A3-201 APPLICATIONS OF DISCONNECTING CIRCUIT-BREAKERS

Size: px
Start display at page:

Download "A3-201 APPLICATIONS OF DISCONNECTING CIRCUIT-BREAKERS"

Transcription

1 21, rue d'artois, F Paris A3-201 Session 2004 CIGRÉ APPLICATIONS OF DISCONNECTING CIRCUIT-BREAKERS P-O Andersson H-E Olovsson B Franzén U Lager J Lundquist* ABB Power Technologies Svenska Kraftnät Sydkraft Nät STRI (Sweden) 1. INTRODUCTION The concept of a disconnecting circuit-breaker (DCB) for air-insulated substations (AIS) has been discussed in several Cigré papers since the middle of the 1990 s [1][2][3]. The DCB is aimed at replacing the traditional combination of a circuit-breaker (CB) and its associated conventional disconnectors (DS). The long intervals between maintenance of the DCB, compared with the conventional open-air DS, provide high availability also with simplified substation configurations. In addition, the lower number of switching devices means that space requirements are reduced and that control systems can be simplified. An example of DCB application in a 400 kv transmission substation is shown in Figure 1. Figure 1. DCB in Hemsjö 400 kv transmission substation. *jan.lundquist@stri.se

2 The main advantage of the DCB compared to a conventional disconnector is that the electrical contacts are enclosed in SF 6 gas, thereby protected from the influence of ambient conditions including the effects of pollution. The protected environment provides improved reliability and prolonged intervals between de-energisation for maintenance of the DCB. The possibility of excluding the conventional disconnectors is based on the reduced maintenance demands of modern circuit-breakers; one major traditional function of the disconnector has been to isolate the breaker for maintenance of the breaker itself. With the prolonged maintenance intervals associated with modern circuit-breakers (de-energisation required typically only every 15 years), this isolating function of the disconnector is becoming obsolete. Furthermore, other major functions of the conventional disconnector, e.g. the isolation of lines, transformers, etc., for operational or maintenance purposes, can be equally well handled by the DCB, as will be described in this paper. The development of a policy for application of disconnectors in the Swedish transmission system is reviewed, and the future trends are discussed in Section 2 of the paper. The technical design aspects of the DCB have been presented in [4]. Other aspects, such as using the DCB to achieve simplified substation configurations with high availability and reduced environmental impact, were discussed in [3]. Since 1999, the DCB concept has been applied in several transmission and sub-transmission substations in various countries, from 72 to 420 kv. A recent example is the application of DCB for rehabilitation of a major 400/130 kv substation in the south of Sweden, owned by Svenska Kraftnät and Sydkraft Nät, respectively. The reasons for selecting the DCB concept for both the 400 kv and the 130 kv voltage levels are discussed in Section 3. An important aspect of the DCB is its ability to provide safe working conditions during maintenance and repair work in substations. When the DCB is used as a disconnector for this purpose, it has to be assured that the open contacts are not closed unintentionally, or bridged by a disruptive discharge. This important aspect has been considered in the design and specification of the DCB. In Section 4 of the paper, the safety locking system of the DCB is described, and an analysis of the insulating properties of the DCB in the open position is presented, taking into account the voltage stresses and the risks and consequences of a disruptive discharge. The importance of the safety aspects is reflected in the upcoming IEC standard for combined function disconnecting circuit-breakers. The current results of the standardisation work are briefly outlined in Section SVENSKA KRAFTNÄT S DISCONNECTOR POLICY Svenska Kraftnät, the Swedish transmission network utility for the 220 kv and 400 kv grids, has developed a strategy for the application of disconnectors in their transmission substations. The policy is based on service experience with conventional open-air disconnectors, the reduced need for maintenance of modern circuit-breakers, and the development of new technologies, e.g. the DCB. Already in the seventies, the open-air disconnector in outdoor substations was identified by Svenska Kraftnät as a component that could jeopardize the availability of the substation, leading to serious problems in the network. A new disconnector policy was introduced and later applied to new or rebuilt 400 kv substations: the circuit-breakers were to be directly connected to the busbars, i.e., no busbar disconnectors were to be used. Instead, manual disconnection facilities were introduced in such a way that the circuit-breaker could quickly be removed from the busbar for maintenance or repair. Conventional disconnectors were still used on the opposite side of the circuit-breakers for disconnection of OH-lines, power transformers etc. The new policy was applied to 400 kv substations beginning in By the reduction in number of conventional disconnectors, the need for maintenance has decreased and the reliability has improved. The following rules are applied regarding manual disconnection towards the busbar: If the work is expected to last less than 8 hours, the busbar is taken out of service and all other bays are connected to the other busbar. If the work is expected to last more than 8 hours, the connection to the busbar is removed and the busbar is re-energised. 2

3 Today, the policy of Svenska Kraftnät is to integrate the breaking and disconnecting functions, which can be obtained by using the DCB. Reliability studies carried out by Svenska Kraftnät have shown that the expected outage rate, and the resulting unavailability of a substation, is lower when DCBs are used to replace conventional circuit-breakers and disconnectors. 3. THE DCB IN SIMPLIFIED SUBSTATION CONFIGURATIONS The availability properties of simplified substation configurations utilising the DCB were analysed in [3] for three common substation types: sectionalised single busbar and double busbar schemes for HV/MV substations, and a 1½-breaker scheme for EHV/HV substations. The studies included timebased maintenance and sustained active failures of equipment, taking into account the switching sequences associated with the failures. It was shown that the simplified substation configurations using DCB have a better availability compared with conventional solutions. In line with the concepts of manual disconnection facilities introduced by Svenska Kraftnät as discussed in Section 2, the availability of simplified substations may be further improved if the DCB is equipped with manual disconnecting devices as shown in Figure 2. The devices are composed of standard substation hardware. They provide convenient and safe disconnection and reconnection of the DCB if the need arises for maintenance or repair of the DCB itself. When the DCB is disconnected in this way, and proper safety distances are ensured, the other parts of the substation may be re-energised. To illustrate the concept of the DCB in combination with manual disconnection possibilities, the recent applications in the Hemsjö 400/130 kv transmission substation are described in the following section. Figure 2. Typical manual disconnection devices during installation DCB application in a 400/130 kv transmission substation kv double-breaker substation configuration The 400 kv part of the Hemsjö substation is owned and operated by Svenska Kraftnät. The substation was completely rebuilt during , i.e., all primary and secondary equipment was replaced. Hemsjö is an important substation in the southern part of the Swedish 400 kv transmission network. Outage of the complete substation due to a busbar fault would endanger the operation of the entire grid in this part of Sweden. Therefore, the busbar configuration was changed from a main and transfer busbar scheme, to a double-breaker configuration when the substation was rebuilt. Thus, a busbar fault will no longer disturb the power flow through the substation, since the busbars are completely redundant with one breaker towards each of the busbars in each bay. As seen from the single line diagram in Figure 3, the 400 kv substation includes four OH-line bays, three capacitor banks and one 750 MVA power transformer feeding the regional 130 kv network. The concept of manual disconnection possibilities is utilised towards the busbars, the OH-line connections, 3

4 and the capacitor bank with two breakers. This will enable the second DCB to sustain service to these objects in case the first DCB needs to be taken out of service. In the rehabilitation of the 400 kv substation, the existing main busbar could be retained and, after extension, be used as one of the busbars in the rebuilt substation. 400/130 kv 750 MVA 150 MVAr 150 MVAr 100 MVAr Figure 3. Single line diagram of Hemsjö 400 kv substation. (Legend: See Figure 4.) kv sectionalised single busbar configuration The 130 kv sub-transmission part of the Hemsjö substation is owned and operated by Sydkraft Nät. The switchgear was rehabilitated during using a simplified busbar scheme based on the DCB. The 130 kv switchgear includes bays for ten 130 kv lines, two capacitor banks, one 130/50 kv transformer, and one incoming bay from the 400/130 kv transformer. Before the rehabilitation, the 130 kv switchgear had a conventional double-busbar configuration, comprising 14 circuit-breakers and 40 disconnectors. When planning the new switchgear, the pervading demand was to minimise the number of switching devices. By this, it would be possible to reduce the maintenance costs and improve the substation availability by reducing both the total failure rate and the need for outages due to maintenance activities. The new switchgear is built in a sectionalised single busbar configuration comprising only 15 DCBs, as shown in the single line diagram in Figure 4. The simplified busbar configuration will limit the switching flexibility compared to a double busbar scheme, however, this aspect is overridden by the improved availability. Manual disconnection devices are utilised towards the busbar, as indicated in Figure 4. In summary, the simplified configuration of the 130 kv substation resulted in higher availability, substantially reduced need for maintenance, space saving, less auxiliary cabling, and a shorter design and installation time. Furthermore, the new switchgear is an improvement from safety point of view, since maintenance personnel will spend less time in the substation. 4

5 130/50 kv 25 MVA 400/130 kv 750 MVA Legend Disconnecting Circuit Breaker Disconnector Earthing switch Current Transformer Voltage Transformer Power Transformer Auto Transformer Capacitor Bank Manual disconnection point Figure 4. Single line diagram of Hemsjö 130 kv substation. 4. SAFETY ASPECTS OF THE DCB 4.1. Description of blocking and interlocking systems When the DCB is used to isolate other equipment for maintenance or repair work, it needs to be locked in the open position in a failsafe way. The locking of the DCB consists of electrical and mechanical locking of the operating mechanism, as well as mechanical locking of the main linkage system for the breaker pole. As an example, the interlocking sequence for the 400 kv DCB is described below: In open position, the operating mechanism of the DCB is blocked by de-energising the coil controlling the latch shown in Figure 5. This prevents the DCB from closing even if an electrical closing signal should be given. Subsequently, mechanical blocking of the operating rod of the DCB is made, see Figure 6 (detail of locking mechanism is shown in Figure 7). When the mechanical blockings have been carried out, the output signal DCB in disconnected position is given to the interlocking system. As soon as all the DCB feeding the point to be earthed are in the disconnected position and the primary voltage of this point is low (checked to ensure that the remote line end is open), the interlocking system will give a release signal making it possible to close the earthing switch. Normal safety actions, e.g. padlocking and labelling of the closed earthing switch, are carried out in the usual way. Indication information is also communicated to the control centre. 5

6 Figure 5. Latch for blocking the operating mechanism in the open position. Figure 6. Operating rod of DCB locked in open position by separate operating device. Figure 7. Detail of locking mechanism for DCB operating rod (locked position) Longitudinal insulation There is a minute risk that a flashover may occur across any high-voltage insulator in a substation during a pollution event or due to an overvoltage caused by lightning or switching. A flashover may constitute hazard to substation personnel since the power arc will cause UV and heat radiation. The personal risks associated with the earth fault current and the corresponding step and touch voltages are controlled by keeping these voltages down to a secure level, by sufficient earthing grid in the same way as for substations with conventional circuit breakers and disconnectors. Specifically for a DCB in the open position, the longitudinal insulation may be subject to dielectric stresses in the form of power frequency voltages and/or transient overvoltages. One terminal may be energised at operating voltage or grounded, while the voltage on the other terminal may be the operating voltage (with arbitrary phase shift) or a transient overvoltage (caused by lightning or switching). The basic requirements on the longitudinal insulation of switching equipment in general are discussed in [5]. The power frequency voltage across the longitudinal insulation may be up to twice the nominal operating voltage in an out-of-phase condition, e.g. during synchronising of generators. However, such conditions are of short duration, typically seconds or minutes, while lower stresses may exist for longer periods. The transient overvoltages are mainly caused by lightning strokes to the lines, or by switching events. It should be noted that phase-to-ground overvoltage levels are limited by flashovers occurring across line insulators, or by the surge arresters. The risk of a disruptive discharge across the longitudinal insulation of a DCB depends on the voltage stresses and the insulating properties. The air gap of a conventional DS is nearly unaffected by time or climatic conditions, while for the CB and the DCB, the risks of flashovers are related to the internal and external insulating properties of the breaker chamber insulator. These properties may change with time; the internal insulation withstand may be reduced by conductive deposits and the external insulation may be temporarily affected by pollution or ice. For the conventional CB, these aspects are to a certain degree covered by international standards. For the DCB, however, the upcoming IEC standard is considerable more stringent with regard to the long-term performance of the insulation, as discussed in Section 5. The combined function of the DCB is achieved by higher longitudinal insulation strength across open terminals compared with a CB, in order to fulfil also the higher insulation requirements on a DS. In addition, the DCB breaker chamber insulator is made of composite material with hydrophobic silicone-rubber weathersheds providing superior long-term insulating properties. When compared with a conventional CB, the risk of disruptive discharges is therefore lower for the DCB due to higher longitudinal insulation strength in terms of the higher insulation level and the hydrophobic external insulation surface. This is independent of the type of voltage stress, whether it is transient or has power 6

7 frequency. Compared with a conventional DS, the risk of disruptive discharges across the DCB is affected by the presence of the breaker chamber insulator. The overall risk of disruptive discharges is lower when one side of the DCB is grounded, due to the lower maximum voltage stress on the longitudinal insulation. The risk of external flashovers due to power frequency voltages are minimised by appropriate coordination of the external insulation with regard to pollution and ice. The risk of internal or external disruptive discharges due to overvoltages are minimised by proper co-ordination between insulation withstand levels and overvoltage levels. In a situation with closed earthing switch, the power arc current resulting from a disruptive discharge across a DCB will be equal to the earth fault current. The earthing switch will handle the fault current, and the ordinary protection system of the substation will clear the fault. If the earthing switch is open, the power arc current will be equal to the current of a closed DCB in the same position. This means that the current level may be high or low, depending on the prevailing load conditions in the network. In the very unlikely event of an internal sparkover, the interrupting chamber is dimensioned to withstand the stresses without explosion Insulation co-ordination Insulation co-ordination with regard to pollution and ice The risk of flashover across the DCB in open position due to pollution or ice is determined by the actual environmental conditions and the performance of the breaker chamber insulator under these conditions. The flashover performance is verified by withstand tests in the laboratory under the specified pollution or ice conditions. For polluted environments, the service conditions are preferably described in terms of the expected maximum equivalent salt deposit density (ESDD). Relevant laboratory test methods are the Dry Salt Layer (DSL) test [6] or the Solid Layer method included in IEC (Artificial pollution tests on high-voltage insulators to be used on a.c. systems). For icing environments, the service conditions are often described in terms of the expected maximum ice conductivity. In addition, the ice thickness may be prescribed. Relevant icing test methods for high-voltage insulators are presented in [7] Insulation co-ordination with regard to transient overvoltages The risk of disruptive discharge across the DCB in open position due to transient overvoltages is determined by the statistical distributions of voltage strengths and stresses of the longitudinal insulation. The statistical insulation co-ordination procedures, based on the rate and distribution of overvoltage levels and withstand levels, are described in IEC (Insulation co-ordination). The rate of lightning overvoltages appearing across the longitudinal insulation depends mainly on the ground flash density, the lightning performance of the transmission lines, and the number and length of transmission lines connected to the energised terminal of the DCB. The rate of switching overvoltages depends primarily on the same parameters; the majority of switching overvoltages are due to high-speed auto re-closing of lines after earth faults caused by lightning. The statistical distributions of overvoltage levels depend on the number of transmission lines connected to the energised terminal of the DCB, and on the flashover voltage of the line insulators. In addition, the overvoltage distributions may be heavily affected by surge arresters in the substation or on the lines. When surge arresters are applied, the distance between the surge arresters and the DCB is important to the lightning overvoltage levels at the DCB terminal. (It should be noted that surge arresters could be mounted closer to the DCB in comparison with conventional switching devices.) The risk of disruptive discharge across the longitudinal insulation can be reduced to an arbitrary low level by selecting the withstand level of the DCB with regard to the rates and distributions of the lightning and switching overvoltages, in accordance with IEC

8 5. INTERNATIONAL STANDARDISATION WORK The disconnecting circuit-breaker is a combined function switching device, which means it has to comply with both circuit-breaker and disconnector standards. The IEC has initiated the work on a new standard for this novel type of equipment: IEC , Combined function disconnecting circuitbreakers, expected to be published in The main difference in the standard s requirements on the combined function disconnecting circuitbreaker compared to a conventional circuit-breaker are the repeated dielectric tests following the mechanical and short-circuit tests. The aim of repeating the dielectric tests (with requirements according to the disconnector standard) is to prove that the disconnecting properties of the DCB are fulfilled during its service life, despite contact wear and any decomposition by-product generated by arc interruption. 6. CONCLUSIONS The concept of disconnecting circuit-breakers has been illustrated by presenting the application of the DCB in a major 400/130 kv transmission substation. It was shown that the substation configuration could be simplified in a considerable way by using the DCB instead of conventional switching devices, at the same time improving the overall availability of the substation. The safety aspects of the DCB have been discussed with reference to the blocking system (ensuring that the DCB is not closed unintentionally when used as a disconnector), and with reference to the longitudinal insulation in open position. The risk of a disruptive discharge across the open DCB is always lower than with a conventional CB. Furthermore, the risk is reduced to an arbitrarily low level by adequate insulation co-ordination with respect to overvoltage levels and environmental conditions. A new international standard, taking into account the special requirements on Combined function disconnecting circuit-breakers, is soon to be published. 7. REFERENCES [1] B Wahlström, Y Aoshima, Y Mino, C Lajoie-Mazenc, D R Torgerson, A N Zomers, The Future Substation: a reflective approach, Report , Cigré Session, Paris, [2] P Norberg, M Tapper, W Lord, A Engqvist, The Future Substation - Reflection About Design, Report , Cigré Session, Paris, [3] C-E Sölver, H-E Olovsson, W Lord, P Norberg, J Lundquist, Innovative Substations with High Availability using Switching Modules and Disconnecting Circuit-breakers, Report , Cigré Session, Paris, [4] H-E Olovsson, C-E Sölver, Innovative Solutions for Increasing Reliability and Availability in AIS Substations, Cigré SC23 Colloquium, Venezuela, [5] K Markussen et al., The Insulation Between Terminals of Circuit-breakers and Disconnectors, Electra No. 26, [6] C S Engelbrecht, R Hartings, H Tunell, B Engström, H Janssen, R Hennings, Pollution Tests for Coastal Conditions on an 800-kV Composite Bushing, IEEE Transactions on Power Delivery, Vol. 18, No. 3, July 2003, pp [7] M. Farzaneh et al., Insulator Icing Test Methods and Procedures A Position Paper Prepared By the IEEE Task Force on Insulator Icing Test Methods, IEEE Transactions on Power Delivery, Vol. 18, No. 4, October 2003, pp

ABB s Disconnecting Circuit Breakers Higher substation availability and lower environmental impact

ABB s Disconnecting Circuit Breakers Higher substation availability and lower environmental impact ABB s Disconnecting Circuit Breakers Higher substation availability and lower environmental impact Authors Carl Ejnar Sölver, ABB High Voltage Products Rasmus Larsson, ABB High Voltage Products 2 ABB ABB

More information

The Intelligent AX1 Switchgear for Medium Voltage

The Intelligent AX1 Switchgear for Medium Voltage The Intelligent AX1 Switchgear for Medium Voltage Leif Lundin, Manager of Research and Development, Division Medium Voltage and Compact Substations, ABB Distribution, Sweden Abstract The newly launched

More information

Advantages of Fixed Circuit Breaker Switchgear

Advantages of Fixed Circuit Breaker Switchgear Advantages of Fixed Circuit Breaker Switchgear by Lionel Mackay, EDF Energy, and Mike Adams, Schneider Electric Ltd Introduction The purpose of this paper is to review the advantages of fixed circuit breaker

More information

High-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv

High-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv High-Voltage Compact Switchgear AP1 DTC for 1 kv and kv Answers for energy. The AP1 DTC Complying with our Customers demands Experience you can rely on - at anytime, anywhere Decades of experience in high-voltage

More information

Circuit Breaker LTB D with Motor Drive. Motor Drive. ABB PP/H/HV - Page 1. Ed 2006-04

Circuit Breaker LTB D with Motor Drive. Motor Drive. ABB PP/H/HV - Page 1. Ed 2006-04 Circuit Breaker LTB D with Motor Drive Motor Drive ABB PP/H/HV - Page 1 Ed 2006-04 Technology Traditional technology Traditional spring operating mechanism: Closing mechanism ABB PP/H/HV - Page 2 Tripping

More information

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV 1. SCOPE This document details PowerSystems requirements for electrical testing of HV Equipment up to and including 33kV. 2. ISSUE RECORD This is a Reference document. The current version of Controlled

More information

SF 6 Gas Insulated Switchgear Type SDF for 170 kv

SF 6 Gas Insulated Switchgear Type SDF for 170 kv Three Phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDF for 170 kv 06B1-E-0001 With Trustworthy Technology, Structure Fuji Electric as a manufacturer of comprehensive substation equipment

More information

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS Meher Capacitors offers reliable and innovative products and solutions in the fields of Reactive Power Compensation, Power Quality and Energy

More information

Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation

Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation Index News Introduction Applications & Segments Main Components Applicable Standards Technical characteristics

More information

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Course No: E02-010 Credit: 2 PDH Boris Shvartsberg, Ph.D., P.E., P.M.P. Continuing Education

More information

UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution

UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution UniGear ZS1 Medium voltage, arc proof, air insulated switchgear for primary distribution UniGear ZS1: an innovative solution for all installation requirements ABB UniGear is medium voltage metal-clad,

More information

www.siemens.com/energy High Voltage Circuit Breakers 3AP Type 72.5 kv to 800 kv Answers for energy.

www.siemens.com/energy High Voltage Circuit Breakers 3AP Type 72.5 kv to 800 kv Answers for energy. s www.siemens.com/energy High Voltage Circuit Breakers AP Type 7.5 kv to 800 kv Answers for energy. The AP High Voltage Circuit Breakers Available up to 800 kv Decades of our experience in high voltage

More information

ABB Power Systems. Substations References

ABB Power Systems. Substations References ABB Power Systems Substations References Jingzhou, China BA PTPS - 2 - Connection of power from the 3-Gorges-Project to Guandong province (940km away) HVDC Transmission station, Filter banks and GIS Extremely

More information

High-Voltage Circuit-Breakers 3AP1/2 72.5 kv up to 550 kv. Power Transmission and Distribution

High-Voltage Circuit-Breakers 3AP1/2 72.5 kv up to 550 kv. Power Transmission and Distribution High-Voltage Circuit-Breakers AP/ 7.5 kv up to 550 kv Power Transmission and Distribution The AP/ High-Voltage Circuit-Breakers Now Applicable for 550 kv Decades of our experience in high-voltage switching

More information

Product brochure Multi Functional Switchgear PASS M00 72.5 kv Flexible and compact switchgear solutions for windfarms

Product brochure Multi Functional Switchgear PASS M00 72.5 kv Flexible and compact switchgear solutions for windfarms Product brochure Multi Functional Switchgear PASS M00 72.5 kv Flexible and compact switchgear solutions for windfarms The future of Wind Farms As offshore wind farms move towards deploying higher capacity

More information

OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd

OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd ACTOM OUTDOOR DISCONNECTORS Single Side Break (SSB) Disconnector 22-132 kv, 800-1 A, 25 ka - 3s Typical bearing assembly. Voltage range 11 kv to 132

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to

More information

High-Voltage GIS yesterday - today - tomorrow

High-Voltage GIS yesterday - today - tomorrow High-Voltage GIS yesterday - today - tomorrow Peter Glaubitz, Siemens AG, Principal Expert GIS-Technology siemens.at/future-of-energy Table of content GIS yesterday beginning and establishment of Gas-

More information

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting 12 SOLAR PHOTOVOLTAIC POWER by John Ware IT IS PLANNED for BS 7671:2008 to include a new Section 712 providing additional requirements for safety applicable to solar photovoltaic (pv) power supply systems.

More information

ISIO 200. Binary Input/Output (I/O) Terminal with IEC 61850 Interface

ISIO 200. Binary Input/Output (I/O) Terminal with IEC 61850 Interface ISIO 200 Binary Input/Output (I/O) Terminal with IEC 61850 Interface Compact and Easy ISIO 200 Put your Binary I/Os where you need them ISIO 200 is a simple and versatile binary I/O terminal with IEC 61850

More information

Siemens Integrated Substation Condition Monitoring System. Circuit Breaker Monitoring

Siemens Integrated Substation Condition Monitoring System. Circuit Breaker Monitoring Siemens Integrated Substation Condition Monitoring System Circuit Breaker Monitoring System Description Introduction The Circuit Breaker Monitor [CBM] is only one example of the way that the Substation

More information

Trip circuit supervision relay. Type RXTCS

Trip circuit supervision relay. Type RXTCS Trip circuit supervision relay Type RXTCS ABB a global technology leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers to improve performance while

More information

FAQs-Main switchboard design criteria

FAQs-Main switchboard design criteria FAQs-Main switchboard design criteria Q: What is the Australian standard for main switchboards? Current Australian standard is AS/NZS 3439.1: 2002 originating from IEC 60439. The new series of standard

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60071-2 Third edition 1996-12 Insulation co-ordination Part 2: Application guide This English-language version is derived from the original bilingual publication by leaving out

More information

Design and testing of polymer-housed surge arresters with special emphasize on seismic stresses and selection of specific creepage in costal areas.

Design and testing of polymer-housed surge arresters with special emphasize on seismic stresses and selection of specific creepage in costal areas. 108 Design and testing of polymer-housed surge arresters with special emphasize on seismic stresses and selection of specific creepage in costal areas. S. Narita, A. Sawada, L. Stenström H. Watanabe, B.

More information

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4 CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,

More information

Modular Systems wind portfolio overview Power Collection and Grid Connection products

Modular Systems wind portfolio overview Power Collection and Grid Connection products Modular Systems wind portfolio overview Power Collection and Grid Connection products Slide 1 Modular Systems wind portfolio Wind power - definition A wind turbine is a device that converts kinetic energy

More information

Relion. Power system protection and automation reference Fast substation busbar protection with IEC 61850 and GOOSE

Relion. Power system protection and automation reference Fast substation busbar protection with IEC 61850 and GOOSE Relion Power system protection and automation reference Fast substation busbar protection with IEC 61850 and GOOSE Fast substation busbar protection with IEC 61850 and GOOSE Falu Elnät AB applies new power

More information

Power transformers. Special transformers Railway

Power transformers. Special transformers Railway Power transformers Special transformers Railway A leader in railway systems Our compact and low-weight transformers fully comply with the customer s specifications. The products are developed together

More information

Electrical Shore Connections / Cold Ironing

Electrical Shore Connections / Cold Ironing STANDARD FOR CERTIFICATION No. 2.25 Electrical Shore Connections / Cold Ironing JULY 2014 The electronic pdf version of this document found through http://www.dnv.com is the officially binding version

More information

On-line monitoring of substation condition a Romanian experience. V. ZAHARESCU, Vl. ROSCA Nova Industrial SA. CN Transelectrica SA Romania

On-line monitoring of substation condition a Romanian experience. V. ZAHARESCU, Vl. ROSCA Nova Industrial SA. CN Transelectrica SA Romania 21, rue d Artois, F-75008 PARIS http : //www.cigre.org B3_201 CIGRE 2012 On-line monitoring of substation condition a Romanian experience C. MOLDOVEANU*, V. BREZOIANU, S. GAL, V. METIU, A. VASILE, V. URSIANU,

More information

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A AUTOMATIC TRANSFER SWITCH Changeover Type from 250A to 2500A Table of Contents Preamble 1.1 Theoretical base 1.2 Selection the size of automatic transfer switch 1.3 Automatic transfer switch components

More information

Engineering innovation

Engineering innovation Eaton's Electrical Engineering Services & Systems Solutions Focus Seamless Solutions for Reliable, Efficient and Safe Power Systems Engineering innovation Progressive solutions for today s power systems

More information

Guide to the electrical parameter classifications of IEC 60950 and IEC 62368 safety standards

Guide to the electrical parameter classifications of IEC 60950 and IEC 62368 safety standards Guide to the electrical parameter classifications of IEC 60950 and IEC 62368 safety standards Abstract This Guide is an informative listing of selected terms and definitions found in IEC Glossary entry

More information

ECE 586b Course Project Report. Auto-Reclosing

ECE 586b Course Project Report. Auto-Reclosing ECE 586b Course Project Report Auto-Reclosing Srichand Injeti May 5, 2008 Department Of Electrical and computer Engineering University Of Western Ontario, London Ontario Table of contents 1. Introduction...1

More information

How To Choose A Transformer

How To Choose A Transformer Consider open loop MV network as an example source 1 source 2 NC NC NC or NO main MV switchboard A B Detail design of substation NC NC NC NO NC NC switchboard 1 switchboard 2 switchboard 3 MV MV MV LV

More information

Preliminary Results from Present Cigre Survey

Preliminary Results from Present Cigre Survey Cigre WG A3-06 HV Equipment Reliability Preliminary Results from Present Cigre Survey Gas Insulated Substations (GIS) DB status : August 2007 Focus on population cards and major failure cards (namely 2004

More information

Residual life aspects on GIS with the focus on SF 6

Residual life aspects on GIS with the focus on SF 6 Residual life aspects on GIS with the focus on SF 6 Speaker: Karsten Pohlink 25. March 2015 The presentation refers to CIGRÉ WORKING GROUP B3.17 RESIDUAL LIFE CONCEPTS APPLIED TO HV GIS CIGRE Technical

More information

Permissible ambient temperature Operation Storage, transport

Permissible ambient temperature Operation Storage, transport The Sitras PRO combined DC protective unit and controller is used in the power supply for DC railways in mass transit and main-line systems up 3,000 V DC. It protects DC switch gear and contact line systems

More information

Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c 91052 Erlangen Germany. www.siemens.

Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c 91052 Erlangen Germany. www.siemens. Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c 91052 Erlangen Germany www.siemens.com/energy For questions on power transmission and distribution, please contact

More information

Condition Monitoring of equipment to improve quality of supply to customers by averting failures

Condition Monitoring of equipment to improve quality of supply to customers by averting failures Condition Monitoring of equipment to improve quality of supply to customers by averting failures Author & presenter: Patrick O Halloran BTECH Manager Technology Services at City Power Johannesburg Abstract

More information

IEC/CIGRE UHV Symposium Beijing 2007-07-23 3-1-4 800KVDC: EXTERNAL INSULATION, INSULATION COORDINATION, TEST LEVELS

IEC/CIGRE UHV Symposium Beijing 2007-07-23 3-1-4 800KVDC: EXTERNAL INSULATION, INSULATION COORDINATION, TEST LEVELS IEC/CIGRE UHV Symposium Beijing 2007-07-23 3-1-4 800KVDC: EXTERL INSULATION, INSULATION COORDITION, TEST LEVELS D. Wu (*) U. Åström V. F. Lescale ABB Power Systems, HVDC Ludvika, Sweden SUMMARY The use

More information

ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F

ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F TABLE OF CONTENTS Appendix F - Electrical Engineering Design Criteria F.1 Introduction...F-1 F.2 Codes and Standards...F-1 F.3 Switchyard and Transformers...F-1

More information

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Title MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Duration 5 days Training Date MV, HV and EHV Switchgear Testing & Commissioning 5 20 24 Apr $3,750 Dubai, UAE In any of the 5 star

More information

Safety technique. Emergency stop module BO 5988 safemaster

Safety technique. Emergency stop module BO 5988 safemaster Safety technique Emergency stop module BO 5988 safemaster 0221562 Function diagram Pushbutton on Mains or emergencystop () K1 According to EC Directive for machines 98/37/EG According to IEC/E 60204-1

More information

Disconnectors and Earthing Switches 36 kv up to 800 kv

Disconnectors and Earthing Switches 36 kv up to 800 kv Power Transmission and Distribution Disconnectors and Earthing Switches 36 kv up to 800 kv Ruhrtal & Siemens: A strong and successful team We manufacture high quality high-voltage disconnectors and earthing

More information

Power products and systems. Intelligent solutions for power distribution Zone concept

Power products and systems. Intelligent solutions for power distribution Zone concept Power products and systems Intelligent solutions for power distribution Zone concept Securing continuous power supply ABB is one of the world's leading power and automation technology companies whose products,

More information

INTERNATIONAL POWER DISTRIBUTION CONGRESS CIDEL ARGENTINA 2002

INTERNATIONAL POWER DISTRIBUTION CONGRESS CIDEL ARGENTINA 2002 INTERNATIONAL POWER DISTRIBUTION CONGRESS CIDEL ARGENTINA 2002 NEW GAS INSULATED SWITCHGEAR (GIS) FOR ALL MEDIUM VOLTAGE APPLICATIONS H. Fink, ABB Calor Emag Mittelspannungs GmbH; M. Hyrenbach, ABB Calor

More information

INTELLIGENT SWITCHGEAR AND INFORMATION TECHNOLOGY

INTELLIGENT SWITCHGEAR AND INFORMATION TECHNOLOGY Wold nergy onference FORN 2000, September 10-14, 2000 INTLLIGNT SWITHGAR AND INFORMATION THNOLOGY Bertil Lundqvist ABB Automation Products AB (Sweden) 1 ABSTRAT The development within the communication

More information

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132

More information

Product Safety Considerations for Insulation Coordination of Low- Voltage Equipment. Scott Aldous, Compliance Engineer

Product Safety Considerations for Insulation Coordination of Low- Voltage Equipment. Scott Aldous, Compliance Engineer Product Safety Considerations for Insulation Coordination of Low- Voltage Equipment Scott Aldous, Compliance Engineer What is Insulation Coordination? From IEC 60664-1, Edition 1.2: So what does that mean

More information

TWENTIES WORKSHOP, EWEA 2012 Unveiling the future energy system: full scale demonstrations to reach 2020 targets. 17th April 2012

TWENTIES WORKSHOP, EWEA 2012 Unveiling the future energy system: full scale demonstrations to reach 2020 targets. 17th April 2012 TWENTIES WORKSHOP, EWEA 2012 Unveiling the future energy system: full scale demonstrations to reach 2020 targets 17th April 2012 Session 2 Technological challenges to cope with in TWENTIES field tests

More information

DISCONNECTORS AND LOAD SWITCHES for railways

DISCONNECTORS AND LOAD SWITCHES for railways DISCONNECTORS AND LOAD SWITCHES for railways GRID Disconnectors and load switches for railways Alstom Grid delivers transmission solutions worldwide to utility and large industrial customers seeking smarter,

More information

What will MV switchgear look like in the future? by Jean-Marc Biasse

What will MV switchgear look like in the future? by Jean-Marc Biasse What will MV switchgear look like in the future? by Jean-Marc Biasse Table of contents Introduction... 2 Brief history of the technologies used in medium voltage switchgear and control gear... 4 Evolution

More information

New Distribution Class Arrester Ground Lead Disconnector Design Enhances Detonation Reliability and Improves Arrester Performance

New Distribution Class Arrester Ground Lead Disconnector Design Enhances Detonation Reliability and Improves Arrester Performance New Distribution Class Arrester Ground Lead Disconnector Design Enhances Detonation Reliability and Improves Arrester Performance Dennis W. Lenk, Fellow, IEEE Abstract-- This paper examines performance

More information

Guidance for upgrading to GB4943.1-2011 (IEC 60950-1: 2005, MOD)

Guidance for upgrading to GB4943.1-2011 (IEC 60950-1: 2005, MOD) Guidance for upgrading to GB4943.1-2011 (IEC 60950-1: 2005, MOD) Note: This guidance document is a translation of official Chinese document which is issued by CQC (China Quality Certification Center) on

More information

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms ABB innovations for changing demands ABB (www.abb.com) is a leader in power and automation technologies that enables utility

More information

Defining the Needs of Modern Data Center Power Systems, Low Voltage Circuit Breaker Application

Defining the Needs of Modern Data Center Power Systems, Low Voltage Circuit Breaker Application Defining the Needs of Modern Data Center Power Systems, Low Voltage Circuit Breaker Application by Reza Tajali, P.E. Square D Company ABSTRACT In modern data centers, Uninterruptible Power Supplies (UPS)

More information

Chapter 1. Network Structures

Chapter 1. Network Structures Chapter 1 Network Structures Definition Standard IEC 60038 defines voltage ratings as follows: Low voltage (): for a phase-to-phase voltage of between 100 V and 1,000 V, the standard ratings are: 400 V

More information

Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy

Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy Our brand A strong brand for strong products: The ENERGOLINE brand represents our product portfolio of INDUSTRIAL SWITCHGEAR SYSTEMS. Our products are characterized by a high degree of safety, flexibility

More information

PowlVac Vacuum Integrity Tester

PowlVac Vacuum Integrity Tester Instructions IB-60025B PowlVac Vacuum Integrity Tester POWELL ELECTRICAL MANUFACTURING COMPANY 8550 MOSLEY DRIVE HOUSTON, TEXAS 77075 USA PHONE (713) 944-6900 FAX (713) 947-4453 www.powellelectric.com

More information

CAPACITOR BANK TESTING SWP

CAPACITOR BANK TESTING SWP 1. PURPOSE AND SCOPE The purpose of this Standard Work Practice (SWP) is to standardise and prescribe the method for testing Capacitor Banks including capacitors, tuning reactors and inrush limiting reactors.

More information

Franco Vecchiato, SAM LPBS Regional Manager New SACE Emax 2 From Circuit-breaker to Power Manager

Franco Vecchiato, SAM LPBS Regional Manager New SACE Emax 2 From Circuit-breaker to Power Manager Franco Vecchiato, SAM LPBS Regional Manager New SACE Emax 2 From Circuit-breaker to Power Manager SACE Emax 2 From Circuit-Breaker to Power Manager Our customers need more efficient solutions, to Increase

More information

Emirates Aluminium starts up World s first fully integrated power distribution system from ABB

Emirates Aluminium starts up World s first fully integrated power distribution system from ABB Reprint from Aluminium World 2009, Volume 2 Emirates Aluminium starts up World s first fully integrated power distribution system from ABB Emirates Aluminium (EMAL), a joint venture between Abu Dhabi s

More information

Grounding of Electrical Systems NEW CODE: Grounding and Bonding

Grounding of Electrical Systems NEW CODE: Grounding and Bonding Grounding of Electrical Systems NEW CODE: Grounding and Bonding Presented By Scott Peele PE Grounding of Electrical Systems Outline Defining the Terms Why should I Ground? Types of Grounding Systems Separately

More information

IEC and IEEE Standards for High-Voltage Switchgear and Controlgear Present Situation and Future Evolution

IEC and IEEE Standards for High-Voltage Switchgear and Controlgear Present Situation and Future Evolution IEC and IEEE Standards for High-Voltage Switchgear and Controlgear Present Situation and Future Evolution Denis Dufournet Chairman IEC TC 17 & SC17A Fellow IEEE Senior Expert Areva T&D Mumbai, January,

More information

MEDIUM VOLTAGE SUBSTATION PRACTICES Medium Voltage (MV) is defined as: 1000V< MV 44kV

MEDIUM VOLTAGE SUBSTATION PRACTICES Medium Voltage (MV) is defined as: 1000V< MV 44kV MEDIUM VOLTAGE SUBSTATION PRACTICES MEDIUM VOLTAGE SUBSTATION PRACTICES Medium Voltage (MV) is defined as: 1000V< MV 44kV MEDIUM VOLTAGE SUBSTATION PRACTICES This presentation covers some safety aspects

More information

Medium voltage products UniSec for Smart Grid Air-insulated medium-voltage secondary distribution switchgear

Medium voltage products UniSec for Smart Grid Air-insulated medium-voltage secondary distribution switchgear Medium voltage products UniSec for Smart Grid Air-insulated medium-voltage secondary distribution switchgear Index 3 Overview 4 Standard Levels 6 Monitoring & Control 7 Measurements 8 Protection & Logic

More information

Lightning Arresters P30027 18 KVA P30038 10 KVA. Description & Installation

Lightning Arresters P30027 18 KVA P30038 10 KVA. Description & Installation Lightning Arresters P30027 18 KVA P30038 10 KVA Description & Installation Printed in USA 09/11 TO330 Rev. B Table of Contents Page 1.0 SCOPE 2 2.0 PRODUCT OVERVIEW 2 2.1 Intended Uses 2 2.2 Lightning

More information

Step Voltage Regulators

Step Voltage Regulators Step Voltage Regulators Don Wareham Field Application Engineer Today s Agenda Introduction Voltage Regulator theory Voltage Regulator application considerations Installation and proper bypassing Wrap-up/questions

More information

The standards mentioned in this document

The standards mentioned in this document The standards mentioned in this document Where can you order IEC publications? Central Offices of the International Electrotechnical Commission 1, rue de Varembé Geneva - Switzerland. The documentation

More information

New Technologies for Electric Power Distribution Systems

New Technologies for Electric Power Distribution Systems New Technologies for Electric Power Distribution Systems 158 New Technologies for Electric Power Distribution Systems to Unify Protection/ Units so They Can Be Incorporated into Intelligent Substations

More information

CAS 36 Ring Main Unit

CAS 36 Ring Main Unit Power distribution networks Ring Main Unit Catalogue 2008 A new path for achieving your electrical installations A comprehensive offer The range is part of a comprehensive offer of products that are perfectly

More information

ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors

ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants Installation instructions Contents Key points of installation Before installation Installation Installation check

More information

Powerformer chosen for Swedish combined heat and power plant

Powerformer chosen for Swedish combined heat and power plant Powerformer chosen for Swedish combined heat and power plant Powerformer, a radically new type of generator developed by ABB, has been chosen for a combined heat and power plant in Eskilstuna, Sweden.

More information

For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz)

For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz) 24 1. NETWORK CONFIGURATIONS definition Standard IEC 38 defines voltage ratings as follows: - Low voltage () For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690

More information

Standards in Marine Power Systems. APEC 2014 Session IS2.1 Power Electronic Standards Roger Dougal University of South Carolina Columbia, SC 29208

Standards in Marine Power Systems. APEC 2014 Session IS2.1 Power Electronic Standards Roger Dougal University of South Carolina Columbia, SC 29208 Standards in Marine Power Systems APEC 2014 Session IS2.1 Power Electronic Standards Roger Dougal University of South Carolina Columbia, SC 29208 Need is Driven by Electrification Oasis of the Seas DDG

More information

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU George CURCANU, Constantin ILINCA, Ilie SBORA ICMET Craiova, Romania, Calea Bucuresti 144, phone:

More information

Nuclear Power Plant Electrical Power Supply System Requirements

Nuclear Power Plant Electrical Power Supply System Requirements 1 Nuclear Power Plant Electrical Power Supply System Requirements Željko Jurković, Krško NPP, zeljko.jurkovic@nek.si Abstract Various regulations and standards require from electrical power system of the

More information

When power interruptions happen.

When power interruptions happen. When power interruptions happen. We know it s never a good time to have your power go out, so we work all year pruning trees and investing in our system to cut down on problems before they start. Outage

More information

Cost Benefit Methodology for Optimal Design of Offshore Transmission Systems

Cost Benefit Methodology for Optimal Design of Offshore Transmission Systems Centre for Sustainable Electricity and Distributed Generation Cost Benefit Methodology for Optimal Design of Offshore Transmission Systems Predrag Djapic and Goran Strbac July 2008 FUNDED BY BERR URN 08/1144

More information

The Application and Benefits of Multi-phase Auto-reclosing

The Application and Benefits of Multi-phase Auto-reclosing he Application and Benefits of Multi-phase Auto-reclosing etsuya Miyoshi*, Atsushi Kasai* Abstract - In this paper we explain the disadvantages in using single- and three-phase auto-reclosing on double

More information

Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution

Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution Medium Voltage Products ZN1 12 kv arc-proof air-insulated switchgear for primary distribution ZN1 an innovative switchgear for power distribution requirements ABB ZN1 primary distribution switchgear is

More information

Reliability requires consulting engineers and end users to grasp design, maintenance basics. By Reza Tajali, P.E. Square D Power Systems Engineering

Reliability requires consulting engineers and end users to grasp design, maintenance basics. By Reza Tajali, P.E. Square D Power Systems Engineering LOW VOLTAGE CIRCUIT BREAKER GUIDELINES FOR DATA CENTERS Reliability requires consulting engineers and end users to grasp design, maintenance basics By Reza Tajali, P.E. Square D Power Systems Engineering

More information

CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN

CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN 5.1 Introduction So far in the development of this research, the focus has been to estimate the available insolation at a particular location on the earth s surface

More information

AC-DC Converter Application Guidelines

AC-DC Converter Application Guidelines AC-DC Converter Application Guidelines 1. Foreword The following guidelines should be carefully read prior to converter use. Improper use may result in the risk of electric shock, damaging the converter,

More information

DS1 Diode-based transient-free capacitor switch

DS1 Diode-based transient-free capacitor switch Medium voltage products DS1 Diode-based transient-free capacitor switch Power and productivity for a better world TM Compensation of reactive power DS1 the future of switches Compensation of reactive power

More information

METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast.

METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast. METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV tgood.com Energy. Fast. TGOOD produces over 5000 switchgear units annually for projects around the globe PRODUCT OVERVIEW Integral substation component

More information

SIEMENS Transmission and Distribution

SIEMENS Transmission and Distribution TITLE Long Term Maintenance and Care for S36A E. C. Wright 02/09/04 This document is to be used in conjunction with Installation, Operation and Maintenance Schedule IOMS 635. Its aim is to provide guidance

More information

Power transformers. Generator step-up and system intertie power transformers Securing high-quality AC transmission

Power transformers. Generator step-up and system intertie power transformers Securing high-quality AC transmission Power transformers Generator step-up and system intertie power transformers Securing high-quality AC transmission Generator step-up transformers Built to withstand continuous full load Generator step-up

More information

Fusible Disconnect Switch

Fusible Disconnect Switch Circuit Breakers Circuit breakers are used in panelboards and switchboards to provide circuit protection and provide a means of energizing and de-energizing a circuit. Siemens Sentron molded case circuit

More information

CO-ORDINATION OF PARALLEL AC-DC SYSTEMS FOR OPTIMUM PERFORMANCE

CO-ORDINATION OF PARALLEL AC-DC SYSTEMS FOR OPTIMUM PERFORMANCE CO-ORDINATION OF PARALLEL AC-DC SYSTEMS FOR OPTIMUM PERFORMANCE Ana Diez Castro & Rickard Ellström Ying Jiang Häfner Christer Liljegren Vattenfall Utveckling AB ABB Power Systems Gotlands Energiverk AB

More information

Model 1756 Test Lead Kit

Model 1756 Test Lead Kit Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-888-KEITHLEY http://www.keithley.com Model 1756 Test Lead Kit Gerneral Purpose Test Lead Information Description These test leads allow you

More information

High Voltage (HV) Electricity System Safety Rules and Associated Safety Guidance

High Voltage (HV) Electricity System Safety Rules and Associated Safety Guidance Annex I To Loughborough University (LU) Facilities Management (FM) Health and Safety Policy High Voltage (HV) Electricity System Safety Rules and Associated Safety Guidance 1. Introduction a. These Safety

More information

SURGE PROTECTIVE DEVICES

SURGE PROTECTIVE DEVICES SURGE PROTECTIVE DEVICES 1. INTRODUCTION In order to ensure safety of people, protection of equipment and, to a certain extent, continuity of supply, insulation co-ordination aims at reducing the likelihood

More information

Design of electrical power system for a 1000MW nuclear power generating station

Design of electrical power system for a 1000MW nuclear power generating station Design of electrical power system for a 1000MW nuclear power generating station K Raja, K Yesunadam Dept. of Electrical & Electronics Engineering, Lingaya s Institute of Management & Technology, Vijayawada,

More information

Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC

Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC Project name: Customer: Address, location of the system: Serial number

More information

Discussion on Class I & II Terminology. IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA

Discussion on Class I & II Terminology. IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA Discussion on Class I & II Terminology IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA What is Class I & II? C57.12.00 2010 is the only document we have that defined these terms. 5.10 Insulation

More information

Application-oriented testing of line differential protection end to end in the field using the corresponding RelaySimTest template

Application-oriented testing of line differential protection end to end in the field using the corresponding RelaySimTest template Application Note Application-oriented testing of line differential protection end to end in the field using the corresponding RelaySimTest template Author Jens Baumeister jens.baumeister@omicron.at Date

More information

NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements

NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems Safe energy distribution that meets the highest industrial requirements NATUS switchgear systems your advantages minimal use of insulant

More information