1 Eni Green Data Center - Specification Green IT Adopting the principles of sustainable development is one of the key missions in the field of information technology today. 2% of the world s CO2 emissions are generated by the consumption of the IT and telecommunications industries: an amount comparable to that produced by the entire airline industry. In 2007, $7 billion was spent on electricity to run and cool servers in Data Centers around the world. Over the next ten years, the powering and cooling of computing infrastructure will become a critical factor for economic development. Developing an eco-friendly information technology is among the objectives of Eni's commitment to sustainable energy. Eni Green Data Center In 2008, Eni studied the idea of setting up a new Data Center, starting with an analysis of the geographic distribution of the Data Centers where its systems are currently housed (none of which are owned by the company), and moving on to consider the evolution trends of spaces and power consumption. With the Green Data Center, Eni has rethought every single component of the Data Center system, with the aim of saving energy and considering every component as part of a larger, more complex machine: an industrial system to be designed as a whole. In 2009, the company devised the idea of building a new Data Center of its own to host all its central data processing systems, intended for both administrative information systems and HPC (High Performance Computing) calculation simulation systems, with more than 7,000 systems and 60,000 core CPUs. 1

2 The center, due to be completed by the end of 2012, is designed to host IT systems which absorb up to 30MW of useable IT power, in a space measuring 5,200 metres square in 6 IT rooms. The project s outstanding features are: the world s most energy efficient Data Center dimensions (in terms of MW of energy) which are unique in Italy and among the top in Europe and the world all-located, designed and constructed within Italy Guidelines of the project All aspects of the projects were rethought starting from the heart of the system (the requirements and features of IT apparatus), both from the point of view of the architecture (with optimal positioning of each space to minimise, for example, the distance travelled by electricity and air) and the engineering solutions. All this, while preserving the necessary flexibility to adapt the new center to fit future technological developments, ensuring they guarantee the highest level of redundancy systems and comply with operating parameters for the data centers established by international regulations. In a data center the main items of energy consumption, besides of course the computer equipment, are cooling systems, ventilation and electrical distribution. For the Green Data Center in Eni, processes were carried out for each category of consumption to try to identify optimal and innovative solutions to reduce energy consumption in order to improve the PUE energy efficiency parameter: the goal is to bring it to below the value of 1.2. The P.U.E. (Power Usage Effectiveness) parameter indicates the ratio between a Data Center s total electricity consumption (IT apparatus, air conditioners, fans, UPSs, etc.) and consumption of IT apparatus alone. Standard non-energy efficient Data Centers normally exceed a value of 3.0; a PUE of 2.0 is considered a good result; a value lower than 1.5 represents a very aggressive policy. For example, with an IT consumption of 10MW, a DC with a PUE of 1.2 consumes a total of 12MW, while one with a PUE of 3 consumes 30MW, saving 18MW of energy. 2

3 The principles of sustainability with which the new Data Center was designed can be traced back to the choice of the place where it's located. The choice of Ferrera Erbognone as a location for the project was determined as it is in the immediate vicinity of the power plant of Enipower, the plant of Eni that best meets the requirements for electrical power for the Data Center: the power required is already available and generated using gas turbines of natural gas, the cleanest of fossil fuels used to produce electricity. The facility will consist of two perfectly symmetrical volumes referred to as clover leaves - which are completely independent and redundant of each other in order to guarantee uninterrupted service from both a structural and engineering point of view. The entire building, except for the central zone separating the two clover leaves, is underground up to the roof, creating an artificial hill which is landscaped to improve its visual impact. The air conditioning system is the Center s most innovative component. The Direct Free- Cooling method will be used, cooling IT systems directly with air from outdoors and keeping the forced ventilation air conditioning system turned off whenever possible. This is possible because the IT systems will work at a temperature of around C: a higher temperature (though controlled and stable) than in conventional Data Centers, where the temperature is usually around C. In this way, even at the latitude of the 45th parallel, in the Po Valley, on the basis of an historical analysis of temperature and humidity, for more than 75% of the year a sufficient amount of air from outdoors can cool up to 30MW of IT systems. The air conditioning system will be tripped for a maximum of 25% of the hours in the year, whereas in a conventional data center it operates 100% of the time. The entire air treatment system is a highly innovative integrated solution in terms of both its operating logic and its scale. The Center s geographic location on the 45th parallel obviously poses an additional challenge for the achievement of a record-breaking PUE as compared to Data Centers located further north (in Ireland, UK and the Rocky Mountains in the US) in areas with more beneficial climates. The system for filtering incoming air was also the subject of specific study and of in-depth simulations. The air from the outside, before being introduced into the system, will be filtered 3

4 for dust, removed to the extent of about 3,000 kilograms per year. Therefore, the air returned outside will be clean. To ensure the correct distribution of hot and cold air flow in the IT rooms, so as to bring the necessary cold air to the IT systems without dispersion, the Data Center will strictly divide the air in CAGE structures, which keep the cold air corridor (along which all the server systems are aligned, with air intakes) closed and separate. Meanwhile the entire IT room will form a warm corridor, in which the air expelled by IT servers is conveyed towards the expulsion point in the stack by thrust and by the stack effect. An innovative idea was applied to limiting the risk of fire, which is statistically high in Data Centers near the emergency diesel generators and especially in the UPS batteries, which are normally present in large quantities in a single room. Additional risky apparatus are always installed in separate premises, and batteries, the biggest source of danger, are divided up in small rooms which are totally isolated. The battery rooms do not have free-cooling but conventional controlled air conditioning, with special stacks featuring natural ventilation which may, if necessary, be used to release any fumes from overheating or combustion. In order to optimise the paths travelled by electricity, the distribution Power Centers are designed to operate at medium voltage (20,000 V), up to only a few metres away from the final distribution system towards the IT servers, positioning them in locations which are aligned with the final distribution systems (UPSs). This positioning of the apparatus ensures that each IT server is always supplied by 2 separate lines coming from the opposite sides of the room, and therefore by 2 different UPSs (each with its own emergency batteries), which are in turn connected to two different general power supplies. Each system is also redundant in terms of electrical panels to ensure that each sub-branch of the system continues to be supplied even in the event of a fault on one of the main distribution lines. A failure on one side of the room can only result in a fault in a single sub-system of apparatus affecting, at most, half of the power supply: the other half will continue to keep the systems running. 4

5 In addition, a truly innovative medium-sized UPS (200kW) is used, which operates with offline technology (that is, it stays off, on standby, and is tripped only in the event of a significant discontinuity in the power supply), with very high efficiency (99.4% at 50% load). The scale and importance of the Eni project convinced the world s principal manufacturers of UPS equipment to start working on the development and sale of products of this type, which were not previously available. All lighting systems and accessory forms of consumption were analysed to optimize their power consumption: indoor lighting is provided by fluorescent bulbs turned on by motion detector sensors; outdoor security lighting employs LED bulbs; even the colours of the walls and rooms were chosen to ensure high luminosity. 5

As close to perfection. development and production. Modular data center

As close to perfection. development and production. Modular data center As close to perfection development and production Modular data center August 2014 What is GreenMDC modular data center? Basically it is the modular design construction which is realized by the principle

More information

State of the Art Energy Efficient Data Centre Air Conditioning

State of the Art Energy Efficient Data Centre Air Conditioning - White Paper - State of the Art Energy Efficient Data Centre Air Conditioning - Dynamic Free Cooling - Release 2, April 2008 Contents ABSTRACT... 3 1. WHY DO I NEED AN ENERGY EFFICIENT COOLING SYSTEM...

More information

Questions to be responded to by the firm submitting the application. Why do you think this project should receive an award? How does it demonstrate:

Questions to be responded to by the firm submitting the application. Why do you think this project should receive an award? How does it demonstrate: Questions to be responded to by the firm submitting the application Why do you think this project should receive an award? How does it demonstrate: innovation, quality, and professional excellence transparency

More information

Energy-efficient data center achieves 2N reliability; MTU Onsite Energy generator sets provide critical backup

Energy-efficient data center achieves 2N reliability; MTU Onsite Energy generator sets provide critical backup Press Release Contact: Gary Mason Tognum America Inc. Phone: +1 248 560 8480 E-mail: gary.mason@tognum.com Agency contact: Robert E. Sheldon, APR Creative Communications Consultants, Inc. Phone: +1 210

More information

AIR-SITE GROUP. White Paper. Green Equipment Room Practices

AIR-SITE GROUP. White Paper. Green Equipment Room Practices AIR-SITE GROUP White Paper Green Equipment Room Practices www.air-site.com Common practices to build a green equipment room 1 Introduction Air-Site (www.air-site.com) is a leading international provider

More information

Data Centres A complete solution to noise control and acoustic packages

Data Centres A complete solution to noise control and acoustic packages Data Centres A complete solution to noise control and acoustic packages Introduction World class noise control. Expertise you can trust. IAC Acoustics is world-renowned for providing cost effective solutions

More information

Heat Recovery from Data Centres Conference Designing Energy Efficient Data Centres

Heat Recovery from Data Centres Conference Designing Energy Efficient Data Centres What factors determine the energy efficiency of a data centre? Where is the energy used? Local Climate Data Hall Temperatures Chiller / DX Energy Condenser / Dry Cooler / Cooling Tower Energy Pump Energy

More information

World s Greenest High Performance Data Center

World s Greenest High Performance Data Center World s Greenest High Performance Data Center EcoDataCenter Sustainability for future generations Our Services Colocation Data Center for Mission Critical Requirements Lockable racks, cages, private rooms

More information

AIRAH Presentation April 30 th 2014

AIRAH Presentation April 30 th 2014 Data Centre Cooling Strategies The Changing Landscape.. AIRAH Presentation April 30 th 2014 More Connections. More Devices. High Expectations 2 State of the Data Center, Emerson Network Power Redefining

More information

Energy Efficiency HOSPITALITY. www.energia.ie

Energy Efficiency HOSPITALITY. www.energia.ie Energy Efficiency HOSPITALITY www.energia.ie Your chance to reduce your business energy usage by as much as 20%! 20% is a significant figure and reducing your energy bill by this amount could make a real

More information

Infrastructure & Cities Sector

Infrastructure & Cities Sector Technical Article Infrastructure & Cities Sector Building Technologies Division Zug (Switzerland), October 18, 2011 Saving Energy in a Data Center A Leap of Faith? New guidelines from ASHRAE (American

More information

BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0

BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0 BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0 To achieve GREEN MARK Award Pre-requisite Requirement All relevant pre-requisite requirements for the specific Green Mark Rating are to be complied

More information

ICT and the Green Data Centre

ICT and the Green Data Centre ICT and the Green Data Centre Scott McConnell Sales Manager c/o Tanya Duncan MD Interxion Ireland Green Data Centres Our Responsibility Data centre greenhouse gas emissions are projected to quadruple by

More information

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES

More information

Data Center 2020: Delivering high density in the Data Center; efficiently and reliably

Data Center 2020: Delivering high density in the Data Center; efficiently and reliably Data Center 2020: Delivering high density in the Data Center; efficiently and reliably March 2011 Powered by Data Center 2020: Delivering high density in the Data Center; efficiently and reliably Review:

More information

How a Ground Source Heat Pump Works for a School or College

How a Ground Source Heat Pump Works for a School or College How a Ground Source Heat Pump Works for a School or College Vertical System Image courtesy of Climate Master 1 Geothermal avoids the need for outdoor equipment..reducing vandalism and liability Image courtesy

More information

Direct Fresh Air Free Cooling of Data Centres

Direct Fresh Air Free Cooling of Data Centres White Paper Introduction There have been many different cooling systems deployed in Data Centres in the past to maintain an acceptable environment for the equipment and for Data Centre operatives. The

More information

DATA CENTRE DESIGN AND

DATA CENTRE DESIGN AND SPUSC 2008 SOUTH PACIFIC USER SERVICES CONFERENCE DATA CENTRE DESIGN AND ENERGY INITIATIVES Presented by Jarrad Clift Electrical Engineer Greenstar Accredited Presentation Content Data Centres General

More information

Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers

Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers Prepared for the U.S. Department of Energy s Federal Energy Management Program Prepared By Lawrence Berkeley National

More information

DataCenter 2020: first results for energy-optimization at existing data centers

DataCenter 2020: first results for energy-optimization at existing data centers DataCenter : first results for energy-optimization at existing data centers July Powered by WHITE PAPER: DataCenter DataCenter : first results for energy-optimization at existing data centers Introduction

More information

USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR

USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR CONTENTS Introduction Safety Notes Identification of parts Installation instructions Operation instructions Maintenance Troubleshooting

More information

IBM Twin Data Center Complex Ehningen Peter John IBM BS peter.john@de.ibm.com. 2011 IBM Corporation

IBM Twin Data Center Complex Ehningen Peter John IBM BS peter.john@de.ibm.com. 2011 IBM Corporation IBM Twin Data Center Complex Ehningen Peter John IBM BS peter.john@de.ibm.com Overview Profile IBM owned facility 6447 m² IT-Space Infrastructure concurrent maintainable (Tier Level 3) Feed-ins of Power

More information

The Quest for Energy Efficiency. A White Paper from the experts in Business-Critical Continuity

The Quest for Energy Efficiency. A White Paper from the experts in Business-Critical Continuity The Quest for Energy Efficiency A White Paper from the experts in Business-Critical Continuity Abstract One of the most widely discussed issues throughout the world today is the rapidly increasing price

More information

Making Existing Server Rooms More Efficient Steve Bowes-Phipps, Data Centre Manager University of Hertfordshire. http://rare-idc.herts.ac.

Making Existing Server Rooms More Efficient Steve Bowes-Phipps, Data Centre Manager University of Hertfordshire. http://rare-idc.herts.ac. Making Existing Server Rooms More Efficient Steve Bowes-Phipps, Data Centre Manager University of Hertfordshire http://rare-idc.herts.ac.uk Making Existing Server Rooms More Efficient Reduction and Re-use

More information

System solution for data centres

System solution for data centres 1 System solution for data centres Energy-efficient air conditioning with ServeLine Cooling IT infrastructure, high availability, low energy costs and communication with DCIM systems all in one from your

More information

Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415. Table of Contents

Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415. Table of Contents Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415 Table of Contents WORK COVERED... 2 WORK NOT COVERED...2 TITLES... 2 GRADE LEVELS... 2 HELPER AND INTERMEDIATE JOBS...

More information

Technical specifications. Containerized data centre NTR CDC 40f+

Technical specifications. Containerized data centre NTR CDC 40f+ Technical specifications Containerized data centre NTR CDC 40f+ CONTENT 1 THE PURPOSE OF CDC... 3 2 BASIC PROPERTIES... 4 2.1 EXTERNAL DIMENSIONS... 4 2.2 INSTALLATION REQIREMENTS... 4 2.3 ELECTRICAL CONNECTION

More information

Security+ Guide to Network Security Fundamentals, Fourth Edition. Chapter 13 Business Continuity

Security+ Guide to Network Security Fundamentals, Fourth Edition. Chapter 13 Business Continuity Security+ Guide to Network Security Fundamentals, Fourth Edition Chapter 13 Business Continuity Objectives Define environmental controls Describe the components of redundancy planning List disaster recovery

More information

How To Improve Energy Efficiency In A Data Center

How To Improve Energy Efficiency In A Data Center Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice

More information

Training Systems for Renewable Energies. Acquiring Practical Skills and Project-oriented Expertise

Training Systems for Renewable Energies. Acquiring Practical Skills and Project-oriented Expertise Training Systems for Renewable Energies Acquiring Practical Skills and Project-oriented Expertise Qualifications through Quality Inexhaustible, sustainable, real the future is green The move away from

More information

CEMEP UPS. The high environmental performance solution for power supply to high-availability data centers

CEMEP UPS. The high environmental performance solution for power supply to high-availability data centers CEMEP UPS The high environmental performance solution for power supply to high-availability data centers Exchanges of information and communication needs are growing at an exponential rate. That growth

More information

HEATING AND COOLING SYSTEMS THAT FIT COMFORTABLY WITHIN YOUR BUDGET.

HEATING AND COOLING SYSTEMS THAT FIT COMFORTABLY WITHIN YOUR BUDGET. HEATING AND COOLING SYSTEMS THAT FIT COMFORTABLY WITHIN YOUR BUDGET. AFFORDABLE SOLUTIONS FROM AMERISTAR. We know that heating and cooling systems can be a major investment for homeowners. Our goal is

More information

Energy Efficiency and Availability Management in Consolidated Data Centers

Energy Efficiency and Availability Management in Consolidated Data Centers Energy Efficiency and Availability Management in Consolidated Data Centers Abstract The Federal Data Center Consolidation Initiative (FDCCI) was driven by the recognition that growth in the number of Federal

More information

Excool Indirect Adiabatic and Evaporative Data Centre Cooling. World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling

Excool Indirect Adiabatic and Evaporative Data Centre Cooling. World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling Excool Indirect Adiabatic and Evaporative Data Centre Cooling World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling Indirect Adiabatic and Evaporative Data Centre Cooling Solutions by

More information

Datacentre Capability March 2015

Datacentre Capability March 2015 Callaghan Engineering Consul-ng Engineers Project Managers Datacentre Capability March 2015 Callaghan Engineering Multi-discipline engineering & project management company Established in 1990 Offices in

More information

It s time for H.E.R.O. Energy Saving Strategy for. Tunnel & Shuttle Kilns

It s time for H.E.R.O. Energy Saving Strategy for. Tunnel & Shuttle Kilns Energy Saving Strategy for Tunnel & Shuttle Kilns SANITARY WARE 1 Introduction The application of the Kyoto protocol and the effects of the recent energy crisis, have highlighted just how important it

More information

CoolTeg Plus Chilled Water (CW) version: AC-TCW

CoolTeg Plus Chilled Water (CW) version: AC-TCW version: 12-04-2013 CONTEG DATASHEET TARGETED COOLING CoolTeg Plus Chilled Water (CW) version: AC-TCW CONTEG, spol. s r.o. Czech Republic Headquarters: Na Vítězné pláni 1719/4 140 00 Prague 4 Tel.: +420

More information

Overview of Green Energy Strategies and Techniques for Modern Data Centers

Overview of Green Energy Strategies and Techniques for Modern Data Centers Overview of Green Energy Strategies and Techniques for Modern Data Centers Introduction Data centers ensure the operation of critical business IT equipment including servers, networking and storage devices.

More information

Modular Datacenter based in a 20' container

Modular Datacenter based in a 20' container Modular Datacenter based in a 20' container RETEX, S.A. Avda Tecnología, 35. 08840 VILADECANS (Barcelona), SPAIN. T. +34 932 649 850 F. +34 936 592 368 info@retex.es www.retex.es INDEX 1. THE DATABOX SOLUTION...

More information

How to choose a heat pump and use it wisely

How to choose a heat pump and use it wisely How to choose a heat pump and use it wisely Contents How does a heat pump work? 2 Insulating your home 3 Heat loss in the home Not all heat pumps are created equal 4 Choosing a heat pump 4 Choosing by

More information

GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group

GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY Public Sector ICT Special Working Group SERVER ROOM ENERGY EFFICIENCY This guide is one of a suite of documents that aims to provide guidance on ICT energy efficiency.

More information

How to Save Over 60% on Cooling Energy Needed by a Data Center? The Roadmap from Traditional to Optimized Cooling

How to Save Over 60% on Cooling Energy Needed by a Data Center? The Roadmap from Traditional to Optimized Cooling How to Save Over 60% on Cooling Energy Needed by a Data Center? The Roadmap from Traditional to Optimized Cooling Abstract Data center managers are increasingly in search of methods and technologies for

More information

Rules of Thumb Energy Efficiency in Buildings

Rules of Thumb Energy Efficiency in Buildings Energy Efficiency in Buildings Energy Savings Cost Savings Increased Productivity Economic Development Other Standard lighting retrofits: $0.90-$1.20 per square foot. High-efficiency packaged and split

More information

Introduction to Aircraft Design and Aviation Systems (ENG3005)

Introduction to Aircraft Design and Aviation Systems (ENG3005) Chapter 3 Emergency power generation 1. Power distribution 1.1 The power source for many civil aircraft: a.main aircraft generator : through a Generator Control Breaker (GCB). Controlled by Generator Control

More information

COMMODITIZING THE DATA CENTER MARKET

COMMODITIZING THE DATA CENTER MARKET COMMODITIZING THE DATA CENTER MARKET Site Summary The building at 1360 Kifer Road has approximately 94,500 SF of server and support space and is currently divided into two independent data center areas.

More information

DATA CENTRES UNDERSTANDING THE ISSUES TECHNICAL ARTICLE

DATA CENTRES UNDERSTANDING THE ISSUES TECHNICAL ARTICLE DATA CENTRES UNDERSTANDING THE ISSUES TECHNICAL ARTICLE Molex Premise Networks EXECUTIVE SUMMARY The term data centre usually conjures up an image of a high-tech IT environment, about the size of a football

More information

RiMatrix S Make easy.

RiMatrix S Make easy. RiMatrix S Make easy. 2 RiMatrix S Rittal The System. The whole is more than the sum of its parts. The same is true of Rittal The System. With this in mind, we have bundled our innovative enclosure, power

More information

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES

More information

Reducing Data Center Loads for a Large-Scale, Net Zero Office Building

Reducing Data Center Loads for a Large-Scale, Net Zero Office Building rsed Energy Efficiency & Renewable Energy FEDERAL ENERGY MANAGEMENT PROGRAM Reducing Data Center Loads for a Large-Scale, Net Zero Office Building Energy Efficiency & Renewable Energy Executive summary

More information

Data Center Facility Basics

Data Center Facility Basics Data Center Facility Basics Ofer Lior, Spring 2015 Challenges in Modern Data Centers Management, Spring 2015 1 Information provided in these slides is for educational purposes only Challenges in Modern

More information

WORLD CLASS, GLOBALLY CERTIFIED, HIGH AVAILABILITY DATA CENTRE INTELLICENTRE 2 MACQUARIE PARK, SYDNEY

WORLD CLASS, GLOBALLY CERTIFIED, HIGH AVAILABILITY DATA CENTRE INTELLICENTRE 2 MACQUARIE PARK, SYDNEY WORLD CLASS, GLOBALLY CERTIFIED, HIGH AVAILABILITY DATA CENTRE INTELLICENTRE 2 MACQUARIE PARK, SYDNEY A NEW GENERATION OF DATA CENTRE SOLUTIONS AUSTRALIA S FIRST SHOWCASE TIER III CERTIFIED DATA CENTRE

More information

IMPORTANT INSTRUCTIONS & OPERATING MANUAL. Houston 50 Inch Electric Wall Mounted Fireplace Black / White

IMPORTANT INSTRUCTIONS & OPERATING MANUAL. Houston 50 Inch Electric Wall Mounted Fireplace Black / White IMPORTANT INSTRUCTIONS & OPERATING MANUAL Houston 50 Inch Electric Wall Mounted Fireplace Black / White Model Number:MFE5050BK Model Number:MFE5050WH Read these instructions carefully before attempting

More information

Case Study. Cool and green: Citigroup s Frankfurt Data Center

Case Study. Cool and green: Citigroup s Frankfurt Data Center Zug, April 16, 2015 Cool and green: Citigroup s Frankfurt Data Center In Frankfurt, Siemens helps optimize Citigroup s data center. When it comes to building automation, security technology and power supply,

More information

Colocation. Introduction. Structure of the service. Service Description

Colocation. Introduction. Structure of the service. Service Description Introduction IP-Only provides colocation services for customers with very high reliability and availability requirements. In combination with its transmission and IP services, IP-Only offers space in high-security

More information

De energievoorziening in 2040;

De energievoorziening in 2040; De energievoorziening in 2040; decentraal, duurzaam en intelligent! Prof. Dr. Ad van Wijk 25-6-2012 20-06-2012 Delft University of Technology Challenge the future There is no energy crisis Energy efficiency

More information

THE OPTIMAL SOLUTION FOR SMALL AND MEDIUM DATA CENTER

THE OPTIMAL SOLUTION FOR SMALL AND MEDIUM DATA CENTER Your Complete Turnkey Server Room Air Condition UPS THE OPTIMAL SOLUTION FOR SMALL AND MEDIUM DATA CENTER AVAILABLE IN WATER AND GAS SYSTEM MODEL AIR-CONDITIONED CABINET EXCELLENT TEMPERATURE CONTROL FOR

More information

Datacentre London 1. Dedicated managed environment for mission critical services. Six Degrees Group www.6dg.co.uk

Datacentre London 1. Dedicated managed environment for mission critical services. Six Degrees Group www.6dg.co.uk Dedicated managed environment for mission critical services www.6dg.co.uk Our datacentres are the core of our business. At we own and manage 30,000 square feet of highly available, geographically diverse

More information

Data Centers: Definitions, Concepts and Concerns

Data Centers: Definitions, Concepts and Concerns Data Centers: Definitions, Concepts and Concerns Arash Mousavi DCC September 2013 Agenda 1. Introduction 2. Issues in Modern Data Centers: Siemens Integrated Data Center Solutions 3. Issues in Modern Data

More information

Power Management of Cell Sites

Power Management of Cell Sites International Refereed Journal of Engineering and Science (IRJES) ISSN (Online) 2319-183X, (Print) 2319-1821 Volume 2, Issue 9 (September 2013), PP.41-45 Power Management of Cell Sites K.Santhosh Kumar

More information

RULES FOR THE SETTING UP OF SUSTAINABLE BRANCHES Summary

RULES FOR THE SETTING UP OF SUSTAINABLE BRANCHES Summary RULES FOR THE SETTING UP OF SUSTAINABLE BRANCHES Summary January 2013 TABLE OF CONTENTS INTRODUCTION... 3 GENERAL RECOMMENDATIONS... 3 Communication with customers in the field of environmental sustainability...

More information

Glossary of Heating, Ventilation and Air Conditioning Terms

Glossary of Heating, Ventilation and Air Conditioning Terms Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment

More information

Capgemini UK Infrastructure Outsourcing

Capgemini UK Infrastructure Outsourcing Together. Free your energies Capgemini UK Infrastructure Outsourcing Project Arthur Improved Data Centre Efficiency Paul Feeney Capgemini Tony Mills Spie Matthew Hall Project Arthur The Toltec data centre,

More information

Top Technology for Industry, Agriculture, Business and Communities

Top Technology for Industry, Agriculture, Business and Communities Top Technology for Industry, Agriculture, Business and Communities CHP The Technology with a Potential for Saving Energy Combined Heat and Power (CHP) is a highly efficient technology for the conversion

More information

Improving Sustainability in Campus Data Centers Click To Edit Master Title Style

Improving Sustainability in Campus Data Centers Click To Edit Master Title Style Improving Sustainability in Campus Data Centers Click To Edit Master Title Style March 31, 2015 12:10-1:00 PM ET Agenda Welcome and Better Buildings Overview Michigan State University Partnering with the

More information

University of St Andrews. Energy Efficient Data Centre Cooling

University of St Andrews. Energy Efficient Data Centre Cooling Energy Efficient Data Centre Cooling St. Andrews and Elsewhere Richard Lumb Consultant Engineer Future-Tech Energy Efficient Data Centre Cooling There is no one single best cooling solution for all Data

More information

Best Practice Guide for Data Centres - a UH Perspective Steve Bowes-Phipps, Data Centres Manager University of Hertfordshire

Best Practice Guide for Data Centres - a UH Perspective Steve Bowes-Phipps, Data Centres Manager University of Hertfordshire Best Practice Guide for Data Centres - a UH Perspective Steve Bowes-Phipps, Data Centres Manager University of Hertfordshire http://rare idc.herts.ac.uk Best Practice Guide for Data Centres RARE-IDC Overview

More information

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS 527 CMR 31.00: CARBON MONOXIDE ALARMS Section 31.01: Purpose and Scope 31.02: Definitions 31.03: General Installation Provisions 31.04: Specific Installation Provisions 31.05: Carbon Monoxide Protection:

More information

Hybrid heat pumps. saving energy and reducing carbon emissions

Hybrid heat pumps. saving energy and reducing carbon emissions Hybrid heat pumps saving energy and reducing carbon emissions Bart Aspeslagh Product planning and new technology manager, Daikin Europe NV. aspeslagh.b@daikineurope.com Stefanie Debaets Design engineer,

More information

Reducing Data Center Energy Consumption

Reducing Data Center Energy Consumption Reducing Data Center Energy Consumption By John Judge, Member ASHRAE; Jack Pouchet, Anand Ekbote, and Sachin Dixit Rising data center energy consumption and increasing energy costs have combined to elevate

More information

Energy'Saving,'Thermal'Comfort'and'Solar'Power'Information'Sheet'

Energy'Saving,'Thermal'Comfort'and'Solar'Power'Information'Sheet' Energy'Saving,'Thermal'Comfort'and'Solar'Power'Information'Sheet' We ve prepared this information sheet to help you to minimise energy consumption and energy costs while maximising thermal comfort at home.

More information

Using Time-of-Day Scheduling To Save Energy

Using Time-of-Day Scheduling To Save Energy The following article was published in ASHRAE Journal, May 29. Copyright 29 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes only.

More information

Our Hosting Infrastructure. An introduction to our Platform, Data Centres and Data Security. www.in-tuition.net

Our Hosting Infrastructure. An introduction to our Platform, Data Centres and Data Security. www.in-tuition.net Our Hosting Infrastructure An introduction to our Platform, Data Centres and Data Security www.in-tuition.net UK Infrastructure Infrastructure Overview Intuition Networks has provided managed Internet

More information

Legacy Data Centres Upgrading the cooling capabilities What are the options?

Legacy Data Centres Upgrading the cooling capabilities What are the options? Legacy Data Centres Upgrading the cooling capabilities What are the options? Presentation Structure What is a Legacy Data Centre? What is CRAC cooling? ASHRAE Standards Overview Available Cooling Systems

More information

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program

More information

Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues

Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues Design Guide Retrofitting Options For HVAC Systems In Live Performance Venues Heating, ventilation and air conditioning (HVAC) systems are major energy consumers in live performance venues. For this reason,

More information

How green is your data center?

How green is your data center? Siemens Answers: Sustainable Future How green is your data center? Istanbul June 01, 2010 Agenda 1 Solution 2 Siemens Data Center Approach 2 Designing with multiple power density zones can reduce energy

More information

Fuel Cell Powered Data Centers: In-Rack DC Generation

Fuel Cell Powered Data Centers: In-Rack DC Generation Fuel Cell Powered Data Centers: In-Rack DC Generation Li Zhao, Jack Brouwer National Fuel Cell Research Center University of California, Irvine Sean James, Eric Peterson, Jie Liu, Di Wang Microsoft 1/18

More information

AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries

AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries Hot tips and cool ideas to save energy and money! Air conditioning units or systems are often used by foundries

More information

Electrical Efficiency Modeling for Data Centers

Electrical Efficiency Modeling for Data Centers Electrical Efficiency Modeling for Data Centers By Neil Rasmussen White Paper #113 Revision 1 Executive Summary Conventional models for estimating electrical efficiency of data centers are grossly inaccurate

More information

INFO HTK. Hybrid dry cooler. The reference for hybrid dry cooling. 100 4,000 kw

INFO HTK. Hybrid dry cooler. The reference for hybrid dry cooling. 100 4,000 kw INFO HTK Hybrid dry cooler The reference for hybrid dry cooling 4, kw JAEGGI The Original Since 929, JAEGGI has been engaged in the development, production and sale of heat exchangers. Since 995, the company

More information

Colocation Scenario @ MIX

Colocation Scenario @ MIX Colocation Scenario @ MIX INTRODUCTION This white paper describes the colocation scene for ISPs interested to connect to MIX. The intended audience is network operator peering coordinators that have been

More information

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10 TECHNICAL SPECIFICATIONS Page 1 of 10 FIRE DETECTION AND ALARM SYSTEM Scope Furnish a complete 24V DC conventional, electrically supervised, zone annunciated, fire detection and alarm system as specified

More information

HVAC Processes. Lecture 7

HVAC Processes. Lecture 7 HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump

More information

Air Conditioning, Comfort and Energy in India s Commercial Building Sector

Air Conditioning, Comfort and Energy in India s Commercial Building Sector Air Conditioning, Comfort and Energy in India s Commercial Building Sector THINK.CHANGE.DO Leena Thomas Richard dedear Rajan Rawal Ashok Lall PC Thomas University of Technology, Sydney Sydney University

More information

Europe s greenest data center

Europe s greenest data center Europe s greenest data center datadock represents the perfect cooperation of humans, machines and nature. In more than three years of planning and construction and with a total budget of over 17 million

More information

Totally Integrated Power SIESTORAGE. The modular energy storage system for a reliable power supply. www.siemens.com/siestorage

Totally Integrated Power SIESTORAGE. The modular energy storage system for a reliable power supply. www.siemens.com/siestorage Totally Integrated Power SIESTORAGE The modular energy storage system for a reliable power supply www.siemens.com/siestorage Totally Integrated Power (TIP) We bring power to the point. Our products, systems,

More information

Previder Datacenters it starts here

Previder Datacenters it starts here Previder Datacenters it starts here Previder Datacenters Introduction Previder has two sustainable, energy efficient and carrier-neutral datacenters in the Netherlands. Both datacenters have a number of

More information

Specialty Environment Design Mission Critical Facilities

Specialty Environment Design Mission Critical Facilities Brian M. Medina PE Associate Brett M. Griffin PE, LEED AP Vice President Environmental Systems Design, Inc. Mission Critical Facilities Specialty Environment Design Mission Critical Facilities March 25,

More information

HySTAT HYDROGEN GENERATORS

HySTAT HYDROGEN GENERATORS HySTAT HYDROGEN GENERATORS Hydrogen On-Site THE POWER OF EXPERTISE Hydrogenics has a long term tradition building high performance water electrolysers. Since its inception in 1948 (under the name Electrolyser

More information

Data Centre Cooling Technologies. Jon Pettitt, EMEA DataCenter Business Development Manager

Data Centre Cooling Technologies. Jon Pettitt, EMEA DataCenter Business Development Manager Data Centre Cooling Technologies 1 Jon Pettitt, EMEA DataCenter Business Development Manager Munters Group Key facts 3.000 Employees 30 Countries Turnover of 470 M HQ in Sweden Global DC Support 25+ Data

More information

Frankfurt Data Centre Overview

Frankfurt Data Centre Overview Technical Services Briefing Document Frankfurt Data Centre Overview Version 2.1 Contents Introduction... 3 TelecityGroup Data Centre in Frankfurt... 4 Data Centre Characteristics... 4 Technologies in Use

More information

New green datacenter launched in the south of Belgium

New green datacenter launched in the south of Belgium PRESS FOLDER AGILITY CENTER COFELY New green datacenter launched in the south of Belgium This datacenter meets the highest market standards in terms of redundancy and energy efficiency. This datacenter

More information

HBOX SOLAR 3A SOLAR POWERED ELECTROLYSER CASE STUDY 03

HBOX SOLAR 3A SOLAR POWERED ELECTROLYSER CASE STUDY 03 HBOX SOLAR 3A SOLAR POWERED ELECTROLYSER CASE STUDY 03 Case Study 03 HBox Solar: A Solar-Powered Electrolyser Background ITM Power is a developer of hydrogen energy systems based on electrolysis. There

More information

Datacentre Studley. Dedicated managed environment for mission critical services. Six Degrees Group www.6dg.co.uk

Datacentre Studley. Dedicated managed environment for mission critical services. Six Degrees Group www.6dg.co.uk Dedicated managed environment for mission critical services www.6dg.co.uk Our datacentres are the core of our business. At we own and manage 30,000 square feet of highly available, geographically diverse

More information

ALWAYS ON GLOBALSWITCH.COM

ALWAYS ON GLOBALSWITCH.COM ALWAYS ON GLOBALSWITCH.COM Data Centre Design Considerations Kelvin Fong Managing Director, Hong Kong ALWAYS ON GLOBALSWITCH.COM Agenda 1. Introduction to Global Switch 2. Customer Requirements 3. Development

More information

INTERFACES FOR RENEWABLE ENERGY SOURCES WITH ELECTRIC POWER SYSTEMS

INTERFACES FOR RENEWABLE ENERGY SOURCES WITH ELECTRIC POWER SYSTEMS INTERFACES FOR RENEWABLE ENERGY SOURCES WITH ELECTRIC POWER SYSTEMS Paulo Ferreira, Manuel Trindade, Júlio S. Martins and João L. Afonso University of Minho, Braga, Portugal paulo.alves.ferreira@sapo.pt,

More information

Energy Efficiency. Bars & RestauRants. www.energia.ie

Energy Efficiency. Bars & RestauRants. www.energia.ie Energy Efficiency Bars & RestauRants www.energia.ie 2 Your chance to reduce your business energy usage by as much as 20%! 20% is a significant figure and reducing your energy bill by this amount could

More information

Heat pumps: better by nature

Heat pumps: better by nature Heat pumps: better by nature For office buildings, hospitals, swimming pools, Heat, more than 80% of our energy consumption The burning of fossil fuels to meet our energy demand is resulting in the emission

More information

AERMEC DATA CENTRE SOLUTIONS THE COMPLETE RANGE OF AERMEC SOLUTIONS FOR DATA CENTRES

AERMEC DATA CENTRE SOLUTIONS THE COMPLETE RANGE OF AERMEC SOLUTIONS FOR DATA CENTRES AERMEC DATA CENTRE SOLUTIONS THE COMPLETE RANGE OF AERMEC SOLUTIONS FOR DATA GLOBAL DATA CENTRE IP TRAFFIC WILL TRIPLE WITHIN 5 YEARS Global data centre IP traffic has set a constant growth path, with

More information

Energy Saving Fact Sheet Energy Management

Energy Saving Fact Sheet Energy Management Energy Saving Fact Sheet Energy Management Energy it s much more manageable than you think Energy is not an unmanageable overhead it is one of the largest controllable costs in most organisations. Cutting

More information