Twin-Cel Energy Recovery Systems Engineering Reference Guide

Size: px
Start display at page:

Download "Twin-Cel Energy Recovery Systems Engineering Reference Guide"

Transcription

1 Twin-Cel Energy Recovery Systems Engineering Reference Guide Reliable, high efficiency desiccant dehumidification systems 1

2 2

3 Table of Contents General Description...2 Operating Principle... 4 Enthalpy Recovery Advantages..6 Performance Estimating Summer... 7 Winter...8 Economic Analysis 10 Unit Drawings 11 Installation Notes...13 Sample Specifications

4 Kathabar Dehumidification Systems Kathabar Dehumidification Systems, Inc., the world leader in industrial humidity control, has manufactured dehumidification equipment for more than 75 years. The name "Kathabar," which is derived from Greek words meaning clean or pure air, describes what Kathabar equipment does best. The primary use of Kathabar is to provide precise and energy efficient air temperature and humidity control. Kathabar maintains the process or space at the required condition regardless of weather or process variations. The "bacteria-free" benefit of Air-to-Air Energy Recovery in Building HVAC The purpose of all air-to-air energy recovery systems is to reduce the energy costs required to air condition a building and to reduce the size of the heating and cooling plants required. Energy recovery systems reduce energy usage by preconditioning the ventilation air entering a building using the available energy in the exhaust air leaving the building. During the summer, hot/humid ventilation air is pre-conditioned using the relatively cool/ dry building exhaust air. During the winter, ventilation air is preheated/ Kathabar is an added feature to temperature and humidity control. Over the last 75 years, the design of Kathabar equipment has been continually evolving. Advances in heat/ mass transfer technology and construction materials have been incorporated. New product lines have been developed to serve the changing needs of industrial, institutional, and commercial users as well as to reflect changes in the cost and availability of energy. These energy cost and availability issues have resulted in the development of the Twin-Cel air-to-air enthalpy recovery system. humidified using the relatively warmer/ wetter exhaust air from the building. Use of air-to-air energy recovery equipment substantially reduces air conditioning energy costs. In addition, installation of air-to-air energy recovery equipment substantially reduces the installed size of heating and cooling equipment required to air condition a new building and, with Twin-Cel, eliminates humidifiers as well as their associated appurtenances, and controls. Types of Air-to-Air Energy Recovery Equipment There are two basic types of air-to-air energy recovery equipment: sensible heat devices and total heat or enthalpy devices. Sensible heat devices transfer only temperature between ventilation and exhaust airstreams. Examples are heat wheels, flat plate exchangers, and coil loops. Total heat devices transfer both temperature and moisture between airstreams. Examples are enthalpy wheels 2 and Twin-Cel. Figure 1 shows that enthalpy recovery allows much greater energy savings than recovery of sensible heat only. Generally in comfort conditioning applications, enthalpy recovery equipment will save about three times as much energy in summer and about 20% more energy in winter than sensible only equipment of the same effectiveness.

5 FIGURE 1 Energy Savings Comparison Sensible Only vs. Enthalpy Recovery SAVINGS WITH SENSIBLE RECOVERY ONLY ADDITIONAL SAVINGS WITH ENTHALPY RECOVERY VENTILATION AIR (SUMMER) SAVINGS WITH ENTHALPY RECOVERY Building Exhaust Air (Summer) AIR HUMIDITY, GRAINS/LB. SAVINGS WITH SENSIBLE RECOVERY ONLY Building Exhaust Air (Winter) VENTILATION AIR (WINTER) 20 The Twin-Cel system consists of one or more supply units pretreating building ventilation air and one or more exhaust units recovering energy from building exhaust air. In operation, supply and exhaust airstreams are scrubbed with a sorbent brine solution that can transfer both temperature and humidity between the airstreams. Enthalpy transfer between supply and exhaust airstreams is accomplished by continuously recirculating the solution between supply and exhaust air units. Building ventilation air is pre-cooled and dehumidified during warm weather, and pre-heated and humidified during cold weather. During mild spring and fall weather, air temperature leaving the supply unit can be limited to any desired value. During extremely cold weather, temperature of the ventilation air delivered by the supply Twin-Cel can be maintained 55 AIR TEMPERATURE F Operating Principle during the winter months at any desired value by adding heat with a solution heater. The relative humidity of the delivered air can be maintained at any value up to 80% by adding makeup water to the supply Twin-Cel. Combining the above control features, the Twin-Cel system can deliver air at a fixed temperature and humidity all winter, regardless of weather conditions (see Figure 2). The system in Figure 3 shows a simple arrangement utilizing one supply unit and one exhaust unit at different elevations. Typical variations include multiple supply or exhaust units and multiple unit systems with units at different elevations. A solution pump can often be eliminated in systems where the elevation difference between supply and exhaust units is great enough to overcome piping friction.

6 100 FIGURE 2 Twin-Cel Energy Recovery Delivered Air Temperature F Solution Heating Winter Operation Pumps Off (Null Cycle) Summer Operation Outside Air Temperature F 125 FIGURE 3 Twin-Cel System Schematic 4

7 Effect of Ventilation Air on Building HVAC Load The ventilation air load represents a substantial portion of the total air conditioning load. Figure 4 shows the percentage of total load represented by ventilation air for cooling and heating in a typical comfort conditioning system without energy recovery. In systems using 100% ventilation air, about 65% of the cooling load and 80% of the heating load is caused by the ventilation air at typical outside design conditions. In 10% ventilation air systems, about 15% of the cooling load and about 30% of the heating load is caused by the ventilation air. % of Total Load Caused by Ventilation Air FIGURE 4 Effect of Ventilation Air on Heating/Cooling Load HEATING COOLING % Ventilation Air Reduction in HVAC Load by Air-to-Air Energy Recovery % Reduction in Air Conditioning Load By Air-to-Air Energy Recovery FIGURE 5 Energy Savings of Air-to-Air Energy Recovery (Based on 65% Recovery Effectiveness) Summer Design % Ventilation Air Winter Design 100 Figure 5 shows the savings in heating and cooling energy requirements when air-to-air energy recovery equipment is applied to building ventilation air. Enthalpy recovery is shown with solid lines, and sensible only recovery is shown with dashed lines. Enthalpy recovery equipment effects about three times as much cooling load reduction as sensible only heat recovery equipment and about 20% more heating load reduction. * Dashed lines indicate savings with sensible recovery * Solid lines indicate savings with enthalpy recovery 100

8 Enthalpy Recovery Advantages Efficient Microbiological Decontamination Both Kathene and Kalsorb solutions are bactericidal and virucidal to most airborne microorganisms. This enables Twin-Cel systems to efficiently decontaminate both ventilation and exhaust airstreams. No Cross-Leakage Since ventilation and exhaust air are handled by separate Twin-Cel units, no cross-leakage of exhaust air to ventilation air can occur. Sensible and Latent Recovery from Remote Airstreams Coil loop systems can recover energy from remote airstreams, but are limited to sensible recovery only. Wheel-type units can recover both sensible and latent energy, but require that the exhaust air be ducted to the same location as the ventilation air, limiting design flexibility. Twin-Cel systems recover both sensible and latent energy from remote air streams. They handle ventilation air and exhaust air in separate units connected only with piping. The Twin- Cel units can be located wherever it is convenient in the air system design. Constant Delivered Air Temperature and Humidity All Winter When other air-to-air recovery equipment is used, an additional heating coil and humidifier are required during winter operation to deliver air at a constant temperature and humidity. Twin-Cel systems can automatically heat and humidify air to a constant delivered air temperature and humidity all winter. This is possible without additional pre-heat or reheat coils or humidifiers and their associated controls. Frost-Free Operation To prevent frosting on the exhaust air side, sensible-only recovery equipment usually must be operated at reduced recovery effectiveness during very cold weather. Wheel-type enthalpy recovery equipment usually requires pre-heating of ventilation air during very cold weather to prevent frost buildup in the wheel, which can block airflow. Twin-Cel systems are designed to operate continuously at outside air temperatures as low as -40 F without frosting, freezing, or icing. Twin-Cel systems do not require ventilation air pre-heating coils, regardless of the humidity of the building exhaust air. Insensitive to Static Pressure Wheel-type equipment requires that the proper static pressure balance be maintained between ventilation and exhaust air to minimize cross-leakage. This usually requires that ventilation and exhaust air fans be located where the density change of the air from summer to winter is greatest. This can affect the building air balance. Twin-Cel units are not affected by the static pressure of ventilation and exhaust airstreams. Ventilation and exhaust fans can be located wherever convenient in the air system for the simplest design. Large Airflow Capacities Several wheel-type units are required to handle airflows in the 80,000 CFM range. Multiple-wheel installations require complex field-built plenums which are costly, can limit maintenance access, and add design complexity. Up to 84,000 CFM can be handled by a single, factory-assembled Twin-Cel unit. This can significantly reduce installation costs, maintenance costs, and control complexity. 6

9 Summer Performance Estimation The enthalpy recovery performance of a Twin-Cel system during summer operation can be estimated using the graphs and procedure given below. The exact performance can be obtained through your Kathabar representative. The recovery effectiveness of a Twin-Cel system is primarily a function of the sensible heat ratio between the outside air and the building exhaust air. The sensible heat ratio can be calculated from the outside air and building air temperatures and humidities and using Figure 6. Example: Outside air 95ºF, 120 Gr/Lb, 50,000 CFM Building air 75ºF, 65 Gr/Lb, 45,000 CFM Air temperature difference (95ºF - 75ºF)= 20ºF Air humidity difference (120ºF - 65ºF) = 55 Gr/Lb From Figure 6, SHR = FIGURE 6 Sensible Heat Ratio (SHR) FIGURE 7 Enthalpy Recovery Effectiveness Air Humidity Difference (Gr/Lb) Air Temperature Difference ºF Effectiveness Sensible Heat Ratio (SHR) Once the sensible heat ratio has been determined, the enthalpy recovery effectiveness can be found using Figure 7. Example: For SHR = 0.36, effectiveness = 63% Effectiveness is always based on the smaller airflow. If the supply airflow is larger than the exhaust airflow, the supply effectiveness must be corrected: E SUPPLY = Exhaust Airflow x E FIG.7 = 45,000 x.63 = 56% Supply Airflow 50,000 Calculate Temperature and Humidity Delivered from the Supply Twin-Cel Unit T DEL = 95ºF -.56ºF(95ºF - 75ºF) = 83.8ºF W DEL = 120ºF -.56ºF(120ºF - 65ºF) = 89.2 Gr/Lb 7

10 Winter Performance Twin-Cel systems are usually installed with a winter solution heater and automatic water makeup in cold climates. This arrangement enables the Twin-Cel supply units to deliver air at a constant temperature and humidity all winter long, regardless of outside air conditions. Furthermore, dry steam humidifiers and preheat coils are not required, even under arctic weather conditions. The recovery effectiveness of a Twin-Cel system and the amount of solution heating required at winter design conditions can be estimated using a psychrometric chart and Figure 8 and the procedure given below. The exact performance should be obtained through your Kathabar representative. Example: Outside air 55,000 CFM at 0ºF, 4 Gr/Lb Exhaust air 50,000 CFM at 72ºF, 42 Gr/Lb (35% R.H.) Desired supply air at 52ºF, 42 Gr/Lb (73% R.H.) Airflow Ratio: Outside Air 55,000 Exhaust Air = 50,000 = 1.1 Enthalpy: h at 0ºF, 4 Gr/Lb = 0.6 BTU/Lb h at 72ºF, 42 Gr/Lb = 23.8 BTU/Lb h at 52ºF, 42 Gr/Lb = 18.5 BTU/Lb Enthalpy Ratio = h Supply ( ) = h Total ( ) = 0.77 From Figure 8, enthalpy recovery efficiency = 0.48 Heat into supply air = 55,000 x 4.5 x ( ) = 4,430,250 BTU/Hr Heat recovered = 0.48 x 50,000 x 4.5 x ( ) = 2,505,600 BTU/Hr Additional heat required = 1,924,650 BTU/Hr FIGURE 8 Winter Enthalpy Recovery Efficiency Enthalpy Ratio, h Supply h Total % 45% 50% 55% 60% Airflow Ratio, SCFM Supply SCFM Exhaust 8

11 Turndown Cycle The purpose of the turndown cycle is to prevent the system from delivering air to the building warmer than desired. This may occur during spring, fall, and warm winter weather. With the turndown cycle, no additional cooling is necessary to maintain desired delivered air temperature. Turndown is accomplished by reducing the recirculation rate of the solution in the system. An automatic turndown is controlled by the supply unit leaving air temperature controller and is staged with the solution heater steam valve. Staging the turndown with the solution heater ensures that the solution is never heated and in turndown at the same time. The turndown set point, which is the supply unit maximum winter leaving air temperature set point, is normally in the range of 50ºF - 60ºF. The turndown temperature is set 5ºF higher than the low temperature setting of the null cycle. This is done to prevent the system from operating when the energy recovery of the system is less than the energy required to run the solution pumps. Null Cycle The null period or null cycle occurs when the outside air temperature is nearly the same as the temperature of the air being exhausted from the building. This temperature range is normally between 50ºF - 70ºF. During this period, energy recovery could cause the leaving air to exceed the desired delivered temperature and humidity. Therefore, the solution pumps are automatically shut down during null cycle operation. Automatic shutdown and restart is controlled by an outside air temperature sensing controller. Outside Air Operating Cycle 55ºF and below Winter 55ºF - 75ºF Null 75ºF and above Summer Summer Operation During the summer operating cycle, the Twin-Cel system is used to cool and dehumidify the outside air entering the building. At this time, it is desirable to recover as much cooling energy as possible. To accomplish this, the supply unit leaving air temperature controller is bypassed and the solution turndown valve is opened fully. This maximizes solution flow between units and energy recovery between airstreams. If the outside air is very hot and dry, water makeup may be required. Fixed Level Units All Twin-Cel systems are designed with at least one Twin-Cel unit operating at a fixed solution level. Multiple fixed level Twin-Cel units are used when the system consists of more than two units. In operation, a modulating level controller (MLC) senses the solution level in the unit pump tank and controls a modulating valve in the Twin-CeI unit pump discharge line. This valve throttles the flow of solution, leaving the unit to keep it in balance with the solution entering the unit. Solution level is also monitored by a limit level controller (LLC) which controls safety functions such as high and low level. 9

12 Economic Analysis Kathabar can provide an estimate of annual utility cost savings and estimated payback for your Twin-Cel installation. This analysis is based on your specific capital and operating costs for utilities and ownership cost for the Twin-Cel equipment. The analysis uses ASHRAE TMY2 weather data, which is available for about 240 locations in the U.S., as well as the design airflows and temperature and humidity conditions specific to your application. A copy of this page may be used to transmit the data required to perform the analysis. This can be ed to sales@kathabar.com. Job name: Location: Engineer: Date: Summer outside design: Summer exhaust design: Winter outside design: Winter exhaust design: Desired winter supply: Supply airflow: Exhaust airflow: ºF, Gr/Lb ºF, Gr/Lb, %R.H. ºF, Gr/Lb ºF, Gr/Lb, %R.H. ºF, Gr/Lb CFM, Unit location CFM, Unit location Operating hours (check one): All day Days only Nights only Cost of owning refrigeration: Cost of operating refrigeration: Cost of owning heating plant: Cost of operating heating plant: Cost of electric power: $ /Ton $ /Ton/Hr $ /HP or MMBTUH $ /Therm $ /KW/Hr 10

13 Module Dimensions FIGURE 9 Unit Size, Airflow Rating, and Dimensions Horizontal Twin-Cel Vertical Twin-Cel UNIT SIZE AIRFLOW (CFM) DIMENSIONS (INCHES) MINIMUM MAXIMUM L H W B C D E F G 800 5,000 10, ,500 15, ,000 20, S 12,500 25, ,000 24, ,000 30, ,000 36, ,000 48, ,000 60, ,000 72, ,000 84, (Dimensions are approximate, for roughing-in) 11

14 UNIT SIZE * AIRFLOW (CFM) MIN. MAX. FIGURE 10 Engineering Data HORIZONTAL T.C. SHIP- PING WEIGHT (LBS) MAX. OPERAT- ING VERTICAL T.C. SHIP- PING MAX. OPERAT- ING PUMP ** 800 5,000 10,000 2,500 7,600 2,000 7, ,500 15,000 3,000 9,800 2,500 9, ,000 20,000 3,500 12,000 3,000 11, S 12,500 25,000 N/A N/A 4,000 14, ,000 24,000 5,400 14,500 4,800 13, ,000 30,000 6,200 17,000 5,600 16, ,000 36,000 7,200 19,800 6,400 18, ,000 48,000 9,000 25,100 7,900 23, ,000 60,000 10,700 30,300 9,400 28, ,000 72,000 12,400 35,500 10,800 33, ,000 84,000 14,300 40,900 12,400 38, * Smaller unit sizes and non-standard sizes are also available. ** Based on 200 ft. equivalent run of pipe, two units at the same elevation. *** Use air face area and actual airflow to determine unit pressure drop. H.P. PIPE SIZE 12

15 Installation Notes The following equipment is normally supplied by Kathabar: Supply and exhaust Twin-Cel units Turndown controls and hardware Winter solution heater and control valve (if required) Control panel Sensors Desiccant solution charge The following equipment may be required for a complete system installation but are not normally supplied by Kathabar: Ductwork Interconnecting solution piping Interconnecting electrical and control wiring Any insulation required Any sound attenuation and vibration isolation required Pre-installation Storage Equipment should be stored indoors or protected outdoors prior to installation. Site Preparation Supply and exhaust units should be set on a level concrete floor, housekeeping pad, or piers. Curbing is recommended with a floor drain located inside the curbing. At least three feet of maintenance clearance should be provided around the equipment. The floor should be sealed with an epoxy sealant before the equipment is set in place. Rigging and Handling Twin-Cel equipment should be lifted only from the bottom, using lifting lugs (if provided) or slings. Spreader bars should be used. Contact Kathabar Engineering for any additional advice you may require. Plenums and Ductwork Twin-Cel units are provided with a two and one-half inches flange at the air supply and discharge openings for connecting ductwork. Supply and discharge plenums should be bolted to the flange with minimum one-quarter of an inch thick closed-cell foam gasketing, supplied by Kathabar. Access doors must be provided in supply and discharge plenums for servicing diffusers and eliminators. Ductwork at the supply plenum should have a design air velocity of 1500 ft/ min or less. Ductwork at the exhaust plenum should have a design air velocity of 1000 ft/min or less. Solution Piping All pipe and fittings in contact with the solution must be CPVC or FRP. Black iron, galvanized and stainless steel pipe must not be used. CPVC piping should be schedule 80, Type IV, Grade I, 4120, in accordance with ASTM Standard Recommended FRP piping is Smith Green Thread or Fibercast Centricast III EP. Valves in the solution piping should be made of CPVC, FRP, or thermoplasticlined cast iron with a non-metallic disc. Contact Kathabar for more detailed materials and construction information, if required. Thermowells in the solution piping must be titanium (available from Kathabar). Stainless, galvanized carbon steel, and copper Thermowells must not be used. All pipe fittings should be socket fittings, and all connections with valves and other components must be flanged. Red rubber or neoprene full-face gaskets are recommended for flanged connections. 13

16 The piping must be supported so no stress is placed on connections to the equipment. Pipe supports and anchors must be installed in accordance with the pipe manufacturer s recommendations. It is important to constrain the piping to prevent lateral and longitudinal motion. If the piping cannot drain completely by gravity, low-point drains with lined metal or non-metallic hand valves must be provided. Insulation Twin-Cel exhaust units need not be insulated. Twin-Cel supply units and interconnecting solution piping need not be insulated unless the equipment is located in areas that will be maintained at 30% R.H. or higher during cold winter weather. If insulation is used, closedcell flexible rubber insulation at least one inch thick is recommended. Insulation exposed to direct sunlight should be covered or treated for ultraviolet resistance. Twin-Cel Sample Specifications The air-to-air enthalpy recovery equipment shall be a Twin-Cel liquid desiccant system as supplied by Kathabar Dehumidification Systems, Inc. The system shall be capable of transferring both sensible and latent energy between supply and exhaust airstreams. The supply and exhaust airstreams shall be handled by separate units. The manufacturer shall guarantee that there will be no cross-leakage of air between supply and exhaust airstreams, and no cross-contamination of dust or microorganisms between supply and exhaust airstreams. The system shall be capable of continuous operation at an outside air temperature as low as -40ºF without frosting, freezing, or icing, and without the need for air preheating or air bypass dampers of any kind. The system shall be capable of automatically conditioning the outside air to a fixed temperature and humidity throughout the winter, regardless of outside air conditions. Supply and exhaust units shall consist of a watertight housing containing the solution-to-air contact surface, solution distribution system and mist eliminator system, a freestanding pump assembly with tank, vertical sealless solution pump and motor, full-flow solution filter screen, and bypass polishing filter. The unit and pump tank housing shall be of vinylester FRP construction with fire retardant additive and UV stabilizer. Internal parts shall be of engineered plastics. The winter solution heater (if required) shall be of the plate-and-frame type, with a steel frame and tie bolts and titanium plates with EPDM gaskets. The heater shall be supplied complete with control valve. 14

17 Notes 15

18 673 Ontario Street Buffalo, NY KATHABAR / 16

Innovent LASER Packaged Fresh Air Conditioning Units

Innovent LASER Packaged Fresh Air Conditioning Units LASER Latent And Sensible Energy Reduction Latent And Sensible Energy Reduction For Outside Air Innovent LASER Packaged Fresh Air Conditioning Units Innovent LASER units provide both sensible and latent

More information

Bring the fresh in. Dedicated Outside Air Systems

Bring the fresh in. Dedicated Outside Air Systems Bring the fresh in. Dedicated Outside Air Systems The inside story on outside air. On average, we breathe in 3,400 gallons of air each day. Ambient indoor air pollution is a major problem, affecting health

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer

More information

Pool Dehumidification Basics

Pool Dehumidification Basics Copyright 2009 Wescor. All rights reserved. Permission granted to reproduce for personal and educational use only. When energy costs were low, many pool owners considered only first cost when choosing

More information

Mechanical Rooftop Custom Capabilities

Mechanical Rooftop Custom Capabilities Mechanical Rooftop Custom Capabilities Mechanical Construction Capabilities Price manufactures a wide range of custom gas heat and DX cooled units to meet your new construction and retrofit needs. In addition

More information

Glossary of Heating, Ventilation and Air Conditioning Terms

Glossary of Heating, Ventilation and Air Conditioning Terms Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment

More information

Dehumidification Frequently Asked Questions

Dehumidification Frequently Asked Questions Dehumidification Basics Why do you want to keep indoor Rh between 30-60%? ASHRAE recommends keeping the relative humidity in a home between 30-60% to limit the effects of many unwanted conditions and harmful

More information

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2

More information

HVAC Simplified Approach Option

HVAC Simplified Approach Option HVAC Simplified Approach Option Part I Project Address: City: HVAC System Designer of Record: Date: Zip: Qualification The building is 2 stories or less in height and has a gross floor area is less than

More information

SAM HOUSTON STATE UNIVERSITY

SAM HOUSTON STATE UNIVERSITY PART 1: GENERAL 1.01 General Requirements A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the

More information

Defining Quality. Building Comfort. Precision. Air Conditioning

Defining Quality. Building Comfort. Precision. Air Conditioning Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air

More information

CE6500 Energy Recovery Ventilator

CE6500 Energy Recovery Ventilator ADVANCED COMMERCIAL Energy Recovery Ventilator PRODUCT SPECIFICATIONS & TECHNICAL DATA Features NOMINAL CAPACITY 5500-7000 CFM CASING Double-wall cabinet White exterior paint, -gauge galvanized steel -gauge

More information

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com

More information

Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida

Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida Optimizing 100% Outside Air Systems with Heat Pipes Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida Introduction To meet increasingly rigorous building codes

More information

Answers to Your Questions from the Webinar

Answers to Your Questions from the Webinar 2008 Desert Aire and USA Swimming. Used by permission. Desert Aire & USA Swimming - Aquatics Webinar - Answers to Your Questions Answers to Your Questions from the Webinar Thank you for your interest in

More information

ENHANCED LABORATORY HVAC SYSTEM

ENHANCED LABORATORY HVAC SYSTEM ENHANCED LABORATORY HVAC SYSTEM INTRODUCTION Since the early 1980's the attention to more energy efficient laboratory designs has been on the rise due to the increase in energy cost and the emergence of

More information

Energy Recovery Ventilation Equipment

Energy Recovery Ventilation Equipment AHRI Standard 1060 (I-P) 2013 Standard for Performance Rating of Airto-Air Exchangers for Energy Recovery Ventilation Equipment IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not

More information

85 F 80 F 50% 75 F 70 F 73.0/61.8 45 F 10% Figure 1

85 F 80 F 50% 75 F 70 F 73.0/61.8 45 F 10% Figure 1 Feb. 07 INTRODUCTION: Wrap around heat pipes are air-to-air heat exchangers that are installed in the airstream upstream and downstream of a cooling coil to deliberately reduce the Sensible Heat Ratio

More information

1.2 Refrigerant Equipment. General

1.2 Refrigerant Equipment. General Part 1 General 1.1 Summary.1 Unless otherwise indicated, follow the standards below when specifying heating, ventilation and air conditioning (HVAC) work. These standards are not intended to restrict or

More information

Why Do I Need Precision Air Conditioning?

Why Do I Need Precision Air Conditioning? Why Do I Need Precision Air Conditioning? Executive Summary Today's technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air

More information

Lesson 36 Selection Of Air Conditioning Systems

Lesson 36 Selection Of Air Conditioning Systems Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section

More information

SWIMMING POOL AIR-HANDLING UNITS KU-DB Series

SWIMMING POOL AIR-HANDLING UNITS KU-DB Series SWIMMING POOL AIR-HANDLING UNITS KU-DB Series ME20 proklima 2 SWIMMING POOL AIR-HANDLING UNITS - KU-DB Series proklima 3 TABLE OF CONTENTS 1 Introduction page 3 2 Features page 4 SWIMMING POOL AREA t =

More information

HIGH EFFICIENCY RTU. www.reznorhvac.com HIGH EFFICIENCY, PACKAGED SPACE CONDITIONING. DX System IEER> 13.2 Gas Heat Efficiency > 92% Capacities Tons

HIGH EFFICIENCY RTU. www.reznorhvac.com HIGH EFFICIENCY, PACKAGED SPACE CONDITIONING. DX System IEER> 13.2 Gas Heat Efficiency > 92% Capacities Tons Capacities 10-25 Tons 100-400 MBH HIGH EFFICIENCY, PACKAGED SPACE CONDITIONING DX System IEER> 13.2 Gas Heat Efficiency > 92% HIGH EFFICIENCY RTU 30-120 kw 3,000-11,550 CFM Comfort Comfort is determined

More information

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same

More information

Commissioning - Construction Documents (Page 1 of 6)

Commissioning - Construction Documents (Page 1 of 6) Commissioning - Construction Documents (Page 1 of 6) A. General Information Climate Zone: Building Type: Conditioned Area (sf): Reviewer's Name: Reviewer's Agency: Note: Design Review for each system/subsystem

More information

Cooling Small Server Rooms Can Be. - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com

Cooling Small Server Rooms Can Be. - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com Cooling Small Server Rooms Can Be Inexpensive, Efficient and Easy - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com Server Rooms Description & Heat Problem Trends

More information

HVAC Calculations and Duct Sizing

HVAC Calculations and Duct Sizing PDH Course M199 HVAC Calculations and Duct Sizing Gary D. Beckfeld, M.S.E., P.E. 2007 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com An

More information

APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application

APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application APPLICATION GUIDE Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application Section Comparison of Latent Cooling Performance of Introduction Most commercial HVAC systems

More information

Controlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements. By Michael O. Davis, PE, November 2015

Controlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements. By Michael O. Davis, PE, November 2015 Controlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements By Michael O. Davis, PE, November 2015 Advised by Heat Pipe Technology Background: HVAC systems are often designed

More information

By Tom Brooke PE, CEM

By Tom Brooke PE, CEM Air conditioning applications can be broadly categorized as either standard or critical. The former, often called comfort cooling, traditionally just controlled to maintain a zone setpoint dry bulb temperature

More information

Hospital Application Guide. Cost-effective climate control for hospitals

Hospital Application Guide. Cost-effective climate control for hospitals Hospital Application Guide Cost-effective climate control for hospitals Munters is the world leader in dehumidification Munters is the largest manufacturer of dehumidifiers in the world. Since developing

More information

SECTION 23 81 43 HEAT PUMPS

SECTION 23 81 43 HEAT PUMPS SECTION 23 81 43 HEAT PUMPS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop heat pumps. 1.2 REFERENCES A. American Society of Heating, Refrigerating and Air-Conditioning Engineers:

More information

Johnson Air-Rotation Systems

Johnson Air-Rotation Systems AR Series TM Johnson Air-Rotation Systems Solution TM D Series TM FF Series TM 80/20 PR Series TM Johnson Air-Rotation systems announces a major addition to its product line, completing its line of high

More information

Operation and Installation Manual. Max Series

Operation and Installation Manual. Max Series Operation and Installation Manual Max Series Models 95MAX 155MAX 155ECM 155MAXRX 200MAX 200MAXRX MAXTOP 195DCS 300DCS 200ERV 200ERVD New Auto Dehumidistat Function prevents unwanted use of the dehumidistat

More information

APPLICATION GUIDE. Moisture Management in Waterborne Climate Systems

APPLICATION GUIDE. Moisture Management in Waterborne Climate Systems APPLICATION GUIDE Moisture Management in Waterborne Climate Systems Contents Introduction 3 WBCS Concept 3 Condensation 4 Moisture Sources in the Space 4 Impact of a High Moisture Load 5 Designing to Manage

More information

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating

More information

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01 GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per

More information

How and Why Mission- Critical Cooling Systems Differ From Common Air Conditioners

How and Why Mission- Critical Cooling Systems Differ From Common Air Conditioners How and Why Mission- Critical Cooling Systems Differ From Common Air Conditioners White Paper #56 Revision 2 Executive Summary Today's technology rooms require precise, stable environments in order for

More information

Total Heat Versus Sensible Heat Evaporator Selection Methods & Application

Total Heat Versus Sensible Heat Evaporator Selection Methods & Application Total Heat Versus Sensible Heat Evaporator Selection Methods & Application Scope The purpose of this paper is to provide specifying engineers, purchasers and users of evaporators in industrial refrigeration

More information

HVAC Checklist - Long Form

HVAC Checklist - Long Form HVAC Checklist - Long Form Page 1 of 14 Appendix B discusses HVAC system components in relation to indoor air quality. utside Air Intake Location pen during occupied hours? Unobstructed? Standing water,

More information

AIR SYSTEMS ENERGY SERIES Energy Recovery Wheels

AIR SYSTEMS ENERGY SERIES Energy Recovery Wheels AIR SYSTEMS ENERGY SERIES Energy Recovery Wheels APPLICATION GUIDE Supercedes: Nothing Form 102.20-AG6 (305) INTRODUCTION As fossil fuel reserves are depleted, the cost of energy continues to rise. According

More information

Energy Efficiency in Industrial HVAC Systems

Energy Efficiency in Industrial HVAC Systems Energy Efficiency in Industrial HVAC Systems Heating, ventilation and air conditioning (HVAC) constitutes up to 35 percent of energy used in manufacturing facilities. This fact sheet is geared towards

More information

Heat Recovery Dehumidification (HRD) system. Designed for municipal swimming pools

Heat Recovery Dehumidification (HRD) system. Designed for municipal swimming pools Heat Recovery Dehumidification (HRD) system Designed for municipal swimming pools A dehumidification and ventilation system with dynamic heat pump heat recovery to swimming pool water and air ENVIRONMENTAL

More information

Energy Efficiency. Energy Efficient Home Cooling:

Energy Efficiency. Energy Efficient Home Cooling: Energy Efficiency Energy Efficient Home Cooling: Choosing an air conditioning system is an important decision. A poor choice may be costly to purchase and operate and yet fail to provide the desired cooling

More information

ROOF TOP MOUNTED Air Handler Specification

ROOF TOP MOUNTED Air Handler Specification ROOF TOP MOUNTED Air Handler Specification PART 1: GENERAL (Model RT) Mechanical Specification 1.01 WORK INCLUDED A. Provide complete air handling unit(s) suitable for outdoor installation. Contractor

More information

Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment

Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment The heating, ventilation and cooling loads of typical commercial office space can range

More information

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates

More information

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715, 4658.4500 PLUMBING SYSTEMS; NEW CONSTRUCTION. Subpart 1. Installation. All plumbing systems must be installed and tested according to this chapter and chapter 4715, the Minnesota Plumbing Code. Subp. 2.

More information

Energy Efficient Building Design College of Architecture Illinois Institute of Technology, Chicago. Relative Humidities RH% 49.4. 0.

Energy Efficient Building Design College of Architecture Illinois Institute of Technology, Chicago. Relative Humidities RH% 49.4. 0. Psychrometrics Psychrometric Chart Relative Humidities RH% 49.4 100% 80% 0.030 Enthalpies 70% H btu/lb 46.5 0.028 85 Not to Scale 0.026 Humidity Numbers and Values 43.7 60% Ratios are approximate 0.024

More information

HVAC Characteristics. Test Space HVAC Characteristics

HVAC Characteristics. Test Space HVAC Characteristics HVAC Characteristics Information on the characteristics of the heating, ventilation, and air conditioning (HVAC) system(s) in the entire BASE building including types of ventilation, equipment configurations,

More information

Cooling Capacity CFM range @.5 in. w.c. (125 Pa)

Cooling Capacity CFM range @.5 in. w.c. (125 Pa) 96% AFUE, Single Stage, ECM Gas Furnace EASIER TO SELL 96% AFUE, all models all positions Xtra SEER ECM blower motor Supports two stage cooling units Dehumidification feature in cooling California NOx

More information

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES After studying this unit, the reader should be able to explain the purpose of the condenser in a refrigeration system. describe differences

More information

Solar air collectors for industry and larger halls S Ø. Efficient dehumidification and air heating for free...

Solar air collectors for industry and larger halls S Ø. Efficient dehumidification and air heating for free... Solar air collectors for industry and larger halls N S Ø Efficient dehumidification and air heating for free... This booklet contains information about SolarVenti Industrial air solar system. The system

More information

Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics

Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics A Presentation of Work in Progress 4 October 2006 in the Intelligent

More information

Example Retrocommissioning Measure: Opening Throttled Discharge Valves

Example Retrocommissioning Measure: Opening Throttled Discharge Valves Opening Throttled Discharge Valves This 21-story building, constructed in 1997, is located in Oregon and contains 589,000 gross square feet of mostly office occupancy. The HVAC system includes six large

More information

Increasing Natural Gas Boiler Efficiency by Capturing Waste Energy from Flue Gas

Increasing Natural Gas Boiler Efficiency by Capturing Waste Energy from Flue Gas Increasing Natural Gas Boiler Efficiency by Capturing Waste Energy from Flue Gas Mark Schiffhauer, ATSI Engineering Services Cameron Veitch, Combustion and Energy Systems Scott Larsen, New York State Energy

More information

Dedicated Outdoor Air Systems (D.O.A.S.)

Dedicated Outdoor Air Systems (D.O.A.S.) Commercial and Industrial Climate Control Systems Dedicated Outdoor Air Systems (D.O.A.S.) AMDOAS-1 What is it? Why use one? What are my options? Selection considerations Design steps What is it? A separate

More information

Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures

Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures Data Realty Colocation Data Center Ignition Park, South Bend, IN Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures Project Overview Data Realty is a data center service provider for middle

More information

Cooling Capacity CFM range @.5 in. w.c. (125 Pa)

Cooling Capacity CFM range @.5 in. w.c. (125 Pa) 96% AFUE, Two Stage ECM Gas Furnace EASIER TO SELL 96% AFUE, all models, all positions Two stage heating operation Xtra SEER ECM blower motor Supports two stage cooling units Dehumidification feature in

More information

M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A

M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A Bulletin 20-20.2 / July 2012 M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A ➀ ➁ ➂ Model Number Key M 2430 C L 1 - A - ➀ Unit Type M=Modular Nominal Capacity 2430=24000 to 30000

More information

PLUG and PLAY VRV Connection

PLUG and PLAY VRV Connection PLUG and PLAY VRV Connection All seasons Perfect c mfort Heating Air Conditioning Applied Systems Refrigeration Pricelist 2010 Air Handling Units for > VRV Indoor units and Air Handling Units on single

More information

HVAC Processes. Lecture 7

HVAC Processes. Lecture 7 HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump

More information

SINGLE PACKAGE VERTICAL AIR CONDITIONERS

SINGLE PACKAGE VERTICAL AIR CONDITIONERS SINGLE PACKAGE VERTICAL AIR CONDITIONERS AIR CONDITIONERS l HEAT PUMPS l ELECTRIC HEAT QUIETER BY DESIGN SIMPLE TO INSTALL CONCEALED INSTALLATION www.friedrich.com VERT-I-PAK ideal for extended stay properties,

More information

REGULATORS 175/153 Series

REGULATORS 175/153 Series 175/153 Series 175 HEATING 153 COOLING Watson McDaniel reserves the right to change the designs and/or materials of its products without notice. 2002 Watson McDaniel Company Revised 7/2002 175 / 153 Screwed

More information

COMMISSIONING OF HVAC SYSTEMS

COMMISSIONING OF HVAC SYSTEMS FORM CL-01 SYSTEMS / EQUIPMENT INCLUDED : SYSTEM STARTUP CHECKLIST I - PRE - STARTUP INSPECTION EQUIPMENT MOUNTING & SETTING CONTROL, INTERLOCK & POWER WIRING ALIGNMENT OF MOTORS & DRIVES PIPING, CONNECTIONS

More information

Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems

Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems If you're a designer or a BCA, this guidance on the energy efficiency of HVAC systems in commercial buildings may

More information

ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE

ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce

More information

saving energy in comfort Factsheet Recair Enthalpy

saving energy in comfort Factsheet Recair Enthalpy saving energy in comfort Factsheet Recair Enthalpy Introduction Enthalpy Exchanger The enthalpy exchanger is able to transfer both sensible heat and latent heat (moisture) from the cooled to the heated

More information

Equivalents & Conversion Factors 406 Capacity Formulas for Steam Loads 407 Formulas for Control Valve Sizing 408-409

Equivalents & Conversion Factors 406 Capacity Formulas for Steam Loads 407 Formulas for Control Valve Sizing 408-409 Engineering Data Table of Contents Page No. I II Formulas, Conversions & Guidelines Equivalents & Conversion Factors 406 Capacity Formulas for Steam Loads 407 Formulas for Control Sizing 408-409 Steam

More information

HVAC Systems: Overview

HVAC Systems: Overview HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct

More information

Air Conditioner Water Heater - A Product of HotSpot Energy LLC

Air Conditioner Water Heater - A Product of HotSpot Energy LLC Air Conditioner Water Heater - A Product of HotSpot Energy LLC PLEASE READ THIS BEFORE YOU INSTALL THE UNIT 1. This air conditioner must be installed and/or repaired by a qualified technician. If you perform

More information

Makeup Air For Exhaust Systems In Tight Houses. Tony Jellen Engineering Projects

Makeup Air For Exhaust Systems In Tight Houses. Tony Jellen Engineering Projects Makeup Air For Exhaust Systems In Tight Houses Tony Jellen Engineering Projects PA Housing & Land Development Conference February 23, 2012 Effects of Kitchen Ventilation on Residential Dwellings Anthony

More information

Glossary of HVAC Terms

Glossary of HVAC Terms Glossary of HVAC Terms Heating, Ventilation and Air Conditioning (HVAC) is a major sub- discipline of mechanical engineering. The goal of HVAC design is to balance indoor environmental comfort with other

More information

KONRAD. Hybrid Fancoil Series

KONRAD. Hybrid Fancoil Series KONRAD Hybrid Fancoil Series Konrad is an innovative radiator which cools you down and warms you up. Indeed, it cools in summer and heats in winter; but it makes it with an incomparable quietness. Thanks

More information

Causes of High Relative Humidity Inside Air Conditioned Buildings. Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates

Causes of High Relative Humidity Inside Air Conditioned Buildings. Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates Causes of High Relative Humidity Inside Air Conditioned Buildings Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates S. FLORIDA AVE. AMBIENT 91 F db / 78 F wb 16,000 HOURS ANNUALLY THAT wb

More information

PRODUCT PRODUCT CODE TECHNICAL INSTRUCTIONS PAGE

PRODUCT PRODUCT CODE TECHNICAL INSTRUCTIONS PAGE Table of Contents PRODUCT PRODUCT CODE TECHNICAL INSTRUCTIONS PAGE # Electric Room Comfort Controller NEW! RDY2000 Room Comfort Controller RDY 129-905 D-3 Electric for Specialized Applications Surface

More information

Measuring The Right Thing For Humidity Control It s the Dew Point Stupid!

Measuring The Right Thing For Humidity Control It s the Dew Point Stupid! Page 1 of 6 Measuring The Right Thing For Humidity Control It s the Dew Point Stupid! By Mike Schell, AirTest Technologies Corp. A version of this article appeared in the June 2004 edition of Indoor Air

More information

Dedicated Outdoor Air-Dual Wheel System Control Requirements

Dedicated Outdoor Air-Dual Wheel System Control Requirements 4428 Dedicated Outdoor Air-Dual Wheel System Control Requirements Stanley A. Mumma, Ph.D., P.E. Fellow ASHRAE ABSTRACT The central thrust of this paper is to develop a clear understanding of the performance

More information

How To Understand Evaporator

How To Understand Evaporator SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES After studying this unit, the reader should be able to Define high-, medium-, and low-temperature refrigeration.

More information

How To Design A Building In New Delhi

How To Design A Building In New Delhi ENERGY EFFICIENT HVAC DESIGN FOR COMPOSITE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce energy consumption

More information

USER S GUIDE For all Packaged Systems (Air Conditioners and Heat Pumps)

USER S GUIDE For all Packaged Systems (Air Conditioners and Heat Pumps) USER S GUIDE For all Packaged Systems (Air Conditioners and Heat Pumps) WA & WL - Series Air Conditioners WH & SH - Series Air Source Heat Pumps IH - Series Air Source Heat Pumps DATE: 02-21-12 QA - Series

More information

To provide good indoor air quality

To provide good indoor air quality Conditioning Ventilation Air for Improved Performance and Air Quality The practice of using a mixing chamber for mixing outdoor and return in a single system should be replaced by a technique with two

More information

FLASH TANK ECONOMIZER PRODUCT GUIDE

FLASH TANK ECONOMIZER PRODUCT GUIDE FLASH TANK ECONOMIZER PRODUCT GUIDE Overview A flash tank is used to recover blowdown energy in the form of flash steam and blowdown. This can only be used with a deaerator or some other pressurized device.

More information

Venice Library Humidity Study. for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205. Report April 13, 2015

Venice Library Humidity Study. for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205. Report April 13, 2015 for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205 Report April 13, 2015 Moses & Associates, Inc. 2209 NW 40 th Terrace, Suite A Gainesville, FL 32605 FL License EB-0003097

More information

Flexibility, Efficiency In San Antonio Arena

Flexibility, Efficiency In San Antonio Arena 2005, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Reprinted by permission from ASHRAE Journal, (Vol. 47, No. 9, September 2005). This article may not

More information

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION 3.1 Purpose of Thermal Load Estimation 3.2 Heating Load versus Cooling Load 3.3 Critical Conditions for Design 3.4 Manual versus Computer Calculations 3.5 Heating

More information

HVAC Systems and Indoor Air Quality. Douglas K. Spratt, M.Sc., P.Eng.

HVAC Systems and Indoor Air Quality. Douglas K. Spratt, M.Sc., P.Eng. HVAC Systems and Indoor Air Quality Douglas K. Spratt, M.Sc., P.Eng. The 5 Senses Architecture Electrical Structural Mechanical Hearing Seeing Smelling Feeling Tasting HVAC Systems are Dynamic Heat Gains

More information

KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO. SAUDI STANDARD DRAFT No. 3457/2005

KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO. SAUDI STANDARD DRAFT No. 3457/2005 KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO SAUDI STANDARD DRAFT No. 3457/2005 NON-DUCTED AIR CONDITIONERS AND HEAT PUMPS TESTING AND RATING PERFORMANCE This standard is developed

More information

TODAY S PARADIGM FOR AIR TO AIR HEAT RECOVERY

TODAY S PARADIGM FOR AIR TO AIR HEAT RECOVERY Tom Brooke, April 11, 2012 TODAY S PARADIGM FOR AIR TO AIR HEAT RECOVERY INTRODUCTION Technology advances! Just as commercial and industrial HVAC controls, chillers, and unitary equipment are constantly

More information

LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air. Trevor Wende Vice President, Marketing Advantix Systems, Inc.

LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air. Trevor Wende Vice President, Marketing Advantix Systems, Inc. LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air Trevor Wende Vice President, Marketing Advantix Systems, Inc. 0 Humidity: The Hidden Cost Driver Conventional A/C process Start

More information

Type A Energy Wheels

Type A Energy Wheels Type A Energy Wheels for Modular and T-Series Climate Changer Air Handlers August 2001 CLCH-PRC006-EN Contents Introduction... 3 Features and Benefits... 4 Energy Wheel Construction... 5 Application Considerations...

More information

HVAC Basic Science - System Capacity

HVAC Basic Science - System Capacity HVAC Basic Science - System Capacity Btu/hour, btu/h, b/h, btuh. btu?? 1 MBH = 1000 btu/hour 1 KBH = 1000 btu/hour 1 ton of cooling= 12,000 btu/hour 1 watt = 3.414 btu/hour 1 kilowatt = 1000 watts = 3,414

More information

PIPES AND TUBES FOR HVAC PIPING AND EQUIPMENT

PIPES AND TUBES FOR HVAC PIPING AND EQUIPMENT PIPES AND TUBES FOR HVAC PIPING AND EQUIPMENT GENERAL INFORMATION 1.1 This section applies to piping systems for chilled water, hot water, condenser water, steam, condensate return, fuel oil, refrigerant

More information

Air Side Economizers and Energy Recovery - Improvements and New Regulations. Richard Lord 09-20-2012

Air Side Economizers and Energy Recovery - Improvements and New Regulations. Richard Lord 09-20-2012 Air Side Economizers and Energy Recovery - Improvements and New Regulations Richard Lord 09-20-2012 Introduction For commercial buildings the use of outside air for cooling and ventilation is an important

More information

HRV and ERV Best Practices. December 18, 2012 Portland Metro Home Builders Association

HRV and ERV Best Practices. December 18, 2012 Portland Metro Home Builders Association HRV and ERV Best Practices December 18, 2012 Portland Metro Home Builders Association The Basics: The X Flow Ports Connected to Inside 72 F 61 F 42 F 32 F Ports Connected to Outside The Single Most Important

More information

THE PSYCHROMETRIC CHART AND ITS USE

THE PSYCHROMETRIC CHART AND ITS USE Service Application Manual SAM Chapter 630-16 Section 3A THE PSYCHROMETRIC CHART AND ITS USE Psychrometry is an impressive word which is defined as the measurement of the moisture content of air. In broader

More information

How To Control Humidity With A Humidifier

How To Control Humidity With A Humidifier Control of ventilation and air conditioning plants Building Technologies s Contents.Temperature control in air treatment systems 2. Humidity controls 3. Recirculated air mixing. Internal heat sources 6.2

More information

Overview. Introduction Cooling Tower Basics Principles of Operation Types of Cooling Towers Common Applications Design Considerations

Overview. Introduction Cooling Tower Basics Principles of Operation Types of Cooling Towers Common Applications Design Considerations Stephen Lowe ASHRAE Hampton Roads Chapter Past President AECOM Design Mechanical Engineering Discipline Manager, Virginia Beach Division Professional Engineer Commonwealth of Virginia, NCEES BSME University

More information

Characteristics of Evaporators

Characteristics of Evaporators Characteristics of Evaporators Roger D. Holder, CM, MSME 10-28-2003 Heat or Energy In this paper, we will discuss the characteristics of an evaporator coil. The variance of the operational condenses of

More information