AQUACIAT. Inverter Heat pump. Use. Range
|
|
- Stanley Glenn
- 7 years ago
- Views:
Transcription
1 High energy efficiency with the R410A Compact and silent Scroll compressors technology High performance brazed-plate heat exchangers Self-adjusting electronic control Cooling capacity: 40 to 50 kw Heating capacity: 45 to 50 kw Cooling and heating Hydraulic module Heat recovery ENVIRNMENTALLY HFC R410A PRTECTIN DE FRIENDLY L'ENVIRNNEMENT Use The IVDC series packaged water chillers or heaters are medium-capacity units specifically designed for heating and air conditioning applications in ffices, Healthcare, Administration, Shopping Centres and the Residential sector. These standard packaged units are designed for outdoor installation and require no special protection against adverse weather conditions. To operate in HEATING or CLING mode, they use the outdoor air as the only external source; this permits the evacuation of heat in summer or the supply of thermal energy for heating in winter. Connected to an underfloor heating or cooling system, fan coil units or an air handling unit, the reversible GRAND INVERTER IVDC series is an extremely easy way to heat and air condition buildings. Each unit is delivered fully assembled, wired (control and power), charged with refrigerant and factory tested. Simply make the necessary electrical and hydraulic connections, and your unit is ready to operate. Range IVDC series Reversible Air/Water modules with hydraulic system (circulation pump). HEAT PUMPS- AIR CNDITINING - REFRIGERATIN - AIR HANDLING - HEAT EXCHANGE - NA C 1
2 Description The IVDC series is supplied as standard with the following components: - air-source condenser with axial fan motor inverter and variable speed inverter, - high efficiency brazed-plate heat exchangers, - chilled water or hot water capacity control, - control, automatic operation and startup box:. Electrical supply: Three-phase 50 Hz V (+6%/-10%) + Earth. Control circuit: Single-phase 50 Hz V (transformers fitted on unit as standard), - casing for outdoor installation. n Complies with European directives (EC): - Machinery directive (98/37/EC) - EMC directive (2004/108 EC) - Pressure equipment directive (97/23/EC, category 2) - Low voltage (2006/95/EC) n Compliance with standards - EN 60204, EN (NFC , France) Standard and ptional Equipment IVDC Power supply: 400 V, 3-Phase, 50 Hz, without neutral, with transformer Coil protection screen Resilient mounts Main disconnect switch Water flow regulator Phase monitor (reversal, loss, over- and undervoltage) Soft start Variable-speed condenser fan Connection frame/duct (XTRAFAN) Sleeve + connection duct/duct (XTRAFAN) 800 micron water filter All-season operation (-20 C) Remote control Additional voltage-free contacts board LNWRKS Protocol MULTICNNECT multiple unit management Partial heat recovery - desuperheater Frost protection BLYGLD coated coil Polyurethane coated coil fins Hydraulic control kit (manifold, control & shut-off valve) Hydraulic hoses Double pump / kw electric auxiliary heater kit è kw electric auxiliary heater module kit / 200 External auxiliary heating management (4-stage) : Supplied as standard : ption Note: Some technical options not listed above may be added on special request (please contact us). 4 HEAT PUMPS- AIR CNDITINING - REFRIGERATIN - AIR HANDLING - HEAT EXCHANGE - NA C
3 Technical data - Reversible heat pumps IVDC 150 V 200 V Net cooling capacity (1) kw 36,77 47,32 Net power input kw 13,86 18,01 Energy efficiency rating (EER) 2,65 2,62 Seasonal energy efficiency rating (ESEER) 3,81 3,72 Lw/Lp (3) (HP high performance version) db(a) 78,5 / 46,5 75,9 / 43,9 Lw/Lp (3) (HT high temperature version) db(a) 86,3 / 54,3 86,3 / 54,3 Net heating capacity (1) kw 41,24 53,49 Net power input kw 13,92 16,73 CP/CP performances 2,96 3,19 Compressor hermetic SCRLL Start-up mode Direct using Soft Starter Number 1 Power control % Variable from 33 to 100% Refrigerant oil type Polyester PE 160 SZ il capacity l No. of refrigerant circuits 1 Refrigerant (GWP) kw eq. C2 R410A (1720) Refrigerant load kg Electrical supply ph/hz/v Three-phase 50 Hz 400 V (+6%/-10%) + Earth Machine protection rating IP 44 Control circuit voltage ph/hz/v Single-phase 50 Hz 230 V (+6%/-10%) - transformer fitted Evaporator Brazed plate exchanger(s) Water capacity l Chilled water outlet temp. (min./max.) C -10 / +15 Hot water outlet temp. (min./max.) C +30 / +55 Minimum water flow rate m 3 /h Maximum water flow rate m 3 /h Water connections Ø 1 ½ M 2 M Max. pressure. water end bar IVDC 4 bar Air-cooled condenser Finned heat exchanger Fan Ø mm 800 HP High Performance Version- No. x motor capacity no. x kw 1 x x HP High Performance Version - Air flow rate m 3 /h HP High Performance Version - Rotational speed rpm HT High Temperature Version- No. x motor capacity no. x kw 1 x x HT High Temperature Version - Air flow rate m 3 /h HT High Temperature version - Rotational speed rpm Min. water volume (IVDC) l Expansion vessel C l 6 12 Maximum capacity of system in litres (4) Pure water Maximum capacity of system in litres (4) Glycol/water mix max. water 36 C (5) max. water 46 C (5) max. water 36 C (5) max. water 46 C (5) Standard pump Qty Height (excluding mounts) mm Length (IVDC) mm 1995 Depth mm 1055 Weight (empty) kg Storage temperature C +50 C (1) HP High Performance version capacities based on: a/ CLING: +12 C/+7 C and condenser air inlet temperature of +35 C at nominal air flow b/ HEATING: hot water outlet at +45 C and external air at +7 C DB, 86% RH (EN and EURVENT conditions) (2) Net EER/CP values (3) Lw: verall sound power level as per IS3744 Lp: verall pressure levels measured at 10m in a free field, calculated using the formula LP=Lw-10 log S(4) System capacity depending on expansion vessel fitted on unit (5) Water temperatures given are those which can be reached when the machine is off HEAT PUMPS- AIR CNDITINING - REFRIGERATIN - AIR HANDLING - HEAT EXCHANGE - NA C 5
4 Main components n Casing - Removable galvanised metal panels, - RAL 7024 and RAL 7035 lacquer coating n Hermetic SCRLL compressors - Built-in electric motor cooled by suction gases - Motor protected by internal winding thermostat - Placed on anti-vibration mounts - Continuously variable power from 33 to 100% n Evaporator - Brazed plate exchanger(s) - End and inside plates in AISI 316 stainless steel - High performance, optimised plate patterns - Thermal insulation n Condenser - High efficiency air-cooled exchanger, aluminium fins with optimised profiles and grooved copper tubes - Condenser or evaporator mode heat exchanger on IVDC reversible heat pumps - Axial fans with aluminium airfoil blades. - Variable speed motors with electronic switching- IP 54, class F n Control functions and safety devices - Water flow control - Electronic expansion valve - Refrigerant high and low pressure safety devices - Safety valves on refrigeration circuit - Temperature and pressure sensors - Evaporator water flow controller - Unit start-up sequence - Phase controller Electronic control module CIAT electronic control module with microprocessor and CPU, with central automatic operation and access to internal operation states. n Features: - Start, stop, reset or remote control, - CLING or HEATING mode selector, - RS485 output for GTC link (ModBus-JBus),. board adapter for additional voltage-free contacts,. remote control adapter (optional) - Multilingual analogue LCD display and LEDs. n Functions: - operation information displayed via:. multilingual clear-text messages. direct temperature and pressure readings - complete management of compressors with start-up sequence, timer and runtime balancing - Self-adjusting and proactive functions with adjustment of settings drift control - Device for adapting the capacity to meet the cooling or heating requirements, checked against the water temperatures - Monitoring of internal operation parameters - Second setpoint management - Direct display of water and pressure temperatures - Diagnosis of operation and fault states: HP/LP, water flow, compressor motor(s), frost protection - Short-cycle protection - Remote management and remote monitoring n Electrics box The fully wired electrics box which houses all the electrical components and the electronic CPU board, controls the entire unit, monitors its operation, adjusts water setpoints and interfaces with an external control system. It comprises: - Control and power circuits, - Wire numbering, - Main safety switch with handle on front, - Control circuit transformer, - Circuit breakers on the power and control circuits, - Compressor and motor switches, - Main earth connection, - Microprocessor-controlled electronic control unit, - Alarm or information signals on free terminals. ptions (kit for installation on site) n Main options - Additional voltage-free contact boards, - Remote control unit, - MULTICNNECT management of up to 8 units. - LNWRKS protocol (gateway) - Frost protection, - Evaporator and condenser flexible couplings, - Hydraulic control kit including manifold pressure gauges, control valve and shut-off valve, - Double pump for models kw auxiliary electric heater kit (IVDC 150) kw auxiliary electric heater Kit MDULE (IVDC 200). - Management of 4 auxiliary heating devices. HEAT PUMPS- AIR CNDITINING - REFRIGERATIN - AIR HANDLING - HEAT EXCHANGE - NA C 7
5 Dimensions IVDC model x 957 (int) connection sleeve (option) Connection frame (option) removable lifting lugs 20.5 x holes 1157 E x Xtrafan Wooden handling blocks, to be removed after fitting C D B D A x Leave a space of 1 metre around the unit for maintenance utdoor air discharge utdoor air intake 5: G ½ male hot water inlet 6: G ½ male hot water outlet 1: G 1½ male chilled water inlet 2: G 1½ male chilled water outlet E: Electrical supply (x 80) Position of mounts Anti-vibration mounts Weight (kg) A B C D empty in operation IVDC P25 50 x HEAT PUMPS- AIR CNDITINING - REFRIGERATIN - AIR HANDLING - HEAT EXCHANGE - NA C
6 Dimensions IVDC models x 957 (int) connection sleeve (option) Connection frame (option) x Xtrafan removable lifting lugs 20.5 x holes C E B E 1145 D A Wooden handling blocks, to be removed after fitting x Leave a space of 1 metre around the unit for maintenance utdoor air discharge utdoor air intake 5: G1 male hot water inlet 6: G1 male hot water outlet 1: G 2 male chilled water inlet 2: G 2 male chilled water outlet E: Electrical supply (x 80) Position of mounts Anti-vibration mounts Weight (kg) A B C D E empty in operation IVDC P25 50 x 200 P25 50 x HEAT PUMPS- AIR CNDITINING - REFRIGERATIN - AIR HANDLING - HEAT EXCHANGE - NA C 25
ECOCIAT. Domestic hot water heat recovery unit
Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY
More informationAIR-COOLED CHILLERS APPLIED SYSTEMS. www.daikin.eu EUWA*5-24KAZW - EUWY*5-24KAZW -
AIR-COOLED CHILLERS APPLIED SYSTEMS www.daikin.eu Cooling Only Heat pump EUWA*5-24KAZW - EUWY*5-24KAZW - Environmental Awareness Daikin and the Environment In recent years, motivated by a global awareness
More informationCondensing unit type EPSILON-ECHOS LE Technical information manual
Condensing unit type EPSILON-ECHOS LE Technical information manual 2 > EPSILON ECHOS Water chiller > EPSILON ECHOS /HP Reversible heat pump > EPSILON ECHOS /ST Water chiller with storage tank and pumps
More informationCool Design for Homes and Offices
AIR BLUE AIR BLUE air conditioning Homes Easy to install and use, quiet, attractive, and designed to fit any space: there are Cool Design for Homes and Offices a lot of reasons why Air Blue air conditioners
More informationCRAC Precision climate control units for data centres
CRAC Precision climate control units for data centres 2 Rittal Computer Room Air Conditioner The whole is more than the sum of its parts The same is true of Rittal The System. With this in mind, we have
More informationCooling kw 5.2 6.0 7.1 Heating kw 5.65 6.35 7.75
Specifications COOLING ONLY / HEAT PUMP 005 006 007 Capacity (Eurovent) Cooling kw 5.2 6.0 7.1 Heating kw 5.65 6.35 7.75 Nominal input (Eurovent) Cooling kw 1.89 2.35 2.95 Heating kw 1.97 2.24 2.83 EER
More informationTechnical data. Danfoss DHP-A
Technical data Danfoss DHP-A An air heat pump which produces both heat and hot water Can operate efficiently down to -0 C Danfoss TWS tank gives plenty of hot water quickly and with low operating costs
More informationHP switch LP switch Discharge thermo Comp. Surface thermo
1 Specifications Zubadan Model Name PUHZ-SHW80VHA PUHZ-SHW11VHA PUHZ-SHW11YHA Power supply (phase, cycle, voltage) 1φ, V, Hz 1φ, V, Hz 3φ, 0V, Hz Max. current A 9.5 35.0 13.0 Breaker size A 3 16 Outer
More informationMAC-120HE-01 Air-Cooled Chiller
MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01
More informationROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system.
ROOFTOP - HEAT PUMP UNIT Technical data Applies to Model YNRA R410A This document applies when installing into an air handler or as part of an air handling system. CONTENTS 1. General description... 2
More informationUR...3 URX CF...7 URHE CF...11. Heat recovery unit. Heat recovery unit with refrigerant circuit(442-1947 cfm)
UR...3 Heat recovery unit URX CF...7 Heat recovery unit with refrigerant circuit(442-1947 cfm) URHE CF...11 High efficiency heat recovery unit with refrigeration circuit(588-1942 cfm) UR Heat recovery
More information1-Way Chilled Water Cassettes KCO 60, 90 & 120. Technical Brochure. TM KCO-W.1GB Date : November 2005 Supersedes : None
1-Way Chilled Water Cassettes KCO 60, 90 & 120 Technical Brochure TM KCO-W.1GB Date : November 2005 Supersedes : None General Features Control valve (optional) Air vent In-tube electric heating elements
More informationHeating, Ventilation, Air Conditioning and Refrigeration (HVACR)
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety
More informationVisions become real. Temperature control and cooling systems. The innovative and reliable solution
Temperature control and cooling systems The innovative and reliable solution With our PulseTemp equipment you have the option of up to 72 cooling circuits in the impulse cooling, temperature control, temperature
More informationTWE+TTA TWE+TWA 6.25-20 T.R.
TWE+TTA TWE+TWA 6.25-20 T.R. Main features : TWE indoor unit : Convertible cabinet, vertical or horizontal. Adjustable speed pulley-belt drive centrifugal fan motor. Aluminium fin coil with copper-tubes.
More informationYCAA-B AIR COOLED LIQUID CHILLER
YCAA-B AIR COOLED LIQUID CHILLER R407C REFRIGERANT COOLING CAPACITIES 46 kw to 152 kw York YCAA-B twin refrigerant circuit air cooled liquid chillers are a compact design suitable for chilled water or
More informationTest Report issued under the responsibility of:
Test Report issued under the responsibility of: TEST REPORT EHPA-DACH Testing Regulation Supplemental requirements for granting the international quality label for heat pumps Testing of Air/Water Heat
More informationINNOVATIVE SOLUTION OF DOMESTIC HEATING SPLIT TYPE SPLIT DHW INTEGRATED TYPE MONOBLOC TYPE
INNOVATIVE SOLUTION OF DOMESTIC HEATING SPLIT TYPE SPLIT DHW INTEGRATED TYPE MONOBLOC TYPE Fujitsu General realizes considerable energy saving operations by the Heat pump heating system using the ambient
More informationElegant ECM. ELEGANT ECM air conditioners allow. The range is made up of 12 models: Ceiling Air Conditioner
Elegant ECM Ceiling Air Conditioner ELEGANT ECM air conditioners allow to heat and cool very economically small and medium areas, like shops, show rooms, workshops, supermarkets. The range is made up of
More informationSECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
More informationDERON Air/Water Swimming pool Heat Pump. CY/DY series for Heating/Cooling. Description
Description Compact air/water heat pump for outside installation. With suction gas cooled rotary compressor. With extensive aluminium/cu lamellar tube evaporator and PVC Titanium condenser. Axial fan Refrigerant
More informationmarine/bespoke split applications
split applications marine/bespoke evaporators, condensers and split air conditioning systems suitable for a multitude of applications such as coastal, extreme high and low ambients, harsh dusty environments
More informationtechnical data air conditioning systems RXS20-25-35E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air
technical data RXS20-25-35E FBQ-B8V-B8V3B (single phase) Split Heat Pump Condensing Units air conditioning systems Split Sky Air Outdoor Units R-40A RXS-E2VB Split Sky Air Outdoor Units Features O u t
More informationNew Deluxe Wall Mounted Heat Pump Series EXTERIOS
New Deluxe Wall Mounted Heat Pump Series EXTERIOS May 2013 New Deluxe Wall Mounted Heat Pump Series Panasonic Adding New Air Conditioner Lineup Setting Another Mile Stone in the US Ductless Split History
More informationRotary screw compressors kw 5,5 7,5 11 15 18,5 22 30 bar 8 10 13 15 MODULO
Rotary screw compressors kw 5,5 7,5 11 15 18,5 22 30 bar 8 10 13 15 MODULO The sum of technology TriAB Air ends The BALMA screw compressors are fitted with the unique TriAB air ends that are designed and
More informationhore PRODUCT CATALOGUE nd Offsh arine an ms for Ma & Refrig AUTONOMOUS AIR CONDITIONERS HV VAC &
hore nd Offsh arine an ms for Ma geration System & Refrig HV VAC & PRODUCT CATALOGUE AUTONOMOUS AIR CONDITIONERS O ! "# $ % & " ' (! ) * +,+( -../01..2 PRODUCT CATALOGUE 72-17 AUTONOMOUS AIR CONDITIONERS
More informationHot Water. Heat pump water heaters. Residential and Commercial R410a
Hot Water Heat pump water heaters Residential and Commercial R410a Heat pump technology Heat Pump Water Heating is a new idea using existing technology and is viewed as the latest generation of water heating
More information32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 113 kva, 90 kw 124 kva, 99 kw 6WDQGE\ 114 kva, 91 kw 125 kva, 100 kw
,1'8675,$/#*(16(7 6HULHV#'9#448 32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 113 kva, 90 kw 124 kva, 99 kw 6WDQGE\ 114 kva, 91 kw 125 kva, 100 kw Generator set consisting of engine and alternator mounted
More informationCOOLSIDE box R410A. conditioned server - racks for direct installation into the room INVERTER E C
COOLS conditioned server - racks for direct installation into the room COOLSIDE box INVERTER R410A E C 2 COOLSIDE box GENERAL FEATURES COOLSIDE BOX is a split system consisting of an outdoor motocondensing
More informationCoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60
CoolTop A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60 Application CoolTop is a new, unique air conditioning unit especially designed for datacenters.
More informationTHERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS.
THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS. NOT ALL CODES ARE POSSIBLE ON ANY INDIVIDUAL UNIT. IF THE ALARM APPLIES
More informationAquaFREE system. Technical Catalogue. Outdoor units: RAS-(3~5)HVRNE RAS-(4/5)HRNE
AquaFREE system Technical Catalogue Outdoor units: RAS(3~5)HVRNE RAS(4/5)HRNE Indoor units: RWM(3~5)FSN1E RWM(3~5)FSN1E(4.5/6)H(1/3) RWM(3~5)FSN1ES1 RWM(3~5)FSN1E(4.5/6)SH(1/3) Specifications in this
More informationwww.inspection-for-industry.com
Quality Control Form (TEST RUNNING RECORD FOR AIR HANDLING UNIT) SUB POWER SUPPLY: MAIN POWER V, Hz, CONTROL V, Blower 1 kw, Blower 2 kw, Compressor: (1) kw (2) kw (3) kw (4) kw Heating Element: kw 1.
More informationRefrigeration Compressed Air Dryer Buran Ultrapulse
Refrigeration Compressed Air Dryer Buran Ultrapulse There is more to compressed air than just compressing air Compressed air is an indispensable source of operating and processing power in all areas of
More information3Aftermarket Systems. Air Conditioners and Kombos.. 411. Heater/Pressurizer...440. System Matrix...441. Aftermarket System Requirements...
3Aftermarket Systems Air Conditioning & Heating Replacement Parts Aftermarket Systems Air Conditioners and Kombos.. 411 KA-300 Air Conditioner... 411 KK-315 Heater/Air Conditioner Kombo...412 KA-400 Air
More informationELECTRIC CENTRAL HEATING FLOW BOILER
ELECTRIC CENTRAL HEATING FLOW BOILER EKCO.T Used product can t be treated as general communal waste. Disassembled appliance has to be delivered to the collection point of electrical and electronic equipment
More informationHEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER:
HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER: It is normal for a heat pump to have a build up of white frost on the outside coil during cold damp weather. The
More informationCLOSE CONTROL SYSTEM. PFD series provide you with highly reliable computer room cooling system. High Reliability
PFD-P250VM-E PUHY-P250YJM-A(-BS) PUHY-P500YSJM-A(-BS) PQHY-P250YHM-A CLOSE CONTROL SYSTEM MITSUBISHI ELECTRIC s Close Control System (PFD series) is specifically designed for computer rooms, laboratories
More informationPHOTOVOLTAIC (PV) solar panels. Specification. Electricity - CE & ISO 9000 certified. 83W panel. 180W panel Maximum power:
PHOTOVOLTAIC (PV) solar panels Electricity - CE & ISO 9000 certified Photovoltaic solar panels convert sunlight into useful electricity. ZEDfabric supplies high quality mono-crystalline silicon cell PV
More informationyork air-conditioning products Residential & VRF News 2015
york air-conditioning products Residential & VRF News 2015 york air-conditioning products Catalogue Content Split Systems Pag. High wall High Efficiency Inverter YWHJZH 09 to 24 K 6 High wall Inverter
More informationSIRIUX. SINGLE AND DOUBLE HIGH EFFICIENCY CIRCULATORS Heating Air-conditioning OPERATING LIMITS APPLICATIONS. 28 m 3 /h* Heads up to: Flows up to:
OPERATING LIMITS Flows up to: m /h* Heads up to: m C Max operating pressure: bars Temperature range: - à + C Max ambient temperature: + C ND of orifices: à * m /h: parallel operation SIRIUX SINGLE AND
More informationDC1100 & 1400 Energy Controllers. Satchwell DC1100 & DC1400 for energy-efficient temperature control in smaller buildings.
1100 & 1400 Energy Controllers Satchwell 1100 & 1400 for energy-efficient temperature control in smaller buildings. 02 1100 & 1400 Energy Controllers Features he 1100 and 1400 Energy Controllers are self-configuring
More informationsip Sanyo Modbus Guide Technical Specification Pinouts, Cable Connections & Wiring Issue 2: February 2009 Synapsys Solutions Ltd, all rights reserved
Sanyo Section : Section : Section : Section : Section : sip Modbus Guide Configuration Modbus Table Technical Specification Pinouts, Cable Connections & Wiring Alarm Fault Codes Issue : February 009 Section
More informationD SERIES MODULAR AIR-COOLED SCROLL CHILLER. TECHNICAL SALES GUIDE-50Hz CAPACITY RANGE:65~130kW SUPER HIGH AMBIENT OPERATION TO 43
D SERIES MODULAR AIR-COOLED SCROLL CHILLER TECHNICAL SALES GUIDE-50Hz CAPACITY RANGE:65~130kW SUPER HIGH AMBIENT OPERATION TO 43 CONTENTS 1.MODELS LIST... 3 2.NOMENCLATURE... 3 3.FEATURES... 3 4.PRODUCT
More informationAquaFREE System. Technical Catalogue. Outdoor units: RAS-(3~5)HVRNE RAS-(4/5)HRNE. Indoor units: RWM-(3~5)FSN1E RWM-(3~5)FSN1E-(4.
AquaFREE System Technical Catalogue Outdoor units: RAS-(3~5)HVRNE RAS-(4/5)HRNE Indoor units: RWM-(3~5)FSN1E RWM-(3~5)FSN1E-(4.5/6)H(1/3) Specifications in this manual are subject to change without notice
More informationCONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM 11 5. EXPLOSION VIEW 12 6.
TCL WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS SERVICE MANUAL No.TE051220 Models TAC-09CHSA/GI TAC-12CHSA/GI CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM
More informationCold Room & Refrigeration System (Casserole Assembly) No of units: 1
Technical Specifications Cold Room & Refrigeration System (Casserole Assembly) No of units: 1 For chiller storage of all sorts of items Chiller storage temperature: 2-5 C Provides excellent thermal efficiency
More informationDIESEL-FUELED, BLOWN AIR, DUCTABLE HEATERS
DIESEL-FUELED, BLOWN AIR, DUCTABLE HEATERS Electronic thermostatically controlled Low power consumption Compact space saving size Short heat-up times Dehumidification of the cabin Quiet when running Combustion
More informationFailure code manual. content
Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一
More informationDIESEL-FUELED, BLOWN AIR, DUCTABLE HEATERS
DIESEL-FUELED, BLOWN AIR, DUCTABLE HEATERS Electronic thermostatically controlled Low power consumption Compact space saving size Short heat-up times Dehumidification of the cabin Quiet when running Combustion
More informationTECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05
TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: AW52AL AW64AL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AW52AL 387030095 AW64AL 387030096 0.8180.463.0 07/05 IMPORTANT! Please read before installation
More informationAir cooled screw chillers
Product Manual KPMAC00606-09EN Date: June 2009 Supersedes: none Air cooled screw chillers AWS SE (Standard Efficiency) 184.2 487.3 XE (Hihg Efficiency) 210.2 515.3 PR (Premium Efficiency) 212.2 378.2 Cooling
More information14. Troubleshooting Guide
14. Guide 14.1 Refrigeration Cycle System In order to diagnose malfunctions, ensure the air conditioner is free from electrical problems before inspecting the refrigeration cycle. Such problems include
More informationLG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units
Multi Split Units If there is a fault on any LG Multi unit, an Error mark is indicated on the display window of the indoor unit, wired-remote controller, and LED s of outdoor unit control board. A two
More informationMAROON 2. 6 78 kw. General information. Unique selling points
6 78 kw General information Dedicated heat pumps new series with Scroll compressors, with and without vapor injection. /HT version in 15 sizes Cooling capacity (35;W7): 6 73 KW Heating capacity (7;W45):
More informationIndoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty
Codes Room Air Conditioner range: Indoor unit alarm s If timer lamp flashes for 1 second on, 1 second off, this indicates pre heating on the coil during heating mode and is not an error. If timer lamp
More informationUnico Inverter. Unique and efficient.
Unico Inverter. Unique and efficient. INTERNATIONAL PATENT PENDING The first fixed air conditioner without outdoor unit featuring DC Inverter technology. Great performance, reduced consumption. Designed
More informationRKE. Heat recovery unit. heat recovery unit RKE. from 200 to 6800 m 3 /h. General features
RKE Heat recovery unit from 200 to 6800 m 3 /h General features RKE heat recovery units are suitable for residential and commercial applications and offer a real energy saving in forced ventilation plants,
More informationSECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled
More informationSMM. Installation Operation Maintenance
SMM Configuration SMM Module for Scroll Units, H Generation Installation Operation Maintenance 1 0 L80 IM 022 GB SMM Configuration SMM Module for Scroll Units, H generation Foreword These installation,
More informationElectric Flow Boiler
Electric Flow Boiler EHC offer the most comprehensive range of electric boilers in the market and with our wealth of knowledge and technical expertise we have designed the Slim Jim Electric Flow Boiler
More informationSERVICE MANUAL OUTDOOR UNIT. No. OBH590 REVISED EDITION-B. Models HFC
SPLIT-TYPE AIR CONDITIONERS Revision B: MUZ-EF25/35/42/50VE - E2 and MUZ-EF25/35VEH - E2 have been added. Please void OBH590 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH590 REVISED
More informationREFRIGERATED TYPE COMPRESSED AIR DRYERS INSTRUCTION MANUAL. For Sales & Service please contact:
7610.478.16 8/99 INSTRUCTION MANUAL Models 8005, 8010, 8015 For Sales & Service please contact: CENTRAIR Air Systems & Supplies Phone: 705-722-5747 Fax: 705-722-5458 Email: sales@centrair.ca Website: www.centrair.ca
More informationChilled Water Precision Air Conditioner For Critical Application
AIRSYS-P-SC-OPTIMA-HD-E1304V01.2 HD Chilled Water Precision Air Conditioner For Critical Application Cooling capacity: 42.1kW~161.5kW OPTIMA product family is designed for medium to large data center.
More informationService manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.
Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6
More informationClimasys Thermal Management System. Schneider Electric Universal Enclosures 2009
Climasys Thermal Management System Schneider Electric Universal Enclosures 2009 Schneider Electric Universal Enclosures The specialist in sealed equipment What is the mission of Schneider Electric Universal
More informationHERZ-Thermal Actuators
HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01
More informationSERVICE MANUAL MUZ-GE25VA - E1 MUZ-GE25VAH - E1 MUZ-GE35VA - E1 MUZ-GE35VAH - E1 MUZ-GE42VA - E1 MUZ-GE42VAH - E1 MUZ-GE50VA - E1 MUZ-GE50VAH - E1
SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-GE42/50VA(H) - E1 has been added. Please void OBH516. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH516 REVISED EDITION-A Models MUZ-GE25VA - E1 MUZ-GE25VAH
More informationPANASONIC TROUBLE SHOOTING GUIDE
A General Guide To Room Style Products Pipework Pipe sizes and lengths should be as the relevant Technical Guide Both lines should be insulated No line accessories or oil traps should be fitted In cooling
More information26 3213.13 Diesel Engine Driven Generators Page 1 of 6
Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at
More informationVersati Air to Water Heat Pump
Versati Air to Water Heat Pump VERSATI DC Inverter Multifunctional Air To Water Heat Pump Nowadays, people are increasingly focusing on heating costs as well as environmental issues. Traditional heating
More informationSECTION 23 81 43 HEAT PUMPS
SECTION 23 81 43 HEAT PUMPS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop heat pumps. 1.2 REFERENCES A. American Society of Heating, Refrigerating and Air-Conditioning Engineers:
More informationSECTION 23 64 10 AIR COOLED WATER CHILLERS
PART 1 GENERAL 1.1 SECTION INCLUDES A. Chiller package B. Charge of refrigerant and oil C. Controls and control connections D. Chilled water connections E. Starters F. Electrical power connections 1.2
More informationMagnum Mobile Generator MMG55 Specifications
Empowering Real People Magnum Mobile Generator MMG55 Specifications ENGINE John Deere PE5030TF270 - turbocharged, diesel engine o Prime - 72 hp @ 1800 rpm o Standby - 80 hp @ 1800 rpm o 4 cylinder o 3.0
More informationDLW 8. POWER RATING 1500 rpm/50 Hz 1800 rpm/60 Hz Prime 7.5 kva, 6 kw 9.1 kva, 7.3 kw Standby 8.5 kva, 6.8 kw 10.1 kva, 8.1 kw
DLW 8 POWER RATING 1500 rpm/50 Hz 1800 rpm/60 Hz Prime 7.5 kva, 6 kw 9.1 kva, 7.3 kw Standby 8.5 kva, 6.8 kw 10.1 kva, 8.1 kw Generator set consisting of engine and alternator mounted on a fabricated steel
More informationSERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER SHARP CORPORATION SHARP CORPORATION CONTENTS
SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER INDOOR UNIT AH-129 AH-MP14 OUTDOOR UNIT AU-129 AU-MP14 CONTENTS SPECIFICATIONS...2 EXTERNAL DIMENSIONS...4 WIRING DIAGRAMS...5 ELECTRICAL PARTS...6 MICROCOMPUTER
More informationMax primary circuit temperature 90ºC Max primary circuit temp. 90ºC Max secondary circuit temperature 45ºC Max secondary circuit temp.
EGLISH 1 Product description exchanger equipped with an electronic control unit and circulation pump for the primary circuit. All Aqua-Mex variants can be ordered with an interior coil of either titanium
More informationDESIGN STANDARDS SECTION 23 60 00
PART 1 - GENERAL 1.01 Work included: A. Piping, tubing and fittings. B. Piping specialties. C. Special duty valves. D. Refrigerants. E. Chillers. F. Refrigerant monitors. 1.02 General requirements: A.
More information32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 10.4 kva, 8.3 kw 12.9 kva, 10.3 kw 6WDQGE\ 11.3 kva, 9 kw 14.4 kva, 11.5 kw
,QGXVWULDO#*HQHUDWRU 32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 10.4 kva, 8.3 kw 12.9 kva, 10.3 kw 6WDQGE\ 11.3 kva, 9 kw 14.4 kva, 11.5 kw Generator set consisting of engine and alternator mounted
More informationKONRAD. Hybrid Fancoil Series
KONRAD Hybrid Fancoil Series Konrad is an innovative radiator which cools you down and warms you up. Indeed, it cools in summer and heats in winter; but it makes it with an incomparable quietness. Thanks
More informationAppendix - Controllers 179
Version: 200703 Appendix - Controllers 179 -3- -4- -5- -6- -7- -8- 2. Specifications 2.1 Specifications for inverter units item Model AB182ACERA Function cooling heating Capacity kw 5.01.8--5.8 5.22.0---6.2
More informationSECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS
SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating
More informationAerona Air Source Heat Pumps
ADDENDUM to INSTALLATION INSTRUCTIONS for Aerona Air Source Heat Pumps DOC.87-05/05 Rev.04 March 2013 ATTENTION INSTALLERS - UPDATED INFORMATION! Your Grant Aerona Air Source Heat Pump has a number of
More informationInstallation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008
Installation Manual Rental Services Air Handling Units July 2008 CHS-SVN01A-EN Copyright 2008 Trane All rights reserved This document and the information in it are the property of Trane and may not be
More informationPRE-ASSEMBLED REMOTE REFRIGERATION SYSTEMS
NOR-LAKE, INCORPORATED 727 Second Street P.O. Box 248 Hudson, Wisconsin 54016 800-955-5253 715-386-2323 866-961-5253 Parts 800-388-5253 Service 715-386-4291 FAX www.norlake.com Split-Pak Pre-Assembled
More informationALL IN ONE. Heat Pump Water Heater
ALL IN ONE Heat Pump Water Heater INSTALLATION AND OPERATION INSTRUCTIONS Please read this user s manual carefully before operate the unit. www.airtradecentre.com CONTENTS A. IMPORTANT REMARKS ------------------------------------------------------------------------------------------------
More informationHEAVY DUTY STORAGE GAS
Multi-Fin flue technology Flue damper saves energy Electronic controls HEAVY DUTY STORAGE GAS Dependability The Rheem heavy duty gas range is the work horse of the industry having proved itself over many
More informationCONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. ELECTRICAL SCHEMATIC DIAGRAM 13 5. EXPLOSION VIEW 16 6
TCL WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS SERVICE MANUAL No.TE080528 Models KFTHP-12 KFTHP-18 KFTHP-24 CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. ELECTRICAL
More informationSWIMMING POOL HEAT PUMP Owners Manual
SWIMMING POOL HEAT PUMP Owners Manual This manual refers to the 17.0kw and 21.0kw models only. The heat pump unit is sold with a 1 year warranty. In addition there is a 2 year parts warranty on the compressor
More informationAE21-1319 R6 December 2013. Digital Capacity Control for Copeland Scroll Refrigeration Compressors AE21-1319 R6
AE21-1319 R6 December 2013 Digital Capacity Control for Copeland Scroll Refrigeration Compressors TABLE OF CONTENTS Section Page Section Page Safety Safety Instructions...2 Safety Icon Explanation...2
More informationSYLLABUS For BASIC TRADE COURSE (360 Hours) On REFRIGERATION AND AIR CONDITIONING
SYLLABUS For BASIC TRADE COURSE (360 Hours) On REFRIGERATION AND AIR CONDITIONING INDEX 1. Introduction 3 2. Objectives 3 3. Employment Opportunity 4 4. Course Structure 4 5. Entry Qualification 4 6. List
More informationTransformer oil cooler ALFA A02
A02 Transformer oil cooler ALFA Transformer oil cooler ALFA The transformer oil cooler ALFA is used to cool power transformers by means of forced air and oil flow. The oil in the cooler is circulated using
More informationWWZ High efficiency HYBRID heat pumps with E.V.I compressor in two sections
High efficiency HYRID heat pumps with E.V.I compressor in two sections infolinia: +48 691 262 691-20 +43 +65 E.V.I..O.P. 4,1 The series of high efficiency hybrid heat pumps has been specifically designed
More informationTest Code: 8297 / Version 1
Blueprint HVAC Maintenance Technology PA Test Code: 8297 / Version 1 Copyright 2014. All Rights Reserved. General Assessment Information HVAC Maintenance Technology PA Blueprint Contents General Assessment
More informationOil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
More informationLG Air conditioning Company Multi V Water Ⅱ. Air Conditioning Academy
LG Air conditioning Company Multi V Water Ⅱ Air Conditioning Academy 1.1 What is Multi V Water II? High Performance Prospect rights Water pipe Refrigerant pipe Indoor unit Beautiful Exterior Convenience
More informationRPV - RP - RA air handling units
APPLICATIONS Heating, ventilation, cooling >> FACTORIES >> WAREHOUSES >> HALLS >> DISTRIBUTION CENTRES >> COMMERCIAL PREMISES >> PLACES OF WORSHIP RPV - RP - RA air handling units www.reznor.eu RPV - RP
More informationMAINTENANCE INSTRUCTIONS. Thermia Robust heat pump
MAINTENANCE INSTRUCTIONS Thermia Robust heat pump 9 6 8 0-5 4 7 4 5 0 0 1 R e v. 3 Table of contents 1 Important information.................. 2 1.1 Product description....................... 2 1.2 General................................
More informationWater Fired Chiller/Chiller-Heater. WFC-S Series: 10, 20 and 30 RT Cooling
Water Fired Chiller/Chiller-Heater WFC-S Series: 1, 2 and 3 RT Cooling W E A R E F R I E N D L Y T O T H E E A R T H Water Fired SINGLE-EFFECT Chiller or Chiller-Heater Absorption Principle Cooling Cycle
More informationOn/off room thermostats range. On/off V30 range. Master/slave PI V200 range. V3000 KNX networked PID range
Electromechanical controls Air control Water control On/off room thermostats range On/off room thermostats range Electronic controls Air control On/off V30 range On/off V30 range Water control Master/slave
More information