Type ICX Outdoor open type cutout

Size: px
Start display at page:

Download "Type ICX Outdoor open type cutout"

Transcription

1 Distribution cutouts Type IC Outdoor open type cutout Product features 7.8 kv, 15 kv, 15/27 kv, 27 kv, or 38 kv on 100 A 7.8 kv, 15 kv, and 15/27 kv only on 200 A 110, 125, 150, 170, or 180 kv BIL 180 kv BIL available as V only 100 A, 200 A continuous current fused and up to 16 ka interrupting current on 15 kv, 100 A only 300 A disconnect blade Porcelain, polymer concrete, or insulators available Seacoast design Cutout/arrester combo Kick-out spring available for the 100 A and 200 A tubes. Description The IC cutout is used on overhead distribution systems to provide overcurrent protection and visible indication of fuse operation. The IC provides a visible break sectionalizing point for maintenance personnel and is equipped with hooks for use with a portable loadbreak tool. This allows the IC to be used as a loadbreak switch to open the circuit with load current flowing. Porcelain, polymer concrete, or insulators, seacoast design, cutout/arrester combination, options are available on certain models. Ratings The IC is offered in several frame sizes to properly match each system BIL. Each fuse support has universal contacts that accommodate a 100 A fuseholder, a 200 A fuseholder, or a 300 A disconnect blade. Design features The IC 100 A fuse is provided with a moisture-proof tube as a standard offering. Cutouts perform by expelling gases during interruption from the bottom of the fuse tube. For the highest interrupting rating, a link extender rod is attached to the fuse tube cap, improving the efficiency of gas expulsion and arc interruption. Fuse tubes are clearly labeled to indicate interrupting capability. Interchangeability The IC cutout is designed to be electrically and mechanically interchangeable with the S&C type S, A.B. Chance type C, and Cooper type L cutouts. Testing has confirmed the performance of the IC fuseholder and fuse support with S&C and Chance. Standards and design testing The IC cutout meets or exceeds all applicable requirements of IEEE C37.41 and C37.42 standards. Warranty A ten-year warranty is offered on and polymer concrete IC cutouts and a five-year warranty is offered on IC cutouts, provided ABB parts are used exclusively.

2 Options and construction details Silicone rubber Silicone rubber has been used for more than thirty years as an outdoor insulation material and is the fastest growing choice for polymeric material for medium and high voltage outdoor insulation. Silicone is used for its superior performance, durability, and insulation properties. It has the unique ability to maintain its hydrophobicity and offers greater stability against heat and ultraviolet radiation compared to other polymers. In addition, cutouts are 30% - 50% lighter than units. Silicone insulators are available in all ratings up to 180 kv BIL. Polymer concrete ABB has been using polymer concrete for more than twenty years. Available in 110 and 125 kv BIL ratings, polymer concrete provides a safe, shatter-proof design with molded-in rods to prevent moisture penetration. Because it resists damage from freeze/thaw cycles, the material is an excellent alternative to in colder climates. Polymer concrete is a fieldproven material that provides excellent electrical properties and dielectric strengths, as well as superior mechanical durability. Kick-out spring All IC 100 A and 200 A fuse tubes are available with an optional kick-out spring. The spring assists the drop-out operation by increasing the kick-out force on the tube. Arrester combinations ABB offers a combination IC cutout with an arrester option This combination unit is pre-assembled at the factory and provides overall savings by reducing installation time and accumulated costs that result from independently purchased parts. Fuse tube construction The IC cutouts utilize two different types of fuse tubes: a moisture-proof fuse tube or a horn fiber fuse tube. The moisture proof fuse tube is standard on all 100 A designs and is notated by the letter M in the 8th digit of the style number (refer to Ordering Instructions on pages 4-5). The moisture-proof tube reduces swelling of the liner that can create problems with interruption. The 200 A design utilizes a horn fiber fuse tube and is notated by the letter A in the 8th digit of the style number (refer to Ordering Instructions on pages 4-5). This fuse tube is composed of a horn fiber liner surrounded by a glass filament wound outer shell. Both designs have a durable tube that withstands the rigors of high fault current interruptions. In addition, the tube is applied with paint to provide protection against the effects of ultraviolet rays. Voltage levels Single voltage rated cutouts can be applied on any single or three-phase system where the line-to-line voltage does not exceed the cutout rating. Dual voltage rated cutouts are suitable on single-phase circuits where maximum line-to-ground voltage does not exceed the value shown to the left of the slash (for example, does not exceed 15 kv in 15/27 kv). IC cutouts may be used on three-phase circuits that are solidly grounded and where the maximum line-to-line voltage does not exceed the value shown to the right of the slash (for example, does not exceed 27 kv in 15/27 kv). IC combination units are available with various mounting brackets to fulfill industry requirements. The combo units are equipped with normal duty, heavy duty, or riser pole polymer metal oxide arresters. 2 Type IC outdoor cutout Product bulletin

3 Dimensions A B 2.25 [57].312 NEMA "A" BRKT.375 NEMA "B" BRKT [76-102] A C [ ] 7.75 [197] B C 2.38 [60] [ ] 7.75 [197] 1.56 [40] F R [68-102] 1.50 [38] F R DEG D D 1.00 [25] E E Note: Metric dimensions are displayed in [mm]. kv Class BIL (kv) Unit dimensions (in) Creep (in) Weight (lb) A B C D E F R Porcelain Silicone Polymer concrete Porcelain Silicone Polymer concrete 7.8 or /27 or or or or kv Class BIL (kv) Unit dimensions (mm) Creep (mm) Weight (kg) A B C D E F R Porcelain Silicone Polymer concrete Porcelain Silicone 7.8 or /27 or or or or Polymer concrete dimensions.312 [8].375 [10].38 [10] 7.8 [198] 7.8 [198] 7.8 [198] 1.6 [40] 1.6 [40] 1.5 [38] 2.6 [67] NEMA A bracket 2.6 [67] NEMA B bracket 5.4 [137] Extended bracket Product bulletin Type IC outdoor cutout 3

4 Ordering instructions IC cutout arrester combination Voltage level 1 = 15 kv 2 = 27 kv 3 = 38 kv (use 150 kv BIL insulator) Cutout cap S = 100A Solid cap L = 100A Link extender T = 200A Solid cap M = 200A Link extender Arrester type C = Polymer normal duty H = Polymer heavy duty R = Polymer riser pole Digit 9 Cutout terminals 1 = Clamshell 2 = Eyebolt Cutout insulator material (Blank) = Porcelain Z = Polymer concrete (only available for 110 and 125 kv BIL cutouts) C 1 = 110 kv BIL 2 = 125 kv BIL 5 = 150 kv BIL U = Standard combo Contact factory for other options Digits 7-8 Arrester voltage 03 = 3 kv 06 = 6 kv 09 = 9 kv 10 = 10 kv 12 = 12 kv 15 = 15 kv 18 = 18 kv 21 = 21 kv 24 = 24 kv 27 = 27 kv Digit 10 1 = None 8 = 12" lead B = Arrester bird guard S = Seacoast cutout = No arrester but in combo box IC Cutouts 15 kv, 110 kv BIL 1 = 110 kv BIL C = Seacoast 1 Z = Polymer concrete A = NEMA A AM11 = 100A, 10 ka asym, solid cap LM11 = 100A, 16 ka asym, link extender KA21 = 200A, 10 ka asym, link extender PA21 = 200A, 12 ka asym, link extender (7.8 kv) CA31 = 300A, solid blade 27 kv, 125 kv BIL 2 = 125 kv BIL C = Seacoast on fuse tube 2 Z = Polymer concrete (125 kv BIL) Digit 7-10 AM12 = 100A, 8 ka asym, solid cap MM12 = 100A, 12 ka asym, link extender BA22 = 200A, 10 ka asym, solid cap (15 kv) DA32 = 300A, solid blade WA22 = 200A, 10 ka asym, link extender (15/27 kv) VA22 = 200A, 12 ka asym, link extender 4 Type IC outdoor cutout Product bulletin

5 27 kv, 150 kv BIL 4 = 150 kv BIL 600 mm creep ( only) 5 = 150 kv BIL C = Seacoast AM12 = 100A, 8 ka asym, solid cap MM12 = 100A, 12 ka asym, link extender BA22 = 200A, 10 ka asym, solid cap DA32 = 300A, Solid blade VA22 = 200A, 12 ka asym, link extender 38 kv, 150 kv BIL 4 = 150 kv BIL 600 mm creep ( only) 5 = 150 kv BIL C = Seacoast (100 A only) TM12 = 100A, 10 ka asym, link extender 15 kv, 27 kv, 38 kv, 150 kv BIL 6 = 150 kv BIL (20" creep) 6 AM12 = 100A, 8 ka asym, solid cap (27 kv) MM12 = 100A, 12 ka asym, link extender (27 kv) BA22 = 200A, 10 ka asym, solid cap (15 kv) DA32 = 300A, Solid blade (27 kv) VA22 = 200A, 12 ka asym, link extender (27 kv) TM12 = 100A, 10 ka asym, link extender (38 kv) Product bulletin Type IC outdoor cutout 5

6 27 kv, 180 kv BIL, V insulator C = Seacoast 8 = 180 kv BIL 8 J MM12 = 100A, 12 ka asym, link extender DA32 = 300A, Solid blade 15 kv, 170 kv BIL 7 = 170 kv BIL 7 N A26 = 200A, 8 ka sym, link extender YM16 = 100A, 8 ka sym, link extender SA24 = 200A, 10 ka asym, link extender (15/27 kv) 27 kv, 170 kv BIL 7 = 170 kv BIL 7 N RM14 = 100A, 12 ka asym, link extender FA34 = 300A, disconnect 38 kv, 170 kv BIL 7 = 170 kv BIL 7 N RM15 = 100A, 10 ka asym, link extender FA35 = 300A, disconnect ZM15 = 100A, 8 ka sym, link extender 6 Type IC outdoor cutout Product bulletin

7 Optional parts and accessories Replacement fuseholders Style number Voltage rating (kv) BIL (kv) Current rating (A) Interrupting rating (kaic) Cap type Corresponding cutout* 7194C60G01MP Solid AM C60G02MP Link extender LM C60G Link extender PA C60G Link extender KA C60G Solid disconnect blade CA C60G05MP or Solid AM C60G06MP , 150, or Link extender MM C60G or Solid BA C60G or Solid disconnect blade DA C60G Solid disconnect blade DA C60G11MP Link extender RM C60G Solid disconnect blade FA C60G or Link extender VA C60G Link extender RM15 * Used with IC cutouts having the following characters in digit positions 7-10 of the ABB cutout style number. Replacement fuseholder caps Style number Voltage rating (kv) BIL (kv) Current rating (A) Interrupting rating (kaic) 3A31186A Solid Cap type 9861A62A Link extender 9861A62A Link extender 3A31187A01 15/ or Solid 3A31186A or Solid 9861A62A , 150, or Link extender 9861A62A Link extender 9861A62A Link extender s Style number 366C723A05 403A101A03 367C802A04 Type NEMA A NEMA B Extended Product bulletin Type IC outdoor cutout 7

8 For more information please contact: ABB Inc. Medium Voltage Apparatus 3022 NC 43 North Pinetops, NC USA Phone: Fax: VAG DB August 2016 Rev. O Note: The information contained in this document is for general information purposes only. While ABB strives to keep the information up to date and correct, it makes no representations or warranties of any kind, express or implied, about the completeness, accuracy, reliability, suitability or availability with respect to the information, products, services, or related graphics contained in the document for any purpose. Any reliance placed on such information is therefore strictly at your own risk. ABB reserves the right to discontinue any product or service at any time. Copyright 2006 ABB. All rights reserved.

AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle

AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle Scope This specification stipulates the minimum requirements for mechanically linked three-phase electronic sectionalizers, for use on outdoor medium voltage overhead lines of 15, 27, and 38 kv. Electronic

More information

S&C TripSaver Dropout Recloser. For enhanced lateral circuit protection at 15 kv and 25 kv

S&C TripSaver Dropout Recloser. For enhanced lateral circuit protection at 15 kv and 25 kv S&C TripSaver Dropout Recloser For enhanced lateral circuit protection at 15 kv and 25 kv Introducing S&C s new TripSaver Dropout Recloser: A better solution for overhead lateral circuit protection at

More information

Vertical Break Parallel (VBP) / Vertical Break Slant (VBS)

Vertical Break Parallel (VBP) / Vertical Break Slant (VBS) August, 2009 Vertical Break Parallel (VBP) / Vertical Break Slant (VBS) Type VBPA (Aluminum) / Type VBPC (Copper) Type VBSA (Aluminum) / Type VBSC (Copper) PASCOR Air Break Switch Technology PASCOR offers

More information

Bypass switches. Type B-1 and type B-2. Answers for energy.

Bypass switches. Type B-1 and type B-2. Answers for energy. Bypass switches Type B-1 and type B-2 Answers for energy. Eliminate voltage regulator bypass switch problems with type B-1 and type B-2 Overview Type B-1 The Bridges Electric type B-1 regulator bypass

More information

OVR Three-Phase Recloser and PCD Control Style Guide 1VAL264001-SG October 13, 2009 Revision F

OVR Three-Phase Recloser and PCD Control Style Guide 1VAL264001-SG October 13, 2009 Revision F OVR Three-Phase Recloser and PCD Control Style Guide 1VAL264001-SG October 13, 2009 Revision F The OVR three-phase recloser style guide aids in the proper selection of your OVR three-phase style number.

More information

HVL 5 38 kv Load Interrupter Switchgear. The Standard for Performance, Protection and Dependability

HVL 5 38 kv Load Interrupter Switchgear. The Standard for Performance, Protection and Dependability HVL 5 38 kv Load Interrupter Switchgear The Standard for Performance, Protection and Dependability For a generation of engineers, Square D High Voltage Load (HVL ) Interrupter Switchgear by Schneider Electric

More information

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms ABB innovations for changing demands ABB (www.abb.com) is a leader in power and automation technologies that enables utility

More information

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information

OVR-3SP Recloser with PCD Control Style Guide 1VAL263901-SG March 30, 2009 Revision B

OVR-3SP Recloser with PCD Control Style Guide 1VAL263901-SG March 30, 2009 Revision B OVR-3SP Recloser with PCD Control Style Guide 1VAL263901-SG March 30, 2009 Revision B The OVR-3SP three-phase recloser style guide aids in the proper selection of your OVR-3SP style number. The OVR-3SP

More information

Specifications. S&C Power Fuses Types SM and SMLa. For use with SM Refill Units or SMU Fuse Units. Indoor Distribution (4.16 kv through 34.

Specifications. S&C Power Fuses Types SM and SMLa. For use with SM Refill Units or SMU Fuse Units. Indoor Distribution (4.16 kv through 34. S&C Power Fuses s SM and SMLa Indoor Distribution (4.16 through 34. ) For use with SM Refill Units or SMU Fuse Units Specifications Conditions of Sale STANDARD: Seller s standard conditions of sale set

More information

Contents. Description. Product Selection Guide

Contents. Description. Product Selection Guide .1 Medium Voltage Switchgear Introduction Indoor Type VCP-W Metal-Clad Switchgear Assembly (5/15 kv shown) Product Selection Guide Product Offering Chart Metal-Enclosed Contents Description Notes Additional

More information

261000 Medium Voltage Electrical Distribution

261000 Medium Voltage Electrical Distribution Sections Included In This Standard: 1.1 General 1.2 Underground Cable 1.3 Medium Voltage Switches 1.4 Transformers 1.5 Electrical Manholes 1.6 Switch Vaults 1.7 Distribution Switchgear/Switchboards This

More information

Section 21. Telecommunication Hardware. www.geindustrial.com BuyLog Catalog 21-1

Section 21. Telecommunication Hardware. www.geindustrial.com BuyLog Catalog 21-1 Introduction...21-1 Fiber Closure Hardware...21-2 Cable Location Surge Protectors...21-4 Introduction GE has been manufacturing Telecommunication Hardware products for over 20 years and has become a leader

More information

Metallic and Non-Metallic Air Conditioning Disconnects. A Complete Family of. Disconnects with Exclusive Time Saving Features

Metallic and Non-Metallic Air Conditioning Disconnects. A Complete Family of. Disconnects with Exclusive Time Saving Features Metallic and Non-Metallic Air Conditioning Disconnects A Complete Family of Disconnects with Exclusive Time Saving Features Enclosed Molded Case Disconnect Switch Not-Fusible The preferred molded case

More information

Dimensions, Inches (mm) No. of Poles Width Height Depth 2, 3 8.25 (210) 16 (407) 5.5 (140) 4 11.125 (283) 16 (407) 5.5 (140)

Dimensions, Inches (mm) No. of Poles Width Height Depth 2, 3 8.25 (210) 16 (407) 5.5 (140) 4 11.125 (283) 16 (407) 5.5 (140) 9-10N Supersedes Selection Data 9-10N, pages, 1-, dated dated March March 1995 1995 Mailed to: E, D, C/9-100A, 31-A, INTERRUPTING CAPACITY RATINGS IEC 947- Interrupting Capacity s➀ Interrupting Capacity

More information

Power Capacitor Units for improved power quality

Power Capacitor Units for improved power quality Power Capacitor Units for improved power quality Applications for capacitors Reactive power compensation Most of the apparatus and loads connected to the electrical power system consume both active and

More information

Power products medium voltage Sales & marketing contacts

Power products medium voltage Sales & marketing contacts Power products medium voltage Sales & marketing contacts Medium voltage apparatus Sales and marketing contacts instrument transformers, sensors, cutouts, disconnect switches, and capacitor fuses (Pinetops,

More information

Electrical Grounding. Appendix C

Electrical Grounding. Appendix C Appendix C Electrical Grounding Low-Voltage Equipment Grounding The most frequently cited Office of Safety and Health Administration (OSHA) electrical violation is improper occupational grounding of equipment

More information

New Distribution Class Arrester Ground Lead Disconnector Design Enhances Detonation Reliability and Improves Arrester Performance

New Distribution Class Arrester Ground Lead Disconnector Design Enhances Detonation Reliability and Improves Arrester Performance New Distribution Class Arrester Ground Lead Disconnector Design Enhances Detonation Reliability and Improves Arrester Performance Dennis W. Lenk, Fellow, IEEE Abstract-- This paper examines performance

More information

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies DATE: November 17, 1999 REVISION: AUTHOR: John Merrell Introduction In some short circuit studies, the X/R ratio is ignored when comparing

More information

Type K current limiting fuse canister Technical information and installation guide

Type K current limiting fuse canister Technical information and installation guide Transformer components Type K current limiting fuse canister Technical information and installation guide The Type K current limiting fuse canister provides an air-insulated receptacle for general-purpose

More information

Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation

Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation Index News Introduction Applications & Segments Main Components Applicable Standards Technical characteristics

More information

High-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv

High-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv High-Voltage Compact Switchgear AP1 DTC for 1 kv and kv Answers for energy. The AP1 DTC Complying with our Customers demands Experience you can rely on - at anytime, anywhere Decades of experience in high-voltage

More information

Corner-Grounded Delta (Grounded B Phase) Systems

Corner-Grounded Delta (Grounded B Phase) Systems Data Bulletin 2700DB0202R03/12 09/2012 Replaces 2700DB0202R2/09 dated 02/2009 Corner-Grounded Delta (Grounded B Phase) Systems Class 2700 Retain for future use. Introduction Corner-grounded delta systems

More information

Siemens Fusesaver. Highest availability and cost savings for your MV distribution network. www.siemens.com/fusesaver

Siemens Fusesaver. Highest availability and cost savings for your MV distribution network. www.siemens.com/fusesaver www.siemens.com/fusesaver Siemens Fusesaver Highest availability and cost savings for your MV distribution network Answers for infrastructure and cities. 2 In high demand: An intelligent solution Improving

More information

How To Choose A Transformer

How To Choose A Transformer Consider open loop MV network as an example source 1 source 2 NC NC NC or NO main MV switchboard A B Detail design of substation NC NC NC NO NC NC switchboard 1 switchboard 2 switchboard 3 MV MV MV LV

More information

Fuse Selection Method Module 2. Date of the presentation

Fuse Selection Method Module 2. Date of the presentation Fuse Selection Method Module 2 Date of the presentation Fuse Selection When selecting LV fuses certain important information must be known. 1.System Voltage This is the voltage of the system or distribution

More information

When power interruptions happen.

When power interruptions happen. When power interruptions happen. We know it s never a good time to have your power go out, so we work all year pruning trees and investing in our system to cut down on problems before they start. Outage

More information

PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors

PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors PRODUCT GUIDE SL Medium Voltage IEC Vacuum Contactors Table of Contents 1 Overview Introduction....................................................2 Features........................................................2

More information

Trade of Electrician. Three-phase Distribution Boards And Socket Circuits

Trade of Electrician. Three-phase Distribution Boards And Socket Circuits Trade of Electrician Standards Based Apprenticeship Three-phase Distribution Boards And Socket Circuits Phase 2 Module No. 2.3 Unit No. 2.3.2 COURSE NOTES Created by Charlie Walsh - Athlone TC Revision

More information

Circuit Breakers. NRC Series. NRC Series. 900 www.idec.com

Circuit Breakers. NRC Series. NRC Series. 900 www.idec.com Switches & Pilot Lights Display Lights NRC series circuit breakers offer circuit protection which is far superior to using fuses in applications containing relay circuits, motor circuits, heater circuits,

More information

SUPPLEMENT TO SPECIFICATIONS FOR ELECTRICAL INSTALLATIONS

SUPPLEMENT TO SPECIFICATIONS FOR ELECTRICAL INSTALLATIONS SUPPLEMENT TO SPECIFICATIONS FOR ELECTRICAL INSTALLATIONS PRIMARY METER POLE ELECTRIC SYSTEM BULLETIN No. 753 JUNE 1993, 2 ND PRINTING APRIL 2002 (Supersedes issue dated March 1983 and incorporates Nov.

More information

INFRARED RADIANT HEATERS. air heaters

INFRARED RADIANT HEATERS. air heaters INFRARED RADIANT HEATERS OVERVIEW Economic, efficient, and clean, WATTCO infrared radiant heaters are designed for comfort heating applications that require radiant heat in indoor, outdoor, and exposed

More information

Tmax MCCBs. Molded case circuit breakers. Tmax

Tmax MCCBs. Molded case circuit breakers. Tmax Molded case circuit breakers Introduction ABB is once again demonstrating its commitment to new product development and its superiority in product performance. Never before has the industry seen such high

More information

Medium voltage indoor circuit breakers ANSI/IEC solutions

Medium voltage indoor circuit breakers ANSI/IEC solutions Medium voltage indoor circuit breakers ANSI/ solutions Table of contents Introduction... 3 Vmax/A... 4 ADVAC... 6 AMVAC... 8 Vmax... 10 VD4... 12 VM1... 16 HD4... 19 V-Contact VSC... 22 2 Medium voltage

More information

OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd

OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd ACTOM OUTDOOR DISCONNECTORS Single Side Break (SSB) Disconnector 22-132 kv, 800-1 A, 25 ka - 3s Typical bearing assembly. Voltage range 11 kv to 132

More information

Secondary Unit Substations

Secondary Unit Substations 14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically

More information

MiCAFIL. 1 RIP Technology. Bushings. Z. Zic 09/2003

MiCAFIL. 1 RIP Technology. Bushings. Z. Zic 09/2003 MiCAFIL 1 RIP Technology Z. Zic 09/2003 )XQFWLRQRI+LJK9ROWDJH%XVKLQJ Uncontrolled (natural) electrical field Capacity-controlled electrical field %XVKLQJV0DLQ,QVXODWLRQ6\VWHPV 7\SH 0DLQ,QVXODWLRQ +RXVLQJFRYHU

More information

Voltage Regulator SPAU 341 C. Product Guide

Voltage Regulator SPAU 341 C. Product Guide Issued: July 1998 Status: Updated Version: D/25.04.2006 Data subject to change without notice Features Comprehensive voltage regulation for power transformers with on-load tapchangers in distribution substations

More information

ABB Fuses Competitive Advantages

ABB Fuses Competitive Advantages GPMM Tomasz Komalski 2009 ABB Fuses Competitive Advantages May 14, 2009 Slide 1 Basic comments ABB is a global manufacturer of both current limiting and expulsion (non-current limiting) fuses for medium

More information

Medium voltage arc flash eliminator units VAM 3ED,

Medium voltage arc flash eliminator units VAM 3ED, Medium voltage arc flash eliminator units VAM 3ED,, Medium voltage arc flash eliminator units Medium voltage arc flash eliminator units The new innovative arc eliminator VAM 3ED is an extremely fast acting

More information

Applications. Remote Display Mounting Kits

Applications. Remote Display Mounting Kits June 200 Sheet 105 Surge Protection Products TVSS General Description Clipper Power System Visor Series.1-5 Clipper Power System Visor Series General Description Eaton s Cutler-Hammer leading-edge surge

More information

How To Build A Germany Power Plant

How To Build A Germany Power Plant Medium Voltage Air Insulated Motor Control Featuring AdvanceTM Technology. Medium Voltage Motor Control Center Product Description Contemporary Design Advance TM medium voltage motor control center (MVMCC)

More information

Insulation Resistance Testing of Low Voltage Cables in the Field

Insulation Resistance Testing of Low Voltage Cables in the Field Insulation Resistance Testing of Low Voltage Cables in the Field Table of Contents 1. Background...3 1.1. Before Making Measurements...3 1.2. How to Apply the Temperature Correction Factor...4 1.2.1. Calculation...4

More information

Reduction of Lightning Caused Interruptions on Electric Power Systems Reduction Des Compures Dues a la Faudre Dans Les Reseaux

Reduction of Lightning Caused Interruptions on Electric Power Systems Reduction Des Compures Dues a la Faudre Dans Les Reseaux Reduction of Lightning Caused Interruptions on Electric Power Systems Reduction Des Compures Dues a la Faudre Dans Les Reseaux Harold S. Brewer Product Manger Ohio Brass Resume L avenement d équipements

More information

Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution

Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution Medium Voltage Products ZN1 12 kv arc-proof air-insulated switchgear for primary distribution ZN1 an innovative switchgear for power distribution requirements ABB ZN1 primary distribution switchgear is

More information

UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution

UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution UniGear ZS1 Medium voltage, arc proof, air insulated switchgear for primary distribution UniGear ZS1: an innovative solution for all installation requirements ABB UniGear is medium voltage metal-clad,

More information

Grounding of Electrical Systems NEW CODE: Grounding and Bonding

Grounding of Electrical Systems NEW CODE: Grounding and Bonding Grounding of Electrical Systems NEW CODE: Grounding and Bonding Presented By Scott Peele PE Grounding of Electrical Systems Outline Defining the Terms Why should I Ground? Types of Grounding Systems Separately

More information

Transformers Energy efficient transformer solutions European Minimum Energy Performance Standard (MEPS)

Transformers Energy efficient transformer solutions European Minimum Energy Performance Standard (MEPS) Transformers Energy efficient transformer solutions European Minimum Energy Performance Standard (MEPS) 2 European MEPS for transformers The EU MEPS (European Minimum Energy Performance Standard) Transformers

More information

Current Limiting Protector For Systems rated 2.8-38kV and continuous currents through 5000A.

Current Limiting Protector For Systems rated 2.8-38kV and continuous currents through 5000A. Current Limiting Protector For Systems rated 2.8-38kV and continuous currents through 5000A. Arc Flash and Arc Blast reduction Network protection SCADA adaptable Indoor/outdoor application Professional

More information

SnoTrace KSR Surface Snow and Ice Melting INSTALLATION PROCEDURES

SnoTrace KSR Surface Snow and Ice Melting INSTALLATION PROCEDURES SnoTrace Surface Snow and Ice Melting INSTALLATION PROCEDURES SnoTrace INSTALLATION PROCEDURES Refer to the SnoTrace Cable Testing Report for required recording of test data and circuit information. Upon

More information

Primary and Secondary Electrical Distribution Systems

Primary and Secondary Electrical Distribution Systems Primary and Secondary Electrical Distribution Systems Critical Facilities Round Table 12th Quarterly Membership Meeting June 2, 2006 David D. Roybal. P.E. Eaton Electrical Cutler-Hammer Products Utility

More information

Masterclad Medium Voltage Passive Arc-Resistant Switchgear

Masterclad Medium Voltage Passive Arc-Resistant Switchgear Masterclad Medium Voltage Passive Arc-Resistant Switchgear Square D Masterclad medium voltage passive arc-resistant (AR) switchgear is designed with utilities and industrial customers in mind who demand

More information

Medium Voltage Terminations, 5 kv 46 kv

Medium Voltage Terminations, 5 kv 46 kv Medium Voltage Terminations, 5 kv 46 kv Over 30 years ago, 3M pioneered cold shrink technology. Since then, field use and laboratory analysis have repeatedly proven its merits and reliability. Through

More information

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp Page 1 2015 Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other Component 15 kv or 25 kv Separable Insulated Connector (elbow) Equipment Connection Power Cable Power Cable Grounded Metal

More information

Type SA-1 Generator Differential Relay

Type SA-1 Generator Differential Relay ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065 Instruction Leaflet 41-348.11C Effective: November 1999 Supersedes I.L. 41-348.11B, Dated August 1986 ( ) Denotes

More information

BRITISH STYLE SEMICONDUCTOR PROTECTION FUSES

BRITISH STYLE SEMICONDUCTOR PROTECTION FUSES The Edison British Style semiconductor protection fuses include a 660VAC line utilizing new filler technology. These new fuses have greatly reduced peak let-through current and energy under fault conditions

More information

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller Overview/Modes of Operation Bulletin 150 Smart Motor Controller The SMC-3 is a compact, simple to use, solid-state motor controller designed to operate 3-phase motors. It features a built-in overload relay

More information

SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less.

SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less. PART 1 - GENERAL SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less. RELATED SECTIONS Division 16 Section "Basic Electrical Materials and Methods" for general

More information

REFRIGERATION. Standard Features & Accessories. Model Options. Built-In 30 W. Full-Height Wine Cellar. All models include. VCWB300 Professional

REFRIGERATION. Standard Features & Accessories. Model Options. Built-In 30 W. Full-Height Wine Cellar. All models include. VCWB300 Professional Standard Features & Accessories All models include Capacity accommodates up to 150 full-size bottles o 84 H./24 D. Exclusive TriTemp storage system o Three independent temperature zones o Settings are

More information

Vario-Series Accessories

Vario-Series Accessories Accessories and spare parts for GMW analogue panel meters and controllers Current Transformers pages 2-9 Shunt Resistors 10-11 Voltage Dividers 12 Power supply for indicator/controllers 13 Blanking Plates

More information

Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services.

Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services. Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services. Spending too much time and money on equipment maintenance? Square D Services: Your source for circuit breaker

More information

Fuseology. Medium Voltage Fuses. Continuous Current-Carrying Capacity. General. Interrupting Rating. Additional Rules.

Fuseology. Medium Voltage Fuses. Continuous Current-Carrying Capacity. General. Interrupting Rating. Additional Rules. Fuseology Medium Voltage Fuses General Fuses above are classified under one of three classifications as defined in ANSI/IEEE C37.40. 1. General Purpose Current-Limiting Fuse: A fuse capable of interrupting

More information

LOADING DOCK EQUIPMENT. A. Section 03100 - Concrete Forms and Accessories: Placement of anchors into concrete.

LOADING DOCK EQUIPMENT. A. Section 03100 - Concrete Forms and Accessories: Placement of anchors into concrete. LOADING DOCK EQUIPMENT PART 1 GENERAL 1.1 SECTION INCLUDES A. Loading dock equipment of the following types: 1. Dock lifts. 2. Control stations. 1.2 RELATED SECTIONS A. Section 03100 - Concrete Forms and

More information

Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection

Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection Technical Data Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection Topic Page 1489-M Miniature Circuit Breakers 2 1492-SP Supplementary Protectors 15 1492-D Circuit Breakers 27 188 Regional

More information

Distribution Voltage Regulators

Distribution Voltage Regulators Distribution Voltage Regulators Type JFR Single Phase 2.5 to 19.9 kv Type SFR Three Phase 13.2 to 34.5 kv Power Transmission & Distribution Siemens JFR & SFR Voltage Regulators Improving Quality of Service

More information

LED High Bay Light 100W

LED High Bay Light 100W LED High Bay Light 100W CRI: Life Hours: LED Count: Net Weight: 100W 7,527lm (5,500K-6,000K) 70 20.25in(D) Reflector 140 Up to 50,000 hrs 1 High Power 10x10 LED Array Hanging Loop -40-113 -277VAC 1.00

More information

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH Cat transfer switches are designed for a variety of standby power applications. They provide flexibility, reliability and value in a

More information

Safe and secure distribution of medium voltage with AX1

Safe and secure distribution of medium voltage with AX1 Safe and secure distribution of medium voltage with AX1 The intelligent switchgear AX1 is a modern, air-insulated switchgear that lies at the very front line of safety and security safety for operating

More information

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS MIOSHA-STD-1313 (10/15) 6 Pages For further information Ph: 517-284-7740 www.michigan.gov/mioshastandards DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS

More information

5SV Residual Current Protective Devices

5SV Residual Current Protective Devices s Siemens AG 2013 SENTRON 5SV Residual Current Protective Devices New portfolio for reliable personnel, material and fire protection Safe protection against residual currents Residual current protective

More information

OLI. Oil level indicator

OLI. Oil level indicator OLI Oil level indicator Oil level indicator Unexpected or accidental oil leakages may occur randomly along transformer s lifetime. Clear indication of oil level inside transformer tank and on load tap

More information

Veri*Lite Deadend & Suspension Insulators for 15-69kV Applications

Veri*Lite Deadend & Suspension Insulators for 15-69kV Applications Veri*Lite Deadend & Suspension Insulators for -69kV Applications Section 22-1 22 Warranty - Material Hubbell Power Systems, Inc. warrants all products sold by it to be merchantable (as such term is defined

More information

KOLMA and IHDA Indoor type Cable Current Transformers Catalogue ABB Power Distribution ABB Transmit 1 KKOLMA 1 GB

KOLMA and IHDA Indoor type Cable Current Transformers Catalogue ABB Power Distribution ABB Transmit 1 KKOLMA 1 GB KOLMA and IHDA Indoor type Cable Current Transformers Catalogue ABB Power Distribution ABB Transmit 1 KKOLMA 1 GB KOLMA and IHDA Indoor Type Cable Current Transformers Index Description... 3 Technical

More information

2. INDUCTIVE VOLTAGE TRANSFORMERS Oil-paper insulation Gas insulation

2. INDUCTIVE VOLTAGE TRANSFORMERS Oil-paper insulation Gas insulation 2. INDUCTIVE VOLTAGE TRANSFORMERS Oil-paper insulation Gas insulation 123 kv Inductive Fingrid (Finland). 18 Instrument transformers igh voltage INTRODUCTION Inductive voltage transformers are designed

More information

Outdoor circuit breaker GVR Recloser Hawker Siddeley Switchgear. rated voltage 15, 27 and 38 kv rated current 630 A

Outdoor circuit breaker GVR Recloser Hawker Siddeley Switchgear. rated voltage 15, 27 and 38 kv rated current 630 A Outdoor circuit breaker GVR Recloser Hawker Siddeley Switchgear rated voltage 15, 27 and 38 kv rated current 630 A Outdoor circuit breakers GVR Recloser GVR switchgear brings the reliability of modern

More information

Overhead Distribution Transformers 5-833 kva Single Phase 30-500 kva Three Phase

Overhead Distribution Transformers 5-833 kva Single Phase 30-500 kva Three Phase X62292-Brochure 8/20/03 1:15 PM Page 1 Overhead Distribution Transformers 5-833 kva Single Phase 30-500 kva Three Phase Represented by and Nameplated for ABB Inc. X62292-Brochure 8/20/03 1:15 PM Page 2

More information

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU George CURCANU, Constantin ILINCA, Ilie SBORA ICMET Craiova, Romania, Calea Bucuresti 144, phone:

More information

26 3213.13 Diesel Engine Driven Generators Page 1 of 6

26 3213.13 Diesel Engine Driven Generators Page 1 of 6 Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at

More information

Lightning Arresters P30027 18 KVA P30038 10 KVA. Description & Installation

Lightning Arresters P30027 18 KVA P30038 10 KVA. Description & Installation Lightning Arresters P30027 18 KVA P30038 10 KVA Description & Installation Printed in USA 09/11 TO330 Rev. B Table of Contents Page 1.0 SCOPE 2 2.0 PRODUCT OVERVIEW 2 2.1 Intended Uses 2 2.2 Lightning

More information

Low Voltage Fuses For Motor Protection

Low Voltage Fuses For Motor Protection Code Requirements The NEC or CEC requires that motor branch circuits be protected against overloads and short circuits. Overload protection may be provided by fuses, overload relays or motor thermal protectors.

More information

CPS 100 480Y S K CPS 100 480Y S C

CPS 100 480Y S K CPS 100 480Y S C Ref. No. 1299 Visor Series Ordering Guidelines Table.1-4. Retrofit Surge Protection Products TVSS General Description Clipper Power System Visor Series CPS 100 480Y S K.1-9 Surge Ratings 100 = /phase 120

More information

CEF 9 CEF-S 23 CEF-VT 27 CMF 31 WBP 39 WBT 47 BPS 61

CEF 9 CEF-S 23 CEF-VT 27 CMF 31 WBP 39 WBT 47 BPS 61 FUSES Catalogue CEF 9 CEF-S 23 CEF-VT 27 CMF 31 WBP 39 WBT 47 BPS 61 INTRODUCTION The main function of current limiting fuses is to protect electrical apparatus, such as distribution transformers, motors

More information

No Heat. No Flames. No Shoving. No Special Tools. 3M Cold Shrink. 3M Cold Shrink. Medium Voltage Joints & Terminations. 3M Cold Shrink Joint

No Heat. No Flames. No Shoving. No Special Tools. 3M Cold Shrink. 3M Cold Shrink. Medium Voltage Joints & Terminations. 3M Cold Shrink Joint M Cold Shrink Medium Voltage Joints & Terminations M Cold Shrink Joint Splice bodies 00% factory tested - ensures reliability Capacitive Stress Relief No Heat No Flames No Special Tools No Shoving Unique

More information

SECTION 16346A METAL-CLAD MEDIUM VOLTAGE ARC RESISTANT SWITCHGEAR

SECTION 16346A METAL-CLAD MEDIUM VOLTAGE ARC RESISTANT SWITCHGEAR METAL-CLAD MEDIUM VOLTAGE ARC RESISTANT SWITCHGEAR PART 1 GENERAL 1.01 SCOPE A. The Contractor shall furnish and install the equipment as specified herein and as shown on the contract drawings. 1.02 RELATED

More information

SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL

SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated

More information

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Course No: E02-010 Credit: 2 PDH Boris Shvartsberg, Ph.D., P.E., P.M.P. Continuing Education

More information

Cable Accessories. for Extruded Dielectric Cable 69kV - 230kV Rated. Catalog Python13

Cable Accessories. for Extruded Dielectric Cable 69kV - 230kV Rated. Catalog Python13 Cable Accessories for Extruded Dielectric Cable 69kV - 230kV Rated Components used in cable systems 100% Tested Factory Molded For outdoor applications through 230kV For gas insulated substations and transformers

More information

Electronic overload relay EF19 and EF45

Electronic overload relay EF19 and EF45 Data sheet Electronic overload relay EF19 and EF45 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays. Motor

More information

AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals

AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals Technical Datasheet 1SBC101403D0201 24/03/11 AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals AF09(Z) contactors are used for controlling power circuits

More information

ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories

ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories 2CDC 251 014 F0t09 Features Monitoring of three-phase mains for grid feeding Type-tested in accordance with DIN V VDE V 0126-1-1: February 2006 Neutral conductor connection configurable Can also be used

More information

NFPA 70E Updates Affect Your Most Valuable Assets

NFPA 70E Updates Affect Your Most Valuable Assets NFPA 70E Updates Affect Your Most Valuable Assets EXECUTIVE SUMMARY Electrocution is a well-known hazard associated with direct contact with electrical energy. According to the U.S. Department of Labor,

More information

Industrial Ringdown/Autodialer Telephone SCR Series

Industrial Ringdown/Autodialer Telephone SCR Series Industrial Communications Worldwide Industrial Ringdown/Autodialer Telephone Installation & Operation SCR 11 SCR 41 P005603 Rev. A 060612 5/28/2007 3:58 PM 7552-10th Street N.E. Calgary, Alberta, Canada

More information

EASIDEW PORTABLE HYGROMETER INSTALLATION, OPERATION AND MAINTENANCE MANUAL

EASIDEW PORTABLE HYGROMETER INSTALLATION, OPERATION AND MAINTENANCE MANUAL EASIDEW PORTABLE HYGROMETER INSTALLATION, OPERATION AND MAINTENANCE MANUAL Issue February 2004 2 TABLE OF CONTENTS SECTION PAGE 1. INTRODUCTION 3 1.1 General 3 1.2 Ceramic Sensing Element 3 1.3 Calibration

More information

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4 CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,

More information

The Intelligent AX1 Switchgear for Medium Voltage

The Intelligent AX1 Switchgear for Medium Voltage The Intelligent AX1 Switchgear for Medium Voltage Leif Lundin, Manager of Research and Development, Division Medium Voltage and Compact Substations, ABB Distribution, Sweden Abstract The newly launched

More information

MCR1900 Media Converter 19-Slot Chassis

MCR1900 Media Converter 19-Slot Chassis MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the

More information

SECTION F HALOGEN LAMPHOLDERS HALOGEN LAMPHOLDERS. 1850 Wilson Avenue, Toronto, Ontario, Canada, M9M 1A1 Ph: 416-741-7336 Fax: 416-741-9104

SECTION F HALOGEN LAMPHOLDERS HALOGEN LAMPHOLDERS. 1850 Wilson Avenue, Toronto, Ontario, Canada, M9M 1A1 Ph: 416-741-7336 Fax: 416-741-9104 1850 Wilson Avenue, Toronto, Ontario, Canada, M9M 1A1 Ph: 416-741-7336 Fax: 416-741-9104 SECTION F HALOGEN LAMPHOLDERS F1 HALOGEN LAMPHOLDERS Halogen Sockets Halogen Lamps F2 Bi-Pin Halogen G4/GZ4 Base

More information

Enhanced Quality with a Touch of Style

Enhanced Quality with a Touch of Style Rudolf Current Transformer Enhanced Quality with a Touch of Style Current Transformer Enhanced Quality with a Touch of Style New Products Rudolf launched our new encapsulated current transformer. Portraying

More information

Transformer Bushings for GIS

Transformer Bushings for GIS Transformer Bushings for GIS Oil to SF6 Connections GARIP RTKG 725-55 kv SQS certified ISO 91 / ISO 141 Bushings RIP - Technology for SF6 / Oil - Bushings In modern metal enclosed switchgear SF6 -gas is

More information