5SJ4...-HG4 Miniature Circuit Breakers

Size: px
Start display at page:

Download "5SJ4...-HG4 Miniature Circuit Breakers"

Transcription

1 Product Guide 5SJ...-HG Miniature Circuit Breakers for North American and International applications usa.siemens.com/5sj

2 Table of contents Certifications 3 Description Circuit breaker catalog number nomenclature 5 Product selection 5SJ1..-.HG0 Product selection 5SJ...-.HG1 7 Product selection 5SJ...-.HG 8 Product selection Accessories; auxiliary switch, fault current contact, shunt trip 9 Product Selection Busbar, connection terminals, protection covers 10 Typical 5SJ miniature circuit breaker markings 11 Typical auxiliary switch (AS) and fault signal (FS) contact markings 13 Typical shunt trip markings 1 Typical busbar markings 15 Current ratings at ambient temperatures other than 0ºC 1 Let-through I t values 17 Power loss 18 Correction factors for rated current at different ambient temperatures 18 Technical specifications 19 Accessory mounting; auxiliary switch, fault current contact, shunt trip 0 Dimensions 1 Limitations of use

3 Certifications and features Certifications and Standards UL Listed UL 89 CSA. No. 5-0 HACR IEC/EN 0 898, IEC/EN Features UL 89 Suitable for branch circuit and feeder protection applications -.HG0: up to 0 VAC, and 0 VDC (1-pole); -.HG1: up to 0 VAC, and 0 VDC (1-pole); and up to 0 VAC, and 15 VDC (- and 3-pole) -.HG: up to 77 VAC, and 0 VDC (1-pole); and, up to 80/77 VAC and 15 VDC (- and 3-pole) culus: UL listed and certified to Canadian Standards. File E31 HACR rated Thermal magnetic protection High interrupting rating: VAC: up to 1,000 (Type HSJ) or 10,000 (Type NSJ) Maximum RMS symmetrical amps depending on the device selected VDC: up to 10,000 amps (Type HSJ and Type NSJ) at 0/15 VDC 0 C (10 F) calibration base (industrial applications) Can be used for field wiring applications, AWG 1 to AWG, Copper (Cu) only -.HG0: suitable for same polarity connections only -.HG1 and -.HG: suitable for reverse feed application No same polarity restrictions Features EN/IEC 0 898, EN/IEC CE marked 30 C (8 F) calibration base Meets trip characteristics -.HG0: B, C and D -.HG1 and -.HG: C and D Rated voltage VAC/DC: minimum VDC/pole: 0 maximum VAC: 0 maximum High interrupting rating (I cn ) to IEC of up to 10,000 A AC High interrupting rating (I cn ) to IEC of up to 15,000 A AC Features Common Available with -.HG0: 1-pole -.HG1 and -HG: 1-, - or 3-poles Available from -.HG0 and -.HG1: 0.3 to 3 amps depending on the device selected -.HG: 0.3 to 0 A (C Characteristic); 0.3 to 3A (D characteristic) Visible indicator for ON and OFF/Trip Finger-safe design Standard DIN rail mounting (35 mm) Identical wire screw connections on line and load sides CFC and silicone free 5SJ miniature circuit breakers are also CE marked according to IEC/EN and IEC/EN making them suitable for use in international applications. 3

4 Description 5SJ...-.HG. Miniature Circuit Breakers (mcb) are 1-, - and 3-pole thermal / magnetic overcurrent protection devices that are intended for general industrial use such as Branch Circuit and Feeder Protection. They are UL Listed (File No. E31, Volume 1, Section 1) in accordance with UL 89, 11th edition, Molded-Case Circuit Breakers, Molded-Case Switches and Circuit-Breaker Enclosures and Certified to Canadian Standards (CSA. No. 5.0). They are provided with a manual means for opening the circuit and they are not ambient compensated. 5SJ...-.HG. Miniature Circuit Breakers are rated -.HG0: 0 VAC max. and 0 VDC max. for 1-pole devices. -.HG1: 0 VAC max. and 0 VDC max. for 1-pole devices; 0 VAC max. and 15 VDC max. for - and 3-pole devices. -.HG: 77 VAC max. and 0 VDC max. for 1-pole devices; 80Y/77 VAC max. and 15 VDC max. for - and 3-pole devices. The load current ranges form 0.3 to 3 A depending on the device selected with interrupting ratings stated in the following table for 1-, - and 3-pole devices. Description Characteristic Current A Rated switching capacity (operational voltage 30 V AC) ka AC Rated switching capacity (operational voltage 80Y/77 V AC) ka AC 5SJ...-.HG0 B C C D D SJ...-.HG1 C C D D SJ...-.HG C D D

5 Circuit breaker catalog number nomenclature 5SJ HG1 Frame style 5SJ Standard Frame Poles 1 = 1-Pole = -Pole 3 = 3-Pole Code Rated current (I n ) 1 = = = 1 15 = 1. 0 = 03 = 3 0 = 11 = 5 0 = 08 = 8 10 = = = 15 1 = 1 0 = 0 5 = 5 30 = 30 3 = 3 35 = 35 0 = 0 5 = 5 50 = 50 0 = 0 3 = 3 Trip curve (Characteristic) = Trip curve B, Magnetic trip point 3 to 5 I n, 1.13 to 1.5 breaker rating 7 = Trip curve C, Magnetic trip point 5 to 10 I n, 1.13 to 1.5 breaker rating 8 = Trip curve D, Magnetic trip point 10 to 0 I n, 1.13 to 1.5 breaker rating Version HG0 = 0 VAC, same polarity HG1 = 0 VAC HG = 80Y/77 VAC 5

6 Product selection 5SJ1..-.HG0 Type HSJ: Interrupting rating 0 VAC: 1,000 maximum RMS symmetrical amps 0 VDC: 10,000 amps Type NSJ: Interrupting rating 0 VAC: 10,000 maximum RMS symmetrical amps 0 VDC: (1-pole) / 15 VDC (- & 3-pole) 10,000 amps TYPE HSJ HSJ NSJ HSJ NSJ No. of Poles I n (A) Characteristic B Order No. Characteristic C Order No. Characteristic C Order No. Characteristic D Order No. Characteristic D Order No SJ11-7HG0* 5SJ11-8HG0* SJ105-7HG0 5SJ105-8HG SJ101-7HG0 5SJ101-8HG SJ115-7HG0 5SJ115-8HG0 1 5SJ10-7HG0 5SJ10-8HG SJ103-7HG0 5SJ103-8HG0 1 5SJ10-7HG0 5SJ10-8HG SJ111-7HG0 5SJ111-8HG0 1 5SJ10-HG0 5SJ10-7HG0 5SJ10-8HG SJ108-7HG0 5SJ108-8HG SJ110-HG0 5SJ110-7HG0 5SJ110-8HG SJ113-HG0* 5SJ113-7HG0 5SJ113-8HG0 * SJ118-HG0 5SJ118-7HG0 5SJ118-8HG SJ11-HG0 5SJ11-7HG0 5SJ11-8HG SJ10-HG0 5SJ10-7HG0 5SJ10-8HG SJ15-HG0 * 5SJ15-7HG0 5SJ15-8HG0 * SJ130-HG0 * 5SJ130-7HG0 5SJ130-8HG SJ13-HG0 * 5SJ13-7HG0 5SJ13-8HG0 * SJ135-HG0 * 5SJ135-7HG0 5SJ135-8HG0 * 1 0 5SJ10-HG0 * 5SJ10-7HG0 5SJ10-8HG SJ15-HG0 * 5SJ15-7HG0 * 5SJ15-8HG SJ150-HG0 * 5SJ150-7HG0 5SJ150-8HG0 * 1 0 5SJ10-HG0 * 5SJ10-7HG0 5SJ10-8HG0 * 1 3 5SJ13-HG0 * 5SJ13-7HG0 * 5SJ13-8HG0 * * Not stocked in the US.

7 Product selection 5SJ..-.HG1 Type HSJ: Interrupting rating 0 VAC: 1 ka maximum RMS symmetrical 0 VDC: (1-pole) / 15 VDC (- & 3-pole) 10,000 A Type NSJ: Interrupting rating 0 VAC: 10 ka maximum RMS symmetrical 0 VDC: (1-pole) / 15 VDC (- & 3-pole) 10,000 ka TYPE HSJ NSJ HSJ NSJ No. of Poles 1) I n (A) Characteristic acteristic C Order r No. Characteristic C Order No. Characteristic D Order No. Characteristic D Order No. * 0.3 5SJ*1-7HG1 5SJ*1-8HG1 * 0.5 5SJ*05-7HG1 5SJ*05-8HG1 * 1 5SJ*01-7HG1 5SJ*01-8HG1 * 1. 5SJ*15-7HG1 5SJ*15-8HG1 * 5SJ*0-7HG1 5SJ*0-8HG1 * 3 5SJ*03-7HG1 5SJ*03-8HG1 * 5SJ*0-7HG1 5SJ*0-8HG1 * 5 5SJ*11-7HG1 5SJ*11-8HG1 * 5SJ*0-7HG1 5SJ*0-8HG1 * 8 5SJ*08-7HG1 5SJ*08-8HG1 * 10 5SJ*10-7HG1 5SJ*10-8HG1 * 13 5SJ*13-7HG1 5SJ*13-8HG1 * 15 5SJ*18-7HG1 5SJ*18-8HG1 * 1 5SJ*1-7HG1 5SJ*1-8HG1 * 0 5SJ*0-7HG1 5SJ*0-8HG1 * 5 5SJ*5-7HG1 5SJ*5-8HG1 * 30 5SJ 30-7HG1 5SJ*30-8HG1 * 3 5SJ*3-7HG1 5SJ*3-8HG1 * 35 5SJ*35-7HG1 5SJ*35-8HG1 * 0 5SJ*0-7HG1 5SJ*0-8HG1 * 5 5SJ*5-7HG1 5SJ*5-8HG1 * 50 5SJ*50-7HG1 5SJ*50-8HG1 * 0 5SJ*0-7HG1 5SJ*0-8HG1 * 3 5SJ*3-7HG1 5SJ*3-8HG1 1) Substitute the * with: 1 for 1-pole mcbs for -pole mcbs 3 for 3-pole mcbs 7

8 Product selection 5SJ..-.HG Type NSJ: Interrupting rating 80Y/77 VAC 10,000 maximum RMS symmetrical amps 0 VDC: (1-pole) / 15 VDC (- & 3-pole) 10,000 amps TYPE HSJ NSJ HSJ NSJ No. of Poles 1) I n (A) Characteristic C Order No. Characteristic C Order No. Characteristic D Order No. Characteristic D Order No. * 0.3 5SJ*1-7HG 5SJ*1-8HG * 0.5 5SJ*05-7HG 5SJ*05-8HG * 1 5SJ*01-7HG 5SJ*01-8HG * 1. 5SJ*15-7HG 5SJ*15-8HG * 5SJ*0-7HG 5SJ*0-8HG * 3 5SJ*03-7HG 5SJ*03-8HG * 5SJ*0-7HG 5SJ*0-8HG * 5 5SJ*11-7HG 5SJ*11-8HG * 5SJ*0-7HG 5SJ*0-8HG * 8 5SJ*08-7HG 5SJ*08-8HG * 10 5SJ*10-7HG 5SJ*10-8HG * 13 5SJ*13-7HG 5SJ*13-8HG * 15 5SJ*18-7HG 5SJ*18-8HG * 1 5SJ*1-7HG 5SJ*1-8HG * 0 5SJ*0-7HG 5SJ*0-8HG * 5 5SJ*5-7HG 5SJ*5-8HG * 30 5SJ*30-7HG 5SJ*30-8HG * 3 5SJ*3-7HG 5SJ*3-8HG * 35 5SJ*35-7HG * 0 5SJ*0-7HG * 5 * 50 * 0 * 3 1) Substitute the * with: 1 for 1-pole mcbs for -pole mcbs 3 for 3-pole mcbs 8

9 Product selection Accessories Auxiliary switches (AS) to UL 89 Length DT Order No. PU PS ) P. unit MW 1) mm Unit(s) Unit(s) kg PG Weight per PU approx. 1 NO + 1 NC 0.5 5ST HG NO 5ST HG NC 5ST3-01-0HG Fault signal contacts (FC) to UL 89 1 NO + 1 NC 0.5 5ST3-00-0HG NO 5ST3-01-0HG NC 5ST3-0-0HG Shunt trips (ST) to UL V AC 1 5ST HG V AC/DC 5ST HG ) 1 MW (module width) = 18 mm. ) You can order this quantity or a multiple thereof. 5ST30..-0HG Accessories are intended for use with UL89 miniature circuit breakers of the 5SJ -.HG.. series. Auxiliary Circuit Switches are available with One Normally Open + One Normally Closed, Two Normally Open or Two Normally Closed contacts. They are primarily used to signal the miniature circuit breaker s trip mechanism position. Fault Signal Contacts are available with One Normally Open + One Normally Closed, Two Normally Open or Two Normally Closed contacts. They are primarily used to signal the automatic tripping of the miniature circuit breaker s trip mechanism; and, trip position. Shunt Trip switches are available in voltages of 110 to 80 VAC and to 0 V AC/DC. They are used for remote tripping of a miniature circuit breaker. A maximum of one shunt trip (ST) and a maximum of two auxiliary switches (AS) or fault current contacts (FC) in any combination may be used; three devices maximum. Refer to mounting diagram on page 0. Siemens Auxiliary Switches and Fault Signal Contacts are UL Listed and Certified to Canadian Standards to 80 VAC maximum. This offers a competitive advantage in that 80Y/77 VAC miniature circuit breakers are not limited to 300 VAC maximum when an auxiliary device is used. 9

10 Product selection Busbar and connection terminals Pin spacing Length DT Order No. MW mm Busbars acc. to UL 89 for use with 5SJ...-.HG.. 1) Single Pole For MCB 1P A 5ST3-3-0HG For 1 MCB 1P 1 05 A 5ST3-3-1HG For 18 MCB 1P A 5ST3-3-HG Two-Pole For 3 MCB P A 5ST3--0HG For MCB P 1 05 A 5ST3--1HG For 9 MCB P A 5ST3--HG Three-Pole For MCBs 3P A 5ST3-5-0HG For MCBs 3P 1 05 A 5ST3-5-1HG For MCBs 3P A 5ST3-5-HG Connection terminals acc. to UL89 for use only with 5SJ...-.HG.. Infeed - MCBs 35 mm A 5ST3--0HG Infeed - busbars A 5ST3--HG 50 mm Touch protection covers for busbars acc. to UL89 1) 3 x 1 pin A 5ST3--1HG 1) All unused busbar terminals must be covered with touch protection covers 5ST3-1HG. 10

11 Typical miniature circuit breaker markings Front markings Interrupting type Current rating (I n ) and trip curve HACR Type Calibration base Interrupting ratings Trip indication window ON OFF 11

12 Typical miniature circuit breaker markings (continued) Left side markings CE mark and country of origin Complete catalog number Terminal tightening torque Conductor wire size (AWG & IEC) Conductor strip length (mm) Right side markings UL label UL label colors: 1-Pole: White -Pole: Blue 3-Pole: Green 1

13 Typical auxiliary switch (AS) and fault signal contact (FC) markings 5ST301. AS Partial catalog number Device type abbreviation (AS, FC) 13 1 Circuit diagram 1 Manufacturer and device type Terminal number references Conductor strip length Tightening torque Wire size range Wire temperature Range and type Catalog number Contact ratings Certification marks and country of origin 13

14 Typical shunt trip (ST) markings 5ST3031-0HG ST... 0V s C1 C Certification marks and country of origin Catalog number Conductor strip length Tightening torque Wire size range Wire temperature Range and type 1

15 Typical busbar markings Busbar cross section Catalog number Rated current Operating voltage UL mark UL file number Country of origin Intended use with 15

16 Current ratings at ambient temperatures other than 0 C (Additional temperature Correction Factors found on page 18) Use the following table to determine the CBs I n current rating for ambient temperature other than 0ºC Device marked current rating at 0ºC I n (A) at different ambient temperatures Current rating (A) No. of poles 15ºC 0ºC 5ºC 30ºC 0ºC 50ºC 55ºC 0.3 1// // / / // // // // // // // // // / / / / / / / / / / SJ miniature circuit breakers are Non 100 percent rated as specified in UL 89, paragraph When selecting a miniature circuit breaker for continuous loads no more than 80% of the device s marked current should be used. 5SJ miniature circuit breakers are Current-Limiting as defined in UL 89, paragraph.5. Current-Limiting Circuit Breakers do not employ a fusible element and when operating within its current-limiting range, limits the let-through I t to a value less than the I t of a ½ cycle wave of the symmetrical prospective current. Current limiting circuit breakers provide a higher level of circuit protection than a typical external breaker. 1

17 Characteristic curves 5SJ...-.HG0, 5SJ...-.HG1, 5SJ...-.HG Let-through I t values Characteristic B Characteristic D [ka s] t 10 3 I_1338 t [ka s] 10 3 I_ /0/3 A 5/30/3/35/0/5 A 13/15/1/0 A 10 A A /5/50/0/3 A 0 A 15/1 A 8/10/13 A 5/ A A 3 A A 1, A 1 A 30/3/35 A 5 A ,5 A 0,3 A p [ka] p [ka] Characteristic C s] I t [ka /15/1 A 8/10 A A 3//5 A A 1, A I_ /5/30/3/35/0 A 50/0/3 A 1 A 0,5 A ,3 A I p [ka] 17

18 Power Loss Rated current Characteristic B Characteristic C Characteristic D I n R i P v R i P v R i P v A m W m W m W Correction factors for rated current at different ambient temperatures Dependence of permissible continuous load current on ambient temperature Reduction Factor 1, 1,3 1, Curve Curve 3 I_1810 1,1 1,0 Curve Curve 1 0,9 0, Ambient Temperature [ C] Curve for correction factor Rated current (A) No. of poles valid curve for correction factor

19 Technical specifications Circuit breakers 5SJ...-.HG0 5SJ...-.HG1 5SJ...-.HG Standards IEC/EN 0898; IEC/EN 097-; UL 89, CSA C. No. 5-0 Certifications UL 89; CSA C. No. 5-0 UL FIle No. E31 Tripping characteristic B, C, D C, D Operational voltage min V AC/DC IEC 0898 max. V DC/pole 0 max. V AC 0 UL 89 and CSA C. No. 5-0 max. V AC 0/ Y/77 V DC/1P V DC/P Rated breaking capacity I cn to IEC ka AC 10 I cu to IEC 097- ka AC 15 UL 89 and CSA C. No. 5-0 ka AC 1/10 1/10 10 Insulation coordination Rated insulation voltage VAC 50 50/0 Degree of pollution for overvoltage category 3/III Touch protection to EN 507 Yes Handle end position, sealable Yes Degree of protection to EN 059 IP0, with connected conductors CFC and silicone-free Yes Mounting On standard mounting rail Terminals Combined terminals at both ends Yes Terminal tightening torque, only for Cu, 0/75º Nm 3.5 lb/in 31 Conductor cross-sections Solid and stranded to UL 89 and CSA C. No. 5-0 AWG 1... Solid and stranded to IEC mm Mains connection Any Mounting position Any Average service life, with rated load 0000 actuations Ambient temperature ºC , occasionally +55 max. 95% humidity, storage temperature: Resistance to climate to IEC cycles Resistance to vibrations to IEC m/s 0 at Hz Additional components Auxiliary switches (AS) 5ST HG 5ST HG 5ST3 01-0HG Fault signal contacts (FC) 5ST3 00-0HG 5ST3 01-0HG 5ST3 0-0HG Shunt trips (ST) 5ST HG 5ST HG Standards UL 89, CSA. No. 5-0 IEC/EN 019, IEC/EN IEC/EN Certifications UL 89; CSA, UL File Nr. E31559 Operational voltage/operational load (current) IEC V AC A AC (NC: AC13, NO: AC1) V DC A DC (DC13) UL V AC A AC V DC A DC 1 3 Short-circuit protection Circuit breaker or fuse A Contact load min. 50 ma, V Response limit x U n Conductor cross-sections AWG mm Terminals terminal tightening torque Nm 0.5 max. 0.8 max. lb/in

20 Technical specifications Busbars 5ST3 3-.HG 5ST3 3-.0HG 5ST3 -.HG 5ST3 -.HG 5ST3 5-.HG Standards UL 89 Certifications UL 89 UL File Nr. E31559 Operational voltage IEC V AC 90 UL 89 V AC 80Y/77 and 0 Rated conditional short-circuit current ka 15kA Dielectric strength kv/mm 30 Surge strength kv >9.5 Rated current at 0ºC ambient temperature A 115 Insulation coordination Degree of pollution Overvoltage category III Busbar cross-section mm Cu 1 Infeed Any Conductor cross-sections AWG mm Terminals terminal tightening torque Nm lb/in Temperature resistance ºC 00 - UL 89-V0/0. mm Mounting concept of accessories 5ST HG to circuit breakers 5SJ...-.HG. The chart shows which additional components can be mounted on the right. Maximum of two accessories, AS or FC, in any combination 5ST30. 5SJ...HG.. or or or AS FC AS FC AS FC AS FC FC AS CB or or or ST AS FC AS FC AS FC AS FC FC AS Maximum of one ST + Maximum of two AS or FC in any combination CB: circuit breaker ST: shunt trip AS: auxiliary switch FC: fault signal contact 0

21 Dimensions 1 I_ I_ , 70 5SJ...-.HG0 5SJ...-.HG1 5SJ...-.HG 5ST HG 5ST HG 5ST3 01-0HG 5ST3 00-0HG 5ST3 01-0HG 5ST3 0-0HG 5ST HG 5ST HG I_101 I_ I_13958a , I_1705 I_170 9, 70 18, ST3 3-0HG 5ST3-0HG 5ST3 5-0HG 5ST3 3-1HG 5ST3-1HG 5ST3 5-1HG 5ST3 3-HG 5ST3 -HG 5ST3 5-HG Pin spacing in MW (module width; 1 MW = 18 mm). Dimensions of side view in mm (approx). 5ST3-1HG Pin spacing in MW (module width; 1 MW = 18 mm). Dimensions of side view in mm (approx). 1

22 Limitations of use The information provided in this product profile contains descriptions or characteristics of performance which in case of actual use do not always apply as described or which may change as a result of further development of the products. An obligation to provide the respective characteristics shall only exist if expressly agreed in the terms of contract. Availability and technical specifications are subject to change without notice. All products designations may be trademarks or product names of Siemens AG or supplier companies whose use by third parties for their own purposes could violate the rights of the owners.

23

24 Siemens Industry, Inc. 500 Triangle Parkway Norcross, GA usa.siemens.com/5sj Subject to change without prior notice. Order No: PDCA-5SJU-0913 All rights reserved. Printed in USA. 013 Siemens Industry, Inc. The information provided in this brochure contains merely general descriptions or characteristics of performance which in case of actual use do not always apply as described or which may change as a result of further development of the products. An obligation to provide the respective characteristics shall only exist if expressly agreed in the terms of contract. Siemens is a registered trademark of Siemens AG. Product names mentioned may be trademarks or registered trademarks of their respective companies. Specificationsare subject to change without notice.

5SV Residual Current Protective Devices

5SV Residual Current Protective Devices s Siemens AG 2013 SENTRON 5SV Residual Current Protective Devices New portfolio for reliable personnel, material and fire protection Safe protection against residual currents Residual current protective

More information

Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection

Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection Technical Data Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection Topic Page 1489-M Miniature Circuit Breakers 2 1492-SP Supplementary Protectors 15 1492-D Circuit Breakers 27 188 Regional

More information

RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage

More information

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592. * see variants. Applications.

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592. * see variants. Applications. Safety Technique SAFEMASTER Emergency Stop Module BG 5924, IP 5924 Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592 BG 5924 IP 5924 Product Description

More information

Electronic overload relay EF19 and EF45

Electronic overload relay EF19 and EF45 Data sheet Electronic overload relay EF19 and EF45 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays. Motor

More information

Molded Case Circuit Breaker Specifications Bulletin Number 140U-D

Molded Case Circuit Breaker Specifications Bulletin Number 140U-D Technical Data Molded Case Circuit Breaker Specifications Bulletin Number 140U-D Topic Page Product Line Overview 2 Specifications 3 Trip Curves 4 Approximate Dimensions 6 Additional Resources These documents

More information

Uncompromising safety and comfort The next generation of miniature circuit breakers MCB S 200/S 200 M

Uncompromising safety and comfort The next generation of miniature circuit breakers MCB S 200/S 200 M Uncompromising safety and comfort The next generation of miniature circuit breakers MCB S 200/S 200 M The details make the difference MCB S 200/S 200 M A range designed to ensure efficiency and protection

More information

RM35UA13MW. range 15..600 V. Main. Product or component type. Relay monitored parameters

RM35UA13MW. range 15..600 V. Main. Product or component type. Relay monitored parameters Characteristics multifunction voltage control relay RM35-U - range 15..600 V Complementary Reset time Maximum switching voltage [Us] rated supply voltage Supply voltage limits Power consumption in W Main

More information

Electronic overload relay EF65, EF96 and EF146

Electronic overload relay EF65, EF96 and EF146 Data sheet Electronic overload relay EF65, EF96 and EF146 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays.

More information

R.C.C.B. s two-pole LEXIC

R.C.C.B. s two-pole LEXIC 87045 LIMOGES Cedex Telephone : (+33) 05 55 06 87 87 Fax : (+ 33) 05 55 06 88 88 R.C.C.B. s two-pole LEXIC 089 06/09/10/11/12/15/16/17/18/ 27/28/29/30/35, CONTENTS PAGES 1. Electrical and mechanical characteristics...

More information

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2...

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2... Magnetic and Hydraulic-Magnetic Circuit Breaker 840-G2... Description Single, two and three pole magnetic circuit breakers with trip-free mechanism and push/pull on/off manual actuation. A choice of fast

More information

Bulletin 1489 Circuit Breakers. Selection Guide

Bulletin 1489 Circuit Breakers. Selection Guide Bulletin 1489 s Selection Guide Bulletin 1489-A Overview/Description Bulletin 1489-A s Energy-limiting design protects downstream components better than conventional breakers during short circuits Field-mountable

More information

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact Data sheet Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact The CT-AHD.12 is an electronic time relay with OFF-delay. It is from the CT-D range. With their MDRC profile and a width of only

More information

RM4TG20 three-phase network control relay RM4-T - range 200..500 V

RM4TG20 three-phase network control relay RM4-T - range 200..500 V Characteristics three-phase network control relay RM4-T - range 200..500 V Complementary [Us] rated supply voltage Output contacts Setting accuracy of time delay Delay at power up Measuring cycle Marking

More information

48.12. 2 pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2,000 500 0.37 8/0.65/0.

48.12. 2 pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2,000 500 0.37 8/0.65/0. 48 Series - Relay interface modules 8 A Features 48.12 2 Pole Safety relay interface modules, 15.8 mm wide 48.12-2 Pole 8 A (screw terminal) DC sensitive coils Relay with forcibly guided contacts according

More information

Relés e Contatores de Estado Sólido SIRIUS

Relés e Contatores de Estado Sólido SIRIUS Relés e Contatores de Estado Sólido SIRIUS Coletânea de dados técnicos ( product data sheet ) Agosto/212 SSR - 3RF21 22,5 mm Ponto Zero SSR - 3RF2 45 mm Ponto Zero SSR - 3RF22 45 mm Ponto Zero Trifásico

More information

Three-phase monitoring relay CM-PFE

Three-phase monitoring relay CM-PFE Data sheet Three-phase monitoring relay CM-PFE The CM-PFE is a three-phase monitoring relay that monitors the phase parameter phase sequence and phase failure in three-phase mains. 2CDC 251 005 S0012 Characteristics

More information

DEK-REL- 24/1/SEN. Extract from the online catalog. Order No.: 2964050

DEK-REL- 24/1/SEN. Extract from the online catalog. Order No.: 2964050 Extract from the online catalog DEK-REL- 24/1/SEN Order No.: 2964050 Relay terminal block for sensor, with soldered-in miniature relays, contact (AgNi+Au): small to medium loads, 1 N/O contact, input voltage

More information

Thermal-Magnetic Circuit Breaker 3120-...-M1-..

Thermal-Magnetic Circuit Breaker 3120-...-M1-.. Thermal-Magnetic Circuit Breaker -...-M-.. Description Single or two pole rocker switch/thermal-magnetic circuit breaker with trip-free mechanism (S-type TM CBE to EN 34). The addition of a magnetic tripping

More information

Residual Current Protective Devices

Residual Current Protective Devices Residual Current Protective Devices /2 Introduction / 5SM3 RCCBs /9 SIQUENCE, 5SM3 and 5SU1 universal -sensitive RCCBs, type B and type B+ /12 Additional components /1 5SM2 RC units /18 5SU1 RCBOs /25

More information

Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information

Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated Ordering information Connection technique Description Description Rated operational current Screw terminals 3 pole AC

More information

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection) Data sheet Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection) The temperature monitoring relays CM-TCS monitor overtemperature,

More information

48 SERIES Relay interface modules 10 A

48 SERIES Relay interface modules 10 A 48 Relay interface modules 10 A 1 CO relay interface modules, mm wide Ideal interface for PLC and electronic systems Type 48.P3 1 CO 10 A s Type 48.31 1 CO 10 A s AC coils or DC sensitive coils Supply

More information

BETA Protecting SITOR Semiconductor Fuses

BETA Protecting SITOR Semiconductor Fuses BETA Protecting SITOR Semiconductor Fuses /2 Product overview /3 /17 SITOR, cylindrical fuse design /22 SILIZED, NEOZED and DIAZED design Siemens ET B1 /2008 Product overview Overview Devices Page Field

More information

The complete range of consumer switchboards and switchgear

The complete range of consumer switchboards and switchgear Power Distribution The complete range of consumer switchboards and switchgear www.nhp.com.au/mod6 The MOD6 range of consumer switchboards and switchgear is specifically designed for domestic and commercial

More information

System pro M compact Miniature Circuit Breaker S 200/S 200 M

System pro M compact Miniature Circuit Breaker S 200/S 200 M Data Sheet System pro M compact Miniature Circuit Breaker S 200/S 200 M 2CDC021023S0012 2CDC021038S0012 The miniature circuit breakers of the System pro M compact series S 200 and S 200 M provide state-of-the-art

More information

Safety technique. Emergency stop module BO 5988 safemaster

Safety technique. Emergency stop module BO 5988 safemaster Safety technique Emergency stop module BO 5988 safemaster 0221562 Function diagram Pushbutton on Mains or emergencystop () K1 According to EC Directive for machines 98/37/EG According to IEC/E 60204-1

More information

Application Switchgear for industrial and commercial applications. U e V AC 230/400. 48 (per pole)

Application Switchgear for industrial and commercial applications. U e V AC 230/400. 48 (per pole) Overcurrentswitch,6A,2p,D-Char,AC Partno. FAZ-D6/2 Articleno. 278777 CatalogNo. FAZ-D6/2 Similar to illustration Deliveryprogramme Basic function Miniature circuit breakers Pole 2 pole Tripping characteristic

More information

Manual motor starter MS116

Manual motor starter MS116 Data sheet Manual motor starter MS116 Manual motor starters are electromechanical devices for motor and circuit protection. These devices offer local motor disconnect means, manual ON/ OFF control, and

More information

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous Safety relay for monitoring E-STOP pushbuttons. Approvals Unit features Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous Safe separation of

More information

Electronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet

Electronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet Characteristics Single-function OFF-delay timer for DC contactors, without auxiliary voltage Width.5 mm CDC 5 6 F3 Approvals A culus E CCC CT-VBS a Circuit diagram b Marker label Marks a CE b C-Tick Order

More information

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A 38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical Relays

More information

Type: DILM32 10(24V50HZ) Article No.: 277247

Type: DILM32 10(24V50HZ) Article No.: 277247 Type: DILM32 10(24V50HZ) Article No.: 277247 Ordering information Rated operational current AC 3 400 V I e A 32 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase motors,

More information

BETA Switching. Switching Devices. 5TT5 8 Insta contactors, AC technology. Overview

BETA Switching. Switching Devices. 5TT5 8 Insta contactors, AC technology. Overview BETA Switching Siemens AG 200 5TT5 Insta contactors, AC technology Overview The 5TT5 Insta contactors are equipped with an AC magnetic system and are ideal for use under harsh conditions. The auxiliary

More information

Circuit Breakers. Next Generation of Protection Capabilities

Circuit Breakers. Next Generation of Protection Capabilities Circuit Breakers Next Generation of Protection Capabilities Circuit Breaker Offering Rockwell Automation offers a full line of Allen-Bradley circuit breakers and motor protection devices to help meet many

More information

Type: DILM50(230V50HZ,240V60HZ) Article No.: 277830

Type: DILM50(230V50HZ,240V60HZ) Article No.: 277830 Type: DILM50(230V50HZ,240V60HZ) Article No.: 277830 Ordering information Rated operational current AC 3 400 V I e A 50 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase

More information

Bimetallic Overload Relay Specifications

Bimetallic Overload Relay Specifications Technical Data Bimetallic Overload Relay Specifications Bulletin Number 193K, 193T1 Topic Page Product Overview 2 Standards compliance and Certifications 2 General Specifications 193K 3 Approximate Dimensions

More information

49 Series - Relay interface modules 8-10 - 16 A. Features

49 Series - Relay interface modules 8-10 - 16 A. Features Features 1 & 2 Pole relay interface modules 5 µm Gold plate contacts for low level switching capability 49.31-50x0-1 Pole 10 A (screw terminal) 49.52-50x0-2 Pole 8 A (screw terminal) 49.72-50x0-2 Pole

More information

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application. 1SR 430 824 F9300 Features Monitoring of three-phase mains for phase sequence and failure Powered by the measuring circuit 2 c/o (SPDT) contacts 1 LED for status indication Approvals R: yellow LED - relay

More information

Technicaldata General

Technicaldata General Currenttransformer-operatedoverloadrelay,60-90A,1N/O+1N/C Partno. ZW7-90 Articleno. 002618 CatalogNo. XTOT090C3S Deliveryprogramme Product range ZW7 current transformer-operated overload relays Description

More information

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages Data sheet Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages The CM-ESS.2 is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of

More information

Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages

Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages Data sheet Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages The CM-ESS.M is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of

More information

Switching Devices. 8/2 Introduction. 8/5 5TE8 control switches. 8/8 5TE4 pushbuttons. 8/11 5TE5 light indicators. 8/13 5TE On/Off switches

Switching Devices. 8/2 Introduction. 8/5 5TE8 control switches. 8/8 5TE4 pushbuttons. 8/11 5TE5 light indicators. 8/13 5TE On/Off switches Siemens AG 2014 Switching Devices /2 Introduction /5 5TE control switches / 5TE4 pushbuttons /11 5TE5 light indicators /13 5TE On/Off switches /20 5TE DC isolators /22 5ST busbars for modular installation

More information

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 SERIES Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical

More information

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 55 Series - General purpose relays 7-10 A Features 55.12 55.13 55.14 Printed circuit mount, general purpose 2, 3 & 4 Pole relays 55.12-2 Pole 10 A 55.13-3 Pole 10 A 55.14-4 Pole 7 A AC coils & DC coils

More information

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23 Data sheet Thermistor motor protection relays CM-MSS.22 and CM-MSS.23 The thermistor motor protection relays CM-MSS.22 and CM-MSS.23 monitor the winding temperature of motors and protect them from overheating,

More information

How can a charging station for electric vehicles be set up simply and safely?

How can a charging station for electric vehicles be set up simply and safely? SB18 Building > Electromobility > Charging Station Design How can a charging station for electric vehicles be set up simply and safely? Requirement In order to supply electric vehicles with electric power,

More information

Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description Type: EASY719 DC RC Article.: 274119 Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC Description 12 digital inputs (4 inputs available as analog inputs) 6 relay outputs LCD display

More information

Catalog. Modular DIN rail components Installation contactors

Catalog. Modular DIN rail components Installation contactors Catalog Modular DIN rail components Installation contactors 0 CDC00C00 Installation contactors Benefits and features Overview Ordering details ESB installation contactors ESB0 ESB ESB0 ESB 7 EN installation

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Unit features Safety features Gertebild ][Bildunterschrift_NOT_Sch.tuer_Licht Safety relay for monitoring E-STOP pushbuttons, safety gates and light beam devices Approvals Gertemerkmale Positive-guided

More information

NF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals

NF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals Technical Datasheet 1SBC101433D0201 28/03/11 NF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals NF(Z) contactor relays are used for switching auxiliary and control circuits.

More information

3RT1015-1BB41 CONTACTOR, AC-3 3 KW/400 V,

3RT1015-1BB41 CONTACTOR, AC-3 3 KW/400 V, Automation Technology > Industrial Controls > Switching Devices > Contactors and Contactor Assemblies > Power Contactors for Switching Motors > Contactors SIRIUS 3RT10, 3-pole, 3... 250 kw 3RT1015-1BB41

More information

AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals

AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals Technical Datasheet 1SBC101403D0201 24/03/11 AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals AF09(Z) contactors are used for controlling power circuits

More information

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller Overview/Modes of Operation Bulletin 150 Smart Motor Controller The SMC-3 is a compact, simple to use, solid-state motor controller designed to operate 3-phase motors. It features a built-in overload relay

More information

Type: DILM9 10(24VDC) Article No.: 276705

Type: DILM9 10(24VDC) Article No.: 276705 Type: DILM9 10(24VDC) Article No.: 276705 Ordering information Rated operational current AC 3 400 V I e A 9 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase motors, 50

More information

MOTOR PROTECTIVE DEVICES

MOTOR PROTECTIVE DEVICES W MOTOR PROTECTIVE DEVICE, SERIES MP 206 BE400206 BE400306 Inherently stable without back-up fuseup to 4 A at 400 V AC, > 4 A main back-up fuse 100 A gl Thermal and magnetic release Terminal and accessory

More information

Feed-through terminal block - SSK 110 KER-EX - 0502058

Feed-through terminal block - SSK 110 KER-EX - 0502058 Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's documentation. Our General Terms of Use for Downloads are valid

More information

ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories

ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories 2CDC 251 014 F0t09 Features Monitoring of three-phase mains for grid feeding Type-tested in accordance with DIN V VDE V 0126-1-1: February 2006 Neutral conductor connection configurable Can also be used

More information

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages Data sheet Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages The CM-ESS.2 is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of

More information

SURGE PROTECTIVE DEVICES

SURGE PROTECTIVE DEVICES SURGE PROTECTIVE DEVICES 1. INTRODUCTION In order to ensure safety of people, protection of equipment and, to a certain extent, continuity of supply, insulation co-ordination aims at reducing the likelihood

More information

Manual Motor Starter MS 116 up to 16 A Technical Data

Manual Motor Starter MS 116 up to 16 A Technical Data Manual Motor Starter MS 116 up to 16 A Technical Data Type MS 116 Standards: Major International IEC 60 947-4-1 / IEC 60 947-2 and European Standards EN 60 947-4-1 / EN 60 947-2 Approvals, Certificates

More information

TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC - 0.5 A - M8 connector

TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC - 0.5 A - M8 connector Product datasheet Characteristics TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC - 0.5 A - M8 connector Main Range of product Product or component type Range compatibility Enclosure material Bus

More information

Uncompromising safety and comfort Miniature Circuit Breaker SU 200 M for branch circuit protection per UL and CSA

Uncompromising safety and comfort Miniature Circuit Breaker SU 200 M for branch circuit protection per UL and CSA Uncompromising safety and comfort Miniature Circuit Breaker SU 200 M for branch circuit protection per UL and CSA Miniature Circuit Breaker SU 200 M The next generation MCB for UL/CSA applications within

More information

Analog signal converters CC-E I/I Current / current isolators

Analog signal converters CC-E I/I Current / current isolators ata sheet Analog signal converters CC-E I/I Current / current isolators The CC-E I/I is an isolator for the electrical isolation of current signals without auxiliary supply. It allows the isolation between

More information

ABB i-bus KNX Switch Actuator, x-fold, 16/20 A, MDRC SA/S x.16.6.1, 2CDG 110 1xx R0011

ABB i-bus KNX Switch Actuator, x-fold, 16/20 A, MDRC SA/S x.16.6.1, 2CDG 110 1xx R0011 , 2CDG 110 1xx R0011 SA/S 8.16.6.1 2CDC 071 006 S0010 The 16/20 A Switch actuators are modular installation devices in Pro M Design for installation in the distribution board. The devices are especially

More information

Three-phase monitoring relays CM-PSS CM-PSS.31 and CM-PSS.41

Three-phase monitoring relays CM-PSS CM-PSS.31 and CM-PSS.41 Data sheet Three-phase monitoring relays CM-PSS CM-PSS.31 and CM-PSS.41 The three-phase monitoring relays CM-PSS.x1 monitor the phase parameters phase sequence, phase failure as well as over- and undervoltage.

More information

PHOENIX CONTACT - 2012-12-14. Features

PHOENIX CONTACT - 2012-12-14. Features Electronic monitoring relay for phase sequence, phase failure, and asymmetry monitoring Data sheet 101748_en_03 1 Description PHOEIX COTACT - 2012-12-14 Features Increasingly higher demands are being placed

More information

8146/5 Series Breaker Panelboards

8146/5 Series Breaker Panelboards 8146/5 Series Breaker Panelboards DISTRIBUTION BREAKER PANELBOARDS FOR HAZARDOUS & CORROSIVE ENVIRONMENTS Breaker Panels Features: Wide variety of Flameproof branch circuit breakers for Zone 1 & Division

More information

CompactLogix Power Supplies Specifications

CompactLogix Power Supplies Specifications Technical Data CompactLogix Power Supplies Specifications 1768 CompactLogix Power Supplies Catalog Numbers 1768-PA3, 1768-PB3 1769 Compact I/O Power Supplies Catalog Numbers 1769-PA2, 1769-PB2, 1769-PA4,

More information

RY2 miniature industrial relays

RY2 miniature industrial relays 6 RY2 Relays of general application For plug-in sockets, 35 mm rail mount acc. to PN-EN 60715 or on panel mounting Flat insert connectors - faston x 0,5 mm Recognitions, certifications, directives: RoHS,

More information

Example of use: Fuse for a solenoid valve. If the fuse is defective, no information is sent to the electronic component.

Example of use: Fuse for a solenoid valve. If the fuse is defective, no information is sent to the electronic component. Overview Switch and button modules The dimensions of the switch and button modules are adapted to the electronic components in the integral housing. The modules are equipped with the universal clip-on

More information

Redundancy Module QUINT-DIODE/40

Redundancy Module QUINT-DIODE/40 Redundancy Module QUT DIODE provides: 00% decoupling of power supplies connected in parallel Can be installed in potentially explosive areas Load currents up to 60 A supported Easy assembly by snapping

More information

LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A - 220 V AC coil

LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A - 220 V AC coil Product data sheet Characteristics LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 -

More information

Fuses for Semiconductor Protection - Cylindrical Fuses. Class: Voltage ratings: Current ratings: Standards: Approvals: Features and Benefits

Fuses for Semiconductor Protection - Cylindrical Fuses. Class: Voltage ratings: Current ratings: Standards: Approvals: Features and Benefits Fuses for Semiconductor Protection - Cylindrical Fuses SIBA cylindrical Ultra-Rapid fuses are available in six different sizes They can be ordered with an integral striker for blown fuse indication or

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Unit features Safety features gang engertebild ][Bildunterschrift_NOT_Sch.tuer_Licht Safety relay for monitoring E-STOP pushbuttons, safety gates and light beam devices Approvals Gertemerkmale Positive-guided

More information

ABB i-bus KNX Switch Actuator, x-fold, 16 A, MDRC SA/S x.16.2.1, 2CDG1101xxR0011

ABB i-bus KNX Switch Actuator, x-fold, 16 A, MDRC SA/S x.16.2.1, 2CDG1101xxR0011 Technical Data 2CDC505051D0205 ABB i-bus KNX Product description Switch Actuators SA/S x.16.2.1, 16 A are modular installation devices in ProM design for installation in the distribution board. They are

More information

Digital input modules

Digital input modules 8 172 TX-I/O Digital input modules TXM1.8D TXM1.16D Two fully compatible versions: TXM1.8D: 8 inputs, each with a three-color LED (green, yellow or red) TXM1.16D: As TXM1.8X, but 16 inputs, each with a

More information

Plug and Socket Devices CES 63 A Series 8579

Plug and Socket Devices CES 63 A Series 8579 www.stahl.de > Switch socket / plug 63 A > Large switch handle with clear switch position indication padlockable in 0- and I-position > Low insertion and withdrawal forces through individually encapsulated

More information

1 pole, 16 A Screw terminal connection 35 mm rail (EN 60715) mounting. 2 pole, 8 A Screw terminal connection 35 mm rail (EN 60715) mounting

1 pole, 16 A Screw terminal connection 35 mm rail (EN 60715) mounting. 2 pole, 8 A Screw terminal connection 35 mm rail (EN 60715) mounting Series - Relay interface modules 8-10 - 16 A Features.01.02 1 & 2 pole relay interface modules, screw terminal socket, mm wide. Ideal interface for PL and electronic systems.01-1 Pole 16 A.02-2 Pole 8

More information

MasterINTERFACE 39 Series - Relay interface modules

MasterINTERFACE 39 Series - Relay interface modules MasterINTERFACE 39 Series - Relay interface modules Common features Space saving 6.2 mm wide Connections for 16-way jumper link Integral coil indication and protection circuit Secure retention and easy

More information

Switching Devices Contactors and Contactor Assemblies Special Applications

Switching Devices Contactors and Contactor Assemblies Special Applications Switching Devices Contactors and Contactor Assemblies Special Applications Price groups PG 1B, 1H /2 Introduction Contactors for special applications / SIRIUS 3RT1 contactors for resistive loads (AC-1),

More information

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw 4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and

More information

Emergency stop As an emergency switching off/emergency stop device. Standards According to IEC/EN 60204-1, VDE 0113 Part 1

Emergency stop As an emergency switching off/emergency stop device. Standards According to IEC/EN 60204-1, VDE 0113 Part 1 MainswitchSurfacemounting Partno. P3-63/I4/SVB Articleno. 207343 CatalogNo. SP3-063-I4CRQ IP65 Deliveryprogramme Product range Switch-disconnectors Basic function Main switches Maintenance switches Manual

More information

Soft Starter. Product Description. Ordering Code. Type Selection. Selection Guide RSG D 40 16 E 0 VD00

Soft Starter. Product Description. Ordering Code. Type Selection. Selection Guide RSG D 40 16 E 0 VD00 Soft Starter Three Phase General Purpose Soft Starters Type RSGD Soft starting and soft-stopping of 3-phase squirrel cage motors 45mm wide IP20 housing Operational Voltage: RSGD40 (220-400V), RSGD60 (220-600V)

More information

Contact expander modules

Contact expander modules Gertebild ][Bildunterschrift Kontakterweiterungen Contact expansion module for increasing the number of available contacts Approvals Zulassungen Unit features Gertemerkmale Positive-guided relay outputs:

More information

Dimensions, Inches (mm) No. of Poles Width Height Depth 2, 3 8.25 (210) 16 (407) 5.5 (140) 4 11.125 (283) 16 (407) 5.5 (140)

Dimensions, Inches (mm) No. of Poles Width Height Depth 2, 3 8.25 (210) 16 (407) 5.5 (140) 4 11.125 (283) 16 (407) 5.5 (140) 9-10N Supersedes Selection Data 9-10N, pages, 1-, dated dated March March 1995 1995 Mailed to: E, D, C/9-100A, 31-A, INTERRUPTING CAPACITY RATINGS IEC 947- Interrupting Capacity s➀ Interrupting Capacity

More information

Product Guide. Cable-in / cable-out miniature circuit breakers and supplementary protectors

Product Guide. Cable-in / cable-out miniature circuit breakers and supplementary protectors Product Guide Cable-in / cable-out miniature circuit breakers and supplementary protectors Cable-in / cable-out miniature circuit breakers and supplementary protectors Eaton offers a complete line of

More information

Mini Motor Contactor J7KNA Main contactor Accessories Approved Standards Standard Guide No (US,C) Ordering Information tage Model Number Legend gear

Mini Motor Contactor J7KNA Main contactor Accessories Approved Standards Standard Guide No (US,C) Ordering Information tage Model Number Legend gear Mini Motor Contactor J7KNA ) Main contactor AC & DC operated Integrated auxiliary contacts Screw fixing and snap fitting (35 mm DIN-rail) Range from 4 to 5.5 (AC 3, 380/415V) 4 -main pole version (4 AC

More information

38 SERIES. Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.

38 SERIES. Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6. 38 Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit 6.2 mm wide EMR - DC, AC or AC/DC

More information

CQM1-SF200/CS1W-SF200

CQM1-SF200/CS1W-SF200 Safety Relay Unit ( I/O Unit Type) CQM1-SF200/CS1W-SF200 CSM_CQM1-SF200_CS1W-SF200_DS_E_2_1 A Safety Relay Unit That Functions as a I/O Unit. Less Installation Space and Wiring Required. Safety Relay Unit

More information

HSP GmbH Zum Handwerkerhof 2 90530 Wendelstein Tel. 09129 / 2852-0 Fax: 09129 / 2852-11 Web: www.hsshsp.de EMAIL: HSP@hsshsp.de NTG-3000.

HSP GmbH Zum Handwerkerhof 2 90530 Wendelstein Tel. 09129 / 2852-0 Fax: 09129 / 2852-11 Web: www.hsshsp.de EMAIL: HSP@hsshsp.de NTG-3000. NTG-3000 Transducer Data Sheet Document Version 2.8 Page 1 of 10 Versions / Revisions: Document Creation Author Description version date 2.0 2012-07-25 P. Compensis First official version 2.1 2012-08-24

More information

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Features SELV Compliant No Detection Passive Injector Gigabit Compatible Full Protection

More information

ZS6-S Screw Clamp Terminal Blocks Disconnect with blade

ZS6-S Screw Clamp Terminal Blocks Disconnect with blade Technical Datasheet SNK646D00 Catalogue Page SNK646S00 ZS6-S Screw Clamp Terminal Blocks Disconnect with blade - Ease your disconnect operations with the disconnect blade operated by hand or with a screwdriver,

More information

Technical Manual Functional Description for S800-RSU-H / S800W-RSU 2CCC413022M0205. 8201 Schaffhausen 1 / 10

Technical Manual Functional Description for S800-RSU-H / S800W-RSU 2CCC413022M0205. 8201 Schaffhausen 1 / 10 ABB ABB Schweiz AG Technical Manual Functional Description for S800-RSU-H / S800W-RSU 2CCC413022M0205 09.04.2014 Page: 8201 Schaffhausen 1 / 10 Please use also the assembly instruction S800-RSU-H Remote

More information

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1 Power Supply Unit, Primary Switched, Narrow Design MINI POWER provides: Extra narrow design with widths of 22.5 mm, 45 mm, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a wide-range input

More information

ZS25 Screw Clamp Terminal Blocks Feed-through

ZS25 Screw Clamp Terminal Blocks Feed-through Technical Datasheet SNK668D0 Catalogue Page SNK678S0 ZS Screw Clamp Terminal Blocks Feed-through Save space by connecting conductors up to mm² AWG in just mm 0.47 in spacing. SNK68V004 SNK004F0000 D CAD

More information

Contact expansion modules

Contact expansion modules Gertebild ][Bildunterschrift Kontakterweiterungen Contact for increasing the number of available contacts Approvals Zulassungen Unit features Gertemerkmale Positive-guided relay outputs: 4 safety contacts

More information

W DATA SHEET: RESIDUAL CURRENT CIRCUIT BREAKER 25-100A, SERIES BCF0 AND BCF6

W DATA SHEET: RESIDUAL CURRENT CIRCUIT BREAKER 25-100A, SERIES BCF0 AND BCF6 W DATA SHEET: RESIDUAL CURRENT CIRCUIT BREAKER 25-100A, SERIES BCF0 AND BCF6 W SCHRACK-INFO Any mains connection If using 4-pole. switches with 3 or 2-poles, ensure connection acc. to assembly instructions

More information

CUSTOMER CLASS FILE. ABB STOTZ-KONTAKT GmbH 3215-30 098793_0_000

CUSTOMER CLASS FILE. ABB STOTZ-KONTAKT GmbH 3215-30 098793_0_000 Seite 1 von 6 Certification Record CUSTOMER CLASS FILE ABB STOTZ-KONTAKT GmbH 3215-30 098793_0_000 Eppelheimer Strasse 82, SUPPLEMENTARY PROTECTORS- COMPONENT ACCEPTANCE PROGRAM Heidelberg Baden-Wurttemberg

More information

Signaling Lights. LH Series Surface Mount Indicators. Part Numbers. Jumbo Dome (one color) Jumbo Dome (two color)

Signaling Lights. LH Series Surface Mount Indicators. Part Numbers. Jumbo Dome (one color) Jumbo Dome (two color) Innovative indicators in a slim & stylish design. uces installation space. LH Series Surface Mount Indicators Key features of the LH series include: Direct mounting on surfaces such as panels, aluminum

More information