Top 5 Trends in Data Center Energy Efficiency
|
|
- Arthur Daniel
- 8 years ago
- Views:
Transcription
1 Top 5 Trends in Data Center Energy Efficiency By Todd Boucher, Principal Leading Edge Design Group Copyright 2012 Leading Edge Design Group 1
2 In 2007, the US Environmental Protection Agency delivered its Report to Congress on Server and Data Center Efficiency Opportunities, in which they stated that the nation s data centers accounted for 1.5% of the total electrical consumption in the United States, or about 61 billion kilowatt-hours (kwh). Since the release of this report, the focus on efficiency and sustainability in the data center has risen exponentially with product and design innovation, government programs focused on data center efficiency, utility company incentives, and most importantly, owner commitment to improving the efficiency of their data center operations. As with any great dialogue, there are varying opinions on what constitutes an energy efficient data center and what strategies yield the most significant reductions in energy consumption. Every data center environment is unique, and the methodologies selected to improve efficiency in your data center should be developed specific to the design conditions of your existing environment, your tolerance for change in the data center, and the projected Return on Investment (ROI) realized from the selected upgrades. However, because most data centers on average are 10 years old, there are a number of changes that can be made that will improve efficiency and reduce operating costs. Increased Supply Air Temperature One of the most impactful efficiency improvements that you can make in your data center is often times the easiest to implement increasing your supply air temperature set point. ASHRAE TC expanded the envelope for recommended operating conditions in the data center; this widened envelope increased the upper limit of the recommended temperature range in the data center from 77 F to 80.6 F (see Figure 1). Given that most data centers today operate in the 68 F to 72 F temperature range 1, substantial efficiency increases can be made through adjustments to your supply air temperature. Every degree you are able to increase your supply air temperature will yield an approximate energy savings of 3%-4%, and many organizations are taking steps to implement these temperature set point changes. Before making any changes to your supply air set points, it is important to ensure that you are measuring temperature in the right locations. It is critical that your supply air temperature in the data center represents the temperature at the server intake only. Many legacy data centers measure temperature via wall-mounted thermostats, which inaccurately represent the actual temperature of the air at the server intake locations. If necessary, relocate temperature monitors to the front of your data center racks before adjusting your set points. In addition, it is recommended that you implement the changes incrementally (one or two degrees at a time) in order to properly monitor the impact that it will have on the environmental condition of your 2004 Version 2008 Version Low End Tempature 20 C [68 F] 18 C [64.4 F] High End Tempature 25 C [77 F] 27 C [80.6 F] Low End Tempature 40% RH 5.5 C DP [41.9 F DP] High End Tempature 50% RH 60% RH &15 C DP [59 F DP) Figure vs Operating Envelope Copyright 2012 Leading Edge Design Group 2
3 data center, as a legacy data center facility is likely not configured to support the upper limits of this temperature threshold. Containment & Airflow Management In order to fully take advantage of the efficiencies of increased supply air temperatures, it is necessary to separate cool supply air from hot exhaust air in the data center. Any mixing of these two air streams leads to inefficiencies and impacts the redundancy and capacity of your Computer Room Air Conditioners (CRAC). The practice of proper airflow management is starting to become more widely accepted by data center operators and many are adopting best practices like Hot Aisle Cold Aisle orientations and blanking panels. Further increases in efficiency can be realized through the implementation of containment, which physically separates supply and exhaust air in the data center. There is considerable debate between which containment strategy Hot Aisle Containment (HACS) or Cold Aisle Containment (CACS) is the most efficient and effective for the data center. Hot Aisle containment seeks to capture hot exhaust air from IT equipment and return it to CRAC (or CRAH 2 ) units as quickly as possible. Cold Aisle Containment isolates cool supply air for IT equipment only, providing an even and consistent supply air temperature at the server intake. In a retrofit application, the best and most cost-effective strategy will depend on your existing environment. Available containment solutions range from plastic containment curtains (similar to what you would find in a grocery store freezer) to fully contained rooms with doors, walls, and a roof. Before selecting a containment solution, careful consideration should be given to the design intent of your data center, existing airflow paths, existing data center equipment, and your local codes 3. When properly implemented, containment solutions can reduce energy costs in the data center by 5% to 10% and can deliver a typical payback of less than two years 4. Figure 2. Water-side Free Cooling Map (Available Hours where Wet Bulb Tempature 10 C [50 F]) Figure 3. Air-side Free Cooling Map (Available Hours where Dry Bulb Tempature 27 C [81 F] AND Dew Point 15 C [59 F]) Economization Economization, or free cooling, has become the most extensively discussed topic regarding data center efficiency, especially with companies like Facebook recently completing data centers that operate with 100% free cooling. Both forms of free cooling, air-side economizers and water-side economizers, provide significant reductions in energy costs for data center operators by taking advantage of favorable environmental (temperature and humidity) conditions. Copyright 2012 Leading Edge Design Group 3
4 Water-side or indirect economizers utilize outside air to cool the water supplied to the chiller, reducing or eliminating the need for the chiller compressors to do so. In retrofit applications, water-side economizers are best suited for data centers that have existing chilled water plants and, more importantly, are in locations where the wet bulb temperature is less than 55 F for 3,000 hours per year or more (this condition is applicable to the majority of the United States, see Figure 2). In data centers that meet these criteria, water-size economizers can be economically retrofitted. Moreover, when operating in water-size economizer mode, the costs of a data center chiller plant can be reduced by up to 70%4. Air-side or direct economizers supply outside air to the data center whenever environmental conditions are appropriate. Exhaust air from IT equipment is typically directed outside. Similar to water-side economizers, location is a critical design element in evaluating the feasibility of implementing air-side economization (see Figure 3). Air-side economizers are typically not a cost-effective retrofit given the complexity in design, infrastructure, and commissioning of the control systems. However, with minimum savings of up to 30% 4 over traditional data centers, new data center builds should consider the potential of implementing air-side economization. Conclusion IT equipment in the data center environment is constantly evolving, and the process of maintaining an energy efficient data center is an ongoing effort. If you have an existing data center that you seek to improve, it is important to first establish and accurately measure your energy usage today. Once you understand this baseline, outline your path for improvement, set goals for energy reductions, and track the progress of your investments against your total energy usage, total energy cost, and metrics like Power Usage Effectiveness (PUE). The best plans for implementing energy efficiency improvements in the data center are incremental and focus first on small changes with low operational impact while having a well-defined path to leverage more complex upgrades like containment or economization going forward. If you are building a new data center, it is important to include energy efficiency as a critical element in the programming or requirements definition stages of your design. Your design team should be able to assist you in defining goals for your data center efficiency as well as to help you understand the cost implications and ROI of implementing energy efficient infrastructures and equipment. Your data center goals, size, budget, location, and lifecycle will help dictate what strategies are most appropriate for your design. Notes 1. Source: IDC 2. CRAH: Computer Room Air Handler 3. A fully contained room will likely require adjustments for fire detection and suppression. Check with your local Authority Having Jurisdiction (AHJ) to determine requirements 4. Source energystar.gov Copyright 2012 Leading Edge Design Group 4
5 Insights on Utility Company Incentives Utility company budgets for energy efficiency incentives are increasing, but so are the challenges that the utilities face in reaching their savings goals. The great news for data center owners and operators is that utility company support for data center incentives is becoming more widespread, creating a much-needed alignment between the data center efficiency goals of the public and private sector with the availability of financial incentives to help improve the ROI of a data center upgrade. The process of applying for and earning incentives is not an easy one, but significant incentives are available and should be pursued. These incentives can help reduce the capital expense of building a new data center or, moreover, can help increase the ROI of renovating your existing data center to make it more energy efficient. Most times, renovating your data center will improve your ability to support high-density loads, free up available white space, and extend the lifecycle of your existing data center footprint. Earning a utility company incentive to do so could be the financial support that helps provide solidify the right ROI to help your project move forward. While there are some utility companies that have created (or are working to create) prescriptive programs for data centers, the majority of data center projects will fall under the custom measures category, meaning that the utility will need to look at the potential savings and associated costs of each project individually before an incentive can be calculated. Knowing this, there are a few important things to keep in mind when preparing to apply for a data center incentive: 1. Be Prepared To Commit Data Center projects, whether new construction or renovation, are extremely time intensive. Adding an application for a utility company incentive for your data center project will add to the resource commitment required from your organization. Ensure that there is a single point of contact responsible for the communication related to the incentive application and build the time requirements and milestones into your overall project schedule. 2. Involve The Utility Company Early Utility companies would rather give you an incentive than a rebate, meaning they generally prefer help influence your design decisions and your equipment choices before you purchase them. Their representatives are a great resource that can help you understand the financial and environmental impacts of your design decision. Having them involved early helps you make informed decisions about your design as they relate to the energy-related ROI and the potential impact on your incentive. 3. Understand What You Have No one knows your data center like you do and all stakeholders involved in creating an incentive application have to rely on you as the end user to provide accurate information about your environment. This includes both IT equipment and physical infrastructure equipment. At minimum, you can get a head start by collecting specification sheets on existing equipment (like your CRACs), checking purchasing records to understand their age, and taking a snapshot of the existing system parameters (i.e. entering water temperature, supply air temperature, delta T). 4. Involve A Resource That Understands The Programs This may be an on staff resource or an outside consultant, but engaging resources that have experience with the programs and that understand the information required by the utility companies specific to data center projects will help expedite the process and ensure that your incentive is maximized. The right resource will help create an accurate baseline that your data center will be compared against, and this requires a knowledge of both data center infrastructures/design and utility company programs. The math is important the utility companies have to justify their savings estimates and any project can be audited, so attention to detail is critical. 5. Get Organizational Buy In Most often choosing the most efficient designs and products involves a greater up front capital expenditure. The utility company incentive can help offset this, but it is critical to look at the overall TCO of the project to understand the long-term savings your organization will achieve by investing in an efficient data center design. It is better to have the organizational support in advance, and most often choosing to prioritize efficiency in the data center will align well with overall corporate strategy for the environmental impact of your operations. Copyright 2012 Leading Edge Design Group 5
6 About Leading Edge Design Group is a leading national provider of energy optimization services that delivers significant energy savings to the public and private marketplaces through efficient data center designs and emerging LED lighting and wireless lighting control technologies. Founded in 2007 with the goal of pursuing, promoting, and providing the finest energy optimization solutions available, we help our customers minimize the environmental impact of their businesses while improving operational reliability and reducing costs. Leading Edge Design Group is dedicated to encouraging, challenging, and contributing to energy industry innovation with an ongoing commitment to our community and our environment. Visit us at and connect with us on Contact LED Headquarters 86 Chosen Vale Lane Suite 201 Enfield, NH Phone: Fax: Copyright 2012 Leading Edge Design Group 6
Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling
Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com
More informationFree Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions
Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the
More informationRe Engineering to a "Green" Data Center, with Measurable ROI
Re Engineering to a "Green" Data Center, with Measurable ROI Alan Mamane CEO and Founder Agenda Data Center Energy Trends Benchmarking Efficiency Systematic Approach to Improve Energy Efficiency Best Practices
More informationAIA Provider: Colorado Green Building Guild Provider Number: 50111120. Speaker: Geoff Overland
AIA Provider: Colorado Green Building Guild Provider Number: 50111120 Office Efficiency: Get Plugged In AIA Course Number: EW10.15.14 Speaker: Geoff Overland Credit(s) earned on completion of this course
More informationEnergy Efficiency Opportunities in Federal High Performance Computing Data Centers
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory
More informationHow To Improve Energy Efficiency In A Data Center
Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice
More informationAdaptive Cooling in Data Centers. Silicon Valley Leadership Group Energy Efficient Data Center Demonstration Project October, 2009
Adaptive Cooling in Data Centers Silicon Valley Leadership Group Energy Efficient Data Center Demonstration Project October, 2009 Maximizing Cooling Efficiency in a Concurrently Maintainable and Fault
More informationAnalysis of data centre cooling energy efficiency
Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe
More informationDealing with Thermal Issues in Data Center Universal Aisle Containment
Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe Daniele.Tordin@Panduit.com AGENDA Business Drivers Challenges
More informationEducation Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009
Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Agenda Overview - Network Critical Physical Infrastructure Cooling issues in the Server Room
More informationManaging Data Centre Heat Issues
Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design
More informationLegacy Data Centres Upgrading the cooling capabilities What are the options?
Legacy Data Centres Upgrading the cooling capabilities What are the options? Presentation Structure What is a Legacy Data Centre? What is CRAC cooling? ASHRAE Standards Overview Available Cooling Systems
More informationCooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings
WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Lars Strong, P.E., Upsite Technologies, Inc. Kenneth G. Brill, Upsite Technologies, Inc. 505.798.0200
More informationData Centre Cooling Air Performance Metrics
Data Centre Cooling Air Performance Metrics Sophia Flucker CEng MIMechE Ing Dr Robert Tozer MSc MBA PhD CEng MCIBSE MASHRAE Operational Intelligence Ltd. info@dc-oi.com Abstract Data centre energy consumption
More informationNational Grid Your Partner in Energy Solutions
National Grid Your Partner in Energy Solutions National Grid Webinar: Enhancing Reliability, Capacity and Capital Expenditure through Data Center Efficiency April 8, 2014 Presented by: Fran Boucher National
More informationCURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers
CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building
More informationEnvironmental Data Center Management and Monitoring
2013 Raritan Inc. Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor
More informationCooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings
WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Kenneth G. Brill, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies, Inc. 505.798.0200
More informationPursuing Operational Excellence. Better Data Center Management Through the Use of Metrics
Pursuing Operational Excellence Better Data Center Management Through the Use of Metrics Objective Use financial modeling of your data center costs to optimize their utilization. Data Centers are Expensive
More informationData Center Cooling & Air Flow Management. Arnold Murphy, CDCEP, CDCAP March 3, 2015
Data Center Cooling & Air Flow Management Arnold Murphy, CDCEP, CDCAP March 3, 2015 Strategic Clean Technology Inc Focus on improving cooling and air flow management to achieve energy cost savings and
More informationCase Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers
Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers Prepared for the U.S. Department of Energy s Federal Energy Management Program Prepared By Lawrence Berkeley National
More informationReducing Data Center Energy Consumption
Reducing Data Center Energy Consumption By John Judge, Member ASHRAE; Jack Pouchet, Anand Ekbote, and Sachin Dixit Rising data center energy consumption and increasing energy costs have combined to elevate
More informationSTULZ Water-Side Economizer Solutions
STULZ Water-Side Economizer Solutions with STULZ Dynamic Economizer Cooling Optimized Cap-Ex and Minimized Op-Ex STULZ Data Center Design Guide Authors: Jason Derrick PE, David Joy Date: June 11, 2014
More informationControl of Computer Room Air Handlers Using Wireless Sensors. Energy Efficient Data Center Demonstration Project
Control of Computer Room Air Handlers Using Wireless Sensors Energy Efficient Data Center Demonstration Project About the Energy Efficient Data Center Demonstration Project The project s goal is to identify
More informationEnergy Management Services
February, 2012 Energy Management Services Data centers & IT environments are often critical to today s businesses, directly affecting operations and profitability. General & Mechanical Services has the
More informationIMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT
DATA CENTER RESOURCES WHITE PAPER IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT BY: STEVE HAMBRUCH EXECUTIVE SUMMARY Data centers have experienced explosive growth in the last decade.
More informationDATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates
More informationBenefits of. Air Flow Management. Data Center
Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment
More informationDATA CENTER ASSESSMENT SERVICES
DATA CENTER ASSESSMENT SERVICES ig2 Group Inc. is a Data Center Science Company which provides solutions that can help organizations automatically optimize their Data Center performance, from assets to
More informationHow Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems
How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems Paul Mathew, Ph.D., Staff Scientist Steve Greenberg, P.E., Energy Management Engineer
More informationData Center Components Overview
Data Center Components Overview Power Power Outside Transformer Takes grid power and transforms it from 113KV to 480V Utility (grid) power Supply of high voltage power to the Data Center Electrical Room
More informationBICSInews. plus. july/august 2012. + Industrial-grade Infrastructure. + I Say Bonding, You Say Grounding + Data Center Containment.
BICSInews m a g a z i n e july/august 2012 Volume 33, Number 4 plus + Industrial-grade Infrastructure and Equipment + I Say Bonding, You Say Grounding + Data Center Containment & design deployment The
More informationData Center Energy Profiler Questions Checklist
Data Center Energy Profiler Questions Checklist Step 1 Case Name Date Center Company State/Region County Floor Area Data Center Space Floor Area Non Data Center Space Floor Area Data Center Support Space
More informationAlan Matzka, P.E., Senior Mechanical Engineer Bradford Consulting Engineers
Information Technology and Data Centers HVAC Showcase November 26, 2013 Alan Matzka, P.E., Senior Mechanical Engineer Bradford Consulting Engineers Welcome. Today s webinar is being recorded and will be
More informationData Centre Energy Efficiency Operating for Optimisation Robert M Pe / Sept. 20, 2012 National Energy Efficiency Conference Singapore
Data Centre Energy Efficiency Operating for Optimisation Robert M Pe / Sept. 20, 2012 National Energy Efficiency Conference Singapore Introduction Agenda Introduction Overview of Data Centres DC Operational
More informationVerizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001
Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue
More informationGuide to Minimizing Compressor-based Cooling in Data Centers
Guide to Minimizing Compressor-based Cooling in Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By: Lawrence Berkeley National Laboratory Author: William Tschudi
More informationThe Effect of Data Centre Environment on IT Reliability & Energy Consumption
The Effect of Data Centre Environment on IT Reliability & Energy Consumption Steve Strutt EMEA Technical Work Group Member IBM The Green Grid EMEA Technical Forum 2011 Agenda History of IT environmental
More informationEnclosure and Airflow Management Solution
Enclosure and Airflow Management Solution CFD Analysis Report Des Plaines, Illinois December 22, 2013 Matt Koukl- DECP Mission Critical Systems Affiliated Engineers, Inc. Contents Executive Summary...
More informationCisco Data Center Facilities Assessment Service
Cisco Data Center Facilities Assessment Service Increase the availability, capacity, and life of your data center facility. Service Overview Data centers must respond to changing business needs, environmental
More informationData center upgrade proposal. (phase one)
Data center upgrade proposal (phase one) Executive Summary Great Lakes began a recent dialogue with a customer regarding current operations and the potential for performance improvement within the The
More informationIncreasing Data Center Efficiency through Metering and Monitoring Power Usage
White Paper Intel Information Technology Computer Manufacturing Data Center Efficiency Increasing Data Center Efficiency through Metering and Monitoring Power Usage To increase data center energy efficiency
More informationDataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences
DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences November 2011 Powered by DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no
More informationCenter Thermal Management Can Live Together
Network Management age e and Data Center Thermal Management Can Live Together Ian Seaton Chatsworth Products, Inc. Benefits of Hot Air Isolation 1. Eliminates reliance on thermostat 2. Eliminates hot spots
More informationData Center Cooling Critical Facility & Infrastructure Optimization. Presented by. Greg Stover SVP NER Data Corporation
Data Center Cooling Critical Facility & Infrastructure Optimization Presented by Greg Stover SVP NER Data Corporation About NER Data Corporation Data Center Infrastructure Optimization NER has been a leading
More informationOptimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER
Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER Lylette Macdonald, RCDD Legrand Ortronics BICSI Baltimore 2011 Agenda: Discuss passive thermal management at the Rack
More informationImproving Data Center Energy Efficiency Through Environmental Optimization
Improving Data Center Energy Efficiency Through Environmental Optimization How Fine-Tuning Humidity, Airflows, and Temperature Dramatically Cuts Cooling Costs William Seeber Stephen Seeber Mid Atlantic
More informationEnergy Efficiency and Availability Management in Consolidated Data Centers
Energy Efficiency and Availability Management in Consolidated Data Centers Abstract The Federal Data Center Consolidation Initiative (FDCCI) was driven by the recognition that growth in the number of Federal
More informationCombining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency
A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency
More informationMaximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages
Objectives Increase awareness of the types of economizers currently used for data centers Provide designers/owners with an overview of the benefits and challenges associated with each type Outline some
More informationDatacenter Efficiency Program
Datacenter Efficiency Program Yuming Qiu, CLEAResult Anna Stieve, CLEAResult Michael Stachowiak, CLEAResult Abstract Worldwide, datacenter energy consumption is skyrocketing and datacenter energy efficiency
More informationEnergy Efficiency Best Practice Guide Data Centre and IT Facilities
2 Energy Efficiency Best Practice Guide Data Centre and IT Facilities Best Practice Guide Pumping Systems Contents Medium-sized data centres energy efficiency 3 1 Introduction 4 2 The business benefits
More informationAisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings
WH I TE PAPE R AisleLok Modular Containment vs. : A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings By Bruce Long, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies,
More informationAIR-SITE GROUP. White Paper. Green Equipment Room Practices
AIR-SITE GROUP White Paper Green Equipment Room Practices www.air-site.com Common practices to build a green equipment room 1 Introduction Air-Site (www.air-site.com) is a leading international provider
More informationEnergy Performance Optimization of Server Room HVAC System
International Journal of Thermal Technologies E-ISSN 2277 4114 2 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijtt/ Research Article Manoj Jadhav * and Pramod Chaudhari Department
More informationEconomizer Modes of Data Center Cooling Systems
Economizer Modes of Data Center Cooling Systems White Paper 132 Revision 0 by John Niemann John Bean Victor Avelar > Executive summary In certain climates, some cooling systems can save over 70% in annual
More informationArch Rock Energy Optimizer in Action Data Center
Arch Rock Energy Optimizer in Action Data Center Business Perspective Recent trends in Information Technology such as dense blade computing, server and storage virtualization, and cloud computing have
More informationAIRAH Presentation April 30 th 2014
Data Centre Cooling Strategies The Changing Landscape.. AIRAH Presentation April 30 th 2014 More Connections. More Devices. High Expectations 2 State of the Data Center, Emerson Network Power Redefining
More informationData Center Infrastructure Management (DCIM) Utility Energy Efficiency Opportunities Discussion & Demos July 2, 2013
Data Center Infrastructure Management (DCIM) Utility Energy Efficiency Opportunities Discussion & Demos July 2, 2013 Ted Brown Sr. Energy Management Analyst Data Center / IT Energy Efficiency ted.brown@seattle.gov
More informationSpeaker: John Peterson Time: April 4, 2014, 9:45-10:45 a.m. Venue: Crystal 1-2. Data Center Design and Commissioning
Speaker: John Peterson Time: April 4, 2014, 9:45-10:45 a.m. Venue: Crystal 1-2 Data Center Design and Commissioning High enterprise relevancy for addressing space, power, and cooling, as well as costs
More informationDOE FEMP First Thursday Seminar. Learner Guide. Core Competency Areas Addressed in the Training. Energy/Sustainability Managers and Facility Managers
DOE FEMP First Thursday Seminar Achieving Energy Efficient Data Centers with New ASHRAE Thermal Guidelines Learner Guide Core Competency Areas Addressed in the Training Energy/Sustainability Managers and
More informationRittal White Paper 507: Understanding Data Center Cooling Energy Usage & Reduction Methods By: Daniel Kennedy
Rittal White Paper 507: Understanding Data Center Cooling Energy Usage & Reduction Methods By: Daniel Kennedy Executive Summary Data center energy usage has risen dramatically over the past decade and
More informationData Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling
Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling Joshua Grimshaw Director of Engineering, Nova Corporation
More informationGreening Data Centers
Greening Data Centers Dallas Thornton SDSC Division Director, Cyberinfrastructure Services March 2, 2011 Data Centers Are Enormous Users of Power US Data Centers (TeraWatt Hours per Year) 125 US Televisions
More informationIntroduction to Datacenters & the Cloud
Introduction to Datacenters & the Cloud Datacenter Design Alex M. Hurd Clarkson Open Source Institute March 24, 2015 Alex M. Hurd (COSI) Introduction to Datacenters & the Cloud March 24, 2015 1 / 14 Overview
More informationWireless Sensor Technology for Data Centers
Wireless Sensor Technology for Data Centers Richard Oberg and Ed Sanchez, Sacramento Municipal Utility District Patricia Nealon, Synapsense Corporation ABSTRACT This paper describes the development and
More informationEnergy Efficiency in Small Server Rooms: Field Surveys and Findings
Energy Efficiency in Small Server Rooms: Field Surveys and Findings Iris (Hoi Ying) Cheung, Steve Greenberg, Roozbeh Mahdavi, Richard Brown, and William Tschudi Lawrence Berkeley National Laboratory ABSTRACT
More informationOverview of Green Energy Strategies and Techniques for Modern Data Centers
Overview of Green Energy Strategies and Techniques for Modern Data Centers Introduction Data centers ensure the operation of critical business IT equipment including servers, networking and storage devices.
More informationFact Sheet (Web Content): Improving Energy Efficiency for Server Rooms and Closets
Fact Sheet (Web Content): Improving Energy Efficiency for Server Rooms and Closets September 2012 Table of Contents A) Simplest, No-Cost, or Very-Low-Cost Measures 1. Determine computational functions
More informationEngineers Ireland Cost of Data Centre Operation/Ownership. 14 th March, 2013 Robert Bath Digital Realty
Engineers Ireland Cost of Data Centre Operation/Ownership 14 th March, 2013 Robert Bath Digital Realty Total Cost of Operation (TCO) Rental TCO - 10 Year Lease Term Power Cooling Connectivity Costs 26%
More informationData Center Leadership In the DOE Better Buildings Challenge
Symposium Southern California February 18th, 2015 Data Center Leadership In the DOE Better Buildings Challenge Applying Best Practices to meet the Challenge Dale Sartor, PE Lawrence Berkeley National Laboratory
More informationThermal Monitoring Best Practices Benefits gained through proper deployment and utilizing sensors that work with evolving monitoring systems
NER Data Corporation White Paper Thermal Monitoring Best Practices Benefits gained through proper deployment and utilizing sensors that work with evolving monitoring systems Introduction Data centers are
More informationGreen Data Centre Design
Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS
More informationEconomizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers
A White Paper from the Experts in Business-Critical Continuity TM Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers Executive Summary The strategic business importance
More informationHot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc.
Business Management Magazine Winter 2008 Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc. Contrary to some beliefs, air is quite
More informationRittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy
Rittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy Executive Summary Data center owners and operators are in constant pursuit of methods
More informationOffice of the Government Chief Information Officer. Green Data Centre Practices
Office of the Government Chief Information Officer Green Data Centre Practices Version : 2.0 April 2013 The Government of the Hong Kong Special Administrative Region The contents of this document remain
More informationWhite Paper. Data Center Containment Cooling Strategies. Abstract WHITE PAPER EC9001. Geist Updated August 2010
White Paper Data Center Containment Cooling Strategies WHITE PAPER EC9001 Geist Updated August 2010 Abstract Deployment of high density IT equipment into data center infrastructure is now a common occurrence
More informationElements of Energy Efficiency in Data Centre Cooling Architecture
Elements of Energy Efficiency in Data Centre Cooling Architecture Energy Efficient Data Center Cooling 1 STULZ Group of Companies Turnover 2006 Plastics Technology 400 Mio A/C Technology 200 Mio Total
More informationUniversity of St Andrews. Energy Efficient Data Centre Cooling
Energy Efficient Data Centre Cooling St. Andrews and Elsewhere Richard Lumb Consultant Engineer Future-Tech Energy Efficient Data Centre Cooling There is no one single best cooling solution for all Data
More informationSelf-benchmarking Guide for Data Center Infrastructure: Metrics, Benchmarks, Actions 6-28-10. Sponsored by:
Self-benchmarking Guide for Data Center Infrastructure: Metrics, Benchmarks, Actions 6-28-10 Sponsored by: Disclaimer This document was prepared as an account of work sponsored by the United States Government.
More informationGUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group
GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY Public Sector ICT Special Working Group SERVER ROOM ENERGY EFFICIENCY This guide is one of a suite of documents that aims to provide guidance on ICT energy efficiency.
More informationBest Practices for Wire-free Environmental Monitoring in the Data Center
White Paper Best Practices for Wire-free Environmental Monitoring in the Data Center April 2012 Introduction Monitoring for environmental threats in the data center is not a new concept. Since the beginning
More informationabstract about the GREEn GRiD
Guidelines for Energy-Efficient Datacenters february 16, 2007 white paper 1 Abstract In this paper, The Green Grid provides a framework for improving the energy efficiency of both new and existing datacenters.
More informationGuideline for Water and Energy Considerations During Federal Data Center Consolidations
Guideline for Water and Energy Considerations During Federal Data Center Consolidations Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory
More informationEnergy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie
Energy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie Mukesh Khattar, Energy Director, Oracle National Energy Efficiency Technology Summit, Sep. 26, 2012, Portland, OR Agenda
More informationData Centers: How Does It Affect My Building s Energy Use and What Can I Do?
Data Centers: How Does It Affect My Building s Energy Use and What Can I Do? 1 Thank you for attending today s session! Please let us know your name and/or location when you sign in We ask everyone to
More informationGuide for Reducing Data Center Physical Infrastructure Energy Consumption in Federal Data Centers
Guide for Reducing Data Center Physical Infrastructure Energy Consumption in Federal Data Centers October 2010/White Paper 250 by Dennis Bouley, Senior Research Analyst Data Center Science Center and Ellen
More informationData Center Optimization Services. Maximize Your Data Center
Data Center Optimization Services Maximize Your Data Center Energy savings was definitely the key driver in my decision to use the SmartAire dampers and DirectAire panels. - Larry Hood Senior Construction
More informationNSIDC Data Center: Energy Reduction Strategies
NSIDC Data Center: Energy Reduction Strategies Airside Economization and Unique Indirect Evaporative Cooling Executive summary The Green Data Center Project was a successful effort to significantly reduce
More information7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
More informationMinimising Data Centre Total Cost of Ownership Through Energy Efficiency Analysis
Minimising Data Centre Total Cost of Ownership Through Energy Efficiency Analysis Sophia Flucker CEng MIMechE Ing Dr Robert Tozer MSc MBA PhD CEng MCIBSE MASHRAE Operational Intelligence Ltd. info@dc-oi.com
More informationDataCenter 2020: first results for energy-optimization at existing data centers
DataCenter : first results for energy-optimization at existing data centers July Powered by WHITE PAPER: DataCenter DataCenter : first results for energy-optimization at existing data centers Introduction
More informationIntroducing AUDIT- BUDDY
Introducing AUDIT- BUDDY Monitoring Temperature and Humidity for Greater Data Center Efficiency 202 Worcester Street, Unit 5, North Grafton, MA 01536 www.purkaylabs.com info@purkaylabs.com 1.774.261.4444
More informationData Center Industry Leaders Reach Agreement on Guiding Principles for Energy Efficiency Metrics
On January 13, 2010, 7x24 Exchange Chairman Robert Cassiliano and Vice President David Schirmacher met in Washington, DC with representatives from the EPA, the DOE and 7 leading industry organizations
More informationManaging Power Usage with Energy Efficiency Metrics: The Available Me...
1 of 5 9/1/2011 1:19 PM AUG 2011 Managing Power Usage with Energy Efficiency Metrics: The Available Metrics and How to Use Them Rate this item (1 Vote) font size Data centers consume an enormous amount
More informationEssential NCPI Management Requirements for Next Generation Data Centers
Essential NCPI Requirements for Next Generation Data Centers By Ted Ives White Paper #14 1 Executive Summary The management of physical infrastructure in data centers can no longer be considered independently
More informationTrends in Data Center Design ASHRAE Leads the Way to Large Energy Savings
Trends in Data Center Design ASHRAE Leads the Way to Large Energy Savings ASHRAE Conference, Denver Otto Van Geet, PE June 24, 2014 NREL/PR-6A40-58902 NREL is a national laboratory of the U.S. Department
More informationAirflow Simulation Solves Data Centre Cooling Problem
Airflow Simulation Solves Data Centre Cooling Problem The owner s initial design for a data centre in China utilized 40 equipment racks filled with blade servers spread out in three rows along the length
More informationHot-Aisle vs. Cold-Aisle Containment for Data Centers
Hot-Aisle vs. Cold-Aisle Containment for Data Centers White Paper 135 Revision 1 by John Niemann, Kevin Brown, and Victor Avelar > Executive summary Both hot-air and cold-air containment can improve the
More information