAL PREREQUISITES Metal to be lined should meet the requirements as stated in section 8 Metal Fabrication and section 12 Blasting and Cementing Procedures. The surface
TEST REPORT. Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana
Architectural Testing TEST REPORT Report No.: D0162.02-201-44 Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana PRODUCT TYPE: Pressure Equalized Rainscreen SERIES/MODEL: 4 mm Composite
RELAZZO DECKING THE TERRACE. INSTALLATION GUIDE. Construction Automotive Industry. REHAU R20680 EN 05.2015 www.rehau.com/relazzo
Construction Automotive Industry RELAZZO DECKING THE TERRACE. INSTALLATION GUIDE REHAU R20680 EN 05.2015 www.rehau.com/relazzo Scan the QR code and learn more: RELAZZO DECKING THE TERRACE. Installation
ROOF FLASHING SPRINGLOK FLASHING SYSTEM FEATURES & BENEFITS PRODUCT DESCRIPTION
SPRINGLOK SYSTEM PRODUCT DESCRIPTION FEATURES & BENEFITS Fry Reglet offers five flashing systems, each tailored for a particular type of substrate so you can get exactly what you need. SM Surface mounted
Avoiding Air Barrier Pitfalls
Avoiding Air Barrier Pitfalls Design & Durability November 2013 Air barriers, when correctly installed, help buildings achieve high levels of energy efficiency by decreasing heat loss. For example, great
Installation Instructions
Installation Instructions READ BEFORE INSTALLING UNIT For Low Profile Window Air Conditioner INSTALLATION WARNINGS AND CAUTION Carefully read the installation manual before beginning. Follow each step
DE Frame with C Series Sidelight
TOOLS REQUIRED Tape measure 6' magnetic level 3' magnetic level Screw gun with clutch adjusted #2 phillips tip #3 phillips tip Screwdriver (used to adjust frame on will using oval slots) Pry Bar Powder
Residential Roofing Guide
Residential Roofing Guide TABLE OF CONTENTS Building Detail and Accessories...... 1 Panel Introduction and Handling...... 2 Cutting and Trimming.... 3 Roof Preparation..... 3 Roof Slope..... 3 Re-roofing...
Installation Guide for Andersen Architectural Clad Outswing Commercial Doors
Installation Guide for Andersen Architectural Clad Outswing Commercial Doors Congratulations! You have just purchased one of the many fine Andersen products. Proper assembly, installation and maintenance
FLASHMAN WINDOW AND DOOR FLASHING SYSTEM. Product. Scope. Appraisal No. 573 [2013]
FLASHMAN WINDOW AND DOOR FLASHING SYSTEM This Appraisal replaces BRANZ Appraisal No. 573 (2007). Amended 05 February 2016. BRANZ Appraisals Technical Assessments of products for building and construction.
This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.
Basement Finishing Guide Community Development Department Building Inspections Division 5200 85 th Avenue North / Brooklyn Park, MN 55443 Phone: (763) 488-6379 / Fax: (763) 493-8171 6/15 www.brooklynpark.org
VA25014B0516 VA CINCINNATI PROJECT NO. 539-328 INPATIENT BED TOWER ADDITION (4 TH AND 5 TH FLOORS) SECTION 09 29 00 GYPSUM BOARD
SECTION 09 29 00 GYPSUM BOARD PART 1 - GENERAL 1.1 DESCRIPTION This section specifies installation and finishing of gypsum board, vapor retarder and air and moisture barrrier. 1.2 RELATED WORK A. Installation
Chapter 3 Pre-Installation, Foundations and Piers
Chapter 3 Pre-Installation, Foundations and Piers 3-1 Pre-Installation Establishes the minimum requirements for the siting, design, materials, access, and installation of manufactured dwellings, accessory
UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS
UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS: Carefully read these instructions before installing your new air-conditioner. AUSTRALIAN AUTOMOTIVE AIR AL00500054E 1 Table
GreenGuard Housewrap Installation Guide
000768PACBPHW_Flashing Bro 5/23/03 2:52 PM Page 1 For the most current product information, go to www.green-guard.com. Pactiv Building Products believes the information and recommendations herein to be
Renovating Your Basement
building science.com 2006 Building Science Press All rights of reproduction in any form reserved. Renovating Your Building America Report - 0309 2003 (revised 2007) Building Science Corporation Abstract:
Brick Veneer Construction
Brick Veneer Construction Check list of suggested tools & support items Claw hammer Tape measure 3/4" [19 or 20] Wood chisel Wood or plastic shims Pry bar Utility knife Caulking and caulking gun Power
4 Installation Requirements
4 Installation Requirements 9 4.1 Code Reference The authority having jurisdiction should be referenced to determine what law, ordinance or code shall apply in the use of flexible duct. Ducts conforming
300mm. 2mm MIN GAP. PLACE 100mm X 100mm. SO THAT IT IS 38mm INTO
INSTALL PEEL & STICK (P&S) GUSSETS WITH PRIMER AS PER MANUFACTURERS INSTRUCTIONS 2mm MIN GAP IN SHEATHING STEP 1 PLACE 100mm X 100mm PIECE OF P&S IN CORNER SO THAT IT IS 38mm INTO THE OPENING EACH WAY
Mark Cramer Inspection Services, Inc.
Mark Cramer Inspection Services, Inc. 492 Twentieth Avenue, Indian Rocks Beach, FL 34635-2970 (727) 595-4211 Fax (727) 596-7583 Certified Member #12085 American Society of Home Inspectors Construction
Installation Instructions
Installation Instructions 1. Position the unit onto bridging packers. These keep the unit away from any water sitting inside the frame. 2. Centralise the unit within the frame and pack the edges with appropriate
Installation Instructions
Installation Instructions One-Piece Deep Wall Sleeve For Use with Packaged Terminal Units Please read these instructions completely before attempting installation. NOTE: Ensure that the unit is only installed
plumbing products guide
plumbing products guide radiator pipe guide & seals A significant development in the drive to reduce air leakage and heat loss. Installations such as that shown are all too common. The detail is poorly
12.1 Schlüter -KERDI-BOARD
I n n o v a t i v e p r o f i l e s 12.1 Schlüter -KERDI-BOARD S u b s t r a t e U N I V E R S A L S T R U C T U R A L P A N E L, B O N D E D W A T E R P R O O F I N G Application and Function Schlüter
GUIDELINES FOR INSTALLATION OF AIR CONDITIONING UNITS 174-180 PHILLIP STREET, SYDNEY
GUIDELINES FOR INSTALLATION OF AIR CONDITIONING UNITS 174-180 PHILLIP STREET, SYDNEY July 2008 1.0 SCOPE These guidelines describe the way in which air conditioning units shall be installed or replaced
LAYING BLOCK AND BRICK
LAYING BLOCK AND BRICK Products highlighted in this section: SAKRETE Type N Mortar Mix SAKRETE Type S Mortar Mix Brick And Block Laying Basics The first step in building a brick or block wall is to construct
After reading this lesson you will be able to: 12.3 IMPORTANCE OF ROOF 12.4 TYPES OF ROOF IN A HOUSE
86 :: Certificate in Construction Supervision (CIVIL) 12 ROOF 12.1 INTRODUCTION The structure provided to cover the house surface (floor) is known as roof. For different situation and requirement, it is
The Butler MR-24 Standing Seam Roof Difference. A comparison between metal roof systems
The Butler MR-24 Standing Seam Roof Difference A comparison between metal roof systems Roof Systems Necessities Weathertight (don t leak!) Low maintenance Weathertightness Roof clips, seams, panel alignment
CONSTRUCTION DETAILS & LOAD DESIGN CHARTS
Office and Production 126 New Pace Rd., PO Box 279 Newcomerstown, OH 43832 1-800-446-2188, Fax: 740-498-4184 www.buildwithsips.com CONSTRUCTION DETAILS & LOAD DESIGN CHARTS Table of Contents Description
Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association
Air-Conditioning, Heating, and Refrigeration Institute Sheet Metal and Air-Conditioning Contractors National Association GUIDELINE B-1997 ACKNOWLEDGEMENT These guidelines for Roof Mounted Outdoor Air-
SECTION 07 42 13 METAL WALL PANELS
Mitsubishi Plastics Composites America, Inc. 401 Volvo Parkway Chesapeake, VA 23320 Phone: (800) 422-7270 Fax: (757) 436-1896 E-mail: [email protected] www.alpolic-northamerica.com This MANU-SPEC utilizes
PLUMBING MAINTENANCE WORK FOR TOILETS IN HEAD OFFICE, SUPPLYCO ESTIMATE
Sl.No. PLUMBING MAINTENANCE WORK FOR TOILETS IN HEAD OFFICE, SUPPLYCO ESTIMATE Description of item Qty Unit Rate Amount 1 Demolishing tile work/cement concrete/( carefully taking out the closet and other
PERFORMANCE TEST REPORT. Rendered to: BAMCO INC. PRODUCT TYPE: ACM Wall Panel Systems
PERFORMANCE TEST REPORT Rendered to: BAMCO INC. PRODUCT TYPE: ACM Wall Panel Systems Summary of Results Title Test Specimen #1 Test Specimen #2 Air Infiltration