Interfacing Fire Alarm, Sprinkler and Elevator Systems

Size: px
Start display at page:

Download "Interfacing Fire Alarm, Sprinkler and Elevator Systems"

Transcription

1 Webinar Series: Interfacing Fire Alarm, Sprinkler and Elevator Systems Bruce Fraser Fraser Fire Protection Services Become an 1

2 Agenda: Elevator Recall and Power Shut-down Historical Perspective Where we are today, code-wise Look at specific code sections Discuss some of the issues Where we appear to be headed 2

3 ASME A17.1 Safety Code for Elevators and Escalators Provides requirements for operational sequences for: - Phase 1 - Emergency Recall Operation - Power Shutdown - Shunt Trip Operation 3

4 ASME A17.1 Phase I - Emergency Recall Operation The operation of an elevator wherein it is automatically or manually recalled to a specific landing and removed from normal service because of activation of firefighters service 4

5 ASME A17.1 Power Shutdown (shunt trip) Mainline elevator power is disconnected from the elevator to eliminate potential problems as a result of sprinkler actuation in the hoistway or elevator machine room 5

6 Elevator Recall: Historical Perspective 1973 ASME A17.1b (supplement to the 1971 Code) Purpose: Prevent people from using elevators Allow firefighters to account for elevators Stage equipment (hose lines, air tanks, etc.) Evacuate occupants with mobility restrictions Prevent cars from being called to the fire floor 6

7 7

8 Elevator Recall: Historical Perspective Identified Designated Level Both Manual and Automatic Recall Key Switch (only by firefighters) Smoke Detectors in Lobbies Travel of 25 above or below designated level 1981 introduced the Alternate Level 8

9 Elevator Recall: Historical Perspective 1984 introduced only lobby and machine room detectors were to initiate recall A17.1 referred users to NFPA 72E, Automatic Fire Detectors NFPA first mentions A17.1 requirements in 1987 edition of NFPA 72A, Installation, Maintenance and use of Local Protective Signaling Systems Elevator Recall for Firefighters Service 9

10 Elevator Recall: Historical Perspective Two elevator zone circuits now required to be terminated at the associated elevator controller In 1989, A17.1 required smoke detectors in hoistways only when hoistways had sprinklers A17.1b, 1992 Supplement drops the 25 ft. criterion now applies to all automatic elevators regardless of travel distance 10

11 Elevator Recall: Historical Perspective 1993 edition of NFPA 72, National Fire Alarm Code addressed cases where there was no required building fire alarm system Elevator Recall and Supervisory Panel 1996 edition of NFPA 72 introduced other fire detection as being permissible if environment was not appropriate for a smoke detector. 11

12 Elevator Recall: Historical Perspective A third control circuit was added to provide a warning of fire in the hoistway or elevator machine room The 2000 A17.1 was harmonized with the Canadian B44 Elevator Safety Standard NFPA 72 [2002] and A17.1 [2004] now both address new technology elevators machine room-less elevators 12

13 Elevator Shunt Trip: Historical Perspective First introduced in ASME A Purpose: Remove main-line power prior to sprinkler activation Prevent elevators from moving/operating dangerously Note: the requirement does not include circuits for ventilation, in-car lights and communication, pit receptacles and lights, etc. 13

14 Recall & Shunt Trip: Historical Perspective A17.1 applies to all new elevator installations A17.3 (where adopted) applies to existing elevators A17.3 re: Firefighters Service Firefighters Service Elevators shall conform to the requirements of ASME/ANSI A Rules through (see Appendix C) unless at the time of installation or alteration it was required to comply with a later edition of A

15 Applicable Codes Elevator & Escalator Safety Code ASME/ANSI A17.1/B44 Building Codes and NFPA 101 NFPA 13 NFPA 70 NFPA 72 15

16 Applicable Codes Elevator & Escalator Safety Code ASME/ANSI A17.1/B44 Building Codes and NFPA 101 NFPA 13 NFPA 70 NFPA 72 15

17 Applicable Codes Elevator & Escalator Safety Code ASME/ANSI A17.1/B44 Building Codes and NFPA 101 NFPA 13 NFPA 70 NFPA 72 15

18 Out of Sync Codes ASME A Year Cycle with Yearly Addenda A A17.1a A17.1S A A17.1a A17.1b A

19 Out of Sync Codes ASME A Year Cycle with Yearly Addenda A A17.1a A17.1S A A17.1a A17.1b NFPA 72 and NFPA 13 3 Year Cycle 2002, 2007, 2010 etc. A

20 Confusion? 17

21 Confusion? Can t find all the information in one place! Must use A17.1, NFPA 72 and NFPA 13 together! 17

22 Here s where to find them! 18

23 ASME A Section 2.27 Emergency Operation and Signaling Devices Phase I Emergency Recall Operation by Fire Alarm Initiating Devices 19

24 ASME A Section 2.27 Emergency Operation and Signaling Devices Phase I Emergency Recall Operation by Fire Alarm Initiating Devices Note: Section 2.27 applies to Electric Elevators and section 3.27 applies to Hydraulic Elevators section 3.27 says refer to

25 ASME A Section 2.8 Equipment in Hoistways, Machinery Spaces, Machine Rooms, Control Spaces and Control Rooms (Shunt Trip / Power Disconnect requirement) 20

26 NFPA Protected Premises Fire Safety Functions Emergency Elevator Operations Emergency elevator operations shall meet the requirements of Sections 21.3, 21.4, 21.5, and

27 NFPA Chapter 21 Emergency Control Functions and Interfaces 21.3* Elevator Recall for Firefighters Service 21.4 Elevator Shutdown 21.5 First Responders Use Elevators 21.6 Elevators for Occupant-Controlled Evacuation 22

28 NFPA Chapter 8 Installation Requirements 8.15 Special Situations Elevator Hoistways and Machine Rooms. 23

29 Simplified Traction Elevator System Elevator Machine Room Alternate Level Designated Level 24

30 Simplified Hydraulic Elevator System Heat Detector Smoke Detector Sprinkler Detector Operation Recall to Alternate Level Recall to Designated Level Flash FF Helmet in Car (warning) Power Disconnect (shunt trip) Alternate Level Designated Level 1 Elevator Machine Room

31 Machine room-less Elevators Alternate Level Designated Level 26

32 Machine room-less Elevators 27

33 Machine room-less Elevators 27

34 Machine room-less Elevators 27

35 Machine room-less Elevators 27

36 A break for Questions? 28

37 ASME A In jurisdictions not enforcing the NBCC, fire alarm initiating devices used to initiate Phase I Emergency Recall Operation shall be installed in conformance with the requirements of NFPA 72, and shall be located (a) at each floor served by the elevator (b) in the associated elevator machine room, machinery space containing a motor controller or electric driving machine, control space, or control room (c) in the elevator hoistway, when sprinklers are located in those hoistways. 29

38 NFPA Elevator Recall for Firefighters Service Smoke detectors shall not be installed in unsprinklered elevator hoistways unless they are installed to activate the elevator hoistway smoke relief equipment. 30

39 NFPA * Elevator Recall for Firefighter s Service If ambient conditions prohibit installation of automatic smoke detection, other automatic fire detection shall be permitted. 31

40 NFPA Smoke-Sensing Fire Detectors * Unless specifically designed and listed for the expected conditions, smoke detectors shall not be installed if any of the following ambient conditions exist: (1) Temperature below 32 F (2) Temperature above 100 F (3) Relative humidity above 93 percent (4) Air velocity greater than 300 ft/min 32

41 33

42 NFPA Elevator Recall for Firefighters Service All initiating devices used to initiate firefighters service recall, shall be connected to the building fire alarm system. 34

43 NFPA Elevator Recall for Firefighters Service * In facilities without a building fire alarm system, initiating devices used to initiate firefighters service recall shall be connected to a dedicated function fire alarm system control unit that shall be designated as elevator recall control and supervisory control unit, permanently identified on the dedicated function fire alarm control unit and on the record drawings. 35

44 NFPA Elevator Recall for Firefighters Service Unless otherwise required by the authority having jurisdiction, only the elevator lobby, elevator hoistway, and the elevator machine room smoke detectors shall be used to recall elevators for firefighters service. 36

45 NFPA Elevator Recall for Firefighters Service * A lobby smoke detector shall be located on the ceiling within 21 ft. of the centerline of each elevator door within the elevator bank under control of the detector. 37

46 Smoke Detector Location 38

47 39

48 NFPA Elevator Recall for Firefighters Service * A lobby smoke detector shall be located on the ceiling within 21 ft. of the centerline of each elevator door within the elevator bank under control of the detector. 40

49 NFPA Elevator Recall for Firefighters Service * A lobby smoke detector shall be located on the ceiling within 21 ft. of the centerline of each elevator door within the elevator bank under control of the detector. Exception: For lobby ceiling configurations exceeding 15 ft in height or that are other than flat and smooth, detector locations shall be determined in accordance with Chapter

50 41

51 42

52 43

53 44

54 44

55 NFPA Location and Spacing * If the intent is to initiate action when smoke/fire threatens a specific object or space, the detector shall be permitted to be installed in close proximity to that object or space. 45

56 NFPA A There are some applications that do not require full area protection, but do require detection to initiate action when specific objects or spaces are threatened by smoke or fire such as at elevator landings that have ceilings in excess of 15 ft. and for protection of fire alarm control units. In high ceiling areas, to achieve the desired initiation such as for elevator recall and protection of FACUs, detection should be placed on the wall above and within 60 in. from the top of the elevator door(s) or FACU. 46

57 47

58 48

59 49

60 50

61 51

62 52

63 NFPA Elevator Recall for Firefighters Service Actuation from the elevator hoistway, elevator machine room, elevator machinery space, elevator control space, or elevator control room smoke detectors shall cause separate and distinct visible annunciation at the building fire alarm control unit and at required annunciators to alert fire fighters and other emergency personnel that the elevators are no longer safe to use. 53

64 ASME A Phase I Emergency Recall Operation by Fire Alarm Initiating Devices When a fire alarm initiating device in the machine room, control space, control room or hoistway initiates Phase 1 Emergency Recall Operation, the visual signal shall illuminate intermittently only in a car(s) with equipment in that machine room, control space, control room or hoistway. 54

65 ASME A Firefighters Emergency Operation - Automatic Elevators FIG (h) Visual Signal or When flashing, exit elevator 55

66 NFPA Designated Level Recall. For each elevator or group of elevators, an output shall be provided to signal elevator recall to the designated level in response to the following: 56

67 NFPA Designated Level Recall. For each elevator or group of elevators, an output shall be provided to signal elevator recall to the designated level in response to the following: (1) Activation of smoke detectors located at any elevator lobby served by the elevator(s) other than the lobby at the designated level. 56

68 NFPA Designated Level Recall. Cont d. (2) Activation of smoke detectors located at any elevator machine room, elevator machinery space, elevator control space, or elevator control room serving the elevator(s) except where such room or spaces are located at the designated level. 57

69 NFPA Designated Level Recall. Cont d. (2) Activation of smoke detectors located at any elevator machine room, elevator machinery space, elevator control space, or elevator control room serving the elevator(s) except where such room or spaces are located at the designated level. (3) Activation of smoke detectors located in the elevator hoistway serving the elevator when sprinklers are located in the elevator hoistway unless otherwise specified in (3). 57

70 NFPA Alternate Level Recall. For each elevator or group of elevators, an output shall be provided to signal elevator recall to the alternate level in response to the following: 58

71 NFPA Alternate Level Recall. For each elevator or group of elevators, an output shall be provided to signal elevator recall to the alternate level in response to the following: (1) Activation of smoke detectors located at the designated lobby served by the elevator(s). 58

72 NFPA Alternate Level Recall. Cont d. (2) Activation of smoke detectors located in the elevator machine room, elevator machinery space, elevator control space, or elevator control room serving the elevator(s) if such rooms or spaces are located at the designated level. 59

73 NFPA Alternate Level Recall. Cont d. (2) Activation of smoke detectors located in the elevator machine room, elevator machinery space, elevator control space, or elevator control room serving the elevator(s) if such rooms or spaces are located at the designated level. (3)* Activation of initiating devices identified in (3) if they are installed at or below the lowest level of recall in the elevator hoistway and the alternate level is located above the designated level. 59

74 NFPA Elevator Recall for Firefighters Service * Visual Warning. For each elevator or group of elevators, an output(s) shall be provided for the elevator visual warning signal in response to the following: (1) Activation of the elevator machine room, elevator machinery space, elevator control space, or elevator control room initiating devices identified in (2) Activation of the elevator hoistway initiating devices identified in 60

75 Pictorial Representation of Signals from Fire Alarm System to Elevator Controller Fire Alarm System Elevator Controller 2 Recall to Designated Level Elevator Lobby Detectors Elevator Machine Room Detector(s) 3 1 Warning to Elevator Cab Recall to Alternate Level Elevator Lobby Detector at Designated Level Elevator Hoistway Detector(s) Activation of smoke detector(s) causes signal(s) to elevator controller 61

76 Pictorial Representation of Signals from Fire Alarm System to Elevator Controller Fire Alarm System Elevator Controller 2 Recall to Designated Level Elevator Lobby Detectors Elevator Machine Room Detector(s) 3 1 Warning to Elevator Cab Recall to Alternate Level Elevator Lobby Detector at Designated Level Elevator Hoistway Detector(s) Activation of smoke detector(s) causes signal(s) to elevator controller 61

77 Pictorial Representation of Signals from Fire Alarm System to Elevator Controller Fire Alarm System Elevator Controller 2 Recall to Designated Level Elevator Lobby Detectors Elevator Machine Room Detector(s) 3 1 Warning to Elevator Cab Recall to Alternate Level Elevator Lobby Detector at Designated Level Elevator Hoistway Detector(s) Activation of smoke detector(s) causes signal(s) to elevator controller 61

78 Pictorial Representation of Signals from Fire Alarm System to Elevator Controller Fire Alarm System Elevator Controller 2 Recall to Designated Level Elevator Lobby Detectors Elevator Machine Room Detector(s) 3 1 Warning to Elevator Cab Recall to Alternate Level Elevator Lobby Detector at Designated Level Elevator Hoistway Detector(s) Activation of smoke detector(s) causes signal(s) to elevator controller 61

79 Fire Alarm System / Elevator Controller Relationship Elevator Controller Elevator Hoistway Smoke Detector(s) Elevator Machine Room Smoke Detector(s) Elevator Lobby Smoke Detector 5th Floor S R 1 R 2 R 3 EOL EOL EOL Elevator Machine Room Heat Detector(s) Elevator Lobby Smoke Detector 4th Floor S Elevator Hoistway Heat Detector(s) Elevator Lobby Smoke Detector 3rd Floor S Elevator Lobby Smoke Detector 2nd Floor (Alternate Level) S Elevator Lobby Smoke Detector Ground Floor (Designated Level) S SCC 1 actuation causes recall to alternate level SCC 2 actuation causes recall to designated level SCC 3 actuation causes flashing of warning signal Conventional or Addressable Zone / Circuit Module Elevator Lobby Smoke Detector Basement S S Fire Alarm Control Unit 62

80 NFPA Chapter 21 - Emergency Control Functions and Interfaces * A listed relay or other listed appliance connected to the fire alarm system used to initiate control of protected premises emergency control functions shall be located within 3 ft of the controlled circuit or appliance The relay or other appliance shall function within the voltage and current limitations of the fire alarm control unit. 63

81 NFPA Chapter 21 - Emergency Control Functions and Interfaces The installation wiring between the fire alarm control unit and the relay or other appliance shall be Class A, Class B, Class D, or Class X in accordance with Chapter

82 Addressable Control Relays 65

83 Addressable Control Relays 66

84 A break for Questions? 67

85 NFPA Elevator Hoistways and Machine Rooms * Upright, pendent, or sidewall spray sprinklers shall be installed at the top of elevator hoistways The sprinkler required at the top of the elevator hoistway by shall not be required where the hoistway for passenger elevators is noncombustible or limited combustible and the car enclosure materials meet the requirements of ASME A

86 NFPA Elevator Hoistways and Machine Rooms Sprinklers shall be installed at the top and bottom of elevators that utilize polyurethane-coated steel belts or other similar combustible belt material. 69

87 NFPA Elevator Hoistways and Machine Rooms Sprinklers shall be installed at the top and bottom of elevators that utilize polyurethane-coated steel belts or other similar combustible belt material. 69

88 NFPA Elevator Hoistways and Machine Rooms Sprinklers shall be installed at the top and bottom of elevators that utilize polyurethane-coated steel belts or other similar combustible belt material. 69

89 NFPA Elevator Hoistways and Machine Rooms * Sidewall spray sprinklers shall be installed at the bottom of each elevator hoistway not more than 2 ft above the floor of the pit The sprinkler required at the bottom of the elevator hoistway by shall not be required for enclosed, noncombustible elevator shafts that do not contain combustible hydraulic fluids. 70

90 ASME A Equipment in Hoistway and Machine Rooms means shall be provided to automatically disconnect the main line power supply to the affected elevator upon or prior to the application of water from the sprinklers located in the machine room or in the hoistway more than 24 in. above the pit floor. 71

91 ASME A Equipment in Hoistways and Machinery Spaces, Machine Rooms, Control Spaces, and Control Rooms In jurisdictions not enforcing the NBCC, where elevator equipment is located or its enclosure is configured such that application of water from sprinklers could cause unsafe elevator operation, means shall be provided to automatically disconnect the main line power supply to the affected elevator and any other power supplies used to move the elevator upon or prior to the application of water. 72

92 NFPA Elevator Shutdown * Where heat detectors are used to shut down elevator power prior to sprinkler operation, the detector shall have both a lower temperature rating and a higher sensitivity as compared to the sprinkler. 73

93 Recommendation: [Example] Use 165 o F, ordinary temperature rated sprinkler. Use 135 o F, thermistor-based heat detector. Or maintain a similar relationship based on ambient temperatures Note: Sprinklers in elevator machine rooms and hoistways must be of ordinary or intermediate temperature rating. (NFPA 13 [2010], ) 74

94 NFPA Elevator Shutdown * If heat detectors are used to shut down elevator power prior to sprinkler operation, they shall be placed within 24 in. of each sprinkler head and be installed in accordance with the requirements of Chapter

95 NFPA Elevator Shutdown * If heat detectors are used to shut down elevator power prior to sprinkler operation, they shall be placed within 24 in. of each sprinkler head and be installed in accordance with the requirements of Chapter 17. Alternatively, engineering methods, such as specified in Annex B, shall be permitted to be used to select and place heat detectors to ensure response prior to any sprinkler head operation under a variety of fire growth rate scenarios. 76

96 NFPA Elevator Shutdown * If pressure or waterflow switches are used to shut down elevator power immediately upon or prior to the discharge of water from sprinklers, the use of devices with time-delay switches or time-delay capability shall not be permitted. 77

97 NFPA Elevator Shutdown The initiating devices described in (HD) and (WFS) shall be monitored for integrity by the control unit required in Section and

98 Background: Water from sprinklers in the hoistway and elevator machine room presents a hazard to safe elevator operation: Shorts on circuit conductors - Uncontrolled and dangerous elevator operation Wet brakes (traction elevators) - Uncontrolled stopping 79

99 80

100 Shunt Trip Operation (theoretical) Smoke detector actuates, initiating elevator recall Elevators arrive at the recall floor and open doors Heat buildup causes heat detector to actuate Shunt trip operates, removing power from the elevator Sprinkler operates 81

101 Concern: Potential of passengers becoming entrapped in the elevator if a heat detector or waterflow switch actuates (to cause shunt trip ) prior to the completion of the recall function! 82

102 Sprinkler/Power Shutdown Concerns: A17.1 Task Group addressed Shunt Trip and Sprinklers Hazard Analysis was performed Concern of over-temperature of elevator controller Equipment stops Equipment runs erratically / uncontrollably Concern water from sprinklers may cause: Braking Failure Shorting out of an electrical safety or control circuit Equipment runs erratically / uncontrollably 83

103 Sprinkler/Power Shutdown Concerns: A17.1 Task Group Recommendations: Exempt sprinklers from being installed in elevator machine rooms and the top of the hoistway If sprinklers are installed in elevator machine rooms and/ or the top of the hoistway, then the delay of the release of water from sprinklers will be required so recall can be completed first. the delay strategy 84

104 NFPA Elevator Shutdown A Upon activation of the heat detector used for elevator power shut down, there should be a delay in the activation of the power shunt trip. This delay should be the time that it takes the elevator cab to travel from the top of the hoistway to the lowest recall level. 85

105 Shunt Trip Operation - Delay Strategy Smoke Detector Recall Heat Detector Recall X Time Delay Shunt Trip Open Valve (Pre-action or Other) Pre-action or Other Listed Valve Sprinkler(s) Release Water 86

106 Shunt Trip Operation - Delay Strategy Smoke Detector Recall Heat Detector Recall X Time Delay Shunt Trip Elevator Arrival Open Valve (Pre-action or Other) Pre-action or Other Listed Valve Sprinkler(s) Release Water 86

107 Shunt Trip Operation - Delay Strategy Either: Pre-Action Sprinkler System Fail-Safe Sprinkler Valve 87

108 Shunt Trip Operation - Delay Strategy Sprinkler Valve Electrically operated 24 VDC from Fire Alarm System Normally energized Held closed Fails open Underwriters Laboratories (UL) UL429, "Electrically Operated Valves" 88

109 Shunt Trip Operation - Delay Strategy Sprinkler Valve Electrically operated 24 VDC from Fire Alarm System Normally energized Held closed Fails open Underwriters Laboratories (UL) UL429, "Electrically Operated Valves" 88

110 Fire Alarm System / Elevator Controller Relationship Elevator Controller Elevator Hoistway Smoke Detector(s) Elevator Machine Room Smoke Detector(s) Elevator Lobby Smoke Detector 5th Floor S R 1 R 2 R 3 EOL EOL EOL Elevator Machine Room Heat Detector(s) Elevator Lobby Smoke Detector 4th Floor S Shunt Trip Breaker Elevator Hoistway Heat Detector(s) Elevator Lobby Smoke Detector 3rd Floor S R 4 EOL Hot Neut 120 VAC Circuit (Power to Operate Shunt Trip Breaker) From Emergency Power Source Conditions Sprinkler Release Elevator Lobby Smoke Detector 2nd Floor (Alternate Level) Elevator Lobby Smoke Detector Ground Floor (Designated Level) S S SCC 1 actuation causes recall to alternate level SCC 2 actuation causes recall to designated level SCC 3 actuation causes flashing of warning signal SCC 4 actuation causes disconnect of main line elevator power actuation causes sprinkler valve to open Conventional or Addressable Zone / Circuit Module SCC 5 Elevator Lobby Smoke Detector Basement S S Fire Alarm Control Unit 89

111 Fire Alarm System / Elevator Controller Relationship Elevator Controller Elevator Hoistway Smoke Detector(s) Elevator Machine Room Smoke Detector(s) Elevator Lobby Smoke Detector 5th Floor S R 1 R 2 R 3 EOL EOL EOL Elevator Machine Room Heat Detector(s) Elevator Lobby Smoke Detector 4th Floor S Shunt Trip Breaker Elevator Hoistway Heat Detector(s) Elevator Lobby Smoke Detector 3rd Floor S R 4 EOL Hot Neut 120 VAC Circuit (Power to Operate Shunt Trip Breaker) From Emergency Power Source Simultaneously Conditions Sprinkler Release Elevator Lobby Smoke Detector 2nd Floor (Alternate Level) Elevator Lobby Smoke Detector Ground Floor (Designated Level) S S SCC 1 actuation causes recall to alternate level SCC 2 actuation causes recall to designated level SCC 3 actuation causes flashing of warning signal SCC 4 actuation causes disconnect of main line elevator power actuation causes sprinkler valve to open Conventional or Addressable Zone / Circuit Module SCC 5 Elevator Lobby Smoke Detector Basement S S Fire Alarm Control Unit 89

112 NFPA Elevator Shutdown * Control circuits to shut down elevator power shall be monitored for presence of operating voltage. Loss of voltage to the control circuit for the disconnecting means shall cause a supervisory signal to be indicated at the control unit and required remote annunciators. 90

113 Fire Alarm System / Elevator Controller Relationship Elevator Controller Elevator Hoistway Smoke Detector(s) Elevator Machine Room Smoke Detector(s) Elevator Lobby Smoke Detector 5th Floor S R 1 R 2 R 3 EOL EOL EOL Elevator Machine Room Heat Detector(s) Elevator Lobby Smoke Detector 4th Floor S Shunt Trip Breaker Elevator Hoistway Heat Detector(s) Elevator Lobby Smoke Detector 3rd Floor S R 4 EOL Hot Neut 120 VAC Circuit (Power to Operate Shunt Trip Breaker) From Emergency Power Source R 5 * EOL *relay R5 contacts shown in deenergized position Conditions Sprinkler Release Elevator Lobby Smoke Detector 2nd Floor (Alternate Level) Elevator Lobby Smoke Detector Ground Floor (Designated Level) S S SCC 1 actuation causes recall to alternate level SCC 2 actuation causes recall to designated level SCC 3 actuation causes flashing of warning signal SCC 4 actuation causes disconnect of main line elevator power IDC 1 (Supervisory) actuation causes supervisory signal SCC 5 actuation causes sprinkler valve to open Elevator Lobby Smoke Detector Basement S Fire Alarm Control Panel Conventional or Addressable Zone / Circuit Module S 91

114 Fire Alarm System / Elevator Controller Relationship Elevator Controller Elevator Hoistway Smoke Detector(s) Elevator Machine Room Smoke Detector(s) Elevator Lobby Smoke Detector 5th Floor S R 1 R 2 R 3 EOL EOL EOL Elevator Machine Room Heat Detector(s) Elevator Lobby Smoke Detector 4th Floor S Shunt Trip Breaker Elevator Hoistway Heat Detector(s) Elevator Lobby Smoke Detector 3rd Floor S R 4 EOL Hot Neut 120 VAC Circuit (Power to Operate Shunt Trip Breaker) From Emergency Power Source R 5 * EOL *relay R5 contacts shown in deenergized position Conditions Sprinkler Release Elevator Lobby Smoke Detector 2nd Floor (Alternate Level) Elevator Lobby Smoke Detector Ground Floor (Designated Level) S S SCC 1 actuation causes recall to alternate level SCC 2 actuation causes recall to designated level SCC 3 actuation causes flashing of warning signal SCC 4 actuation causes disconnect of main line elevator power IDC 1 (Supervisory) actuation causes supervisory signal SCC 5 actuation causes sprinkler valve to open Elevator Lobby Smoke Detector Basement S Fire Alarm Control Panel Conventional or Addressable Zone / Circuit Module S 91

115 A break for 92

116 A break for Questions? 92

117 Ongoing Industry Effort 93

118 Background: Emergency egress and evacuation strategies for high-rise structures re-examined for tall buildings as a result of September 11, 2001 attack on the WTC 94

119 Background: Workshop on the Use of Elevators in Fires and other Emergencies (Atlanta March 2-4, 2004) Co-sponsored by ASME, NIST, ICC, NFPA, IAFF, and the US Access Board Representation from a cross section of industry 20 Fire service representatives funded by NIST and FEMA 95

120 Workshop Program: Focus: Use of Elevators by Firefighters Use of Elevators by Occupants During Emergencies Goal: to develop proposals that can be submitted to various code writing organizations 96

121 Process: ASME took lead on the hazard analysis 2 Task groups Occupant Use - to evaluate the use of elevators for egress in emergencies what can be done to decrease egress time Firefighter Use to evaluate use of elevators by firefighters during fire operations what can be done to mitigate existing hazards 97

122 Workshop : Consistent Themes - Concerns: Culture change since 9-11 total evacuation Elevators are not a substitute for stairs Evacuation of mobility impaired people Lack of firefighter confidence in using elevators Elevator reliability issues Water entering hoistways 98

123 Workshop : Consistent Themes - Concerns: Rescue of passengers Shunt trip entrapment Loss of elevator power from elsewhere in the building Retraining occupants to use elevators (in some buildings) Cost concerns Not enough information for occupants to make an informed decision 99

124 Workshop : Consistent Themes - Recommendations: Mandatory adoption of ASME A17.3 everywhere Ensure reliability of Phase I, Phase II operation Better training on elevator operation for firefighters Regular testing by qualified (certified?) personnel Building Emergency Action Plan enforcement 100

125 Workshop : Consistent Themes - Recommendations: Sprinkler all buildings Compartmented/pressurized lobbies/vestibules Area of Refuge / Rescue Assistance Better real time communications to occupants Better real time communications to firefighters Elevator technician respond to building emergencies 101

126 Workshop : Consistent Themes - Process: Utilize Hazard Analysis Involve firefighters in decisions Involve appropriate committees and organizations (A17-B44, IBC, NFPA, Access Board, etc.) 102

127 Process: Hazard Analysis (not a risk analysis) Develop scenarios Identify hazards Mitigate the hazard Identify residual hazards Mitigate the residual hazards 103

128 Residual hazard 104

129 Residual hazard 104

130 Recommendations: Robust Fire Service Elevators Provides greater protection allowing the elevator to continue to operate for the firefighters during their operations. Protection from water Protection from smoke and heat Direct access to protected lobby and stairwell containing standpipe Protection of primary and backup power supplies 105

131 Recommendations: Occupant Evacuation Operation [OEO] Scalable: OEO can be applied to one or more elevators in the building but is not necessarily required on all elevators. Allows elevators to be used for evacuation until they are recalled. Routing of elevators Cancel all pre-existing calls Respond only to hall calls at affected floors As the fire grows to include more floors, the zone of affected floors would also increase 106

132 Recommendations: Provide protected elevator lobbies Dynamic signage at elevator lobbies Early warning detection 2-hour fire rating for elevator power feeders Remote control operation of elevators for firefighter use (shuttle equipment, etc.) 107

133 Current Status: 108

134 Current Status: Proceeding at GLACIAL SPEED 108

135 A Edition (has been released) NFPA Edition (has been released) Elevator Use in Fires and Other Emergencies For Occupants For Firefighters Hazard Analysis almost finished NFPA and ICC jumping the gun NFPA 101 and IBC 109

136 NFPA First Responders Use Elevators The conditions monitored and displayed shall include, but are not limited to the following: (various temperatures, availability of emergency power, elevator location and status, etc.) The conditions shall be displayed on a standard emergency services interface complying with Section

137 NFPA Elevators for Occupant-Controlled Evacuation 21.6 talks about required status indicators (red and green) and signage for the use of these elevators, however this is really premature For instance, the current thinking of the task group is that these status indicators and signage will be provided by the elevator provider. 111

138 Response to current construction demand Different terms used occupant-controlled evacuation elevator evacuation operation occupant evacuation elevators NFPA 101 Annex B in mandatory language so can be adopted as needed Conference in Orlando, FL - 12/2010 Provide status report 112

139 113

140 Stay tuned! 113

141 Stay tuned! Questions? 113

142 Thank You for Attending: Interfacing Fire Alarm, Sprinkler and Elevator Systems Bruce Fraser Fraser Fire Protection Services Become an 114

Interfacing Elevators with Fire Alarm and Sprinklers

Interfacing Elevators with Fire Alarm and Sprinklers Interfacing Elevators with Fire Alarm and Sprinklers IEEE Atlanta Chapter May 15, 2006 Brian K Fabel, PE Agenda Today s Codes NFPA, ASME, IBC/IFC Conflicts/Issues Tomorrow s Codes? Applicable Codes NFPA

More information

rpsa FIRE PROTECTION ENGINEERS www.rpsa-fire.com

rpsa FIRE PROTECTION ENGINEERS www.rpsa-fire.com www.-fire.com R.P. SCHIFILITI ASSOCIATES, INC. P.O. Box 297 Reading, MA 01867-0497 USA 781.944.9300 Fax / Data 781.942.7500 Telephone Elevator Fire Safety: Elevator Recall and Elevator Power Shutdown Disclaimer:

More information

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:

More information

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 105.8a-6.1 TITLE: FIRE ALARM SYSTEM REQUIREMENTS SCOPE: This guideline

More information

Interfacing Fire Alarm Systems and Elevator Controls

Interfacing Fire Alarm Systems and Elevator Controls SUPPLEMENT 2 Interfacing Fire Alarm Systems and Elevator Controls Bruce Fraser SimplexGrinnell, L.P. Editor s Note: The relationship between fire alarm systems and elevator control systems, and how these

More information

Original Document 10/16/07 Revised 01/30/09 2 nd Revision 01-23-12 3 rd Revision- 12/18/14

Original Document 10/16/07 Revised 01/30/09 2 nd Revision 01-23-12 3 rd Revision- 12/18/14 North Collier Fire Control & Rescue District Greater Naples Fire Rescue District Immokalee Fire Control & Rescue District 2800 North Horseshoe Drive Naples, Florida 34104 SYSTEM REHABILITATION PLAN CHECKLIST

More information

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems

More information

CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002

CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002 CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002 Three new chapters were added. What was chapter 1 in 1999 was reorganized into chapters 1 (Fundamentals), 2 (Referenced Publications), and 3 (Definitions).

More information

Life Safety Code Enabling References

Life Safety Code Enabling References SUPPLEMENT 4 Life Safety Code Enabling References Editor s Note: Supplement 4 provides users of NFPA 72, National Fire Alarm and Signaling Code, with a summary of requirements from NFPA 101, Life Safety

More information

The Mission Critical Fire Protection Experts

The Mission Critical Fire Protection Experts The Mission Critical Fire Protection Experts Protection Systems Protection Systems HFC-227ea / FM200 / FE-227 FE-25 / ECARO-25 Novec 1230 Inergen / Argonite Halon Drop-in Systems High and Low Pressure

More information

FIRE-FIGHTING DESIGN BRIEF REPORT

FIRE-FIGHTING DESIGN BRIEF REPORT P a g e 1 SECTION 04 (Doc.No.A/DBR 001) FIRE-FIGHTING DESIGN BRIEF REPORT P a g e 2 1.0 SCOPE 2.0 STANDARDS AND CODES 3.0 TYPES OF SYSTEM PROPOSED 4.0 FIRE HYDRANT SYSTEM 5.0 AUTOMATIC SPRINKLER SYSTEM

More information

2012 Ontario Building Code Changes Affecting Fire Alarm Systems

2012 Ontario Building Code Changes Affecting Fire Alarm Systems 2012 Ontario Building Code Changes Affecting Fire Alarm Systems CFAA Annual Technical Seminar May 31, 2013 Ken Baird VP Systems www.lrifire.com LRI 2010 Developments in Life Safety Introduction Code Development

More information

Module 4, Lesson 12 Fire Alarm Systems

Module 4, Lesson 12 Fire Alarm Systems Student Manual Module 4, Lesson 12 Fire Alarm Systems Performance Objectives At the conclusion of this lesson, you will be able to: Identify the components and functions of a fire alarm system and determine

More information

CFAA NCR CHAPTER ANNUAL SENINAR. Commonly Overlooked Fire Alarm Requirements

CFAA NCR CHAPTER ANNUAL SENINAR. Commonly Overlooked Fire Alarm Requirements CFAA NCR CHAPTER ANNUAL SENINAR Commonly Overlooked Fire Alarm Requirements Introduction of Who I Am And My Experience (aka: only legitimate chance to catch a quick nap) Definitions ( if you nap during

More information

CBD-233. Fire Alarm and Detection Systems

CBD-233. Fire Alarm and Detection Systems Page 1 of 5 CBD-233. Fire Alarm and Detection Systems Originally published August 1984. R.H.L. McEwen Fire alarm systems are normally required by building codes. In the case of new buildings, this is usually

More information

NFPA 72. Exception No. 1: Where ambient conditions prohibit installation of automatic smoke detection, automatic heat detection shall be permitted.

NFPA 72. Exception No. 1: Where ambient conditions prohibit installation of automatic smoke detection, automatic heat detection shall be permitted. NFPA 72 3.3.7.2 3.3.7.2 False Alarm. Activation or reporting of an alarm for which no such alarm condition, fire or emergency actually exists. Additionally, False Alarm is the willful and knowing initiating

More information

Fire Alarm System Plans Review Checklist Property location Date of Review

Fire Alarm System Plans Review Checklist Property location Date of Review Fire Alarm System Plans Review Checklist Property location Date of Review 1. Is application completed in entirety? 2. Are the plans review fee submitted with the application? 3. Does floor plan include

More information

HERNANDO COUNTY FIRE ALARM GUIDELINES

HERNANDO COUNTY FIRE ALARM GUIDELINES HERNANDO COUNTY FIRE ALARM GUIDELINES To be used for all commercial building fire alarm system plan review. The procedures set forth in this document are the minimum requirements necessary to ensure a

More information

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

Rancho Cucamonga Fire Protection District Prevention Bureau Standard Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Revised: January 2014 INTENT The intent

More information

James R. Quiter, P.E., Senior Vice President Rolf Jensen & Associates, Inc.

James R. Quiter, P.E., Senior Vice President Rolf Jensen & Associates, Inc. AT THE STRATOSPHERE TOWER, LAS VEGAS NEVADA By: James R. Quiter, P.E., Senior Vice President Rolf Jensen & Associates, Inc. INTRODUCTION This paper discusses the performance based approach to fire protection

More information

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM 1. GENERAL 1.1. Related Documents: 1.2. Scope: 1.1.1. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements apply to the work specified in this

More information

2007 ICC FINAL ACTION AGENDA

2007 ICC FINAL ACTION AGENDA 907.2.1.1 System initiation in Group A occupancies with an occupant load of 1,000 or more. Activation of the fire alarm in Group A occupancies with an occupant load of 1,000 or more shall initiate a signal

More information

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting

More information

City of Bettendorf Fire Alarm System Requirements

City of Bettendorf Fire Alarm System Requirements City of Bettendorf Fire Alarm System Requirements Section 907 of the 2009 Edition of the International Fire Code (IFC) and Section 10-7-3 of the Municipal Code provide fire alarm requirements. IFC Section

More information

FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011

FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011 Office of the Fire Marshal 1.0 PERMITS FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011 1.1 To acquire an installation

More information

c. As mandated by law, facilities must obtain and maintain valid zoning permits as well as permits for intended use.

c. As mandated by law, facilities must obtain and maintain valid zoning permits as well as permits for intended use. Walmart Standards for Suppliers Section 7. Health and Safety 7. Health and Safety Suppliers must provide workers with a safe and healthy work environment. Suppliers must take proactive measures to prevent

More information

Mobile Fire Rescue Department Bureau of Fire Prevention

Mobile Fire Rescue Department Bureau of Fire Prevention 222 Mobile Fire Rescue Department Bureau of Fire Prevention Samuel L. Jones Mayor Stephen A. Dean Fire Chief February 2011 2009 International Fire Code Fire Alarm and Detection Systems 907.1 General. This

More information

CHAPTER 9 FIRE PROTECTION SYSTEMS

CHAPTER 9 FIRE PROTECTION SYSTEMS CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope. Provisions of this chapter shall govern the application, design, installation, testing and maintenance of automatic sprinklers, standpipes

More information

FIRE DETECTION AND ALARM

FIRE DETECTION AND ALARM Scope Provide a fire alarm system, or expand the existing system, as required by Code, the requirements in the Special Instructions to Designers (SID) of the Design Guidelines, and/or as noted in the Program

More information

DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION

DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION Phone System Owner Phone System Engineered by: of Record Drawings: of System Manuals: of Test Reports: System Installer 1. GENERAL INFORMATION Phone Delaware License No: Certificate Holder No. System Supplier

More information

2.4 Protected Elevators For Egress And Access During Fires In Tall Buildings

2.4 Protected Elevators For Egress And Access During Fires In Tall Buildings 2.4 Protected Elevators For Egress And Access During Fires In Tall Buildings Richard W. Bukowski, P.E., FSFPE NIST Building and Fire Research Laboratory The events of September 11, 2001 have generated

More information

FIRE ALARM SYSTEM RECORD OF COMPLETION

FIRE ALARM SYSTEM RECORD OF COMPLETION FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. Protected Property Information Name of property: Description

More information

Module 5. Fire and Emergency Alarm System Part I- Basics

Module 5. Fire and Emergency Alarm System Part I- Basics Module 5 Fire and Emergency Alarm System Part I- Basics 1 This module will describe: 1. Components and the arrangements of components in fire and emergency alarm systems. 2. How these systems work. 3.

More information

Bold items are particular to the City of Euless

Bold items are particular to the City of Euless EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 2/12 Fire Chief Wes Rhodes Fire Marshal Paul Smith EFD-FMO 3-2 2009 International Fire & Building Code as Amended NFPA Standards Adopted

More information

PLAN REVIEW GUIDE FOR FIRE ALARM

PLAN REVIEW GUIDE FOR FIRE ALARM PLAN REVIEW GUIDE FOR FIRE ALARM PROJECT NAME: PERMIT # PROJECT ADDRESS: CONTACT PERSON: PHONE Fire alarm system installation information shall be provided on the appropriate architectural and electrical

More information

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 PART 1 - GENERAL 1.01 WORK INCLUDED FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 A. Provide a complete fully addressable, power limited, fire detection and evacuation system. The system shall be connected

More information

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems Fire Alarm System Plans Submittal Guidelines For New and Existing Systems SCOPE The Temecula Fire Prevention Bureau (TFPB) has established the following requirements for the submittal of all fire alarms,

More information

Area of Rescue Assistance Communication System ADA Code Applicable excerpts:

Area of Rescue Assistance Communication System ADA Code Applicable excerpts: Area of Rescue Assistance Communication System ADA Code Applicable excerpts: CONTENTS (Guidelines and Definitions) Page 1 Area of Rescue Assistance Requirements Page 2 Emergency Communication Equipment

More information

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011, Updated March 2012 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or

More information

FIRE ALARM SYSTEM RECORD OF COMPLETION

FIRE ALARM SYSTEM RECORD OF COMPLETION FUNDAMENTALS OF FIRE ALARM SYSTEMS 72 33 FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. PROTECTED PROPERTY

More information

Overview of Hotel Fire Safety Requirements

Overview of Hotel Fire Safety Requirements Overview of Hotel Fire Safety Requirements in the Fire Code Susan Clarke, P.Eng. Office of the Fire Marshal - January 10, 2012 1 Agenda Regulation History - Hotels Fire Code Overview (Parts 1 to 8) Defined

More information

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Plan Review 2009 International Fire Code and NFPA 20 Date of Review / / BLD201 - Project Address: Project Name: Contractor s Business

More information

PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS

PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS January 1997 PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS 1.0 PERMIT 1.1 After receipt of a Building Permit from the City of San Jose Building Department, submit

More information

5-8.1.4* Any required illumination shall be arranged so that the failure of any single lighting unit shall not leave any area in darkness.

5-8.1.4* Any required illumination shall be arranged so that the failure of any single lighting unit shall not leave any area in darkness. NFPA 101 Life Safety Code Section 5-8 Illumination of Means of Egress 5-8.1 General. 5-8.1* Illumination of means of egress shall be provided in accordance with this section for every building and structure

More information

CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS

CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS PROPERTY ADDRESS (BRT Address Required) TESTING CONTRACTOR (Name and Address) License No. ANNUAL

More information

An inventory of hazardous materials used in your workplace will prove useful.

An inventory of hazardous materials used in your workplace will prove useful. Introduction Fire Protection is an organized approach designed to prevent fires. In the event of a fire, a fire protection program will help prevent or minimize personal injuries, losses, and harm to the

More information

Fire Pump Plan Review March 2010

Fire Pump Plan Review March 2010 Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:

More information

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS 527 CMR 31.00: CARBON MONOXIDE ALARMS Section 31.01: Purpose and Scope 31.02: Definitions 31.03: General Installation Provisions 31.04: Specific Installation Provisions 31.05: Carbon Monoxide Protection:

More information

B. NICET: National Institute for Certification in Engineering Technologies.

B. NICET: National Institute for Certification in Engineering Technologies. PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

More information

Construction Warehouse. Culminating Experience in Fire Protection Engineering FPE 596 Prepared by Ben Johnson

Construction Warehouse. Culminating Experience in Fire Protection Engineering FPE 596 Prepared by Ben Johnson Construction Warehouse Culminating Experience in Fire Protection Engineering FPE 596 Prepared by Ben Johnson Construction Warehouse Waste Treatment and Immobilization Plant (WTP) Project U.S. Department

More information

Errata has been identified as follows:

Errata has been identified as follows: 2009 IFC Performing Commercial Fire Inspections Inventory Number: 1424S09 Second Printing; July 2014 Changes HAVE been made- Third Printing: September 2014 Errata has been identified as follows: 1. Page

More information

FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION

FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION PERMITS AND INSPECTIONS FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION 911 Assigned PROJECT LOCATION Subdivision: Lot: Blk: Sec: PROJECT New Construction Addition/Remodel Demolition Other: Number

More information

MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS

MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS CHAPTER 93 MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS Note: Chapter 93 is entirely Seattle amendments to the International Fire Code and is not underlined. Point of Information The requirements of this

More information

FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION

FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. It shall be permitted to modify this

More information

SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS

SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS SECTION 16721 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire Alarm Control Panels B. Manual Fire Alarm Stations C. Automatic Smoke D. Fire Alarm Notification Appliances E. Auxiliary Fire Alarm Equipment

More information

Fire. The Fire Installers Mate. A guide to fire alarm systems design

Fire. The Fire Installers Mate. A guide to fire alarm systems design Fire The Fire Installers Mate A guide to fire alarm systems design BS 5839 Part 1:2002 A guide to BS 5839 Part 1:2002 Disclaimer This booklet is not intended to be a comprehensive guide to all aspects

More information

SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS

SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS I. APPLICATION AND DEFINITIONS 1.01 Authorization for Standards 1.02 Application of Standards 1.03 Definitions

More information

Decree of the Ministry of the Environment. on fire safety of garages

Decree of the Ministry of the Environment. on fire safety of garages E4 THE NATIONAL BUILDING CODE OF FINLAND Fire safety of garages Guidelines 2005 Decree of the Ministry of the Environment on fire safety of garages Adopted in Helsinki, 22 March 2005 Pursuant to the Decision

More information

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval. Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's

More information

Sprinkler and Fire Alarm Systems for the Building Official

Sprinkler and Fire Alarm Systems for the Building Official Sprinkler and for the Building Official Randall Kovacs, P.Eng., CP, FEC Gage-Babcock & Associates, Ltd. Topics Coordinated System Testing 1 Wet Dry Pre-action Deluge Wet System: Pipes filled with water

More information

Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems. April 2013

Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems. April 2013 Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems April 2013 The National Multi Housing Council and the National Apartment Association (NMHC/NAA) have

More information

EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM

EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29CFR1910.36-29CFR1910.38-29CFR1910.157-29CFR1910.165 NFPA-10 BASIS: The OSHA Emergency Action Planning and the

More information

Reference numbers following checklist statements represent an NFPA code section unless otherwise specified.

Reference numbers following checklist statements represent an NFPA code section unless otherwise specified. Fire Alarm System Plan Review Checklist 2010 OFC and 2007 NFPA 72 This checklist is for jurisdictions that permit the use of the 2007 NFPA 72 in lieu of IFC s referenced 2002 NFPA 72. Date of Review: Permit

More information

FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY

FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fire-alarm control unit. 2. Addressable interface

More information

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable

More information

BS5839 Part 1:2002 Overview

BS5839 Part 1:2002 Overview BS5839 Part 1:2002 Overview 1 Contents Introduction So why is the current standard being revised? The brief for the new standard Changes to structure of current Standard Enhanced certification of Fire

More information

Pollution CO CO 2. Carbonaceo us soot H 2 S, NOX, SO2

Pollution CO CO 2. Carbonaceo us soot H 2 S, NOX, SO2 Pollution CO CO 2 Carbonaceo us soot H 2 S, NOX, SO2 The National Building Code (NBC) contains set of minimum provisions, designed to protect the safety of the public with regard to structural sufficiency,

More information

Educational. Educational-Existing 1/28/2014. OCCUPANT LOADS [no change] Application. Application

Educational. Educational-Existing 1/28/2014. OCCUPANT LOADS [no change] Application. Application February 2014 Code Requirements and Inspections in Educational Occupancies Presented By: Barry W. Rickert Douglas M. Schanne Fire Marshal Training Program Supervisor Office of Education & Data Management

More information

Ammonia Detection System Codes and Design Specifications

Ammonia Detection System Codes and Design Specifications Ammonia Detection System Codes and Design Specifications December 28, 2015 Revision 5 920 N Trade Winds Pkwy Columbia, MO 65201 Ammonia detection system codes and design specifications Following is a discussion

More information

Building Codes Update: The 2009 International Fire Code and the Apartment Industry

Building Codes Update: The 2009 International Fire Code and the Apartment Industry ! Building Codes Update: The 2009 International Fire Code and the Apartment Industry Apartment operators and developers should be aware of organizational changes in the 2009 edition of the International

More information

University Design Standard. Fire Alarm Systems

University Design Standard. Fire Alarm Systems University Design Standard Fire Alarm Systems 1.0 Overview This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit

More information

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1 How to configure Part Numbers: Step : Select Switch Amperage Power Module Switch Rating (Amps) Power Module Switch Catalog No. 30 3 60 6 00 200 2 400 4 Step 2: Select Options Needed 5 Bussmann Power Module

More information

*.ppt 11/2/2009 12:48 PM 1

*.ppt 11/2/2009 12:48 PM 1 Digital Compressor Controller *.ppt 11/2/2009 12:48 PM 1 Copeland Scroll Digital Controller Simple Controller That Enables OEM s To Use Digital Scrolls Relieves OEM From Developing Special Controllers

More information

NATIONAL FIRE ALARM AND SIGNALING CODE

NATIONAL FIRE ALARM AND SIGNALING CODE GAP.11.1.1.0 A Publication of Global Asset Protection Services LLC NATIONAL FIRE ALARM AND SIGNALING CODE INTRODUCTION National Fire Protection Association (NFPA) documents describe a level of fire protection

More information

INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT

INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according

More information

1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri.

1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri. GENERAL: 1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri. 2. Fire alarm systems are Life Safety Systems

More information

FIRE ALARM PLAN REVIEW. Office of the State Fire Marshal Massachusetts Department of Fire Services December 2009

FIRE ALARM PLAN REVIEW. Office of the State Fire Marshal Massachusetts Department of Fire Services December 2009 FIRE ALARM PLAN REVIEW Office of the State Fire Marshal Massachusetts December 2009 SURPRISE QUIZ 1. A fire alarm system is required to be installed by the MSBC, what edition of NFPA 72 do you use? 2.

More information

Fire Alarm FAQs. Q: How many zone/circuit fire alarm panel do I need? Q: What candela strobes do I need?

Fire Alarm FAQs. Q: How many zone/circuit fire alarm panel do I need? Q: What candela strobes do I need? 5/2/2014 Fire Alarm FAQs Question Answer Q: How many zone/circuit fire alarm panel do I need? Q: What candela strobes do I need? A: The size of a fire alarm panel is determined by a number of factors,

More information

EMERGENCY LIGHTING AND CONTROL

EMERGENCY LIGHTING AND CONTROL I. Overview Emergency lighting control options are rapidly expanding in response to growing needs by design professionals and building owners to save energy and achieve aesthetic and functional design

More information

Understanding Emergency Power Off (EPO)

Understanding Emergency Power Off (EPO) Understanding Emergency Power Off (EPO) White Paper #22 Executive Summary Emergency Power Off (EPO) is the capability to power down a piece of electronic equipment or an entire installation from a single

More information

Maintaining Fire Protection Systems

Maintaining Fire Protection Systems Maintaining Fire Protection Systems Fire continues to be a major threat to your business and your personal safety. Each year several thousand people are injured or killed by fires and billions of dollars

More information

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Fire Alarm Systems Design. a guide to BS5839

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Fire Alarm Systems Design. a guide to BS5839 AVAILABLE TO DOWNLOAD ON THE APOLLO APP a guide to Fire Alarm Systems Design BS5839 Part1:2013 The Regulatory Reform (Fire Safety) Order (FSO) became law on 1 October 2006 Legally you must comply! What

More information

CITY AND COUNTY OF DENVER POLICY DENVER FIRE DEPARTMENT SUBMITTAL OF CONVEYANCE INSTALLATION/ALTERATION PLANS

CITY AND COUNTY OF DENVER POLICY DENVER FIRE DEPARTMENT SUBMITTAL OF CONVEYANCE INSTALLATION/ALTERATION PLANS Subject: SUBMITTAL OF CONVEYANCE INSTALLATION/ALTERATION PLANS Reference: Denver Fire Code Section 105.7.29 Approved: Joseph L. Gonzales, Division Chief, Fire Prevention Division Number: 105-1 Effective

More information

Inspection and Testing of Water-Based Systems

Inspection and Testing of Water-Based Systems Inspection and Testing of Water-Based Systems Standard Model/Computer-Based Testing Level III Content Outline The candidate for NICET certification at Level III in the Inspection and Testing of Water-Based

More information

FACILITY SAFETY SIGNAGE GUIDE: 10 SIGNS TO SPOT DURING A PLANT WALKTHROUGH

FACILITY SAFETY SIGNAGE GUIDE: 10 SIGNS TO SPOT DURING A PLANT WALKTHROUGH FACILITY SAFETY SIGNAGE GUIDE: 10 SIGNS TO SPOT DURING A PLANT WALKTHROUGH Safety signs are the primary way to communicate important warnings and messages to your employees, on-site contractors and other

More information

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011 FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or comments regarding the

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 21 22 13 - SAPPHIRE CLEAN-AGENT FIRE SUPPRESSION SYSTEM PART 1 GENERAL 1.1 RELATED DOCUMENTS A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and this Section

More information

Environment of Care Fire Safety Management Plan 2014

Environment of Care Fire Safety Management Plan 2014 Environment of Care Fire Safety Management Plan 2014 Updated 4.29.2014 PURPOSE The purpose of the Fire Safety Management Plan is to ensure that all facilities are designed, constructed, maintained, and

More information

Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007

Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007 Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007 FIRE ALARM SYSTEMS POLICY TELLURIDE FIRE PROTECTION DISTRICT TABLE OF CONTENTS FIRE ALARM PROTECTION POLICY PLAN REVIEW SUBMITTAL

More information

SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective

SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective The National Fire Alarm Code, NFPA 72, sets the minimum requirements of performance, selection, use and location of automatic detection

More information

BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS

BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS DCD-0304 Identification # Rev. 9/08 County Date of Inspection NAME OF OPERATION BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS ADDRESS TELEPHONE: CITY STATE ZIP BUILDING INSPECTORS CERTIFICATE

More information

Ch. 58 DIVISION D-O 34 CHAPTER 58. DIVISION D-O ORDINARY COMMERCIAL, INDUSTRIAL, OFFICE OCCUPANCY GROUP CONSTRUCTION TYPE MAXIMUM STORY HEIGHT

Ch. 58 DIVISION D-O 34 CHAPTER 58. DIVISION D-O ORDINARY COMMERCIAL, INDUSTRIAL, OFFICE OCCUPANCY GROUP CONSTRUCTION TYPE MAXIMUM STORY HEIGHT Ch. 58 DIVISION D-O 34 CHAPTER 58. DIVISION D-O ORDINARY COMMERCIAL, INDUSTRIAL, OFFICE Sec. 58.1. Division D-O occupancies. 58.2. Separation and mixed occupancy. OCCUPANCY GROUP CONSTRUCTION TYPE MAXIMUM

More information

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short

More information

MONTGOMERY COUNTY EXECUTIVE REGULATION Offices of the County Executive. 101 Monroe Street. Rockville, Maryland 20850

MONTGOMERY COUNTY EXECUTIVE REGULATION Offices of the County Executive. 101 Monroe Street. Rockville, Maryland 20850 Montgomery County Regulation on: ADOPTION OF THE 2008 NATIONAL ELECTRICAL CODE DEPARTMENT OF PERMITTING SERVICES Issued by County Executive Regulation # 15-09 Authority: Code Section 17-2 and 17-3 Supersedes:

More information

EXHIBIT A SCOPE OF WORK

EXHIBIT A SCOPE OF WORK EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,

More information

Spray Booth Guideline

Spray Booth Guideline Department of Development Service 135 North D Street, Perris CA. 92570 Phone: (951) 443-1029 Fax: (951) 943-3293 PURPOSE The intent of this guideline is to provide the information necessary to ensure that

More information

Important Ontario Fire Code Information for Building Owners in the City of Windsor

Important Ontario Fire Code Information for Building Owners in the City of Windsor Important Ontario Fire Code Information for Building Owners in the City of Windsor This information is intended to be used a reference only. For a complete listing consult the Ontario Fire Code or contact

More information

ENVIRONMENTAL HEALTH & SAFETY 6 East Dr., Amherst MA 01002-5000

ENVIRONMENTAL HEALTH & SAFETY 6 East Dr., Amherst MA 01002-5000 AMHERST COLLEGE ENVIRONMENTAL HEALTH & SAFETY 6 East Dr., Amherst MA 01002-5000 Michael Zlogar April 11, 2001 Assistant Fire Chief Amherst Fire Department 68 North Pleasant St. Amherst, MA 01004 FIRE ALARM

More information

COMMONWEALTH OF MASSACHUSETTS STATE BUILDING CODE 780 CMR, 6 th Edition FIRE PROTECTION SYSTEMS CHAPTER 9

COMMONWEALTH OF MASSACHUSETTS STATE BUILDING CODE 780 CMR, 6 th Edition FIRE PROTECTION SYSTEMS CHAPTER 9 COMMONWEALTH OF MASSACHUSETTS STATE BUILDING CODE 780 CMR, 6 th Edition FIRE PROTECTION SYSTEMS CHAPTER 9 GUIDELINES FOR THE PREPARATION OF FIRE PROTECTION SYSTEM NARRATIVE REPORTS 780 CMR 903.1.1 State

More information