Class II Based Signalling Power Supplies. Tahir Ayub Senior Design Authority Engineer IP Signalling, Signalling Innovations Group

Size: px
Start display at page:

Download "Class II Based Signalling Power Supplies. Tahir Ayub Senior Design Authority Engineer IP Signalling, Signalling Innovations Group"

Transcription

1 Class Based Signalling Power Supplies Tahir Ayub Senior Design Authority Engineer P Signalling, Signalling nnovations Group 1

2 Signalling Power Systems Utility ntakes Signalling Supply Point (SSP), Principal Supply Point (PSP) Signalling Power Distribution System nterface to final Signalling Loads Date Tahir Ayub Railway LV Systems 2

3 Signalling Distribution System Utility PSP SP LOC Asset

4 T System Operation Line side Equipment PSP/SSP 650V PSP 400/650 TX Power Enclosure C e C e C e C e C e C e 650/110 Tx 325V 325V Signaling Load Earthing System (R A )

5 T ndividual irst ault (ECP) Line side Equipment 650V R PSP 400/650 TX Power Enclosure C e C e C e C e C e C e 650/110 Tx Signaling Load Earthing System (R A ) Elevated Voltage between exposed conductive part and earth dependant on cable length and impedance of Ra. Very unlikely to exceed 60V.

6 T ndividual irst ault (Cable) Line side Equipment 650V PSP 400/650 TX R Power Enclosure C e C e C e C e C e C e 650/110 Tx Signaling Load Earthing System (R A ) Very Small Residual risk of Direct Contact on exposed cables. The risk is consistent with installations with unarmoured cables

7 T ndividual Second ault R PSP 400/650 TX R Residual risk of Direct Contact on exposed cables. The risk is consistent with installations with unarmoured cables

8 T ndividual Second ault (ECP) R PSP 400/650 TX R Vt Vt Vt Touch Voltage ault Current Elevated Voltage between Exposed Conductive Part and Earth likely to be very small (<60V)

9 T ndividual Second ault (Same ECP) R PSP 400/650 TX R Vt System protection not rated to disconnect on L-L or 2 L-E fault Vt Touch Voltage ault Current Elevated Voltage between exposed conductive parts and earth likely to be > 60V

10 T ndividual Line to Line ault R PSP 400/650 TX Protection must operate before thermal damage Vt Touch Voltage ault Current

11 T Collective System Line side Equipment 1 Line side Equipment X R PSP 400/650 TX Collective earth Power Enclosure 650/110 Tx Circuit Protective Conductor (CPC) Other LOC or REB nstallations Power Enclosure 650/110 Tx CPC PSP Earthing System Signaling Load Signaling Load Earthing System Typically 10 Ohms (SS8503) Earthing System Typically 10 Ohms (SS8503)

12 T Collective irst ault (Cable) R PSP 400/650 TX CPC Vt Vt Vt Vt Vt Touch Voltage ault Current Elevated Voltage between Exposed Conductive Part and Earth likely to be very small (<60V). All location cases will see an elevated voltage. Vt dependant on local earth impedance and cable distribution length

13 T Collective Second ault R R PSP 400/650 TX CPC Protection must operate to manage lethal touch voltages Vt Vt Vt Vt Vt Touch Voltage ault Current Elevated Voltage between Exposed Conductive Part and Earth likely to be very lethal (>60V) and is dependant on voltage divider produced by current passing through the CPC and Local earth. This could reach half system voltage depending on all location cases. Vt dependant on local earth impedance and cable distribution length

14 T Collective Second ault (CPC Optimisation) R R PSP 400/650 TX CPC Protection must operate to manage lethal touch voltages Vt Vt Vt Vt Local Earth mpedance utilised to optimise CPC Vt Touch Voltage ault Current Elevated Voltage between Exposed Conductive Part and Earth likely to be very lethal (>60V) and is dependant on voltage divider produced by current passing through the CPC and Local earth. This could reach half system voltage depending on all location cases. Vt dependant on local earth impedance and cable distribution length. f Local earth is not maintained then the elevated voltage could be lethal at the ECP.

15 T Collective Line to Line ault R PSP 400/650 TX CPC Protection must operate before thermal damage Vt Touch Voltage ault Current

16 Class Engineering Strategy Engineering Strategy Reduced CAPEX costs without reducing safety mprovement in Personnel Safety Reduction in System Risk Compliant to Standards Reduced Maintenance Burden Greater Tolerability to DC Corrosion Simplified Earthing and Bonding in AC Electrified Areas Ability to integrate into Legacy Systems

17 Class Proposal Reduce the probability of insulation failure in the LOCs and REBs to a negligible level so that power supply equipment enclosures need not be earthed for protection, so earthing or bonding to a CPC is not necessary. Utilising Class Equipment as a protective measure against electric shock Utilising a 2-core cable Distribution Strategy in place of a 3-core Strategy Realise the opportunity of complying with the requirements of BS 7671 Realise the opportunity of reducing costs associated with signalling power supplies

18 Class Strategy No Circuit Protective Conductor (CPC)

19 Class Strategy Double nsulation or Reinforced nsulation

20 Class Scope The Class Based Design Solution is to be implemented into: New Build Signalling Power Distribution Systems Existing Signalling Power Distribution Systems [3-core Armoured cable - CPC based system] Legacy Signalling Power Distribution Systems [2-core Unarmoured cable system]

21 Design Strategy Location Case/REB Equipment Class Switchgear Housings Class Signalling Transformers Encased Cabling between Class Switchgear and Class Signalling Transformer Cable Consumables (Glands, Joints, Terminations etc) Distribution Equipment 2 Core Enhanced Unarmoured Cable OR 2 Core Armoured Solid Bonded Cable

22 Solid Bonded Armoured Cable Solution EPR M Line side Equipment 1 BS 5467 Armoured Cable Line side Equipment X PSP 400/650 TX Gapped MET Class Power Enclosure Class 650/110 TX MET Class Power Enclosure Class 650/110 TX Signaling Load Signaling Load Earthing System (R A ) Earthing System (R A )

23 Enhanced Unarmoured Cable Solution EPR M Line side Equipment 1 Enhanced Unarmoured Cable Line side Equipment X PSP 400/650 TX Class Power Enclosure Class Power Enclosure MET Class 650/110 TX MET Class 650/110 TX Signaling Load Signaling Load Earthing System (R A ) Earthing System (R A )

24 Risk Assessment Results Risk of electrocution inside the LOC will, in practical terms, be removed by the introduction of Class equipment. Power cable options ranked in order of safety are as follows: 1.Armoured, solid bonded (=1 st ) 2.Enhanced unarmoured (=1 st ) 3.Armoured, resistance bonded 4.Armoured, direct bonded Other performance factors considered: Conclusion Reliability, Availability, Maintainability, Logistics and Whole-Life Costs. The Enhanced Unarmoured Cable option presents the highest overall level of Safety.

25 Legacy, Existing and Class Schemes Stage 1 Basic Comparison Table eature Legacy Existing Class Safety < Norm > Availability of supply = Norm > Compliance with Standards N Y Y Maintenance burden > Norm* < Ease of fault location = Norm = Resilience to corrosion > Norm > mmunity to stray a.c. currents > Norm > * Assumes design relies on earth electrodes as well as CPC to control touch voltages 25 Document Title 18 ebruary 2014

26 Maintenance Comparisons with Legacy and Existing Systems Maintenance factor Solid Bonded Armoured Cable (Class ) Enhanced Unarmoured Cable (Class ) 1 st inspection Reduced dependency on LOC electrode condition No dependency on LOC electrode condition Periodic inspection Reduced dependency on LOC electrode condition Armour continuity/loop impedance test required No dependency on LOC electrode condition Mid life degradation Reduced dependency on LOC electrode condition Armour/gland corrosion No dependency on LOC electrode condition Cable troughs and ducts maintained in good order mpact of possession restriction No impact No impact

27 PRAMS Conclusion Cable options ranked in descending order of preference PRAMS ranking of cable options 0 = lower, 1 = higher Performance Reliability/Availability Maintainability Personnel Safety System Enh UnArm Arm solid

28 Cable mpact & Crush Tests mpact Tests Crush Tests

29 Cable Damage Tests mpact Tests Armoured Cables maximum 6 impacts to failure Enhanced Unarmoured Cables 26 impacts, no failure Crushing tests Armoured Cables maximum 1.2 tonnes to failure Enhanced Unarmoured Cables, minimum 2.2 tonnes to failure The tests showed that the Enhanced Unarmoured Cable design has greater resistance to impact and crushing faults than a standard Armoured cable.

30 Safety Case The update of the Safety Case from Stage 1 was undertaken to incorporate the results of the MECA and PRAMS analysis The report presents evidence that the project has reached a stage where the identified design options, may be selected for detailed design. Conclusions There is no identified safety reason to prevent the design development stage of Class Equipment using Enhanced Unarmoured Cable proceeding. t is important to recognise that Armoured Solid Bonded Cables remain a viable alternative both in terms of risk and standards compliance however, MECA analysis identified the highest failure mode criticality is associated with the use of Armoured Cable.

31 New Standards NR/L2/ELP/27408 Product Specification for Signalling Power Distribution Cables NR/L2/ELP/27409 Product Specification for unctional Supply Points (SP) NR/L2/SG/30007 [ssue: 2] Product Specification for Power Transformers for Signalling Systems NR/L2/ELP/27410 Specification for Class Based Signalling Power Distribution Systems

32 solating Overcurrent TX Device System Transformation nsulation Monitor Enhanced Unarmoured Cable Enhanced Unarmoured Cable Enhanced Unarmoured Cable PSP nstallation Class SP Switchgear Assembly Conduit System Class Hybrid SP solating Transformer Signalling Load Signalling Load PSP Earthing System Signalling Earthing System Signalling Earthing System Date

33 nnovating through Collaboration Date

PROTECTION AGAINST ELECTRIC SHOCK by John Ware

PROTECTION AGAINST ELECTRIC SHOCK by John Ware 16 become live under fault conditions. The potential of the metal enclosure is higher than that of the main earthing terminal of the installation (and that of Earth) because of a potential difference created

More information

DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations)

DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) DETAILS OF THE CLEINT Client and address ADDRESS OF THE INSTALLATION Installation

More information

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting 12 SOLAR PHOTOVOLTAIC POWER by John Ware IT IS PLANNED for BS 7671:2008 to include a new Section 712 providing additional requirements for safety applicable to solar photovoltaic (pv) power supply systems.

More information

Enphase Microinverters and Ungrounded Renewable Energy Systems: Canadian Electrical Code Compliance

Enphase Microinverters and Ungrounded Renewable Energy Systems: Canadian Electrical Code Compliance WHITE PAPER Enphase Microinverters and Ungrounded Renewable Energy Systems: Canadian Electrical Code Compliance Overview Enphase has developed a new microinverter family that includes the M250 and new

More information

4 IX D N E P P A Installation methods Current-carrying capacity and voltage drop for cables Reference method IET Wiring Matters

4 IX D N E P P A Installation methods Current-carrying capacity and voltage drop for cables Reference method IET Wiring Matters 8 Appendix 4 of BS 7671 by Mark Coles Appendix 4, Current-carrying capacity and voltage drop for cables and flexible cords, has seen significant changes with the publishing of BS 7671:2008. This article

More information

Interfacing electrification and system reliability. Earthing of AC and DC railways 4,10,13

Interfacing electrification and system reliability. Earthing of AC and DC railways 4,10,13 Interfacing electrification and system reliability Roger White Professional Head of Electrification and Plant Rail Abstract Integration is the term given to ensuring that the different elements of an electrified

More information

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV 1. SCOPE This document details PowerSystems requirements for electrical testing of HV Equipment up to and including 33kV. 2. ISSUE RECORD This is a Reference document. The current version of Controlled

More information

ELECTRICAL INSTALLATION CONDITION REPORT (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations)

ELECTRICAL INSTALLATION CONDITION REPORT (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) Original Certificate DETAILS OF THE CLIENT Certificate reference: ELECTRICAL INSTALLATION CONDITION REPORT (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) Name: Address: PURPOSE

More information

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5 White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code June 2015 Revision 1.5 Shalhevet Bar-Asher; SolarEdge Technologies, Inc. Bill Brooks, PE; Brooks Engineering LLC

More information

Fault location on power cables. Fault location on power cables

Fault location on power cables. Fault location on power cables Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 01. Introduction Fault location on communication and power cables

More information

chapter8 Testing and commissioning Unit 2 outcome 2

chapter8 Testing and commissioning Unit 2 outcome 2 Testing and commissioning chapter8 Unit 2 outcome 2 It is important that electricians are not just able to construct; they should also be able to recognise faults and take action to help prevent them.

More information

CHECKING AND TESTING ELECTRICAL INSTALLING WORK

CHECKING AND TESTING ELECTRICAL INSTALLING WORK CHECKING AND TESTING ELECTRICAL INSTALLING WORK Department of Consumer and Employment Protection Energy Safety Preface It is a requirement of the Electricity (Licensing) Regulations 1991 that all electrical

More information

GroundRod AC Substation Earthing Tutorial

GroundRod AC Substation Earthing Tutorial 1 GroundRod AC Substation Earthing Tutorial 1. Functions of an earthing system The two primary functions of a safe earthing system are: To ensure that a person who is in the vicinity of earthed facilities

More information

HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE

HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE Appendix B-2 - Electrical Safety In Design Final Report TECHNOLOGIES THAT REDUCE LIKELIHOOD OF INJURY FROM ELECTRICAL HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE The following are technologies that reduce

More information

SURGE PROTECTIVE DEVICES

SURGE PROTECTIVE DEVICES SURGE PROTECTIVE DEVICES 1. INTRODUCTION In order to ensure safety of people, protection of equipment and, to a certain extent, continuity of supply, insulation co-ordination aims at reducing the likelihood

More information

GUIDANCE ON ELECTRICAL INSPECTIONS

GUIDANCE ON ELECTRICAL INSPECTIONS GUIDANCE ON ELECTRICAL INSPECTIONS Electricity Electricity is a versatile and convenient source of energy. However, it can be potentially dangerous if the system has not been properly designed, installed,

More information

ELECTRICAL SAFETY Information Bulletin

ELECTRICAL SAFETY Information Bulletin ELECTRICAL SAFETY Information Bulletin January 2016 CEC-10 [rev-9] Page 1 of 8 CANADIAN ELECTRICAL CODE SUBJECT: Section 10 Grounding and Bonding Rule 10-204 Grounding Connections for Alternating-Current

More information

EARTHING AND BONDING AT SECONDARY SUBSTATIONS

EARTHING AND BONDING AT SECONDARY SUBSTATIONS DISTRIBUTION CONSTRUCTION MANUAL SECTION 4 - SUBSTATIONS ISSUE B SEPT 1996 4.4.4 EARTHING AND BONDING AT SECONDARY SUBSTATIONS 1 SCOPE This section of the Distribution Construction Manual lays down the

More information

Electrical Grounding. Appendix C

Electrical Grounding. Appendix C Appendix C Electrical Grounding Low-Voltage Equipment Grounding The most frequently cited Office of Safety and Health Administration (OSHA) electrical violation is improper occupational grounding of equipment

More information

Cable Size Selection for Energy Efficiency

Cable Size Selection for Energy Efficiency Cable Size Selection for Energy Efficiency Introduction The traditional method for determining the appropriate cable size for a particular installation involves the selection of the smallest size conductor

More information

Guidance for upgrading to GB4943.1-2011 (IEC 60950-1: 2005, MOD)

Guidance for upgrading to GB4943.1-2011 (IEC 60950-1: 2005, MOD) Guidance for upgrading to GB4943.1-2011 (IEC 60950-1: 2005, MOD) Note: This guidance document is a translation of official Chinese document which is issued by CQC (China Quality Certification Center) on

More information

Charging what can be more simple? SAE J1772

Charging what can be more simple? SAE J1772 Charging what can be more simple? SAE J1772 Charging What Can Be More Simple? We charge our electronic devices everyday Laptops Cell phones PDAs Bluetooth devices Power tools MP3 players Toys Other Why

More information

BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E

BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E Training is not a substitute for following corporate safety guidelines. Always refer to the latest safety

More information

6 ELECTRICAL PARAMETERS

6 ELECTRICAL PARAMETERS 6 ELECTRICAL PARAMETERS For power, low voltage and medium voltage cables, cross section nominal areas are calculated in taking into account several parameters as: permissible current carrying capacities

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to

More information

270526-TC Grounding and Bonding for Telecommunications Systems

270526-TC Grounding and Bonding for Telecommunications Systems 270526-TC Grounding and Bonding for Telecommunications Systems Part 1 - General Related Documents The following related sections of the OT standards shall also be applicable to this section. OT Engineer

More information

A B Brown. This sheet forms part of *Inspection Report Number/*Certificate Number NA/ * EC/ * PIR *Delete as applicable DB1 60898

A B Brown. This sheet forms part of *Inspection Report Number/*Certificate Number NA/ * EC/ * PIR *Delete as applicable DB1 60898 NAPIT Electrical Test Continuation Sheet Requirements for Electrical Installations BS 767 [IEE Wiring Regulations] and for Please complete all the unshaded areas. This sheet forms part of *Inspection Report

More information

Guide to the electrical parameter classifications of IEC 60950 and IEC 62368 safety standards

Guide to the electrical parameter classifications of IEC 60950 and IEC 62368 safety standards Guide to the electrical parameter classifications of IEC 60950 and IEC 62368 safety standards Abstract This Guide is an informative listing of selected terms and definitions found in IEC Glossary entry

More information

Grounding of Electrical Systems NEW CODE: Grounding and Bonding

Grounding of Electrical Systems NEW CODE: Grounding and Bonding Grounding of Electrical Systems NEW CODE: Grounding and Bonding Presented By Scott Peele PE Grounding of Electrical Systems Outline Defining the Terms Why should I Ground? Types of Grounding Systems Separately

More information

Givare NC-SRS 280 och 880

Givare NC-SRS 280 och 880 Givare NC-SRS 280 och 880 Aratron AB/Nordic Control, 02 03 SRS280SEALED ROTARY SENSOR PERFORMANCE ±2 Resistance ±20% Hysteresis (repeatability) Accuracy Applied voltage maximum Resolution Output smoothness

More information

Earthing Guidance Notes

Earthing Guidance Notes Central Networks Earthing Manual Section E2 Earthing Guidance Notes Version: 2 Date of Issue: September 2007 Author: Nigel Johnson Job Title: Earthing Specialist Approver: John Simpson Job Title: Head

More information

Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers

Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers 9229 Waterford Centre Dr. Bldg C, Suite 110 Austin, Tx 78758 Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers Current Version: 13 AC Modules are a new product

More information

EARTHING SYSTEM CALCULATION

EARTHING SYSTEM CALCULATION BAZIAN STEAL FACTORY S/S 132/11kV, 1x30/40MVA EARTHING SYSTEM CALCULATION Kurdistan Region Sulaimani May 2011 Bazian Steal Factory S/S 132/11kV, 1x30/40 MVA Contents: 1. Introduction... 3 2. List of references

More information

EDS 06-0017 CUSTOMER LV INSTALLATION EARTHING DESIGN

EDS 06-0017 CUSTOMER LV INSTALLATION EARTHING DESIGN THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE Document Number: EDS 06-0017 ENGINEERING DESIGN STANDARD EDS 06-0017 CUSTOMER LV INSTALLATION EARTHING DESIGN Network(s):

More information

By Mark Coles. This article looks at the temporary use of portable generators in floating, earthed and reference-earthing scenarios.

By Mark Coles. This article looks at the temporary use of portable generators in floating, earthed and reference-earthing scenarios. 16 Operation of portable generators Operation of portable generators By Mark Coles This article looks at the temporary use of portable generators in floating, earthed and reference-earthing scenarios.

More information

Are you aware. Outline

Are you aware. Outline Electrical Safety of Medical Equipment Hasan Al-Nashash School of Engineering American University of Sharjah (AUS) 1 Are you aware Electrocutions are the 5th leading cause of accidental death in the U.S.

More information

David O Brien, CMP Products (David.OBrien@cmp-products.com)

David O Brien, CMP Products (David.OBrien@cmp-products.com) David O Brien, CMP Products (David.OBrien@cmp-products.com) 1) Main Function of Cable Glands 2) Common Issues with Cable Glands 3) Compliance / Standards, changing times 4) How do we select Cable Glands?

More information

Changing industry standards: friend or foe?

Changing industry standards: friend or foe? Changing industry standards: friend or foe? In 1998, Google was founded, the first Apple imac was introduced and the legendary Windows 98 was released by Microsoft. In a less glamorous but equally important

More information

A Guide to 17th Edition Testing

A Guide to 17th Edition Testing Seaward, Bracken Hill, South West Industrial Estate, Peterlee, County Durham, SR8 2SW United Kingdom Tel: +44 (0) 191 586 3511 Fax: +44 (0) 191 586 0227 Email: sales@seaward.co.uk Web: www.seaward.co.uk

More information

Network Standard Advice No. 1420C 9/6/2011

Network Standard Advice No. 1420C 9/6/2011 Network Standard Advice No. 1420C 9/6/2011 TO: Customers, Service Providers and Ausgrid Staff. Advisory Note on Changes to the Use of 11kV Cable Types. Introduction This Network Standard Advice (NSA) provides

More information

Manual Ranging MultiMeter

Manual Ranging MultiMeter Owner s Manual Manual Ranging MultiMeter Model 82345 CAUTION: Read, understand and follow Safety Rules and Operating Instructions in this manual before using this product.! Safety! Operation! Maintenance!

More information

MEM10019 Select circuit protection devices by type and rating, fit to switchboards and install earthing

MEM10019 Select circuit protection devices by type and rating, fit to switchboards and install earthing MEM10019 Select circuit protection devices by type and rating, fit to switchboards and install earthing Release: 1 MEM10019 Select circuit protection devices by type and rating, fit to switchboards and

More information

Cables, Cable Laying & Accessories Manual

Cables, Cable Laying & Accessories Manual Distribution Business Cables, Cable Laying & Accessories Manual Database ref: File Ref: Title Page & Revision Log For Cables & Access v4 - Nov 2003.doc Manual Name: Cables & Accessories Manual Version

More information

Listed are common requirements that apply to existing solar installations when altered, added to or reconfigured.

Listed are common requirements that apply to existing solar installations when altered, added to or reconfigured. SOLAR ALTERATIONS REQUIREMENTS August 2015 These requirements address typical alterations to solar installations; they cannot address every scenario. In Victoria, an alteration to a solar installation

More information

Gas Discharge Tubes GTCX26-XXXM-R05 Series

Gas Discharge Tubes GTCX26-XXXM-R05 Series Raychem Circuit Protection 6mm 2Pole GDTs (ceramic gas discharge tubes), are commonly used to help protect sensitive telecom equipment such as communication lines, signal lines and data transmission lines

More information

Evaluating Water-Damaged Electrical Equipment

Evaluating Water-Damaged Electrical Equipment Evaluating Water-Damaged Electrical Equipment 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been exposed to water through flooding, fire

More information

National Craft Assessment and Certification Program S P E C I F I C A T I O N S

National Craft Assessment and Certification Program S P E C I F I C A T I O N S National Craft Assessment and Certification Program S P E C I F I C A T I O N S INDUSTRIAL ELECTRICIAN V4 ELEC26_O4 Released September 2013 Focus Statement An Industrial Electrician must be able to interpret

More information

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER

More information

Evaluating Water-Damaged Electrical Equipment

Evaluating Water-Damaged Electrical Equipment Evaluating Water-Damaged Electrical www.nema.org Evaluating Water-Damaged Electrical 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been

More information

EDS 06-0016 LV NETWORK EARTHING DESIGN

EDS 06-0016 LV NETWORK EARTHING DESIGN THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE Document Number: EDS 06-0016 ENGINEERING DESIGN STANDARD EDS 06-0016 LV NETWORK EARTHING DESIGN Network(s): EPN, LPN, SPN

More information

EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM

EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM INSTALLATION MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0) 1282 717273

More information

Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time

Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time Trial Exams C Standards and Regulations Examination No: GH-08-C- This test is intended to gauge your knowledge of essential information contained within AS/CA S009:2013. To qualify for an allpication to

More information

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Title MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Duration 5 days Training Date MV, HV and EHV Switchgear Testing & Commissioning 5 20 24 Apr $3,750 Dubai, UAE In any of the 5 star

More information

Evaluating Water-Damaged Electrical Equipment

Evaluating Water-Damaged Electrical Equipment Evaluating Water-Damaged Electrical Equipment 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been exposed to water through flooding, fire

More information

CUSTOMER REQUIREMENTS AT POWER SUBSTATIONS

CUSTOMER REQUIREMENTS AT POWER SUBSTATIONS CUSTOMER REQUIREMENTS AT POWER SUBSTATIONS Customer Handout Date Aug 2, 2010 Version 1.0 File Name Customer Requirements At Power Substations Document Id Outside Plant Engineering 1 Table Of Contents 1.0

More information

Level 3 Certificate in the Certification of Electrical Installations (Design, Erection and Verification of Electrical Installations) (2391-20)

Level 3 Certificate in the Certification of Electrical Installations (Design, Erection and Verification of Electrical Installations) (2391-20) Level 3 Certificate in the Certification of Electrical Installations (Design, Erection and Verification of Electrical Installations) (2391-20) www.cityandguilds.com March 2007 Version 1.0 Qualification

More information

Instruction Bulletin. MCS025 Sync-Check Module Installation Sheet

Instruction Bulletin. MCS025 Sync-Check Module Installation Sheet Instruction Bulletin 63230-216-244B1 LaVergne, TN, USA MCS025 Sync-Check Module Installation Sheet Retain for future use. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Only qualified electrical

More information

chapter6 Basic electrical circuitry and applications Unit 2 Outcome 3

chapter6 Basic electrical circuitry and applications Unit 2 Outcome 3 Basic electrical circuitry and applications chapter6 Unit 2 Outcome 3 The primary role of an electrician is the installation of electrical circuits and applications. In order to install any type of application,

More information

DIOCESE OF LINCOLN GUIDELINES

DIOCESE OF LINCOLN GUIDELINES DIOCESE OF LINCOLN GUIDELINES FOR ELECTRICAL INSTALLATIONS INSIDE CHURCHES Diocesan Advisory Committee for the Care of Churches Revised March 2006 Electrical Installations inside Churches As with all

More information

Screened cable and data cable segregation

Screened cable and data cable segregation December 2007 Screened cable and data cable segregation Can an armoured power cable be considered a screened cable and how does this relate to power and data cable segregation? The short answer is yes;

More information

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE 380/415/690 Volt AC 50/65/80/100 ka 1. Product Guide Low Voltage Motor Control Centre CONTSTRUCTION Continuous "poured in place" gasket

More information

AC and DC Drive System Installation Information

AC and DC Drive System Installation Information Purpose This document contains the Parker SSD Drives recommendations for installing drive systems. These instructions must be followed for safe and reliable operation. Instructions CODES AND REGULATIONS

More information

AFUMEX LSX LOW SMOKE ZERO HALOGEN SCREENED WIRING CABLES BS8436 BASEC APPROVED PRODUCT DATASHEET & APPLICATIONS GUIDE KEY BENEFITS:

AFUMEX LSX LOW SMOKE ZERO HALOGEN SCREENED WIRING CABLES BS8436 BASEC APPROVED PRODUCT DATASHEET & APPLICATIONS GUIDE KEY BENEFITS: PRODUCT DATASHEET & APPLICATIONS GUIDE BASEC APPROVED AFUMEX LSX LOW SMOKE ZERO HALOGEN SCREENED WIRING CABLES BS8436 KEY BENEFITS: BASEC approved for the full size range of BS8436 (1.0mm 2 to 2.5mm 2

More information

GROUND DETECTION CIRCUITS FOR STATIONARY APPLICATIONS (IN PLAIN DOWN TO EARTH LANGUAGE)

GROUND DETECTION CIRCUITS FOR STATIONARY APPLICATIONS (IN PLAIN DOWN TO EARTH LANGUAGE) GROUND DETECTION CIRCUITS FOR STATIONARY APPLICATIONS (IN PLAIN DOWN TO EARTH LANGUAGE) Matthew Theriault Designer Hindle Power Inc. Easton, PA SCOPE AND PURPOSE OF THE PAPER Why do we bother to monitor

More information

NZECP 14: 1995 ISSN 0114-0663 COVER PAGE

NZECP 14: 1995 ISSN 0114-0663 COVER PAGE NZECP 14: 1995 ISSN 0114-0663 COVER PAGE NZECP 14:1995 NEW ZEALAND ELECTRICAL CODE OF PRACTICE FOR CONTROL PROTECTION AND SWITCHBOARDS Issued by the Office of The Chief Electrical Engineer, Energy and

More information

Circuit Electrical Testing

Circuit Electrical Testing Safe Isolation Procedure Circuit Electrical Testing Site Safety Management It is essential from the outset that effective management and control of the system, apparatus and equipment used on site is achieved

More information

Current Probes. User Manual

Current Probes. User Manual Current Probes User Manual ETS-Lindgren L.P. reserves the right to make changes to any product described herein in order to improve function, design, or for any other reason. Nothing contained herein shall

More information

CAPACITOR BANK TESTING SWP

CAPACITOR BANK TESTING SWP 1. PURPOSE AND SCOPE The purpose of this Standard Work Practice (SWP) is to standardise and prescribe the method for testing Capacitor Banks including capacitors, tuning reactors and inrush limiting reactors.

More information

Insulation resistance

Insulation resistance The insulation resistance is particularly important for the prevention of damage and injury, and for the reliability of electrical systems and equipment. On the one hand it is basis for the protection

More information

R4D0-FB-IA* FieldBarrier. Features. Assembly. Function. Connection IN + - S OUT ... ... Spur 2. Spur 1. Zone 1. Zone 0

R4D0-FB-IA* FieldBarrier. Features. Assembly. Function. Connection IN + - S OUT ... ... Spur 2. Spur 1. Zone 1. Zone 0 FieldBarrier Features Assembly 8... 12 outputs Ex ia IIC, FISCO and Entity Advanced fault isolation and diagnostics at the spur FieldBarrier in Zone 1/Div. 2 Instruments in Zone 0...1/Div. 1 For FOUNDATION

More information

THE IMPORTANCE OF HIPOT ISOLATION ON INDUSTRIAL ETHERNET SWITCHES

THE IMPORTANCE OF HIPOT ISOLATION ON INDUSTRIAL ETHERNET SWITCHES THE IMPORTANCE OF HIPOT ISOLATION ON INDUSTRIAL ETHERNET SWITCHES THE IMPORTANCE OF HIPOT ISOLATION ON INDUSTRIAL ETHERNET SWITCHES What is Hipot? HIPOT is the short term for high potential (high voltage).

More information

Extend the Life of Existing Switchgear

Extend the Life of Existing Switchgear Extend the Life of Existing Switchgear January 2011/1910DB1002 by Hal Theobald, Product Manager Schneider Electric USA, Inc. Make the most of your energy SM Summary Introduction... p 3 Maintenance Requirements...

More information

employed to ensure the continuing reliability of critical systems.

employed to ensure the continuing reliability of critical systems. 4 Regulations 1989, Regulation 4, places a duty on employers to provide safe systems for their workers: Regulation 4 of the Electricity at Work Regulations 1989 Systems, work activities and protective

More information

Corporate Profile ROYAL. MODERN ROYAL ELECTRIC Ideal Power Solution MRE ELECTRICAL, INSTRUMENTATION & COMMUNICATION SYSTEMS

Corporate Profile ROYAL. MODERN ROYAL ELECTRIC Ideal Power Solution MRE ELECTRICAL, INSTRUMENTATION & COMMUNICATION SYSTEMS Corporate Profile MODERN ROYAL ELECTRIC Ideal Power Solution ROYAL MRE ELECTRICAL, INSTRUMENTATION & COMMUNICATION SYSTEMS MAJOR STOCKIST >>> CATHODIC PROTECTION CABLES >>> LOW VOLTAGE CABLES >>> MEDIUM

More information

reduction ore = metal oxides metal oxidation

reduction ore = metal oxides metal oxidation Cathodic Protection and Interferences René Gregoor Madrid, June 18 th and 19 th 2009 1 Cathodic protection and interferences Corrosion Cathodic protection Protection criterion ON potential measurements

More information

Krav til sikkerhed for sekundære batterier og installationer af batterier Del 2: Stationære batterier

Krav til sikkerhed for sekundære batterier og installationer af batterier Del 2: Stationære batterier Dansk standard DS/EN 50272-2 1. udgave 2001-08-10 Krav til sikkerhed for sekundære batterier og installationer af batterier Del 2: Stationære batterier Safety requirements for secondary batteries and battery

More information

FORMS for the 17th Edition

FORMS for the 17th Edition FORMS for the 17th Edition Usage and Reproduction of IEE Forms Subject to your agreement to the following conditions, you are permitted to, free of charge, photocopy and/or electronically manipulate the

More information

Removal of EP 20 10 00 02 SP High Voltage Cable

Removal of EP 20 10 00 02 SP High Voltage Cable TN 018: 2014 Technical Note For queries regarding this document standards@asa.transport.nsw.gov.au www.asa.transport.nsw.gov.au TN 018: 2014 Issued date 12 March 2014 Effective dates 12 March 2014 Subject:

More information

APPENDIX A PIN-OUT OF RJ12 / RJ45 CONNECTORS. RJ12 connectors

APPENDIX A PIN-OUT OF RJ12 / RJ45 CONNECTORS. RJ12 connectors APPENDIX APPENDIX A PIN-OUT OF RJ12 / RJ45 CONNECTORS RJ12 connectors Pin # 1 Signal Name Not Used 2 +TR Description + Data Line 3 +R Remote OFF Required or Remote OFF control 4 -TR 5 Not Used 6 RTN -

More information

Article 10 - ADMINISTRATIVE SECTION

Article 10 - ADMINISTRATIVE SECTION Article 10 - ADMINISTRATIVE SECTION 10.1 TITLE These Administrative Regulations along with the requirements included in the 2011 Edition of the National Electrical Code (NFiPA-70-2011) as adopted by the

More information

Permissible ambient temperature Operation Storage, transport

Permissible ambient temperature Operation Storage, transport The Sitras PRO combined DC protective unit and controller is used in the power supply for DC railways in mass transit and main-line systems up 3,000 V DC. It protects DC switch gear and contact line systems

More information

ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors

ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants Installation instructions Contents Key points of installation Before installation Installation Installation check

More information

PABIAC Safety-related Control Systems Workshop

PABIAC Safety-related Control Systems Workshop Health and and Safety Executive PABIAC Safety-related Control Systems Workshop KEY STANDARDS FOR ELECTRICAL & FUNCTIONAL SAFETY OF PAPERMAKING MACHINES: APPLICATION & USE Steve Frost HM Principal Electrical

More information

Regulation IO-6.0: Electrical Safety Regulations

Regulation IO-6.0: Electrical Safety Regulations Regulation IO-6.0: Electrical Safety Regulations 6.1 Workmanship & Material 6.2 Electrical Conductors 6.3 Overcurrent Protective Devices 6.4 Precautions against Earth Leakage and Earthfault Currents 6.5

More information

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw 4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and

More information

The easy way to build switchgear and controlgear assemblies in compliance with the regulations

The easy way to build switchgear and controlgear assemblies in compliance with the regulations The easy way to build switchgear and controlgear assemblies in compliance with the regulations A guide for partially type-tested switchgear and controlgear assemblies in compliance with EN 60 439 What

More information

www.klmtechgroup.com TABLE OF CONTENT

www.klmtechgroup.com TABLE OF CONTENT Page : 1 of 13 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia ELECTIRAL GROUNDING TABLE OF CONTENT

More information

BS 7671:2008+A3:2015 MODEL FORMS

BS 7671:2008+A3:2015 MODEL FORMS BS 7671:2008+A3:2015 MODEL FORMS Usage and Reproduction of IET Forms Subject to your agreement to the following conditions, you are permitted to, free of charge, photocopy and/or electronically manipulate

More information

Engineering Recommendation G81 - Part 1: Design and Planning

Engineering Recommendation G81 - Part 1: Design and Planning PRODUCED BY THE ENGINEERING DIRECTORATE OF THE ENERGY NETWORKS ASSOCIATION Engineering Recommendation G81 - Part 1: Design and Planning Issue 2 Ammendment 1 January 2008 Framework for design and planning,

More information

GUIDE TO THE MAINTENANCE, INSPECTION AND TESTING OF PORTABLE EQUIPMENT (ELECTRICAL APPLIANCES AND TOOLS) IN THE WORKPLACE

GUIDE TO THE MAINTENANCE, INSPECTION AND TESTING OF PORTABLE EQUIPMENT (ELECTRICAL APPLIANCES AND TOOLS) IN THE WORKPLACE GUIDE TO THE MAINTENANCE, INSPECTION AND TESTING OF PORTABLE EQUIPMENT (ELECTRICAL APPLIANCES AND TOOLS) IN THE WORKPLACE ET 215:2008 ELECTRO-TECHNICAL COUNCIL OF IRELAND 2008 Page 1 of 6 Published by

More information

A guide to our training courses and premises. 01444 872 145 www.electriciancourses4u.co.uk

A guide to our training courses and premises. 01444 872 145 www.electriciancourses4u.co.uk A guide to our training courses and premises Contents 3. About Us 4. Why Us? 5. Our Premises 6-16. Training Courses 6. Domestic Electrician Course 7. Domestic Electrician Package 8. 17th Edition Course

More information

1 General Responsibility. 1.1 Participants. 1.2 Documentation. 1.3 Lockout/Tagout

1 General Responsibility. 1.1 Participants. 1.2 Documentation. 1.3 Lockout/Tagout Electrical Safety Plan This plan establishes rules for both the design and operation of the LPRDS. These rules are intended to enhance the safety of the participants in the initial project and future users

More information

Release: 2. UEENEEJ194A Solve problems in low voltage refrigeration circuits

Release: 2. UEENEEJ194A Solve problems in low voltage refrigeration circuits Release: 2 UEENEEJ194A Solve problems in low voltage refrigeration circuits UEENEEJ194A Solve problems in low voltage refrigeration circuits Modification History Not Applicable Unit Descriptor Unit Descriptor

More information

Electrical Resistance Resistance (R)

Electrical Resistance Resistance (R) Electrical Resistance Resistance (R) Any device in a circuit which converts electrical energy into some other form impedes the current. The device which converts electrical energy to heat energy is termed

More information

Candidate Self-Assessment Checklist

Candidate Self-Assessment Checklist General Information This is a compulsory document which must be completed by all candidates due to undertake the AM2 Assessment of Occupational Competence and provided to the assessment centre prior to

More information

Elementary circuits. Resources and methods for learning about these subjects (list a few here, in preparation for your research):

Elementary circuits. Resources and methods for learning about these subjects (list a few here, in preparation for your research): Elementary circuits This worksheet and all related files are licensed under the Creative Commons Attribution License, version 1.0. To view a copy of this license, visit http://creativecommons.org/licenses/by/1.0/,

More information

High Voltage (HV) Electricity System Safety Rules and Associated Safety Guidance

High Voltage (HV) Electricity System Safety Rules and Associated Safety Guidance Annex I To Loughborough University (LU) Facilities Management (FM) Health and Safety Policy High Voltage (HV) Electricity System Safety Rules and Associated Safety Guidance 1. Introduction a. These Safety

More information

Variable speed drives for synchronous and asynchronous motors

Variable speed drives for synchronous and asynchronous motors Imptant infmation Altivar XXXXXX Variable speed drives f synchronous and asynchronous mots ATEX manual F ATEX applications in explosive gas atmosphere in the presence of combustible dust 0/010 S1A0 www.schneider-electric.com

More information

Securing your electrical installations Prisma,

Securing your electrical installations Prisma, Securing your electrical installations Prisma, an optimised solution for type tested low voltage switchboards up to 3200 A Table of contents Developing installation safety 4 Prisma P * Electrical switchboards

More information

ACTIV-8 PLUS Insulated Conductor Bar

ACTIV-8 PLUS Insulated Conductor Bar ACTIV-8 PLUS Insulated Conductor Bar A product made in Australia www.conductix.com.au ACTIV-8 PLUS ACTIV-8 is the most widely used and stocked conductor rail in use in Australia. It was designed by Conductix

More information