ESFR Sprinkler Systems
|
|
- Beatrice Thornton
- 7 years ago
- Views:
Transcription
1 ESFR Sprinkler Systems Paul Kennedy
2 Evolution of Sprinkler Systems 1870 s Perforated Pipes followed by tar coated perforated pipes 1890 s Temperature Activated Fusible Link Sprinkler with toothed deflector 1920 s Glass Bulb with toothed deflector (Grinnell) 1950 s Development of the Standard [or] Spray Sprinkler 1970 s In-Rack Sprinkler Protection Introduced 1980 s Development of ESFR Sprinkler by FM for Storage Hazards
3 Development ESFR Sprinkler Systems What is required to eliminate In-Rack Sprinkler Protection without increasing the risk to property / life? Residential Sprinkler Research Project Large Drop Sprinkler Research Project Fast Response Sprinkler ESFR Early Suppression Fast Response Larger Drops with Higher Kinetic Energy
4 Fire Control versus Fire Suppression Up to the introduction of ESFR Sprinklers, Sprinkler Systems were designed to Control a Fire by limiting it s size by distribution of water so as to decrease the heat release rate and pre-wet adjacent combustibles, while controlling ceiling gas temperatures to avoid structural damage [NFPA ]. Fire Suppression refers to sharply reducing the heat release rate of a fire and preventing its regrowth by means of direct and sufficient application of water through the fire plume to the burning fuel surface [NFPA ].
5 Comparison of Control & Suppression
6 Design Codes and Standards for ESFR NFPA 13 FM Data Sheet 8-9 LPC Rules Incorporating BS EN [ TB 209 ]
7 New FM Terminology Old Terminology CMDA Control Mode Density Area CMSA Control Mode Specific Application SM Suppression Mode ESFR Early Suppression Fast Response New Terminology Storage Sprinkler Non Storage Sprinkler Special Protection
8 Choosing the Correct Storage Scheme Determine the highest applicable Commodity Hazard [FM Data Sheet 8-1] Class 1 (Metal Products, Glass Products in corrugated cartons) Class 2 (Class 1 products in wooden boxes or small cartons in larger corrugated cartons) Class 3 (Paper Products, Leather Products, Wood Products, Textiles) Class 4 (Class 1, 2 or 3 with 15% by weight of expanded or unexpanded plastic) Cartoned Unexpanded Plastic (High-density Plastic) Cartoned Expanded Plastic (Low-density Plastic) Uncartoned Unexpanded Plastic Uncartoned Expanded Plastic Establish the storage type Solid Piled Palletized Shelving Bin-Box Open Frame Racks Apply the appropriate Protection Table in Data Sheet 8 9
9 Protection Tables Data Sheet Protection Tables available in Data Sheet 8 9 Commodity Commodity Hazard Solid-Piled, Palletized, Shelf, or Bin-Box Storage Arrangement Storage Type Open-Frame Rack Storage Arrangements Class 1, 2 and 3 Table 2 Table 7 Class 4 and Cartoned Unexpanded Plastic Table 3 Table 8 Cartoned Expanded Plastic Table 4 Table 9 Uncartoned Unexpanded Plastic Table 5 Table 10 Uncartoned Expanded Plastic Table 6 Table 11
10 Protection Table Data Sheet 8-9 Green Areas represent those options for which a reduced hose stream allowance of 950 L / min. and a reduced duration of 1 hour is allowed.
11 Comparison Storage to Control Mode Commodity Hazard : Class 3 Storage Type : Open Frame Rack Storage Ceiling Height : 13.5 meters Storage Height : 12.0 meters Commodity Solid-Piled, Palletized, Shelf, or Bin-Box Storage Arrangement Storage Type Open-Frame Rack Storage Arrangements Class 1, 2 and 3 Table 2 Table 7 Class 4 and Cartoned Unexpanded Plastic Table 3 Table 8 Cartoned Expanded Plastic Table 4 Table 9 Uncartoned Unexpanded Plastic Table 5 Table 10 Uncartoned Expanded Plastic Table 6 Table 11
12 Storage Height = 12.0 m Ceiling Height = 13.5 m Comparison Storage to Control Mode Commodity Hazard : Class 3 Storage Type : Open Frame Rack Storage Ceiling Height : 13.5 meters Storage Height : 12.0 meters Description Roof & Rack Ceiling Area (m 2 ) Ceiling Density (L /min. / m 2 ) 12.2 No. In-Rack Sprinklers Operating 10.0 Min. Flow In-Rack (L / min. / Sprinkler) Storage K320 K320 No. Sprinklers 12 Sprinkler Head Pressure (bar) 3.5 Hose Allowance (L / min.) 1, Duration (min.) Water Storage Volume (m 3 )
13 Limitations to Storage Sprinkler The use of solid shelving (i.e., plywood shelves) > 6.0m 2 within storage racks is not allowable, without additional in-rack sprinklers. A minimum of 36 [920mm] must be maintained between the top of storage and the ESFR sprinkler head. Flue spaces between storage pallet loads within storage racks must be maintained. The storage of flammable/combustible liquids is generally not allowed. Certain foam containing products such as unboxed (exposed) furniture within storage racks. Roof vents are generally not allowed unless certain restrictions are met.
14 Impact of Obstructions to Storage ESFR systems are very intolerant of obstructions, which may be caused by steel roof supports (trusses), light fixtures, and ductwork. It is critical that no objects between the top of storage and the ceiling-level sprinklers interfere with the sprinkler s proper discharge pattern. NFPA
15 Inspection, Testing & Maintenance NFPA 25 FM Data Sheet 2-81 LPC Rules Incorporating BS EN [ TB 203 ]
16 THANK YOU
FireLock LP-46 Storage Sprinkler V4601 Pendent FM Approved, culus Listed See Submittal Publication 40.95
.61 FireLock Storage Design Guide This Firelock Storage Design Guide (the "Guide") illustrates the performance characteristics of the full offering of Victaulic Storage s based upon selected design criteria
More informationStored Palletized, Solid Piled, Bin Boxes, or Shelf Storage (12.2)
Stored Palletized, Solid Piled, Bin Boxes, or Shelf Storage (12.2) Formally part of NFPA 231 12.2.1 General 12.2.2 Protection of Class I - IV Commodities 12.2.3 Protection of Plastic & Rubber Commodities
More informationDenver Fire Department Idle Pallet Storage Guidelines Per NFPA 13_Chpt 12
Idle wood and plastic pallets introduce a severe fire condition. Stacking idle pallets in piles is the best arrangement of combustibles to promote rapid spread of fire, heat release, and complete combustion.
More informationNFPA 13 2002 FAQs. 3. Can plastic pipe be used on a sprinkler system complying with NFPA 13?
NFPA 13 2002 FAQs Responses to FAQs are prepared by NFPA technical staff to assist users in reading and understanding NFPA codes and standards. The responses, however, are not Formal Interpretations issued
More informationesfr pendent sprinkler vk510 (k25.2)
January 17, 2014 Sprinkler 124a 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK510 incorporates the capability to suppress specific high-challenge fires. The addition
More informationESFR DRY PENDENT SPRINKLER VK502 (K14.0) TECHNICAL DATA
December 19, 2013 Sprinkler 122j 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Dry Pendent Sprinkler VK502 is a fast response fusible element type sprinkler designed for use in storage areas
More informationTechnical Article. Sprinkler Protection for High Bay and Automated Storage in Warehouse-Type Storage Facilities
Technical Article for High Bay and Automated Storage in Warehouse-Type Storage Facilities Scott Martorano, CFPS Senior Manager Technical Services February, 2010 Worldwide Fire Protection www.vikinggroupinc.com
More informationFlammable and Combustible Liquid
Flammable and Combustible Liquid Storage Challenges Christopher J. Wieczorek, Ph.D., FM Global David Nugent, The Valspar Corporation Global Research Update: High Challenge Storage Protection 27 June 2012,
More informationExtended Coverage Sprinklers
Extended Coverage Sprinklers Welcome ASPE Wally Barker Sprinkler Systems 101 MATERIALS OF CONSTRUCTION The components that make up a sprinkler head are: Frame or casting Deflector Fusible element or frangible
More informationEFSN Training i Module 1. 90 Minutes
Introduction to Sprinklers EFSN Training i Module 1 90 Minutes Topics How sprinklers work Performance of sprinkler systems Types of Sprinkler Introduction to sprinkler systems Introduction ti to sprinkler
More informationWarehouse Checklist. Warehouse Construction
PAGE 1 Warehouse Checklist Recent NFPA statistics estimate that in 1998 approximately 36,000 fires occurred in structures used for storage, accounting for $687mm of damage (over 10% of total fire damage
More informationConstruction Warehouse. Culminating Experience in Fire Protection Engineering FPE 596 Prepared by Ben Johnson
Construction Warehouse Culminating Experience in Fire Protection Engineering FPE 596 Prepared by Ben Johnson Construction Warehouse Waste Treatment and Immobilization Plant (WTP) Project U.S. Department
More informationRisk Guidance Note 03. Management of In-Rack Automatic Sprinklers (IRAS)
Risk Guidance Note 03 Management of In-Rack Automatic Sprinklers (IRAS) Overview In-rack automatic sprinklers (IRAS) are often a fundamental part of the fire protection solution for racked storage areas.
More informationHIGH-PILED COMBUSTIBLE STORAGE
CHAPTER 23 HIGH-PILED COMBUSTIBLE STORAGE SECTION 2301 GENERAL 2301.1 Scope. High-piled combustible storage shall be in accordance with this chapter. In addition to the requirements of this chapter, the
More informationHIGH-PILED COMBUSTIBLE STORAGE
CHAPTER 23 HIGH-PILED COMBUSTIBLE STORAGE SECTION FC 2301 GENERAL 2301.1 Scope. This chapter shall govern high-piled combustible storage, and the design, installation, operation and maintenance of any
More informationFLAMMABLE AND COMBUSTIBLE LIQUIDS
GAP.8.1.0 A Publication of Global Asset Protection Services LLC FLAMMABLE AND COMBUSTIBLE LIQUIDS INTRODUCTION National Fire Protection Association (NFPA) documents describe a level of fire protection
More informationName Of Occupancy Date. Yes No Describe
FIRE PREVENTION INSPECTION CHECKLIST For Class A Occupancy (For Assembly Buildings, Bars, Restaurants, Gyms, Churches, Arenas, Theatres or wherever people gather) Name Of Occupancy Date Physical Address
More informationHigh Pressure Water Mist Systems: Alternative Solution For Critical Civil Applications
International Water Mist Conference, London, United Kingdom,23-24 September, 2009 High Pressure Water Mist Systems: Alternative Solution For Critical Civil Applications Fire Fighting In Civil Applications
More informationHealthandSafetyOntario.ca. Introduction. Storage Containers. Storing Flammable Liquids
Flammable Liquids Storage Introduction This guideline is designed to help you store flammable liquids safely. It is based on the requirements of the Ontario Fire Code, Part 4, and of the Regulations for
More informationInsight. Storage Fires. Balanced Risk Engineering Solutions. Understanding the Risk. Commodity Classification. Storage Configuration
Balanced Risk Engineering Solutions Storage Fires Understanding the Risk Many of the most costly fires occur in warehouses and storage areas, where often a high fire risk is combined with high values and/or
More informationWatermist fire suppression systems for commercial low hazard occupancies
Watermist fire suppression systems for commercial low hazard occupancies Watermist fire protection systems are fire suppression systems that have emerged as an alternative fire safety solution for specific
More informationFIRE SPRINKLER SYSTEM DESIGN, ENGINEERING EXEMPTION POLICY FOR (Effective April 1, 2006)
State of Tennessee Department of Commerce and Insurance Board of Architectural and Engineering Examiners 500 James Robertson Parkway Nashville, TN 37243 1142 800 256 5758 615 741 3221 (Nashville Area)
More informationFire Protection Requirements of Empty Intermediate Bulk Containers (IBCs)
Research TECHNICAL REPORT Fire Protection Requirements of Empty Intermediate Bulk Containers (s) Fire Protection Requirements of Empty Intermediate Bulk Containers (s) by Seth E. Sienkiewicz FM Global
More informationAON SPRINKLER CERTIFICATION
Form 1 Application for Approval of Basic Design Parameters for Automatic Sprinkler System Installations 1. Name of Protected Premises Site Name Address 2. Work to be Carried Out New System Extension or
More informationSPRINKLER RULES & STANDARDS IN EUROPE CEA 4001 & EN 12845
SPRINKLER RULES & STANDARDS IN EUROPE CEA 4001 & EN 12845 DAEGU: 20 th August 2010 Karim KARZAZI 1 Development of sprinkler rules & standards in Europe. Overview of past, existing and future situation
More informationFighting Fire in Sprinklered Buildings. Student Guide
Fighting Fire in Sprinklered Buildings Student Guide Fighting Fire in Sprinklered Buildings Student Guide Table of Contents Purpose........................................................... 3 Instruction
More informationFlammable Liquids Storage
A Health and Safety Guideline for Your Workplace Flammable Liquids Storage Introduction This guideline is designed to help you store flammable liquids safely. It is based on the requirements of the Ontario
More informationI.CHEM.E. SYMPOSIUM SERIES NO. 97
FIRE HAZARDS OF FLAMMABLE LIQUIDS IN SMALL CONTAINERS J. F. Siddle* Standards of fire protection for metal drums and smaller metal containers of flammable liquids have been well defined and have proved
More informationFull scale tunnel fire tests of VID Fire-Kill Low Pressure Water Mist Tunnel Fire Protection System in Runehamar test tunnel, spring 2009
Full scale tunnel fire tests of VID Fire-Kill Low Pressure Water Mist Tunnel Fire Protection System in Runehamar test tunnel, spring 2009 By Carsten Palle, VID Fire-Fill, www.vid.eu Presented at ISTSS
More informationIn accordance with NFPA 30, these containers are not to store Class I flammable liquids.
In accordance with NFPA 30, these containers are not to store Class I flammable liquids. Zurich recommends storing these containers in dedicated liquid storage rooms, detached buildings, or in listed dispensing
More informationFlammable Liquids Storage
A Health and Safety Guideline for Your Workplace Flammable Liquids Storage Introduction This guideline is designed to help you store flammable liquids safely. It is based on the requirements of the Ontario
More informationHATFIELD TOWNSHIP. FLAMMABLE and COMBUSTIBLE LIQUIDS PERMIT APPLICATION PROCEDURES
HATFIELD TOWNSHIP FLAMMABLE and COMBUSTIBLE LIQUIDS PERMIT APPLICATION PROCEDURES A flammable and combustible liquids permit is required to store, transport on site, dispense, use or handle flammable and
More informationWAREHOUSE PROPERTY PROTECTION
STRATEGIC OUTCOMES PRACTICE TECHNICAL ADVISORY BULLETIN October 2011 WAREHOUSE PROPERTY PROTECTION Among the most challenging occupancies from a property loss control viewpoint are warehouses, distribution
More informationCasey C. Grant, P.E., FSFPE Research Director Fire Protection Research Foundation
RESEARCH FOUNDATION ACTIVITIES AND OUTCOMES IN DETECTION AND SUPPRESSION SYSTEMS Casey C. Grant, P.E., FSFPE Research Director Fire Protection Research Foundation Madrid, del 23 al 25 de febrero de 2010
More informationType EA-1 PROTECTOSPRAY Directional Spray Nozzles, Automatic, Medium Velocity General Description
Worldwide Contacts www.tyco-fire.com Type EA-1 PROTECTOSPRAY Directional Spray Nozzles, Automatic, Medium Velocity General Description The TYCO Type EA-1 PROTECTO- SPRAY Directional Spray Nozzles are automatic
More information1.0 Purpose... 4. 2.0 Definitions...4. 3.0 Hot Work Operations. 5
HOT WORK PROGRAM Introduction The University of Kentucky recognizes a potential for fire from hot work operations. For that reason this program should be implemented in all departments at the University
More informationAutomatic Fire Sprinkler Submittal Requirements
Automatic Fire Sprinkler Submittal Requirements All commercial and industrial buildings with a total floor area of 5000 sq. ft. shall have an approved automatic sprinkler system installed. The Windsor-Severance
More informationARE YOU IN COMPLIANCE WITH THE OSHA COMBUSTIBLE DUST DIRECTIVE? Revised March 18, 2009
Kidde Fenwal, Inc. Industrial Explosion Protection Group A UTC Fire & Security Company 400 Main Street Ashland, MA 01721 Tel 508-881-2000 Fax 508-485-3115 www.fenwalprotection.com FENWAL Protection Systems
More informationSeries ELO-231B 11.2 K-factor Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Series ELO-231B 11.2 K-factor Upright and Pendent Sprinklers Standard Response, Standard Coverage General Description IMPORTANT Always refer
More information2007 Edition HAZARD CLASSIFICATION FOR NFPA 13 SPRINKLER DESIGN NFPA 13 HAZARD CLASSIFICATION. Why does it matter? Chapter 11-21
HAZARD CLASSIFICATION FOR NFPA 13 SPRINKLER DESIGN Division of Fire Safety Why does it matter? Chapter 11-21 Sprinkler Demand Hose Demand Duration MFA Course #644 - May 2010 Current NFPA 13? Why does it
More informationWillis Technical Advisory Bulletin
Willis Technical Advisory Bulletin Warehouse Property Protection February 2007 Among the most challenging occupancies from a property loss control viewpoint are warehouses, distribution centers and large
More informationModel SW-20 and SW-24 11.2 K-factor Extended Coverage Ordinary Hazard Horizontal Sidewall Sprinklers (Standard Response) General Description
Worldwide Contacts www.tyco-fire.com Model SW-20 and SW-24 11.2 K-factor Extended Ordinary Hazard Horizontal Sidewall s (Standard ) General Description 11.2 K-factor, Extended Ordinary s, Standard are
More informationINTERACTION OF SPRINKLERS WITH SMOKE AND HEAT VENTS
INTERACTION OF SPRINKLERS WITH SMOKE AND HEAT VENTS Craig L. Beyler and Leonard Y. Cooper Fire Science and Engineering Baltimore, Maryland EXECUTIVE SUMMARY There has been an ongoing controversy about
More informationA Code Review for Emergency Generators and Indoor Use of Portable Generators
A Code Review for Emergency Generators and Indoor Use of Portable Generators By: the Fire and Life-Safety Group (FLS) Fire Code requires that emergency generators be stationary generators. Therefore, a
More informationEffectiveness of sprinklers in residential premises: Section 4: Benchmark tests. Project report number 204505. Dr Corinne Williams and R Harrison
Effectiveness of sprinklers in residential premises: Section 4: Benchmark tests Project report number 2455 Dr Corinne Williams and R Harrison February 24 Section 4: Benchmark tests Contents 4 Benchmark
More informationQuick response concealed horizontal sidewall sprinkler
January 1, 2011 Sprinkler 63a 1. DESCRIPTION Viking Quick Response Concealed Horizontal Sidewall Sprinkler VK408 is a small solder link and lever spray sprinkler designed for installation on concealed
More informationTECHNICAL DATA 2. LISTINGS AND APPROVALS. Spray Nozzle 11. December 20, 2013
Spray Nozzle 11 1. DESCRIPTION Viking Model C-1 Window Sprinklers are non-automatic, open, outside intended for protection of windows, walls, and roofs against exposure fires. The directional discharge
More informationCONSULTING from DESIGN to PROJECT MANAGEMENT We Transform your Vision into Productive Force
2012 CONSULTING from DESIGN to PROJECT MANAGEMENT We Transform your Vision into Productive Force Consulting : from Design to Project IBLS can provide complete solutions in the Design, Procurement and Project
More informationF.Y.I. Specifying Fire Protection Systems Using Division 13
F.Y.I. Specifying Fire Protection Systems Using Division 13 Automatic fire sprinkler systems and fire alarm and detection systems are increasingly installed in modern buildings. Even where building codes
More informationcity of edmonds development information
#B17 city of edmonds development information Commercial Kitchen Hood & Hood Fire Suppression System Permit Submittal Requirements PERMIT REQUIRED: CODES: FEES: A Commercial Kitchen Hood Mechanical Permit
More informationHATFIELD TOWNSHIP DRY CLEANING PLANT PERMIT APPLICATION PROCEDURES
HATFIELD TOWNSHIP DRY CLEANING PLANT PERMIT APPLICATION PROCEDURES A Dry Cleaning Plant Operational Permit is required to engage in the business of dry cleaning or to change to a more hazardous cleaning
More informationFire Extinguishers Water Extinguishers
Water Extinguishers Water extinguishers are suitable for Class A fires caused by combustion of solid materials such as wood, paper, straw, textiles and coal etc. Water additive extinguishers use an environmentally
More informationOntario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal
Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable
More informationSprinkler Identification Number. Page 1 of 6 MARCH 2014 TFP288. Worldwide Contacts. www.tyco-fire.com
Worldwide Contacts www.tyco-fire.com Model EC-HS 80 K-factor, Quick Response Extended Coverage Horizontal Sidewall Sprinklers Installations per VdS CEA 400, Annex E, LH/OH General Description The Model
More informationClark County Fire Prevention
Clark County Fire Prevention Mission Statement: To provide the highest level of fire protection and related services TITLE: REQUIREMENTS FOR A NEW SPRINKLER SYSTEM IN ACCORDANCE WITH THE 2002 EDITION OF
More informationBuilding Code Clarifications - 7. Fire Resistance
Building Code Clarifications - 7. Fire Resistance 7.1 (15-12-030) Use of combustibles in Type III construction roof assemblies Code Section (15-12-030) Use of Combustibles was revised on May 17, 2000,
More informationFixed or Semi-Fixed Fire Protection Systems for Storage Tanks
Fixed or Semi-Fixed Fire Protection Systems for Storage Tanks In the early years of the oil industry, fire in a storage tank was a common occurrence. Virtually all products were stored in cone roof tanks
More informationCOMPARISON TESTING IN A SIMULATED DATA PROCESSING/ TELECOMMUNICATIONS FACILITY: FM-200 AND AUTOMATIC SPRINKLER SYSTEMS
COMPARISON TESTING IN A SIMULATED DATA PROCESSING/ TELECOMMUNICATIONS FACILITY: FM-200 AND AUTOMATIC SPRINKLER SYSTEMS Mark L. Robin and Eric W. Forssell Hughes Associates, Inc. 5415 Hillside Lane West
More informationALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.252 WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600
OSHA REGULATION: 9 CFR 90.5 WELDING, CUTTING, AND BRAZING ( HOT WORK ) A. POLICY. This procedure follows requirements set forth in 9 CFR 90.5.. This policy applies to all Hot Work operations being done
More informationLogisticsCentre IV Distribution Center
KCI Intermodal BusinessCentre LogisticsCentre IV LogisticsCentre IV Distribution Center Modern Warehouse/Distribution Space Ranging From 108,000± SF to 432,000± SF 10221 NW Transcon Drive 112th Street
More informationNew Ontario Building Code Requirements for Mid-rise Wood Frame Buildings
New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings Note: This information addresses complex issues in a summary fashion. Consideration should be given to the official version of the
More informationPETROLEUM STORAGE TANK FIRE PROTECTION SECTION INDEX
PETROLEUM SECTION INDEX Foam Application Method: Fixed Surface Systems (Design Reference NFPA 11)... K2 Fixed, Full Surface Foam Application...K3-K4 BFC Series Custom Fitted Foam Chambers...K5-K6 BFC-HC
More informationCOMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
More informationRESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS
RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS The following guidelines are intended to assist with the permit acquisition process with regard to Plumbing Alterations. Not all information, or additional
More informationLithium Ion Batteries Hazard and Use Assessment
Lithium Ion Batteries Hazard and Use Assessment Phase IIB Flammability Characterization of Li-ion Batteries for Storage Protection Prepared by: R. Thomas Long Jr. Jason A. Sutula Michael J. Kahn Exponent,
More informationModel KFR56 Series Quick Response Standard Spray
Bulletin 036 Model KFR56 Series Quick Response Standard Spray Bulletin 036 Model KFR56 Sprinkler Types Standard Upright Standard Pendent Horizontal Sidewall Model KFR56 Sprinkler Types Pendent F1/F2/FP
More informationOntario Association of Fire Chiefs Position Paper Residential Fire Sprinklers
Ontario Association of Fire Chiefs Position Paper Residential Fire Sprinklers The Ontario Association of Fire Chiefs (OAFC) supports changes to the Ontario Building Code to require that all new residential
More informationSeries TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description
Worldwide Contacts www.tyco-fire.com Series 2.8,.2,.6, 8.0 K-Factor Upright, Pendent, Recessed Pendent Sprinklers Quick Response, Stard Coverage General Description The TYCO Series, 2.8,.2,.6, 8.0 K-factor,
More informationModel WS Specific Application Window Sprinklers Horizontal and Pendent Vertical Sidewall 5.6 K-factor General Description
Worldwide Contacts www.tyco-fire.com Model WS Specific Application Window Sprinklers Horizontal and Pendent Vertical Sidewall 5.6 K-factor General Description The TYCO Model WS Specific Application Window
More informationTYPICAL FIRE SAFETY INSPECTION VIOLATIONS
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved;
More informationWinnipeg Fire Department Fire Prevention Branch
Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of
More informationInstallation Instructions
Installation Instructions Pedestal Models FS 500 LE FS 800 LE Insert Models IS 500 LE IS 800 LE Pecan Engineering Pty Ltd 13 Acorn Road Dry Creek South Australia 5094 Email info@pecan-eng.com.au Phone:
More informationLIFE SAFETY UPDATE. FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc.
LIFE SAFETY UPDATE FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc. The purpose of this update is as follows: Remind all state
More informationSeries TY-FRB 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall Sprinklers Quick and Standard Response (Light Hazard) General Description
Worldwide Contacts www.tyco-fire.com Series TY-FRB 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall s Quick and Standard Response (Light Hazard) General Description TYCO Series TY-FRB 5.6 and
More informationDuPont FM-200 COMPARISON TESTING IN A SIMULATED DATA PROCESSING/TELECOMMUNICATIONS FACILITY
DuPont FM-200 COMPARISON TESTING IN A SIMULATED DATA PROCESSING/TELECOMMUNICATIONS FACILITY DuPont FM-200 and Automatic Sprinkler Systems Mark L. Robin and Eric W. Forssell, DuPont Fluoroproducts Data
More informationSprinkler Identification Numbers
Worldwide Contacts www.tyco-fire.com Series TY-FRB 5.6 K-factor Horizontal Quick Response, Standard Coverage General Description described in this data sheet are quick response -standard coverage, decorative
More informationWorking Towards Protection Guidance for Warehouse Storage Li-ion Batteries
Working Towards Protection Guidance for Warehouse Storage Li-ion Batteries Benjamin Ditch, FM Global Tom Long, Exponent Inc. SUPDET 2016, March 1 4, San Antonio TX Experimental Knowledge Timeline Reducedcommodity
More informationGeneral Fire Code Requirements Within Commercial Tenant Spaces
FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding
More informationApproval Standard for Plastic Suspended Ceiling Panels
Approval Standard for Plastic Suspended Ceiling Panels Class Number 4651 February 1978 2002 FM Approvals LLC. All rights reserved. Foreword The FM Approvals certification mark is intended to verify that
More informationEthanol Vehicle and Infrastructure Codes and Standards Citations
Ethanol Vehicle and Infrastructure Codes and Standards Citations This document lists codes and standards typically used for U.S. ethanol vehicle and infrastructure projects. To determine which codes and
More informationFlammable Liquids 29 CFR 1910.106
Flammable Liquids 29 CFR 1910.106 OSHA s Directorate of Training and Education These materials were developed by OSHA s Directorate of Training and Education and are intended to assist employers, workers,
More informationSafe Operating Procedure
Safe Operating Procedure (Revised 07/09) HOT WORK PERMIT OPERATIONS (For assistance, please contact EHS at (402) 472-4925, or visit our web site at http://ehs.unl.edu/) Authority In recognition of the
More informationFire Sprinkler System Maintenance and Testing Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS
Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Introduction When properly installed and maintained, automatic fire sprinkler systems have proven to be the most effective means for protecting
More informationViking Residential Sprinkler Installation Guide
Viking Residential Sprinkler Installation Guide January, 2009 Trusted Above AllT M www.flowbusiness.cl Sprinkler RES1 January 9, 2009 1. DESCRIPTION Viking residential automatic sprinklers are equipped
More informationDepending on your facility and the equipment contained within, all or part of the checklists/logs can be printed for use.
Large Facility Fire Safety Checklists and Logs This package contains checklists to ensure that all fire and life safety equipment are properly inspected. There are also logs on which to record the inspections
More informationCombustible Dust - Things that go Boom. W. Jon Wallace, CSP, MBA Workplace Group, LLC O: 919.933.5548 E: jwallace@workplacegroup.
Combustible Dust - Things that go Boom W. Jon Wallace, CSP, MBA Workplace Group, LLC O: 919.933.5548 E: jwallace@workplacegroup.net Presentation Objectives After attending this presentation you will: Learn
More informationRESIDENTIAL COURSE OF CONSTRUCTION QUESTIONNAIRE
RESIDENTIAL COURSE OF CONSTRUCTION QUESTIONNAIRE Residential Course of Construction policies, also known as Builder s Risk, are designed to cover the property owner for potential loss while the property
More information19" Data Racks. Adjustable feet To compensate for uneven floors and assure great stability all feet can be up to 20 mm adjusted.
19" Data Racks Attractive design and high quality are characteristic. Basic framework is welded from multiple bent metal plate, which assures great rigidity suitable for heavier equipment. All profile
More informationPyroguard Wired Glass
Fire-rated Glass Pyroguard Wired Glass Where glass becomes architecture Section 15 03 Introduction Oldcastle Glass stocks nonwired Pyroguard laminated safety glass and polished wired glass for commercial,
More informationStatic Electricity. A Health and Safety Guideline for Your Workplace. What Are Some Sources of Static Electricity? What is Static Electricity?
A Health and Safety Guideline for Your Workplace What is static electricity? What causes it? How is it hazardous? And, most importantly, how can it be controlled? All of these questions will be answered
More informationModel F822 thru F834 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description
Worldwide Contacts www.tyco-fire.com Model F thru F3 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description The Mulsifyre Nozzles are open (nonautomatic) nozzles and they are designed
More informationModuSec. Secure and efficient IT room solutions Composite Panel Systems Compared. Panel Systems are not all the same!
Secure and efficient IT room solutions Composite Panel Systems Compared Panel Systems are not all the same! When it comes to accommodating critical IT systems, the first issue to look at is the environment
More informationResidential Inspection Guidelines
Residential Inspection Guidelines 201 Pre-Pour Foundation Dimensions Building Location Certificate - if required in the building consent Construction and Advice Notes Check the building dimensions against
More informationFLAMMABLE AND COMBUSTIBLE LIQUIDS. n OSHA Changes
FLAMMABLE AND COMBUSTIBLE LIQUIDS OSHA Changes Introduction This module covers the two primary hazards associated with flammable and combustible liquids: explosion and fire. In order to prevent these hazards,
More informationPRE APPLICATION CONFERENCE - INTRODUCTION
CITY OF AUBURN Planning & Development Department Auburn City Hall Annex, 2 nd Floor 1 East Main Street Auburn, WA 98001 Tel: 253.931.3090 Fax: 253.804.3114 permitcenter@auburnwa.gov www.auburnwa.gov PRE-APPLICATION
More informationFDNY C14 Certificate of Fitness Quiz
FDNY C14 Certificate of Fitness Quiz Name: Date: 1. Who issues a New York City laboratory permit? a) Department of Environmental Protection (DEP) b) Department of Environmental Conservation (DEC) c) Occupational
More information(This report is endorsed) Industrivej 20, 9900 Frederikshavn, Danmark
Spectrum Laboratories Ltd is accredited by International Accreditation New Zealand (formerly Telarc). The tests reported herein have been performed in accordance with the terms of our accreditation. This
More informationDecember Newsletter by Vincent Dunn Backdraft and flashover, what is the difference?
Photo By: Steve Spak December Newsletter by Vincent Dunn Backdraft and flashover, what is the difference? What is a backdraft explosion and how does differ from a flashover? Explosions kill and injure
More information