Use EMS to Improve Simulation of Outside Air Economizer and Fan Control for Unitary Air Conditioners
|
|
- Oscar Ferguson
- 7 years ago
- Views:
Transcription
1 Building Energy Simulation Forum Use EMS to Improve Simulation of Outside Air Economizer and Fan Control for Unitary Air Conditioners Reid Hart, PE with help from: Rahul Athalye; Weimin Wang, Ph.D.; Michael Rosenberg January 2014 PNNL-SA
2 Outline RTUs, Economizers & Fans OSA Economizer Modeling Energy Management System (EMS)* in EnergyPlus Economizer simulation with EMS Fan speed reduction simulation with EMS Overall energy impact *EMS here refers to an EnergyPlus feature that provides a way to develop custom control and modeling routines for EnergyPlus models. 2
3 RTUs: Economizers & Fans
4 Why Rooftop Units 4 Significant Volume Represents over 40% of commercial building area. Energy Code Opportunities DCV on RTUs serving high occupancy Single Zone VAV on RTUs > 9 tons Economizer performance (integrated vs. non integrated) 4
5 Why HVAC 5 Because HVAC energy represents a significant percentage of energy use in a commercial building ~ 60% Largest percentage of savings is gas Misc. Equip. 24% Typical Office Building Area Lights 19% Space Cool 8% Vent. Fans 14% Space Heat 35%
6 Breakdown of HVAC Energy 0.4 Office (Functioning Economizer) Space Cool (kbtu/sf) Vent Cool (kbtu/sf) Vent Heat (kbtu/sf) Space Heat (kbtu/sf) Fans (kbtu/sf) Econo Savings (kbtu/sf) Energy Use Breakdown Cooling = 15% / Heating = 55% / Fan = 30% 6
7 Basic RTU Components T Damper Actuator Digital Controller VSD or 2 spd CO2 Sensor OA Temp Fan Airflow Control: 33% Fan Energy Savings Ventilation Control: 50% Ventilation Energy Savings Economizer Control: 33% Cooling Energy Savings Ventilation Cooling Economizer Cooling Ventilation Heating 7 Space Cooling Fan Energy Space Heating
8 RTU Cooling Energy Use 8 Million Btu's Baseline HVAC Energy Use Fan Heat Cool Cooling is common down to 44 F OAT in offices in winter OSA Te m perature Bin 8 No Economizer
9 Economizer Energy Savings Potential 9 Million Btu's ECM HVAC Energy Use Fan Heat Cool % Cooling Energy Savings OSA Temperature Bin 9 Optimized Economizer
10 Variation of Supply Fan Airflow 90.1 addendum AQ added fan control requirements phasing in 110 MBH 2013; 75 MBH 2014; 65 MBH 2016 Source: Carrier 10
11 Need for Improved Simulation Addendum AQ to introduced several items: Multi-stage or variable cooling capacity to improve economizer and fan operation. Economizers on RTUs with direct expansion (DX) mechanical cooling to remain fully open during integrated operation until discharge air temperature (DAT) drops to 45 F (7 C). Multi-speed or variable speed fans to reduce fan energy use. Future items under consideration Reduced return (RA) air damper leakage Current modeling would not show savings: Economizer operation is now modeled as ideal Multi-speed fan not correctly implemented in EnergyPlus 11
12 PNNL Prototypes for 90.1 ASHRAE 90.1 progress indicator: Tracks progress between versions of ASHRAE Standard 90.1 Results are weighted for national construction occurrence of the prototypes E+ files available (search: PNNL prototypes) Stand Alone Retail Prototype: Used for this example Single floor 24,695 square feet construction 12 Package Rooftop Units (RTU) with dry-bulb air economizer
13 OSA Economizer Modeling
14 RTU Economizers: Modeling vs. Reality Modeling of unitary system economizers in EnergyPlus & DOE2 Modeled in a single mode per time step; actually multiple modes Assume full economizer benefit is available, regardless of DAT Operational reality When economizer operates alone, full economizer is available With full economizer, typical outside air fraction is closer to 70% In integrated operation, low DAT closes economizer 14 A m ps / Volts Tem perature, o F :52 AM 10:12 AM 10:32 AM 10:52 AM 11:12 AM 11:32 AM 11:52 AM AMPS TSTAT OSA DA RA
15 DX Economizer Alternating Integration Alternating integration means 2 cooling modes Full economizer without DX cooling coil operation Partial economizer with DX cooling coil operation needed to: Maintain comfortable discharge air temperature Avoid coil freezing Source: PECI & Taylor Engineering,
16 Economizer Effectiveness Ideal OSA economizer contribution to sensible cooling (100% OA) (RA-OA) [time] Is impacted by the actual % of OA (RA-OA) [time] [%OA] We need to cover both alternating modes for DX cooling (RA-OA) [t 1 ] [%OA withdx ] + (RA-OA) [t 2 ] [%OA nodx ] e.g., (75-65) [t 1 ] [40%] + (75-65) [t 2 ] [70%] By magic of algebra, for t = timestep (RA-OA) t ( [%t 1 ] [%OA withdx ] + [1-%t 1 ] [%OA nodx ] ) or, (RA-OA) t [economizer effectiveness %] where [%t 1 ] = f (Load%, OA DB, OA WB ) Economizer effectiveness for time step is input into E+ with EMS using the economizer effectiveness in a schedule as the maximum outdoor air fraction in the outdoor air controller object 16
17 Maximum Economizer Outside Air Fraction Smaller RTUs have lower cost economizer dampers High quantity of return air leakage Acknowledging this impact allows future credit for improved return air damper seals Source: Davis,
18 Find Economizer Effectiveness Mostly, cooling control is a function of dry-bulb space temperature So if we correctly determine the sensible load contribution of the economizer, our input will be correct, the model will adapt DX cooling capacity is strongly impacted by entering wet-bulb So, to find [economizer effectiveness %], we need to solve [%OA withdx ] + [1-%t 1 ] [%OA nodx ] )where [%t 1 ] = f (Load%, OA DB, OA WB ) So run many humidity conditions to find eff ECON given know DX operation Matrix eff ECON as f (Load%, OA DB ) for multiple OA WB & RA WB 18
19 Economizer Contribution Relates to OAT Maximum %OA during DX cooling is limited by comfort Economizer-only time is relative to internal load Share of ideal economizer depends on OAT & load Source: PECI & Taylor Engineering,
20 Simplified Economizer Effectiveness For a range of loads, time in each stage of cooling found Impact of alternating integration on economizer performance calculated, assuming 70% maximum With more stages of DX, impact not as great 20
21 EMS Modeling in EnergyPlus
22 Custom Simulation Control 22 equest / DOE2 Two different methods Input Macros (v2.2) allow parts of BDL files to be mixed and matched Selective skipping parts of input file before run Defining blocks for reference Apply math to input generation User Functions Allow on the fly runtime control changes Limited to versions 2.1e May be available in the 2.2 engine from text BDL, but not recognized or editable by the equest database EnergyPlus E+ also has input macros EMS = Energy Management System Erl = E+ Runtime Language Intended to simulate functions normally available in an EMS Can be used for other conditional inputs during run Essentially adjusts Actuators based on Sensors EMS Examples: Reset flows based on load or environmental conditions Activate humidification only under certain conditions
23 Economizer in Erl EMS Erl code requires: 1. Sensors (inputs) 2. Internal Variables 3. Actuators (outputs) 4. Global Variables 5. Programs 6. Program Calling Managers See the separate Application Guide for EMS (a.k.a. The Book of Erl) in the E+ documentation 23
24 Why do we need to use E+ EMS? Why not just use short time steps? Then E+ can alternate between economizer and not economizer, right? No it won t E+ does not model true temperature differential control (nor does DOE2) For cycling units, the capacity & load is needed vs. a power curve that has cycling losses built in. Ppwer is used for power for the whole time step! Also, going from 15 to 1 minute timestep = long run times (260 runs/ecm) Since only one mode is modeled we need to fool E+ by Entering a maximum OA flow that matches the average OA airflow during the time step Entering fan power equivalent to the actual average fan power during the time step 24
25 Economizer Logical Steps in Erl Establish Stepwise logic 1. Coil Entering Conditions (MAT) when OAT at minimum ventilation position 2. Coil Entering Conditions (MAT) when OAT at maximum economizer position 3. Find MAT at each stage of cooling (may need iteration) 4. Find total sensible dt at each stage, including economizer benefit dt 5. Find stages operating during the time step & MAT each stage 6. Find economizer effectiveness for each stage and average during the time step 7. Find Fan average kw during the time step 25
26 Economizer Logical Steps in Erl 26
27 Abandoned full Erl Implementation Abandoned full Erl Implementation Difficult to debug Long runtime, as MAT was iterative calculation Perform step by step calculations in a spreadsheet for range of conditions Max OA Fraction is f(cool Load, OAT WB, OAT DB ) Develop from regressions 27
28 Streamline Code with Regressions 28
29 Note on EMS Algebra & Quality Assurance Use more parenthesis than you ever thought you would need! EMS/Erl does not understand algebraic priorities!!! Example: economizer effectiveness regression for 2- & 1-stage cooling: As always, inspect hourly or time step runs with output of Sensor inputs; Intermediate variables; Actuator outputs Once debugged can comment out to improve speed 29
30 Regression Development Full simulation with EMS resulted in long run times DX coil capacity adjustment determined based on entering temperature, dry bulb and wet bulb The required DX cooling run time was determined At multiple loads For multiple outside dry bulb (DB) and wet bulb (WB) conditions For multiple return air wet bulb conditions Economizer operation in both modes determined 3 minute delay for addendum AQ 45 F integration requirement Effective maximum economizer operation determined Regressions for 1-stage (R ) and 2-stage (R ) Regressions programmed into EMS for max OA fraction Based on cooling load, OA WB, OA DB (RA WB not significant) 30
31 Regression: Economizer Effectiveness OAT, DB, F: 72 F 65 F 58 F Two-Stage Single Stage 31
32 Energy Impact of Improved Model Improved model reduces economizer effectiveness and more correctly models mechanical cooling energy use 32
33 Fan Modeling
34 RTU Fan Speed Control Small RTUs use multi-speed fans, not variable speed drives (VSDs) By affinity laws, fan power will reduce as some exponent of airflow However the modeled operation does not match time-weighted power Example: 30% coil load has 30% time at full speed with the DX coil on the rest at 50% speed for ventilation or economizer 34
35 Time vs. Flow Weighting EnergyPlus and other models use flow weighting for fan power on unitary systems EnergyPlus allows different fan speeds for cooling, heating, ventilation, but not economizer mode Sequence for first stage cooling may have: Low speed when economizer locked out Full speed when economizer is OK Low speed for partial economizer Actual operation is time weighted; 100% cooling, 50% ventilation Flow-weighting estimates fan power 20% low at 30% cooling load Actual RTU Operation Time-weighted Flow-weighted Flow vs. Factor High Speed Low Speed Average Average Time Weighting Mode Cooling Ventilation Mixed Time in Mode 30% 70% Mass Flow or CFM (Q) 100% 50% 65% Fan Power Ratio (W ratio ) % Low 35
36 EMS Fan Power Development EMS calculations in each time step Use the coil fraction to determine time in each mode Adjust speed for economizer operation Calculate the time-weighted fan power for time step Fan power is proportional to static pressure, so Set the fan in E+ for full speed/ full flow Apply an adjustment to the static pressure The proper fan power is calculated Fan energy matched the multi-speed fan use by mode Fan heat added to airstream is correct for time step 36
37 Determine Fan Control in each Time Step 37
38 Other Examples of Use of EMS Turn on a relief fan when economizer is in use Simulate pressure control If OA > Min Ventilation Energize relief fan Reduce cooling temperature setpoint if space humidity exceeds threshold If RH > 60% Cooling setpoint deg. F 38
39 Overall Results
40 HVAC Energy End Use Salem Oregon, climate zone 4C Stand-Alone Retail prototype Correct for less economizer cooling, then improvements from two-stage cooling, then corrected multi-speed fan operation savings 40
41 HVAC Energy End Use HVAC Energy Use Index 1000 Btu s per square foot Stand-Alone Retail prototype Overall impact in multiple climate zones 41
42 Conclusions EnergyPlus (and DOE2) understate RTU energy use Economizer effectiveness is overstated Fan savings from speed reduction is overstated In EnergyPlus EMS can be used to improve results Based on cooling load, OA WB & OA DB, economizer effectiveness is found in each time step Fan time-weighted power is found in each time step 42 Future possibilities Revise RTU native simulation in programs to account for multiple modes occurring in one time step Determine time in each mode to meet load Calculate each mode operation and energy impact separately Sum mode results for the time step
43 References ASHRAE. (2010). ASHRAE/ASHRAE/IES Standard : Energy Standard for Buildings except Low-Rise Residential Buildings. American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc., Atlanta, GA. Davis, R., Francisco, P., Kennedy, M., Baylon, D., and Manclark, B. (2002). Enhanced Operations & Maintenance Procedures for Small Packaged Rooftop HVAC Systems: Protocol Development, Field Review, and Measure Assessment. Ecotope for Eugene Water & Electric Board. EIA. (2008) Commercial Buildings Energy Consumption Survey. U.S. Energy Information Administration. Hart, R. (2011). DOE Work-Arounds to Hidden Problems: equest - A half hour to learn; three years to master. Portland, OR. Hart, R., Price, W., and Morehouse, D. (2006). The Premium Economizer: An Idea Whose Time Has Come. Proceedings of the 2006 ACEEE Summer Study on Energy Efficiency in Buildings, American Council for an Energy-Efficient Economy (ACEEE), Pacific Grove, CA, LBNL. (2012a). EnergyPlus Engineering Reference: The Reference to EnergyPlus Calculations. Lawrence Berkeley National Laboratory for USDOE. LBNL. (2012b). Application Guide for EMS: Energy Management System User Guide. Lawrence Berkeley National Laboratory for USDOE. PECI & Taylor Engineering. (2011) Light Commercial Unitary HVAC for Codes and Standards Enhancement Initiative (CASE). California Utilities Statewide Codes and Standards Team for California Public Utilities Commission. Thornton, B. A., Wang, W., Cho, H., Xie, Y., Mendon, V. V., Richman, E. E., Zhang, J., Athalye, R. A., Rosenberg, M. I., and Liu, B. (2011). Achieving the 30% Goal: Energy and Cost Saving Analysis of ASHRAE/IES Standard PNNL for USDOE. 43
44 Questions? Reid Hart, PE
Ventilation Retrofit Opportunities for Packaged HVAC
Ventilation Retrofit Opportunities for Packaged HVAC Reid Hart, PE National Energy Efficiency Technology Summit September 2012 PNNL-SA-90782 Acknowledgements Bonneville Power Administration City of Eugene
More informationAPPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application
APPLICATION GUIDE Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application Section Comparison of Latent Cooling Performance of Introduction Most commercial HVAC systems
More informationAir Side Economizers and Energy Recovery - Improvements and New Regulations. Richard Lord 09-20-2012
Air Side Economizers and Energy Recovery - Improvements and New Regulations Richard Lord 09-20-2012 Introduction For commercial buildings the use of outside air for cooling and ventilation is an important
More informationPresentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks
Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same
More informationfor Plans Examiners and Building Inspectors
Building Technologies Program HVAC Controls Guide for Plans Examiners and Building Inspectors September 2011 Authors: Eric Makela, PNNL James Russell, PECI Sarah Fujita, PECI Cindy Strecker, PECI Prepared
More informationUNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01
GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per
More informationHVAC Systems: Overview
HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct
More informationAIR COOLED CHILLER CHILLED WATER PUMP CONTROL: The chilled water pump with the lowest runtime will automatically start when the outside air temperature rises above the system enable setpoint. When the
More information5.6 Technical Specification: Premium Efficiency Electric Air Conditioning Equipment
5.6 Technical Specification: Premium Efficiency Electric Conditioning Equipment Small Premium Project Type: For Premium Conditioning Retrofit Projects: Projects that voluntarily replace existing unitary
More informationMeeting the Challenge of Persistence Energy Efficiency in Rooftop Units
Meeting the Challenge of Persistence Energy Efficiency in Rooftop Units Reid Hart, PE Associate Director PECI Karen des Sr. Program Manager PECI AIA Quality Assurance Learning Objectives 1. Identify the
More informationImpacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance
More informationModeling and Simulation of HVAC Faulty Operations and Performance Degradation due to Maintenance Issues
LBNL-6129E ERNEST ORLANDO LAWRENCE BERKELEY NATIONAL LABORATORY Modeling and Simulation of HVAC Faulty Operations and Performance Degradation due to Maintenance Issues Liping Wang, Tianzhen Hong Environmental
More informationDr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida
Optimizing 100% Outside Air Systems with Heat Pipes Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida Introduction To meet increasingly rigorous building codes
More informationNEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB
More informationFLORIDA SOLAR ENERGY CENTER
FLORIDA SOLAR ENERGY CENTER Creating Energy Independence Since 1975 Impact of Energy-Efficiency Parameters on Home Humidity Rob Vieira Florida Solar Energy Center A Research Institute of the University
More informationImpacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions
Impacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions M. Liu, Y. Zhu, D. E. Claridge Energy Systems Laboratory Texas A&M University Ed. White Energy Management Operation
More informationTips and Tricks for Estimating Energy Savings. Celeste Cizik, P.E. Project Manager E M C Engineers, Inc.
Tips and Tricks for Estimating Energy Savings Celeste Cizik, P.E. Project Manager E M C Engineers, Inc. AIA Quality Assurance Learning Objectives 1. Understand the pros and cons of various energy calculation
More informationUsing Time-of-Day Scheduling To Save Energy
The following article was published in ASHRAE Journal, May 29. Copyright 29 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes only.
More informationData Centers WHAT S ONTHEHORIZON FOR NR HVAC IN TITLE 24 2013? SLIDE 1
WHAT S ONTHEHORIZON FOR NR HVAC IN TITLE 24 2013? SLIDE 1 Data Center CASE Scope Existing Title 24 2008 Scope Current scope ( 100 T24-2008) exempts process space from many of the requirements, however
More informationThe Impact of Demand-Controlled and Economizer Ventilation Strategies on Energy Use in Buildings
4276 The Impact of Demand-Controlled and Economizer Ventilation Strategies on Energy Use in Buildings Michael J. Brandemuehl, Ph.D., P.E. Member ASHRAE James E. Braun, Ph.D., P.E. Member ASHRAE ABSTRACT
More informationnewsletter Let s take a high-level look at airside economizing: what it is, what it requires, and how it s done. How does economizer cooling work?
engineers volume 35 2 newsletter providing insights for today s hvac system designer keeping cool with outdoor air Airside Economizers from the editor For the denizens of commercial buildings, comfort
More informationHVAC Simplified Approach Option
HVAC Simplified Approach Option Part I Project Address: City: HVAC System Designer of Record: Date: Zip: Qualification The building is 2 stories or less in height and has a gross floor area is less than
More informationExample Retrocommissioning Measure: Opening Throttled Discharge Valves
Opening Throttled Discharge Valves This 21-story building, constructed in 1997, is located in Oregon and contains 589,000 gross square feet of mostly office occupancy. The HVAC system includes six large
More informationHeating, Ventilation & Air Conditioning Equipment
FinAnswer Express Utah Incentive Catalog Effective as of May 19, 2012 Heating, Ventilation & Air Conditioning Equipment Rocky Mountain Power provides incentives for many types of energy-efficient technologies.
More informationRating Water-Source Heat Pumps Using ARI Standard 320 and ISO Standard 13256-1
Rating Water-Source Heat Pumps Using ARI Standard 320 and ISO Standard 13256-1 W. Vance Payne and Piotr A. Domanski National Institute of Standards and Technology Building and Fire Research Laboratory
More informationHVAC Basic Science - System Capacity
HVAC Basic Science - System Capacity Btu/hour, btu/h, b/h, btuh. btu?? 1 MBH = 1000 btu/hour 1 KBH = 1000 btu/hour 1 ton of cooling= 12,000 btu/hour 1 watt = 3.414 btu/hour 1 kilowatt = 1000 watts = 3,414
More informationJ O U R N A L. Energy Performance for. Proper Specification of Air Terminal Units Future Climate Impacts on Building Design
Copyright 24, American Society of Heating, Refrigerating & Air-Conditioning Engineers, Inc., 79 Tullie Circle NE, Atlanta, GA. 3329. Reprinted by permission from the September 24 Issue of ASHRAE Journal
More informationTom Brooke, PE, MBA, CEM tabrooke@embarqmail.com
Tom Brooke, PE, MBA, CEM tabrooke@embarqmail.com Framework, perspective or example in a particular discipline at a given time These four new models are: New and additional, or Updated Today's Paradigm
More informationHVAC Checklist - Long Form
HVAC Checklist - Long Form Page 1 of 14 Appendix B discusses HVAC system components in relation to indoor air quality. utside Air Intake Location pen during occupied hours? Unobstructed? Standing water,
More informationHVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation. Richard Lord Carrier Fellow
HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation Richard Lord Carrier Fellow HVAC Industry Challenges and Issues Ozone Deletion Global Warming
More informationLower Energy Costs with Rooftop Air-Conditioning Package Units
Lower Energy Costs with Rooftop Air-Conditioning Package Units Sponsored by Mike West, PhD, PE Advantek Consulting, Inc Package Unit Efficiency Factors Sensible and latent performance ratings Unit efficiency
More informationCONTROL STRATEGIES FOR HVAC SYSTEMS
CONROL SRAEGIES FOR HVAC SYSEMS ZBIGNIEW POPIOLEK Department of Heating, Ventilation and Dust Removal echnology Silesian University of echnology, Poland 1 Definition of control: to apply a regulating influence
More informationComparisons of HVAC Simulations between EnergyPlus and DOE-2.2 for Data Centers
ERNEST ORLANDO LAWRENCE BERKELEY NATIONAL LABORATORY Comparisons of HVAC Simulations between EnergyPlus and DOE-2.2 for Data Centers Tianzhen Hong, Dale Sartor, Paul Mathew, Mehry Yazdanian Environmental
More informationWO32 HVAC Evaluation Interim Findings of Commercial Quality Maintenance HVAC Programs
WO32 HVAC Evaluation Interim Findings of Commercial Quality Maintenance HVAC Programs DNV KEMA Energy and Sustainability Robert Mowris & Associates, Inc. 1 Acknowledgements Work Order 32 EM&V Team, Jarred
More informationDesignBuilder EMS - Intro
DesignBuilder EMS - Intro Functionality not provided in standard E+ can be programmed Programming language called E+ Runtime Language (Erl) DesignBuilder extensions added to form DB Erl E+ interprets and
More informationThe Chilled Water and Hot Water Building Deferential Pressure Setpoint Calculation Chilled Water and Hot Water Pump Speed Control
The Chilled Water and Hot Water Building Deferential Pressure Setpoint Calculation Chilled Water and Hot Water Pump Speed Control Chenggang Liu Research Associate Homer L. Bruner, Jr., CEM Mechanical Systems
More informationIntegrating Kitchen Exhaust Systems with Building HVAC
Design Guide 3 Improving Commercial Kitchen Ventilation System Performance Integrating Kitchen Exhaust Systems with Building HVAC This design guide provides information that may help achieve optimum performance
More informationBring the fresh in. Dedicated Outside Air Systems
Bring the fresh in. Dedicated Outside Air Systems The inside story on outside air. On average, we breathe in 3,400 gallons of air each day. Ambient indoor air pollution is a major problem, affecting health
More informationBy Donald Fisher, P.Eng., Associate Member ASHRAE
By Donald Fisher, P.Eng., Associate Member ASHRAE Decisions to purchase a commercial kitchen ventilation (CKV) system often are based on rule-of-thumb estimates using a $/cfm index (i.e., annual energy
More informationAIR SYSTEMS ENERGY SERIES Energy Recovery Wheels
AIR SYSTEMS ENERGY SERIES Energy Recovery Wheels APPLICATION GUIDE Supercedes: Nothing Form 102.20-AG6 (305) INTRODUCTION As fossil fuel reserves are depleted, the cost of energy continues to rise. According
More informationElement D Services Heating, Ventilating, and Air Conditioning
Load Calculation Criteria PART 1 - GENERAL 1.01 OVERVIEW A. This section includes requirements for calculating HVAC cooling and heating loads. B. Load calculations must be performed in accordance with
More informationZoned Air Conditioners - A Real Value?
H114 Prepared by: Proctor Engineering Group, Ltd. San Rafael, CA 94901 (415)451-2480 Zoning Ducted Air Conditioners, Heat Pumps, and Furnaces: Summary of a Case Study prepared for the California Statewide
More informationSelf-benchmarking Guide for Data Center Infrastructure: Metrics, Benchmarks, Actions 6-28-10. Sponsored by:
Self-benchmarking Guide for Data Center Infrastructure: Metrics, Benchmarks, Actions 6-28-10 Sponsored by: Disclaimer This document was prepared as an account of work sponsored by the United States Government.
More informationAC System Equipment Specification, Installation and Operational Options for Improved Indoor Humidity Control
AC System Equipment Specification, Installation and Operational Options for Improved Indoor Humidity Control Authors Don B. Shirey, III Original Publication Shirey III, D., "AC System Equipment Specification,
More informationAchieving ENERGY EFFICIENCY with Standard Air-Conditioning Units. Mike West, PhD, PE Advantek Consulting, Inc
Achieving ENERGY EFFICIENCY with Standard Air-Conditioning Units Mike West, PhD, PE Advantek Consulting, Inc Standard Air Conditioning Unit Packaged Unit Split System DX (not chilled water) Air-cooled
More informationSmart School Symposium Heating Ventilation and Air Conditioning Session HVAC Products. Richard Lord
Smart School Symposium Heating Ventilation and Air Conditioning Session HVAC Products Richard Lord Overview and Agenda My goal today is to give you quick an overview of the current status of HVAC products
More informationSIMULATION OF RADIANT COOLING PERFORMANCE WITH
SUMMARY REPORT MAY 2008 SIMULATION OF RADIANT COOLING PERFORMANCE WITH EVAPORATIVE COOLING SOURCES Timothy Moore Center for the Built Environment (CBE) University of California, Berkeley May 2008 EXECUTIVE
More informationAMCA International. Investigation of the Impact of Building Entrance Air Curtain on Whole Building Energy Use AIR MOVEMENT AND CONTROL
AMCA International Investigation of the Impact of Building Entrance Air Curtain on Whole Building Energy Use AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC. The International Authority on Air
More informationMaximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages
Objectives Increase awareness of the types of economizers currently used for data centers Provide designers/owners with an overview of the benefits and challenges associated with each type Outline some
More informationComparing Energy Savings of Different VAV Systems
Comparing Energy Savings of Different VAV Systems Prepared By: Martyn Dodd mart@energysoft.com EnergySoft LLC 1025 5th Street, Suite A Novato, CA 94945 415-897-6400 www.energysoft.com Last Modified: March
More informationVariable Air Volume - VAV
Mode Enable Sensor Options Variable Air Volume - VAV The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during occupied operation. The following options are available:
More informationHow To Design A Building In New Delhi
ENERGY EFFICIENT HVAC DESIGN FOR COMPOSITE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce energy consumption
More informationHow Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems
How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems Paul Mathew, Ph.D., Staff Scientist Steve Greenberg, P.E., Energy Management Engineer
More informationAPPLICATION GUIDE. Moisture Management in Waterborne Climate Systems
APPLICATION GUIDE Moisture Management in Waterborne Climate Systems Contents Introduction 3 WBCS Concept 3 Condensation 4 Moisture Sources in the Space 4 Impact of a High Moisture Load 5 Designing to Manage
More informationDefining Quality. Building Comfort. Precision. Air Conditioning
Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air
More informationIndirect Evaporative Cooling (IDEC) Unit for Data Centers
Indirect Evaporative Cooling (IDEC) Unit for Data Centers NORTEK AIR SOLUTIONS Cool3 IDEC UNIT INDIRECT EVAPORATIVE COOLING The new Nortek Air Solutions Cool 3 IDEC unit is a proven approach for highly
More informationVRF Life Cycle Cost Analysis. January 23, 2011
VRF Life Cycle Cost Analysis January 23, 2011 Brian Thornton P.E., PNNL brian.thornton@pnnl.gov Introduction Purpose: Discuss life cycle cost trade-offs for VRF with other HVAC systems Outline Life cycle
More information85 F 80 F 50% 75 F 70 F 73.0/61.8 45 F 10% Figure 1
Feb. 07 INTRODUCTION: Wrap around heat pipes are air-to-air heat exchangers that are installed in the airstream upstream and downstream of a cooling coil to deliberately reduce the Sensible Heat Ratio
More informationDual Maximum VAV Box Controls
ASHRAE Golden Gate Chapter November 13, 2014 Dual Maximum VAV Box Controls Steven T. Taylor, PE FASHRAE Taylor Engineering LLC staylor@taylor engineering.com Agenda VAV Box basics Sizing VAV Boxes How
More informationUNDERSTANDING AND USING THE HVAC DESIGN REVIEW FORM
Page 1 UNDERSTANDING AND USING THE HVAC DESIGN REVIEW FORM Each of the 38 points of requested information is discussed, and references to the supporting manual are given to substantiate the requirement.
More informationEngineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER
Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER SUMMARY A proper balance of temperature and humidity control is essential for efficient data center operation, and integral
More informationMoisture Control. It s The Dew Point. Stupid! Its not the humidity.
Moisture Control Its not the humidity. It s The Dew Point Stupid! Mike Schell EpiphanyTec Inc. Santa Barbara, CA mschell@epiphanytec.com 805 687-3175 Matching great technology to market need! Topics SHR
More informationMODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING
MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING V. Vakiloroaya*, J.G. Zhu, and Q.P. Ha School of Electrical, Mechanical and Mechatronic Systems,
More informationEconomic Evaluation of Residential Air Conditioner Designs for Hot and Dry Climates
Economic Evaluation of Residential Air Conditioner Designs for Hot and Dry Climates Arthur Rosenfeld, California Energy Commission Gregory Rosenquist, Lawrence Berkeley National Laboratory C. Keith Rice,
More informationGet the FACTS about SEER and Deliver Better Customer Value
What is SEER? SEER stands for Seasonal Energy Efficiency Ratio. It s a number that describes how well air-conditioning equipment works. A higher SEER means better efficiency and lower energy bills. SEER
More informationHeat Recovery In Retail Refrigeration
This article was published in ASHRAE Journal, February 2010. Copyright 2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not
More informationComponents HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis
Components HVAC General System Selection Life Cycle Cost Analysis Outdoor Air Design Values Indoor Air Design Values Outdoor Air Ventilation Welding Ventilation Temperature Control Systems Ductwork HVAC
More informationEnergy and Energy Cost Savings Analysis of the 2015 IECC for Commercial Buildings
PNNL-24269 Energy and Energy Cost Savings Analysis of the 2015 IECC for Commercial Buildings June 2015 J Zhang Y Xie R Athalye J Zhuge M Rosenberg R Hart B Liu PNNL-24269 Energy and Energy Cost Savings
More informationEvaporative Cooling for Residential and Light-Commercial
EMERGING TECHNOLOGIES This article was published in ASHRAE Journal, October 2011. Copyright 2011 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org.
More informationENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE
ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce
More informationIDEA Presentation SMALL CAMPUS CHILLED WATER PLANT OPTIMIZATION.
IDEA Presentation SMALL CAMPUS CHILLED WATER PLANT OPTIMIZATION. Pre-Project Details Hawaiian Community College Campus consisting of 16 individual buildings totaling 308,000 sq.ft of conditioned space.
More informationEnhanced Operations & Maintenance Procedures for Small Packaged Rooftop HVAC Systems
Enhanced Operations & Maintenance Procedures for Small Packaged Rooftop HVAC Systems Protocol Development, Field Review, and Measure Assessment Final Report April 2002 Prepared for: Eugene Water and Electric
More informationHIGH EFFICIENCY RTU. www.reznorhvac.com HIGH EFFICIENCY, PACKAGED SPACE CONDITIONING. DX System IEER> 13.2 Gas Heat Efficiency > 92% Capacities Tons
Capacities 10-25 Tons 100-400 MBH HIGH EFFICIENCY, PACKAGED SPACE CONDITIONING DX System IEER> 13.2 Gas Heat Efficiency > 92% HIGH EFFICIENCY RTU 30-120 kw 3,000-11,550 CFM Comfort Comfort is determined
More informationRole of Economizers in Dedicated Outdoor Air Systems
Introduction: Role of Economizers in Dedicated Outdoor Air Systems A question that frequently arises when a dedicated outdoor air system (DOAS) (Mumma, 2001) is discussed, particularly when the parallel
More informationLaboratory Test Report for Fujitsu 12RLS and Mitsubishi FE12NA Mini-Split Heat Pumps
Laboratory Test Report for Fujitsu 12RLS and Mitsubishi FE12NA Mini-Split Heat Pumps Jon Winkler, Ph.D. September 2011 NOTICE This report was prepared as an account of work sponsored by an agency of the
More informationEnergy Recovery Ventilation Equipment
AHRI Standard 1060 (I-P) 2013 Standard for Performance Rating of Airto-Air Exchangers for Energy Recovery Ventilation Equipment IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not
More informationCRITICAL COOLING FOR DATA CENTERS
IDEA 100 th Annual Conference & Trade Show CRITICAL COOLING FOR DATA CENTERS Presented by Ron Johanning, PE, LEED AP Mission Critical Market Leader Agenda EPA Report Data Center Energy Trends IT Best Practice
More informationHVAC Systems in Schools & Commercial Buildings and Radon
HVAC Systems in Schools & Commercial Buildings and Radon References US EPA Radon Prevention in the Design and Construction of Schools and Other Large Buildings http://www.epa.gov/ordntrnt/ord/nrmrl/pubs/1993/air/
More informationEngineers Newsletter. Understanding Single-Zone VAV Systems. providing insights for today s hvac system designer. volume 42 2
providing insights for today s hvac system designer Engineers Newsletter volume 42 2 Understanding Single-Zone VAV Systems Single-zone variable-air-volume (VAV) is not a new concept, but due to new energy
More informationfor K-12 School Buildings
Advanced Energy Design Guide for K-12 School Buildings HVAC Section John Murphy Applications Engineer, LEED AP Trane La Crosse, Wisconsin jmurphy@trane.com www.trane.com AEDG-K12 HVAC Subcommittee John
More informationStrategy Guideline: HVAC Equipment Sizing
Strategy Guideline: HVAC Equipment Sizing Arlan Burdick IBACOS, Inc. February 2012 This report received minimal editorial review at NREL NOTICE This report was prepared as an account of work sponsored
More informationMULTIZONE APPLICATION OF SOLUTION UNITS
MULTIZONE APPLICATION OF SOLUTION UNITS APPLICATION GUIDE Supersedes: 102.20-AG12 (206) Form: 102.20-AG12 (307) GENERAL Multi-zone heating and air conditioning units offer design and application advantages
More informationDedicated Outdoor Air-Dual Wheel System Control Requirements
4428 Dedicated Outdoor Air-Dual Wheel System Control Requirements Stanley A. Mumma, Ph.D., P.E. Fellow ASHRAE ABSTRACT The central thrust of this paper is to develop a clear understanding of the performance
More informationDehumidification Design
Dehumidification Design Using Data-Center Heat Utilizing free heat from a server room was the concept behind an air-handling system in a college-campus building Considerable energy savings are possible
More informationApplying Schedules and Profiles in HAP
This HAP e-help discusses the importance of properly applying schedules and profiles in HAP. We will also discuss potential misapplications of these user inputs. First, we need to understand the differences
More informationSample - Existing Building Commissioning Plan
Sample - Existing Building Commissioning Plan Version: Draft for Review Final Approved: Owner Site Address: Primary Site Contact Name and Telephone Number: Date Building Description The site consists of
More informationCURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers
CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building
More informationEnclosed Football Stadium Design History and Lessons Learned
Enclosed Football Stadium Design History and Lessons Learned Robert L. Towell, P.E., LEED AP, QCxP btowell@cxegroup.com CxE Group LLC St. Louis, Missouri 314-436-6543 With thanks to the St. Louis Convention
More informationLawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory
Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory Title: Comparison of energy efficiency between variable refrigerant flow systems and ground source heat pump systems Author:
More informationAdvanced Automated HVAC Fault Detection and Diagnostics Commercialization Program. Project 4: Advanced Rooftop Unit. ARTU Cost Benefit Analysis
Advanced Automated HVAC Fault Detection and Diagnostics Commercialization Program California Energy Commission Contract # 500-03-030 Project 4: Advanced Rooftop Unit Deliverable D4.3d DRAFT 3 ARTU Cost
More informationTwo-Stage High Efficiency Air Conditioners: Laboratory Ratings vs. Residential Installation Performance
Two-Stage High Efficiency Air Conditioners: Laboratory Ratings vs. Residential Installation Performance John Proctor and Gabriel Cohn, Proctor Engineering Group, Ltd. ABSTRACT The increased installation
More informationHeating, Ventilation & Air Conditioning Equipment
FinAnswer Express Wyoming Incentive Catalog Effective as of October 1, 2011 Heating, Ventilation & Air Conditioning Equipment Rocky Mountain Power provides incentives for many types of energy efficient
More informationCHAPTER 5 Energy Efficient HVAC Design
CHAPTER 5 Energy 5.1 Guideline 5.2 Mandatory clause 5.3 Technical notes #$$% #$$% #$$& ( ) +, (./ 5.3.1 on optimization of cooling load estimation %0 Table 5.3.1: Inside design conditions for airconditioned
More informationTODAY S PARADIGM FOR HEAT RECOVERY - PART 2
TODAY S PARADIGM FOR HEAT RECOVERY - PART 2 Tom Brooke PE, MBA, CEM ASHRAE Member July 14, 2012 INTRODUCTION Part 1 of this webinar by the same name and conducted by Engineered Systems magazine was held
More informationThe Sun Devil in the Details: Lessons Learned from Residential HVAC Programs in the Desert Southwest
Kevin Cooney Marshall Keneipp Justin Spencer Chris Newton Navigant Consulting, Inc. Boulder, CO Presented at the International Energy Program Evaluation Conference Paris, France June 9 & 10, 2010 The Sun
More informationFundamentals of HVAC Control Systems
ASHRAE Hong Kong Chapter Technical Workshop Fundamentals of HVAC Control Systems 18, 19, 25, 26 April 2007 2007 ASHRAE Hong Kong Chapter Slide 1 Chapter 5 Control Diagrams and Sequences 2007 ASHRAE Hong
More informationArizona State University. Understanding the Impact of Urban Heat Island in Phoenix
Understanding the Impact of Urban Heat Island in Phoenix ( ) Summer Night-time 'min-low' temperatures and its impact on the energy consumption of various building typologies Presented By: Sandeep Doddaballapur
More informationThe Development of a Frost-Less Heat Pump
The Development of a Frost-Less Heat Pump V. C. Mei, R. E. Domitrovic, and F. C. Chen, Oak Ridge National Laboratory J. K. Kilpatrick, Tennessee Valley Authority ABSTRACT There are two major concerns associated
More informationRaising the Bar: A Comparison Study of Iowa s Current and Proposed Energy Code
Raising the Bar: A Comparison Study of Iowa s Current and Proposed Energy Code Julia Gauthier, LEED AP BD+C Jeanne Huntsman, AIA, LEED Green Associate The Weidt Group Raising the Bar Special statements
More informationCase Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program
More information