DC Motor Troubleshooting Based on the EASA TechNote Troubleshooting DC Motors
|
|
|
- Sharlene Mathews
- 9 years ago
- Views:
Transcription
1 DC Motor Troubleshooting Based on the EASA TechNote Troubleshooting DC Motors ALWAYS Disconnect the power before handling any parts of the electrical equipment Lock out and tag out all electrical circuits Test for voltage before touching any components Check for and eliminate the danger of stored energy caused by raised or spring loaded equipment The basic testing equipment you will need to troubleshoot DC motors in the field includes: Megohmmeter AC voltmeter DC clamp on ammeter Ohmmeter DC voltmeter Tachometer Find out if the failed motor was: 1. Operating successfully for a period of time before failing; or if it was 2. Installed recently. 1
2 MOTORS WITH A PREVIOUS HISTORY OF SUCCESSFUL OPERATION If the motor has been operated successfully, problems such as incorrect hook up or internal misconnection can be ruled out immediately. Before proceeding, 1. Record relevant motor nameplate data (hp, RPM, rated voltages and currents for armature and field) 2. Inspect the motor for any obvious defects that would prevent safe testing such as: Damaged windings (Smoke, copper particles) Loose connections (melted wire nuts, burned insulation) Broken or missing parts (pulleys, belts, covers, etc ) Defective brushes or brush holders PROBLEM: MOTOR WILL NOT START Check to make sure adequate AC power is available at the control unit (use AC voltmeter) If the main fuse is blown, DO NOT apply power to the motor until you have completed a determination of why the fuse blew. Use the megohmmeter to measure the insulation resistance of all windings 1. Armature Circuit (armature winding, commutator, brush holders, interpoles, series field) 2. Shunt Field (any ground conditions must be repaired before power is applied to the motor) If the main fuses are OK, press the start button and measure the armature and shunt field voltages at the controller using a DC voltmeter. All output voltages must be in accordance with the motor nameplate. If rated voltage is measured, the problem is in the motor or motor wiring. A zero or a very low reading indicates that something is wrong with the controller or control wiring. Procedure 1: Test and inspect controller If no output is read from the controller, determine if the problem is in the control circuit and correct it. Is the controller tripped? If tripped determine cause and correct problem. Over current (excessive load over a period of time) Over voltage (overhauling type of load) Over Heat (high ambient temperatures overloading) Are the thermostats in the motor is tripped (N/C contacts)? No tach signal Attempt a reset Make sure the controller is getting a start signal (N/O contacts) Make sure there is not a STOP signal (N/C contacts) If the controller isn t functioning by this point, it s pretty safe to say that the controller is defective. 2
3 Procedure 2: Test and inspect motor Inspect electrical connections to the motor. Correct any loose or broken connections. Check for signs of heating or resistive connections Examine the brushes Are they all making good contact on the commutator? Are there any loose brush leads (replace any brushes that are too short or damaged) If the motor still does not operate, disconnect the power supply from the motor and use the ohmmeter to check the armature circuit for continuity. An open connection in the armature circuit could be caused by: 1. Worn and hung up brushes 2. Blown brush shunts 3. Open interpole circuit 4. Open series field (if so equipped) 5. Open armature (Commutator connections or winding) PROBLEM: OVERLOAD RELAY TRIPS OR FUSES BLOW WHEN MOTOR STARTS A starting current that is too high causes tripping the overload relay or blowing fuses when starting. Grounded windings Test all windings for ground failure using the megohmmeter. Any grounded windings must be repaired before power is applied to the motor Mechanical problems with the motor or driven equipment 1. Mechanical problems such as worn bearings or a broken pinion could cause a mechanical overload. 2. Determine if the problem is in the motor itself or in the driven equipment. Uncouple the motor and turn the armature by hand. If the armature moves freely and the motor starts without tripping the overload relay or blowing fuses when uncoupled, the problem is most likely in the driven equipment and not in the motor. Shorted armature winding 1. You can check the armature for shorts while the motor is uncoupled. After removing all brushes from the commutator, apply rated voltage to the shunt field and rotate the armature by hand. One or more shorted coils is indicated if the armature seems to be bound up or cogs as you rotate it. 2. If the motor will run for a short while before the overload trips or the fuse blows, shut down the motor and then feel the armature coils with your hand. Shorted coils will feel hotter than the others because they will have had heavy circulating currents induced into the shorted turns. Defective field winding A DC motor must have 100% field strength to produce its maximum torque and to keep the armature amperage within proper limits. Reduced field strength will cause high armature currents. 1. Test the shunt field continuity by measuring and recording the resistance of the shunt with an ohmmeter. A reading of infinity indicates an open circuit in the winding, which requires repairs to the motor. 3
4 2. Test the shunt field winding for shorted turns. Compare your shunt field resistance measurement to the nameplate data The motor nameplate may tell you field resistance. Remember, if the motor is HOT, your measured resistance will be higher than 20 C resistance listed on the nameplate. If the resistance of the field is equal to or less than the resistance listed on the nameplate, your winding is probably shorted If the nameplate doesn t tell you the correct resistance, you can calculate a good estimate using this formula: Field Volts/Field Amps = Field Resistance (Ω) Note: The field amps on the nameplate will be correct for the motor running at its normal full load condition with HOT fields. To estimate HOT resistance when you are measuring a COLD field, use this old rule of thumb : (Ω cold 10) / 8 = Ω hot 3. In Compound Wound or Stabilized Shunt Wound motors, test for shorts between the shunt and the series coils using the megohmmeter. Any shorts between the windings will require repairs to the motor. PROBLEM: MOTOR RUNS AT HIGHER THAN RATED RPM Verify correct tachometer feedback Measure the armature and the shunt field voltages at the motor terminals to be sure they are in accordance with the nameplate data. 1. The speed of the motor will increase if the armature voltage is higher than shown on the nameplate 2. The speed may also be higher if the applied shunt field voltage is lower than the value shown on the nameplate. If applied voltages are in accordance with the motor rating, there is a defect in the winding. Test for: 1. Grounds in all windings 2. Shorts in shunt field 3. Shorts between shunt and series field (if it is a compound wound motor) 4. Continuity in shunt and series coils (high resistance indicates an open circuit) PROBLEM: MOTOR RUNS AT LOWER THAN RATED RPM Measure the armature and field voltage at the controller and compare it with the nameplate value. 1. Reduced armature voltage will decrease motor speed 2. Increased field voltage will decrease motor speed If applied armature and field voltages are in accordance with the motor nameplate, inspect for high resistance connections in the armature circuit. 1. Loose connections and check for hot spots and discolored insulation around the connections 2. Contactors in controller making good contact 3. Broken or breaking conductors due to flexing 4. Shorting contactors must be closed during operation 4
5 If the speed of the motor varies continuously with constant voltages applied, and you have eliminated excessive resistance in the armature circuit, check for shorted armature coils. 1. You can check the armature for shorts while the motor is uncoupled. After removing all brushes from the commutator, apply rated voltage to the shunt field and rotate the armature by hand. One or more shorted coils is indicated if the armature seems to be bound up or cogs as you rotate it. 2. Shut down the motor and then feel the armature coils with your hand. Shorted coils will feel hotter than the others because they will have had heavy circulating currents induced into the shorted turns. PROBLEM: SPARKING UNDER THE BRUSHES Sparking under the brushes is a commutation problem. Mechanical problems (rather than electrical ones) are usually the cause. First of all, measure the armature current with the DC ammeter to see if the motor is overloaded. If the armature current is OK, concentrate on mechanical problems associated with the brushes. Inspect the Brushes 1. Make sure no brushes are missing and that all of them are properly seated on the commutator 2. Check that all brush leads are intact and that they are securely fastened to the brush holder 3. Check brush springs for correct pressure 4. Make sure the brushes fit properly and move freely in their brush boxes. They should not be too tight or too loose 5. Check brush holder mountings for looseness, which could be caused by burnt brush holder insulation (carbonization) or loose fasteners 6. Check the brush rigging jumpers to be certain that they are tight and securely connected 7. Inspect the brush mounting ring for damage, and make sure it is securely locked in the neutral position Inspect the Commutator (mechanical focus) 1. Physical damage (for example, from rubbing) 2. Is the commutator run out excessive? Commutator run out should be less than when the commutator is new. The normal operating speed of the machine will dictate how much tolerance in run out can be allowed. Generally, if the commutator run out exceeds to the commutator should be turned. 3. Inspect the commutator, making certain there are no raised segments 4. Make sure there are no segments with flat spots 5. Check for high mica 6. Be sure there is no foreign matter between the commutator bars 7. All of the conditions above can cause the brushes to bounce at high motor speeds. The interruption of the armature current will invariably cause sparking 8. Severe vibrations from an unbalanced armature 9. Run the motor uncoupled before removing it for service to see if the imbalance is in the motor or the machine 10. Worn bearings 11. Uneven air gaps can result if bearing clearances are out of whack. The movement of the armature can also cause the brushes to bounce 5
6 Inspect the Commutator (electrical focus) Inspect the commutator segments for signs of discoloration 1. Burned segments indicate open circuits Broken coil leads behind the risers. Thrown solder and loose connections at the risers. 2. Darkened segments can indicate shorted armature coils. The armature can be tested as we mentioned earlier to determine if it is shorted. Be Advised, a definite pattern of darkened commutator segments (every third or fourth segment, for instance), is often mistakenly assumed to indicate a problem. The design of the armature can produce patterns in the film that the brushes put down. Some characteristics of armature design that can cause current fluctuations and bar patterning are: Odd turns in armature coils Commutator bar and armature core slot combinations The bottom line is, if the discoloration pattern is repeated around the entire diameter of the commutator, there is probably NOT a problem with the armature winding. 6
7 NEWLY INSTALLED MOTORS The troubleshooting procedures outlined previously all apply to motors that fail after having been in operation for sometime. Now we will discuss troubleshooting motors that fail shortly after installation. PROBLEM: NEWLY INSTALLED MOTOR DOES NOT START OR FAILS SHORTLY AFTER INSTALLATION If a new motor or newly repaired motor malfunctions the first time it is put in service: 1. Make sure the control unit is properly matched to the motors nameplate ratings 2. Determine if the overcurrent devices are properly sized and properly adjusted 3. Check the control unit s input and output connections 4. Check the motor lead connections to be sure they are correct and tight 5. Make sure the controller is functioning properly If these checks indicate no reason for the malfunction, gather all the facts that you can and call Electrical Equipment Company for assistance. Some of the procedures outlined below require special equipment and great familiarity with the construction of DC motors. We highly recommend that they should be undertaken only with the aid and assistance of motor shop personnel. You will especially want the motor shop personnel there to protect your interests if you feel there are any manufacturer or repair warranty considerations. PROBLEM: NEWLY INSTALLED MOTOR RUNS AT HIGHER THAN RATED RPM Make sure the shunt field is properly connected for the voltage provided by the controller. If a dual voltage shunt field motor has the fields connected for high voltage and low voltage is applied to the field, the motor will run at higher than rated RPM. This condition will also produce high armature currents. To restore the speed of the motor to its normal range, reconnect the shunt field for low voltage. A note of caution: A shunt field connected (in parallel) for low voltage and then connected to a high voltage field supply will result in the shunt field burning out if adequate overcurrent protection is not provided. The manufacturer or the repair shop could NOT warrant such an overcurrent condition. Reversed Series Field polarities may cause compound wound motors to run at above the nameplate RPM when the motor is under load. If the motor rotation is correct, go ahead and interchange the series field leads. An incorrectly rewound armature can also cause a DC motor to run above its rated speed. This will happen if fewer turns were used in the new armature winding. Another winding error can be that the repairman put the first coil lead down into the wrong commutator bar. Hence, all the coil ends in the top of the commutator bars are in the wrong position. This error will generally double, or halve the motors speed depending on the motors original connection, and which error was made. 7
8 PROBLEM: NEWLY INSTALLED MOTOR RUNS IN REVERSE DIRECTION After a DC motor has been repaired, you will sometimes find that the direction of rotation has been reversed. Correct this problem by interchanging the armature leads. PROBLEM: SPARKING UNDER THE BRUSHES IN NEWLY INSTALLED MOTORS It is not uncommon to find sparking under the brushes in a newly installed motor. In most cases minor adjustments will correct the problem. Brush holder alignment Check that the brush holders align all brushes with the commutator bars and that equal spacing between the brushes is maintained. Make sure the brushes are in the neutral position In the neutral position, the line marking on the rocker ring must match the marking on the end bell. Make any adjustments necessary. If you suspect that the marking on the rocker ring is incorrect, you can determine the neutral position by following this procedure: 1. Unlock the brush rigging so that you can shift it freely 2. Disconnect the shunt field leads from the wiring 3. Connect an AC voltmeter to the shunts of brushes on adjacent brush holders 4. Apply single phase power (110 VAC) directly to the shunt field winding 5. Shift the brush rigging left, and right, while observing the voltage indicated by the AC voltmeter. The brushes are on neutral when minimum voltage is indicated (usually less than 1 volt AC) 6. Lock the brush rigging securely and mark the rocker ring and the endbell to indicate the correct neutral position. Relative polarity of main poles and interpoles Check the polarity of all main poles and interpoles using a magnetic compass. The polarities are correct when the polarity of the interpole is the same as that of the main pole preceding it in the direction of rotation. Should the polarities not be in the proper relationship, interchange the two brush holder leads. Brush grade: Check to be sure that the brush grade is compatible with the environment in which the motor operates. All brushes must be of the same grade. Brush grade selection requires specialized knowledge of the carbon materials and fabrication methods used. Electrical Equipment Company can help you acquire the data needed to make informed decisions on specifying new brushes. If the cause of the motor failure cannot be determined using procedures described in this Tech Note, the motor should be brought to the Electrical Equipment Company location nearest you. We will have the equipment and know how that you need. 8
DC MOTOR ANALYSIS & TROUBLESHOOTING
DC MOTOR ANALYSIS & TROUBLESHOOTING By Don Shaw Condition assessment of DC motors requires a basic understanding of the design and operating characteristics of the various types available: the series motor,
DC GENERATOR THEORY. LIST the three conditions necessary to induce a voltage into a conductor.
DC Generators DC generators are widely used to produce a DC voltage. The amount of voltage produced depends on a variety of factors. EO 1.5 LIST the three conditions necessary to induce a voltage into
Tuning Up DC Motors and Generators for Commutation and Performance
Tuning Up DC Motors and Generators for Commutation and Performance Rich Hall- National Electrical Carbon Western Mining Electrical Association June 8, 2007, Billings Montana Sometimes your machine may
SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS
SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the different types of open single-phase motors used to drive
(3) Explosion proof. Designed to prevent ignition of any explosive gases or dust and dirt which may surround the motor.
ELECTRIC MOTORS Enclosures for Motors Types of motor enclosures generally used in farm applications: (1) Open type; drip proof or splash-proof. A general purpose motor for use in dry locations which are
A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps
A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps Troubleshooting Submersible Pumps Fuse overload or circuit breaker trips when motor is started 1. Incorrect line voltage. Check the line
The Charging System. Section 5. Charging System. Charging System. The charging system has two essential functions:
The Charging System Charging System The charging system has two essential functions: Generate electrical power to run the vehicle s electrical systems Generate current to recharge the vehicle s battery
Lab 14: 3-phase alternator.
Lab 14: 3-phase alternator. Objective: to obtain the no-load saturation curve of the alternator; to determine the voltage regulation characteristic of the alternator with resistive, capacitive, and inductive
DIRECT CURRENT GENERATORS
DIRECT CURRENT GENERATORS Revision 12:50 14 Nov 05 INTRODUCTION A generator is a machine that converts mechanical energy into electrical energy by using the principle of magnetic induction. This principle
Single Phase Soft Starter
Single Phase Soft Starter Installation & Operating Manual 6/02 Table of Contents Section 1 General Information................................................... 1 1 General Description................................................
The DC Motor/Generator Commutation Mystery. Commutation and Brushes. DC Machine Basics
The DC Motor/Generator Commutation Mystery One small, yet vital piece of the DC electric motor puzzle is the carbon brush. Using the correct carbon brush is a key component for outstanding motor life,
Chapter 22: Electric motors and electromagnetic induction
Chapter 22: Electric motors and electromagnetic induction The motor effect movement from electricity When a current is passed through a wire placed in a magnetic field a force is produced which acts on
Single-Phase AC Synchronous Generator
ST Series Single-Phase AC Synchronous Generator Instructions for Operation and Maintenance English to English translation by R.G. Keen, May 2004. ST Series of Single-Phase AC Synchronous Generators Description
4 DEDICATED SINGLE PHASE LIMA MAC GENERATOR LIGHT TOWER DUTY MODELS 250MSL1278 AND 250MSL1299 SERVICE PROCEDURE ELECTRICAL COMPONENT TESTING
HI POTENTIAL TESTS 4 DEDICATED SINGLE PHASE LIMA MAC GENERATOR LIGHT TOWER DUTY MODELS 250MSL1278 AND 250MSL1299 SERVICE PROCEDURE ELECTRICAL COMPONENT TESTING None of the windings, either rotating or
Automatic taper of charge rate for superior battery life through good equalization of cells and low water use rate.
*00151* FEATURES Automatic taper of charge rate for superior battery life through good equalization of cells and low water use rate. Silicon diodes with inherent surge protection operated at a conservative
Motors and Generators
Motors and Generators Electro-mechanical devices: convert electrical energy to mechanical motion/work and vice versa Operate on the coupling between currentcarrying conductors and magnetic fields Governed
Direct Current Motors
Direct Current Motors DC MOTORS The DC machine can operate as a generator and as a motor. Chap 5. Electrical Machines by Wildi, 6 e Lecturer: R. Alba-Flores Alfred State College Spring 2008 When a DC machine
TROUBLESHOOTING PRELIMINARY
TROUBLESHOOTING PRELIMINARY To troubleshoot, one must first have a working knowledge of the individual parts and their relation to one another. Must have adequate hand tools Must have basic instrumentation:
3.0 CHARACTERISTICS. AR Auxiliary Relay High Speed, High Threshold 41-759.3C
41-759.3C the magnetic core upon energizing of the switch. When the switch closes, the moving contacts bridge two stationary contacts, completing the trip circuit. Also during this operation two fingers
SYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION
SYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION Introduction Howard W. Penrose, Ph.D., CMRP Vice President, Engineering and Reliability Services Dreisilker Electric Motors, Inc.
4 LEAD DEDICATED SINGLE PHASE LIMA MAC GENERATOR MODELS 250MSL1185 AND 250MSL1152
4 LEAD DEDICATED SINGLE PHASE LIMA MAC GENERATOR MODELS 250MSL1185 AND 250MSL1152 SERVICE PROCEDURE ELECTRICAL COMPONENT TESTING HI POTENTIAL TETS None of the windings, either rotating or stationary should
Rutland 913 Windcharger Fault Finding Guide
Rutland 913 Windcharger Fault Finding Guide Document No. SM-133 Issue A LOW VOLTAGE CHARGE CURRENT? TE 4 REGULATOR TE 5 REG RETURN REG TO MANUFACTURER CHARGE CURRENT INTERMITTENT CHARGE CURRENT SUFFICIENT
ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE
ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE Protected by one or more of the following U.S. Patents (3,507,354; 3,575,234; 3,596,936; 3,605,797; 3,685,329; 4,045,977; 4,698,982; 926,673 and
AND8008/D. Solid State Control Solutions for Three Phase 1 HP Motor APPLICATION NOTE
Solid State Control Solutions for Three Phase 1 HP Motor APPLICATION NOTE INTRODUCTION In all kinds of manufacturing, it is very common to have equipment that has three phase motors for doing different
Lab 8: DC generators: shunt, series, and compounded.
Lab 8: DC generators: shunt, series, and compounded. Objective: to study the properties of DC generators under no-load and full-load conditions; to learn how to connect these generators; to obtain their
Troubleshooting Guide, Freedom and Fleet Power Inverter/Chargers
Technical Note Freedom/Fleet Power 512-0084-01-01 Rev 1 Troubleshooting Guide, Freedom and Fleet Power Inverter/Chargers Overview This document is a guide for troubleshooting inverters, battery chargers,
Fan Coil EC Motor Control
Fan Coil EC Motor Control G3 PWM BARD The Enviro-Tec Generation 3 PWM (G3 PWM) board provides a pulse-width modulated (PWM) signal to the EC motor to control fan speed. The board is factory programmed
TROUBLESHOOTING GUIDE
TROUBLESHOOTING GUIDE LESTRONIC II BATTERY CHARGER FOR MOTIVE POWER BATTERIES PLEASE SAVE THESE IMPORTANT SAFETY AND OPERATING INSTRUCTIONS For correct operation of the equipment, it is important to read
SINGLE PHASE MOTORS. INSTALLATION AND MAINTENANCE MANUAL March 21, 2006
SINGLE PHASE MOTORS INSTALLATION AND MAINTENANCE MANUAL March 21, 2006 Irvine, California (800) 474-0520 Indianapolis, Indiana (800) 866-7973 Hamilton, Ontario (800) 809-0330 e-mail: [email protected]
INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR THREE PHASE INDUCTION MOTORS
INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR THREE PHASE INDUCTION MOTORS Frames 143T - 449TZ 5100 North IH 35 Round Rock, Texas 78681 Phone: 800-451-8798 512-255-4141 Fax: 512-244-5512 RECEIVING 1. Check
1. The diagram below represents magnetic lines of force within a region of space.
1. The diagram below represents magnetic lines of force within a region of space. 4. In which diagram below is the magnetic flux density at point P greatest? (1) (3) (2) (4) The magnetic field is strongest
PANCAKE CAPACITOR GENERATOR Installation, Operation and Maintenance Manual
PANCAKE CAPACITOR GENERATOR Installation, Operation and Maintenance Manual A Regal Brand TABLE OF CONTENTS INTRODUCTION 2 General Data 2 Initial Inspection 2 SAFETY 2 INSTALLATION 3 Location / Environment
INSTALLATION & SERVICE MANUAL. Display Panel
INSTALLATION & SERVICE MANUAL Display Panel The PowerLine EMS TM is a specialized power distribution and energy management system intended to be used in recreational vehicles. The Control Module is housed
ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013
ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 READ CAREFULLY These instructions are intended to cover good practices in
The Starting System. Section 4. Starting System Overview. Starter. The starting system:
The Starting System Starter The starter motor drives the engine through a pinion gear that engages the ring gear on the flywheel. Fig. 4-01 TL623f401c Starting System Overview The starting system: Uses
Section B: Electricity
Section B: Electricity We use mains electricity, supplied by power stations, for all kinds of appliances in our homes, so it is very important to know how to use it safely. In this chapter you will learn
Heavy Duty Alternator Charging System Troubleshooting
Heavy Duty Alternator Charging System Troubleshooting Alternator Charging System Troubleshooting Squealing noises under the hood? Headlight bulbs blow out repeatedly or dim? Is the dash voltmeter gauge
Welcome to Linear Controls Quarterly Training
Welcome to Linear Controls Quarterly Training Introduction to Power Generation Objectives Supply attendees with basic knowledge of power generators and voltage regulators and provide the fundamentals of
********* ELECTRICAL ***********
SECTION 9... ELECTRICAL Note. Major changes and/or additions are in bold face font. Contributions by web members are underlined with dots and credit given when known. Minor changes, usually just wording,
ABB ! CAUTION. Type COQ Negative Sequence Generator Relay. (50/60 Hertz) 41-161J. Instruction Leaflet
ABB Instruction Leaflet 41-161J Effective: May 1997 Supersedes I.L. 41-161H Dated July 1984 ( ) Denotes Change Since Previous Issue Type COQ Negative Sequence Generator Relay (50/60 Hertz)! CAUTION Before
TOYOTA STARTING SYSTEMS. General
General Starting the engine is possibly the most important function of the vehicle's electrical system. The starting system performs this function by changing electrical energy from the battery to mechanical
System Tel 0845 121 4008 (Telephones) Ltd Fax 0845 121 4009 Email [email protected] Web www.bellsystem.co.uk
Troubleshooting Guide Audio Door Entry Systems (single entrance) (9nn, VRKn or BLn series) Most systems use the 801 phone, 801P on systems above 20 flats. Twisted-pair cable must be used (CW1308 telephone
IA Renewal Seminar 2014
IA Renewal Seminar 2014 Introductions Introductions Scott Durham President, Co-Owner Overview of FAA / EASA Certified Repair Station Instrument & Accessory Overhaul Location: McClellan CA (Sacramento)
Motor Fundamentals. DC Motor
Motor Fundamentals Before we can examine the function of a drive, we must understand the basic operation of the motor. It is used to convert the electrical energy, supplied by the controller, to mechanical
Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao. x x. x x. Figure 10: Cross sectional view
4 Armature Windings Main field Commutator & Brush Compole field haft v Compensating winding Armature winding Yoke Figure 10: Cross sectional view Fig. 10 gives the cross sectional view of a modern d.c.
. Failure. Analysis... Report...
. Failure. Analysis... Report..... for (Generation Company) (Station) Purchase Order Number XXXX (Dated XX/XX/XXXX) Report N-XXXX-FA, Revision 0 Schulz Electric Company Job Number N-XXXX Motor ID Number
543-0032-00, 943-0032-00. User s Manual
543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and
ELECTRICAL CIRCUITS. Electrical Circuits
Electrical Circuits A complete path, or circuit, is needed before voltage can cause a current flow through resistances to perform work. There are several types of circuits, but all require the same basic
Oil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?
Extra Questions - 2 1. A straight length of wire moves through a uniform magnetic field. The e.m.f. produced across the ends of the wire will be maximum if it moves: a) along the lines of magnetic flux
THE LUCAS C40 DYNAMO & ITS ARMATURE.
THE LUCAS C40 DYNAMO & ITS ARMATURE. H. Holden, March 2011. The Dynamo as a DC generating machine was used extensively in the pre- Alternator era, from the early 1900 s up to the late 1960 s and early
Service and Maintenance. SEW-EURODRIVE Driving the world
SEW Brakes Service and Maintenance 2 Objectives Upon completion of this session, you will be able to do the following: - Identify the components of an SEW brakemotor - Explain the operation of the SEW
Chen. Vibration Motor. Application note
Vibration Motor Application note Yangyi Chen April 4 th, 2013 1 Table of Contents Pages Executive Summary ---------------------------------------------------------------------------------------- 1 1. Table
EVANS ELECTRONIC TEMPERATURE CONTROL TROUBLESHOOTING GUIDE for systems equipped with electric coolant valve and external PC board.
EVANS ELECTRONIC TEMPERATURE CONTROL TROUBLESHOOTING GUIDE for systems equipped with electric coolant valve and external PC board. This Troubleshooting Guide covers the electric coolant valve and control
12-Volt Negative Ground Installation Instructions
12-Volt Negative Ground Installation Instructions For Part Number: 1141, 1164, 1165, 1181 CAUTION!!! Before installing, please read the following important information... 1. The Ignitor is designed for
Service Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTM3-SF-1. Split System Cooling 4TTM3018-4TTM3060
4TTM3-SF-1 Service Facts Split System Cooling 4TTM3018-4TTM3060! CAUTION UNIT CONTAINS R-410A REFRIGERANT! R-410A OPERATING PRESSURE EXCEEDS THE LIMIT OF R-22. PROPER SERVICE EQUIPMENT IS REQUIRED. FAILURE
REDI-LINE ELECTRIC GENERATORS USER'S GUIDE. Rugged, Reliable, DC to AC Power Conversion
REDI-LINE ELECTRIC GENERATORS USER'S GUIDE Rugged, Reliable, DC to AC Power Conversion REDI-LINE ELECTRIC GENERATOR MODEL INPUT ACTUAL OUTPUT ACTUAL OUTPUT WATTS SERIAL NO. PACIFIC SCIENTIFIC MOTOR PRODUCTS
Features and Benefits. Product Overview. Installation Overview. Sales Strategy Overview FPO
RESCUE EcoTech Direct Drive Blower Motor The High Efficiency ECM/BPM Drop-in Replacement Blower Motor Agenda Features and Benefits Product Overview Installation Overview Sales Strategy Overview FPO High
Load Cell Troubleshooting
VPG TRANSDUCERS Load Cells and Weigh Modules Technical Note VPGT-08 Scope Load cells are designed to sense force or weight under a wide range of adverse conditions; they are not only the most essential
User Guide. Model 380260 Insulation Tester / Megohmmeter
User Guide Model 380260 Insulation Tester / Megohmmeter Introduction Congratulations on your purchase of Extech s Insulation Tester/Megohmmeter. The Model 380260 provides three test ranges plus continuity
COMPUTER AIDED ELECTRICAL DRAWING (CAED) 10EE65
COMPUTER AIDED ELECTRICAL DRAWING (CAED) EE Winding Diagrams: (i) DC Winding diagrams (ii) AC Winding Diagrams Terminologies used in winding diagrams: Conductor: An individual piece of wire placed in the
CENTERLINE Motor Control Centers Bulletin 2100 Smoke Detector Unit
Instructions CENTERLINE Motor Control Centers Bulletin 2100 Smoke Detector Unit Catalog Number 2100-SD1 Description The Bulletin 2100 smoke detector unit is a 0.5 space factor unit for use in Bulletin
STUDY GUIDE: ELECTRICITY AND MAGNETISM
319 S. Naperville Road Wheaton, IL 60187 www.questionsgalore.net Phone: (630) 580-5735 E-Mail: [email protected] Fax: (630) 580-5765 STUDY GUIDE: ELECTRICITY AND MAGNETISM An atom is made of three
KBIC Solid State SCR DC Motor Speed Controls See table 2 page 4 for KBIC models covered by this manual
KBIC Solid State SCR DC Motor Speed Controls See table 2 page 4 for KBIC models covered by this manual Patented Ultra Fast CL Circuit Prevents Demagnetization in PM Motors Installation and Operating Instructions
ANALOG AND DIGITAL METERS ANALOG VS. DIGITAL METERS VOLTMETERS ANALOG AND DIGITAL
ANALOG VS. DIGITAL METERS Ultimately, your diagnosis of vehicle electrical system problems will come down to using a voltmeter, ammeter, or ohmmeter to pinpoint the exact location of the problem. There
Electrical Diagnostic Tools
Electrical Diagnostic Tools Learning Objectives: 1. Explain what to look for when making a visual inspection. 2. Show the proper techniques for using a jumper wire. 3. Explain the advantages and features
Current Transformers
Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 Current Transformers Current transformers (CT's) provide
ROTOTWIST BELMONT TEXTILE MACHINERY COMPANY
ROTOTWIST BELMONT TEXTILE MACHINERY COMPANY PROCESS DESCRIPTION ROTOTWIST is a process to produce twisted, plied yarns of 2 to 6 plys in a continuous, highspeed operation. Individual ends are fed from
Battery Chargers. Revised 8/00 Form Number 56041170 FORM NO. 56041170 / BATTERY CHARGER SERVICE MANUAL / PARTS LIST - 45
Battery Chargers SERVICE MANUAL / PARTS LIST AUTOMATIC Advance MODELS 0980, 098, 797, 8809, 90, 880, 880, 099, 08,, 09788, 098, 7, 097, 70, 790, 889 Lester MODELS 007,, 8, 8, 89, 80, 9, 00, 00, 008 MANUAL
PENNTEX FOUR-STEP CHARGING SYSTEM TEST AND GENERAL INFORMATION FOR ANY PENNTEX SYSTEM EXCEPT 2009-UP FORDS WITH A PX-7000 VOLTAGE REGULATOR
PENNTEX FOUR-STEP CHARGING SYSTEM TEST AND GENERAL INFORMATION FOR ANY PENNTEX SYSTEM EXCEPT 2009-UP FORDS WITH A PX-7000 VOLTAGE REGULATOR PennTex Industries, Inc. is a manufacturer of Heavy Duty Charging
SERVICE MANUAL RESIDENTIAL ELECTRIC AND LIGHT DUTY COMMERCIAL ELECTRIC WATER HEATERS. Troubleshooting Guide and Instructions for Service
RESIDENTIAL ELECTRIC AND LIGHT DUTY COMMERCIAL ELECTRIC WATER HEATERS SERVICE MANUAL Troubleshooting Guide and Instructions for Service (To be performed ONLY by qualified service providers) Models Covered
3) What is the difference between "Insulating", "Isolating", and "Shielded Winding" transformers?
Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 1) What is a transformer and how does it work? A transformer
Equipment: Power Supply, DAI, Universal motor (8254), Electrodynamometer (8960), timing belt.
Lab 12: The universal motor. Objective: to examine the construction of the universal motor; to determine its no-load and full-load characteristics while operating on AC; to determine its no-load and full-load
Installation and Operating Manual
DC DRIVE BC138 BC139 DC CONTROL Installation and Operating Manual 7/2001 MN708 TABLE OF CONTENTS Section Page i. Simplified Operating Instructions.......................................... 1 ii. Safety
Owner s Manual. ULTRA-POWER II ACCU-POWER & ACCU-POWER ONBOARD Solid State Fully Automatic Chargers. Manual Number 1017361. Edition Code 0493B0101A
Owner s Manual ULTRA-POWER II ACCU-POWER & ACCU-POWER ONBOARD Solid State Fully Automatic Chargers Manual Number 1017361 Edition Code 0493B0101A General Information This instruction manual should be read
Chapter 5. Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams
Chapter 5 Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams Objectives Upon completion of this course, you will be able to: Explain what electrical loads are and their general purpose
Odyssey of the Mind Technology Fair. Simple Electronics
Simple Electronics 1. Terms volts, amps, ohms, watts, positive, negative, AC, DC 2. Matching voltages a. Series vs. parallel 3. Battery capacity 4. Simple electronic circuit light bulb 5. Chose the right
Electric Motor Brake Horsepower Calculations
Electric Motor Brake Horsepower Calculations By Norm Christopherson These motor calculations are contained here as they apply to the changing conditions of the blower motor when pulley adjustments are
LESTRONIC DV AUTOMATIC 12 OR 24 VOLT DUAL OUTPUT DUAL MODE BATTERY CHARGER MODEL 16350 TYPE 12/24EL40-10ET
LESTRONIC DV AUTOMATIC 12 OR 2 VOLT DUAL OUTPUT DUAL MODE BATTERY CHARGER MODEL 16350 TYPE 12/2EL0-10ET PLEASE SAVE THESE IMPORTANT SAFETY AND OPERATING INSTRUCTIONS For correct operation of the equipment,
Understanding the Alternator
http://www.autoshop101.com THIS AUTOMOTIVE SERIES ON ALTERNATORS HAS BEEN DEVELOPED BY KEVIN R. SULLIVAN PROFESSOR OF AUTOMOTIVE TECHNOLOGY AT SKYLINE COLLEGE SAN BRUNO, CALIFORNIA ALL RIGHTS RESERVED
Essential Electrical Concepts
Essential Electrical Concepts Introduction Modern vehicles incorporate many electrical and electronic components and systems: Audio Lights Navigation Engine control Transmission control Braking and traction
UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual
UHIR Series Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater Owner s Manual This manual covers installation, maintenance and repair parts. Read carefully before attempting to
Installation/Operator Manual For use with WFCO ULTRA III Power Center Model WF-8712P and WF-8725P
Installation/Operator Manual For use with WFCO ULTRA III Power Center Model WF-8712P and WF-8725P Distributed in the U.S.A. and Canada by CHENG USA, INC. Sales (574) 294-8997 Warranty Service (877) 294-8997
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS ELECTRIC HEATING UNITS MODEL: ETA / EKI
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS ELECTRIC HEATING UNITS MODEL: ETA / EKI Page 2 / 16 CONTENTS 1 GENERAL... 3 2 SAFETY... 3 2.1 Safety instructions... 3 2.2 Correct use... 3 3 DESCRIPTION
ST Style Generator. Owners/Operators Manual
ST Style Generator Owners/Operators Manual LLC 216 Airport Rd NE Milledgeville, GA 31061 478-453-9358-Office 478-457-5524- Tom Cell 478-251-2914- Chris Cell Table of Contents Page 2. Table of Contents
Digital Energy ITI. Instrument Transformer Basic Technical Information and Application
g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER
Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.
Table V Troubleshooting Checklist for Refrigeration Systems TROUBLE POSSIBLE CAUSE CORRECTIVE MEASURE High condensing pressure. Low condensing pressure. Air or non-condensable gas in system. Inlet water
Replace That Bad Diode
Replace That Bad Diode A common problem in any restoration is fixing and replacing inoperative or missing electrical components. If the exact part cannot be located then the restorer is forced to improvise.
Rotary Phase Converters
FACTS from Ronk Electrical Industries, Inc. Bulletin 11981 Rotary Phase Converters ROTOVERTER Pat. No. 3,670,238 ROTO-CON Pat. No. 4,158,225 What are the ROTO-CON and ROTOVERTER power converters? The ROTO-CON
Rotating Machinery Diagnostics & Instrumentation Solutions for Maintenance That Matters www.mbesi.com
13 Aberdeen Way Elgin, SC 29045 Cell (803) 427-0791 VFD Fundamentals & Troubleshooting 19-Feb-2010 By: Timothy S. Irwin, P.E. Sr. Engineer [email protected] Rotating Machinery Diagnostics & Instrumentation
BRUSHHOLDERS AND THE PERFORMANCE OF CARBON BRUSHES
Tech Note No. 22 TECH NOTE NO. 22 Brushholders and the Performance of Carbon Brushes Reliable Solutions Today! EA SA ELECTRICAL SERVICE APPARATUS ASSOCIATION BRUSHHOLDERS AND THE PERFORMANCE OF CARBON
HPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80
Buck-Boost Transformers Single and Three Phase Potted Buck-Boost Transformers Buck-Boost Applications & Standard Specification... 80 Selecting Buck-Boost Transformers... 81 Single Phase Selection Tables...
ENGINE ELECTRICAL SYSTEM
ENGINE ELECTRICAL SYSTEM Return To Main Table of Contents GENERAL... 2 IGNITION SYSTEM... 4 CHARGING SYSTEM... 21 STARTING SYSTEM... 38 GENERAL GENERAL SPECIFICATIONS Distributor MPI FBC Type Contact pointless
Hydraulic Trouble Shooting
Hydraulic Trouble Shooting Hydraulic systems can be very simple, such as a hand pump pumping up a small hydraulic jack, or very complex, with several pumps, complex valving, accumulators, and many cylinders
Troubleshooting and Diagnostics
Troubleshooting and Diagnostics The troubleshooting and diagnostics guide provides instructions to assist in tracking down the source of many basic controller installation problems. If there is a problem
Section 1 Overview of Heavy-Duty Auto Throttle Controls. Heavy Duty Auto Throttle Applications
Section 1 Overview of Heavy-Duty Auto Throttle Controls Heavy Duty Auto Throttle Applications Utility and Maintenance Vehicles Increases engine RPM to provide full current output of the alternator when
Service Guide 12/27/03 TESTING, SERVICE & REPAIR GUIDE (For SH Space Heating Models & RA Water Heating Models)
TESTING, SERVICE & REPAIR GUIDE (For SH Space Heating Models & RA Water Heating Models) WARNING - HIGH VOLTAGE AC electrical circuits are connected to this heater. Do not attempt any service work on the
GLOLAB Two Wire Stepper Motor Positioner
Introduction A simple and inexpensive way to remotely rotate a display or object is with a positioner that uses a stepper motor to rotate it. The motor is driven by a circuit mounted near the motor and
Principles and Working of DC and AC machines
BITS Pilani Dubai Campus Principles and Working of DC and AC machines Dr Jagadish Nayak Constructional features BITS Pilani Dubai Campus DC Generator A generator consists of a stationary portion called
ELECTRICAL FUNDAMENTALS
General Electricity is a form of energy called electrical energy. It is sometimes called an "unseen" force because the energy itself cannot be seen, heard, touched, or smelled. However, the effects of