1 E2-E3: ELECTRICAL CHAPTER-13 FIRE PROTECTION SYSTEM- EVOLVING TRENDS AND APPLICABILITY TO DATA CENTRE BSNL, India For Internal Circulation Only Page: 1
2 Fire Protection System- Evolving Trends & Applicability to Data Centers 1.0 Introduction: The objective of this chapter is to understand the evolving trends in fire detection and extinguishing system, and to discuss its possible application in Telecom installations. A telecom installation with high concentrations of cables and electronics switching equipment within relatively small areas constitutes a HIGH RISK installation. 2.0 Objective: At the end of this Chapter, participants will be able to under stand : Evolving Trends in fire Detection System Modern Trends in Fire Extinguishing System Fire fighting for data Centers 3.0 Evolving Trends In Fire Detection System: The modern trend is to provide one of the following automatic fire detection systems for protecting the Telecom installations. - High Sensitivity Smoke Detection System [HSSD] - Linear Heat Detection Cables [LHD] - Analogue Addressable Intelligent System. 3.1 HSSD System Description: High sensitivity smoke detector is a relatively new form of smoke detector. It is an aspirating detection system which comprises of : - Pipe work to collect samples of Air from the protected area. - High sensitivity Detector capable of detecting smoke concentrations as low as 0.01% per meter. - A fan to draw air through the pipe network. - A display and control card to show increased smoke levels in increments from 1-10 and provide the necessary alarm outputs. HSSD system provides smoke detection sensitivities up to 500 times greater than conventional point detectors. Fig. (1) Illustrates the incipient stages of fire and contrast the relative response of detectors. BSNL, India For Internal Circulation Only Page: 2
3 Fig -1 BSNL, India For Internal Circulation Only Page: 3
4 3.1.1 HSSD Principle Of Operation: HSSD is a digital particle counter utilizing advance optics and electronics. A fan through a ducting / pipe system continuously draws air from the high value components. A laser is focused by a lens assembly to provide a high intensity spot of light within the centre of the air stream. This spot is 100 micron in diameter, which provide good light intensity to be scattered by a particle entering at this point. Focused at this point is the light receive optics which transfers the photons of lights scattered by each particle to the receive electronics. The throughput of particles is effectively counted through integration circuitry, which then convert the digital system to an analogue where smoke density is displayed on 1 to 10 segments Bar Graph. The electronic of the system ignores pulses generated from particles over 10 microns, thus, effectively, discriminating against false alarms due to dust or environmental conditions. The system has been used in some Telecom System has FM approval. applications in West. M/S KIDDE UK 3.2 Linear Heat Detection Cables: LHD System Description: Linear heat detection [LHD] cable based system provides economical temperature monitoring thereby fire detection capabilities at the precise point of risk. They are reliable, flexible and have ability to detect abnormal temperature variations of fire before the break out. LHD system is a continuous heat detection cable capable of measuring and reporting adverse changes in temperature at a spot location. Linear Heat detection is - Continuous heat detector in the form of cable. - Analogue [Alarm line] averaging heat detector or rate of rise. - Digital [KIDDE BICC] Point of risk heat detector Fixed temperature LHD Principle Of Operation: Analogue [Alarm Line]: Alarm Line high resistance sensor cable is a 4-core cable. Two cores are used for monitoring and two cores for sensing temperature changes. An increase in temperature reduces the resistance value of the cable. This value is measured by associated electronic interfaced unit, which provides the alarm indication once the predetermined alarm level has been reached. The cable senses the rate of rise of temperature and not the fixed temperature. BSNL, India For Internal Circulation Only Page: 4
5 Digital [KIDDE BICC]: Digital heat sensor cable is a twin conductor cable with temperature sensitive insulation. The cable operates by melting [thereby short-circuiting] once the temperature of sensor cable is exceeded. Unlike analogue [alarm line] the operating temperature is fixed within the temperature rating of the temperature sensitive insulation. The temperature alarm setting depending upon the outer sheet of the cable used and the requirement can be seen as under: ALARM COATING 70 ºC Polythene 90 ºC Polythene 113 ºC PVC 180 ºC PVC 238 ºC Fluoro Polymer The digital cables can be directly connected into a fire panel as a zone. These cables can be effectively installed to protect the cable runways or the telecom racks. M/S KIDDE UK LHD has FM approval. 3.3 Analogue Address Intelligent Fire Surveillance System: System Description: - Analogue The feedback from the sensors is in the form of Analogue Counts. The value of these counts changes depending upon fire, fault, dust conditions and can be analyzed by the micro processor. - Addressable The detectors have a fixed address which can be read by the control panel and the sensor can be addressed by the control panel. - Intelligent The micro processor in the control panel provides the intelligence and the decision making is through this micro processor. The system hardware [Fig -2] depends upon the actual requirement and usually has combination of the following: [a] Control panel [b] Sensors [c] Bells/ Sounders [d] System Wiring and Fittings. [e] Power Supply Unit. BSNL, India For Internal Circulation Only Page: 5
6 [f] Optional Items :- Repeater Control Unit, External status Interface, Personal Computer/ Networking. Control Panel : The Control panel [As shown in Fig -3] is having micro- processor on a PCB that automatically controls the system. The control panel holds a combination of electronic circuit cards as per the site requirements for pulse bells and sensors. They also provide interface to external facilities through peripherals printed circuit boards. The key pad on the control panel enables certain supervisory function to be undertaken. It also provides for authorized only coded access to enable certain system functions to be interrogated for maintenance. Access to the control panels itself is by key. A built in printer is a standard item on the control panel. BSNL, India For Internal Circulation Only Page: 6
7 BSNL, India For Internal Circulation Only Page: 7
8 Fig -2 Fig -3 BSNL, India For Internal Circulation Only Page: 8
9 Sensors: As per the site requirement combination of following sensors also termed as field units/input devices is provided: - Analogue Addressable ionization smoke detectors with dual ionization chamber. - Analogue Addressable optical smoke detectors, photo electric type using internal infrared light source. - Analogue Addressable fixed temperature, heat detector and rate of rise hear detectors. - Analogue addressable manual call Point / Break glass Unit :- With frangible glass, splinter protected for activation by manually breaking the glass. Bells / Sounders: The externally wired bells and electronic sounders/ PA system provide audible warning to emergencies. The Bells/Sounders can create disturbances on the system and thus, have to be properly chosen. System Wiring And Fittings: Two wire cable is used for linking the sensors and the control panel and for the PA system / interface unit etc. etc. The wiring is looped [Fig. 4.0] and in some cases, a standby [loop] is also provided so as to make the system fool proof. Fittings such as short circuit isolators are fixed at strategic position to isolate sensors section in case of break or fault. Generally one isolator is provided for every 20 devices. Power Supply Unit: Two 12 volts sealed lead acid batteries provide the 24volt DC supply to operate the system. The batteries are on constant charge from an integral Charging unit fed through AC MAINS. Optional Items: Repeater control unit for monitoring of system at strategic or remote locations can be provided. Status interface can be provided for linking the system with personal computer., in networking or external building management system Principle Of Operation: The Analogue addressable intelligent fire surveillance system uses state of- theart microprocessor control with built in Software program to maintain automatic two ways communication with a large number of remote sensors which detects fire and smoke. The system provides for an activation signal to be transmitted by any sensor to BSNL, India For Internal Circulation Only Page: 9
10 the control unit and also enables the operational readiness of each sensor to be routinely monitored. The detectors used in the system are addressable analogue detectors. Unlike the conventional detectors, the analogue detector does not operate on the threshold basis. The analogue voltage signal produced by the activation of the detector is converted into a analogue count by the electronic circuitry and transmitted to the control panel on interrogation. The unique address [1 to 126] of the sensor provided by means of XPERT CARD/ DIL [DUAL INPUT LINE] switch [Fig. 5] is read by the microprocessor whenever the sensor is addressed by the control panel. Built in programmes address and interrogate in turn each sensor in the system.the interval between addressing any sensor is 2 to 3 seconds depending upon the number per loop. Each sensor responds with a signal indicating that it is in operational readiness. Though the principle of operation may vary from manufacturer to manufacturer, a commonly employed method is on the pulse position modulation principle. Each and every detector is scanned by the pulses generated [Fig. 6.0] from the control panels and feedback is processed by the control panel to generate the required signals. Intelligent pulses of 5 to 9 volts are super-imposed on the DC supplies volts on the two wires. Since there is a constant communications between the Control Panel and the various detectors, the exact condition of the detector is conveyed to the Panel in the form of an Analogue count [1 to 126]. It gives the information that the detector is non-functional / fault/ dead [count of 1 to 12], normal/ healthy [15 to 40]. A count of 40 to 55 is a prealarm stage which is generally due to non-maintenance of the detectors or the poor environmental conditions. This information is extremely important because timely action by the supervisor can prevent the false-alarm. A condition beyond 55 is generally an alarm condition. It is this feature of the intelligent system which is the most important, useful and powerful in comparison to the conventional system. The programmes routinely execute supervisory commands within the control unit to validate the operational readiness of the electronic circuits. On switching on, the control unit automatically calibrates each sensor against its ambient temperature or particular level as appropriate, ensuring constant sensitivity of sensors throughout the systems. The calibration, together with lamp testing is performed routinely every day at a fixed time ( say 1200 hours) through system software. The system is able to discriminate between a false alarm and the real fire conditions by analyzing various fire characteristics and environmental conditions [Fig. 7.0] BSNL, India For Internal Circulation Only Page: 10
11 3.3.4 Advantages Of Analogue Addressable System: Large number of detectors in one loop and flexibility Status Display Programming For Exact Location Of Fire Adjustment Of Detector Sensitivity Dirty Pre-Warning For Detectors Simple Cabling Origin / Flow Of Fire Can Be Ascertained Discrimination Between Genuine Fire And Other Conditions Isolation Of Faulty Detectors / Output Devices/ Areas Under Mtce. Logging Of Past Events Ease Of Maintenance 4.0 Modern Trends In Fire Extinguishing Systems: - Fire Trace Extinguishing System. - Halon Alternative Extinguishing System (A) Total Flooding Agents (B) Portable Fire Extinguishers - Wet Riser & Sprinklers 4.1 Fire Trace Extinguishing System: System Description: The system consists of following: - A specialized flexible Fire detection and Fire extinguishing Delivery tube. - The tube is wrapped around or installed within the Protected equipment Exchange Racks, cabinets etc. etc. - [Avoiding surface above 80 ºC] - Fire extinguishing media cylinder connected at one end of the tube, thus, the tube is charged with extinguishing media Principle Of Operation: When an area is overheated or should a small fire take place the tube adjacent or above the fire will soften and burst at hottest point allowing swift and accurate delivery of the extinguisher directly to the source of the fire. BSNL, India For Internal Circulation Only Page: 11
12 4.1.3 Fire Trace Advantages: The system does not require Electricity / or battery supply for operating the detection system. It has no wiring, detectors or control panel. It can be connected to any extinguishing agent depending upon application and has been approved by LOSS PREVENTION CONTROL BOARD 4.2 Halon Alternative Extinguishing System: Halon is a very effective fire extinguishing agent. However, because of the high ozone depletion potential, its use has to be phased out as per the provisions in Montreal protocol without comprising with Fire safety. As per Government of India Ministry of Home affairs & DGCD [Fire Cell] letter dated , the following HALON alternatives have been identified. [A] [B] Alternative For Halon 1211 Portable Fire Extinguishers Are: (I) ABC Powder extinguisher. (II) Co2 squeeze grip type extinguisher. (III) HCPC based compounds like NAF P IV, Halotron, FE-36 etc. Alternative For Halon 1301 Fixed Fire Protection Systems Are: [i] CO2 fire extinguishing in-cabinet and subfloor systems, including low Pressure CO2 systems. [ii] Inert gas extinguishing systems [nitrogen based] [iii] Water mist fire extinguishing system. [iv] Fast response sprinklers. [v] Halocarbons such as HFC 227 (FM-200), PE-13, HCFC blends, The HALON alternatives as above can be classified under[nafs 111] following categories. [I] Traditional Fire Protection Agents: [Ii] Halocarbon Agents [Iii] Inert Gases [Iv] Water Mists [V] Powdered Aerosols 4.3 Wet Riser & Sprinklers: These are continued to be provided for high-rise buildings and basements as per local Fire byelaws and Fire Protection manual of the department. BSNL, India For Internal Circulation Only Page: 12
13 5.0 Fire Fighting In Data Centre A complete and thorough fire protection strategy in the data center seems like an obvious priority. Protection = Detection + Suppression. The ideal protection strategy should include a smoke detection package with a fire suppression system. There are a variety of possibilities to choose from in both categories. Detection. Typically, detection is cross-zoned using both photoelectric and ionization type spot detectors. Cross zoning allows the end user protection against false discharges of the suppression system, by requiring one of each type of detector to be in alarm, prior to the initiation of a discharge. High sensitivity smoke detection is also an option. Suppression. There are multiple options to choose from for both suppression agents, and suppression systems. Some suppression agent brands you'll want to consider: FM-200, Inergen, Argonite, Novec Also, because these halon alternatives are a more mature product set now, several applications specific systems are available. For example, 'in-cabinet' systems for protection of a small closet or cabinet spaces. The FM-200 agent is a popular halon replacementtypesystem. Fm 200 Based Fire Extinguishing System The FM-200 extinguishing system include the following components: Agent storage container with cylinder valve. FM-200 agent. Discharge nozzle (s). Electronic control head for master cylinder (s) and pressure operated control head for slave cylinder(s) as releasing devices. Mounting brackets. Discharge hoses. EL Check valves on manifold. Actuation hoses for slave cylinder(s) Master cylinder adapter kit for slave cylinder system Any other required for the completeness of the system Any other required for the completeness of the system. The Heptafluropropane - CCF 3 CHFCF 3 (FM-200), is a clean Fire suppression agent. FM-200 is stored in seamless storage containers. The FM-200 Fire Suppression System includes a detection and control switch provision for both pre-alarm and automatic agent release. BSNL, India For Internal Circulation Only Page: 13
14 The detection and control system used to trigger the FM-200 suppression employs multiple smoke detectors. A single detector in one zone activated, shall cause an alarm signal to be generated. Another detector in the second zone activated, shall generate a pre-discharge signal and start the pre-discharge condition. The suppression sub-system provides high- speed release of FM-200 Based on the concept of total flooding fire protection for enclosed areas. A uniform extinguishing concentration shall be seven- (7) percent v/v concentration of FM-200 at 70 degree F. The system discharge time shall be 10 seconds or less, in accordance with NFPA Standard The discharge nozzles are located in the protected volume in compliance to the limitation with regard to the spacing, floor and ceiling coverage etc. The nozzle locations are such that the design concentration is established in all parts of the protected volumes. The FM- 200 discharge shall be activated by an output directly from the FM-200 Gas Release control panel, which will activate the Electric control head based releasing device. FM- 200 agent is stored in the container as a liquid, having a natural vapor pressure of 66.4 psi at 77 degree F. To aid release and distribution, the container shall be super pressurized to 360 psi(g) at 70 degree F with dry nitrogen. The FM-200 valve, operating actuators is an Electric (Solenoid) type, and is capable of resetting manually. Provision is provided on the Electric Control Head for a Manual Lever for over-ride in case of failure of the Electrical components. The Electric Control Head ( Actuator ) operates at 24 VDC. The Electric Control Head should be capable of being functionally tested for periodic servicing requirements, and without any need to replace consumable parts. The system flow calculations are carried out on certified software, suitable for the particular container being offered for the project.the releasing device is also capable of direct mechanical actuation, providing a means of discharge in the event of total electrical malfunction. Provided with a manual lever and a face plate with clear instruction of how to mechanically activate the system. In all cases, FM-200 cylinders is fitted with a manual mechanical operating facility that requires two-action actuation to prevent accidental actuation. FM-200 storage cylinders is provided with a safety rupture disc. An increase in internal pressure due to high temperature ruptures the safety disc and allow the contents to vent before the rupture pressure of the container is reached. The contents do not vented BSNL, India For Internal Circulation Only Page: 14
15 through the discharge piping and nozzles. FM-200 containers is equipped with a pressure gauge to display internal pressure. The gauge is an integral part of the container and shall be color-coded for fast referencing of pressure reading. Brass Discharge nozzles is used to disperse the FM-200. The nozzles are of brass with female threads and available in ½ through 2 sizes. FM-200 Gas Release Panel: The FM-200 release signal output shall be from the Microprocessor based Main Fire Alarm Control panel with battery charger and battery stand-by. This panel is not of the zone card type, but shall have the entire operational logic on a microchip. The panel should be capable of enhanced features such as printer and computer interface, auto dialer interface, by addition of extra cards on the motherboard. Release of FM-200 agent is accomplished by an electrical output from the FM-200 Gas Release Panel to the Electric control head release device and is in accordance with the requirements set forth in the current edition of the National Fire Protection Association Standard BSNL, India For Internal Circulation Only Page: 15
16 Question 1. Write the advantages of Analogue Addressable Microprocessor based Fire Detection System as compared to conventional system. 2. Which type of Fire Fighting and detection systems should be used in Data centre of BSNL 3. Briefly describe Fire Trace Extinguishing system. What are the Advantages? 4. Briefly describe High Sensitivity Smoke Detection system (HSSD) system used in fire protection system. Mention the advantages also. 5. What is Linear Heat Detection system (LHD). Write down the principle of operation. 6. Write down the Halon Alternative Fire Extinguishing systems. 7. List down the categories in which HALON alternatives can be classified. 8. List down the components of FM-200 Fire Extinguishing system. 9. Write short Notes on FM Gas Release Panel. 10. What is the difference between Digital Linear heat Detection system and Analogue Linear heat Detection system. BSNL, India For Internal Circulation Only Page: 16
Alarm and Detection/Suppression
Alarm and Detection/Suppression Fire Safety American Fire Technologies To provide special hazard services world wide to the industrial market through the integration of components and services Clean Agent
More informationENGINEERING SPECIFICATIONS
ENGINEERING SPECIFICATIONS FM-200 CLEAN-AGENT FIRE SUPPRESSION SYSTEM with PYRO-CHEM DETECTION/RELEASE SYSTEM March 2001 SECTION 1 - GENERAL I. SCOPE This specification outlines the requirements for a
More informationSECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines
PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting
More informationUniversity of Houston Master Construction Specifications Insert Project Name
SECTION 21 22 13 - SAPPHIRE CLEAN-AGENT FIRE SUPPRESSION SYSTEM PART 1 GENERAL 1.1 RELATED DOCUMENTS A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and this Section
More informationSPECIAL APPLICATIONS
Page 1 SPECIAL APPLICATIONS The protection of microelectronics clean rooms using aspirating smoke detection systems requires special consideration. The physical configuration of the room(s) and the direction
More informationProtection Systems. A UTC Fire & Security Company F-73-01. Linear Heat Detector FEATURES DESCRIPTION APPLICATIONS BENEFITS
Effective: May 2007 AlarmLine TM R Protection Systems Linear Heat Detector A UTC Fire & Security Company F-73-01 FEATURES Integrating Type Linear Heat Detector Analog Sensing Field Adjustable Alarm Set
More informationFIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10
TECHNICAL SPECIFICATIONS Page 1 of 10 FIRE DETECTION AND ALARM SYSTEM Scope Furnish a complete 24V DC conventional, electrically supervised, zone annunciated, fire detection and alarm system as specified
More informationFire detection equipment
PRODUCT CATALOG Fire detection equipment www.apollo-fire.com Apollo Fire Detectors is one of the world s largest manufacturers of fire detectors, modules and notification devices. Established in 1980,
More informationSECTION 16721 FIRE ALARM AND DETECTION SYSTEMS
SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS The equipment requirements of this section apply to the IUB Campus. The IUPUI Campus has a preferred vendor agreement for fire alarm systems. Contact Pat
More informationFIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 19
TECHNICAL SPECIFICATIONS Page 1 of 19 FIRE DETECTION AND ALARM SYSTEM Scope Furnish a complete 24V DC analogue addressable, electrically supervised, zone annunciated, fire detection and alarm system as
More informationSPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi CONTROL PANEL
SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with a Cheetah Xi addressable detection and control system.
More informationHART HSSD High Sensitivity Smoke Detection
HART HSSD High Sensitivity Smoke Detection The HART High Sensitivity Smoke Detection system (HSSD) is an Aspirating Smoke Detection system (ASD) designed to give very early indication of an incipient
More informationAmerex CPS FM-200 Waterless Pre-engineered Fire Suppression System
Amerex CPS FM-200 Waterless Pre-engineered Fire Suppression System A Simple Solution An Affordable Approach An Industry Innovation I N T R O D U C T I O N A SIMPLE SOLUTION. AN AFFORDABLE How many days
More informationENGINEERING SPECIFICATION. Engineering Specification SAPPHIRE 42 Bar
Engineering Specification SAPPHIRE 42 Bar PART 1 GENERAL 1.1 DESCRIPTION OF WORK This specification outlines the requirements for a "Total Flood" SAPPHIRE Clean Agent Fire Suppression System. The work
More informationDTW Works Master Specification Version 2006
Issued 2006/08/01 Section 13852 Multiplex Fire Alarm System Page 1 of 10 PART 1 GENERAL 1.1 RELATED WORK.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Procedures..3 Section 01810 Commissioning..4
More informationConventional Fire Detection and Extinguishant Control System Specification
Conventional Fire Detection and Extinguishant Control System Specification Page 1 of 9 Scope Furnish a complete 24VDC Conventional, electrically supervised, combined fire detection and extinguishant release
More informationRelative Sensitivity based Fire Detection Systems used in High Density Computer Rooms with In-Row Air Conditioning Units
Relative Sensitivity based Fire Detection Systems used in High Density Computer Rooms with In-Row Air Conditioning Units By Suresh Soundararaj & David Admirand, PE Experts for Your Always Available Data
More informationModule 5. Fire and Emergency Alarm System Part I- Basics
Module 5 Fire and Emergency Alarm System Part I- Basics 1 This module will describe: 1. Components and the arrangements of components in fire and emergency alarm systems. 2. How these systems work. 3.
More informationThe supplier and installer of the system should be approved by the local civil defence authority.
ANALOGUE ADDRESSABLE FIRE ALARM SYSTEM 1. Scope of Work The contractor shall supply, install, test and commission a modern Analogue Addressable Fire Detection and Alarm System of an approved manufacturer
More informationAerosol Fire Suppression. Your Choice for Special Hazard Fire Protection
Aerosol Fire Suppression Your Choice for Special Hazard Fire Protection Traditional Special Hazard Fire Protection Centers Around Two Technologies Water deluge and chemical agent fixed systems protect
More informationFIRE ALARM AND DETECTION SYSTEMS SECTION 16721
PART 1 - GENERAL 1.01 WORK INCLUDED FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 A. Provide a complete fully addressable, power limited, fire detection and evacuation system. The system shall be connected
More informationNYC SUB-SYSTEMS INSTALLATION & SERVICE REQUIREMENTS OF THE FDNY
NYC SUB-SYSTEMS INSTALLATION & SERVICE REQUIREMENTS OF THE FDNY Presented by: James Goerl Metro Protection Systems, Inc. jgoerl@metroprotectionsystems.com Agenda Introduction & Learning Objectives History
More informationPASSIVE INFRARED INTRUSION DETECTOR PASSIVE INFRAROOD DETECTOR DETECTEUR D INTRUSION PASSIF INFRAROUGE
MODEL HAA51 PASSIVE INFRARED INTRUSION DETECTOR PASSIVE INFRAROOD DETECTOR DETECTEUR D INTRUSION PASSIF INFRAROUGE OPERATING MANUAL HAA51 PASSIVE INFRARED INTRUDER DETECTOR INTRODUCTION HAA51 Passive Infrared
More informationALARMLINE ANALOGUE Linear Heat Detection System
ALARMLINE ANALOGUE Alarmline Analogue sensor cable senses temperature variations by continuously monitoring the resistance of specially doped N.T.C. polymeric insulation. A change in temperature produces
More informationINSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according
More informationEXHIBIT A SCOPE OF WORK
EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,
More informationENGINEERING SPECIFICATIONS FOR CO2 EXTINGUISHING AGENT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS
ENGINEERING SPECIFICATIONS FOR CO2 EXTINGUISHING AGENT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS SECTION 1 GENERAL SPECIFICATIONS I. SCOPE This specification outlines the requirements for a pre-engineered
More informationBARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell
Data, installation, operation and maintenance 4 & 8 Zone Fire Panels Zircon range BARDIC by Honeywell LED flashing LED Continuous FAULT DISABLE/TEST Power General Fault Sounder Fault/ Disable System Fault
More informationFIRE-FIGHTING DESIGN BRIEF REPORT
P a g e 1 SECTION 04 (Doc.No.A/DBR 001) FIRE-FIGHTING DESIGN BRIEF REPORT P a g e 2 1.0 SCOPE 2.0 STANDARDS AND CODES 3.0 TYPES OF SYSTEM PROPOSED 4.0 FIRE HYDRANT SYSTEM 5.0 AUTOMATIC SPRINKLER SYSTEM
More informationSECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS
SECTION 16721 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire Alarm Control Panels B. Manual Fire Alarm Stations C. Automatic Smoke D. Fire Alarm Notification Appliances E. Auxiliary Fire Alarm Equipment
More informationBERMAD Fire Protection
400E-2M/700E-2M IOM Bermad Electrically Controlled Deluge Valve with EasyLock Manual Reset Model: 400E-2M/700E-2M INSTALLATION OPERATION MAINTENANCE Application Engineering BERMAD 400E-2M/700E-2M Bermad
More informationMODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE
DESCRIPTION MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE DESCRIPTION The SST Model 5010 Two Channel Smoke/Fire Detection Module provides two independent detection input channels for the NOVA-5000
More informationMTI10 Insertion and MTL10 In-line Thermal Mass Flowmeter and Temperature Transmitter
Thermal Mass meter and Temperature Transmitter Description The MTI10 insertion thermal mass flowmeter and the MTL10 in-line thermal mass flowmeter provide accurate mass flow measurement of clean, dry gases
More informationsingapore//singapore data center specifications tel: +61 2 9948 8888 fax: +61 2 9948 1111 internet + intellectual property + intelligence
internet + intellectual property + intelligence We thank you for the opportunity to work with you regarding your colocation needs in Singapore. We can colocate standard rack-mountable servers or other
More informationSMART SENSOR COLLECTION
TEMPERATURE SENSOR This sensor measures temperature in degrees Celsius or Fahrenheit. It works with all SensorHawk base units (SensorHawk-2, SensorHawk-8 and SensorHawk8/20) as well as the SecurityHawk-8
More informationFIRE ALARM SYSTEM CHECKLIST For Addressable Systems PRIOR TO INSPECTION
Building Name/Location: Installing Company: Observation By: Date: Time: 1 Building Occupants, Authorities and Alarm Monitoring Co Have Been Notified 2 FACP Manufacturer and Panel is Approved for NCSU Campus
More informationDELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION
Phone System Owner Phone System Engineered by: of Record Drawings: of System Manuals: of Test Reports: System Installer 1. GENERAL INFORMATION Phone Delaware License No: Certificate Holder No. System Supplier
More informationSECTION 13850 DETECTION AND ALARM
SECTION 13850 DETECTION AND ALARM PART 1 GENERAL 1.01 SUMMARY A. Section Includes 1. Control Panel 2 Associated Equipment B. Products Installed But Not Supplied Under This Section 1. Section 16140 - Wiring
More informationModel: 400E-2M. Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset. Installation Operation Maintenance. Application Engineering
Model: 400E-2M Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Application Engineering BERMAD 1. Safety First BERMAD believes that the safety
More informationFLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL
FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:
More informationDepending on your facility and the equipment contained within, all or part of the checklists/logs can be printed for use.
Large Facility Fire Safety Checklists and Logs This package contains checklists to ensure that all fire and life safety equipment are properly inspected. There are also logs on which to record the inspections
More informationBERMAD Fire Protection
Model: 400E-2M BERMAD Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Safety First BERMAD believes that the safety of personnel working with and around
More informationAttachment 9. Trouble signals. Interfaced equipment. Primary (main) power supply
FIRE DETECTION, ALARM AND MASS NOTIFICATION SYSTEMS Inspection, testing, and maintenance of fire detection, alarm and Mass Notification systems shall be performed in accordance with the manufacturer's
More informationThe Mission Critical Fire Protection Experts
The Mission Critical Fire Protection Experts Protection Systems Protection Systems HFC-227ea / FM200 / FE-227 FE-25 / ECARO-25 Novec 1230 Inergen / Argonite Halon Drop-in Systems High and Low Pressure
More informationC. Conform to requirements of Americans with Disabilities Act (ADA).
SECTION 28 31 00 - FIRE ALARM AND DETECTION SYSTEMS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire alarm and detection systems 1.2 REFERENCES A. NFPA 70 - National Electrical Code B. NFPA 72 - National
More informationFire. The Fire Installers Mate. A guide to fire alarm systems design
Fire The Fire Installers Mate A guide to fire alarm systems design BS 5839 Part 1:2002 A guide to BS 5839 Part 1:2002 Disclaimer This booklet is not intended to be a comprehensive guide to all aspects
More informationDATA CENTER FIRE PROTECTION
DATA CENTER FIRE PROTECTION DATA CENTER FIRE PROTECTION The following is a summary of a few key fire protection, detection, and suppression technologies used by Minimax Fire Solutions in data centers and
More informationNC State University Design and Construction Guidelines Division 26 Fire Alarm Systems
NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems 1.0 Purpose A. The following guideline provides the minimum standards and requirements for fire alarm systems. 2.0
More informationNATIONAL FIRE ALARM AND SIGNALING CODE
GAP.11.1.1.0 A Publication of Global Asset Protection Services LLC NATIONAL FIRE ALARM AND SIGNALING CODE INTRODUCTION National Fire Protection Association (NFPA) documents describe a level of fire protection
More informationMaximum uptime and optimum fire safety for your data center
Maximum uptime and optimum fire safety for your data center Integrated and tailored fire safety solutions from one partner Answers for infrastructure. Complete solutions for a safe data center with a single
More informationEDA-Z5008 & Z5020. Radio Fire Alarm System. User Manual
EDA-Z5008 & Z5020 Radio Fire Alarm System User Manual Electro-Detectors Ltd. Electro House, Edinburgh Way Harlow, Essex, CM20 2EG UK Tel: 01279 635668. Fax 01279 450185 Email: eda@electrodetectors.co.uk
More informationSPECIFICATION FOR A TOTAL FLOOD HFC-227ea CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE Cheetah Xi CONTROL PANEL SYSTEM
SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Total Flood Clean Agent Fire Suppression System with automatic detection and control. The work described in this
More informationPLAN REVIEW GUIDE FOR FIRE ALARM
PLAN REVIEW GUIDE FOR FIRE ALARM PROJECT NAME: PERMIT # PROJECT ADDRESS: CONTACT PERSON: PHONE Fire alarm system installation information shall be provided on the appropriate architectural and electrical
More informationHeating and Hot Water Services Controls General Technical Specification
Construction Services Heating and Hot Water Services Controls General Technical Specification Version 1.0 Environment Heating and Hot Water Services Controls General Technical Specification Contents 1.
More informationDiocese of St Albans Diocesan Advisory Committee Advisory Leaflet 40. Fire Alarm Systems. A short guide to fitting them in Churches and Church Halls
Diocese of St Albans Diocesan Advisory Committee Advisory Leaflet 40 Fire Alarm Systems A short guide to fitting them in Churches and Church Halls Introduction The majority of churches will not need to
More informationEVALUATION OF THE PERFORMANCE OF FIRE DETECTION SYSTEM IN AN INSTITUTIONAL BUILDING
, Volume 6, Number 4, p.333-343, 2004 EVALUATION OF THE PERFORMANCE OF FIRE DETECTION SYSTEM IN AN INSTITUTIONAL BUILDING C.M. Tse Department of Building Services Engineering, The Hong Kong Polytechnic
More informationRecommended Practice for Installation of Transit Vehicle Fire Protection Systems
Recommended Practice for Installation of Transit Vehicle Fire Protection Systems Approved October 25, 2007 APTA Fire Safety Working Group Approved May 3, 2008 APTA Bus Safety Committee Approved October
More informationFire Alarm Control Panel. Family. Operating Manual
Fire Alarm Control Panel Family Operating Manual CONTENTS System Description AH-03312 System Characteristics... Fire Signal Receiving Board Description-4L... Fire Signal Receiving Board Description-8L...
More informationTAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems
More informationBURGLAR ALARM SYSTEMS BURGLAR ALARM SYSTEMS BURGLAR ALARM SYSTEM EURO ALARM WIRELESS BURGLAR ALARM SYSTEM OASIS
BURGLAR ALARM SYSTEMS BURGLAR ALARM SYSTEMS BURGLAR ALARM SYSTEM EURO ALARM WIRELESS BURGLAR ALARM SYSTEM OASIS BURGLAR ALARM SYSTEM EURO ALARM Six zones with the following connection capabilities: One
More informationQCS Section 23 Part 2 Fire Alarm and Detection Systems Page 1 2. FIRE ALARM DETECTION SYSTEMS...2
QCS Section 23 Part 2 Fire Alarm and Detection Systems Page 1 2. FIRE ALARM DETECTION SYSTEMS...2 2.1 GENERAL...2 2.1.1 Scope 2 2.1.2 References 2 2.1.3 Contractor s Responsibility 2 2.1.4 System Description
More informationSECTION 16721 FIRE ALARM AND DETECTION SYSTEM
SECTION 16721 FIRE ALARM AND DETECTION SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification
More informationGlobal System Technology(UK) PLC The Intelligent Solution
Global System Technology(UK) PLC The Intelligent Solution MANUFACTURED IN ACCORDANCE WITH Intelligent Photoelectric Smoke Detector Aesthetically pleasing Low profile design 8 Bit intelligent processor
More informationFIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION
FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. It shall be permitted to modify this
More informationFIRE DETECTION AND FM-200 SUPPRESSION SYSTEM
FIRE DETECTION AND FM-200 SUPPRESSION SYSTEM A. SCOPE: This specification outlines the requirements for a cross-zoned detection and total flooding FM-200 fire suppression system. The work described in
More informationMaximum uptime and optimum fire safety for your data center
Maximum uptime and optimum fire safety for your data center Integrated and tailored fire safety solutions from one partner Answers for infrastructure. Complete solutions for a safe data center with a single
More informationOverview of Fire Alarm Systems and Maintenance
Overview of Fire Alarm Systems and Maintenance By Mr. David Goh Vice President Fire Safety Managers Association Convener of Working Group for CP 10 : 2005 Er. Matthew Kwek Committee Member Fire Safety
More informationLEVEL 3 DATA CENTER ASSESSMENT
Nationwide Services Corporate Headquarters 410 Forest Street Marlborough, MA 01752 USA Tel: 800-342-5332 Fax: 508-303-0579 www.eecnet.com LEVEL 3 DATA CENTER ASSESSMENT Submitted by: Electronic Environments
More informationAnalogue addressable devices
Discovery Analogue addressable devices from Channel Safety Systems Discovery Analogue addressable devices Discovery is a range of high-specification, intelligent fire detectors that are developed to meet
More informationAspirating Smoke Detectors 420 Series Special environments require very early detection
Aspirating Smoke Detectors 420 Series Special environments require very early detection 2 Aspirating Smoke Detectors: A sure-fire investment Actively protect your investments with a smoke aspiration system
More information1.0 General. Inspection, Testing, and Maintenance 1 of 8
1.0 General 1.1 Scope This specifications covers the minimum requirements for the inspection, testing, and maintenance of the existing Notifier fire alarm systems at Bergen Community College (BCC) campus
More information14. Troubleshooting Guide
14. Guide 14.1 Refrigeration Cycle System In order to diagnose malfunctions, ensure the air conditioner is free from electrical problems before inspecting the refrigeration cycle. Such problems include
More information600-GD & 600-GDL 600 SERIES GAS DETECTOR
600-GD & 600-GDL 600 SERIES GAS DETECTOR INSTALLATION AND OPERATING INSTRUCTIONS This page has been deliberately left blank. Page 1 Table of Contents 1 WARRANTY...3 2 IMPORTANT...3 3 CAUTIONS WHEN USING
More informationSECTION 16721 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION
SECTION 16721 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION A. This section of the specifications includes the furnishing, installation, and connection of the microprocessor-controlled
More informationCB200 1 8 Zone Conventional Control Panel
CB200 1 8 Zone Conventional Control Panel > features Built-in detector removal indication facility From 1 to 8 zones 4 Alarm circuits on 4-8 zone panels Conforms to the requirements of EN54-2 User-friendly
More informationNFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code
Part 1 - GENERAL 1.1 DESCRIPTION OF WORK A. Design and installation of an engineered Kidde ECS Advanced Delivery Systems (ADS), clean agent/waterless fire suppression system employing DuPont FM-200 agent,
More informationOHIO BOARD OF BUILDING STANDARDS. Smoke Alarms and Fire Safety
OHIO BOARD OF BUILDING STANDARDS Smoke Alarms and Fire Safety Updated January 2016 2 UNDERSTANDING THE TERMINOLOGY Detector. An initiation device suitable for connection to a circuit that has a sensor
More informationAlarmSense 2-wire detection and alarm system. Product Guide
AlarmSense 2-wire detection and alarm system Product Guide Contents What is AlarmSense? 2 The purpose of AlarmSense 4 How AlarmSense works 4 Alarmsense Features 5 Detector removal monitoring 5 Priority/non-priority
More informationFIRE ALARM SYSTEM RECORD OF COMPLETION
FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. Protected Property Information Name of property: Description
More informationPerimeter Security System
TM Perimeter Security System The Next Generation Perimeter Security System ICRONET combines patented Southwest Microwave technology with microprocessor power and laptop computer convenience. It is a sophisticated
More informationSanitary Type Electronic Flow Switches
Industries Pharmaceutical Sanitary Type Electronic Flow Switches Food and Beverage Biotechnology Semiconductor Water Treatment S Series Ameritrol, Inc. Instruments and Controls Features No Moving Parts
More informationFIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.
Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's
More informationQCS 2014 Section 23: Fire Fighting and Fire Alarm Systems Page 1 Part 01: General
QCS 2014 Section 23: Fire Fighting and Fire Alarm Systems Page 1 Part 01: General 1 GENERAL... 2 1.1 INTRODUCTION... 2 1.1.1 Scope 2 1.1.2 General 2 1.2 REGULATIONS... 2 1.2.1 Electrical Installations
More informationUFGS-28 33 00.00 40 (February 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-28 33 00.00 40 (February 2014) ----------------------------------- Preparing Activity: NASA Superseding UFGS-28 33 00.00 40 (February 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS
More informationOPAL TM Detector range
OPAL TM Detector range Data Sheet The revolutionary OPAL range delivers a totally new detector platform incorporating an advanced digital protocol. The advanced protocol delivers more devices on the loop
More informationBUILDING OWNERS - SERVICE RELATED ISSUES FOR FIRE ALARM SYSTEMS
BUILDING OWNERS - SERVICE RELATED ISSUES FOR FIRE ALARM SYSTEMS Owners have numerous responsibilities as it pertains to the maintenance and operation of a building s fire safety equipment. The liabilities
More informationABB Stotz-Kontakt GmbH ABB safe&smart Project planning of security systems
ABB Stotz-Kontakt GmbH ABB safe&smart Project planning of security systems Content Introduction Preventing unauthorized access by perimeter surveillance Monitoring unauthorized access by indoor surveillance
More informationBold items are particular to the City of Euless
EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 2/12 Fire Chief Wes Rhodes Fire Marshal Paul Smith EFD-FMO 3-2 2009 International Fire & Building Code as Amended NFPA Standards Adopted
More informationSECTION 16700 FIRE ALARM SYSTEM
SECTION 16700 FIRE ALARM SYSTEM PART ONE: GENERAL 1.1 GENERAL REQUIREMENTS A. Definition of Work : This section of the specification includes the furnishing, installation, connection and testing of the
More informationZone B: comprises of NOC room, reception area, Help Desk area, Call Centre, Testing/Monitoring room. This zone requires approximately 1500 sq. feet.
Annexure 1 Best practices and Guidelines to Physical Security of the State Data Centre The Data Centre should ideally be built in a central location within the building complex. An approximate area of
More informationSECTION 16721 FIRE ALARM AND DETECTION SYSTEM
1. GENERAL 1.1. Related Documents: 1.2. Scope: 1.1.1. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements apply to the work specified in this
More informationSPACE TYPE: LABORATORY (WET) FOR CHEMISTRY AND BIOLOGY
SPACE TYPE: LABORATORY (WET) FOR CHEMISTRY AND BIOLOGY Construction Criteria The unit costs for (Wet) space types are based on the construction quality and design features in the following table. This
More informationElectronic Flow Switches
Industries Electronic Flow Switches Petrochemical Refining Oil Production Water Treatment Pharmaceutical Food and Beverage Pulp and Paper Power Production Gas Processing Mining Biotechnology Semiconductor
More informationUSER MANUAL, MAINTENANCE GUIDE & LOG BOOK
Software Versions: PANEL 1.52 & LOOP CARD 2.0 ONE TO FOUR LOOPS ANALOGUE ADDRESSABLE FIRE ALARM PANEL USER MANUAL, MAINTENANCE GUIDE & LOG BOOK #Doc No. GLT.MAN-135 TABLE OF CONTENTS WHAT TO DO IF THE
More informationINTREPID Perimeter Intrusion Detection System
TM INTREPID Perimeter Intrusion Detection System Next Generation Perimeter Protection icropoint Cable combines patented Southwest Microwave technology with microprocessor power and laptop computer convenience.
More informationmelbourne//australia data center specifications internet + intellectual property + intelligence tel: +61 2 9948 8888 fax: +61 2 9948 1111
internet + intellectual property + intelligence We thank you for the opportunity to work with you regarding your colocation needs in Melbourne,. We can colocate standard rack-mountable servers or other
More informationElement D Services Plumbing
Medical Vacuum and Gas PART 1 - GENERAL 1.01 OVERVIEW A. This section addresses medical vacuum, waste anesthetic gas disposal, compressed air, oxygen, nitrous oxide, nitrogen and carbon dioxide systems.
More informationFIRE ALARM SYSTEM RECORD OF COMPLETION
FUNDAMENTALS OF FIRE ALARM SYSTEMS 72 33 FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. PROTECTED PROPERTY
More informationFSD Circular Letter No. 7/95 Automatic Fire Detection System - Design and Maintenance Considerations
Our Ref.: 1 5 (49) in FPB 314/07 III FIRE SERVICES DEPARTMENT FIRE PROTECTION COMMAND FIRE SERVICES HEADQUARTERS BUILDING, No. 1 Hong Chong Road, 5/F., Tsim Sha Tsui East, Kowloon, Hong Kong Your Ref.:
More informationPremier M Plus & Infinity 8
25 Years of Manufacturing Excellence Premier M Plus & Infinity 8 Conventional Fire Alarm Systems 007 Assessed to ISO 9001: 2008 Certificate number 330 Premier M Plus 8-24 Zone Conventional Fire Alarm Panel
More information