BCTC/BC Hydroʹs operational experience with Distributed Temperature Sensing (DTS) Systems for Transmission Cables. Presented by

Size: px
Start display at page:

Download "BCTC/BC Hydroʹs operational experience with Distributed Temperature Sensing (DTS) Systems for Transmission Cables. Presented by"

Transcription

1 BCTC/BC Hydroʹs operational experience with Distributed Temperature Sensing (DTS) Systems for Transmission Cables Presented by S. Cherukupalli Transmission Cables Design BC Hydro at the ICC Spring Meeting, St. Petersburgh on March 11,

2 OVERVIEW OF PRESENTATION Theory of Distributed Temperature Sensing. What is the technology application? Who are the suppliers and what are the issues related to testing of these equipment in a utility environment? Describe the BC Hydro/BCTC installations. Describe the type of on-site calibrations and some of the challenges experienced. Describe some desirable features of processing data from a utility perspective. 2

3 WHAT IS DTS? By using only one optical fiber, you can measure actual temperature distribution along the entire fiber in real time, without data transmission devices. Sensor is telecommunication-grade fiber itself, it is compact, lightweight, easy to install, and immune from Electro-magnetic Interference (EMI). 3

4 CONCEPT OF DTS Flash movie courtesy Brad Ellerman 4

5 RAMAN SCATTERING Optical Fiber Sensor DTS Unit Cool water Raman Scattering Anti-Stokes light Injected light Stokes light Molecular vibration weak Scattering Intensity weak Hot water large strong 2 Components of Raman Scattering Rayleigh light Anti-Stokes Stokes λas λo λst 5

6 SPATIAL INFORMATION DTS Unit Optical Fiber Sensor Cool water Hot water Thermal anomalies OP-Thermo t1 L1 Raman Scattering Light t2 L2 Distance is obtained from the roundtrip - time of Raman Scattering Light 6

7 DTS SYSTEM FEATURES High Reliability and Long Life Time of Light Source (MTBF >200,000 hours ) High Speed of Signal Processing Circuit Low Noise and Wide Bandwidth of Photodetector Circuit Useful and excellent GUI control software on PC Total support of system (from fiber sensor until software) Light Source RAMAN SCATTERING PC Signal Processing Circuit Photo - detector DTS Main Unit Optical Fiber (GI 50/125μm) 7

8 TYPICAL DTS SYSTEM Alarm Output PERSONAL COMPUTER Control Main Unit Optical Switch Fiber-optic Sensor Temp.Info. PC Controls OP- Thermo, saves the measured temperature data, and outputs alarm on its display. The light pulse is injected from one end of an optical fiber, and back scattering (Raman Scattering) is measured. By using Optical Switch,several Fiber-Optic Sensors can be measured one after another (Max.16CH). By using only optical fiber, you can measure actual temperature distribution along the entire fiber, at real time, without data transmission devices. 8

9 SUPPLIERS OF DTS EQUIPMENT SENSA Schlumberger (UK) (30km, 2m resolution, 0.5 C) Sensornet (UK) (30km-2m resolution, 0.05 C) SensorTran (Austin, USA) Sumitomo Corporation (Japan) Luna Innovations (Blacksburgh, Virginia) (10mm ±0.1 C) USi representing Agilent 12km, 1m, 0.1 C) LIOS (Germany) (0.5m to 1m resolution) Hitachi (Hitele) 30km, ±1.0 C 9

10 ISSUES RELEVANT TO UTILITY-1 How many channels do we need? What is the monitoring distance in km? What kind of spatial resolution (1m?) do we need? Temperature accuracy (±1.0 C adequate?) What should be the response time? 10

11 ISSUES RELEVANT TO UTILITY-2 Are the results repeatable? How does one specify the equipment How does one undertake site calibration? What are EMC compliance requirements? Do I need local data storage? How do I communicate with the device? Do I need to integrate this data with Power System Control Centre? 11

12 Examples of BC Hydro installations BC Hydro has been using DTS Technology from Monitoring 69kV circuits in the downtown core. Along spare duct on a 49-year old cable system (2L40). Along spare duct on a 49-year old cable system (2L50). Along a spare duct on a brand new 230kV SCFF cable (2L33). Retrofitted in the conductor of a 525 kv AC submarine cable installation. BC Hydro/BCTC have four DTS units that range from 2km to 10km systems. 12

13 PHOTOS OF SOME INSTALLATIONS 13

14 BLOWING FIBER INTO SPARE DUCT 242 kv SCFF Cable 3.5km long FO Cable blown into duct 14

15 FO CABLE IN SPARE DUCT 242 kv SCFF CABLE 9km long 15

16 MITIGATION AT STEAM CROSSING Duct bank Insulation on Steam crossing Copper straps 16

17 MITIGATION AT STEAM CROSSING 17

18 THERMAL BACK-FILL 18

19 DTS SYSTEM MONITORING A HPFF CABLE 19

20 525kV Submarine Cable Terminal Station Low-low water mark 20

21 CROSS-SECTION of THE 525 kv CABLE 155 mm dia 21

22 GENERAL ARRANGEMENTS 22

23 FIBER INSTALLATION 23

24 HIGH-ALTITUDE OPTICAL SPLICING 24

25 DTS Units at Two sites 25

26 DTS CALIBRATION 26

27 DTS On-site calibration Calibration of loop near base of termination Calibration of loop at the top of the pothead 27

28 RESULTS 28

29 RESULTS ALONG A 69kV CABLE 60L52 - Fiber # Temperature Distance (m) 29

30 EFFECTS OF MITIGATION Cct. 60L51 & 60L53 - Steam Beatty St 500mm Steam Pipe Crossing Under (2.9m down to Top of Ductbank) Grade 2.2 m mm Dia. Steam Pipe Dec Jan Mar Apr Jun-99 8-Aug Sep Nov-99 5-Jan Feb Apr-00 Temp (C) Remediation Excavate & Insulate Feb. 13, m. C F B A 0.5 m. C A B View tow ard Murrin Steam Manhole Fiber Re-located in Ductbank March 24 Date 30

31 MEASUREMENTS WITH WATER CIRCULATION 40 DTS Measurements along 60L51/53 During Water circulation in ducts between two manholes (MH # KQ to KP) 35 Temperature (deg C) Before water circulation 5 After water circulation Location along the optical cable 31

32 RESULTS FROM STEAM CROSSING ACROSS HPFF CABLE Steam crossing 32

33 MEASUREMENTS ALONG A NEW 230kV CABLE Temperature measurements along 2L33 from HPN-CSQ on Fibre 1 on Apr 28 at 14:17 HPN Temperature (deg C) MH 3759 Near steam crossing CSQ MH Near water main Distance (m) 33

34 RESULTS FROM 525kV CABLE 70 Alarm Threshold 60 DTS Temperatures (deg C) CONTROL ROOM Warning Threshold Traces for G1 at 8:00 and 16:00 hrs FIMT loop in the corona shield of cable termination measuring air temperature Cable G2 Change in cable conductor temperature attributed to the tidal charges cooling the section in the ocean Cable G3 Cable G4 Cable G5 REMOTE FIBRE END 10 Cable G Distance along fibre from control room (m) 34

35 ARCHITECTURE- An option? * 35

36 Desired features of DTS System Local data storage Remote access to unit Data reliability and consistency Ease of equipment use Warning alarms System integration 36

37 QUESTIONS? 37

N4385A / N4386A Distributed Temperature System (DTS)

N4385A / N4386A Distributed Temperature System (DTS) N4385A / N4386A Distributed Temperature System (DTS) Enabling fast, reliable and cost-effective sensing through highly integrated optical measurement systems s Distributed Temperature Sensing Oil & Gas

More information

Distributed Temperature Sensing - DTS

Distributed Temperature Sensing - DTS Intelligent Solutions Distributed Temperature Sensing - DTS Enabling fast, reliable and cost-effective sensing through highly integrated optical measurement systems Fire detection Power cable monitoring

More information

Christine E. Hatch University of Nevada, Reno

Christine E. Hatch University of Nevada, Reno Christine E. Hatch University of Nevada, Reno Roadmap What is DTS? How Does it Work? What Can DTS Measure? Applications What is Distributed Temperature Sensing (DTS)? Temperature measurement using only

More information

CABLE ASSET MANAGEMENT PREDICT WITH CERTAINTY. Kuljit Singh BSc Honours MIEE(IET,UK) 5 June 2014

CABLE ASSET MANAGEMENT PREDICT WITH CERTAINTY. Kuljit Singh BSc Honours MIEE(IET,UK) 5 June 2014 CABLE ASSET MANAGEMENT PREDICT WITH CERTAINTY Kuljit Singh BSc Honours MIEE(IET,UK) 5 June 2014 Definitions International Workshop 2014 DTS: Distributed Temperature Sensor DCR: Dynamic Cable Ratings (

More information

CABLE MONITORING SOLUTION

CABLE MONITORING SOLUTION POWER CABLE MONITORING SOLUTION Kuljit Singh BSc Honours MIEE(IET,UK) Dan Watley Ph. D, B.A MEng (UK), MIEEE, UK 8-9 November 2011 PREDICT WITH CERTAINTY Definition DTS: Distributed Temperature Sensor

More information

LNG Monitoring. Fiber-Optic Leakage Detection System. Pipeline leakage detection. Regasification and liquefaction monitoring

LNG Monitoring. Fiber-Optic Leakage Detection System. Pipeline leakage detection. Regasification and liquefaction monitoring LNG Monitoring Fiber-Optic Leakage Detection System Pipeline leakage detection Regasification and liquefaction monitoring Tank annulus and base slab monitoring Spill containment control Intelligent Solutions

More information

Distributed Temperature Monitoring of Energy Transmission and Distribution Systems

Distributed Temperature Monitoring of Energy Transmission and Distribution Systems 1 m 40000m0 range 61850 IEC spatial resolution Distributed Temperature Monitoring of Energy Transmission and Distribution Systems Ensuring a Reliable Supply of Electrical Power for Today s World www.en-sure.pro

More information

Intelligent Solutions DTS Applications LNG Facilities

Intelligent Solutions DTS Applications LNG Facilities DTS Applications LNG Facilities Dan Danskin LNG Tech Global Summit 2013 1 Agenda What, Why, Who and Where to use DTS Established LNG Applications Emerging LNG Applications Summary Technology (if required)

More information

AT&T Global Network Client for Windows Product Support Matrix January 29, 2015

AT&T Global Network Client for Windows Product Support Matrix January 29, 2015 AT&T Global Network Client for Windows Product Support Matrix January 29, 2015 Product Support Matrix Following is the Product Support Matrix for the AT&T Global Network Client. See the AT&T Global Network

More information

Fiber Optic Distributed Temperature Sensor (B-DTS)

Fiber Optic Distributed Temperature Sensor (B-DTS) Fiber Optic Distributed Temperature Sensor (B-DTS) Low-cost Brillouin BOTDA scattering version For more information about our strain and temperature sensor system and related products, please visit www.ozoptics.com

More information

6 th Pipeline Technology Conference 2011

6 th Pipeline Technology Conference 2011 6 th Pipeline Technology Conference 2011 Leakage Detection using Fibre Optics Distributed Temperature Sensing Ashim Mishra, Ashwani Soni Engineers India Limited, New Delhi, India Abstract Pipelines have

More information

Fiber Optic High Density ACC Sensor System Faser Optisches Beschleunigungs-Messsystem

Fiber Optic High Density ACC Sensor System Faser Optisches Beschleunigungs-Messsystem End Winding Remote unit PNR: 9600.30.180 Remote unit and 6 x One-Axis optical, MIC-Accelerometer Frequency response 1 1000 Hz Easy installation on the end-winding High voltage electrical insulation between

More information

COMPARISON OF FIXED & VARIABLE RATES (25 YEARS) CHARTERED BANK ADMINISTERED INTEREST RATES - PRIME BUSINESS*

COMPARISON OF FIXED & VARIABLE RATES (25 YEARS) CHARTERED BANK ADMINISTERED INTEREST RATES - PRIME BUSINESS* COMPARISON OF FIXED & VARIABLE RATES (25 YEARS) 2 Fixed Rates Variable Rates FIXED RATES OF THE PAST 25 YEARS AVERAGE RESIDENTIAL MORTGAGE LENDING RATE - 5 YEAR* (Per cent) Year Jan Feb Mar Apr May Jun

More information

COMPARISON OF FIXED & VARIABLE RATES (25 YEARS) CHARTERED BANK ADMINISTERED INTEREST RATES - PRIME BUSINESS*

COMPARISON OF FIXED & VARIABLE RATES (25 YEARS) CHARTERED BANK ADMINISTERED INTEREST RATES - PRIME BUSINESS* COMPARISON OF FIXED & VARIABLE RATES (25 YEARS) 2 Fixed Rates Variable Rates FIXED RATES OF THE PAST 25 YEARS AVERAGE RESIDENTIAL MORTGAGE LENDING RATE - 5 YEAR* (Per cent) Year Jan Feb Mar Apr May Jun

More information

Analysis One Code Desc. Transaction Amount. Fiscal Period

Analysis One Code Desc. Transaction Amount. Fiscal Period Analysis One Code Desc Transaction Amount Fiscal Period 57.63 Oct-12 12.13 Oct-12-38.90 Oct-12-773.00 Oct-12-800.00 Oct-12-187.00 Oct-12-82.00 Oct-12-82.00 Oct-12-110.00 Oct-12-1115.25 Oct-12-71.00 Oct-12-41.00

More information

Underground Cable Temperature Monitoring in the Real World

Underground Cable Temperature Monitoring in the Real World Underground Cable Temperature Monitoring in the Real World Executive Summary Background Brain Storming Possible Causes to Duct Bank Over Heating Mitigating Duct Bank Overheating DTS Installation for Duct

More information

How To Use A Fibre Optic Temperature Sensor

How To Use A Fibre Optic Temperature Sensor Fibre Optic Distributed Temperature Sensing System Introduction of FODTS The Fibre Optic Distributed Temperature Sensing (DTS) technology using Raman-effect was initially developed in 1980s at Southampton

More information

DTS / PDMS / Portable. www.mpc2001.com

DTS / PDMS / Portable. www.mpc2001.com DTS / PDMS / Portable www.mpc2001.com Contents DTS/CTM/DRS System PD Monitoring System Portable Diagnosis 2 DTS System DTS Principle Use the optic cable for sensor of temperaturere Sensing of temperature

More information

Lucien Antonissen Key Account Manager LIOS Technology Germany

Lucien Antonissen Key Account Manager LIOS Technology Germany Lucien Antonissen Key Account Manager LIOS Technology Germany Content Company Markets DTS Controller Software Configuration RTTR Demonstration Q&A NKT Holding 2013 NKT Holding Nilfisk-Advance NKT Cables

More information

- 33 - This paper describes an instrumentation system concept which should be capable of early detection of a leak-before* break in main steam lines.

- 33 - This paper describes an instrumentation system concept which should be capable of early detection of a leak-before* break in main steam lines. - 33 - DETECTION OF LEAKS IN STEAM LINES BY DISTRIBUTED FIBRE-OPTIC TEMPERATURE SENSING (DTS) Author; Neil G.Craik, Nuclear Generation Consultant, Frederic ton, N.B., Canada ABSTRACT This paper describes

More information

Case 2:08-cv-02463-ABC-E Document 1-4 Filed 04/15/2008 Page 1 of 138. Exhibit 8

Case 2:08-cv-02463-ABC-E Document 1-4 Filed 04/15/2008 Page 1 of 138. Exhibit 8 Case 2:08-cv-02463-ABC-E Document 1-4 Filed 04/15/2008 Page 1 of 138 Exhibit 8 Case 2:08-cv-02463-ABC-E Document 1-4 Filed 04/15/2008 Page 2 of 138 Domain Name: CELLULARVERISON.COM Updated Date: 12-dec-2007

More information

Using Industrial Ethernet Switches to Assure Maximum Uptime White Paper

Using Industrial Ethernet Switches to Assure Maximum Uptime White Paper Six Best Practices for Effective Wind Farm Operation Using Industrial Ethernet Switches to Assure Maximum Uptime White Paper Six Best Practices for Effective Wind Farm Operation Using Industrial Ethernet

More information

M. GELDON Brugg Kabel CZ. Ing. D. RÚŽEK PREdistribuce. Switzerland Czech Rep. Czech Rep. Czech Rep., Switzerland Germany

M. GELDON Brugg Kabel CZ. Ing. D. RÚŽEK PREdistribuce. Switzerland Czech Rep. Czech Rep. Czech Rep., Switzerland Germany 21, rue d Artois, F-75008 PARIS Paper number CIGRE 2012 http : //www.cigre.org 6 characters (to be provided later) Correlation between calculated transmission capacity and actual one D. WALD* Eifelkabel

More information

Real Time Monitoring of Power Cables by Fibre Optic Technologies Tests, Applications and Outlook

Real Time Monitoring of Power Cables by Fibre Optic Technologies Tests, Applications and Outlook Real Time Monitoring of Power Cables by Fibre Optic Technologies Tests, Applications and Outlook LUTON Marie-Hélène SAGEM SA, Activité Câbles Rue de Varennes Prolongée 77876 Montereau Cedex France Phone

More information

Subsea Asset Monitoring using Distributed Fiber Optic Sensing

Subsea Asset Monitoring using Distributed Fiber Optic Sensing Subsea Asset Monitoring using Distributed Fiber Optic Sensing Carlos Borda Omnisens S.A. Subsea Asia Conference June 2014 Agenda Who is Omnisens? Distributed Fiber Optic Monitoring Power Umbilicals Flow

More information

Climatography of the United States No. 20 1971-2000

Climatography of the United States No. 20 1971-2000 Climate Division: CA 4 NWS Call Sign: Month (1) Min (2) Month(1) Extremes Lowest (2) Temperature ( F) Lowest Month(1) Degree s (1) Base Temp 65 Heating Cooling 1 Number of s (3) Jan 59.3 41.7 5.5 79 1962

More information

Commercial Cable Installation Philadelphia PA

Commercial Cable Installation Philadelphia PA Commercial Cable Installation Philadelphia PA About Us Squid Wire is a low voltage cabling company which is dedicated to providing solid, reliable technology advice and solutions to support our clients

More information

Solution 1: Algorithm Positioning

Solution 1: Algorithm Positioning Model No: OEAFP Series All-Fiber Pipeline Security System Solutions Solution 1: Algorithm Positioning Application conditions Applicable for outdoor long-distance oil-gas pipeline security monitoring without

More information

Enhanced Vessel Traffic Management System Booking Slots Available and Vessels Booked per Day From 12-JAN-2016 To 30-JUN-2017

Enhanced Vessel Traffic Management System Booking Slots Available and Vessels Booked per Day From 12-JAN-2016 To 30-JUN-2017 From -JAN- To -JUN- -JAN- VIRP Page Period Period Period -JAN- 8 -JAN- 8 9 -JAN- 8 8 -JAN- -JAN- -JAN- 8-JAN- 9-JAN- -JAN- -JAN- -JAN- -JAN- -JAN- -JAN- -JAN- -JAN- 8-JAN- 9-JAN- -JAN- -JAN- -FEB- : days

More information

Climatography of the United States No. 20 1971-2000

Climatography of the United States No. 20 1971-2000 Climate Division: CA 6 NWS Call Sign: SAN Month (1) Min (2) Month(1) Extremes Lowest (2) Temperature ( F) Lowest Month(1) Degree s (1) Base Temp 65 Heating Cooling 100 Number of s (3) Jan 65.8 49.7 57.8

More information

Distributed Temperature Sensing using Fibre-Optics (DTS Systems)

Distributed Temperature Sensing using Fibre-Optics (DTS Systems) Distributed Temperature Sensing using Fibre-Optics (DTS Systems) Presented to 2000 Electricity Engineers Association Annual Conference, Auckland, New Zealand 16/17 June 2000 Authors: David Peck, Managing

More information

Practical Application of Industrial Fiber Optic Sensing Systems

Practical Application of Industrial Fiber Optic Sensing Systems Practical Application of Industrial Fiber Optic Sensing Systems John W. Berthold and David B. Needham Davidson Instruments, Inc. P.O. Box 130100, The Woodlands, TX 77393 ABSTRACT In this presentation,

More information

GLOBAL COLLEGE OF ENGINEERING &TECHNOLOGY: YSR DIST. Unit VII Fiber Optics Engineering Physics

GLOBAL COLLEGE OF ENGINEERING &TECHNOLOGY: YSR DIST. Unit VII Fiber Optics Engineering Physics Introduction Fiber optics deals with the light propagation through thin glass fibers. Fiber optics plays an important role in the field of communication to transmit voice, television and digital data signals

More information

Introduction to SensorTran

Introduction to SensorTran 4401 Freidrich Lane, Bldg. 307, Austin, TX 78744, USA P: +1 512-583-3520 F: +1 512-583-3565 Houston, USA Richmond, USA Southampton, England, UK Introduction to SensorTran SensorTran offers smart fiber

More information

How To Monitor Temperature On A Power Line

How To Monitor Temperature On A Power Line Distributed Temperature Monitoring of Energy Transmission Systems Ensuring a Reliable Supply of Electrical Power for Today s World Preventive Measures to Avoid Power Outages As demand for electricity continues

More information

Utilizing Furukawa Optical Fiber Technology. Optical Fiber Sensing System

Utilizing Furukawa Optical Fiber Technology. Optical Fiber Sensing System Utilizing Furukawa Optical Fiber Technology Optical Fiber Sensing Point Special features of optical fiber sensing s 1Reduced installation cost Sensors (measurement location) require no electrical work

More information

FOM-5A, 6A. Asynchronous Fiber Optic Modem

FOM-5A, 6A. Asynchronous Fiber Optic Modem FOM-5A, 6A Asynchronous Fiber Optic Modem FEATURES Asynchronous transmission at up to 19.2 kbps Transmission range up to 3 km (1.8 mi), regardless of data rate Full- or half-duplex Transfers one control

More information

HV Submarine Cable Systems Design, Testing and Installation

HV Submarine Cable Systems Design, Testing and Installation HV Submarine Cable Systems Design, Testing and Installation CIGRE Ireland Technical Seminar 6 th October 2010 Robert Donaghy Senior Consultant Engineer, ESB International Presentation Overview Applications

More information

XFEL DAQ and control network infrastructure Minutes of the 27 th March 2008 meeting (Revised 3.4.2008)

XFEL DAQ and control network infrastructure Minutes of the 27 th March 2008 meeting (Revised 3.4.2008) XFEL DAQ and control network infrastructure Minutes of the 27 th March 2008 meeting (Revised 3.4.2008) 1. Present DESY-IT: Kars Ohrenberg, Thomas Witt, XFEL: Thomas Hott. WP76: Sergey Esenov and Christopher

More information

Fiber Optics. Integrated Photo Detector Receiver for Plastic Fiber Plastic Connector Housing SFH551/1-1 SFH551/1-1V

Fiber Optics. Integrated Photo Detector Receiver for Plastic Fiber Plastic Connector Housing SFH551/1-1 SFH551/1-1V Fiber Optics Integrated Photo Detector Receiver for Plastic Fiber Plastic Connector Housing SFH551/1-1 Features Bipolar IC with open-collector output Digital output, TTL compatible Sensitive in visible

More information

Silicon Seminar. Optolinks and Off Detector Electronics in ATLAS Pixel Detector

Silicon Seminar. Optolinks and Off Detector Electronics in ATLAS Pixel Detector Silicon Seminar Optolinks and Off Detector Electronics in ATLAS Pixel Detector Overview Requirements The architecture of the optical links for the ATLAS pixel detector ROD BOC Optoboard Requirements of

More information

USB 3.0 Cables. Color. Black Black Black Black Black 3021003-03 3021009-06 3021015-10 3021021-16 3021027-16. Black Black Black Black Black

USB 3.0 Cables. Color. Black Black Black Black Black 3021003-03 3021009-06 3021015-10 3021021-16 3021027-16. Black Black Black Black Black USB.0 CableS USB.0 and backwards compatible for USB.0 and. Supports high speed, 480Mbps Twisted-pair construction reduces cross talk to ensure error free transfer USB A male to USB B male 00-0 007-0 0-09-

More information

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw 4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and

More information

Introducing TransitVUE Perimeter IDS, the most advanced perimeter intrusion detection system available today! Protecting Perimeters Around the World

Introducing TransitVUE Perimeter IDS, the most advanced perimeter intrusion detection system available today! Protecting Perimeters Around the World Introducing TransitVUE Perimeter IDS, the most advanced perimeter intrusion detection system available today! Introduction The rising demand for advanced perimeter security detection systems against intrusion

More information

Cable Network Transparency Unified Monitoring System UMS

Cable Network Transparency Unified Monitoring System UMS Cable Network Transparency Unified System UMS Fault recognition, localisation and reporting UMS Universal cable network and equipment monitoring cable networks and associated equipment used to be considered

More information

Real-time Subsea Pipeline Leak Monitoring using Fiber Optic Sensing Technology

Real-time Subsea Pipeline Leak Monitoring using Fiber Optic Sensing Technology Real-time Subsea Pipeline Leak Monitoring using Fiber Optic Sensing Technology Prem Thodi, Ph.D., P.Eng., Senior Engineering Specialist INTECSEA Canada, WorleyParsons 12 th March 2015, Perth, Australia

More information

Applying ICT and IoT to Multifamily Buildings. U.S. Department of Energy Buildings Interoperability Vision Meeting March 12, 2015 Jeff Hendler, ETS

Applying ICT and IoT to Multifamily Buildings. U.S. Department of Energy Buildings Interoperability Vision Meeting March 12, 2015 Jeff Hendler, ETS Applying ICT and IoT to Multifamily Buildings U.S. Department of Energy Buildings Interoperability Vision Meeting March 12, 2015 Jeff Hendler, ETS ETS is an Energy Technology, Behavior Management, and

More information

Climatography of the United States No. 20 1971-2000

Climatography of the United States No. 20 1971-2000 Climate Division: CA 2 NWS Call Sign: SAC Month (1) Min (2) Month(1) Extremes Lowest (2) Temperature ( F) Lowest Month(1) Degree s (1) Base Temp 65 Heating Cooling 100 Number of s (3) Jan 53.8 38.8 46.3

More information

Optical fiber intrusion detection fence sensor

Optical fiber intrusion detection fence sensor Optical fiber intrusion detection fence sensor This is an Intrusion detection fence sensor More accurate detection More reliable detection Simpler installation Wider detection coverage 6 7 8 Better immunity

More information

FOSTCDR. Industrial Serial to Multimode Fiber Optic Converter PRODUCT INFORMATION B&B ELECTRONICS. Specifications Serial Technology

FOSTCDR. Industrial Serial to Multimode Fiber Optic Converter PRODUCT INFORMATION B&B ELECTRONICS. Specifications Serial Technology FOSTCDR pn 8684R1 FOSTCDR-0812ds page 1/5 Industrial Serial to Multimode Fiber Optic Converter Data Rates up to 115.2 kbps 2.5 Mile (4 km) Range 10 to 30 VDC Input Voltage Wide Operating Temperature 2000V

More information

CENTERPOINT ENERGY TEXARKANA SERVICE AREA GAS SUPPLY RATE (GSR) JULY 2015. Small Commercial Service (SCS-1) GSR

CENTERPOINT ENERGY TEXARKANA SERVICE AREA GAS SUPPLY RATE (GSR) JULY 2015. Small Commercial Service (SCS-1) GSR JULY 2015 Area (RS-1) GSR GSR (LCS-1) Texarkana Incorporated July-15 $0.50690/Ccf $0.45450/Ccf $0.00000/Ccf $2.85090/MMBtu $17.52070/MMBtu Texarkana Unincorporated July-15 $0.56370/Ccf $0.26110/Ccf $1.66900/Ccf

More information

Hybrid-Cable-System with an Advanced Data and Power Architecture Product Brief

Hybrid-Cable-System with an Advanced Data and Power Architecture Product Brief Hybrid-Cable-System with an Advanced Data and Power Architecture Product Brief Brugg Cables and PowiDian 11-11-2015 What is PowiDian? PowiDian is a Smart-Energy-Systems-Integrator and is covering: Production

More information

Computers Are Your Future. 2006 Prentice-Hall, Inc.

Computers Are Your Future. 2006 Prentice-Hall, Inc. Computers Are Your Future 2006 Prentice-Hall, Inc. Computers Are Your Future Chapter 3 Wired and Wireless Communication 2006 Prentice-Hall, Inc Slide 2 What You Will Learn... ü The definition of bandwidth

More information

CPCI-3U-AC-300W-R. Rugged 300W AC Input 3U CompactPCI Power Supply. Electrical Specification for: Telkoor Part Number: 900-4602-0000

CPCI-3U-AC-300W-R. Rugged 300W AC Input 3U CompactPCI Power Supply. Electrical Specification for: Telkoor Part Number: 900-4602-0000 Electrical Specification for: CPCI-3U-AC-300W-R Rugged 300W AC Input 3U CompactPCI Power Supply Telkoor Part Number: 900-4602-0000 GENERAL SCALE RELEASE DATE 12/9/06 SHEET 1 OF 6 REVISION HISTORY Rev Level

More information

PIPELINE LEAKAGE DETECTION USING FIBER-OPTIC DISTRIBUTED STRAIN AND TEMPERATURE SENSORS WHITE PAPER

PIPELINE LEAKAGE DETECTION USING FIBER-OPTIC DISTRIBUTED STRAIN AND TEMPERATURE SENSORS WHITE PAPER PIPELINE LEAKAGE DETECTION USING FIBER-OPTIC DISTRIBUTED STRAIN AND TEMPERATURE SENSORS WHITE PAPER Lufan Zou and Taha Landolsi OZ Optics Limited, 219 Westbrook Road, Ottawa, ON, Canada, K0A 1L0 E-mail:

More information

Power over Ethernet technology for industrial Ethernet networks

Power over Ethernet technology for industrial Ethernet networks Power over Ethernet technology for industrial Ethernet networks Introduction Ethernet networking has grown beyond office and home usage to become a very successful protocol suite used in many industrial

More information

Permanent Distributed Temperature Sensing at the Ketzin CO 2 Storage Test Site. ieaghg 6th Wellbore Network Meeting, April 28-29, 2010

Permanent Distributed Temperature Sensing at the Ketzin CO 2 Storage Test Site. ieaghg 6th Wellbore Network Meeting, April 28-29, 2010 Permanent Distributed Temperature Sensing at the Ketzin CO 2 Storage Test Site Jan Henninges ieaghg 6th Wellbore Network Meeting, April 28-29, 2010 Introduction Objectives of temperature measurements at

More information

Optical fibre sensors for hydro-geological applications

Optical fibre sensors for hydro-geological applications Optical fibre sensors for hydro-geological applications L. Schenato National Research Council, Research Institute for Hydro-Geological Protection - Padova Unit - Italy 2 Spoiler alert! Giving away the

More information

ALARMLINE ANALOGUE Linear Heat Detection System

ALARMLINE ANALOGUE Linear Heat Detection System ALARMLINE ANALOGUE Alarmline Analogue sensor cable senses temperature variations by continuously monitoring the resistance of specially doped N.T.C. polymeric insulation. A change in temperature produces

More information

3-Channel Supervisor IC for Power Supply

3-Channel Supervisor IC for Power Supply 3-Channel Supervisor IC for Power Supply Features Over-voltage protection and lockout Under-voltage protection and lockout Open drain power good output signal Built-in 300mS delay for power good 38mS de-bounce

More information

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK Pressure monitoring equipment for oil-sf 6 bushings, type GOEK Installation and maintenance guide 5693 827-6 en, Rev. 3, 2002-01-30 This document must not be copied without our written permission, and

More information

Assessing, Maintaining & Replacing Fluid Filled Cable Systems at PEPCO

Assessing, Maintaining & Replacing Fluid Filled Cable Systems at PEPCO April 2, 2014 Assessing, Maintaining & Replacing Fluid Filled Cable Systems at PEPCO Todd Goyette, P.E., POWER Engineers Mousa Hejazi, P.E., Pepco Holdings Inc. 1 Pepco Quick Facts First incorporated in

More information

Removing the Mystery from OTDR Measurements. Keith Foord Product Manager Greenlee Communications

Removing the Mystery from OTDR Measurements. Keith Foord Product Manager Greenlee Communications Removing the Mystery from OTDR Measurements Keith Foord Product Manager Greenlee Communications Why an OTDR? Terminology Theory Standards Key specifications Trade-offs Cleaning and Inspection Measurements

More information

Security & Surveillance Cabling Systems

Security & Surveillance Cabling Systems Security & Surveillance Cabling Systems Security and Surveillance Cabling Systems The video security industry is growing and ever-changing, offering a wealth of opportunity for today s security professionals.

More information

Cable Condition Monitoring to Improve Reliability

Cable Condition Monitoring to Improve Reliability Cable Condition Monitoring to Improve Reliability by Hilary Marazzato, Ken Barber, Mark Jansen, and Graeme Barnewall Olex Australia Page 1-1 - Cable Condition Monitoring of Improve Reliability Hilary Marazzato,

More information

www.quicknetworksolutions.net RC: 960240

www.quicknetworksolutions.net RC: 960240 QSL is a growing business that s offering IT Solutions and services to SME and Established Organizations with a high level of understanding and fully qualified, friendly and knowledgeable consultants.

More information

Temperature Monitoring Windfarm Cable Circuits

Temperature Monitoring Windfarm Cable Circuits Temperature Monitoring Windfarm Cable Circuits Close Down Report DTS Tier 1 LCNF SPT1005 Temperature Monitoring Windfarm Cable Circuits July 2015 For enquiries please contact: Geoff Murphy, Technology

More information

DETECTION AND LOCALIZATION OF MICRO LEAKAGES IN

DETECTION AND LOCALIZATION OF MICRO LEAKAGES IN IBP1248_13 DETECTION AND LOCALIZATION OF MICRO LEAKAGES IN MULTIPHASE PIPELINES USING DISTRIBUTED FIBER OPTIC SENSING Daniele Inaudi 1, Riccardo Belli 2, Francesco Gasparoni 3 Federico Bruni 4, Angelo

More information

Aerial Fibre Optics. Complete One Stop Solution for Aerial Fibre Optics. OPGW Cable and Fittings for OPGW

Aerial Fibre Optics. Complete One Stop Solution for Aerial Fibre Optics. OPGW Cable and Fittings for OPGW Complete One Stop Solution for OPGW Cable and Fittings for OPGW 53, Justice Chandra Madhav Road, Kolkata - 700020. India. Phone: 91-33-24748575 / 7565 Fax: 91-33-2476-1955 Email: sales@supremeco.com Website:

More information

Optical Fibers Fiber Optic Cables Indoor/Outdoor

Optical Fibers Fiber Optic Cables Indoor/Outdoor presents Optical Fibers Fiber Optic Cables Indoor/Outdoor Content Optical fiber function, types optical effects applications production of optical fibre Cable - general types Indoor Indoor / outdoor Outdoor

More information

Heller Industries, Inc. PN: 689011 Rev-I Heller Oven Windows-XP Software Version log for HC1 controller

Heller Industries, Inc. PN: 689011 Rev-I Heller Oven Windows-XP Software Version log for HC1 controller PN: 689011 RevI Heller Oven WindowsXP Software Version log for HC1 controller Page 1 of 5 Software Version 4.0.0.0 11202005 4.0.0.1 Feb2706 4.0.0.2 Mar2706 4.0.0.3 Apr2706 4.0.0.3a Jun2706 4.0.0.4 7132006

More information

API Marine. BMS Presentation. Ballast Measurement Systems

API Marine. BMS Presentation. Ballast Measurement Systems API Marine BMS Presentation Ballast Measurement Systems BMS4 Typical Configuration BMS4 Typical Configuration BMS4 Extended Configuration BMS4 System (24 tanks) Air regulator Terminal block Drain/Air Filter

More information

- Monitoring Array: a seismic or infrasound array, including from 1(4) to 20 Remote Elements (RE) and one Central Recording Facility (CRF).

- Monitoring Array: a seismic or infrasound array, including from 1(4) to 20 Remote Elements (RE) and one Central Recording Facility (CRF). Page 1 of 30 Page 2 of 30 1. Basic terminology - Monitoring Array: a seismic or infrasound array, including from 1(4) to 20 Remote Elements (RE) and one Central Recording Facility (CRF). - Remote Element:

More information

Long step-outs, but avoiding increases in electrical core size. AOG 2012, 23 February 2012 Jan van den Akker, Product Manager, Controls

Long step-outs, but avoiding increases in electrical core size. AOG 2012, 23 February 2012 Jan van den Akker, Product Manager, Controls Long step-outs, but avoiding increases in electrical core size AOG 2012, 23 February 2012 Jan van den Akker, Product Manager, Controls Introduction Power and Communication Distribution Step-out and Voltage

More information

Fiber Optic Cable Pipeline Leak Detection Systems for Arctic & Cold Region Applications

Fiber Optic Cable Pipeline Leak Detection Systems for Arctic & Cold Region Applications Fiber Optic Cable Pipeline Leak Detection Systems for Arctic & Cold Region Applications Prem Thodi, Mike Paulin, Duane DeGeer & Craig Young INTECSEA November 18-19, 2014 Outline Who we are Experience with

More information

AMSC s Superconductor Cable Technologies for Electric Utilities

AMSC s Superconductor Cable Technologies for Electric Utilities International Workshop 2014 AMSC s Superconductor Cable Technologies for Electric Utilities Michael Ross, P.E. Managing Director of Superconductor Power Systems AMSC Corporate Facts Headquartered in MA,

More information

Multi Media Cable Tester TM-901N/TM-902/TM-903

Multi Media Cable Tester TM-901N/TM-902/TM-903 Multi Media Cable Tester TM-901N/TM-902/TM-903 User Manual HB2TM9020010 TENMARS ELECTRONICS CO., LTD Table of Contents 1 Introduction... 1 2 Safety Precaution... 1 3 The verifier does the following:...

More information

This page intentionally blank.

This page intentionally blank. This page intentionally blank. Sentinal DTS User Guide SEN2-UM1.0 Page i CONTENTS 1. INTRODUCTION...1 2. AFTER SALES SERVICE...2 3. WARRANTY...3 Sensornet 12 month Warranty (Support Level 1)... 3 Extended

More information

Medium voltage arc flash eliminator units VAM 3ED,

Medium voltage arc flash eliminator units VAM 3ED, Medium voltage arc flash eliminator units VAM 3ED,, Medium voltage arc flash eliminator units Medium voltage arc flash eliminator units The new innovative arc eliminator VAM 3ED is an extremely fast acting

More information

Section D..General Auto Electrical Corporation

Section D..General Auto Electrical Corporation 43 Section D..General Auto Electrical Corporation 1. LED Based Signal unit GAEC manufacture LED based signaling system for use in electrified and non electrified sections of Indian railways. The exceptional

More information

By Manitoba Hydro, March 4 th 2013

By Manitoba Hydro, March 4 th 2013 Rebuttal to Bipole III Coalition underground cable report Potential Use of Underground Cables for Sections of the Planned 500 kvdc Bipole III Overhead Line in Manitoba By Manitoba Hydro, March 4 th 2013

More information

FLOW CALCULATOR INSTRUCTION MANUAL MESURES BAMOPHOX 759 26-06-2007 759 M1 02 E MES FLOW CALCULATOR 759-02/1

FLOW CALCULATOR INSTRUCTION MANUAL MESURES BAMOPHOX 759 26-06-2007 759 M1 02 E MES FLOW CALCULATOR 759-02/1 BAMOPHOX 759 E - M FLOW CALCULATOR INSTRUCTION MANUAL MESURES 22, Rue de la Voie des Bans - Z.I. de la Gare - 95100 ARGENTEUIL Tél : (33) 01 30 25 83 20 - Web : www.bamo.fr Fax : (33) 01 34 10 16 05 -

More information

WATER / WASTEWATER & POWER PROJECTS LAST 5 YEARS. No of Staff Provided by BCE. Overall Project Value (SR)

WATER / WASTEWATER & POWER PROJECTS LAST 5 YEARS. No of Staff Provided by BCE. Overall Project Value (SR) WATER / WASTEWATER & POWER PROJECTS LAST 5 YEARS A. Completed December 2001 Shedgum Debottlenecking # 45943/00 47.34 Million Total 600.8 Million 154 n American Oil Co. (ARAMCO) ARAMCO Feb. 1998 to Dec.

More information

Soil Moisture Estimation Using Active DTS at MOISST Site

Soil Moisture Estimation Using Active DTS at MOISST Site MOISST Workhsop, 2014 Soil Moisture Estimation Using Active DTS at MOISST Site June 4, 2014 Chadi Sayde, Daniel Moreno, John Selker Department of Biological and Ecological Engineering Oregon State University,

More information

TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY

TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY 2 TRACTION NETWORK MONITORING AND PROTECTION SYSTEM Traction network monitoring and protection system,

More information

Cable management for rack-mounted systems

Cable management for rack-mounted systems Cable management for rack-mounted systems technology brief, 2 nd edition Abstract... 2 Introduction... 2 Cable routing guidelines... 3 Separation of power and data cables... 3 Retention of excess cable...

More information

Student Contact Center: From Development to Delivery. A Vision for Anytime, Anywhere Student Services

Student Contact Center: From Development to Delivery. A Vision for Anytime, Anywhere Student Services Student Contact Center: From Development to Delivery A Vision for Anytime, Anywhere Student Services The Vision Single Source of Information Walk In Needs Met Here! Phone Email Agents empowered Departments

More information

nr 28 nr 68 nr 4 nr 1

nr 28 nr 68 nr 4 nr 1 SEEB INTERNATIONAL BILL OF QUANTITIES AIRPORT ELECTRICAL WORKS NEW TERMINAL PIER ITEM ITEM DESCRIPTION UNIT QUANTITY BILL PART SECTION No. VOLUME 3 4 UNIT RATE (R.O.) (in words) (in figures) SECTION R:

More information

The main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building.

The main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building. MSV: Square Footage: 24,844 No. of Floors: 1 Year Built: 1963 Type of Use: Lounge and dining area open all night for snacks Steam Water-cooled condenser, 50-Ton York unit with a 6 cylinder-reciprocating

More information

www.orient-cables.com

www.orient-cables.com AC subsea power cables(ac SPC) 35 kv and below Submarine Optical Composite Power Cable 110kV Submarine Power Cable Composite with FO 220kV Submarine Power Cable Composite with FO 500kV Submarine Power

More information

Latest Power Plant Control System

Latest Power Plant Control System Hitachi Review Vol. 52 (2003), No. 2 101 Latest Power Plant Control System Takashi Kamei Takashi Tomura Yoichi Kato OVERVIEW: Along with advances in system component technologies, modern state-of-the-art

More information

Rated Power(W) 8W 2. EG-LED0840-01 8W 3. EG-LED1027-01 10W

Rated Power(W) 8W 2. EG-LED0840-01 8W 3. EG-LED1027-01 10W 14713221 001 Seite 2 von 37 Page 2 of 37 Model List: No Model Rated Voltage(V) 1. EG-LED0827-01 Rated Power(W) 8W 2. EG-LED0840-01 8W 3. EG-LED1027-01 10W 4. EG-LED1040-01 AC 100-240V, 10W 5. EG-LED1027-02

More information

Technical Description U00980 Revision 2

Technical Description U00980 Revision 2 Technical Description U00980 Revision 2 TLON Author: Mikael Rivarola Date of issue: 2000-01-07 Date of rev: 2009-01-30 Table of contents 1 Introduction 2 2 Definitions / Explanations 3 3 General description

More information

I STAR COMPUTER CO., LTD

I STAR COMPUTER CO., LTD I STAR COMPUTER CO., LTD Mini Redundant Power Supply 300W+300W for IPC-Computer Model No. TC-300R8 Table of content 1. Introduction...1 2. Specification 2.1 Input Voltage...1 2.2 DC Output...1 2.3 PS-ON

More information

Unit 4: Electricity (Part 2)

Unit 4: Electricity (Part 2) Unit 4: Electricity (Part 2) Learning Outcomes Students should be able to: 1. Explain what is meant by power and state its units 2. Discuss the importance of reducing electrical energy wastage 3. State

More information

Power Feeding Equipment for Optical Submarine Cable Systems

Power Feeding Equipment for Optical Submarine Cable Systems Power Feeding Equipment for Optical Submarine Cable Systems KANEKO Tomoyuki, CHIBA Yoshinori, KUNIMI Kaneaki, NAKAMURA Tomotaka Abstract A submarine cable system is fed power from power feeding equipment

More information

Sea Water Heat Pump Project

Sea Water Heat Pump Project Sea Water Heat Pump Project Alaska SeaLife Center, Seward, AK Presenter: Andy Baker, PE, YourCleanEnergy LLC Also Present is ASLC Operations Manager: Darryl Schaefermeyer ACEP Rural Energy Conference Forum

More information

AC and DC Drive System Installation Information

AC and DC Drive System Installation Information Purpose This document contains the Parker SSD Drives recommendations for installing drive systems. These instructions must be followed for safe and reliable operation. Instructions CODES AND REGULATIONS

More information

REMOTE MONITORING AND CONTROL OF THE KAKKONDA GEOTHERMAL POWER PLANTS

REMOTE MONITORING AND CONTROL OF THE KAKKONDA GEOTHERMAL POWER PLANTS REMOTE MONITORING AND CONTROL OF THE KAKKONDA GEOTHERMAL POWER PLANTS Shinji Nishikawa 1, Toshiyuki Takahashi 1, Takeshi Koi 1, and Katsuyoshi Yamada 2 1 Toshiba Corporation Power Systems & Services Company,

More information