1 Technical Specification HIGH MAST SYSTEM Height of mast : 20 Meter No. of sections : Two Material construction : S 355 grade as per BS-EN Base dia. and top diameter (A/F) : Top : 150 mm, Bottom : 460 mm Plate thickness & section Length : Top : 4 mm, Bottom : 5 mm Cross section of Mast : 20 side polygon. Standard for of galvanization : As per BS EN ISO 1461 Size of opening and door at base : 1200 x 250 mm Diameter of base plate : 670 mm Thickness of base plate : 25 mm Lightning protection finial : G.I single spike of length 1200 mm Max.wind speed : 62.5 m/s Number of foundation bolts : 8 nos. PCD of foundation bolts : 590 mm Type / diameter / length of foundation bolts : TS 600 / 32 mm dia / 850 mm long LUMINAIRES CARRIAGE Material of construction : 50 NB ERW Class B - M. S. Pipe Diameter of carriage ring (mm) : 710 mm (ID) Construction : 6 Arm, Welded, 2 sections Load carrying capacity : 12 Luminaire TRAILING CABLE Conductor Insulation No. of circuits per mast WINCH/ POWER TOOL Type / SWL of winch Method of operation Motor capacity No of speeds Torque limitor : Copper, 5 core, 4 sq mm : EPR insulated PCP sheathed : One : Double drum, SWL 750 Kg : Flame Proof Integral Motor : 1.5 HP : 6 Pole, Single speed : With mechanical tripping facility STAINLESS STEEL WIRE ROPE Grade / construction : AISI 316, 7/19 construction Number of ropes : Two continuous Diameter (mm) : 6 mm Braking load capacity : 2350 kg x 2 Control panel will be of Flame proof type Page 1 of 10

2 EQUIPMENT SPECIFICATION HIGH MAST LIGHTING HIGHMAST GENERAL: The scope of this specification also covers the manufacture, transport, installation, testing and commissioning of the complete lighting system, using Raising and Lowering type of High mast Towers, including the Civil Foundation Works. HPCL will only provide the supply point. However, all items required for the safe and efficient operation and maintenance of the lighting system including the high mast, whether explicitly stated in the following pages or not shall be included by the Contractor. STRUCTURE: The High mast shall be of continuously tapered, polygonal cross section, at least 20 sided. Presenting a good and pleasing appearance and shall be based on proven In Tension design conforming to the standards specified, to give an assured performance, and reliable service. The mast shall be with decorative type umbrella and suitable for wind loading as per IS 875 Part CONSTRUCTION: The mast shall be fabricated from steel plates, cut and folded to form a polygonal section, welded and shall be telescopically jointed by welding/stress fit method. The procedural weld geometry and the workmanship shall be exhaustively tested on the completed welds. Mast can be fabricated in multiple sections of length approximately 10 metres. Thus a 20 M shall be delivered in two sections. No site welding or bolted joint shall be done on the mast. The minimum Overlap distance shall be 1.5 times the diameter at penetration. The mast shall be provided with fully penetrated flange, which shall be free from any lamination or incursion. The welded connection of the base-flange shall be fully developed to the strength of the entire section. The base flange shall be provided with supplementary gussets between the bolt holes to ensure elimination of helical stress concentration. For the environmental protection of the mast, the entire fabricated mast shall be hot dip galvanized, internally and externally. The thickness of galvanizing shall be a minimum of 85 microns. DOOR OPENING: An adequate door opening shall be provided at the base of the mast and the opening shall be such that it permits clear access to equipment like winches, cables, plug and socket etc. and also facilitate easy removal of the winch. The door opening shall be complete with a close fitting, vandal resistant, weatherproof door provided with a heavy duty internal lock with special paddle key. The door opening shall be carefully designed and reinforced with welded steel section, so that the mast section at the base shall be unaffected and undue buckling of the cut portion is prevented. Size of door opening shall Page 2 of 10

3 be around 1200 x 250 mm and shall be strengthened, if required to avoid buckling of the mast section under heavy wind conditions. DYNAMIC LOADING FOR THE MAST: The mast structure shall be suitable to sustain an assumed maximum reaction arising from a wind speed as per IS 875 and shall be measured at a height of 10 metres above ground level. The design life of the mast shall be a minimum of 25 years. LANTERN CARRIAGE: a) Fabrication A fabricated Lantern Carriage shall be provided for fixing and holding the flood light fittings and control gearboxes. The Lantern Carriage shall be of special design and shall be of steel tube construction. The tubes acting as conduits for wires, with holes fully protected by grommets. The Lantern Carriage shall be so designed and fabricated to hold the required number of flood light fittings and the control gearboxes, and also have a perfect self-balance. The Lantern Carriage can be fabricated in two/three sections and joined by bolted flanges with stainless steel bolts and nylon type stainless steel nuts to enable easy installation or removal from the erected mast. The inner lining of the carriage shall be provided with suitable protective arrangement, so that no damage is caused to the surface of the mast during the raising and lowering operation of the carriage. The entire Lantern Carriage shall be hot dip galvanized after fabrication. The design shall provide a perfect balance for the lantern carriage during raising and to lowering also. b) Junction Box Weather proof junction box, made of Cast Aluminium shall be provided on the Carriage Assembly as required from which the inter-connections to the designed number of the flood light luminaires and associated control gears fixed on the carriage shall be made. c) Raising and lowering mechanism For installation and maintenance of luminaries and lamps, it will be necessary to lower and raise the Lantern Carriage Assembly. To enable this, a suitable Winch Arrangement shall be provided, with the winch fixed at the base of the mast and the specially designed head frame assembly at the top. Suitable end limit switches shall be provided to trip the winch motor at both top & bottom ends of the designed travel. Suitable thermal relay shall be provided to trip the mechanism in case of overload. d) Winch The winch shall be of completely self-sustaining type, without the need for brake shoe, springs or clutches. Individual drum also should be operated for fine adjustment of lantern carriage. The capacity, operating speed, safe working load, recommended lubrication and serial number of the winch shall be clearly marked on each winch. The winch shall be self-lubricating type by means of an oil bath and the oil shall be readily available grades of reputed producers. The winch drums Page 3 of 10

4 shall be grooved to ensure perfect seat for stable and tidy rope lay, with no chances of rope slippage. The rope termination in the winch shall be such that distortion or twisting is eliminated and at least 5 to 6 turns of rope remains on the drum even then the lantern carriage is fully lowered and rested on the rest pads. It should be possible to operate the winch manually by a suitable handle and by an integral/ external power tool. It shall be possible to remove the double drum after dismantling through the door opening provided at the base of the mast. Also, a winch gearbox for simultaneous and reversible operation of the double drum winch shall be provided as part of the contract. The winch shall be type tested in presence of a reputed Institution and the test certificates shall be furnished before supply of materials. A test certificate shall be furnished by the Contractor form the original equipment manufacturer, for each winch in support of the maximum load operated by the winch. e) Head Frame The head frame, which is to be designed as a capping unit of the mast, shall be of welded steel construction, galvanized both internally and externally. The top pulley shall be of appropriate diameter, large enough to accommodate the stainless steel wire ropes and the multi-core electric cable. The pulley block shall be made of non-corrodable material, like diecast Aluminium Alloy (LM-6). Self-lubricating bearings and stainless steel shaft shall be provided to facilitate smooth and maintenance free operation for a long period. The pulley assembly shall be fully protected by a canopy galvanized internally and externally. Close fitting guides and sleeves shall be provided to ensure that the ropes and cables do not dislodged from their respective positions in the grooves. The head frame shall be provided with guides and stops with PVC buffer for docking the lantern carriage. f) Stainless Steel Wire Ropes The suspension system shall essentially be without any intermediate joint and shall consist of only non-corrodable stainless steel of AISI 316 or better grade. The stainless steel wire ropes shall be of multi strand construction, the central core being of the same material. The overall diameter of the rope shall not be less than 6 mm. The breaking load of each rope shall have factor of safety of over 5 for the system at full load. The end Constructions of rope to the winch drum shall be fitted with talurit. The thimbles shall be secured on ropes by compression splices. Two continuous lengths of stainless steel wire ropes shall be used in the system and no intermediate joints are acceptable in view of the required safety. No intermediate joints / terminations, either bolted or else, shall be provided on the wire ropes between winch and lantern carriage. ELECTRICAL SYSTEM, CABLE AND CABLE CONNECTIONS A suitable terminal box shall be provided as part of the contract at the base compartment of the high mast for terminating the incoming cable. Supply of Incoming cable from the substation/ supply point to the highmast comes under the scope of the party. All necessary items shall be supplied by the party for drawing power from the Page 4 of 10

5 dummy feeder at the substation. Cable laying in the trench, sand filling & brick laying comes under the scope of the contractor. The electrical connections from the bottom to the top shall be made by special trailing cable. The cable shall have enough flexibility and endurance, and have copper conductors. The cable shall be of reputed make. At the top there shall be weather proof junction box(es) to terminate the trailing cable. Connections from the top junction box to the individual luminaries shall be made by using 3 core flexible PVC cables of adequate size. The system shall have in-built facilities for testing the luminaries while in lowered position. Also, suitable provision shall be made at the base compartment of the mast to facilitate the operation of externally mounted, electrically operated power tool for raising and lowering of the lantern carriage assembly. The trailing cables of the lantern carriage rings shall be terminated by means of specially designed, metal clad. Multi-pin plug and socket provided in the base compartment to enable easy disconnection when required. A distribution board with suitably rated 3-phase incomer MCB and separate MCB's controlled folders for lighting and power tool shall also be supplied. The board shall Incorporate timer for control of lighting and control circuit for winch operation with all necessary contactors etc. The board shall have IP 55 protection with rainwater protections canopy and epoxy powder coated suitable for outdoor mounting in coastal area. The work shall also include necessary foundation cable glands,etc. complete as required. POWER TOOL FOR THE WINCH A suitable, high-powered, electrically driven internally mounted power tool, with manual over ride shall be supplied for the raising and lowering of the lantern carriage for maintenance purposes. The speed of the power tool shall suit the system. The power tool shall be single speed provided with a motor of the required rating. The power tool shall be supplied complete with push button type remote control switch, together with 5/6 metres of power cable, so that the operations can be carried out from a safe distance of 5 (five) metres. The capacity and speed of the electric motor used in the power tool shall be suitable for the lifting of the design load installed on the lantern carriage. The power tool mounting shall be so designed that it will be not only self-supporting but also aligns the power tool perfectly with respect to the winch spindle during the operations. Also, a handle for the manual operation of the winches in case of problems with the electricityoperated tool, shall be provided and shall incorporate a torque-limiting device. There shall be a separate torque-limiting device to protect the wire ropes from over stretching. It shall be mechanism with suitable load adjusting device. The torque limiter shall trip the load when it exceeds the adjusted limits. There shall be suitable provision for warning the operator once the load is tripped off. The torque limiter is a requirement as per the relevant standards in view of the overall safety of the system. High mast shall have its own power tool motor. LIGHTNING FINIAL One number heavy duty hot dip galvanized lightning finial shall be provided for the mast. The lightning finial shall be minimum 1.2 M in length or as required so that the lantern carriage also comes within the safety zone and shall be provided at the centre of the head frame. It shall be bolted solidly to the head frame to get a direct conducting path to the earth through the mast. The lightning finial shall not be provided on the lantern carriage under any circumstances in view of safety of the system. Page 5 of 10

6 AVIATION OBSTRUCTION LIGHTS Approved LED type Single dome Aviation Obstruction Lights of reliable design and reputed manufacturer shall be provided on top of each mast. EARTHING TERMINALS Suitable earth terminal using 12 mm diameter stainless steel bolts shall be provided at a convenient location on the base of the Mast, for lightning and electrical earthing of the mast. The mast shall be provided with duplicate earthing including necessary earth pits as per IS. FOUNDATION FOR HIGH MAST The scope also includes supplying all materials and casting of RCC foundation along with necessary Anchor bolts etc. The detailed drawing for the foundation should be submitted and got approved by HPCL before starting of the work. FEEDER PILLAR DISTRIBUTION BOARDS DESIGN CRITERIA: The feeder pillar distribution boards shall be sheet steel enclosed, outdoor type having suitable canopy for rain water protection, pedestal type, FLP type conforming to IP: 55 suitable for use on 415V, 50 Hz., 3 phase, 4 wire AC system. The board shall have TPN / DP isolator / switch fuse unit / MCB as incoming and TPN / SP MCB as outgoing feeders. These boards are meant for lighting the High Masts. These shall be factory built standardized boards or fabricated based on specification and approved drawing. The feeder pillar box shall be approved by CCOE. The feeder pillar box shall have required interface for remote control PB station through cable for raising and lowering of lantern carriage. The feeder pillar box shall be mounted on a raised concrete platform above ground level at min height of 1 meter. The light fittings provided on the light mast shall have individual switch controls in the feeder pillar box to have the flexibility to put the selected light fittings ON / OFF. Three phase supply to be equally distributed to the 12 light fittings alternatively (eg: light Fittings 1,4,7,10 to R-phase; 2,5,8,11 to Y-Phase; 3,6,9,12 to B-Phase ) to ensure equal light coverage in all directions even if one phase supply is available. One Feeder pillar at VDS requires separate provision for outgoing supply through 4 core cable to the feeder pillar of second highmast. CONSTRUCTIONAL DETAILS: a) The lighting distribution boards shall be pedestal mounted type made of minimum 1.6 mm thick sheet steel totally enclosed rain, dust and vermin proof construction having separate chambers for incoming and outgoing feeders. b) The board shall conform to IP: 55 class of protection as per IS: 2147and suitable canopy for rain water protection. c) The board shall be fabricated using high quality CRCA sheet steel. Suitable neoprene gaskets shall be provided for all doors and covers for making the board dust proof. Page 6 of 10

7 d) The operating handle of the incoming switch fuse unit shall be accessible from the front side.operating handle shall be suitably interlocked mechanically with the door of the incomer chamber so that the door can be opened or closed only when the switch is in 'OFF' position. A manual interlock defeat shall also be provided. e) The outgoing MCB's shall be housed in a separate chamber. The operating knobs of the MCB's shall be accessible through front door. The outgoings chamber shall be covered completely with FRP sheet. The 4mm thick FRP sheet provided shall effectively shroud all the live parts against accidental contact. The door shall have pad looking facility. f) Bus bars shall be of Tinned copper. Bus bars shall be shrouded. Phase & neutral Busbars shall have the same cross sections. The earth bus shall have the same size as the Neutral bus. g) The incoming compartment door shall have 3 Nos. (for 3 phase) 1 No. (for single phase) Neon indicating lamps (red colour). h) Safety clearances as per IE rules shall be provided for components of the board. i) Board shall have continuous earth bus of size same as that of neutral. j) Link between neutral and earth shall be provided. PAINTING : The final painting of all boards shall be light siemens grey RAL 7032 IS: 5 unless otherwise specified. TESTING : All the distribution boards shall be tested as per IS:8623 at factory site. FLOOD LIGHT LUMINAIRE (SUITABLE FOR HPSV/MH T LAMPS) The flood light fitting shall be integral or non-integral type, complete with suitable weatherproof control gearbox. The fitting shall consist of a lamp compartment housing a reflector made of spun aluminium electrochemically brightened and anodized. Flat toughened front glass suitable to withstand the high temperature and humid conditions shall be fixed to the housing using neoprene gasket. Focusing knob to help in adjusting the lamp center shall be provided. Mild steel cradle shall be mounted on the control gear. The control gear shall consist of heavy-duty polyester filled copper choke suitable for lamp wattage specified p.f. improvement condensers. The minimum power factor required is 0.9 for all light fixtures connectors and fittings duly wired with provision of cable entry provided. The provision for relamping is to be made in such a way that aiming angles not disturbed. The chokes shall be manufactured from high quality silicon laminations with tapping at 200/220/240V; this shall conform to IS Holders shall be made out of porcelain and shall have brass contacts. These shall be rated for 240V. The tip of the holder shall be spring-loaded. Capacitors shall be of 250 V rating. This shall have fiberglass covered wire of suitable cross section to withstand high temperature generated in the control gear/lamp holder. The main supply shall be connected to the terminal book made out of porcelain/ bakelite of suitable quality. The terminal block housing shall have flexible conduit for taking the main supply leads. The control gear and lamp holder housing shall be provided with a sufficient number of vertical fins to dissipate heat produced. A protractor plate with degrees marked on it shall be provided to enable the fitting to be tilted to any required angle. Rotating of the fitting shall be limited to 360-degree horizontal and 180- degree vertical and locking arrangement shall be provided for both vertical and Page 7 of 10

8 horizontal position. All hardware shall be made of mild steel and passivated. The fitting shall be complete and suitable for taking HPSV lamp, provided with gaskets to make the unit weatherproof. All the cast aluminium parts shall be finished in epoxy powder coating, 3 x 2.5 sq.mm PVC cable, copper conductor shall connect the terminals of the luminaries with sub circuit at 240 V via the control gear unit, 1 no. earthing terminal shall be provided. Both the luminaries and the control gearbox shall conform to IP 54 or better and suitable for outdoor application. The control gearbox shall have the required electronic igniter for starting of the lamp. FLOOD LIGHT LUMINAIRE (SUITABLE FOR LED LAMPS) The flood light fitting shall be integral or non-integral type, complete with suitable weatherproof control gearbox. The fitting shall consist of a lamp compartment housing a reflector made of spun aluminium electrochemically brightened and anodized. Flat toughened front glass suitable to withstand the high temperature and humid conditions shall be fixed to the housing using neoprene gasket. The minimum power factor required is 0.9 for all light fixtures connectors and fittings duly wired with provision of cable entry provided. The control gear and lamp holder housing shall be provided with a sufficient number of vertical fins to dissipate heat produced. All the cast aluminium parts shall be finished in epoxy powder coating, 3 x 2.5 sq.mm PVC cable, copper conductor shall connect the terminals of the luminaries with sub circuit at 240 V via the control gear unit, 1 no. earthing terminal shall be provided. Both the luminaries and the control gearbox shall conform to IP 54 or better and suitable for outdoor application. Proper Surge and over current protections to be provided for the lumaire. The luminaire shall be approved by Site-engineer/ project incharge of HPCL. TIMER Timer (Time switch) shall be accurate & quartz driven. The timer shall have a built-in chargeable Ni-Cd cells for 150 hours continuous operation in the event of power failure. The timer shall be suitable for switching ON/OFF highmast etc. at predetermined time. The timer shall be supplied with enclosure or panel mounted as required. CONTROL PANEL HOUSING, CONTROL CKT S A suitable control panel housing for control circuits shall be provided for safe & efficient Operation of the highmast. It should also consist suitable control for the power tool motor with Contactors. LAMP SODIUM VAPOUR LAMP : The lamps shall be suitable for universal burning position and shall be colour corrected and shall have caps E-40 with ES/GES threads. All the lamps shall be suitable for external igniter. Lamps shall be ovoid or tubular type as specified. The approved makes of lamps is limited to the following only. 1.) Philips 2.) Crompton Page 8 of 10

9 3.) Bajaj HIGH POWER LED LAMP : LED luminary shall be a High power LED type and of 200W rating. LED inside the lamp shall be of Philips/Osram make with proper surge and over current protection. The lamp shall be approved by Site-engineer/ project incharge of HPCL. EARTHING Earthing shall confirm to IS MATERIAL REQUIRED FOR AN EARTH PIT a) 65 mm diameter, Gl pipe, 3.00 meters long in one single piece with (40 x 6)/ (25 x 6) mm GI flat of required length welded to the pipe on top and 12 mm holes made on all sides of the pipe at 150 mm apart upto height of minimum 2.5 meters from bottom... 1 No. b) Bolts, nuts, washers and sockets for earthing connection... 1 set. c) Charcoal of not less than 12 mm size d) Salt granular. e) 80 mm long funnel having suitable diameter with wire mesh welded at top and GI nut welded at bottom (to fit the GI pipe electrode). f) RCC cover for earth pit chamber 1 no. METHOD OF ERECTION a) The pit for an earth electrode will be dug with its center normally at minimum 2.5 meters away from the edge of any building/ masonry work. b) The GI pipe will be erected vertically at the center of the pit, with top of the pipe minimum 200 mm below ground level. c) Alternate layers of charcoal and salt each 150 mm, will be put into the pit beginning from the bottom of pit, around the pipe to cover the same upto minimum 3.0 meters length from bottom. Alternately charcoal and salt shall be thoroughly mixed at site and poured into earth pit. d) The space above the salt / charcoal layers will be filled with loose sandy soil, upto a level of 550 mm from ground level. e) A cement concrete chamber of inner dimension 350 x 350 mm will be erected around the top of the earth pipe so that top surface of the chamber is flushed with the outside finished ground level. f) A GI earthing strip (40 x 6) I (25 x 6) mm, of required length size will be tightly connected to the electrode GI plate by means of GI bolt. nuts and washers. End of this GI strip will be welded to the earthing ring GI wires / strip. In areas of rocky terrain, where it is not possible to vertically drive the electrode, horizontally installed electrode at a minimum depth of 1000 mm may be provided as per the instruction offsite engineer. Alternately bentorite or chemical treatment to obtain ohmic value-as required shall be done. Page 9 of 10

10 EARTHING RING MAIN The earthing ring shall be made by GI strip/ insulated single core cable of specified size. The ring shall be laid in the cable trench along with lighting cable and connected to all the earthing pits. EARTHING OF FEEDER PILLAR DISTRIBUTION BOARDS The distribution board shall be provided with two separate earth terminals. An earth busbar of appropriate cross section shall be provided inside the lighting board and connected to the earth terminals provided on either side of the board. Adequate number of holes/ terminals shall be provided on earth bus with suitable provision for terminating the earth wire. GI strip/ GI wire insulated single core cable of suitable size shall be used for earthing the lighting board, by connecting the two earth terminals separately to the earthing main in the shop/earth pit. EARTHING OF LIGHT FIXTURES The single core PVC insulated wire/ bare copper wire or 14 SWG GI wire and the third core of the flexible wiring cable shall be used for earthing the light fixtures. EARTHING OF METAL BOXES & BRACKETS Not less than 14 SWG Gl wire or suitable size PVC insulated copper wire shall be used for earthing a U metal boxes and brackets. Page 10 of 10

SPECIFICATIONS FOR TENDER NO: PSNR/SCP/VKS/E 1635 ANNEXURE I TECHNICAL SPECIFICATIONS FOR LIGHTING HIGH MAST

SPECIFICATIONS FOR TENDER NO: PSNR/SCP/VKS/E 1635 ANNEXURE I TECHNICAL SPECIFICATIONS FOR LIGHTING HIGH MAST TECHNICAL SPECIFICATIONS FOR LIGHTING HIGH MAST ANNEXURE I Sl.No. Description for BHEL Requirement Offered Deviation Scope of supply, erection and commissioning: 1 The scope of this specification covers

More information

TECHNICAL SPECIFICATION FOR HIGH MAST LIGHTING SYSTEM, 20 MTRS HEIGHT

TECHNICAL SPECIFICATION FOR HIGH MAST LIGHTING SYSTEM, 20 MTRS HEIGHT TECHNICAL SPECIFICATION FOR HIGH MAST LIGHTING SYSTEM, 20 MTRS HEIGHT Annexure A Sl.No. Description 1 Scope: The scope cover the design, manufacturing, supply and delivery at GCF Jabalpur on FOR basis

More information

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132

More information

TS 813 GROUNDING AND BONDING TTD 813.001 TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD 813.005 CONTROLLER CABINET GROUNDING

TS 813 GROUNDING AND BONDING TTD 813.001 TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD 813.005 CONTROLLER CABINET GROUNDING TORONTO TRANSPORTATION January 2012 TS 813 GROUNDING AND BONDING TABLE OF CONTENTS 1. DRAWINGS TTD 813.001 TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD 813.005 CONTROLLER CABINET

More information

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4 CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,

More information

Sports and High Mast Lighting Poles Phone: (866) 474-7200 Fax: (817) 924-7049

Sports and High Mast Lighting Poles Phone: (866) 474-7200 Fax: (817) 924-7049 Sports and High Mast Lighting Poles 4 High Mast Lighting Poles General American LitePole offers a raising and lowering system that allows for ease of maintaining the lighting system at ground level. Ideal

More information

Installation guide for the SafeLine type anchorage device. Tested in compliance with EN 795: 1996. No.: SE-...

Installation guide for the SafeLine type anchorage device. Tested in compliance with EN 795: 1996. No.: SE-... Installation guide for the SafeLine type anchorage device Tested in compliance with EN 795: 1996 No.: SE-... Version: 09.10.2008 SE 67 Subject to technical alterations! Contents 1. General information

More information

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations. DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,

More information

DESIGN CLARIFICATION (DC)

DESIGN CLARIFICATION (DC) DESIGN CLARIFICATION (DC) Owner: Victor Valley Wastewater Reclamation Authority Date: 03/03/2015 Contractor: W M Lyles Carollo Project No.: 8299A.20 Project Name: Subregional WRPs DC No.: 001 DC Title:

More information

MODEL HSR-007 Direct Drive Rolling Steel

MODEL HSR-007 Direct Drive Rolling Steel MODEL HSR-007 Direct Drive Rolling Steel 200 Fairview Road, Unit #2, Barrie, Ontario L4N 8Z8 Tel: 866-792-9968 or 705-792-9968 Fax: 705-735-9564 www.tnrdoors.com email: info@tnrdoors.com Model HSR-007

More information

understanding medium frequency induction melting furnace and its components

understanding medium frequency induction melting furnace and its components understanding medium frequency induction melting furnace and its components 9 Spruce Street, Jersey City, NJ 07306 USA sales@electroheatinduction.com INDUCTION MELTING FURNACE AND ITS COMPONENTS The purpose

More information

James M. Pleasants Company

James M. Pleasants Company James M. Pleasants Company SUBMITTAL DATA GAINESVILLE MECHANICAL DECEMBER 20, 2013 PROJECT: GSU: J-183 HUMANITIES LAW BLDG. QUOTE NO:12116 ENGINEER: STEVENS & WILKINSON GASKETED PLATE HEAT EXCHANGER Tag:

More information

Trade of Electrician. Three-phase Distribution Boards And Socket Circuits

Trade of Electrician. Three-phase Distribution Boards And Socket Circuits Trade of Electrician Standards Based Apprenticeship Three-phase Distribution Boards And Socket Circuits Phase 2 Module No. 2.3 Unit No. 2.3.2 COURSE NOTES Created by Charlie Walsh - Athlone TC Revision

More information

EARTHING AND BONDING AT SECONDARY SUBSTATIONS

EARTHING AND BONDING AT SECONDARY SUBSTATIONS DISTRIBUTION CONSTRUCTION MANUAL SECTION 4 - SUBSTATIONS ISSUE B SEPT 1996 4.4.4 EARTHING AND BONDING AT SECONDARY SUBSTATIONS 1 SCOPE This section of the Distribution Construction Manual lays down the

More information

DESCRIPTION UNIT QTY RATE TOTAL (KSHS) Supply and install the following: -

DESCRIPTION UNIT QTY RATE TOTAL (KSHS) Supply and install the following: - PROPOSED KISUMU HOUSING 3 BEDROOM-TYPE 1 ELECTRICAL INSTALLATION -SITE 01 DESCRIPTION UNIT QTY RATE TOTAL (KSHS) Supply and install the following: - 1.0 Final sub-circuit from Consumer Unit to lighting

More information

OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd

OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd ACTOM OUTDOOR DISCONNECTORS Single Side Break (SSB) Disconnector 22-132 kv, 800-1 A, 25 ka - 3s Typical bearing assembly. Voltage range 11 kv to 132

More information

TELESCOPE Motorized Lighting Suspension

TELESCOPE Motorized Lighting Suspension TELESCOPE Motorized Lighting Suspension Mod. 8400 FEATURES The De Sisti TELESCOPE is a single point suspension specifically designed to provide rigidity and stabilization of all moving parts. It can extend

More information

TARIFF CODE and updates standard

TARIFF CODE and updates standard TARIFF CODE and updates standard No HS CODE AHTN CODE PRODUCT DESCRIPTION PRODUCT TYPE STANDARDS IDENTIFIED 7207 Semi finished products of iron or non alloy steel Containing by weight less than 0.25% of

More information

SECTION 08332 COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)

SECTION 08332 COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here) SECTION 08332 COILING COUNTER DOORS Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Coiling Metal Counter Doors. B. Coiling Counter Fire Doors. 1.2

More information

Linear Luminaire for Fluorescent Lamps Series EXLUX 6001

Linear Luminaire for Fluorescent Lamps Series EXLUX 6001 > As wall, ceiling and pendant light fitting or side entry lamp > Version with 2 lamps: 18 W, 36 W and 58 W > Central locking > All-pole disconnection by means of an N/C switch when the lamp is opened

More information

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK Pressure monitoring equipment for oil-sf 6 bushings, type GOEK Installation and maintenance guide 5693 827-6 en, Rev. 3, 2002-01-30 This document must not be copied without our written permission, and

More information

MAST ARMS & POLES. Ornamental Pole Top & Bases

MAST ARMS & POLES. Ornamental Pole Top & Bases Ornamental Pole Top & Bases Pelco s decorative pole top and bases help make the traffic signal aesthetically pleasing to the eye. Available for various pole diameters and multiple finish options. Ornamental

More information

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information

Urban lighting luminaire ECOLO. Registered models - Design Massimo Sacconi. NERO e GRIGIO per marchi piccoli (ha il filo ingrossato)

Urban lighting luminaire ECOLO. Registered models - Design Massimo Sacconi. NERO e GRIGIO per marchi piccoli (ha il filo ingrossato) Urban lighting luminaire ECOLO Registered models - Design Massimo Sacconi NERO e GRIGIO per marchi piccoli Ecolo is a versatile and multifunctional solution designed to enhance the most different urban

More information

GE Power Controls. MiniFORM Switchboards

GE Power Controls. MiniFORM Switchboards GE Power Controls MiniFORM Switchboards MiniFORM MiniFORM MiniFORM switchboards Arrangement Modules Arrangement modules 1-6 6 Arrangement modules 7-12 7 Arrangement modules 12-14 8 Arrangement modules

More information

Schedule of Quantities

Schedule of Quantities CIVIL WORK (A) 1 Providing and fixing corrugated galvanised iron sheets of 20 B.W.G. for roofing with wind ties including fastening with galvanised iron screw and bolts and lead and bitumen washers as

More information

SERIES ASM NEOPRENE/EPMD FLANGED SINGLE SPHERE CONNECTOR CONNECTORS. Pressures to 225 PSIG (15.51 barg) Temperatures to 230ºF (110ºC)

SERIES ASM NEOPRENE/EPMD FLANGED SINGLE SPHERE CONNECTOR CONNECTORS. Pressures to 225 PSIG (15.51 barg) Temperatures to 230ºF (110ºC) APPLICATIONS Process Industry Weak Acids Alkalies Compressed Air Pulp & Paper MODELS ASM - Flanged Connection OPTIONS Control Rods Oil & Gas Water & Waste Pump suction & discharge Sea water Chemical lines

More information

Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling

Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling 250_P1 R10/7/2015 Copyright 2015 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.

More information

INFRARED QUARTZ WALL HEATER

INFRARED QUARTZ WALL HEATER INFRARED QUARTZ WALL HEATER MODEL NO: IQ2000 PART NO: 6939004 MOUNTING & OPERATION INSTRUCTIONS GC0715 INTRODUCTION Thank you for purchasing this CLARKE Infrared Wall Heater. Before attempting to use this

More information

RAILWAY CATENARY SYSTEMS. Components and Systems for the Electrification of Railway Lines. ibemo

RAILWAY CATENARY SYSTEMS. Components and Systems for the Electrification of Railway Lines. ibemo Connectors, Clamps, Compensating Devices, Insulators and Safety Equipment for Overhead Catenary Lines RAILWAY CATENARY SYSTEMS Components and Systems for the Electrification of Railway Lines. Welcome to

More information

IRRIGATION PUMPING Table of Contents - Section 900

IRRIGATION PUMPING Table of Contents - Section 900 IRRIGATION PUMPING Table of Contents - Section 900 PARAGRAPH 900.1 GENERAL 1 900.2 METERING REQUIREMENTS 1 900.3 CUSTOMER S CONTROL EQUIPMENT 2 900.4 SERVICE CONDUCTOR REQUIREMENTS 2 900.5 RECOMMENDATIONS

More information

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage:

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage: Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016 * Garage construction requires permits (electrical, building) * Permits must be applied for at the time. * Dial

More information

Owners & Installation Manual for the Sheridan, Mountainair, Pine Valley and Old Forge Ceiling Fan Family

Owners & Installation Manual for the Sheridan, Mountainair, Pine Valley and Old Forge Ceiling Fan Family Owners & Installation Manual for the Sheridan, Mountainair, Pine Valley and Old Forge Ceiling Fan Family Part of the Kiva Lighting Family Custom Lighting and Fans Since 1992 1312 12th St NW Albuquerque,

More information

Awning Instructions. Full Cassette 1.5m to 6m

Awning Instructions. Full Cassette 1.5m to 6m Awning Instructions Full Cassette 1.5m to 6m English Full Cassette Manual & Electric Instructions Contents Warning 1.5m - 3.5m Awnings 8 x Expansion bolts ** 2 x brackets 1 x Awning 1 x Winder 4.0m -

More information

Rollers. from the UK s largest roller manufacturer. Quality Performance Reliability

Rollers. from the UK s largest roller manufacturer. Quality Performance Reliability Rollers from the UK s largest roller manufacturer Quality Performance Reliability 42 Index Gravity Rollers Light to Medium Duty 4 Heavy Duty 5 Plastic Rollers 6 Stainless Steel Rollers 7 Grooved Rollers

More information

TECHNICAL SPECIFICATIONS

TECHNICAL SPECIFICATIONS 1. Standards BOS Item / System I ii iii TECHNICAL SPECIFICATIONS Applicable BIS /Equivalent IEC Standards / Applicable MNRE Specifications Standard Description Standard Number Crystalline Silicon Terrestrial

More information

HORIZONTAL INSTALLATION

HORIZONTAL INSTALLATION THERMO/SOLAR Žiar s.r.o. MANUAL FOR INSTALLATION PV SUPPORTING FRAMES HORIZONTAL INSTALLATION Technical alternation reserved A1410 1 12/2014 CONTENT ORD.NO. PAGE Mounting information 3 Mounting, flat roof

More information

FAQs-Main switchboard design criteria

FAQs-Main switchboard design criteria FAQs-Main switchboard design criteria Q: What is the Australian standard for main switchboards? Current Australian standard is AS/NZS 3439.1: 2002 originating from IEC 60439. The new series of standard

More information

Linear Luminaire with LED Series EXLUX 6402/2

Linear Luminaire with LED Series EXLUX 6402/2 > Latest LED technology with a high luminous efficacy and a long service life > As pendant light fitting or side entry lamp > Central locking > All-pole disconnection by means of an N/C switch when the

More information

Vertical Break Parallel (VBP) / Vertical Break Slant (VBS)

Vertical Break Parallel (VBP) / Vertical Break Slant (VBS) August, 2009 Vertical Break Parallel (VBP) / Vertical Break Slant (VBS) Type VBPA (Aluminum) / Type VBPC (Copper) Type VBSA (Aluminum) / Type VBSC (Copper) PASCOR Air Break Switch Technology PASCOR offers

More information

BOQ SPECIFICATIONS. The Blind system consist of a coated aluminium tube of 38 mm diameter with provision of fabric clamping.

BOQ SPECIFICATIONS. The Blind system consist of a coated aluminium tube of 38 mm diameter with provision of fabric clamping. BOQ SPECIFICATIONS VERTICAL BLINDS Vertical Blinds made of glass fibre fabrics in width 5 (or 4 ). Minimum overlapping of ¾ in fabric. Top aluminium anodized rail of 1.4 mm thickness. 2 inch wide channel

More information

Section 21. Telecommunication Hardware. www.geindustrial.com BuyLog Catalog 21-1

Section 21. Telecommunication Hardware. www.geindustrial.com BuyLog Catalog 21-1 Introduction...21-1 Fiber Closure Hardware...21-2 Cable Location Surge Protectors...21-4 Introduction GE has been manufacturing Telecommunication Hardware products for over 20 years and has become a leader

More information

Superlight Compact Nano

Superlight Compact Nano Willy Meyer+Sohn GmbH+Co. KG Stemmessiepener Weg 5 D-58675 Hemer Telephone: +49 (0) 23 72/98 91-0 Telefax: +49 (0) 23 72/98 91-48 E-mail: info@meyer-lighting.com www.meyer-lighting.com 258 00 530-1211

More information

Petrol Station Canopies

Petrol Station Canopies Petrol Station Canopies High bay & Low Bay Warehouses & Factories Security Lighting General Area Lighting 320W High Bay Ideal for warehouses and factories, the Advantage Hi-Bay offers 20% energy savings

More information

PART-II (COMMERCIAL / PRICE BID) DESIGN, SUPPLY AND INSTALLATION OF CUSTOMIZED STEEL LAB FURNITURE.AT N.C.C.S., PUNE

PART-II (COMMERCIAL / PRICE BID) DESIGN, SUPPLY AND INSTALLATION OF CUSTOMIZED STEEL LAB FURNITURE.AT N.C.C.S., PUNE (An Autonomous Institution of the Department of Biotechnology, Govt. of India) N.C.C.S. Complex, Ganeshkhind, Pune University Campus, Pune 411007. PART-II (COMMERCIAL / PRICE BID) DESIGN, AND INSTALLATION

More information

K17.12 Door closers K17. Doors 01.09.2013

K17.12 Door closers K17. Doors 01.09.2013 K17 Doors K17.12 01.09.2013 Waregemstraat 5-9870 Zulte - Belgium - T. +32 9 388 88 81 - F. +32 9 388 88 21 - commercial@sobinco.com - www.sobinco.com Contents 1. OPTIC door closer TS40(V) with scissor

More information

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2

More information

UNIVERSAL RAILING, STEEL

UNIVERSAL RAILING, STEEL RAILINGS Page Universal Railing, steel 108-109 Large Module Railing, steel 110-111 Allround Railing, aluminium 112-113 Module Railing, aluminium 114-115 Standard Type Railing, aluminium 116-117 107 UNIVERSAL

More information

SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS

SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word

More information

VCE VET ENGINEERING STUDIES

VCE VET ENGINEERING STUDIES Victorian Certificate of Education 2013 SUPERVISOR TO ATTACH PROCESSING LABEL HERE STUDENT NUMBER Letter Figures Words VCE VET ENGINEERING STUDIES Written examination Section Wednesday 20 November 2013

More information

E S T I M A T E TENDER FOR ELECTRICAL & DATA CABLING WORK FOR BANK OF INDIA, KALAWAD ROAD BRANCH(GROUND FLOOR)-RAJKOT CITY

E S T I M A T E TENDER FOR ELECTRICAL & DATA CABLING WORK FOR BANK OF INDIA, KALAWAD ROAD BRANCH(GROUND FLOOR)-RAJKOT CITY PART- IV - ELECTRIC WORK FOR BRANCH Supply, installation, testing and commissioning of following point wiring as per the specifications and drawings. The unit rate for the switch board and further to point

More information

WE-350 Series ¼ Turn Electric Actuator

WE-350 Series ¼ Turn Electric Actuator WE-350 Series ¼ Turn Electric Actuator Operation and Installation Manual Pg 1 (Rev. 020113) Table of Contents 1.0 General 1.1 Pre-Installation Inspection 1.2 Storage 1.3 Features & General Information

More information

V1504 Vertical Platform Lift OWNER S MANUAL

V1504 Vertical Platform Lift OWNER S MANUAL V1504 Vertical Platform Lift OWNER S MANUAL (To Be Retained by Owner After Installation by Authorized Savaria Dealer) Part No. 000692 01-m03-2016 2 IMPORTANT Ensure that only an authorized Savaria Dealer

More information

Standard Buccaneer - Ethernet

Standard Buccaneer - Ethernet IP6 rated compliant PUR jacket on cable Shielded system shielded coupler Shroud on RJ45 Screw coupling Rewireable flex connector PCB mounted panel connector IDC termination panel connector Earth lead version

More information

SECTION 22 LIGHTNING PROTECTION SYSTEM

SECTION 22 LIGHTNING PROTECTION SYSTEM SECTION 22 LIGHTNING PROTECTION SYSTEM 22.01 SCOPE: A. These Specifications shall form a part of the Contract Documents and shall govern construction work for all buildings to be built or modified for

More information

Spare Parts List M96A.24SM/B M96A.28SM/B

Spare Parts List M96A.24SM/B M96A.28SM/B *16202390* 162.0239.0 REV5 14/04 2015 Spare Parts List M96A.24SM/B M96A.28SM/B Issue Table description Issue n. of pages Overall view 09/2008 1 C.h. return group and d.h.w. heat exchanger 09/2008 1 C.h.

More information

Paper on Basbar Trunking System for Electrical Supply to Industrial & commercial Installation

Paper on Basbar Trunking System for Electrical Supply to Industrial & commercial Installation IOSR Journal of Engineering (IOSRJEN) ISSN (e): 2250-3021, ISSN (p): 2278-8719 Vol. 04, Issue 01 (January. 2014), V6 PP 01-12 www.iosrjen.org Paper on Basbar Trunking System for Electrical Supply to Industrial

More information

PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES

PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES BUSHING WITH PLUG CONNECTION WITH OUTER CONE PPS CHARACTERISTICS The PPS bushing can be used as a fixed section for the entry of medium

More information

Voltage Rated operating voltage [kv] 12 24 Rated power frequency withstand voltage [kv] 28 50 Rated lightning impulse withstand voltage [kv] 75 125

Voltage Rated operating voltage [kv] 12 24 Rated power frequency withstand voltage [kv] 28 50 Rated lightning impulse withstand voltage [kv] 75 125 Standards and Regulations IEC 62271-200 ; VDE 0671-200 ; BS EN 62271-200 Technical Data MC3-12 MC3-24 Voltage Rated operating voltage [kv] 12 24 Rated power frequency withstand voltage [kv] 28 50 Rated

More information

Awning Instructions. Standard Manual 1.5m to 4.5m

Awning Instructions. Standard Manual 1.5m to 4.5m Awning Instructions Standard Manual 1.5m to 4.5m English Standard Manual Instructions Contents Warning 1.5m 3.0m Awnings 4 x Expansion bolts (2 per bracket)** 2 x brackets 1 x Awning 1 x Winder handle

More information

REVIEWED BY CAPITAL PROJECTS MANAGER (DAN REDDY) GENERAL MANAGER EQUIPMENT ENGINEERING & ASSET MANAGEMENT (HAMILTON NXUMALO)

REVIEWED BY CAPITAL PROJECTS MANAGER (DAN REDDY) GENERAL MANAGER EQUIPMENT ENGINEERING & ASSET MANAGEMENT (HAMILTON NXUMALO) SA Port Operations DOCUMENT TYPE: REFERENCE EEAM-Q-014 (ORIGINAL SPECIFICATION HE8.2.3 Ver5) REVISION 0 SPECIFICATION TITLE: SPECIFICATION FOR ELECTRICAL MOTORS AND GENERATORS PAGE 0 of 07 COMPILED BY

More information

EH-20 20m antenna. By VE3RGW

EH-20 20m antenna. By VE3RGW EH-20 20m antenna By VE3RGW Equivalent circuit of EH-20 (prototype 2A) antenna system. Upper cylinder Lower cylinder Ground Counter pose Phasing coil Impedance transformer and tune circuit Tune coil Feed

More information

Architectural Specifications* MODEL HDE

Architectural Specifications* MODEL HDE MODEL HDE 200 Fairview Road, Unit #2, Barrie, Ontario L4N 8Z8 Tel: 866-792-9968 or 705-792-9968 Fax: 705-735-9564 www.tnrdoors.com email: info@tnrdoors.com TNR Model HDE Tech Specs September 4, 2012 Page

More information

Project : CONSTRUCTION OF BUILDING(including electrical and plumbing works) FOR NATIONAL CENTRE FOR SUSTAINABLE COASTAL MANAGEMENT,CHENNAI

Project : CONSTRUCTION OF BUILDING(including electrical and plumbing works) FOR NATIONAL CENTRE FOR SUSTAINABLE COASTAL MANAGEMENT,CHENNAI Project : CONSTRUCTION OF BUILDING(including electrical and plumbing works) FOR NATIONAL CENTRE FOR SUSTAINABLE COASTAL MANAGEMENT,CHENNAI TENDER CLARIFICATIONS- no 3 dated 3rd Oct 13 issued in response

More information

TECHNICAL SPECIFICATION FOR HIGH TENSION LINE HARDWARE AND ACCESSORIES FOR ACSR PANTHER & WOLF CONDUCTOR

TECHNICAL SPECIFICATION FOR HIGH TENSION LINE HARDWARE AND ACCESSORIES FOR ACSR PANTHER & WOLF CONDUCTOR TECHNICAL SPECIFICATION FOR HIGH TENSION LINE HARDWARE AND ACCESSORIES FOR ACSR PANTHER & WOLF CONDUCTOR 1.1.0 SCOPE : This specification covers design, manufacture, testing at manufacture s works before

More information

INTER PLANT STANDARD STEEL INDUSTRY

INTER PLANT STANDARD STEEL INDUSTRY INTER PLANT STANDARD STEEL INDUSTRY CODE OF PRACTICE FOR REVAMPING OF EOT CRANES IPSS:3-02-014-03 IPSS Corresponding IS does not exist 0. FOREWORD 0.1 This Inter Plant Standard has been prepared by the

More information

ECOCIAT. Domestic hot water heat recovery unit

ECOCIAT. Domestic hot water heat recovery unit Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY

More information

C O N V E Y O R C O M P O N E N T S C H A I N S B E L T S B E A R I N G S

C O N V E Y O R C O M P O N E N T S C H A I N S B E L T S B E A R I N G S C O N V E Y O R C O M P O N E N T S C H A I N S B E L T S B E A R I N G S January 2009 Issue 6 Valu Guide Brackets The Ultimate in Adjustability and Cost Savings Valu Guide brackets are part of a family

More information

POLE MOUNT SYSTEM-3 INSTALLATION

POLE MOUNT SYSTEM-3 INSTALLATION 1 May 2014 POLE MOUNT SYSTEM-3 INSTALLATION The Pole Mount System-3 is an easy to install and flexible system designed to allow ONE SYSTEMS loudspeaker products to be mounted to pole structures. The only

More information

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE 380/415/690 Volt AC 50/65/80/100 ka 1. Product Guide Low Voltage Motor Control Centre CONTSTRUCTION Continuous "poured in place" gasket

More information

LED LEONARDO 120 W. LED Fresnel SPOTLIGHT White light, either Tungsten or Daylight balanced Correlated Color Temperature

LED LEONARDO 120 W. LED Fresnel SPOTLIGHT White light, either Tungsten or Daylight balanced Correlated Color Temperature LED LEONARDO 120 W LED Fresnel SPOTLIGHT White light, either Tungsten or Daylight balanced Correlated Color Temperature OVERVIEW The LED LEONARDO 120W is a highly efficient Fresnel lens spotlight using

More information

CODE OF PRACTICE FOR EARTHING AND BONDING SYSTEM FOR SIGNALLING EQUIPMENTS SPECIFICATION NO. RDSO/SPN/197/2008 SIGNAL DIRECTORATE

CODE OF PRACTICE FOR EARTHING AND BONDING SYSTEM FOR SIGNALLING EQUIPMENTS SPECIFICATION NO. RDSO/SPN/197/2008 SIGNAL DIRECTORATE CODE OF PRACTICE FOR EARTHING AND BONDING SYSTEM FOR SIGNALLING EQUIPMENTS SPECIFICATION NO. RDSO/SPN/197/2008 SIGNAL DIRECTORATE RESEARCH, DESIGNS & STANDARDS ORGANISATION LUCKNOW - 226011 1 CODE OF PRACTICE

More information

STB Series Enclosures

STB Series Enclosures STB Series Enclosures Features/Applications: The STB series of sheet steel enclosures are designed to meet the requirement for distribution and lighting junction boxes. Available in 14 sizes with standard

More information

Distribution Boards & Consumer Units

Distribution Boards & Consumer Units Distribution Boards & Consumer Units Enclosures for system pro M compact Distribution Boards & Consumer Units Contents General 2/ Distribution Boards Mini Center compact Mounting kits for compact accessories

More information

TECHNICAL SPECIFICATION FOR PROJECTION WELDING MACHINE (Qty. 2 Nos.)

TECHNICAL SPECIFICATION FOR PROJECTION WELDING MACHINE (Qty. 2 Nos.) TECHNICAL SPECIFICATION FOR PROJECTION WELDING MACHINE (Qty. 2 Nos.) 1. Requirement: Two (02) Nos. DC Type, 3 phase, 3 wire Projection Welding Machine is required for welding of ventilation M.S. / Stainless

More information

V1504 Vertical Platform Lift OWNER S MANUAL

V1504 Vertical Platform Lift OWNER S MANUAL V1504 Vertical Platform Lift OWNER S MANUAL (To Be Retained by Owner After Installation by Authorized Savaria Dealer) Part No. 000692 03-m12-2013 2 IMPORTANT Ensure that only an authorized Savaria Dealer

More information

BOQ FOR ELECTRICAL WORK OF HLST IN GROUND FLOOR AT S.B.I. LHO BHOPAL.

BOQ FOR ELECTRICAL WORK OF HLST IN GROUND FLOOR AT S.B.I. LHO BHOPAL. BOQ FOR ELECTRICAL WORK OF HLST IN GROUND FLOOR AT S.B.I. LHO BHOPAL. Note: Use of Flexible conduits & Elbows in Circuit wiring is not allowed except in exceptional site conditions with the approval of

More information

K17.11 DOOR BOLTS K17 DOORS 01.09.2013

K17.11 DOOR BOLTS K17 DOORS 01.09.2013 K17 DOORS K17.11 01.09.2013 Waregemstraat 5-9870 Zulte - Belgium - T. +32 9 388 88 81 - F. +32 9 388 88 21 - commercial@sobinco.com - www.sobinco.com CONTENTS 1. Locking set series 86000...K17.11.03 2.

More information

Removable Aluminium posts

Removable Aluminium posts Post Solent Sail Shades Ltd 120 Billington Gardens Hedge End Southampton SO30 2RT Tel/Fax: 01489 788243 www.solentsailshades.co.uk Email: info@solentsailshades.co.uk Removable Aluminium posts Single Pole

More information

SECTION 16461 DRY-TYPE TRANSFORMERS

SECTION 16461 DRY-TYPE TRANSFORMERS SECTION 16461 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Furnishing and installation of and testing of cast resin dry type MV/LV distribution transformer in accordance with specifications and drawings. Any

More information

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp Page 1 2015 Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other Component 15 kv or 25 kv Separable Insulated Connector (elbow) Equipment Connection Power Cable Power Cable Grounded Metal

More information

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264 BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used

More information

Dock Hardware & Accessory Products Catalog

Dock Hardware & Accessory Products Catalog Dock Hardware & Accessory Products Catalog Product Page # Product Page # Angle Brackets/Clips 8 Back Up Plate 5 Backing Plate/Hurricane Stop 10 Carriage Bolt Sets 4 Chain Retainer 10 Connector Pin Set

More information

Residential Garage Door Terminology

Residential Garage Door Terminology A Air Infiltration: The leakage or passage of air through a door system Anodize: A hard non-corrosive oxide film on the surface of aluminum Astragal: A compressible or deformable seal provided on the bottom

More information

PRESENTATION ON REPAIR AND REHABILITATION OF BUILDINGS DAMAGED IN EARTHQUAKE. By H P Gupta & D K Gupta

PRESENTATION ON REPAIR AND REHABILITATION OF BUILDINGS DAMAGED IN EARTHQUAKE. By H P Gupta & D K Gupta PRESENTATION ON REPAIR AND REHABILITATION OF BUILDINGS DAMAGED IN EARTHQUAKE By H P Gupta & D K Gupta DIFFERENT TYPES OF DAMAGES 1.Minor cracks 0.5 to 5 mm wide in load or non-load bearing walls 2.Major

More information

Section M POWER LIFTS

Section M POWER LIFTS Section M POWER LIFTS December 2009 1M Index 1. 53-520244-000 Poly V Idler Assembly 2. 53-520205-000 N.A. Mounting Bracket 3. 53-520212-000 Cable Assembly 4. 53-600149-000 Wire Harness Assembly 5. 53-860322-010

More information

GENERAL SPECIFICATION FOR CIVIL ENGINEERING WORKS SECTION 13 WORK FOR ELECTRICAL AND MECHANICAL INSTALLATIONS

GENERAL SPECIFICATION FOR CIVIL ENGINEERING WORKS SECTION 13 WORK FOR ELECTRICAL AND MECHANICAL INSTALLATIONS GENERAL SPECIFICATION FOR CIVIL ENGINEERING WORKS SECTION 13 WORK FOR ELECTRICAL AND MECHANICAL INSTALLATIONS 13.1 13.2 2006 Edition SECTION 13 WORK FOR ELECTRICAL AND MECHANICAL INSTALLATIONS GENERAL

More information

Explosion proof enclosures

Explosion proof enclosures 1 of 7 Explosion proof enclosures DE8 C 2 of 7 The Ex d enclosures are rugged and designed for harsh environment like: Oil and gas industry Chemical industry Pharmaceutical industry Agribusiness Without

More information

ADDING AN ELECTRIC AUXILIARY FAN TO RADIATOR STACK ON 03 ALPINE COACH

ADDING AN ELECTRIC AUXILIARY FAN TO RADIATOR STACK ON 03 ALPINE COACH ADDING AN ELECTRIC AUXILIARY FAN TO RADIATOR STACK ON 03 ALPINE COACH The original design of the 03 Alpine Coaches (and perhaps other years as well) did not include any kind of engine fan engage mechanism

More information

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Optional Standby Power Generator Systems A. Furnish and install automatic transfer switches

More information

Cluster Box Units. (CBU s) 3300 Series CBU Door Sizes. Fully Integrated Parcel Lockers CLUSTER BOX UNITS FRONT LOADING. continued on pages 7-11

Cluster Box Units. (CBU s) 3300 Series CBU Door Sizes. Fully Integrated Parcel Lockers CLUSTER BOX UNITS FRONT LOADING. continued on pages 7-11 Cluster Box Units (CBU s) continued on pages 7-11 CLUSTER BOX UNITS FRONT LOADING Made of heavy duty aluminum and stainless steel hardware, Salsbury 3300 series U.S.P.S. approved Cluster Box Units (CBU

More information

ILLUSTRATED PARTS LIST

ILLUSTRATED PARTS LIST TW400 WITH 390cc HONDA ENGINE 390cc 2 WHEEL DRIVE UTILITY VEHICLE ILLUSTRATED S LIST 390cc 2WD B O D Y D I A G R A M 390cc 2WD F R A M E D I A G R A M 390cc 2WD D R I V E T R A I N D I A G R A M DESCRIPTION

More information

INSTALLATION INSTRUCTIONS HUSTLER 4-BTV, 5-BTV TRAP VERTICAL WARNING INSTALLATION OF THIS PRODUCT NEAR POWER LINES IS DANGEROUS

INSTALLATION INSTRUCTIONS HUSTLER 4-BTV, 5-BTV TRAP VERTICAL WARNING INSTALLATION OF THIS PRODUCT NEAR POWER LINES IS DANGEROUS INSTALLATION INSTRUCTIONS HUSTLER 4-BTV, 5-BTV TRAP VERTICAL WARNING INSTALLATION OF THIS PRODUCT NEAR POWER LINES IS DANGEROUS FOR YOUR SAFETY, FOLLOW THE INSTALLATION DIRECTIONS GENERAL DESCRIPTION:

More information

www.klmtechgroup.com TABLE OF CONTENT

www.klmtechgroup.com TABLE OF CONTENT Page : 1 of 13 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia ELECTIRAL GROUNDING TABLE OF CONTENT

More information

Morgue refrigeration unit

Morgue refrigeration unit Morgue refrigeration unit The Morgue refrigeration units are made of sturdy, self-supporting walls, floor and ceiling elements. They are delivered in separate components and are to be assembled on site

More information

Front axle components, overview

Front axle components, overview just a test. Front axle components, overview 40-1 General Information Load bearing components and parts of the suspension must not be welded or straightened. Vehicles without drive axle must not be moved,

More information

Technical Information

Technical Information Technical Information This section of the catalogue provides technical information that will help specify, install and maintain Surelock McGill devices and components. The topics are listed below: Blast

More information

RAUFOSS EXPLOSIVE COMPRESSION FITTINGS

RAUFOSS EXPLOSIVE COMPRESSION FITTINGS INSTRUCTION MANUAL FOR RAUFOSS EXPLOSIVE COMPRESSION FITTINGS Box 7 2831 Raufoss Norway Tlf.: +47 61 15 17 87 Fax: +47 61 15 25 56 25 January 2013, rev 2 Available on www.vpmetall.no Page 1 CONTENTS GENERAL

More information

OPL BASIC. Dosing System for Professional Laundry machines. Contents

OPL BASIC. Dosing System for Professional Laundry machines. Contents OPL BASIC Dosing System for Professional Laundry machines Contents 1 Getting Started. Page 2 2 Installation. Page 4 3 Set Up & Operation. Page 8 4 Maintenance & Accessories. Page 10 5 Troubleshooting Page

More information

TOP RUNNING SINGLE GIRDER BRIDGE CRANE

TOP RUNNING SINGLE GIRDER BRIDGE CRANE SECTION 14630 TOP RUNNING SINGLE GIRDER BRIDGE CRANE 1.01 SUMMARY PART 1- GENERAL A. The work required under this section shall include the designing, manufacturing, shipping, installing and field testing

More information