1 Fire Risk Mitigation in Mission Critical Facilities Mark L. Robin, PhD DuPont Chemicals & Fluoroproducts 2015 NFPA Conference & Expo McCormick Place in Chicago, IL June 23,
2 Air Traffic Control Towers: Mission Critical Typical Monday Morning Air Traffic Snapshot 2
3 Airline traffic at 10:20 a.m. EDT over the United States Sept. 26, 2014, following a fire at a suburban Chicago ATC Facility 3
4 Consequences of Fire at a Mission Critical Facility: Aurora ATC Facility More than 2,000 flights in and out of Chicago cancelled by evening of fire Flights as far away as Dallas cancelled Ultimate cancellation of 3900 flights in the four days following the fire a Cost to American, United and Southwest estimated in the hundreds of millions of dollars for each airline b $123 million cost in passengers lost economic activity a Some passengers diverted to Detroit a US Travel Association estimate b Boyd Group Int l estimate 4
5 Fires in Mission Critical Facilities: Recent Examples Facility Location Aurora ATC Tower Chicago, IL State Police Data Center Maryland, USA Iowa Legislative Building Samsung SDS Iron Mountain Cowboyminers NSA Spy Center Shaw Communications Iowa, USA Fires DO occur in Gwacheon, South Korea mission critical facilities Buenos Aires, Argentina Bangkok, Thailand Utah, USA Calgary, Canada Macomb County IT facility Michigan, USA Cowboyminers Fire Samsung SDS Facility Fire 5
6 Fire Risk in IT Facilities Fire History Typically involve small fires Potentially large impact Equipment, Data and Business Continuity at Risk Equipment and data loss High cost of downtime Leading cause: electrical distribution equipment Fire Hazard Wires, cables, cord, plugs, outlets Fuel load primarily electronic equipment and power cables: plastics 6
7 Electronic Equipment: Fire Damage Thermal Damage - Due to fire itself (heat) Non-thermal Damage: Combustion Products - Smoke, soot, water, acids Non-thermal Damage: Suppression Agent - e.g., water, foam, dry chemical Electronic equipment is very susceptible to damage from fire 7
8 Electronics: Thermal Damage Component Onset of Damage Storage media (magnetic tape, floppies, etc.) 125 o F (52 o C) Hard drives 150 o F (66 o C) Electronic components 174 o F (79 o C) Paper 350 o F (177 o C) Polystyrene cases, reels 650 o F (310 o C) Microfilm 225 o F (107 o C) Damage results in loss of equipment and data 8
9 Electronics: Non-Thermal Damage from Combustion Products Steam, Smoke, Soot, Various Combustion Products Hydrogen Chloride - From combustion of PVC - Reacts with galvanized zinc components forming ZnCl 2 - ZnCl 2 layer formed, reacts with humidity to produce a corrosive ZnCl 2 solution Corrosive Combustion Gases - HF, HBr, SO 2, CH 3 COOH, NO 2, HCN 9
10 Cost of Business Interruption Cost of datacenter downtime is high and getting higher Average cost per minute increased 41% from : $5,617 per minute 2013: $7,908 per minute Source: Ponemon Institute
11 Fire Protection Options for Mission Critical Facilities FOAM WATER CO 2 POWDER CLEAN AGENTS 11
12 Carbon Dioxide (CO 2 ) Extinguishment via oxygen depletion and heat absorption Is a clean agent Toxicity concerns CO 2 lethal at its required extinguishing concentrations 12
13 Powder-based Agents Efficient fire extinguishment via chemical interaction with flame All incorporate solid particles Corrosion concerns Major cleanup required Significant downtime 13
14 Foam Efficient extinguishment via separation of fuel from air Aqueous = Corrosion concerns Major cleanup required Significant downtime 14
15 Fire Protection Options for Mission Critical Facilities FOAM WATER Corrosive Extensive Clean-up CO 2 Corrosive Extensive Clean-up Toxic POWDER CLEAN AGENTS 15
16 Fire Protection Options for Mission Critical Facilities WATER- BASED SYSTEMS Required by code for STRUCTURE protection CLEAN AGENTS Protection of Structure s CONTENTS 16
17 Automatic Sprinkler Standards NFPA 13 Standard for the Installation of Sprinkler Systems Principle document addressing design and installation of sprinkler systems NFPA 72 National Fire Alarm Code NFPA 75 Standard for the Protection of Electronic Computer/Data Processing Equipment NFPA 76 Recommended Practice for the Fire Protection of Telecommunications Facilities 17
18 Automatic Sprinkler Systems: Design Objectives - In general terms of property protection, sprinkler systems are typically designed to achieve fire control... - Fire control can be described as limiting the fire size by decreasing the rate of heat release and pre-wetting adjacent combustibles, while maintaining ceiling gas temperatures so as to avoid structural damage NFPA Fire Protection Handbook, 19th Edition, p
19 Fire Control Heat Release Rate sprinkler activation Time 19
20 Automatic Sprinkler Systems Thermal Response Heat detection serves as basis of sprinkler system response fusible link glass bulb Activation at ceiling temperatures 135 o F Fire size at activation 100s of kw 20
21 Fire Protection Basics: Clean Agents Clean Agents NFPA 2001 (2015) Electrically nonconducting, volatile, or gaseous fire extinguishant that does not leave a residue upon evaporation. ISO Edition Minimum cleanup required No to minimum downtime 21
22 Clean Agent Fire Suppression Systems NFPA 2001 Standard for Clean Agent Fire Extinguishing Systems (2015) Total flooding agents Uniform distribution of agent throughout enclosure Ability to extinguish hidden and obstructed fires Primary Design Objective = Fire Extinguishment Rapid detection Rapid extinguishment Fire size at activation 0.1 to several kw 22
23 Clean Agent System vs. Sprinkler System (Fire Extinguishment vs. Fire Control) sprinkler activation FIRE CONTROL Heat Release Rate detection clean agent system activation FIRE EXTINGUISHMENT Time 23
24 Comparison Testing of Preaction Sprinkler and Clean Systems a Clean Agent System: FM-200 System designed and installed in accordance with NFPA 2001 Preaction Sprinkler System Designed and installed in accordance with NFPA 13 Detection/Alarm Systems Designed and installed in accordance with NFPA 72 In-cabinet fire: ABS sheets a M.L. Robin and E.W. Forssell, "Comparison Testing in a Simulated Data Processing/ Telecommunications Facility: FM-200 and Automatic Sprinkler Systems, 2004 Halon Options Technical Working Conference, May 4-6, 2004, Albuquerque, NM. 24
25 Fire Location 25
26 ABS Sheets 26
27 Preaction Sprinkler System Designed in accordance with NFPA 13 Based on Ordinary Hazard Class I classification Nine sprinkler heads in main space Nine sprinkler heads above suspended ceiling 11 ft spacing for area coverage of 121 ft 2 Maximum spacing allowed under NFPA 13 is 15 ft Recessed pendant standard response glass bulb sprinklers Temperature rating 135 o F Application density of 0.15 gpm/ft 2 required 27
28 FM-200 Suppression System Designed in accordance with NFPA % by volume FM-200 Discharge time: 9.5 seconds Hygood Ltd cylinder Hygood Ltd 8-port aluminum nozzle orifice area 1.57 in 2 System design via Hygood Ltd s design software 30 s delay employed from detection to system activation Maximum delay time allowed under recommendations of FM Global Property Loss Prevention Sheet 5-14 on Telecommunication Facilities 28
29 Results: Preaction Sprinkler System Photoelectric detector in NE corner in full alarm at 94 seconds from ignition Ionization detector in NE corner in full alarm at 112 seconds from ignition Complete obscuration due to smoke at approximately 240 seconds from ignition Sprinkler head in NE corner actuated at 273 seconds from ignition Sprinkler head in N corner actuated at 347 seconds from ignition 29
30 Results: Preaction Sprinkler System Fire not extinguished by sprinkler system IR camera shows fire burning through entirety of test Fire contained to source cabinet Max ceiling temperature of 560 o F observed at thermocouple tree nearest fire Fire Damage Entire cabinet and contents destroyed Non-Fire Damage Extensive water, smoke and soot damage 30
31 Results: Preaction Sprinkler System Non-Fire Damage Black ring around entire enclosure Ceiling tiles discolored Soot particles scrubbed from smoke layer cover floor, horizontal surfaces Walls discolored from smoke damage Water damage to paper goods 31
32 Pre-action System 32
33 Pre-action System 33
34 Pre-action System 34
35 Pre-action System 35
36 Pre-action System 36
37 Pre-action System 37
38 Pre-Action Sprinkler System Performance Summary Design objective attained: Fire was controlled System performed exactly as expected Fire contained to origin Ceiling temperatures managed such that structural damage and/or collapse did not occur Structure saved 38
39 Results: FM-200 System AnaLASER II alarmed at 78 seconds from ignition FM-200 system activated at 108 seconds from ignition Fire extinguished at 125 seconds from ignition 7 seconds from end of system discharge No change in ceiling temperatures Fire damage Slight scorching of inside of test cabinet Non-fire damage Several ceiling tiles displaced 39
40 FM-200 System: Before.. 40
41 FM-200 System: After.. 41
42 FM-200 System Performance Summary Design objective attained: Fire extinguished System performed exactly as expected Contents of structure saved 42
43 Fire Risk Management 101 Fire risk analysis is a process to characterize the risk associated with fire that addresses the fire scenario or fire scenarios of concern, their probability, and their potential consequences. Risk factors to be considered include life safety and (direct and indirect) economic losses from the loss of function (capacity) or data, loss of professional reputation, and the costs of redundant systems R.W. Bukowski, Fire Protection Engineering Emerging Trends, Issue 76 (09/2013) Risk Considerations for Data /Center Fire Protection 43
44 Fire Risk Management 101 KEY ELEMENTS 1. Risk 2. Scenario 3. Probability 4. Consequences Direct Indirect Mission Critical Facilities: Equipment-related fire Cables, electronic equipment NOT zero Due to fire and extinguishant Ex: Business interruption 44
45 Fire Risk Management Standards & Guides SFPE Engineering Guide: Fire Risk Assessment (SFPE G ) NFPA 551 Guide for the Evaluation of Fire Risk Assessments NFPA Handbook of Fire Protection, Chapter 8, Section 3, Fire Risk Analysis ASTM E a Standard Guide for Development of Fire-Hazard-Assessment Standards 45
46 Mission Critical Facility Fire Protection Sprinkler and Clean Agent systems vastly different Design objectives different: Control vs Extinguishment Preaction systems best suited to protection of structure Clean agent systems best suited to protection of contents of structure Sprinkler systems alone inappropriate for protection of high value assets Clean agents not ideally suited for structural protection Loss during a fire NOT limited to fire damage Potential loss differs for clean agent vs sprinkler systems 46
47 Quantifying Loss: Direct vs. Indirect Costs of Fire Losses and costs associated with a fire are not limited to the equipment involved in the fire Direct: Equipment involved in the fire Data Historical and Intellectual Property Financial records Cost of Clean up Indirect: Business interruption & downtime Insurance Lawsuits Collateral Damage Loss of customer confidence 47
48 Shaw Datacenter Fire: Minimum Fire Protection and Its Consequences The potential consequences of adopting a minimum protection approach to fire protection can be clearly seen in the results of the recent Shaw datacenter outage in Calgary 48
49 Shaw Datacenter Fire: Transformer fire sets off sprinkler system Sprinklers take out backup systems housed on site Knockout out of primary and backup systems supporting key public services Crippled city services, including 311 services Delay of 100s of surgeries at local hospitals IBM Canada forced to fly backup tapes holding vehicle and property registration data to a backup facility in Markham, Ontario 49
50 Shaw Datacenter Fire: Extensive water damage to furniture, walls and sensitive electronic equipment on the floors below the top story fire location Temporary relocation of over 900 Shaw employees while damage is repaired Six days of service outage 50
51 Shaw Datacenter Fire: More than 20,000 Shaw business and household clients watched their cable, telephone and Internet services disappear almost immediately City and provincial clients watched their own networks go dark as the water trickled down, affecting other data companies below the fire. Some cellular carriers were also said to be affected, as well as ATB banking services, ATMs and debit terminals throughout the city 51
52 Shaw Datacenter Fire: Competitor Q9 Networks Inc., which operates three data centres in the city, has early detection systems that can detect smoke and use gases that don t harm people to prevent fires from starting. Water needs to be there by law, said Q9 chief executive Osama Arafat, but you want to try and deal with a fire using less destructive means first. Source: 52
53 Case Study: Iowa State Legislature Building Datacenter Fire: February 18, 2014 Mission Critical Facility Payroll processing for state employees was scheduled for that evening Dept of Revenue needed to process tax collections. Justice Dept needed to process claims and fee payments. 53
54 Iowa Legislature Fire Timeline 3pm Fire ignites: FM-200 System deploys 9pm Data Center Cleared of burnt equipment 2am Major websites and agency systems restored 3am Remaining major agency applications restored 54
55 Fire Protection for Mission Critical Facilities Fires DO Occur in Mission Critical Facilities Risk, Consequences, Losses dependent on facility & fire protection system Sprinklers : fire control/structure protection Clean agents: fire extinguishment/content protection Substantial risk reduction at very high benefit/cost ratios may be realized by protecting sensitive, valuable and mission-critical assets, such as those found in IT and telco facilities, with both a clean agent system and a sprinkler system. 55
56 Thank You 56
Fire Protection Options for Data Centres
Fire Protection Options for Data Centres Mark L. Robin, PhD DuPont Chemicals & Fluoroproducts mark.l.robin@usa.dupont.com Introduction Modern data centres are characterized by spaces filled with ever-increasing
More informationDuPont FM-200 COMPARISON TESTING IN A SIMULATED DATA PROCESSING/TELECOMMUNICATIONS FACILITY
DuPont FM-200 COMPARISON TESTING IN A SIMULATED DATA PROCESSING/TELECOMMUNICATIONS FACILITY DuPont FM-200 and Automatic Sprinkler Systems Mark L. Robin and Eric W. Forssell, DuPont Fluoroproducts Data
More informationCOMPARISON TESTING IN A SIMULATED DATA PROCESSING/ TELECOMMUNICATIONS FACILITY: FM-200 AND AUTOMATIC SPRINKLER SYSTEMS
COMPARISON TESTING IN A SIMULATED DATA PROCESSING/ TELECOMMUNICATIONS FACILITY: FM-200 AND AUTOMATIC SPRINKLER SYSTEMS Mark L. Robin and Eric W. Forssell Hughes Associates, Inc. 5415 Hillside Lane West
More informationFIRE PROTECTION. FOR COMPUTER ROOMS By Mark L. Robin CLEAN AGENT. FS-World.com. 8 ire & Safety Magazine
S-World.com CLEAN AGENT IRE PROTECTION OR COMPUTER ROOMS By Mark L. Robin Mark L. Robin, Ph.D., is Technical Services Consultant for Specialty luorochemicals with DuPont luoroproducts and has over 20 years
More informationmelbourne//australia data center specifications internet + intellectual property + intelligence tel: +61 2 9948 8888 fax: +61 2 9948 1111
internet + intellectual property + intelligence We thank you for the opportunity to work with you regarding your colocation needs in Melbourne,. We can colocate standard rack-mountable servers or other
More informationAll You Ever Wanted to Know About Fire Extinguishers...
All You Ever Wanted to Know About Fire Extinguishers... There are basically four different types or classes of fire extinguishers, each of which extinguishes specific types of fire. Newer fire extinguishers
More informationAlarm and Detection/Suppression
Alarm and Detection/Suppression Fire Safety American Fire Technologies To provide special hazard services world wide to the industrial market through the integration of components and services Clean Agent
More informationAmerex CPS FM-200 Waterless Pre-engineered Fire Suppression System
Amerex CPS FM-200 Waterless Pre-engineered Fire Suppression System A Simple Solution An Affordable Approach An Industry Innovation I N T R O D U C T I O N A SIMPLE SOLUTION. AN AFFORDABLE How many days
More informationRelative Sensitivity based Fire Detection Systems used in High Density Computer Rooms with In-Row Air Conditioning Units
Relative Sensitivity based Fire Detection Systems used in High Density Computer Rooms with In-Row Air Conditioning Units By Suresh Soundararaj & David Admirand, PE Experts for Your Always Available Data
More informationData Centre alwas protected always up and running.
Data Centre alwas protected always up and running. Stefano Valdrighi - Siemens Business continuity is the critical asset to protect 609,500 Average cost per downtime 7,908 Average cost per minute The total
More information10/10/2011. Reducing Losses by Restoration. BELFOR Worldwide Leader in Restoration. BELFOR Restoration - a brief definition Equipment restoration
Reducing Losses by Restoration BELFOR Restoration - a brief definition Equipment restoration Definition Process Cases Conclusion www.belfor.com BELFOR Worldwide Leader in Restoration Some 4.600 Employees
More informationWHITE PAPER Fire & safety performance standards
WHITE PAPER Fire & safety performance standards Terminologies describing Fire Performance Terminologies describing Fire Performance often present a challenge to understand as how they apply to a cable
More informationValidation of Modeling Tools for Detection Design in High Airflow Environments
Validation of Modeling Tools for Detection Design in High Airflow Environments Joshua B. Dinaburg Dr. Jason Floyd, Ph.D. Dr. Sai Thumuluru, Ph.D FM Global MODELING DETECTION RESPONSE Establish validated
More informationPLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS
January 1997 PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS 1.0 PERMIT 1.1 After receipt of a Building Permit from the City of San Jose Building Department, submit
More informationOntario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal
Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable
More informationAerosol Fire Suppression. Your Choice for Special Hazard Fire Protection
Aerosol Fire Suppression Your Choice for Special Hazard Fire Protection Traditional Special Hazard Fire Protection Centers Around Two Technologies Water deluge and chemical agent fixed systems protect
More informationFor Data Center and Control Room Applications
For Data Center and Control Room Applications Nearly zero wetting No costly clean up or equipment replacement Sustainable design Quick system recharge, minimal downtime No need for assurance of tight room
More informationCombustible Dust - Things that go Boom. W. Jon Wallace, CSP, MBA Workplace Group, LLC O: 919.933.5548 E: jwallace@workplacegroup.
Combustible Dust - Things that go Boom W. Jon Wallace, CSP, MBA Workplace Group, LLC O: 919.933.5548 E: jwallace@workplacegroup.net Presentation Objectives After attending this presentation you will: Learn
More informationVehicle Fire Protection. An Ownerʼs Manual for ANSUL Fire Suppression/Detection Systems
Vehicle Fire Protection An Ownerʼs Manual for ANSUL Fire Suppression/Detection Systems 002792 Off-road vehicles do have fires Statistics show that off-road vehicles burn with alarming frequency. These
More informationMODELING THE PERFORMANCE OF FIRE PROTECTION SYSTEMS IN MODERN DATA CENTERS
MODELING THE PERFORMANCE OF FIRE PROTECTION SYSTEMS IN MODERN DATA CENTERS Richard W. Bukowski. P.E., FSFPE and Ralph Transue, P.E. Rolf Jensen and Associates, Chicago, IL 60661 USA Data Centers Society
More informationEFSN Training i Module 1. 90 Minutes
Introduction to Sprinklers EFSN Training i Module 1 90 Minutes Topics How sprinklers work Performance of sprinkler systems Types of Sprinkler Introduction to sprinkler systems Introduction ti to sprinkler
More informationDennis Fire Department Fire Prevention Mark Dellner Fire Chief
Dennis Fire Department Fire Prevention Mark Dellner Fire Chief FIRE SAFETY INSPECTION GUIDELINES FOR COMMERCIAL PROPERTIES (MA Fire Prevention Regulations 527 CMR, MGL Chapter 148) FIRE PREVENTION CHECKLIST-
More informationFire Alarm System Accessories
Approved by APPROVED Fire Alarm System Accessories FM Approved* Intrinsically Safe Devices Single and Dual Channel Isolated Barrier Modules Features Single or dual channel intrinsically safe, transformer
More informationGeneral Fire Code Requirements Within Commercial Tenant Spaces
FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding
More informationANNUAL FIRE PROTECTION SUMMARY INFORMATION REPORTING GUIDE Revised: May 2011
ANNUAL FIRE PROTECTION SUMMARY INFORMATION REPORTING GUIDE Revised: May 2011 Organizations responsible for maintaining property under stewardship of DOE and the Administrator, NNSA, will seek concurrence
More informationClass A - Wood, paper, cloth, trash, plastics Solid combustible materials that are not metals. (Class A fires generally leave an Ash.
Not all fires are the same, and they are classified according to the type of fuel that is burning. If you use the wrong type of fire extinguisher on the wrong class of fire, you can, in fact, make matters
More informationFire Life Safety ORC Review Guidelines for PPD Experimental Installations
Fire Life Safety ORC Review Guidelines for PPD Experimental Installations Fire Protection Review for the Fixed Target ES&H Review Committee September 2010 By James Priest PhD DRAFT Overview: When reviewing
More informationOverview. Components of an alarm system Technology behind the equipment Communication Platforms Industry Terminology False Alarm Tips DSC products
Basic Security 101 Overview Components of an alarm system Technology behind the equipment Communication Platforms Industry Terminology False Alarm Tips DSC products Components of an Alarm System Main Control
More informationStatic Electricity. A Health and Safety Guideline for Your Workplace. What Are Some Sources of Static Electricity? What is Static Electricity?
A Health and Safety Guideline for Your Workplace What is static electricity? What causes it? How is it hazardous? And, most importantly, how can it be controlled? All of these questions will be answered
More informationFire Security Systems
Fire Security Systems Fire Security Systems mail@fire-security.net www.fire-security.net P: 1 604 941 1001 F: 1 604 648 9311 Who is Fire Security Systems For 25 years, Fire Security has been involved in
More informationLEVEL 3 DATA CENTER ASSESSMENT
Nationwide Services Corporate Headquarters 410 Forest Street Marlborough, MA 01752 USA Tel: 800-342-5332 Fax: 508-303-0579 www.eecnet.com LEVEL 3 DATA CENTER ASSESSMENT Submitted by: Electronic Environments
More informationData Centre Services. JT First Tower Lane Data Centre Facility Product Description
JT First Tower Lane Data Centre Facility Product Description JT s Data Centre Hosting Service provides a secure computer room enviroment with protected incoming power supplies, state-of-the-art security
More informationFire Performance Standard
Fire Performance Standard At present, in cable industry, Fire Retardant, Low Smoke Halogen Free (LSZH), Low Smoke Fume (LSF) and Fire Resistant cables are all described as Fire survival Cables. Flame Retardant
More informationFor Data Center and Control Room Applications
For Data Center and Control Room Applications Nearly zero wetting No costly clean up or equipment replacement Sustainable design Quick system recharge, minimal downtime No need for assurance of tight room
More informationFIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or comments regarding the
More informationWHMIS After GHS: Preparing for Change. Canadian Centre for Occupational Health and Safety
WHMIS After GHS: Preparing for Change Canadian Centre for Occupational Health and Safety 1. About this publication WHMIS is changing. The substance of WHMIS (labels, MSDSs, and training) will remain, but
More informationMechanical Systems Competency 1.20
Competency 1.20 Mechanical systems personnel shall demonstrate a working level knowledge of the safety and health fundamentals of mechanical systems and/or components. 1. Supporting Knowledge and Skills
More informationData Centre Services. JT Rue Des Pres Data Centre Facility Product Description
JT Rue Des Pres Data Centre Facility Product Description JT s Data Centre Hosting Service provides a secure computer room environment with protected and backup power, security and bandwidth. Data Centre
More informationFIRE SAFETY FOR OFFICE WORKERS
FIRE SAFETY FOR OFFICE WORKERS This easy-to-use Leader s Guide is provided to assist in conducting a successful presentation. Featured are: INTRODUCTION: A brief description of the program and the subject
More informationNMSU FIRE DEPARTMENT Commercial Kitchen Fire Suppression Worksheet
This Commercial Kitchen Automatic Fire has been created to assure all documentation has been submitted to assist you in assuring proper plans and documentations has been submitted and reviewed by New Mexico
More informationApproval Standard for Plastic Suspended Ceiling Panels
Approval Standard for Plastic Suspended Ceiling Panels Class Number 4651 February 1978 2002 FM Approvals LLC. All rights reserved. Foreword The FM Approvals certification mark is intended to verify that
More informationFIRE-FIGHTING DESIGN BRIEF REPORT
P a g e 1 SECTION 04 (Doc.No.A/DBR 001) FIRE-FIGHTING DESIGN BRIEF REPORT P a g e 2 1.0 SCOPE 2.0 STANDARDS AND CODES 3.0 TYPES OF SYSTEM PROPOSED 4.0 FIRE HYDRANT SYSTEM 5.0 AUTOMATIC SPRINKLER SYSTEM
More informationFLORIDA A&M UNIVERSITY FIRE SAFETY AND EMERGENCY GUIDELINES FOR RESIDENT ADVISORS AND RESIDENT ASSISTANTS
FLORIDA A&M UNIVERSITY FIRE SAFETY AND EMERGENCY GUIDELINES FOR RESIDENT ADVISORS AND RESIDENT ASSISTANTS PREPARED BY OWEN N. HART, SR. ENVIRONMENTAL HEALTH AND SAFETY PLANT OPERATIONS BUILDING UNIT 'A'
More informationWatermist fire suppression systems for commercial low hazard occupancies
Watermist fire suppression systems for commercial low hazard occupancies Watermist fire protection systems are fire suppression systems that have emerged as an alternative fire safety solution for specific
More informationCoastside County Water District Board of Directors
To: From: Coastside County Water District Board of Directors David Dickson, General Manager Report Date: February 5, 2014 Subject: District Office Fire Recovery Recommendation: None. Information only.
More informationFighting Fire in Sprinklered Buildings. Student Guide
Fighting Fire in Sprinklered Buildings Student Guide Fighting Fire in Sprinklered Buildings Student Guide Table of Contents Purpose........................................................... 3 Instruction
More informationFire Detection, Protection, and Suppression Systems. Objectives (1 of 5) Objectives (2 of 5) Chapter 36
Fire Detection, Protection, and Suppression Systems Chapter 36 Objectives (1 of 5) Explain why all firefighters should have a basic understanding of fire protection systems. Describe the basic components
More informationFIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011, Updated March 2012 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or
More informationFIRE EXTINGUISHER TRAINING
FIRE EXTINGUISHER TRAINING Fire safety, at its most basic, is based upon the principle of keeping fuel sources and ignition sources separate. Three things must be present at the same time to produce fire:
More informationFACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST
FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST Date of Inspection: Conducted by: Location: Reviewed by: Date of Review: Comments or additional corrective action taken as a result
More informationSecurity+ Guide to Network Security Fundamentals, Fourth Edition. Chapter 13 Business Continuity
Security+ Guide to Network Security Fundamentals, Fourth Edition Chapter 13 Business Continuity Objectives Define environmental controls Describe the components of redundancy planning List disaster recovery
More informationIAC 6/17/09 Public Safety[661] Ch 275, p.1 CHAPTER 275 CERTIFICATION OF AUTOMATIC FIRE EXTINGUISHING SYSTEM CONTRACTORS
IAC 6/17/09 Public Safety[661] Ch 275, p.1 CHAPTER 275 CERTIFICATION OF AUTOMATIC FIRE EXTINGUISHING SYSTEM CONTRACTORS 661 275.1(100C) Establishment of program. There is established within the fire marshal
More informationsingapore//singapore data center specifications tel: +61 2 9948 8888 fax: +61 2 9948 1111 internet + intellectual property + intelligence
internet + intellectual property + intelligence We thank you for the opportunity to work with you regarding your colocation needs in Singapore. We can colocate standard rack-mountable servers or other
More informationData Center Infrastructure & Managed Services Outline
Data Center Infrastructure & Managed Services Outline The 360 Technology Center Solutions Data Center is located in Lombard, IL, USA. We are 20 minutes outside of downtown Chicago. The 360TCS staff consists
More informationChallenges for Use of Fixed Fire Suppression Systems in Road Tunnel Fire Protection
Challenges for Use of Fixed Fire Suppression Systems in Road Tunnel Fire Protection Z. G. Liu *, A. Kashef, G. Lougheed, and A. K. Kim Fire Research Program, Institute for Research in Construction National
More informationFLAMMABLE AND COMBUSTIBLE LIQUIDS. n OSHA Changes
FLAMMABLE AND COMBUSTIBLE LIQUIDS OSHA Changes Introduction This module covers the two primary hazards associated with flammable and combustible liquids: explosion and fire. In order to prevent these hazards,
More informationDisaster Ready. By: Katie Tucker, Sales Representative, Rolyn Companies, Inc
By: Katie Tucker, Sales Representative, Rolyn Companies, Inc Are you and your facility disaster ready? As reported by the Red Cross, as many as 40 percent of small businesses do not reopen after a major
More informationPerformance of Smoke Detectors and Sprinklers in Residential and Health-Care Occupancies
Performance of Smoke Detectors and Sprinklers in Residential and Health-Care Occupancies James A. Milke, Ph.D., P.E., A.J. Campanella, Cathleen T. Childers and Brittany D. Wright Department of Fire Protection
More informationFire Extinguishers. A Health and Safety Guideline for Your Workplace. Fire Extinguishing Methods. Introduction. Types of Extinguishers
A Health and Safety Guideline for Your Workplace Introduction Fire extinguishers are designed to put out or control small fires. A small fire, if not checked immediately, will soon spread out of control.
More informationCBD-233. Fire Alarm and Detection Systems
Page 1 of 5 CBD-233. Fire Alarm and Detection Systems Originally published August 1984. R.H.L. McEwen Fire alarm systems are normally required by building codes. In the case of new buildings, this is usually
More informationFlammable Liquids 29 CFR 1910.106
Flammable Liquids 29 CFR 1910.106 OSHA s Directorate of Training and Education These materials were developed by OSHA s Directorate of Training and Education and are intended to assist employers, workers,
More informationfire detection CCTV access control alarms network cabling Camdetech Technologies (Pty) Ltd. Reg. No: 2000 / 028631 / 07 COMPANY PROFILE
Camdetech Technologies (Pty) Ltd. Reg. No: 2000 / 028631 / 07 COMPANY PROFILE Introduction Camdetech is a quality driven company and in terms of the ISO 9001 commitment offers only the finest equipment
More informationAnnual Fire Safety Training Module
Annual Fire Safety Training Module 6 March 2014, v4 1 Course Overview: Annual Fire Safety Training This training module has been developed for workers at the University of Queensland, and forms part of
More informationFull scale tunnel fire tests of VID Fire-Kill Low Pressure Water Mist Tunnel Fire Protection System in Runehamar test tunnel, spring 2009
Full scale tunnel fire tests of VID Fire-Kill Low Pressure Water Mist Tunnel Fire Protection System in Runehamar test tunnel, spring 2009 By Carsten Palle, VID Fire-Fill, www.vid.eu Presented at ISTSS
More informationEXETER TOWNSHIP DRY OR WET CHEMICAL FIRE SUPPRESSION SYSTEMS
DRY OR WET CHEMICAL FIRE SUPPRESSION SYSTEMS POLICY STATEMENT This policy applies to NEW Dry or Wet chemical fire suppression systems. The Authority Having Jurisdiction will not waive major criteria in
More informationIMPORTANT INSTRUCTIONS & OPERATING MANUAL. Houston 50 Inch Electric Wall Mounted Fireplace Black / White
IMPORTANT INSTRUCTIONS & OPERATING MANUAL Houston 50 Inch Electric Wall Mounted Fireplace Black / White Model Number:MFE5050BK Model Number:MFE5050WH Read these instructions carefully before attempting
More informationOur data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.
AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled
More informationExperience Matters...
Experience Matters... Travelport Data Center offers confidence and space to meet your demanding IT needs Transwestern presents the Travelport Data Center in Denver, Colorado totaling 267,000 SF with 121,600
More informationFire Event Electronic and Mechanical System Damage Mechanisms Is Acid Gas for Real?
Equipment Damage Consultants, LLC Fire Event Electronic and Mechanical System Damage Mechanisms Is Acid Gas for Real? Irreparable damage to electronic equipment and mechanical systems away from the actual
More informationQuality Assurance Calendar Maintenance Responsible Party Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Generator fire up Generator 1 hour load test Generator 4 hour load test Fire extinguisher integrity checks Fire extinguisher certification Fire drills Fire door integrity Fire signage lighting Fire alarm
More informationEXPERIMENT 12: Empirical Formula of a Compound
EXPERIMENT 12: Empirical Formula of a Compound INTRODUCTION Chemical formulas indicate the composition of compounds. A formula that gives only the simplest ratio of the relative number of atoms in a compound
More informationANNEXURE 07: CHECK-LIST FOR OFF-SITE STORAGE FACILITIES
ANNEXURE 07: CHECK-LIST FOR OFF-SITE STORAGE FACILITIES NAME OF PRIVATE STORAGE FACILITY: DATE VISITED: 1. COMPANY PROFILE 1.1 What is the company's mission? 1.2 How does that mission compare with the
More information12 Things Facility Managers Need to Know About Critical Power System Installation
12 Things Facility Managers Need to Know About Critical Power System Installation Are you considering managing your next power system installation in-house? As a facilities manager or other facility professional,
More informationThe Collection of Topics which Comprise Fire Protection Engineering
The Collection of Topics which Comprise Fire Protection Engineering FCIA Key Biscayne, FL November 12, 2009 Jim Milke, Professor and Assoc. Chair Department of Fire Protection Engineering University of
More informationFOR CERTIFICATION AS PRESCRIBED BY THE STATE FIRE PREVENTION COMMISSION ON NOVEMBER 11, 2009 IN ACCORDANCE WITH THE STATE FIRE PREVENTION REGULATIONS
EXAMINATION REQUIREMENTS FOR FIRE SUPPRESSION SYSTEM CERTIFICATION AS PRESCRIBED BY THE STATE FIRE PREVENTION COMMISSION ON NOVEMBER 11, 2009 IN ACCORDANCE WITH THE STATE FIRE PREVENTION REGULATIONS REGULATION
More informationDATA CENTER FIRE PROTECTION
DATA CENTER FIRE PROTECTION DATA CENTER FIRE PROTECTION The following is a summary of a few key fire protection, detection, and suppression technologies used by Minimax Fire Solutions in data centers and
More informationFIRE PREVENTION PLAN
FIRE PREVENTION PLAN 1 FIRE PREVENTION PLAN OSHA s Fire Prevention Plan regulation, found at 29 CFR 1910.38(b) and 29 CFR 1926.24, requires Northern Clearing, Inc. to have a written fire prevention plan
More information3M Novec 1230 Fire Protection Fluid For Telecommunications and Data Center Applications. Stay
3M Novec 1230 Fire Protection Fluid For Telecommunications and Data Center Applications Stay in Touch 3M Novec 1230 Fire Protection Fluid For Telecommunications and Data Center Applications Engineered
More informationData Center Presentation
Data Center Presentation The NetSource Datacenter. Agenda General Layout of Data Center Policies and Procedures Designed to Latest Standards High Performance High Reliability High Security Design Details
More information9/15/2011. Presented by: Jason Reason, CIH, CSP, CHMM Senior Industrial Hygienist Indiana Occupational Safety and Health Administration
OSHA Combustible Dust Inspections Presented by: Jason Reason, CIH, CSP, CHMM Senior Industrial Hygienist Indiana Occupational Safety and Health Administration Overview Background Information OSHA Combustible
More informationand Extinguisher Training
RACES Field Operations Course -Unit 10 Fire Safety Awareness and Extinguisher Training Developed in cooperation with the National Fire Protection Association and the Public Information and Life Safety
More informationThe Fire Safety Manager at 312 791 6079 (FAX 312 791 6013) can answer any questions or provide a set of fire code information.
FIRE SAFETY REGULATIONS Fire Prevention reserve the right to make any final decisions regarding the outlined requirements, according to Section 2 36 220 of the Municipal Code of Chicago on Fire Prevention.
More informationTYPICAL FIRE SAFETY INSPECTION VIOLATIONS
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to
More informationBUILDING DYNAMICS, LLC
BUILDING DYNAMICS, LLC www.building-dynamics.com INDUSTRIAL HYGIENE 1216 Ashton Road Ashton, MD 20861 240.899.6926 (mobile) elight@building-dynamics.com HVAC ENGINEERING 703.963.0824 (mobile) jbailey@building-dynamics.com
More informationManchaca Fire / Rescue Probationary Firefighter Academy. Salvage and Overhaul. SFFMA Section 5: Salvage and Overhaul
Manchaca Fire / Rescue Probationary Firefighter Academy Salvage and Overhaul SFFMA Section 5: Salvage and Overhaul Loss Control Definition Salvage and overhaul operations are grouped together into the
More informationCertificate of Conformity Certificate num. Registration date Version Valid until
CSIRO Verification Services Highett, Victoria, Australia +61 (0)3 9252 6000 http://www.activfire.gov.au/ Page 1 of 5 Issued by Product designation Thorn Security, FM-200, engineered gaseous 'total flooding',
More informationRestoring Peace of Mind.SM
Contact Information Emergency Fire & Smoke Service Understanding Fire & Smoke Damage Service Explantation & Checklist Frequently Asked Questions Restoring Peace of Mind.SM important contact information
More informationWorking Towards Protection Guidance for Warehouse Storage Li-ion Batteries
Working Towards Protection Guidance for Warehouse Storage Li-ion Batteries Benjamin Ditch, FM Global Tom Long, Exponent Inc. SUPDET 2016, March 1 4, San Antonio TX Experimental Knowledge Timeline Reducedcommodity
More informationFedEx s Fire Suppression System
FedEx s Fire Suppression System In September of 1996 a FedEx DC-10 had an in flight fire. While the crew was able to land and evacuate the aircraft, the aircraft hull and its entire contents were destroyed.
More informationNYC SUB-SYSTEMS INSTALLATION & SERVICE REQUIREMENTS OF THE FDNY
NYC SUB-SYSTEMS INSTALLATION & SERVICE REQUIREMENTS OF THE FDNY Presented by: James Goerl Metro Protection Systems, Inc. jgoerl@metroprotectionsystems.com Agenda Introduction & Learning Objectives History
More informationEMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM
EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29CFR1910.36-29CFR1910.38-29CFR1910.157-29CFR1910.165 NFPA-10 BASIS: The OSHA Emergency Action Planning and the
More informationResponse, Reliability and Results. for Managed Property
Response, Reliability and Results for Managed Property Contents Response, Reliability and Results 1 Profit from your property 2 Property Performance Services 3 Energy assessments - beyond compliance 4
More informationClick here to see a video example of cable being burned outside the controlled lab environment. UL-910 Test for Flame-Propagation and Smoke Density
Plenum (CMP) Rated Cable Often found on building material lists, the Plenum rating (CMP) signifies cable that has passed stringent burn testing and is suitable for installation into Air Plenum spaces.
More informationOxidation States of Copper Two forms of copper oxide are found in nature, copper(i) oxide and copper(ii) oxide.
The Empirical Formula of a Copper Oxide Reading assignment: Chang, Chemistry 10 th edition, pp. 55-58. Goals The reaction of hydrogen gas with a copper oxide compound will be studied quantitatively. By
More informationUse Of Residential Fire Sprinklers In New Housing Projects
STAFF REPORT ACTION REQUIRED Use Of Residential Fire Sprinklers In New Housing Projects Date: May 22, 2007 To: From: Wards: Reference Number: Community Development and Recreation Toronto Fire Services
More informationFIRE SAFETY ONLINE TRAINING
INTRODUCTION This Fire Safety Training module is designed to teach you preventive measures that will eliminate or minimize causes of fire or fire hazards in the workplace, and to teach you proper emergency
More informationEXHIBIT A SCOPE OF WORK
EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,
More informationEmergency Evacuation Plan: 232 King St.
Emergency Evacuation Plan: 232 King St. Effective Date: July 2003 Revisions: 0 Approved on: April 20, 2004 Table of Contents 1.0 Building Resources... 1 2.0 Human Resources... 2 3.0 Definitions... 3 4.0
More informationWEEKLY SAFETY MEETING All Euramax Subsidiaries COMBUSTIBLE DUST. Safety Meeting Contents. Meeting Notice. Leaders Guide.
Safety Meeting Contents Meeting Notice Leaders Guide Employee Handout Employee Quiz Meeting Sign-In Sheet Employee Puzzle PRIOR TO THE WEEKLY MEETING: - Post the meeting notice by the timeclock - Read
More information