FIRE DOORS - GENERAL SPECIFICATIONS / EMPLOYERS REQUIREMENTS (ERs) & QUICK OVERVIEW
|
|
|
- Samson Lambert
- 9 years ago
- Views:
Transcription
1 Fire Safety Technical Guide FIRE DOORS - GENERAL SPECIFICATIONS / EMPLOYERS REQUIREMENTS (ERs) & QUICK OVERVIEW Fire Door Provision In UCL Buildings - what you need to know: Not Acceptable Opening direction - fire doors on circulation routes NOT opening in the direction of escape; Double swing fire doors - in locations other than doors forming a mid-corridor smoke break; Inner Rooms - doors to Inner Rooms not provided with Vision Panels; Vision Panels (VP) - NOT providing VP in doors to laboratories, kitchens and areas where hazardous items such as chemicals or glassware pass through; Perko fittings - NOT normally acceptable on standard doors (but acceptable on ½ leafs due to size restrictions); Air Transfer Grilles / Letter boxes - fire doors should not have any grilles or letter boxes etc. where no alternative to be discussed with UCL Fire Safety Manager; Mandatory Signs - blue door signs must be provided for all fire doors as a legal instruction (see table below); All Laboratory and Sleeping Accommodation to have Fire Doors [FD30(S)SC]; Small Leafs - fire doors with ½ leaves to be fitted with a self-closing device either using an overhead unit where practical or Perko type unit for smaller leafs; MIP Access - auto opening devices for Mobility Impaired Persons (MIP) on certain fire doors locations NOT acceptable - See UCL technical note TN001; Clear Pyro Fire Glazing - identification is by means of each glass sheet provided with an Acid Etching in the corner of the pane giving the trade name & marked with BS 476 Part 22 - if acid etched trade name / BS standard NOT visible then the UCL Fire Safety Manager will not accept the glazing as FRG - and it will need to be replaced for correct specification and clear identification; Acceptable Vision Panels - all doors on main traffic and circulation routes, corridors, lobbies or stair enclosures to be provided with Vision Panels (VP); Inner Rooms - generally doors to Inner Rooms should be provided with VP; Smoke Seals - recommended that the smoke seals fitted to all new & upgraded fire doors are the brush type and NOT rubber blade type; Security Doors (SR2/SR3/SR4) - fire rated use Stafford Bridge Doors (see below); Security Doors (SR2/SR3/SR4) - fire rated use ASSA Abloy Doors also (see below); Definition of a Fire Door - a door assembly, which is designed to hold back fire and smoke for a designated period and has been tested under conditions for door assemblies described in British Standard 476 Part 22; Fire Door Guidance - British Standard (Code of Practice for Fire Door Assemblies). Date Last Amended: Dec 15 1.
2 Contents: Fire doors provision in UCL buildings - what you need to know: General Information Fire Doors (General) Where fire doors are generally required: Halls of Residences - where fire doors are generally required: Fire resisting Door Widths and Means of Escape: UCL Design Requirements / Criteria for Fire Doors: Self-Closing (SC) Devices Intumescent Materials: Air Transfer Grilles: Security and Fire Rated (Croydon) Door Sets Ironmongery Glazing in Fire Doors General View of a Fire Door and Associated Furniture Approved Document M - The Building Regulations General Information 1.1. Fire Door Key Key: Description: Key: Description: FD30 A Fire Door with 30 minutes Integrity properties (also shown as FD30) and complete with intumescent seals FD60 A Fire Door with 60 minutes Integrity properties (also shown as FD60) and complete with intumescent seals (S) Smoke Seals (use brush type as generally found to wear better than rubber blade types) SC Self-closing device complying with BS EN 1154: Door Closers FRG 30 / 60 Fire Resisting Glazing - 30 minutes Resistance including integrity (FRG30 or FRG60) Fire Resisting Glazing integrity and insulation (FRG30/30) or (FRG60/60) FD30(S)S C & VP FD30(S)SC&VP - Fire Door 30 or 60 (Smoke Seals) Self Closing & Vision Panel required VP Vision Panel - required (if within a fire door then glazing must meet FRG 30/60) PB Push Bar - emergency opening device complying with BS EN Fire Door Signs - all fire doors MUST be signed using one of the following standard signs (as a minimum it is recommended 80 mm x 80 mm Ridged Plastic signs in size with 4 x screw holes) but, others styles may be provided appropriate to door design & surfaces: Sign, Colour & Pictogram Description, Uses and Conventions 1. Fire Door Keep Shut / Closed - positioned at eye level, on both faces of each fire doors leaf that are fitted with a self-closing device - include any ½ leafs which should also be signed in addition to the main door leaf. Note - on fire rated glazed partitions & doors, FDKS signs may not be practicable or visually acceptable - suggest FDKS glazed manifestation used instead. 2. Fire Locked Shut - used on fire doors that are not fitted with self-closing devices (for example cleaner s cupboard, some types of stores, plant rooms & service risers) - sign fixed to outer door face, at eye level. Date Last Amended: Dec 15 2.
3 3. Automatic Fire Door Keep Clear - used on doors connected to fire door hold open devices that release the doors on activation of the fire alarm system. Signs to be placed on the visible open leaf at eye level when the door is held open by device; this is to avoid obstructing the fire door on being released automatically. 3a. Provide a fire door keep shut sign on the door leaf facing to the wall at eye level when held open Fire Doors (General) 2.1. Where fire doors are generally required: All doors to escape stair enclosures (both internal & external and protected fire routes); Office & reception accommodation particularly if off stairs and single escape routes etc. (note - not required where there is escape in two directions or relaxed if automatic fire detection (AFD) has been provided in each room off the dead end); Laboratory and equipment rooms; Cleaners cupboards and storage rooms; Service risers access doors and hatches; Electrical switch cupboards on Means of Escape; Plant equipment rooms and switch rooms; In some locations, information systems / server cupboards or rooms; 2.2. Halls of Residences - where fire doors are generally required: All bedrooms (including within cluster flats); All cluster flat kitchens; All studio flats; All cleaner cupboards / laundry rooms / storage rooms or cupboards; All service riser access doors and hatches; Electrical switch cupboards (particaurly on corridors and lobbies); Plant equipment rooms and switch rooms; All information systems / server cupboards or rooms; Depending on location, office & reception accommodation; Date Last Amended: Dec 15 3.
4 2.3. Fire resisting Generally, indicates that the construction is designated as capable of resisting the passage of flame and smoke, and providing insulation as defined in under the prescribed conditions of test appropriate to such construction in accordance with the current British Standard 476. FD30 doors generally should not be less than 44mm in thickness; FD60 doors generally should not be less than 54mm in thickness; 2.4. Door Widths and Means of Escape: The following guide can be used to determine the general capacities of escape routes based on clear opening door widths: Door Widths: 750 mm (absolute minimum width) 60 persons (normal risk) 850 mm 110 persons (normal risk) 950 mm (minimum width for wheelchairs) 160 persons (normal risk) 1050 mm 220 persons (normal risk) Doors greater than 1050 mm wide Numbers of persons able to pass through: 1050mm = 220 persons then Add 5mm per person on width greater than 1050mm (e.g. door width of 1500mm mm = 450mm (450 5mm = 90) = max 310 persons An additional 75mm should be allowed for each additional 15 persons (or part thereof 15); 2.5. UCL Design Requirements / Criteria for Fire Doors: All fire-resisting doors should be: (a). (b). (c). (d). Close fitting to the frame with a maximum gap of 5mm, but 3mm is the accepted working gap; Hung by a minimum of 1½ pairs of all metal hinges with a melting point of not less than 800 C (both nylon and nylon bushed hinges are unacceptable); Fitted with an effective self-closing device that is capable of closing the door tight against the stop, overcoming the resistance of any latch or lock provided; Generally - all fire doors on circulation routes should open in the direction of escape and but rebated to ensure intumescent and smoke seals work correctly: (1). Doors should Not be double swing in stairs or circulation areas; Date Last Amended: Dec 15 4.
5 (2). The exception is doors forming a mid-corridor smoke break; these may be double swing meeting [FD30(S)SC]. (e). Vision Panels (VP) (Note - these recommendations may be in addition to current regulations / guidance): (1). All doors on main traffic and circulation routes, corridors, lobbies or stair enclosures etc., must be provided with Vision Panels for general safety (regardless of being fire doors or not but VPs should be fire resisting embedded with a fire door); (2). All doors to laboratories, kitchens and areas where hazardous items such as chemicals or glassware pass through the doors regularly are also provided Vision Panels for general safety; (3). Inner Rooms - doors to Inner Rooms should be provided with Vision Panels; (4). Exceptions to providing Vision Panels - where there is a need for privacy such as WCs / sleeping accommodation / rooms used for Patients / store rooms / dark rooms or light sensitive equipment rooms some specialist laboratory space etc. (5). Disability Access - require vison panels (see approved Document Part M, The Building Regulations below); (f). (g). Smoke Seals - fire doors MUST be fitted with intumescent and cold smoke seals / brushes ; For UCL projects cold smoke seals fitted to all new & upgraded fire doors are the brush type where ever possible and not rubber blade type. Rubber blade type, appear from experience, not to be as durable and long lasting in maintenance terms, as the brushes Self-Closing (SC) Devices Where self-closing devices are specified, then standard overhead units are to be used meeting the latest edition BS6459: Door Closers. Door closers and accessories should comply fully with the latest edition BSEN1154-Building hardware - controlled door closing devices. Note the strength and features of the self-closer will depend of door location and usage: (a). (b). (c). the door is subject to other factors such as air pressure, draughts, heavy traffic use, abusive treatment and use by elderly, infirm or disabled; whether the SC unit fitted to the door is to be latched or unlatched in its closing movement; whether smoke or other seals are to be fitted to the door set; Date Last Amended: Dec 15 5.
6 (d). Fire doors with ½ leaves - where fire doors are provided with a ½ leaf then these should be also self-closing either using an overhead unit where practical or using a Perko type fitting in smaller leafs, as necessary. (1). Perko fitting are not normally acceptable on UCL doors with the exception of ½ leafs due to size restrictions; (2). Perkomatic / Powermatic concealed door closers are acceptable for certain applications where an overhead SC unit is not practical due to local restrictions or for ½ leafs fitted to fire doors for self-closing; (e). Door Frames - the selection and installation of doorframes is as important as the door itself. Where purpose built frames are installed they should be matched with the recommended door as the fire resistance of one may depend on design features of the other. Any gaps between the rear of the frame and the wall must be infilled with mineral wool, plaster or intumescent paste to meet FR Intumescent Materials: Door edges are the part of a door-set most susceptible to penetration by fire. The pressure of a developed fire drives hot gases between the door and frame leading to loss of integrity. Traditionally this weakness was countered using a large doorstop. However, this method relied on a very close fitting door with a gap of less than 3mm between door and frame. The modern solution to this problem relies on the use of intumescent materials applied or set into the edge of doors or doorframes opposite the door edge. Intumescent materials expand at around 100 C to several times their original size and fill the gap between the door and the frame. An intumescent strip can be fitted either in the frame or in the door edge itself and must follow the centre line of the door edge; on no account must an intumescent strip be fitted to the door stop as the door will be forced open when the strip expands. Several points should be considered in their use: They are applied along the top edge and sides; intumescent material is not required along the bottom edge; There are several types of intumescent material and it is important to use the correct type as specified by the manufacturer or the door-set. The differing types are not interchangeable; Where a door is required to have intumescent strips and flexible seals this is best achieved by using a single strip combining both functions; Date Last Amended: Dec 15 6.
7 On fire doors up to 30 minutes fire resistance, it is acceptable to interrupt the intumescent strip for hinges or latches; On fire doors exceeding 30 minutes fire resistance, where double intumescent strips are required, one of the strips must be continuous the other may be interrupted; The long-standing requirement to provide oversize doorstops on fire doors is no longer applicable to doors with edges fitted with intumescent protection. A 12mm planted stop fixed with nails is acceptable in this case; Intumescent materials must not be reduced in size during installation by planing or sawing. In particular, installers should be aware that some are fitted beneath veneers or door trims; 2.8 Air Transfer Grilles: Air transfer grilles in fire doors will not only allow air to pass through but smoke and fire also. It is, therefore, essential that whatever fire door a transfer grille is fitted, the fire and smoke resisting qualities of the door must not be reduced as a result: (a). (b). Where a fire door is fitted purely to resist the passage of fire and not to resist the combination of fire and smoke, a heat activated fire damper is usually acceptable. These are normally of the intumescent honeycomb or fusible strut type of operation. Where a fire door is fitted to protect an internal escape route and especially if the door has Smoke Seals fitted, the only air transfer grille permitted is one that resists the passage of smoke as well as fire. This type of damper is electro-magnetically released by the activation of a smoke detector located on the risk side(s) of the door [e.g. a Gilbert Damper]. Air transfer grilles in fire doors should not be fitted higher than 1000 mm from the floor threshold Security and Fire Rated (Croydon) Door Sets UCL has standardised its requirements for those areas requiring security doors (SR2/SR3/SR4) with a fire rating using Croydon Security Doorsets, which are available from Stafford Bridge Doors ( who offer a range of security doorsets fully certified to the Loss Prevention Certification Board s LPS 1175 standard. See attached guidance sheet. ASSA- ABLOY also provide SR Security and Fire rated Doors, which meet UCL locking and security requirements - security door specifications need to be discussed with UCL Access Systems in the first instance. Date Last Amended: Dec 15 7.
8 4.0. Ironmongery 4.1. Ironmongery - provide strong and fully functioning ironmongery that is approved for use with fire doors. Essential Ironmongery - items vital to achieve the fire resistance performance of a fire door assembly; Non-Essential Ironmongery - items which are not required to achieve the fire resistance performance of a fire door assembly but which if fitted may affect the performance; Lock - a mechanism combining, in one case, a spring bolt and a dead bolt operated respectively by handle and a removable key; Latch - a device, operable from both sides and generally self engaging, for holding closed a door, gate or the like, consisting of a moveable part operated by a handle, falling by gravity or sliding or moving by means of a spring into a retaining member; D Handles - in many cases the installation of a D handle allows the tension to be released on locks to allow ease of opening - pulling a door open on a thumb turn, key or a small knob is difficult and not acceptable on an escape route where the door needs to open inwards without a suitable handle Locks - locking devices fitted with Thumb Turns (known as Emergency Fastenings(EF)) should always be used on the inside leaf in direction of escape, unless other types of escape furniture is to be provided; or no locking furniture at all designated 'Free From Fastenings' (FFF) for Means of Escape purposes Glazing in Fire Doors 5.1. If a Vision Panel (VP) or glazing is required in a fire door or partition then the glazing has to be Fire Resisting Glazing of 30 or 60 minutes integrity (FRG30/60) meeting BS 476: Part 22. Note 1: Note 2: Clear Fire Glazing - it is extremely important to be able identify clear glazing as fire glazing (Pyro) this is generally done by ensuring each glass sheet is provided with a visible Acid Etching giving the trade name in the corner of the pane and marked with BS 476: Part 22. If the acid etched trade name or BS 476: Part 22 information is NOT visible then the UCL Fire Safety Manager will not accept the glazing as FRG30 - the glazing will be required to be replaced for correct specification and visible etching. Date Last Amended: Dec 15 8.
9 Note 3: Safety Glazing - glazing that is marked with BS 6206: 1981 / BS 6262 Series (or latest issue) is not fire resisting glazing. It is often is mistaken for FRG30 and the UCL Fire Safety Manager will require this glazing to be replaced for FRG where necessary Glazing to FRG30 in design, imbedded in intumescent paste rebates etc. as per manufactures specification Fanlights above fire doors are to be sealed so they cannot be opened and the construction to meet either FRG30 or FR30, as required General View of a Fire Door and Associated Furniture Date Last Amended: Dec 15 9.
10 UCL Fire Technical Note - TN Approved Document M - The Building Regulations 7.1. General guidance on Vision Panel dimensions, however if Vision Panels form part of a fire resisting door set then the area of the glass may be determined by the fire resistance properties and the manufactures s specifications etc All door glazing on traffic routes and public areas should be Safety Glazing Standard, in addition to any fire resistance required. Date Last Amended: Dec Issued by - Fire Safety Manager, UCL Estates, Gower Street, London, WC1E 6BT - this guide is to be regarded as a general statement of requirements and is in addition to relevant British Standards or any other instructions received from the Local Fire or Building Control Authorities.
11 SBD /05 Stafford Bridge Doors Ltd Bedford Road, Pavenham Bedfordshire MK43 7PS T +44 (0) F +44 (0) E [email protected] W Quick Reference Guide Number of Leaves Door Finish Lock Fitting Vision Panels Safety Security Door Range Single Double Timber Steel Faced Concealed Surface Fire Rating FD30 FD60 FD90 Blast Ballistics BS EN 1522 Panic Emergency BS EN 1125 BS EN 179 ACPO Secured by Design LPCB LPS 1175 CLASS Bedford Hendon Rating 2 Class 1 Sandhurst FB1 Rating 3 Class 2 Croydon * FB1 Rating 3 Class 2 Wilton FSG FB4-FB7 Rating 4 Class 3 Halton FSG FB4-FB7 Rating 4 Class 3 Whitehall FSG FB4-FB7 Rating 5 ø Class 4 Cranwell FSG FB4-FB7 Rating 5 ø Class 4 FD30, FD60 30-, 60- & 90-minute fire resistant options on single, & FD90 double, inward & outward opening doors BS EN Latest European Panic Exit standard BS EN Latest European Emergency Exit standard BS EN 1522 FB1 to FB7; hand gun and rifle round (in order of magnitude). FSG; solid slug shot gun ammunition LPCB - Loss Prevention Certification Board ACPO - Association of Chief Police Officers Blast - Ensures blast protection to the requirements of HM Government explosion test standard for protected spaces * Approved manufacturer of HM Government Croydon Security Doorset Currently under test ø Aimed at LPS 1175 but as yet untested A member of LPS Loss Prevention Standard for Forced Entry N.B. Our doorsets are regularly tested and assessed - refer to current certificates 516a for full list of product conformity Certificate No. TT-COC-1818 Assessed to ISO 9001:2000 Certificate No Police Preferred Specification SECURING THE PEOPLE WHO SECURE THE COUNTRY
GENERAL FIRE SAFETY TERMS & DEFINITIONS
UCL Fire Technical Note - TN006 Fire Safety Technical Guide GENERAL FIRE SAFETY TERMS & DEFINITIONS Reference: BS4422-2005 Fire Safety Vocabulary - for further information and definitions BS EN ISO 13943-2000:
Fire Doors Basic Guidance & Checklist
Fire Doors Basic Guidance & Checklist Introduction Fire doors and all passive fire protection products play a unique role in fire safety by containing a fire to a single compartment of a building and therefore
Fire doors guidance. Safety and Health Services. Document control information. Date issued: January 2011. Version: 2. Previous review dates: 2011
Document control information Fire doors guidance Published document name: Firedoors-gn.pdf Date issued: January 2011 Version: 2 Previous review dates: 2011 Next review date: Related documents: Governing
The Role of Fire Doors. BWF-Certifire Fire Door and Doorset Scheme
The Role of Fire Doors BWF-Certifire Fire Door and Doorset Scheme Fire doors today s agenda 1. Fire doors are essential in passive fire protection A requirement in compartmenting a building Protecting
Code of Practice for fire resisting metal doorsets
COP 1005 Code of Practice for fire resisting metal doorsets Scope The aim of this document is to provide guidance on the best practice for, and a better understanding of, hinged or pivoted fire resisting
Standard Door Specification
Element General Requirement To be defined in the project brief but should meet Building Regulations. All doors to be a minimum of 30 minute fire rated and must comply with all relevant UK legislation and
Guidance on loft conversions in two-storey houses
Guidance on loft conversions in two-storey houses Technical guidance for building control surveyors, designers and installers 01 Guidance on loft conversions in two-storey houses Technical guidance for
Building Control Guidance Note
Issued 01/01/13 Rev Page 1 of 5 If you intend to convert an existing loft space into additional rooms you will need to apply for Building Regulation Approval. You may also need Planning Permission if you
Loss Prevention Standard
Loss Prevention Standard : ISSUE 3.0 Requirements for the LPCB Approval and Listing of Companies Undertaking the Maintenance and Repair of Doorsets, Shutters, and Active Smoke/Fire Barriers This standard
ModuSec. Secure and efficient IT room solutions. Turnkey Modular Construction Fast clean build to any size or shape
ModuSec Secure and efficient IT room solutions Turnkey Modular Construction Fast clean build to any size or shape Room in room Standalone external build Transportable Modusec SR Options Modusec SR Options
Office of the State Fire Marshal. Fire Rated Doors
Office of the State Fire Marshal Fire Rated Doors Fire Rated Doors These doors serve a purpose. They are manufactured in a way that is to help reduce the spread of fire and smoke. Fire rated doors allow
Basic Fire Door Requirements
TECHNICAL DATA SERIES S D I 118-01 Basic Fire Door Requirements 2001 Steel Door Institute STEEL DOOR INSTITUTE 30200 DETROIT ROAD - CLEVELAND, OHIO 44145 Technical Data Series SDI 118-2001 Basic Fire Door
Relevant British, European and International standards
Relevant British, European and International standards BS 1245:1975 Specification for metal door frames (steel) BS 3621:2007 + A1:2009 Thief resistant lock assemblies - Key egress BS 476-20:1987 Fire tests
Fire Doors The Role of a Fire Door
Fire Doors The Role of a Fire Door BWF-Certifire Fire Door and Doorset Scheme Presented by John Fletcher John Fletcher Consulting Ltd. Fire doors main messages 1. Fire doors are essential in passive fire
Approved Document Q: Security
Approved Document Q: Security Requirement Q1 Unauthorised access Consultation draft September 2014 1 The approved documents What is an approved document? The Secretary of State has approved a series of
Fire precautions in dwellings. Private sector housing Providing homes building communities
Fire precautions in dwellings Private sector housing Providing homes building communities Version 3 Published by Norwich City Council August 2011 Contents Page Introduction 1 2 Types of dwellings (A) Shared
ACCESS AUDIT OF WESTPORT HOUSE
ACCESS AUDIT OF WESTPORT HOUSE Large sign on the highway to indicate the entrance to Purbeck District Council Large and wide entrance Entrance showing sign for opening times Entrance sign Main entrance
Droveway ARCHITECTURAL SERVICES. Disability Access Audit. Sample Gospel Hall. 22 September 2005. For
22 September 2005 Disability Access Audit For Droveway ARCHITECTURAL SERVICES Droveway House 11 Lilac Avenue, Streetly Sutton Coldfield West Midlands B74 3TH Tel : 0121 352 0150 www.droveway.co.uk Page
5.1. Smoke Sealing. General: The test procedure for smoke sealed doorsets is given by reference to BS476 Section 31.1.
v8 5.1 General: The test procedure for smoke sealed doorsets is given by reference to BS476 Section 31.1. The performance criteria for smoke sealed doorsets is given by reference to BS5588 (and BS9999)
- 5 - Table1. Maximum Compartment Volumes
- 5 - Part II - SPECIFIC REQUIREMENTS 5. Compartmentation 5.1 Every building should be divided into compartments by walls and floors to inhibit the spread of fire. 5.2 Compartment walls, compartment floors,
Panic & emergency exit devices
CFPA-E Guideline CFPA-E No 2:2007 - Appendix Appendix No: 1 Panic & emergency exit devices FOREWORD This Appendix offers technical solutions according to table 8.1 in the European Guide Line ""Panic &
FIRE SAFETY SIGNAGE - UCL FIRE SAFETY STANDARD
Fire Safety Technical Guide FIRE SAFETY SIGNAGE - UCL FIRE SAFETY STANDARD Fire Safety Signage - what you need to know: Prohibited or Check First! Local purchase of fire safety signs - departmental staff,
WHI 90-Minute Rated Veneered Door Frame Installation Instructions
No. 940-03-10 INSTALLATION INSTRUCTIONS 90 MINUTE RATED VENEERED DOOR FRAME DOOR REQUIREMENTS: Consult the door manufacturer to make sure that the doors are qualified for the hardware to be installed,
Property Accreditation Standards 2014/2015
Property Accreditation Standards 2014/2015 Promoting responsible renting of student housing in the city of Southampton Letting period 1st July 2014 to 30th June 2015 Version 1, 10/12/2013 All properties
Fire Resistant Systems
Fire Resistant Systems A R C H I T E C T U R A L A L U M I N I U M G L A Z I N G S Y S T E M S Fire Resistant Systems Introduction Kawneer are pleased to introduce two new comprehensive Fire Resistant
EMERGENCY LIGHTING - UCL GENERAL DESIGN GUIDANCE
Fire Safety Technical Guide EMERGENCY LIGHTING - UCL GENERAL DESIGN GUIDANCE Reference: A. British Standard 5266-1 Emergency Lighting - Code of Practice for the emergency lighting of premises; B. BS 5266-7
Composite Panel Firewall Systems
Composite Panel Firewall Systems part of the Protecting more than your business Insulated mineral fibre panels have excellent thermal and acoustic properties, ideal for factory and office partition walls.
Security steel door dw 52-1 Teckentrup DF WK 2 optionally with glazing/ventilation grille
Security steel door dw 52-1 Teckentrup DF WK 2 optionally with glazing/ventilation grille Text example Compile and tender according to requirements. Please refer to technical data below for respective
FURNITURE & FURNISHINGS - FIRE SAFETY STANDARDS
Fire Safety Technical Guide FURNITURE & FURNISHINGS - FIRE SAFETY STANDARDS 1.0. Introduction 1.1. Furniture and furnishings may significantly increase fire spread in rooms and those circulation spaces,
RADAR. 227 www.ncdirect.co.uk
RADAR solutions RADAR RADAR Key System 228 RADAR Lockset 229 RADAR Cover Plate 229 RADAR Padlock 230 RADAR Automatic Toilet Entry System 231 RADAR Ramp 231 RADAR Ramp Sign 231 227 www.ncdirect.co.uk RADAR
The risk assessment of fire damper installations
The risk assessment of fire damper installations June 2010 Paul White OVERVIEW OVERVIEW The purpose of this presentation is to highlight that fire dampers form a key part of the passive fire protection
CERTIFICATE OF APPROVAL No CF 291 SCHOTT UK LIMITED
CERTIFICATE OF APPROVAL No CF 291 This is to certify that, in accordance with TS General Requirements for Certification of Fire Protection Products The undermentioned products of Drummond Road, Stafford.
SECTION 6. Glass Storefront Doors:
SECTION 6 Glass Storefront Doors: Table of Contents 3070 Storefront Door System Description & Dimensions 6070 Storefront Door System Description & Dimensions Door Leaf Detail Optional 10 Bottom Rail Detail
Gordon Cooke BSc PhD CEng MICE MIMechE FIFireE
International Symposium on Protection of Cultural Heritage Buildings from Fire, Kyoto, April 6-7, 2003 Upgrading the fire resistance of floors and doors in heritage buildings Gordon Cooke BSc PhD CEng
Classroom Door Security & Locking Hardware
Classroom Door Security & Locking Hardware The ability to protect students and teachers while in the classroom is a high priority in all educational institutions. Many schools and school districts have
A ROAD MAP FOR YOUR CODE, SMOKE BARRIER & SMOKE PARTITION REQUIREMENTS
A ROAD MAP FOR YOUR CODE, SMOKE BARRIER & SMOKE PARTITION REQUIREMENTS International Code Council National Fire Protection Association Underwriters Laboratories Inc. 5203 Leesburg Pike, Suite 600 1 Batterymarch
CATALOGO PRODOTTI PORTONI INDUSTRIALI COIBENTATI
CATALOGO PRODOTTI PORTONI INDUSTRIALI COIBENTATI The Company Founded in 1973 by Mr Imes Tinti in association with his son Vanni Tinti. In 1999 the locksmith workshop became a modern industrial company
PROOF ONLY. Police and Fire Service Home Security & Fire Safety Checklist. Student Accommodation Security Checklist
Police and Fire Service Home Security & Fire Safety Checklist Student Accommodation Security Checklist A Self Assessment Guide for Landlords This checklist contains all the standards needed to make sure
FIRE RATED GLAZING System Guide
SYSTEM GUIDE Issue date: 05-05-2015 Expiry date: 31-12-2016 System Guide Introduction Pyropanel Developments are specialists in fire rated glazing solutions, and our systems are designed for easy installation
Fire. The Fire Installers Mate. A guide to fire alarm systems design
Fire The Fire Installers Mate A guide to fire alarm systems design BS 5839 Part 1:2002 A guide to BS 5839 Part 1:2002 Disclaimer This booklet is not intended to be a comprehensive guide to all aspects
A Complete Solution CREATING WALLS THAT DEFINE SPACE
A Complete Solution CREATING WALLS THAT DEFINE SPACE COMPANY HISTORY CLIPPER WALL Clipper partitions are part of the Saint- Gobain Group, one of the worldwide leaders in the construction products industry.
ABLOY DOOR AUTOMATICS Easy access for all types of swing doors
ABLOY DOOR AUTOMATICS Easy access for all types of swing doors Automatic door operators bring additional convenience in situations where the doors opening manually would be inconvenient or laborious. Recommended
Technical Information
Technical Information This section of the catalogue provides technical information that will help specify, install and maintain Surelock McGill devices and components. The topics are listed below: Blast
Planet Frameless Glazing. Planet 20 frameless glass swing door
Planet Frameless Glazing Planet 20 frameless glass swing door Contents Introduction Pg 2 Planet 20 - Single Glazing Pg 3-7 Planet 100 - Double Glazing Pg 8-12 Joint Options Pg13 Sectional Drawings for
Passive Fire Protection Guidance for the Fire Risk Assessor. Niall Rowan Technical Officer Association for Specialist Fire Protection
Passive Fire Protection Guidance for the Fire Risk Assessor Niall Rowan Technical Officer Association for Specialist Fire Protection ASFP has just completed a guide on what to look for when undertaking
Area of Rescue Assistance Communication System ADA Code Applicable excerpts:
Area of Rescue Assistance Communication System ADA Code Applicable excerpts: CONTENTS (Guidelines and Definitions) Page 1 Area of Rescue Assistance Requirements Page 2 Emergency Communication Equipment
CERTIFICATE OF APPROVAL No CF 388 ALLEGION (UK) LIMITED
CERTIFICATE OF APPROVAL No CF 88 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Bescot Crescent, Walsall,
Narrow stile lock 1314
3 2 4 6 6 1 3 2 4 4 5 3 2 4 3 5.... ( (. ). ) 11 12 5 3 5 4 8 1 6 20 8.5 6.5 19 Backset 15 3 5 2 1 5 2 5 5 0 8 9 2 8 1 1 21-1mm 12 8 24 1 6 8 1 ( 9 2 5 ) ) ). ) Narrow stile lock 1314 CE EN 12209 2 4 5
Services Enclosures and Protected Shafts - Maintaining Compartmentation
Introduction When a fire resisting element is used to provide fire compartmentation, every opening that allows services to pass through the element must be adequately protected by sealing, or fire stopping
ABLOY EXIT. Functional and technical descriptions Single and double leaf doors. An ASSA ABLOY Group brand
SSFN 014/2 2 ABLOY EXIT Functional and technical descriptions Single and double leaf doors An ASSA ABLOY Group brand ABLOY EXIT - EXIT PRODUCTS It is time to take the exit safety standards to a new level.
Installation Instructions
Installation Instructions READ BEFORE INSTALLING UNIT For Low Profile Window Air Conditioner INSTALLATION WARNINGS AND CAUTION Carefully read the installation manual before beginning. Follow each step
Automatic Door Selection Guide
Automatic Door Selection Guide AAADM 1300 Sumner Avenue Cleveland, OH 44115 P: 216-241-7333 F: 216-241-0105 [email protected] Automatic Door Selection Guide General: The members of AAADM manufacture an assortment
MagTek A. Aluminium Manual Attack Resistant Doors
MagTek A Aluminium Manual Attack Resistant Doors MANUAL ATTACK-RESISTANCE Gunnebo s manual attack resistant doors have been designed to satisfy the ever increasing need to protect people, property and
FIRE ALARMS SYSTEMS - UCL GENERAL INSTALLATION EMPLOYERS & REQUIREMENTS DESIGN GUIDANCE
Fire Safety Technical Guide Contents FIRE ALARMS SYSTEMS - UCL GENERAL INSTALLATION EMPLOYERS & REQUIREMENTS DESIGN GUIDANCE (Student Hals of Residences - Sleeping Accommodation) 1.0. Introduction... 1
CI/SfB. (31.59) X NOVEMBER 2003 Coburn Interior Sliding Systems
Uniclass L4181 EPIC D181 CI/SfB (31.59) X NOVEMBER 2003 Coburn Interior Sliding Systems Interior Sliding Door Gears FOR CUPBOARDS, WARDROBES, INTERIOR SLIDING AND FOLDING DOORS A comprehensive range of
SPECIFIC GUIDANCE FOR A HOUSE IN MULTIPLE OCCUPATION (HMO) CONVERTED ENTIRELY INTO SELF CONTAINED FLATS
Document F SPECIFIC GUIDANCE FOR A HOUSE IN MULTIPLE OCCUPATION (HMO) CONVERTED ENTIRELY INTO SELF CONTAINED FLATS This document is intended as a specific guide for persons who own, manage or control Houses
How To Write A Fire Risk Assessment
Fire Safety Risk Assessment This form is to aid you in carrying out a fire safety risk assessment of a property. The form is separated in to two parts: Part 1 initial assessment form and guidance notes
STAIRCASES I DOORS I WINDOWS
ARU JOINERY Timber Processing since 1994 WINDOWS DOORS STAIRCASES WINDOWS We offer timber and alu-clad windows in 3 basic varieties: CASEMENT, TILT & TURN, and SASH windows, with a vast array of design
WINDOW AND DOOR REPLACEMENT REQUIREMENTS
WINDOW AND DOOR REPLACEMENT REQUIREMENTS Should you have any questions after reading the following information, please call the Building Inspection Department at 651-439-4439 to discuss the topics of concern.
Walking and Working Surface Checklist:
Walking and Working Surfaces Purpose: This information is presented to improve the level of safety in our operations, and to inform you that we will comply with the OSHA Standard 29 CFR 1910.23. Responsibility:
Glass partitions SFB 3074
Glass partitions SFB 3074 Our facade system SFB 3074 is innovative in its design. We have made a great effort to obtain an energy effective system. The future requirements regarding the economical use
Name Of Occupancy Date. Yes No Describe
FIRE PREVENTION INSPECTION CHECKLIST For Class A Occupancy (For Assembly Buildings, Bars, Restaurants, Gyms, Churches, Arenas, Theatres or wherever people gather) Name Of Occupancy Date Physical Address
BUILDING CONTROL GUIDANCE SHEET REPLACEMENT WINDOWS AND DOORS Last updated 16/11/2010
Building Control Charnwood Borough Council Southfield Road Loughborough LE11 2TN BUILDING CONTROL GUIDANCE SHEET REPLACEMENT WINDOWS AND DOORS Last updated 16/11/2010 Page 1 of 6 PURPOSE: This Guidance
SECURITY COUNTER AND SCREEN DESIGN MANUFACTURE SUPPLY INSTALLATION
SECURITY COUNTER AND SCREEN DESIGN MANUFACTURE SUPPLY INSTALLATION Our Clients Include British Transport Police HM Prison Service NHS Vinci Construction Taylor Woodrow DVLA HMCS Hover Travel The Post Office
FIRE DETECTION AND ALARM SYSTEMS
HMO Information Sheet No 1 FIRE DETECTION AND ALARM SYSTEMS 1. Introduction When a property is in multiple occupation, the risk of fire breaking out is greater than in an ordinary single family home. Some
LONDON BOROUGH OF BROMLEY STANDARDS FOR HOUSES IN MULTIPLE OCCUPATION (HMO) INTRODUCTION
LONDON BOROUGH OF BROMLEY STANDARDS FOR HOUSES IN MULTIPLE OCCUPATION (HMO) INTRODUCTION 1. Minimum Standards: This document sets out the minimum standards required in HMOs located within the London Borough
CLEAR-DIVISIONS CENTERFOLD
CLEAR-DIVISIONS CENTERFOLD Introduction: The following three (3) part specification offers the Standard and Optional features for the CLEAR-DIVISIONS CENTERFOLD moveable The yellow highlighted areas in
All-Season Sunroom Sliding Glass Door Installation Instructions
ASRESGD-08 All-Season Sunroom Sliding Glass Door Installation Instructions Panel Frame Door Frame Left Side Foam Insulator IE241 H Bar Assembly Door Frame Top Track Panel Frame Door Frame Right Side Stationary
BASIC FIRE DOOR REQUIREMENTS TECHNICAL DATA SHEET NO. 401
BASIC FIRE DOOR REQUIREMENTS SHEET NO. 401 Fire door openings are classified by their locations in the building. The location determines the length of exposure protection required, based on the potential
SERVER ROOM CABINET INSTALLATION CONCEPTS
SERVER ROOM CABINET INSTALLATION CONCEPTS SERVER ROOM CABINET INSTALLATION CONCEPTS SERVER ROOM CABINET INSTALLATION CONCEPTS ZPAS 169 EXAMPLES OF SERVER ROOMS PROJECTS WITH ZPAS CABINETS Data Box in the
Energy Company Obligation (ECO): Technical Monitoring Questions
Energy Company Obligation (ECO) Technical Monitoring Questions v1 30/05/2013 Energy Company Obligation (ECO): Technical Monitoring Questions Under ECO suppliers are required to instruct suitably qualified
London Borough of Barnet. Fire Safety in Houses in Multiple Occupation. A Guide to Landlords
London Borough of Barnet Fire Safety in Houses in Multiple Occupation A Guide to Landlords March 2016 Contents Introduction p.3 Summary of main requirements p.3 Fire Safety Precautions p.4 Protecting the
HMMA 830 HARDWARE SELECTION FOR HOLLOW METAL DOORS AND FRAMES HOLLOW METAL MANUAL -02 NAAMM STANDARD METAL DOORS & FRAMES NAAMM 01 NAAMM 01
HOLLOW METAL MANUAL NAAMM STANDARD HMMA 830-02 METAL S & FRAMES 8d NAAMM 01 02 HARDWARE SELECTION FOR HOLLOW METAL S AND FRAMES NAAMM 01 02 8d METAL S & FRAMES A Division of HOLLOW METAL MANUFACTURERS
Building Code Clarifications - 7. Fire Resistance
Building Code Clarifications - 7. Fire Resistance 7.1 (15-12-030) Use of combustibles in Type III construction roof assemblies Code Section (15-12-030) Use of Combustibles was revised on May 17, 2000,
Base Cabinet with Self-storing Folding Doors and Floor
Usable Kitchens When designing a kitchen for use by persons with mobility impairments, especially those who use wheelchairs, careful layout of the kitchen is crucial to maintaining accessibility. People
CHARISMA SHOWER/TUB DOOR INSTALLATION INSTRUCTIONS
CHARISMA SHOWER/TUB DOOR INSTALLATION INSTRUCTIONS IMPORTANT DreamLine reserves the right to alter, modify or redesign products at any time without prior notice. For the latest up-to-date technical drawings,
Guide to Houses in Multiple Occupation Self Contained Flats
Guide to Houses in Multiple Occupation Self Contained Flats Kitchens Bathrooms Fire Safety Room Sizes Toilets HMO self contained flat std0 Version 4 201106 INTRODUCTION GENERAL INFORMATION The Housing
PHA 2000 PHB 3000 EXIT PAD
PHA 2000 PHB 000 EXIT PAD Panic Hardware in Contur Design PHA 2000 PHB 000 EXIT PAD THE MODULAR PANIC HARDWARE-SSTEM IN CONTUR DESIGN Prior knowledge of how to open the escape door is not expected. DANGER
SCHOTT PYRANOVA Planline System
Schott_050_Pyranova_E_RZ.fh8.07.005 0:50 Uhr Seite HOME T E C H The Planline system The patented glass fixing method is a clear multi- is based on a fire resistant double glazed allows quick and easy replacement
Fire-Rated Doors and Hardware. A Guide to Field Inspection
Fire-Rated Doors and Hardware A Guide to Field Inspection Foundation s Mission To promote secure and safe openings that enhance life safety Awareness To be a source of information through awareness campaign
All the above mentioned technical characteristics of the MU 2500 Thermal system indemnify its air and water tightness.
MU INTRODUCTION MU 2500 Thermal,.,,,,. The MU 2500 Thermal system can be used for doors and windows in domestic and commercial applications such as houses, villas, big complexes of flats and offices.
LPCB Red Book Listed Products and Passive Fire Protection Installer Schemes Answering the needs of the market
LPCB Red Book Listed Products and Passive Fire Protection Installer Schemes Answering the needs of the market Ian Stewart Passive installer scheme manager September 2011 Introduction to BRE Global Research,
Exit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection. OSHA Office of Training and Education 1
Exit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection OSHA Office of Training and Education 1 Introduction Fires and explosions kill more than 200 and injure more than 5,000 workers
CDW Systems Ltd Contemporary Doors & Windows
CDW Systems Ltd Contemporary Doors & Windows The comprehensive product overview A complete specification guide to CDW Systems range of Aluminium windows, doors and curtain walling for commercial and residential
Windows, French doors, folding windows, terrace doors SFB 1074 with low U-values
Windows, French doors, folding windows, terrace doors SFB 1074 with low U-values SFB 1074 is available in two versions. In the first version the profiles are insulated with 30 mm glass fibre reinforced
Sliding and Folding Door Fittings Sliding Door Accessories
Sliding door lock Toplock For 1- and 2-leaf sliding doors Suitable for toughened safty glass and laminated sheet glass Suitable for DIN left and DIN right Max. weight per door leaf 120 kg For glass thickness:
Premier & Deluxe 3-Season Room Sliding Glass Door
DTSSGD-11 Premier & Deluxe 3-Season Room Sliding Glass Door Installation Instructions Screen Door Seal Left Side Track Top Track Assembly Right Side Track Right Side Trim Sliding Glass Door Sliding Screen
AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Fire Alarm Systems Design. a guide to BS5839
AVAILABLE TO DOWNLOAD ON THE APOLLO APP a guide to Fire Alarm Systems Design BS5839 Part1:2013 The Regulatory Reform (Fire Safety) Order (FSO) became law on 1 October 2006 Legally you must comply! What
MEANS OF EXIT / ESCAPE / EGRESS SELF INSPECTION CHECKLIST
OPTIONAL INFORMATION Name of School: Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: MEANS OF EXIT / ESCAPE / EGRESS Guidelines: This checklist covers some of the regulations
Product Management - Glass ALEXA PRODUCT PRESENTATION. Region SAARC Nitin Lloyd, Product Management. Chennai, FY 2013 / 2014
Product Management - Glass ALEXA PRODUCT PRESENTATION Region SAARC Nitin Lloyd, Product Management Chennai, FY 2013 / 2014 PRODUCT MANAGEMENT - GLASS Alexa Partitioning Systems DESIGN: Slim Profile system
SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS
SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word
Northern Ireland Housing Executive: HMO Fire Safety Guide
Northern Ireland Housing Executive: HMO Fire Safety Guide Contents Equality Statement 5 Houses in Multiple Occupation (HMOs) means of escape in case of fire and other fire precautions 6 1.0 Introduction
UPP Residential Services Fire Risk Assessment
UPP Residential Services Fire Risk Assessment TS11151-R02-DRAFT1 15 August 2011 for: Keynes College University Road Canterbury Kent Recommended latest review date 14 August 2011 Executive summary This
Architectural Nylon. Architectural. Nylon
Architectural Nylon Architectural Nylon Contents Paris Series 273-279 Pull Handles and Accessories 281-292 269 Architectural Nylon HOPPE nylon levers and pull handles are manufactured to exacting standards
Fire and Security Products and Services
www.redbooklive.com Fire and Security Products and Services Making LPCB Approval work for you Not all fire and security products and services on the market can be trusted in the event of a fire or attempted
WARNING: Important: Keep these instructions for future reference. Gate Instructions (1) Assembly and Installation Instructions
Assembly and Installation Instructions Please read these instructions carefully. Please follow these instructions carefully to ensure that your gate extension is properly installed. Improper installation
Installation Instructions
Installation Instructions 1. Position the unit onto bridging packers. These keep the unit away from any water sitting inside the frame. 2. Centralise the unit within the frame and pack the edges with appropriate
