Underground Cable Temperature Monitoring in the Real World
|
|
- Joseph Francis
- 8 years ago
- Views:
Transcription
1 Underground Cable Temperature Monitoring in the Real World
2 Executive Summary Background Brain Storming Possible Causes to Duct Bank Over Heating Mitigating Duct Bank Overheating DTS Installation for Duct Bank Temperature Monitoring October Heat Storm Wrap-Up
3 Background (Jan 2014) Hot conditions were first noticed by Troublemen performing switching operations during early morning hours. A new circuit was needed at the substation, so the ductbank was split in two. (May 2014) While work was being performed, elevated temperatures were again observed. A temperature of 183 F was measured in an empty conduit. Duct from substation cable trench.
4 Brain Storming Possible Causes 1. Neutral Imbalance 2. Load Factor 3. Vault Blower 4. Soil Conditions 5. Over Crowding
5 Possible Causes 1. Neutral Imbalance West Wall inside M from Sub (Line Side) Panther 12kv - Gnd 9 amps Gazelle 12kv - Gnd 16 amps Cougar 12kv - Gnd 12.5 amps Elephant 12kv - Gnd 14.8 amps Jaguar 12kv - Gnd 6 amps Bison 12kv - Gnd 3 amps East Wall inside M (Load Side) Panther 12kv - Gnd 13 amps Elephant 12kv - Gnd 11.5 amps Gazelle12kv - Gnd 14.7amps Bison12kv - Gnd 14amps Cougar 12kv - Gnd 4.4amps Jaguar 12kv - Gnd 10.7amps
6 Possible Causes 2. Load Factor Monthly load factor was calculated for all phases of each circuit. The highest load factor from the three phases was then used as that respective circuit s load factor during simulations. Circuit Name January Monthly Load Factor July Monthly Load Factor Phase A Phase B Phase C Phase A Phase B Phase C Bison Cheetah Cougar Elephant Gazelle Leopard Lynx Panther
7 Possible Causes 3. Vault Blower Not working since Was not the hottest vault.
8 Possible Causes 4. Soil Conditions Hired consultant to measure: Soil thermal resistivity, Ambient temperature, and Moisture content.
9 Possible Causes 4. Soil Conditions Industry Standards ICEA P (WC ) a. Earth thermal resistivity-60, 90 and 120 C-cm/w, designated as 60 RHO through 120 RHO. AEIC CG6-2005, Section 6.1 IEEE (R2006)
10 Possible Causes 4. Soil Conditions Soil around old and new installation was tested for thermal resistivity. Maximum reading around existing conduit was found to be 353 C cm/w. Maximum reading around new conduit was found to be 250 C cm/w. A large amount of trees were present in the area of the duct banks. Large trees are known to dry out the soil, thereby increasing the soil thermal resistivity. Issue 1: Poor Soil Conditions Location Run Comments Thermal Resistivity ( C-cm/W ) Soil Percent Tempera Moisture ture (%) ( C) 1 1 Side Wall Side Wall Bottom of Trench Side Wall Side Wall Side Wall na 2 4 Bottom of Trench Location Run Comments Thermal Resistivity ( C-cm/W ) Soil Percent Tempera Moisture ture (%) ( C) 1 1 North Side Wall East Side Wall South Side Wall South Side Wall East Side Wall North Side Wall South Side Wall East Side Wall North Side Wall
11 Possible Causes 5. Over Crowding of Duct Banks Existing Duct Banks: Original duct banks crossed at two locations First crossing was at a small angle, which allows the highest of mutual heating Second crossing was at 90 degrees, which allows the least amount of mutual heating Transition Duct Bank Six circuits in one duct bank Issue 2: Over Crowding of Duct Banks Issue Existing Duct Banks Transition Duct Bank
12 Possible Causes 5. Over Crowding of Duct Banks In the transition design, 6 circuits were together in one duct bank. High temperature of C Issue 2: Over Crowding of Duct Banks
13 Solution 1: Soil Mitigation with Slurry Backfill With Native Soil Backfill Temperatures are above 90 C With 1-sack slurry Backfill All temperatures are below 90 C
14 Solution 1: Soil Mitigation with Slurry Backfill In order to mitigate the high thermal resistivity of the soil, a slurry backfill was used to replace the soil above the new cable duct bank installations. A thermal resistivity of 60 C cm/w was used for the slurry back fill.
15 Solution 2: Re-Routing of Duct Bank Duct Bank was re-routed to reduce overcrowding. Trees were removed to make room for the duct bank route. New Vault Trees Removed
16 Solution 2: Re-Routing of Duct Bank New duct banks were routed towards the outside, furthest away from the trees and other duct banks.
17 Validation of Solutions How do we know if the separation of duct banks and the use of the slurry backfill addressed the heating issues?
18 Distributed Temperature Sensor (DTS) Fiber Cable: 24 Multi Mode 62.5/125mil Length: ~2600 ft One Continuous Loop Standard SCE fiber cable Zones: Control trench, power cable trench, north duct bank, south duct bank, and fiber well. Conduit: 2 inch Power to control cable trench. 5 inch Control trench to fiber well. 3 1/c 1000 kcmil, TR-XLPE 220 mils V DTS MEER 12kV SWITCHRACK No. 1 CAP BK No. 2 CAP BK FIBER WELL FIBER SPLICE SUBSTATION FENCE
19 Benefits of Distributed Temperature Sensor (DTS) System Thermal Study are an estimate of the thermal characteristics of the cable, ductbank, ambient temperature, soil conditions and loading. Soil thermal properties cannot be known throughout a duct bank run, without taking multiple measurements throughout the run. No other method of determining the actual cable temperature in the middle of the duct bank. Knowing the temperature of the cable: Make better, more accurate decisions in real time. Extend the life of cable by monitoring the cables temperature. Possible increase of current capacity, by loading the cable up to the actual loading limits, rather than an estimate.
20 Duct Bank Performance Monitoring (DTS) The DTS system was implemented to monitor cable temperatures inside the duct banks. Utilizes a fiber optic cable to monitor temperatures along the entire length of the duct bank. DTS and Computer Rack Fiber splice in power cable trench
21 Fiber Route Temperature Profile
22 October Heat Storm - Temperatures Max Ambient Temperature Data in Garden Grove for October 2014
23 Heat Storm Circuit Loading -North For SCE Internal Use Only 23
24 Duct Bank Temperature Performance Validation Measured Duct Bank Model Cable Detail Model Calculated DTS Temperature was as expected. (63 deg. C measured & 65 deg.c calculated.) Improved duct bank design, slurry back fill & tree removal prevent duct bank overheating (Conductor Temperature ~ 68.8*C during heat wave at 103 deg. F) 24
25 Wrap Up - Conclusion Predominant causal factors in the Lampson overheated duct bank condition are the high soil thermal resistivity and the overcrowding of the duct banks. The corrective actions implemented have mitigated both causal factors: Splitting the circuits into two paths (4 circuits and 3 circuits) and cable placement in the duct arrangement to address the circuit density. Adding slurry to address the soil thermal resistivity issue. The DTS system has proven that the integrated solution of splitting the duct bank and adding slurry backfill prevented overheating during the October heat wave.
26 Wrap Up Lessons Learned / Challenges Installing the fiber cable in the same duct as power cables. Damage may occur during installation. Small clearances in duct. Communication fiber cable requirements / standards are higher than needed for monitoring cable temperature. Paying more attention to the contractors, they work fast and may not have the same goals as you do. Cost was small to add fiber cable to an existing power cable pull. Fiber splicing Coordinating non electrical crews. Fiber cables are normal treated as separate installations Setting up computer for DTS Cost is of the project is in the DTS unit.
27 Wrap Up Future Needs Possible installation of fiber cable in highly loaded circuit sections (ie. Substation getaways, highly loaded customers, etc.) Installing fiber cable at the same time as power cable is reasonably low cost.
28 References CYMCAP 6.2, rev2 Duct Bank Modeling Software IEEE 442- Guide for Soil Thermal Resistivity Measurements SENSA-Distributed Temperature Sensor SCE Circuit Loading Data Thermal Images Provided by SCE Troubleman Santa Ana,CA AEIC CG6-2005, Section 6.1 Guide for Establishing The Maximum Operating Temperatures of Extruded Dielectric Insulated Shielded Power Cables IEEE 835 IEEE Standard Power Cable Ampacity Tables ICEA P (WC-50) Ampacities Including Effect of Shield Losses for Single Conductor Solid Dielectric Power Cable 15 kv through 69 kv
Least Cost Cable System. Strategies to Reduce Cable and Infrastructure Costs When Transitioning to an All Conduit Systems
Least Cost Cable System Strategies to Reduce Cable and Infrastructure Costs When Transitioning to an All Conduit Systems Cost Sharing of Cable Systems Underground Extensions The Company will construct
More informationKNOW YOUR OPTIONS: 69 KV XLPE POWER CABLE
Know Your Options: 69 kv XLPE Power Cable 3 material and size material is a matter of both customer preference and required current carrying capacity Copper conductor common for larger loads When both
More informationKNOW YOUR OPTIONS: 230 KV POWER CABLES
KNOW YOUR OPTIONS: 230 KV POWER CABLES 71 CONDUCTOR MATERIAL AND SIZE Conductor material is a matter of both customer preference and required current carrying capacity At 230 kv, copper is most common
More informationSection 5 161 kv Power Cables
Know Your Options: 161 kv Power Cable 61 material and size material is a matter of both customer preference and required current carrying capacity Copper conductor common for larger loads When both copper
More informationUptown Campus, Primary Electric Master Plan - Program Study State University of New York At Albany, SUCF Project No. 01832 V.
V. DESIGN STANDARDS i. Medium Voltage Cables ii. iii. iv. Separable Connectors Splices & Fault Indicators Manholes & Ductbanks Primary Switches & Medium Voltage Transformers v. Metering, Monitoring, &
More informationIEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO
IEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO WHEN YOU HEAR AN ENGINEER SAY A NUMBER OF DIFFERENT APPROACHES ARE BEING IMPLEMENTED
More informationTELUS Residential Service Conduit Requirements for Stand Alone Homes and Duplexes in Fibre Only Communities
1 TELUS Residential Service Conduit Requirements for Stand Alone Homes and Duplexes in Fibre Only Communities Beginning in January 2010 TELUS began designing new subdivisions within the Top 48 population
More informationTAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS. What Is Tan δ, Or Tan Delta?
TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS What Is Tan δ, Or Tan Delta? Tan Delta, also called Loss Angle or Dissipation Factor testing, is a diagnostic method of testing
More informationAMSC s Superconductor Cable Technologies for Electric Utilities
International Workshop 2014 AMSC s Superconductor Cable Technologies for Electric Utilities Michael Ross, P.E. Managing Director of Superconductor Power Systems AMSC Corporate Facts Headquartered in MA,
More informationElectric Engineering Division FIBER CONDUIT RULES AND REGULATIONS
Electric Engineering Division FIBER CONDUIT RULES AND REGULATIONS TABLE OF CONTENTS I. RULES AND REGULATIONS A. TABLE OF CONTENTS... 2 B. TERMS AND DEFINITIONS... 3 C. DEVELOPER S/CONTRACTOR S RESPONSIBILITIES...
More informationNetwork Standard Advice No. 1420C 9/6/2011
Network Standard Advice No. 1420C 9/6/2011 TO: Customers, Service Providers and Ausgrid Staff. Advisory Note on Changes to the Use of 11kV Cable Types. Introduction This Network Standard Advice (NSA) provides
More informationMultiple Meter Installation - 200 Amperes Per Position -Single Phase, Self-contained
Overhead Meters TABLE OF CONTENTS D D Consumer Service Pole for Mobile Home Park Temporary Service -wire Single Phase D. Overhead Meter Installation - Single Phase D. Connection Diagram - Single Phase
More informationElectrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage:
Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016 * Garage construction requires permits (electrical, building) * Permits must be applied for at the time. * Dial
More informationBCTC/BC Hydroʹs operational experience with Distributed Temperature Sensing (DTS) Systems for Transmission Cables. Presented by
BCTC/BC Hydroʹs operational experience with Distributed Temperature Sensing (DTS) Systems for Transmission Cables Presented by S. Cherukupalli Transmission Cables Design BC Hydro at the ICC Spring Meeting,
More informationCABLE MONITORING SOLUTION
POWER CABLE MONITORING SOLUTION Kuljit Singh BSc Honours MIEE(IET,UK) Dan Watley Ph. D, B.A MEng (UK), MIEEE, UK 8-9 November 2011 PREDICT WITH CERTAINTY Definition DTS: Distributed Temperature Sensor
More informationREQUIREMENTS AND SPECIFICATIONS FOR HIGH VOLTAGE CUSTOMER BUILT FACILITIES PEPCO ENGINEERING
REQUIREMENTS AND SPECIFICATIONS FOR HIGH VOLTAGE CUSTOMER BUILT FACILITIES PEPCO ENGINEERING Revised October, 2013 TABLE OF CONTENTS 1.0 INTRODUCTION... 3 2.0 REQUIRED DRAWINGS... 3 2.1 Site Plan... 3
More informationNational Science Foundation Funds Request
University Corporation for Atmospheric Research National Science Foundation Funds Request 1. (NSF USE ONLY) 2. FACILITY NAME & LOCATION 3. PROJECT NAME 4. UCAR TRACKING NUM. NCAR Mesa Lab 15KV FEEDER REPLACEMENT
More information345 kv Underground Report
POWER ENGINEERS, INC. February 24, 2010 345 kv Underground Report PROJECT NUMBER: 117910 PROJECT CONTACT: Mike Mueller Richard C. Mues, PE EMAIL: mike.mueller@powereng.com rmues@powereng.com PHONE: 314-851-4050
More informationM. GELDON Brugg Kabel CZ. Ing. D. RÚŽEK PREdistribuce. Switzerland Czech Rep. Czech Rep. Czech Rep., Switzerland Germany
21, rue d Artois, F-75008 PARIS Paper number CIGRE 2012 http : //www.cigre.org 6 characters (to be provided later) Correlation between calculated transmission capacity and actual one D. WALD* Eifelkabel
More informationErrors Related to Cable Resistance Imbalance in Three Wire RTDs
Errors Related to Cable Resistance Imbalance in Three Wire RTDs 1.0 Introduction There are multiple sources of error that can impact the accuracy of an RTD measurement. The cable incorporated into the
More informationCABLE TRENCH INSTALLATION GUIDE
1.0 INDEX 1.0 INDEX 2.0 PURPOSE 3.0 GENERAL INFORMATION 4.0 PLANNING INFORMATION 5.0 CREW INFORMATION 6.0 CONTRACTOR INFORMATION 7.0 PRECASTED/ POURED-IN-PLACE TRENCH DRAWINGS 2.0 PURPOSE This standard
More informationReal Time Monitoring of Power Cables by Fibre Optic Technologies Tests, Applications and Outlook
Real Time Monitoring of Power Cables by Fibre Optic Technologies Tests, Applications and Outlook LUTON Marie-Hélène SAGEM SA, Activité Câbles Rue de Varennes Prolongée 77876 Montereau Cedex France Phone
More informationCHUGACH ELECTRIC ASSOCIATION, INC. Anchorage, Alaska. February 10, 2014
CHUGACH ELECTRIC ASSOCIATION, INC. Anchorage, Alaska February 10, 2014 QUESTIONS AND ANSWERS TO: Prospective Proposers FROM: Chugach Electric Association, Inc. 5601 Electron Drive Anchorage, Alaska SUBJECT:
More information16300 MEDIUM VOLTAGE DISTRIBUTION
16300 MEDIUM VOLTAGE PART 1: GENERAL 1.01 SYSTEM DESCRIPTION A. Most new loads will be served from the underground electric distribution system. This system is a primary open loop configuration served
More informationLightning Arresters P30027 18 KVA P30038 10 KVA. Description & Installation
Lightning Arresters P30027 18 KVA P30038 10 KVA Description & Installation Printed in USA 09/11 TO330 Rev. B Table of Contents Page 1.0 SCOPE 2 2.0 PRODUCT OVERVIEW 2 2.1 Intended Uses 2 2.2 Lightning
More informationHIGH- AND EXTRA-HIGH-VOLTAGE GLOBAL CABLE SYSTEM SOLUTIONS Rely On Our Experience... Experience Our Capabilities
HIGH- AND EXTRA-HIGH-VOLTAGE GLOBAL CABLE SYSTEM SOLUTIONS Rely On Our Experience... Experience Our Capabilities RELY ON OUR EXPERIENCE... EXPERIENCE OUR CAPABILITIES For close to half a century, Silec
More informationTop Drive Service Loops. Conventional, Enhanced and Superior Solutions for Drilling Applications
Top Drive Service Loops Conventional, Enhanced and Superior Solutions for Drilling Applications Linking the future As the worldwide leader in the cable industry, Prysmian Group believes in the effective,
More informationStephen G. Whitley, Senior Vice President & Chief Operating Officer
Peter T. Brandien Vice President, System Operations To: Stephen G. Whitley, Senior Vice President & Chief Operating Officer From: Peter T. Brandien Re: Discussion of Cable Technologies Under Evaluation
More informationCTI TECHNICAL BULLETIN Number 9: A publication of the Cable Tray Institute
CTI TECHNICAL BULLETIN Number 9: A publication of the Cable Tray Institute Cable Tray Wiring Systems Have Many Cost Advantages Cost is usually a major consideration in the selection of a wiring system.
More informationEast Central College 14434.03 HANSEN HALL LEVEL 300/400 RENOVATIONS PACKAGE
SECTION 260519 - BUILDING WIRE AND CABLE PART 1 - GENERAL 1.1 WORK INCLUDES A. Base and Alternate Bids: 1. Contractor Provide: a. Building wire and cable as shown on drawings or specified including feeders,
More informationMonitoring Underground Power Networks
Monitoring Underground Power Networks By Mark Stiles Merve Cankaya ABSTRACT Underground electric distribution systems are common in large cities throughout the United States. Power usage for the entire
More informationDistributed Temperature Monitoring of Energy Transmission and Distribution Systems
1 m 40000m0 range 61850 IEC spatial resolution Distributed Temperature Monitoring of Energy Transmission and Distribution Systems Ensuring a Reliable Supply of Electrical Power for Today s World www.en-sure.pro
More informationWIRE AND CABLE ENGINEERING GUIDE
DC Hi Pot Testing Excerpt from PRYSMIAN S WIRE AND CABLE ENGINEERING GUIDE (FOR INFORMATIONAL PURPOSES ONLY) Page 1 of 6 DC HIGH POTENTIAL TESTING DC Hi-Pot testing can be applied as a withstand test (a
More informationDISCUSSION OF CROSS-LINKED POLYETHYLENE INSULATED CABLES FOR UNDERGROUND PORTIONS OF THE MIDDLETOWN-NORWALK 345 kv PROJECTS.
DISCUSSION OF CROSS-LINKED POLYETHYLENE INSULATED CABLES FOR UNDERGROUND PORTIONS OF THE MIDDLETOWN-NORWALK 345 kv PROJECTS December 20, 2004 David W. Forrest Rachel I. Mosier 1. EXECUTIVE SUMMARY CL&P
More informationMEASUREMENTS OF THRUST LOAD IN CABLE SYSTEMS SEMI-RIGIDLY INSTALLED IN DUCT / MANHOLE STRUCTURES
MEASUREMENTS OF THRUST LOAD IN CABLE SYSTEMS SEMI-RIGIDLY INSTALLED IN DUCT / MANHOLE STRUCTURES Riccardo BODEGA, Prysmian Cables and Systems, The Netherlands, riccardo.bodega@prysmian.com Henk GEENE,
More informationIndustrial Cable Solutions for Variable Frequency Drives
Industrial Cable Solutions for Variable Frequency Drives Tough challenges call for innovative solutions, and General Cable is your worldwide source for new products and a wide range of industry-leading
More informationGUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables
Engineering Department SEPTEMBER, 2007 GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables General Requirements This section applies to all public and private utilities,
More information100% EMI Emission Containment
100% EMI Emission Containment Designed for Longer Service Life Highly Flexible for Easier Handling and Faster Installation Authorized Distributor Industrial VFD Cables Index n Variable Frequency Drive
More informationUnderground Service Requirements and Instructions
This packet includes all FKEC underground service requirements, instructions, procedures and drawings. If you are considering underground power service please review this document in its entirety (3 page
More informationCivil. 2. City of Seattle Supplement to the Specification for Road, Bridge and Municipal Construction, most current addition.
Design Guide Basis of Design This section applies to the design and installation of earthwork and backfill. Design Criteria No stockpiling of excavation materials is allowed unless the Geotechnical Engineer
More informationELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS
Prepared by: ABB1 ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS 052521 Asset Type: Electric Metering Function: Construction Issued by: Quoc Hoang (QxH1) Date: 07-01-16 Rev. #06: This document
More informationBy Anne Bartosewicz, Northeast Utilities, and J. Brett Williams and Jim Hogan, Burns & McDonnell
By Anne Bartosewicz, Northeast Utilities, and J. Brett Williams and Jim Hogan, Burns & McDonnell CONNECTICUT LIGHT & POWER SERVES ONE OF THE MOST POWER-CONSTRAINED REGIONS IN THE UNITED STATES. Recognizing
More informationFault location on power cables. Fault location on power cables
Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 01. Introduction Fault location on communication and power cables
More informationUnderground Transmission Lines
Underground Transmission Lines INTRODUCTION In today s urban, environmentally sensitive environment, how are you going to get power to the people who need it? In many cities, overhead transmission lines
More informationLucien Antonissen Key Account Manager LIOS Technology Germany
Lucien Antonissen Key Account Manager LIOS Technology Germany Content Company Markets DTS Controller Software Configuration RTTR Demonstration Q&A NKT Holding 2013 NKT Holding Nilfisk-Advance NKT Cables
More informationVDE Information. Degree of Pollution, Clearances and Creepage Distances and Insulating Materials
VDE Information General Information The voltage which can be applied to a terminal depends on the relevant regulations, the installation conditions and, of course, the dimensions and insulating materials
More informationRadial Distribution Test Feeders
Radial Distribution Test Feeders Distribution System Analysis Subcommittee Report Abstract: Many computer programs are available for the analysis of radial distribution feeders. In 1992 a paper was published
More informationCONTENTS. Yale University Design Standards. Underground Electrical Duct Bank. A. Summary. B. System Design and Performance Requirements
16600 Underground Electrical Duct Bank This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications
More informationQ: PLEASE STATE YOUR NAME AND BUSINESS ADDRESS. A: Gerry Sheerin. Sheerin Technical, 25 Eastville Avenue, Toronto, Ontario Canada
DIRECT TESTIMONY OF GERRY SHEERIN, P. ENG ON BEHALF OF PIEDMONT ENVIRONMENTAL COUNCIL BEFORE THE STATE CORPORATION COMMISSION OF VIRGINIA CASE NOS. PUE-00-0001 AND PUE-00-000 1 1 1 1 1 1 1 1 1 Q: PLEASE
More informationSECTION 27 05 36 CABLE TRAYS FOR COMMUNICATIONS SYSTEMS
SECTION 27 05 36 CABLE TRAYS FOR COMMUNICATIONS SYSTEMS PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such
More informationCABLE ASSET MANAGEMENT PREDICT WITH CERTAINTY. Kuljit Singh BSc Honours MIEE(IET,UK) 5 June 2014
CABLE ASSET MANAGEMENT PREDICT WITH CERTAINTY Kuljit Singh BSc Honours MIEE(IET,UK) 5 June 2014 Definitions International Workshop 2014 DTS: Distributed Temperature Sensor DCR: Dynamic Cable Ratings (
More informationTwo different types of cables are used in primary airfield lighting circuits: - unshielded cables and - shielded cables
Two different types of cables are used in primary airfield lighting circuits: - unshielded cables and - shielded cables Classically both cables have a single AWG 8 copper conductor or a cross section of
More informationSession 14 Cable Support Systems
Session 14 Cable Support Systems Cable Support Systems in the IEC World A new IEC Standard, IEC61537 2001 has been developed If full details of the cabling layout are available then the likely cable load
More informationGrid Solutions. PROJECT MANAGEMENT SOLUTIONS for infrastructure projects from Border States. Border States
Border States Grid Solutions PROJECT MANAGEMENT SOLUTIONS for infrastructure projects from Border States Aging infrastructure, increased energy demands and emerging markets have fueled the growth of transmission,
More informationGrounding of Electrical Systems NEW CODE: Grounding and Bonding
Grounding of Electrical Systems NEW CODE: Grounding and Bonding Presented By Scott Peele PE Grounding of Electrical Systems Outline Defining the Terms Why should I Ground? Types of Grounding Systems Separately
More informationElectrical Design Training Class Ampacity WSDOT Winter 2008 BZA
Electrical Design Training Class Ampacity WSDOT Winter 2008 BZA presented by: Keith Calais 1 What is it? Ampacity is the current, in Amperes, that a conductor can carry continuously under the conditions
More information4 IX D N E P P A Installation methods Current-carrying capacity and voltage drop for cables Reference method IET Wiring Matters
8 Appendix 4 of BS 7671 by Mark Coles Appendix 4, Current-carrying capacity and voltage drop for cables and flexible cords, has seen significant changes with the publishing of BS 7671:2008. This article
More informationCable Selection for Medium Voltage Capacitor Banks and Harmonic Filter Banks
Cable Selection for Medium Voltage Capacitor Banks and Harmonic Filter Banks Introduction This document presents the fundamental aspects of cable and conductor selection for connecting pad mounted shunt
More information337500 MEDIUM VOLTAGE DISTRIBUTION
337500 MEDIUM VOLTAGE DISTRIBUTION PART 1: GENERAL 1.01 SYSTEM DESCRIPTION A. Most new loads will be served from the underground electric distribution system. This system is a primary selective open loop
More informationAC and DC Drive System Installation Information
Purpose This document contains the Parker SSD Drives recommendations for installing drive systems. These instructions must be followed for safe and reliable operation. Instructions CODES AND REGULATIONS
More informationWHY CABLE TRAY? BECAUSE A CABLE TRAY WIRING SYSTEM PROVIDES SAFE AND DEPENDABLE WAYS TO SAVE NOW AND LATER
Large numbers of electrical engineers have limited detail knowledge concerning wiring systems. There is the tendency by engineers to avoid becoming involved in the details of wiring systems, leaving the
More informationTECHNICAL SERVICE DEPARTMENT Technical Service Bulletin 1-800-432-8373. 2 Inch PowerVent LED Indicator Explanations & Troubleshooting Table
New Robertshaw control valve was introduced in May 2008 as a replacement part. See last page for troubleshooting this replacement part. All voltage inputs are 120V. All electrical connectors are Molex
More informationHow To Test For Safety On A Power Cable
T H E M A G A Z I N E O F 7 x 2 4 E X C H A N G E I N T E R N AT I O N A L A Green Approach to Building a Superior Data Center S P R I N G 0 9 BUILD FOR TODAY. EXPAND ON DEMAND. Modularity in the data
More informationLEAD FREE FIREX. Interlock Armored Cables TECK90 and MC Industrial Cables. w w w. n e x a n s e n e r g y. c o m
FIREX Interlock Armored Cables TECK90 and MC Industrial Cables LEAD FREE O V E R 1 8 0 Y E A R S O F E X P E R I E N C E 866-663-9267 w w w. n e x a n s e n e r g y. c o m Interlock Armored Cables Introduction....2
More informationCable Tray Selection-
Cable Selection- For allowable cable types see the Appendix page A-9. The following guidelines are based on the 2002 National Electrical Code, Article 392. I) Number of Multiconductor Cables rated 2000
More informationGulf Cable & Electrical Ind. Co.
CONTENTS INTRODUCTION PRODUCT RANGE I PRODUCT DATA TABLES XLPE INSULATED 600/1000V CABLES Two Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC 1 Three Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC 2 Four Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC
More informationPRIMARY SERVICE LINE: The Company's conductors which connect the supply line with a transformer located on private property.
INTRODUCTION These rules are issued for use by Customers, builders, electrical contractors, architects, engineers, etc. The rules require the installation of safe and adequate wiring and electrical equipment,
More information3. TYPES OF SERVICE AVAILABLE. 3.1 Scope
3. TYPES OF SERVICE AVAILABLE 3.1 Scope UI supplies 60 hertz, alternating current with different voltage and ampere ratings. Not all voltage and ampere ratings are available throughout the entire service
More informationInsulation Resistance Testing of Low Voltage Cables in the Field
Insulation Resistance Testing of Low Voltage Cables in the Field Table of Contents 1. Background...3 1.1. Before Making Measurements...3 1.2. How to Apply the Temperature Correction Factor...4 1.2.1. Calculation...4
More informationHistory of Secondary Cable Designs
History of Secondary Cable Designs John Hans Consulting Engineer Commonwealth Edison, Chicago Illinois Presented at the ICC Education Session St. Petersburg Beach, FL April 20, 2005 ComEd Background System
More informationDistributed Temperature Sensing using Fibre-Optics (DTS Systems)
Distributed Temperature Sensing using Fibre-Optics (DTS Systems) Presented to 2000 Electricity Engineers Association Annual Conference, Auckland, New Zealand 16/17 June 2000 Authors: David Peck, Managing
More informationA Method to Detect and Locate Roof Leaks Using Conductive Tapes
BEST2 Moisture Measurement Session WB8-2 A Method to Detect and Locate Roof Leaks Using Conductive Tapes ABSTRACT David Vokey, P.Eng. Detec Systems, LLC Undetected roof leaks and the subsequent deterioration
More informationHyperlinks are Inactive
Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)
More informationTO MEMBERS OF THE COMMITTEE ON GROUNDS AND BUILDINGS: ACTION ITEM
GB6 Office of the President TO MEMBERS OF THE COMMITTEE ON : For Special Meeting of ACTION ITEM APPROVAL OF PHASE 1 OF THE UTILITY LINE REMEDIATION PROJECT RELATED TO THE MISSION BAY DILLER BUILDING, ROCK
More information2 8 k V, 1 / C, T R X L P E I N S U L A T E D, F L A T S T R A P S H I E L D E D C A B L E, C O M P R E S S E D S T R A N D I N G
Seattle Cit y Light 1 of 4 2 8 k V, 1 / C, T R X L P E I N S U L A T E D, F L A T S T R A P S H I E L D E D C A B L E, C O M P R E S S E D S T R A N D I N G 1. Scope This standard covers the detailed requirements
More informationState, trends and evolutions of HV/EHV power cables systems and contributions of SC B1 to their ongoing progress
0611-048-Mep229 12/12/06 6:44 Page 22 State, trends and evolutions of HV/EHV power cables systems and contributions of SC B1 to their ongoing progress Reinhard SCHROTH, Chairman of SC B1 2002-2006 High
More informationAPPLICATION ORIENTED DESIGN OF CABLES
APPLICATION ORIENTED DESIGN OF CABLES Mrs. Rohini Bhattacharyya, Dubai cables Ltd.P. O. Box 11529,Dubai. rohinib@ducab.com Mr. Nawaf Ahmad Al Mohaideb Dubai Cables Ltd. P. O. Box 11529, Dubai. Nawaf@ducab.com
More informationProtection Systems. A UTC Fire & Security Company F-73-01. Linear Heat Detector FEATURES DESCRIPTION APPLICATIONS BENEFITS
Effective: May 2007 AlarmLine TM R Protection Systems Linear Heat Detector A UTC Fire & Security Company F-73-01 FEATURES Integrating Type Linear Heat Detector Analog Sensing Field Adjustable Alarm Set
More informationGreat Lakes Data Room Case Study
Great Lakes Data Room Case Study WeRackYourWorld.com Problem: During a warm summer period in 2008, Great Lakes experienced a network outage due to a switch failure in the network enclosure. After an equipment
More informationTEST PLAN SUPERSEDES: None
NYE COUNTY NUCLEAR WASTE REPOSITORY PROJECT OFFICE TEST PLAN TITLE: Thermal Logging in Early Warning Drilling Program Wells Using Sensornet Equipment Revision: 0 Date: 6-19-06 Page: 1 of 10 TEST PLAN NUMBER:
More informationAORC Technical meeting 2014
http : //www.cigre.org B1-1055 AORC Technical meeting 2014 220 kv Long Distance Underground HVAC Cable Circuit NAVEED RAHMAN Nexans Olex Melbourne, Australia SUMMARY In 2009, the Victorian state government
More informationMCR1900 Media Converter 19-Slot Chassis
MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the
More informationPart 1 System Modeling & Studies for Existing Systems
Part 1 System Modeling & Studies for Existing Systems Operation Technology, Inc. Copyright 2009 Result of rapid release of energy due to an arcing fault between two conductors. Bus voltages > 208V Temperatures
More informationDIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION
DIVISION 26 - ELECTRICAL PART 1 - GENERAL 1.01 SUMMARY A. Section Includes 1. Instrumentation Cables 1.02 SUBMITTALS A. Submit in accordance with requirements of Section 01 33 00. B. Product Data: Submit
More informationSection 21. Telecommunication Hardware. www.geindustrial.com BuyLog Catalog 21-1
Introduction...21-1 Fiber Closure Hardware...21-2 Cable Location Surge Protectors...21-4 Introduction GE has been manufacturing Telecommunication Hardware products for over 20 years and has become a leader
More informationOptical Cable Pre-Construction Survey. Keywords Stationary Reel Method, empty innerducts, sub-ducts, microducts, Intermediate-feed manholes
Optical Cable Pre-Construction Survey Author John Peters Issued December 2012 Abstract Pre-construction site survey is one of the most important steps in the engineering and placement of a new optical
More informationRequirements for the Attachment of Communication Cable Facilities on PPL Poles
Page 99 of 137 Requirements for the Attachment of Communication Cable Facilities on Replaces: URS-3002 URS-3004 URS-101C-304 A-157649 Page 100 of 137 Reference Notes for Drawings: General 1. The term communication
More informationOptimum Climate Control For Datacenter - Case Study. T. Prabu March 17 th 2009
Optimum Climate Control For Datacenter - Case Study T. Prabu March 17 th 2009 Agenda 2 About EDEC (Emerson) Facility Data Center Details Design Considerations & Challenges Layout Design CFD Analysis Of
More informationGas Meter Clearances and Service Installation Requirements
March 2015 Gas Meter Clearances and Service Installation Requirements Builder/Owner/Developer Requirements Call PSE s Customer Construction Services 1-888-321-7779 or visit PSE.com/CustomerConstruction
More informationGroundRod AC Substation Earthing Tutorial
1 GroundRod AC Substation Earthing Tutorial 1. Functions of an earthing system The two primary functions of a safe earthing system are: To ensure that a person who is in the vicinity of earthed facilities
More informationCUSTOMER REQUIREMENTS AT POWER SUBSTATIONS
CUSTOMER REQUIREMENTS AT POWER SUBSTATIONS Customer Handout Date Aug 2, 2010 Version 1.0 File Name Customer Requirements At Power Substations Document Id Outside Plant Engineering 1 Table Of Contents 1.0
More informationenvironment briefing02
PRODUCED BY THE SAFETY, HEALTH & ENVIRONMENT GROUP OF THE ENERGY NETWORKS ASSOCIATION - JULY 2006 environment briefing02 transporting electricity Overhead Lines or Underground Cables? Introduction The
More informationTesting and Demonstration Results of the 350m Long HTS Cable System Installed in Albany, NY
1 Testing and Demonstration Results of the 35m Long Cable System Installed in Albany, NY C. S. Weber, SuperPower, Inc.; R. Lee, S. Ringo, The BOC Group; T. Masuda, H. Yumura, SEI and J. Moscovic, National
More informationAll Wires and Cables Are Not Created Equal
All Wires and Cables Are Not Created Equal When comparing life cycle costs for wires and cables in wind systems, consider the specific applications, cost per failure and dielectric losses to determine
More informationNexus Technology Review -- Exhibit A
Nexus Technology Review -- Exhibit A Background A. Types of DSL Lines DSL comes in many flavors: ADSL, ADSL2, ADSL2+, VDSL and VDSL2. Each DSL variant respectively operates up a higher frequency level.
More informationGas Meter Clearances and Service Installation Requirements
March 2016 Gas Meter Clearances and Service Installation Requirements Builder/Owner/Developer Requirements Call PSE's Customer Construction Services 1 888 321 7779 or visit PSE.com/CustomerConstruction
More informationCurrent valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
More informationUnderground Commercial Electric Service
Underground Commercial Electric Service SCANA Corporation 2013 Revised: June 2013 Table of Contents SECTION PAGE I. Specification and Requirements 2 A. General B. Definition of Terms C. Company and Developer
More informationElectric Service Conversion Overhead-to-Underground. Minnesota
Electric Service Conversion Overhead-to-Underground Xcel Energy Electric Connections Minnesota Process Please fill out these forms and complete this checklist to begin your application process: 1) Overhead-to-Underground
More informationCalculation of Underground Cable Ampacity
Calculation of Underground Cable Ampity Francisco de León CYME International T&D 485 Roberval, Suite 04 St. Bruno, Quebec, Canada, J3V 3P8 Tel. (450) 46 3655 info@cyme.com Abstrt This paper introduces
More information