1 Interfacing Elevators with Fire Alarm and Sprinklers IEEE Atlanta Chapter May 15, 2006 Brian K Fabel, PE
2 Agenda Today s Codes NFPA, ASME, IBC/IFC Conflicts/Issues Tomorrow s Codes?
3 Applicable Codes NFPA 1, 13, 70, 72 IFC Building Codes IBC, NFPA 101 Atlanta, Georgia Elevator & Escalator Safety Code ASME/ANSI A17.1
4 Problem! Can t find all the requirements in one place! Must use Codes together!
5 Bigger Problem! Codes are out of Synch! ASME A17.1 A A17.1a 1997 A17.1b 1998 A17.1c 1999 A17.1d 2000 A17.1a 2002 A17.1b 2003 A NFPA 13 &
6 ASME A17.1 Safety Code for Elevators and Escalators Provides Operational Sequences for: Phase 1 - Emergency Recall Operation Power Shutdown Shunt Trip Operation
7 ASME A17.1 Phase 1 - Emergency Recall Operation The Operation of an elevator wherein it is automatically or manually recalled to a specific landing and removed from normal service because of activation of firefighters service
8 ASME A17.1 Power Shutdown (Shunt Trip) Mainline elevator power is disconnected from the elevator to eliminate potential problems as a result of sprinkler actuation in the hoistway or elevator machine room
9 ASME A17.1 Added in 2004 Section Emergency Operation and Signaling Devices Phase 1 Emergency recall operation by fire alarm initiating devices
10 ASME A Section 2.8 Equipment in Hoistways, Machinery Spaces, Machine Room, Control Spaces and Control Rooms Shunt Trip/Power Disconnect Requirement
11 International Building Code Chapter 30 Elevators and Conveying Systems Section 3003 Emergency Operations Section 3006 Machine Rooms
12 International Fire Code Section 607 Elevator Recall and Maintenance Required.
13 NFPA Chapter 13 Fire Protection Systems 13.7 Detection Alarm & Communication Systems
14 NFPA Chapter 6 Protected Premises 6.15 Protected Premises Fire Safety Functions Elevator Recall for Fire Fighters Service Elevator Shutdown
15 NFPA Chapter 8 Installation Requirements 8.14 Special Situations Elevator Hoistway and Machine Rooms
16 Code of Ordinances, Atlanta ARTICLE C. ELECTRICITY* Sec Elevator code; adopted by reference.
17
18
19 ASME A In Jurisdiction not enforcing the NBCC, fire alarm initiating devices used to initiate Phase 1 Emergency Recall Operation shall be installed in conformance with the requirements of NFPA 72, and shall be located (a) At each floor served by the elevator; (b) in the associated elevator machine room; and (c) in the elevator hoistway, when sprinklers are located in those hoistways.
20 International Building Code Chapter 30 Elevators and Conveying Systems Section 3003 Emergency Operations Fire Fighter s emergency operation. Elevators shall be provided with Phase I emergency recall operation in accordance with ASME A17.1.
21 International Building Code Chapter 30 Elevators and Conveying Systems Section 3006 Machine Rooms Shunt Trip. Where elevator hoistways or elevator machine rooms containing elevator control equipment are protected with automatic sprinklers, a means installed in accordance with NFPA 72, Section , Elevator Shutdown, (now ) shall be provided to disconnect automatically the main line power supply to the affected elevator prior to the application of water. This means shall be self-resetting. The activation of sprinklers outside the hoistway or machine room shall not disconnect the main line power supply.
22 International Fire Code Section 607 Elevator Recall and Maintenance Required. Existing elevators with a travel distance of 25 feet or more above or below the main floor or other level of a building and intended to serve the needs of emergency personnel for fire-fighting or rescue purposes shall be provided with emergency operation in accordance with ASME A17.3. New elevators shall be provided with Phase I emergency recall operation and Phase II emergency in-car operation in accordance with ASME A17.1.
23 Code of Ordinances, Atlanta ARTICLE C. ELECTRICITY* Sec Elevator code; adopted by reference. CHAPTER IADMINISTRATIONSECTION 101 TITLE AND SCOPE, The provisions of this code shall apply to the construction, installation, alteration, repair, location, use, and maintenance of all new and existing elevators, escalators, manlifts, personnel hoists, and related equipment unless specifically exempted by statute or ordinance within the corporate limits of the City of Atlanta, Georgia.The scope of this code does not apply to Georgia laws regulating and licensing carnival rides (see title 34 of the Official Code of Georgia Annotated).This code is hereby declared to be remedial; other codes and ordinances affecting the construction installation, alteration, repair, location, use, and maintenance of elevators, escalators, manlifts, personnel hoists, and related equipment are as follows: (j) Georgia Fire Safety Law: For regulations governing means of egress and safety to life requirements, see the Georgia Fire Safety Law and the rules of the Georgia Safety Fire Commissioner pertaining thereto, Bureau of Buildings, Building Inspection Division.
24 NFPA NFPA Detection Alarm & Communication Systems * Elevator lobby, hoistway, and associated machine room smoke detectors used solely for elevator recall, and heat detectors used solely for elevator power shutdown, shall not be required to activate the building evacuation alarm if the power supply and installation wiring to such detectors are monitored by the building fire alarm system, and if the activation of such detectors initiates a supervisory signal at a constantly attended location.
25 NFPA Detection Alarm & Communication Systems Visible signals shall not be required in elevator cars The general evacuation signal shall not be required to operate in elevator cars.
26 NFPA Elevator Recall System-type smoke detectors or other automatic fire detection as permitted by located in elevator lobbies, elevator hoistways, and elevator machine rooms including machine space, control room and control space used to initiate fire fighters service recall shall be connected to the building fire alarm system.
27 NFPA Elevator Recall If ambient conditions prohibit installation of automatic smoke detection, other automatic fire detection shall be permitted.
28 NFPA Special Conditions * - Unless specifically designed and listed for the expected conditions, smoke detectors shall not be installed if any of the following ambient conditions exist: (1) Temperature below 0ºC (32 ºF) (2) Temperature above 38ºC (100 ºF) (3) Relative Humidity above 93 percent (4) Air velocity greater than 1.5 m/sec (300 ft/min)
29 NFPA Elevator Recall Smoke detectors shall not be installed in unsprinklered elevator hoistways unless they are installed to activate the elevator hoistway smoke relief equipment
30 NFPA Elevator Recall * - In facilities without a building fire alarm system, these smoke detectors shall be connected to a dedicated fire alarm system control unit that shall be designated as elevator recall control and supervisory panel permanently identified on the control unit and on the record drawings.
31 NFPA Elevator Recall Unless otherwise required by the authority having jurisdiction, only the elevator lobby, elevator hoistway, and the elevator machine room smoke detectors shall be used to recall elevators for firefighters service.
32 NFPA Elevator Recall * - A lobby smoke detector shall be located on the ceiling within 21 ft. of the centerline of each elevator door within the elevator bank under control of the detector. Exception; for lobby ceiling configurations exceeding 15 ft. in height or that are other than flat and smooth, detector locations shall be determined in accordance with Chapter 5.
33 Smoke Detector Location
34
35
36
37 NFPA Elevator Recall Actuation from elevator hoistway and elevator machine room smoke detectors shall cause separate and distinct visible annunciation at the control unit and required annunciators to alert fire fighters and other emergency personnel that the elevators are no longer safe to use.
38 ASME A Phase 1 Emergency Recall Operation by Fire Alarm Initiating Devices When activated, a fire alarm initiating device in the machine room shall cause the visual signal to illuminate intermittently only in car(s) with equipment in that machine room.
39 ASME A Phase 1 Emergency Recall Operation by Fire Alarm Initiating Devices When activated, a fire alarm initiating device in the machine room shall cause the visual signal to illuminate intermittently only in the car(s) with equipment in that machine room. When activated, a fire alarm initiating device in the hoistway shall cause the visual signal to illuminate intermittently only in car(s) with equipment in that hoistway.
40 ASME A Firefighters Emergency Operation Automatic Elevators FIG (h) Visual Signal
41 NFPA Elevator Recall * - For each group of elevators within a building, a minimum of three separate elevator control circuits shall be terminated at the designated elevator controller within the group s elevator machine room(s) the smoke detectors shall actuate the elevator control circuits as follows:
42 NFPA Elevator Recall * cont d (1) The smoke detector located in the designated elevator recall lobby shall actuate the first elevator control circuit. In addition, if the elevator is equipped with front and rear doors, or if the elevator machine room is located at the designated level, the required detectors shall actuate the first elevator control circuit. The detectors in both lobbies at the designated level shall actuate the first elevator control circuit.
43 NFPA Elevator Recall * cont d (2) The detectors in the remaining elevator lobbies shall actuate the second elevator control circuit. (3) The detectors in elevator hoistways and the elevator machine room(s) shall actuate the third elevator control circuit.
44
45
46 NFPA Protected Premises Fire Safety Functions A listed relay or other listed appliance connected to the fire alarm system used to initiate control of protected premises fire safety functions shall be located within 3 ft of the controlled circuit or appliance The relay or other appliance shall function within the voltage and current limitations of the fire alarm control unit.
47 NFPA Protected Premises Fire Safety Functions The installation wiring between the fire alarm control unit and the relay or other appliance shall be monitored for integrity. Exception: Relays or appliances that operate on loss of power shall be considered selfmonitoring for integrity.
48 Addressable Control Relays
49 Addressable Control Relays
50 NFPA Elevator Recall A It will be necessary sometimes to provide more than three (3) signals to the elevator controller. A17.1 requires differentiation between separate hoistways that share a common elevator machine room.
51 NFPA Elevator Recall A It will be necessary sometimes to provide more than three (3) signals to the elevator controller. A17.1 requires differentiation between separate hoistways that share a common elevator machine room. For instance, in a situation where there is more than one single hoistway sharing the same elevator machine room, a separate signal must be derived from each hoistway.
52
53
54
55 NFPA Elevator Hoistway and Machine Rooms * - Upright or pendent spray sprinklers shall be installed at the top of elevator hoistways The sprinkler required a the top of the elevator hoistway by shall not be required where the hoistway for passenger elevators is noncombustible and the car enclosure matierials meet the requirements of ASME A17.1.
56 NFPA Elevator Hoistway and Machine Rooms * - Sidewall spray sprinklers shall be installed at the bottom of each elevator hoistway not more than 2 ft above the floor of the pit The sprinkler required at the bottom of the elevator hoistway by shall not be required for enclosed, noncombustible elevator shafts that do not contain combustible hydraulic fluids.
57 ASME A Equipment in Hoistways and Machine Rooms means shall be provided to automatically disconnect the main line power supply to the affected elevator upon or prior to the application of water from the sprinklers located in the machine room or in the hoistway more than 24 in. above the pit floor.
58 NFPA Elevator Shutdown * - If pressure or waterflow switches are used to shut down elevator power immediately upon or prior to the discharge of water from sprinklers, the use of devices with time-delay switches or time-delay capability shall not be permitted.
59 NFPA Elevator Shutdown * - Where heat detectors are used to shut down elevator power prior to sprinkler operation, the detector shall have both a lower temperature rating and a higher sensitivity as compared to the sprinkler.
60 Recommendation- Use 165ºF, ordinary temperature rated sprinkler head Use 135 ºF, thermistor-type heat detector Or maintain similar relationship on ambient temperatures Note: Sprinklers in elevator machine rooms and hoistways must be of ordinary or intermediate temperature rating. (NFPA 13 (2002), )
61 NFPA Elevator Shutdown If heat detectors are used to shutdown elevator power prior to sprinkler operation, they shall be placed within 2 ft of each sprinkler head and be installed in accordance with the requirements of Chapter 5.
62 NFPA Elevator Shutdown If heat detectors are used to shutdown elevator power prior to sprinkler operation, they shall be placed within 2 ft of each sprinkler head and be installed in accordance with the requirements of Chapter 5. Alternatively, engineering methods, such as specified in Annex B shall be permitted to be used to select and place heat detectors to ensure response prior to any sprinkler head operation under a variety of fire growth scenarios.
63 NFPA Elevator Shutdown The initiating devices described in (WFS) and (HD) shall be monitored for integrity by the control unit required in Section
64 Background- Water from sprinklers in the hoistway and elevator machine room presents a hazard to safe elevator operation: Shorts on circuit conductors Uncontrolled elevator operation Wet brakes (traction elevators) Uncontrolled stopping
65
66 Shunt Trip Operation (theoretical) Smoke detector activates, causing elevator recall Elevators arrive at the recall floor and open doors Heat buildup causes heat detector to activate Shunt trip operates, removing power from elevator Sprinkler operates
67 Concern! Potential of passengers becoming entrapped in the elevator if a heat detector or waterflow switch actuates (to cause shunt trip ) prior to the completion of the recall function!
68 Sprinkler/Power Shutdown Concerns A17.1 Task Group addressed Shunt Trip and Sprinklers Risk Analysis was performed Concern of over-temperature of elevator controller Equipment stops Equipment runs erratically/uncontrollably Concern water from sprinklers may cause: Brake Failure Shorting out of an electrical safety or control circuit
69 Sprinkler/Power Shutdown Concerns A17.1 Task Group Recommendations: Exemption of sprinklers in elevator machine rooms If sprinklers are installed in elevator machine rooms, then the delay of the release of water from sprinklers will be required so recall can be completed first. The delay strategy Consideration of Earthquake Mode strategy Stop at next floor
70 NFPA Elevator Shutdown A Upon activation of the heat detector used for elevator power shut down, there should be a delay in the activation of the power shunt trip.
71 NFPA Elevator Shutdown A Upon activation of the heat detector used for elevator power shut down, there should be a delay in the activation of the power shunt trip. This delay should be the time that it takes the elevator cab to travel from the top of the hoistway to the lowest recall level.
72
73
74 NFPA Elevator Shutdown * - Control circuits to shut down elevator power shall be monitored for presence of operating voltage. The loss of voltage to the control circuit for disconnecting means shall cause a supervisory signal to be indicated at the control unit and required remote annunciators.
75
76 THANK YOU!?QUESTIONS?
rpsa FIRE PROTECTION ENGINEERS www.rpsa-fire.com
www.-fire.com R.P. SCHIFILITI ASSOCIATES, INC. P.O. Box 297 Reading, MA 01867-0497 USA 781.944.9300 Fax / Data 781.942.7500 Telephone Elevator Fire Safety: Elevator Recall and Elevator Power Shutdown Disclaimer:
FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL
FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems
Interfacing Fire Alarm Systems and Elevator Controls
SUPPLEMENT 2 Interfacing Fire Alarm Systems and Elevator Controls Bruce Fraser SimplexGrinnell, L.P. Editor s Note: The relationship between fire alarm systems and elevator control systems, and how these
CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services
CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 105.8a-6.1 TITLE: FIRE ALARM SYSTEM REQUIREMENTS SCOPE: This guideline
Original Document 10/16/07 Revised 01/30/09 2 nd Revision 01-23-12 3 rd Revision- 12/18/14
North Collier Fire Control & Rescue District Greater Naples Fire Rescue District Immokalee Fire Control & Rescue District 2800 North Horseshoe Drive Naples, Florida 34104 SYSTEM REHABILITATION PLAN CHECKLIST
Life Safety Code Enabling References
SUPPLEMENT 4 Life Safety Code Enabling References Editor s Note: Supplement 4 provides users of NFPA 72, National Fire Alarm and Signaling Code, with a summary of requirements from NFPA 101, Life Safety
Module 4, Lesson 12 Fire Alarm Systems
Student Manual Module 4, Lesson 12 Fire Alarm Systems Performance Objectives At the conclusion of this lesson, you will be able to: Identify the components and functions of a fire alarm system and determine
FIRE ALARM SYSTEM RECORD OF COMPLETION
FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. Protected Property Information Name of property: Description
FIRE ALARM SYSTEM RECORD OF COMPLETION
FUNDAMENTALS OF FIRE ALARM SYSTEMS 72 33 FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. PROTECTED PROPERTY
B. NICET: National Institute for Certification in Engineering Technologies.
PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION
Phone System Owner Phone System Engineered by: of Record Drawings: of System Manuals: of Test Reports: System Installer 1. GENERAL INFORMATION Phone Delaware License No: Certificate Holder No. System Supplier
CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS
CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS PROPERTY ADDRESS (BRT Address Required) TESTING CONTRACTOR (Name and Address) License No. ANNUAL
PLAN REVIEW GUIDE FOR FIRE ALARM
PLAN REVIEW GUIDE FOR FIRE ALARM PROJECT NAME: PERMIT # PROJECT ADDRESS: CONTACT PERSON: PHONE Fire alarm system installation information shall be provided on the appropriate architectural and electrical
SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS
SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS I. APPLICATION AND DEFINITIONS 1.01 Authorization for Standards 1.02 Application of Standards 1.03 Definitions
Mobile Fire Rescue Department Bureau of Fire Prevention
222 Mobile Fire Rescue Department Bureau of Fire Prevention Samuel L. Jones Mayor Stephen A. Dean Fire Chief February 2011 2009 International Fire Code Fire Alarm and Detection Systems 907.1 General. This
2007 ICC FINAL ACTION AGENDA
907.2.1.1 System initiation in Group A occupancies with an occupant load of 1,000 or more. Activation of the fire alarm in Group A occupancies with an occupant load of 1,000 or more shall initiate a signal
FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION
FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. It shall be permitted to modify this
Rancho Cucamonga Fire Protection District Prevention Bureau Standard
Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Revised: January 2014 INTENT The intent
The Mission Critical Fire Protection Experts
The Mission Critical Fire Protection Experts Protection Systems Protection Systems HFC-227ea / FM200 / FE-227 FE-25 / ECARO-25 Novec 1230 Inergen / Argonite Halon Drop-in Systems High and Low Pressure
2.4 Protected Elevators For Egress And Access During Fires In Tall Buildings
2.4 Protected Elevators For Egress And Access During Fires In Tall Buildings Richard W. Bukowski, P.E., FSFPE NIST Building and Fire Research Laboratory The events of September 11, 2001 have generated
HERNANDO COUNTY FIRE ALARM GUIDELINES
HERNANDO COUNTY FIRE ALARM GUIDELINES To be used for all commercial building fire alarm system plan review. The procedures set forth in this document are the minimum requirements necessary to ensure a
SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines
PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting
NFPA 72. Exception No. 1: Where ambient conditions prohibit installation of automatic smoke detection, automatic heat detection shall be permitted.
NFPA 72 3.3.7.2 3.3.7.2 False Alarm. Activation or reporting of an alarm for which no such alarm condition, fire or emergency actually exists. Additionally, False Alarm is the willful and knowing initiating
FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY
FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fire-alarm control unit. 2. Addressable interface
FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011
Office of the Fire Marshal 1.0 PERMITS FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011 1.1 To acquire an installation
SECTION 16721 FIRE ALARM AND DETECTION SYSTEM
1. GENERAL 1.1. Related Documents: 1.2. Scope: 1.1.1. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements apply to the work specified in this
Reference numbers following checklist statements represent an NFPA code section unless otherwise specified.
Fire Alarm System Plan Review Checklist 2010 OFC and 2007 NFPA 72 This checklist is for jurisdictions that permit the use of the 2007 NFPA 72 in lieu of IFC s referenced 2002 NFPA 72. Date of Review: Permit
City of Bettendorf Fire Alarm System Requirements
City of Bettendorf Fire Alarm System Requirements Section 907 of the 2009 Edition of the International Fire Code (IFC) and Section 10-7-3 of the Municipal Code provide fire alarm requirements. IFC Section
FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION
PERMITS AND INSPECTIONS FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION 911 Assigned PROJECT LOCATION Subdivision: Lot: Blk: Sec: PROJECT New Construction Addition/Remodel Demolition Other: Number
Finance and Administration Department 907 Billy Mitchell Blvd. P: (210) 228-1022 Fire Alarm Permit Application
PERMIT FEE: $ Finance and Administration Department 907 Billy Mitchell Blvd. P: (210) 228-1022 Fire Alarm Permit Application PAYMENT TYPE: Check Credit Card Charge to Job #: (Please complete all of the
FIRE ALARM APPLICATION
FIRE ALARM APPLICATION ENUMCLAW FIRE DEPARTMENT 1330 Wells St, Enumclaw, WA 98022 Phone: 360-825-5544 Fax: 360-825-9442 COMMUNITY DEVELOPMENT, BUILDING DEPARTMENT 1309 Myrtle Ave Enumclaw WA 98022 Phone:
EXETER TOWNSHIP DRY OR WET CHEMICAL FIRE SUPPRESSION SYSTEMS
DRY OR WET CHEMICAL FIRE SUPPRESSION SYSTEMS POLICY STATEMENT This policy applies to NEW Dry or Wet chemical fire suppression systems. The Authority Having Jurisdiction will not waive major criteria in
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according
Module 5. Fire and Emergency Alarm System Part I- Basics
Module 5 Fire and Emergency Alarm System Part I- Basics 1 This module will describe: 1. Components and the arrangements of components in fire and emergency alarm systems. 2. How these systems work. 3.
CHAPTER 8. Village of Caledonia Alarm Systems Ordinance (2013-11 07/01/13)
CHAPTER 8 Village of Caledonia Alarm Systems Ordinance (2013-11 07/01/13) Section Title Number 5-8-1 Title 5-8-2 Declaration of Purpose 5-8-3 Definitions 5-8-4 Administrative Rules 5-8-5 Supervised Fire
Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems. April 2013
Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems April 2013 The National Multi Housing Council and the National Apartment Association (NMHC/NAA) have
CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002
CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002 Three new chapters were added. What was chapter 1 in 1999 was reorganized into chapters 1 (Fundamentals), 2 (Referenced Publications), and 3 (Definitions).
Fire Alarm System Plans Review Checklist Property location Date of Review
Fire Alarm System Plans Review Checklist Property location Date of Review 1. Is application completed in entirety? 2. Are the plans review fee submitted with the application? 3. Does floor plan include
Bold items are particular to the City of Euless
EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 2/12 Fire Chief Wes Rhodes Fire Marshal Paul Smith EFD-FMO 3-2 2009 International Fire & Building Code as Amended NFPA Standards Adopted
FIRE DETECTION AND ALARM
Scope Provide a fire alarm system, or expand the existing system, as required by Code, the requirements in the Special Instructions to Designers (SID) of the Design Guidelines, and/or as noted in the Program
FIRE ALARM PLAN REVIEW. Office of the State Fire Marshal Massachusetts Department of Fire Services December 2009
FIRE ALARM PLAN REVIEW Office of the State Fire Marshal Massachusetts December 2009 SURPRISE QUIZ 1. A fire alarm system is required to be installed by the MSBC, what edition of NFPA 72 do you use? 2.
Construction Warehouse. Culminating Experience in Fire Protection Engineering FPE 596 Prepared by Ben Johnson
Construction Warehouse Culminating Experience in Fire Protection Engineering FPE 596 Prepared by Ben Johnson Construction Warehouse Waste Treatment and Immobilization Plant (WTP) Project U.S. Department
Errata has been identified as follows:
2009 IFC Performing Commercial Fire Inspections Inventory Number: 1424S09 Second Printing; July 2014 Changes HAVE been made- Third Printing: September 2014 Errata has been identified as follows: 1. Page
Fire Alarm System Plans Submittal Guidelines For New and Existing Systems
Fire Alarm System Plans Submittal Guidelines For New and Existing Systems SCOPE The Temecula Fire Prevention Bureau (TFPB) has established the following requirements for the submittal of all fire alarms,
Area of Rescue Assistance Communication System ADA Code Applicable excerpts:
Area of Rescue Assistance Communication System ADA Code Applicable excerpts: CONTENTS (Guidelines and Definitions) Page 1 Area of Rescue Assistance Requirements Page 2 Emergency Communication Equipment
EXHIBIT A SCOPE OF WORK
EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,
CFAA NCR CHAPTER ANNUAL SENINAR. Commonly Overlooked Fire Alarm Requirements
CFAA NCR CHAPTER ANNUAL SENINAR Commonly Overlooked Fire Alarm Requirements Introduction of Who I Am And My Experience (aka: only legitimate chance to catch a quick nap) Definitions ( if you nap during
Michael Catalano 24 Nassau Avenue, Islip NY 11751 Phone (631) 224-5477 Chief Fire Marshal [email protected] Fax (631) 224-5458
OFFICE OF THE FIRE MARSHAL BUREAU OF FIRE PREVENTION Michael Catalano, Phone Chief Fire Marshal [email protected] Fax To whom it may concern: Enclosed please find the NFPA 72 forms needed for
CBD-233. Fire Alarm and Detection Systems
Page 1 of 5 CBD-233. Fire Alarm and Detection Systems Originally published August 1984. R.H.L. McEwen Fire alarm systems are normally required by building codes. In the case of new buildings, this is usually
Sam Docknevich, PSP, Security Service Portfolio Manager. Are You Prepared? The impending impact of Code on Servicing Security Systems
Sam Docknevich, PSP, Security Service Portfolio Manager Are You Prepared? The impending impact of Code on Servicing Security Systems usa.siemens.com/infrastructure-cities Share current and upcoming standards
The Jefferson County Board of Supervisors does ordain as follows:
ORDINANCE NO. 18 The Jefferson County Board of Supervisors does ordain as follows: 18.01 TITLE. This ordinance shall be known as the Jefferson County Alarm Systems Ordinance. 18.02 DECLARATION OF PURPOSE.
Fire Alarm Systems Permit Packet. City of Greer Fire Department
Fire Alarm Systems Permit Packet City of Greer Fire Department Updated July 2004 If you have any questions or comments regarding the information contained within; or of you need assistance interpreting
FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual
FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual P/N 315-049403-1 Siemens Building Technologies Fire Safety Table Of Contents Introduction...1 The Access levels...1 User Level...1 Maintenance
AETNA FIRE ALARM SERVICE CO., INC.
FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM INSPECTION AND TESTING FORM To be completed by the system inspector or tester at the inspection or test. It shall be permitted to modify this form as needed
FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM INSPECTION AND TESTING FORM
FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM INSPECTION AND TESTING FORM To be completed by the system inspector or tester at the time of the inspection or test. It shall be permitted to modify this form
2012 Ontario Building Code Changes Affecting Fire Alarm Systems
2012 Ontario Building Code Changes Affecting Fire Alarm Systems CFAA Annual Technical Seminar May 31, 2013 Ken Baird VP Systems www.lrifire.com LRI 2010 Developments in Life Safety Introduction Code Development
CHAPTER 9 FIRE PROTECTION SYSTEMS
CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope. Provisions of this chapter shall govern the application, design, installation, testing and maintenance of automatic sprinklers, standpipes
SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS
SECTION 16721 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire Alarm Control Panels B. Manual Fire Alarm Stations C. Automatic Smoke D. Fire Alarm Notification Appliances E. Auxiliary Fire Alarm Equipment
University of Houston Master Construction Specifications Insert Project Name
SECTION 21 22 13 - SAPPHIRE CLEAN-AGENT FIRE SUPPRESSION SYSTEM PART 1 GENERAL 1.1 RELATED DOCUMENTS A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and this Section
FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST
FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST Date of Inspection: Conducted by: Location: Reviewed by: Date of Review: Comments or additional corrective action taken as a result
CITY AND COUNTY OF DENVER POLICY DENVER FIRE DEPARTMENT SUBMITTAL OF CONVEYANCE INSTALLATION/ALTERATION PLANS
Subject: SUBMITTAL OF CONVEYANCE INSTALLATION/ALTERATION PLANS Reference: Denver Fire Code Section 105.7.29 Approved: Joseph L. Gonzales, Division Chief, Fire Prevention Division Number: 105-1 Effective
1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri.
GENERAL: 1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri. 2. Fire alarm systems are Life Safety Systems
Elevating and Amusement Devices Safety Division Elevating Devices Code Adoption Document - Amendment
Elevating and Amusement Devices Safety Division Elevating Devices Code Adoption Document - Amendment Ref. No.: Date: Rev. No.: 261-13 1 May 1, 2013 Date: September 15, 2013 IN THE MATTER OF: Technical
TESTING, INSPECTION, AND MAINTENANCE FREQUENCIES FOR FIRE DETECTION AND ALARM SYSTEMS
TESTING, INSPECTION, AND MAINTENANCE FREQUENCIES FOR FIRE DETECTION AND ALARM SYSTEMS The following information regarding testing frequencies for fire detection and alarm systems. All of the following
Sprinkler and Fire Alarm Systems for the Building Official
Sprinkler and for the Building Official Randall Kovacs, P.Eng., CP, FEC Gage-Babcock & Associates, Ltd. Topics Coordinated System Testing 1 Wet Dry Pre-action Deluge Wet System: Pipes filled with water
FIRE-FIGHTING DESIGN BRIEF REPORT
P a g e 1 SECTION 04 (Doc.No.A/DBR 001) FIRE-FIGHTING DESIGN BRIEF REPORT P a g e 2 1.0 SCOPE 2.0 STANDARDS AND CODES 3.0 TYPES OF SYSTEM PROPOSED 4.0 FIRE HYDRANT SYSTEM 5.0 AUTOMATIC SPRINKLER SYSTEM
Understanding Fire Alarm Requirements & Inspections. Presented By Bill Conroy Technical Sales For Briscoe Protective Systems Inc
Understanding Fire Alarm Requirements & Inspections Presented By Bill Conroy Technical Sales For Briscoe Protective Systems Inc Introduction Fire Alarm Requirements are structured through a system of codes.
SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective
SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective The National Fire Alarm Code, NFPA 72, sets the minimum requirements of performance, selection, use and location of automatic detection
Fire Pump Plan Review March 2010
Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:
FIRE ALARM AND DETECTION SYSTEMS SECTION 16721
PART 1 - GENERAL 1.01 WORK INCLUDED FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 A. Provide a complete fully addressable, power limited, fire detection and evacuation system. The system shall be connected
CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES
CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES Review the following information pertaining to Construction Fire Safety Planning: B.C. Building Code Sections 8.1 up to and including Subsection 8.2.3 B.C.
PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS
January 1997 PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS 1.0 PERMIT 1.1 After receipt of a Building Permit from the City of San Jose Building Department, submit
c. As mandated by law, facilities must obtain and maintain valid zoning permits as well as permits for intended use.
Walmart Standards for Suppliers Section 7. Health and Safety 7. Health and Safety Suppliers must provide workers with a safe and healthy work environment. Suppliers must take proactive measures to prevent
University Design Standard. Fire Alarm Systems
University Design Standard Fire Alarm Systems 1.0 Overview This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit
Fire Alarm Log Book. Any activity regarding this system must be documented in writing.
CASTLE ROCK FIRE AND RESCUE DEPARTMENT 300 Perry Street Castle Rock, Colo. 80104 303-660-1066 Do not remove from the premises: Fire Alarm Log Book Any activity regarding this system must be documented
Building Codes Update: The 2009 International Fire Code and the Apartment Industry
! Building Codes Update: The 2009 International Fire Code and the Apartment Industry Apartment operators and developers should be aware of organizational changes in the 2009 edition of the International
MODIFIED INDUSTRY STANDARDS FOR ELEVATORS AND CONVEYING SYSTEMS
MODIFIED INDUSTRY STANDARDS FOR ELEVATORS AND CONVEYING SYSTEMS CHAPTER K1 MODIFICATIONS TO ASME A17.1-2000, SAFETY CODE FOR ELEVATORS AND ESCALATORS K101.1 General. As referenced by Chapter 30 of the
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Plan Review 2009 International Fire Code and NFPA 20 Date of Review / / BLD201 - Project Address: Project Name: Contractor s Business
Fire Alarm FAQs. Q: How many zone/circuit fire alarm panel do I need? Q: What candela strobes do I need?
5/2/2014 Fire Alarm FAQs Question Answer Q: How many zone/circuit fire alarm panel do I need? Q: What candela strobes do I need? A: The size of a fire alarm panel is determined by a number of factors,
Danville, IN Code of Ordinances CHAPTER 90: ALARM SYSTEMS, SMOKE DETECTORS AND THE LIKE. Alarm Systems. Smoke Detectors. Key and Data Storage Boxes
Danville, IN Code of Ordinances CHAPTER 90: ALARM SYSTEMS, SMOKE DETECTORS AND THE LIKE Section Alarm Systems 90.01 Purpose 90.02 Definitions 90.03 Exemptions 90.04 Registration 90.05 Violations; fines
MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS
CHAPTER 93 MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS Note: Chapter 93 is entirely Seattle amendments to the International Fire Code and is not underlined. Point of Information The requirements of this
NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems
NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems 1.0 Purpose A. The following guideline provides the minimum standards and requirements for fire alarm systems. 2.0
527 CMR: BOARD OF FIRE PREVENTION REGULATIONS
527 CMR 24.00: FIRE WARNING SYSTEMS INSTALLED IN BUILDINGS WITHIN THE COMMONWEALTH OF MASSACHUSETTS Section 24.01: Purpose 24.02: Scope 24.03: Definitions 24.04: Approval of Design 24.05: Power Supply
ENGINEERING SPECIFICATIONS
ENGINEERING SPECIFICATIONS FM-200 CLEAN-AGENT FIRE SUPPRESSION SYSTEM with PYRO-CHEM DETECTION/RELEASE SYSTEM March 2001 SECTION 1 - GENERAL I. SCOPE This specification outlines the requirements for a
ENGINEERING SPECIFICATION. Engineering Specification SAPPHIRE 42 Bar
Engineering Specification SAPPHIRE 42 Bar PART 1 GENERAL 1.1 DESCRIPTION OF WORK This specification outlines the requirements for a "Total Flood" SAPPHIRE Clean Agent Fire Suppression System. The work
NATIONAL FIRE ALARM AND SIGNALING CODE
GAP.11.1.1.0 A Publication of Global Asset Protection Services LLC NATIONAL FIRE ALARM AND SIGNALING CODE INTRODUCTION National Fire Protection Association (NFPA) documents describe a level of fire protection
Chapter 9 Fire Protection Systems
Chapter 9 Fire Protection Systems 1 Introduction Keith Glaunert, P.E. (262) 548-8604 8604 [email protected] Lynne LeCount (262) 262-8621 [email protected] Mark Gardetto (262)523-3044 3044 [email protected]
Proposed Residential Complex At Holding No. - 98, B.T. Road, Kolkata - 700090 Developer Premier Mica Mining And Manufacturing Company
RISK MANAGEMENT PLAN is an integral part of a modernized and sophisticated residential complex. No efforts will be spared in identifying the all possible risks and disasters, evaluating them, installing
Educational. Educational-Existing 1/28/2014. OCCUPANT LOADS [no change] Application. Application
February 2014 Code Requirements and Inspections in Educational Occupancies Presented By: Barry W. Rickert Douglas M. Schanne Fire Marshal Training Program Supervisor Office of Education & Data Management
FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.
Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's
COMMISSIONING OF FIRE ALARM SYSTEMS
COMMISSIONING OF FIRE ALARM SYSTEMS OWNER FURNISHED The owner directly contracts an independent third party commissioning agent for this project. This Commissioning Plan has been included for reference
Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007
Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007 FIRE ALARM SYSTEMS POLICY TELLURIDE FIRE PROTECTION DISTRICT TABLE OF CONTENTS FIRE ALARM PROTECTION POLICY PLAN REVIEW SUBMITTAL
Agenda. Agenda (continued) Fundamentals of Fire Alarm Systems
Fundamentals of Fire Alarm Systems Sponsored by UL SFPE Austin/San Antonio Chapter San Marcos, Texas 7 January 2015 Agenda Introduction and Administration Historical Context of Today s NFPA 72 Fire Alarm
527 CMR: BOARD OF FIRE PREVENTION REGULATIONS
527 CMR 31.00: CARBON MONOXIDE ALARMS Section 31.01: Purpose and Scope 31.02: Definitions 31.03: General Installation Provisions 31.04: Specific Installation Provisions 31.05: Carbon Monoxide Protection:
Winnipeg Fire Department Fire Prevention Branch
Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of