Low voltage switchboards Quality inspection guide
|
|
|
- Dennis Tyler
- 9 years ago
- Views:
Transcription
1 Low voltage switchboards Quality guide 2010
2 Preface Foreword On the strength of its experience, Schneider Electric has always sought to produce hight-quality equipment, fully complying with IEC and IEC standards. But what exactly do we mean by Quality? The ISO 9000 standard defines quality as: the degree to which a set of inherent characteristics fulfils requirements. Although final is in some respects a recognition of failure (as we have not been able to control the necessary quality throughout the assembly process), it is nevertheless a vital stage in equipment production. This stage must be performed with care and rigour, in compliance both with customer specifications (explicit needs) and with proper operating procedures (implicit needs), in order to satisfy the customer. Quality is also the determination of all the staff, from the manager to the line worker, to satisfy the customer. This guide is a good means to help you in this and to achieve excellence. Thank you for your contribution.
3 Quality guide Means and processes 1. Introduction to quality 4 2. Incoming delivery Final Summary of tasks after final stage 16 Detailed instructions 6. Performing in-process Performing final 28 Follow-up 8. Quality status chart 38 Facilities and calibration 9. Facilities Control of facilities 43 Appendix 11. Model form Glossary 59 1
4
5 Means and process 1. Introduction to quality 1.1. Justification for quality Quality function Quality responsibility Quality inspector s profile Necessary documents Required human resources Inspection diagram 6 2. Incoming delivery 2.1. Justification for the incoming Procedures Inspection during manufacturing Justification for the during the manufacturing stage Process Means Final 4.1. Final process Operating rules Non-conformity treatment process Conformity declaration Summary of tasks after final stage 5.1. Customer acceptance before installation Installation Commissioning 16 3
6 Means and process 1. Introduction to quality 1.1. Justification for quality Implementation of the quality process in the production plant will entail organising the work station so as to achieve the quality target as imposed by the standard. A quality process has always been recommended to all our partners and subsidiaries. A part of quality assurance, it is a normative obligation of the IEC and IEC standards which stipulate that three routine tests should be performed under the scope of the quality procedures to complete the type tests: giving the equipment the TTA label (Type Tested Assembly) and which are the panel builder s responsibility. These three routine tests are of the assembly dielectric tests and/or measurement of insulation resistance checking of protective measures and of the electrical of the protective circuit. Human factors The specificity and complexity of low voltage equipment, the numerous human operations, and thus risk of errors, are the principal source of mistakes in our field, and hence the main reasons for implementation of the quality process. Each job must be checked. Cost reduction Manufacturing non-quality entails extra costs in term of time and money due to: product examination, repair, scrapping, impacts on delivery schedule, brand image, etc. A study shows that a fault detected on a customer site can cost one hundred to one thousand times more than if it had been detected during the switchboard design phase (see graph below). The in-process checking operation and final also ensure good economic management of the switchboard manufacturing process. 4
7 Means and process 1. Introduction to quality The Quality therefore contributes to guaranteed quality of the equipment: by preserving the company s brand image by guiding staff training according to the anomalies observed. to the safety of personnel and equipment to the company's profitability Quality function Guarantee the quality of service and protect the brand image. Detect and settle internal dysfunctions and thereby increase plant profitability. Perform with respect to: the project file and the customer's documents Schneider and product rules IEC standards Carry out acceptance tests in the customer's presence Perform quality follow-up and corrective actions Ensure information, preventive action and training for production staff Ensure regular calibration of and production facilities Quality responsibility Quality department s directly to management and is independent from manufacturing can postpone the delivery of a project and require reworking to ensure conformity in the event of a dispute, informs the unit manager who alone has the power to decide is responsible for the safety of all people entering the quality zone Quality inspector s profile Graduate as electrical technician (technician s certificate) Versatile Good knowledge of Schneider equipment and devices Authorised to work near electric currents: knowledge of the risk of electric current authorisation by approved training course basic notions of first-aid Necessary documents To carry out the various checks, the quality inspector must possess a complete, updated production file of the project, including the check list, missing parts list, etc Required For an accurate and reliable quality process, quality inspectors represent approximately 10 % of workforce, i.e. 1 quality inspector for 8 to 10 fitters. 5
8 Means and process 1. Introduction to quality 1.7. Inspection diagram Design Procurement Manufacturing stage Design office Receptionist Operator Commercial contract Design Procurement order Basic check list for incoming Framework Assembly plan specifications Busbar Assembly plan Dimensional specifications Device & drawer Assembly plan specifications Enclosure Assembly plan specifications Reference document Document to be fulfilled in Example of " delivered with assembly drawing control specification : Framework Inspection To do Dimensions of cubicle Mechanical assembly Framework combination Check the cubicle dimensions according to those required in the project production file Check the overall assembly, the orientation and position of uprights relative to the horizontal busbar, the junction between uprights (no gap at the junction point of 2 uprights) the presence and tightening of all screws the presence of screws on back upright for drawer fixed part. Check presence of accessories for combination Handling system Verify presence of accessories for handling the cubicle Ground fixing & civil engineering Verify presence and conformity of ground fixing according to the "affaire" (job) file Bottom plate form 2 Verify presence of isulating plate on the bottom plate form 2 Cleanness Check the cleanness of the assembly: no scratch, no grease 6
9 Means and process 1. Introduction to quality Final Quality inspector Customer acceptance Customer Installation Contractor Commissioning Customer Quality guide Installation guide Design Installation Customer acceptance Quality plan Quality control plan Example of " " Checking programme: Framework Index: Product type: Drawing No.: Cubicle No.: Project No.: Customer: Date: Checking programme Quality Conformity Repair Checked by Checked by Conforming Remarks Observations OK Not OK Dimensions of cubicle Mechanical assembly Cleanness Checking during process: fill in the grey box Final and testing: fill in the white box 7
10 Means and process 2. Incoming delivery Design Design office Procurement Receptionist Manufacturing stage Operator Final Quality inspector Customer acceptance Customer Installation Installator Commissioning Customer Commercial contract Design Procurement order Basic check list for incomming Dimensional Framework Assembly plan specifications Busbar Assembly plan specifications Device & drawer Assembly plan specifications Enclosure Assembly plan specifications Quality guide Design Quality plan Installation guide Installation Customer acceptance Quality control plan Applicable to external and internal products and assemblies. In the case of sub-assemblies and internally manufactured products, an internal procedure could be used to perform a final of one process, combined with incoming of another Justification for incoming As a final stage before the assembly process, this quality is a significant part of the final quality of the job and will ensure its profitability. The reason for implementing the incoming process is to ensure that the received materials and components comply with: the specifications indicated in the order form (colours, etc.) standard product specifications good practice rules. 8
11 X Y Z Means and process 2. Incoming delivery 2.2. Procedures Verification Quantity@and@appearance@@of@products@could@be@performed@by@the@ receiving@offi@cer@according@to@the@"basic@checklist@for@incoming@". Quality@checking@should@be@done@by@the@quality@inspector. In@cases@of@large@product@volumes,@this@operation@could@be@done@ on@a@sample. If@the@drawing@of@the@component@to@be@inspected@includes@a@dimensional@warning@!,@the@quality@inspector@shall@check@the@dimensions@on@5@samples. 25±0.25! Example All@incoming@items@should@be@received@and@stored@in@such@conditions@that@they@will@ not@be@damaged@untill@their@fi@nal@installation. Non-conformity processing All@non-conforming@products@shall@be: _@ confi@ned@in@a@separate@location _@ registered@as@a@non-conforming@product@and@clearly@identifi@ed.@ All@precautions@should@be@taken@to@prevent@their@repetition. Basic checklist for incoming of sheet metal parts The type of material is right Aluminium Steel Stainless Plastic Color The component looks like the drawing and the 3D view all shapes and holes exist the component is bent in the correct side all cut edges are straight, without stairs or burs no deformation due to punching sub-assembly is consistent with the bill of material Checking programme: manufactured parts checking card Product type: Drawing No.: Quantity: Dimensions to be measured on 5 samples Dimesion to be checked Location Parts or lot checked The coating is well done on visible sides: no grains no tears no craters no scratch overall: adherence uniformity Grain Crater Not OK Not OK The dimensions identified by! are measured on 5 samples Comments checking card is written Purpose of the document: This document lists the basic checks to be performed in order to ensure the quality of the switchboard manufactured parts (see the "Blokset Transfer File" for further details) Approved Rejeted Date: / / Signature: 9
12 Means and process 3. Design Design office Procurement Receptionist Manufacturing stage Operator Final Quality inspector Customer acceptance Customer Installation Installator Commissioning Customer Commercial contract Design Procurement order Basic check list for incomming Dimensional Framework Assembly plan specifications Busbar Assembly plan specifications Device & drawer Assembly plan specifications Enclosure Assembly plan specifications Quality guide Design Quality plan Installation guide Installation Customer acceptance Quality control plan 3.1. Inspection during manufacturing To ensure the conformity of the product or sub-assembly with the expected needs, the quality assurance programme may recommend the implementation of a specific procedure. Done on parts of an assembly or at the end of various assembly operations. The following diagram represents the operations on which in-process s are carried out and the main items concerned by incoming quality. Design Framework Busbar assembly Device assembly Wiring Enclosure Copper bars Devices Sheet metal 3.2. Justification for during the manufacturing stage The reasons for performing during the manufacturing process are: the complexity of some equipment systems. It could be necessary to perform a quality process during manufacturing to ensure the conformity of parts or assembly stages due to: difficulty of access: current transformer, bar characteristics, connections, installation, etc.; the time (profitability) needed for the final inspector to remove some covers or other parts; the will to involve and motivate the staff for the quality of their work; the workshop organisation; existence of dedicated assembly line for frame, busbars, functional units (withdrawable, disconnectable, plug-in, fixed); presence of a device adaptation work station; mass produced manufacturing system. 10
13 Means and process Process Inspection during the manufacturing stage could be described by the following process. Inspection during the manufacturing stage. This operation involves carrying out checks at different stages of the assembly process: done at the end of each key manufacturing step (framework assembly, busbar installation, device & drawer mounting, wiring, enclosure assembly) is part of the operators' work. Each operator must fill in an " " quality inspectors have responsability for overseeing and compiling all "Inprocess s". Continuous The assembly operations require constant observance of good practice rules. Due to this, this procedure involves carrying out checks throughout manufacturing in the form of operator or project supervisor checks. It will make them responsible for the quality of their work. These checks should always be validated by the final inspectors. Notice: The cleaning process is an integral part of the checking operations and should be performed during and at the end of the manufacturing process and registered on the check list. (i.e.: Okken or Blokset busbar compartment) Means The instructions ( specifications) provided with assembly drawings enable these checks to be formally defined on check list s. One check list is commonly dedicated to each manufacturing stage, and located on the cubicle frame. The fitter should fill in the check list dedicated to his manufacturing stage to allow the quality inspector to verify that all the points have been checked and that the procedures have been implemented. These checklist s are used to log the status of the s performed. The same forms are finally validated by the quality inspector during the final stage. N.B.: Despite the operator checks performed for each operation, final is always necessary, as stipulated by the IEC and IEC standards. 11
14 Means and process 4. Final Design Design office Procurement Receptionist Manufacturing stage Operator Final Quality inspector Customer acceptance Customer Installation Contractor Commissioning Customer Commercial contract Design Procurement order Basic check list for incomming Dimensional Framework Assembly plan specifications Busbar Assembly plan specifications Device & drawer Assembly plan specifications Enclosure Assembly plan specifications Quality guide Design Quality plan Installation guide Installation Customer acceptance Quality control plan Final guarantees operation and conformity of products in accordance with applicable drawings and standards. It is performed by the unit s quality department. One document per project formulating the customer s requirements and transcribing the specification is used for the checking phases during assembly and for final. It forms the first reference document (production file).@ The following table gives you an idea of the average time required to perform a final according to the type of switchboard to be inspected. The following information is given as an average % of assembly process. Switchboard Simple Complex PCC 3% 8% MCC Final process Final takes place as follows Carry out the conformity check by compiling the " s". Conduct the final tests. Modify the production file by adding any necessary annotations (throughout testing). List all the non conformities: by noting all the faults or modifications observed; by drafting a list of missing parts. Ensure reworking for conformity. Point out any areas of dispute between customer and supplier. Ensure that the design documents have been properly by checking final version status and updating. Ensure that all the check lists have been filled in. Draft and record the quality control plan. Sign the quality control plan and other documents. If customer acceptance is scheduled, receive the customer and/or his representative in the quality zone.@ Sign the "Quality control plan" after customer acceptance. Archive the documents. 12
15 Means and process 4. Final List of the various final tests: Conformity checks These checks consist of validating all " s": framework busbar device and drawer enclosure. Mechanical checks These checks consist of testing proper operation of the mechanisms and manual controls, the sturdiness of the switchgear, etc. Electrical checks Operating tests Dielectric withstand Electrical continuity of protection circuits 4.2. Operating rules The operating rules can be modelled using the following diagram. 13
16 Means and process 4. Final 4.3. Non-conformity treatment process The following diagram describes the various possible cases of treatment of non conformities. During the final operations, any errors detected must be recorded on a "non-quality record board" and all non conformities corrected. E.g.: type of table. Non-quality record board Corrective action Location / Type of fault BB assembly Cabling Performed by Time Cabling error b Jean 5 min Signature Busbar support missing b Alain 1 hour 14
17 Means and process 4. Final 4.4. Conformity declaration On completion of final, the quality inspector's signature declaring conformity of the equipment should be affixed on the identification label placed on the drawers and Panel builder lene X0 000 ile Tel : XX XX XX XX XX Fax : XX XX XX XX XX Quality Checked by: Conformity DATE:..././. frame Conformity Job No.: device Mechanical check Switchboard: power Electrical test Cubicle:. auxiliairies Dielectric test Equipment No./location: Rating:.. Design No.: finishing Protective measures check Insulation test Index: Only fully inspected cubicles can be dispatched. A label, resembling the one below, is used to identify them before packaging. Final sheet Ready for dispatch Client: Purchase order No. Switchboard designation:... Quality control plan No.:... Design file reference... Issue on: Quality Inspector Name: Signature: Date:.../.../... Quality Manager Name: Signature: On request, and depending on the product's destination, it is also uo to the quality manager to establish a mark declaration of conformity (e.g. CE) which certifies that the industrial product complies with the technical directives and obligations incumbent on the product manufacturer. 15
18 A: IN SHOP INSPECTION H : HOLD POINT W1: FULL WITNESS INSPECTION (during FAT*) M : MONITORING XXXXXXX 0 dd/mm/yyyy W2 : SPOT WITNESS INSPECTION (during FAT*) 1 = 100 % *FAT : Factory Acceptance Tests 2 = 5 % QUALITY ACTIVITY CHARACTERISTICS TO BE PROCEDURE ACCEPTANCE REFERENCE CONTROL POINTS - BY TYPE AND EXTENT ACTIVITY EPC or Third Party Purchaser No. VERIFIED REFERENCE CRITERIA DOCUMENT VENDOR if applicable in Customer if applicable in the project the project 1.2 Presence of distinctive Blokset features: * Schneider Electric logo on each cubicle * handling eyebolts * Danger (triangle) logo on each plate or door covering conductors 1.3 Compliance of colour with Front View Diagram indication, with absence of scratches and stains PRESENCE COMPLIANCE Front View Diagram 1.8 IP degree construction compliance COMPLIANCE Assembly Drawings 1.10 Strict use of Schneider Electric genuine busbar supporting parts (horizontal Proof of purchase to busbar comb supports, vertical drawers cubicle busbar supports, drawer COMPLIANCE Schneider Electric A plugs, drawer auxiliary contacts) 1.11 Visual check of all power connections Marked with solid red varnish A (paint), with no cracking 1.12 Drawers & other functional units interlocks: Single Line Diagram and drawers interchangeability interlock Interlocking Diagram drawers insertion/extraction interlock COMPLIANCE A ACB insertion/extraction interlock Mechanical ACB source switching interlock 2 VERIFICATION OF ELECTRICAL FUNCTIONALITY COMPLIANCE / IN SHOP INSPECTION 2.1 Compliance of LV devices identification & tagging COMPLIANCE Wiring diagrams A 2.2 Compliance of wiring COMPLIANCE Wiring diagrams A Compliance of protection & automatic functionalities, local/remote controls, Wiring diagrams 2.3 COMPLIANCE A timings, etc. Functional schemes 2.4 Power circuits dielectric test NO FLASHOVER / SPARK IEC A 2.5 Power circuits insulation test NO FLASHOVER / SPARK IEC A 2.6 Ground continuity on switchboard ELECTRICAL CONTINUITY IEC A A A Means and process 5. Summary of tasks after final stage Design Design office Procurement Receptionist Manufacturing stage Operator Final Quality inspector Customer acceptance Customer Installation Contractor Commissioning Customer Commercial contract Design Procurement order Basic check list for incomming Dimensional Framework Assembly plan specifications Busbar Assembly plan specifications Device & drawer Assembly plan specifications Enclosure Assembly plan specifications Quality guide Design Quality plan Installation guide Installation Customer acceptance Quality control plan Quality Control Plan DOCUMENT NUMBER REVISION NUMBER DATE AR: APPROVAL REQUIRED T/C : TEST CERTIFICATE REQUIRED 1 GENERAL VERIFICATION OF COMPLIANCE / IN SHOP INSPECTION 1.1 Compliance of quantity, order and tagging of cubicles. COMPLIANCE Single Line Diagram A 1.4 Switchboard overall dimensions and functional units dimensions COMPLIANCE Front View Diagram A 1.5 Doors opening & locking functionality FUNCTIONAL A 1.6 Keylocking system compliance COMPLIANCE Interlocking Diagram A 1.7 Drawers mechanical insertion/extraction/latching functionality FUNCTIONAL A 1.9 Compliance of equipment and switchgear type and rating COMPLIANCE Single Line Diagram A VENDOR: Remarks CERTIFIED COMPLETE : DATE: 5.1. Customer acceptance before installation After final and according to the contract clauses, the Quality Inspector may perform a check on the project accompanied by a sales engineer and the customer or his representative. During the acceptance procedure, the customer makes sure that the specifications have been complied with. N.B.: The procedures mentioned in this guide are given as an indication. After final, the following are required: Check that all the boxes of the checking programme have been filled in. Check any reworks noted on the "non-quality record board" and sign in the relevant boxes. Draft and record the quality control plan. Note the quality control plan registration number on the checking programme. Ask the quality manager to validate the (the final should be signed by the customer or his representative after customer acceptance ). Draft and record the Installation See "Installation CUSTOMER'S ACCEPTANCE REPORT 5.3. Commissioning Fill in and sign the costumer's acceptance with the costumer. Customer Project Switchboard Project No. Participants : Other concerned people : Plant's Manager, Sales Manager, Quality Manager, Design office Manager Dispatching Manager QI : Mr... DOF : Mr... N Record STAGE OBSERVATIONS AND ACTIONS RESP.* VISA QI Time spent for resamption Design Office Assembling QI Customer's representative Quality attendant Salesman Final acceptance date of shipping Date : Date : Date : Date : Name : Name : Name : Signature Qual. Manager : date of delively Signature : Signature : Signature : Resp.* : A Design Office, Production, = Automatism, D = S = Shipping, P = QI = Quality Inspection page / 16
19 Means and process Notes 17
20
21 Detailed instructions 6. Performing in-process 6.1. Design Framework Busbars Device and drawer Enclosure Performing final 7.1. First routine test: of the assembly, conformity check Second routine test: protective measures & protective circuit Third routine test: dielectric test Pre-dispatching checks 34 19
22 Detailed instructions 6. Performing in-process Design Design office Procurement Receptionist Manufacturing stage Operator Final Quality inspector Customer acceptance Customer Installation Contractor Commissioning Customer Commercial contract Design Procurement order Basic check list for incoming Framework Assembly plan specifications Busbar Assembly plan specifications Device & drawer Assembly plan specifications Enclosure Assembly plan specifications Quality guide Design Quality plan Installation guide Installation acceptance Quality control plan Okken local adaptation rules Can do (in autonomy) WARNING Warning: authorized and forbidden operations are defined in the Adaptation rules. They must be scrictly followed. You can adapt the enclosure panels (front and rear panels) to end-user needs, ensuring the phase-to-phase & phase-to-ground clearances remain the same as in Okken (14mm minimum) Why? This does not have any impact on IEC TTA characteristics of Okken (short circuit, thermal rise, clearance/creepage distances) You can adapt outgoing power connection by increasing their length or cross section (to have more cables connectable), ensuring the phase-to-phase & phase-to-ground clearances remain the same as in Okken (14mm minimum) Why? Increasing the connection dimensions, with due care with clearances, will have a slightly positive effect on thermal rise. This does not affect negatively the IEC type tested performance. You can increase the size of b functional unit (feeder, drawer, incomer) b busbar b power connection b cable from Okken DVD Panelbuilder Tools, without changing its defined power/current rating. Why? Increasing the dimensions of functional unit/busbar/power connection/cable, with due respect of rules expressed in Okken Panelbuilder Tools (last version), will have a slightly positive effect on thermal rise. This does not affect negatively the IEC type tested performance. Reminder The purpose of in-process is to ensure product conformity after each manufacturing operation. This process concerns all the manufacturing operations done by the workshop operators. Composition One check list sheet for each manufacturing stage is completed for each cubicle and/or functional unit (depending on the manufacturing process). These documents are used by both the operators and the quality inspectors (see model check list in appendix). These are used from the first manufacturing phase through to final. These check lists should mention: the designation of each point to be controlled the operator's identification and the checking period. Process After each stage, the operator checks and declares the product in conformity by signing this follow-up check list sheet and noting any observations. On completion of the s, a copy of this sheet could be archived. 20
23 Detailed instructions 6. Performing in-process 6.1. Design Switchboard characteristics Check the protection index required in the project production file. Check that the corrosion resistance required in the project production file is taken in account. Check the form partitioning level. Check the organisation of spares. Make sure that separate equipment delivery is defined. Cubicle characteristics Check that the dimensions, number and layout of cubicles are in accordance with the layout and the civil engineering works specified in the project production file. Check that the incoming cable cut-outs comply with the incoming cables' characteristics (section number, position). Busbar characteristics Check the environmental installation (temperature, humidity) specification required in the project production file. Check that the horizontal and vertical busbar cross-sections are in accordance with the short-circuit and/or peak current. Check that busbars are in conformity with the corrosion resistance required in the project production file. Make sure that the type of busbar coating is defined. Device and drawer characteristics Make sure that device characteristics defined comply with the project production file and derating tables. Make sure that the jaw characteristics comply with the corrosion resistance. Check that the mismatch coding is defined. Wiring characteristics Validate the single-line diagram. Check that BUS architecture rules are complied with (cf. wiring guide) 6.2. Framework Dimensions of cubicle Check the cubicle dimensions (height, width, length and by measuring and comparing them with those required in the production file. Mechanical assembly Check the overall assembly, frame position (top, bottom), the presence and location of the screws required for assembling and joining the cubicles, bottom plate, mounting plate, etc. Check that screws are properly tightened. Cleanness Check the cleanness of the framework assembly: no grease, no scratch, etc Busbars Type and characteristics Check the bars' characteristics according to the type of the project specifications and the project design. Cross-section According to nominal current (In), short-circuit current and/or peak current, IP, circuit-breaker breaking time, etc. Check that the cross-section corresponds to that shown in the project production file and product documentation. Coating Check the type of busbar coating (bare copper, tin-coated, sheathed busbars, epoxy paint, silver-plating, nickel, etc.). 21
24 Detailed instructions 6. Performing in-process Layout and installation Busbars Check their position (horizontal, vertical, top, etc). Check that the layout or arrangement of the busbars does not obstruct the routing of customer cable. Ensure the extension possibilities of the busbars according to specific features. Supports Check the spacing, fastening, characteristics and number of busbar supports. Refer to technical documents, switchboard characteristics, etc. Type of supports: Check their type and characteristics (material) referring to the switchboard characteristics. Check the alignment of the support, and presence of deformation due to extra torque applied to the fixing bolt. Bending radius and bar alignment Check that the bending radius and angle are in accordance with the drawing. If specified, use the jig to check dimensions. Check the perfect alignment of the various bar assemblies: Ensure good positioning in the support; Make insertion of the connection bolt easier. Busbar junctions and links Joint cross-sections Characteristics and number Check positioning and accessibility of the joint screws Insulating distances versus frame, form partition, etc. Bar overlapping surfaces: H = th. x n. For all non-standard bar connections done under supervision of the fitter, an overlapping height equal to 5 times the thickness of the derived busbar must be allowed for order to obtain a suitable connection. Contact surfaces Quality of drilling/punching and surface finish (no burr or cutting deformations on the conductors, no oil stains, etc.). Correspondence between the hole diameter and bolt. Bolt characteristics Check the bolt type (in accordance with the product quality: class 8/8, stainless steel, etc. Installation and tightening torque Bolt insertion method (insulating distance), length of bolt, etc. Presence, position and type of washer. Tightening torque in accordance with bolt, devices and other part characteristics. Consult the product and devices documentation. Presence of varnish certifying tightening to correct torque. In case of doubt: Number of threads protruding from the nut, for connections of the same type, differs on screws of the same length. Contact washers excessively crushed or moving, carry out a sampling check. If a number of faults are detected, ask the person responsible for assembling the switchboard to verify all its connections. Clearances Shortest distance in the air between two live conductors or between live conductors and exposed conductive parts. 14 mm for 12 kv impulse voltage (main Masterpact busbar) 8 mm for 8 kv impulse voltage (Compact) 5.5 mm for 6 kv impulse voltage (Multi 9). The IEC and IEC standards stipulate the minimum clearances required to withstand impulse voltage up to 2000 m above sea level. Pollution degree 3. 22
25 Detailed instructions 6. Performing in-process Creepage distances Shortest distance along an insulated material surface between two live conductors or between live conductors and exposed conductive parts. 16 mm for rated insulation voltage 1000 V AC and DC (main busbar Masterpact) 12.5 mm for rated insulation voltage 750 V AC and DC (Compact) 8 mm for rated insulation voltage 500 V AC and DC (Multi 9). See IEC and IEC table 16. Pollution degree 3, Material group 3a. Marking and phase order Check phase labelling type conformity. Check that phase order (phases 1, 2, 3, neutral and PE) is complied with according to the product specifications. Cleanness After busbar installation, ensure that no foreign bodies are lost in the bars compartment. In particular in the case of access difficulties Device and drawer Conformity of devices Device characteristics Type, rating Breaking capacity and number of poles Masterpact terminal pad characteristics and installation (according to product). Inspection to be performed prior to installation in the cubicle. Toroïds Check the technical data of each toroid. Also ensure the correct mounting direction: the arrow shows the current direction. Current transformer Check the technical data of the current transformers together with the installation direction. Check the correspondence between the current transformer and the associated device, ammeter, etc. Ensure that the current delivered by its secondary circuit is compatible with the associated device. Check compliance with clearances between the fastenings and the secondary connecting screws of the current transformer relative to live conductors or metal parts. Check whether the current transformers are well secured on the conductor. Shunt Check the connection between the shunt and the measuring instrument. Safety perimeters Check the circuit-breaker safety perimeters, referring to their installation guides. No devices, equipment or bundles should be located in the safety perimeter. Mounting Contact surfaces Quality of drillings/punching and surface finish (no burr or cutting deformations on the conductors, no oil stains, etc.). Correspondence between the hole diameter and bolt. Bar overlapping surfaces: H = th. x n. For all the non-standard bar connections done under supervision of the fitter, an overlapping height equal to 5 times the thickness of the derived busbar must be allowed for in order to obtain a suitable connection. Avoid problems (flexion, torsion, etc.) due to incorrect busbar positioning on devices or terminal pad connections. Bolt characteristics Check the bolt type (in accordance with the product quality: class 8/8, stainless steel, etc. 23
26 Detailed instructions 6. Performing in-process Installation and tightening torque Bolt insertion method (insulating distance), length of bolt, etc. Check the Linergy sliding bolt position. Presence, position and type of washer. Tightening torque in accordance with bolt, devices and other parts' characteristics. Consult the product and devices documentation. Presence of varnish certifying tightening to the correct torque. In case of doubt: Number of threads protruding from the nut, for connections of the same type, differs on screws of the same length. Contact washers excessively crushed or moving, carry out a sampling check. If a number of faults are detected, ask the person responsible for assembling the switchboard to verify all the connections. Clearances Shortest distance in the air between two live conductors or between live conductors and exposed conductive parts: 14 mm for 12 kv impulse voltage (main busbar Masterpact) 8 mm for 8 kv impulse voltage (Compact) 5.5 mm for 6 kv impulse voltage (Multi 9). The IEC and IEC standards stipulate the minimum clearances required to withstand impulse voltage up to 2000 m above sea level. Pollution degree 3. Creepage distances Shortest distance along an insulated material surface between two live conductors or between live conductors and exposed conductive parts: 16 mm for rated insulation voltage 1000 V AC and DC (main busbar Masterpact) 12.5 mm for rated insulation voltage 750 V AC and DC (Compact) 8 mm for rated insulation voltage 500 V AC and DC (Multi 9). See IEC and IEC Table 16. Pollution degree 3, Material group 3a. Wiring To be checked according to the device and switchboard characteristics. Flexible bar characteristics and installation Check characteristics and cross-section. Radius of curvature of the flexible bars (at least once times bar thickness). Manual bending operations are recommended to avoid damaging the bar insulator. In the event of a superimposed flexible bar installation, ensure that insulating spacers are placed between the conductors to provide proper ventilation. Binding and cable trunking Check that the characteristics and number of bindings used match the electrodynamic force that could affect the assembly in case of short circuit. No direct binding on metal parts. If necessary fit an insulating wedge. Check connections: presence of thick flat washer and contact washer. Maximum cable size 6 mm² in cable trunking. Ensure that the spare space in the cable trunking is approximately 30 cable fasteners should preferably be made of insulating accessories (e.g. polycarbonate screws or rivets). The maximum centre-to-centre distance between two trunking fasteners must not exceed 600 mm. Cable characteristics Cross-section of power and auxiliary conductors: check cross-sections with reference to the switchboard specifications and product documentation. Type and colours. Nature of cables: Schneider recommends use of U 1000 V insulation with an insulation temperature resistance of < 105 C (self-extinguishing). Using these cables, we meet class 2 requirements, so these cables may be secured directly on metal supports. Cables installation Protection of cables: Check that the cables do not run near sharp edges, moving parts, against or between exposed live parts, air blast areas, etc. No cables should be inserted in ventilation grille hole or mechanical fixing holes. Radius of curvature: Ensure that the cable radius of curvature is roughly 6 to 8 times cable diameter. 24
27 Detailed instructions 6. Performing in-process Number of cables per Refer to the switchboard assembly and installation guide. Separating the Check that the power and control strands are separated as well as the strands receiving an auxiliary voltage of more than 500 V AC and the DC circuit and communication network (cf. Communication wiring guide) Cable fixing:@ Make sure that the conductors are fastened in accordance with their characteristics, size and network short circuit withstand. Check collar characteristics. Non-protected active conductors Ensure that cables not protected by short-circuit devices are installed safely along their entire path. Separated bundle, no risk of mechanical damage, safe connection, etc. Cable connections Three types of are performed according to the connections: Visual (A) of: the crimping recess (quality, pressure, etc.); the correspondence between the lug or terminal and the cable section; the position of the conductor core in the lug shaft, and proper cable insertion; the bolt diameter relative to the lug fixing hole; the quality of the cable insulation and strands (no damage during cable installation or wire stripping operation). Mechanical (B) by manual pulling (performed by random sampling). Verification (C) of: presence and direction of contact washers; presence of varnish certifying tightening to the right torque (on visible connections) or use of torque nuts. The following table gives the s to be performed according to the type of connection used: where A, B, C stand for the various types. A = visual B = mechanical C = checking presence and positioning. Connections Power Other circuits Jaws and auxiliaries pins A + B A + B Lugs A + C B + C Clips - A + B Cable connectors A B Terminals B + C B Screws C C Connection stresses and fastening: Check that the lugs match with the connector type. Be sure that the cables are properly inserted in the terminal. Reminder: Make sure that the crimping tools are calibrated. Test It is recommended to use the drawer test equipment for mechanical and electrical testing of each drawer (cf. Industrial guide). Manual operation of equipment Manoeuvre the manual mechanisms of the devices, to ensure their proper operation. Check the operation of the functional units based on drawers, disconnectable, plug-in on base or chassis version. Equipment fastening Check the fastening of the devices on the drawers, on Polyfast ( during manufacturing process), on mounting plates, on doors, etc. Check that they are correctly fitted and that all the necessary screws or miscellaneous additional items are present. Special attention should be paid to: assembly compliance with functional dimension tolerances; jaw installation and validation in the check list. Check that the auxiliary blocks are correctly identified and assembled and that the mechanical assemblies remain free to move. 25
28 Detailed instructions 6. Performing in-process Mechanical operation To be checked: Installation and operations of the position contact, door, drawer position, extended rotary handle, etc. Operation of the limit switch, position of drawers, circuit breakers, contact located on door. Functional units (drawers - plug-in, disconnectable, etc.) operating margin. Jaws Check power jaws plug-in penetrations and installation. With Blokset, use the specific jig to check the bars' position (jaw operation). Accessibility of functional units or devices Check accessibility of the terminal, current transformer, etc. Always check the ease of access to pivoting front face locking devices. If stipulated in the project specifications, check also check the access facilities for thermography Enclosure PE and/or PEN protection busbar characteristics Cross-section: Check using the technical guide. Presence and cross-section of fishplates between cublicles: Check that fishplate cross-section is at least equal to the cross-section of the busbar to be connected (see technical guide). Earthing systems: In some configurations (earthing systems: TNC, TNS), check presence of the PEN/ PE connection. Two-colour green/yellow marking: Check presence of the green/yellow marking and PE or PEN lozenges on the conductors. Earthing fishplate: Check presence and cross-section of fishplate. Then ensure that its cross-section is the same as that of the earth busbar (for PEN). Wiring (terminal blocks and protection busbar connection) Bolt characteristics and tightening torque Check the bolt type (in accordance with the product quality: class 8/8, stainless steel, etc. Bolt insertion method (insulating distance), length of bolt, etc. Check the Linergy sliding bolt position. Presence, position and type of washer. Presence of varnish certifying tightening to the correct torque. Check that all screws, picot washers and earth braids (if required) for fixing these components are present. In case of doubt: Number of threads protruding from the nut, for connections of the same type, differing on screws of the same length. Contact washers excessively crushed or loose: carry out a random check. If a number of faults are detected, ask the person responsible for assembling it to verify all the switchboard connections. Cable characteristics Check cross-section of power and auxiliary conductors:@ Check cross-section with reference to the switchboard specifications and product documentation. Type and colours. Nature of cables:@ Schneider recommends use of U 1000 V insulation with an insulation temperature resistance of < 105 C (self-extinguishing). Using these cables, we meet class 2 requirements, so these cables may be secured directly on metal supports. Cable installation Protection of cables: Check that the cables do not run near sharp edges, moving parts, against or between exposed live parts, air blast areas, etc. No cables should be inserted in ventilation grille holes or mechanical fixing holes. Radius of curvature:@ Ensure that the cable radius of curvature is roughly 6 to 8 times cable diameter. 26
29 Detailed instructions 6. Performing in-process Number of cables per Refer to the switchboard assembly and installation guide. Separating the Check that the power and control strands are separated as well as the strands receiving an auxiliary voltage of more than 500 V AC and the DC circuit and communication network (cf. Communication wiring guide). Cable fixing:@ Make sure that the conductors are fastened in accordance with their characteristics, size and network short circuit withstand. Check collar characteristics. Wiring in cable trunking: Maximum cable size 6 mm² in cable trunking. Ensure that the spare space in the cable trunking is approximately 30 cable fasteners should preferably be made of insulating accessories (e.g. polycarbonate screws or rivets). The maximum centre-to-centre distance between two trunking fasteners must not exceed 600 mm. Non-protected active conductors Ensure that cables not protected by short-circuit devices are installed safely along their entire path. Separated bundle, no risk of mechanical damage, safe connection, etc. Accessibility and client connection facilities@ Accessibility of power connection points on devices, and terminal blocks: Compliance with the cable curvature radius and cable routing (entry from the top/bottom) Check the length of pads and number of connecting holes taking into account the size and number of cables (check the devices or product information). Check: that the number and cross-section of cables ensure compliance with clearances (lugs)@ Reminder: the arrange must ensure safety of the operators (maintenance); the number and sturdiness of cable supports; the ease of connection of client cable on earth or PEN bar nearby the functional unit. Appearance Paint colour and reference Use the colour palette to ensure that the reference of the paint in the project file matches the colour of the cubicle. Verification generally carried out at the incoming delivery stage. Mounting Panelling Operation of drawers: check the operating safety margin of the drawers and ease of operation; drawer inserting and withdrawal should be performed without damaging the internal components or wiring. Operation of doors and mechanical accessories: Check their operation by manoeuvring them. Ensure that the cubicle equipment is complete and has been installed properly. Check the presence, characteristics (IP, material, etc.) and proper fitting of: ventilation grille, bottom plate; side and rear cover; roof, blanking plate, etc. Conformity of apertures in the plates:@ Using the drawing, check the presence of any apertures in the roofs, mounting plates and separation plates allowing fish plating, coupling bar installation, interlock cable or rod installation, etc. Degree of protection This check is performed by checking the presence of the components ensuring the IP level stated in the project production file. Needs vary according to the required IP degree: awning, seal, front plate, cable glands, etc. (information given in the product catalogues or guides). If a seal is used, ensure it is properly positioned and continuous. Make sure that the IP degree of the equipment located on the door or the device manoeuvring mode (apertures on doors or presence of specific cover), matches the switchboard requirements. Safety check Ensure that no foreign body is lost in the bar compartment. 27
30 Detailed instructions 7. Performing final Design Design office Procurement Receptionist Manufacturing stage Operator Final Quality inspector Customer acceptance Customer Installation Contractor Commissioning Customer Commercial contract Design Procurement order Basic check list for incoming Dimensional Framework Assembly plan specifications Busbar Assembly plan specifications Device & drawer Assembly plan specifications Enclosure Assembly plan specifications Quality guide Design Quality plan Installation guide Installation acceptance Quality control plan 7.1. First routine test: of the assembly, conformity check The Quality Inspector must: take delivery of the switchboards to be inspected in the dedicated zone become acquainted with the product production file; check the observations and information given in the assembly follow-up sheet (could be a part of the follow-up check list); perform final using the follow-up check list. checklist validation Check and validate the in-process check list fullfilled by operators during at each manufacturing stage. Composition, dimensions and identification label Number and order of cubicles Use the drawing of the project front face to ensure that the number and order of cubicles is respected. Check that the information marked on the label match with the project file. Check the presence of a product identification marker on each cubicle. This is normally in the form of a self-adhesive label. Ensure that this label contains the registration number, signature, switchboard number and the design update version. On completion of final, the Quality Inspector must place his registration number (or signature) and indicate the date at which the was performed. Homogeneity - Finish Perform a visual to check the homogeneity of the colours of the various switchboard components (doors, panels, etc.). Check external appearance by a visual : no scratches, deformations, etc. Front face and mimic diagram: Visually check that the front face of the switchboard matches that shown in the product drawing. Check conformity of the mimic diagram compared with the power diagram and front layout. Framework ground fixing, handling devices, keys Ground fixing: Use the product design drawing to check the location of the ground fixing points. Handling devices: Check their fastening and layout according to the documentation. Keys: Check matching of lock references and key numbers with the references given in the product production file. 28
31 Detailed instructions 7. Performing final Connection facilities, space and equipment Check the special facilities provided for cable routing (top or bottom) and bus way connections. Fixing of mounting plates, protection screens and partitioning or cowling parts: Check that all the screws for fixing these parts are present, and properly secured; Check the quality of the riveted assembly: type of rivets, direction, pressure. Conformity of devices Location/identification: Use the layout diagrams in the product production file to ensure that the devices are properly located and identified (QF1, QF2, etc.). At the same time, the nature of the labels associated with the devices and the content of the text can be checked. Check presence and technical data of circuit breaker s associated devices (Vigi, fault signal switch, trip unit, etc.). Check the supply voltages for: switchgear motor mechanisms; coils (contactors, relays, impulse relays, undervoltage or shunt coils of the Compact, Masterpact and multi 9); indicator lights; all electronic devices; soft starter, capacitor bank, etc. Check compatibility of the toroid with the customer connection cables. Current transformer: Check the technical data of the current transformers together with the installation direction check the correspondence between the current transformer and the associated device, ammeter, etc. Make sure that the current delivered by its secondary circuit is compatible with the associated device. Check compliance with the clearances between the fastenings and the secondary connecting screws of the current transformer relative to live conductors and metal parts. Check that the current transformer is well secured on the conductor. Accessories: Visual checking of the presence of: crank handles for circuit-breaker and/or drawer extraction; door stops, light; clamps for fuse extraction; pins for fixing certain relays; etc. Mechanical check on safety and locking system. All mechanisms making the various operations (possible or impossible) to be checked. Functional unit pre-tripping and locking. Check that during plug-in or plug-out operation of the functional units (withdrawable, disconnectable, plug-in on base or chassis version) is impossible when the device is closed (Pre-tripping accessories, mechanical locking and/or micro-switch). Check pre-tripping of the devices, on plug-in and plug-out operations. Devices on chassis, plug on base, drawers, disconnectable on strip, contactors, etc. Check fuse blowing mechanical operation. Fault trip and position indicator Position of the mechanical indicators after operation, a fault trip, drawer manoeuvring. Check that the circuit-breaker is reset after an electrical fault trip or after pressing the tripping test button. Check the position of the handle. Make sure of the correct resetting of the devices and drawers after a fault trip or switching operation. 29
32 Detailed instructions 7. Performing final Safety systems Check sturdiness of the various locking and mismatching systems. Check that closing of one device prevents closing of the other associated one: Locking by rods: check their mechanical fasteners and adjustment. Locking by cables: check their radius of curvature using the installation guide and ensure that they do not run near exposed live parts. Locking by key-locks: check the type and references of the key-locks and make sure that the key-lock prevents the device from operating. Check that the code of the polarising slots matches the specifications (drawers, devices on chassis). Check padlocking operation (devices, drawers, etc.). Inter change: check the possibility of interchange of circuit-breakers or of the same type. Clearances Shortest distance in the air between two live conductors or between live conductors and exposed conductive parts: 14 mm for 12 kv impulse voltage (main busbar Masterpact) 8 mm for 8 kv impulse voltage (Compact) 5.5 mm for 6 kv impulse voltage (Multi 9). The IEC and IEC standards stipulate the minimum clearances required to withstand impulse voltage up to 2000 m above sea level. Pollution degree 3. Creepage distances Shortest distance along an insulated material surface between two live conductors or between live conductors and exposed conductive parts: 16 mm for rated insulation voltage 1000 V AC and DC (main busbar Masterpact) 12.5 mm for rated insulation voltage 750 V AC and DC (Compact) 8 mm for rated insulation voltage 500 V AC and DC (Multi 9). See IEC and IEC Pollution degree 3, Material group 3a. Manual equipment of operation Operate the devices' manual mechanisms, to ensure their proper operation. Check the operation of the functional units based on drawers, disconnectable, plug-in on base or chassis version. Check the operating safety margin of the drawers and their ease of operation; inserting and withdrawal of drawers should be performed without damaging the internal component or wiring. Mechanical operation: To be checked: installation and operation of the position contact, door, drawer position, extended rotary handle, etc.; operation of the limit switch, drawer position, circuit breakers, contact located on door; functional units (drawers - plug-in, disconnectable, etc.) operating margin. Installation and maintenance access Check accessibility of: joint, cubicle coupling accessories; settings, HPC fuses for replacement, contactor coils, interlocking mechanism, arc chute chamber. In some particular cases (e.g. plug-in auxiliary terminal blocks), check the ease of removing these items from their mounting with regard to screw access for modifications and maintenance. The associated bundles should be long enough to have access to the screws without difficulties. Presence of electrical and mechanical grease Jaw lubrication. Mechanical parts lubrication. Consult the technical product documentation. Freedom of the power clamp fingers, contact pressure. Make sure that during the functional units' operation, the various types of power and command and control clamps will not be damaged. Check carefully whether the contact pressure seems well distribued. 30
33 Detailed instructions 7. Performing final Electrical operations checks Equipment preparation. Connect the equipment circuit and be sure of the earth link between sections. Before energising, open the auxiliary control devices (relays, measuring instruments, coils, etc.). Power the switchboard from the control desk, ensuring that voltage and phase rotation direction is complied with. Check power circuits Carry out the operations Open all the devices. Check the order of the phases Check correspondence of circuit and conductor identifications Check correspondence of the phases on each device by closing them one by one from line side to load side (see example on the left). Testing is always performed downstream of the devices in order to check the poles at the same time. However, a different method can be used. When the devices are connected to terminals or pads, perform tests on them. Check the control circuits Check the power supply of the auxiliary circuits by examining the phase order on their associated control devices. Reminder: special attention should be paid to non-protected circuits (see IEC and IEC ). Electrical indicator light and command and control button: Check operatoin of indicator lights Check correspondence of the command and control button with the associated devices. Remote/local operating mechanisms: Check their operation. If necessary use accessories (pin tip, small box equipped with pushbuttons, indicator lights, etc.). Supply circuits: Systematically check the electronic switchgear supply circuits and the DC circuits using a tester (voltmeter). Check the information supplied on the connection terminals: Contact status Other information (voltage, current, etc.). Motor mechanisms Close the relevant protection devices. Activate the devices' operating mechanisms according to the command and control diagram: local, remote, automatic, etc. Electrical locking Check that it is impossible to close a device equipped with a locking contact. Metering circuits Check the winding direction, and input and output characteristics of the current transformers. To check the metering circuits, the CT secondary must be powered using a phase shift box (failing this, you can use any other calibrated device offering the same possibilities). Example of operations performance: Select the supply voltage. Adjust the maximum value of the current to be injected into the secondary circuit; inject the current into one of the circuits or into all three at once to check cabling. Check the test function Circuit-breaker operation is checked by a variety of tests depending on the device type: Earth leakage module test (Multi 9 range, NS range): Close the circuit-breaker Press the test button of the Vigilohm part. This test is used to regularly check device tripping by simulating an earth fault Trip unit test (NS and Masterpact range):@ This test is performed using an external electronic tripping box Close the circuit-breaker. Make it trip using the box by connecting its cord to the specially provided socket on the front face of the trip unit part. For increased dependability, repeat this operation. If the circuit-breaker opens for each test, the device is operating correctly. 31
34 Detailed instructions 7. Performing final Voltage relays, time delay relays, fault tracking devices. For voltage relays, check that the contacts are in the status defined in the electric design. For time delay relays, check correct operation of the time delays. If mentioned, check that these settings comply with the product design file. For the fault tracking devices, create a fault and check that the device detects and indicates its presence. In order to create a fault, a resistance box can be supplied: Pre-set the value of the resistance required to create a fault according to fault tracking device characteristic. Make the resistance vary by reducing its value. When the resistance is adjusted below the pre-set value, the device must indicate the fault Second routine test: protective measures & protective circuit Protective measures and electrical continuity of protection circuits (IEC and IEC standards) Monitoring protection circuits The is either visual and/or electrical as required by the customer. Mechanical (Visual) PE and/or PEN protection bars. Check the presence of all the constituent elements of the assembly which ensure the electrical continuity between the metal part and the earth bar (see technical file). Cross-section in accordance with electrical characteristics. Presence and cross-section of the joints between the cubicles: they should be at least equal to the cross-section of the PE/PEN bar to be connected. Depending of earth/neutral connection systems, check presence of the PEN/PE disconnecting link and access. Ensure that its cross-section is the same as that of the earth bar. Check that the protective conductors are identified by the two colours green/yellow marking plus PE or PEN lozenges; the accessibility of the terminals for external conductors; the contact efficiency between sections or parts of the protective circuit; the presence of only one conductor per connection on the protective bar. If, for maintenance reasons, a part of the equipment is removed from the enclosure, the protective circuit of the other parts should not be interrupted. Electrical N.B.: There exist some electrical measuring devices able to perform this The above method is given only for information. Example of operating mode: A DC source is used, with an electromotive force of less than 6 V / 2 A current is injected between the input of the earth busbar and the parts to be inspected (doors, front face, frame, etc.) Measured resistance: R = U/I Result: the is satisfactory if the measured resistance between the circuits and exposed conductive parts is below 0.1 Ohm. Register the result on the final record list. Operator safety, protection of persons During normal operations devices adjustment; operating handle access; drawer operation. Be sure that persons are protected during the following operations: pre-tripping of devices on plug-in and plug-out operation; operating safety; drawer mechanical locking. During maintenance and safety operations (emergency stop, padlocking, etc.) Warning plate: Check the presence of the various warning plates such as "do not step", "danger", "danger supply side", form door, advertising plate for voltage equal or greater than 660 V, etc. No live part near the operating handle, adjustment screw, etc. 32
35 Detailed instructions 7. Performing final Plug-in protection flaps. Check the presence of the plug-in flap: chassis, etc. Insulation screen / phase separator / terminal shield. Check that they are fitted (if required), firmly fixed and connected to earth for the metallic parts. Conformity of partitions and form Check the presence of all screens, form partitioning and protection covers of devices located on the door (direct contact). Protection against contact This is performed by checking the presence of component parts such as: picot washers earthing braids, doors, device chassis (according to type and installation method); barriers, front plate, etc. For earthing braids, check their strength by exerting a slight pressure on their connections Third routine test: dielectric test Dielectric withstand (IEC and IEC standards) Preparation The dielectric test is always performed before the insulation test. Before performing the test, make sure that you disconnect: the surge absorbers (if any); the covers from the Vigi modules of the Compact NS; the electrical control motors; and any other device not withstanding the applied voltage (electronic switchgear, contactor coils, indicator lights, miniature relays, horn, measuring instruments, etc.). The interference suppression capacitors installed between the live parts and the frames must not be disconnected, but be able to withstand the test voltage. This test does not need to be performed on auxiliary circuits which are connected to the main busbar if it: is protected by a device of rating < 16 A; has previously undergone operating tests (IEC and IEC ). N.B.: Check that no unprotected connections are left. For example: remove the neutral connection wire for permanent insulation measurement. Operating mode Perform this test using a dielectrometer (or dielectrimeter) to deliver a variable voltage V AC. Voltage to be applied: Rated insulation voltage Ui Dielectric test voltage Main circuit 300 V < Ui y 690 V 2500 V 800 V < Ui y 1000 V 3500 V Ui y 60 V 1000 V Auxiliary circuit Ui > 60 V (2 Ui ) V with 1500 V min. Apply voltage on each phase in turn and on the other phases which are interconnected and led back to the switchboard frame. The standard stipulates that this test voltage must be maintained for one second. N.B.: If, for any reason, the dielectric test must be repeated, it will be done with a voltage lowered to 85% of the previous value. 33
36 Detailed instructions 7. Performing final Carrying out the operations Example of the phase live part test: All switching devices shall be closed-interconnect the exposed conductive parts and earth them. Interconnect the live parts to one another and then to the assembly conductive parts. Connect the measuring instrument earthing wire to the assembly frame. Connect the injection cable to the circuit to be monitored and gradually increase voltage up to the required value. The test voltage should be applied for 1 second. Gradually reduce voltage before disconnecting. Once this check is complete, repeat it for the other live circuits. Result The tests are satisfactory if there is no puncture or flashover. Register the result on the final record list. Insulation resistance Preparation Before performing the test, make sure that you disconnect: the surge arrestor (if any); the covers from the Vigi modules of the Compact NS; electrical control motors; current consuming devices, so as not to create connections between live conductors and loads such as measuring instruments, coils, relays, indicator lights, contactor electromagnets, etc.). Operating procedure Using an insulation measuring instrument (megohmmeter), measure insulation at a voltage of 500 V DC. This measurement is performed between each live part and the other interconnected parts of the assembly. Operating procedure: The procedure is the same as that used for testing dielectric withstand. Result The test is correct if insulation resistance between the circuits and the frame is at least 1000 W/V with respect to the nominal voltage of this circuit. Register the result on the final record list Pre-dispatching checks Cleanness Prior to packing, check that the equipment is clean: No dust No foreign body forgotten in the equipment. Reminder: See Chapter 3.2 concerning assemblies for witch access is difficult at the final stage. Miscellaneous Using a detailed check list established by the design office, perform of: all the equipment to be delivered separately, spare parts, devices dismantled for transport, etc.; roof, coupling screws; busbar joints, etc. Documentation Presence of the name plate and/or the "as built design". Make sure that all the documentation relating to the quality procedures are filled in: missing parts list; quality control plan; checking program; corrective action form; non-quality record board; delivery slip; etc. 34
37 Detailed instructions 7. Performing final Associated documentation delivered with the equipment: device and switchboard technical documentation; maintenance documentation; missing parts list; and on request quality control plan. Be sure that all internal devices and other parts are well secured, inserted or locked in the switchboard Packaging Inspection of packaging before delivery according to: the type of product to be carried; the means of transport; the destination; storage conditions; climatic conditions. 35
38
39 Follow up 8. Quality status chart 8.1. Purpose Principles Produced non-quality Example of a Produced Non-Quality index board Non-conformity weight example 39 37
40 Follow up 8. Quality status chart 8.1. Purpose This status chart allows the measurement of quality performance and reveals the necessary corrective actions to be taken Principles The quality assurance manager issues a monthly quality entitled "Quality indicator ". Performance is evaluated according to the four indicators below: purchased non-quality produced non-quality non service quality external non-quality. The non-quality index: is an indicator used to measure changes in non-quality defines the target objectives reveals the weaknesses of the various operations and allows the relevant actions to be taken. These non-quality indices can be calculated using specific formulas (see chapter 9.3). The index which is directly associated with final is "produced nonquality". Purchased non-quality can be monitored by different indicators depending on the origin of supplies: Overall ratio Ratio of supplies purchased Internal manufactured supplies ratio. External non-quality: Taking customer complaints into account (intermediate or end users) Produced non-quality This index is calculated after the final process the "non-quality record board". It is calculated using this formula: Non-quality index = Sum of weighted faults Total number of cubicles* The faults revealed by quality are assigned, according to their origin, to Production, the product design department or Sales. The faults are classified in 3 categories: minor: a fault corresponding to a non-conformity; major: a fault risking a considerable reduction in the achievement of a function in the switchboard; critical: a fault which, based on judgement and experience, is likely to result in a lack of safety or risk of accidents for the user. It presents a real danger for persons and equipment. Weighting The weighting applied to these three types of faults is: minor fault = 1 major fault = 3 critical fault = 10 Produced non-quality is monitored by means of indicators for each type of product and a overall indicator. Remarks: Note 1: In the distribution switchboards (PCC), the number of cubicles indicated corresponds to the number of cubicles produced. Note 2: In the motor control panel (MCC), the rules are as follows: - Framework = 0.3 cubicle - < 12 m (1) drawers or functional units = 0.1 cubicle - u 12 m (1) drawers = 0.2 cubicle (1) Modules. Example of an MCC cubicle made up of:@ 1 framework (1 x 0.3) = 0.3@ 2 drawers 250 A - 6 modules (2 x 0.1) = 0.2@ Total = 0.5@ Cubicle equivalent =
41 Follow up 8. Quality status chart 8.4. Example of a Produced Non-quality index board Product Number Non-conforming Faults Responsibilities Weighting version Qty % A B C Weight, total Prod. Product design dept. Ext. Equip Equip Equip Total Equipment 1: Prisma Plus A: Minor = 1. Equipment 2: Prisma Plus B: Major = 3. Equipment 3: Okken C: Critical = 10. Example of a graph showing the non-quality index. The peaks shown on the graph may be due to: the number of projects handled the complexity of certain projects (complicated operating sequence) insufficient personnel training insufficient sensitivity of personnel poor control of supplies poor quality of the product production file Non-conformity weight example Item Description Weight 1 Labelling 1 2 Wire marking 1 3 Wiring appearance 1 4 Accessibility of equipment 1 5 Apparatus fastening 1 6 Space for customer connection 1 7 Bad crimping 3 8 Auxiliary wire section 3 9 Auxiliary protection rating 3 10 IP degree 3 11 Earth connection 3 12 Phase polarity 3 13 Electrical sequence operation 3 14 Auxiliary wire damage 3 15 Power wire damage Insulating distance Power cable or busbar cross-section Protection devices conformity Number and clearance of busbar supports Interlocking 10 39
42
43 Facilities and calibration 9. Facilities 9.1. The Quality Inspector s individual tools Common quality facilities Quality zone Necessary documents Control of facilities Purpose Reminders of basic principles Responsibility Diagram of operations Application rules Listing and monitoring and production facilities Occasional checks Devices outside the accuracy class 44 41
44 Facilities and calobration 9. Facilities 9.1. The Quality Inspector s individual tools These are the switchboard fitter s tools (screwdriver, wrenches, with, in addition: a small rule or measuring rods to check clearances; a lamp; an articulated mirror; a set of crocodile clips; a bell tester; a set of probe fingers Common quality facilities Control desk:@ Enables the main and auxiliary circuits to be energised. Equipped with a voltage regulator and a number of selector switches and indicators, to make the various operating sequences easier. Dielectrometer:@ To perform the dielectric testing followed by insulation resistance testing. Megohmmeter:@ To perform the insulation resistance testing Earth continuity tester Phase order tester Drawer test equipment Test cords and a variety of plugs, supply cords and other connection systems Steps, pallet-mover or other transportation facilities Quality zone Quality zone: is independent from production must be physically separated from the other departments: for reasons linked to the hazards of electric current for protection of people and equipment is clearly marked out (tapes, partitions, etc.) is clearly indicated (warning beacon, flashing light, sign, etc.). This area should be equipped in compliance with applicable legislation and local regulations Necessary documents To carry out the various checks, the quality inspector must have: a complete, updated production file of the project, check list; a missing parts list; update procedures and associated document; updated products documentations (devices, equipment system...); standards. He must have the necessary facilities (mechanical and electrical): test desk, variable current and voltage sources; measurement devices, multi-meter; bell tester; phase order monitor. 42
45 Facilities and calobration 10. Control of facilities Purpose The purpose of these operations is to check the and production facilities used in the unit for maintenance and calibration. To organize facilities tracking to set up possible corrections on delivered equipment Reminders of basic principles Inspection facilities List and identify the facilities. Have them checked at specific intervals, according to the accuracy of the measurements to be taken, by an approved international or national (For example, the organisation for France is the B.N.M. National Metrology Office). Identify by a "not followed up in calibration" label, the devices not assigned to measurement (e.g. power on detection devices). Store, use and transport these means in conditions guaranteeing their proper operation and level of accuracy. Rule on delivered project equipment inspected using non-conforming measuring instruments. Production facilities Torque wrenches. Crimping equipement Responsibility The and production facilities supervisor appointed by the quality manager is in charge of: listing and identifying these facilities; implementing and monitoring the checks; decision-making after checking; archiving the documents Diagram of operations 43
46 Facilities and calobration 10. Control of facilities List the projects delivered and tested using the faulty means Application rules Choice of facilities Inspection and production facilities are chosen according to: the type of measurement; the theoretical values to be measured; the required accuracy; the type of process to be performed. Classification of facilities For checking All the and production facilities identified and monitored. The items of equipment identified by a "not followed up in calibration" label and listed on the associated document are used as indicators only. Checking frequency Inspection facilities The normal frequencies chosen are: 1 check once a year for normally used (e.g. dielectricmeter, etc.) 1 check once every 2 years for seldom used means. Production facilities Torque wrenches: must be calibrated at least once a year. Crimping means: must be checked once a year Listing and monitoring and production facilities A list of and production facilities, plus a checking schedule, are updated by the quality manager. Each and production means has a life sheet, which is opened for each acquisition and completed after each check by the manager. A label is placed on tools by an authorised organisation. It gives the check date and the date of the next check to be carried out. The checking s, measurement readings and non-conformity sheets transmitted by the organisation are filed with the life sheet Occasional checks These checks must be performed after: acquisition of a new and production means (without verification or conformity certificate); an impact; a repair; a loan; a long period of inactivity Devices outside the accuracy class Should the calibration organisation declare the means to fall outside the accuracy class, it is up to the manager to isolate it and implement one of the decisions listed below: Repair; downgraded to an operation means not assigned to measurement (indicator only); scrapping (most common case for production means). The calibration manager must also decide whether to initiate a notification of non-conformity (NNC) used to rule on delivered project equipment which was inspected using the defective device in question as on the left: (*) See the example of a corrective action request in the appendix. 44
47 Appendix 11. Model form Follow-up of missing parts Checking programme Checking program: manufactured parts checking card Non-quality record board Corrective action request Quality control plan Missing parts list Glossary Abbreviations Vocabulary 59 45
48 Appendix 11. Model form Follow-up of missing parts 2. Follow-up of missing parts at end of project Project no.:... Date received by or factory availability lead time Missing at end of assembly Issued by:... Date:... (copy) V Q.I. Items Project co-ordinator References Quantities Supplies Lead time announced 2 - Missing parts at end of /customer acceptance Issued by:... Date:... Items Project co-ordinator References (copy) V Q.I. (copy) V Warehouse Quantities Supplies Lead time announced 3 - Sales department notification Can the project be dispatched with missing parts? Yes No Can the missing parts be partially dispatched? Yes No Which ones?... Missing parts dispatch address: Project site delivery date:... 46
49 Appendix 11. Model form Checking programme Back to Checking programme: Design Index: Product type: Drawing No.: Cubicle No.: Project No.: Customer: Date: Checking programme Quality Conformity Observations Checked by OK Not OK Repair Checked by Conforming Remarks Compliance with the project production file Switchboard characteristics Cubicles characteristics Busbars characteristics Devices and drawer characteristics Wiring characteristics Checking during process: fill in the grey box Final and testing: fill in the white box 47
50 X Basic checklist for incoming of sheet metal parts The kind of material is the good one Aluminium Steel Stainless Plastic Color The component looks like the drawing and the 3D all@cut@edges@are@straight,@ sub-assembly@is@consistent@ with@the@bill@of@material Y Z The coating is well done no@scratch uniformity Grain Crater Not OK Not OK The dimensions identified by! are measured on 5 checking@card@is@written Goal of the document: This document lists the basic checks to be performed in order to ensure the quality of the switchboard manufactured parts (see the "Blokset Transfer File" for further details).
51 Appendix 11. Model form Checking program: manufactured parts checking card Dimensions to be mesured on 5 samples Dimension to be checked Location Parts or lot checked Comments Approved Rejected Date: / / Signature: 49
52 Appendix 11. Model form Checking programme: Framework Index: Product type: Drawing No.: Cubicle No.: Project No.: Customer: Date: Checking programme Quality Conformity Checked by Observations OK Not OK Repair Checked by Conforming Remarks Dimensions of cubicle Mechanical assembly Cleanness Checking during process: fill in the grey box Final and testing: fill in the white box 50
53 Appendix 11. Model form Checking programme: Busbars Index: Product type : Project No.: Drawing No.: Customer: Cubicle No.: Checking programme Date: Quality Conformity Checked by Observations OK Not OK Repair Checked by Conforming Remarks Type and characteristics Layout and installation Bending radius and bar alignment Busbar junctions and links Contact surfaces Bolt characteristics and tightening torque Clearances Creepage distances Marking and phase order Cleanness Checking during process: fill in the grey box Final and testing: fill in the white box 51
54 Appendix 11. Model form Checking programme: Device & Drawer Index: Product type : Project No.: Drawing No.: Customer: Cubicle No.: Checking programme Conformity Checked by Observations OK Not OK Date: Repair Quality Checked by Conforming Remarks Conformity of devices Type and characteristics Toroïd Current transformers Shunt Safety perimeters Mounting Contact surfaces Bolt characteristics and tightening torque Clearances Creepage distances Wiring Flexible bars characteristics and installation Cables characteristics and installation Binding and cable trunking Cable connections Test Equipment manual operation Equipment fixing mechanical operation Jaws characteristics and installation accessibility of functionnal units or devices Cleanness Checking during process: fill in the grey box Final and testing: fill in the white box 52
55 Appendix 11. Model form Checking program: Enclosure Index: Product type : Drawing No.: Cubicle No.: Project No.: Customer: Date: Checking programme Quality Conformity Checked by Observations OK Not OK Repair Checked by Conforming Remarks PE and/or PEN protection busbars characteristics Wiring terminal blocks Bolt characteristics and tightening torque Cables characteristics Cables installation Appearance Painting color and reference Mounting Panelling Degree of protection Safety contol Checking during process: fill in the grey box Final and testing: fill in the white box 53
56 Appendix 11. Model form Checking programme: Final Index: Product type : Drawing No.: Cubicle No.: Project No.: Customer: Date: Checking programme Quality Conformity Checked by Observations OK Not OK Repair Remarks First routine test / of the assembly, conformity check cheklist validation Composition, dimensions and identification label Homogeneity - Finishing Framework grounding fixing, handling devices, keys Connection facilities space and equipment Conformity of devices Mechanical check of safety and locking system Clearances and creepage distances Equipment manual operation Installation and maintenance access Electrical and mechanical grease Electrical operations checks Second routine test / protective measures & protective circuit Monitoring of the protection circuit Mechanical Electrical Operator safety - protection of persons Third routine test / dielectric test Dielectric withstand Insulation resistance Cleanness Final and testing: fill in the white box 54
57 Appendix 11. Model form Non-quality record board Non-quality record board Quality inspector: Manufacturing: Project name: Date: Product: Quantity: Job number: Number of faulty column: Client: Number of drawer: Repair action A: minor fault B: major fault C: critical fault A B C A B C Repaired Checked by Location and type of fault Design / tendering Manufacturing By: Duration Q.I. Sum of faults Page: 55
58 Appendix 11. Model form Corrective action request Corrective action request Action request of:... Date:... From:... To:... Copy to:... Non-conformity detected by customer Detected internally Concerned product:... Project No.:... Issued by:... Date :... Customer:... Description of the non-conformity Any suggestions Answer Corrective actions Performed by Date Corrective action settled Date:... Quality assurance. signature 56
59 Appendix 11. Model form Quality control plan Procès verbal de contrôle final / Quality control plan Client :... PV n / Registration Nr Affaire / Project :... N Cde client / Client ref.: Nom du tableau / Switchboard identification N affaire / Job ref.: Produit / Product :... Quantité / Qty :... final check delivery Plan n / Drawing No. :... Indice / Index: Gamme de contrôle / Checking programme 1. Contrôle de conformité / Conformity checking - Les enveloppes / Enclosures... - L appareillage / Switchgear... - Les conducteurs / Conductors Vérifications mécaniques/ Mechanical checking Essais electriques / Performances electric test Continuité électrique des masses mécaniques Exposed conductive parts electrical continuity Visuel / Visual Electrique / Electrical Réf. Appareil / Measuring device ref.:... Valeur / Value Essais diélectriques / Dielectric test Réf. Appareil / Measuring device ref.... Circuit / Circuit Auxiliaires / Auxiliaries Puissance / Power Tension nominale / Nominal voltage V Tension injection / Injection voltage V 6. Essais d isolement / Insulating test Réf. Appareil / Measuring device ref.... Circuit / Circuit Auxiliaires / Auxiliaries Puissance / Power Tension d applicat. / Applied voltage V Valeur d isolement / Insulation value V Observation / Comment:...@...@ Inspecteur client / Client représentative Inspecteur qualité / Quality inspector Respons. I.Q / Quality manager Date... Date... Visa... Visa... Visa... 57
60 Appendix 11. Model form Missing @ Plant Tel.: Fax: Missing parts list / Liste des composants non expédiés avec l affaire Project number / N d affaire :... Item / Poste Description / Désignation Quantity / Quantité Quality control / Contrôle qualité... Quality inspector / Inspecteur qualité... Date... 58
61 Appendix 12. Glossary Abbreviations B.N.M.: National Metrology Office. L.V.: Low Voltage. I.E.C.: International Electro-technical Commission. Dielectrimeter: A device used only to perform dielectric tests. Dielectrometer: A device used for withstand testing. It measures dielectric withstand and insulation resistance. I.P.: Degree of Protection. Q.I.: Quality Inspection. N.N.C.: Notification of Non-Conformity. I.T.P.: Inspection and Test Programme. P.E.: Electrical Protection. P.E.N.: Electrical Protection and Neutral. C.T.: Current Transformer. MCC: Motor Command and Control PCC: Power Command and Control Vocabulary Main definitions (ISO 9000 standard) Quality Degree to which a set of inherent characteristics meets a requirement Quality audit Methodical examination of all the measures described in the quality manual and the relevant procedures, in co-operation with the involved parties. This in order to assess whether the real state of the plant is in accordance with the description in the quality manual. Quality management Co-ordinated activities dedicated to managing and controlling organisation with regard to quality. Also includes assessment of the results and the corresponding cost. Quality manual Written documents specifying information about the quality management system of an organisation. Quality plans Documents describing the quality management system, and specifying which procedures and associated resources shall be applied by whom and when, in order to obtain the quality level of the considered project, product, process or contract. Also called "quality assurance programme". Procedures Specified way of carrying out an activity or process. Written document describing the organisation and manufacturing method, control,, checking, assessment, corrective actions intended to be strictly applied in order to reach the predefined quality level. Inspection Conformity evaluation performed within the scope of the defined process by observation, measurement, testing or gauging. Non-conformity Non-fulfilment or deviation of a need or expectation with respect to the specified requirement. Traceability Ability, from registered identification, to trace the process history and the location of the product after delivery. 59
62
63
64 Schneider Electric Industries SAS 35 rue Joseph Monier CS30323 F Rueil Malmaison Cedex RCS Nanterre Capital social As standards, specification and designs change from time to time. Please, ask for confirmation of the information given in this document. This document has been printed on ecological paper. Design: Schneider Electric Illustrations: Schneider Electric Printing: Schneider Electric - All rights reserved DESWED101005EN
P System Cubicles. Certified for more safety
P System Cubicles Prisma Plus LV Switchboards Certified for more safety Prisma Plus, an offer thought out for greater professionalism With the Prisma Plus P system, Schneider Electric proposes high-performance
3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance
SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132
MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4
CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,
FAQs-Main switchboard design criteria
FAQs-Main switchboard design criteria Q: What is the Australian standard for main switchboards? Current Australian standard is AS/NZS 3439.1: 2002 originating from IEC 60439. The new series of standard
IEC 61439-1 & 2 standard. The reference for safe and reliable LV switchboards
IEC 61439-1 & 2 standard The reference for safe and reliable LV switchboards IEC61439-1 & 2 The power of a standard adapted to your needs IEC standards are today legal or market references. The new IEC
White paper. SACE Tmax XT Circuit-Breaker Terminals and Connection
White paper SACE Tmax XT Circuit-Breaker Terminals and Connection Circuit-Breaker Terminals and Connections Index Introduction... 2 1. Components used for wiring... 3 1.1. Electrical...3 1.2. Flexibility
IEC 60439 >>> IEC 61439 GUIDE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES
xl 3 configurable assemblies IEC 60439 >>> IEC 61439 GUIDE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES XL 3 configurable assemblies guide to migration from IEC 60439 to IEC 61439
Submit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
Securing your electrical installations Prisma,
Securing your electrical installations Prisma, an optimised solution for type tested low voltage switchboards up to 3200 A Table of contents Developing installation safety 4 Prisma P * Electrical switchboards
Type-Tested Power Distribution Board 8PT with Rear Busbars. sivacon
Type-Tested Power Distribution Board 8PT with Rear Busbars sivacon The Obvious Solution for Global Challenges SIVACON Type-testing is one of today s important issues for low-voltage technology and will
Explosion proof enclosures
1 of 7 Explosion proof enclosures DE8 C 2 of 7 The Ex d enclosures are rugged and designed for harsh environment like: Oil and gas industry Chemical industry Pharmaceutical industry Agribusiness Without
Installation. Smart-UPS VT MGE Galaxy 3500. Maintenance Bypass Panel. 10-40 kva 400 V
Installation Smart-UPS VT MGE Galaxy 3500 Maintenance Bypass Panel 10-40 kva 400 V Contents Safety.................................................. 1 Save these instructions...................................
Unified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE
LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE 380/415/690 Volt AC 50/65/80/100 ka 1. Product Guide Low Voltage Motor Control Centre CONTSTRUCTION Continuous "poured in place" gasket
AMPSEAL* Automotive Plug Connector and Header Assembly
AMPSEAL* Automotive Plug Connector and Header Assembly Application Specification 24 SEP 97 Rev E All dimensions are given in millimeters unless otherwise specified. All dimensional tolerances are +0.2
NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements
NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems Safe energy distribution that meets the highest industrial requirements NATUS switchgear systems your advantages minimal use of insulant
know-how Giant in distributing electricity for industry Prisma GK
Prisma GK Giant know-how in distributing electricity for industry Installation system up to 630A for electrical power distribution and circuit control. Prisma GK: technology and innovation for an IP55
SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less.
PART 1 - GENERAL SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less. RELATED SECTIONS Division 16 Section "Basic Electrical Materials and Methods" for general
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to
SIVACON The Versatile Low-Voltage Switchboard
s SIVACON The Versatile Low-Voltage Switchboard Type-Tested Power Distribution Board 8PT The Obvious Solution for Global Challenges SIVACON Type testing in low-voltage switchgear is increasingly becoming
25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp
Page 1 2015 Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other Component 15 kv or 25 kv Separable Insulated Connector (elbow) Equipment Connection Power Cable Power Cable Grounded Metal
ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU
ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU George CURCANU, Constantin ILINCA, Ilie SBORA ICMET Craiova, Romania, Calea Bucuresti 144, phone:
ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA
MRO Modularne Razdelilne Omare d.o.o. ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 2, 000 Ljubljana, LOVENIA MC GENERAL When to use? MC - modular switchgear cabinets are type-tested, factory built switchgears,
Figure 1 (end) Updated document to corporate requirements Added text to Paragraph 2.4
This specification covers the requirements for application of ELCON Drawer Series Connectors: True Hot Plug, Blind Mating Mixed Signal and Power Connectors. These connectors are designed for use in pluggable
Pressure monitoring equipment for oil-sf 6. bushings, type GOEK
Pressure monitoring equipment for oil-sf 6 bushings, type GOEK Installation and maintenance guide 5693 827-6 en, Rev. 3, 2002-01-30 This document must not be copied without our written permission, and
NEW RANGE OF CABINETS DRIVIATM. Innovation at your service. THE GLOBAL SPECIALIST in electrical and digital building infrastructures
NEW RANGE OF CABINETS DRIVIATM Innovation at your service THE GLOBAL SPECIALIST in electrical and digital building infrastructures Drivia true innovation The new electrical panel for the residential and
Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.
Low voltage Direct Current Network Compact NSX DC PV Circuit breakers and switch disconnectors for solar application Catalogue 2012 Compact NSX DC PV A complete DC offer for solar application from 80
Digital input modules
8 172 TX-I/O Digital input modules TXM1.8D TXM1.16D Two fully compatible versions: TXM1.8D: 8 inputs, each with a three-color LED (green, yellow or red) TXM1.16D: As TXM1.8X, but 16 inputs, each with a
GE Power Controls. MiniFORM Switchboards
GE Power Controls MiniFORM Switchboards MiniFORM MiniFORM MiniFORM switchboards Arrangement Modules Arrangement modules 1-6 6 Arrangement modules 7-12 7 Arrangement modules 12-14 8 Arrangement modules
PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES
PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES BUSHING WITH PLUG CONNECTION WITH OUTER CONE PPS CHARACTERISTICS The PPS bushing can be used as a fixed section for the entry of medium
Trapezoidal-Connectors Series TMC
Trapezoidal-Connectors Series TMC Subminiature-D Connectors to DIN 41 652/IEC 807-3 General Series TMC connectors are available in 5 different housing sizes with 9, 15, 25, 37 and 50 pins. In applications
Distribution Boards & Consumer Units
Distribution Boards & Consumer Units Enclosures for system pro M compact Distribution Boards & Consumer Units Contents General 2/ Distribution Boards Mini Center compact Mounting kits for compact accessories
Functional system Prisma P
Enclosures and cubicles Functional system Prisma P Catalogue Prisma functional system Contents general page Index 2 Choice of switchboards 6 Prisma P functional system 11 b General presentation 12 b Installation
KAM 25-32 A Lighting Busbar System KAP 40-63 A Plug-in Busbar Distribution System
2-32 A Lighting Busbar System 4-63 A Plug-in Busbar Distribution System / E-LINE KX Compact Busbar Distribution System 63...63 A E-LINE KB Compact Busbar Distribution System 8...63 A E-LINE KO Plug-in
UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution
UniGear ZS1 Medium voltage, arc proof, air insulated switchgear for primary distribution UniGear ZS1: an innovative solution for all installation requirements ABB UniGear is medium voltage metal-clad,
METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast.
METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV tgood.com Energy. Fast. TGOOD produces over 5000 switchgear units annually for projects around the globe PRODUCT OVERVIEW Integral substation component
The Intelligent AX1 Switchgear for Medium Voltage
The Intelligent AX1 Switchgear for Medium Voltage Leif Lundin, Manager of Research and Development, Division Medium Voltage and Compact Substations, ABB Distribution, Sweden Abstract The newly launched
ATS Overhead Table Shelf System INSTRUCTION MANUAL
ATS Overhead Table Shelf System INSTRUCTION MANUAL ATS Overhead Table Shelf System Instruction Manual Warranty Newport Corporation warrants this product to be free of defects in material and workmanship
Comparative study for cables and busbars
Comparative study for cables and busbars Preliminary considerations To compare the prices of two categories of product as different as traditional cables and busbars, it is necessary to make some preliminary
SIRCOVER. Manual changeover switches from 125 to 3200 A. Changeover switches. Function. Advantages. The solution for.
The solution for Changeover switches svr_099_b_1_cat > Manufacturing industry. > Power distribution. 3200 Strong points svr_059_a_1_cat > complete range. > Easy connections. > Stable positions. > mproved
EARTHING AND BONDING AT SECONDARY SUBSTATIONS
DISTRIBUTION CONSTRUCTION MANUAL SECTION 4 - SUBSTATIONS ISSUE B SEPT 1996 4.4.4 EARTHING AND BONDING AT SECONDARY SUBSTATIONS 1 SCOPE This section of the Distribution Construction Manual lays down the
SOHOline and SOHO Slimline The SOHOline and SOHO Slimline offer a modular, sturdy and compact design
SOHOline and SOHO Slimline The SOHOline and SOHO Slimline offer a modular, sturdy and compact design Ideal installation for; Offices Branch Offices Schools Computer Aided Classes Government Offices Hotels
All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.
DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,
CAS 36 Ring Main Unit
Power distribution networks Ring Main Unit Catalogue 2008 A new path for achieving your electrical installations A comprehensive offer The range is part of a comprehensive offer of products that are perfectly
Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2...
Magnetic and Hydraulic-Magnetic Circuit Breaker 840-G2... Description Single, two and three pole magnetic circuit breakers with trip-free mechanism and push/pull on/off manual actuation. A choice of fast
Installation guide for the SafeLine type anchorage device. Tested in compliance with EN 795: 1996. No.: SE-...
Installation guide for the SafeLine type anchorage device Tested in compliance with EN 795: 1996 No.: SE-... Version: 09.10.2008 SE 67 Subject to technical alterations! Contents 1. General information
5.2. Overview. The better method to install solderless compression connectors on power cable
5.2 Overview The better method to install solderless compression connectors on power cable The Thomas & Betts method of installing compression connectors on power cables is designed to provide a high degree
Advantages of Fixed Circuit Breaker Switchgear
Advantages of Fixed Circuit Breaker Switchgear by Lionel Mackay, EDF Energy, and Mike Adams, Schneider Electric Ltd Introduction The purpose of this paper is to review the advantages of fixed circuit breaker
Series 8146/5-V37 and Series 8150/5-V37
www.stahl.de > Clear assignment safe technology easy installation > Intelligent structure only one rotary actuator for frequency-controlled drives ) 20 ms leading auxiliary contact for safe motor disconnection
Checklist Testing and inspection without interconnection
Shams Dubai Checklist Testing and inspection without interconnection Version.0 AUGUST 205 TABLE OF CONTENTS Scope...5. PV PLANT AND INSPECTION DATA... 6 2 TESTING EQUIPMENT...7 3 DOCUMENTS... 8 3. Reference
e 2 ALPHA Medium Voltage Switchgear Data Sheet K-1.1.2 EN
e 2 ALPHA Medium Voltage Switchgear Data Sheet K-1.1.2 EN We create ideas with power! ELEKTROMETAL ENERGETYKA SA is a new Polish company providing solutions for electrical power engineering. Our services
Low Voltage Switchboards The Best Technical Solution for Your Ship
The Best Technical Solution for Your Ship Wärtsilä SAM Electronics Optimal Power Distribution The uninterrupted supply of power to systems and consumers onboard modern ships is an extremly important matter.
UGVCL/SP/591/11KV HT AB CABLE
TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED) 1. SCOPE This specification covers requirements of XLPE insulated, 11 KV Aerial Bunched
The power distribution board that sets new standards
SIVACON The power distribution board that sets new standards SIVACON S4 safe, cost-efficient and flexible Answers for infrastructure. Contents We support you with system 04 05 Maximum safety is our top
39HQ Airovision Air Handling Units
39HQ Airovision Air Handling Units Mounting instructions CONTENTS 1 - TRANSPORT AND LIFTING INSTRUCTIONS... 3 1.1 - General... 3 1.2 - Transport and storage... 3 1.3 - Roof edge protection during transport
5SV Residual Current Protective Devices
s Siemens AG 2013 SENTRON 5SV Residual Current Protective Devices New portfolio for reliable personnel, material and fire protection Safe protection against residual currents Residual current protective
Low Voltage Products. Switches Automatic Transfer Switches
Low Voltage Products Switches Automatic Transfer Switches Growing importance of a secure power supply Standby power is an integral part of many industrial and domestic electrical systems. High energy prices,
R.C.C.B. s two-pole LEXIC
87045 LIMOGES Cedex Telephone : (+33) 05 55 06 87 87 Fax : (+ 33) 05 55 06 88 88 R.C.C.B. s two-pole LEXIC 089 06/09/10/11/12/15/16/17/18/ 27/28/29/30/35, CONTENTS PAGES 1. Electrical and mechanical characteristics...
Installation instructions of the MIDI-Heki roof light with operating bar, with crank or electrical version
Installation instructions of the MIDI-Heki roof light with operating bar, with crank or electrical version with operating bar with crank electrical version 1. Prerequisite for a correct installation of
SECTION 22 LIGHTNING PROTECTION SYSTEM
SECTION 22 LIGHTNING PROTECTION SYSTEM 22.01 SCOPE: A. These Specifications shall form a part of the Contract Documents and shall govern construction work for all buildings to be built or modified for
METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D
12 - ELECTRIC SERVICE HANDBOOK SECTION D METER REQUIREMENTS This chapter gives you information on Central Lincoln s metering requirements. It's divided into three sections: General requirements This section
INSTALLATION AND OPERATING INSTRUCTIONS For Model GL1 Gate Locks
Securitron Magnalock Corp. www.securitron.com ASSA ABLOY, the global leader Tel 800.624.5625 [email protected] in door opening solutions INSTALLATION AND OPERATING INSTRUCTIONS For Model GL1 Gate
Agilent X/P/K281C Adapters
Agilent X/P/K281C Adapters Including Options 006, 012, 013, 106 Operating and Service Manual Contents 1 Introduction 7 Product Overview 8 Options 8 Instruments Covered by Manual 10 2 Installation 11 Initial
Electrical Shore Connections / Cold Ironing
STANDARD FOR CERTIFICATION No. 2.25 Electrical Shore Connections / Cold Ironing JULY 2014 The electronic pdf version of this document found through http://www.dnv.com is the officially binding version
Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c 91052 Erlangen Germany. www.siemens.
Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c 91052 Erlangen Germany www.siemens.com/energy For questions on power transmission and distribution, please contact
-1- SPECIFICATIONS 002085 CONE SETTER PLATFORM ATTACHMENT INDEX
-1-002085 CONE SETTER PLATFORM ATTACHMENT INDEX I. GENERAL EQUIPMENT : A. Intent Statement B. Cone Setter Platform II. III. 1. Understructure Frame 2. Mounting Components 3. Paint 4. Basket 5. Labels 6.
INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1
City of Cotati Building Division 201 W. Sierra Ave. Cotati, CA 94931 707 665-3637 Fax 792-4604 INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 Any PV system on a new structures should be included
BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET
BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET Berthold Electric Company s Generator Connection Cabinet provides a quick and convenient station to connect a portable generator to a facility s main service
Operating Instructions
Operating Instructions Cable Glands Ex d and Ex e with Compound > Contents 1 Contents 1 Contents...2 2 General Information...2 3 General Safety Information...3 4 Designated Use...4 5 Technical Data...4
SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions
SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS POWER DISTRIBUTION RACKS IN A MISSION CRITICAL SYSTEM MODULES IN A MISSION CRITICAL SYSTEM UPS Convertor Main Inverter Load Battery BPC UPS & BATTERY
Drive shaft, servicing
Volkswagen Passat B6 - Drive shaft, servicing Стр. 1 из 41 40-7 Drive shaft, servicing Drive shafts, overview I - Assembly overview: Drive axle with CV joint VL100 40-7, Drive axle with CV joint VL100,
OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd
OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd ACTOM OUTDOOR DISCONNECTORS Single Side Break (SSB) Disconnector 22-132 kv, 800-1 A, 25 ka - 3s Typical bearing assembly. Voltage range 11 kv to 132
HS5D. Miniature Interlock Switches First in. Head Removal Detection Function for Safer Performance. First in. the Industry.
y HS5D First in the Industry Miniature Interlock Switches First in the Industry Head Removal Detection Function for Safer Performance (*based on IDEC research, July 09) New Generation Miniature Interlock
Operating Instructions
Important information: These instructions contain safety information, read and follow them carefully. Dialight will not accept any responsibility for injury, damage or loss which may occur due to incorrect
DF-DT (G) MEDIUM VOLTAGE SWITCHGEAR THE MODULAR CONCEPT. User Manual. SGC - SwitchGear Company nv - Moorstraat 24 - B-9850 Nevele - Belgium
DF-DT (G) MEDIUM VOLTAGE SWITCHGEAR THE MODULAR CONCEPT User Manual SGC - SwitchGear Company nv - Moorstraat 24 - B-9850 Nevele - Belgium +32 (0)9/321.91.12 - Fax +32 (0)9/321.91.13 - e-mail: [email protected]
SYSTEM 1850-SE SERVICE ENTRANCE CABLE SYSTEM
Pyrotenax SYSTEM 1850-SE SERVICE ENTRANCE CABLE SYSTEM Contents Introduction This section provides an overview of general circuit design considerations and installation guidelines for a Pyrotenax System
EC DECLARATION OF CONFORMITY FOR MACHINES
EC DECLARATION OF CONFORMITY FOR MACHINES (DIRECTIVE 98/37/EC) Manufacturer: Address: Declares that: FAAC S.p.A. Via Benini, 1-40069 Zola Predosa BOLOGNA - ITALY 770 mod. operator is built to be integrated
HVL 5 38 kv Load Interrupter Switchgear. The Standard for Performance, Protection and Dependability
HVL 5 38 kv Load Interrupter Switchgear The Standard for Performance, Protection and Dependability For a generation of engineers, Square D High Voltage Load (HVL ) Interrupter Switchgear by Schneider Electric
Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers
Specification Guide for RVAC Direct Replacement AC Medium Voltage Circuit Breakers Table of Contents 1.0 General Work Scope...3 2.0 Standards...3 3.0 Supplier Qualifications...4 4.0 Circuit Breaker Element
produces and delivers products worldwide can provide the optimal are dedicated to supplying you with superior advice and global support.
www.ppcinsulators.com The very Best. The very Best. That s what we deliver. ong od Insulators Only a company that develops, produces and delivers products worldwide can provide the optimal solution for
SECTION 16461 DRY-TYPE TRANSFORMERS
SECTION 16461 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Furnishing and installation of and testing of cast resin dry type MV/LV distribution transformer in accordance with specifications and drawings. Any
Installation, Operation and Maintenance Instructions. Uniflex ABB PTMV
Installation, Operation and Maintenance Instructions Uniflex ABB PTMV SAFETY FIRST! For safe and correct usage note the following recommendations: Only install switchgear and switchboards in enclosed rooms
Industrial Process Plants. Residential & Commercial Buildings. Roads & Tunnels. Airports & Seaports
APPLICATION TYPE TEST Industrial Process Plants ANT-V: Reliable, safety switchgear Hundreds of ANT s Switchboards have been supplied to industrial factories. ANT-V siwtchboards are designed, fabricated
UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation
Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers
BBWX1 Satellite Weather Receiver. Installation and Maintenance Guide
BBWX1 Satellite Weather Receiver Installation and Maintenance Guide Rev FUSA 15JUL2007 Table of Contents Safety Precautions 3 Disclaimer. 3 Contents of Package. 4 Tools Required..4 Installation General
Linkeo 19" freestanding cabinets
87045 LIMOGES Cedex France Telephone: (+33) 05 55 06 87 87 - Fax: (+33) 05 55 06 88 88 Linkeo 19" freestanding cabinets Page 1. General characteristics....1 2. Range....2 3. Technical characteristics...3
Technical data UNIBLOCK UBSF 180 625
Data TECHNICL DT Technical data UNIBLOCK UBSF 80 6 Output data Type UBSF 80 UBSF 0 UBSF 00 UBSF 6 Output power 80 kv 0 kv 00 kv 6 kv Output voltage 80/77 V 0/ V 0/ V 0/ V Output current 7 8 66 80 Power
WIRE, TERMINAL AND CONNECTOR REPAIR CONDUCTORS
CONDUCTORS Conductors are needed to complete the path for electrical current to flow from the power source to the working devices and back to the power source. Special wiring is needed for battery cables
270526-TC Grounding and Bonding for Telecommunications Systems
270526-TC Grounding and Bonding for Telecommunications Systems Part 1 - General Related Documents The following related sections of the OT standards shall also be applicable to this section. OT Engineer
12 Volt 30 Amp Digital Solar Charge Controller Installation & Operation Manual
12 Volt 30 Amp Digital Solar Charge Controller Installation & Operation Manual This 30Amp charge controller is designed to protect your 12Volt Lead-acid or Gel-cell battery from being overcharge by solar
Voltage Rated operating voltage [kv] 12 24 Rated power frequency withstand voltage [kv] 28 50 Rated lightning impulse withstand voltage [kv] 75 125
Standards and Regulations IEC 62271-200 ; VDE 0671-200 ; BS EN 62271-200 Technical Data MC3-12 MC3-24 Voltage Rated operating voltage [kv] 12 24 Rated power frequency withstand voltage [kv] 28 50 Rated
Terminal Boxes Series 8146
Series > Enclosures in shock-resistant glass fibre reinforced polyester resin > basic enclosure sizes various heights > Fitted according to the customer's requirements > For terminals up to max. 00 mm
INSTALLATION INSTRUCTIONS: Viewline 52 mm
-5 Safety information The product was developed, manufactured and inspected according to the basic safety requirements of EC Guidelines and state-of-the-art technology. The instrument is designed for use
Rittal s Comprehensive Family Of... NETWORK RACK SOLUTIONS
Rittal s Comprehensive Family Of... NETWORK RACK SOLUTIONS STANDARD & ECONOMICAL BasicRack A complete low-cost, high-quality basic equipment management system. Design Six web channel holes per side allow
42U/45U 28" Wide Rack Installation & Service Guide
42U/45U 28" Wide Rack Installation & Service Guide 96-00171-005 Rev B Important Information Information in this document is subject to change without notice and does not represent a commitment on the part
The range of rail-mounted terminal blocks. for a perfect electrical installation.
The range of rail-mounted terminal blocks for a perfect electrical installation. The range of rail-mounted terminal blocks for a perfect electrical installation. The new standard for rail-mounted terminal
Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC
Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC Project name: Customer: Address, location of the system: Serial number
ELECTRIC METERING COMMERCIAL & INDUSTRIAL
ELECTRIC METERING COMMERCIAL & 1.0 INDEX 1.0 INDEX 2.0 SCOPE 3.0 GENERAL REQUIREMENTS 4.0 METER LOCATIONS 5.0 UNDERGROUND TERMINATIONS 6.0 METERING TRANSFORMER ENCLOSURES 7.0 SINGLE CUSTOMER METER INSTALLATIONS
Linear Luminaire with LED Series EXLUX 6402/2
> Latest LED technology with a high luminous efficacy and a long service life > As pendant light fitting or side entry lamp > Central locking > All-pole disconnection by means of an N/C switch when the
ODU MEDI-SNAP. Miniature Circular Connectors with Push-Pull Locking Made of Plastic or Metal. www.odu.de
Miniature Circular Connectors with Push-Pull Locking Made of Plastic or Metal Miniature Circular Connectors with Push-Pull Locking for Medical Applications Applications Medical Test and measure equipment