1 IDEA 100 th Annual Conference & Trade Show CRITICAL COOLING FOR DATA CENTERS Presented by Ron Johanning, PE, LEED AP Mission Critical Market Leader

2 Agenda EPA Report Data Center Energy Trends IT Best Practice Recommendations ASHRAE Environmental Operating Changes HVAC System Optimization Techniques Air Side Economization Water Side Economization Combined Heat & Power

3 Projected Energy Use Trends Source: Report to Congress on Server and Data Center Efficiency Public Law

4 Power Consumption Power Consumption: 100 W System Load Total 275W Load 100W Room cooling system 70W UPS +PDU 20W Server fans 15W PSU 50W VR 20W Source: Intel Corporation

5 Energy System Flow 205W UPS PDU 185W IT 16W 4 W 185 W 275 W 70W Chiller 205W Cooling Coil HEAT

6 Best Practice IT Revisions Turn off unused servers Avg. $400/year/server Virtualize computer applications onto a common server Turn on energy management software, allow processor speed to ramp down when not needed ~ $80 - $120/yr/server

7 Best Practices HVAC Revisions Optimize air flow CFD analysis Improve air flow management hot air containment Variable speed chillers/fans/pumps Optimize cooling systems Environmental set point revisions

8 Typical Data Center HVAC Layout

9 Rear Hot Air Containment

10 Total Hot Air Containment Systems Containment Concept Neutralizes hot air by preventing exhaust air from mixing with cool air Neutralized ambienttemperature air returns to room Equipment racks take in ambient air from front All hot exhaust air is captured within chamber and neutralized

11 Energy Economization Techniques Air side economizers Water side economizers Adiabatic humidified/cooling air side economizers Absorption cooling

12 Class 1 & 2 Recommended Operating Environment (2008) (2004) Temp: 18 C (64.4 F) 20 C (68 F) 27 C (80.6 F) 25 C (77 F) Humidity: 5.5 C (41.9 F) DP 40% RH 59% RH, 15 C 55% RH (59 F) DP New Class 1&2 Allowable Range

13 Air Side Economizers Takes advantage of wider ASHRAE operating ranges Bring in outside air to central AHU to provide cool air to equipment reducing use of mechanical cooling Applicable where geographical and climate conditions allow

14 Region IIA 100% Outside Air Partial Refrigerator Dehumidification Region IV Min. Outside Air Refrigeration (Sensible & Latent Cooling) Region IA Modulating Outside Air Dehumidification Region I Modulate Outside Air No Refrigeration Region II 100% Outside Air Partial Refrigeration/ Humidification Region III Min. Outside Air Refrigeration & Humidification

15 Region IIA 100% Outside Air Partial Refrigerator Dehumidification Region IV Min. Outside Air Refrigeration (Sensible & Latent Cooling) Region IA Modulating Outside Air Dehumidification Region I Modulate Outside Air No Refrigeration Region II 100% Outside Air Partial Refrigeration/ Humidification Region III Min. Outside Air Refrigeration & Humidification

16 Air Side Economizer Hours Without Mechanical Cooling Los Angeles San Jose Denver Chicago Boston Atlanta Seattle Outdoor Air Dry Bulb Bin, o F ( o C) Supply Air Temp o F ( o C) 69 (21) 70 (21) 86% 80% 82% 80% 83% 65% 65% 63 ( 17) 64 ( 17) 59% 64% 72% 70% 71% 51% 51% 57 (14) 58 (14) 32% 39% 61% 62% 61% 41% 41% 51 (11) 52 (11) 6% 18% 51% 52% 50% 29% 29% ASHRAE BIN Data

17 Air Side Economizer Hours Without Mechanical Cooling Los Angeles San Jose Denver Chicago Boston Atlanta Seattle Outdoor Air Dry Bulb Bin, o F ( o C) Supply Air Temp o F ( o C) 69 (21) 70 (21) 86% 80% 82% 80% 83% 65% 65% 63 ( 17) 64 ( 17) 59% 64% 72% 70% 71% 51% 51% 57 (14) 58 (14) 32% 39% 61% 62% 61% 41% 41% 51 (11) 52 (11) 6% 18% 51% 52% 50% 29% 29% ASHRAE BIN Data

18 Water Side Economizers Uses cool outdoor dry-bulb or wet bulb conditions to generate condenser water that can partially or fully meet cooling needs Either direct or indirect free cooling

19 Water Side Economizer Hours Without Mechanical Cooling Los Angeles San Jose Denver Chicago Boston Atlanta Seattle Outdoor Air Dry Bulb Bin, o F ( o C) CWS o F ( o C) Supply Air Temp o F ( o C) 59 (15) 66 (19) 70 (21) 68% 78% 93% 75% 75% 66% 90% 53 (12) 60 (16) 64 ( 17) 36% 46% 77% 64% 63% 44% 68% 47 (8) 54 (12) 58 (14) 13% 21% 63% 55% 52% 33% 45% 41 (5) 48 (9) 52 (11) 3% 6% 51% 46% 41% 22% 21% ASHRAE BIN Data

20 Water Side Economizer Hours Without Mechanical Cooling Los Angeles San Jose Denver Chicago Boston Atlanta Seattle Outdoor Air Dry Bulb Bin, o F ( o C) CWS o F ( o C) Supply Air Temp o F ( o C) 59 (15) 66 (19) 70 (21) 68% 78% 93% 75% 75% 66% 90% 53 (12) 60 (16) 64 ( 17) 36% 46% 77% 64% 63% 44% 68% 47 (8) 54 (12) 58 (14) 13% 21% 63% 55% 52% 33% 45% 41 (5) 48 (9) 52 (11) 3% 6% 51% 46% 41% 22% 21% ASHRAE BIN Data

21 Adiabatic Humidified/Cooled Air Side Economizer Hours Without Mechanical Cooling Los Angeles San Jose Denver Chicago Boston Atlanta Seattle Outdoor Air Dry Bulb Bin, o F ( o C) Supply Air Temp o F ( o C) 69 (21) 70 (21) 99% 100% 100% 93% 95% 82% 100% 63 (17) 64 ( 17) 87% 93% 99% 83% 85% 65% 98% 57 (14) 58 (14) 53% 70% 89% 71% 72% 51% 85% 51 (11) 52 (11) 23% 39% 73% 60% 60% 39% 62% ASHRAE BIN Data

22 Adiabatic Humidified/Cooled Air Side Economizer Hours Without Mechanical Cooling Los Angeles San Jose Denver Chicago Boston Atlanta Seattle Outdoor Air Dry Bulb Bin, o F ( o C) Supply Air Temp o F ( o C) 69 (21) 70 (21) 99% 100% 100% 93% 95% 82% 100% 63 (17) 64 ( 17) 87% 93% 99% 83% 85% 65% 98% 57 (14) 58 (14) 53% 70% 89% 71% 72% 51% 85% 51 (11) 52 (11) 23% 39% 73% 60% 60% 39% 62% ASHRAE BIN Data

23 CHP for Data Centers Electricity and Absorption Cooling Reduced energy costs Increased reliability Facility expansion Increased energy efficiency Emissions benefits

24 Reduced Energy Costs CHP System Capacity KW Heat Rate BTU/k Wh Capital Costs O&M costs Annual Gas Cost Annual Avoided Electricity Savings Payback in years Microturbine / Chiller Pkg Gas Turbine Chiller ,300 $817,600 $36,617 $178,507 $354, ,364 13,930 $7,778,200 $615,895 $2,924,767 $5,153, Based on gas prices of $7.50MMBtu and electricity prices of $0.13kWh, reflective of California and Northeast energy costs

25 Increased Reliability Distributed Generation (DG) systems typically support the need for grid power beyond UPS and batteries Systems always running eliminates failure to start during grid power outage Continuous operation reduces battery backup time for UPS systems Continuous operation DG can smooth out voltage sags and power quality disturbances

26 System Availability Availability factor is important component Reciprocating engines ~ 96-98% Gas turbines ~ % Fuel cells ~? But combined with grid sources can reach % availability

27 Facility Expansion Grid capacity may limit data center expansion Small scale CHP may allow for flexibility to create multiple power and cooling sources Minimize additional utility infrastructure

28 Emissions Benefits Combined Heat and Power Central Power Capacity, kw Heat Rate, Btu/kWh Microturbine / Chiller Pkg Gas Turbine / Chiller U.S Fossil Fuel Power Average* CHP Emissions Factors ( for generated electricity minus avoided air conditioning emissions) NO x lb. MWh NA SO 2 lb. MWh NA CO 2 lb. MWh NA Annual Emissions (Based on 8760 hours) NO x lb./ MW-year 2, ,725 SO 2 lb / MW-year ,501 CO 2 lb / MW-year 4,103 4,103 6,899 * Based on 2000 egrid emission data

29 Recommendations Reduce IT load turn off unused equipment Make existing distribution more efficient Change the environmental conditions Optimize the cooling systems Look at CHP for redundant and efficient power and cooling capacity

30 Questions

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building

More information

Legacy Data Centres Upgrading the cooling capabilities What are the options?

Legacy Data Centres Upgrading the cooling capabilities What are the options? Legacy Data Centres Upgrading the cooling capabilities What are the options? Presentation Structure What is a Legacy Data Centre? What is CRAC cooling? ASHRAE Standards Overview Available Cooling Systems

More information

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates

More information

Maximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages

Maximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages Objectives Increase awareness of the types of economizers currently used for data centers Provide designers/owners with an overview of the benefits and challenges associated with each type Outline some

More information

85 F 80 F 50% 75 F 70 F 73.0/61.8 45 F 10% Figure 1

85 F 80 F 50% 75 F 70 F 73.0/61.8 45 F 10% Figure 1 Feb. 07 INTRODUCTION: Wrap around heat pipes are air-to-air heat exchangers that are installed in the airstream upstream and downstream of a cooling coil to deliberately reduce the Sensible Heat Ratio

More information

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com

More information

The Effect of Data Centre Environment on IT Reliability & Energy Consumption

The Effect of Data Centre Environment on IT Reliability & Energy Consumption The Effect of Data Centre Environment on IT Reliability & Energy Consumption Steve Strutt EMEA Technical Work Group Member IBM The Green Grid EMEA Technical Forum 2011 Agenda History of IT environmental

More information

Tim Facius Baltimore Aircoil

Tim Facius Baltimore Aircoil Presented By: Tim Facius Baltimore Aircoil Slide No.: 1 CTI Mission Statement To advocate and promote the use of environmentally responsible Evaporative Heat Transfer Systems (EHTS) for the benefit of

More information

Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions

Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the

More information

Analysis of data centre cooling energy efficiency

Analysis of data centre cooling energy efficiency Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe

More information

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program

More information

Benefits of Water-Cooled Systems vs. Air-Cooled Systems for Air-Conditioning Applications

Benefits of Water-Cooled Systems vs. Air-Cooled Systems for Air-Conditioning Applications Benefits of Water-Cooled Systems vs. Air-Cooled Systems for Air-Conditioning Applications Kavita A. Vallabhaneni U. S. Government commitment to reduce greenhouse gas emissions can have a significant impact

More information

Guide to Minimizing Compressor-based Cooling in Data Centers

Guide to Minimizing Compressor-based Cooling in Data Centers Guide to Minimizing Compressor-based Cooling in Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By: Lawrence Berkeley National Laboratory Author: William Tschudi

More information

By Tom Brooke PE, CEM

By Tom Brooke PE, CEM Air conditioning applications can be broadly categorized as either standard or critical. The former, often called comfort cooling, traditionally just controlled to maintain a zone setpoint dry bulb temperature

More information

Trends in Data Center Design ASHRAE Leads the Way to Large Energy Savings

Trends in Data Center Design ASHRAE Leads the Way to Large Energy Savings Trends in Data Center Design ASHRAE Leads the Way to Large Energy Savings ASHRAE Conference, Denver Otto Van Geet, PE June 24, 2014 NREL/PR-6A40-58902 NREL is a national laboratory of the U.S. Department

More information

DATA CENTRE DESIGN AND

DATA CENTRE DESIGN AND SPUSC 2008 SOUTH PACIFIC USER SERVICES CONFERENCE DATA CENTRE DESIGN AND ENERGY INITIATIVES Presented by Jarrad Clift Electrical Engineer Greenstar Accredited Presentation Content Data Centres General

More information

Specialty Environment Design Mission Critical Facilities

Specialty Environment Design Mission Critical Facilities Brian M. Medina PE Associate Brett M. Griffin PE, LEED AP Vice President Environmental Systems Design, Inc. Mission Critical Facilities Specialty Environment Design Mission Critical Facilities March 25,

More information

How to Save Over 60% on Cooling Energy Needed by a Data Center? The Roadmap from Traditional to Optimized Cooling

How to Save Over 60% on Cooling Energy Needed by a Data Center? The Roadmap from Traditional to Optimized Cooling How to Save Over 60% on Cooling Energy Needed by a Data Center? The Roadmap from Traditional to Optimized Cooling Abstract Data center managers are increasingly in search of methods and technologies for

More information

How to Build a Data Centre Cooling Budget. Ian Cathcart

How to Build a Data Centre Cooling Budget. Ian Cathcart How to Build a Data Centre Cooling Budget Ian Cathcart Chatsworth Products Topics We ll Cover Availability objectives Space and Load planning Equipment and design options Using CFD to evaluate options

More information

Dharam V. Punwani President, Avalon Consulting, Inc. Presented at Turbine Inlet Cooling Association Webinar April 9, 2014

Dharam V. Punwani President, Avalon Consulting, Inc. Presented at Turbine Inlet Cooling Association Webinar April 9, 2014 Dharam V. Punwani President, Avalon Consulting, Inc. Presented at Turbine Inlet Cooling Association Webinar April 9, 2014 Background: What is the problem that needs a solution? What is Turbine Inlet Cooling

More information

Self-benchmarking Guide for Data Center Infrastructure: Metrics, Benchmarks, Actions 6-28-10. Sponsored by:

Self-benchmarking Guide for Data Center Infrastructure: Metrics, Benchmarks, Actions 6-28-10. Sponsored by: Self-benchmarking Guide for Data Center Infrastructure: Metrics, Benchmarks, Actions 6-28-10 Sponsored by: Disclaimer This document was prepared as an account of work sponsored by the United States Government.

More information

Using Wet-Bulb Economizers. Data Center Cooling

Using Wet-Bulb Economizers. Data Center Cooling The following article was published in ASHRAE Journal, August 2008. Copyright 2008 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes

More information

Energy Efficient Cooling Solutions for Data Centers

Energy Efficient Cooling Solutions for Data Centers A White Paper from the Experts in Business-Critical Continuity TM Energy Efficient Cooling Solutions for Data Centers Introducing an Emerson Network Power tool for evaluating cooling system total cost

More information

Heat Recovery from Data Centres Conference Designing Energy Efficient Data Centres

Heat Recovery from Data Centres Conference Designing Energy Efficient Data Centres What factors determine the energy efficiency of a data centre? Where is the energy used? Local Climate Data Hall Temperatures Chiller / DX Energy Condenser / Dry Cooler / Cooling Tower Energy Pump Energy

More information

Data Center Heat Rejection

Data Center Heat Rejection This article was published in ASHRAE Journal, March 2011. Copyright 2011 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not be

More information

Improving Data Center Energy Efficiency Through Environmental Optimization

Improving Data Center Energy Efficiency Through Environmental Optimization Improving Data Center Energy Efficiency Through Environmental Optimization How Fine-Tuning Humidity, Airflows, and Temperature Dramatically Cuts Cooling Costs William Seeber Stephen Seeber Mid Atlantic

More information

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014 ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014 Explanation of the refrigeration cycle. Compressors. Benefits and operating characteristics. -Reciprocating

More information

The Role of Distributed Generation and Combined Heat and Power (CHP) Systems in Data Centers

The Role of Distributed Generation and Combined Heat and Power (CHP) Systems in Data Centers The Role of Distributed Generation and Combined Heat and Power (CHP) Systems in Data Centers U. S. Environmental Protection Agency Combined Heat and Power Partnership August 2007 Foreword The U.S. Environmental

More information

Data Center Combined Heat and Power (CHP): Benefits and Implementation

Data Center Combined Heat and Power (CHP): Benefits and Implementation Data Center Combined Heat and Power (CHP): Benefits and Implementation by Sam Brewer Justin Grau Page 1 of 14 I. Common Causes of Failure Major trends in the United States have reached an intersection

More information

How To Evaluate Cogeneration

How To Evaluate Cogeneration Power topic #7018 Technical information from Cummins Power Generation Inc. Evaluating cogeneration for your facility: A look at the potential energy-efficiency, economic and environmental benefits > White

More information

Energy Efficient Server Room and Data Centre Cooling. Computer Room Evaporative Cooler. EcoCooling

Energy Efficient Server Room and Data Centre Cooling. Computer Room Evaporative Cooler. EcoCooling Energy Efficient Server Room and Data Centre Cooling Computer Room Evaporative Cooler EcoCooling EcoCooling CREC Computer Room Evaporative Cooler Reduce your cooling costs by over 90% Did you know? An

More information

APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application

APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application APPLICATION GUIDE Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application Section Comparison of Latent Cooling Performance of Introduction Most commercial HVAC systems

More information

Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER

Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER SUMMARY A proper balance of temperature and humidity control is essential for efficient data center operation, and integral

More information

Defining Quality. Building Comfort. Precision. Air Conditioning

Defining Quality. Building Comfort. Precision. Air Conditioning Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air

More information

Green Data Center: Energy Reduction Strategies

Green Data Center: Energy Reduction Strategies Federal Energy ManagEment Program Green Data Center: Energy Reduction Strategies Airside Economization and Unique Indirect Evaporative Cooling Executive summary The Green Data Center Project was a successful

More information

Thermal Energy Storage and LEED GOLD

Thermal Energy Storage and LEED GOLD Thermal Energy Storage and LEED GOLD Mark M. MacCracken, PE, LEED AP, Pte CALMAC Mfg. Corp. Englewood, NJ USA Calmac.com ECOSTOCK 5-31-06 Storage is Natural Most common TES System Water Heater (Electric)

More information

White Paper. Data Center Containment Cooling Strategies. Abstract WHITE PAPER EC9001. Geist Updated August 2010

White Paper. Data Center Containment Cooling Strategies. Abstract WHITE PAPER EC9001. Geist Updated August 2010 White Paper Data Center Containment Cooling Strategies WHITE PAPER EC9001 Geist Updated August 2010 Abstract Deployment of high density IT equipment into data center infrastructure is now a common occurrence

More information

Paul Oliver Sales Director. Paul Oliver, Airedale Tom Absalom, JCA

Paul Oliver Sales Director. Paul Oliver, Airedale Tom Absalom, JCA Paul Oliver Sales Director Paul Oliver, Airedale Tom Absalom, JCA Airedale an overview 25,000m 2 UK premier test centre 450 staff Global distribution A Modine company Modine centre of excellence Airedale

More information

How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems

How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems Paul Mathew, Ph.D., Staff Scientist Steve Greenberg, P.E., Energy Management Engineer

More information

Jeff Sloan, P.E., McKinstry Co. Wednesday, April 29

Jeff Sloan, P.E., McKinstry Co. Wednesday, April 29 AABC Commissioning Group AIA Provider Number 50111116 Exploring ASHRAE 90.4P, Energy Standard for Data Centers & Telecommunications CXENERGY1534 Jeff Sloan, P.E., McKinstry Co. Wednesday, April 29 Credit(s)

More information

Data Center Combined Heat and Power Benefits and Implementation. Justin Grau, Google Inc. Sam Brewer, GEM Energy

Data Center Combined Heat and Power Benefits and Implementation. Justin Grau, Google Inc. Sam Brewer, GEM Energy Data Center Combined Heat and Power Benefits and Implementation Justin Grau, Google Inc. Sam Brewer, GEM Energy Data Center Challenges Electric Load Densification Thermal Dissipation Requires constant

More information

Award-Winning Innovation in Data Center Cooling Design

Award-Winning Innovation in Data Center Cooling Design Award-Winning Innovation in Data Center Cooling Design Oracle s Utah Compute Facility O R A C L E W H I T E P A P E R D E C E M B E R 2 0 1 4 Table of Contents Introduction 1 Overview 2 Innovation in Energy

More information

Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint

Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint Energy usage in the data center Electricity Transformer/ UPS Air 10% Movement 12% Cooling 25% Lighting, etc. 3% IT Equipment

More information

Liebert EFC from 100 to 350 kw. The Highly Efficient Indirect Evaporative Freecooling Unit

Liebert EFC from 100 to 350 kw. The Highly Efficient Indirect Evaporative Freecooling Unit Liebert EFC from 100 to 350 kw The Highly Efficient Indirect Evaporative Freecooling Unit Liebert EFC, the Highly Efficient Indirect Evaporative Freecooling Solution Emerson Network Power delivers innovative

More information

NSIDC Data Center: Energy Reduction Strategies

NSIDC Data Center: Energy Reduction Strategies NSIDC Data Center: Energy Reduction Strategies Airside Economization and Unique Indirect Evaporative Cooling Executive summary The Green Data Center Project was a successful effort to significantly reduce

More information

Energy Efficient High-tech Buildings

Energy Efficient High-tech Buildings Energy Efficient High-tech Buildings Can anything be done to improve Data Center and Cleanroom energy efficiency? Bill Tschudi Lawrence Berkeley National Laboratory Wftschudi@lbl.gov Acknowledgements California

More information

Benefits. Air-Cooled Systems

Benefits. Air-Cooled Systems Benefits of Water-Cooled Systems vs Air-Cooled Systems for Air-Conditioning Applications Written by: Michael D.Pugh U.S. Government commitment to reduce greenhouse gas emissions can have a significant

More information

I-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 4, Lancaster University, 2 nd July 2014

I-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 4, Lancaster University, 2 nd July 2014 I-STUTE Project - WP2.3 Data Centre Cooling Project Review Meeting 4, Lancaster University, 2 nd July 2014 Background Data centres estimated to use 2-3% of total electricity consumption in the UK and generate

More information

Moisture Control. It s The Dew Point. Stupid! Its not the humidity.

Moisture Control. It s The Dew Point. Stupid! Its not the humidity. Moisture Control Its not the humidity. It s The Dew Point Stupid! Mike Schell EpiphanyTec Inc. Santa Barbara, CA mschell@epiphanytec.com 805 687-3175 Matching great technology to market need! Topics SHR

More information

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory

More information

THE PSYCHROMETRIC CHART: Theory and Application. Perry Peralta NC State University

THE PSYCHROMETRIC CHART: Theory and Application. Perry Peralta NC State University THE PSYCHROMETRIC CHART: Theory and Application Perry Peralta NC State University PSYCHROMETRIC CHART Identify parts of the chart Determine moist air properties Use chart to analyze processes involving

More information

GLOBACON 05 HVAC Systems for Cogen

GLOBACON 05 HVAC Systems for Cogen GLOBACON 05 HVAC Systems for Cogen Track 2, Session 2B Advanced HVAC and Building Systems Date: March 24th, 2005 Gearoid Foley President Integrated CHP Systems Corp. Integrated CHP Systems Corp. Electricity

More information

AIRAH Presentation April 30 th 2014

AIRAH Presentation April 30 th 2014 Data Centre Cooling Strategies The Changing Landscape.. AIRAH Presentation April 30 th 2014 More Connections. More Devices. High Expectations 2 State of the Data Center, Emerson Network Power Redefining

More information

Advanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings

Advanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings Advanced Energy Design Guide LEED Strategies for Schools and High Performance Buildings Today s Presenters Stephen Koontz, LEED AP Energy Services Leader Tampa Bay Trane Allen Irvine General Sales Manager

More information

CHP Strategies and Options / Stored Energy. 2014 ENERGY SYMPOSIUM April8, 2014 Reading Country Club

CHP Strategies and Options / Stored Energy. 2014 ENERGY SYMPOSIUM April8, 2014 Reading Country Club CHP Strategies and Options / Stored Energy Jim Freihaut, Ph.D. Director, DOE Mid Atlantic CHP Technical Assistance Partnership Director, Indoor Aerosol Laboratory Professor, Architectural Engineering 104

More information

Optimization of Water - Cooled Chiller Cooling Tower Combinations

Optimization of Water - Cooled Chiller Cooling Tower Combinations Optimization of Water - Cooled Chiller Cooling Tower Combinations by: James W. Furlong & Frank T. Morrison Baltimore Aircoil Company The warm water leaving the chilled water coils is pumped to the evaporator

More information

Greening Data Centers

Greening Data Centers Greening Data Centers Dallas Thornton SDSC Division Director, Cyberinfrastructure Services March 2, 2011 Data Centers Are Enormous Users of Power US Data Centers (TeraWatt Hours per Year) 125 US Televisions

More information

THE OPTIMAL SOLUTION FOR SMALL AND MEDIUM DATA CENTER

THE OPTIMAL SOLUTION FOR SMALL AND MEDIUM DATA CENTER Your Complete Turnkey Server Room Air Condition UPS THE OPTIMAL SOLUTION FOR SMALL AND MEDIUM DATA CENTER AVAILABLE IN WATER AND GAS SYSTEM MODEL AIR-CONDITIONED CABINET EXCELLENT TEMPERATURE CONTROL FOR

More information

3/29/2012 INTRODUCTION HVAC BASICS

3/29/2012 INTRODUCTION HVAC BASICS INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O HVAC systems or Heating, Ventilating and Air-Conditioning systems control the environment for people and equipment in our facilities.

More information

Recommendation For Incorporating Data Center Specific Sustainability Best Practices into EO13514 Implementation

Recommendation For Incorporating Data Center Specific Sustainability Best Practices into EO13514 Implementation Recommendation For Incorporating Data Center Specific Sustainability Best Practices into EO13514 Implementation Version 1.0 - November, 2011 Incorporating Data Center-Specific Sustainability Measures into

More information

Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001

Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue

More information

GEOTHERMAL HEAT PUMP SYSTEMS ARE RED HOT BUT ARE THEY REALLY GREEN?

GEOTHERMAL HEAT PUMP SYSTEMS ARE RED HOT BUT ARE THEY REALLY GREEN? GEOTHERMAL HEAT PUMP SYSTEMS ARE RED HOT BUT ARE THEY REALLY GREEN? Richard C. Niess 1 Gilbert & Associates / Apogee Interactive, Inc., Gloucester Point, Virginia 23062 Phone & Fax (804) 642 0400 ABSTRACT

More information

Data Center Leadership In the DOE Better Buildings Challenge

Data Center Leadership In the DOE Better Buildings Challenge Symposium Southern California February 18th, 2015 Data Center Leadership In the DOE Better Buildings Challenge Applying Best Practices to meet the Challenge Dale Sartor, PE Lawrence Berkeley National Laboratory

More information

Heat Recovery In Retail Refrigeration

Heat Recovery In Retail Refrigeration This article was published in ASHRAE Journal, February 2010. Copyright 2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not

More information

How To Design A Building In New Delhi

How To Design A Building In New Delhi ENERGY EFFICIENT HVAC DESIGN FOR COMPOSITE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce energy consumption

More information

ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE

ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce

More information

Five Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency

Five Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency Five Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Executive Summary As electricity prices and IT

More information

By Donald Fisher, P.Eng., Associate Member ASHRAE

By Donald Fisher, P.Eng., Associate Member ASHRAE By Donald Fisher, P.Eng., Associate Member ASHRAE Decisions to purchase a commercial kitchen ventilation (CKV) system often are based on rule-of-thumb estimates using a $/cfm index (i.e., annual energy

More information

Source: EIA Natural Gas Issues and Trends 1998

Source: EIA Natural Gas Issues and Trends 1998 7.0 System Redesign Analysis 7.1 Emissions Natural gas is a clean burning fossil fuel. It consists of a mixture of hydrocarbon gases, primarily Methane (CH 4 ). In analyzing the combustion process, it

More information

Zero Refrigeration for Data Centres in the USA

Zero Refrigeration for Data Centres in the USA Zero Refrigeration for Data Centres in the USA Robert Tozer PhD CEng MASHRAE Sophia Flucker CEng ABSTRACT Data centre energy consumption has grown significantly in recent years; cooling energy forms a

More information

Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers

Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers A White Paper from the Experts in Business-Critical Continuity TM Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers Executive Summary The strategic business importance

More information

Optimizing the Efficiency of the NCAR-Wyoming Supercomputing Center Facility. Ademola Olarinde Mentor: Aaron Andersen

Optimizing the Efficiency of the NCAR-Wyoming Supercomputing Center Facility. Ademola Olarinde Mentor: Aaron Andersen Optimizing the Efficiency of the NCAR-Wyoming Supercomputing Center Facility Ademola Olarinde Mentor: Aaron Andersen August 2, 2013 1 Education: Mechanical Engineering Grad Student Texas A&M University

More information

Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures

Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures Data Realty Colocation Data Center Ignition Park, South Bend, IN Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures Project Overview Data Realty is a data center service provider for middle

More information

CHP - The Business Case

CHP - The Business Case CHP - The Business Case An Introduction to Combined Heat and Power CHP 100 1 Acknowledgements 2 Overview! When Does CHP Make Sense! Where is CHP Practical?! Problems in CHP Economic Analysis 3 When Does

More information

Data Center Energy Efficiency. SC07 Birds of a Feather November, 2007 Bill Tschudi wftschudi@lbl.gov

Data Center Energy Efficiency. SC07 Birds of a Feather November, 2007 Bill Tschudi wftschudi@lbl.gov Data Center Energy Efficiency SC07 Birds of a Feather November, 2007 Bill Tschudi wftschudi@lbl.gov Benchmark results helped to find best practices The ratio of IT equipment power to the total (or its

More information

Recommendations for Measuring and Reporting Overall Data Center Efficiency

Recommendations for Measuring and Reporting Overall Data Center Efficiency Recommendations for Measuring and Reporting Overall Data Center Efficiency Version 1 Measuring PUE at Dedicated Data Centers 15 July 2010 Table of Contents 1 Introduction... 1 1.1 Purpose Recommendations

More information

Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory

Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory Title: Energy Implications of Economizer Use in California Data Centers Author: Shehabi, Arman Publication Date: 09-23-8 Permalink:

More information

Overview of Green Energy Strategies and Techniques for Modern Data Centers

Overview of Green Energy Strategies and Techniques for Modern Data Centers Overview of Green Energy Strategies and Techniques for Modern Data Centers Introduction Data centers ensure the operation of critical business IT equipment including servers, networking and storage devices.

More information

ASHRAE Rocky Mountain Chapter. RickPhillips Phillips, P.E., PE LEED AP Senior Mechanical Engineer The RMH Group, Inc.

ASHRAE Rocky Mountain Chapter. RickPhillips Phillips, P.E., PE LEED AP Senior Mechanical Engineer The RMH Group, Inc. ASHRAE Rocky Mountain Chapter Evaporative Cooling RickPhillips Phillips, P.E., PE LEED AP Senior Mechanical Engineer The RMH Group, Inc. April 19, 2013 1 Fundamentals Dry Bulb Temperature Wet Bulb Temperature

More information

Electrical Systems. <Presenter>

Electrical Systems. <Presenter> Review Root Causes of Energy Inefficiency Roadmap to Maximize Energy Efficiency Best Practices Alternative Energy Sources Controls Take Aways Seek Professional Help. ENERGY INEFFICIENCY OF

More information

Environmental Data Center Management and Monitoring

Environmental Data Center Management and Monitoring 2013 Raritan Inc. Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor

More information

Rittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy

Rittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy Rittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy Executive Summary Data center owners and operators are in constant pursuit of methods

More information

Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers

Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers Prepared for the U.S. Department of Energy s Federal Energy Management Program Prepared By Lawrence Berkeley National

More information

Causes of High Relative Humidity Inside Air Conditioned Buildings. Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates

Causes of High Relative Humidity Inside Air Conditioned Buildings. Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates Causes of High Relative Humidity Inside Air Conditioned Buildings Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates S. FLORIDA AVE. AMBIENT 91 F db / 78 F wb 16,000 HOURS ANNUALLY THAT wb

More information

Enabling an agile Data Centre in a (Fr)agile market

Enabling an agile Data Centre in a (Fr)agile market Enabling an agile Data Centre in a (Fr)agile market Phil Dodsworth Director, Data Centre Solutions 2008 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without

More information

CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS

CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS Air / Water / DX Cooled Cabinet Solutions Mini Data Centre All in One Solution: Where there is a requirement for standalone computing and communications, or highly

More information

How To Test A Theory Of Power Supply

How To Test A Theory Of Power Supply A CASE STUDY ON: THE EFFECTS OF HIGHER OPERATING TEMPERATURES ON DATA CENTER EFFICIENCY Victor Garcia Director of Facilities Brocade October 24, 2012 Jeff Stein, PE Principal Taylor Engineering 2010 Brocade

More information

Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics

Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics A Presentation of Work in Progress 4 October 2006 in the Intelligent

More information

Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc.

Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc. Business Management Magazine Winter 2008 Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc. Contrary to some beliefs, air is quite

More information

Wet Bulb Temperature and Its Impact on Building Performance

Wet Bulb Temperature and Its Impact on Building Performance Wet Bulb Temperature and Its Impact on Building Performance By: Kurmit Rockwell, PE, CEM, LEED AP and Justin Lee, PE, LEED, AP BD+C Energy Solution Services, AtSite, Inc. 1 What is Wet Bulb Temperature?

More information

Data Centre Cooling Air Performance Metrics

Data Centre Cooling Air Performance Metrics Data Centre Cooling Air Performance Metrics Sophia Flucker CEng MIMechE Ing Dr Robert Tozer MSc MBA PhD CEng MCIBSE MASHRAE Operational Intelligence Ltd. info@dc-oi.com Abstract Data centre energy consumption

More information

Fact Sheet (Web Content): Improving Energy Efficiency for Server Rooms and Closets

Fact Sheet (Web Content): Improving Energy Efficiency for Server Rooms and Closets Fact Sheet (Web Content): Improving Energy Efficiency for Server Rooms and Closets September 2012 Table of Contents A) Simplest, No-Cost, or Very-Low-Cost Measures 1. Determine computational functions

More information

Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida

Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida Optimizing 100% Outside Air Systems with Heat Pipes Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida Introduction To meet increasingly rigorous building codes

More information

Distributed polygeneration: desiccant-based air handling units interacting with microcogeneration systems

Distributed polygeneration: desiccant-based air handling units interacting with microcogeneration systems Distributed polygeneration: desiccant-based air handling units interacting with microcogeneration systems G. Angrisani *,1, C. Roselli 1, M. Sasso 1 1 DING, Università degli Studi del Sannio, Piazza Roma

More information

UMass Medical School Power Plant Expansion Presentation for the Northeast Clean Heat and Power Initiative. March 24, 2015

UMass Medical School Power Plant Expansion Presentation for the Northeast Clean Heat and Power Initiative. March 24, 2015 UMass Medical School Power Plant Expansion Presentation for the Northeast Clean Heat and Power Initiative March 24, 2015 John Baker Associate Vice Chancellor, Facilities Management Joseph Collins Chief

More information

National Grid Your Partner in Energy Solutions

National Grid Your Partner in Energy Solutions National Grid Your Partner in Energy Solutions National Grid Webinar: Enhancing Reliability, Capacity and Capital Expenditure through Data Center Efficiency April 8, 2014 Presented by: Fran Boucher National

More information

FEAR Model - Review Cell Module Block

FEAR Model - Review Cell Module Block F.E.A.R. Returns: 5 Steps Toward Data Center Efficiency Today Objectives Benefits for ITS professionals Brief review of the FEAR data center Define data center efficiency Link efficiency to the FEAR data

More information

Recommendations for Measuring and Reporting Overall Data Center Efficiency

Recommendations for Measuring and Reporting Overall Data Center Efficiency Recommendations for Measuring and Reporting Overall Data Center Efficiency Version 2 Measuring PUE for Data Centers 17 May 2011 Table of Contents 1 Introduction... 1 1.1 Purpose Recommendations for Measuring

More information

Sustainability and Data Centers

Sustainability and Data Centers Sustainability and Data Centers Energy Efficiency and Beyond Tim Chadwick, President, Alfa Tech Jessica Kennedy, California Operations Director, Brightworks San Diego Sustainability and Data Centers Beyond

More information