GUIDE TO FIRE PROTECTION IN MALAYSIA

Size: px
Start display at page:

Download "GUIDE TO FIRE PROTECTION IN MALAYSIA"

Transcription

1 GUIDE TO FIRE PROTECTION IN MALAYSIA

2

3 FIRE PROTECTION SYSTEMS (FPS) REASON FOR INSTALLING FPS 1. MEETING CODES BY THE GOVERNMENT 2. MAKING TRADE-OFF allows more flexibility in architectural design i.e ATRIUM etc 3. SATISFYING THE LAWS 4. PROTECTING ASSETS & LIFE 5. MAINTAINING COMMUNITY RELATIONS ENVIROMENTAL FIRE FIGHTING EQUIPMENT OR SAFETY INSTALLATION 1. EXTINGUISHING, FIGHTING, PREVENTING, OR LIMITING A FIRE 2. FIRE DECTECTION & ALARM SYSTEMS 3. PROVIDE ACCESS TO THE PREMISSES FOR No.1.

4 4. PROVIDE EMERGENCY POWER SUPPLY 5. PROVIDE EMERGENCY LIGHT 6. GIVING ESCAPE DIRECTION 7. GIVING ADEQUATE SAFE EGRESS FOR THE PURPOSE OF EVACUATION THE PREMISSES 8. SMOKE MANAGEMENT FIRE FIGHTING SYSTEMS USED IN MALAYSIA 1. PORTABLE FIRE EXTINGUISHERS 2. EXTERNAL FIRE HYDRANT 3. HOSE REEL SYSTEM 4. DRY RISER SYSTEM 5. WET RISER SYSTEM 6. DOWNCOMER SYSTEM

5 7. AUTOMATIC SPRINGKLER SYSTEM 1. PORTABLE FIRE EXTINGUISHERS DESCRIPTION FOUR TYPES OF FIRE EXTINGUISHERS: WATER DRY POWDER CARBON DIOXIDE CO2 FOAM

6 CLASSIFICATIONS CLASS BURNING TYPE OF F/FIGHTING MATERIAL A COMBUSTIBLE SOLID MATERIAL WATER OR DRY POWDER SUCH AS WOOD, PAPER, RUBBER etc B LIQUID SUCH AS PETROL, OIL, DIESEL, KEROSENE etc FOAM OR DRY POWDER (DO NOT USE WATER) C GAS SUCH AS LPG, ACETYLEENE & DRY POWDER OR WATER NATURAL GAS D REACTIVE METAL SUCH AS ALUMNINIUM, ZINC, SODIUM, DRY POWDER (DO NOT USE WATER) POTASIUM & CALCIUM E IGNITION BY ELECTRICITY CARBON DIOXIDE, CO2

7 DESIGN REQUIREMENTS DESIGN STANDARDS MUST COMPLY WITH FOLLOWING MALAYSIAN STANDARD; M.S. 1179: Specification for portable fire extinguishers M.S. 1180: Fire Extinguisher s Media M.S. 1181: Recharging fire extinguishers M.S. 1182: Classification of fire LOCATION AND SPACING Located along exit routes Beside exit doors Beside staircase doors About 15 m distance from the nearest people CO2 portable fire extinguishers should be installed in electrical rooms, fire pump rooms and lift motor rooms. Dry powder portable fire extinguishers should be installed in storerooms.

8 2. EXTERNAL FIRE HYDRANT DESCRIPTION Installation consist of a system of pipework connected directly to the water supply mains to provide water to each hydrant outlet. Intended to provide water to fireman to fight a fire. The water is discharged into the fire engine from which it is then pumped and spray over the fire. If pressure is too low, use hydrant pumps. DESIGN REQUIREMENTS DESIGN STANDARDS RELEVEN STANDARDS AS FOLLOWS; B.S. 5306: Part 1 or the equivalent Malaysian Standard; M.S. 1395: specification for pillar hydrant

9 HYDRANT OUTLETS Not less than 6 m from building & not more than 30 m from entrance to the building Space not more than 90 m apart along the minimum 6 m in width road Capable of withstanding a load of 26 tons of Fire brigade vehicles. 2 or 3 outlets pillar type with underground sluice valve In owner s boundary: should be provided with 30m of 65mm rubber-lined hose (complete with nozzles) in steel cabinet beside each hydrant. Underground hydrants are not encouraged due to difficulty of access Capable to handle 1000 l/min & running pressure of 4 bars but max to 7 bars only The hydrant mains are usually laid underground with cement lined steel pipe. ABS (Acrylonitrile Butadiene Styrene) material used for an area where corossion is a major concern HYDRANT PUMPS Two sets of pumps (one duty & one standby) Capable to supply 3000 l/min & running pressure of 4-7 bars to 3 hydrants at the same time

10 Should be supplied with backup diesel/power generator incase of black out for at least 2 hours Batteries for diesel engine must be maintanance free type Normally Jockey pumps driven by electrical motor at 120 l/min required to maintain system presure The pumps should be protected from the weather and away from flood area. Pumps room should be ventilated plus signage HYDRANT TANKS Minimum capacity 180,000 litres ( 1 hr water supply for 3 hydrants) Should be refilled automatically by supply pipe at 20l/s Hydrant tanks are usually separate from other water storage tanks but may be combined with other fire fighting system water tanks. So, tank s capacity is the sum total of all tanks. Tank material: pressed steel, fibreglass reinforced polyester (FRP) or concrete. The tank should be compartmented and water level indicator must be provided External tank should be painted red OR at least red band of minimum 200 mm should be painted.

11 3. HOSE REEL SYSTEM DESCRIPTION Hose reel system is intended for the occupant to use during early stages of a fire and comprises hose reel pumps, water storage tanks, hose reels, pipe work and valves. DESIGN REQUIREMENTS DESIGN STANDARDS MUST COMPLY WITH FOLLOWING STANDARD; B.S. 5306: Part 1 or the equivalent Malaysian Standard; M.S. 1447: Hose reels with semi-rigid hose Pr EN 694 : Semi-rigid hose for first aid fixed installations

12 HOSE REELS Coverage range of 30 m for each reel One hose reel for every 800 sq. m space area. Usually located along escape routes or beside exit doors or staircases Minimum discharge by each hose reel 30 l/m & 6 m jet length The rubber hoses should be comply with pr EN 694 standard & 30 m in length and 25 mm diameter Nozzles should be of the jet & spray adjustable type of different diameters but 8 mm is a recommended size. Pipework is generally 50 mm diameter and the pipe feed to individual hose not less than 25mm diameter Above ground pipework : minimum galvanised steel medium grade (Class B) Underground pipework : minimum heavy grade (Class C) Pipe painted with primer & finished with red paint (OR at least elbow & tee must be painted with red bands)

13 HOSE REEL PUMPS Two sets of pumps. One on duty & the other on standby 120 l/m and at least 2 bars in pressure for any four hose reels opearting at the same time Emergency generator/diesel engine adequate for minimum of 1 hr operation Electrical cabling should be run in galvanised steel conduit Batteries for diesel engine must be maintanance free type If total number of hose reel is not more than 4, electrically driven is enough no need to have an emergency generator/diesel engine. Should provide with CO2 portable extinguisher The pumps should be protected from the weather and away from flood area. HOSE REEL TANKS Tank size based on 2275 litres for the first hose reel & others litres to maximum of 9100 litres for eqach system Tank material: pressed steel, fibreglass reinforced polyester (FRP) or concrete. The tank should be compartmented and water level indicator must be provided External tank should be painted red OR at least red band of minimum 200 mm should be painted.

14 The tank will automatically refill from water supply pipe of 50mm diameter and minimum flow is 150/m Usually hose reel tanks are separated from domestic water storage tank. However, the two can be combined to give sum total capacity. Tap off point of the domestic use must be above the tap off point of for the hose reels so that minimum fire reserve is always maintained GRAVITY FEED HOSE REEL SYSTEM Tank located on the roof or upper floors and the static pressure is adequate to achive the required pressure & flowrate. If pumps required, a bypass pipe is usually provided

15 4. DRY RISER SYSTEM DESCRIPTION Internal hydrant to use by fireman which normally dry & depend on fire engine to pump water into the system Required for building of top most floor is higher than 18.3 m & less than 30.5 m above the fire appliance access level Breeching Inlets to the system are located at ground level (See Fig 8.1) DESIGN REQUIREMENTS DESIGN STANDARDS MUST COMPLY WITH FOLLOWING STANDARD; B.S. 5306: Part 1 or the equivalent Malaysian Standard;

16 M.S. 1210: Part 2 - Landing Valves for Dry Risers M.S. 1210: Part 3 - Inlet Breeching Riser inlets M.S. 1210: Part 4 Boxes for Landing Valves for Dry Risers M.S. 1210: Part 5 Boxes for Inlet Breeching LANDING VALVE Landing valves (comply with M.S. 1210: Part 2) are provided on each floor Located at lobbies & staircases Installed 0.75 m above floor level Protected by Boxes comply with M.S. 1210: Part 4 Fire hose rubber-lined type complete with 65 mm diameter coupling & nozzle should be provided in a hose cradle beside each landing valve BREECHING INLET The fire brigade breeching inlet (comply with M.S. 1210: Part 3) installed at the bottom of the riser Protected by Boxes comply with M.S. 1210: Part 5 & labelled Dry Riser Inlet A drain should be provided at the bottom of the riser to drain the system after use

17 A two-way breeching inlet for 100 mm diameter dry riser A 4-way breeching inlet for 150 mm diameter dry riser Located not more than 18 m from fire appliance access road & not more than 30 m from the nearest external hydrant outlet RISER PIPE If the highest outlet is more than 23 m above the breeching inlet, use 150 mm dry riser else 100 mm. Pipe material: galvanised iron to B.S (Heavy gauge) or class C tested at 21 bars Horizontal pipework feeding the risers should be sloped for proper draining after use An air release valve installed at the top to release air trapped in the system Electrically earthed to achieve equipotential with the buliding STATIC PRESSURE TEST

18 First, flush the system to clear all debris insider riser Hydraulically tested to a pressure of 14 bars (measured an inlet) for 2 hours for leakage at joints and connections Inspection & testing regularly all parts to ensure that they are in good operation condition 5. WET RISER SYSTEM DESCRIPTION Internal hydrant to use by fireman and are always charged with water Required for building of top most floor is higher than 30.5 m above the fire appliance access level Need pumps Wet riser pipe is 150 mm.

19 Rubber-lined hose with nozzles For high rise buildings, each stage of wet riser should not exceed 71 m See Fig 9.1 for the typical wet riser installation DESIGN REQUIREMENTS DESIGN STANDARDS MUST COMPLY WITH FOLLOWING STANDARD; B.S. 5306: Part 1 or the equivalent Malaysian Standard; M.S. 1210: Part 1 - Landing Valves for Wet Risers M.S. 1210: Part 3 - Inlet Breeching Riser inlets M.S. 1210: Part 4 Boxes for Landing Valves for Dry Risers M.S. 1210: Part 5 Boxes for Inlet Breeching WET RISER LANDING VALVE Landing valves (comply with M.S. 1210: Part 2) are provided on each floor

20 Located at lobbies & staircases Installed 0.75 m above floor level Protected by Boxes comply with M.S. 1210: Part 4 Pressure at landing valve should be between 4-7 bars Fire hose rubber-lined type (not less than 35mm dia. & 30 m in length) complete with 65 mm diameter coupling & nozzle should be provided in a hose cradle beside each landing valve BREECHING INLET Should be a 4-way type complying with M.S. 1210: Part 3) Protected by Boxes comply with M.S. 1210: Part 5 & labelled Wet Riser Inlet A drain should be provided at the bottom of the riser Located not more than 18 m from fire appliance access road & not more than 30 m from the nearest external hydrant outlet WET RISER PIPE

21 Each wet riser should cover not more than 900 m sq floor area. If more than one wet riser per floor, the distance apart between then not more than 60 m The top most and the lowest wet riser should be less than 71 m Pipe material: galvanised iron to B.S (Heavy gauge) or class C Pipe should be coated with primer and finished with red gloss paint alternatively the pipe can be colour coded by red band of 100 mm width with elbows and tees painted red Electrically earthed to achieve equipotential with the buliding WET RISER PUMPS 2 sets op pumps. One on duty & the other on standby The pump capacity 1500 l/m & pressure between 4-7 bars when any three landing valves are in use at the same time. Should be supplied with backup diesel/power generator incase of black out for at least 2 hours Electrical cabling should be fire rated type Batteries for diesel engine must be maintanance free type Should provide with CO2 portable extinguisher The pumps should be protected from the weather and away from flood area.

22 WET RISER TANKS Minimum capacity of 45,500 litres with automatic refill rate 455 l/m The intermediate break tank for for upper stages of the wet riser should be not less than 11,375 litres with automatic refill rate 1365 l/m Tank material: pressed steel, fibreglass reinforced polyester (FRP) or concrete. The tank should be compartmented and water level indicator must be provided External tank should be painted red OR at least red band of minimum 200 mm should be painted. Tanks located on the ground floor or basement Wet riser tanks separated from other water storage tank However, it may be combined with hose reel tanks and the capacity is the sum total from both tanks. Hose reel tap off level should be above the wet riser tap off such that wet riser reserve is maintained STATIC PRESSURE TEST First, flush the system to clear all debris insider riser

23 Hydraulically tested to a pressure of 14 bars or 150% of the working pressure (measured an inlet), whichever is the higher for 2 hours for leakage at joints and connections Inspection & testing regularly all parts to ensure that they are in good operation condition A three way landing valve should be provided on the roof or topmost floor for testing purposes. Flowmeter should be provided to measure flowrate 6. DOWNCOMER SYSTEM DESCRIPTION Internal hydrant for fireman to use and always charge with water from water tank located on the top of the building WITHOUT any pump. Only permitted to residential buildings with open balcony & the topmost floor is not more than 60 maboe the fire appliance access level 150mm riser pipe with landing valve on each floor and to which rubber-lined hose with nozzles

24 Should be adopted for low cost flats only A typical downcomer Installation shown in Fig 10.1 DESIGN REQUIREMENTS DESIGN STANDARDS MUST COMPLY WITH FOLLOWING STANDARD; M.S. 1210: Part 1 - Landing Valves for Wet Risers M.S. 1210: Part 3 - Inlet Breeching Riser Inlets M.S. 1210: Part 4 Boxes for Landing Valves for Dry Risers M.S. 1210: Part 5 Boxes for Inlet Breeching DOWNCOMER LANDING VALVE Provided on each floor & complying with M.S. 1210: Part 1 Located at lobbies & staircases Installed less than 0.75 m from the floor Protected by Boxes comply with M.S. 1210: Part 4

25 Pressure at landing valve depends on the static pressure on the valve from the roof tank 2 sets of fire hose rubber-lined type (not less than 35mm dia. & 30 m in length) complete with 65 mm diameter coupling & nozzle should be provided at the caretaker s unit or management office BREECHING INLET The fire brigate breeching inlets into which fireman will pump water into the downcomer system located at ground floor Should be a 4-way type complying with M.S. 1210: Part 3) Protected by Boxes comply with M.S. 1210: Part 5 & labelled Downcomer Inlet A drain should be provided at the bottom of the riser Located not more than 18 m from fire appliance access road & not more than 30 m from the nearest external hydrant Check valve is installed between the topmost landing valve and the tank to prevent back flow of the water from the downcomer into the tank DOWNCOMER PIPE

26 Each downcomer should cover not more than 900 m sq floor area. If more than one riser per floor, the distance apart between then not more than 60 m The downcomer pipe diameter is 150 mm Pipe material: galvanised iron to B.S (Heavy gauge) or class C An air release valve installed at the top to release air trapped in the system Pipe should be coated with primer and finished with red gloss paint alternatively the pipe can be colour coded by red band of 100 mm width with elbows and tees painted red Electrically earthed to achieve equipotential with the buliding DOWNCOMER WATER TANKS Minimum capacity of 45,500 litres with automatic refill rate 455 l/m Tank material: pressed steel, fibreglass reinforced polyester (FRP) or concrete. The tank should be compartmented and water level indicator must be provided External tank should be painted red OR at least red band of minimum 200 mm should be painted. Tanks located on the roof

27 Wet riser tanks separated from other water storage tank However, it may be combined with hose reel tanks and the capacity is the sum total from both tanks. Hose reel tap off level should be above the downcomer tap off such that water is reserve for the downcomer STATIC PRESSURE TEST First, flush the system to clear all debris insider riser Hydraulically tested to a pressure of 14 bars or 150% of the working pressure (measured an inlet), whichever is the higher for 2 hours for leakage at joints and connections Inspection & testing regularly all parts to ensure that they are in good operation condition. 7. AUTOMATIC SPRINKLER SYSTEM DESCRIPTION Intent to detect,control, extinguish a fire, and warn the occupants of the occurance of fire automatically

28 System consist of pumps, water tanks, control valve sets, sprinkler heads, flow switches, pressure switches, pipework & valves Sprinkler head has a liquid filled in glass bulb that breaks due to heat of the fire & release water that spray over the fire Common type sprinkler system installation shown in Fig 11.1 TYPE OF SPRINKLERS Four types of sprinkler system as follows; (i.) (ii.) Wet pipe installation Pipeworks always filled with water & ready to discharge once the sprinkler bulb breaks Dry pipe installation Pipeworks always filled with air under pressure. Air released once the sprinkler bulb breaks and water filled the pipeworks and discharge at the sprinkler head

29 (iii.) Pre-action installation Pipeworks always filled with air under pressure. A valves release air and pipeworks filled with water when fire is detected by smoke or heat detectors. Water is discharged through the sprinkler head only when the sprinkler bulb breaks (iv.) Deluge Installation Sprinkler head has no bulb.and water is discharge simultaneously from all heads when fire is detected and the deluge valve is opened DESIGN REQUIREMENTS DESIGN STANDARDS MUST COMPLY WITH FOLLOWING STANDARDS; LPC rules for Automatic Sprinklers,UK

30 B.S. 5306: Part 2 Specification for Sprinkler systems NFPA 13 (National Fire Protection Association) Australian Std. A.S HAZARD CLASSIFICATION As describe in B.S Part 2, hazard is devided into three main categories as follows: a) Light Hazard non-industrial occupancies low quantity of combustibility contents example: apartments, flat, schools, hostel UTM & hospital b) Ordinary Hazard Group I : Offices, restaurants & hotels Group II : Laundries, bakeries & tobacco factories Group III : Car parks, department stores, hypermarket, cinema, clothing & paint factories.

31 Group IV : Match factories, film & television studios c) High Hazard Group I : Process risk.e.g. clothing, rubber,woodwool & paint factories Group II : High piled storage risk which divided into 4 categories i) Category I : Carpets and textile storage exceeding 4 m in height ii) Category II : Furniture factory storage exceeding 3 m in height iii) Category III: Rubber, wax coated paper storage exceeding 2 m in height iv) Category IV: foam & plastics storage exceeding 1.2 m in height SPRINKLER PUMPS Require to feed sprinkler network Two sets of pumps: one on duty & the other on standby A jockey pump provided to maintain system pressure Pump s capacity as describe in B.S Part 2 as follows;

32 i) Light Hazard Head =15 m; Q = 300 dm 3 /min at P = 1.5 bars Head =30 m; Q = 340 dm 3 /min at P = 1.8 bars Head =45 m; Q = 375 dm 3 /min at P = 2.3 bars ii) Ordinary Hazard Group I : Offices, restaurants & hotels Head =15 m; Q = 900 dm 3 /min at P = 1.2 bars Head =30 m; Q = 1150 dm 3 /min at P = 1.9 bars Head =45 m; Q = 1360 dm 3 /min at P = 2.7 bars Group II : Laundries, bakeries & tobacco factories Head =15 m; Q = 1750 dm 3 /min at P = 1.4 bars Head =30 m; Q = 2050 dm 3 /min at P = 2.0 bars Head =45 m; Q = 2350 dm 3 /min at P = 2.6 bars Group III : Car parks, department stores, hypermarket, cinema, clothing & paint factories. Head =15 m; Q = 2250 dm 3 /min at P = 1.4 bars Head =30 m; Q = 2700 dm 3 /min at P = 2.0 bars

33 Head =45 m; Q = 3100 dm 3 /min at P = 2.5 bars Group IV : Match factories, film & television studios Head =15 m; Q = 2650 dm 3 /min at P = 1.9 bars Head =30 m; Q = 3050 dm 3 /min at P = 2.4 bars iii) High Hazard Refer to B.S. 5306: Part 2 WATER TANKS iv) Light Hazard Head =15 m; Tank capacity 9 m 3 Head =30 m; Tank capacity 10 m 3 Head =45 m; Tank capacity 11 m 3

34 v) Ordinary Hazard Group I : Offices, restaurants & hotels Head =15 m; Tank capacity 55 m 3 Head =30 m; Tank capacity 70 m 3 Head =45 m; Tank capacity 80 m 3 Group II : Laundries, bakeries & tobacco factories Head =15 m; Tank capacity 105 m 3 Head =30 m; Tank capacity 125 m 3 Head =45 m; Tank capacity 140 m 3 Group III : Car parks, department stores, hypermarket, cinema, clothing & paint factories. Head =15 m; Tank capacity 135 m 3 Head =30 m; Tank capacity 160 m 3 Head =45 m; Tank capacity 185 m 3 Group IV : Match factories, film & television studios Head =15 m; Tank capacity 160 m 3 Head =30 m; Tank capacity 185 m 3

35 vi) High Hazard Refer to B.S. 5306: Part 2 SPRINKLER HEAD Generally of the conventional pendant or upright type Temperature rating: minimum = (T+30) 0 C where T=maximum ambient temperature of the protected space in degree C. Nominal temperature rating = 68 0 C In kitchen nominal temperature rating = 79 0 C INSTALLATION CONTROL VALVE Each sprinkler installation should have installation control valves which consist of main stop valves, alarm valves, drain line with stop valve, flow rate & pressure gauges

36 Maximum number of sprinklers to be fed from one set of installation control valve shall be; i) Light Hazard : 500 sprinklers ii) Ordinary Hazard : 1000 sprinklers iii) High Hazard : 1000 sprinklers SPRINKLER PIPEWORK Black steel or galvanised iron BS.1387 (medium grade ) Class B minimum Underground pipe: heavy gauge Class C For Pipes of size 80 mm and below use screw joints For Pipes of size above 100 mm may be welded OR grooved coupling up to 250 mm Sprinkler pipes should not be concealed in the floor or ceiling concrete slabs. Pipe should be coated with primer and finished with red gloss paint alternatively the pipe can be colour coded by red band of 100 mm width with elbows and tees painted red

37 INSPECTION & TESTING First, flush the system to clear all debris insider riser Hydraulically tested to a pressure of 14 bars or 150% of the working pressure (measured an inlet), whichever is the higher for 24 hours for leakage at joints and connections Each zone should be tested by opening the valve on the test line. The flow switch for that zone should indicate an alarm on the fire alarm panel. Flow test to ensure the pumps are in proper working condition. Inspection & testing regularly all parts & joints to ensure no leakage and they are in good operation condition as recommended by checklist attached.

FIRE-FIGHTING DESIGN BRIEF REPORT

FIRE-FIGHTING DESIGN BRIEF REPORT P a g e 1 SECTION 04 (Doc.No.A/DBR 001) FIRE-FIGHTING DESIGN BRIEF REPORT P a g e 2 1.0 SCOPE 2.0 STANDARDS AND CODES 3.0 TYPES OF SYSTEM PROPOSED 4.0 FIRE HYDRANT SYSTEM 5.0 AUTOMATIC SPRINKLER SYSTEM

More information

Fire Safety In High Rise Building

Fire Safety In High Rise Building Fire Safety In High Rise Building CLASSIFICATION OF BUILDINGS AS PER NATIONAL BUILDING CODE 1. GROUPING. Group A - Residential : Lodgings, Dwellings, Dormitories, Flats, Hotels. Group B Group C - Educational

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved;

More information

EFSN Training i Module 1. 90 Minutes

EFSN Training i Module 1. 90 Minutes Introduction to Sprinklers EFSN Training i Module 1 90 Minutes Topics How sprinklers work Performance of sprinkler systems Types of Sprinkler Introduction to sprinkler systems Introduction ti to sprinkler

More information

Pollution CO CO 2. Carbonaceo us soot H 2 S, NOX, SO2

Pollution CO CO 2. Carbonaceo us soot H 2 S, NOX, SO2 Pollution CO CO 2 Carbonaceo us soot H 2 S, NOX, SO2 The National Building Code (NBC) contains set of minimum provisions, designed to protect the safety of the public with regard to structural sufficiency,

More information

www.klmtechgroup.com TABLE OF CONTENT

www.klmtechgroup.com TABLE OF CONTENT Page : 1 of 36 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia TABLE OF CONTENT SCOPE 3 REFERENCES

More information

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable

More information

THE FACTORIES A D OTHER PLACES OF WORK ACT (Cap 514)

THE FACTORIES A D OTHER PLACES OF WORK ACT (Cap 514) THE FACTORIES A D OTHER PLACES OF WORK ACT (Cap 514) I EXERCISE of the powers conferred by section 41 2(k) of the Factories and other places of Work Act, the Minister for Labour and Human Resource Development

More information

RESIDENTS FIRE SAFETY INFORMATION PACK

RESIDENTS FIRE SAFETY INFORMATION PACK RESIDENTS FIRE SAFETY INFORMATION PACK CASTLEMEAD CAMBERWELL ROAD LONDON SE5 THE CONTENTS OF YOUR PACK Section Page No. 1. 3. Introduction Here we will explain the purpose of the Fire Safety Information

More information

RESIDENTS FIRE SAFETY INFORMATION PACK

RESIDENTS FIRE SAFETY INFORMATION PACK RESIDENTS FIRE SAFETY INFORMATION PACK MARIE CURIE SCEAUX GARDENS ESTATE LONDON SE5 THE CONTENTS OF YOUR PACK Section Page No. 1. 3. Introduction Here we will explain the purpose of the Fire Safety Information

More information

ELECTRIC/DIESEL FIRE PUMP CHECK LIST

ELECTRIC/DIESEL FIRE PUMP CHECK LIST BUILDING NAME: DESIGNER: SCO REPRESENTATIVE: PUMP MANUF.: LOCATION: INSTALLER: DATE: OWNER NAME: INSTALLATION Certificate for flushing and hydrostatic test furnished Piping been hydrostatically tested

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved;

More information

AON SPRINKLER CERTIFICATION

AON SPRINKLER CERTIFICATION Form 1 Application for Approval of Basic Design Parameters for Automatic Sprinkler System Installations 1. Name of Protected Premises Site Name Address 2. Work to be Carried Out New System Extension or

More information

RESIDENTS FIRE SAFETY INFORMATION PACK

RESIDENTS FIRE SAFETY INFORMATION PACK RESIDENTS FIRE SAFETY INFORMATION PACK PERRONET HOUSE PRINCESS STREET LONDON SE1 THE CONTENTS OF YOUR PACK Section Page No. 1. 3. Introduction Here we will explain the purpose of the Fire Safety Information

More information

Automatic Fire Sprinkler Submittal Requirements

Automatic Fire Sprinkler Submittal Requirements Automatic Fire Sprinkler Submittal Requirements All commercial and industrial buildings with a total floor area of 5000 sq. ft. shall have an approved automatic sprinkler system installed. The Windsor-Severance

More information

Fire Pump Plan Review March 2010

Fire Pump Plan Review March 2010 Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:

More information

Important Ontario Fire Code Information for Building Owners in the City of Windsor

Important Ontario Fire Code Information for Building Owners in the City of Windsor Important Ontario Fire Code Information for Building Owners in the City of Windsor This information is intended to be used a reference only. For a complete listing consult the Ontario Fire Code or contact

More information

UCL FIRE RISK ASSESSMENT POLICY& ARRANGEMENTS

UCL FIRE RISK ASSESSMENT POLICY& ARRANGEMENTS Fire Safety Technical Guide UCL FIRE RISK ASSESSMENT POLICY& ARRANGEMENTS 1.0. BACKGROUND 1.1. The Regulatory Reform (Fire Safety) Order (known Fire Safety Order) applies to England and Wales (Northern

More information

Clark County Fire Prevention

Clark County Fire Prevention Clark County Fire Prevention Mission Statement: To provide the highest level of fire protection and related services TITLE: REQUIREMENTS FOR A NEW SPRINKLER SYSTEM IN ACCORDANCE WITH THE 2002 EDITION OF

More information

Fire Evacuation Procedures Network Building, 97 Tottenham Court Road, London, W1

Fire Evacuation Procedures Network Building, 97 Tottenham Court Road, London, W1 Network Building Fire Safety Management Plan & Fire Evacuation Procedures Contents 1.0 Introduction 2.0 Means of Escape in Case of Fire 3.0 Means for Giving Warning in Case of Fire 4.0 Means for Fighting

More information

Series MJC Multiple Jet Controls DN20, DN25, DN40, and DN50, 12 bar BSPT Inlet & Outlets Threads General Description.

Series MJC Multiple Jet Controls DN20, DN25, DN40, and DN50, 12 bar BSPT Inlet & Outlets Threads General Description. Worldwide Contacts www.tyco-fire.com Series Multiple Jet Controls DN20, DN25, DN40, and DN50, 2 bar BSPT Inlet & Outlets Threads General Description The TYCO Series Multiple Jet Controls are control valves

More information

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Plan Review 2009 International Fire Code and NFPA 20 Date of Review / / BLD201 - Project Address: Project Name: Contractor s Business

More information

EAST LINDSEY DISTRICT COUNCIL ~ RESIDENTIAL CARAVAN SITES CONDITIONS OF SITE LICENCE

EAST LINDSEY DISTRICT COUNCIL ~ RESIDENTIAL CARAVAN SITES CONDITIONS OF SITE LICENCE Residential Site Licence Conditions of Licence February 2014 EAST LINDSEY DISTRICT COUNCIL ~ RESIDENTIAL CARAVAN SITES Index of conditions CONDITIONS OF SITE LICENCE 1. Period of use 2. Bases 3. Siting

More information

Proposed Residential Complex At Holding No. - 98, B.T. Road, Kolkata - 700090 Developer Premier Mica Mining And Manufacturing Company

Proposed Residential Complex At Holding No. - 98, B.T. Road, Kolkata - 700090 Developer Premier Mica Mining And Manufacturing Company RISK MANAGEMENT PLAN is an integral part of a modernized and sophisticated residential complex. No efforts will be spared in identifying the all possible risks and disasters, evaluating them, installing

More information

Extended Coverage Sprinklers

Extended Coverage Sprinklers Extended Coverage Sprinklers Welcome ASPE Wally Barker Sprinkler Systems 101 MATERIALS OF CONSTRUCTION The components that make up a sprinkler head are: Frame or casting Deflector Fusible element or frangible

More information

Name Of Occupancy Date. Yes No Describe

Name Of Occupancy Date. Yes No Describe FIRE PREVENTION INSPECTION CHECKLIST For Class A Occupancy (For Assembly Buildings, Bars, Restaurants, Gyms, Churches, Arenas, Theatres or wherever people gather) Name Of Occupancy Date Physical Address

More information

MAINTENANCE AND SERVICE OF AUTOMATIC FIRE EXTINGUISHING SYSTEMS

MAINTENANCE AND SERVICE OF AUTOMATIC FIRE EXTINGUISHING SYSTEMS FIRE DEPARTMENT Bureau of Fire Protection and Life Safety www.cityofsanmateo.org 1900 O Farrell, Suite 140 San Mateo, CA 94403-1332 (650) 522-7940 FAX: (650) 522-7941 TDD: (650) 522-7047 MAINTENANCE AND

More information

FIRE EXTINGUISHER TRAINING

FIRE EXTINGUISHER TRAINING FIRE EXTINGUISHER TRAINING Fire safety, at its most basic, is based upon the principle of keeping fuel sources and ignition sources separate. Three things must be present at the same time to produce fire:

More information

Fire Safety Requirements for Child Care Centre

Fire Safety Requirements for Child Care Centre Fire Safety Requirements for Child Care Centre A. Restrictions on Location Child care centre shall not be located : - (a) (b) in any premises designed for residential use; in any industrial building, warehouses,

More information

(2) Various fire sections enclosed by various classes of fire divisions; (3) Arrangement of fire detectors and manual fire alarm stations;

(2) Various fire sections enclosed by various classes of fire divisions; (3) Arrangement of fire detectors and manual fire alarm stations; (1979) (Rev.1 1990) (Rev.2 1996) (Rev.3 Jan 2012) Safety features.1 Fire protection and extinction.1.1 General Fire protection arrangements and fire extinguishing systems are to be in accordance with the

More information

- 5 - Table1. Maximum Compartment Volumes

- 5 - Table1. Maximum Compartment Volumes - 5 - Part II - SPECIFIC REQUIREMENTS 5. Compartmentation 5.1 Every building should be divided into compartments by walls and floors to inhibit the spread of fire. 5.2 Compartment walls, compartment floors,

More information

Decree of the Ministry of the Environment on fire safety of ventilation systems

Decree of the Ministry of the Environment on fire safety of ventilation systems THE NATIONAL BUILDING CODE OF FINLAND MINISTRY OF THE ENVIRONMENT Housing and Building Department Decree of the Ministry of the Environment on fire safety of ventilation systems Adopted in Helsinki, 18

More information

NFPA 13 2002 FAQs. 3. Can plastic pipe be used on a sprinkler system complying with NFPA 13?

NFPA 13 2002 FAQs. 3. Can plastic pipe be used on a sprinkler system complying with NFPA 13? NFPA 13 2002 FAQs Responses to FAQs are prepared by NFPA technical staff to assist users in reading and understanding NFPA codes and standards. The responses, however, are not Formal Interpretations issued

More information

St. John s University

St. John s University St. John s University Fire Safety Plan Founder s Village Townhouses Page 1 St. John s University Fire Safety Plan Part 1-Building Information Section Founder s Village Townhouses 8000 Utopia Parkway Jamaica

More information

IFE Level 4 Certificate in Fire Science and Fire Safety (HL)

IFE Level 4 Certificate in Fire Science and Fire Safety (HL) IFE Level 4 Certificate in Fire Science and Fire Safety (HL) Unit 2: Fire Safety Unit Reference Number: D/505/5932 Introduction This unit focuses on the prevention and detection of fire in premises and

More information

Winnipeg Fire Department Fire Prevention Branch

Winnipeg Fire Department Fire Prevention Branch Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of

More information

FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST

FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST Date of Inspection: Conducted by: Location: Reviewed by: Date of Review: Comments or additional corrective action taken as a result

More information

FLAMMABLE AND COMBUSTIBLE LIQUIDS. n OSHA Changes

FLAMMABLE AND COMBUSTIBLE LIQUIDS. n OSHA Changes FLAMMABLE AND COMBUSTIBLE LIQUIDS OSHA Changes Introduction This module covers the two primary hazards associated with flammable and combustible liquids: explosion and fire. In order to prevent these hazards,

More information

Commercial Fire Inspections

Commercial Fire Inspections Commercial Fire Inspections Fire Department Inspection Requests and Procedures The following guidelines shall be used when calling for inspection requests: 1. All inspection requests shall be coordinated

More information

FIRE PROTECTION AT CONSTRUCTION SITE

FIRE PROTECTION AT CONSTRUCTION SITE FIRE PROTECTION NOTICE N0.13 FIRE PROTECTION AT CONSTRUCTION SITE Serious fires have occurred in buildings under construction which will not only delay their completion dates but also result in serious

More information

This unit is a pump that will clear the waste from a domestic shower and washbasin, bath, washing machine, glass washer and a sink.

This unit is a pump that will clear the waste from a domestic shower and washbasin, bath, washing machine, glass washer and a sink. 1. Description This unit is a pump that will clear the waste from a domestic shower and washbasin, bath, washing machine, glass washer and a sink. The unit will start automatically. Please pay particular

More information

FIVE YEAR CERTIFICATION REPORT

FIVE YEAR CERTIFICATION REPORT GARDEN GROVE FIRE DEPARTMENT FIRE PREVENTION DIVISION FIVE YEAR CERTIFICATION REPORT Service and maintenance report of automatic fire extinguishing systems, including fire sprinklers, dry, deluge, and

More information

Planning Information. Passenger and Freight Elevators.

Planning Information. Passenger and Freight Elevators. A company of ThyssenKrupp Elevator Thyssen Aufzüge tk This planning information will give you an overview of the most important planning criteria of passenger and freight elevators. However you should

More information

Fighting Fire in Sprinklered Buildings. Student Guide

Fighting Fire in Sprinklered Buildings. Student Guide Fighting Fire in Sprinklered Buildings Student Guide Fighting Fire in Sprinklered Buildings Student Guide Table of Contents Purpose........................................................... 3 Instruction

More information

CHAPTER 9 FIRE PROTECTION SYSTEMS

CHAPTER 9 FIRE PROTECTION SYSTEMS CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope. Provisions of this chapter shall govern the application, design, installation, testing and maintenance of automatic sprinklers, standpipes

More information

CIBSE Guide M: Maintenance engineering and management Statutory compliance legislation and guidance

CIBSE Guide M: Maintenance engineering and management Statutory compliance legislation and guidance CIBSE Guide M: Maintenance engineering and management compliance legislation and guidance Types of System/Plant Action required Frequency by Type of Fire and Smoke Fire extinguishers Discharge (not CO

More information

c. As mandated by law, facilities must obtain and maintain valid zoning permits as well as permits for intended use.

c. As mandated by law, facilities must obtain and maintain valid zoning permits as well as permits for intended use. Walmart Standards for Suppliers Section 7. Health and Safety 7. Health and Safety Suppliers must provide workers with a safe and healthy work environment. Suppliers must take proactive measures to prevent

More information

Caravan Sites and Control of Development Act 1960. Permanent Residential Mobile Home Sites Licence Conditions

Caravan Sites and Control of Development Act 1960. Permanent Residential Mobile Home Sites Licence Conditions Caravan Sites and Control of Development Act 1960 Permanent Residential Mobile Home Sites Licence Conditions 1 Permanent Residential Mobile Home Site Licence Conditions Caravan Sites and Control of Development

More information

REVIEW ON FIRE REGULATIONS FOR NEW HIGH-RISE COMMERCIAL BUILDINGS IN HONG KONG AND A BRIEF COMPARISON WITH THOSE IN OVERSEAS

REVIEW ON FIRE REGULATIONS FOR NEW HIGH-RISE COMMERCIAL BUILDINGS IN HONG KONG AND A BRIEF COMPARISON WITH THOSE IN OVERSEAS , Volume 3, Number 1, p.25-51, 2001 REVIEW ON FIRE REGULATIONS FOR NEW HIGH-RISE COMMERCIAL BUILDINGS IN HONG KONG AND A BRIEF COMPARISON WITH THOSE IN OVERSEAS W.Y. Hung and W.K. Chow Department of Building

More information

PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS

PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS January 1997 PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS 1.0 PERMIT 1.1 After receipt of a Building Permit from the City of San Jose Building Department, submit

More information

CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES

CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES Review the following information pertaining to Construction Fire Safety Planning: B.C. Building Code Sections 8.1 up to and including Subsection 8.2.3 B.C.

More information

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011, Updated March 2012 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or

More information

SPRINKLER SYSTEM PLANS AND CALCULATIONS CHECK LIST

SPRINKLER SYSTEM PLANS AND CALCULATIONS CHECK LIST SPRINKLER SYSTEM PLANS AND CALCULATIONS CHECK LIST 1. Working plans shall be drawn to an indicated scale, on sheets of uniform size, with a plan of each floor, and shall show those items from the following

More information

Appraisal of Passive and Active Fire Protection Systems in Student s Accommodation

Appraisal of Passive and Active Fire Protection Systems in Student s Accommodation MATEC Web of Conferences 10, 06002 (2014) DOI: 10.1051/ matecconf/ 20141006002 C Owned by the authors, published by EDP Sciences, 2014 Appraisal of Passive and Active Fire Protection Systems in Student

More information

Spray Booth Guideline

Spray Booth Guideline Department of Development Service 135 North D Street, Perris CA. 92570 Phone: (951) 443-1029 Fax: (951) 943-3293 PURPOSE The intent of this guideline is to provide the information necessary to ensure that

More information

Firefighter Review. Instructor Guide

Firefighter Review. Instructor Guide Firefighter Review Instructor Guide Session Reference: 3 Topic: Attack Line Handling Level of Instruction: Time Required: Three Hours Materials: Two Fully Equipped Pumpers Structure for Use in Advancing

More information

FLAMMABLE AND COMBUSTIBLE LIQUIDS

FLAMMABLE AND COMBUSTIBLE LIQUIDS GAP.8.1.0 A Publication of Global Asset Protection Services LLC FLAMMABLE AND COMBUSTIBLE LIQUIDS INTRODUCTION National Fire Protection Association (NFPA) documents describe a level of fire protection

More information

Fire Safety Risk Assessment

Fire Safety Risk Assessment 1 Sources of ignition The main sources of ignition in Cass building are: PAF arrange for the fixed electrical installation to be tested in accordance with the British Standards. Test certificates are kept

More information

Please also see 10 golden rules for correct Saniflo installation on www.saniflo.co.uk

Please also see 10 golden rules for correct Saniflo installation on www.saniflo.co.uk 1. Description Sanicom is a lifting pump for wastewater used in commercial applications (restaurants, hairdressing salons, the catering industry etc.). The unit operates automatically, has a high performance

More information

ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS

ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS In this document are the fire safety equipment maintenance requirements that are found in Division B of the Alberta Fire Code (AFC 2006) for

More information

Full scale tunnel fire tests of VID Fire-Kill Low Pressure Water Mist Tunnel Fire Protection System in Runehamar test tunnel, spring 2009

Full scale tunnel fire tests of VID Fire-Kill Low Pressure Water Mist Tunnel Fire Protection System in Runehamar test tunnel, spring 2009 Full scale tunnel fire tests of VID Fire-Kill Low Pressure Water Mist Tunnel Fire Protection System in Runehamar test tunnel, spring 2009 By Carsten Palle, VID Fire-Fill, www.vid.eu Presented at ISTSS

More information

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011 FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or comments regarding the

More information

Civil Engineering Sector Labour-Management Health and Safety Committee

Civil Engineering Sector Labour-Management Health and Safety Committee PROCEDURE FOR THE STORAGE AND HANDLING OF FUEL ON CONSTRUCTION SITES Civil Engineering Sector Labour-Management Health and Safety Committee July 2008 PROCEDURE FOR THE STORAGE AND HANDLING OF FUEL ON CONSTRUCTION

More information

FIRE DETECTION AND ALARM SYSTEMS

FIRE DETECTION AND ALARM SYSTEMS HMO Information Sheet No 1 FIRE DETECTION AND ALARM SYSTEMS 1. Introduction When a property is in multiple occupation, the risk of fire breaking out is greater than in an ordinary single family home. Some

More information

SPECIFIC GUIDANCE FOR A HOUSE IN MULTIPLE OCCUPATION (HMO) CONVERTED ENTIRELY INTO SELF CONTAINED FLATS

SPECIFIC GUIDANCE FOR A HOUSE IN MULTIPLE OCCUPATION (HMO) CONVERTED ENTIRELY INTO SELF CONTAINED FLATS Document F SPECIFIC GUIDANCE FOR A HOUSE IN MULTIPLE OCCUPATION (HMO) CONVERTED ENTIRELY INTO SELF CONTAINED FLATS This document is intended as a specific guide for persons who own, manage or control Houses

More information

Static Electricity. A Health and Safety Guideline for Your Workplace. What Are Some Sources of Static Electricity? What is Static Electricity?

Static Electricity. A Health and Safety Guideline for Your Workplace. What Are Some Sources of Static Electricity? What is Static Electricity? A Health and Safety Guideline for Your Workplace What is static electricity? What causes it? How is it hazardous? And, most importantly, how can it be controlled? All of these questions will be answered

More information

EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM

EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29CFR1910.36-29CFR1910.38-29CFR1910.157-29CFR1910.165 NFPA-10 BASIS: The OSHA Emergency Action Planning and the

More information

FIRE RISK ASSESSMENT

FIRE RISK ASSESSMENT REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT This template has been provided to assist the Responsible Person with the preparation of a Fire Risk Assessment and is not intended for commercial

More information

Reticulation sewers in basements Technical guidelines

Reticulation sewers in basements Technical guidelines Reticulation sewers in basements Technical guidelines Overview What These guidelines explain our technical requirements for laying sewers in building basements. The scope of the guide is restricted to

More information

FIRE PREVENTION PLAN

FIRE PREVENTION PLAN FIRE PREVENTION PLAN 1 FIRE PREVENTION PLAN OSHA s Fire Prevention Plan regulation, found at 29 CFR 1910.38(b) and 29 CFR 1926.24, requires Northern Clearing, Inc. to have a written fire prevention plan

More information

Decree of the Ministry of the Environment. on fire safety of garages

Decree of the Ministry of the Environment. on fire safety of garages E4 THE NATIONAL BUILDING CODE OF FINLAND Fire safety of garages Guidelines 2005 Decree of the Ministry of the Environment on fire safety of garages Adopted in Helsinki, 22 March 2005 Pursuant to the Decision

More information

SPRINKLER RULES & STANDARDS IN EUROPE CEA 4001 & EN 12845

SPRINKLER RULES & STANDARDS IN EUROPE CEA 4001 & EN 12845 SPRINKLER RULES & STANDARDS IN EUROPE CEA 4001 & EN 12845 DAEGU: 20 th August 2010 Karim KARZAZI 1 Development of sprinkler rules & standards in Europe. Overview of past, existing and future situation

More information

Annual Fire Safety Training Module

Annual Fire Safety Training Module Annual Fire Safety Training Module 6 March 2014, v4 1 Course Overview: Annual Fire Safety Training This training module has been developed for workers at the University of Queensland, and forms part of

More information

ADMINISTRATIVE SERVICES MANUAL

ADMINISTRATIVE SERVICES MANUAL Purpose Responsibilities Proper Storage and use of flammable liquids can significantly reduce the possibility of accidental fires and injuries. To minimize risk to life and properly, the requirements of

More information

Notes. Material 1. Appropriate Flammable Liquids

Notes. Material 1. Appropriate Flammable Liquids 29 CFR 1910.106 Flammable Materials Flammable Liquids Preparation 1. Read Applicable Background information and related Company Policy Chapter. 2. Make Copies of this Lesson Plan for Personnel 3. Make

More information

Portable Fire Extinguisher Presentation

Portable Fire Extinguisher Presentation Slide 1 Fire Extinguisher Training A requirement of all Clemson University Employees as mandated by OSHA: Portable fire extinguishers. - 1910.157 Welcome to the Clemson University Online Fire Extinguisher

More information

Fire Extinguishers Water Extinguishers

Fire Extinguishers Water Extinguishers Water Extinguishers Water extinguishers are suitable for Class A fires caused by combustion of solid materials such as wood, paper, straw, textiles and coal etc. Water additive extinguishers use an environmentally

More information

Fire Protection Program Of Chashma Nuclear Power Generating Station Pakistan Atomic Energy Commission 5/28/2015 1

Fire Protection Program Of Chashma Nuclear Power Generating Station Pakistan Atomic Energy Commission 5/28/2015 1 Fire Protection Program Of Chashma Nuclear Power Generating Station Pakistan Atomic Energy Commission 5/28/2015 1 Nuclear Power in Pakistan Nuclear Power Plants Capacity (MWe) Year of Commissioning In

More information

CHAPTER. Standpipes and Hose Systems OVERVIEW. Standpipe and Hose Systems Defined

CHAPTER. Standpipes and Hose Systems OVERVIEW. Standpipe and Hose Systems Defined Standpipes and Hose Systems CHAPTER 3 This chapter, which opens with an overview of standpipe and hose systems, is intended to assist the registered design professional (RDP), commissioning agent, authority

More information

MOTOR FUEL DISPENSING SAFETY

MOTOR FUEL DISPENSING SAFETY STRATEGIC OUTCOMES PRACTICE TECHNICAL ADVISORY BULLETIN January 2010 MOTOR FUEL DISPENSING SAFETY Fire! Not an alarm anyone wants to hear, especially not when the fire is burning at a major fuel source.

More information

OREGON FIRE CODE Interpretations and Technical Advisories

OREGON FIRE CODE Interpretations and Technical Advisories OREGON FIRE CODE Interpretations and Technical Advisories A collaborative service by local and state fire professionals, along with our stakeholders and customers, to provide consistent and concise application

More information

Fire & Explosion Risks in Service Stations

Fire & Explosion Risks in Service Stations Fire & Explosion Risks in Service Stations Petrol Vapour Petrol gives off highly flammable vapour even at very low temperatures. Because of the flammability of petrol vapours, service stations carry a

More information

High Pressure Water Mist Systems: Alternative Solution For Critical Civil Applications

High Pressure Water Mist Systems: Alternative Solution For Critical Civil Applications International Water Mist Conference, London, United Kingdom,23-24 September, 2009 High Pressure Water Mist Systems: Alternative Solution For Critical Civil Applications Fire Fighting In Civil Applications

More information

SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT

SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT INTRODUCTION No matter how reliable fire protection equipment may seem, periodic maintenance is needed to ensure proper operation. Fire protection

More information

FIRE SAFETY HANDBOOK

FIRE SAFETY HANDBOOK 29 CFR 1960.20, Alternate Standard For Fire Safety In Airport Traffic Control Towers (ATCTs) Fire Prevention Plan (FPP) Emergency Action Plan (EAP) FIRE SAFETY HANDBOOK DEPARTMENT OF TRANSPORTATION FEDERAL

More information

Fire Alarm system Installation Guide

Fire Alarm system Installation Guide Fire Alarm system Installation Guide Fire Alarm System Categories Systems designed for Protection of Property only, fall into two classifications P1 or P2. but a manual system is also needed, then this

More information

Flammable Liquids 29 CFR 1910.106

Flammable Liquids 29 CFR 1910.106 Flammable Liquids 29 CFR 1910.106 OSHA s Directorate of Training and Education These materials were developed by OSHA s Directorate of Training and Education and are intended to assist employers, workers,

More information

Arapahoe County Residential Water Heater Installation and Inspection Guide

Arapahoe County Residential Water Heater Installation and Inspection Guide Arapahoe County Residential Water Heater Installation and Inspection Guide The attached handout is designed to be a general permit submittal and inspection guide covering most installation instances, however

More information

Fire Safety Log Book. Premises Name: Premises Address: Date From: Date To: Location of Log Book:

Fire Safety Log Book. Premises Name: Premises Address: Date From: Date To: Location of Log Book: Fire Safety Log Book Premises Name: Premises Address: Date From: Date To: Location of Log Book: CONTENTS PART 1 FIRE SAFETY ADVICE 1 PART 2 FIRE PRECAUTIONS 2 Section 1 Guidance on Fire Risks and Preventative

More information

GUIDELINE 5. CLASSES OF FIRE, TYPES OF PORTABLE FIRE EXTINGUISHERS, INSPECTION & MAINTENANCE OF FIRE EXTINGUISHERS IN UNIVERSITY BUILDINGS

GUIDELINE 5. CLASSES OF FIRE, TYPES OF PORTABLE FIRE EXTINGUISHERS, INSPECTION & MAINTENANCE OF FIRE EXTINGUISHERS IN UNIVERSITY BUILDINGS GUIDELINE 5. CLASSES OF FIRE, TYPES OF PORTABLE FIRE EXTINGUISHERS, INSPECTION & MAINTENANCE OF FIRE EXTINGUISHERS IN UNIVERSITY BUILDINGS 1.0 PURPOSE 1.1 To provide an overview of fire extinguisher use

More information

Certification: Building Plans Examiner. Exam ID: B3

Certification: Building Plans Examiner. Exam ID: B3 Certification: Building Plans Examiner Exam ID: B3 Scope: A Building Plans Examiner will be responsible for reviewing submitted plans to determine if they meet the requirements of the various Building

More information

Restaurant & café guide

Restaurant & café guide 'Helping our customers stay in business by reducing risk' NZI Risk Solutions TM About NZI Risk Solutions NZI has extensive experience in providing expert risk management advice to help our commercial customers

More information

HAZARDS AND THREATS WILDFIRES HOMEOWNERS CHECKLIST INSIDE THE HOME

HAZARDS AND THREATS WILDFIRES HOMEOWNERS CHECKLIST INSIDE THE HOME HAZARDS AND THREATS WILDFIRES HOMEOWNERS CHECKLIST INSIDE THE HOME KITCHEN Keep a working extinguisher in the kitchen. Maintain electric and gas stoves in good operating condition. Keep baking soda on

More information

TYPICAL FIRE SAFETY INSPECTION VIOLATIONS

TYPICAL FIRE SAFETY INSPECTION VIOLATIONS TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to

More information

1. Description. 2. List of Accessories included A B C F G H

1. Description. 2. List of Accessories included A B C F G H 1. Description This unit is a pump that will clear the waste from a domestic shower and washbasin. The unit will start automatically. Please pay particular attention to the following: Possible danger to

More information

Fire Safety Risk Assessment Checklist for Residential Care Premises

Fire Safety Risk Assessment Checklist for Residential Care Premises Checklist for Residential Care Premises Name of Premises: Address of Premises: Name of Responsible Person: What area / location does the assessment cover? Does the assessment cover the whole site YES or

More information

TESTING AND COMMISSIONING PROCEDURE FOR FIRE SERVICE INSTALLATION GOVERNMENT BUILDINGS THE HONG KONG SPECIAL ADMINISTRATIVE REGION

TESTING AND COMMISSIONING PROCEDURE FOR FIRE SERVICE INSTALLATION GOVERNMENT BUILDINGS THE HONG KONG SPECIAL ADMINISTRATIVE REGION TESTING AND COMMISSIONING PROCEDURE FOR FIRE SERVICE INSTALLATION IN GOVERNMENT BUILDINGS OF THE HONG KONG SPECIAL ADMINISTRATIVE REGION 2007 EDITION ARCHITECTURAL SERVICES DEPARTMENT THE GOVERNMENT OF

More information

NFPA31FuelOilPiping 1 Revised 3-1-11

NFPA31FuelOilPiping 1 Revised 3-1-11 NFPA 31 Fuel Oil Piping, Installation and Testing Chapter 8 Fuel Piping Systems and Components 8.1 Scope. This chapter shall apply to piping systems and their components used to transfer fuel oil from

More information