CRITICAL COOLING FOR DATA CENTERS
|
|
- Miranda Williams
- 8 years ago
- Views:
Transcription
1 IDEA 100 th Annual Conference & Trade Show CRITICAL COOLING FOR DATA CENTERS Presented by Ron Johanning, PE, LEED AP Mission Critical Market Leader
2 Agenda EPA Report Data Center Energy Trends IT Best Practice Recommendations ASHRAE Environmental Operating Changes HVAC System Optimization Techniques Air Side Economization Water Side Economization Combined Heat & Power
3 Projected Energy Use Trends Source: Report to Congress on Server and Data Center Efficiency Public Law
4 Power Consumption Power Consumption: 100 W System Load Total 275W Load 100W Room cooling system 70W UPS +PDU 20W Server fans 15W PSU 50W VR 20W Source: Intel Corporation
5 Energy System Flow 205W UPS PDU 185W IT 16W 4 W 185 W 275 W 70W Chiller 205W Cooling Coil HEAT
6 Best Practice IT Revisions Turn off unused servers Avg. $400/year/server Virtualize computer applications onto a common server Turn on energy management software, allow processor speed to ramp down when not needed ~ $80 - $120/yr/server
7 Best Practices HVAC Revisions Optimize air flow CFD analysis Improve air flow management hot air containment Variable speed chillers/fans/pumps Optimize cooling systems Environmental set point revisions
8 Typical Data Center HVAC Layout
9 Rear Hot Air Containment
10 Total Hot Air Containment Systems Containment Concept Neutralizes hot air by preventing exhaust air from mixing with cool air Neutralized ambienttemperature air returns to room Equipment racks take in ambient air from front All hot exhaust air is captured within chamber and neutralized
11 Energy Economization Techniques Air side economizers Water side economizers Adiabatic humidified/cooling air side economizers Absorption cooling
12 Class 1 & 2 Recommended Operating Environment (2008) (2004) Temp: 18 C (64.4 F) 20 C (68 F) 27 C (80.6 F) 25 C (77 F) Humidity: 5.5 C (41.9 F) DP 40% RH 59% RH, 15 C 55% RH (59 F) DP New Class 1&2 Allowable Range
13 Air Side Economizers Takes advantage of wider ASHRAE operating ranges Bring in outside air to central AHU to provide cool air to equipment reducing use of mechanical cooling Applicable where geographical and climate conditions allow
14 Region IIA 100% Outside Air Partial Refrigerator Dehumidification Region IV Min. Outside Air Refrigeration (Sensible & Latent Cooling) Region IA Modulating Outside Air Dehumidification Region I Modulate Outside Air No Refrigeration Region II 100% Outside Air Partial Refrigeration/ Humidification Region III Min. Outside Air Refrigeration & Humidification
15 Region IIA 100% Outside Air Partial Refrigerator Dehumidification Region IV Min. Outside Air Refrigeration (Sensible & Latent Cooling) Region IA Modulating Outside Air Dehumidification Region I Modulate Outside Air No Refrigeration Region II 100% Outside Air Partial Refrigeration/ Humidification Region III Min. Outside Air Refrigeration & Humidification
16 Air Side Economizer Hours Without Mechanical Cooling Los Angeles San Jose Denver Chicago Boston Atlanta Seattle Outdoor Air Dry Bulb Bin, o F ( o C) Supply Air Temp o F ( o C) 69 (21) 70 (21) 86% 80% 82% 80% 83% 65% 65% 63 ( 17) 64 ( 17) 59% 64% 72% 70% 71% 51% 51% 57 (14) 58 (14) 32% 39% 61% 62% 61% 41% 41% 51 (11) 52 (11) 6% 18% 51% 52% 50% 29% 29% ASHRAE BIN Data
17 Air Side Economizer Hours Without Mechanical Cooling Los Angeles San Jose Denver Chicago Boston Atlanta Seattle Outdoor Air Dry Bulb Bin, o F ( o C) Supply Air Temp o F ( o C) 69 (21) 70 (21) 86% 80% 82% 80% 83% 65% 65% 63 ( 17) 64 ( 17) 59% 64% 72% 70% 71% 51% 51% 57 (14) 58 (14) 32% 39% 61% 62% 61% 41% 41% 51 (11) 52 (11) 6% 18% 51% 52% 50% 29% 29% ASHRAE BIN Data
18 Water Side Economizers Uses cool outdoor dry-bulb or wet bulb conditions to generate condenser water that can partially or fully meet cooling needs Either direct or indirect free cooling
19 Water Side Economizer Hours Without Mechanical Cooling Los Angeles San Jose Denver Chicago Boston Atlanta Seattle Outdoor Air Dry Bulb Bin, o F ( o C) CWS o F ( o C) Supply Air Temp o F ( o C) 59 (15) 66 (19) 70 (21) 68% 78% 93% 75% 75% 66% 90% 53 (12) 60 (16) 64 ( 17) 36% 46% 77% 64% 63% 44% 68% 47 (8) 54 (12) 58 (14) 13% 21% 63% 55% 52% 33% 45% 41 (5) 48 (9) 52 (11) 3% 6% 51% 46% 41% 22% 21% ASHRAE BIN Data
20 Water Side Economizer Hours Without Mechanical Cooling Los Angeles San Jose Denver Chicago Boston Atlanta Seattle Outdoor Air Dry Bulb Bin, o F ( o C) CWS o F ( o C) Supply Air Temp o F ( o C) 59 (15) 66 (19) 70 (21) 68% 78% 93% 75% 75% 66% 90% 53 (12) 60 (16) 64 ( 17) 36% 46% 77% 64% 63% 44% 68% 47 (8) 54 (12) 58 (14) 13% 21% 63% 55% 52% 33% 45% 41 (5) 48 (9) 52 (11) 3% 6% 51% 46% 41% 22% 21% ASHRAE BIN Data
21 Adiabatic Humidified/Cooled Air Side Economizer Hours Without Mechanical Cooling Los Angeles San Jose Denver Chicago Boston Atlanta Seattle Outdoor Air Dry Bulb Bin, o F ( o C) Supply Air Temp o F ( o C) 69 (21) 70 (21) 99% 100% 100% 93% 95% 82% 100% 63 (17) 64 ( 17) 87% 93% 99% 83% 85% 65% 98% 57 (14) 58 (14) 53% 70% 89% 71% 72% 51% 85% 51 (11) 52 (11) 23% 39% 73% 60% 60% 39% 62% ASHRAE BIN Data
22 Adiabatic Humidified/Cooled Air Side Economizer Hours Without Mechanical Cooling Los Angeles San Jose Denver Chicago Boston Atlanta Seattle Outdoor Air Dry Bulb Bin, o F ( o C) Supply Air Temp o F ( o C) 69 (21) 70 (21) 99% 100% 100% 93% 95% 82% 100% 63 (17) 64 ( 17) 87% 93% 99% 83% 85% 65% 98% 57 (14) 58 (14) 53% 70% 89% 71% 72% 51% 85% 51 (11) 52 (11) 23% 39% 73% 60% 60% 39% 62% ASHRAE BIN Data
23 CHP for Data Centers Electricity and Absorption Cooling Reduced energy costs Increased reliability Facility expansion Increased energy efficiency Emissions benefits
24 Reduced Energy Costs CHP System Capacity KW Heat Rate BTU/k Wh Capital Costs O&M costs Annual Gas Cost Annual Avoided Electricity Savings Payback in years Microturbine / Chiller Pkg Gas Turbine Chiller ,300 $817,600 $36,617 $178,507 $354, ,364 13,930 $7,778,200 $615,895 $2,924,767 $5,153, Based on gas prices of $7.50MMBtu and electricity prices of $0.13kWh, reflective of California and Northeast energy costs
25 Increased Reliability Distributed Generation (DG) systems typically support the need for grid power beyond UPS and batteries Systems always running eliminates failure to start during grid power outage Continuous operation reduces battery backup time for UPS systems Continuous operation DG can smooth out voltage sags and power quality disturbances
26 System Availability Availability factor is important component Reciprocating engines ~ 96-98% Gas turbines ~ % Fuel cells ~? But combined with grid sources can reach % availability
27 Facility Expansion Grid capacity may limit data center expansion Small scale CHP may allow for flexibility to create multiple power and cooling sources Minimize additional utility infrastructure
28 Emissions Benefits Combined Heat and Power Central Power Capacity, kw Heat Rate, Btu/kWh Microturbine / Chiller Pkg Gas Turbine / Chiller U.S Fossil Fuel Power Average* CHP Emissions Factors ( for generated electricity minus avoided air conditioning emissions) NO x lb. MWh NA SO 2 lb. MWh NA CO 2 lb. MWh NA Annual Emissions (Based on 8760 hours) NO x lb./ MW-year 2, ,725 SO 2 lb / MW-year ,501 CO 2 lb / MW-year 4,103 4,103 6,899 * Based on 2000 egrid emission data
29 Recommendations Reduce IT load turn off unused equipment Make existing distribution more efficient Change the environmental conditions Optimize the cooling systems Look at CHP for redundant and efficient power and cooling capacity
30 Questions
CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers
CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building
More informationLegacy Data Centres Upgrading the cooling capabilities What are the options?
Legacy Data Centres Upgrading the cooling capabilities What are the options? Presentation Structure What is a Legacy Data Centre? What is CRAC cooling? ASHRAE Standards Overview Available Cooling Systems
More informationDATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates
More informationMaximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages
Objectives Increase awareness of the types of economizers currently used for data centers Provide designers/owners with an overview of the benefits and challenges associated with each type Outline some
More information85 F 80 F 50% 75 F 70 F 73.0/61.8 45 F 10% Figure 1
Feb. 07 INTRODUCTION: Wrap around heat pipes are air-to-air heat exchangers that are installed in the airstream upstream and downstream of a cooling coil to deliberately reduce the Sensible Heat Ratio
More informationData Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling
Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com
More informationThe Effect of Data Centre Environment on IT Reliability & Energy Consumption
The Effect of Data Centre Environment on IT Reliability & Energy Consumption Steve Strutt EMEA Technical Work Group Member IBM The Green Grid EMEA Technical Forum 2011 Agenda History of IT environmental
More informationTim Facius Baltimore Aircoil
Presented By: Tim Facius Baltimore Aircoil Slide No.: 1 CTI Mission Statement To advocate and promote the use of environmentally responsible Evaporative Heat Transfer Systems (EHTS) for the benefit of
More informationFree Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions
Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the
More informationAnalysis of data centre cooling energy efficiency
Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe
More informationCase Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program
More informationBenefits of Water-Cooled Systems vs. Air-Cooled Systems for Air-Conditioning Applications
Benefits of Water-Cooled Systems vs. Air-Cooled Systems for Air-Conditioning Applications Kavita A. Vallabhaneni U. S. Government commitment to reduce greenhouse gas emissions can have a significant impact
More informationGuide to Minimizing Compressor-based Cooling in Data Centers
Guide to Minimizing Compressor-based Cooling in Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By: Lawrence Berkeley National Laboratory Author: William Tschudi
More informationBy Tom Brooke PE, CEM
Air conditioning applications can be broadly categorized as either standard or critical. The former, often called comfort cooling, traditionally just controlled to maintain a zone setpoint dry bulb temperature
More informationTrends in Data Center Design ASHRAE Leads the Way to Large Energy Savings
Trends in Data Center Design ASHRAE Leads the Way to Large Energy Savings ASHRAE Conference, Denver Otto Van Geet, PE June 24, 2014 NREL/PR-6A40-58902 NREL is a national laboratory of the U.S. Department
More informationDATA CENTRE DESIGN AND
SPUSC 2008 SOUTH PACIFIC USER SERVICES CONFERENCE DATA CENTRE DESIGN AND ENERGY INITIATIVES Presented by Jarrad Clift Electrical Engineer Greenstar Accredited Presentation Content Data Centres General
More informationSpecialty Environment Design Mission Critical Facilities
Brian M. Medina PE Associate Brett M. Griffin PE, LEED AP Vice President Environmental Systems Design, Inc. Mission Critical Facilities Specialty Environment Design Mission Critical Facilities March 25,
More informationHow to Save Over 60% on Cooling Energy Needed by a Data Center? The Roadmap from Traditional to Optimized Cooling
How to Save Over 60% on Cooling Energy Needed by a Data Center? The Roadmap from Traditional to Optimized Cooling Abstract Data center managers are increasingly in search of methods and technologies for
More informationHow to Build a Data Centre Cooling Budget. Ian Cathcart
How to Build a Data Centre Cooling Budget Ian Cathcart Chatsworth Products Topics We ll Cover Availability objectives Space and Load planning Equipment and design options Using CFD to evaluate options
More informationDharam V. Punwani President, Avalon Consulting, Inc. Presented at Turbine Inlet Cooling Association Webinar April 9, 2014
Dharam V. Punwani President, Avalon Consulting, Inc. Presented at Turbine Inlet Cooling Association Webinar April 9, 2014 Background: What is the problem that needs a solution? What is Turbine Inlet Cooling
More informationSelf-benchmarking Guide for Data Center Infrastructure: Metrics, Benchmarks, Actions 6-28-10. Sponsored by:
Self-benchmarking Guide for Data Center Infrastructure: Metrics, Benchmarks, Actions 6-28-10 Sponsored by: Disclaimer This document was prepared as an account of work sponsored by the United States Government.
More informationUsing Wet-Bulb Economizers. Data Center Cooling
The following article was published in ASHRAE Journal, August 2008. Copyright 2008 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes
More informationEnergy Efficient Cooling Solutions for Data Centers
A White Paper from the Experts in Business-Critical Continuity TM Energy Efficient Cooling Solutions for Data Centers Introducing an Emerson Network Power tool for evaluating cooling system total cost
More informationHeat Recovery from Data Centres Conference Designing Energy Efficient Data Centres
What factors determine the energy efficiency of a data centre? Where is the energy used? Local Climate Data Hall Temperatures Chiller / DX Energy Condenser / Dry Cooler / Cooling Tower Energy Pump Energy
More informationData Center Heat Rejection
This article was published in ASHRAE Journal, March 2011. Copyright 2011 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not be
More informationImproving Data Center Energy Efficiency Through Environmental Optimization
Improving Data Center Energy Efficiency Through Environmental Optimization How Fine-Tuning Humidity, Airflows, and Temperature Dramatically Cuts Cooling Costs William Seeber Stephen Seeber Mid Atlantic
More informationASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014
ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014 Explanation of the refrigeration cycle. Compressors. Benefits and operating characteristics. -Reciprocating
More informationThe Role of Distributed Generation and Combined Heat and Power (CHP) Systems in Data Centers
The Role of Distributed Generation and Combined Heat and Power (CHP) Systems in Data Centers U. S. Environmental Protection Agency Combined Heat and Power Partnership August 2007 Foreword The U.S. Environmental
More informationData Center Combined Heat and Power (CHP): Benefits and Implementation
Data Center Combined Heat and Power (CHP): Benefits and Implementation by Sam Brewer Justin Grau Page 1 of 14 I. Common Causes of Failure Major trends in the United States have reached an intersection
More informationHow To Evaluate Cogeneration
Power topic #7018 Technical information from Cummins Power Generation Inc. Evaluating cogeneration for your facility: A look at the potential energy-efficiency, economic and environmental benefits > White
More informationEnergy Efficient Server Room and Data Centre Cooling. Computer Room Evaporative Cooler. EcoCooling
Energy Efficient Server Room and Data Centre Cooling Computer Room Evaporative Cooler EcoCooling EcoCooling CREC Computer Room Evaporative Cooler Reduce your cooling costs by over 90% Did you know? An
More informationAPPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application
APPLICATION GUIDE Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application Section Comparison of Latent Cooling Performance of Introduction Most commercial HVAC systems
More informationEngineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER
Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER SUMMARY A proper balance of temperature and humidity control is essential for efficient data center operation, and integral
More informationDefining Quality. Building Comfort. Precision. Air Conditioning
Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air
More informationGreen Data Center: Energy Reduction Strategies
Federal Energy ManagEment Program Green Data Center: Energy Reduction Strategies Airside Economization and Unique Indirect Evaporative Cooling Executive summary The Green Data Center Project was a successful
More informationThermal Energy Storage and LEED GOLD
Thermal Energy Storage and LEED GOLD Mark M. MacCracken, PE, LEED AP, Pte CALMAC Mfg. Corp. Englewood, NJ USA Calmac.com ECOSTOCK 5-31-06 Storage is Natural Most common TES System Water Heater (Electric)
More informationWhite Paper. Data Center Containment Cooling Strategies. Abstract WHITE PAPER EC9001. Geist Updated August 2010
White Paper Data Center Containment Cooling Strategies WHITE PAPER EC9001 Geist Updated August 2010 Abstract Deployment of high density IT equipment into data center infrastructure is now a common occurrence
More informationPaul Oliver Sales Director. Paul Oliver, Airedale Tom Absalom, JCA
Paul Oliver Sales Director Paul Oliver, Airedale Tom Absalom, JCA Airedale an overview 25,000m 2 UK premier test centre 450 staff Global distribution A Modine company Modine centre of excellence Airedale
More informationHow Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems
How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems Paul Mathew, Ph.D., Staff Scientist Steve Greenberg, P.E., Energy Management Engineer
More informationJeff Sloan, P.E., McKinstry Co. Wednesday, April 29
AABC Commissioning Group AIA Provider Number 50111116 Exploring ASHRAE 90.4P, Energy Standard for Data Centers & Telecommunications CXENERGY1534 Jeff Sloan, P.E., McKinstry Co. Wednesday, April 29 Credit(s)
More informationData Center Combined Heat and Power Benefits and Implementation. Justin Grau, Google Inc. Sam Brewer, GEM Energy
Data Center Combined Heat and Power Benefits and Implementation Justin Grau, Google Inc. Sam Brewer, GEM Energy Data Center Challenges Electric Load Densification Thermal Dissipation Requires constant
More informationAward-Winning Innovation in Data Center Cooling Design
Award-Winning Innovation in Data Center Cooling Design Oracle s Utah Compute Facility O R A C L E W H I T E P A P E R D E C E M B E R 2 0 1 4 Table of Contents Introduction 1 Overview 2 Innovation in Energy
More informationMeasuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint
Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint Energy usage in the data center Electricity Transformer/ UPS Air 10% Movement 12% Cooling 25% Lighting, etc. 3% IT Equipment
More informationLiebert EFC from 100 to 350 kw. The Highly Efficient Indirect Evaporative Freecooling Unit
Liebert EFC from 100 to 350 kw The Highly Efficient Indirect Evaporative Freecooling Unit Liebert EFC, the Highly Efficient Indirect Evaporative Freecooling Solution Emerson Network Power delivers innovative
More informationNSIDC Data Center: Energy Reduction Strategies
NSIDC Data Center: Energy Reduction Strategies Airside Economization and Unique Indirect Evaporative Cooling Executive summary The Green Data Center Project was a successful effort to significantly reduce
More informationEnergy Efficient High-tech Buildings
Energy Efficient High-tech Buildings Can anything be done to improve Data Center and Cleanroom energy efficiency? Bill Tschudi Lawrence Berkeley National Laboratory Wftschudi@lbl.gov Acknowledgements California
More informationBenefits. Air-Cooled Systems
Benefits of Water-Cooled Systems vs Air-Cooled Systems for Air-Conditioning Applications Written by: Michael D.Pugh U.S. Government commitment to reduce greenhouse gas emissions can have a significant
More informationI-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 4, Lancaster University, 2 nd July 2014
I-STUTE Project - WP2.3 Data Centre Cooling Project Review Meeting 4, Lancaster University, 2 nd July 2014 Background Data centres estimated to use 2-3% of total electricity consumption in the UK and generate
More informationMoisture Control. It s The Dew Point. Stupid! Its not the humidity.
Moisture Control Its not the humidity. It s The Dew Point Stupid! Mike Schell EpiphanyTec Inc. Santa Barbara, CA mschell@epiphanytec.com 805 687-3175 Matching great technology to market need! Topics SHR
More informationEnergy Efficiency Opportunities in Federal High Performance Computing Data Centers
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory
More informationTHE PSYCHROMETRIC CHART: Theory and Application. Perry Peralta NC State University
THE PSYCHROMETRIC CHART: Theory and Application Perry Peralta NC State University PSYCHROMETRIC CHART Identify parts of the chart Determine moist air properties Use chart to analyze processes involving
More informationGLOBACON 05 HVAC Systems for Cogen
GLOBACON 05 HVAC Systems for Cogen Track 2, Session 2B Advanced HVAC and Building Systems Date: March 24th, 2005 Gearoid Foley President Integrated CHP Systems Corp. Integrated CHP Systems Corp. Electricity
More informationAIRAH Presentation April 30 th 2014
Data Centre Cooling Strategies The Changing Landscape.. AIRAH Presentation April 30 th 2014 More Connections. More Devices. High Expectations 2 State of the Data Center, Emerson Network Power Redefining
More informationAdvanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings
Advanced Energy Design Guide LEED Strategies for Schools and High Performance Buildings Today s Presenters Stephen Koontz, LEED AP Energy Services Leader Tampa Bay Trane Allen Irvine General Sales Manager
More informationCHP Strategies and Options / Stored Energy. 2014 ENERGY SYMPOSIUM April8, 2014 Reading Country Club
CHP Strategies and Options / Stored Energy Jim Freihaut, Ph.D. Director, DOE Mid Atlantic CHP Technical Assistance Partnership Director, Indoor Aerosol Laboratory Professor, Architectural Engineering 104
More informationOptimization of Water - Cooled Chiller Cooling Tower Combinations
Optimization of Water - Cooled Chiller Cooling Tower Combinations by: James W. Furlong & Frank T. Morrison Baltimore Aircoil Company The warm water leaving the chilled water coils is pumped to the evaporator
More informationGreening Data Centers
Greening Data Centers Dallas Thornton SDSC Division Director, Cyberinfrastructure Services March 2, 2011 Data Centers Are Enormous Users of Power US Data Centers (TeraWatt Hours per Year) 125 US Televisions
More informationTHE OPTIMAL SOLUTION FOR SMALL AND MEDIUM DATA CENTER
Your Complete Turnkey Server Room Air Condition UPS THE OPTIMAL SOLUTION FOR SMALL AND MEDIUM DATA CENTER AVAILABLE IN WATER AND GAS SYSTEM MODEL AIR-CONDITIONED CABINET EXCELLENT TEMPERATURE CONTROL FOR
More information3/29/2012 INTRODUCTION HVAC BASICS
INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O HVAC systems or Heating, Ventilating and Air-Conditioning systems control the environment for people and equipment in our facilities.
More informationRecommendation For Incorporating Data Center Specific Sustainability Best Practices into EO13514 Implementation
Recommendation For Incorporating Data Center Specific Sustainability Best Practices into EO13514 Implementation Version 1.0 - November, 2011 Incorporating Data Center-Specific Sustainability Measures into
More informationVerizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001
Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue
More informationGEOTHERMAL HEAT PUMP SYSTEMS ARE RED HOT BUT ARE THEY REALLY GREEN?
GEOTHERMAL HEAT PUMP SYSTEMS ARE RED HOT BUT ARE THEY REALLY GREEN? Richard C. Niess 1 Gilbert & Associates / Apogee Interactive, Inc., Gloucester Point, Virginia 23062 Phone & Fax (804) 642 0400 ABSTRACT
More informationData Center Leadership In the DOE Better Buildings Challenge
Symposium Southern California February 18th, 2015 Data Center Leadership In the DOE Better Buildings Challenge Applying Best Practices to meet the Challenge Dale Sartor, PE Lawrence Berkeley National Laboratory
More informationHeat Recovery In Retail Refrigeration
This article was published in ASHRAE Journal, February 2010. Copyright 2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not
More informationHow To Design A Building In New Delhi
ENERGY EFFICIENT HVAC DESIGN FOR COMPOSITE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce energy consumption
More informationENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE
ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce
More informationFive Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency
Five Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Executive Summary As electricity prices and IT
More informationBy Donald Fisher, P.Eng., Associate Member ASHRAE
By Donald Fisher, P.Eng., Associate Member ASHRAE Decisions to purchase a commercial kitchen ventilation (CKV) system often are based on rule-of-thumb estimates using a $/cfm index (i.e., annual energy
More informationSource: EIA Natural Gas Issues and Trends 1998
7.0 System Redesign Analysis 7.1 Emissions Natural gas is a clean burning fossil fuel. It consists of a mixture of hydrocarbon gases, primarily Methane (CH 4 ). In analyzing the combustion process, it
More informationZero Refrigeration for Data Centres in the USA
Zero Refrigeration for Data Centres in the USA Robert Tozer PhD CEng MASHRAE Sophia Flucker CEng ABSTRACT Data centre energy consumption has grown significantly in recent years; cooling energy forms a
More informationEconomizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers
A White Paper from the Experts in Business-Critical Continuity TM Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers Executive Summary The strategic business importance
More informationOptimizing the Efficiency of the NCAR-Wyoming Supercomputing Center Facility. Ademola Olarinde Mentor: Aaron Andersen
Optimizing the Efficiency of the NCAR-Wyoming Supercomputing Center Facility Ademola Olarinde Mentor: Aaron Andersen August 2, 2013 1 Education: Mechanical Engineering Grad Student Texas A&M University
More informationData Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures
Data Realty Colocation Data Center Ignition Park, South Bend, IN Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures Project Overview Data Realty is a data center service provider for middle
More informationCHP - The Business Case
CHP - The Business Case An Introduction to Combined Heat and Power CHP 100 1 Acknowledgements 2 Overview! When Does CHP Make Sense! Where is CHP Practical?! Problems in CHP Economic Analysis 3 When Does
More informationData Center Energy Efficiency. SC07 Birds of a Feather November, 2007 Bill Tschudi wftschudi@lbl.gov
Data Center Energy Efficiency SC07 Birds of a Feather November, 2007 Bill Tschudi wftschudi@lbl.gov Benchmark results helped to find best practices The ratio of IT equipment power to the total (or its
More informationRecommendations for Measuring and Reporting Overall Data Center Efficiency
Recommendations for Measuring and Reporting Overall Data Center Efficiency Version 1 Measuring PUE at Dedicated Data Centers 15 July 2010 Table of Contents 1 Introduction... 1 1.1 Purpose Recommendations
More informationLawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory
Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory Title: Energy Implications of Economizer Use in California Data Centers Author: Shehabi, Arman Publication Date: 09-23-8 Permalink:
More informationOverview of Green Energy Strategies and Techniques for Modern Data Centers
Overview of Green Energy Strategies and Techniques for Modern Data Centers Introduction Data centers ensure the operation of critical business IT equipment including servers, networking and storage devices.
More informationASHRAE Rocky Mountain Chapter. RickPhillips Phillips, P.E., PE LEED AP Senior Mechanical Engineer The RMH Group, Inc.
ASHRAE Rocky Mountain Chapter Evaporative Cooling RickPhillips Phillips, P.E., PE LEED AP Senior Mechanical Engineer The RMH Group, Inc. April 19, 2013 1 Fundamentals Dry Bulb Temperature Wet Bulb Temperature
More informationElectrical Systems. <Presenter>
Review Root Causes of Energy Inefficiency Roadmap to Maximize Energy Efficiency Best Practices Alternative Energy Sources Controls Take Aways Seek Professional Help. ENERGY INEFFICIENCY OF
More informationEnvironmental Data Center Management and Monitoring
2013 Raritan Inc. Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor
More informationRittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy
Rittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy Executive Summary Data center owners and operators are in constant pursuit of methods
More informationCase Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers
Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers Prepared for the U.S. Department of Energy s Federal Energy Management Program Prepared By Lawrence Berkeley National
More informationCauses of High Relative Humidity Inside Air Conditioned Buildings. Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates
Causes of High Relative Humidity Inside Air Conditioned Buildings Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates S. FLORIDA AVE. AMBIENT 91 F db / 78 F wb 16,000 HOURS ANNUALLY THAT wb
More informationEnabling an agile Data Centre in a (Fr)agile market
Enabling an agile Data Centre in a (Fr)agile market Phil Dodsworth Director, Data Centre Solutions 2008 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without
More informationCANNON T4 MINI / MICRO DATA CENTRE SYSTEMS
CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS Air / Water / DX Cooled Cabinet Solutions Mini Data Centre All in One Solution: Where there is a requirement for standalone computing and communications, or highly
More informationHow To Test A Theory Of Power Supply
A CASE STUDY ON: THE EFFECTS OF HIGHER OPERATING TEMPERATURES ON DATA CENTER EFFICIENCY Victor Garcia Director of Facilities Brocade October 24, 2012 Jeff Stein, PE Principal Taylor Engineering 2010 Brocade
More informationCarnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics
Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics A Presentation of Work in Progress 4 October 2006 in the Intelligent
More informationHot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc.
Business Management Magazine Winter 2008 Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc. Contrary to some beliefs, air is quite
More informationWet Bulb Temperature and Its Impact on Building Performance
Wet Bulb Temperature and Its Impact on Building Performance By: Kurmit Rockwell, PE, CEM, LEED AP and Justin Lee, PE, LEED, AP BD+C Energy Solution Services, AtSite, Inc. 1 What is Wet Bulb Temperature?
More informationData Centre Cooling Air Performance Metrics
Data Centre Cooling Air Performance Metrics Sophia Flucker CEng MIMechE Ing Dr Robert Tozer MSc MBA PhD CEng MCIBSE MASHRAE Operational Intelligence Ltd. info@dc-oi.com Abstract Data centre energy consumption
More informationFact Sheet (Web Content): Improving Energy Efficiency for Server Rooms and Closets
Fact Sheet (Web Content): Improving Energy Efficiency for Server Rooms and Closets September 2012 Table of Contents A) Simplest, No-Cost, or Very-Low-Cost Measures 1. Determine computational functions
More informationDr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida
Optimizing 100% Outside Air Systems with Heat Pipes Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida Introduction To meet increasingly rigorous building codes
More informationDistributed polygeneration: desiccant-based air handling units interacting with microcogeneration systems
Distributed polygeneration: desiccant-based air handling units interacting with microcogeneration systems G. Angrisani *,1, C. Roselli 1, M. Sasso 1 1 DING, Università degli Studi del Sannio, Piazza Roma
More informationUMass Medical School Power Plant Expansion Presentation for the Northeast Clean Heat and Power Initiative. March 24, 2015
UMass Medical School Power Plant Expansion Presentation for the Northeast Clean Heat and Power Initiative March 24, 2015 John Baker Associate Vice Chancellor, Facilities Management Joseph Collins Chief
More informationNational Grid Your Partner in Energy Solutions
National Grid Your Partner in Energy Solutions National Grid Webinar: Enhancing Reliability, Capacity and Capital Expenditure through Data Center Efficiency April 8, 2014 Presented by: Fran Boucher National
More informationFEAR Model - Review Cell Module Block
F.E.A.R. Returns: 5 Steps Toward Data Center Efficiency Today Objectives Benefits for ITS professionals Brief review of the FEAR data center Define data center efficiency Link efficiency to the FEAR data
More informationRecommendations for Measuring and Reporting Overall Data Center Efficiency
Recommendations for Measuring and Reporting Overall Data Center Efficiency Version 2 Measuring PUE for Data Centers 17 May 2011 Table of Contents 1 Introduction... 1 1.1 Purpose Recommendations for Measuring
More informationSustainability and Data Centers
Sustainability and Data Centers Energy Efficiency and Beyond Tim Chadwick, President, Alfa Tech Jessica Kennedy, California Operations Director, Brightworks San Diego Sustainability and Data Centers Beyond
More information