ESFR Sprinkler Systems

Size: px
Start display at page:

Download "ESFR Sprinkler Systems"

Transcription

1 ESFR Sprinkler Systems Paul Kennedy

2 Evolution of Sprinkler Systems 1870 s Perforated Pipes followed by tar coated perforated pipes 1890 s Temperature Activated Fusible Link Sprinkler with toothed deflector 1920 s Glass Bulb with toothed deflector (Grinnell) 1950 s Development of the Standard [or] Spray Sprinkler 1970 s In-Rack Sprinkler Protection Introduced 1980 s Development of ESFR Sprinkler by FM for Storage Hazards

3 Development ESFR Sprinkler Systems What is required to eliminate In-Rack Sprinkler Protection without increasing the risk to property / life? Residential Sprinkler Research Project Large Drop Sprinkler Research Project Fast Response Sprinkler ESFR Early Suppression Fast Response Larger Drops with Higher Kinetic Energy

4 Fire Control versus Fire Suppression Up to the introduction of ESFR Sprinklers, Sprinkler Systems were designed to Control a Fire by limiting it s size by distribution of water so as to decrease the heat release rate and pre-wet adjacent combustibles, while controlling ceiling gas temperatures to avoid structural damage [NFPA ]. Fire Suppression refers to sharply reducing the heat release rate of a fire and preventing its regrowth by means of direct and sufficient application of water through the fire plume to the burning fuel surface [NFPA ].

5 Comparison of Control & Suppression

6 Design Codes and Standards for ESFR NFPA 13 FM Data Sheet 8-9 LPC Rules Incorporating BS EN [ TB 209 ]

7 New FM Terminology Old Terminology CMDA Control Mode Density Area CMSA Control Mode Specific Application SM Suppression Mode ESFR Early Suppression Fast Response New Terminology Storage Sprinkler Non Storage Sprinkler Special Protection

8 Choosing the Correct Storage Scheme Determine the highest applicable Commodity Hazard [FM Data Sheet 8-1] Class 1 (Metal Products, Glass Products in corrugated cartons) Class 2 (Class 1 products in wooden boxes or small cartons in larger corrugated cartons) Class 3 (Paper Products, Leather Products, Wood Products, Textiles) Class 4 (Class 1, 2 or 3 with 15% by weight of expanded or unexpanded plastic) Cartoned Unexpanded Plastic (High-density Plastic) Cartoned Expanded Plastic (Low-density Plastic) Uncartoned Unexpanded Plastic Uncartoned Expanded Plastic Establish the storage type Solid Piled Palletized Shelving Bin-Box Open Frame Racks Apply the appropriate Protection Table in Data Sheet 8 9

9 Protection Tables Data Sheet Protection Tables available in Data Sheet 8 9 Commodity Commodity Hazard Solid-Piled, Palletized, Shelf, or Bin-Box Storage Arrangement Storage Type Open-Frame Rack Storage Arrangements Class 1, 2 and 3 Table 2 Table 7 Class 4 and Cartoned Unexpanded Plastic Table 3 Table 8 Cartoned Expanded Plastic Table 4 Table 9 Uncartoned Unexpanded Plastic Table 5 Table 10 Uncartoned Expanded Plastic Table 6 Table 11

10 Protection Table Data Sheet 8-9 Green Areas represent those options for which a reduced hose stream allowance of 950 L / min. and a reduced duration of 1 hour is allowed.

11 Comparison Storage to Control Mode Commodity Hazard : Class 3 Storage Type : Open Frame Rack Storage Ceiling Height : 13.5 meters Storage Height : 12.0 meters Commodity Solid-Piled, Palletized, Shelf, or Bin-Box Storage Arrangement Storage Type Open-Frame Rack Storage Arrangements Class 1, 2 and 3 Table 2 Table 7 Class 4 and Cartoned Unexpanded Plastic Table 3 Table 8 Cartoned Expanded Plastic Table 4 Table 9 Uncartoned Unexpanded Plastic Table 5 Table 10 Uncartoned Expanded Plastic Table 6 Table 11

12 Storage Height = 12.0 m Ceiling Height = 13.5 m Comparison Storage to Control Mode Commodity Hazard : Class 3 Storage Type : Open Frame Rack Storage Ceiling Height : 13.5 meters Storage Height : 12.0 meters Description Roof & Rack Ceiling Area (m 2 ) Ceiling Density (L /min. / m 2 ) 12.2 No. In-Rack Sprinklers Operating 10.0 Min. Flow In-Rack (L / min. / Sprinkler) Storage K320 K320 No. Sprinklers 12 Sprinkler Head Pressure (bar) 3.5 Hose Allowance (L / min.) 1, Duration (min.) Water Storage Volume (m 3 )

13 Limitations to Storage Sprinkler The use of solid shelving (i.e., plywood shelves) > 6.0m 2 within storage racks is not allowable, without additional in-rack sprinklers. A minimum of 36 [920mm] must be maintained between the top of storage and the ESFR sprinkler head. Flue spaces between storage pallet loads within storage racks must be maintained. The storage of flammable/combustible liquids is generally not allowed. Certain foam containing products such as unboxed (exposed) furniture within storage racks. Roof vents are generally not allowed unless certain restrictions are met.

14 Impact of Obstructions to Storage ESFR systems are very intolerant of obstructions, which may be caused by steel roof supports (trusses), light fixtures, and ductwork. It is critical that no objects between the top of storage and the ceiling-level sprinklers interfere with the sprinkler s proper discharge pattern. NFPA

15 Inspection, Testing & Maintenance NFPA 25 FM Data Sheet 2-81 LPC Rules Incorporating BS EN [ TB 203 ]

16 THANK YOU

FireLock LP-46 Storage Sprinkler V4601 Pendent FM Approved, culus Listed See Submittal Publication 40.95

FireLock LP-46 Storage Sprinkler V4601 Pendent FM Approved, culus Listed See Submittal Publication 40.95 .61 FireLock Storage Design Guide This Firelock Storage Design Guide (the "Guide") illustrates the performance characteristics of the full offering of Victaulic Storage s based upon selected design criteria

More information

Stored Palletized, Solid Piled, Bin Boxes, or Shelf Storage (12.2)

Stored Palletized, Solid Piled, Bin Boxes, or Shelf Storage (12.2) Stored Palletized, Solid Piled, Bin Boxes, or Shelf Storage (12.2) Formally part of NFPA 231 12.2.1 General 12.2.2 Protection of Class I - IV Commodities 12.2.3 Protection of Plastic & Rubber Commodities

More information

Denver Fire Department Idle Pallet Storage Guidelines Per NFPA 13_Chpt 12

Denver Fire Department Idle Pallet Storage Guidelines Per NFPA 13_Chpt 12 Idle wood and plastic pallets introduce a severe fire condition. Stacking idle pallets in piles is the best arrangement of combustibles to promote rapid spread of fire, heat release, and complete combustion.

More information

NFPA 13 2002 FAQs. 3. Can plastic pipe be used on a sprinkler system complying with NFPA 13?

NFPA 13 2002 FAQs. 3. Can plastic pipe be used on a sprinkler system complying with NFPA 13? NFPA 13 2002 FAQs Responses to FAQs are prepared by NFPA technical staff to assist users in reading and understanding NFPA codes and standards. The responses, however, are not Formal Interpretations issued

More information

esfr pendent sprinkler vk510 (k25.2)

esfr pendent sprinkler vk510 (k25.2) January 17, 2014 Sprinkler 124a 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK510 incorporates the capability to suppress specific high-challenge fires. The addition

More information

ESFR DRY PENDENT SPRINKLER VK502 (K14.0) TECHNICAL DATA

ESFR DRY PENDENT SPRINKLER VK502 (K14.0) TECHNICAL DATA December 19, 2013 Sprinkler 122j 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Dry Pendent Sprinkler VK502 is a fast response fusible element type sprinkler designed for use in storage areas

More information

Technical Article. Sprinkler Protection for High Bay and Automated Storage in Warehouse-Type Storage Facilities

Technical Article. Sprinkler Protection for High Bay and Automated Storage in Warehouse-Type Storage Facilities Technical Article for High Bay and Automated Storage in Warehouse-Type Storage Facilities Scott Martorano, CFPS Senior Manager Technical Services February, 2010 Worldwide Fire Protection www.vikinggroupinc.com

More information

Flammable and Combustible Liquid

Flammable and Combustible Liquid Flammable and Combustible Liquid Storage Challenges Christopher J. Wieczorek, Ph.D., FM Global David Nugent, The Valspar Corporation Global Research Update: High Challenge Storage Protection 27 June 2012,

More information

Extended Coverage Sprinklers

Extended Coverage Sprinklers Extended Coverage Sprinklers Welcome ASPE Wally Barker Sprinkler Systems 101 MATERIALS OF CONSTRUCTION The components that make up a sprinkler head are: Frame or casting Deflector Fusible element or frangible

More information

EFSN Training i Module 1. 90 Minutes

EFSN Training i Module 1. 90 Minutes Introduction to Sprinklers EFSN Training i Module 1 90 Minutes Topics How sprinklers work Performance of sprinkler systems Types of Sprinkler Introduction to sprinkler systems Introduction ti to sprinkler

More information

Warehouse Checklist. Warehouse Construction

Warehouse Checklist. Warehouse Construction PAGE 1 Warehouse Checklist Recent NFPA statistics estimate that in 1998 approximately 36,000 fires occurred in structures used for storage, accounting for $687mm of damage (over 10% of total fire damage

More information

Construction Warehouse. Culminating Experience in Fire Protection Engineering FPE 596 Prepared by Ben Johnson

Construction Warehouse. Culminating Experience in Fire Protection Engineering FPE 596 Prepared by Ben Johnson Construction Warehouse Culminating Experience in Fire Protection Engineering FPE 596 Prepared by Ben Johnson Construction Warehouse Waste Treatment and Immobilization Plant (WTP) Project U.S. Department

More information

Risk Guidance Note 03. Management of In-Rack Automatic Sprinklers (IRAS)

Risk Guidance Note 03. Management of In-Rack Automatic Sprinklers (IRAS) Risk Guidance Note 03 Management of In-Rack Automatic Sprinklers (IRAS) Overview In-rack automatic sprinklers (IRAS) are often a fundamental part of the fire protection solution for racked storage areas.

More information

HIGH-PILED COMBUSTIBLE STORAGE

HIGH-PILED COMBUSTIBLE STORAGE CHAPTER 23 HIGH-PILED COMBUSTIBLE STORAGE SECTION 2301 GENERAL 2301.1 Scope. High-piled combustible storage shall be in accordance with this chapter. In addition to the requirements of this chapter, the

More information

HIGH-PILED COMBUSTIBLE STORAGE

HIGH-PILED COMBUSTIBLE STORAGE CHAPTER 23 HIGH-PILED COMBUSTIBLE STORAGE SECTION FC 2301 GENERAL 2301.1 Scope. This chapter shall govern high-piled combustible storage, and the design, installation, operation and maintenance of any

More information

FLAMMABLE AND COMBUSTIBLE LIQUIDS

FLAMMABLE AND COMBUSTIBLE LIQUIDS GAP.8.1.0 A Publication of Global Asset Protection Services LLC FLAMMABLE AND COMBUSTIBLE LIQUIDS INTRODUCTION National Fire Protection Association (NFPA) documents describe a level of fire protection

More information

Name Of Occupancy Date. Yes No Describe

Name Of Occupancy Date. Yes No Describe FIRE PREVENTION INSPECTION CHECKLIST For Class A Occupancy (For Assembly Buildings, Bars, Restaurants, Gyms, Churches, Arenas, Theatres or wherever people gather) Name Of Occupancy Date Physical Address

More information

High Pressure Water Mist Systems: Alternative Solution For Critical Civil Applications

High Pressure Water Mist Systems: Alternative Solution For Critical Civil Applications International Water Mist Conference, London, United Kingdom,23-24 September, 2009 High Pressure Water Mist Systems: Alternative Solution For Critical Civil Applications Fire Fighting In Civil Applications

More information

HealthandSafetyOntario.ca. Introduction. Storage Containers. Storing Flammable Liquids

HealthandSafetyOntario.ca. Introduction. Storage Containers. Storing Flammable Liquids Flammable Liquids Storage Introduction This guideline is designed to help you store flammable liquids safely. It is based on the requirements of the Ontario Fire Code, Part 4, and of the Regulations for

More information

Insight. Storage Fires. Balanced Risk Engineering Solutions. Understanding the Risk. Commodity Classification. Storage Configuration

Insight. Storage Fires. Balanced Risk Engineering Solutions. Understanding the Risk. Commodity Classification. Storage Configuration Balanced Risk Engineering Solutions Storage Fires Understanding the Risk Many of the most costly fires occur in warehouses and storage areas, where often a high fire risk is combined with high values and/or

More information

Watermist fire suppression systems for commercial low hazard occupancies

Watermist fire suppression systems for commercial low hazard occupancies Watermist fire suppression systems for commercial low hazard occupancies Watermist fire protection systems are fire suppression systems that have emerged as an alternative fire safety solution for specific

More information

FIRE SPRINKLER SYSTEM DESIGN, ENGINEERING EXEMPTION POLICY FOR (Effective April 1, 2006)

FIRE SPRINKLER SYSTEM DESIGN, ENGINEERING EXEMPTION POLICY FOR (Effective April 1, 2006) State of Tennessee Department of Commerce and Insurance Board of Architectural and Engineering Examiners 500 James Robertson Parkway Nashville, TN 37243 1142 800 256 5758 615 741 3221 (Nashville Area)

More information

Fire Protection Requirements of Empty Intermediate Bulk Containers (IBCs)

Fire Protection Requirements of Empty Intermediate Bulk Containers (IBCs) Research TECHNICAL REPORT Fire Protection Requirements of Empty Intermediate Bulk Containers (s) Fire Protection Requirements of Empty Intermediate Bulk Containers (s) by Seth E. Sienkiewicz FM Global

More information

AON SPRINKLER CERTIFICATION

AON SPRINKLER CERTIFICATION Form 1 Application for Approval of Basic Design Parameters for Automatic Sprinkler System Installations 1. Name of Protected Premises Site Name Address 2. Work to be Carried Out New System Extension or

More information

SPRINKLER RULES & STANDARDS IN EUROPE CEA 4001 & EN 12845

SPRINKLER RULES & STANDARDS IN EUROPE CEA 4001 & EN 12845 SPRINKLER RULES & STANDARDS IN EUROPE CEA 4001 & EN 12845 DAEGU: 20 th August 2010 Karim KARZAZI 1 Development of sprinkler rules & standards in Europe. Overview of past, existing and future situation

More information

Fighting Fire in Sprinklered Buildings. Student Guide

Fighting Fire in Sprinklered Buildings. Student Guide Fighting Fire in Sprinklered Buildings Student Guide Fighting Fire in Sprinklered Buildings Student Guide Table of Contents Purpose........................................................... 3 Instruction

More information

Flammable Liquids Storage

Flammable Liquids Storage A Health and Safety Guideline for Your Workplace Flammable Liquids Storage Introduction This guideline is designed to help you store flammable liquids safely. It is based on the requirements of the Ontario

More information

I.CHEM.E. SYMPOSIUM SERIES NO. 97

I.CHEM.E. SYMPOSIUM SERIES NO. 97 FIRE HAZARDS OF FLAMMABLE LIQUIDS IN SMALL CONTAINERS J. F. Siddle* Standards of fire protection for metal drums and smaller metal containers of flammable liquids have been well defined and have proved

More information

Full scale tunnel fire tests of VID Fire-Kill Low Pressure Water Mist Tunnel Fire Protection System in Runehamar test tunnel, spring 2009

Full scale tunnel fire tests of VID Fire-Kill Low Pressure Water Mist Tunnel Fire Protection System in Runehamar test tunnel, spring 2009 Full scale tunnel fire tests of VID Fire-Kill Low Pressure Water Mist Tunnel Fire Protection System in Runehamar test tunnel, spring 2009 By Carsten Palle, VID Fire-Fill, www.vid.eu Presented at ISTSS

More information

In accordance with NFPA 30, these containers are not to store Class I flammable liquids.

In accordance with NFPA 30, these containers are not to store Class I flammable liquids. In accordance with NFPA 30, these containers are not to store Class I flammable liquids. Zurich recommends storing these containers in dedicated liquid storage rooms, detached buildings, or in listed dispensing

More information

Flammable Liquids Storage

Flammable Liquids Storage A Health and Safety Guideline for Your Workplace Flammable Liquids Storage Introduction This guideline is designed to help you store flammable liquids safely. It is based on the requirements of the Ontario

More information

HATFIELD TOWNSHIP. FLAMMABLE and COMBUSTIBLE LIQUIDS PERMIT APPLICATION PROCEDURES

HATFIELD TOWNSHIP. FLAMMABLE and COMBUSTIBLE LIQUIDS PERMIT APPLICATION PROCEDURES HATFIELD TOWNSHIP FLAMMABLE and COMBUSTIBLE LIQUIDS PERMIT APPLICATION PROCEDURES A flammable and combustible liquids permit is required to store, transport on site, dispense, use or handle flammable and

More information

WAREHOUSE PROPERTY PROTECTION

WAREHOUSE PROPERTY PROTECTION STRATEGIC OUTCOMES PRACTICE TECHNICAL ADVISORY BULLETIN October 2011 WAREHOUSE PROPERTY PROTECTION Among the most challenging occupancies from a property loss control viewpoint are warehouses, distribution

More information

Casey C. Grant, P.E., FSFPE Research Director Fire Protection Research Foundation

Casey C. Grant, P.E., FSFPE Research Director Fire Protection Research Foundation RESEARCH FOUNDATION ACTIVITIES AND OUTCOMES IN DETECTION AND SUPPRESSION SYSTEMS Casey C. Grant, P.E., FSFPE Research Director Fire Protection Research Foundation Madrid, del 23 al 25 de febrero de 2010

More information

Type EA-1 PROTECTOSPRAY Directional Spray Nozzles, Automatic, Medium Velocity General Description

Type EA-1 PROTECTOSPRAY Directional Spray Nozzles, Automatic, Medium Velocity General Description Worldwide Contacts www.tyco-fire.com Type EA-1 PROTECTOSPRAY Directional Spray Nozzles, Automatic, Medium Velocity General Description The TYCO Type EA-1 PROTECTO- SPRAY Directional Spray Nozzles are automatic

More information

1.0 Purpose... 4. 2.0 Definitions...4. 3.0 Hot Work Operations. 5

1.0 Purpose... 4. 2.0 Definitions...4. 3.0 Hot Work Operations. 5 HOT WORK PROGRAM Introduction The University of Kentucky recognizes a potential for fire from hot work operations. For that reason this program should be implemented in all departments at the University

More information

Automatic Fire Sprinkler Submittal Requirements

Automatic Fire Sprinkler Submittal Requirements Automatic Fire Sprinkler Submittal Requirements All commercial and industrial buildings with a total floor area of 5000 sq. ft. shall have an approved automatic sprinkler system installed. The Windsor-Severance

More information

ARE YOU IN COMPLIANCE WITH THE OSHA COMBUSTIBLE DUST DIRECTIVE? Revised March 18, 2009

ARE YOU IN COMPLIANCE WITH THE OSHA COMBUSTIBLE DUST DIRECTIVE? Revised March 18, 2009 Kidde Fenwal, Inc. Industrial Explosion Protection Group A UTC Fire & Security Company 400 Main Street Ashland, MA 01721 Tel 508-881-2000 Fax 508-485-3115 www.fenwalprotection.com FENWAL Protection Systems

More information

Series ELO-231B 11.2 K-factor Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description

Series ELO-231B 11.2 K-factor Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Series ELO-231B 11.2 K-factor Upright and Pendent Sprinklers Standard Response, Standard Coverage General Description IMPORTANT Always refer

More information

2007 Edition HAZARD CLASSIFICATION FOR NFPA 13 SPRINKLER DESIGN NFPA 13 HAZARD CLASSIFICATION. Why does it matter? Chapter 11-21

2007 Edition HAZARD CLASSIFICATION FOR NFPA 13 SPRINKLER DESIGN NFPA 13 HAZARD CLASSIFICATION. Why does it matter? Chapter 11-21 HAZARD CLASSIFICATION FOR NFPA 13 SPRINKLER DESIGN Division of Fire Safety Why does it matter? Chapter 11-21 Sprinkler Demand Hose Demand Duration MFA Course #644 - May 2010 Current NFPA 13? Why does it

More information

Willis Technical Advisory Bulletin

Willis Technical Advisory Bulletin Willis Technical Advisory Bulletin Warehouse Property Protection February 2007 Among the most challenging occupancies from a property loss control viewpoint are warehouses, distribution centers and large

More information

Model SW-20 and SW-24 11.2 K-factor Extended Coverage Ordinary Hazard Horizontal Sidewall Sprinklers (Standard Response) General Description

Model SW-20 and SW-24 11.2 K-factor Extended Coverage Ordinary Hazard Horizontal Sidewall Sprinklers (Standard Response) General Description Worldwide Contacts www.tyco-fire.com Model SW-20 and SW-24 11.2 K-factor Extended Ordinary Hazard Horizontal Sidewall s (Standard ) General Description 11.2 K-factor, Extended Ordinary s, Standard are

More information

INTERACTION OF SPRINKLERS WITH SMOKE AND HEAT VENTS

INTERACTION OF SPRINKLERS WITH SMOKE AND HEAT VENTS INTERACTION OF SPRINKLERS WITH SMOKE AND HEAT VENTS Craig L. Beyler and Leonard Y. Cooper Fire Science and Engineering Baltimore, Maryland EXECUTIVE SUMMARY There has been an ongoing controversy about

More information

A Code Review for Emergency Generators and Indoor Use of Portable Generators

A Code Review for Emergency Generators and Indoor Use of Portable Generators A Code Review for Emergency Generators and Indoor Use of Portable Generators By: the Fire and Life-Safety Group (FLS) Fire Code requires that emergency generators be stationary generators. Therefore, a

More information

Effectiveness of sprinklers in residential premises: Section 4: Benchmark tests. Project report number 204505. Dr Corinne Williams and R Harrison

Effectiveness of sprinklers in residential premises: Section 4: Benchmark tests. Project report number 204505. Dr Corinne Williams and R Harrison Effectiveness of sprinklers in residential premises: Section 4: Benchmark tests Project report number 2455 Dr Corinne Williams and R Harrison February 24 Section 4: Benchmark tests Contents 4 Benchmark

More information

Quick response concealed horizontal sidewall sprinkler

Quick response concealed horizontal sidewall sprinkler January 1, 2011 Sprinkler 63a 1. DESCRIPTION Viking Quick Response Concealed Horizontal Sidewall Sprinkler VK408 is a small solder link and lever spray sprinkler designed for installation on concealed

More information

TECHNICAL DATA 2. LISTINGS AND APPROVALS. Spray Nozzle 11. December 20, 2013

TECHNICAL DATA 2. LISTINGS AND APPROVALS. Spray Nozzle 11. December 20, 2013 Spray Nozzle 11 1. DESCRIPTION Viking Model C-1 Window Sprinklers are non-automatic, open, outside intended for protection of windows, walls, and roofs against exposure fires. The directional discharge

More information

CONSULTING from DESIGN to PROJECT MANAGEMENT We Transform your Vision into Productive Force

CONSULTING from DESIGN to PROJECT MANAGEMENT We Transform your Vision into Productive Force 2012 CONSULTING from DESIGN to PROJECT MANAGEMENT We Transform your Vision into Productive Force Consulting : from Design to Project IBLS can provide complete solutions in the Design, Procurement and Project

More information

F.Y.I. Specifying Fire Protection Systems Using Division 13

F.Y.I. Specifying Fire Protection Systems Using Division 13 F.Y.I. Specifying Fire Protection Systems Using Division 13 Automatic fire sprinkler systems and fire alarm and detection systems are increasingly installed in modern buildings. Even where building codes

More information

city of edmonds development information

city of edmonds development information #B17 city of edmonds development information Commercial Kitchen Hood & Hood Fire Suppression System Permit Submittal Requirements PERMIT REQUIRED: CODES: FEES: A Commercial Kitchen Hood Mechanical Permit

More information

HATFIELD TOWNSHIP DRY CLEANING PLANT PERMIT APPLICATION PROCEDURES

HATFIELD TOWNSHIP DRY CLEANING PLANT PERMIT APPLICATION PROCEDURES HATFIELD TOWNSHIP DRY CLEANING PLANT PERMIT APPLICATION PROCEDURES A Dry Cleaning Plant Operational Permit is required to engage in the business of dry cleaning or to change to a more hazardous cleaning

More information

Fire Extinguishers Water Extinguishers

Fire Extinguishers Water Extinguishers Water Extinguishers Water extinguishers are suitable for Class A fires caused by combustion of solid materials such as wood, paper, straw, textiles and coal etc. Water additive extinguishers use an environmentally

More information

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable

More information

Sprinkler Identification Number. Page 1 of 6 MARCH 2014 TFP288. Worldwide Contacts. www.tyco-fire.com

Sprinkler Identification Number. Page 1 of 6 MARCH 2014 TFP288. Worldwide Contacts. www.tyco-fire.com Worldwide Contacts www.tyco-fire.com Model EC-HS 80 K-factor, Quick Response Extended Coverage Horizontal Sidewall Sprinklers Installations per VdS CEA 400, Annex E, LH/OH General Description The Model

More information

Clark County Fire Prevention

Clark County Fire Prevention Clark County Fire Prevention Mission Statement: To provide the highest level of fire protection and related services TITLE: REQUIREMENTS FOR A NEW SPRINKLER SYSTEM IN ACCORDANCE WITH THE 2002 EDITION OF

More information

Building Code Clarifications - 7. Fire Resistance

Building Code Clarifications - 7. Fire Resistance Building Code Clarifications - 7. Fire Resistance 7.1 (15-12-030) Use of combustibles in Type III construction roof assemblies Code Section (15-12-030) Use of Combustibles was revised on May 17, 2000,

More information

Fixed or Semi-Fixed Fire Protection Systems for Storage Tanks

Fixed or Semi-Fixed Fire Protection Systems for Storage Tanks Fixed or Semi-Fixed Fire Protection Systems for Storage Tanks In the early years of the oil industry, fire in a storage tank was a common occurrence. Virtually all products were stored in cone roof tanks

More information

COMPARISON TESTING IN A SIMULATED DATA PROCESSING/ TELECOMMUNICATIONS FACILITY: FM-200 AND AUTOMATIC SPRINKLER SYSTEMS

COMPARISON TESTING IN A SIMULATED DATA PROCESSING/ TELECOMMUNICATIONS FACILITY: FM-200 AND AUTOMATIC SPRINKLER SYSTEMS COMPARISON TESTING IN A SIMULATED DATA PROCESSING/ TELECOMMUNICATIONS FACILITY: FM-200 AND AUTOMATIC SPRINKLER SYSTEMS Mark L. Robin and Eric W. Forssell Hughes Associates, Inc. 5415 Hillside Lane West

More information

ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.252 WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600

ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.252 WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600 OSHA REGULATION: 9 CFR 90.5 WELDING, CUTTING, AND BRAZING ( HOT WORK ) A. POLICY. This procedure follows requirements set forth in 9 CFR 90.5.. This policy applies to all Hot Work operations being done

More information

LogisticsCentre IV Distribution Center

LogisticsCentre IV Distribution Center KCI Intermodal BusinessCentre LogisticsCentre IV LogisticsCentre IV Distribution Center Modern Warehouse/Distribution Space Ranging From 108,000± SF to 432,000± SF 10221 NW Transcon Drive 112th Street

More information

New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings

New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings Note: This information addresses complex issues in a summary fashion. Consideration should be given to the official version of the

More information

PETROLEUM STORAGE TANK FIRE PROTECTION SECTION INDEX

PETROLEUM STORAGE TANK FIRE PROTECTION SECTION INDEX PETROLEUM SECTION INDEX Foam Application Method: Fixed Surface Systems (Design Reference NFPA 11)... K2 Fixed, Full Surface Foam Application...K3-K4 BFC Series Custom Fitted Foam Chambers...K5-K6 BFC-HC

More information

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression

More information

RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS

RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS The following guidelines are intended to assist with the permit acquisition process with regard to Plumbing Alterations. Not all information, or additional

More information

Lithium Ion Batteries Hazard and Use Assessment

Lithium Ion Batteries Hazard and Use Assessment Lithium Ion Batteries Hazard and Use Assessment Phase IIB Flammability Characterization of Li-ion Batteries for Storage Protection Prepared by: R. Thomas Long Jr. Jason A. Sutula Michael J. Kahn Exponent,

More information

Model KFR56 Series Quick Response Standard Spray

Model KFR56 Series Quick Response Standard Spray Bulletin 036 Model KFR56 Series Quick Response Standard Spray Bulletin 036 Model KFR56 Sprinkler Types Standard Upright Standard Pendent Horizontal Sidewall Model KFR56 Sprinkler Types Pendent F1/F2/FP

More information

Ontario Association of Fire Chiefs Position Paper Residential Fire Sprinklers

Ontario Association of Fire Chiefs Position Paper Residential Fire Sprinklers Ontario Association of Fire Chiefs Position Paper Residential Fire Sprinklers The Ontario Association of Fire Chiefs (OAFC) supports changes to the Ontario Building Code to require that all new residential

More information

Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description

Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description Worldwide Contacts www.tyco-fire.com Series 2.8,.2,.6, 8.0 K-Factor Upright, Pendent, Recessed Pendent Sprinklers Quick Response, Stard Coverage General Description The TYCO Series, 2.8,.2,.6, 8.0 K-factor,

More information

Model WS Specific Application Window Sprinklers Horizontal and Pendent Vertical Sidewall 5.6 K-factor General Description

Model WS Specific Application Window Sprinklers Horizontal and Pendent Vertical Sidewall 5.6 K-factor General Description Worldwide Contacts www.tyco-fire.com Model WS Specific Application Window Sprinklers Horizontal and Pendent Vertical Sidewall 5.6 K-factor General Description The TYCO Model WS Specific Application Window

More information

TYPICAL FIRE SAFETY INSPECTION VIOLATIONS

TYPICAL FIRE SAFETY INSPECTION VIOLATIONS TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved;

More information

Winnipeg Fire Department Fire Prevention Branch

Winnipeg Fire Department Fire Prevention Branch Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of

More information

Installation Instructions

Installation Instructions Installation Instructions Pedestal Models FS 500 LE FS 800 LE Insert Models IS 500 LE IS 800 LE Pecan Engineering Pty Ltd 13 Acorn Road Dry Creek South Australia 5094 Email info@pecan-eng.com.au Phone:

More information

LIFE SAFETY UPDATE. FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc.

LIFE SAFETY UPDATE. FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc. LIFE SAFETY UPDATE FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc. The purpose of this update is as follows: Remind all state

More information

Series TY-FRB 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall Sprinklers Quick and Standard Response (Light Hazard) General Description

Series TY-FRB 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall Sprinklers Quick and Standard Response (Light Hazard) General Description Worldwide Contacts www.tyco-fire.com Series TY-FRB 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall s Quick and Standard Response (Light Hazard) General Description TYCO Series TY-FRB 5.6 and

More information

DuPont FM-200 COMPARISON TESTING IN A SIMULATED DATA PROCESSING/TELECOMMUNICATIONS FACILITY

DuPont FM-200 COMPARISON TESTING IN A SIMULATED DATA PROCESSING/TELECOMMUNICATIONS FACILITY DuPont FM-200 COMPARISON TESTING IN A SIMULATED DATA PROCESSING/TELECOMMUNICATIONS FACILITY DuPont FM-200 and Automatic Sprinkler Systems Mark L. Robin and Eric W. Forssell, DuPont Fluoroproducts Data

More information

Sprinkler Identification Numbers

Sprinkler Identification Numbers Worldwide Contacts www.tyco-fire.com Series TY-FRB 5.6 K-factor Horizontal Quick Response, Standard Coverage General Description described in this data sheet are quick response -standard coverage, decorative

More information

Working Towards Protection Guidance for Warehouse Storage Li-ion Batteries

Working Towards Protection Guidance for Warehouse Storage Li-ion Batteries Working Towards Protection Guidance for Warehouse Storage Li-ion Batteries Benjamin Ditch, FM Global Tom Long, Exponent Inc. SUPDET 2016, March 1 4, San Antonio TX Experimental Knowledge Timeline Reducedcommodity

More information

General Fire Code Requirements Within Commercial Tenant Spaces

General Fire Code Requirements Within Commercial Tenant Spaces FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding

More information

Approval Standard for Plastic Suspended Ceiling Panels

Approval Standard for Plastic Suspended Ceiling Panels Approval Standard for Plastic Suspended Ceiling Panels Class Number 4651 February 1978 2002 FM Approvals LLC. All rights reserved. Foreword The FM Approvals certification mark is intended to verify that

More information

Ethanol Vehicle and Infrastructure Codes and Standards Citations

Ethanol Vehicle and Infrastructure Codes and Standards Citations Ethanol Vehicle and Infrastructure Codes and Standards Citations This document lists codes and standards typically used for U.S. ethanol vehicle and infrastructure projects. To determine which codes and

More information

Flammable Liquids 29 CFR 1910.106

Flammable Liquids 29 CFR 1910.106 Flammable Liquids 29 CFR 1910.106 OSHA s Directorate of Training and Education These materials were developed by OSHA s Directorate of Training and Education and are intended to assist employers, workers,

More information

Safe Operating Procedure

Safe Operating Procedure Safe Operating Procedure (Revised 07/09) HOT WORK PERMIT OPERATIONS (For assistance, please contact EHS at (402) 472-4925, or visit our web site at http://ehs.unl.edu/) Authority In recognition of the

More information

Fire Sprinkler System Maintenance and Testing Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS

Fire Sprinkler System Maintenance and Testing Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Introduction When properly installed and maintained, automatic fire sprinkler systems have proven to be the most effective means for protecting

More information

Viking Residential Sprinkler Installation Guide

Viking Residential Sprinkler Installation Guide Viking Residential Sprinkler Installation Guide January, 2009 Trusted Above AllT M www.flowbusiness.cl Sprinkler RES1 January 9, 2009 1. DESCRIPTION Viking residential automatic sprinklers are equipped

More information

Depending on your facility and the equipment contained within, all or part of the checklists/logs can be printed for use.

Depending on your facility and the equipment contained within, all or part of the checklists/logs can be printed for use. Large Facility Fire Safety Checklists and Logs This package contains checklists to ensure that all fire and life safety equipment are properly inspected. There are also logs on which to record the inspections

More information

Combustible Dust - Things that go Boom. W. Jon Wallace, CSP, MBA Workplace Group, LLC O: 919.933.5548 E: jwallace@workplacegroup.

Combustible Dust - Things that go Boom. W. Jon Wallace, CSP, MBA Workplace Group, LLC O: 919.933.5548 E: jwallace@workplacegroup. Combustible Dust - Things that go Boom W. Jon Wallace, CSP, MBA Workplace Group, LLC O: 919.933.5548 E: jwallace@workplacegroup.net Presentation Objectives After attending this presentation you will: Learn

More information

RESIDENTIAL COURSE OF CONSTRUCTION QUESTIONNAIRE

RESIDENTIAL COURSE OF CONSTRUCTION QUESTIONNAIRE RESIDENTIAL COURSE OF CONSTRUCTION QUESTIONNAIRE Residential Course of Construction policies, also known as Builder s Risk, are designed to cover the property owner for potential loss while the property

More information

19" Data Racks. Adjustable feet To compensate for uneven floors and assure great stability all feet can be up to 20 mm adjusted.

19 Data Racks. Adjustable feet To compensate for uneven floors and assure great stability all feet can be up to 20 mm adjusted. 19" Data Racks Attractive design and high quality are characteristic. Basic framework is welded from multiple bent metal plate, which assures great rigidity suitable for heavier equipment. All profile

More information

Pyroguard Wired Glass

Pyroguard Wired Glass Fire-rated Glass Pyroguard Wired Glass Where glass becomes architecture Section 15 03 Introduction Oldcastle Glass stocks nonwired Pyroguard laminated safety glass and polished wired glass for commercial,

More information

Static Electricity. A Health and Safety Guideline for Your Workplace. What Are Some Sources of Static Electricity? What is Static Electricity?

Static Electricity. A Health and Safety Guideline for Your Workplace. What Are Some Sources of Static Electricity? What is Static Electricity? A Health and Safety Guideline for Your Workplace What is static electricity? What causes it? How is it hazardous? And, most importantly, how can it be controlled? All of these questions will be answered

More information

Model F822 thru F834 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description

Model F822 thru F834 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description Worldwide Contacts www.tyco-fire.com Model F thru F3 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description The Mulsifyre Nozzles are open (nonautomatic) nozzles and they are designed

More information

ModuSec. Secure and efficient IT room solutions Composite Panel Systems Compared. Panel Systems are not all the same!

ModuSec. Secure and efficient IT room solutions Composite Panel Systems Compared. Panel Systems are not all the same! Secure and efficient IT room solutions Composite Panel Systems Compared Panel Systems are not all the same! When it comes to accommodating critical IT systems, the first issue to look at is the environment

More information

Residential Inspection Guidelines

Residential Inspection Guidelines Residential Inspection Guidelines 201 Pre-Pour Foundation Dimensions Building Location Certificate - if required in the building consent Construction and Advice Notes Check the building dimensions against

More information

FLAMMABLE AND COMBUSTIBLE LIQUIDS. n OSHA Changes

FLAMMABLE AND COMBUSTIBLE LIQUIDS. n OSHA Changes FLAMMABLE AND COMBUSTIBLE LIQUIDS OSHA Changes Introduction This module covers the two primary hazards associated with flammable and combustible liquids: explosion and fire. In order to prevent these hazards,

More information

PRE APPLICATION CONFERENCE - INTRODUCTION

PRE APPLICATION CONFERENCE - INTRODUCTION CITY OF AUBURN Planning & Development Department Auburn City Hall Annex, 2 nd Floor 1 East Main Street Auburn, WA 98001 Tel: 253.931.3090 Fax: 253.804.3114 permitcenter@auburnwa.gov www.auburnwa.gov PRE-APPLICATION

More information

FDNY C14 Certificate of Fitness Quiz

FDNY C14 Certificate of Fitness Quiz FDNY C14 Certificate of Fitness Quiz Name: Date: 1. Who issues a New York City laboratory permit? a) Department of Environmental Protection (DEP) b) Department of Environmental Conservation (DEC) c) Occupational

More information

(This report is endorsed) Industrivej 20, 9900 Frederikshavn, Danmark

(This report is endorsed) Industrivej 20, 9900 Frederikshavn, Danmark Spectrum Laboratories Ltd is accredited by International Accreditation New Zealand (formerly Telarc). The tests reported herein have been performed in accordance with the terms of our accreditation. This

More information

December Newsletter by Vincent Dunn Backdraft and flashover, what is the difference?

December Newsletter by Vincent Dunn Backdraft and flashover, what is the difference? Photo By: Steve Spak December Newsletter by Vincent Dunn Backdraft and flashover, what is the difference? What is a backdraft explosion and how does differ from a flashover? Explosions kill and injure

More information