1 Technical Bulletin Network Room Module Issue Date January 22, 2010 Network Room Module Introduction to Network Room Module (NRM)... 3 Concepts... 4 Features... 4 Controls... 5 Functions and Setup of the Network Room Module... 6 Network Room Module Parameters (Room Sensor Object) Installing and Commissioning the Network Room Module Introduction North American Emissions Compliance Key Concepts Location of the Network Room Module Dimensions of the Network Room Module Wiring Addressing Service Port Commissioning the Network Room Module Procedure Overview Detailed Procedures Opening the Network Room Module Mounting the NRM Directly on a Wall Surface Mounting the NRM (80 x 80 mm) on a Wall Surface Using the Plastic Base for Surface Mounting Mounting the NRM (80 x 80 mm) on a Recessed Wall Box Commissioning the NRM Module Johnson Controls, Inc. Code No. LIT

2 2 Network Room Module Technical Bulletin Troubleshooting Specifications and Ordering Codes Specifications and Technical Data Ordering Codes... 32

3 Network Room Module Technical Bulletin 3 Introduction to Network Room Module (NRM) Network Room Modules (NRMs) are electronic, wall-mountable temperature sensors designed to be used with the Facility Explorer field controllers. Note: See the Specifications and Ordering Codes section for details about compatible controllers. All NRM models monitor room or space temperature. In addition, you can order NRMs with a backlit Liquid Crystal Display (LCD) to display the room temperature and local setpoint. Graphical display symbols can indicate fan speed selection and the need for maintenance. Optional operating controls include a dial to locally adjust the space temperature setpoint, a push button to manually override the fan speed, and a push button to select Fahrenheit ( F) and Celsius ( C) units of measure. The NRM connects to the Remote Display link of the Facility Explorer field controller. Terminals are located in the mounting base for ease of wiring. The NRM is enclosed in an attractively styled plastic housing, which easily mounts on a wall. Figure 1: Network Room Modules

4 4 Network Room Module Technical Bulletin Concepts Features The NRM (Figure 2) is styled to blend with the decor of today s commercial and public buildings. Terminals are located in the mounting base for ease of wiring. The module also has a built-in temperature sensor used to measure space temperature for display and transmission to the connected controller. If the controller has its own space temperature sensor, then it communicates its temperature values to the module for display. Located on the front of the room command module are the operating controls and an LCD with three numerical digits and various operating mode symbols. With the NRM, you can: view the space (room) temperature view and manually adjust the space temperature setpoint manually override the speed of the fan in the controlled equipment see when the controller is in the Off mode see when a maintenance condition exists request the temporary occupied mode during unoccupied or standby mode operation by pressing a push button or rotating the dial change the temperature display units from F to C (North American models only) Some of these functions may not be available or are limited by the configuration of the module or controller.

5 Network Room Module Technical Bulletin 5 The NRM has a service port (located on the lower edge of the module). Use the service port to gain access to the serial bus for the host FX field controller. Two types of service ports are available (see Figure 2 for service port location). The service port for NRM model LP-NRM0xx-000C is a 4-pin connector and is used to interface with the FX Programming Key. The service port for NRM models LP-NRM5xx-000C and LP-NRM6xx-000C is a 6-pin Modular Jack connector and is used to interface with the Medium User Interface (MUI). Figure 2: Features of the Network Room Module Controls Table 1 shows how the dial and buttons are used in the NRM. Table 1: Controls Control Setpoint Dial Description Used to change the temperature setpoint value: turning right increases the setpoint and turning left decreases the setpoint. When you move the dial, the display shows the current space temperature setpoint. Used to override the fan status from Auto to Off, low, medium, or high speed. Fan Push Button F/ C F/ C Push Button Used to toggle the temperature display units between C and F.

6 6 Network Room Module Technical Bulletin Figure 3 shows the layout and symbols of the LCD, and Table 2 describes the symbols. Table 2: Symbols on the LCD Control Figure 3: LCD Symbol Options Description Temperature display digits Fan speed status bars low, medium, and high speed (high speed shown) C Celsius temperature unit F Fahrenheit temperature unit AUTO OFF The Auto icon indicates that the fan is in auto mode. The Off icon indicates that the fan has been manually set to Off (not running). The Maintenance icon indicates an off-normal condition that requires attention. The Occupancy Mode icon indicates the occupied/unoccupied mode of the controller (LP-NRM5xx-000C and LP-NRM6xx- 000C Series only). Functions and Setup of the Network Room Module The NRM is a network device with no hardware inputs or outputs and connects to the Facility Explorer controller via the display (or local link) bus. All the communication access and setup of the NRM is done through the controller where the NRM is connected. The configuration properties of the NRM are set in the Room Sensor object in the controller when the control application for the controller is generated in the FX Builder tool. When the application is downloaded to the controller, you use the FX CommPro N2, LON, or BACnet commissioning tool to monitor the network variables of the NRM in the Room Sensor object through the network profile of the controller. This section describes the various functions and display features of the NRM, the network variables used by each function, and the configuration properties used to set up each function.

7 Network Room Module Technical Bulletin 7 See Network Room Module Parameters (Room Sensor Object) for a detailed list of the variables and properties of the NRM. The names of the network variables and configuration properties appear in boldface type throughout this document. Note: After a power failure, the NRM restarts using the values in its configuration properties and any setpoint changes or fan speed overrides are cancelled. In particular, if you set the Setpoint Configuration to absolute, you should also set the Default Absolute Setpoint for the controlled space in case of a power interruption. The factory set value is 21 C (70 F). Display The NRM models with display are factory-configured to show space temperature. The models with the fan speed override function are configured for three-speed fan control. As soon as you connect the NRM to a controller with a configured Room Sensor object, the properties in the Room Sensor object transmit to the NRM and replace the factory set values. You can change the setpoint temperature by rotating the dial. The space setpoint value appears and blinks for a few seconds, waiting for a change. The NRM then confirms the change to the controller and displays the space temperature again (if enabled). In models with the fan speed override function, you can change the fan speed by pressing the fan push button. The fan status display cycles through the steps AUTO, OFF, Low Speed, Medium Speed, and High Speed, according to the fan configuration. If you set the Enable Space Temperature Display configuration property to disabled (OFF), the NRM always shows the space setpoint temperature and does not show the actual space temperature. Note: The network variable output Space Temperature Output always sends its internal space temperature value, even if the space temperature does not appear. Depending on the values of the Setpoint Configuration and Temperature Units configuration properties, the display shows either the absolute setpoint or the setpoint offset. The absolute setpoint is stored in the Setpoint Output (Absolute) network variable output. The setpoint offset is stored in the Setpoint Output (Offset) network variable output. Some space setpoint temperature display examples are shown in Figure 4 and Figure 5.

8 8 Network Room Module Technical Bulletin Figure 4: Absolute Setpoint Values in Celsius and Fahrenheit Units Figure 5: Relative (Offset) Setpoint Values in Celsius Units Setpoint Adjustment You can change the value of the setpoint by rotating the NRM dial to the right to increase the setpoint, and to the left to decrease the setpoint. The display stops at the high and low limits. The high and low limits are: ±3 C (±5 F) - if the NRM is configured to display the setpoint offset, or the values are defined in the Space Temperature Setpoint Low Limit and Space Temperature Setpoint High Limit configuration properties, if the NRM is configured to display the absolute setpoint. The default absolute setpoint limits are 12 and 28 C (53.5 and 82.5 F). When you adjust the setpoint, the value you enter is transmitted to the controller via either the network variable output Setpoint Output (Absolute) or Setpoint Output (Offset), depending on the value of Setpoint Configuration. The network variable that is not used is set to an invalid value. The Setpoint Output (Absolute) value when the NRM starts up is determined by the Default Absolute Setpoint value in the Room Sensor object in the controller. The factory set value is 21 C (70 F). The Setpoint Output (Offset) value is zero at startup. Fan Speed Adjustment In NRM models with the fan speed override function, you can change the speed of the fan by pressing the fan push button until the desired speed appears on the fan speed bars. See Figure 6. The override value then transmits to the controller via the network variable output Fan Speed Override. When the fan is set to Off mode by an override command, the OFF symbol appears.

9 Network Room Module Technical Bulletin 9 When the fan is set to Auto mode, the Auto symbol appears, and the controller determines the fan speed using its internal control algorithm. Figure 6: Fan Speed Display in Manual Override The fan symbol ( ) is always shown, whether the fan is running or not. Examples of the fan speed display are shown in Table 3. Table 3: Examples of Fan Speed Display Control Description Fan speed was overridden to medium speed by the user. Fan speed is overridden to OFF by the user. Fan in AUTO mode no override by user. The actual fan speed is not shown. The type of fan is configurable in the property Fan Configuration for: None (no fan) There is no fan. The fan override function is disabled (Figure 7). Figure 7: No Fan Display One speed If you set the property to One speed fan, pressing the fan push button cycles the fan status: AUTO, OFF, and ON. The display fills all three fan bars to indicate the ON status. Two speed If you set the property to Two speed fan, pressing the fan push button cycles the fan status: AUTO, OFF, low, and high speed. The display shows two fan bars for low speed and three bars for high speed.

10 10 Network Room Module Technical Bulletin Three speed If you set the property to Three speed fan, pressing the fan push button cycles the fan status: AUTO, OFF, low, medium, and high speed. Occupancy Mode The LED display indicates the Effective Occupancy Status when the Enable Unoccupied State Blink configuration property is set to enabled (ON) and the network variable input Effective Occupancy Status value shows that the occupancy mode is UNOCCUPIED or STANDBY. See Figure 8 and Table 4. Figure 8: Occupancy Mode Icon for LP-NRM5xx-000C and LP-NRM6xx-000C Series NRMs Table 4: Effective Occupancy Status NRM Series Effective Occupancy Status Icon/Description LP-NRM0xx-000C Series LP-NRM5xx-000C and LP-NRM6xx-000C Series Occupied Unoccupied or Standby Occupied Unoccupied or Standby The display remains on. The display blinks off/on approximately every 3 seconds. This feature indicates to the unexpected occupant (or an occupant present during nonstandard hours) that the controller is not in the OCCUPIED mode. You can disable this feature by setting the Enable Unoccupied State Blink configuration property to disabled (OFF).

11 Network Room Module Technical Bulletin 11 Temporary Occupied Mode The Temporary Occupancy Mode Request output network variable normally reflects the value of the Effective Occupancy Status input network variable as received from the controller. In UNOCCUPIED or STANDBY mode, you can force the Temporary Occupancy Mode Request output variable to Temporary Occupied (BYPASS) mode for the time duration (in minutes) set in the configuration property Temporary Occupied Time. You achieve this Temporary Occupied mode when you press the fan push button or rotate the setpoint dial. The BYPASS state of the Temporary Occupancy Mode Request network variable is then transmitted to the connected controller to set the occupancy status of the controller to the Temporary Occupied (BYPASS) mode. When the temporary occupied time expires, the value of Temporary Occupancy Mode Request returns to the value of the Effective Occupancy Status input variable. This operation depends on the correct configuration of the application in the controller using FX Builder. Off Mode When the network variable input HVAC Application Mode has the OFF (state 6) value, the display shows OFF in the upper display field to indicate that no control action is possible. Figure 9: OFF Mode Display (HVAC Application Mode) Maintenance Icon The maintenance icon ( ) appears on the display when the configuration property Enable Maintenance Icon is enabled (ON) and one of the following conditions exists: The network variable input Display Maintenance Icon is ON. The control application in the controller determines the conditions for the network variable to be on. The internal space temperature value, as seen in Space Temperature Output, is unreliable (out of range). There is no communication with an FX controller. You can choose not to display the maintenance icon on the NRM by setting the configuration property Enable Maintenance Icon to disabled (OFF).

12 12 Network Room Module Technical Bulletin Back Light Time-out The LCD is back-lit in the NRM and lights up when the fan or F/ C push button is pressed or the dial is turned. The back-light time-out is set in the Back-light Time-out configuration property. The factory default setting is 30 seconds. A value of 0 disables the back-light; a value greater than 60 keeps the back-light permanently on. Temperature Units on Display In NRM models without the F/ C push button, the temperature units on the display are determined by the Temperature Units configuration property. In NRM models with the F/ C push button, the Temperature Units configuration property determines the temperature units on the display at start-up, but the units are toggled between F and C by pressing the push button. Physical Address The NRM has a physical address that you must set in the PhysicalAddress configuration property in the Room Sensor object of the FX controller. Non-addressable NRM models have a fixed address of 191, which is the default setting of the Room Sensor object. Addressable NRM models include DIP switches, allowing you to set the physical address between 191 and 194. Note: You must cycle power to the NRM (disconnect/reconnect the NRM or cycle power to the field controller) for the address change to take effect.

13 Network Room Module Technical Bulletin 13 Network Room Module Parameters (Room Sensor Object) Table 5, Table 6, and Table 7 list the network variables and configuration properties available in the NRM Room Sensor object. You must create an instance of this object in the FX controller for the connected NRM. The controller automatically transfers the configuration data to the NRM module and transmits and receives the network variable information over the local link bus. Note: The configuration properties are also available as network variable inputs so that they can be dynamically changed in the application in the controller at runtime. Table 5: Network Variable Inputs Description Variable Name Data Type Space Temperature Override SpaceTempOverride Analog temperature Effective Occupancy Status EffectOccupancyStatus 1 Enumeration Occupancy HVAC Application Mode HVACMode 2 Enumeration HVAC Mode Display Maintenance Icon MaintenanceIcon 3 Binary logic 1. 0=Occupied, 1=Unoccupied, 2=Temp.Occ (Bypass), 3=Standby, 4-255=Invalid (Null). 2. 6=Off, All except 6 and 255=On, 255=Invalid. (When Off, the LCD shows OFF.) 3. 0=Off, 1=On, 2 to 255=Invalid. (When On, the LCD shows the maintenance icon.) Table 6: Network Variable Outputs Name/Description Variable Name Data Type Setpoint Output (Absolute) AbsoluteSetpoint Analog temperature Space Temperature Output SpaceTempVal Analog temperature Sends displayed temperature: either valid input from space temperature override input or value of internal sensor Setpoint Output (Offset) OffsetSetpoint Analog temp diff. Fan Speed Override FanSpeedOverride 1 Enumeration Fan Speed auto, off, low, medium, high Temporary Occupancy Mode Request Occupancy Mode 2 Enumeration - Occupancy 1. 0=Auto, 1=Off, 2=Low Speed, 3=Medium Speed, 4= High Speed 3, 5-255=Auto 2. 0=Occupied, 1=Unoccupied, 2=Temp.Occ (Bypass), 3=Standby, 4-255=Invalid (Null).

14 14 Network Room Module Technical Bulletin Table 7: Configuration Properties Name/Description Property Name Data Type Default Limits Space Temperature Setpoint High Limit Space Temperature Setpoint Low Limit Temporary Occupied Time SpaceTempSetptHighLimit Analog - Temperature SpaceTempSetptLowLimit Analog - Temperature 28.0 C (82.5 F) 12.0 C (53.5 F) Max. 40 C (99.5 F) Min. 0 C (32.0 F) TemporaryOccupiedTime Analog - minutes 60 min 0 to 255 min Fan Configuration FanConfiguration 1 Enumeration fan Three speed 0, 1, 2, 3 speed Setpoint SetpointConfig 2 Binary logic 0 = Absolute Absolute or Offset Configuration (absolute or offset) Temperature Units TemperatureUnits 3 Binary logic 0 = SI ( C) SI or US (display units C or F) Enable Space Temperature Display (defines if space temperature is shown) EnableSpaceTempDisplay Binary logic ON=Enabled OFF or ON Default Absolute Setpoint DefaultAbsoluteSetpt Analog - temperature 21 C (70 F) 0 to 40 C ( F) Back-light Time-out BackLightTime 4 Analog - seconds 30 sec 0 to 60 seconds Temperature Sensor Offset TemperatureOffset Analog temp. diff. 0 C ±5 C (±9 F) Enable Unoccupied EnableUnoccupiedBlinking Binary logic ON=Enabled OFF or ON State Blink Enable Maintenance EnableMaintDispIcon Binary logic ON=Enabled OFF or ON Icon Physical Address PhysicalAddress Integer to =None, 1=One speed fan, 2=Two speed fan, 3=Three speed fan 2. 0=Absolute Setpoint, 1=Offset Setpoint (±3 C) (±5 F) 3. 0=SI ( C), 1=US ( F) 4. 0=No back-light, >60=Back-light always on

15 Network Room Module Technical Bulletin 15 Installing and Commissioning the Network Room Module Introduction The Network Room Module is designed to mount directly on a wall surface in the room you want to control. Separate kits are also available for wall surface mounting with conduits and recessed wall box mounting (see Ordering Codes). The wiring enters the module from the back. IMPORTANT: Use this Network Room Module only as an operating control. Where failure or malfunction of the NRM could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the NRM. North American Emissions Compliance United States This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy, and if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his/her own expense. Canada This Class (A) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations. Cet appareil numérique de la Classe (A) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.

16 16 Network Room Module Technical Bulletin Key Concepts Location of the Network Room Module Choose a location for the NRM, taking the following information into consideration: Place the NRM where the occupant can easily read the LCD and use the controls. Place the NRM where the ambient temperature is representative of the general room conditions if you want to use the built-in temperature sensor to measure space temperature. For example, there should be sufficient air circulation. Avoid cold or warm air drafts, radiant heat, and direct sunlight. Place some insulating material in the wiring access hole or conduit to prevent the introduction of air from outside the room. IMPORTANT: The installation of electrical wiring must conform to local codes and should be carried out by authorized personnel only. Users should ensure that all Johnson Controls products are used safely and without risk to health or property.

17 Network Room Module Technical Bulletin 17 Dimensions of the Network Room Module Figure 10: Network Room Module Dimensions, mm (in.)

18 18 Network Room Module Technical Bulletin Wiring Terminations are made on the terminal block in the base of the module, which is accessible after removing the cover from the base. The screw terminals accept up to 1.5 mm 2 (16 AWG) wires, and Figure 11 shows the terminal block connections. Complete and verify all wiring connections before you apply power to the module N2 RT+ COM N2 RT- POWER SUPPLY INPUT Figure 11: Wiring to the NRM Follow this information when you wire an FX controller to an NRM:! CAUTION: Risk of Electric Shock. Disconnect power supply before making electrical connections to avoid electric shock. IMPORTANT: The LP-NRM0xx-000C Series NRM accepts VAC or VDC power. The LP-NRM5xx-000C and LP-NRM6xx-000C Series accept VDC power only. Connect power to terminals 11 (+ VDC or VAC) and 14 (- VDC or VAC). You may take power from the FX controller (15 VDC). Note: The COM terminal of the NRM is connected to the common potential of the FX controller. If an independent power supply is used for the NRM, ensure the proper connection of the multiple power supplies to avoid a short circuit through the NRM module or FX controller. Use screw terminals 12 (N2 RT+), 13 (N2 RT-) and 14 (COM) to connect to the FX controller display (local ink) bus terminals (LL+, LL-, and COM, respectively). This is an RS-485 bus where the wires are polarity sensitive. A common or reference wire is required and the N2 Open protocol is used. All the installation rules for the N2 bus apply to this connection. If shielded cable is used for the network wiring, connect the shields together and insulate with tape. Do not use the COM terminal for cable shields.

19 Network Room Module Technical Bulletin 19 Note: The device does not require a ground/earth connection. IMPORTANT: Cables and wiring at Safety Extra Low Voltage (SELV) and Class 2 wiring (North America) must be separated from power line voltage wiring. A minimum separation distance of 30 cm (12 in.) is recommended. Do not run extra low voltage cables parallel to power line voltage cables for long distances greater than 3 m (10 ft). Do not run extra low voltage wiring close to transformers or high frequency generating equipment. Addressing Non-addressable NRM models have a fixed physical address of 191. For those models which are addressable, the NRM s address must be set using its dual-switch DIP switch block, located on the printed wiring board. See Figure 12 and Table 8 for details on addressing the NRM. Note: You must cycle power to the NRM (disconnect/reconnect the NRM or cycle power to the field controller) for the address change to take effect. Figure 12: Dual-Switch DIP Switch Block Table 8: NRM Addressing DIP Switch Address Switch 2 Switch OFF OFF 192 OFF ON 193 ON OFF 194 ON ON

20 20 Network Room Module Technical Bulletin Service Port The NRM features a service port which is located on the bottom-right side of the module (Figure 13 and Figure 15). Two types of service ports are supported, depending on the NRM model number. The service port for NRM model LP-NRM0xx-000C is a 4-pin connector and is used for the connection of the FX Programming Key (Figure 14) to download applications to the connected FX field controller over the local link bus. The connector provides access to the local link bus and a power supply of 9 VDC for the Programming Key. Figure 13: LP-NRM0xx-000C Series Service Tool Socket (4-pin Connector) Figure 14: FX Programming Key

21 Network Room Module Technical Bulletin 21 The service port for NRM models LP-NRM5xx-000C and LP-NRM6xx-000C is a 6-pin Modular Jack connector and is used for the connection of the Medium User Interface (Figure 15) to provide advanced monitoring and adjustment access to the connected FX field controller over the local link bus. The connector provides access to the local link bus and a power supply of 15 VDC for the MUI. Tool Port Pin Number Assignment for MUI Interface Cable Printed Circuit Board +15 VDC Common +15 VDC Common RT - RT + Figure 15: LP-NRM5xx-000C and LP NRM6xx-000C Series Service Tool Socket (6-pin Modular Jack Connector)

22 22 Network Room Module Technical Bulletin Commissioning the Network Room Module General The FX CommPro N2, LON, or BACnet commissioning tool is required to commission the NRM room module and set up the parameters of the module in the connected FX controller. The commissioning tool is connected to the FX controller. You access the network variables and configuration properties of the NRM through the network profile of the FX controller application. Refer to the FX Tools Software Package FX Builder User Guide (LIT ) for details on how to build an application and the corresponding network profile for either an N2, LON, or BACnet MS/TP network (according to the network interface card installed in the FX controller). Temperature Sensor During commissioning, if you find that the internal temperature sensor does not read the exact value measured by a calibrated temperature monitor, or you wish to compensate for a poorly located sensor, you can adjust the space temperature value using the configuration property Temperature Sensor Offset. Do not use this parameter to compensate for a faulty sensor in the NRM module. Replace the module if the reading is more than a few degrees too high or low.

23 Network Room Module Technical Bulletin 23 Procedure Overview Table 9: Installing and Commissioning the Network Room Module To Do This Follow These Steps Open the Room Command Module Mount the NRM directly on a wall surface Mount the NRM (80 x 80 mm) on a wall surface using the Plastic Base for Surface Mounting Mount the NRM (80 x80 mm) on a Recessed Wall Box Mounting Kit Commission the NRM Insert the pointed tool or special tool available from Johnson Controls into the narrow slot at the center top of the module. While pressing down gently, pry the cover away from the base. In North American models, the anti-tamper screw must first be removed. Hold the module base on the wall to cover the electrical outlet and mark the position of at least two holes. Drill holes and insert plastic plugs (wall anchors) into holes if required. Mount the module base on the wall and secure with at least two screws. Use insulating material to prevent air from the wiring channel from entering the room module. Remove one of the conduit notches on the plastic base for surface mounting. Mark the position of the holes on the wall and drill holes 5 mm in diameter. Insert plastic plugs (wall anchors) into holes. Position and fix the mounting base to the wall using the two long screws provided in the kit. Fix the base of the NRM to the surface mounting base using the two short screws provided in the kit. Turn the screws on the recessed wall box mounting kit to adjust the assembly to the depth of the wall box. Insert the kit into the wall box, and tighten the other screws until the prongs clamp properly in the wall box. Mount the NRM module base on the kit by inserting the two screws included in the kit into two opposite holes of the kit. Connect and check the power and network wiring from the module to the FX controller. Apply power to the FX controller (or switch on the separate power source if used). Connect the FX CommPro N2, LON, or BACnet software tool to the FX controller to monitor the NRM network variables within the control application. Use the setpoint dial and fan push button to verify that the module is operating and sending and receiving valid data from the controller. Detailed Procedures Opening the Network Room Module To open the Network Room Module: 1. (North American models only) Remove the anti-tamper screw in the top of the module enclosure with a small cross-head screwdriver (Figure 16). 2. Remove the module cover from the base by inserting a pointed tool into the narrow slot at the center top of the cover. A special tool is available from Johnson Controls (see Ordering Codes).

24 24 Network Room Module Technical Bulletin Figure 16: FX Tool to Open Module 3. While pressing down gently, pry the cover away from the base. As the two parts separate, remove the tool and continue to pull the cover away from the base until the cover is free. 4. To reassemble the room command module, place the cover over the lower edge of the base, and push the upper part of the cover until it clicks firmly into place. 5. Replace the anti-tamper screw in the top of the module enclosure (North American models only). Mounting the NRM Directly on a Wall Surface To mount the NRM directly on a wall surface (see Figure 17 and Figure 18 for dimensions): 1. Hold the module base on the wall to cover the electrical outlet and mark the position of at least two holes. Drill holes and insert plastic plugs (wall anchors) into holes. 2. Mount the module base on the wall and secure with at least two screws.

25 Network Room Module Technical Bulletin 25 Figure 17: Module Base Dimensions (80 x 80 mm) Figure 18: Module Base Dimensions (120 x 80 mm)

26 26 Network Room Module Technical Bulletin Mounting the NRM (80 x 80 mm) on a Wall Surface Using the Plastic Base for Surface Mounting To mount the NRM on a wall surface using the plastic base for surface mounting (see Figure 21 for dimensions): 1. Remove one of the conduit notches (A) with a suitable cutting tool (Figure 19). U P B OB EN A Figure 19: Notches and Drill Holes of Plastic Base 2. Mark the position of the holes (B) on the wall and drill holes 5 mm (.20 in.) in diameter (Figure 20). Insert plastic plugs (wall anchors) into holes. 3. Position and fix the mounting base to the wall using the two long screws (C) provided in the kit (Figure 20). C D Conduit Figure 20: Side View of Plastic Base with Module Base Mounted 4. Fix the base of the NRM to the mounting base using the two short screws (D) provided in the kit.

27 Network Room Module Technical Bulletin 27 U P OB EN Figure 21: Dimensions (mm) of the Plastic Surface Mounting Base Mounting the NRM (80 x 80 mm) on a Recessed Wall Box To install the recessed wall box mounting kit (see Figure 25 for dimensions): 1. Turn the screws (A) to adjust distance (D) to match the depth of the wall box (Figure 22): A D Figure 22: Side View of Wall Box Mounting Kit 2. Insert the kit into the wall box, positioning it as shown in Figure 23.

28 28 Network Room Module Technical Bulletin B C C Figure 23: Front View of Wall Box Mounting Kit 3. Tighten screws (B) until the prongs clamp properly in the wall box. 4. Mount the base of the module on the kit, as shown in Figure 24, using the two screws included in the kit and inserting them into two opposite holes of the four holes marked (C). C Figure 24: Wall Box Mounting Kit with Module Base Wall-Box.cdr Figure 25: Dimensions (mm) of the Recessed Wall Box Mounting Kit

29 Network Room Module Technical Bulletin 29 Commissioning the NRM Module To commission the NRM module: 1. Check the network and power wiring to the NRM module. 2. Turn on the module. If the power comes from the connected FX controller, apply power to the controller. On powerup, the NRM displays all symbols and segments of the display while a self test is performed. If the NRM passes the self test, the module begins to operate as configured with a display of space temperature or setpoint and fan symbol (if supported). If the NRM fails the self test, the display continues to show all symbols. 3. Connect the FX CommPro N2, LON, or BACnet software tool to the FX controller to monitor the NRM network variables through the network profile as configured within the control application. 4. Use the setpoint dial and fan push button to verify that the module is operating and sending and receiving valid data from the controller.

30 30 Network Room Module Technical Bulletin Troubleshooting Table 10: Troubleshooting NRM Installation Problem Cause/Action No indication is on LCD. Maintenance icon display. is visible on A symbol does not appear as expected. A manual change at the NRM does not work as expected (setpoint change, fan speed override or occupancy command). NRM shows a fan override status but it is not active in the connected controller. Display shows a different value for the setpoints as the FX controller. No power available. Check the wiring and supply voltage to the module. One or more of the following has occurred: PT1000 temperature sensor in the NRM has failed. Replace the NRM module. No communication with the FX controller. Check the bus wiring to the display (local link) bus of the controller and that the +, - and COM wires are correctly connected. An off normal condition is being reported by the controller. Verify that the configuration properties to enable the display of the symbol are set correctly in the Room Sensor object in the FX controller. Verify that the FX controller to which the NRM module is connected has been loaded with the correct configuration. Verify that the configuration properties to enable the command are set correctly. Using the FX CommPro Commissioning Tool, check that the values of the network variable outputs from the Room Sensor object respond in accordance with the display changes as the dial is rotated or the fan push button is pressed. Verify that the controller to which the NRM module is connected has been loaded with the correct configuration. Verify that the controller to which the NRM module is connected has been loaded with the correct configuration and that the configuration is designed to react correctly to an override status. Check for other conditions that could override the NRM module override. Verify that the controller to which the NRM module is connected has been loaded with the correct configuration. Verify that the configuration properties have been set correctly. Using the FX CommPro Commissioning Tool, check that the value of the relevant network variable output of the Room Sensor object is equal to the value on the LCD. If not, replace the NRM module.

31 Network Room Module Technical Bulletin 31 Specifications and Ordering Codes Specifications and Technical Data Table 11: Network Room Module Specifications and Technical Data Parameter/Component Power Supply LP-NRM0xx-000C Series Power Supply LP-NRM5xx-000C and LP-NRM6xx-000C Series Ambient Operating Conditions Value/Description 14.3 to 27.6 VDC (15 to 18 VDC from connected FX controller) at 500 mw maximum, or 24 VAC ± 15%, 50/60 Hz, 1 VA maximum Class 2 or Safety Extra-Low Voltage (SELV) 9.8 to 16.5 VDC (15 VDC nominal) at 35 ma maximum Class 2 or Safety Extra-Low Voltage (SELV) 0 to 50 C (32 to 122 F) 10 to 90% RH noncondensing (and maximum 30 C [86 F] dew point) Ambient Storage -20 to 70 C (0 to 160 F) Conditions 10 to 90% RH noncondensing (and max. 30 C [86 F] dew point) Terminations Terminal block with screw terminals in base for 1.5 mm 2 /16 AWG (maximum) wires. Recommended tightening torque 0.5 N m Temperature Sensor Pt1000 Class A, DIN EN Range 0 to 40 C (32 to 104 F) Accuracy better than ±0.5 C (±0.9 F) with a display resolution of 0.5 C or 0.5 F Suitable for residential and commercial office environments only Display LCD Display with three digits and six symbols (except temperature only models) Controls Dial and push buttons (depending on model) Communications Serial Bus RS-485 N2 Open Protocol at 9600 baud Interface Network Variable Standard FX Platform NRM Room Sensor Object variables and attributes Interface Service Port Model LP-NRM0xx: For FX Programming Key with 9 VDC power Models LP-NRM5xx and LP-NRM6xx: For MUI with 15 VDC power Mounting Direct surface mount. Plastic base for surface mount with wiring conduits, recessed wall box, and panel mounting kits available to order. Housing Material: ABS + polycarbonate, UL94-HB flammability rating Protection: IP30 (CEI/EN60529) Dimensions (H x W x D) 80 x 80 x 35 mm (3.15 x 3.15 x 1.4 in.), or 120 x 80 x 35 mm (4.72 x 3.15 x 1.4 in.) Continued on next page...

32 32 Network Room Module Technical Bulletin Parameter/Component (Cont.) Shipping Weight Compatible FX Controllers and Firmware Versions Compliance Value/Description 0.2 kg (7 oz.), 80 x 80 mm (3.15 x 3.15 in.) housing or 0.25 kg (9 oz), 120 x 80 mm (4.72 x 3.15 in.) housing FX06 FX07 FX14 V 2.32 and higher V 3.01 and higher V 2.32 and higher FXVMA All versions Europe 2004/108/EEC, EMC Directive: EN , EN Canada UL Listed (PAZX7), C22.2 No. 205, Signal Equipment Industry Canada, ICES-003 United UL Listed (PAZX), UL 916, Energy Management Equipment States FCC compliant to CFR 47, Part 15, Subpart B, Class A Table 12: Recommended FX Controller and MUI/NRM Configuration Limits FX Controller Type MUI/NRM Configuration Limits FX06 One MUI and one NRM FX06 Rev A One MUI and one NRM FX07 One MUI and one NRM FX07 Rev A One MUI and one NRM FX14 One MUI and two NRMs 1 FX14 Rev A One MUI and two NRMs 1 FX14 Rev B One MUI and two NRMs 1 FX15 Universal NRM is not supported FX15 NRM is not supported FX15 Rev A NRM is not supported FX16 NRM is not supported FX16 Rev A NRM is not supported FX16 Rev B NRM is not supported FXVMA One MUI and one NRM FXVMA Rev A One MUI and one NRM 1. One addressable NRM is required. Ordering Codes Table 13: Network Room Modules Ordering Information (Available in Europe) Product Code Features/Options Size (mm) Service Port Type LCD Display Temperature Adjustment Dial Fan Speed Selector Button F/ C Button LP-NRM C 80 x 80 Program No No No No No LP-NRM C Key Yes Yes No No No LP-NRM C Yes Yes Yes No No LP-NRM C MUI No No No No Yes LP-NRM C Yes Yes No No No LP-NRM C Yes Yes Yes No No Addressable

33 Network Room Module Technical Bulletin 33 Table 14: Network Room Modules Ordering Information (Available in North America) Product Code Size, mm (inch) Service Port Type LCD Display Features/Options Temperature Adjustment Dial Fan Speed Selector Button F/ C Button LP-NRM C 80 x 80 MUI No No No No Yes LP-NRM C (3.15 x Yes Yes No Yes No LP-NRM C 3.15 in.) Yes Yes Yes Yes No LP-NRM C 120 x 80 MUI No No No No Yes LP-NRM C (4.72 x Yes Yes No Yes No 3.15 in.) LP-NRM C Yes Yes Yes Yes No Addressable Table 15: Network Room Modules Mounting Kits and Accessories Ordering Code Description TM TM W TM W NS-WALLPLATE-0 TM (Europe) T (North America) LP-KIT C Plastic base for surface mounting (white) Recessed wall box mounting kit (white) Panel mounting kit (white) Wall plate kit used to mount an 80 x 80 mm (3.15 x 3.15 in.) NRM onto a 2 x 4 in. wall box. Special tool (to open module) Programming Key The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. Building Efficiency 507 E. Michigan Street, Milwaukee, WI Johnson Controls is a registered trademark of Johnson Controls, Inc. All other marks herein are the marks of their respective owners Johnson Controls, Inc.

FX07 Field Controller

FX07 Field Controller Product Bulletin FX07 Field Controller Issue Date March 25, 2008 FX07 Field Controller The FX07 is a high performance field controller designed specifically for commercial Heating, Ventilating, Air Conditioning,

More information

FX07 Field Controller

FX07 Field Controller Product Bulletin FX07 Field Controller Issue Date May 5, 2011 FX07 Field Controller The FX07 is a high performance field controller designed specifically for commercial Heating, Ventilating, Air Conditioning,

More information

Electronic Control Devices The European Product Catalogue 2007

Electronic Control Devices The European Product Catalogue 2007 FX14 Field Controller (1/4) FX14 Field Controller The FX14 is an equipment field controller in the Facility Explorer range of products. The controller is designed specifically for commercial Heating, Ventilating,

More information

Electronic Control Devices The European Product Catalogue 2007

Electronic Control Devices The European Product Catalogue 2007 FX07 Field Controller (1/4) FX07 Field Controller Display Model Dimensions in mm (inches) The FX07 is a terminal unit controller in the Facility Explorer range of products. The controller is designed specifically

More information

T7560A,B,C Digital Wall Module

T7560A,B,C Digital Wall Module T7560A,B,C Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. Digital

More information

Duct Humidity Transmitter

Duct Humidity Transmitter SDC-H Duct Humidity Transmitter Features Replaceable sensor element Humidity measurement for air ducts Minimum and maximum value memory 0 0V, 0 0mA or 0V, 4 0mA measuring signals selectable with jumpers

More information

HMI display Installation Guide

HMI display Installation Guide HMI display Installation Guide Product Description Specifications Important Information o Package Contents o Related Documents o Accessories Cautions and Warnings Mounting and Dimensions o BAC-DIS-ENC

More information

AXIS T81B22 DC 30W Midspan

AXIS T81B22 DC 30W Midspan INSTALLATION GUIDE AXIS T81B22 DC 30W Midspan ENGLISH About this Document This document includes instructions for installing AXIS T81B22 on your network. Previous experience of networking will be beneficial

More information

MCR1900 Media Converter 19-Slot Chassis

MCR1900 Media Converter 19-Slot Chassis MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the

More information

English plain text messages with constant backlight that brightens during user interaction. On/Off, Floating, or Proportional 0 to 10 VDC Control

English plain text messages with constant backlight that brightens during user interaction. On/Off, Floating, or Proportional 0 to 10 VDC Control TEC26x6(H)-4 and TEC26x6H-4+PIR Series BACnet MS/TP Networked Thermostat Controllers with Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Product Bulletin Code No. LIT-12011587

More information

I nstallation. M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications. Tools Needed.

I nstallation. M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications. Tools Needed. FANs 268.1, 1628.3 Installation Bulletin M100Q Issue Date 1099 M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications I nstallation Parts Included M110QGA-1 and

More information

Protects against unwanted thermostat controller tampering. Increases occupancy comfort by providing dehumidification.

Protects against unwanted thermostat controller tampering. Increases occupancy comfort by providing dehumidification. TEC22x6(H)-4 and TEC22x6H-4+PIR Series LONWORKS Network Thermostat Controllers with Dehumidification Capability, Fan Control, and Occupancy Sensing Capability Product Bulletin Code No. LIT-12011607 Issued

More information

A99B Series Temperature Sensors

A99B Series Temperature Sensors FANs 125, 121, 930, 930.5 Product/Technical Bulletin A99 Issue Date 0615 A99B Series Temperature s The A99B Series Temperature s are passive PTC (Positive Temperature Coefficient) sensors. The A99B sensors

More information

CD-Pxx-00-1 Series Duct Mount CO 2 Transmitter

CD-Pxx-00-1 Series Duct Mount CO 2 Transmitter CD-Pxx-00-1 Series Duct Mount CO 2 Transmitter Product Bulletin CD-Pxx-00-1 Code No. LIT-216525 Issued December 6, 2010 Supersedes September 12, 2008 Johnson Controls offers a complete line of Carbon Dioxide

More information

Drayton Digistat +2RF/+3RF

Drayton Digistat +2RF/+3RF /+3RF Programmable Room Thermostat Wireless Model: RF700/22090 Model: RF701/22092 Power Supply: Battery - Thermostat Mains - Digistat SCR Invensys Controls Europe Customer Service Tel: 0845 130 5522 Customer

More information

Installing the Tracer ZN517 Unitary Controller Ordering number: 4950 0496, 4950 0596

Installing the Tracer ZN517 Unitary Controller Ordering number: 4950 0496, 4950 0596 Installing the Tracer ZN517 Unitary Controller Ordering number: 4950 0496, 4950 0596 Product overview The Tracer ZN517 controller is a field-installed, application-specific controller that provides directdigital

More information

Vroom Hardware manual ver. 1.00 Code 114VROOHWE00. Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR

Vroom Hardware manual ver. 1.00 Code 114VROOHWE00. Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR Vroom CANBUS USER INTERFACE WITH LCD GRAPHIC DISPLAY AND WITH TEMPERATURE AND HUMIDITY SENSOR ENGLISH HARDWARE MANUAL ver. 1.00 CODE 114VROOHWE00 page 1 of 22 Important Important Read these instructions

More information

TR21, TR22, TR23, and TR24 Wall Modules

TR21, TR22, TR23, and TR24 Wall Modules TR21, TR22, TR23, and TR24 Wall Modules FEATURES INSTALLATI INSTRUCTIS The TR21, TR22, TR23, and TR24 family of wall modules include: Models with setpoint adjustment. Models with humidity output. Models

More information

HP-1000E v2. User s Manual. Powerline Ethernet Adapter. HP1000E v2 User s Manual

HP-1000E v2. User s Manual. Powerline Ethernet Adapter. HP1000E v2 User s Manual HP-1000E v2 Powerline Ethernet Adapter User s Manual HP1000E v2 User s Manual Table of Contents Chapter 1: Introduction...1 Chapter 2: Planning your Powerline Network...1 Network Topology...1 Chapter 3:

More information

EPSON USB/Parallel Adapter User s Guide

EPSON USB/Parallel Adapter User s Guide EPSON USB/Parallel Adapter User s Guide EPSON Stylus COLOR 440 EPSON Stylus COLOR 800 EPSON Stylus COLOR 600 EPSON Stylus COLOR 850 EPSON Stylus COLOR 640 EPSON Stylus COLOR 1520 EPSON Stylus Photo EX

More information

TraceTek TTDM Series Leak Detection and Location Modules Replacement Parts Installation Instructions

TraceTek TTDM Series Leak Detection and Location Modules Replacement Parts Installation Instructions TraceTek TTDM Series Leak Detection and Location Modules Replacement Parts Installation Instructions TRACETEK TraceTek TTDM Replacement Parts General Information These instructions detail the steps to

More information

FCC COMPLIANCE STATEMENT FOR AMERICAN USERS

FCC COMPLIANCE STATEMENT FOR AMERICAN USERS FCC COMPLIANCE STATEMENT FOR AMERICAN USERS This equipment has been tested and found to comply with the limits for a CLASS A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed

More information

ADSL Modem Installation Guide. Model # 36R515 Part # 030-300108 Rev. D Revision Date 12/2000. ADSL Modem Installation Guide

ADSL Modem Installation Guide. Model # 36R515 Part # 030-300108 Rev. D Revision Date 12/2000. ADSL Modem Installation Guide ADSL Modem Installation Guide Model # 36R515 Part # 030-300108 Rev. D Revision Date 12/2000 ADSL Modem Installation Guide Installation Instructions Westell ADSL Modem 1. Package Inspection and Contents...2

More information

T0118 T2118 T3118. Instruction Manual

T0118 T2118 T3118. Instruction Manual Programmable indoor transmitter of temperature T0118 Programmable indoor transmitter of atmospheric pressure T2118 Programmable indoor transmitter of temperature, relative humidity and other derived humidity

More information

About the HotWire 7900 10-Slot Standalone Shelf

About the HotWire 7900 10-Slot Standalone Shelf TM HotWire Model 7900 10-Slot Standalone Shelf Installation Instructions Document Number 7900-A2-GN10-10 About the HotWire 7900 10-Slot Standalone Shelf The HotWire 7900 10-Slot Standalone Shelf is designed

More information

Power Supply Guide Version 1.0 for D-Show

Power Supply Guide Version 1.0 for D-Show Power Supply Guide Version 1.0 for D-Show Digidesign 2001 Junipero Serra Boulevard Daly City, CA 94014-3886 USA tel: 650 731 6300 fax: 650 731 6399 Technical Support (USA) tel: 650 731 6100 fax: 650 731

More information

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL RANCO INSTALLATION INSTRUCTIONS ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL Relay Electrical Ratings PRODUCT DESCRIPTION The Ranco ETC is a microprocessor-based family of electronic temperature controls,

More information

Radiant Temperature Sensor TY7321

Radiant Temperature Sensor TY7321 AB-5361-U Specifications/Instructions Radiant Temperature TY7321 General TY7321 Radiant Temperature s are designed to measure infrared radiation from perimeter windows and walls and provide a proportional

More information

System 350 A350E Electronic Cooling Control

System 350 A350E Electronic Cooling Control FANs 930, 930.5, 125, 121 Product/Technical Bulletin A350E Issue Date 0899 System 350 A350E Electronic Cooling Control The A350E is an on/off, electronic, cooling-only control with Single-Pole, Double-Throw

More information

MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module (MS/TP)

MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module (MS/TP) Installation and Maintenance Manual IM 852 Group: Controls Part Number: IM 852 Date: June 2007 Supercedes: New MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module (MS/TP)

More information

=============================== WARNING

=============================== WARNING =============================== WARNING EXPLANATION OF GRAPHICAL SYMBOLS This symbol is intended to alert the user to the presence of unprotected dangerous voltage" within the product's enclosure that

More information

Perle 10/100 Ethernet Media Converters

Perle 10/100 Ethernet Media Converters Perle 10/100 Ethernet Media Converters Installation Guide S-110-XXXXXX S-110-XXXXXX-XT P/N 5500302-16 (Rev B) Overview This document contains instructions necessary for the installation and operation of

More information

NC-12 Modbus Application

NC-12 Modbus Application NC-12 Modbus Application NC-12 1 Table of Contents 1 Table of Contents... 2 2 Glossary... 3 SCADA...3 3 NC-12 Modbus in general... 3 4 Entire system... 4 4.1 PFC to PC connection alternatives...4 4.1.1

More information

Wireless Indoor/ Outdoor Thermometer

Wireless Indoor/ Outdoor Thermometer Wireless Indoor/ Outdoor Thermometer Owner s Manual Please read before using this equipment. ˆ Contents FCC Information... 3 FCC Declaration of Conformity... 5 Preparation... 5 Installing Batteries...

More information

Modular I/O System Analog and Digital Interface Modules

Modular I/O System Analog and Digital Interface Modules OPERATING INSTRUCTIONS Modular I/O System Analog and Digital Interface Modules Installation Operation Maintenance Document Information Document ID Title: Operating Instructions Modular I/O System Part

More information

HLWLAN 802.11b/g/n Transceiver Kit

HLWLAN 802.11b/g/n Transceiver Kit 092524 RevB HLWLAN 802.11b/g/n Transceiver Kit Wireless Communications for OmniLogic Owner s Manual Contents Introduction...1 Installation...2 Configuration...6 Operation...8 Troubleshooting...9 HLWLAN

More information

T5000 T000 LCD Digital Fan Coil Thermostat

T5000 T000 LCD Digital Fan Coil Thermostat T5000 T000 LCD Digital Fan Coil Thermostat T000 LCD Digital Fan Coil Thermostat T000 LCD Digital Fan Coil Thermostats are designed to control heating, cooling, or year round air conditioning unit in Commercial,

More information

Square D Clipsal DIN-Rail Four-Channel Auxiliary Input Unit

Square D Clipsal DIN-Rail Four-Channel Auxiliary Input Unit Square D Clipsal DIN-Rail Four-Channel Auxiliary Input Unit SLCLE5504AUX for Use with Wired C-Bus Networks Instruction Bulletin Retain for future use. Square D Clipsal DIN-Rail Four-Channel Auxiliary Input

More information

Installation Instructions. Wireless Adapter/Repeater. Introduction. 30-3001-887 Rev C

Installation Instructions. Wireless Adapter/Repeater. Introduction. 30-3001-887 Rev C /Repeater Installation Instructions 30-3001-887 Rev C Workstation Ethernet bcx Controller Repeater Repeater Introduction Schneider Electric has designed a device that allows Andover Continuum controllers

More information

Zlinx Wireless I/O. Peer-to-Peer and Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION

Zlinx Wireless I/O. Peer-to-Peer and Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION Modular, Customizable Wire Replacement 128 / 256 Bit AES Encryption Software Selectable RF Transmit Power Software Selectable Over-the-air Data Rate Modbus ASCII /RTU Compatible Wide Operating Temperature

More information

User's Guide. Integrating Sound Level Datalogger. Model 407780. Introduction

User's Guide. Integrating Sound Level Datalogger. Model 407780. Introduction User's Guide 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com Back to the Extech 407780 Product Page Integrating Sound Level Datalogger

More information

HP UPS R1500 Generation 3

HP UPS R1500 Generation 3 HP UPS R1500 Generation 3 Installation Instructions Part Number 650952-001 NOTE: The rating label on the device provides the class (A or B) of the equipment. Class B devices have a Federal Communications

More information

PD 100A. Printing data system

PD 100A. Printing data system PD 100A Printing data system Operating instructions ENGLISH IMPORTANT: Read these instructions carefully before installing and using the device; do not forget following all additional information. Keep

More information

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER Application : The RISH CON - Hz transducer is used for frequency measurement. The output signal is proportional to measured frequency and is either load independent DC Current or load independent DC Voltage.

More information

DVI DA2 and DVI DA 4 User Guide

DVI DA2 and DVI DA 4 User Guide DVI DA2 and DVI DA 4 User Guide This guide describes the installation and operation of the Extron DVI DA2 and DVI DA4 Distribution Amplifiers. Unless stated otherwise, distribution amplifier or the unit

More information

Series P215PR/RM Direct- and Remote-Mount Pressure-Actuated Condenser Fan Speed Controllers for Single-Phase Motors

Series P215PR/RM Direct- and Remote-Mount Pressure-Actuated Condenser Fan Speed Controllers for Single-Phase Motors European Refrigeration Controls Catalogue Catalogue Section 4 Product Bulletin P215PR/RM Issue 01/03/2013 Series P215PR/RM Direct- and Remote-Mount Pressure-Actuated Condenser Fan Speed Controllers for

More information

FX16 Master Controller

FX16 Master Controller Product Bulletin FX16 Master Controller Issue Date October 20, 2008 FX16 Master Controller The FX16 Master Controller is a high performance field controller designed specifically for commercial Heating,

More information

Back-UPS Pro 1300/1500 Installation and Operation

Back-UPS Pro 1300/1500 Installation and Operation Back-UPS Pro 1300/1500 Installation and Operation Inventory Safety Do not install the Back-UPS in direct sunlight, in excessive heat, humidity, or in contact with fluids. Connect the battery bu059a bu058a

More information

M9102-AGA-2S, -3S and M9104-xxA-2S, -3S Series Electric Non-Spring Return Actuators

M9102-AGA-2S, -3S and M9104-xxA-2S, -3S Series Electric Non-Spring Return Actuators M9102-AGA-2S, -3S and M9104-xxA-2S, -3S Series Electric Non-Spring Return Actuators Product Bulletin Code No. LIT-1201742 Issued February 12, 2015 The M9102 and M9104 Series Actuators are directmount,

More information

IN-OUT Thermometer with Cable Free Sensor and Clock

IN-OUT Thermometer with Cable Free Sensor and Clock IN-OUT Thermometer with Cable Free Sensor and Clock MODEL: RAR232 USER'S MANUAL INTRODUCTION Congratulations on your purchase of the RAR232 In-Out Thermometer with 433MHz cable free sensor and calendar

More information

Tebis application software

Tebis application software Tebis application software Input products / ON / OFF output / RF dimmer Electrical / Mechanical characteristics: see product user manual Product reference Product designation TP device RF devices WYC81xQ

More information

PT-6000 Power Tower INSTALLATION MANUAL SPECIFICATIONS

PT-6000 Power Tower INSTALLATION MANUAL SPECIFICATIONS PT-6000 Power Tower INSTALLATION MANUAL 10.5 9.75 12 22.75 10.75 MAXIMUM SOIL HEIGHT: DO NOT ALLOW FILL TO EXCEED THIS LEVEL! 11.5 4 4 13 Optional PT-BASE for new installations or when previous 2000/6000

More information

UniStream CPU-for-Panel

UniStream CPU-for-Panel UniStream CPU-for-Panel Installation Guide USC-P-B10 Unitronics UniStream platform comprises control devices that provide robust, flexible solutions for industrial automation. This guide provides basic

More information

Alpha Climatic Programmable Modulating Boiler Energy Manager. Installation and User Instructions

Alpha Climatic Programmable Modulating Boiler Energy Manager. Installation and User Instructions Alpha Climatic Programmable Modulating Boiler Energy Manager Part No 3.022144 (Hard Wired) Part No 3.022143 (Radio Frequency) Installation and User Instructions 1. Description The Alpha Climatic energy

More information

Conference Phone UserÕs Manual. Part No. 54-2070-01R1 Printed in Korea. 2002 Bogen Communications, Inc.

Conference Phone UserÕs Manual. Part No. 54-2070-01R1 Printed in Korea. 2002 Bogen Communications, Inc. Part No. 54-2070-01R1 Printed in Korea. 2002 Bogen Communications, Inc. UserÕs Manual Notice Every effort was made to ensure that the information in this guide was complete and accurate at the time of

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS LIGHTING CONTROL PANELS 4 AND 8 RELAYS INSTALLATION INSTRUCTIONS INSTALLATION OVERVIEW The installation instructions contained in this document are provided as a guide for proper and reliable installation.

More information

USB Mini Print Server PS121. Installation Guide

USB Mini Print Server PS121. Installation Guide USB Mini Print Server PS121 Installation Guide Introduction Thank you for purchasing a NETGEAR PS121 USB Mini Print Server. With this print server you can share your printer with all the computers in your

More information

MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS

MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS MAKING MODERN LIVING POSSIBLE AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS How to Use This Guide Read this Guide completely as you install and start up your new AK-SC 255 controller.

More information

System 350 A350R Electronic Temperature Reset Control (with Relay)

System 350 A350R Electronic Temperature Reset Control (with Relay) FANs 930, 930.5, 125, 121 Product/Technical Bulletin A350R Issue Date 0899 System 350 A350R Electronic Temperature Reset Control (with Relay) The A350R Electronic Temperature Reset Control is designed

More information

5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual

5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual 5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual Content Overview... 1 Introduction... 1 Features... 3 Packing List... 4 Safety Precaution... 4 Hardware Description... 5 Front Panel...

More information

AXIS 291 1U Video Server Rack Installation Guide

AXIS 291 1U Video Server Rack Installation Guide AXIS 291 1U Video Server Rack Installation Guide About This Document This document describes how to install Axis blade video servers in the AXIS 291 1U Video Server Rack. Updated versions of this document

More information

EBDSPIR-PRM, EBDSPIR-PRM-IP

EBDSPIR-PRM, EBDSPIR-PRM-IP Product Guide EBDSPIR-PRM, EBDSPIR-PRM-IP Ceiling PIR presence/absence detector Overview The EBDSPIR-PRM PIR (passive infrared) presence detector provides automatic control of lighting loads with optional

More information

SLIM LINE FUME HOOD MONITOR

SLIM LINE FUME HOOD MONITOR SLIM LINE FUME HOOD MONITOR Phoenix Controls FHM420 Fume Hood Monitor is sized to fit any fume hood and includes icons for simple and universal operation. The FHM420 slim line monitor works in conjunction

More information

Kvaser Mini PCI Express User s Guide

Kvaser Mini PCI Express User s Guide Kvaser Mini PCI Express User s Guide Copyright 2013-2014 Kvaser AB, Mölndal, Sweden http://www.kvaser.com Printed Sunday 28 th September, 2014 We believe that the information contained herein was accurate

More information

LIEBERT VNSA Installation Sheet

LIEBERT VNSA Installation Sheet LIEBERT VNSA Installation Sheet Description The Liebert vnsa network switch is designed for connecting multiple Ethernet-ready devices and comes in various models. The unit may have: A Liebert icom display

More information

5-Port Switch 10/100/1000 Mbps Gigabit Ethernet GS105

5-Port Switch 10/100/1000 Mbps Gigabit Ethernet GS105 5-Port Switch 10/100/1000 Mbps Gigabit Ethernet GS105 Installation Guide Introduction The NETGEAR 5-Port Gigabit Ethernet Switch Model GS105 provides you with a low-cost, reliable, high-performance switch

More information

16-port Gigabit Switch 10/100/1000 Mbps GS116. Installation Guide

16-port Gigabit Switch 10/100/1000 Mbps GS116. Installation Guide 16-port Gigabit Switch 10/100/1000 Mbps GS116 Installation Guide Introduction The NETGEAR 16-port Gigabit Switch Model GS116 provides you with a low-cost, reliable, high-performance switch to connect up

More information

WARNING CANADIAN D.O.C. WARNING

WARNING CANADIAN D.O.C. WARNING Each product and program carries a respective written warranty, the only warranty on which the customer can rely. Avery Dennison Corp. reserves the right to make changes in the product, the programs, and

More information

Perle Protocol Transparent Media Converter Modules

Perle Protocol Transparent Media Converter Modules Perle Protocol Transparent Media Converter Modules Installation Guide C-4GPT-DSFP CM-4GPT-DSFP Part# 5500335-10 Overview This document contains instructions necessary for the installation and operation

More information

Portable BACnet /IP to MS/TP Router

Portable BACnet /IP to MS/TP Router Portable BACnet /IP to MS/TP Router Installation Instructions TL-BRTRP-0 Part No. 24-10414-2, Rev. F Issued April 2016 Refer to the QuickLIT website for the most up-to-date version of this document. Applications

More information

EVOLUTION Thermal Imaging Camera Remote Wireless Video Receiver System

EVOLUTION Thermal Imaging Camera Remote Wireless Video Receiver System EVOLUTION Thermal Imaging Camera Remote Wireless Video Receiver System Instruction Manual DELUXE AND MINI RECEIVER KIT (RX) INSTRUCTIONS " WARNING THIS MANUAL MUST BE READ CAREFULLY BY ALL INDIVIDUALS

More information

EPSON USB/Parallel Adapter User s Guide

EPSON USB/Parallel Adapter User s Guide EPSON USB/Parallel Adapter User s Guide EPSON Stylus COLOR 440 EPSON Stylus COLOR 1520 EPSON Stylus COLOR 600 EPSON Stylus COLOR 3000 EPSON Stylus COLOR 640 EPSON Stylus Photo 700 EPSON Stylus COLOR 660

More information

Product Documentation on the World Wide Web

Product Documentation on the World Wide Web Hotwire M/SDSL Standalone Termination Units Models 7974-A2, 7975-A2, and 7976-A2 Installation Instructions Document Number 7900-A2-GN11-00 August 2000 Product Documentation on the World Wide Web We provide

More information

OEM Manual MODEL 2350 ELECTRONIC DUAL CYLINDER SCALE

OEM Manual MODEL 2350 ELECTRONIC DUAL CYLINDER SCALE OEM Manual MODEL 2350 ELECTRONIC DUAL CYLINDER SCALE Scaletron Industries, Ltd. Bedminster Industrial Park 53 Apple Tree Lane P.O. Box 365 Plumsteadville, PA 18949 USA Toll Free: 1-800-257-5911 (USA &

More information

Ventostat Wall Mount. Telaire Wall Mount CO 2. , Humidity and Temperature Transmitters. GE Measurement & Control. Features:

Ventostat Wall Mount. Telaire Wall Mount CO 2. , Humidity and Temperature Transmitters. GE Measurement & Control. Features: GE Measurement & Control Ventostat Wall Mount Telaire Wall Mount, Humidity and Temperature Transmitters Features: Patented, Absorption Infrared Gas sensing engine provides high accuracy in a compact low

More information

Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS

Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS + Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS Inventory Safety and General Information bu001c This unit is intended for indoor use only. Do not operate this unit in direct sunlight,

More information

110244-003. PrintPAD CN3/4/3e/4e. User Guide

110244-003. PrintPAD CN3/4/3e/4e. User Guide 110244-003 PrintPAD CN3/4/3e/4e User Guide TABLE OF CONTENTS PrintPAD CN3/4 & PrintPAD CN3e/4e Printer Views...1 Open View...1 Closed View...1 Using Batteries: General Guidelines...1 Installing and/or

More information

Triple Expansion Chassis

Triple Expansion Chassis Triple Expansion Chassis AP9604 Installation Manual Contents Introduction............................. 1 Installation.............................. 2 Power Considerations...................... 5 Operations..............................

More information

Wireless Alarm System. Wireless Keypad. User s Manual. Choice ALERT. Control all sensors, accessories and remote transmitters from one location

Wireless Alarm System. Wireless Keypad. User s Manual. Choice ALERT. Control all sensors, accessories and remote transmitters from one location Wireless Alarm System Wireless Keypad User s Manual 1 2 3 4 Choice ALERT Control all sensors, accessories and remote transmitters from one location Table of Contents Important Safeguards 4 Introduction

More information

Introduction. Refrigerant Leak Detecting System. Feature and Benefits

Introduction. Refrigerant Leak Detecting System. Feature and Benefits PSC European Refrigeration Controls Catalogue Catalog Section 9 Product Bulletin PD-GAS-E Refrigerant Leak Detecting System Introduction This range of refrigerant leak detecting systems is designed for

More information

1. SAFETY INFORMATION

1. SAFETY INFORMATION RS-232 Sound Level Meter 72-860A INSTRUCTION MANUAL www.tenma.com 1. SAFETY INFORMATION Read the following safety information carefully before attempting to operate or service the meter. Use the meter

More information

Product and functional description

Product and functional description Product and functional description The KNX / DALI gateway N 141/02 is a 4 MU wide, DINrail mounted KNX device with one DALI interface to which up to 64 DALI actuators (e.g. DALI ballasts) can be connected

More information

KNX TH65-AP. Thermo-Hygrometer. Technical specifications and installation instructions Item number 70184

KNX TH65-AP. Thermo-Hygrometer. Technical specifications and installation instructions Item number 70184 EN KNX TH65-AP Thermo-Hygrometer Technical specifications and installation instructions Item number 70184 Elsner Elektronik GmbH Control and Automation Engineering Herdweg 7 D 75391 Gechingen Phone +49

More information

DMX2PWM 9 Channel Dimmer Setup Manual

DMX2PWM 9 Channel Dimmer Setup Manual DMX2PWM 9 Channel Dimmer Setup Manual www.ecue.de DMX2PWM 9ch Dimmer - Setup Manual e:cue control GmbH An OSRAM Company Rev. 1.3_01/2010 DMX2PWM 9ch Dimmer - Setup Manual Table of Contents 1. Device Overview....................................4

More information

PolyGard Carbon Monoxide CO Transmitter ADTX3 1110

PolyGard Carbon Monoxide CO Transmitter ADTX3 1110 PolyGard Carbon Monoxide CO Transmitter ADTX3 1110 DESCRIPTION CO transmitter including digital measurement value processing and temperature compensation for the continuous monitoring of the ambient air

More information

RC8021 Indoor Camera Installation Guide

RC8021 Indoor Camera Installation Guide RC8021 Indoor Camera Installation Guide P/N: 957YL502GJ Document Version: 1.0 Copyright 2011. All Rights Reserved. All trademarks and trade names are the properties of their respective owners i Package

More information

Nevco, Inc. Installation Manual

Nevco, Inc. Installation Manual Nevco, Inc. Installation Manual Serial No. Model GLH-5 Size: Each module is 18 L x 19 ¾ H x 4 D (.46 x.50 x.10 meters) Approximate hanging weight: 11 lbs each (5 kg) Power requirements 120V,.4 Amps each

More information

HE-6800 Series Humidity Transmitters with Temperature Sensor

HE-6800 Series Humidity Transmitters with Temperature Sensor HE-6800 Series Humidity Transmitters with Installation Instructions HE-68xx-xN00WS Applications The HE-6800 Series Humidity Transmitters with provide both humidity and temperature sensing in room wall-mount

More information

TAC I/NETTM MR-VAV-AX. Application Specific MicroRegulator TM

TAC I/NETTM MR-VAV-AX. Application Specific MicroRegulator TM TAC I/NETTM TM TAC s TM has an extensive range ofpre-engineered VAV control sequences, which combined with a fully integrated actuator and airflow transducer, makes it a low Total Installed Cost solution

More information

PowerLogic Sub Meter Display (SMD and SMDOPN)

PowerLogic Sub Meter Display (SMD and SMDOPN) Instruction Bulletin Z203742-0B PowerLogic Sub Display (SMD and SMDOPN) CONTENTS Introduction... 2 Parts of the Sub Display... 3 Dimensional Drawing... 4 Installation... 5 Mounting the SMD... 5 Mounting

More information

Installation Guide. LR-HWLV-HVAC TouchPRO Wireless. System Types

Installation Guide. LR-HWLV-HVAC TouchPRO Wireless. System Types Installation Guide LR-HWLV-HVAC TouchPRO Wireless Touchscreen Thermostat System Types Gas, oil, or electric heat with air conditioning Warm air, hot water, high efficiency furnaces, heat pumps, steam,

More information

Temperature & Humidity SMS Alert Controller

Temperature & Humidity SMS Alert Controller Temperature & Humidity Alert Controller METERS 3 simple steps starting the unit: Insert the SIM card Plug in the sensors connectors Connect the AC power cord. Specifications: AC 90~260V Auto Select Internal

More information

Gigabit Ethernet Switch 10/100/1000 Mbps GS605 / GS608. Installation Guide

Gigabit Ethernet Switch 10/100/1000 Mbps GS605 / GS608. Installation Guide Gigabit Ethernet Switch 10/100/1000 Mbps GS605 / GS608 Installation Guide Introduction The NETGEAR 5/8-Port Gigabit Ethernet Switch Model GS605 / GS608 provides you with a high-speed, reliable, easy-to-use

More information

LevelOne IFE-0500 4-Port PoE + 1-Port TP Industrial Fast Ethernet Switch User Manual

LevelOne IFE-0500 4-Port PoE + 1-Port TP Industrial Fast Ethernet Switch User Manual LevelOne IFE-0500 4-Port PoE + 1-Port TP Industrial Fast Ethernet Switch User Manual Ver. 1.0.0-0711 1 FCC Warning This Equipment has been tested and found to comply with the limits for a Class-A digital

More information

Energy Smart Electric Water Heater Controller

Energy Smart Electric Water Heater Controller Installation, Operation and Troubleshooting Instructions Energy Smart Electric Water Heater Controller Table of Contents Installation and Setup, 2 Operation, 5 Troubleshooting, 7 Regulatory Notices, 11

More information

OZW30. Central Unit SYNERGYR

OZW30. Central Unit SYNERGYR 2 841 SYNERGYR Central Unit OZW30 Collects billing data from the apartments. Generates an image of each apartment's heat consumption and makes it available for readout. Acts on room temperature control

More information

Installation and Operation Back-UPS 1250, 1300, 1500

Installation and Operation Back-UPS 1250, 1300, 1500 Installation and Operation Back-UPS 1250, 1300, 1500 Inventory bu001a Safety and General Information This unit is intended for indoor use only. Do not operate this unit in direct sunlight, in contact with

More information

Table of Contents. 1 - Specifications...3. 2 - Installation...3. 3 - Wiring...5. 4 - User controls...7

Table of Contents. 1 - Specifications...3. 2 - Installation...3. 3 - Wiring...5. 4 - User controls...7 THERMOSTATS Table of Contents Page 1 - Specifications...3 1.1 - Product range...3 ARTTH001 (DSL-610)...3 ARTTH002 (DSL-700)...3 ARTTH003 (DSL-600)...3 1.2 - Technical data...3 1.3 - Power failures...3

More information

Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information.

Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information. Product and Applications Description The power supply units N 125/x2 can supply DC 24 V power from an additional pair of terminals (yellowwhite). This DC 24 V output voltage can be used to power e.g. an

More information

omega.com ΩOMEGA RS232 Multi-Drop www.omega.com FMA1600-MDB Multi-Drop Box

omega.com ΩOMEGA RS232 Multi-Drop www.omega.com FMA1600-MDB Multi-Drop Box omega.com ΩOMEGA RS232 Multi-Drop www.omega.com FMA1600-MDB Multi-Drop Box 1 3/29/2010 Rev.0 DOC-OMEGABB9MAN 2 Introduction FMA1600-MDB Multi-Drop Box Operating Bulletin The FMA1600-MDB Multi-Drop Box

More information