Daikin Altherma Selection Report

Size: px
Start display at page:

Download "Daikin Altherma Selection Report"

Transcription

1 Daikin Altherma Selection Report Produced on 11/24/2012 with Daikin Altherma Simulator V database Central_USA Project name Typical Reference House Client name GMP Revision 1 Only the data published in the data book are correct. This program uses close approximations of these data. 1. Solution Overview System layout Low temp - Outdoor/indoor Low temp - Outdoor/indoor Outdoor unit model ERLQ054BAVJU ERLQ030BAVJU Indoor unit model EKHBX054BA3VJU EKHBX030BA6VJU Extra BTU/h BTU/h Domestic hot water tank EKHWS050BA3VJU EKHWS050BA3VJU Required heating capacity BTU/h BTU/h % covered by HP 99.2% 88.8% % covered by BUH 0.8% 11.2% Energy consumption heating 6964 kwh 8785 kwh Energy cost heating 1045 dollars 1318 dollars Spare cap. in heating, including BUH 1411 BTU/h 620 BTU/h Seasonal COP Required cooling capacity BTU/h BTU/h % covered by HP 100.0% 100.0% Energy consumption cooling 410 kwh 746 kwh Energy cost cooling 61 dollars 112 dollars Spare cap. in cooling BTU/h 9637 BTU/h Annualized EER Page 1

2 2. Low temp - Outdoor/indoor ERLQ054BAVJU 2.1. Material List Model Qty Description ERLQ054BAVJU 1 Outdoor EKHBX054BA3VJU 1 Indoor EKHWS050BA3VJU 1 Domestic hot water tank EKHBDP 1 Condensate Kit (for EKHBX Cooling Mode) - Altherma DACA-HBA /4" BSPT (F) to 1-1/4" NPT Adaptor (M) - Inlet/Outlet (EKHB_054) DACA-THXA-1 1 3/4" BSPP (M) to 1" NPT Adaptor (F) - DHW Inlet/Outlet (EKHWS) DACA-3WVTA-1 1 1" BSPT (M) to 1-1/4" NPT (F) Adaptor - 3-Way Valve (EKHWS) DACA-3WVTH-1 1 1" BSPT (M) to 1" NPT (F) Adaptor - 3-Way Valve Hot Water (EKHWS) DACA-DHWTA-1 1 3/4" BSPP (M) to 3/4" NPT (F) Adaptor - Cold Inlet/Hot Outlet (EKHWS) Page 2

3 2.2. Selection Criteria Location Country USA Vermont City Rutland State * Design conditions Conditioned surface Required capacity for space heating at min. night temp. Required capacity for space cooling at max. day temp. Application System layout Hydrobox placement Leaving water temperature range heating Leaving water temperature range cooling Power supply 1400 sqft BTU/h BTU/h Heat pump Low temp - Outdoor/indoor Wall mounted 86.0 F F 41.0 F F 230V 1ph Domestic hot water Solar connection Material inside Tank type Volume Power supply No Stainless steel Standard tank 53 gal 230V 1ph Page 3

4 2.3. System Diagram Domestic hot w ater tank EKHWS050BA 3V JU 53 gal Domestic hot water usage Heating & cooling Outdoor ERLQ 054BA V JU Indoor EKHBX054BA 3V JU 230V 1ph R410A Space heating/cooling 230V 1ph 230V 1ph Page 4

5 2.4. Technical Details Indoor EKHBX054BA3VJU Application Function Reversible Application Low temperature Leaving water range heating F Leaving water range cooling F Technical data Dimensions (WxHxD) 19.8x36.3x14.2 inch Weight 143lbs Drain connection 0.0inch Material Epoxy polyester painted galvanized steel Electrical data Power supply 230V 1ph Fuse size 20A Capacity electric backup heater 3.0 kw Capacity steps 1 Domestic hot water tank Technical data Water volume Max. water temperature Material inside tank Material outside tank Dimensions (WxHxD) Weight Electrical data Electric heater Power supply Fuse size EKHWS050BA3VJU 53 gal F Stainless steel Epoxy-Coated Mild Steel 22.8x45.3x22.8 inch 99lbs BTU/h 230V 1ph 20A Outdoor ERLQ054BAVJU Performance Nominal heating capacity BTU/h COP 4.2 Operation range heating F Nominal cooling capacity BTU/h EER 8.7 Operation range cooling F Technical data Dimensions (WxHxD) 38.6x53.1x16.5 inch Weight 227lbs Refrigerant R410A Base charge 8.2lbs Sound data Sound pressure 53dBA Sound power Electrical data Power supply 230V 1ph Fuse size 30A Page 5

6 2.5. Energy Consumption of the Domestic Hot Water Tank Type of usage Hot water consumption Water temperature Volume per day at F Occurrences per day Small 0.8 gal F 12.7 gal 16 Floor 0.8 gal F 0.8 gal 1 Clean 0.5 gal F 1.6 gal 2 Small dishwash 1.6 gal F 2.4 gal 1 Medium dishwash 2.1 gal F 0.0 gal 0 Larger dishwash 3.7 gal F 5.5 gal 1 Large 4.0 gal F 0.0 gal 0 Shower 10.6 gal F 21.1 gal 2 Bath 27.2 gal F 0.0 gal 0 Total per day at F 44.1 gal 5.8 kwh Actual total thermal energy consumption per year = 2126 kwh. Actual total electricity consumption per year = 886 kwh. COP calculations for DHW heating. The COP used in the energy calculation is based on the FprEN16147 (replaces the former pren255-3) large tapping pattern at a standard temp set of F for preparation of DHW and avoiding the use of booster heater. Page 6

7 2.6. Graphs Operation period Temperature ( F) Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Heating period 0 heating cap. above C ooling period 0 cooling cap. below Month Location Country USA Vermont City Rutland State * Temperatures (min / max) Summer Day 77.4 / 84.4 F Summer Night 63.3 / 70.3 F Winter Day 31.8 / 53.8 F Winter Night -4.0 / 10.0 F The graph shows the simulated outdoor temperature variations within the defined heating months. For heat pumps the graph also shows the temperatures in the cooling months. Page 7

8 Heating energy cost Heating energy cost (dollars) ERLQ 054BA V JU Gas boiler F uel boiler Electric heating Electricity normal tariff High price period 0.15 dollars/kwh Low price period 0.15 dollars/kwh Electricity heat pump tariff High price period 0.15 dollars/kwh Low price period 0.15 dollars/kwh Electricity Direct heater efficiency 100% Connection cost 0 dollars Gas Tariff dollars/thm Efficiency 80% Connection cost 0 dollars Fuel Tariff dollars/gal Efficiency 80% Design conditions Conditioned surface 1400 sqft Required capacity for space heating at min. night temp BTU/h Zero heating capacity at outside temperature 60.0 F The graph shows a comparison of the simulated annual running costs for Daikin Altherma, a gas boiler and an oil boiler. The calculation is based upon the selected buildings yearly required thermal input, each systems coefficient of performance (without pump) and the inputted energy prices. Page 8

9 Heating CO2 emission Heating C O 2 emission (x1000 lbs/y ear) ERLQ 054BA V JU Gas boiler Fuel boiler Electric heating Location Country USA Vermont Electricity Heating CO2 emission lbs/kwh Direct heater efficiency 100% Gas Heating CO2 emission lbs/kwh Efficiency 80% Fuel Heating CO2 emission lbs/kwh Efficiency 80% Design conditions Conditioned surface 1400 sqft Required capacity for space heating at min. night temp BTU/h Zero heating capacity at outside temperature 60.0 F The graph shows a comparison of the annual CO2 emissions for Daikin Altherma, an electric heating system, a gas boiler and an oil boiler sized to cover the yearly heat load for the simulated building. Neither Daikin Altherma nor the electric heater will have any direct emissions. The emission from these systems is based on calculations according to the average CO2 emission from the selected country's electricity production. Page 9

10 Energy consumption per month Energy consumption (kwh) Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Heat pump high price period: 6799 kwh / 97.6% (heating) Heat pump low price period: / 0.0% (heating) Heater high price period: 165 kwh / 2.4% Heater low price period: / 0.0% Heat pump high price period: 410 kwh / 100.0% (cooling) Heat pump low price period: / 0.0% (cooling) Month Yearly energy consumption (heating) 6964 kwh Primary energy use (heating) kwh Yearly energy consumption (cooling) 410 kwh Primary energy use (cooling) 1024 kwh Yearly energy consumption (heat/cool) 7373 kwh Primary energy use (heat/cool) kwh Electricity normal tariff High price period 0.15 dollars/kwh Low price period 0.15 dollars/kwh Electricity heat pump tariff High price period 0.15 dollars/kwh Low price period 0.15 dollars/kwh Design conditions Conditioned surface 1400 sqft Required capacity for space heating at min. night temp BTU/h Zero heating capacity at outside temperature 60.0 F Required capacity for space cooling at max. day temp BTU/h Zero cooling capacity at outside temperature 72.0 F The graph shows the energy consumption (input) per month for the heat pump and back up heater. There is made a separation between day and night operation to show the amount of energy consumption that falls under day and night tariff. Page 10

11 Energy cost per month Energy cost (dollars) Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Heating C ooling Month Total cost for year (heating) 1045 dollars Total cost for year (cooling) 61 dollars Total cost for year (heat/cool) 1106 dollars Electricity normal tariff High price period 0.15 dollars/kwh Low price period 0.15 dollars/kwh Electricity heat pump tariff High price period 0.15 dollars/kwh Low price period 0.15 dollars/kwh Design conditions Conditioned surface 1400 sqft Required capacity for space heating at min. night temp BTU/h Zero heating capacity at outside temperature 60.0 F Required capacity for space cooling at max. day temp BTU/h Zero cooling capacity at outside temperature 72.0 F The graph shows the running cost per month for Daikin Altherma according to the inputted electricity prices and the power input as given in the graph "energy consumption per month". Page 11

12 2.7. Supplementary Explanations Design conditions: The Daikin Altherma simulation software is a static calculation tool, which can be used as an indication for dimensioning Daikin Altherma heat pump systems. The software works with following assumptions. - A detailed study to calculate the heat load should be made. The heat load of the house is a crucial input in the software. Miscalculating the heat load will lead to badly dimensioned heat pump systems with a reduced efficiency. Calculating the heat load cannot be done with the simulation software. - The software uses climatological data, which has been measured and averaged over a number of years. Real conditions will differ from these averaged values. - The simulation is based on the assumption that heating is required 24h/24h. The daytime capacity is calculated in function of ambient temperature and design heat load. The nighttime capacity (night setback) is calculated in function of ambient temperature and fraction of design heat load, for which this fraction is defined as required indoor night temperature divided by 69.8 F. - Eurelectric provides the CO2 emissions per kwh electricity for every country. If Eurelectric does not give a value, the software uses an average value of lbs/kwh instead. Personalising the input data: Under 'Preferences', following input data should be reviewed for every new simulation. - Minimum ambient temperature at which the heating capacity is 0 BTU/h. - Prices for gas, fuel and electricity (including day and night price period) used for comparison. - Day and night period for design room temperature, including night setback temperature. Efficiencies of gas and oil boilers: The efficiency values for gas and oil boilers used for comparative calculations are adjustable under 'Preferences'. The default efficiencies are chosen to reflect the minimum requirements of the European Boiler Efficiency Directive 92/42/EC for low temperature boilers. Domestic warm water production: The Daikin Altherma system can optionally be combined with a sanitary warm water tank for the preparation of domestic warm water. The type of tank and its capacity can be selected in the simulation for the investment cost calculation. Cooling mode: The reversible version of the Low Temperature Daikin Altherma system can provide cooling. The energy consumption for cooling is included in the energy and cost calculations when a reversible system is selected and cooling operation requirements and design parameters/conditions are defined. Page 12

13 2.8. Field Settings Report 1st code 2nd code 0 User permission level Setting name Date (*) Value (*) Date (*) Value (*) Default value Range Step Unit 00 User permission level 3 2/3 1-1 Weather dependent set point 00 Low ambient temperature (Lo_A) ~ F 01 High ambient temperature (Hi_A) ~ F 02 Set point at low ambient temperature (Lo_TI) ~ F 03 Set point at high ambient temperature (Hi_TI) ~ F 05 Weather dependent for cooling function enable/disable 0 (OFF) 0/ Low ambient temperature (Lo2_A) ~ F 07 High ambient temperature (Hi2_A) ~ F 08 Set point at low ambient temperature (Lo2_TI) ~ F 09 Set point at high ambient temperature (Hi2_TI) ~ F 2 Disinfection function 00 Operation interval Fri Mon~Sun, All Status 1 (ON) 1 (ON) 0/ Start time 23:00 0:00~23:00 1:00 hour 03 Set point ~176 9 F 04 Interval 10 5~60 5 min 3 Auto restart 00 Status 0 (ON) 0 (ON) 0/ Backup/booster heater operation and space heating off temperature 00 Backup heater operation 1 (ON) 1 (ON) 0/ Backup/booster heater priority 0 (OFF) 0 (OFF) 0/1/ Space heating off temperature ~ F 03 Booster heater operation 3 0/1/2/3/ Not applicable Not applicable Backup heater emergency operation 1 (enabled) 07 Backup heater second step 1 (enabled) 5 Equilibrium/Balanced temperature and space heating priority temperature 0/1 1-0/ Equilibrium/Balanced temperature status 1 (ON) 1 (ON) 0/ Equilibrium/Balanced temperature ~ F 02 Space heating priority status 1 (ON) 0/ Space heating priority temperatures 32 5~ F 04 Set point correction for domestic hot water temperature ~ F 6 DT for heat pump domestic water heating mode 00 Start ~ F 01 Stop ~ F Scheduled storage and reheat domestic water heating (a) 03 Scheduled time storage 1 (ON) 0/ Scheduled time storage start time 1:00 0:00~23:00 1:00 hour 05 Scheduled time reheat or continuous reheat 0 (OFF) 0/1/ Scheduled time reheat start time 15:00 0:00~23:00 1:00 hour 07 Domestic hot water reheat set point 81 54~ F 08 Domestic hot water reheat set point hysteresis ~ F 7 DT for booster heater and dual set point control 00 Domestic hot water step length ~ F 01 Hysteresis value booster heater ~ F 02 Dual set point control status 0 (OFF) 0/ Second set point heating ~43.2 / 45~ F 04 Second set point cooling ~ F 8 Domestic hot water heating mode timer Page 13

14 1st code 2nd code Setting name Date (*) Value (*) Date (*) Value (*) Default value Range Step Unit 00 Minimum running time 5 5 0~20 1 min 01 Maximum running time ~95 5 min 02 Anti-recycling time 3 3 0~ hour 03 Booster heater delay time ~95 5 min 04 Additional running time at [4-02]/[F-01] 95 0~95 5 min 9 Heating and cooling set point ranges C D E F 00 Heating set point upper limit ~ F 01 Heating set point lower limit ~ F 02 Cooling set point upper limit ~ F 03 Cooling set point lower limit ~ F 04 Overshoot setting (b) ~ F Automatic set back function 05 Set back operation 0 (OFF) 0/ Set back operation start time 23:00 0:00~23:00 1:00 hour 07 Set back operation stop time 5:00 0:00~23:00 1:00 hour 08 Leaving water set back value 3.6 0~ F Setup on EKRP1HB digital I/O PCB 00 Solar priority mode setting 0 0/ Alarm output logic 0 0/ X1-X2 function. Bivalent operation status 0 0/ Bivalent ON temperature 32-13~ F 04 Bivalent hysteresis ~ F 05 Not applicable Benefit kwh rate power supply/local shift value weather dependent 00 Switching off heaters 0 0/1/2/ Unit connection to benefit kwh rate power supply 0 (OFF) 0/1/ Not applicable. Do not change the default value (OFF) Local shift value weather dependent 0 (OFF) 0/1/2/3/ Confirm option setting 1 0 0/ Pump operation forced off or permitted during backup heater is forced off at benefit kwh rate power supply ([D-00]=0 or 1) 0 (forced off) 0/ Not applicable Unit information readout 00 Software version Read only EEPROM version Read only Unit model identification (b) - EKCBX008BBV / EKCBH008BBV / Liquid refrigerant temperature Read only F 04 Inlet water temperature Read only F Option setup 00 Pump operation stop 0 (enabled) 0/ Space cooling permission temperature 68 50~ F 02 Bottom plate heater ON temperature ~ F 03 Bottom plate heater hysteresis ~ F 04 Functionality of X14A (b) 1 0/1 - - Underfloor heating screed dry-out program 05 Action number selection 1 1~ Heating set point of selected action number [F-05] 77 (c) 59~ F 07 Time of selected action number [F-05] 0 (c) 0~72 12 hour 08 Underfloor heating screed dry-out program enabled/disabled 0 (OFF) 0/ Latest action number executed 0 0~21 (Read only) (*) Installer setting at variance with default value. (a) The storage and reheat function is only applicable in case [4-03]=4. (b) Only possible to modify the first 3 minutes after power ON. (c) For all action numbers of [F-05]. 0 - Page 14

15 Note: The preferred settings of your Daikin Altherma system are mentioned in field settings report. For more details see installation manual. Page 15

16 Information Form for Customers Guidance for purchasing a heat pump - information form for customers - Warning! Read before purchasing Efficient operation of this heat pump will only be ensured if the system is correctly matched to the heat loss of the building and climate zone in which it is installed! Always consult a competent installer and ask them to complete this form before purchasing! This form should be completed by a qualified installer to provide you with information and recommendations about the most suitable heat pump system for your home. In this way you will obtain the benefits of the very high efficiency of heat pumps which concentrate the heat stored in the air, ground or water. Some systems are also reversible and can produce cooling through extracting heat and ejecting it to the immediate surroundings. Some systems may also provide hot water for sanitary use. Heat pumps can be selected which can be used with most distribution systems including radiators, warm air and under floor heating, and can be retrofitted to most existing heating systems with some suitable precautions as set out below. Reducing heat loss and solar gain of buildings If your dwelling is more than 10 years old, before choosing a heat pump, it may be cost effective to first improve your insulation, to reduce heat loss for heating you building or heat gain if you are looking to cool it. (It is actually more efficient to fit a smaller heat pump in a well insulated building, for example) If you accept the installer s recommendations for improving insulation, the heat pump you buy should then be sized appropriately. For further information on reducing heat loss or solar gain and sizing and installing heat pumps systems consult Page 16

17 Customer name... Address... Building type: detached / semi-detached / terraced / apartment Approximate year built: Description of existing heating system / building Fuel type Existing distribution system Minimum design temperature for heating of current system ( F) Heat loss of building in current state (BTU/h) Maximum design temperature for cooling of current system ( F) Potential solar heat gain of building in current state (BTU/h) oil / mains gas / direct electricity / coal / bottled gas / other radiators / warm air / under floor heating / other 2. Recommendations for upgrading building insulation Measures for reducing heat loss Reduced heat loss (BTU/h) Measures for reducing solar gain Reduced solar gain (BTU/h) 3. Primary heating Heat pump manufacturer Daikin Model ERLQ054BAVJU Heat source air Distribution medium Refrigerant R410A Heat capacity (BTU/h) Heat output / electricity input 4.2 Seasonal efficiency over year 2.9 Capable of supplying domestic hot water? Yes Auxiliary heating Type EKHBX054BA3VJU Heat capacity (kw) 3.0 Cooling (if required) Cooling capacity (BTU/h) Cold output / electricity input Annual demands and emissions Renewable energy (kwh) Energy consumption (kwh) 6964 Carbon dioxide emissions (tonnes CO2) 2.5 Carbon dioxide savings (%) 66 Installer signature... Qualifications... Company... Address... Date... Page 17

18 Information Form for Installers Guidance for installing a heat pump - information form for installers - Warning! Read before purchasing Efficient operation of this heat pump requires a competent installer to design the heating system to match the heat loss of the building and climate zone and to install the system in accord with the manufacturers instructions. Heat pumps have a very high efficiency because they only use energy to concentrate the heat present in the ground, water or air. Some models can also operate in reverse mode and produce cooling by rejecting heat from a dwelling. The information contained in this form will enable you to ensure that the benefits of the heat pump unit are carried over to the collector and distribution systems and to complete the form which shall be given to the customer to explain your choice. 1. Minimum information to be supplied by the manufacturer Manufacturer Daikin Model ERLQ054BAVJU Heat collector Brazed plate heat exchanger Heat distribution medium Heating capacity (BTU/h) Cooling capacity (BTU/h) Hot water supply Yes Refrigerant type R410A / GWP = 1975 Noise level (dba) 53 Parts available from date of sale (years) 10 Coefficient of performance (heating) 4.2 Specifying inlet and outlet temperatures ( F) LWC=89.4 (DT=9.0) Energy efficiency ratio (cooling) 8.7 Specifying inlet and outlet temperatures ( F) LWE=64.4 (DT=9.0) For retrofitting to existing heating systems, the heat pump should be selected to match the existing distribution system which may be ducted warm air, hot water via radiators or underfloor heating. As the outlet temperature may be lower than that of the boiler it will replace, it is essential to identify ways of reducing the heat loss or solar gain in order to maintain the same size of distribution system. Definitions Coefficient of performance (COP) is the ratio of heat output to electricity input for a specified source and output temperature. Energy efficiency ratio (EER) is the ratio of cold output to electricity input for a specified source and output temperature. Seasonal coefficient of performance (SCOP) is the coefficient of performance averaged over the length of the heating season for the heat pump system at a specified location. Annualized energy efficiency ratio (SEER) is the energy efficiency ratio averaged over the length of the cooling season for the heat pump system at a specified location. Page 18

19 The primary energy ratio (PER) is given by: COP 0,40 (or COP/2,5) for heat pumps with electrically driven compressors and by COP 0,91 (or COP/1,1) for heat pumps with gas driven compressors, where 0,40 is the current European average electricity power generation efficiency including grid losses and 0,91 is the current European average gas efficiency including distribution losses. The manufacturer shall provide programs, tools and guidelines to help you perform the following calculations. Climatic data should be appropriate for the geographical location of the building. 2. Reducing the heat loss and solar gain of buildings If the dwelling is more than 10 years old, then it will probably be cost effective to reduce the heat loss by increasing the insulation level and to reduce the solar gain by restricting the direct rays of the sun during the summer. If the customer accepts your recommendations then the system should be sized for the reduced heat loss and solar gain. For further information on reducing heat loss or solar gain and sizing and installing heat pumps systems consult 3. Heat loss and sizing of the heating system The heat loss of the building shall be calculated in accordance with national practice or using a suitable validated computer program based on EN 12831, the Euronorm for calculating heat loss. This heat loss should then be compared with the current values required by building codes. For existing buildings, it is generally cost effective to bring the insulation standard closer to current values before sizing the heat pump for the reduced heat loss. Seasonal performance factor and energy consumption for heating The calculation shall consider: - climate (outdoor air temperature), - design outdoor temperature, - the variation of the ground-temperature over a year (for ground-source heat pumps, both with vertical and horizontal collectors), - desired temperature indoors, - temperature level of hydronic heating systems, - annual energy demand for space heating, - annual energy demand for domestic hot water (if applicable), Primary Energy Ratio (PER) and Annual CO2 emissions The average efficiency for power/gas generation as well as electric grid/gas distribution losses to be used in the calculation. CO2 emissions and savings to be calculated based on the primary energy usage. 4. Solar gain and sizing of the cooling system If the system can also produce cooling then the solar gain of the building shall be calculated in accordance with national practice or using a validated computer program. This gain should then be compared with the current values required by building codes. For existing buildings, it is generally cost effective to reduce the solar gain before sizing the heat pump for the reduced solar gain. Annualized energy efficiency ratio and energy consumption for cooling The calculation shall consider: - climate (outdoor air temperature), - design outdoor temperature, - the variation of the ground-temperature over a year (for ground-source heat pumps, both with vertical and horizontal collectors), - desired temperature indoors, Page 19

20 - temperature level of hydronic heating systems, - annual energy demand for space cooling. Primary Energy Ratio (PER) and Annual CO2 emissions The average efficiency for power/gas generation as well as electric grid/gas distribution losses to be used in the calculation. CO2 emissions and savings to be calculated based on the primary energy usage. 5. Training for installers and drillers Suitable courses are available in most Member States to enable installers to obtain appropriate national or European accredited qualifications. Manufacturers shall either organise their own courses to assist installers with using their equipment or work with local training institutes to provide such information as part of their courses. For ground source heat pumps where a vertical bore hole is required, suitable courses for drillers are available in some Member States. Page 20

21 3. Low temp - Outdoor/indoor ERLQ030BAVJU 3.1. Material List Model Qty Description ERLQ030BAVJU 1 Outdoor EKHBX030BA6VJU 1 Indoor EKHWS050BA3VJU 1 Domestic hot water tank EKHBDP 1 Condensate Kit (for EKHBX Cooling Mode) - Altherma DACA-HBA-2 1 1" BSPT (F) to 1" NPT Adaptor (M) - Inlet/Outlet (EKHB_030) DACA-THXA-1 1 3/4" BSPP (M) to 1" NPT Adaptor (F) - DHW Inlet/Outlet (EKHWS) DACA-3WVTA-1 1 1" BSPT (M) to 1-1/4" NPT (F) Adaptor - 3-Way Valve (EKHWS) DACA-3WVTH-1 1 1" BSPT (M) to 1" NPT (F) Adaptor - 3-Way Valve Hot Water (EKHWS) DACA-DHWTA-1 1 3/4" BSPP (M) to 3/4" NPT (F) Adaptor - Cold Inlet/Hot Outlet (EKHWS) Page 21

22 3.2. Selection Criteria Location Country USA Vermont City Rutland State * Design conditions Conditioned surface Required capacity for space heating at min. night temp. Required capacity for space cooling at max. day temp. Application System layout Hydrobox placement Leaving water temperature range heating Leaving water temperature range cooling Power supply 1400 sqft BTU/h BTU/h Heat pump Low temp - Outdoor/indoor Wall mounted 86.0 F F 41.0 F F 230V 1ph Domestic hot water Solar connection Material inside Tank type Volume Power supply No Stainless steel Standard tank 53 gal 230V 1ph Page 22

23 3.3. System Diagram Domestic hot w ater tank EKHWS050BA 3V JU 53 gal Domestic hot water usage Heating & cooling Outdoor ERLQ 030BA V JU Indoor EKHBX030BA 6V JU 230V 1ph R410A Space heating/cooling 230V 1ph 230V 1ph Page 23

24 3.4. Technical Details Indoor EKHBX030BA6VJU Application Function Reversible Application Low temperature Leaving water range heating F Leaving water range cooling F Technical data Dimensions (WxHxD) 19.8x36.3x14.2 inch Weight 143lbs Drain connection 0.7inch Material Epoxy polyester painted galvanized steel Electrical data Power supply 230V 1ph Fuse size 30A Capacity electric backup heater 6.0 kw Capacity steps 2 Domestic hot water tank Technical data Water volume Max. water temperature Material inside tank Material outside tank Dimensions (WxHxD) Weight Electrical data Electric heater Power supply Fuse size EKHWS050BA3VJU 53 gal F Stainless steel Epoxy-Coated Mild Steel 22.8x45.3x22.8 inch 99lbs BTU/h 230V 1ph 20A Outdoor ERLQ030BAVJU Performance Nominal heating capacity BTU/h COP 4.0 Operation range heating F Nominal cooling capacity BTU/h EER 9.3 Operation range cooling F Technical data Dimensions (WxHxD) 32.5x28.9x11.8 inch Weight 123lbs Refrigerant R410A Base charge 3.7lbs Sound data Sound pressure 49dBA Sound power Electrical data Power supply 230V 1ph Fuse size 20A Page 24

25 3.5. Energy Consumption of the Domestic Hot Water Tank Type of usage Hot water consumption Water temperature Volume per day at F Occurrences per day Small 0.8 gal F 12.7 gal 16 Floor 0.8 gal F 0.8 gal 1 Clean 0.5 gal F 1.6 gal 2 Small dishwash 1.6 gal F 2.4 gal 1 Medium dishwash 2.1 gal F 0.0 gal 0 Larger dishwash 3.7 gal F 5.5 gal 1 Large 4.0 gal F 0.0 gal 0 Shower 10.6 gal F 21.1 gal 2 Bath 27.2 gal F 0.0 gal 0 Total per day at F 44.1 gal 5.8 kwh Actual total thermal energy consumption per year = 2126 kwh. Actual total electricity consumption per year = 886 kwh. COP calculations for DHW heating. The COP used in the energy calculation is based on the FprEN16147 (replaces the former pren255-3) large tapping pattern at a standard temp set of F for preparation of DHW and avoiding the use of booster heater. Page 25

26 3.6. Graphs Operation period Temperature ( F) Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Heating period 0 heating cap. above C ooling period 0 cooling cap. below Month Location Country USA Vermont City Rutland State * Temperatures (min / max) Summer Day 77.4 / 84.4 F Summer Night 63.3 / 70.3 F Winter Day 31.8 / 53.8 F Winter Night -4.0 / 10.0 F The graph shows the simulated outdoor temperature variations within the defined heating months. For heat pumps the graph also shows the temperatures in the cooling months. Page 26

27 Heating energy cost Heating energy cost (dollars) ERLQ 030BA V JU Gas boiler F uel boiler Electric heating Electricity normal tariff High price period 0.15 dollars/kwh Low price period 0.15 dollars/kwh Electricity heat pump tariff High price period 0.15 dollars/kwh Low price period 0.15 dollars/kwh Electricity Direct heater efficiency 100% Connection cost 0 dollars Gas Tariff dollars/thm Efficiency 80% Connection cost 0 dollars Fuel Tariff dollars/gal Efficiency 80% Design conditions Conditioned surface 1400 sqft Required capacity for space heating at min. night temp BTU/h Zero heating capacity at outside temperature 60.0 F The graph shows a comparison of the simulated annual running costs for Daikin Altherma, a gas boiler and an oil boiler. The calculation is based upon the selected buildings yearly required thermal input, each systems coefficient of performance (without pump) and the inputted energy prices. Page 27

28 Heating CO2 emission Heating C O 2 emission (x1000 lbs/y ear) ERLQ 030BA V JU Gas boiler Fuel boiler Electric heating Location Country USA Vermont Electricity Heating CO2 emission lbs/kwh Direct heater efficiency 100% Gas Heating CO2 emission lbs/kwh Efficiency 80% Fuel Heating CO2 emission lbs/kwh Efficiency 80% Design conditions Conditioned surface 1400 sqft Required capacity for space heating at min. night temp BTU/h Zero heating capacity at outside temperature 60.0 F The graph shows a comparison of the annual CO2 emissions for Daikin Altherma, an electric heating system, a gas boiler and an oil boiler sized to cover the yearly heat load for the simulated building. Neither Daikin Altherma nor the electric heater will have any direct emissions. The emission from these systems is based on calculations according to the average CO2 emission from the selected country's electricity production. Page 28

29 Energy consumption per month Energy consumption (kwh) Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Heat pump high price period: 6572 kwh / 74.8% (heating) Heat pump low price period: / 0.0% (heating) Heater high price period: 2214 kwh / 25.2% Heater low price period: / 0.0% Heat pump high price period: 746 kwh / 100.0% (cooling) Heat pump low price period: / 0.0% (cooling) Month Yearly energy consumption (heating) 8785 kwh Primary energy use (heating) kwh Yearly energy consumption (cooling) 746 kwh Primary energy use (cooling) 1866 kwh Yearly energy consumption (heat/cool) 9532 kwh Primary energy use (heat/cool) kwh Electricity normal tariff High price period 0.15 dollars/kwh Low price period 0.15 dollars/kwh Electricity heat pump tariff High price period 0.15 dollars/kwh Low price period 0.15 dollars/kwh Design conditions Conditioned surface 1400 sqft Required capacity for space heating at min. night temp BTU/h Zero heating capacity at outside temperature 60.0 F Required capacity for space cooling at max. day temp BTU/h Zero cooling capacity at outside temperature 72.0 F The graph shows the energy consumption (input) per month for the heat pump and back up heater. There is made a separation between day and night operation to show the amount of energy consumption that falls under day and night tariff. Page 29

30 Energy cost per month Energy cost (dollars) Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Heating C ooling Month Total cost for year (heating) 1318 dollars Total cost for year (cooling) 112 dollars Total cost for year (heat/cool) 1430 dollars Electricity normal tariff High price period 0.15 dollars/kwh Low price period 0.15 dollars/kwh Electricity heat pump tariff High price period 0.15 dollars/kwh Low price period 0.15 dollars/kwh Design conditions Conditioned surface 1400 sqft Required capacity for space heating at min. night temp BTU/h Zero heating capacity at outside temperature 60.0 F Required capacity for space cooling at max. day temp BTU/h Zero cooling capacity at outside temperature 72.0 F The graph shows the running cost per month for Daikin Altherma according to the inputted electricity prices and the power input as given in the graph "energy consumption per month". Page 30

31 3.7. Supplementary Explanations Design conditions: The Daikin Altherma simulation software is a static calculation tool, which can be used as an indication for dimensioning Daikin Altherma heat pump systems. The software works with following assumptions. - A detailed study to calculate the heat load should be made. The heat load of the house is a crucial input in the software. Miscalculating the heat load will lead to badly dimensioned heat pump systems with a reduced efficiency. Calculating the heat load cannot be done with the simulation software. - The software uses climatological data, which has been measured and averaged over a number of years. Real conditions will differ from these averaged values. - The simulation is based on the assumption that heating is required 24h/24h. The daytime capacity is calculated in function of ambient temperature and design heat load. The nighttime capacity (night setback) is calculated in function of ambient temperature and fraction of design heat load, for which this fraction is defined as required indoor night temperature divided by 69.8 F. - Eurelectric provides the CO2 emissions per kwh electricity for every country. If Eurelectric does not give a value, the software uses an average value of lbs/kwh instead. Personalising the input data: Under 'Preferences', following input data should be reviewed for every new simulation. - Minimum ambient temperature at which the heating capacity is 0 BTU/h. - Prices for gas, fuel and electricity (including day and night price period) used for comparison. - Day and night period for design room temperature, including night setback temperature. Efficiencies of gas and oil boilers: The efficiency values for gas and oil boilers used for comparative calculations are adjustable under 'Preferences'. The default efficiencies are chosen to reflect the minimum requirements of the European Boiler Efficiency Directive 92/42/EC for low temperature boilers. Domestic warm water production: The Daikin Altherma system can optionally be combined with a sanitary warm water tank for the preparation of domestic warm water. The type of tank and its capacity can be selected in the simulation for the investment cost calculation. Cooling mode: The reversible version of the Low Temperature Daikin Altherma system can provide cooling. The energy consumption for cooling is included in the energy and cost calculations when a reversible system is selected and cooling operation requirements and design parameters/conditions are defined. Page 31

32 3.8. Field Settings Report 1st code 2nd code 0 User permission level Setting name Date (*) Value (*) Date (*) Value (*) Default value Range Step Unit 00 User permission level 3 2/3 1-1 Weather dependent set point 00 Low ambient temperature (Lo_A) ~ F 01 High ambient temperature (Hi_A) ~ F 02 Set point at low ambient temperature (Lo_TI) ~ F 03 Set point at high ambient temperature (Hi_TI) ~ F 05 Weather dependent for cooling function enable/disable 0 (OFF) 0/ Low ambient temperature (Lo2_A) ~ F 07 High ambient temperature (Hi2_A) ~ F 08 Set point at low ambient temperature (Lo2_TI) ~ F 09 Set point at high ambient temperature (Hi2_TI) ~ F 2 Disinfection function 00 Operation interval Fri Mon~Sun, All Status 1 (ON) 1 (ON) 0/ Start time 23:00 0:00~23:00 1:00 hour 03 Set point ~176 9 F 04 Interval 10 5~60 5 min 3 Auto restart 00 Status 0 (ON) 0 (ON) 0/ Backup/booster heater operation and space heating off temperature 00 Backup heater operation 1 (ON) 1 (ON) 0/ Backup/booster heater priority 0 (OFF) 0 (OFF) 0/1/ Space heating off temperature ~ F 03 Booster heater operation 3 0/1/2/3/ Not applicable Not applicable Backup heater emergency operation 1 (enabled) 07 Backup heater second step 1 (enabled) 5 Equilibrium/Balanced temperature and space heating priority temperature 0/1 1-0/ Equilibrium/Balanced temperature status 1 (ON) 1 (ON) 0/ Equilibrium/Balanced temperature ~ F 02 Space heating priority status 1 (ON) 0/ Space heating priority temperatures 32 5~ F 04 Set point correction for domestic hot water temperature ~ F 6 DT for heat pump domestic water heating mode 00 Start ~ F 01 Stop ~ F Scheduled storage and reheat domestic water heating (a) 03 Scheduled time storage 1 (ON) 0/ Scheduled time storage start time 1:00 0:00~23:00 1:00 hour 05 Scheduled time reheat or continuous reheat 0 (OFF) 0/1/ Scheduled time reheat start time 15:00 0:00~23:00 1:00 hour 07 Domestic hot water reheat set point 81 54~ F 08 Domestic hot water reheat set point hysteresis ~ F 7 DT for booster heater and dual set point control 00 Domestic hot water step length ~ F 01 Hysteresis value booster heater ~ F 02 Dual set point control status 0 (OFF) 0/ Second set point heating ~43.2 / 45~ F 04 Second set point cooling ~ F 8 Domestic hot water heating mode timer Page 32

33 1st code 2nd code Setting name Date (*) Value (*) Date (*) Value (*) Default value Range Step Unit 00 Minimum running time 5 5 0~20 1 min 01 Maximum running time ~95 5 min 02 Anti-recycling time 3 3 0~ hour 03 Booster heater delay time ~95 5 min 04 Additional running time at [4-02]/[F-01] 95 0~95 5 min 9 Heating and cooling set point ranges C D E F 00 Heating set point upper limit ~ F 01 Heating set point lower limit ~ F 02 Cooling set point upper limit ~ F 03 Cooling set point lower limit ~ F 04 Overshoot setting (b) ~ F Automatic set back function 05 Set back operation 0 (OFF) 0/ Set back operation start time 23:00 0:00~23:00 1:00 hour 07 Set back operation stop time 5:00 0:00~23:00 1:00 hour 08 Leaving water set back value 3.6 0~ F Setup on EKRP1HB digital I/O PCB 00 Solar priority mode setting 0 0/ Alarm output logic 0 0/ X1-X2 function. Bivalent operation status 0 0/ Bivalent ON temperature 32-13~ F 04 Bivalent hysteresis ~ F 05 Not applicable Benefit kwh rate power supply/local shift value weather dependent 00 Switching off heaters 0 0/1/2/ Unit connection to benefit kwh rate power supply 0 (OFF) 0/1/ Not applicable. Do not change the default value (OFF) Local shift value weather dependent 0 (OFF) 0/1/2/3/ Confirm option setting 1 0 0/ Pump operation forced off or permitted during backup heater is forced off at benefit kwh rate power supply ([D-00]=0 or 1) 0 (forced off) 0/ Not applicable Unit information readout 00 Software version Read only EEPROM version Read only Unit model identification (b) - EKCBX008BBV / EKCBH008BBV / Liquid refrigerant temperature Read only F 04 Inlet water temperature Read only F Option setup 00 Pump operation stop 0 (enabled) 0/ Space cooling permission temperature 68 50~ F 02 Bottom plate heater ON temperature ~ F 03 Bottom plate heater hysteresis ~ F 04 Functionality of X14A (b) 1 0/1 - - Underfloor heating screed dry-out program 05 Action number selection 1 1~ Heating set point of selected action number [F-05] 77 (c) 59~ F 07 Time of selected action number [F-05] 0 (c) 0~72 12 hour 08 Underfloor heating screed dry-out program enabled/disabled 0 (OFF) 0/ Latest action number executed 0 0~21 (Read only) (*) Installer setting at variance with default value. (a) The storage and reheat function is only applicable in case [4-03]=4. (b) Only possible to modify the first 3 minutes after power ON. (c) For all action numbers of [F-05]. 0 - Page 33

34 Note: The preferred settings of your Daikin Altherma system are mentioned in field settings report. For more details see installation manual. Page 34

35 Information Form for Customers Guidance for purchasing a heat pump - information form for customers - Warning! Read before purchasing Efficient operation of this heat pump will only be ensured if the system is correctly matched to the heat loss of the building and climate zone in which it is installed! Always consult a competent installer and ask them to complete this form before purchasing! This form should be completed by a qualified installer to provide you with information and recommendations about the most suitable heat pump system for your home. In this way you will obtain the benefits of the very high efficiency of heat pumps which concentrate the heat stored in the air, ground or water. Some systems are also reversible and can produce cooling through extracting heat and ejecting it to the immediate surroundings. Some systems may also provide hot water for sanitary use. Heat pumps can be selected which can be used with most distribution systems including radiators, warm air and under floor heating, and can be retrofitted to most existing heating systems with some suitable precautions as set out below. Reducing heat loss and solar gain of buildings If your dwelling is more than 10 years old, before choosing a heat pump, it may be cost effective to first improve your insulation, to reduce heat loss for heating you building or heat gain if you are looking to cool it. (It is actually more efficient to fit a smaller heat pump in a well insulated building, for example) If you accept the installer s recommendations for improving insulation, the heat pump you buy should then be sized appropriately. For further information on reducing heat loss or solar gain and sizing and installing heat pumps systems consult Page 35

36 Customer name... Address... Building type: detached / semi-detached / terraced / apartment Approximate year built: Description of existing heating system / building Fuel type Existing distribution system Minimum design temperature for heating of current system ( F) Heat loss of building in current state (BTU/h) Maximum design temperature for cooling of current system ( F) Potential solar heat gain of building in current state (BTU/h) oil / mains gas / direct electricity / coal / bottled gas / other radiators / warm air / under floor heating / other 2. Recommendations for upgrading building insulation Measures for reducing heat loss Reduced heat loss (BTU/h) Measures for reducing solar gain Reduced solar gain (BTU/h) 3. Primary heating Heat pump manufacturer Daikin Model ERLQ030BAVJU Heat source air Distribution medium Refrigerant R410A Heat capacity (BTU/h) Heat output / electricity input 4.0 Seasonal efficiency over year 2.2 Capable of supplying domestic hot water? Yes Auxiliary heating Type EKHBX030BA6VJU Heat capacity (kw) 6.0 Cooling (if required) Cooling capacity (BTU/h) Cold output / electricity input Annual demands and emissions Renewable energy (kwh) Energy consumption (kwh) 8785 Carbon dioxide emissions (tonnes CO2) 3.1 Carbon dioxide savings (%) 55 Installer signature... Qualifications... Company... Address... Date... Page 36

37 Information Form for Installers Guidance for installing a heat pump - information form for installers - Warning! Read before purchasing Efficient operation of this heat pump requires a competent installer to design the heating system to match the heat loss of the building and climate zone and to install the system in accord with the manufacturers instructions. Heat pumps have a very high efficiency because they only use energy to concentrate the heat present in the ground, water or air. Some models can also operate in reverse mode and produce cooling by rejecting heat from a dwelling. The information contained in this form will enable you to ensure that the benefits of the heat pump unit are carried over to the collector and distribution systems and to complete the form which shall be given to the customer to explain your choice. 1. Minimum information to be supplied by the manufacturer Manufacturer Daikin Model ERLQ030BAVJU Heat collector Brazed plate heat exchanger Heat distribution medium Heating capacity (BTU/h) Cooling capacity (BTU/h) Hot water supply Yes Refrigerant type R410A / GWP = 1975 Noise level (dba) 49 Parts available from date of sale (years) 10 Coefficient of performance (heating) 4.0 Specifying inlet and outlet temperatures ( F) LWC=94.2 (DT=9.0) Energy efficiency ratio (cooling) 9.3 Specifying inlet and outlet temperatures ( F) LWE=64.4 (DT=9.0) For retrofitting to existing heating systems, the heat pump should be selected to match the existing distribution system which may be ducted warm air, hot water via radiators or underfloor heating. As the outlet temperature may be lower than that of the boiler it will replace, it is essential to identify ways of reducing the heat loss or solar gain in order to maintain the same size of distribution system. Definitions Coefficient of performance (COP) is the ratio of heat output to electricity input for a specified source and output temperature. Energy efficiency ratio (EER) is the ratio of cold output to electricity input for a specified source and output temperature. Seasonal coefficient of performance (SCOP) is the coefficient of performance averaged over the length of the heating season for the heat pump system at a specified location. Annualized energy efficiency ratio (SEER) is the energy efficiency ratio averaged over the length of the cooling season for the heat pump system at a specified location. Page 37

38 The primary energy ratio (PER) is given by: COP 0,40 (or COP/2,5) for heat pumps with electrically driven compressors and by COP 0,91 (or COP/1,1) for heat pumps with gas driven compressors, where 0,40 is the current European average electricity power generation efficiency including grid losses and 0,91 is the current European average gas efficiency including distribution losses. The manufacturer shall provide programs, tools and guidelines to help you perform the following calculations. Climatic data should be appropriate for the geographical location of the building. 2. Reducing the heat loss and solar gain of buildings If the dwelling is more than 10 years old, then it will probably be cost effective to reduce the heat loss by increasing the insulation level and to reduce the solar gain by restricting the direct rays of the sun during the summer. If the customer accepts your recommendations then the system should be sized for the reduced heat loss and solar gain. For further information on reducing heat loss or solar gain and sizing and installing heat pumps systems consult 3. Heat loss and sizing of the heating system The heat loss of the building shall be calculated in accordance with national practice or using a suitable validated computer program based on EN 12831, the Euronorm for calculating heat loss. This heat loss should then be compared with the current values required by building codes. For existing buildings, it is generally cost effective to bring the insulation standard closer to current values before sizing the heat pump for the reduced heat loss. Seasonal performance factor and energy consumption for heating The calculation shall consider: - climate (outdoor air temperature), - design outdoor temperature, - the variation of the ground-temperature over a year (for ground-source heat pumps, both with vertical and horizontal collectors), - desired temperature indoors, - temperature level of hydronic heating systems, - annual energy demand for space heating, - annual energy demand for domestic hot water (if applicable), Primary Energy Ratio (PER) and Annual CO2 emissions The average efficiency for power/gas generation as well as electric grid/gas distribution losses to be used in the calculation. CO2 emissions and savings to be calculated based on the primary energy usage. 4. Solar gain and sizing of the cooling system If the system can also produce cooling then the solar gain of the building shall be calculated in accordance with national practice or using a validated computer program. This gain should then be compared with the current values required by building codes. For existing buildings, it is generally cost effective to reduce the solar gain before sizing the heat pump for the reduced solar gain. Annualized energy efficiency ratio and energy consumption for cooling The calculation shall consider: - climate (outdoor air temperature), - design outdoor temperature, - the variation of the ground-temperature over a year (for ground-source heat pumps, both with vertical and horizontal collectors), - desired temperature indoors, Page 38

Daikin Altherma hybrid heat pump. The natural combination

Daikin Altherma hybrid heat pump. The natural combination Daikin Altherma hybrid heat pump The natural combination Daikin Altherma hybrid heat pump, the natural combination Why choose Daikin Altherma hybrid heat pump? What the customer wants: more energy efficient

More information

The natural ombination

The natural ombination The natural ombination DAIKIN ALTHERMA HYBRID HEAT PUMP 2 A new pportunity in residential heating! There is a growing demand from home owners to replace heating systems, especially replacing of gas boilers,

More information

Daikin Altherma Hybrid Heat Pump

Daikin Altherma Hybrid Heat Pump your comfort. our world. Daikin Altherma Hybrid Heat Pump Smart heating technology for the best of both worlds Heating Integrated Solutions Ventilation Air Conditioning Refrigeration Forward thinking About

More information

Daikin Altherma Hybrid Heat Pump

Daikin Altherma Hybrid Heat Pump Daikin Altherma Hybrid Heat Pump Smart technology for the best of both worlds NATIONAL HEAT PUMP 19 JUNE 2014 ICC BIRMINGHAM WINNER Forward thinking Now is the time to rethink the way we heat our homes

More information

Operation manual. Daikin Altherma hybrid heat pump EHYHBH05AA EHYHBH08AA EHYHBX08AA. Operation manual Daikin Altherma hybrid heat pump.

Operation manual. Daikin Altherma hybrid heat pump EHYHBH05AA EHYHBH08AA EHYHBX08AA. Operation manual Daikin Altherma hybrid heat pump. EHYHBH05AA EHYHBH08AA EHYHBX08AA English Table of contents Table of contents 1 About this document 2 2 About the system 2 2.1 Components in a typical system layout... 2 3 Operation 3 3.1 Overview: Operation...

More information

LG Electronics AE Company, Commercial Air Conditioning

LG Electronics AE Company, Commercial Air Conditioning www.lgeaircon.com New concept Ecofriendly Highefficiency Heating solution Total heating & Hot water Solution for MULTI V LG Electronics AE Company, Commercial Air Conditioning 2 Yeouidodong, Yeongdeungpogu,

More information

Hybrid heat pumps. saving energy and reducing carbon emissions

Hybrid heat pumps. saving energy and reducing carbon emissions Hybrid heat pumps saving energy and reducing carbon emissions Bart Aspeslagh Product planning and new technology manager, Daikin Europe NV. aspeslagh.b@daikineurope.com Stefanie Debaets Design engineer,

More information

The natural ombination

The natural ombination The natural ombination DAikin Altherma Hybrid heat pump system The future is now The new hybrid system Heat pump solution for gas boiler replacement market Daikin Altherma hybrid combines heat pump technology

More information

Daikin Altherma Hybrid Heat Pump

Daikin Altherma Hybrid Heat Pump your comfort. our world. Daikin Altherma Hybrid Heat Pump The natural combination Heating Integrated Solutions Ventilation Air Conditioning Refrigeration About Daikin Forward thinking... Daikin has a worldwide

More information

The natural ombination

The natural ombination The natural ombination DAikin Altherma Hybrid heat pump system HEATING & DOMESTIC HOT WATER end user leaflet 2 The future is now 3 and the future is more eco-friendly, energy efficient and cost conscious.

More information

Operation manual. Daikin Altherma ground source heat pump EGSQH10S18AA9W. Operation manual Daikin Altherma ground source heat pump.

Operation manual. Daikin Altherma ground source heat pump EGSQH10S18AA9W. Operation manual Daikin Altherma ground source heat pump. English Table of contents Table of contents 1 About this document 2 2 About the system 2 2.1 Components in a typical system layout... 2 3 Operation 3 3.1 Overview: Operation... 3 3.2 The user interface

More information

Hot Water. Heat pump water heaters. Residential and Commercial R410a

Hot Water. Heat pump water heaters. Residential and Commercial R410a Hot Water Heat pump water heaters Residential and Commercial R410a Heat pump technology Heat Pump Water Heating is a new idea using existing technology and is viewed as the latest generation of water heating

More information

All-in-one, all year round heating, cooling and domestic hot water supply solution HEAT PUMP INVERTER R-410A

All-in-one, all year round heating, cooling and domestic hot water supply solution HEAT PUMP INVERTER R-410A All-in-one, all year round heating, cooling and domestic hot water supply solution HEAT PUMP INVERTER R-410A HIGH TIME FOR Energy efficient AND CLEVER SOLUTIONS! The climate is changing. The effects are

More information

Operation manual. Daikin Altherma low temperature monobloc EBLQ05CAV3 EBLQ07CAV3 EDLQ05CAV3 EDLQ07CAV3

Operation manual. Daikin Altherma low temperature monobloc EBLQ05CAV3 EBLQ07CAV3 EDLQ05CAV3 EDLQ07CAV3 EBLQ05CAV3 EBLQ07CAV3 EDLQ05CAV3 EDLQ07CAV3 English Table of Contents Table of Contents 1 About this document 2 2 About the system 2 2.1 Components in a typical system layout... 2 3 Operation 3 3.1 Overview:

More information

Daikin Altherma. hybrid heat pump. The natural combination

Daikin Altherma. hybrid heat pump. The natural combination Daikin Altherma hybrid heat pump The natural combination Why choose Daikin? As an industry leader, Daikin combines broad experience, technical innovation and responsive customer service to help you meet

More information

Natural geothermal energy.

Natural geothermal energy. ROTEX ground source heat pump Natural geothermal energy. ROTEX HPU ground the ground source heat pump that heats with free geothermal energy. Compact, environmentally responsible and uniquely efficient.

More information

All-in-one, all year round heating, cooling and domestic hot water supply solution HEAT PUMP INVERTER R-410A

All-in-one, all year round heating, cooling and domestic hot water supply solution HEAT PUMP INVERTER R-410A All-in-one, all year round heating, cooling and domestic hot water supply solution HEAT PUMP INVERTER R-410A Heat pump solution to fit both new build homes and the harder to heat older properties High

More information

ROTEX gas hybrid heat pump. A strong team.

ROTEX gas hybrid heat pump. A strong team. ROTEX gas hybrid heat pump A strong team. The new ROTEX HPU hybrid gas hybrid heat pump always selects the most favourable heating mode automatically. For a long time the general opinion was that a heat

More information

Ecodan Air Source Heat Pump and Flow Temperature Controller 2

Ecodan Air Source Heat Pump and Flow Temperature Controller 2 HOMEOWNER STANDALONE Homeowner Information SEPTEMBER 2011 Ecodan Air Source Heat Pump and Flow Temperature Controller 2 Ecodan Air Source Heat Pump Model Number PUHZ-W50VHA(2)-BS PUHZ-W85VHA(2)-BS PUHZ-HW140VHA(2)-BS

More information

OPERATION MANUAL. Indoor unit and options for air to water heat pump system

OPERATION MANUAL. Indoor unit and options for air to water heat pump system OPERATION MANUAL Indoor unit and options for air to water heat pump system EKHBH016BB3V3 EKHBH016BB6V3 EKHBH016BB6WN EKHBH016BB6T1 EKHBH016BB9WN EKHBH016BB9T1 EKHBX016BB3V3 EKHBX016BB6V3 EKHBX016BB6WN

More information

Sea Water Heat Pump Project

Sea Water Heat Pump Project Sea Water Heat Pump Project Alaska SeaLife Center, Seward, AK Presenter: Andy Baker, PE, YourCleanEnergy LLC Also Present is ASLC Operations Manager: Darryl Schaefermeyer ACEP Rural Energy Conference Forum

More information

INNOVATIVE SOLUTION OF DOMESTIC HEATING SPLIT TYPE SPLIT DHW INTEGRATED TYPE MONOBLOC TYPE

INNOVATIVE SOLUTION OF DOMESTIC HEATING SPLIT TYPE SPLIT DHW INTEGRATED TYPE MONOBLOC TYPE INNOVATIVE SOLUTION OF DOMESTIC HEATING SPLIT TYPE SPLIT DHW INTEGRATED TYPE MONOBLOC TYPE Fujitsu General realizes considerable energy saving operations by the Heat pump heating system using the ambient

More information

INSTALLER CATALOGUE DAIKIN ALTHERMA LOW TEMPERATURE HEAT PUMP

INSTALLER CATALOGUE DAIKIN ALTHERMA LOW TEMPERATURE HEAT PUMP INSTALLER CATALOGUE DAIKIN ALTHERMA LOW TEMPERATURE HEAT PUMP The Daikin Altherma low temperature heat pump, part of an innovative product range, is designed to deliver only the best in climate control:

More information

Professional Report. Map section. Location of the system. Valkkinen Longitude: 23.667 Latitude: 61.267 Elevation: 89 m

Professional Report. Map section. Location of the system. Valkkinen Longitude: 23.667 Latitude: 61.267 Elevation: 89 m Puulämmitys 6 x SF3 Location of the system Map section Valkkinen Longitude: 23.667 Latitude: 61.267 Elevation: 89 m This report has been created by: Samppa Takala Samppa Takala Nyrhintie 14 28760 Pori

More information

HEAT PUMPS A KEY COMPONENT IN LOW CARBON FUTURE

HEAT PUMPS A KEY COMPONENT IN LOW CARBON FUTURE HEAT PUMPS A KEY COMPONENT IN LOW CARBON FUTURE Satish Joshi Managing Director CONTENTS 1. INTRODUCTION, APPLICATIONS 2. TECHNOLOGY, PROJECTS DONE, COST COMPARISION 3. HEAT PUMPS IN THE RENEWABLES DIRECTIVE,

More information

Air-to-water heat pumps: Making the most of renewables. Richard Pickford, Daikin UK

Air-to-water heat pumps: Making the most of renewables. Richard Pickford, Daikin UK Air-to-water heat pumps: Making the most of renewables Richard Pickford, Daikin UK 1 Overview 1. ASHPs potential 2. Heat pump system design 3. Installation best practice 4. Renewable Heat Incentive 5.

More information

New Deluxe Wall Mounted Heat Pump Series EXTERIOS

New Deluxe Wall Mounted Heat Pump Series EXTERIOS New Deluxe Wall Mounted Heat Pump Series EXTERIOS May 2013 New Deluxe Wall Mounted Heat Pump Series Panasonic Adding New Air Conditioner Lineup Setting Another Mile Stone in the US Ductless Split History

More information

Hitachi Air Conditioning. Engineered for tomorrow. Room Air Conditioning GENERAL CATALOGUE

Hitachi Air Conditioning. Engineered for tomorrow. Room Air Conditioning GENERAL CATALOGUE Hitachi Air Conditioning Engineered for tomorrow. Room Air Conditioning GENERAL CATALOGUE Contents Page 04 Product Range 08-09 RAC Summit Wall Mounted 10 RAC Shirokuma Wall mounted 11 RAC S Series - Wall

More information

1116, Suenaga, Takatsu-ku, Kawasaki 213-8502, Japan http://www.fujitsu-general.com/

1116, Suenaga, Takatsu-ku, Kawasaki 213-8502, Japan http://www.fujitsu-general.com/ 1116, Suenaga, Takatsu-ku, Kawasaki 213-8502, Japan http://www.fujitsu-general.com/ ISO 9001 ISO 14001 Certified number : 01 100 89394 Certified number : 01 104 9245101 Fujitsu General (Thailand) Co.,

More information

Information Guide Domestic Air Source Heat Pumps

Information Guide Domestic Air Source Heat Pumps Information Guide Domestic Air Source Heat Pumps Issue 41 Domestic Air Source Heat Pumps This is an independent guide produced by Mitsubishi Electric to enhance the knowledge of its customers and provide

More information

DAikin Altherma low temperature heat pump. end user leaflet

DAikin Altherma low temperature heat pump. end user leaflet DAikin Altherma low temperature heat pump HEATING, COOLING & DOMESTIC HOT WATER end user leaflet 2 The natural choice D 3 in1: heating, cooling and hot water Daikin Altherma is a total heating and domestic

More information

Hybrid. Daikin Altherma. heat pump systems A POWERFUL TOOL TO CONTRIBUTE TO THE 20/20/20-TARGETS

Hybrid. Daikin Altherma. heat pump systems A POWERFUL TOOL TO CONTRIBUTE TO THE 20/20/20-TARGETS Daikin Altherma Hybrid heat pump systems 99 Environmentally friendly 99 Flexible in use 99 Affordable renewable energy SPACE HEATING 600mm NATURAL GAS SUPPLY DOMESTIC HOT WATER A POWERFUL TOOL TO CONTRIBUTE

More information

Delivering exceptional performance and Ecovalue. Ecocent

Delivering exceptional performance and Ecovalue. Ecocent 1 Delivering exceptional performance and Ecovalue. Ecocent 2 The Ecocent Hot Water System As the cost of providing heating and hot water continues to increase, homes and businesses are seeking out more

More information

york air-conditioning products Residential & VRF News 2015

york air-conditioning products Residential & VRF News 2015 york air-conditioning products Residential & VRF News 2015 york air-conditioning products Catalogue Content Split Systems Pag. High wall High Efficiency Inverter YWHJZH 09 to 24 K 6 High wall Inverter

More information

Rainwater Harvesting

Rainwater Harvesting Rainwater Harvesting With climate change now a reality rather than a speculated possibility, the demand on water resources has gone up, whilst the amount of water available for supply has gone down. Forth

More information

Is an air source heat pump the right choice for my home? Important information and key things to consider before installing an air source heat pump

Is an air source heat pump the right choice for my home? Important information and key things to consider before installing an air source heat pump Is an air source heat pump the right choice for my home? Important information and key things to consider before installing an air source heat pump The basics... This guide can help you make an informed

More information

Glossary of Heating, Ventilation and Air Conditioning Terms

Glossary of Heating, Ventilation and Air Conditioning Terms Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment

More information

Direct Fresh Air Free Cooling of Data Centres

Direct Fresh Air Free Cooling of Data Centres White Paper Introduction There have been many different cooling systems deployed in Data Centres in the past to maintain an acceptable environment for the equipment and for Data Centre operatives. The

More information

Time to Rethink Heating

Time to Rethink Heating your comfort. our world. Time to Rethink Heating Daikin Altherma Hybrid heat pump Presented by Stuart Tandy Contents 1. Introducing Daikin 2. The time is right for hybrid 3. Rethink heating 4. How hybrid

More information

Range Tribune HE Solar Unvented Direct and Indirect Cylinders

Range Tribune HE Solar Unvented Direct and Indirect Cylinders Range Tribune HE Solar Unvented Direct and Indirect Cylinders Range Tribune HE Solar cylinders have been designed specifically with Solar applications in mind and are based on the highly successful Range

More information

Renewable Heat Pumps. A guide for the technically minded

Renewable Heat Pumps. A guide for the technically minded Renewable Heat Pumps A guide for the technically minded How do heat pumps work? A heat pump is an environmental energy technology that extracts heat from low temperature sources (air, water, ground), upgrades

More information

The main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building.

The main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building. MSV: Square Footage: 24,844 No. of Floors: 1 Year Built: 1963 Type of Use: Lounge and dining area open all night for snacks Steam Water-cooled condenser, 50-Ton York unit with a 6 cylinder-reciprocating

More information

omfort all-in-one applications for residential & commercial DAIKIN ALTHERMA HEATING CATALOGUE

omfort all-in-one applications for residential & commercial DAIKIN ALTHERMA HEATING CATALOGUE omfort all-in-one for residential & commercial applications DAIKIN ALTHERMA HEATING CATALOGUE Heating, domestic hot water and cooling Sustainable energy solutions for residential and commercial use 2 3

More information

Unico Inverter. Unique and efficient.

Unico Inverter. Unique and efficient. Unico Inverter. Unique and efficient. INTERNATIONAL PATENT PENDING The first fixed air conditioner without outdoor unit featuring DC Inverter technology. Great performance, reduced consumption. Designed

More information

Create the right atmosphere with renewables.

Create the right atmosphere with renewables. The complete ROTEX heat pump product range Create the right atmosphere with renewables. ROTEX air-to-water and ground source heat pumps for new build and modernisation. The inexhaustible heat source on

More information

Commercial Gas Heat Pump - VRF

Commercial Gas Heat Pump - VRF SANYO GHP Introduction Commercial Gas Heat Pump - VRF 01.12.2011 Agenda 1. SANYO GHP History 2. SANYO GHP Range 3. GHP Market Position 4. 2-WAY 5. GHP Power 6. 3-WAY 7. EER/COP 8. Water Heat Exchanger

More information

ROTEX Gas-Hybrid-Heat Pump

ROTEX Gas-Hybrid-Heat Pump ROTEX Gas-Hybrid-Heat Pump Heating market Europe Market potential New built Emitter modernization Building structure Keep emitters Oil replacement Gas replacement 1.000.000,00 700.000,00 800.000,00 5.500.000,00

More information

Codes and High Performance Hot Water Systems. Gary Klein Affiliated International Management, LLC 916 549 7080 gary@aim4sustainability.

Codes and High Performance Hot Water Systems. Gary Klein Affiliated International Management, LLC 916 549 7080 gary@aim4sustainability. Codes and High Performance Hot Water Systems Gary Klein Affiliated International Management, LLC 916 549 7080 gary@aim4sustainability.com Annual Energy Use for Heating Water Natural Gas Gallons Per Day

More information

Federation of European Heating, Ventilation and Air-conditioning Associations

Federation of European Heating, Ventilation and Air-conditioning Associations Federation of European Heating, Ventilation and Air-conditioning Associations Address: Rue Washington 40 1050 Brussels Belgium www.rehva.eu info@rehva.eu Tel: +32 2 514 11 71 Fax: +32 2 512 90 62 REHVA

More information

THE EUROPEAN GREEN BUILDING PROGRAMME. Technical Module on Combined Heat and Power

THE EUROPEAN GREEN BUILDING PROGRAMME. Technical Module on Combined Heat and Power THE EUROPEAN GREEN BUILDING PROGRAMME Technical Module on Combined Heat and Power Contents Foreword...1 1. Introduction...2 2. Inventory of the CHP system...3 3. Assessment of technical energy saving measures...5

More information

Economic Evaluation of Residential Air Conditioner Designs for Hot and Dry Climates

Economic Evaluation of Residential Air Conditioner Designs for Hot and Dry Climates Economic Evaluation of Residential Air Conditioner Designs for Hot and Dry Climates Arthur Rosenfeld, California Energy Commission Gregory Rosenquist, Lawrence Berkeley National Laboratory C. Keith Rice,

More information

Cooling kw 5.2 6.0 7.1 Heating kw 5.65 6.35 7.75

Cooling kw 5.2 6.0 7.1 Heating kw 5.65 6.35 7.75 Specifications COOLING ONLY / HEAT PUMP 005 006 007 Capacity (Eurovent) Cooling kw 5.2 6.0 7.1 Heating kw 5.65 6.35 7.75 Nominal input (Eurovent) Cooling kw 1.89 2.35 2.95 Heating kw 1.97 2.24 2.83 EER

More information

DIETRISOL SOLAR WATER HEATING SYSTEMS ENERGY SAVINGS AND ECOLOGICAL BENEFITS SUSTAINED COMFORT SIMPLICITY AND RELIABILITY INNOVATIVE, MODULAR SYSTEMS

DIETRISOL SOLAR WATER HEATING SYSTEMS ENERGY SAVINGS AND ECOLOGICAL BENEFITS SUSTAINED COMFORT SIMPLICITY AND RELIABILITY INNOVATIVE, MODULAR SYSTEMS DIETRISOL SOLAR WATER HEATING SYSTEMS ENERGY SAVINGS AND ECOLOGICAL BENEFITS SUSTAINED COMFORT SIMPLICITY AND RELIABILITY INNOVATIVE, MODULAR SYSTEMS DIETRISOL SOLAR WATER HEATING SYSTEMS NON-POLLUTING,

More information

New technical solutions for energy efficient buildings

New technical solutions for energy efficient buildings - New technical solutions for energy efficient buildings State of the Art Report New technologies for heat pumps Authors: Heimo Staller, Angelika Tisch, IFZ Oct. 2010 Background Heat pumps are machines

More information

A Class Air Source Heat Pump User Guide

A Class Air Source Heat Pump User Guide A Class Air Source Heat Pump User Guide IMPORTANT THIS MANUAL MUST BE LEFT WITH THE USER AFTER INSTALLATION 8/60476/0 Issue 1.03 Contents 1: Introduction 1 2: How the Heat Pump Works 1 2.1 Tips and advice

More information

Natural gas heating versus split system heating and the current and future viability of the Natural gas network

Natural gas heating versus split system heating and the current and future viability of the Natural gas network Natural gas heating versus split system heating and the current and future viability of the Natural gas network Discussion Paper: Energy Consumer Reference Council meeting 7. August 2015 While ActewAGL

More information

The heat is there let s use it! Using free environmental heat from the air with heat pump technology for central heating and domestic hot water

The heat is there let s use it! Using free environmental heat from the air with heat pump technology for central heating and domestic hot water RENEWABLES AIR SOURCE HEAT PUMPS The heat is there let s use it! Using free environmental heat from the air with heat pump technology for central heating and domestic hot water 01 2016 STIEBEL ELTRON is

More information

CLOSE CONTROL SYSTEM. PFD series provide you with highly reliable computer room cooling system. High Reliability

CLOSE CONTROL SYSTEM. PFD series provide you with highly reliable computer room cooling system. High Reliability PFD-P250VM-E PUHY-P250YJM-A(-BS) PUHY-P500YSJM-A(-BS) PQHY-P250YHM-A CLOSE CONTROL SYSTEM MITSUBISHI ELECTRIC s Close Control System (PFD series) is specifically designed for computer rooms, laboratories

More information

Tackling the renovation challenge: high temperature hybrid heat pumps. François Bruggemans, DAIKIN Europe NV

Tackling the renovation challenge: high temperature hybrid heat pumps. François Bruggemans, DAIKIN Europe NV Tackling the renovation challenge: high temperature hybrid heat pumps François Bruggemans, DAIKIN Europe NV The target: further reduction of CO 2 emissions from heating - - - Current downward trend by

More information

Air conditioners Heating & Cooling

Air conditioners Heating & Cooling Air conditioners Heating & Cooling Replacement VRV Cost effective upgrade for R-22 s High efficiency Possibility to increase capacity Limited and planned downtime Limited and phased investment cost www.daikin.eu

More information

How to choose a heat pump and use it wisely

How to choose a heat pump and use it wisely How to choose a heat pump and use it wisely Contents How does a heat pump work? 2 Insulating your home 3 Heat loss in the home Not all heat pumps are created equal 4 Choosing a heat pump 4 Choosing by

More information

HEATING OF DOMESTIC OUTDOOR SWIMMING POOLS

HEATING OF DOMESTIC OUTDOOR SWIMMING POOLS HEATING OF DOMESTIC OUTDOOR SWIMMING POOLS INTRODUCTION 1. There are no general EU regulations and standards for outdoor swimming pool heating. Local regulations in the member countries are covering most

More information

OPTIMAL POLYGEN COOLING CONCEPT FOR ST. OLAVS HOSPITAL IN TRONDHEIM, NORWAY

OPTIMAL POLYGEN COOLING CONCEPT FOR ST. OLAVS HOSPITAL IN TRONDHEIM, NORWAY 1st European Conference on Polygeneration OPTIMAL POLYGEN COOLING CONCEPT FOR ST. OLAVS HOSPITAL IN TRONDHEIM, NORWAY G. Eggen 1, A. Utne 2 1) COWI A/S, PB 2564 Sentrum, NO-7414 Trondheim, Norway, e-mail:

More information

HIGH-EFFICIENCY CO 2 HEAT PUMP WATER HEATER SYSTEMS FOR RESIDENTIAL AND NON-RESIDENTIAL BUILDINGS

HIGH-EFFICIENCY CO 2 HEAT PUMP WATER HEATER SYSTEMS FOR RESIDENTIAL AND NON-RESIDENTIAL BUILDINGS 1 HIGH-EFFICIENCY CO 2 HEAT PUMP WATER HEATER SYSTEMS FOR RESIDENTIAL AND NON-RESIDENTIAL BUILDINGS Jørn Stene SINTEF Energy Research, 7465 Trondheim, Norway Jorn.Stene@sintef.no In hotels, hospitals,

More information

ECOCIAT. Domestic hot water heat recovery unit

ECOCIAT. Domestic hot water heat recovery unit Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY

More information

Vitocaldens 222-F Compact Gas-Hybrid appliance

Vitocaldens 222-F Compact Gas-Hybrid appliance Vitocaldens 222-F Compact Gas-Hybrid appliance Heating systems Industrial systems Refrigeration systems 2/3 Vitocaldens 222-F: The future-proof energy-source mix in one appliance Choosing Vitocaldens

More information

HP switch LP switch Discharge thermo Comp. Surface thermo

HP switch LP switch Discharge thermo Comp. Surface thermo 1 Specifications Zubadan Model Name PUHZ-SHW80VHA PUHZ-SHW11VHA PUHZ-SHW11YHA Power supply (phase, cycle, voltage) 1φ, V, Hz 1φ, V, Hz 3φ, 0V, Hz Max. current A 9.5 35.0 13.0 Breaker size A 3 16 Outer

More information

RESEARCH HIGHLIGHT. The Impact of Heat Pump Water Heaters on Whole-House Energy Consumption

RESEARCH HIGHLIGHT. The Impact of Heat Pump Water Heaters on Whole-House Energy Consumption RESEARCH HIGHLIGHT December 2014 Technical Series 14-104 The Impact of Heat Pump Water Heaters on Whole-House Energy Consumption INTRODUCTION Heat pump water heaters are one of the most energyefficient

More information

omfort all-in-one applications for residential & commercial DAIKIN ALTHERMA HEATING CATALOGUE

omfort all-in-one applications for residential & commercial DAIKIN ALTHERMA HEATING CATALOGUE omfort all-in-one for residential & commercial applications catalogue 2013 DAIKIN ALTHERMA HEATING CATALOGUE Heating, domestic hot water and cooling Sustainable energy solutions for residential and commercial

More information

Improving comfort and energy efficiency in a nursery school design process S. Ferrari, G. Masera, D. Dell Oro

Improving comfort and energy efficiency in a nursery school design process S. Ferrari, G. Masera, D. Dell Oro Improving comfort and energy efficiency in a nursery school design process S. Ferrari, G. Masera, D. Dell Oro Dept. Building Environment Science &Technologies Politecnico di Milano Italy Research funded

More information

Gas Absorption Heat Pumps. Future proofing your heating and hot water

Gas Absorption Heat Pumps. Future proofing your heating and hot water Gas Absorption Heat Pumps Future proofing your heating and hot water Gas Absorption Heat Pumps 1 Contents Gas Absorption Heat Pumps (GAHPs) The heating solution What is a Gas Absorption Heat Pump? How

More information

Module 2.2. Heat transfer mechanisms

Module 2.2. Heat transfer mechanisms Module 2.2 Heat transfer mechanisms Learning Outcomes On successful completion of this module learners will be able to - Describe the 1 st and 2 nd laws of thermodynamics. - Describe heat transfer mechanisms.

More information

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES

More information

The ASHRAE HQ Building Can the energy efficiency of the different mechanical systems really be compared? RESIDENTIAL LIGHT COMMERCIAL COMMERCIAL

The ASHRAE HQ Building Can the energy efficiency of the different mechanical systems really be compared? RESIDENTIAL LIGHT COMMERCIAL COMMERCIAL The ASHRAE HQ Building Can the energy efficiency of the different mechanical systems really be compared? RESIDENTIAL LIGHT COMMERCIAL COMMERCIAL Technical Article April 2013 The ASHRAE HQ Building Can

More information

FTQ. Daikin Inverter Ducted Heat Pump

FTQ. Daikin Inverter Ducted Heat Pump FTQ Daikin Inverter Ducted Heat Pump A TRADITIONAL CENTRAL AIR SYSTEM MADE BETTER WITH DAIKIN CONSTANT COMFORT INVERTER TECHNOLOGY. The Daikin Inverter Ducted Heat Pump line is a cost effective alternative

More information

ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system.

ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system. ROOFTOP - HEAT PUMP UNIT Technical data Applies to Model YNRA R410A This document applies when installing into an air handler or as part of an air handling system. CONTENTS 1. General description... 2

More information

GEOTHERMAL HEATING AND COOLING INTRODUCTION

GEOTHERMAL HEATING AND COOLING INTRODUCTION GEOTHERMAL HEATING AND COOLING INTRODUCTION Geothermal Heating and Cooling Systems provide space conditioning -- heating, cooling, and humidity control. They may also provide water heating -- either to

More information

Technical data. Danfoss DHP-A

Technical data. Danfoss DHP-A Technical data Danfoss DHP-A An air heat pump which produces both heat and hot water Can operate efficiently down to -0 C Danfoss TWS tank gives plenty of hot water quickly and with low operating costs

More information

TICS - Integrated Control Strategy TICS - Total Integrated Control Strategy Mid Range System

TICS - Integrated Control Strategy TICS - Total Integrated Control Strategy Mid Range System TICS - Total Integrated Control Strategy Mid Range System Underfloor Heating & Cooling Control Solutions Energy efficient Heating and cooling TICS - Mid Range System Mid Range System TICS Mid Range Install

More information

YUTAKI S. Domestic Heating

YUTAKI S. Domestic Heating YUTAKI S ECOLOGY & COMFORT OUTDOOR UNIT RAS 3HVRNME-AF YUTAKI-S MODULE RWM 2~10.0HFSN3E The Yutaki S heat pump is the ideal solution both in new installations and refurbishments. Its exceptional performance

More information

Map section. 87,390 kbtu

Map section. 87,390 kbtu Closed-loop Solar System Closed-loop Solar Preheat with Back-Up Heater Location of the system Map section Richmond Longitude: -77.52 Latitude: 37.582 Elevation: 217 ft This report has been created by:

More information

Congratulations! Your unique solar monitor ID is located on your monitoring unit as seen on this page.

Congratulations! Your unique solar monitor ID is located on your monitoring unit as seen on this page. Congratulations! Your unique solar monitor ID is located on your monitoring unit as seen on this page. To access your unique solar monitoring website, simply type: www.welserver.com/welxxxx/ into your

More information

CHP Plant based on a Hybrid Biomass and Solar System of the Next Generation EU project No. ENER/FP7/249800/"SUNSTORE 4" Dipl.-Ing. Alfred Hammerschmid

CHP Plant based on a Hybrid Biomass and Solar System of the Next Generation EU project No. ENER/FP7/249800/SUNSTORE 4 Dipl.-Ing. Alfred Hammerschmid CHP Plant based on a Hybrid Biomass and Solar System of the Next Generation EU project No. ENER/FP7/249800/"SUNSTORE 4" Dipl.-Ing. Alfred Hammerschmid BIOS BIOENERGIESYSTEME GmbH, Austria TEL.: +43 (316)

More information

NIBE INSTALLER GUIDE TO ErP, SIMPLE AS 1 2 3

NIBE INSTALLER GUIDE TO ErP, SIMPLE AS 1 2 3 NIBE INSTALLER GUIDE TO ErP, SIMPLE AS 1 2 3 WHAT IS ErP? ErP stands for Energy Related Products. The ErP is a new European Directive designed to drive improvements in efficiency and performance of heating

More information

Sino-Italian Environment & Energy Building S I E E B

Sino-Italian Environment & Energy Building S I E E B MOST Ministry of Science and Technology Republic of China Sino-Italian Environment & Energy Building S I E E B Concept The Sino-Italy Environment & Energy Building (SIEEB) is an intelligent, ecological

More information

The new Ecodesign regulation for heaters: what does it mean for heat pumps?

The new Ecodesign regulation for heaters: what does it mean for heat pumps? The new Ecodesign regulation for heaters: what does it mean for heat pumps? Michel Roffe-Vidal AIRWELL citat: there are persistent sales of lowefficiency heaters, because end-user base their purchase decision

More information

THE ROOFPOINT ENERGY AND CARBON CALCULATOR A NEW MODELING TOOL FOR ROOFING PROFESSIONALS

THE ROOFPOINT ENERGY AND CARBON CALCULATOR A NEW MODELING TOOL FOR ROOFING PROFESSIONALS THE ROOFPOINT ENERGY AND CARBON CALCULATOR A NEW MODELING TOOL FOR ROOFING PROFESSIONALS James L. Hoff, VP of Research Center for Environmental Innovation in Roofing Tools and Models Tools require models

More information

Building Energy Systems. - HVAC: Heating, Distribution -

Building Energy Systems. - HVAC: Heating, Distribution - * Some of the images used in these slides are taken from the internet for instructional purposes only Building Energy Systems - HVAC: Heating, Distribution - Bryan Eisenhower Associate Director Center

More information

I-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 8, Loughborough University, 29 th June 2015

I-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 8, Loughborough University, 29 th June 2015 I-STUTE Project - WP2.3 Data Centre Cooling Project Review Meeting 8, Loughborough University, 29 th June 2015 Topics to be considered 1. Progress on project tasks 2. Development of data centre test facility

More information

Nordic Heat Pump Product Guide

Nordic Heat Pump Product Guide Nordic Heat Pump Product Guide About Maritime Geothermal Maritime Geothermal is a privately owned, Canadian based manufacturer of geothermal heat pumps. We began manufacturing the Nordic line of heat pumps

More information

SEERS International. Hybrid Hot Water Systems. Innovation Technology

SEERS International. Hybrid Hot Water Systems. Innovation Technology SEERS International Hybrid Hot Water Systems Innovation Technology EFFECTS OF GLOBAL WARMING Invented & Manufactured By : Seers International Patent Number: PI-20082195 5 th Generation Hybrid Hot Water

More information

Solar Hot Water. What systems are available?

Solar Hot Water. What systems are available? Solar Hot Water Using the sun s energy to heat water will save you energy, lower your hot water bills, and reduce greenhouse pollution. Solar hot water systems work effectively in Victoria using mature

More information

White Paper Nest Learning Thermostat Efficiency Simulation for France. Nest Labs September 2014

White Paper Nest Learning Thermostat Efficiency Simulation for France. Nest Labs September 2014 White Paper Nest Learning Thermostat Efficiency Simulation for France Nest Labs September 2014 Introduction This white paper gives an overview of potential energy savings using the Nest Learning Thermostat

More information

User manual. 086U6297 Rev. 9 EN

User manual. 086U6297 Rev. 9 EN User manual Atria Atria Duo Atria Duo Optimum Atria Optimum Comfort Diplomat Diplomat Duo Diplomat Duo Optimum Diplomat Duo Optimum G2 Diplomat Optimum Diplomat Optimum G2 086U6297 Rev. 9 EN Thermia Värme

More information

Heating & Cooling Efficiency

Heating & Cooling Efficiency Heating & Cooling Efficiency Advantages of Geothermal HVAC Efficiency Keith Swilley Gulf Power Company Why Gulf Power Promotes Energy Efficiency? Customer Satisfaction Education Help Customers Make Smart

More information

Vicot Solar Air Conditioning. V i c o t A i r C o n d i t i o n i n g C o., l t d Tel: 86-531-8235 5576 Fax: 86-531-82357911 Http://www.vicot.com.

Vicot Solar Air Conditioning. V i c o t A i r C o n d i t i o n i n g C o., l t d Tel: 86-531-8235 5576 Fax: 86-531-82357911 Http://www.vicot.com. Vicot Solar Air Conditioning V i c o t A i r C o n d i t i o n i n g C o., l t d Tel: 86-531-8235 5576 Fax: 86-531-82357911 Http://www.vicot.com.cn Cooling, heating, and domestic hot water. Return on investment

More information

Water Fired Chiller/Chiller-Heater. WFC-S Series: 10, 20 and 30 RT Cooling

Water Fired Chiller/Chiller-Heater. WFC-S Series: 10, 20 and 30 RT Cooling Water Fired Chiller/Chiller-Heater WFC-S Series: 1, 2 and 3 RT Cooling W E A R E F R I E N D L Y T O T H E E A R T H Water Fired SINGLE-EFFECT Chiller or Chiller-Heater Absorption Principle Cooling Cycle

More information

OPERATION MANUAL. Daikin Altherma indoor unit EKHVMRD50AAV1 EKHVMRD80AAV1 EKHVMYD50AAV1 EKHVMYD80AAV1

OPERATION MANUAL. Daikin Altherma indoor unit EKHVMRD50AAV1 EKHVMRD80AAV1 EKHVMYD50AAV1 EKHVMYD80AAV1 OPERATION MANUAL EKHVMRD50AAV1 EKHVMRD80AAV1 EKHVMYD50AAV1 EKHVMYD80AAV1 EKHVMRD50+80AAV1 EKHVMYD50+80AAV1 CONTENTS Page 1. Definitions... 1 2. Introduction... 2 2.1. General information... 2 2.2. Scope

More information

How a Ground Source Heat Pump Works for a School or College

How a Ground Source Heat Pump Works for a School or College How a Ground Source Heat Pump Works for a School or College Vertical System Image courtesy of Climate Master 1 Geothermal avoids the need for outdoor equipment..reducing vandalism and liability Image courtesy

More information

GEOTHERMAL HEATING APPLICATIONS FOR RESIDENTIAL HOMES

GEOTHERMAL HEATING APPLICATIONS FOR RESIDENTIAL HOMES GEOTHERMAL HEATING APPLICATIONS FOR RESIDENTIAL HOMES GAGNON HEATING & AIR CONDITIONING RT. 302, P.O. BOX 814 BRIDGTON, ME 04009 207-647-8782 mainegeothermal.com GOODWIN WELL & WATER, INC. 2282 AUBURN

More information