The Negative Branch Impedance in the Transformer Sequence Circuit Model

Size: px
Start display at page:

Download "The Negative Branch Impedance in the Transformer Sequence Circuit Model"

Transcription

1 The Negative Branch Impedance in the Transformer Sequence ircuit Model Elmo Price ABB Inc. Krzysztof Kulasek ABB Inc. Gary Kobet Tennessee Valley Authority Introduction The neutral (to ground) or delta tertiary current in transformers with high and low voltage wye-grounded windings and a delta tertiary winding is usually used to provide a sensitive polarizing quantity for legacy discrete directional relays or microprocessor functions to determine correct fault direction on transmission lines. A common assumption is that the polarizing current, either neutral current, I N, and delta current, I 0, as shown in figure 1(a) is always in the same direction regardless of the fault location being on the high () or low () voltage side. owever, incorrect directional relay (function) operations have occurred due to the reversal of the polarizing current obtained from either of the two locations. The current reversal is the result of transformer design characteristics that produce a negative or very small positive branch impedance value in its equivalent circuit model usually the low voltage. Refer to figure 1(b). This paper will address the development and effect of the sequence circuit model on polarizing current reversals and the aspects of transformer design that affect it. Also, a review of transformer characteristics and their application from two utilities is provided to identify potential application issues and their mitigation I N 2 N I 0 1 I 0 S Z 0 I 0 (+/-) Z 0 Z Polarizing urrent N 2 (a) Autotransformer with delta tertiary (b) Zero sequence circuit Figure 1. Expected current direction in an autotransformer and its zero sequence model for a ground fault on the high or low voltage side Leakage impedance First it is important to have a fundamental understanding of leakage impedance between transformer windings. Leakage impedance is directly related to leakage flux. Leakage flux is that part of the total flux that is produced by energizing a winding that does not link the other winding. This is illustrated rather simply in figure 2(a) where φ L is the leakage flux produced when the primary P winding is energized and

2 does not link (flow through the center of) the secondary S winding. Figure 2(b) illustrates the leakage flux where the primary and secondary are wound concentrically. φl - leakage Primary Secondary Secondary Primary φl - leakage E P N P N S ES ORE φps - links primary and secondary coils (a) Leakage flux illustration Figure 2. Leakage flux φl - leakage (b) Leakage flux between concentric windings Since the amount of flux in the secondary winding (the winding not directly energized in this case) is smaller than that in the primary winding there will be a smaller percent voltage induced into the secondary winding. Percent (leakage) impedance between two windings represents the induced voltage difference (drop) between the two windings. Figures 3 and 4 show the main parameters that influence the leakage impedance between windings where the windings are circular and wound concentrically on the core. This would be typical of core form construction. Shell form construction will be constructed differently, but equally as complex. The parameters include, but are not limited to, the winding diameters, winding heights, winding radial build, winding turns, the duct space between windings, the winding s placement relative to the core and the winding connections. The following approximate formula is provided to illustrate how the relative winding-to-winding impedances change with the transformer geometry [2] using the impedance as an example. 6 N I D + D t + t Z = f ( + d ) K R [%] e hw 2 3 Where: t + t + d K R = 1 - Rogowski factor π hw D, D, D - Mean winding diameters t, t, t - Radial build of the winding d, d, d - Duct space between windings h W Winding height (or average winding height in case there are not equal) e volt-per-turn NI = N 1 I 1 = N 2 I 2 mmf (ampere-turns) at the reference current of winding of the pair f Frequency (1) The above equation shows the impedance calculated for the - windings. Other impedances for a 3 winding transformer (- and -) can be calculated as well using the dimensions as per figure 3. 2

3 Primary winding N Primary winding turns D Primary winding mean diameter D D D N T N S N P Series ommon D D D N T N S N P Secondary winding N Secondary winding turns D Secondary winding mean diameter Tertiary winding N Tertiary winding turns D Tertiary winding mean diameter h h Winding height d, d, d Duct space between windings t, t, t Winding radial build ORE d (a) onventional D three winding d d 00 2 S ORE t (b) Autotransformer D Figure 3. Parameters affecting leakage impedance between windings t t Series ommon Series ommon Series ommon 00 2 (a) onfiguration 1 Tertiary next to core ORE ORE 2 00 (b) onfiguration 2 Tertiary between series and common winding Figure 4. Placement of tertiary winding ORE 2 00 (c) onfiguration 3 Tertiary outside of series winding Equation (1) can be also used to calculate the impedance of an autotransformer. In that case we should enter N I either for the common or the series winding. The calculated impedance - is on the basis of the equivalent power, not the rated (through) power. owever, in system studies we have to refer to the rated power and therefore, this impedance must be multiplied by the reduction factor R which is equal to (V V )/ V. Impedance - can be calculated directly from the equation (1). owever, when calculating the - impedance for an autotransformer winding arrangement as per fig. 3b one has to take into consideration that the current will flow in the series and common winding (see fig. 6 b) and therefore the total ampere-turns have to be considered with the equivalent and winding dimensions. The calculation of winding-to-winding leakage impedance becomes increasingly difficult with additional windings and their relative placement (for example, with the tertiary winding located between and L (fig. 4 b) windings). This task is generally left to the manufacturers using FEM (finite element method) design programs for the magnetic field calculations. 3

4 When working on a new transformer design or running a system study engineers have to consider transformer and network impedances when calculating short circuit currents and forces. Symmetrical and unsymmetrical fault cases must be evaluated to find the maximum mechanical and thermal stress for the design. The method of the symmetrical components is used to calculate short circuit current. It is described in several publications including the Electrical Transmission and Distribution Reference Book [1]. The paragraph above described how the positive sequence impedance for a transformer can be calculated. The negative sequence is equal to the positive. The calculations of the zero sequence impedance of a transformer are more complex and cannot be represented by simplified formulas. In general the following factors must be considered: transformer construction (shell or core type), type of the core (three or five legs), windings connections, presence of the neutral terminal (N), and existence of a delta connected winding. When zero-sequence current flows in only one winding of a phase (e.g. the secondary winding in the -N connection) without corresponding balancing ampere-turns in another winding, a flux in all three phase legs will be generated that have equal amplitude and the same phase angle. The return path for this flux will depend on the transformer core construction. Three single-phase units, three-phase shell form and three-phase five-legged core form units (see fig. 5, a, c and d) offer a low reluctance return path through the core, and therefore, the zero sequence impedance will be high. The values will be of the order of the magnetizing branch impedance. For a three-phase three-legged design (see fig. 5(b)) with a wye-wye connection the zero sequence flux saturates the top and bottom core yokes forcing a return path of the flux outside of the core. The flux in this case will have a relatively high reluctance path, and therefore a low zero sequence impedance. owever, this impedance is usually 5 to 10 times greater than the positive sequence leakage impedance between winding [2]. This order of magnitude is due to the effect of the tank that can be regarded as a short-circuited delta connected winding for the circulation of zero sequence currents. The zero-sequence impedances in these cases are influenced by the degree of saturation in the core and, therefore, will vary with the zero-sequence currents. When zero-sequence currents can flow through two windings per phase, with equal and opposite ampereturns (D-N connection), the transformer zero-sequence impedance approaches the positive sequence leakage impedance between those two windings. Analysis of that with different winding connections is given in reference [2]. The zero sequence impedance, and therefore its relation/ratio to positive sequence impedance, varies greatly depending on: Winding arrangement Winding connection - wye or delta Winding location relative to core and other windings Whether LV windings are vertically stacked Transformer core construction The above factors cause the Z 0/Z 1 ratio to vary in value between a minimum of around 0.35 to nearly 1.0. When working on the short circuit calculations of a power transformer the designer has to calculate the zero sequence impedance with good accuracy. Using a factor may lead to wrong calculation of the current and under or overestimate the S currents. Since the forces are proportional to the square of the current it is an important factor in the design evaluation. It is equally important for the protection engineer to have accurate winding-to-winding zero sequence impedances rather than depending on factors. 4

5 A I 0 B I 0 I 0 φ 0 φ 0 φ 0 A I 0 φ 0 3I 0 (a) Three single phase cores A B I 0 I 0 I 0 B A I 0 I 0 I 0 B I 0 φ 0 φ0 φ 0 φ 0 φ0 φ 0 φ 0 I 0 3I 0 φ 0 3I 0 3I 0 (b) Three phase three legged core form Impedance testing (c) Three phase five legged core form Figure 5. Zero sequence flux path for different transformer core constructions (d) Three phase shell form Impedance testing of a transformer is addressed in IEEE Standard , Section 9. Testing measures the positive and zero sequence impedances between any two windings. Zero sequence testing is essential when an accurate transformer model is needed for ground fault studies and polarization current requirements. Basically, positive sequence impedance is measured between windings by applying a voltage to one winding and shorting the other winding being tested. All other windings are left open. The voltage is increased until the winding s nominal rated current is flowing. Since the current is at 100% of rated the measured voltage in % of rated voltage is equal to the % impedance between the two windings. The losses are also measured to give the real (resistance) part of the impedance. Resistance, however, will not be considered further in this paper. The basic test connections for a single-phase three winding conventional and autotransformer are shown in figure 6. I T I T V T I V T I I I I I Z Z Z Z Z Z (a) onventional transformer (b) Autotransformer Figure 6. Test connections for a single-phase three winding D conventional and autotransformer Single phase units do not require zero sequence testing as the positive and zero sequence impedances are equal. This is also generally true for three phase shell form designs and core form designs with more than three legs. Zero sequence testing is warranted for three legged core designs with or without a delta 5

6 winding. Test connections for a three-phase D autotransformer with a delta tertiary winding are shown in figure 7. These tests will provide the transformer s positive and zero sequence impedances. Zero sequence testing will include the effect of the tank [acting as a buried tertiary winding]. Testing the zero sequence impedance between windings of a three-phase transformer uses a single phase voltage source and the connections of figures 7(c) and 7(d). Also, not shown, is the test connection for Z 0 where in figure 7(d) the test voltage is applied to the terminals of the common winding and the terminals are left open. The standard provides the connections and equations to determine the zero sequence T branch model. The difference between the positive and zero sequence impedances is the effect of the core and tank design on zero sequence flux I 2 3 I 3 I T 3 I=0 I T 3 I 1 V T I 3 2 N 1 S 1 1 V T 2 N 1 S 1 1 V I 2 I 1 2 V (a) Three-phase autotransformer Z 1 positive sequence test (b) Three-phase autotransformer Z 1 positive sequence test (accessible delta tertiary winding connections) 3I I I 0 I 0 V N I 0 1 S I V N I 0 1 S I I 0 2 ommon winding terminals shorted and grounded. I 0 2 ommon winding terminals open circuited. 2 2 (c) Three-phase autotransformer Z 0 zero sequence test (d) Three-phase autotransformer Z 0 zero sequence test Figure 7. Three-phase positive and zero sequence impedance tests 6

7 The effect of tertiary winding placement There are multiple types of transformers where particular application and system conditions set the ratings, working conditions and unit application; substation, distribution and network tie autotransformers. The most common in the USA and in anada for V transmission lines are autotransformers. The electrical characteristics of an autotransformer or any other three winding D transformer are generally represented in system analysis by an equivalent circuit T diagram as shown in figure 8(b). When impedances Z, Z and Z of figure 8(a) are known equivalent Z, Z and Z of figure 8(b) are calculated using equations 2 4 where all impedances are expressed in percent or per unit on the same reference power (MVA base). Z Z Z Z Z Z (a) Three winding transformer sequence circuit model with winding-to-winding impedances as tested (b) Three winding transformer sequence circuit equivalent T model Figure 8. Equivalent T diagram for an autotransformer ZZ = ZZ + ZZ ZZ 2 ZZ = ZZ + ZZ ZZ 2 ZZ = ZZ + ZZ ZZ 2 (2) (3) (4) Unless all impedances between different systems are listed in the transformer specification a designer can choose to put the delta connected winding in three different relative positions in relation to the high and low voltage winding as presented in figure 4. The selection is based on the optimized production cost and loss evaluation. Generally this is configuration 1 of figure 4(a), which is guided primarily by insulation requirements. In some applications, however, it could be beneficial to have the tertiary () winding as the outermost and wind the main low () and high () voltage coils with smaller diameters as shown in configuration 3 of figure 4(c). This is often feasible for transformers with a high / turns ratio such as 260/72 kv or 345/34.5 kv because it will reduce copper weight and load losses in the main windings and offset the cost of insulation. Such high turns ratio applications with an outer tertiary winding are being used with wind farm and other small generation utilities. With the same reference power the impedance between windings is a function of the geometry as was explained earlier when discussing equation (1). Figures 3 and 4 also give a visual explanation of the dimensions and tertiary placement. When looking at the winding configuration 1 of figure 4(a) we can 7

8 see that the impedances based on the distance between windings that Z and Z are smaller than Z, at the same time Z + Z is very close in value to Z being slightly larger or smaller due to the variance in other parameters. Using the equation (3) above for this winding configuration we can see that in the equivalent T diagram low voltage impedance, Z, may have a small negative value with the right parameter values. It will be a similar situation for the configuration 3 of figure 4(c) where the impedances Z + Z < Z is possible using equation (2). In case it is required to have all positive branch impedances in the T diagram, winding configuration 2 of figure 4(b) can be used. This cannot be changed by adding a reactor in the tertiary winding (to limit current during faults) since this will simultaneously increase impedances ZZ and ZZ. In order to illustrate the change in the impedances, short circuit zero sequence currents and other transformer design criteria, the authors selected a 280 MVA 161.7/69 kv autotransformer with a 56.6 MVA 13.8 kv buried tertiary winding. Analysis included the 3 winding configurations per figure 4. Fault currents were calculated using IEEE with Z0/Z1=1 for the V and LV systems. The equivalent sequence network used is shown in figure 9. Sequence circuit interconnection for fault on high voltage () side Sequence circuit interconnection for fault on low voltage () side Z S1 Z 1 Z 1 Z LS1 1.0 pu I 1 Z 1 I pu Positive Z S2 Z 1 Z 1 Z LS2 I 2 Z 1 I 2 Negative Z S0 Z 0 Z 0 Z LS0 I 0 I 0 Z 0 I 0 Zero Figure 9. Sequence network interconnection for analysis Results are shown in tables 1 and 2. Analysis shows that there are zero sequence current reversals in the tertiary and common windings for configurations 1 and 3. It is also shown that with positive tertiary current a reversal in the common winding can still occur. Table MVA Autotransformer - impedances for different winding arrangements. Winding configuration Positive sequence Impedance Positive sequence impedance 8

9 ore-tv-lv-v ore-lv-tv-v ore-lv-vr-v-tv All impedances are in % on MVA base at rated winding voltage. ZBase = kv 2 /MVA, ZΩ = ZBase x Z%/100 VR - regulating winding Table MVA Autotransformer Zero sequence currents for single Φ-G ground fault on V and LV S ase Winding V (ka) LV (ka) TV (ka) configuration Line Series Line ommon Line Winding winding winding 1φ fault on V φ fault on LV The effect of the negative branch impedance on current polarization All of the measured winding-to-winding impedances in table 1 above will be positive. One of the branch impedances, however, is likely to be negative unless design constraints are imposed. With winding configuration 1 being the usual case, Z will be the largest of the three branch impedances, possibly causing Z to be negative. In Figure 10(a), k 0 represents the per-unit current that flows in the Z leg with 1.0 per unit of current flowing to the point of discontinuity (for example a ground fault) on the highvoltage system. This distribution factor is very important in identifying whether or not neutral or tertiary current in the transformer is a reliable polarizing quantity. Z S0 is the source impedance for the low voltage system. With one per-unit current flowing in the high voltage winding, for a ground fault on the highvoltage system, k 0 per-unit current flows in the low voltage system and 1- k 0 flows to ground through the common and tertiary windings. Translating per unit current to amperes, in figure 10(b) with one ampere of zero sequence current in the high voltage winding of an autotransformer, there will be k 0V /V amperes of zero sequence current in the low voltage system, 1 - k 0V /V amperes of zero sequence current will flow to ground through the common winding and (1 - k 0)V /V amperes will circulate in the delta tertiary winding. For the conventional three winding transformer of figure 10(c) the currents have the same high and low side ct primary distribution, the ct secondary neutral current sum and tertiary current are proportional to (1 k 0) provided the neutral cts have the ratios as indicated. Therefore, the neutral sum of a conventional transformer does not have the same limitations as an autotransformer neutral. 9

10 k 0 = Z LS0 k 0 Z 0 Z 0 + Z LS0 + Z 0 Z 0 Z 0 1-k pu Z 0 Tertiary current reverses if k 0 > 1 (a) Zero sequence circuit of a three winding transformer (values in perunit) k 0 V /V 1.0 (1 - k 0 )V /V Polarizing urrent 3(1 - k 0 V /V ) (b) Relative ampere values in autotransformer k 0 V /V V /V :1 1:1 1.0 (1 - k 0 )V /V Polarizing urrent 3(1 - k 0 ) (c) Relative ampere values in three winding transformer Figure 10. Zero sequence current reversal in the delta tertiary and common windings The summary of requirements for correct operation (no current reversal) for a fault on the high voltage side is: ZZ From figure 9 kk 0xx = 0 ZZ 0 +ZZ LLLL0 +ZZ 0 (5) Delta kk 0xx < 1 (6) Neutral kk 0xx < VV /VV (7) Equations for correct operation for a fault on the low side are derived similarly as: ZZ kk 0h = 0 ZZ 0 +ZZ 0 +ZZ 0 (8) Delta kk 0h < 1 (9) Neutral kk 0h < VV /VV (10) Usually there are no issues for faults on the low side of the transformer (equations 8 10). Most transformer designs will not usually result in a negative Z O branch and therefore k 0h will be less than 1. owever, it was shown in tables 1 and 2 that a unit such as configuration 3 (winding placement from the core:, and ) could result in k 0h of equation (9) not being satisfied and the delta tertiary winding current reverses. On the other hand the neutral current would most likely always be a good polarizing source. Analyzing the values for a high voltage fault (equations 5 7) we reach some very important conclusions; the common neutral of a wye-delta-wye three winding transformer or the neutral of a wye-wye autotransformer with a delta tertiary will supply a reliable polarizing current only if k 0 < V/V. If it were greater than the ratio V/V, the direction of the polarizing current to the relay would be in the opposite direction to that shown in figure 10(b or c). This is unacceptable because this current should always be up the neutral when there is current flow to a ground fault on the low voltage wye system. Also, keep in mind that k 0 may even be greater than V/V for small positive values of the low side impedance Z LS0 + Z 0 causing a neutral polarizing current reversal. The delta winding of such a transformer is virtually always a reliable polarizing source unless the net impedance to the system is not positive. For example, if the quantity Z LS0 + Z 0 is negative, the current inside the delta would not be suitable as a polarizing source. When using polarizing current one must stay aware of the application s sensitivity to decreasing source impedance with system configuration changes. As systems grow and become more interconnected, the 10

11 short circuit capacity increases and thus reduces the high and low voltage source impedances to the transformer. A previously installed application, which operated correctly, may misoperate due to the subsequent system changes. Field data analysis Autotransformer application impedance data from two utilities can be found in Appendix A. Table 3 summarizes the data. Table 3. Summary of autotransformer application data Utility A Utility B Both Total units in survey # (%) with negative high side branch impedance # (%) with negative low side branch impedance 42 (72%) 17 (61%) 60 (71%) # (%) not suitable for tertiary current polarization, k 0 > 1 1 (2%) 0 1 (1%) # (%) not suitable for neutral current polarization, k 0 > V /V 38 (67%) 10 (36%) 48(56%) The study of the utility applications suggests that autotransformers are designed, unless otherwise specified, with their winding configuration build from core, -- as shown in figure 4(a), such that negative low voltage branch impedance in the auto transformer equivalent circuit is rather common occurring in 60% to 75% of transmission voltage level autotransformers. These negative impedances are generally small enough such that the low voltage source impedance overcomes the effect of the transformer s negative low voltage branch impedance making the use of the delta tertiary suitable for most applications 99% of the applications studied here. owever, 71% of these are subject to the possibility of decreasing source impedances due to system changes. In 56% of the cases studied the transformer s neutral current is not suitable as a polarizing source. These numbers will vary with transformer design and likewise from utility to utility that use them. A review of each utility s applications the following: Utility A Most applications involving newer technology used voltage polarizing Tertiary current polarizing was used mostly for legacy products where available Neutral current polarizing was not used Utility B Most applications involving newer technology used voltage polarizing Tertiary current polarizing was used where available mostly for legacy products and newer products where dual polarization (using both voltage and current) was desired. Polarizing current derived from high and low voltage line ct connections was used in one application (figure 12(c)). Neutral current polarizing was used in some cases where tertiary current was not available and there were no application issues. While this study was limited to autotransformers it should be noted that conventional full winding transformers are subject to delta tertiary current reversals and the criteria of equations 6 and 9 still apply. 11

12 Mitigation Use Delta Tertiary urrent Where applications of neutral current polarization are not reliable and a current transformer (ct) is available in the unloaded delta tertiary winding (or 3 cts in a loaded tertiary) then it would be possible to change current polarization sources. LOAD Polarizing urrent (a) Buried or non-loaded delta tertiary winding (b) Loaded delta tertiary winding Figure 11. onnection of delta tertiary current transformers V/V k 0 V /V (1 - k 0 )V /V V/V k 0 V /V (1 - k 0 )V /V 3 3k 0 3 3V /V S 3 S 3k 0 I P = 3(1 - k 0 ) Aux ct /(S+)= V /V V/V I NS = 3(V /V - k 0 ) (a) Polarizing with neutral and low voltage cts I N = 3(1 - k 0 V /V ) I N = 3(1 - k 0 V /V ) 3k 0 V /V 1 Aux ct /(S+)= V /V I NS = 3(1 - k 0 V /V ) (b) Polarizing with neutral and high voltage cts I P = 3(1 - k 0 ) I P = 3(1 - k 0 ) 3 3k k 0 V /V (1 - k 0 )V /V V/V I N = 3(1 - k 0 V /V ) (c) Polarizing with high and low voltage cts Figure 12. Delta tertiary polarizing current using neutral, high voltage and low voltage cts As is sometimes the case tertiary cts may not have been provided. In such cases it is possible to obtain a secondary ct polarization current that is equal to the tertiary ct secondary current by using a combination 12

13 of the neutral, high voltage and low voltage cts. Three connection methods are shown in figure 12. These are polarizing with the neutral and sum of low voltage cts, polarizing with the neutral and sum of high voltage cts and polarizing with the sums of high and low voltage cts. An auxiliary current-balancing auto transformer is required for connections with the neutral ct. The neutral ct has the same ratio as the high or low voltage cts with which it is being used and the ct ratios are normalized with the high voltage ct ratio equal to 1 to simplify the expressions. The ct schemes may be subject to incorrect operation if a fault occurs within the zone defined by the ct locations. It is expected that other protections, e.g. transformer differential and restricted earth fault, will have operated. If tertiary current cannot be used based on the provided criteria then sequence voltage or current compensated sequence voltage is suggested. Transformer Design The issue of polarizing current reversal can be eliminated through transformer design. Using configuration 2 of figure 4(b) is an example. In this case the tertiary is placed between the high and low voltage windings altering the tested winding-to-winding impedances and calculated branch impedances shown in table 1. With these impedances immunity to polarizing current reversal is guaranteed barring human connection errors. This can be validated by calculating k 0 for both high and low voltage faults with source impedance set to zero (I S0 = I LS0 = 0) and using equations If both k 0h and k 0l values meet the criteria of the equations then there will never be issues. Alternative Polarizing Methods The primary advantage of current polarization is that the quantity provides more sensitive directional control in those applications where measuring a polarizing voltage may be a problem. This is particularly true when polarizing voltage is measured near a strong ground source (small source impedance). Also, using polarizing current has been a long established with many utilities and is very much a part of their installed base where changing to alternative methods can be very expensive. In such cases frequent review of the application is warranted. Zero and Negative sequence voltages are far more reliable polarization methods, and are indeed preferred, if sensitivity is not an issue. This is particularly true in applications where mutual coupling affects the reliability of both zero sequence voltage and current polarization methods and negative sequence voltage polarization has to be used. With the increased use of microprocessor technology methods have been developed to reliably compensate zero and negative sequence polarizing voltages with the respective line zero or negative sequence current to address sensitivity issues. One method is illustrated in figure 13. In figure 13(a) we see the zero sequence voltage profile for a forward fault. The zero (or negative) sequence voltage is highest at the fault location and reduces in value as the measurement moves back towards a source. The zero sequence voltage measured at relay A is the voltage drop across the source impedance and equal to I 0AZ 0A. This quantity may not be a voltage sufficient for polarizing. Observe the voltage profile. By adding some line impedance voltage drop, I 0AkZ 0L, to the measured quantity we get I 0A(Z 0A + kz 0L), a quantity sufficient for polarization for detecting forward faults accurately. This is as if the voltage transformer was moved out on the transmission line by a distance k times line length. Now we must investigate how setting this compensation affects reverse faults. Observe the voltage profile on figure 13(b) for a reverse fault. Reliable polarizing for a reverse fault requires that (Z 0L + Z 0B) > kz 0L plus some margin to assure sufficient reverse fault voltage polarization. If the protected line, Z 0L, is long (in impedance) and k is set less than 0.4 there is no problem. 13

14 These methods vary from manufacturer to manufacturer, but all generally work the same. Applying this compensation usually eliminates the need for the transformer polarizing current for these applications. -V 0 - I 0A (kz 0L ) Fault Location Zero Sequence Voltage Distribution Z 0A kz 0L mz 0L (1-m)Z 0L Z 0B I 0A REL A V 0A = - I 0A Z 0A V 0k = - I 0A(Z 0A+kZ 0L) V 0(MA) REL B I 0B A (a) Forward Fault Fault Location B -V 0 I 0B (kz 0L ) Zero Sequence Voltage Distribution Z 0A I 0B Z 0L Z 0B I 0A V 0(MA) REL A V0k = - I 0B (Z 0B +(1-k)Z 0L ) V 0A = - I 0B (Z 0B +Z 0L ) REL B I 0B A Fault Location (b) Reverse Fault B Figure 13. ompensating zero sequence voltage with zero sequence line current onclusions and Recommendations The negative branch impedance of the transformer s T branch model was investigated as to its effects on current reversals in the delta tertiary winding and transformer neutral. Along with the negative branch values small positive values allowed current reversals in the transformer s neutral. Given the importance of accuracy the model should be developed with zero sequence impedances derived from zero sequence testing. It was also pointed out how transformer design affects the T branch model. Generally the negative or low impedance is on the low voltage side of the transformer model. owever, different winding configurations can eliminate or even move the negative impedance to the high voltage side. The latter case being possible or even likely for transformers with high / turns ratios (e.g. 345/34.5/13.8 kv). The following recommendations are made from the results of the investigation. Voltage polarization and impedance compensated voltage polarization are wise alternatives and are recommended as first choices. Reliable polarization current can generally always be obtained from the delta tertiary winding. There are a few exceptions where zero sequence source impedance is very small and does not allow its use. Also schemes involving the neutral and line cts are available to provide a proportional quantity when tertiary windings are not provided with cts. Each application should be reviewed with system changes. 14

15 Polarization current from the neutral ct is not generally reliable and, therefore, not recommended where alternatives are available. Using the neutral ct connected to line cts with an auxiliary transformer may very well be suitable. Accurate zero sequence testing is desired for development of the T branch model. The problem of negative branch impedances can be eliminated with the design of transformer winding configurations. The possible extra costs, first and evaluated, should be considered. References [1] Electrical Transmission and Distribution Reference Book. ABB Inc. Raleigh, North arolina [2] Giorgio Bertagnolli. Short ircuit Duty of Power Transformers. ABB Ltd. Zurich, Switzerland 2007 [3] Elmore, W., Price, E. Polarization Fundamentals. 27 th Annual Western Protective Relay onference. Spokane, Washington. October 24 26, [4] Andrichak, J., Patel, S. Polarizing Sources for Directional Ground Relays. Publication GER3182A. GE power Management. Malvern, PA. [4] IEEE Standard , 2010 [5] IEEE Standard ,

16 Biographies Elmo Price, PE Elmo is currently a Senior onsultant with ABB Inc. e received his BSEE degree in 1970 from Lamar State ollege of Technology and his MSEE degree in 1978 from the University of Pittsburgh. e began his career with Westinghouse in 1970 and worked in many engineering positions in various manufacturing divisions, and as a District Engineer located in New Orleans providing engineering support for Westinghouse power system products. With the consolidation of Westinghouse into ABB in 1988 Elmo assumed regional responsibility for product application for the Protective Relay Division. Since then he has worked in various technical management positions responsible for product management, product design, application support and relay schools. Elmo is a registered professional engineer and a Life Senior member of the IEEE. e is a member of the IEEE Power System Relay ommittee and the Line Protection Subcommittee, serving as a contributing member to many working groups. e has two patents and has authored and presented numerous industry papers. Krzysztof Kulasek Krzysztof is Vice President of Engineering for ABB Large and Medium Power Transformers in North America located in Varennes, Q, anada. While working in the transformer business for more than 20 years he has been involved in new technology implementations in different factories as well as product and production process development. Krzysztof s areas of expertise include: transformer optimization, insulation design, S calculations, stray loss heating, process improvement and production optimization. While being part of the ABB global technical team he contributed to R&D projects, technology and quality improvement initiatives and new engineers training. e received his electrical engineering degree in 1993 at the Technical University of Lodz, Poland from the faculty of Electrical Machines and Transformers and has been an IEEE member since Gary Kobet Gary is an Electrical Engineer (short-term planning) for the Tennessee Valley Authority (TVA) in hattanooga, Tennessee. is responsibilities include machine and voltage stability studies for the operating horizon, developing operating guides, and disturbance analysis. Previously he worked in the System Protection department scoping relaying schemes for transmission and generation projects, as well as developing relay set point calculations. e has performed transient studies using EMTP for breaker TRV studies and switching surge overvoltages. Previously he worked as a field engineer and as power quality specialist. Mr. Kobet earned the B.S.E. (electrical) from the University of Alabama in untsville in 1989 and the M.S.E.E. from Mississippi State University in e is a member of the IEEE Power Engineering Society, IGRE, Eta Kappa Nu, Tau Beta Pi, and is a registered professional engineer in the state of Alabama. Presently he is serving on the NER Geomagnetic Disturbance Task Force. 16

17 Appendix A - Autotransformer Application Data Utility A 17

18 Utility A continued 18

19 Utility B 19

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER

More information

THE PER-UNIT SYSTEM. (2) The per-unit values for various components lie within a narrow range regardless of the equipment rating.

THE PER-UNIT SYSTEM. (2) The per-unit values for various components lie within a narrow range regardless of the equipment rating. THE PER-UNIT SYSTEM An interconnected power system typically consists of many different voltage levels given a system containing several transformers and/or rotating machines. The per-unit system simplifies

More information

Open Phase Conditions in Transformers Analysis and Protection Algorithm

Open Phase Conditions in Transformers Analysis and Protection Algorithm Open Phase Conditions in Transformers Analysis and Protection Algorithm Amir Norouzi GE Digital Energy Markham, ON amir.norouzi@ge.com Abstract This paper first provides an in-depth analysis of open phase

More information

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION ÿþ üûúùø öõöôùóùõò CT Dimensioning DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION Application note GER3973 1 CT Dimensioning ÿþ üûúùø öõöôùóùõò GER-3973 Application note ÿþ üûúùø öõöôùóùõò

More information

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392 1 Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading By Ramandeep Kaur Aujla S.NO 250447392 ES 586b: Theory and applications of protective relays Department of

More information

Protection of Phase Angle Regulating Transformers

Protection of Phase Angle Regulating Transformers Protection of Phase Angle Regulating Transformers A report to the Substation Subcommittee of the IEEE Power System Relaying Committee prepared by Working Group K1 IEEE Special Publication Members of the

More information

Transformer Design & Design Parameters

Transformer Design & Design Parameters Transformer Design & Design Parameters - Ronnie Minhaz, P.Eng. Power Transmission + Distribution GENERATION TRANSMISSION SUB-TRANSMISSION DISTRIBUTION DISTRIBUTED POWER 115/10 or 20 kv 500/230 230/13.8

More information

13 ELECTRIC MOTORS. 13.1 Basic Relations

13 ELECTRIC MOTORS. 13.1 Basic Relations 13 ELECTRIC MOTORS Modern underwater vehicles and surface vessels are making increased use of electrical actuators, for all range of tasks including weaponry, control surfaces, and main propulsion. This

More information

1 Introduction. 2 The Symmetrical Component Transformation. J.L. Kirtley Jr.

1 Introduction. 2 The Symmetrical Component Transformation. J.L. Kirtley Jr. Massachusetts Institute of Technology Department of Electrical Engineering and Computer Science 6.06 Introduction to Power Systems Class Notes Chapter 4 Introduction To Symmetrical Components J.L. Kirtley

More information

100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd

100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd 100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center Introduction Roger Hedding Steven Schoenherr, P.E. ABB Inc. Minnesota Power 598 N. Buth Rd 3215 Arrowhead Rd Dousman,

More information

Tutorial One: Calculation of leakage inductance of transformer using FEM. 31.5 MVA, 132 kv/33kv, Y/, Ampere-turns: 135024, No.

Tutorial One: Calculation of leakage inductance of transformer using FEM. 31.5 MVA, 132 kv/33kv, Y/, Ampere-turns: 135024, No. Tutorial One: Calculation of leakage inductance of transformer using FEM Consider a transformer with the following rating: 31.5 MVA, 132 kv/33kv, Y/, Ampere-turns: 135024, No. of HV turns = 980 Although

More information

The following table shows approximate percentage wise the

The following table shows approximate percentage wise the SHORT-CIRCUIT CALCULATION INTRODUCTION Designing an electrical system is easy and simple, if only the normal operation of the network is taken into consideration. However, abnormal conditions which are

More information

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E. By Darrell G. Broussard, P.E. Introduction: As engineers, we are aware that electrical power systems have grown. How much have they grown? When was the last time you specified a 2400-volt system, a 4160-volt

More information

Power Technology Issue 104. Modeling of Two-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E

Power Technology Issue 104. Modeling of Two-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E SIEMENS Siemens Energy, Inc. Power Technology Issue 104 Modeling of TwoWinding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E Carlos GrandeMoran, Ph.D. Principal Consultant

More information

Transformers. Special transformers Reactors products

Transformers. Special transformers Reactors products Transformers Special transformers Reactors products Reactors Custom designed, custom built ABB Oy Transformers has extensive experience and numerous references from different reactor applications, having

More information

Power Technology Issue 106. Modeling of Three-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E

Power Technology Issue 106. Modeling of Three-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E SIEMENS Siemens Energy, Inc. Power Technology Issue 106 Modeling of Three-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E Carlos Grande-Moran, Ph.D. Principal

More information

Introduction to Paralleling of LTC Transformers by the Circulating Current Method

Introduction to Paralleling of LTC Transformers by the Circulating Current Method TAPCHANGER CONTROLS Application Note #11 Introduction to Paralleling of LTC Transformers by the Circulating Current Method 1.0 ABSTRACT This Application Note discusses the elements of paralleling load

More information

Drive circuit basics + V. τ e. Industrial Circuits Application Note. Winding resistance and inductance

Drive circuit basics + V. τ e. Industrial Circuits Application Note. Winding resistance and inductance ndustrial Circuits Application Note Drive circuit basics For a given size of a stepper motor, a limited space is available for the windings. n the process of optimizing a stepper motor drive system, an

More information

WINDING RESISTANCE TESTING

WINDING RESISTANCE TESTING WINDING RESISTANCE TESTING WINDING RESISTANCE TEST SET, MODEL WRT-100 ADWEL INTERNATIONAL LTD. 60 Ironside Crescent, Unit 9 Scarborough, Ontario, Canada M1X 1G4 Telephone: (416) 321-1988 Fax: (416) 321-1991

More information

HPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80

HPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80 Buck-Boost Transformers Single and Three Phase Potted Buck-Boost Transformers Buck-Boost Applications & Standard Specification... 80 Selecting Buck-Boost Transformers... 81 Single Phase Selection Tables...

More information

GE Multilin technical note

GE Multilin technical note Digital Energy Multilin GE Multilin technical note eutral voltage unbalance function at grounded wye capacitor banks GE publication number: GET-8544 Copyright 00 GE Multilin eutral voltage unbalance function

More information

ACCURACY OF POTENTIALTRANSFORMERS

ACCURACY OF POTENTIALTRANSFORMERS 8 VOLTAGE TRANSFORMERS Two types of voltage transformer are used for protective-relaying purposes, as follows: (1) the "instrument potential transformer," hereafter to be called simply "potential transformer,"

More information

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies DATE: November 17, 1999 REVISION: AUTHOR: John Merrell Introduction In some short circuit studies, the X/R ratio is ignored when comparing

More information

Percentage Restrained Differential, Percentage of What?

Percentage Restrained Differential, Percentage of What? Percentage Restrained Differential, Percentage of What? Michael J. Thompson Schweitzer Engineering Laboratories, Inc. 2011 IEEE. Personal use of this material is permitted. Permission from IEEE must be

More information

7CURRENT TRANSFORMERS

7CURRENT TRANSFORMERS 7CURRENT TRANSFORMERS Protective relays of the a-c type are actuated by current and voltage supplied by current and voltage transformers. These transformers provide insulation against the high voltage

More information

Discussion on Class I & II Terminology. IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA

Discussion on Class I & II Terminology. IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA Discussion on Class I & II Terminology IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA What is Class I & II? C57.12.00 2010 is the only document we have that defined these terms. 5.10 Insulation

More information

DIRECT CURRENT GENERATORS

DIRECT CURRENT GENERATORS DIRECT CURRENT GENERATORS Revision 12:50 14 Nov 05 INTRODUCTION A generator is a machine that converts mechanical energy into electrical energy by using the principle of magnetic induction. This principle

More information

Type SA-1 Generator Differential Relay

Type SA-1 Generator Differential Relay ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065 Instruction Leaflet 41-348.11C Effective: November 1999 Supersedes I.L. 41-348.11B, Dated August 1986 ( ) Denotes

More information

Power Quality Paper #3

Power Quality Paper #3 The Effect of Voltage Dips On Induction Motors by: M D McCulloch 1. INTRODUCTION Voltage depressions caused by faults on the system affect the performance of induction motors, in terms of the production

More information

Shunt Capacitor Bank Fundamentals and Protection

Shunt Capacitor Bank Fundamentals and Protection 2003 Conference for Protective Relay Engineers - Texas A&M University April 8-10, 2003, College Station (TX) Shunt Capacitor Bank Fundamentals and Protection Gustavo Brunello, M.Eng, P.Eng Dr. Bogdan Kasztenny

More information

Outline. Systems and Signals 214 / 244 & Energy Systems 244 / 344. Ideal Inductor. Ideal Inductor (cont... )

Outline. Systems and Signals 214 / 244 & Energy Systems 244 / 344. Ideal Inductor. Ideal Inductor (cont... ) Outline Systems and Signals 214 / 244 & Energy Systems 244 / 344 Inductance, Leakage Inductance, Mutual Inductance & Transformers 1 Inductor revision Ideal Inductor Non-Ideal Inductor Dr. P.J. Randewijk

More information

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS Terence Hazel Senior Member IEEE Schneider Electric 38050 Grenoble France Abstract The power requirements for large industrial sites is increasing.

More information

SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3. Symmetrical Components & Faults Calculations

SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3. Symmetrical Components & Faults Calculations SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3 3.0 Introduction Fortescue's work proves that an unbalanced system of 'n' related phasors can be resolved into 'n' systems of balanced phasors called the

More information

Power Plant Electrical Distribution Systems

Power Plant Electrical Distribution Systems PDH Course E184 Power Plant Electrical Distribution Systems Gary W Castleberry, PE 2008 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com

More information

Instrument Transformers Application Guide

Instrument Transformers Application Guide Instrument Transformers Application Guide Edited by ABB AB High Voltage Products Department: Marketing & Sales Text: Knut Sjövall, ABB Layout, 3D and images: Mats Findell, ABB SE-771 80 LUDVIKA, Sweden

More information

Grounding of Electrical Systems NEW CODE: Grounding and Bonding

Grounding of Electrical Systems NEW CODE: Grounding and Bonding Grounding of Electrical Systems NEW CODE: Grounding and Bonding Presented By Scott Peele PE Grounding of Electrical Systems Outline Defining the Terms Why should I Ground? Types of Grounding Systems Separately

More information

Product Data Bulletin

Product Data Bulletin Product Data Bulletin Power System Harmonics Causes and Effects of Variable Frequency Drives Relative to the IEEE 519-1992 Standard Raleigh, NC, U.S.A. INTRODUCTION This document describes power system

More information

Fault Analysis I13-1. 2008 PowerWorld Corporation

Fault Analysis I13-1. 2008 PowerWorld Corporation Fault Analysis Analysis of power system parameters resulting from a ground or line to line fault somewhere in the system Simulator contains a tool for analyzing faults in an automatic fashion Can perform

More information

CURRENT TRANSFORMERS INSTALLATION GUIDE

CURRENT TRANSFORMERS INSTALLATION GUIDE CURRENT TRANSFORMERS INSTALLATION GUIDE Information contained within this document is subject to change without notice and does not represent a commitment on the part of PRI Ltd or its agents. E&OE. Copyright

More information

Power transformers. Special transformers Railway

Power transformers. Special transformers Railway Power transformers Special transformers Railway A leader in railway systems Our compact and low-weight transformers fully comply with the customer s specifications. The products are developed together

More information

Coupled Inductors. Introducing Coupled Inductors

Coupled Inductors. Introducing Coupled Inductors Coupled Inductors From power distribution across large distances to radio transmissions, coupled inductors are used extensively in electrical applications. Their properties allow for increasing or decreasing

More information

Introduction to PowerWorld Simulator: Interface and Common Tools

Introduction to PowerWorld Simulator: Interface and Common Tools Introduction to PowerWorld Simulator: Interface and Common Tools 2001 South First Street Champaign, Illinois 61820 +1 (217) 384.6330 support@powerworld.com http://www.powerworld.com Fault Analysis Analysis

More information

OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS

OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS Data center power systems are constructed with a premium on reliability at a significant cost. The return on this investment is realized if it

More information

Protection of a Three- Winding Transformer

Protection of a Three- Winding Transformer Protection of a Three- Winding Transformer Three-winding transformer 110 kv/25 kv/10 kv Yyn0d5 25 kv-side: Solidly earthed Protection functions ANSI 87 T - Differential protection ANSI 87 N - Earth-fault

More information

8 Speed control of Induction Machines

8 Speed control of Induction Machines 8 Speed control of Induction Machines We have seen the speed torque characteristic of the machine. In the stable region of operation in the motoring mode, the curve is rather steep and goes from zero torque

More information

Line Reactors and AC Drives

Line Reactors and AC Drives Line Reactors and AC Drives Rockwell Automation Mequon Wisconsin Quite often, line and load reactors are installed on AC drives without a solid understanding of why or what the positive and negative consequences

More information

Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao. x x. x x. Figure 10: Cross sectional view

Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao. x x. x x. Figure 10: Cross sectional view 4 Armature Windings Main field Commutator & Brush Compole field haft v Compensating winding Armature winding Yoke Figure 10: Cross sectional view Fig. 10 gives the cross sectional view of a modern d.c.

More information

Paralleling Power Sources Which Share a Common Neutral

Paralleling Power Sources Which Share a Common Neutral Paralleling Power Sources Which Share a Common Neutral By: Tony Hoevenaars, P.E., President & CEO, Mirus International, Inc. Mike McGraw, President, NSOEM, Inc. When paralleling power sources that share

More information

Presentation of the France Transfo factories

Presentation of the France Transfo factories Presentation of the France Transfo factories France Transfo's internationally recognised and highly esteemed expertise is today exported to more than 80 countries throughout the world. Over the past 15

More information

Basic Load Tap Changer Operation

Basic Load Tap Changer Operation Basic Load Tap Changer Operation Topics Basic Transformer Theory Differences from LTC s to DETC s LTC Definitions Transformer Nameplates Purpose of a Tap Changer How Does an LTC Work? Topics Reactance

More information

System Grounding and Ground-Fault Protection Methods for UPS-Supplied Power Systems

System Grounding and Ground-Fault Protection Methods for UPS-Supplied Power Systems System Grounding and Ground-Fault Protection Methods for -Supplied Power Systems Bill Brown, P.E., Square D Critical Power Competency Center 1. INTRODUCTION The use of solid grounding for -supplied power

More information

Chapter 9 Balanced Faults

Chapter 9 Balanced Faults Chapter 9 alanced Faults 9.1 Introduction The most common types of fault are (in order) single-line-to-ground fault, line-to-line fault, and double-line-to-ground fault. All of these are unbalanced faults.

More information

Step Voltage Regulators

Step Voltage Regulators Step Voltage Regulators Don Wareham Field Application Engineer Today s Agenda Introduction Voltage Regulator theory Voltage Regulator application considerations Installation and proper bypassing Wrap-up/questions

More information

INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012

INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012 INTRODUCTION TO SYSTEM PROTECTION Hands-On Relay School 2012 CONGRATULATIONS On choosing the field of system protection. It is an exciting, challenging profession. System protection has changed considerably

More information

VOLTAGE REGULATOR AND PARALLEL OPERATION

VOLTAGE REGULATOR AND PARALLEL OPERATION VOLTAGE REGULATOR AND PARALLEL OPERATION Generator sets are operated in parallel to improve fuel economy and reliability of the power supply. Economy is improved with multiple paralleled generators by

More information

Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems

Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems by Reza Tajali, P.E. Square D Company, Power Systems Engineering Group 295 Tech Park Drive LaVergne, Tennessee 37086

More information

Pilot-wire differential relay for lines with two or more terminals

Pilot-wire differential relay for lines with two or more terminals Pilot-wire differential relay for lines with two or more terminals Page 1 Issued: March 2003 Revision: A Data subject to change without notice Pilot-wire differential relay with RXHL 401 Features Phase

More information

Short Circuit Current Calculations

Short Circuit Current Calculations Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that

More information

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Course No: E02-010 Credit: 2 PDH Boris Shvartsberg, Ph.D., P.E., P.M.P. Continuing Education

More information

Radial Distribution Test Feeders

Radial Distribution Test Feeders Radial Distribution Test Feeders Distribution System Analysis Subcommittee Report Abstract: Many computer programs are available for the analysis of radial distribution feeders. In 1992 a paper was published

More information

NO LOAD & BLOCK ROTOR TEST ON THREE PHASE INDUCTION MOTOR

NO LOAD & BLOCK ROTOR TEST ON THREE PHASE INDUCTION MOTOR INDEX NO. : M-142 TECHNICAL MANUAL FOR NO LOAD & BLOCK ROTOR TEST ON THREE PHASE INDUCTION MOTOR Manufactured by : PREMIER TRADING CORPORATION (An ISO 9001:2000 Certified Company) 212/1, Mansarover Civil

More information

Current transformer selection guide

Current transformer selection guide The selection of a current transformer is a simple task. There are four phases in the selection procedure. Current transformer selection guide KEEP IN MIND efine customer requirements based on the primary

More information

Current Transformers

Current Transformers Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 Current Transformers Current transformers (CT's) provide

More information

Transformer protection

Transformer protection 8 Transformer protection 8.1 Introduction The inherent characteristics of power transformers introduce a number of unique problems that are not present in the protection of transmission lines, generators,

More information

Current Transformers. Bonneville Power Administration. Steve Laslo For the Hands On Relay School (3-12) Revision 1.1. February 21, 2012 1

Current Transformers. Bonneville Power Administration. Steve Laslo For the Hands On Relay School (3-12) Revision 1.1. February 21, 2012 1 Current Transformers Bonneville Power Administration Steve Laslo For the Hands On Relay School (3-12) Revision 1.1 February 21, 2012 1 Basic Theory: CT as a Voltage Transformer February 21, 2012 2 CT as

More information

TA Kahraman Yumak ELK412 - Distribution of Electrical Energy Lab. Notes v1.0 2013 Spring web.itu.edu.tr/yumakk. Distance Protection

TA Kahraman Yumak ELK412 - Distribution of Electrical Energy Lab. Notes v1.0 2013 Spring web.itu.edu.tr/yumakk. Distance Protection Distance Protection Announcement: You are not supposed to prepare a pre-report. But there will be an oral examination, so you are strongly advised to study this note regarding to the pre-study questions

More information

Selecting IHLP Composite Inductors for Non-Isolated Converters Utilizing Vishay s Application Sheet

Selecting IHLP Composite Inductors for Non-Isolated Converters Utilizing Vishay s Application Sheet VISHAY DALE www.vishay.com Magnetics Selecting IHLP Composite Inductors for Non-Isolated Converters INTRODUCTION This application note will provide information to assist in the specification of IHLP composite

More information

Safety technique. Emergency stop module BO 5988 safemaster

Safety technique. Emergency stop module BO 5988 safemaster Safety technique Emergency stop module BO 5988 safemaster 0221562 Function diagram Pushbutton on Mains or emergencystop () K1 According to EC Directive for machines 98/37/EG According to IEC/E 60204-1

More information

PacifiCorp Original Sheet No. 476 FERC Electric Tariff, Substitute 6 th Rev Volume No. 11 APPENDIX 2 TO SGIP

PacifiCorp Original Sheet No. 476 FERC Electric Tariff, Substitute 6 th Rev Volume No. 11 APPENDIX 2 TO SGIP PacifiCorp Original Sheet No. 476 APPENDIX 2 TO SGIP SMALL GENERATOR INTERCONNECTION REQUEST (Application Form) Transmission Provider: Designated Contact Person: Address: Telephone Number: An Interconnection

More information

Powerformer chosen for Swedish combined heat and power plant

Powerformer chosen for Swedish combined heat and power plant Powerformer chosen for Swedish combined heat and power plant Powerformer, a radically new type of generator developed by ABB, has been chosen for a combined heat and power plant in Eskilstuna, Sweden.

More information

SYNCHRONOUS MACHINES

SYNCHRONOUS MACHINES SYNCHRONOUS MACHINES The geometry of a synchronous machine is quite similar to that of the induction machine. The stator core and windings of a three-phase synchronous machine are practically identical

More information

Transformer Calculations

Transformer Calculations Transformer Calculations Transformers Transformers are one of the most basic yet practical devices used today. No matter where you are there is always a transformer nearby. They are used throughout alternating-current

More information

Three-phase AC circuits

Three-phase AC circuits Three-phase AC circuits This worksheet and all related files are licensed under the Creative Commons Attribution License, version 1.0. To view a copy of this license, visit http://creativecommons.org/licenses/by/1.0/,

More information

Loading Considerations When Paralleling Transformers

Loading Considerations When Paralleling Transformers Application Guide 7400DB0701 02/2007 Nashville, TN, USA Loading Considerations When Paralleling Transformers Class 7400 Retain for future use. Introduction Principles of Paralleling This application guide

More information

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV 1. SCOPE This document details PowerSystems requirements for electrical testing of HV Equipment up to and including 33kV. 2. ISSUE RECORD This is a Reference document. The current version of Controlled

More information

LAB1 INTRODUCTION TO PSS/E EE 461 Power Systems Colorado State University

LAB1 INTRODUCTION TO PSS/E EE 461 Power Systems Colorado State University LAB1 INTRODUCTION TO PSS/E EE 461 Power Systems Colorado State University PURPOSE: The purpose of this lab is to introduce PSS/E. This lab will introduce the following aspects of PSS/E: Introduction to

More information

SELECTION OF CURRENT TRANSFORMERS & WIRE SIZING IN SUBSTATIONS. Sethuraman Ganesan ABB Inc. Allentown, PA

SELECTION OF CURRENT TRANSFORMERS & WIRE SIZING IN SUBSTATIONS. Sethuraman Ganesan ABB Inc. Allentown, PA SELECTION OF CURRENT TRANSFORMERS & WIRE SIZING IN SUBSTATIONS Sethuraman Ganesan ABB Inc. Allentown, PA ABSTRACT More and more sub-stations are retrofitted with numerical relays, meters and monitoring

More information

SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE WELDERS

SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE WELDERS SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE S By Jack Farrow, May, 2004 WELDING TECHNOLOGY CORPORATION ABSTRACT Information on how to select the correct size of substation transformer and 480V bus to

More information

Chapter 22: Electric motors and electromagnetic induction

Chapter 22: Electric motors and electromagnetic induction Chapter 22: Electric motors and electromagnetic induction The motor effect movement from electricity When a current is passed through a wire placed in a magnetic field a force is produced which acts on

More information

DC GENERATOR THEORY. LIST the three conditions necessary to induce a voltage into a conductor.

DC GENERATOR THEORY. LIST the three conditions necessary to induce a voltage into a conductor. DC Generators DC generators are widely used to produce a DC voltage. The amount of voltage produced depends on a variety of factors. EO 1.5 LIST the three conditions necessary to induce a voltage into

More information

Full representation of the real transformer

Full representation of the real transformer TRASFORMERS EQVALET CRCT OF TWO-WDG TRASFORMER TR- Dots show the points of higher potential. There are applied following conventions of arrow directions: -for primary circuit -the passive sign convention

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60071-2 Third edition 1996-12 Insulation co-ordination Part 2: Application guide This English-language version is derived from the original bilingual publication by leaving out

More information

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER. Power Voltage Transformers for Air Insulated Substations THE PROVEN POWER. Introduction Trench Power Voltage Transformers (Power VTs) combine the attributes of an inductive voltage transformer with the

More information

Power System Simulation for Engineers (PSS/E): Fault Analysis

Power System Simulation for Engineers (PSS/E): Fault Analysis Power System Simulation for Engineers (PSS/E): Fault Analysis Table of contents: A. GENERAL INSTRUCTIONS 1 B. REQUIRED DATA 2 C. READING AN EXISTING CASE 2 D. SAVING A CASE 4 E. CREATING A NEW CASE 4 F.

More information

This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB

This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB Relion. Thinking beyond the box. Designed to seamlessly consolidate functions, Relion relays are smarter,

More information

Vrieswijk, T & Srinivasan,A Amerongen,NL, 25 januari 2012

Vrieswijk, T & Srinivasan,A Amerongen,NL, 25 januari 2012 Theory Current Transformers Vrieswijk, T & Srinivasan,A Amerongen,NL, 25 januari 2012 Theory Current Transformers 25 januari 2012 Topics - Theory of current transformers (CTs) - Equivalent Circuit for

More information

Instrument Transformers. Technical Information and Application Guide

Instrument Transformers. Technical Information and Application Guide Instrument Transformers Technical Information and Application Guide Table of Contents Technology Review An introduction to instrument transformer fundamentals, a discussion on power quality, and a detailed

More information

Circulating Current Relay. Type IRXm

Circulating Current Relay. Type IRXm Circulating Current Relay Type IRXm ABB a global technology leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers to improve performance while lowering

More information

Engineering innovation

Engineering innovation Eaton's Electrical Engineering Services & Systems Solutions Focus Seamless Solutions for Reliable, Efficient and Safe Power Systems Engineering innovation Progressive solutions for today s power systems

More information

PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA

PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA What are phasors??? In normal practice, the phasor represents the rms maximum value of the positive half cycle of the sinusoid

More information

AMSC s Superconductor Cable Technologies for Electric Utilities

AMSC s Superconductor Cable Technologies for Electric Utilities International Workshop 2014 AMSC s Superconductor Cable Technologies for Electric Utilities Michael Ross, P.E. Managing Director of Superconductor Power Systems AMSC Corporate Facts Headquartered in MA,

More information

Bill is the author of 15 papers and lectures on transmission lines and other power system topics.

Bill is the author of 15 papers and lectures on transmission lines and other power system topics. Transmission Lines Electricity s Highway This talk starts with an explanation of Surge Impedance Loading and demonstrates how it is used for transmission line work. The St. Clair Curve widely used in transmission

More information

DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE2302 - ELECTRICAL MACHINES II UNIT-I SYNCHRONOUS GENERATOR

DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE2302 - ELECTRICAL MACHINES II UNIT-I SYNCHRONOUS GENERATOR 1 DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Constructional details Types of rotors EE2302 - ELECTRICAL MACHINES II UNIT-I SYNCHRONOUS GENERATOR PART A 1.

More information

Chapter 24. Three-Phase Voltage Generation

Chapter 24. Three-Phase Voltage Generation Chapter 24 Three-Phase Systems Three-Phase Voltage Generation Three-phase generators Three sets of windings and produce three ac voltages Windings are placed 120 apart Voltages are three identical sinusoidal

More information

Power transformers. Generator step-up and system intertie power transformers Securing high-quality AC transmission

Power transformers. Generator step-up and system intertie power transformers Securing high-quality AC transmission Power transformers Generator step-up and system intertie power transformers Securing high-quality AC transmission Generator step-up transformers Built to withstand continuous full load Generator step-up

More information

ECE 586b Course Project Report. Auto-Reclosing

ECE 586b Course Project Report. Auto-Reclosing ECE 586b Course Project Report Auto-Reclosing Srichand Injeti May 5, 2008 Department Of Electrical and computer Engineering University Of Western Ontario, London Ontario Table of contents 1. Introduction...1

More information

3) What is the difference between "Insulating", "Isolating", and "Shielded Winding" transformers?

3) What is the difference between Insulating, Isolating, and Shielded Winding transformers? Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 1) What is a transformer and how does it work? A transformer

More information

Buck - Boost Transformers

Buck - Boost Transformers Buck - Boost Transformers Contents Buck - Boost Transformers - Terms & Definitions... 48 Buck - Boost Transformers - Sizing... 50 Quick Reference Chart - 08, 0, 40 Volts Single & Three Phase... 5 Single

More information

Unit 6 Transformers. Lead-in. Basic principles. Task 1. Task 2. What applications of transformers do you know?

Unit 6 Transformers. Lead-in. Basic principles. Task 1. Task 2. What applications of transformers do you know? Unit 6 Transformers Lead-in What applications of transformers do you know? Basic principles Task 1 Match the words and phrases with the translations. 1. magnetic field 2. induced voltage 3. conductors

More information

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the different types of open single-phase motors used to drive

More information