FIRE-RESISTING DOOR ASSEMBLY

Size: px
Start display at page:

Download "FIRE-RESISTING DOOR ASSEMBLY"

Transcription

1 1. Introduction HMO Information Sheet No 2 FIRE-RESISTING DOOR ASSEMBLY In the event of a fire, it is normal practice to evacuate a property via the main escape route. The main escape route is normally along the landing and down the stairs and out through the front door to a place of safety. Action should be taken to ensure that, in the event of a fire, occupants have enough time to safely exit a property. Effective fire-resisting door assemblies are vital to ensure that the occupants can evacuate to a place of safety. Correctly specified and well-fitted doors and frames will hold back fire and smoke and will prevent escape routes from becoming unusable, as well as preventing the fire spreading from one area of the property to another, until the emergency services arrive. A fire-resisting door assembly is necessary in any doorway that opens onto the emergency escape route. Most internal doors in a property are constructed of timber and whilst they give some limited protection against fire spread, it is only a purpose-built fire-resisting door assembly, tested to an approved standard that will provide the necessary protection. In order to assess sufficient protection of the escape route, it is important to consider whether the standard of fire resistance and surface finishing in the escape routes is satisfactory, if it has been affected by wear and tear and alterations and whether any improvements are necessary. This fact sheet will detail the components of a fire door assembly in a House of Multiple Occupation (HMO), as one measure to ensure the occupants have sufficient time to exit a property in the event of a fire. For the purposes of this fact sheet it is assumed that any reference to a fireresisting door is to one of wooden construction. The use of fire doors made of alternative materials would require further specific advice. 2. What is a Fire-Resisting Door Assembly? A purpose-built fire-resisting door assembly can be obtained from a specialist manufacturer and is installed by a competent person. This is the fire-resisting door combined with the doorframe. The installer will provide a certificate detailing the level of fire resistance that has been achieved i.e. 30 minutes. The significant findings of your fire risk assessment will determine those doors within the property that need to be fire-resisting door assemblies. Normally in a HMO, any habitable room, or high-risk area, opening directly onto the escape route will need to have a fire-resisting door assembly installed. The level of fire 1

2 resistance the door should provide will depend on the presence of a suitable and sufficient automatic fire detection and alarm system in place, as per Fact Sheet 1. However if a LD2 Grade A or D AFD system is present (depending on the size of HMO) the fire-resisting door assembly can be rated to give 30-minutes fire resistance. Otherwise a 60-minute fire-resisting door may be necessary e.g. a cellar door - where there is no AFD in the cellar and thus no early detection to raise the alarm in the event of a fire. The lack of early detection of a fire but the increased fire resistance of the door assembly would still provide sufficient time to retain the spread of fire and ensure the occupants can evacuate to safety. A typical 30-minute fire-resisting door assembly consists of the following: 30 minute fire-resisting door and frame Self-closing devices Cold smoke seal and intumescent heat seal Door furniture 3. Components of a 30-minute Fire-Resisting Door Assembly The fire-resisting door and frame should be purchased as a complete set thus ensuring the satisfactory fit of the door in the frame and the installation will provide the necessary 30-minute fire resistance. This can be verified by the certification that accompanies the door set, if installed as per the manufacturers instructions. The main components included in a 30-minute fire-resisting door assembly covered by this fact sheet are included in Figure 1 below. 2

3 Figure 1 Components of a 30-Minute Fire-Resisting Door Assembly This fact sheet will cover the specification and installation of the individual components of a fire door assembly as follows: A - Fire-Resisting Doors All fire-resisting doors are rated by their performance when tested to an appropriate standard. The level of protection provided by the door is measured, primarily by determining the time taken for a fire to breach the integrity of the door assembly, together with its resistance to the passage of hot gases and flame. The rule of thumb is a 30-minute fire-resisting door is 45mm thick and a 60- minute fire-resisting door is 54mm thick. This does not necessarily apply but the majority of fire doors still fall within these categories. Timber fire-resisting doors require a gap of 2-4mm between the door leaf and the frame. The gap between the fire-resisting door and the finished threshold must be kept to a minimum, and must not exceed 10mm. Where the gap exceeds 10mm, or the floor is out of level, a hardwood threshold must be fitted. It is important to consider the size of door opening when preparing a scheme. A standard fire-resisting door can only be trimmed within the limits specified by the 3

4 manufacturer. Where there is a non-standard door opening it will be necessary to use solid door blanks cut to the appropriate size and then hardwood door lippings applied to the edges. 30-minute fire-resisting doors can be obtained in the following formats: (i) (ii) Door Blanks solid timber Framed Leaves FD30 half hour fire door to BS 476 Part 22 with intumescent heat seals. FD30S half hour fire door to BS 476 Part 22 with intumescent heat and cold smoke seals. Every BWF-CERTIFIRE Fire Door Assembly carries a permanent and tamper evident label. For more information go to their web site [see below]. 4

5 Upgrading Existing Doors In the past doors were routinely upgraded into fire doors, lining the door panels with fire resisting sheeting and fitting large doorstops. Previously upgraded doors are very unlikely to meet the required specification unless the paperwork is available to confirm the extent of work carried out and the degree of fire resistance achieved. In addition cold smoke seals and intumescent heat seals still need to be fitted. Upgraded doors that are damaged or a poor fit to the frame will not be accepted under any circumstances. In some circumstances, such as where a property is a listed building, the replacement of doors with fire doors may not be an option. In such cases the door must first be examined by a specialist contractor to assess its suitability. Some doors will be in too poor a condition, or not thick enough to make upgrade possible, in which case alternatives will need to be considered. Guidance on how to improve the fire resistance of existing timber doors can be found in: Increasing the Fire Resistance of Existing Timber Doors, Information Paper 8/82, Building Research Establishment (BRE). Glazing Glazing can only be fitted to doors, which are designed for the purpose and tested to the relevant BS. The doors are often sold without the glazing panel and glazing must be fitted in accordance with manufacturer s instructions. Any plain glazing should be replaced by, or backed with, 6mm wire reinforced glass or equivalent, not exceeding 1.2m 2 in area and fitted with solid wood beading not less than 13mm in cross section. If you install a door with glazing, you will be required to demonstrate that it has been installed in accordance with the manufacturers instructions. B - Fire-Resisting Door Frames In all circumstances the fire-resisting door and frame should be installed as a complete set. Where the door and frame cannot be installed as a complete set the following information provides advice on how to upgrade the existing doorframe: In all openings where a fire door is fitted, or is to be fitted, the existing linings and architraves must be thoroughly checked to determine whether or not they provide sufficient fire resistance. In particular, consider the following: If the existing frame is in poor condition or warped so that it will be difficult to achieve a proper, close fit and good smoke seal for the fire door, then a new fire-resisting frame will be required. In many cases this will be more cost/time effective than trying to patch up an old frame. 5

6 If the existing frame is to be retained it must be capable of supporting the additional weight of the new fire door, and must be of sound, welljointed timber. If new timbers are to be added to the frame to improve the fit of the door, they must be glued and screwed to the existing linings. If the existing architraves do not provide an adequate seal with the wall they must be removed on the risk side (i.e. the room side) and all gaps between the door lining, wall/partitioning and non risk side architrave must be filled and sealed with fire-resisting materials e.g. 12.5mm plasterboard with skim finish or intumescent paste. Suitable architraves must be re-fitted to the risk side. The original architraves may be reused if they are in sound condition. All new architraves must be a minimum of 15mm thick and 45mm wide. Doorstops The doorstops on the existing frame are likely to be 12mm or less and are inadequate when the doorframe is being upgraded. These have to be removed and replaced by 25mm stops so the doorframe has a rebate or stop not less than 25mm wide and 38mm long glued and screwed to the existing doorframe at 300mm centres. Guidance on how to improve the fire resistance of frames can be found in: Fire Resisting Doorsets by Upgrading, Wood Information Sheet 1-32, Timber Research and Development Association (TRADA). C - Self-Closing Devices Self-closing devices fitted to fire-resisting doors must be positive in action and capable of closing and latching the door and holding it firmly against the rebates of the frame. Rising butt hinges and garden gate type coil springs do not meet the specification and are not acceptable due to their inability to close and latch the door. Overhead hydraulic closers are recommended as being the most effective and reliable type, allowing the door to close in a controlled manner. Chain spring closer (Perco) can be used as an alternative; however, the chain closer does not control the closing speed of the door, thus causing the door to slam. It is recommended that you fit self-closing devices that are easily adjustable. D - Cold Smoke Seal and Intumescent Heat Seal The cold smoke seal and intumescent heat seal (IHS) is ideally fitted to the doorframe or alternatively rebated into the two vertical and top horizontal edges of the fire-resisting door. The intumescent heat seal and cold smoke seal can be 6

7 fitted as combined unit. See Figure 2 - which details examples of the positioning of intumescent heat seals and cold smoke seals. The cold smoke seal (which consists of small brush hairs or flexible blades) acts initially to prevent smoke escaping through the closed door. If the fire develops the heat will cause the IHS to expand and hold the door in the frame to give 30- minutes fire resistance. Perimeter smoke seals that are fitted to the door stops so that the door closes against them are not usually accepted. Where appropriate they may be accepted when upgrading a door in a listed building, where it is often difficult to get a smoke seal on the edge of the door to form an adequate seal with a lining. No intumescent material must be fitted to the front face of the door or to the doorframe against the front face of the door. This is because in the event of a fire the intumescent material will expand and force the door open. All door furniture i.e. hinges, locks and latches should be bedded in intumescent putty/paste to ensure continuity of the intumescent seal to prevent any weakness of the fire door assembly at these weak points. The seals must be fitted in accordance with the manufacturers instructions. CLOSE ATTENTION MUST BE GIVEN TO THE GAP BETWEEN THE DOOR AND FRAME. As a guide it should not be more than 2-4mm. A larger gap may render the intumescent seal ineffective in a fire. In addition, you must ensure that if a door edge mounted smoke seal is being used it brushes right up against the door lining. It is important that you do not paint or varnish over the cold smoke seal when decorating the door as this will render it ineffective. 7

8 Figure 2 Position of Intumescent Heat and Cold Smoke Seals Combined intumescent heat and cold smoke seal (brush type) fitted in door leaf. Combined intumescent heat and cold smoke seal (flexible blade) fitted in door leaf. Perimeter cold smoke seal fitted to doorstop and intumescent heat seal fitted in door leaf. E Door Furniture Hinges Fire-resisting doors must be hung on 1 1/ 2 pairs (i.e. 3 hinges) of 100mm pressed steel butt hinges. The central hinge should be approximately 500mm down from the top of the door i.e. closer to the top hinge than the bottom hinge. Brass hinges cannot be used. Latches Latches have an important role in ensuring the integrity of the fire-resisting door; a door must be fitted with a handle and latch. The latch is the only holding device on the closing edge, hence it is important that it should be strong and that the nib of the latch should engage into the latch plate at least 12mm to ensure that the closing edge will not spring open when the door deforms. After the edges, the latch areas represent the next zone of weakness. Filling the voids in the cut-out section with intumescent paste will markedly lessen the weakness in this area. 8

9 Locking Arrangements Where a lock is to be fitted to the fire-resisting door it must be of the type that allows the door to be held shut but which does not lock unless a key is used on the outside, such as a thumb turn opening on the inside. The door, whether locked or not, must be openable from inside the room without the use of a key. A cylinder rim dead lock with roller bolt is recommended e.g. Yale 81 or Union 1158 or the Euro Mortice Lock with thumb turn. Other locks may be acceptable, providing they meet the same specification. Additional bolts, chains etc, must not be fitted by the landlord or tenant. Any provision made for increased security must not compromise the means of escape of the occupants. Any redundant door furniture should be removed and the pockets filled with timber bedded in intumescent material. Apertures in Fire-Resisting Doors Generally the fitting of standard letterboxes, door viewers, cat flaps, etc, will undermine the effectiveness of a fire door. It is possible to get products that will protect the integrity of the door and which meet the relevant BS but the specification for installation must be closely followed. 4. Certification of a Fire-Resisting Door Assembly The installer will provide a certificate detailing the level of fire resistance that has been achieved i.e. 30 minutes. A copy of the certificate must be forwarded to Private Sector Housing, Deene House, Corby Borough. Council, New Post Office Square, Corby, Northamptonshire, NN17 1GD 5. Maintenance of a Fire-Resisting Door Assembly The fire-resisting door assembly must be regularly checked to ensure that all the component parts are in place and working correctly. The fire-resisting door must close securely to the latch without the use of force. This document has been produced by Corby Borough Council and provides a guide to a Fire-resisting Door Assembly for HMOs. For specific advice please contact the Private Sector Housing Team on

Fire Doors Basic Guidance & Checklist

Fire Doors Basic Guidance & Checklist Fire Doors Basic Guidance & Checklist Introduction Fire doors and all passive fire protection products play a unique role in fire safety by containing a fire to a single compartment of a building and therefore

More information

The Role of Fire Doors. BWF-Certifire Fire Door and Doorset Scheme

The Role of Fire Doors. BWF-Certifire Fire Door and Doorset Scheme The Role of Fire Doors BWF-Certifire Fire Door and Doorset Scheme Fire doors today s agenda 1. Fire doors are essential in passive fire protection A requirement in compartmenting a building Protecting

More information

Guidance on loft conversions in two-storey houses

Guidance on loft conversions in two-storey houses Guidance on loft conversions in two-storey houses Technical guidance for building control surveyors, designers and installers 01 Guidance on loft conversions in two-storey houses Technical guidance for

More information

Building Control Guidance Note

Building Control Guidance Note Issued 01/01/13 Rev Page 1 of 5 If you intend to convert an existing loft space into additional rooms you will need to apply for Building Regulation Approval. You may also need Planning Permission if you

More information

Fire Doors The Role of a Fire Door

Fire Doors The Role of a Fire Door Fire Doors The Role of a Fire Door BWF-Certifire Fire Door and Doorset Scheme Presented by John Fletcher John Fletcher Consulting Ltd. Fire doors main messages 1. Fire doors are essential in passive fire

More information

Code of Practice for fire resisting metal doorsets

Code of Practice for fire resisting metal doorsets COP 1005 Code of Practice for fire resisting metal doorsets Scope The aim of this document is to provide guidance on the best practice for, and a better understanding of, hinged or pivoted fire resisting

More information

GENERAL FIRE SAFETY TERMS & DEFINITIONS

GENERAL FIRE SAFETY TERMS & DEFINITIONS UCL Fire Technical Note - TN006 Fire Safety Technical Guide GENERAL FIRE SAFETY TERMS & DEFINITIONS Reference: BS4422-2005 Fire Safety Vocabulary - for further information and definitions BS EN ISO 13943-2000:

More information

Approved Document Q: Security

Approved Document Q: Security Approved Document Q: Security Requirement Q1 Unauthorised access Consultation draft September 2014 1 The approved documents What is an approved document? The Secretary of State has approved a series of

More information

FIRE DOORS - GENERAL SPECIFICATIONS / EMPLOYERS REQUIREMENTS (ERs) & QUICK OVERVIEW

FIRE DOORS - GENERAL SPECIFICATIONS / EMPLOYERS REQUIREMENTS (ERs) & QUICK OVERVIEW Fire Safety Technical Guide FIRE DOORS - GENERAL SPECIFICATIONS / EMPLOYERS REQUIREMENTS (ERs) & QUICK OVERVIEW Fire Door Provision In UCL Buildings - what you need to know: Not Acceptable Opening direction

More information

Fire doors guidance. Safety and Health Services. Document control information. Date issued: January 2011. Version: 2. Previous review dates: 2011

Fire doors guidance. Safety and Health Services. Document control information. Date issued: January 2011. Version: 2. Previous review dates: 2011 Document control information Fire doors guidance Published document name: Firedoors-gn.pdf Date issued: January 2011 Version: 2 Previous review dates: 2011 Next review date: Related documents: Governing

More information

Office of the State Fire Marshal. Fire Rated Doors

Office of the State Fire Marshal. Fire Rated Doors Office of the State Fire Marshal Fire Rated Doors Fire Rated Doors These doors serve a purpose. They are manufactured in a way that is to help reduce the spread of fire and smoke. Fire rated doors allow

More information

Standard Door Specification

Standard Door Specification Element General Requirement To be defined in the project brief but should meet Building Regulations. All doors to be a minimum of 30 minute fire rated and must comply with all relevant UK legislation and

More information

FIRE DETECTION AND ALARM SYSTEMS

FIRE DETECTION AND ALARM SYSTEMS HMO Information Sheet No 1 FIRE DETECTION AND ALARM SYSTEMS 1. Introduction When a property is in multiple occupation, the risk of fire breaking out is greater than in an ordinary single family home. Some

More information

PROOF ONLY. Police and Fire Service Home Security & Fire Safety Checklist. Student Accommodation Security Checklist

PROOF ONLY. Police and Fire Service Home Security & Fire Safety Checklist. Student Accommodation Security Checklist Police and Fire Service Home Security & Fire Safety Checklist Student Accommodation Security Checklist A Self Assessment Guide for Landlords This checklist contains all the standards needed to make sure

More information

BUILDING CONTROL GUIDANCE SHEET REPLACEMENT WINDOWS AND DOORS Last updated 16/11/2010

BUILDING CONTROL GUIDANCE SHEET REPLACEMENT WINDOWS AND DOORS Last updated 16/11/2010 Building Control Charnwood Borough Council Southfield Road Loughborough LE11 2TN BUILDING CONTROL GUIDANCE SHEET REPLACEMENT WINDOWS AND DOORS Last updated 16/11/2010 Page 1 of 6 PURPOSE: This Guidance

More information

5.1. Smoke Sealing. General: The test procedure for smoke sealed doorsets is given by reference to BS476 Section 31.1.

5.1. Smoke Sealing. General: The test procedure for smoke sealed doorsets is given by reference to BS476 Section 31.1. v8 5.1 General: The test procedure for smoke sealed doorsets is given by reference to BS476 Section 31.1. The performance criteria for smoke sealed doorsets is given by reference to BS5588 (and BS9999)

More information

Loss Prevention Standard

Loss Prevention Standard Loss Prevention Standard : ISSUE 3.0 Requirements for the LPCB Approval and Listing of Companies Undertaking the Maintenance and Repair of Doorsets, Shutters, and Active Smoke/Fire Barriers This standard

More information

Thanks go to the following officers who have produced this guide:

Thanks go to the following officers who have produced this guide: London Fire Safety Guidance for Houses in Multiple Occupation Introduction Part 1 of the Housing Act 2004 introduced the Housing Health and Safety Rating System (HHSRS). Statutory Operating Guidance provides

More information

London Borough of Barnet. Fire Safety in Houses in Multiple Occupation. A Guide to Landlords

London Borough of Barnet. Fire Safety in Houses in Multiple Occupation. A Guide to Landlords London Borough of Barnet Fire Safety in Houses in Multiple Occupation A Guide to Landlords March 2016 Contents Introduction p.3 Summary of main requirements p.3 Fire Safety Precautions p.4 Protecting the

More information

CERTIFICATE OF APPROVAL No CF 291 SCHOTT UK LIMITED

CERTIFICATE OF APPROVAL No CF 291 SCHOTT UK LIMITED CERTIFICATE OF APPROVAL No CF 291 This is to certify that, in accordance with TS General Requirements for Certification of Fire Protection Products The undermentioned products of Drummond Road, Stafford.

More information

How To Write A Fire Risk Assessment

How To Write A Fire Risk Assessment Fire Safety Risk Assessment This form is to aid you in carrying out a fire safety risk assessment of a property. The form is separated in to two parts: Part 1 initial assessment form and guidance notes

More information

Basic Fire Door Requirements

Basic Fire Door Requirements TECHNICAL DATA SERIES S D I 118-01 Basic Fire Door Requirements 2001 Steel Door Institute STEEL DOOR INSTITUTE 30200 DETROIT ROAD - CLEVELAND, OHIO 44145 Technical Data Series SDI 118-2001 Basic Fire Door

More information

Fire-Rated Doors and Hardware. A Guide to Field Inspection

Fire-Rated Doors and Hardware. A Guide to Field Inspection Fire-Rated Doors and Hardware A Guide to Field Inspection Foundation s Mission To promote secure and safe openings that enhance life safety Awareness To be a source of information through awareness campaign

More information

Installation Instructions

Installation Instructions Installation Instructions 1. Position the unit onto bridging packers. These keep the unit away from any water sitting inside the frame. 2. Centralise the unit within the frame and pack the edges with appropriate

More information

Fire precautions in dwellings. Private sector housing Providing homes building communities

Fire precautions in dwellings. Private sector housing Providing homes building communities Fire precautions in dwellings Private sector housing Providing homes building communities Version 3 Published by Norwich City Council August 2011 Contents Page Introduction 1 2 Types of dwellings (A) Shared

More information

WHI 90-Minute Rated Veneered Door Frame Installation Instructions

WHI 90-Minute Rated Veneered Door Frame Installation Instructions No. 940-03-10 INSTALLATION INSTRUCTIONS 90 MINUTE RATED VENEERED DOOR FRAME DOOR REQUIREMENTS: Consult the door manufacturer to make sure that the doors are qualified for the hardware to be installed,

More information

FIRE RATED GLAZING System Guide

FIRE RATED GLAZING System Guide SYSTEM GUIDE Issue date: 05-05-2015 Expiry date: 31-12-2016 System Guide Introduction Pyropanel Developments are specialists in fire rated glazing solutions, and our systems are designed for easy installation

More information

Panic & emergency exit devices

Panic & emergency exit devices CFPA-E Guideline CFPA-E No 2:2007 - Appendix Appendix No: 1 Panic & emergency exit devices FOREWORD This Appendix offers technical solutions according to table 8.1 in the European Guide Line ""Panic &

More information

CLEAR-DIVISIONS CENTERFOLD

CLEAR-DIVISIONS CENTERFOLD CLEAR-DIVISIONS CENTERFOLD Introduction: The following three (3) part specification offers the Standard and Optional features for the CLEAR-DIVISIONS CENTERFOLD moveable The yellow highlighted areas in

More information

Property Accreditation Standards 2014/2015

Property Accreditation Standards 2014/2015 Property Accreditation Standards 2014/2015 Promoting responsible renting of student housing in the city of Southampton Letting period 1st July 2014 to 30th June 2015 Version 1, 10/12/2013 All properties

More information

Technical Information

Technical Information Technical Information This section of the catalogue provides technical information that will help specify, install and maintain Surelock McGill devices and components. The topics are listed below: Blast

More information

SPECIFIC GUIDANCE FOR A HOUSE IN MULTIPLE OCCUPATION (HMO) CONVERTED ENTIRELY INTO SELF CONTAINED FLATS

SPECIFIC GUIDANCE FOR A HOUSE IN MULTIPLE OCCUPATION (HMO) CONVERTED ENTIRELY INTO SELF CONTAINED FLATS Document F SPECIFIC GUIDANCE FOR A HOUSE IN MULTIPLE OCCUPATION (HMO) CONVERTED ENTIRELY INTO SELF CONTAINED FLATS This document is intended as a specific guide for persons who own, manage or control Houses

More information

Technical data sheet PVC Bi-fold doors

Technical data sheet PVC Bi-fold doors Standard Specifications White internally beaded, Deceuninck 3000 series profile 28mm Low-e toughened sealed units with argon gas Open in doors with white handles and hinges Tracks are fitted to the top

More information

White Paper FIRE DOOR INSPECTIONS, REPAIRS AND LABELING

White Paper FIRE DOOR INSPECTIONS, REPAIRS AND LABELING INTRODUCTION When the 2012 edition of the Life Safety Code is adopted by the Centers for Medicare Services (CMS) the following accreditation organizations The Joint Commission, AOA Healthcare Facilities

More information

CLEAR-DIVISIONS VARIOFOLD

CLEAR-DIVISIONS VARIOFOLD CLEAR-DIVISIONS VARIOFOLD Introduction: The following three (3) part specification offers the Standard and Optional features for the CLEAR-DIVISIONS VARIOFOLD moveable The yellow highlighted areas in the

More information

RESIDENTS FIRE SAFETY INFORMATION PACK

RESIDENTS FIRE SAFETY INFORMATION PACK RESIDENTS FIRE SAFETY INFORMATION PACK PERRONET HOUSE PRINCESS STREET LONDON SE1 THE CONTENTS OF YOUR PACK Section Page No. 1. 3. Introduction Here we will explain the purpose of the Fire Safety Information

More information

ISSUE 2. Installation Guide

ISSUE 2. Installation Guide ISSUE 2 Installation Guide Here at Slide and Fold, we LOVE our Bi-Fold Plus range of folding-sliding doors. We want to ensure that your customers love them too. So we have created a new, detailed installation

More information

FIRE-RESISTANT GLAZING Mr Leslie O May Sales Consultant Wright Style Limited England

FIRE-RESISTANT GLAZING Mr Leslie O May Sales Consultant Wright Style Limited England FIRE-RESISTANT GLAZING Mr Leslie O May Sales Consultant Wright Style Limited England Fire is a life-threatening and destructive force, which if unchecked, can spread rapidly through a building. Every year,

More information

RESIDENTS FIRE SAFETY INFORMATION PACK

RESIDENTS FIRE SAFETY INFORMATION PACK RESIDENTS FIRE SAFETY INFORMATION PACK MARIE CURIE SCEAUX GARDENS ESTATE LONDON SE5 THE CONTENTS OF YOUR PACK Section Page No. 1. 3. Introduction Here we will explain the purpose of the Fire Safety Information

More information

Fire 2This Technical Bulletin has been commissioned by the UK SIP Association in

Fire 2This Technical Bulletin has been commissioned by the UK SIP Association in REV 1-12.12.11/TB002 Technical Bulletin Fire 2This Technical Bulletin has been commissioned by the UK SIP Association in conjunction with TRADA Technology and is intended to provide the reader with introductory

More information

Gordon Cooke BSc PhD CEng MICE MIMechE FIFireE

Gordon Cooke BSc PhD CEng MICE MIMechE FIFireE International Symposium on Protection of Cultural Heritage Buildings from Fire, Kyoto, April 6-7, 2003 Upgrading the fire resistance of floors and doors in heritage buildings Gordon Cooke BSc PhD CEng

More information

Relevant British, European and International standards

Relevant British, European and International standards Relevant British, European and International standards BS 1245:1975 Specification for metal door frames (steel) BS 3621:2007 + A1:2009 Thief resistant lock assemblies - Key egress BS 476-20:1987 Fire tests

More information

SCHEDULE OF FINISHES AMBLE RIDGE RETIREMENT VILLAGE

SCHEDULE OF FINISHES AMBLE RIDGE RETIREMENT VILLAGE SCHEDULE OF FINISHES AMBLE RIDGE RETIREMENT VILLAGE SITEWORKS FOUNDATIONS & SURFACE BED Site to be cleared and leveled. Builder s rubble to be carted away. As per Engineer s design, with USB green waterproofing.

More information

Make it Difficult for the burglar. Contents. Look at your home through a burglar s eyes: Alarms 4_5. Distraction burglary 6 _ 7.

Make it Difficult for the burglar. Contents. Look at your home through a burglar s eyes: Alarms 4_5. Distraction burglary 6 _ 7. HOME SECURITY Make it Difficult for the burglar Home security is the best way to reduce your chances of being burgled. A lot of burglaries are spur of the moment, carried out by opportunist thieves who

More information

RESIDENTS FIRE SAFETY INFORMATION PACK

RESIDENTS FIRE SAFETY INFORMATION PACK RESIDENTS FIRE SAFETY INFORMATION PACK CASTLEMEAD CAMBERWELL ROAD LONDON SE5 THE CONTENTS OF YOUR PACK Section Page No. 1. 3. Introduction Here we will explain the purpose of the Fire Safety Information

More information

Fire Doors Explained. Presented by - Peter Barker

Fire Doors Explained. Presented by - Peter Barker Fire Doors Explained Presented by - Peter Barker Objectives and Outline 1. The role of fire resisting doors 2. Proving the performance of fire resisting doors 3. Common problems and solutions The Role

More information

Classroom Door Security & Locking Hardware

Classroom Door Security & Locking Hardware Classroom Door Security & Locking Hardware The ability to protect students and teachers while in the classroom is a high priority in all educational institutions. Many schools and school districts have

More information

How to secure your property after a disaster

How to secure your property after a disaster How to secure your property after a disaster The Red Guide to Recovery HOuse secured properly Board-Up of Windows, Doors and Roof Hole. Lot secured with Perimeter Fencing. Fires, floods, tornadoes, hurricanes,

More information

Panic Exit Devices. We take the worry out of protecting what s valuable to you. Lockwood: no worries. www.lockweb.com.au

Panic Exit Devices. We take the worry out of protecting what s valuable to you. Lockwood: no worries. www.lockweb.com.au Panic Exit Devices We take the worry out of protecting what s valuable to you. Lockwood: no worries www.lockweb.com.au Contents 9000/9100 Series 9300/9400 Series 9500/9600 Series 9000/9100 Series Rim Type

More information

An overview of mechanical lock and security related standards and why they re important to the Insurance Industry

An overview of mechanical lock and security related standards and why they re important to the Insurance Industry An overview of mechanical lock and security related standards and why they re important to the Insurance Industry In order to minimise risk it s essential for Insurers to be able to recommend the fitting

More information

Guide For Owners, Agents and Managers of HMOs

Guide For Owners, Agents and Managers of HMOs Guide to Fire Safety in Houses in Multiple Occupation This guide outlines the fire safety provisions recommended for HMOs in Hertfordshire and is based upon the national guidance produced by LACORS. Guide

More information

What locks do I have Timber Doors

What locks do I have Timber Doors What locks do I have Timber Doors Introduction Locking mechanisms on doors are varied and it can be difficult to judge whether what you have is good, bad or indifferent. This information takes you through

More information

SECTION 6. Glass Storefront Doors:

SECTION 6. Glass Storefront Doors: SECTION 6 Glass Storefront Doors: Table of Contents 3070 Storefront Door System Description & Dimensions 6070 Storefront Door System Description & Dimensions Door Leaf Detail Optional 10 Bottom Rail Detail

More information

MEANS OF EXIT / ESCAPE / EGRESS SELF INSPECTION CHECKLIST

MEANS OF EXIT / ESCAPE / EGRESS SELF INSPECTION CHECKLIST OPTIONAL INFORMATION Name of School: Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: MEANS OF EXIT / ESCAPE / EGRESS Guidelines: This checklist covers some of the regulations

More information

SWIMMING POOL, SPA, & HOT TUB GUIDELINES

SWIMMING POOL, SPA, & HOT TUB GUIDELINES SWIMMING POOL, SPA, & HOT TUB GUIDELINES Pool permit cost is based on the total value of the project. See Permit Fee Schedule Table 1A. A. Adopted construction codes and installation requirements 1. 2015

More information

LONDON BOROUGH OF BROMLEY STANDARDS FOR HOUSES IN MULTIPLE OCCUPATION (HMO) INTRODUCTION

LONDON BOROUGH OF BROMLEY STANDARDS FOR HOUSES IN MULTIPLE OCCUPATION (HMO) INTRODUCTION LONDON BOROUGH OF BROMLEY STANDARDS FOR HOUSES IN MULTIPLE OCCUPATION (HMO) INTRODUCTION 1. Minimum Standards: This document sets out the minimum standards required in HMOs located within the London Borough

More information

SKAC222 (SQA Unit Code - DD38 04) Carry out basic glazing and carpentry repairs

SKAC222 (SQA Unit Code - DD38 04) Carry out basic glazing and carpentry repairs Overview This unit is about carrying out basic repairs to windows, doors and carrying out other carpentry repairs. Manual and power operated tools are used. The purpose of the repair could be to: 1. repair

More information

Key in Knob & Key in Lever

Key in Knob & Key in Lever Key in Knob & Key in Lever We take the worry out of protecting what s valuable to you. Lockwood: no worries www.lockweb.com.au Contents 530 Series Key in Knob & Key in Lever Door Furniture Locksets 930/950

More information

DOMESTIC WINDOW SECURITY

DOMESTIC WINDOW SECURITY DOMESTIC WINDOW SECURITY A GUIDE TO THE ASSESSMENT OF SECURITY AFFORDED BY DOMESTIC WINDOWS June 2013 This guide has been written by BRE Global in partnership with the Centre for the Protection of National

More information

Cluster Box Units. (CBU s) 3300 Series CBU Door Sizes. Fully Integrated Parcel Lockers CLUSTER BOX UNITS FRONT LOADING. continued on pages 7-11

Cluster Box Units. (CBU s) 3300 Series CBU Door Sizes. Fully Integrated Parcel Lockers CLUSTER BOX UNITS FRONT LOADING. continued on pages 7-11 Cluster Box Units (CBU s) continued on pages 7-11 CLUSTER BOX UNITS FRONT LOADING Made of heavy duty aluminum and stainless steel hardware, Salsbury 3300 series U.S.P.S. approved Cluster Box Units (CBU

More information

NUstudenthomes PROPERTY MANAGEMENT SERVICE A GUIDE FOR LANDLORDS

NUstudenthomes PROPERTY MANAGEMENT SERVICE A GUIDE FOR LANDLORDS NUstudenthomes PROPERTY MANAGEMENT SERVICE A GUIDE FOR LANDLORDS NUstudenthomes Student Services Newcastle University King s Gate Newcastle upon Tyne NE1 7RU Tel 0191 208 3333 WHAT IS THE NUstudenthomes

More information

- 5 - Table1. Maximum Compartment Volumes

- 5 - Table1. Maximum Compartment Volumes - 5 - Part II - SPECIFIC REQUIREMENTS 5. Compartmentation 5.1 Every building should be divided into compartments by walls and floors to inhibit the spread of fire. 5.2 Compartment walls, compartment floors,

More information

Fire Safety Management Strategy 2015-2018

Fire Safety Management Strategy 2015-2018 Fire Safety Management Strategy 2015-2018 Introduction This strategy is a plan and method of approach to how Medway Council Housing Services (the council) will both continue to meet our statutory obligations

More information

anatomy of a window lintel architrave inner staff bead top rail lintel upper sash glazing bar meeting rails horn pane lower sash reveal

anatomy of a window lintel architrave inner staff bead top rail lintel upper sash glazing bar meeting rails horn pane lower sash reveal windows introduction Windows make a vital contribution to the character and appearance of historic buildings.the insertion of modern windows can completely ruin the look of a traditional building and considerably

More information

For use by landlords of small premises Premises Address

For use by landlords of small premises Premises Address fire risk assessment For use by landlords of small premises Premises Address FIRE RISK ASSESSMENT for use by landlords of small premises Person having control of the premises: Name of landlord (if different):

More information

How. secure. is your home? www.met.police.uk

How. secure. is your home? www.met.police.uk How secure is your home? www.met.police.uk Contents Introduction....................... 1 Front door security................. 2 Back door security................. 4 Window security...................

More information

St. John s University

St. John s University St. John s University Fire Safety Plan Founder s Village Townhouses Page 1 St. John s University Fire Safety Plan Part 1-Building Information Section Founder s Village Townhouses 8000 Utopia Parkway Jamaica

More information

Tested to BS 6375: Part 1: 1989 and achieved a weathertightness classification of 2000 Pa (Special)

Tested to BS 6375: Part 1: 1989 and achieved a weathertightness classification of 2000 Pa (Special) THE B6 GLAZING SYSTEM GLAZING SYSTEMS FOR SEPTEMBER 2013 THE B6 HEEL BEAD SEAL SECURITY GLAZING SYSTEM Page 1 DESCRIPTION The B6 Heel Bead Seal Security Glazing System is suitable for installing all types

More information

Crime Prevention through Environmental Design (CPTED) - Checklist

Crime Prevention through Environmental Design (CPTED) - Checklist Crime Prevention through Environmental Design (CPTED) - Checklist * Where relevant, each item is to be shown on the architectural plans. A description of how the development complies, together with the

More information

Droveway ARCHITECTURAL SERVICES. Disability Access Audit. Sample Gospel Hall. 22 September 2005. For

Droveway ARCHITECTURAL SERVICES. Disability Access Audit. Sample Gospel Hall. 22 September 2005. For 22 September 2005 Disability Access Audit For Droveway ARCHITECTURAL SERVICES Droveway House 11 Lilac Avenue, Streetly Sutton Coldfield West Midlands B74 3TH Tel : 0121 352 0150 www.droveway.co.uk Page

More information

Narrow stile lock 1314

Narrow stile lock 1314 3 2 4 6 6 1 3 2 4 4 5 3 2 4 3 5.... ( (. ). ) 11 12 5 3 5 4 8 1 6 20 8.5 6.5 19 Backset 15 3 5 2 1 5 2 5 5 0 8 9 2 8 1 1 21-1mm 12 8 24 1 6 8 1 ( 9 2 5 ) ) ). ) Narrow stile lock 1314 CE EN 12209 2 4 5

More information

Housing Act 2004 Regulatory Reform (Fire Safety) Order 2005 Fire Safety in Purpose-Built Flats Have you taken sufficient action?

Housing Act 2004 Regulatory Reform (Fire Safety) Order 2005 Fire Safety in Purpose-Built Flats Have you taken sufficient action? Housing, Culture & Enterprise Private Sector Housing Hove Town Hall (Room 217) Norton Road Hove BN3 3BQ Telephone: (01273) 293156 Fax No: (01273) 292452 Email: psh@brighton-hove.gov.uk D G Prichard QFSM,

More information

Security Dwellings. The Building Regulations 2010. 2015 edition for use in England* ONLINE VERSION APPROVED DOCUMENT ONLINE VERSION

Security Dwellings. The Building Regulations 2010. 2015 edition for use in England* ONLINE VERSION APPROVED DOCUMENT ONLINE VERSION The Building Regulations 2010 Security Dwellings APPROVED DOCUMENT Q Q1 Unauthorised access 2015 edition for use in England* The 2015 Edition This approved document supports requirement Q1 of Schedule

More information

Area of Rescue Assistance Communication System ADA Code Applicable excerpts:

Area of Rescue Assistance Communication System ADA Code Applicable excerpts: Area of Rescue Assistance Communication System ADA Code Applicable excerpts: CONTENTS (Guidelines and Definitions) Page 1 Area of Rescue Assistance Requirements Page 2 Emergency Communication Equipment

More information

These instructions will show you how to install an internal door into a non-loadbearing partition wall. The instructions are split into three parts.

These instructions will show you how to install an internal door into a non-loadbearing partition wall. The instructions are split into three parts. No 8 in the series of 'How to' brochures produced by PlaceMakers, New Zealand How to Frame and Hang a Door These instructions will show you how to install an internal door into a non-loadbearing partition

More information

Charter Township of Shelby Harry Reese Building Director

Charter Township of Shelby Harry Reese Building Director Charter Township of Shelby Harry Reese Building Director Phone: (586) 731-5969 52700 Van Dyke Fax: (586) 803-2099 Shelby Township, MI 48316-3572 E-mail: building@shelbytwp.org OUTLINE PROCEDURES FOR PRIVATE

More information

For use by landlords of small premises Premises Address

For use by landlords of small premises Premises Address fire risk assessment For use by landlords of small premises Premises Address FIRE RISK ASSESSMENT for use by landlords of small premises Person having control of the premises: Name of landlord (if different):

More information

Security steel door dw 52-1 Teckentrup DF WK 2 optionally with glazing/ventilation grille

Security steel door dw 52-1 Teckentrup DF WK 2 optionally with glazing/ventilation grille Security steel door dw 52-1 Teckentrup DF WK 2 optionally with glazing/ventilation grille Text example Compile and tender according to requirements. Please refer to technical data below for respective

More information

Walking and Working Surface Checklist:

Walking and Working Surface Checklist: Walking and Working Surfaces Purpose: This information is presented to improve the level of safety in our operations, and to inform you that we will comply with the OSHA Standard 29 CFR 1910.23. Responsibility:

More information

HMMA 830 HARDWARE SELECTION FOR HOLLOW METAL DOORS AND FRAMES HOLLOW METAL MANUAL -02 NAAMM STANDARD METAL DOORS & FRAMES NAAMM 01 NAAMM 01

HMMA 830 HARDWARE SELECTION FOR HOLLOW METAL DOORS AND FRAMES HOLLOW METAL MANUAL -02 NAAMM STANDARD METAL DOORS & FRAMES NAAMM 01 NAAMM 01 HOLLOW METAL MANUAL NAAMM STANDARD HMMA 830-02 METAL S & FRAMES 8d NAAMM 01 02 HARDWARE SELECTION FOR HOLLOW METAL S AND FRAMES NAAMM 01 02 8d METAL S & FRAMES A Division of HOLLOW METAL MANUFACTURERS

More information

CLEAR-DIVISIONS APERTO

CLEAR-DIVISIONS APERTO CLEAR-DIVISIONS Introduction: The following three (3) part specification offers the Standard and Optional features for the CLEAR-DIVISIONS moveable glass wall system. The yellow highlighted areas in the

More information

Eggers meticulously-crafted door frames are rivaled only by their beauty, quality and lasting performance. Turning nature s beauty into works of art

Eggers meticulously-crafted door frames are rivaled only by their beauty, quality and lasting performance. Turning nature s beauty into works of art D O O R F R A M E S Eggers meticulously-crafted door frames are rivaled only by their beauty, quality and lasting performance. Turning nature s beauty into works of art D O O R F R A M E S Eggers Industries

More information

Wren Kitchens Installation Tips... 3. Carefully check your kitchen delivery... 4. Measuring out and marking up... 5. Fitting the base cabinets...

Wren Kitchens Installation Tips... 3. Carefully check your kitchen delivery... 4. Measuring out and marking up... 5. Fitting the base cabinets... tra 1 Index Wren Kitchens Installation Tips... 3 Carefully check your kitchen delivery... 4 Measuring out and marking up... 5 Fitting the base cabinets... 6 Fitting the corner cabinets... 7 The 972mm or

More information

Can you design a frameless shower enclosure that doesn't leak?

Can you design a frameless shower enclosure that doesn't leak? Can you design a frameless shower enclosure that doesn't leak? With proper design and installation frameless shower enclosures should not have any problems with water leakage, but they are not 100 percent

More information

EXIT HARDWARE. Uniclass L418184. CI/SfB (31.59) Xt7 VERSION: AUGUST-11. An ASSA ABLOY Group brand

EXIT HARDWARE. Uniclass L418184. CI/SfB (31.59) Xt7 VERSION: AUGUST-11. An ASSA ABLOY Group brand EXIT HARDWARE The safe choice in eiting. High performance, high traffic devices that provide egress efficiency, freedom of movement and robust security. Uniclass L418184 VERSION: AUGUST-11 CI/SfB (31.59)

More information

Guide to Houses in Multiple Occupation Self Contained Flats

Guide to Houses in Multiple Occupation Self Contained Flats Guide to Houses in Multiple Occupation Self Contained Flats Kitchens Bathrooms Fire Safety Room Sizes Toilets HMO self contained flat std0 Version 4 201106 INTRODUCTION GENERAL INFORMATION The Housing

More information

HMMA 810 HOLLOW METAL DOORS HOLLOW METAL MANUAL -87 NAAMM STANDARD FOURTH EDITION METAL DOORS & FRAMES NAAMM 2 NAAMM 2 METAL DOORS & FRAMES

HMMA 810 HOLLOW METAL DOORS HOLLOW METAL MANUAL -87 NAAMM STANDARD FOURTH EDITION METAL DOORS & FRAMES NAAMM 2 NAAMM 2 METAL DOORS & FRAMES HOLLOW METAL MANUAL NAAMM STANDARD HMMA 810-87 8d METAL DOORS & FRAMES NAAMM 2 87 HOLLOW METAL HOLLOW METAL DOORS FOURTH EDITION NAAMM 2 87 8d METAL DOORS & FRAMES A Division of NATIONAL ASSOCIATION OF

More information

RADAR. 227 www.ncdirect.co.uk

RADAR. 227 www.ncdirect.co.uk RADAR solutions RADAR RADAR Key System 228 RADAR Lockset 229 RADAR Cover Plate 229 RADAR Padlock 230 RADAR Automatic Toilet Entry System 231 RADAR Ramp 231 RADAR Ramp Sign 231 227 www.ncdirect.co.uk RADAR

More information

Sliding and Folding Door Fittings Sliding Door Accessories

Sliding and Folding Door Fittings Sliding Door Accessories Sliding door lock Toplock For 1- and 2-leaf sliding doors Suitable for toughened safty glass and laminated sheet glass Suitable for DIN left and DIN right Max. weight per door leaf 120 kg For glass thickness:

More information

Premier & Deluxe 3-Season Room Sliding Glass Door

Premier & Deluxe 3-Season Room Sliding Glass Door DTSSGD-11 Premier & Deluxe 3-Season Room Sliding Glass Door Installation Instructions Screen Door Seal Left Side Track Top Track Assembly Right Side Track Right Side Trim Sliding Glass Door Sliding Screen

More information

STANDARD SPECIFICATION. for. Plumbing, Heating, Hot Water, Cold Water & Electrical work. Sussex Lodge London W2 & 16 Stanhope Terrace London W2

STANDARD SPECIFICATION. for. Plumbing, Heating, Hot Water, Cold Water & Electrical work. Sussex Lodge London W2 & 16 Stanhope Terrace London W2 STANDARD for Plumbing, Heating, Hot Water, Cold Water & Electrical work undertaken by owners within the building known as Sussex Lodge London W2 & 16 Stanhope Terrace London W2 BPME Consulting Engineers

More information

Planet Frameless Glazing. Planet 20 frameless glass swing door

Planet Frameless Glazing. Planet 20 frameless glass swing door Planet Frameless Glazing Planet 20 frameless glass swing door Contents Introduction Pg 2 Planet 20 - Single Glazing Pg 3-7 Planet 100 - Double Glazing Pg 8-12 Joint Options Pg13 Sectional Drawings for

More information

A Guide to Fire and Security Protection in Multi-Occupied Residential Properties

A Guide to Fire and Security Protection in Multi-Occupied Residential Properties A Guide to Fire and Security Protection in Multi-Occupied Residential Properties Advice for Property Owners, Managers and Contractors Revision 2015 Foreword HOMESTAMP is a partnership consortium with an

More information

Fire-Rated Glass and Glazing START

Fire-Rated Glass and Glazing START Fire-Rated Glass and Glazing START www.pilkington.com/fire Fire-Rated Glass and Glazing Pilkington Fire Protection Glass North America 946 Kane Street, Suite A Toledo, OH 43612 Provider Number: J200 Course

More information

WINDOW AND DOOR REPLACEMENT REQUIREMENTS

WINDOW AND DOOR REPLACEMENT REQUIREMENTS WINDOW AND DOOR REPLACEMENT REQUIREMENTS Should you have any questions after reading the following information, please call the Building Inspection Department at 651-439-4439 to discuss the topics of concern.

More information

KITCHENS. Tip PAGE 1 FITTING YOUR KITCHEN GUIDE. How to mark out a kitchen. Tools required for installing a kitchen STEP ONE STEP TWO STEP THREE

KITCHENS. Tip PAGE 1 FITTING YOUR KITCHEN GUIDE. How to mark out a kitchen. Tools required for installing a kitchen STEP ONE STEP TWO STEP THREE FITTING YOUR KITCHEN GUIDE How to mark out a kitchen PAGE 1 Before starting on the installation, measure 870mm from the lowest point of the floor and mark a datum line around the room to indicate where

More information

How To Ensure Fire Safety

How To Ensure Fire Safety Additional Guidance Agreed Between & In respect of A Guide to Fire Safety Standards for Residential Properties in Bedfordshire (Based on LACORS National Standards for HMOs and CLG Fire Safety Risk Assessment

More information

LPCB Red Book Listed Products and Passive Fire Protection Installer Schemes Answering the needs of the market

LPCB Red Book Listed Products and Passive Fire Protection Installer Schemes Answering the needs of the market LPCB Red Book Listed Products and Passive Fire Protection Installer Schemes Answering the needs of the market Ian Stewart Passive installer scheme manager September 2011 Introduction to BRE Global Research,

More information

DIVISION 08 70 00 HARDWARE FORMAT 1. Technical specifications content and numbering system shall be based on 2004 CSI MasterFormat.

DIVISION 08 70 00 HARDWARE FORMAT 1. Technical specifications content and numbering system shall be based on 2004 CSI MasterFormat. FORMAT 1. Technical specifications content and numbering system shall be based on 2004 CSI MasterFormat. BASIS OF DESIGN 1. BGSU Design Standards shall not replace fully developed, project and market specific

More information