Fire & Gas Detection; Reducing Risks in Rail Loading/Unloading Facilities. By Todd Spicer Technical Specialist Spartan Controls Fire & Security

Size: px
Start display at page:

Download "Fire & Gas Detection; Reducing Risks in Rail Loading/Unloading Facilities. By Todd Spicer Technical Specialist Spartan Controls Fire & Security"

Transcription

1 Fire & Gas Detection; Reducing Risks in Rail Loading/Unloading Facilities By Todd Spicer Technical Specialist Spartan Controls Fire & Security

2 Reality Rail Loading/Unloading Facilities Rail loading/unloading facilities for hydrocarbons such as crude oil, diluent or refined products are increasing in numbers throughout North America. Incidences related to Crude on Rail are increasing and becoming more frequently reported in the media. Society is calling for higher safety within the industry. Spartan Controls Confidential Page 2

3 Risks Rail Loading/Unloading Facilities The hazard and potential for fire/gas leak is high typically at the hatch, couplings, vents, and process piping. Electro-static discharge from the nozzle to car, diesel engines, and lightning strikes on the rail car and/or rack is the most common source of ignition If vapors are present between the LFL (lower flammable limit) and the UFL (Upper flammable limit) levels in the area of the ignition source, a fire is ignited. Spartan Controls Confidential Page 3

4 Why be concerned about a Fire or Gas Leak? Potential loss of life and equipment Environmental impact Social License Cost of fighting a fire Financial impact Spartan Controls Confidential Page 4

5 How do we reduce the risks? Proper safeties designed into the facilities 3D mapping Good Engineering Risk assessments Early indication of unsafe conditions and proper shutdowns Fire & Gas detection Process Shutdowns Manual ESD buttons Proper safety procedures HSE manuals Spartan Controls Confidential Page 5

6 What options do we have for Gas Detection? Manual Gas Detection: Personal or Portable Monitors Point Gas Detection: LFL(LEL) or Toxic (H2S) Open Path Detection: Det-Tronics LS2000 LFL Senscient LFL and/or H2S Spartan Controls Confidential Page 6

7 Why is there a need for gas detection? Gas Detection is the first line of defense against gas or vapor hazards both flammable and toxic The need to detect & measure gas or vapor before a hazardous concentration is present Provide outputs to enable emergency action (shut down, evacuation, etc) Spartan Controls Confidential Page 7

8 Gas Detection Overview Point Detection A point detector measures the concentration at the point where it is located and reads the percentage of LFL The detector must be in contact of the gas leaked 100% LFL 50% LFL 20% LFL 0% LFL Spartan Controls Confidential Page 8

9 Gas Detection Overview Open Path Detection Output is a function of gas concentration times the length of the surveillance path, and is expressed in units of LFL - m, or ppm - m. 2 m 100 ppm 4 m 200 ppm.m PAC at 40m =5ppm.m 50 ppm 20 m 10ppm Spartan Controls Confidential Page 9

10 Point + Beam Application Open Path systems are recommended for use in conjunction with point IR detectors or catalytic sensor systems for optimal combustible gas detection within a hazardous area. Spartan Controls Confidential Page 10

11 What options do we have for Flame Detection? Manual Actuation: - Push Button (PB) Requires human intervention Heat Detection: - Linear Heat Cable (LHD) or Point Heat Detector (PHD) performance susceptible to effects of environment. i.e. ambient temp, conditions. Optical Flame Detection: - Optical Flame Detector (X3301) Earliest/fastest method of detection. Spartan Controls Confidential Page 11

12 Flame & Gas Detection Overview Flame detectors are optical devices and therefore cannot see through solid/opaque objects Radiation emitted from the visible flame is the source of detection Wavelengths of focus are in the UV, IR or both Spartan Controls Confidential Page 12

13 Optical Flame Detection - Understanding Flame Dynamics Sense radiant energy from an open flame. Varies by fuel type. Provide different performance capabilities depending on technology type and spectral emissions of the fire. Provide varying levels of nuisance alarm rejection capability depending on the technology 13 Spartan Controls Confidential Page 13

14 The Challenge The Challenge: Undetected hazards How many detectors and where to locate Blind spots with zero coverage Lack of adequate coverage in high risk areas Obstructions in a detector s field of view Spartan Controls Confidential Page 14

15 Conventional Approaches to Determine Detector Placement Conventional approaches to mapping have evolved from rudimentary sketches Spartan Controls Confidential Page 15

16 Conventional Approaches to Determine Detector Placement To Visio-type drawings Spartan Controls Confidential Page 16

17 Conventional Approaches to Determine Detector Placement To formal 2D CAD oriented-type drawings Spartan Controls Confidential Page 17

18 Conventional Approaches to Determine Detector Placement Basic and rudimentary bird s eye view - does not account for: Blind spot changes in different planes Partially obscured fires which can provide false positives/negatives Accurate statistical data, especially with cylindrical shapes Spartan Controls Confidential Page 18

19 The 3D Mapping Method 3D Mapping Software + In-house Expertise Spartan Controls Confidential Page 19

20 The 3D Mapping Method Applicable to: Flame detection Gas detection Both Spartan Controls Confidential Page 20

21 Justification Mapping report provided to the end user with key information to be used for: Installation Auditing Insurers Regulators Process will determine the following: Detector location x, y, z axis, inclination and declination Visual confirmation of coverage and zero coverage Statistical analysis (1ooN, voted 2ooN, etc) Detection recommendation technology, sensitivity, optimized settings Spartan Controls Confidential Page 21

22 Examples Spartan Controls Confidential Page 22

23 Flame & Gas Detection Overview Detection range, field of view are highly dependent on: Fuel source Range Environment Proper alignment Optical gas detection either point or line of sight are dependent upon: Proximity to leak source Leak rates Environmental effects Obstructions Spartan Controls Confidential Page 23

24 In Summary Mitigation of undetected hazards by: Quantitative data provides another layer of protection and increased level of safety Ensures proper and precise detector placement with optimum coverage Flame and gas detection and fire protection engineers with years of experience Spartan Controls Confidential Page 24

25 Thank you for your time.any questions? Fire & Gas Detection; Reducing Risks in Rail Loading/Unloading Facilities Todd Spicer, Technical Specialist Fire & Security Spartan Controls Confidential Page 25 Spartan Controls Confidential

How to Select a Flame Detector

How to Select a Flame Detector How to Select a Flame Detector Process and plant engineers in the oil and gas industry and a wide range of other hazardous process and manufacturing industries require continuous flame monitoring equipment

More information

THE DETECTION OF GREENHOUSE GASES

THE DETECTION OF GREENHOUSE GASES THE DETECTION OF GREENHOUSE GASES Roy Montemarano Heath Consultants Incorporated KEYWORDS: greenhouse gas, remote detection, leak, natural gas, infrared, optical, imaging ABSTRACT Natural gas providers

More information

Vehicle Fire Protection. An Ownerʼs Manual for ANSUL Fire Suppression/Detection Systems

Vehicle Fire Protection. An Ownerʼs Manual for ANSUL Fire Suppression/Detection Systems Vehicle Fire Protection An Ownerʼs Manual for ANSUL Fire Suppression/Detection Systems 002792 Off-road vehicles do have fires Statistics show that off-road vehicles burn with alarming frequency. These

More information

Flame detection across the spectrum. Range Brochure

Flame detection across the spectrum. Range Brochure talentum Flame detection across the spectrum Range Brochure Talentum - Why use our Flame Detectors... Talentum Flame Detectors are ideal for applications where fast acting and accurate detection of fire

More information

TOXIC AND FLAMMABLE GAS CLOUD DETECTORS LAYOUT OPTIMIZATION USING CFD

TOXIC AND FLAMMABLE GAS CLOUD DETECTORS LAYOUT OPTIMIZATION USING CFD Introduction to the case Gas detectors are commonly installed in process facilities to automatically alarm and trigger safety measures in response to hazardous leaks. Without effective leak detection,

More information

www.klmtechgroup.com TABLE OF CONTENT

www.klmtechgroup.com TABLE OF CONTENT Page : 1 of 13 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia TABLE OF CONTENT SCOPE 2 REFERENCES

More information

Application Requirement

Application Requirement Hazardous Gas Monitors Sensor Selection Overview Safety Monitoring (LEL) Toxic Limit Detection (PEL) Leak Detection Personal Safety Application Requirement Exposure Assessment (TWA) Ambient Air Quality

More information

Methane to Markets Oil and Natural Gas Technology Transfer Workshop

Methane to Markets Oil and Natural Gas Technology Transfer Workshop Methane to Markets Oil and Natural Gas Technology Transfer Workshop Airborne Differential Absorption Lidar (DIAL) Detection and Measurement of Fugitive Emissions Steven Stearns ANGEL Service ITT Space

More information

Basic Fundamentals Of Safety Instrumented Systems

Basic Fundamentals Of Safety Instrumented Systems September 2005 DVC6000 SIS Training Course 1 Basic Fundamentals Of Safety Instrumented Systems Overview Definitions of basic terms Basics of safety and layers of protection Basics of Safety Instrumented

More information

OPERATION MANUAL INFRARED THERMOMETER

OPERATION MANUAL INFRARED THERMOMETER OPERATION MANUAL INFRARED THERMOMETER Features: Precise non-contact measurements Built-in laser pointer Automatic selection range and Resolution to 0.1ºor 1º / switchable button Automatic Data Hold & Auto

More information

Recommended Practice for Installation of Transit Vehicle Fire Protection Systems

Recommended Practice for Installation of Transit Vehicle Fire Protection Systems Recommended Practice for Installation of Transit Vehicle Fire Protection Systems Approved October 25, 2007 APTA Fire Safety Working Group Approved May 3, 2008 APTA Bus Safety Committee Approved October

More information

Triple Waveband Infra-Red Flame Detection

Triple Waveband Infra-Red Flame Detection Minerva S200PLUS Ex ia Intrinsically Safe & Ex d Flameproof Solar Blind Flame Detectors Triple Waveband Infra-Red Flame Detection Key Features Unrivalled black body rejection over a wide range of source

More information

Integrating Performance Standards into an Asset Management System

Integrating Performance Standards into an Asset Management System Integrating Performance Standards into an Asset Management System Leveraging ISO 55000 in the Oil and Gas Industry By Mike Poland, CMRP, CRL 4360 Corporate Road Charleston, SC 29405-7445 843.744.7110 www.lce.com

More information

Process Heater Burners, Flare Systems, Thermal Oxidizers and Catalyst Systems. Combustion Technology

Process Heater Burners, Flare Systems, Thermal Oxidizers and Catalyst Systems. Combustion Technology Combustion Technology INNOVATIVE SOLUTIONS FOR COMBUSTION AND EMISSIONS CHALLENGES Process Heater Burners, Flare Systems, Thermal Oxidizers and Catalyst Systems Callidus Technologies by Honeywell - Experie

More information

MICROPACK Visual Flame Detection Application Note

MICROPACK Visual Flame Detection Application Note MICROPACK Visual Flame Detection Application Note ABSTRACT Optical flame detection has evolved over the last 30 years with improved sensors, processing power, and high electronics reliability, which has

More information

HSE information sheet. Fire and explosion hazards in offshore gas turbines. Offshore Information Sheet No. 10/2008

HSE information sheet. Fire and explosion hazards in offshore gas turbines. Offshore Information Sheet No. 10/2008 HSE information sheet Fire and explosion hazards in offshore gas turbines Offshore Information Sheet No. 10/2008 Contents Introduction.. 2 Background of gas turbine incidents in the UK offshore sector...2

More information

Hydrogen Detection in Oil Refineries

Hydrogen Detection in Oil Refineries Hydrogen Detection in Oil Refineries Because every life has a purpose... Hydrogen Detection in Oil Refineries MSA Gas Detection: Hydrogen Gas Detection in Oil Refineries Oil refineries are large producers

More information

THE USE OF FIRE AND GAS DETECTION SYSTEMS AS PART OF THE SAFETY CONTROL PACKAGE

THE USE OF FIRE AND GAS DETECTION SYSTEMS AS PART OF THE SAFETY CONTROL PACKAGE THE USE OF FIRE AND GAS DETECTION SYSTEMS AS PART OF THE SAFETY CONTROL PACKAGE I G Buckland Health and Safety Executive, Technology and Health Sciences Division, Magdalen House, Bootle, Merseyside. The

More information

Overview. Components of an alarm system Technology behind the equipment Communication Platforms Industry Terminology False Alarm Tips DSC products

Overview. Components of an alarm system Technology behind the equipment Communication Platforms Industry Terminology False Alarm Tips DSC products Basic Security 101 Overview Components of an alarm system Technology behind the equipment Communication Platforms Industry Terminology False Alarm Tips DSC products Components of an Alarm System Main Control

More information

ABSTRACT INTRODUCTION

ABSTRACT INTRODUCTION Infrared Technology for Fail-To-Safe Hydrocarbon Gas Detection Authors: Dr. Shankar Baliga is Manager of Research & Development at General Monitors. He has a Ph.D. in Physics from Ohio State University

More information

Performance Based Gas Detection System Design for Hydrocarbon Storage Tank Systems

Performance Based Gas Detection System Design for Hydrocarbon Storage Tank Systems Performance Based Gas Detection System Design for Hydrocarbon Storage Tank Systems Srinivasan N. Ganesan, M.S., P.E. MENA Region Manager, Kenexis DMCC, Dubai, UAE Edward M. Marszal, PE, ISA 84 Expert ABSTRACT

More information

FLARE MONITORS FLARE MONITOR (FM) PILOT MONITOR (PM) FLAME INTENSITY (FI)

FLARE MONITORS FLARE MONITOR (FM) PILOT MONITOR (PM) FLAME INTENSITY (FI) FLARE MONITORS Infrared Sensors for Monitoring Smokeless Flares, Pilots, and Flame Intensity FMDS2014 FLARE MONITOR (FM) Monitor smokeless flare combustion efficiency to maximize destruction of hazardous

More information

Fire and Gas Solutions. Improving Safety and Business Performance

Fire and Gas Solutions. Improving Safety and Business Performance Fire and Gas Solutions Improving Safety and Business Performance Industrial Fire & Gas (F&G) systems play a critical role in protecting people, processes and the environment. They continuously monitor

More information

Technical Cleaning Ó

Technical Cleaning Ó Technical Cleaning JUSTIFICATION Cleaning of Data Centers and Communications Rooms should be performed by qualified personnel who will use techniques and equipment designed to clean without re-contaminating

More information

Hydrogen Detection in Oil Refineries

Hydrogen Detection in Oil Refineries Hydrogen Detection in Oil Refineries Hydrogen Gas Detection in Oil Refineries Oil refineries are some of the largest producers and consumers of hydrogen gas. Hydrogen plays a pivotal role in a whole host

More information

ENGINEERED DRAWINGS FOR PETROLEUM STORAGE TANKS

ENGINEERED DRAWINGS FOR PETROLEUM STORAGE TANKS Facility Name: ENGINEERED DRAWINGS FOR PETROLEUM STORAGE TANKS The following is intended to be used as a guideline for information required to appear on engineered drawings involving petroleum storage

More information

Data center solutions from Siemens. For the factories of the 21 st century. siemens.com/datacenters

Data center solutions from Siemens. For the factories of the 21 st century. siemens.com/datacenters Data center solutions from Siemens For the factories of the 21 st century siemens.com/datacenters We face the challenges for the factories of the 21 st century Based on our vast experience, we offer a

More information

An Overview of the International Road Tunnel Fire Detection Research Project

An Overview of the International Road Tunnel Fire Detection Research Project An Overview of the International Road Tunnel Fire Detection Research Project Introduction Z. Liu 1, A. Kashef, G. Lougheed, J. Z. Su and N. Benichou Fire Research Program, Institute for Research in Construction

More information

Module 5. Fire and Emergency Alarm System Part I- Basics

Module 5. Fire and Emergency Alarm System Part I- Basics Module 5 Fire and Emergency Alarm System Part I- Basics 1 This module will describe: 1. Components and the arrangements of components in fire and emergency alarm systems. 2. How these systems work. 3.

More information

Buckeye Detection Systems Fixed Detection Systems Application Survey

Buckeye Detection Systems Fixed Detection Systems Application Survey Buckeye Detection Systems Fixed Detection Systems Application Survey Channel Partner Representative : Company Name: Representative: BDS Representative: Client Contact Information : Company Name: Company

More information

Maximum uptime and optimum fire safety for your data center

Maximum uptime and optimum fire safety for your data center Maximum uptime and optimum fire safety for your data center Integrated and tailored fire safety solutions from one partner Answers for infrastructure. Complete solutions for a safe data center with a single

More information

Experion Integrated Fire & Gas Safety and Security Monitoring at your fingertips! Ajay Varghese

Experion Integrated Fire & Gas Safety and Security Monitoring at your fingertips! Ajay Varghese 1 2014 Honeywell Users Group Asia Pacific Experion Integrated Fire & Gas Safety and Security Monitoring at your fingertips! Ajay Varghese Document control number Sometimes. it doesn t take much time Over

More information

BRANCH SOLUTION. Automatic fire extinguishing systems for paint spraying plants. Safe for certain.

BRANCH SOLUTION. Automatic fire extinguishing systems for paint spraying plants. Safe for certain. BRANCH SOLUTION Automatic fire extinguishing systems for paint spraying plants Safe for certain. ISK IDENTIFYING With the extreme high degree of automation in painting technology, the risk of fire has

More information

White Paper. Detecting Hydrogen Sulfide Gas and Understanding its Danger in the Field. Introduction

White Paper. Detecting Hydrogen Sulfide Gas and Understanding its Danger in the Field. Introduction White Paper PN FGD_TWP_H2S_Hydrogen_Sulfide_Gas_Understand_Danger January 2015 Detecting Hydrogen Sulfide Gas and Understanding its Danger in the Field Introduction Many oil fields, especially mature ones,

More information

Fire. The Fire Installers Mate. A guide to fire alarm systems design

Fire. The Fire Installers Mate. A guide to fire alarm systems design Fire The Fire Installers Mate A guide to fire alarm systems design BS 5839 Part 1:2002 A guide to BS 5839 Part 1:2002 Disclaimer This booklet is not intended to be a comprehensive guide to all aspects

More information

FSD Circular Letter No. 7/95 Automatic Fire Detection System - Design and Maintenance Considerations

FSD Circular Letter No. 7/95 Automatic Fire Detection System - Design and Maintenance Considerations Our Ref.: 1 5 (49) in FPB 314/07 III FIRE SERVICES DEPARTMENT FIRE PROTECTION COMMAND FIRE SERVICES HEADQUARTERS BUILDING, No. 1 Hong Chong Road, 5/F., Tsim Sha Tsui East, Kowloon, Hong Kong Your Ref.:

More information

NMSU FIRE DEPARTMENT Commercial Kitchen Fire Suppression Worksheet

NMSU FIRE DEPARTMENT Commercial Kitchen Fire Suppression Worksheet This Commercial Kitchen Automatic Fire has been created to assure all documentation has been submitted to assist you in assuring proper plans and documentations has been submitted and reviewed by New Mexico

More information

Type Testing Procedure for Crankcase Oil Mist Detection and Alarm Equipment

Type Testing Procedure for Crankcase Oil Mist Detection and Alarm Equipment (Jan 2005) (Corr.1 Nov 2005) (Rev.1 Oct 2006) (Corr.1 Oct 2007) (Rev.2 Feb 2015) Type Testing Procedure for Crankcase Oil Mist Detection and Alarm Equipment 1. Scope 1.1 To specify the tests required to

More information

ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.252 WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600

ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.252 WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600 OSHA REGULATION: 9 CFR 90.5 WELDING, CUTTING, AND BRAZING ( HOT WORK ) A. POLICY. This procedure follows requirements set forth in 9 CFR 90.5.. This policy applies to all Hot Work operations being done

More information

PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS

PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS January 1997 PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS 1.0 PERMIT 1.1 After receipt of a Building Permit from the City of San Jose Building Department, submit

More information

DC400 Dispensing Cutoff System

DC400 Dispensing Cutoff System DC400 Dispensing Cutoff System DC404 and DC406 Installation Instructions Franklin Fueling Systems 3760 Marsh Rd. Madison, WI 53718 USA Tel: +1 608 838 8786 800 225 9787 Fax: +1 608 838 6433 www.franklinfueling.com

More information

Measuring of optical output and attenuation

Measuring of optical output and attenuation Measuring of optical output and attenuation THEORY Measuring of optical output is the fundamental part of measuring in optoelectronics. The importance of an optical power meter can be compared to an ammeter

More information

Example Confined Space Entry Programs

Example Confined Space Entry Programs Example Confined Space Entry Programs Use with the Confined Spaces book, Chapter 296-809 WAC These example confined space entry programs are provided for your information, and to help you determine the

More information

Improving Steam Methane Reformer Performance with the ZoloSCAN-SMR

Improving Steam Methane Reformer Performance with the ZoloSCAN-SMR Improving Steam Methane Reformer Performance with the SCAN-SMR The global demand for hydrogen continues to increase as heavier crudes are processed and stricter governmental mandates require reductions

More information

TESTING, INSPECTION, AND MAINTENANCE FREQUENCIES FOR FIRE DETECTION AND ALARM SYSTEMS

TESTING, INSPECTION, AND MAINTENANCE FREQUENCIES FOR FIRE DETECTION AND ALARM SYSTEMS TESTING, INSPECTION, AND MAINTENANCE FREQUENCIES FOR FIRE DETECTION AND ALARM SYSTEMS The following information regarding testing frequencies for fire detection and alarm systems. All of the following

More information

Alarm and Detection/Suppression

Alarm and Detection/Suppression Alarm and Detection/Suppression Fire Safety American Fire Technologies To provide special hazard services world wide to the industrial market through the integration of components and services Clean Agent

More information

The Behaviour Of Vertical Jet Fires Under Sonic And Subsonic Regimes

The Behaviour Of Vertical Jet Fires Under Sonic And Subsonic Regimes The Behaviour Of Vertical Jet Fires Under Sonic And Subsonic Regimes Palacios A. and Casal J. Centre for Technological Risk Studies (CERTEC), Department of Chemical Engineering, Universitat Politècnica

More information

Integrated Fire and Gas Solution - Improves Plant Safety and Business Performance

Integrated Fire and Gas Solution - Improves Plant Safety and Business Performance Integrated Fire and Gas Solution - Improves Plant Safety and Business Performance Integrated Fire and Gas Solution - Improves Plant Safety and Business Performance 1 Table of Contents Table of Figures...1

More information

LASER SAFETY PROGRAM FOR CANISIUS COLLEGE (Department of Chemistry and Biochemistry) Effective: October 1, 2007 Revised: June 3, 2010

LASER SAFETY PROGRAM FOR CANISIUS COLLEGE (Department of Chemistry and Biochemistry) Effective: October 1, 2007 Revised: June 3, 2010 LASER SAFETY PROGRAM FOR CANISIUS COLLEGE (Department of Chemistry and Biochemistry) Effective: October 1, 2007 Revised: June 3, 2010 1. BACKGROUND Procedures and guidelines for working with lasers can

More information

Grounding and Bonding Against Static Electricity. Jon Koppari, CSP, MS Occupational Safety and Health Instructor OSHA Training Institute

Grounding and Bonding Against Static Electricity. Jon Koppari, CSP, MS Occupational Safety and Health Instructor OSHA Training Institute Grounding and Bonding Against Static Electricity Jon Koppari, CSP, MS Occupational Safety and Health Instructor OSHA Training Institute Objectives Identify Sources of Ignition. Identify Hazards associated

More information

Emergency Response Guide

Emergency Response Guide Emergency Response Guide Honda Fuel Cell Vehicle Prepared for Fire Service, Law Enforcement, Emergency Medical, and Professional Towing Personnel by American Honda Motor Co., Inc. Contents Key Components...2

More information

FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST

FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST Date of Inspection: Conducted by: Location: Reviewed by: Date of Review: Comments or additional corrective action taken as a result

More information

OREGON FIRE CODE Interpretations and Technical Advisories

OREGON FIRE CODE Interpretations and Technical Advisories OREGON FIRE CODE Interpretations and Technical Advisories A collaborative service by local and state fire professionals, along with our stakeholders and customers, to provide consistent and concise application

More information

OPERATIONS & MAINTENANCE (O&M) FOR PROPANE STORAGE FACILITIES

OPERATIONS & MAINTENANCE (O&M) FOR PROPANE STORAGE FACILITIES OPERATIONS & MAINTENANCE (O&M) FOR PROPANE STORAGE FACILITIES Reference: National Fire Protection Association (NFPA) Pamphlet No. 58 Liquefied Petroleum Gas Code, 2001, Chapter 11 Type of Facility: Petroleum

More information

FACILITY SAFETY SIGNAGE GUIDE: 10 SIGNS TO SPOT DURING A PLANT WALKTHROUGH

FACILITY SAFETY SIGNAGE GUIDE: 10 SIGNS TO SPOT DURING A PLANT WALKTHROUGH FACILITY SAFETY SIGNAGE GUIDE: 10 SIGNS TO SPOT DURING A PLANT WALKTHROUGH Safety signs are the primary way to communicate important warnings and messages to your employees, on-site contractors and other

More information

Calculation of Liquefied Natural Gas (LNG) Burning Rates

Calculation of Liquefied Natural Gas (LNG) Burning Rates Calculation of Liquefied Natural Gas (LNG) Burning Rates Carolina Herrera, R. Mentzer, M. Sam Mannan, and S. Waldram Mary Kay O Connor Process Safety Center Artie McFerrin Department of Chemical Engineering

More information

Intelligent Terminal Automation System

Intelligent Terminal Automation System Intelligent Terminal Automation System. Rockwell Automation intelligent Terminal Automation Systems provide a complete automation solution for tank terminals beyond your expectations The Rockwell Automation

More information

APPLICATION OF QUALITATIVE AND QUANTITATIVE RISK ANALYSIS TECHNIQUES TO BUILDING SITING STUDIES

APPLICATION OF QUALITATIVE AND QUANTITATIVE RISK ANALYSIS TECHNIQUES TO BUILDING SITING STUDIES APPLICATION OF QUALITATIVE AND QUANTITATIVE RISK ANALYSIS TECHNIQUES TO BUILDING SITING STUDIES John B. Cornwell, Jeffrey D. Marx, and Wilbert W. Lee Presented At 1998 Process Plant Safety Symposium Houston,

More information

Natural Gas Emergencies

Natural Gas Emergencies Natural Gas Emergencies Purpose To protect the personnel within the department, and citizens from the hazards involved in a natural gas emergency. The Incident Commander is to use his/her best judgment

More information

Piotr Tofiło a,*, Marek Konecki b, Jerzy Gałaj c, Waldemar Jaskółowski d, Norbert Tuśnio e, Marcin Cisek f

Piotr Tofiło a,*, Marek Konecki b, Jerzy Gałaj c, Waldemar Jaskółowski d, Norbert Tuśnio e, Marcin Cisek f Available online at www.sciencedirect.com Procedia Engineering 57 (2013 ) 1156 1165 11th International Conference on Modern Building Materials, Structures and Techniques, MBMST 2013 Expert System for Building

More information

White Paper. Best Practices for Gas Monitoring in the Commercial Kitchen

White Paper. Best Practices for Gas Monitoring in the Commercial Kitchen White Paper Best Practices for Gas Monitoring in the Commercial Kitchen Enhancing Kitchen Safety through Strategic Gas Monitoring Overview Commercial kitchens are one of the most hazardous commercial building

More information

Version: 1.0 Last Edited: 2005-10-27. Guideline

Version: 1.0 Last Edited: 2005-10-27. Guideline Process hazard and risk Comments on this report are gratefully received by Johan Hedberg at SP Swedish National Testing and Research Institute mailto:johan.hedberg@sp.se -1- Summary This report will try

More information

Control Device Requirements Charts For Oil and Gas Handling and Production Facilities

Control Device Requirements Charts For Oil and Gas Handling and Production Facilities Device Charts For Oil and Gas Handling and Production Facilities Purpose/Scope: The purpose of this document is to provide standardized guidance for use by the regulated community and air permit reviewers,

More information

Shell s Health, Safety and Environment (HSE) management system (see Figure 11-1) provides the framework for managing all aspects of the development.

Shell s Health, Safety and Environment (HSE) management system (see Figure 11-1) provides the framework for managing all aspects of the development. Section 11.1 APPLICATION FOR APPROVAL OF THE DEVELOPMENT PLAN FOR NIGLINTGAK FIELD PROJECT DESCRIPTION INTRODUCTION 11.1.1 HSE MANAGEMENT SYSTEM Shell s Health, Safety and Environment (HSE) management

More information

Intelligent Solutions DTS Applications LNG Facilities

Intelligent Solutions DTS Applications LNG Facilities DTS Applications LNG Facilities Dan Danskin LNG Tech Global Summit 2013 1 Agenda What, Why, Who and Where to use DTS Established LNG Applications Emerging LNG Applications Summary Technology (if required)

More information

LNG Fuel Tank System LNG Tank overview

LNG Fuel Tank System LNG Tank overview Index 1. LNG Tank Overview 2. 3. Gas Flow Diagram 4. Tank Operation 5. 6. Maintenance Boil off line Slave tank Master tank manual gas line vacuum control manual liquid line Check nonreturn filling line

More information

E2-E3: ELECTRICAL CHAPTER-13 FIRE PROTECTION SYSTEM- EVOLVING TRENDS AND APPLICABILITY TO DATA CENTRE

E2-E3: ELECTRICAL CHAPTER-13 FIRE PROTECTION SYSTEM- EVOLVING TRENDS AND APPLICABILITY TO DATA CENTRE E2-E3: ELECTRICAL CHAPTER-13 FIRE PROTECTION SYSTEM- EVOLVING TRENDS AND APPLICABILITY TO DATA CENTRE BSNL, India For Internal Circulation Only Page: 1 Fire Protection System- Evolving Trends & Applicability

More information

Challenges for Use of Fixed Fire Suppression Systems in Road Tunnel Fire Protection

Challenges for Use of Fixed Fire Suppression Systems in Road Tunnel Fire Protection Challenges for Use of Fixed Fire Suppression Systems in Road Tunnel Fire Protection Z. G. Liu *, A. Kashef, G. Lougheed, and A. K. Kim Fire Research Program, Institute for Research in Construction National

More information

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable

More information

(2) Various fire sections enclosed by various classes of fire divisions; (3) Arrangement of fire detectors and manual fire alarm stations;

(2) Various fire sections enclosed by various classes of fire divisions; (3) Arrangement of fire detectors and manual fire alarm stations; (1979) (Rev.1 1990) (Rev.2 1996) (Rev.3 Jan 2012) Safety features.1 Fire protection and extinction.1.1 General Fire protection arrangements and fire extinguishing systems are to be in accordance with the

More information

Maximum uptime and optimum fire safety for your data center

Maximum uptime and optimum fire safety for your data center Maximum uptime and optimum fire safety for your data center Integrated and tailored fire safety solutions from one partner Answers for infrastructure. Complete solutions for a safe data center with a single

More information

Leak detection technologies for the oil and gas industry. Chris Neidre Alex Robertson July 17, 2015

Leak detection technologies for the oil and gas industry. Chris Neidre Alex Robertson July 17, 2015 Leak detection technologies for the oil and gas industry Chris Neidre Alex Robertson July 17, 2015 Our company Leek s most recent milestones - Created as a division of Seacoast Science in 2013 - Spun-off

More information

Exit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection. OSHA Office of Training and Education 1

Exit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection. OSHA Office of Training and Education 1 Exit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection OSHA Office of Training and Education 1 Introduction Fires and explosions kill more than 200 and injure more than 5,000 workers

More information

Liberty Mutual Insurance RISK ENGINEERING PROCEDURE. REP 07 Incident Planning For external use

Liberty Mutual Insurance RISK ENGINEERING PROCEDURE. REP 07 Incident Planning For external use Liberty Mutual Insurance RISK ENGINEERING PROCEDURE REP 07 Incident Planning For external use Risk Engineering Procedure Incident Planning CONTENTS Page PURPOSE... 3 BACKGROUND... 4 INCIDENT PLANNING PREPARATION...

More information

READ FIRST. Confined Space Entry Procedure. San José State University Environmental Health and Safety. Confined Space Entry Procedure

READ FIRST. Confined Space Entry Procedure. San José State University Environmental Health and Safety. Confined Space Entry Procedure READ FIRST 1. The purpose of a is to save lives by controlling the inherent hazards of a confined space prior to entry. a. If possible, avoid entering a confined space. Every consideration should be given

More information

Verizon NEBS TM Compliance: Data Center Equipment NEBS Requirements Verizon Technical Purchasing Requirements VZ.TPR.9703 Issue 2, March 2012

Verizon NEBS TM Compliance: Data Center Equipment NEBS Requirements Verizon Technical Purchasing Requirements VZ.TPR.9703 Issue 2, March 2012 Verizon NEBS TM Compliance: Data Center Equipment NEBS Requirements Verizon Technical Purchasing Requirements VZ.TPR.9703 Issue 2, March 2012 CHANGE CONTROL RECORD: Version Date Action* Reason for Revision

More information

Gas Standards and Safety. Guidance Note GAS INSTALLATIONS SUPPLIED FROM BIOGAS FACILITIES - ACCEPTANCE REQUIREMENTS GAS ACT 2000

Gas Standards and Safety. Guidance Note GAS INSTALLATIONS SUPPLIED FROM BIOGAS FACILITIES - ACCEPTANCE REQUIREMENTS GAS ACT 2000 Gas Standards and Safety Guidance Note January 2015 (GN106) Version 1.0 GAS INSTALLATIONS SUPPLIED FROM BIOGAS FACILITIES - ACCEPTANCE REQUIREMENTS GAS ACT 2000 A guide to assist in the design of biogas

More information

WORK IN CONFINED SPACES

WORK IN CONFINED SPACES WORK IN CONFINED SPACES STFC Safety Code No 11 Rev. 1.4, Issued April, 2015 Note - This document may have been superseded by a more recent version. Revisions 1 Initial Launch November 2007 1.1 Minor changes

More information

Emergency Isolation Valves at Pump Suction: Application for Flammable Liquids

Emergency Isolation Valves at Pump Suction: Application for Flammable Liquids 667 A publication of CHEMICAL ENGINEERING TRANSACTIONS VOL. 48, 2016 Guest Editors: Eddy de Rademaeker, Peter Schmelzer Copyright 2016, AIDIC Servizi S.r.l., ISBN 978-88-95608-39-6; ISSN 2283-9216 The

More information

EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM

EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29CFR1910.36-29CFR1910.38-29CFR1910.157-29CFR1910.165 NFPA-10 BASIS: The OSHA Emergency Action Planning and the

More information

ANNEX 17 DRAFT AMENDMENTS TO SOLAS REGULATIONS II-2/4 AND II-2/16. Part B Prevention of fire and explosion

ANNEX 17 DRAFT AMENDMENTS TO SOLAS REGULATIONS II-2/4 AND II-2/16. Part B Prevention of fire and explosion Annex 17, page 1 ANNEX 17 DRAFT AMENDMENTS TO SOLAS REGULATIONS II-2/4 AND II-2/16 Part B Prevention of fire and explosion Regulation 4 Probability of ignition 1 The existing paragraph 5.5 is replaced

More information

Static Electricity. A Health and Safety Guideline for Your Workplace. What Are Some Sources of Static Electricity? What is Static Electricity?

Static Electricity. A Health and Safety Guideline for Your Workplace. What Are Some Sources of Static Electricity? What is Static Electricity? A Health and Safety Guideline for Your Workplace What is static electricity? What causes it? How is it hazardous? And, most importantly, how can it be controlled? All of these questions will be answered

More information

Compressed Gas Cylinder Storage and Handling Guide

Compressed Gas Cylinder Storage and Handling Guide Overview Compressed gas cylinders are used in many workplaces to store gases that vary from extremely flammable (acetylene) to extremely inert (helium). Many compressed gas cylinders are stored at extremely

More information

HOW TO SELECT A LOW VOLUME (L.V ) BOILER

HOW TO SELECT A LOW VOLUME (L.V ) BOILER HOW TO SELECT A LOW VOLUME (L.V ) BOILER FREQUENTLY ASKED QUESTIONS OR COMMENTS ON BOILERS Dear Potential Customer: Low Volume Operator Exempt boilers have been marketed in Ontario to eliminate the requirement

More information

Highlights of Colorado s New Oil and Gas Hydrocarbon Emission Reduction Rules - Adopted February 2014

Highlights of Colorado s New Oil and Gas Hydrocarbon Emission Reduction Rules - Adopted February 2014 Highlights of Colorado s New Oil and Gas Hydrocarbon - Adopted February 2014 Presentation to the Colorado Counties, Inc. June 3, 2014 Mike Silverstein Colorado Department of Public Health and Environment

More information

MOTOR FUEL DISPENSING SAFETY

MOTOR FUEL DISPENSING SAFETY STRATEGIC OUTCOMES PRACTICE TECHNICAL ADVISORY BULLETIN January 2010 MOTOR FUEL DISPENSING SAFETY Fire! Not an alarm anyone wants to hear, especially not when the fire is burning at a major fuel source.

More information

The photoionization detector (PID) utilizes ultraviolet

The photoionization detector (PID) utilizes ultraviolet Chapter 6 Photoionization Detectors The photoionization detector (PID) utilizes ultraviolet light to ionize gas molecules, and is commonly employed in the detection of volatile organic compounds (VOCs).

More information

Fire Safety Log Book

Fire Safety Log Book Fire Safety Log Book Company... Address........ Responsible Person. Competent Person. Date Started For Additional Information: Safety Management (UK) Ltd Holme Suite, Clawthorpe Hall Business Centre, Burton

More information

SL280UHV SERIES GAS FURNACE WARNING

SL280UHV SERIES GAS FURNACE WARNING 2010 Lennox Industries Inc. Dallas, Texas, USA 506677 01 11/2010 Supersedes 506409 01 SL280UHV SERIES GAS FURNACE Litho U.S.A. FIRE OR EXPLOSION HAZARD. Failure to follow safety warnings exactly could

More information

Continuous Monitoring of Flue and Combustible or Hazardous Gases and Vapors

Continuous Monitoring of Flue and Combustible or Hazardous Gases and Vapors Continuous Monitoring of Flue and Combustible or Hazardous Gases and Vapors www.static-control.in 1 Introduction The detection or monitoring of flue gases and or hazardous gases has been a complex subject

More information

For use by landlords of small premises Premises Address

For use by landlords of small premises Premises Address fire risk assessment For use by landlords of small premises Premises Address FIRE RISK ASSESSMENT for use by landlords of small premises Person having control of the premises: Name of landlord (if different):

More information

Example of SOP for IR Laser

Example of SOP for IR Laser Example of SOP for IR Laser Standard Operating Procedures (SOP) for Class 4 HPD semiconductor Laser Manufacturer HPD Building & Room Number EH&S 101 Model Number HPD-1/100/975 Laser Class 4 Serial Number

More information

Q U A D S C A N I I GENERAL User Interface Enclosure Display QUADSCAN II Temperature Range RECEIVER DISPLAY Sensor Weight Optional Relay Enclosure

Q U A D S C A N I I GENERAL User Interface Enclosure Display QUADSCAN II Temperature Range RECEIVER DISPLAY Sensor Weight Optional Relay Enclosure QUADSCAN II SERIES 7400 ONE TO FOUR CHANNEL RECEIVER QUADSCAN II SERIES 7400 ONE TO FOUR CHANNEL RECEIVER Centralizes Monitoring and Alarming for Gas Transmitters and Fire Detectors. The QuadScan II receiver

More information

Distributed Temperature Sensing - DTS

Distributed Temperature Sensing - DTS Intelligent Solutions Distributed Temperature Sensing - DTS Enabling fast, reliable and cost-effective sensing through highly integrated optical measurement systems Fire detection Power cable monitoring

More information

GEORGIA DEPARTMENT OF COMMUNITY AFFAIRS (DCA) STATE CODES ADVISORY COMMITTEE (SCAC) CARBON MONOXIDE DETECTORS FOR SCHOOLS TASK FORCE

GEORGIA DEPARTMENT OF COMMUNITY AFFAIRS (DCA) STATE CODES ADVISORY COMMITTEE (SCAC) CARBON MONOXIDE DETECTORS FOR SCHOOLS TASK FORCE Important Discussion Points about Carbon Monoxide and Schools 1. What happened to make carbon monoxide in schools an important issue for the State? On December 3, 2012, approximately 40 students and staff

More information

Fossil fuel heating equipment

Fossil fuel heating equipment Fossil fuel heating equipment principles and troubleshooting techniques Application Note This application note was written to provide you with an understanding of the basic principles of fossil fuel heating

More information

How To Stop A Gas Leak

How To Stop A Gas Leak Natural Gas / Propane Emergencies Probationary Firefighter Academy Properties of Natural Gas / Propane Natural Gas and Propane are gaseous fossil fuels Natural Gas is primarily Methane(CH 4 ) Propane is

More information

An Open Platform for Digitizing Real World through Sentient Artefact Model. Fahim Kawsar Waseda University, Japan

An Open Platform for Digitizing Real World through Sentient Artefact Model. Fahim Kawsar Waseda University, Japan An Open Platform for Digitizing Real World through Sentient Artefact Model Fahim Kawsar Waseda University, Japan 1 Talk Outline Motivation Scenario Sentient Artefact Design Principle Sentient Artefact

More information

Guidelines for Use and Handling of HFO-1234yf

Guidelines for Use and Handling of HFO-1234yf Guidelines for Use and Handling of HFO-1234yf HFO-1234yf can be described as being mildly flammable as measured by standard methodology. This descriptor is used to characterize the flammability in simplistic

More information