SWP-21 Rev. 0 Fire Protection 5/24/2009
|
|
- Morgan Kennedy
- 7 years ago
- Views:
Transcription
1 POLICY It is the policy of the facility to provide equipment to insure a reasonable degree of protection for life and property from fire and to establish requirements for inspecting, testing and maintaining fire protection systems. 1. Deluge systems testing FREQUENCY: Annual A. Notify the Control Room of the test. Provide name and the location of the test. B. Trip the system. (1) Verify no alarms. (2) Trip sensors. (3) Check flow pressure. (4) Inspect nozzles for flow. (5) Repair/replace defective nozzles, systems, pipe etc., as needed. (6) Reset systems for normal service. C. Repeat this procedure (1A and 1B) with the remainder of the deluge system. D. Upon completing this test, notify the Control Room to instruct Water Treatment personnel to shut down the fire pump, if running. E. Complete the inspection forms/reports and return them to Central Files. 1. Fire pump testing FREQUENCY: Monthly (1) The pump will stop automatically when the system pressure returns to normal (plus or minus 145 psi). A. Diesel fire pump: (1) Slowly open the drain valve (on floor behind engine) and observe the psi gauge until the pump starts. (2) Close the drain valve and record the pressure reading. Page 1 of 8
2 (3) Throttle the engine to idle and allow it to cool for five minutes before stopping the engine. (4) Turn the ignition switch to Off, return the throttle to its original position and switch the ignition switch to Auto (throttle and ignition switches located between electric and diesel pump). 2. Fire extinguisher inspecting, tagging, and timing A. Fire extinguishers are inspected monthly by Getz. Defective extinguishers are replace and problems with fire hose cabinets are corrected. Inspection forms are returned to the Central Files. B. PSI gauges are visually checked to be sure they are within the green area (dry chemical and halon since CO 2 extinguishers do not have gauges). C. Pull pins are checked to insure that the safety seals are intact. D. Inspect for any visible damage. E. When the pressure gauge is not in the green area, a pull pin safety seal has been broken, or visible damage exists that could render the extinguisher unusable, the extinguisher is recharged or disposed of. F. Immediately replace any fire extinguisher removed from service. G. Check the appropriate month on the inspection tag and complete the inspection form. Return the form to the Central Files. H. Spare fire extinguishers will be kept on the generating floor across from the Unit 1 and 2 control room. 4. Fire hydrants and associated valves A. Will be inspected monthly. B. Maintenance and operational test annually. 1. Testing, inspection, and maintenance A. Certain parts of the Fire Protection Systems will be inspected and tested in accordance with applicable NFPA standards by Prevention Fire Protection Systems Company, which includes the annual test of Fire-Smoke detectors, Alarm Circuits and Manual Alarms. B. All other fire protection systems and equipment will be inspected and tested monthly according to the inspection forms for each area. Page 2 of 8
3 C. Testing, inspection and maintenance will be documented; results and follow-up actions recorded. All forms and reports will be maintained in the Central Files located in the Safety Coordinators Office. 6. Impairments A. When the protection system or equipment, including the detection system, is removed from service, either partially or completely the control room operator is responsible to immediately notify: Hartford Steam Boiler (HSB) Professional Loss Control Timber Hollis Fire Department Safety Coordinator ext B. Impairments to the Fire Protection System should be as short in duration as practical. When an impairment is planned, HSB, Timber Hollis Fire Department and the Safety Coordinator will be notified at a minimum forty-eight hours before the impairment. All necessary parts, materials and people should be assembled prior to removing the Protection System from service. When impairment is not planned, the repair work should be expedited until the repairs are completed. C. Control Room Operator to log the date and description of the impairment. D. Follow the SWP-20, Lockout/Tagout Procedure. E. Once repairs are complete, tests that will ensure proper operation and restoration of full Fire Protection equipment capabilities were made. Following restoration to service, the control room operator will notify the HSB, Timber Hollis Fire Department and the Safety Coordinator that the fire protection system has been restored to service. F. Questions and concerns regarding the impairment of a system can be directed to our HSB Project Manager/Principal consultant, Richard Rendleman at Page 3 of 8
4 7. Inspection, Testing and Maintenance Schedule TYPE OF SYSTEM ACTIVITIES PERFORMED BY FACILITY PERFORMED BY CONTRACTOR Fire Pump Pump Suction Sources Valves Dry pipe Sprinkler Systems WEEKLY Fire pump churn test by automatic operation, usually drop in sensing line pressure (30 minutes for diesel) and associated engine inspections. Verify that pump running alarms are received in control room. Check intake level of river. Check and clean the suction screen after each operation. Inspect indicating sectional and system control valves to verify that they are in the open position (if they have neither locks nor tamper switches. It is recommended that all valves be locked in the fully open position). This should include special suppression systems. Inspect dry pipe sprinkler risers. MONTHLY Fire Pump Test battery system and main circuit. Fire Extinguishers Inspect each fire extinguisher and cart. Page 4 of 8
5 Fire Hoses Inspect each fire hose station/hydrant house. Hoses should be properly racked or rolled and the proper nozzles as well as hose wrenches and other hardware should be provided. Sprinkler Systems Inspect each sprinkler/water spray system riser. This should include water/air pressures and alarm valves. Special Suppression Inspect each system (agent level and pressures, panels, nozzles). Valves Inspect indicating sectional and system control valves (locks and/or tamper switches provided). This should include special suppression systems. Fire Pump Test battery system and main circuit. Fire Extinguishers Inspect each fire extinguisher and cart. Fire Hoses Inspect each fire hose station/hydrant house. Hoses should be properly racked or rolled and the proper nozzles as well as hose wrenches and other hardware should be provided. Sprinkler Systems Inspect each sprinkler/water spray system riser. This should include water/air pressures and alarm valves. Special Suppression Inspect each system (agent level and pressures, panels, nozzles). Page 5 of 8
6 Valves Inspect indicating sectional and system control valves (locks and/or tamper switches provided). This should include special suppression systems. QUARTERLY Sprinkler Systems Test water flow alarms and perform main drain test on sprinkler/water spray systems. Valves Test valve tamper switches by turning the supervised valves until an alarm is obtained at the alarm panel. Post Indicator Valves (PIV) Test by turning them through the full cycle and reopening them. Follow by a main drain test at the sprinkler riser controlled. SEMI-ANNUALLY Special Suppression Systems Weigh high-pressure cylinders (halon, CO 2, halon-alternatives). Cylinders should be refilled if a volume drop of more than 10 percent (CO 2 ) and 5 percent (halon) from the design requirements is observed. Test system actuators for proper operation. Page 6 of 8
7 ANNUALLY Emergency Lighting Ninety second functional test Sprinkler Systems Trip test of dry pipe, preaction and deluge sprinkler/water spray systems. A full discharge test should be conducted whenever possible to verify free flow through all piping nozzles. Fire Pump Fire pump performance test (usually done with insurance fire protection consultants). Hydrants Yard main flush/hydrant test (usually done with insurance fire protection consultants). Fire Detectors Test all heat and smoke detectors. Alarms Test alarm control equipment (batteries, lamps, power supplies, etc.) Manual Fire Alarms Test all manual fire alarm boxes. Fire Extinguishers Service each extinguisher and cart. Page 7 of 8
8 OTHER THAN ANNUALLY Fire Hoses Portable Extinguishers Halon Hydrostatic test at 150 psi for most hose, five years after installation, three years thereafter. Hydrostatic test, every twelve years for halon and dry chemical (steel, brass or aluminum shells). Every five years for all other extinguishers. Hydrostatic test of cylinders after discharge, if more than five years have elapsed since the last hydrostatic test. NOTES: 1 Facility people must be properly trained. 2 - Contractors must be a licensed and qualified fire protection contractor. Page 8 of 8
SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT
SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT INTRODUCTION No matter how reliable fire protection equipment may seem, periodic maintenance is needed to ensure proper operation. Fire protection
More informationFIVE YEAR CERTIFICATION REPORT
GARDEN GROVE FIRE DEPARTMENT FIRE PREVENTION DIVISION FIVE YEAR CERTIFICATION REPORT Service and maintenance report of automatic fire extinguishing systems, including fire sprinklers, dry, deluge, and
More informationInspection, Testing and Maintenance
Page 18 ABOUT CODE CORNER CCFS would like to remind you to check with your local Authority Having Jurisdiction (AHJ) for questions and opinions concerning your local Fire and Building Codes. The information
More informationDepending on your facility and the equipment contained within, all or part of the checklists/logs can be printed for use.
Large Facility Fire Safety Checklists and Logs This package contains checklists to ensure that all fire and life safety equipment are properly inspected. There are also logs on which to record the inspections
More informationInspection and Testing Program Fire Protection Equipment
I. Introduction Inspection and Testing Program Fire Protection Equipment State of Minnesota Emergencies seldom give warning before they strike. Thus, it is essential that fire protection equipment be inspected,
More informationINSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS AND EQUIPMENT
CITY OF SPRING LAKE PARK Code Enforcement Department 1301 81 st Avenue NE Spring Lake Park MN 55432 Business Phone 763-784-6491 Fax 763-792-7257 INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS
More informationINSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according
More informationMAINTENANCE AND SERVICE OF AUTOMATIC FIRE EXTINGUISHING SYSTEMS
FIRE DEPARTMENT Bureau of Fire Protection and Life Safety www.cityofsanmateo.org 1900 O Farrell, Suite 140 San Mateo, CA 94403-1332 (650) 522-7940 FAX: (650) 522-7941 TDD: (650) 522-7047 MAINTENANCE AND
More informationALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS
ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS In this document are the fire safety equipment maintenance requirements that are found in Division B of the Alberta Fire Code (AFC 2006) for
More informationWinnipeg Fire Department Fire Prevention Branch
Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of
More informationELECTRIC/DIESEL FIRE PUMP CHECK LIST
BUILDING NAME: DESIGNER: SCO REPRESENTATIVE: PUMP MANUF.: LOCATION: INSTALLER: DATE: OWNER NAME: INSTALLATION Certificate for flushing and hydrostatic test furnished Piping been hydrostatically tested
More informationModel: 400E-2M. Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset. Installation Operation Maintenance. Application Engineering
Model: 400E-2M Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Application Engineering BERMAD 1. Safety First BERMAD believes that the safety
More informationCommercial Fire Inspections
Commercial Fire Inspections Fire Department Inspection Requests and Procedures The following guidelines shall be used when calling for inspection requests: 1. All inspection requests shall be coordinated
More informationEXHIBIT A SCOPE OF WORK
EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,
More informationInspection and Testing of Water-Based Systems
Inspection and Testing of Water-Based Systems Standard Model/Computer-Based Testing Level III Content Outline The candidate for NICET certification at Level III in the Inspection and Testing of Water-Based
More informationMaintaining Fire Protection Systems
Maintaining Fire Protection Systems Fire continues to be a major threat to your business and your personal safety. Each year several thousand people are injured or killed by fires and billions of dollars
More informationBERMAD Fire Protection
Model: 400E-2M BERMAD Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Safety First BERMAD believes that the safety of personnel working with and around
More informationHERNANDO COUNTY FIRE ALARM GUIDELINES
HERNANDO COUNTY FIRE ALARM GUIDELINES To be used for all commercial building fire alarm system plan review. The procedures set forth in this document are the minimum requirements necessary to ensure a
More informationFire Alarm System Standpipes Sprinkler Systems Fire Drills Commercial Cooking Hood and more
FIRE PROTECTION SYSTEMS Fire protection systems, measures and equipment are all related to the safety of the occupants and the protection of the property. As part of a building design and its intended
More informationENVIRONMENTAL HEALTH AND SAFETY. Fire Protection System Impairment Procedure
ENVIRONMENTAL HEALTH AND SAFETY Fire Protection System Impairment Procedure April 2013 Fire Protection System Impairment Procedures Table of Contents I. Purpose II. III. IV. Fire Protection Systems Compliance
More informationImportant Ontario Fire Code Information for Building Owners in the City of Windsor
Important Ontario Fire Code Information for Building Owners in the City of Windsor This information is intended to be used a reference only. For a complete listing consult the Ontario Fire Code or contact
More informationKODAK VERSAMARK, INC.
KODAK VERSAMARK, INC. PREPARED BY : Gary Rowland 6/6/06 Kodak Versamark, Inc. 3000 Research Blvd. Dayton, Ohio 45420 APPROVED BY : Fire Suppression System Inspection, Testing and Maintenance SHEET 1 OF
More informationCITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS
CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS PROPERTY ADDRESS (BRT Address Required) TESTING CONTRACTOR (Name and Address) License No. ANNUAL
More informationFIRE EXTINGUSIHER INSPECTION, MAINTENANCE, AND TESTING PROCEDURES
FIRE EXTINGUSIHER INSPECTION, MAINTENANCE, AND TESTING PROCEDURES Fire and Life-Safety Group (FLS) FLS has organized the following information to act as a guideline/checklist for any inspection, maintenance,
More informationRisk Control Bulletin Inspection, Testing & Maintenance (ITM) of Water-Based Fire Protection Systems
Risk Control Bulletin Inspection, Testing & Maintenance (ITM) of Water-Based Fire Protection Systems Introduction Fire protection systems are provided in or at a building to safeguard the lives of building
More informationProgram No. 1.6.1. Section Heading
ENVIRONMENTAL HEALTH AND SAFETY EHS PROGRAM MANUAL Program Title 1.0 INTRODUCTION The New York City Fire Department (FDNY) is responsible for approving and/or inspecting fire alarm systems, buildings,
More informationAutomatic fire-extinguishing systems for commercial cooking
Automatic fire-extinguishing systems for commercial cooking Leading Items First Ignited in Eating and Drinking Establishment Structure Fires, 2000-2004 Annual Averages Cooking materials, incl. food and
More informationFACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST
FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST Date of Inspection: Conducted by: Location: Reviewed by: Date of Review: Comments or additional corrective action taken as a result
More informationBERMAD Fire Protection
400E-2M/700E-2M IOM Bermad Electrically Controlled Deluge Valve with EasyLock Manual Reset Model: 400E-2M/700E-2M INSTALLATION OPERATION MAINTENANCE Application Engineering BERMAD 400E-2M/700E-2M Bermad
More information1.0 General. Inspection, Testing, and Maintenance 1 of 8
1.0 General 1.1 Scope This specifications covers the minimum requirements for the inspection, testing, and maintenance of the existing Notifier fire alarm systems at Bergen Community College (BCC) campus
More informationInspection, Testing and Preventive Maintenance
Fire Protection Systems and Equipment Introduction HSB Professional Loss Control Two Crossroads Drive Bedminster, NJ 07921 1-800-472-1866 www.hsbplc.com The owners and operators of industrial plants, shopping
More informationFire Protection Program Of Chashma Nuclear Power Generating Station Pakistan Atomic Energy Commission 5/28/2015 1
Fire Protection Program Of Chashma Nuclear Power Generating Station Pakistan Atomic Energy Commission 5/28/2015 1 Nuclear Power in Pakistan Nuclear Power Plants Capacity (MWe) Year of Commissioning In
More informationFire Sprinkler System Maintenance and Testing Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS
Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Introduction When properly installed and maintained, automatic fire sprinkler systems have proven to be the most effective means for protecting
More informationManual Document Page Issue Date TABLE OF CONTENTS
, Manual USQ #15-1163-D ESHQ 1 of 23 TABLE OF CONTENTS 1.0 PURPOSE AND SCOPE... 2 2.0 IMPLEMENTATION... 2 3.0 STANDARD... 2 3.1 Facility Management Support Requirements... 3 3.2 Fire System Discrepancy
More informationPANAMA MARITIME AUTHORITY MERCHANT MARINE CIRCULAR MMC-281
PANAMA MARITIME AUTHORITY MERCHANT MARINE CIRCULAR MMC-281 PanCanal Building Albrook, Panama City Republic of Panama Tel: (507) 501-5355 jortega@segumar.com To: Ship-owners/Operators, Company Security
More informationGeneral Fire Code Requirements Within Commercial Tenant Spaces
FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding
More informationFire Pump Plan Review March 2010
Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:
More informationMOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Plan Review 2009 International Fire Code and NFPA 20 Date of Review / / BLD201 - Project Address: Project Name: Contractor s Business
More informationVehicle Fire Protection. An Ownerʼs Manual for ANSUL Fire Suppression/Detection Systems
Vehicle Fire Protection An Ownerʼs Manual for ANSUL Fire Suppression/Detection Systems 002792 Off-road vehicles do have fires Statistics show that off-road vehicles burn with alarming frequency. These
More informationOVERVIEW SCOPE DEFINITIONS
Procedure No 400.10 Subject: Fire Protection Impairment Program Reference: NFPA (see bottom of page 5) Effective Date: March 2008 Distribution All Employees Review Date: April 2008 Purpose: To establish
More informationCity of Columbus Department of Building and Zoning Services
City of Columbus Department of Building and Zoning Services Introduction This manual is designed to provide you, the contractor, owner or design professional with a step-by-step guide to our process, beginning
More informationTECHNICAL ADVISORY BULLETIN
RISK CONTROL AND CLAIM ADVOCACY PRACTICE TECHNICAL ADVISORY BULLETIN November 2014 www.willis.com FIRE PUMP TESTING Fire pumps are a critical part of a fire protection system, especially when they are
More informationTRAINING AND EQUIPMENT MANUAL HOSE PRACTICES EFFECTIVE: OCTOBER 2007
TRAINING AND EQUIPMENT MANUAL HOSE PRACTICES 301.010 ANNUAL SERVICE TEST FOR FIRE HOSE EFFECTIVE: OCTOBER 2007 The Department will test all fire hose annually. The testing of fire hose determines its serviceability.
More informationElgin Fire Department
Breathing Operations Elgin Fire Department Safety - Respiratory Protection Program - Self Contained Apparatus (SCBA) Policy # 2024.01 Issued: 09/08/06 Subject: Purpose: Scope: Self Contained Breathing
More informationButch Browning State Fire Marshal, Bobby Jindal Governor - Licensing Requirements
LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS OFFICE OF STATE FIRE MARSHAL, CODE ENFORCEMENT AND BUILDING SAFETY H. Butch Browning State Fire Marshal Bobby Jindal Governor Licensing Law and Rules
More informationDesign & Construction Standards, Revised January 2013 5.21.30-1
PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for fire pumps. This document is not intended to serve as a guide specification.
More informationTo: All Shipowners, Ship Managers, Ship Masters and Classification Societies
海 事 處 船 舶 事 務 科 香 港 中 環 統 一 碼 頭 道 38 號 海 港 政 府 大 樓 ---------- 香 港 郵 箱 4155 號 MARINE DEPARTMENT Shipping Division Harbour Building 38 Pier Road, Central, Hong Kong ----------- G.P.O.Box 4155 網 站 Website
More informationRisk Engineering Guideline
www.hdi.global HDI Risk Consulting Risk Engineering Guideline Impairment of fire protection systems Basic protection systems should not be impaired without adequate replace compensation with provisions.
More informationFIRE SPRINKLER SYSTEM SUPERVISORY SERVICE User s Guide (DamarNet RAR Service)
FIRE SPRINKLER SYSTEM SUPERVISORY SERVICE User s Guide (DamarNet RAR Service) The information provided in this user guide pertains to fire suppression sprinkler system monitoring service provided over
More informationNMSU FIRE DEPARTMENT Commercial Kitchen Fire Suppression Worksheet
This Commercial Kitchen Automatic Fire has been created to assure all documentation has been submitted to assist you in assuring proper plans and documentations has been submitted and reviewed by New Mexico
More informationDivision 21. Fire Suppression
21 00 00. Fire Suppression For campus projects that require a fire suppression system shut down in a campus facility, a Shut Down Procedure of Fire Safety System Sheet must be completed and filed seven
More informationBUILDING OWNERS - SERVICE RELATED ISSUES FOR FIRE ALARM SYSTEMS
BUILDING OWNERS - SERVICE RELATED ISSUES FOR FIRE ALARM SYSTEMS Owners have numerous responsibilities as it pertains to the maintenance and operation of a building s fire safety equipment. The liabilities
More informationACADEMY ACADEMY CUSTOMER GUIDE. ACADEMY FIRE PROTECTION (800)773-4736 www.academyfire.com. Academy Fire Protection Customer Guide.
FIRE PROTECTION CUSTOMER GUIDE THE ADVANTAGE 24/7 Fast, Reliable Service AHJ Interaction and Consultation Automated Custom Reporting Client Web Portal Dedicated Account Manager Flat Rate Price Plans Inventory
More informationFIRE ALARM /FIRE PROTECTION OUTAGE/IMPAIRMENT RESPONSE GUIDELINE
Page 1 of 10 FIRE ALARM /FIRE PROTECTION OUTAGE/IMPAIRMENT RESPONSE GUIDELINE SYSTEM TESTING 1. Testing of the Fire Alarm and Fire Protection Systems 1.1. The Building Engineer, Electrician, Plumber (or
More informationFire Alarm and Protection Impairment Policy and Procedures
1.0 Policy Statement The University of New Haven has developed a Fire Alarm and Protection Impairment Plan in accordance with the National Fire Protection Associations (NFPA) codes. Specific codes referenced
More informationEnvironment of Care Fire Safety Management Plan 2014
Environment of Care Fire Safety Management Plan 2014 Updated 4.29.2014 PURPOSE The purpose of the Fire Safety Management Plan is to ensure that all facilities are designed, constructed, maintained, and
More informationGUIDELINE 5. CLASSES OF FIRE, TYPES OF PORTABLE FIRE EXTINGUISHERS, INSPECTION & MAINTENANCE OF FIRE EXTINGUISHERS IN UNIVERSITY BUILDINGS
GUIDELINE 5. CLASSES OF FIRE, TYPES OF PORTABLE FIRE EXTINGUISHERS, INSPECTION & MAINTENANCE OF FIRE EXTINGUISHERS IN UNIVERSITY BUILDINGS 1.0 PURPOSE 1.1 To provide an overview of fire extinguisher use
More informationFactory owners must ensure the boiler is:
Factory owners must ensure the boiler is: * Registered with the Boilers and Pressure Vessels Division, Labour Department * Examined by an appointed examiner and has a valid certificate of fitness * Supervised
More informationFLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL
FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:
More informationTECHNICAL DATA. Dry 122a. November 12, 2013
Dry 122a 1. PRODUCT DESCRIPTION The Viking is a quick-opening device. When installed with the required external Anti-flood Device, the assembly is designed to increase the operating speed of Viking Model
More informationENGINEERING SPECIFICATION. Engineering Specification SAPPHIRE 42 Bar
Engineering Specification SAPPHIRE 42 Bar PART 1 GENERAL 1.1 DESCRIPTION OF WORK This specification outlines the requirements for a "Total Flood" SAPPHIRE Clean Agent Fire Suppression System. The work
More informationCDS TROUBLESHOOTING SECTION I. VACUUM. 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg)
CDS TROUBLESHOOTING SECTION I. VACUUM 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg) 1.1. Clogged hoses or wand tube. Disconnect hoses and carefully check for an obstruction. 1.2. Excessive
More informationISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK. Website www.iomfire.com
ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK Website www.iomfire.com ADDRESS OF PREMISES FIRE CERTIFICATE No. (where applicable).. LOCATION OF LOG BOOK. CONTENTS OF LOG BOOK Useful telephone
More informationFire Safety Plan (Single-Stage Fire Alarm System - Small Establishment)
1 Fire Safety Plan (Single-Stage Fire Alarm System - Small Establishment) Fire Safety Plan Single-Stage Fire Alarm System (small establishment) for: (Business Name) (Business Address) The reproduction
More informationAutomatic Fire Sprinkler Submittal Requirements
Automatic Fire Sprinkler Submittal Requirements All commercial and industrial buildings with a total floor area of 5000 sq. ft. shall have an approved automatic sprinkler system installed. The Windsor-Severance
More informationFIRE PROTECTION SYSTEMS ACCEPTANCE INSPECTION AND TESTING PROCEDURE
ACCEPTANCE INSPECTION AND TESTING PROCEDURE Wet Pipe Sprinkler Systems...2 Dry Pipe Sprinkler Systems...2 Clean Agent Fire Extinguishing System...4 Total Flooding Systems...4 Fire Dampers...5 Smoke Dampers...5
More informationName Of Occupancy Date. Yes No Describe
FIRE PREVENTION INSPECTION CHECKLIST For Class A Occupancy (For Assembly Buildings, Bars, Restaurants, Gyms, Churches, Arenas, Theatres or wherever people gather) Name Of Occupancy Date Physical Address
More informationDATA CENTER FIRE PROTECTION
DATA CENTER FIRE PROTECTION DATA CENTER FIRE PROTECTION The following is a summary of a few key fire protection, detection, and suppression technologies used by Minimax Fire Solutions in data centers and
More informationModule 4, Lesson 12 Fire Alarm Systems
Student Manual Module 4, Lesson 12 Fire Alarm Systems Performance Objectives At the conclusion of this lesson, you will be able to: Identify the components and functions of a fire alarm system and determine
More informationSPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT
SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT The purpose of these specifications is to insure that there are minimum
More informationTHE REPUBLIC OF LIBERIA LIBERIA MARITIME AUTHORITY
Office of Deputy Commissioner of Maritime Affairs THE REPUBLIC OF LIBERIA LIBERIA MARITIME AUTHORITY Marine Notice FIR-001 Rev. 06/12 TO: SUBJECT: ALL SHIPOWNERS, OPERATORS, MASTERS AND OFFICERS OF MERCHANT
More informationFIRE SAFETY PRECAUTIONS
FIRE SAFETY PRECAUTIONS LOG BOOK PLEASE KEEP AVAILABLE 1 Business Name Premises Information Building / Unit Number Property Name Road: (Address Line 1) (Address Line 2) Locality: Town: Post Code: Name
More informationFIRE SAFETY PLAN FOR KITCHENER, ONTARIO
FIRE SAFETY PLAN FOR KITCHENER, ONTARIO Additional information of fire safety plans may be found at our website at www.kitchener.ca/fire.htm. Before submission, please read and change all sections to address
More informationFighting Fire in Sprinklered Buildings. Student Guide
Fighting Fire in Sprinklered Buildings Student Guide Fighting Fire in Sprinklered Buildings Student Guide Table of Contents Purpose........................................................... 3 Instruction
More informationpresents Cooking With Fire Fixed Fire Suppression & Exhaust Systems for Cooking Environments Monday, 17 June, 13
presents Cooking With Fire Fixed Fire Suppression & Exhaust Systems for Cooking Environments Who is the AFSA? Safe and Secure Alberta Fire Safety Association Fire industry members working together to improve
More informationOntario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal
Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable
More informationLAWS AND REGULATIONS for AUTOMATIC EXTINGUISHING SYSTEMS
DEPARTMENT OF FORESTRY AND FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING DIVISION LAWS AND REGULATIONS for AUTOMATIC EXTINGUISHING SYSTEMS AUTOMATIC EXTINGUISHING SYSTEM PROGRAM 1131
More informationFire Safety Log Book. Premises Name: Premises Address: Date From: Date To: Location of Log Book:
Fire Safety Log Book Premises Name: Premises Address: Date From: Date To: Location of Log Book: CONTENTS PART 1 FIRE SAFETY ADVICE 1 PART 2 FIRE PRECAUTIONS 2 Section 1 Guidance on Fire Risks and Preventative
More informationUNIFIED FACILITIES CRITERIA (UFC) OPERATION AND MAINTENANCE: INSPECTION, TESTING, AND MAINTENANCE OF FIRE PROTECTION SYSTEMS
UNIFIED FACILITIES CRITERIA (UFC) OPERATION AND MAINTENANCE: INSPECTION, TESTING, AND MAINTENANCE OF FIRE PROTECTION SYSTEMS APPROVED FOR PUBLIC RELEASE; DISTRIBUTION UNLIMITED UNIFIED FACILITIES CRITERIA
More informationSTATEMENT OF WORK FOR FIRE ALARM SYSTEM TESTING & MAINTENANCE. Project No. SAQMMA-07-C0060 ***OUAGA, BURKINA FASO***
STATEMENT OF WORK FOR FIRE ALARM SYSTEM TESTING & MAINTENANCE Project No. SAQMMA-07-C0060 ***OUAGA, BURKINA FASO*** CONTENTS: 1.0 Introduction 2.0 Objectives 3.0 General Requirements 4.0 Specific Requirements
More informationColumbia University Medical Center. Policies and Procedures for Shutdowns and Modifications to Fire Alarm Systems and Fire Suppression Systems
Columbia University Medical Center Policies and Procedures for Shutdowns and Modifications to Fire Alarm Systems and Fire Suppression Systems 1. Modifications to Fire Alarm or Fire Suppression System A.
More informationCHAPTER 120-3-23 TABLE OF CONTENTS
THE RULES OF THE SAFETY FIRE COMMISSIONER ARE HEREBY FURTHER AMENDED BY ADDING A NEW CHAPTER 120-3-2 3 E N T I T L E D RULES AND REGULATIONS FOR INSTALLATION; INSPECTION; RECHARGING, REPAIRING, SERVICING
More informationFIRE ALARM SYSTEM CHECKLIST For Addressable Systems PRIOR TO INSPECTION
Building Name/Location: Installing Company: Observation By: Date: Time: 1 Building Occupants, Authorities and Alarm Monitoring Co Have Been Notified 2 FACP Manufacturer and Panel is Approved for NCSU Campus
More informationEXETER TOWNSHIP DRY OR WET CHEMICAL FIRE SUPPRESSION SYSTEMS
DRY OR WET CHEMICAL FIRE SUPPRESSION SYSTEMS POLICY STATEMENT This policy applies to NEW Dry or Wet chemical fire suppression systems. The Authority Having Jurisdiction will not waive major criteria in
More informationFIRE SAFETY REGISTER. Premises Name: Premises Address: Fire Safety Manager: Contact No. Kerry County Fire Service www.kerrycoco.ie
FIRE SAFETY REGISTER Premises Name: Premises Address: Fire Safety Manager: Contact No. Kerry County Fire Service www.kerrycoco.ie 1 CONTENTS Section Title Page 1.0 Introduction 3 2.0 Guidance for the completion
More informationINSPECTION, MAINTENANCE AND RECHARGE SERVICE MANUAL P/N 16303
WATER MIST HAND PORTABLE FIRE EXTINGUISHERS Model B270 ¾ Gallon Model B272 2 ½ Gallon INSPECTION, MAINTENANCE AND RECHARGE SERVICE MANUAL P/N 6303 All fire extinguishers should be installed, inspected
More informationAerosol Fire Suppression. Your Choice for Special Hazard Fire Protection
Aerosol Fire Suppression Your Choice for Special Hazard Fire Protection Traditional Special Hazard Fire Protection Centers Around Two Technologies Water deluge and chemical agent fixed systems protect
More informationPotter Electric Sprinkler Monitoring Training Manual
R Potter Electric Sprinkler Monitoring Training Manual 1 #8704200D 2 Contents Foreword... 4 Introduction... 5 Fire Alarm Signals... 6 Types Of Sprinkler Systems... 7 Wet Pipe Sprinkler Systems... 8 Straight
More informationCHAPTER. Standpipes and Hose Systems OVERVIEW. Standpipe and Hose Systems Defined
Standpipes and Hose Systems CHAPTER 3 This chapter, which opens with an overview of standpipe and hose systems, is intended to assist the registered design professional (RDP), commissioning agent, authority
More informationFirefighter Review. Instructor Guide
Firefighter Review Instructor Guide Session Reference: 3 Topic: Attack Line Handling Level of Instruction: Time Required: Three Hours Materials: Two Fully Equipped Pumpers Structure for Use in Advancing
More informationHOUSTON FIRE DEPARTMENT LIFE SAFETY BUREAU (LSB)
HOUSTON FIRE DEPARTMENT LIFE SAFETY BUREAU (LSB) LSB STANDARD 02, REV 03 INSPECTION AND TESTING OF FIRE PROTECTION AND LIFE-SAFETY EQUIPMENT. SUPERSEDES: LSB Standard 02, Rev 02, dated 12/31/2010 Note:
More informationINSPECTION, TESTING AND MAINTENANCE OF WATER-BASED FIRE PROTECTION SYSTEMS
GAP.12.0.1 A Publication of Global Asset Protection Services LLC INSPECTION, TESTING AND MAINTENANCE OF WATER-BASED FIRE PROTECTION SYSTEMS INTRODUCTION National Fire Protection Association (NFPA) documents
More informationFire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines
Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines Red Oak Fire Rescue Office of the Fire Marshal 547 N. Methodist Red Oak, TX 75154 Phone: 469-218-7713 Fax: 468-218-7719
More informationF.Y.I. Specifying Fire Protection Systems Using Division 13
F.Y.I. Specifying Fire Protection Systems Using Division 13 Automatic fire sprinkler systems and fire alarm and detection systems are increasingly installed in modern buildings. Even where building codes
More informationFire detection, alarm, and suppression systems are installed to:
Fire detection, alarm, and suppression systems are installed to: Notify occupants to escape a fire Summon emergency responders Initiate suppression systems Supervise suppression systems for operational
More informationNYC SUB-SYSTEMS INSTALLATION & SERVICE REQUIREMENTS OF THE FDNY
NYC SUB-SYSTEMS INSTALLATION & SERVICE REQUIREMENTS OF THE FDNY Presented by: James Goerl Metro Protection Systems, Inc. jgoerl@metroprotectionsystems.com Agenda Introduction & Learning Objectives History
More informationTechnical Data. Installation
Technical Services: Tel: (800) 81-91 / Fax: (800) 791-5500 Model 51 (1) Riser Manifold 1-1/ thru 6 Inch (DN40 thru DN150) For NFPA 1 Sprinkler Systems General Description The Figure 51 (1) Riser Manifolds
More informationFire Protection Systems, Appliances and Compressed Gas Cylinders Periodic Maintenance, Inspection and Testing
Fire Protection Systems, Appliances and Compressed Gas Cylinders Periodic Maintenance, Inspection and Testing Notice to Shipowners, Ship Operators, Managers, Masters, Owners Representatives and Recognised
More informationPART II: New Construction Inspections and Acceptance Testing Procedures
Stafford County Fire Marshal s Office Handbook for Building/Fire Code Policies and Guidelines PART II: New Construction Inspections and Acceptance Testing Procedures Phone: 540-658-8648 Fax: 540-658-9128
More informationINSPECTION AND TESTING OF FIRE ALARM SYSTEMS
Page 1 January 2, 2009 INSPECTION AND TESTING OF FIRE ALARM SYSTEMS Introduction Early warning plays a key role in a healthcare facility s ability to safely evacuate its residents during a fire emergency.
More information