INVESTIGATION OF FAILURES OF 230-KV OIP COPPER CONDUCTOR BUSHINGS. Arturo Del Rio Keith Ellis Trench Ltd, Canada

Size: px
Start display at page:

Download "INVESTIGATION OF FAILURES OF 230-KV OIP COPPER CONDUCTOR BUSHINGS. Arturo Del Rio Keith Ellis Trench Ltd, Canada"

Transcription

1 INVESTIGATION OF FAILURES OF 230-KV OIP COPPER CONDUCTOR BUSHINGS ABSTRACT Arturo Del Rio Keith Ellis Trench Ltd, Canada The fact that copper ions from conductor surfaces are taken into solution in some mineral transformer oils and then deposited onto paper insulation in bushings and transformers has been well documented. These deposits have been implicated in a number of instances of equipment failure. Corrosive sulfur in transformer oil has been suggested as the cause for both the migration and the deposition of copper on the paper insulation in these instances even though the oil has consistently tested as non-corrosive. The migration and deposition of copper in transformer oils has been demonstrated to be independent of sulfur, corrosive or otherwise. The process of taking copper into solution and then depositing the copper as a fixed, stable compound on paper insulation is dependent upon the formation of copper-organic polar compounds in solution in the oil, attraction of these compounds to the surface of Kraft paper, and the formation of stable copper compounds in a pattern that decreases the dielectric strength of the paper insulation [1]. This paper presents one case of a copper migration induced failure in three separate transformer bushings manufactured by Trench France and oil filled with Shell Diala D mineral oil. INTRODUCTION In May and June of 2006, two Trench COTA 750-F AG3-01-ADP bushings failed on two separate transformers on the Southern Company s system. Inspection of the failed bushings revealed very similar details: The failures were below the flange and the air-side porcelain insulator remained intact. The epoxy inboard end insulator was shattered. Arc marks were evident from the same point on the ground sleeve to the copper conductor 5-8 inches above the bottom terminal (breaker plate). Arc marks were also evident to the breaker plate and/or the shield. Preliminary Investigation revealed further similarities between the failed bushings: The bushings were identical 750kV BIL copper conductor bushings. The bushings were manufactured in the Trench France facility. The bushings were of similar age (5-6 years service). The bushings were applied on 230kV transformers. The transformers were produced by the same transformer manufacturer. Both transformers were relatively lightly loaded and the transformer service data indicated they had not seen excessive temperatures. Although the bushing nameplate rating is 1200 Amps, these bushings were physically built as 2000 Amps units and only saw service duties of maximum of 800 Amps. Shell Diala D was the mineral oil used. There was no identifiable cause of failure from the site investigation. For reference, the first failed bushing, which failed May 2006 at Georgia Power, was identified as A. The sister bushings from this bank were identified as B and C. The second failed bushing, which failed June 2006 at Alabama Power, was identified as D and the sister bushings from the bank were identified as E and F.

2 Bushings A, B, and D were dismantled and inspected at the Georgia Power Forest Park repair facility. No oil remained in the failed bushings ( A and D ). Unfortunately, no oil was collected from bushing B. The paper and foil in the vicinity of each failure was badly damaged and presented no clear identifiable cause of failure. Georgia Power Bushing A S/N 99A6424 Failed May 2006 Bushing B S/N 99A6427 No failure - field tear down Bushing C S/N 99A6429 No failure Trench Canada tear down Alabama Power Bushing D S/N 01A3930 Failed June 2006 Bushing E S/N 01A3931 No failure returned to Trench Canada Bushing F S/N 01A3933 No failure returned to Trench Canada Review of historical data revealed that the bushings from the Georgia Power bank, bushings A, B and C, had been tested in January 2006 and were found to have elevated power factors. Subsequent to the failures and after dielectric tests had been performed on bushing C, Alabama Power bushings E and F were field tested and also found to have increased power factors leading to their removal from service [2]. INVESTIGATION PROCESS BUSHING C Bushing C S/N 99A6429 became the main focus for the investigation. This bushing was shipped to the Trench facilities in Ajax, Canada, where routine dielectric test including impulse test at 85% of rating were performed. The bushing passed the partial discharge, hi-pot and impulse tests. The increased C1 power factor readings were confirmed. There was no change in C1 or C2 capacitance when compared to the original factory tests and no significant change in C2 power factor was observed. Table 1 summarizes the C1 increased power factor readings for bushing C. Table 1 Bushing C Power Factor Results C1 Nameplate % C1 Commissioning 0.30% C1 Jan % C1 When removed from service 0.52% C1 After Impulse and Hipot Test September kV: 0.516% 50kV: 0.465% 102kV: 0.385% 2

3 Oil Analysis Oil samples were analyzed before and after the dielectric test and the results are included in Table 2, below: Table 2 Bushing C Oil Test Results Bushing ID Bushing C, as Trench Bushing C, after all voltage tests New Tested by/date: Trench MS Trench MS bushing oil (ppm) Hydrogen (H 2 ) Oxygen + Argon (O 2 + Ar) Nitrogen (N 2 ) Carbon Monoxide (CO) Methane (CH 4 ) Carbon Dioxide (CO 2 ) Ethylene (C 2 H 4 ) < 0.04 ND < 2 ND <0.04 ND < 2 ND 2 Ethane (C 2 H 6 ) < 0.04 ND 3 <0.04 ND < 2 ND 2 Acetylene (C 2 H 2 ) < 0.04 ND < 2 ND <0.04 ND < 2 ND 2 Total gas content% 2.28% 6.98% 2.25% 8.33% - Water content RT N/A N/A 4.38% N/A 0.05% 90C N/A N/A 25.4% N/A Although some discrepancy was evident in the test results, there were no significant gases that could indicate electrical discharges within the bushing and the moisture in the oil was relatively normal at 9 to 12 ppm. However the oil power factor showed high values at 25 C and 100 C. This was determined to be significant to this investigation, since an increase in oil power factor is an indicator of contamination. Additional oil samples were taken from bushing C in order to verify the questionable oil power factor results; these results are shown in Table 3. Pilot clay treatment done by Doble on one of the samples was successful in removing some degradation byproducts and/or contamination of the oil resulting in improved interfacial tension (IFT) and 25 C power factor; this is indication that polar material was removed from the oil by the clay as this test is greatly affected by such compounds. Because of the type of containers used to collect the samples, this test was deemed inconclusive since the contamination could have been introduced from the materials of the sealing system of the jars. Table 3 Oil Test Results Verification Source of Test 25 0 C (%) C (%) Trench France n/a Trench BU Trench IT Doble* Morgan Schaffer *Worst case of multiple samples taken during bushing oil draining. 3

4 The bushing was dismantled while collecting samples for suspect materials including the o-rings and flat gaskets, cast epoxy parts, Belleville compression washers. Collected samples were sent for analysis failing to pinpoint the source of contamination. Analysis of the Paper around a Puncture Hole The active part was unwound turn by turn with measurements taken of foil layer placement. There were no abnormalities found such as paper wrinkling or foil displacement. One significant finding was a puncture next to the bottom of the first foil layer. It was thought that this probably occurred during the impulse test but it was undetermined why. This finding and additional evidence collected from bushings E and F led to the finding of a fine faint dark line at the edge of the aluminum foil where the puncture had occurred. The puncture area and the dark treeing line are shown in Figure 1. Puncture Mark and Dark Treeing Line Figure 1 Analysis of the paper around the puncture hole showed Kraft paper in very good condition with a degree of polymerization (DP) of 938 and moisture content of 1.2% [3]. Under a stereo microscope the paper appeared to be in good condition. The darkened material adjacent to the hole exhibited a smooth compressed area of fibers. The chemical composition demonstrated a strong concentration of aluminum (~82.1 %), with minor amounts of copper (~12%), calcium (~3.4%) and sulfur (~2.5%), along with the background of carbon and oxygen. See Figure 2, below. 4

5 Paper fibers Burn Hole Darkened Material Adjacent to the Hole Figure 2 The dark treeing line on this sample exhibited copper (~61.1%), sulfur (~20.2%) and calcium (~13.2%), with minor amounts of silicon (~4.4%) and aluminum (~1%). OTHER SIGNIFICANT FINDINGS Bushings E and F and another suspect bushing named G removed from service were also tested, dismantled and samples of paper and oil obtained for analysis. Dielectric tests revealed increased power factor at 10 KV and tip-up test performed up to line-to-ground voltage showed a gradual increase in power factor at lower voltage levels followed by a gradual decrease as it approached the 100 KV level resembling a typical Garton effect curve. Results are shown in Figure 3. For comparison purposes, a new 138 KV bushing COTA 650 was tested in similar way and the results were plotted in the same graph. It was found that the measured power factor for the new bushing was very consistent independently of the applied voltage with a slight drop in power factor as the test voltage was increased. No changes in capacitance readings were observed. Upon active part tear down, faint treeing lines were found at the edge of the lower end of the aluminum foils similar to those found in bushing C (Figure 4). The extent and intensity of the treeing lines were somehow related to the increase in power factor. It would be expected that these treeing lines would be comprised mostly of aluminum and copper and oxygen. Then carbon would be formed from the degradation of the paper due to heating along that aluminum/paper interface or heating due to partial discharge along that interface. If this treeing was due to partial discharge at the edge of the foil/paper interface a lot of aluminum would be found embedded in the treeing line. This was not the case in the samples examined. More copper and sulfur were found at these locations than aluminum. Aluminum was found in very small concentrations or not present at all. Similar to the findings in bushing C, DGA analysis from oil samples did not indicate any type of incipient fault condition and DP tests did not show significant aging of the paper. 5

6 Tip-up Test Results for Bushing E Figure 3 Treeing Lines from Bushing E Figure 4 The Shell Diala D bushing oil was tested for corrosive sulfur according to several industry standards with consistent non-corrosive results therefore failing to identify corrosive sulfur as the root cause of the failures. Corrosive results were obtained only after prolonged aging test time at higher test temperatures [4, 5]. A summary of test results for in-service aged Shell Diala D oil from bushing G in included in APPENDIX A for reference. The dissipation factor of the oil showed a very strange behavior with time and temperature. A rapid increase of the dissipation factor with temperature was observed. The further heating at the same temperature for 2 hours led to a decrease in the power factor. A second heating procedure led to a much lower power factor. This strange kind of behavior may be an indication of volatile polar compounds dissolved in the oil and leading to an increase in the power factor. Figure 5 shows the behavior of the oil conductivity versus temperature [6]. Moreover, the power factor of the oil impregnated paper from the bushing was 25% at 90 C. After a vacuum treatment and a further heating at 90 C the value was 1.6%. This is a further indication, that some polar compounds are adsorbed in paper and may undergo further reactions. 6

7 Behavior of the Oil Conductivity versus Temperature Figure 5 Analysis of Copper Core Sections Two sections of copper core from bushing D were analyzed. Pictures of the blackened copper core are shown in Figure 6. Copper Core Samples from Bushing D Figure 6 The concentrations for the SEM/EDX analysis clearly show that most of the content is copper and sulfur with some carbon and oxygen. Therefore, the blackened area on the copper core of the bushing is in the initial stages of copper sulfide formation or the sulfur content would be slightly higher. Figure 7 shows some flakes of copper sulfide at 1000 times magnification which have formed on the surface of the copper conductor. The very high copper to sulfur ratio and significant proportions of carbon and oxygen suggest the deposit is not only copper sulfide but mostly organic compounds such as polymerized oil. 7

8 Flakes of Copper Sulfide at 1000X Figure 7 Analysis of the Treeing Lines Figure 8 is a region along a random treeing line on the paper from bushing F. Four out of the five major tracks shown in the picture follow single paper fibers for most of the discharge. The fact that the discharges follow the fibers indicates that the properties of the fiber/oil interface dominate the process. The discharge path tends to go slowly through the thickness of the paper rather than following the surface on the aluminum foil side of the paper. Aluminum Foil Location Flakes of Copper Sulfide at 1000X Figure 8 For illustration purposes, the single trace of the treeing line shown in the red circle is analyzed here. This trace is shown in Figure 9. In Figure 9, the plane of focus for the picture is set near the aluminum foil side of the paper. The branches near the opposite side of the paper are out of focus midway through the paper. The drawing in Figure 10 helps to illustrate that. In the illustration the aluminum foil would be on the left side (dotted line). The path followed by the traces often reaches the opposite side of the paper and into the adjacent paper layers. There is an indication that the pattern begins as an electrostatic deposition of particles on the surface and along the edge of fibers adjacent to the aluminum foil. The particles that have collected at that location are semi-conductors at best. They included sludge particles, copper oxides, copper sulfides, and other particles. This deposition modifies 8

9 the electrostatic field and collects more particles at greater distance from the aluminum foil forming fractal agglomerates and chains along the edges of single paper fibers and resulting in very low level energy discharges. The discharge patterns follow the edges of paper fibers in the same pattern seen for the deposited particles. Finally, a discharge path is created along the particles on the surface of the paper fibers not affecting the fiber itself. Aluminum Foil Edge Trace from a Treeing Line Figure 9 Discharge Path Figure 10 Copper and sulfur are associated with the discharge paths but they form following the discharge and are not the cause of the discharge. Copper sulfide forms on the surface of the discharge as very small filamentous fragments. That indicates the mobility of both copper and sulfur ions in the system. Figure 11 is a photomicrograph taken with a scanning electron microscope of one part of one of the traces. The individual paper fibers can be clearly seen as smooth-walled structures. Some of the fibers show a dark grainy deposit on their surface. This is the trace line, which is made up of carbonaceous debris primarily from the oil. On top of this debris are a number of white threadlike deposits. These white thread-like deposits are the copper sulfide deposits. They form after the trace has formed. The area between these threads is deficient in copper and sulfur. The trace is not the result of copper sulfide but seems to provide a sight where copper and sulfur are brought together. 9

10 Figure 11 Photomicrograph of One Part of One of the Traces DISCUSSION Since materials at the point of failure were destroyed and dispersed it is not possible to attempt to reconstruct initial condition from the failed materials. It is also not possible to know the state of the system at the moment the failure was initiated. Consequently, the search for the cause of failure relies more significantly on inferences that can be drawn from the investigation of comparable circumstances. It is apparent that at the moment of failure the bushing insulation could not withstand the condition or conditions to which it was subjected. Transient and harmonic conditions may have been present and should not be eliminated as potential contributing factors. The work conducted during this investigation helped to clarify the involvement of some of the potential factors that could have contributed to the failures. Specifically: 1. Heating of the oil or the paper has not been identified as a contributing factor from dissolved gas analysis performed. 2. Arcing has not been identified as an active incipient fault process from dissolved gas analysis performed. 3. Oxygen levels in tested oils were found to be consistent with vacuum processed oils. The one directly measurable oxidation product, total acid number, was at low levels in the tested oils. 4. Moisture levels were acceptable for both paper and oil samples collected during the dismantling and inspection of bushing C. The moisture in the paper in the vicinity of the puncture hole was an acceptable 1.2%. The moisture in oil for oil sampled from bushing E was comparable to values obtained for bushing C oil. 5. Acid levels were found to be low in tested oils. 6. Broad surface contamination with sludges, waxes, films, or sediments was not observed. 7. Fluid particle counts were not unacceptable in the fluids tested, although some of the ASTM D1816 dielectric breakdown voltage measurements of the fluid samples were unacceptable. This particular dielectric breakdown voltage method is sensitive to particles and moisture and typically shows more variation than other methods. 8. Corrosive sulfur was not identified in any of the tested fluids by any existing standard or method. A determined effort was made to produce a positive CCD corrosive sulfur test result for the tested oil. To produce a positive result, it was required that the sample be subjected to a temperature of 140ºC for 15 days. It should be noted that under these conditions other serious issues would arise within the equipment. 10

11 9. Copper and sulfur have been identified on paper surfaces, but copper sulfide formations have not been specifically identified on any of the paper samples. 10. Polar compounds have observed and directly related to elevated fluid power factor measurements for the fluid from bushing E and another service aged Diala D. High fluid power factor measurements have been observed for all of the bushing fluids tested. Observation of elevated power factor and the Garton Effect in power factor testing on bushing E also demonstrated the presence of polar compounds in the fluid. Elevated power factors have been observed for all of the bushings. 11. Ionic species transported by ligands are possibly indicated by some of the SEM measurements 12. Discharge like treeing patterns were observed in bushings C, E, F and G. Also, discharge like lines were found in one inspected bushing from the Georgia Power Dorchester substation failure [7]. CONCLUSIONS It could not been determined if the tree pattern seen on the paper of the examined sister or failed bushings are related to the cause of the actual failure in the Trench bushings A and D ; however, the puncture hole found at the edge of the foil in bushing C, which coincides with the treeing line, is a good indication that the area had become a weak point in the bushing s insulation. The following conclusions have been drawn from this investigation. The preponderance of information indicates the failures are due to insulation failure. The failures are related to insulation compromising phenomena linked with the oil. Shell Diala D is the identified oil that has developed the features allowing this type of failure to occur. Not all Shell Diala D develops these features. The specific features are a high power factor that displays the Garton Effect and elevated levels of oil soluble copper. Some copper conductor bushings with Shell Diala D will be at risk for this type of failure. Most copper conductor bushings with Shell Diala D will not be at risk for this type of failure The copper conductor bushings without Shell Diala D are not at risk for this type of failure. The aluminum conductor bushings with Shell Diala D are not at risk for this type of failure. Compromised bushings can be identified by routine field tests. Recommendations: Identify those Trench France copper conductor bushings that contain Shell Diala D, manufactured between 1998 and Identify which of these bushings has an increasing power factor. When the C1 power factor increase is 1.5 to 2 x nameplate value and when the power factor indicates a tip up, typically: Test KV PF % replace the bushing. 11

12 ACKNOWLEDGEMENTS The authors would like to express gratitude to Russ Crutcher, Microlab Northwest; Dave Hanson, TJH2b; Danny Bates, Alabama Power; Joseph Benefield, Georgia Power, for their contributions during this investigation. REFERENCES [1] E. R. Crutcher, E. R. and Warner, Ken, Copper Mobility and Failure in Electrical Equipment: It Is Not Corrosive Sulfur, Proceedings of EuroTechCon, [2] Bates, D., Back to Back Bushings Failures - An Ongoing Investigation, Proceedings of TechCon USA [3] Doble Laboratory Test Analysis Report 71090, November 30, [4] Doble Materials Report 72486, March [5] Doble Materials Report 75585, August [6] Siemens Test Report MCSL 068/07, April [7] Del Rio, Arturo and Hanson, Dave, Copper Migration in Bushings: Update to Southern Co. Trench Bushing Failure Investigation, Siemens Transforming Know-how into Solutions Conference, BIOGRAPHY Arturo Del Rio started his professional career as a Field Engineer in the oil fields of Colombia and as an Electrical Engineer for Hatch Associates consulting firm in Toronto, Canada, were he was involved in several projects and studies related to electric arc furnaces and the metallurgical industry. He joined Trench Canada in 1991 where he has held various design and engineering positions in the fields of instrument transformers, power electronics and air-core reactors. He is currently Engineering Manager at the Trench Transformer Bushing Division in Ajax, ON, Canada. Arturo holds a bachelor s degree in Electrical Engineering from the Universidad Industrial de Santander, Colombia, and an M.A.Sc. degree in the field of power devices and systems from the University of Toronto, Canada. He has been an IEEE member since 1988 and is a registered Professional Engineer in Ontario. Keith P. Ellis is responsible for the development, promotion, sales and technical support for bushings for the Trench Bushing Group including HSP, serving as Bushing Product Manager and OEM Sales Manager, Americas. Before joining Trench Keith was Sales Manager for the ABB Power T & D Company s Components Division. This position was also held under the company names of Westinghouse/ABB and ASEA Electric. Before assuming the Sales and Marketing responsibilities of transformer components, Keith was Senior Sales Representative for RTE and RTE-ASEA in Upstate New York. Keith began his career in the power transformer industry with RTE/ASEA as an Application Engineer. Keith graduated from Mare Island Naval Shipyard with a journeyman certificate in Machine Technology. Attended the University of California, where he majored in Mechanical Engineering. After serving with distinctions in the US Navy during the Vietnam War he continued his education at the University of Wisconsin, Milwaukee. He is a member of IEEE, PES, Transformers Committee and Working Group Chairman for C He takes particular interest in component applications to power transformers with special interest in high voltage bushings and on-load tap changers. 12

13 APPENDIX A Summary of Results for Service Aged Diala D from Bushing G 13

14 Doble Test Results Service Aged Diala D from Bushing G TABLE A1 DGA Analysis, ASTM D 3612, ppm v/v GAS Syr Syr Conc, Conc, Hydrogen Oxygen 3,960 3,700 Nitrogen 50,500 50,600 Methane Carbon Monoxide Ethane Carbon Dioxide 2,183 2,234 Ethylene Acetylene Total Combustible Gas TABLE A2 Oil Quality Results After Clay Treatment Test Method Before Treatment After Treatment Interfacial Tension, mn/m ASTM D 971, ISO Neut. No., mgkoh/g ASTM D 974 <0.01 <0.01 Power Factor at 25 C, % ASTM D Power Factor at 100 C, % ASTM D TABLE A3 Sulfur Related Test Results on the Oil As Received Test Method Result Corrosive Sulfur ASTM D 1275B Non-corrosive Tarnish Level ASTM D 1275B/D 130 1b Corrosive Sulfur Extended Test (8 days) ASTM D 1275B - Extended Tarnish Level Extended Test (8 days) ASTM D 1275B/D Extended Total Sulfur, mg/kg ASTM D Elemental Sulfur, mg/kg UOP 286 < 1 Dibenzyl disulfide (DBDS), mg/kg Doble < 1 14

15 TABLE A4 Additional Sulfur Test Results on the Oil As received, Doble CCD Test at 140 C 4-day Testing, 18 gauge needle Method Result CCD Test by Air Ingress - Paper Doble Method Light Deposit, dull in color Dielectric Strength of Paper used in CCD test (Air Ingress) ASTM D 149* CCD Test by Air Ingress - Copper Doble Method Non-corrosive CCD Test by Air Ingress Copper Tarnish Level ASTM D 130 1b CCD Test, Sealed Doble Method Moderate Deposit, dull in color Dielectric Strength of Paper used in CCD test (Sealed) ASTM D 149* CCD Test, Sealed- Copper Doble Method Non-corrosive CCD Test, Sealed- Copper Tarnish level ASTM D 130 2b 6-day Testing, 20 gauge needle Method Result CCD Test by Air Ingress - Paper Doble Method Moderate Deposit, dull in color Dielectric Strength of Paper used in CCD test (Air Ingress) ASTM D 149* CCD Test by Air Ingress - Copper Doble Method Non-corrosive CCD Test by Air Ingress Copper Tarnish Level ASTM D 130 2b CCD Test, Sealed Doble Method Moderate Deposit, dull in color Dielectric Strength of Paper used in CCD test (Sealed) ASTM D 149* CCD Test, Sealed- Copper Doble Method Non-corrosive CCD Test, Sealed- Copper Tarnish level ASTM D 130 2c *Analysis was performed under the following conditions: Sample Preparation: Paper dried for 16 hours at 80 C and then oil impregnated Electrodes: brass, 0.25 inch diameter Voltage Rise: 500 volts/second Temperature: C Material Thickness: 6 mils (paper was in 2 layers to get an accurate result) 15

Electrical Maintenance Workshop

Electrical Maintenance Workshop Electrical Maintenance Workshop Transformer Maintenance & Testing Thursday, November 6, 2003 Transformer Maintenance & Testing Purpose This presentation provides an overview of the major considerations

More information

ON-LINE DIAGNOSTIC CASE STUDY INVOLVING A GENERAL ELECTRIC TYPE U BUSHING

ON-LINE DIAGNOSTIC CASE STUDY INVOLVING A GENERAL ELECTRIC TYPE U BUSHING ON-LINE DIAGNOSTIC CASE STUDY INVOLVING A GENERAL ELECTRIC TYPE U BUSHING Pamelyn Bahr and Jon Christensen Intermountain Power Service Corp. Robert C. Brusetti, P.E. Doble Engineering Company ABSTRACT

More information

UNDERSTANDING CORROSIVE SULFUR PROBLEMS IN ELECTRIC APPARATUS. Paul J. Griffin and Lance R. Lewand Doble Engineering Company

UNDERSTANDING CORROSIVE SULFUR PROBLEMS IN ELECTRIC APPARATUS. Paul J. Griffin and Lance R. Lewand Doble Engineering Company UNDERSTANDING CORROSIVE SULFUR PROBLEMS IN ELECTRIC APPARATUS Paul J. Griffin and Lance R. Lewand Doble Engineering Company ABSTRACT Corrosive sulfur in oil has become a problem in electric apparatus.

More information

Dissolved Gas Analysis Guide for Transformers Filled with Beta Fluid

Dissolved Gas Analysis Guide for Transformers Filled with Beta Fluid DSI Ventures, Inc. PHONE: (903) 526-7577 FAX: (903) 526-0021 www.dsiventures.com Dissolved Gas Analysis Guide for Transformers Filled with Beta Fluid Introduction Analysis of dissolved gases in transformer

More information

DGA - Method in the Past and for the Future

DGA - Method in the Past and for the Future DGA - Method in the Past and for the Future Page 2 May 2012 1970 1973 Doerenburg introduced the differentiation between electrical and thermal failure mode and introduced ratios for fault gases with similar

More information

THE VALUE OF POWER FACTOR TESTING

THE VALUE OF POWER FACTOR TESTING THE VALUE OF POWER FACTOR TESTING Nov 1, 2005 12:00 PM by John Bleyer and Phillip Prout, National Grid NATIONAL GRID DISCOVERED A HIGH POWER FACTOR DURING ACCEPTANCE TESTING of a new 40-MVA transformer

More information

DISSOLVED GAS ANALYSIS OF MINERAL OIL INSULATING FLUIDS

DISSOLVED GAS ANALYSIS OF MINERAL OIL INSULATING FLUIDS DISSOLVED GAS ANALYSIS OF MINERAL OIL INSULATING FLUIDS Written by: Joseph B. DiGiorgio, Ph.D. Dr. DiGiorgio conducts seminars on request. 1996-2013 NTT Copyrighted material. Contact Dr. DiGiorgio Insulating

More information

An Overview of Lapp Insulator High Voltage Bushing Design

An Overview of Lapp Insulator High Voltage Bushing Design An Overview of Lapp Insulator High Voltage Bushing Design W.A. Young Lapp Insulator Company LeRoy, NY 14482 USA INTRODUCTION High voltage bushings are devices designed to transmit electric energy through

More information

Transformer Bushings for GIS

Transformer Bushings for GIS Transformer Bushings for GIS Oil to SF6 Connections GARIP RTKG 725-55 kv SQS certified ISO 91 / ISO 141 Bushings RIP - Technology for SF6 / Oil - Bushings In modern metal enclosed switchgear SF6 -gas is

More information

FULLER S EARTH AS THE CAUSE OF OIL CORROSIVENESS AFTER THE OIL RECLAIMING PROCESS

FULLER S EARTH AS THE CAUSE OF OIL CORROSIVENESS AFTER THE OIL RECLAIMING PROCESS FULLER S EARTH AS THE CAUSE OF OIL CORROSIVENESS AFTER THE OIL RECLAIMING PROCESS Maria Augusta MARTINS Rui Manuel MARTINS Anabela PEIXOTO EDP Labelec EDP Labelec EDP Labelec maria.augusta@edp.pt ruimanuel.martins@edp.pt

More information

Mylar polyester film. Electrical Properties. Product Information. Dielectric Strength. Electrode Size. Film Thickness

Mylar polyester film. Electrical Properties. Product Information. Dielectric Strength. Electrode Size. Film Thickness Product Information Mylar polyester film Electrical Properties Mylar offers unique design capabilities to the electrical industry due to the excellent balance of its electrical properties with its chemical,

More information

OPTIMIZE YOUR FLEET MANAGEMENT RESOURCES

OPTIMIZE YOUR FLEET MANAGEMENT RESOURCES OPTIMIZE YOUR FLEET MANAGEMENT RESOURCES PROACTIVE RISK MANAGEMENT Inside View DGA Diagnostic Software: Integrates Lab, On-line and Portable Data Continuous Data Interpretation Automated Alerts And Notifications

More information

A GUIDE TO TRANSFORMER OIL ANALYSIS BY I.A.R. GRAY Transformer Chemistry Services

A GUIDE TO TRANSFORMER OIL ANALYSIS BY I.A.R. GRAY Transformer Chemistry Services A GUIDE TO TRANSFORMER OIL ANALYSIS BY I.A.R. GRAY Transformer Chemistry Services INTRODUCTION The fault free operation of power transformers is a factor of major economic importance and safety in power

More information

MiCAFIL. 1 RIP Technology. Bushings. Z. Zic 09/2003

MiCAFIL. 1 RIP Technology. Bushings. Z. Zic 09/2003 MiCAFIL 1 RIP Technology Z. Zic 09/2003 )XQFWLRQRI+LJK9ROWDJH%XVKLQJ Uncontrolled (natural) electrical field Capacity-controlled electrical field %XVKLQJV0DLQ,QVXODWLRQ6\VWHPV 7\SH 0DLQ,QVXODWLRQ +RXVLQJFRYHU

More information

Enhance Power Equipment Reliability with Predictive Maintenance Technologies

Enhance Power Equipment Reliability with Predictive Maintenance Technologies Enhance Power Equipment Reliability with Predictive Maintenance Technologies November 2012/1910DB1208 by S. Frank Waterer, Electrical Engineerinig, Fellow Schneider Electric USA, Inc. Make the most of

More information

WIRE AND CABLE ENGINEERING GUIDE

WIRE AND CABLE ENGINEERING GUIDE DC Hi Pot Testing Excerpt from PRYSMIAN S WIRE AND CABLE ENGINEERING GUIDE (FOR INFORMATIONAL PURPOSES ONLY) Page 1 of 6 DC HIGH POTENTIAL TESTING DC Hi-Pot testing can be applied as a withstand test (a

More information

Siemens TMDS transformer monitoring and diagnostic system. Solutions for transformer life-cycle management. Answers for energy.

Siemens TMDS transformer monitoring and diagnostic system. Solutions for transformer life-cycle management. Answers for energy. Siemens TMDS transformer monitoring and diagnostic system Solutions for transformer life-cycle management Answers for energy. We strive to unlock value in your transformer monitoring and Smart Grid investments.

More information

PRODUCTION OF CORROSIVE SULPHUR FREE TRANSFORMER FLUIDS vs. COMMON NAPHTHENIC MINERAL OILS

PRODUCTION OF CORROSIVE SULPHUR FREE TRANSFORMER FLUIDS vs. COMMON NAPHTHENIC MINERAL OILS PRODUCTION OF CORROSIVE SULPHUR FREE TRANSFORMER FLUIDS vs. COMMON NAPHTHENIC MINERAL OILS Steve Krawiec Senior Technical Services Advisor Petro-Canada, Mississauga, Ontario ABSTRACT This paper focuses

More information

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp Page 1 2015 Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other Component 15 kv or 25 kv Separable Insulated Connector (elbow) Equipment Connection Power Cable Power Cable Grounded Metal

More information

CHAPTER 3: MATTER. Active Learning Questions: 1-6, 9, 13-14; End-of-Chapter Questions: 1-18, 20, 24-32, 38-42, 44, 49-52, 55-56, 61-64

CHAPTER 3: MATTER. Active Learning Questions: 1-6, 9, 13-14; End-of-Chapter Questions: 1-18, 20, 24-32, 38-42, 44, 49-52, 55-56, 61-64 CHAPTER 3: MATTER Active Learning Questions: 1-6, 9, 13-14; End-of-Chapter Questions: 1-18, 20, 24-32, 38-42, 44, 49-52, 55-56, 61-64 3.1 MATTER Matter: Anything that has mass and occupies volume We study

More information

SIX REASONS TO DRY BIOGAS To A LOW DEWPOINT BEFORE COMBUSTION IN A CHP ENGINE STEVEN SCOTT MARKET DEVELOPMENT MANAGER ALTERNATIVE ENERGIES

SIX REASONS TO DRY BIOGAS To A LOW DEWPOINT BEFORE COMBUSTION IN A CHP ENGINE STEVEN SCOTT MARKET DEVELOPMENT MANAGER ALTERNATIVE ENERGIES SIX REASONS TO DRY BIOGAS To A LOW DEWPOINT BEFORE COMBUSTION IN A CHP ENGINE STEVEN SCOTT MARKET DEVELOPMENT MANAGER ALTERNATIVE ENERGIES Filippo Turra Product Manager Cooling Technology INTRODUCTION

More information

Hydro Plant Risk Assessment Guide

Hydro Plant Risk Assessment Guide September 2006 Hydro Plant Risk Assessment Guide Appendix E5: Transformer Condition Assessment E5.1 GENERAL Power transformers are key components in the power train at hydroelectric powerplants and are

More information

Session Five: Modern XLPE Materials for Extruded Energy Cable Systems

Session Five: Modern XLPE Materials for Extruded Energy Cable Systems Session Five: Modern XLPE Materials for Extruded Energy Cable Systems Abstract Hakan Lennartsson Senior Technical Service Manager, Borouge Hong Kong Pte. Ltd. The first medium voltage cables using extruded

More information

Chapter 5 - Aircraft Welding

Chapter 5 - Aircraft Welding Chapter 5 - Aircraft Welding Chapter 5 Section A Study Aid Questions Fill in the Blanks 1. There are 3 types of welding:, and, welding. 2. The oxy acetylene flame, with a temperature of Fahrenheit is produced

More information

OXIDATION INHIBITORS FOR INSULATING OILS

OXIDATION INHIBITORS FOR INSULATING OILS OXIDATION INHIBITORS FOR INSULATING OILS By I.A.R. Gray Transformer Chemistry Services Background: Mineral oil insulating fluids undergo oxidative degradation in the presence of oxygen to give a number

More information

THE OLTC AS AN "OIL ISOLATED SYSTEM" IN THE TRANSFORMER & OIL ANALYSIS IN OLTC. I Hr. Dr. Hurm, Hr. Dr. Schübel I 26.06.2014 I

THE OLTC AS AN OIL ISOLATED SYSTEM IN THE TRANSFORMER & OIL ANALYSIS IN OLTC. I Hr. Dr. Hurm, Hr. Dr. Schübel I 26.06.2014 I THE OLTC AS AN "OIL ISOLATED SYSTEM" IN THE TRANSFORMER & OIL ANALYSIS IN OLTC MR Hr. Dr. Hurm, MESSKO Hr. Dr. Schübel 26.06.2014 Seite 1 von 39 Table of contents Part 1: 1. Introduction: working principle

More information

Molecular Models in Biology

Molecular Models in Biology Molecular Models in Biology Objectives: After this lab a student will be able to: 1) Understand the properties of atoms that give rise to bonds. 2) Understand how and why atoms form ions. 3) Model covalent,

More information

Power-factor testing of rotating machinery is another valuable test

Power-factor testing of rotating machinery is another valuable test Feature Power-Factor Testing of Stator Winding Insulation: Understanding the Test Technique and Interpretation of Results Power-factor testing of rotating machinery is another valuable test technique providing

More information

AUTOCLAVE CORROSION INHIBITOR EVALUATION

AUTOCLAVE CORROSION INHIBITOR EVALUATION AUTOCLAVE CORROSION INHIBITOR EVALUATION Cormetrics Job #: 12-123 Prepared for: ABC Company Lab: Bay 4-2280 39 th Avenue NE, Calgary, AB. T2E 6P7 Phone: 258-2853 Fax: 291-1423 ABC Company Page 1 of 9 1.

More information

7.4. Using the Bohr Theory KNOW? Using the Bohr Theory to Describe Atoms and Ions

7.4. Using the Bohr Theory KNOW? Using the Bohr Theory to Describe Atoms and Ions 7.4 Using the Bohr Theory LEARNING TIP Models such as Figures 1 to 4, on pages 218 and 219, help you visualize scientific explanations. As you examine Figures 1 to 4, look back and forth between the diagrams

More information

Energy Efficient Operations and Maintenance Strategies for Boilers

Energy Efficient Operations and Maintenance Strategies for Boilers Energy Efficient Operations and Maintenance Strategies for Boilers Large, complex and widely used, industrial boilers are major consumers of fuel. Proper operations and maintenance (O&M) procedures must

More information

How Sensors Work. How Oxygen, Electrochemical Toxic, and Metal Oxide Semiconductor Sensors Work *

How Sensors Work. How Oxygen, Electrochemical Toxic, and Metal Oxide Semiconductor Sensors Work * How Oxygen, Electrochemical Toxic, and Metal Oxide Semiconductor Sensors Work * 1. Oxygen sensor detection principle Most portable or survey instruments used for workplace evaluation of oxygen concentrations

More information

The benefits of inhibited transformer oils using gas-to-liquids based technology

The benefits of inhibited transformer oils using gas-to-liquids based technology The benefits of inhibited transformer oils using gas-to-liquids based technology CWIEME - Berlin 2013 Coil winding, Insulation & Electrical Manufacturing Exhibition Use this area for cover image (height

More information

TMDS Smart Monitor. Solutions for transformer life-cycle management. Answers for energy.

TMDS Smart Monitor. Solutions for transformer life-cycle management. Answers for energy. TMDS Smart Monitor Solutions for transformer life-cycle management Answers for energy. TMDS Smart Monitor Selecting a transformer monitoring solution is a critical step in achieving your company s Smart

More information

GE Energy Transformer Monitoring: How Moving forward from Monitoring to Diagnostics can Positively Impact Indian Business and Industry

GE Energy Transformer Monitoring: How Moving forward from Monitoring to Diagnostics can Positively Impact Indian Business and Industry GE Energy Transformer Monitoring: How Moving forward from Monitoring to Diagnostics can Positively Impact Indian Business and Industry Brian Sparling, SMIEEE GridTech 2007, Delhi February 5-6, 2007 The

More information

Wipe Analysis to Determine Metal Contamination on Critical Surfaces

Wipe Analysis to Determine Metal Contamination on Critical Surfaces By Albert Dato, Ph.D., Warren York, Jennifer Jew, Laarni Huerta, Brice Norton, and Michael Coste On-wafer metallic contamination is detrimental to the fabrication and performance of semiconductor devices.

More information

This chapter is devided into two sections:

This chapter is devided into two sections: This chapter is devided into two sections: Page Installation requirements........................................................................ 127 The installation process..........................................................................

More information

CHAPTER 7 THE DEHYDRATION AND SWEETENING OF NATURAL GAS

CHAPTER 7 THE DEHYDRATION AND SWEETENING OF NATURAL GAS CHAPTER 7 THE DEHYDRATION AND SWEETENING OF NATURAL GAS Natural gases either from natural production or storage reservoirs contain water, which condense and form solid gas hydrates to block pipeline flow

More information

A discussion of condensate removal systems for clarifier and thickener drives for water and wastewater facilities.

A discussion of condensate removal systems for clarifier and thickener drives for water and wastewater facilities. A discussion of condensate removal systems for clarifier and thickener drives for water and wastewater facilities. Richard L. Dornfeld, BSME, P.E. Staff Engineer September 25, 2014 Moisture can be a problem

More information

Weld Cracking. An Excerpt from The Fabricators' and Erectors' Guide to Welded Steel Construction. The James F. Lincoln Arc Welding Foundation

Weld Cracking. An Excerpt from The Fabricators' and Erectors' Guide to Welded Steel Construction. The James F. Lincoln Arc Welding Foundation Weld Cracking An Excerpt from The Fabricators' and Erectors' Guide to Welded Steel Construction The James F. Lincoln Arc Welding Foundation Weld Cracking Several types of discontinuities may occur in welds

More information

Honors Chemistry: Unit 6 Test Stoichiometry PRACTICE TEST ANSWER KEY Page 1. A chemical equation. (C-4.4)

Honors Chemistry: Unit 6 Test Stoichiometry PRACTICE TEST ANSWER KEY Page 1. A chemical equation. (C-4.4) Honors Chemistry: Unit 6 Test Stoichiometry PRACTICE TEST ANSWER KEY Page 1 1. 2. 3. 4. 5. 6. Question What is a symbolic representation of a chemical reaction? What 3 things (values) is a mole of a chemical

More information

produces and delivers products worldwide can provide the optimal are dedicated to supplying you with superior advice and global support.

produces and delivers products worldwide can provide the optimal are dedicated to supplying you with superior advice and global support. www.ppcinsulators.com The very Best. The very Best. That s what we deliver. ong od Insulators Only a company that develops, produces and delivers products worldwide can provide the optimal solution for

More information

Balancing chemical reaction equations (stoichiometry)

Balancing chemical reaction equations (stoichiometry) Balancing chemical reaction equations (stoichiometry) This worksheet and all related files are licensed under the Creative Commons Attribution License, version 1.0. To view a copy of this license, visit

More information

1ZSE 2750-105 en, Rev. 8. Transformer bushings, type GOE and GOE(2) Technical guide

1ZSE 2750-105 en, Rev. 8. Transformer bushings, type GOE and GOE(2) Technical guide 1ZSE 2750-105 en, Rev. 8 Transformer bushings, type GOE and GOE(2) Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible

More information

Capacitor Voltage Transformer. Answers for energy.

Capacitor Voltage Transformer. Answers for energy. Capacitor Voltage Transformer Answers for energy. Capacitor Voltage Transformer Siemens Capacitor Voltage Transformers are based on technology from Trench, a recognized world leader in the design and manufacture

More information

Properties and Classifications of Matter

Properties and Classifications of Matter PS-3.1 Distinguish chemical properties of matter (including reactivity) from physical properties of matter (including boiling point, freezing/melting point, density [with density calculations], solubility,

More information

The photoionization detector (PID) utilizes ultraviolet

The photoionization detector (PID) utilizes ultraviolet Chapter 6 Photoionization Detectors The photoionization detector (PID) utilizes ultraviolet light to ionize gas molecules, and is commonly employed in the detection of volatile organic compounds (VOCs).

More information

Cat S O SSM. Services. Understanding Your Results. Understanding Your: S O S Oil Reports S O S Oil Results S O S Coolant Reports S O S Coolant Results

Cat S O SSM. Services. Understanding Your Results. Understanding Your: S O S Oil Reports S O S Oil Results S O S Coolant Reports S O S Coolant Results Cat S O SSM Services Understanding Your Results Understanding Your: S O S Oil Reports S O S Oil Results S O S Coolant Reports S O S Coolant Results Contents Overview of S O S Oil Reports...4-5 Overview

More information

ALS TRIBOLOGY Engine Coolant Reference Guide

ALS TRIBOLOGY Engine Coolant Reference Guide ALS TRIBOLOGY Engine Coolant Reference Guide Engine coolants are a mixture of, inhibitors, and water. Each formula is designed for specific protection and engine requirements. Mixing different coolants

More information

Lecture 35: Atmosphere in Furnaces

Lecture 35: Atmosphere in Furnaces Lecture 35: Atmosphere in Furnaces Contents: Selection of atmosphere: Gases and their behavior: Prepared atmospheres Protective atmospheres applications Atmosphere volume requirements Atmosphere sensors

More information

Power Capacitor Units for improved power quality

Power Capacitor Units for improved power quality Power Capacitor Units for improved power quality Applications for capacitors Reactive power compensation Most of the apparatus and loads connected to the electrical power system consume both active and

More information

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER

More information

Name Class Date. What is ionic bonding? What happens to atoms that gain or lose electrons? What kinds of solids are formed from ionic bonds?

Name Class Date. What is ionic bonding? What happens to atoms that gain or lose electrons? What kinds of solids are formed from ionic bonds? CHAPTER 1 2 Ionic Bonds SECTION Chemical Bonding BEFORE YOU READ After you read this section, you should be able to answer these questions: What is ionic bonding? What happens to atoms that gain or lose

More information

Spandrel Glass Types and Recommendations

Spandrel Glass Types and Recommendations Spandrel Glass Types and Recommendations Introduction PPG has long offered recommendations regarding alternatives for glass spandrel applications. Over the years these recommendations were included in

More information

North American Stainless

North American Stainless Introduction: North American Stainless Flat Products Stainless Steel Grade Sheet 309S (S30908)/ EN1.4833 SS309 is a highly alloyed austenitic stainless steel used for its excellent oxidation resistance,

More information

ASSESSMENT OF OIL ANALYSIS DATA FOR MEDIUM VOLTAGE DISTRIBUTION TRANSFORMERS

ASSESSMENT OF OIL ANALYSIS DATA FOR MEDIUM VOLTAGE DISTRIBUTION TRANSFORMERS ASSESSMENT OF OIL ANALYSIS DATA FOR MEDIUM VOLTAGE DISTRIBUTION TRANSFORMERS A. Müller 1*, M. Jovalekic 1, S. Tenbohlen 1 1 Institute of Power Transmission and High Voltage Technology, University of Stuttgart,

More information

1ZSC000563-AAC en, Rev. 7. Resin impregnated paper bushing, oil to air, type GSB Technical guide

1ZSC000563-AAC en, Rev. 7. Resin impregnated paper bushing, oil to air, type GSB Technical guide 1ZSC000563-AAC en, Rev. 7 Resin impregnated paper bushing, oil to air, type GSB Technical guide Original instruction The information provided in this document is intended to be general and does not cover

More information

Automotive Base Oil Presentation

Automotive Base Oil Presentation Automotive Base Oil Presentation What is a Base Oil? The refined petroleum mineral or synthetic material that is produced by a refinery to a required set of specifications. A lubricant s quality can depend

More information

LEAD CRYSTAL. User Manual. Valve-regulated lead-crystal batteries Energy storage Cells

LEAD CRYSTAL. User Manual. Valve-regulated lead-crystal batteries Energy storage Cells Engineering Production Sales LEAD CRYSTAL Valve-regulated lead-crystal batteries Energy storage Cells User Manual www.axcom-battery-technology.de info@.axcom-battery-technology.de Chapter 1: 1. Introduction

More information

DC MOTOR ANALYSIS & TROUBLESHOOTING

DC MOTOR ANALYSIS & TROUBLESHOOTING DC MOTOR ANALYSIS & TROUBLESHOOTING By Don Shaw Condition assessment of DC motors requires a basic understanding of the design and operating characteristics of the various types available: the series motor,

More information

White Paper. Moisture in Hermetic Packages By Craig Hillman, PhD

White Paper. Moisture in Hermetic Packages By Craig Hillman, PhD White Paper Moisture in Hermetic Packages By Craig Hillman, PhD Moisture in Hermetic Packages Hermetic packaging of micro-electronic and opto-electronic devices is commonly utilized to protect the devices

More information

North American Stainless

North American Stainless North American Stainless Flat Products Stainless Steel Grade Sheet 310S (S31008)/ EN 1.4845 Introduction: SS310 is a highly alloyed austenitic stainless steel designed for elevated-temperature service.

More information

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin 1-800-432-8373. Anode Rods, Cathodic Protection and the Porcelain (glass) Lining

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin 1-800-432-8373. Anode Rods, Cathodic Protection and the Porcelain (glass) Lining Corrosion can be defined as the destructive attack of a metal by an electrochemical reaction with its environment. Steel exposed to moisture and oxygen will rust and corrode. Corrosion is defined as the

More information

ENERGY CARRIERS AND CONVERSION SYSTEMS Vol. II - Liquid Hydrogen Storage - Takuji Hanada, Kunihiro Takahashi

ENERGY CARRIERS AND CONVERSION SYSTEMS Vol. II - Liquid Hydrogen Storage - Takuji Hanada, Kunihiro Takahashi LIQUIDHYDROGEN STORAGE Takuji Hanada Air Liquide Japan Co., Ltd., Tokyo, Japan Kunihiro Center for Supply Control and Disaster Management, Tokyo Gas Co., Ltd., Tokyo, Japan Keywords: liquidhydrogen, insulation

More information

Section 10.0: Electrode Erosion

Section 10.0: Electrode Erosion Section 10.0: Electrode Erosion The primary reason for failure of plasma torches usually involves the inability of the electrodes to operate as they were designed, or operation under adverse conditions.

More information

Ionic and Metallic Bonding

Ionic and Metallic Bonding Ionic and Metallic Bonding BNDING AND INTERACTINS 71 Ions For students using the Foundation edition, assign problems 1, 3 5, 7 12, 14, 15, 18 20 Essential Understanding Ions form when atoms gain or lose

More information

States of Matter CHAPTER 10 REVIEW SECTION 1. Name Date Class. Answer the following questions in the space provided.

States of Matter CHAPTER 10 REVIEW SECTION 1. Name Date Class. Answer the following questions in the space provided. CHAPTER 10 REVIEW States of Matter SECTION 1 SHORT ANSWER Answer the following questions in the space provided. 1. Identify whether the descriptions below describe an ideal gas or a real gas. ideal gas

More information

LASER CUTTING OF STAINLESS STEEL

LASER CUTTING OF STAINLESS STEEL LASER CUTTING OF STAINLESS STEEL Laser inert gas cutting is the most applicable process type used for cutting of stainless steel. Laser oxygen cutting is also applied in cases where the cut face oxidation

More information

Mole Notes.notebook. October 29, 2014

Mole Notes.notebook. October 29, 2014 1 2 How do chemists count atoms/formula units/molecules? How do we go from the atomic scale to the scale of everyday measurements (macroscopic scale)? The gateway is the mole! But before we get to the

More information

WIRE AND CABLE ENGINEERING GUIDE

WIRE AND CABLE ENGINEERING GUIDE Excerpt From Prysmian s WIRE AND CABLE ENGINEERING GUIDE Page 1 of 8 CABLE TESTING Testing represents an integral part in the life of a cable. A cable will be subjected to multiple tests in its lifetime

More information

IEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO

IEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO IEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO WHEN YOU HEAR AN ENGINEER SAY A NUMBER OF DIFFERENT APPROACHES ARE BEING IMPLEMENTED

More information

Evaluation of Laminated Flexible Printed Circuit Boards Under Wide Temperature Cycling

Evaluation of Laminated Flexible Printed Circuit Boards Under Wide Temperature Cycling Evaluation of Laminated Flexible Printed Circuit Boards Under Wide Temperature Cycling Richard Patterson, Glenn Research Center/NASA; Ahmad Hammoud, QSS Group, Inc.; Scott Gerber, ZIN Technologies; James

More information

LUXEON LEDs. Circuit Design and Layout Practices to Minimize Electrical Stress. Introduction. Scope LED PORTFOLIO

LUXEON LEDs. Circuit Design and Layout Practices to Minimize Electrical Stress. Introduction. Scope LED PORTFOLIO LED PORTFOLIO LUXEON LEDs Circuit Design and Layout Practices to Minimize Electrical Stress Introduction LED circuits operating in the real world can be subjected to various abnormal electrical overstress

More information

Treatment options for hydrogen sulfide. Testing for hydrogen sulfide

Treatment options for hydrogen sulfide. Testing for hydrogen sulfide Sometimes hot water will have a sour smell, similar to that of an old damp rag. This smell often develops when the thermostat has been lowered to save energy or reduce the potential for scalding. Odor-causing

More information

Problems in Welding of High Strength Aluminium Alloys

Problems in Welding of High Strength Aluminium Alloys Singapore Welding Society Newsletter, September 1999 Problems in Welding of High Strength Aluminium Alloys Wei Zhou Nanyang Technological University, Singapore E-mail: WZhou@Cantab.Net Pure aluminium has

More information

Name: Class: Date: ID: A

Name: Class: Date: ID: A Name: Class: Date: ID: A Chapter 2 Assessment Multiple Choice Identify the choice that best completes the statement or answers the question. Complete short answer questions on a separate sheet of paper.

More information

DIN 2403 Identification of pipelines according to the fluid conveyed. Marking of pipes according to fluid transported

DIN 2403 Identification of pipelines according to the fluid conveyed. Marking of pipes according to fluid transported DIN 2403 Identification of pipelines according to the fluid conveyed. Marking of pipes according to fluid transported 1 Field of application This standard specifies the colours for the identification of

More information

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS Meher Capacitors offers reliable and innovative products and solutions in the fields of Reactive Power Compensation, Power Quality and Energy

More information

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Title MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Duration 5 days Training Date MV, HV and EHV Switchgear Testing & Commissioning 5 20 24 Apr $3,750 Dubai, UAE In any of the 5 star

More information

. Failure. Analysis... Report...

. Failure. Analysis... Report... . Failure. Analysis... Report..... for (Generation Company) (Station) Purchase Order Number XXXX (Dated XX/XX/XXXX) Report N-XXXX-FA, Revision 0 Schulz Electric Company Job Number N-XXXX Motor ID Number

More information

PBX Series Quick Fit Connector Bimetallic Steam Traps

PBX Series Quick Fit Connector Bimetallic Steam Traps 6262100/6 IM-P626-01 ST Issue 6 PBX Series Quick Fit Connector Bimetallic Steam Traps Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Commissioning

More information

T A B L E T 1 T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A

T A B L E T 1 T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A T A B L E T 1 1 of 7 Tests & Inspection Cable PCUT & PCUT-A (Table T1) T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A No. Test Scale MOC Requirements G 20:10:001:01 Defined Test

More information

Practical Transformers: Operation, Maintenance and Testing

Practical Transformers: Operation, Maintenance and Testing Practical Transformers: Operation, Maintenance and Testing YOU WILL GAIN: 4 hour live, practical online course Saturday, 2 nd May, 2015 8.00AM WST; 10.00AM AEST An understanding of the fundamental theory

More information

IB Chemistry. DP Chemistry Review

IB Chemistry. DP Chemistry Review DP Chemistry Review Topic 1: Quantitative chemistry 1.1 The mole concept and Avogadro s constant Assessment statement Apply the mole concept to substances. Determine the number of particles and the amount

More information

ph Value of Common Household Items and the Environmental Effects ph on Water; http://www.epa.gov/acidrain/education/site_students/phscale.

ph Value of Common Household Items and the Environmental Effects ph on Water; http://www.epa.gov/acidrain/education/site_students/phscale. ACID RAIN What is acid rain? Acid rain is a broad term that is often used to describe several forms of acid deposition. Wet deposition is when rain, snow, fog, or mist contains high amounts of sulfuric

More information

AN UPDATE ON UNDERSTANDING CORROSIVE SULFUR PROBLEMS IN ELECTRIC APPARATUS. Paul J. Griffin and Lance R. Lewand Doble Engineering Company

AN UPDATE ON UNDERSTANDING CORROSIVE SULFUR PROBLEMS IN ELECTRIC APPARATUS. Paul J. Griffin and Lance R. Lewand Doble Engineering Company AN UPDATE ON UNDERSTANDING CORROSIVE SULFUR PROBLEMS IN ELECTRIC APPARATUS ABSTRACT Paul J. Griffin and Lance R. Lewand Doble Engineering Company Corrosive sulfur oil is known to have caused problems in

More information

Electrical Predictive and Preventative Maintenance

Electrical Predictive and Preventative Maintenance Electrical Predictive and Preventative Maintenance Electrical and mechanical equipment is subject to failure at the worst possible time for no apparent reason. - Mose Ramieh III There are two types

More information

The Effect. Spring Pressure. Carbon Brush Wear Rate

The Effect. Spring Pressure. Carbon Brush Wear Rate The Effect of Spring Pressure on Carbon Brush Wear Rate Jeff D. Koenitzer, P.E. Milwaukee, Wisconsin, USA Preface 2008 For decades there was extensive testing of countless different carbon brush contact

More information

The Contractor shall furnish and install all shielded power cable suitable for use on this project.

The Contractor shall furnish and install all shielded power cable suitable for use on this project. Section 16122 PRIMARY POWER CABLES PART 1 GENERAL: WORK INCLUDED The Contractor shall furnish and install all shielded power cable suitable for use on this project. RELATED WORK Section 16020: Tests SUBMITTALS

More information

Lecture 11. Etching Techniques Reading: Chapter 11. ECE 6450 - Dr. Alan Doolittle

Lecture 11. Etching Techniques Reading: Chapter 11. ECE 6450 - Dr. Alan Doolittle Lecture 11 Etching Techniques Reading: Chapter 11 Etching Techniques Characterized by: 1.) Etch rate (A/minute) 2.) Selectivity: S=etch rate material 1 / etch rate material 2 is said to have a selectivity

More information

Vacuum Evaporation Recap

Vacuum Evaporation Recap Sputtering Vacuum Evaporation Recap Use high temperatures at high vacuum to evaporate (eject) atoms or molecules off a material surface. Use ballistic flow to transport them to a substrate and deposit.

More information

Chapter Test A. Elements, Compounds, and Mixtures MULTIPLE CHOICE. chemically combined? MIXs2 a. element b. compound c. mixture d.

Chapter Test A. Elements, Compounds, and Mixtures MULTIPLE CHOICE. chemically combined? MIXs2 a. element b. compound c. mixture d. Assessment Chapter Test A Elements, Compounds, and Mixtures MULTIPLE CHOICE Write the letter of the correct answer in the space provided. 1. What is a pure substance made of two or more elements that are

More information

TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS. What Is Tan δ, Or Tan Delta?

TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS. What Is Tan δ, Or Tan Delta? TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS What Is Tan δ, Or Tan Delta? Tan Delta, also called Loss Angle or Dissipation Factor testing, is a diagnostic method of testing

More information

Johnson Controls Parts Centre. Sabroe S68 refrigeration oil

Johnson Controls Parts Centre. Sabroe S68 refrigeration oil Johnson Controls Parts Centre refrigeration oil Hydro-treated, high performance oil for refrigeration Sabroe offers the highest quality lubricants available for today s refrigeration market. The increased

More information

Chapter 2: The Chemical Context of Life

Chapter 2: The Chemical Context of Life Chapter 2: The Chemical Context of Life Name Period This chapter covers the basics that you may have learned in your chemistry class. Whether your teacher goes over this chapter, or assigns it for you

More information

CAUTION. 4. Cable Connections DANGER WARNING CAUTION. 3. Bushing Components

CAUTION. 4. Cable Connections DANGER WARNING CAUTION. 3. Bushing Components Instruction Manual for POC Bushings 1. Scope This instruction contains general procedures to be followed during receiving, installation, storage and maintenance of all PCORE POC bushings. This instruction

More information

Article published: May 2004, www.flowcontrolnetwork.com

Article published: May 2004, www.flowcontrolnetwork.com Article published: May 2004, www.flowcontrolnetwork.com Electrostatic Filtration How Saturn Quadrupled Its Hydraulic Oil Life by Mickey Jackson My vantage point: It has been my privilege to serve as a

More information

Physical & Chemical Properties. Properties

Physical & Chemical Properties. Properties Physical & Chemical Properties Properties Carbon black can be broadly defined as very fine particulate aggregates of carbon possessing an amorphous quasi-graphitic molecular structure. The most significant

More information

electrical services WWW.AU.SGS.COM/INDUSTRIAL

electrical services WWW.AU.SGS.COM/INDUSTRIAL electrical services WWW.AU.SGS.COM/INDUSTRIAL OUR PROFILE SGS offers a full range of electrical engineering services covering the commissioning test of new plant as well as the maintenance and continual

More information

Peasouper Operator s Manual

Peasouper Operator s Manual Peasouper Operator s Manual Contact Information Le Maitre Special Effects, Inc. Canada 1960 Blue Heron Drive, London, ON. N6H 5L9 Phone Direct: (519) 659.7972 Phone Toll Free Direct: (800) 388.0617 Fax:

More information